AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0

AIR-TO-WATER HEAT PUMP (50Hz/R410A) 5BPU0
AIR-TO-WATER HEAT PUMP
(50Hz/R410A)
5BPU0-03C(Replace:5BPU0-03B)
CONTENTS
Part 1. Indoor Unit(Hydro kit)
Part 2. Outdoor Unit
Part 3. Accessories
Part 1. Indoor Unit (Hydro kit)
1. Features
2. Nomenclature
3. Specification
4. Drawing
5. Wiring Diagram
6. Piping Diagram
7. Operation Range
8. Pump Hydraulic Performance
1. Features
• Providing eco-friendly heating
• High energy efficiency
• Easy installation
• Space heating, cooling, and sanitary water heating
Indoor Unit
Air-to-Water Heat Pump _ 1
2. Nomenclature
2.1 Global Model Name
AH N W 16 A 06 A 1
Serial Number
Chassis Name
Heater Capacity (kW)
Ex) 06 : 6kW Class
Heater Electrical Ratings
6 : 1 phase 220-240V 50Hz
8 : 3 phase 380-415V 50Hz
A : 3 phase 220V 50Hz
Heating Capacity (kW)
Ex) 16 : 16kW Class
Model Type
W : DC Inverter Heat Pump
H : Heat Pump
Indoor Unit
Classification
N : Indoor Unit
U : Outdoor Unit
- : Set
Air-to-Water Heat Pump for R410A
2.2 Europe Model Name
H N 09 1 4
Heater Capacity (kW)
Ex) 04 : 4kW Class 06 : 6kW Class
09 : 9kW Class
Electrical Ratings
1 : 1 Phase 220-240V 50Hz
2 : 3 Phase 220V 50Hz
3 : 3 Phase 380-415V 50Hz
Classification
09 (Combined with 09kW of Outdoor Unit)
16 (Combined with 12/14/16kW of Outdoor Unit)
N : Hydro kit (Indoor Unit)
H : Air to Water Heat Pump
2 _ Air-to-Water Heat Pump
3. Specification
Technical Specification
W
A
°C
°C
°C
°C
EA
W
LPM
EA
EA
liter
bar
bar
mm
bar
inch
inch
mm(inch)
mm(inch)
mm
mm
kg
kg
kW
Ø / V / Hz
°C
A
mm(inch)
-
Electrical Specification
Electric Heater
Type
Number of Heating Coil
Capacity Combination
Operation
Heating Steps
Power Supply
Rated Current
Maximum Current(MCA)
EA
kW
Step
Ø / V / Hz
A
A
AHNW166**A1
(HN161* NK1)
Sheath
2
3+3
Automatic
2
1 / 220-240 / 50
25
32
AHNW168**A1
(HN163* NK1)
Sheath
3
6 or 9
Automatic
2
3 / 380-415 / 50
-
AHNW16A**A1
(HN162* NK1)
Sheath
3
6 or 9
Automatic
2
3 / 220 / 50
-
Note :
1. The specification may be subject to change without prior notice for purpose of improvement.
Air-to-Water Heat Pump _ 3
Indoor Unit
Nominal Power Input
Nominal Running Current without Electric Heater
Operation Range
Cooling(Fan coil unit)
(Min.~Max.)
Cooling(Under floor)
Leaving Water
Heating(Fan coil unit or Radiator)
Temperature
Heating(Under floor)
Pump
Type
Steps of Speed
Power Input
Water Flowrate Limit
Heat Exchanger
Type
Number of Plate
Quantity
Expansion Vessel Volume
Water Pressure(Max.)
Water Pressure(Pre)
Strainer
Mesh Size
Material
Water Circuit
Safety Valve
Entering Side Diameter
Leaving Side Diameter
Manometer
Drain Valve / Fill Valve
Shut Off Valve
Air Vent
Refrigerant Circuit Gas Side Diameter
Liquid Side Diameter
Dimensions
Unit(H x W x D)
Packed Unit(H x W x D)
Weight
Unit
(Without water)
Packed Unit
Sanitary Water Tank Type
Heater Capacity
Power Supply
Power Supply Type
Thermal Protector Range
Magnet switch
MCCB
Sensor Adaptor Diameter
Accessory Kit
AHNW166**A1
AHNW168**A1
AHNW16A**A1
(HN161* NK1)
(HN163* NK1)
(HN162* NK1)
205
205
205
0.89
0.89
0.89
6 ~ 30
6 ~ 30
6 ~ 30
16 ~ 30
16 ~ 30
16 ~ 30
15 ~ 55
15 ~ 55
15 ~ 55
15 ~ 55
15 ~ 55
15 ~ 55
Canned type for hot water circulation
2 (In Max. / Med. / Min., Min. step is not used)
205
205
205
At least 15.0
At least 15.0
At least 15.0
Brazed Plate HEX
Brazed Plate HEX
Brazed Plate HEX
67
67
67
1
1
1
8
8
8
3
3
3
1
1
1
1x1
1x1
1x1
Stainless Steel
Stainless Steel
Stainless Steel
3
3
3
Male PT 1
Male PT 1
Male PT 1
Male PT 1
Male PT 1
Male PT 1
O
O
O
O
O
O
O
O
O
O
O
O
15.88 (5/8)
15.88 (5/8)
15.88 (5/8)
9.52 (3/8)
9.52 (3/8)
9.52 (3/8)
850 x 490 x 315
850 x 490 x 315
850 x 490 x 315
1080 x 563 x 375
1080 x 563 x 375
1080 x 563 x 375
54.5
54.5
54.5
61.5
61.5
61.5
Indirect heating(+ Electric heater)
Max. 3
1 / 230 / 50
Separated power source
Max. 90
Needed
40
12.7 (1/2)
LG Supply (model : PHLTA) LG Supply (model : PHLTC) LG Supply (model : PHLTC)
3. Specification
AHNW09604A1
(HN0914 NK1)
Indoor Unit
Technical Specification
Nominal Power Input
Nominal Running Current without Electric Heater
Operation Range
Cooling(Fan coil unit)
(Min.~Max.)
Cooling(Under floor)
Leaving Water
Heating(Fan coil unit or Radiator)
Temperature
Heating(Under floor)
Pump
Type
Steps of Speed
Power Input
Water Flowrate Limit
Heat Exchanger
Type
Number of Plate
Quantity
Expansion Vessel Volume
Water Pressure(Max.)
Water Pressure(Pre)
Strainer
Mesh Size
Material
Water Circuit
Safety Valve
Entering Side Diameter
Leaving Side Diameter
Manometer
Drain Valve / Fill Valve
Shut Off Valve
Air Vent
Refrigerant Circuit Gas Side Diameter
Liquid Side Diameter
Dimensions
Unit(H x W x D)
Packed Unit(H x W x D)
Weight
Unit
(Without water)
Packed Unit
Sanitary Water Tank Type
Heater Capacity
Power Supply
Power Supply Type
Thermal Protector Range
Magnet switch
MCCB
Sensor Adaptor Diameter
Accessory Kit
Type
Number of Heating Coil
Capacity Combination
Heating Steps
Power Supply
Maximum Current(MCA)
AHNW09806A1
(HN0936 NK1)
135
0.59
6~30
16~30
15~55
15~55
Canned type for hot water circulation
2 (In Max. / Med. / Min. , Min. step is not used)
135
At least 15 LPM
Blazed Plate HEX
54
1
8
3
1
1x1
Stainless Steel
3
Male PT 1
Male PT 1
O
O
O
O
15.88 (5/8)
9.52 (3/8)
850 x 490 x 315
1,032 x 563 x 375
48
55
Indirect heating (+ Electric heater)
Max. 3
1/ 230 / 50
Separated power source
Max. 90
Needed
40
12.7 (1/2)
LG Supply (model : PHLTA) LG Supply (model : PHLTA) LG Supply (model : PHLTC) LG Supply (model : PHLTC)
EA
kW
Step
Ø / V / Hz
A
AHNW09604A1
AHNW09606A1
(HN0914 NK1)
(HN0916 NK1)
Sheath
Sheath
2
2
2+2
3+3
2
2
1 / 220-240 / 50 1 / 220-240 / 50
30
32
Note :
1. The specification may be subject to change without prior notice for purpose of improvement.
4 _ Air-to-Water Heat Pump
AHNW09A06A1
(HN0926 NK1)
W
A
°C
°C
°C
°C
EA
W
LPM
EA
EA
liter
bar
bar
mm
bar
inch
inch
mm(inch)
mm(inch)
mm
mm
kg
kg
kW
Ø / V / Hz
°C
A
mm(inch)
-
Electrical Specification
Electric Heater
AHNW09606A1
(HN0916 NK1)
AHNW09A06A1
(HN0926 NK1)
Sheath
3
6
2
3 / 220 / 50
-
AHNW09806A1
(HN0936 NK1)
Sheath
3
6
2
3 / 380-415 / 50
-
474
305
[Unit:mm]
Thermal switch
Control Box
Flow Switch
Plate Heat Exchanger
Pressure Gage
Expansion Tank
Air Vent
Electric Heater
Strainer
Shut-off valve
Carrying handle
8'
9
10
11
12
13
14
15
16
17
18
Hydro kit
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
1. Unit should be installed in compliance with the installation manual in
the product box.
Note
AHNW09***A1 (HN09** NK1)
AHNW16***A1 (HN16** NK1)
Remarks
Ø15.88mm
Ø9.52mm
Male PT 1 inch
Male PT 1 inch
Built-in Remote Controller
Max Head 7.5 / 6.5 meter
Open at water pressure 3 bar
Cut-off power input to electric heater at 90 centigrade (manual return at 55 centigrade)
Cut-off power input to electric heater at 90(primary) and 200(secondary) centigrade (auto
return at 70 centigrade for first thermal switch)
PCB and terminal blocks
Minimum operation range at 12 LPM
Heat exchange between refrigerant and water
Indicates circulating water pressure
Absorbing Volume change of heated water
Air purging when Charging water
Additional heating source
Filtering and stacking particles inside circulating water
When connecting water pipes,drain water or block the flow from indoor unit
To carry the product
Notice : Item 8 and Item 8’ will be applied exclusively
Name
Refrigerant Pipe
Refrigerant Pipe
Entering Water Pipe
Leaving Water Pipe
Control Panel
Water Pump
Safety Valve
Thermal switch
No
1
2
3
4
5
6
7
8
Indoor Unit
848
AWHP
4. Drawing
4.1 Internal
Air-to-Water Heat Pump _ 5
6 _ Air-to-Water Heat Pump
[Unit:mm]
Name
Door
Handle
Remarks
Control panel is shown after this door is opened.
Used to cover or uncover the front case
AHNW09***A1 (HN09** NK1)
AHNW16***A1 (HN16** NK1)
AWHP
Hydro kit
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
1. Unit should be installed in compliance with the installation manual in
the product box.
Note
No
1
2
Indoor Unit
4. Drawing
4.2 External
Step 2. Attach "Installation Sheet" to the wall and mark the location of bolts. This sheet helps to
find correct location to the bolts.
Remove
Bottom
screws
Step 1. After releasing eight screws, detach front cover from the indoor unit. While detaching the
front cover, grab the carrying handles at left and right sides of the front cover. Then pull
into upward direction. When assemble the front cover, remove detached side brackets of
the front cover and ONLY tighten two screws of bottom.
AHNW09***A1 (HN09** NK1)
AHNW16***A1 (HN16** NK1)
ll m
ark
s)
Hydro kit
Step 4. Hang the indoor unit at the supporting plate. Also, catch the carrying handles at left and right sides of the indoor unit.
(Ha
Step 3. Detach the Installation sheet. Screw bolts with supporting plate at the hole
marks on the wall. When screwing bolts, use M8 ~ M11 anchor bolts to
secure hanging the indoor unit.
Indoor Unit
Mounting to Wall
AWHP
4. Drawing
4.3 For Installation
Air-to-Water Heat Pump _ 7
Fixation
200
241
350
Service Space
500
AWHP
Hydro kit
248
AHNW09***A1 (HN09** NK1)
AHNW16***A1 (HN16** NK1)
250
1300
8 _ Air-to-Water Heat Pump
[Unit:mm]
384
Indoor Unit
4. Drawing
4.3 For Installation
5. Wiring Diagram
AHNW**6**A1 (HN**1* NK1)
Indoor Unit
Air-to-Water Heat Pump _ 9
5. Wiring Diagram
Indoor Unit
AHNW**A**A1 (HN**2* NK1), AHNW**8**A1 (HN**3* NK1)
10 _ Air-to-Water Heat Pump
5. Wiring Diagram (External Connection)
AHNW**6**A1 (HN**1* NK1)
Indoor Unit
Air-to-Water Heat Pump _ 11
5. Wiring Diagram (External Connection)
M/C
M/C
MCCB
3
M/C
MCCB
3~
220V
50Hz
1~
230V
50Hz
Indoor Unit
AHNW**A**A1 (HN**2* NK1), AHNW**8**A1 (HN**3* NK1)
12 _ Air-to-Water Heat Pump
Air-to-Water Heat Pump _ 13
Basic installation
(IDU + ODU)
Underfloor
Heating
Radiator
Sanitary water tan
k is installed
(Sanitary water tan
k kit is necessary)
Solar thermal syst
em is connected
(Solar thermal kit i
s necessary)
Indoor Unit
Fan
Coil
Unit
Solar
Thermal
Componets
6. Piping Diagram
AHNW*****A1 (HN**** NK1)
6. Piping Diagram
Category
Symbol
TH1
TH2
Indoor Unit
TH3
TH4
TH5
F/S
CN_PIPE/OUT
CN_PIPE/IN
CN_TH3
Remarks
- Meaning is expressed based on Cooling
mode.
- TH3, TH4, and TH5 are connected at 6 pin
type connector CN_TH3.
CN_FLOW1
Electric Heater
W_PUMP1
Internal Water Pump
CN_W/PUMP(A)
EXP/TANK
Expansion Tank
TH8
Indoor Unit
PCB Connector
- Heating capacity is divided into two level :
partial capacity by E/HEAT(A) and full
capacity by E/HEAT(A) + E/HEAT(B).
CN_E/HEAT(A)
- Operating power(230V AC 50Hz) of
CN_E/HEAT(B)
E/HEAT(A) and E/HEAT(B) are supplied by
external power source via magnet switch
and MCCB
E/HT
CTR/PNL
2WAY V/V_1
W/TANK
B/HT
Water
Heating
3WAY V/V_1
CITY WATER
SHOWER
TH6
TH7
3WAY V/V_2
Solar
Heating
Meaning
Refrigerant temperature sensor
(Gas side)
Refrigerant temperature sensor
(Liquid side)
Entering Water temperature sensor
Interim Water temperature sensor
Leaving Water temperature sensor
Flow Switch
W_PUMP/2
Remote Air temperature sensor
CN_ROOM
- Operating power(230V AC 50Hz) of internal
water pump is supplied by the connector.
- Absorb volume change of heated water,
- Optional accessory (sold separately)
- Model : PQRSTA0
Control Panel (or ‘Remote Controller’)
CN_REMO
- Pre built-in at indoor unit
To control water flow for Fan Coil Unit
Sanitary Water Tank
Electric Heater
- Flow control for water which is leaving from
indoor unit.
- Flow direction switching between underfloor and water tank
Water to be heated by Indoor unit and B/HT
of W/TANK
Water supplied to end-user
(no connector)
CN_2WAY(A)
- 3rd party accessory and Field installation
(sold separately)
(no connector)
- Generating and storing sanitary hot water by
AWHP or built-in electric heater- 3rd party accessory and Field installation
(usually built-in at W/TANK)
CN_B/HEAT(A)
- Supplying additional water heating capacity.
CN_3WAY(A)
- 3rd party accessory and Field installation
(sold separately)
- SPDT type 3way valve is supported.
(no connector)
- Field installation
(no connector)
- Field installation
CN_TH4
- TH6 and TH7 are connected at 4 pin type
connector CN_TH4.
- TH6 is a part of sanitary water tank kit.
(model: PHLTA)
- TH7 is a part of solar thermal kit
(model: PHLLA)
CN_3WAY(B)
- 3rd party accessory and Field installation
(sold separately)
- SPDT type 3way valve is supported.
W/TANK water temperature sensor
Solar-heated water temperature sensor
- Flow control for water which is heated and
circulated by SOLAR THERMAL SYSTEM.
- Flow direction switching between SOLAR
THERMAL SYSTEM and W/TANK
External Water Pump
- This system can include following components : Solar panel, Sensors, Thermostats,
SOLAR THER- Interim heat exchanger, Water pump, etc.
MAL SYSTEM - To utilized hot water heated by SOLAR
THERMAL SYSTEM, end-user must by LG
AWHP Solar-Kit.
14 _ Air-to-Water Heat Pump
- 3rd party accessory and Field installation
(sold separately)
- 2wire NO or NC type 2way valve is
supported.
- 3rd party accessory and Field installation
(sold separately)
CN_W/PUMP(B) - If water pump of SOLAR THERMAL SYSTEM
is incapable of circulation,external water pump
can be used.
(no connector)
- 3rd party accessory and Field installation
(sold separately)
7. Operation Range
7.1 Cooling Operation
AHUW096A1 (HU091 U41), AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31), AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)
48
43
)
43
10
Outdoor Temperature(
10
5
5
6
16
25
Leaving Water Temperature(
30
)
16
25
Leaving Water Temperature(
30
)
Continuous Operation
Operative
Air-to-Water Heat Pump _ 15
Indoor Unit
48
)
(Under floor)
Outdoor Temperature(
(Fan coil unit)
7. Operation Range
7.2 Heating Operation
AHUW096A1 (HU091 U41), AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31), AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)
(Fan coil unit or Radiator)
(Under floor)
)
30
24
Outdoor Temperature(
Outdoor Temperature(
Indoor Unit
)
30
-15
-20
24
-15
-20
15 20
50 55
Leaving Water Temperature(
)
15 20
50 55
Leaving Water Temperature(
)
Continuous Operation
Operative
16 _ Air-to-Water Heat Pump
8. Pump Hydraulic Performance
8.1 Static Pressure Drop
Model : AHNW09***A1 (HN09** NK1)
8.0
7.5
7.0
6.5
Hydraulic Head Loss(mH2O)
6.0
5.5
5.0
4.5
4.0
3.5
3.0
2.5
2.0
Med.
Max.
1.0
12.0
0.5
0.0
0
10
20
30
40
50
60
70
Water Flowrate(l/min)
80
90
100
110
Model : AHNW16***A1 (HN16** NK1)
8.0
7.5
7.0
6.5
Hydraulic Head Loss(mH2O)
6.0
5.5
5.0
4.5
Max.
4.0
3.5
Med.
3.0
2.5
2.0
1.5
15.0
1.0
0.5
0.0
0
10
20
30
40
50
60
70
80
90
100
110
Water Flowrate(l/min)
H Max. : high speed setting
Med. : low speed setting
Warning : Selecting a water flowrate outside the curves can cause damage to or malfunction of the unit.
: Operation cutoff range
Air-to-Water Heat Pump _ 17
Indoor Unit
1.5
Part 2. Outdoor Unit
1. Features
2. Nomenclature
3. Specification
4. Drawing
5. Wiring Diagram
6. Piping Diagram
7. Performance Data
8. Noise Criteria
1. Features
• Providing eco-friendly heating
• High energy efficiency
• Easy installation
• Space heating, cooling, and sanitary water heating
Outdoor Unit
Air-to-Water Heat Pump _ 1
2. Nomenclature
2.1 Global Model Name
AH U W 16 8 A 1
Serial Number
Chassis Name
Electrical Ratings
6 : 1 phase 220-240V 50Hz
8 : 3 phase 380-415V 50Hz
Nominal Heating Capacity Indication
Conversion to kW
Ex) "09" : 9 kW Class
"12" : 12 kW Class
"14" : 14 kW Class
"16" : 16 kW Class
Combination of Inverter Type
and Cooling Only or Heat Pump
W : DC Inverter Heat Pump
Classification
U : Outdoor Unit
Air-to-Water Heat Pump for R410A
2.2 Europe Model Name
H U 09 1 M
Leaving Water Combination
None : Low Temperature Leaving Water
H : High Temperature Leaving Water
M : Middle Temperature Leaving Water
Outdoor Unit
1 : 1 Phase 220-240V 50Hz
3 : 3 Phase 380-415V 50Hz
Nominal Heating Capacity Indication
Conversion to kW Class
Ex) "09" : 9 kW Class
"12" : 12 kW Class
"14" : 14 kW Class
"16" : 16 kW Class
U : Outdoor Unit
H : Air to Water Heat Pump
2 _ Air-to-Water Heat Pump
3. Specification
AHUW126A1
(HU121 U31)
* Capacity
* Power Input
* EER
COP
Cooling
Heating
Cooling
Heating
Cooling
Heating
9.00
9.00
2.65
2.20
3.40
4.09
14.5
12.0
4.00
2.67
3.63
4.49
AHUW096A1
(HU091 U41)
AHUW126A1
(HU121 U31)
°C DB
°C DB
EA
3
cm /Rev.
kW
EA
W
g(oz)
cc
EA
EA
EA
Fins/inch
EA
CMM(l/s)
EA
W
dB(A)±3
dB(A)±3
mm(inch)
mm(inch)
m
m
m
5~48
-20~30
Hermetic Motor
GJT240DAA
1
24
7.28
Brushless
1
1,700
R410A
1,900(67.0)
Electronic Expansion Valve
FVC68D
900
1
2
38
17
Propeller
1
60(1,000)
SIC-72FW-F1124-3
1
124
52
52
Flare
9.52(3/8)
Flare
15.88(5/8)
3
7.5
50
5 ~ 48
-20 ~ 30
Hermetic Motor
GPT425DBA
1
42.5
12.05
Brushless
1
4,000
R410A
2,850(100.5)
Electronic Expension Valve
FVC68D
1,300
2
2
32
17
Propeller
2
60(1,000)
SIC-72FW-F1124-3
2
124
54
53
Flare
9.52(3/8)
Flare
15.88(5/8)
3
7.5
50
m
30
30
g/m
mm
mm
kg
kg
30
950 x 834 x 330
1,140 x 900 x 461
64
69
60
950 Χ 1,380 Χ 330
1,140 Χ 1,462 Χ 461
105
116
AHUW096A1
(HU091 U41)
AHUW126A1
(HU121 U31)
Ø / V / Hz
A
A
1 / 220-240 / 50
15
15
1 / 220-240 / 50
28
28
Number of wires
3
3
Number of wires
4
4
kW
kW
kW
kW
W/W
W/W
Technical Specification
Operation Range(Min.~Max.) Cooling
Outdoor Temperature
Heating
Compressor
Type
Model
Quantity
Displacement
Capacity
Compressor Motor
Type
Quantity
Rated Output
Refrigerant
Type
Charge
Control
Refrigerant Oil
Type
Charged Volume
Heat Exchanger
Quantity
Rows
Columns
FPI
Fan
Type
Quantity
Air Flow Rate
Fan Motor
Model
Quantity
Output
Sound Pressure
Cooling
Level
Heating
Liquid Piping
Type
Connection
Outer Diameter
Gas Piping
Type
Connection
Outer Diameter
Piping Length
Minimum
(Outdoor Unit ~
Standard
Indoor Unit)
Maximum
Height Difference
Maximum
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge
Dimensions
Unit(W x H x D)
Packed Unit(W x H x D)
Weight
Unit
Packed Unit
Electrical Specification
Power Supply
Maximum Running
Current
Wiring Connections
Cooling
Heating
For Power Supply
(Included Earth)
For Connection with
Indoor Unit (Included Earth)
Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Air-to-Water Heat Pump _ 3
Outdoor Unit
AHUW096A1
(HU091 U41)
Nominal Capacity and Nominal Input
3. Specification
AHUW146A1
(HU141 U31)
AHUW166A1
(HU161 U31)
AHUW128A1
(HU123 U31)
15.5
14.0
4.69
3.15
3.30
4.44
16.1
16.0
5.07
3.81
3.18
4.2
14.6
12.0
4.02
2.72
3.60
4.41
AHUW146A1
(HU141 U31)
AHUW166A1
(HU161 U31)
AHUW128A1
(HU123 U31)
°C DB
°C DB
EA
3
cm /Rev.
kW
EA
W
g(oz)
cc
EA
EA
EA
Fins/inch
EA
CMM(l/s)
EA
W
dB(A)±3
dB(A)±3
mm(inch)
mm(inch)
m
m
m
5 ~ 48
-20 ~ 30
Hermetic Motor
GPT425DBA
1
42.5
12.05
Brushless
1
4,000
R410A
2,850(100.5)
Electronic Expension Valve
FVC68D
1,300
2
2
32
17
Propeller
2
60(1,000)
SIC-72FW-F1124-3
2
124
54
53
Flare
9.52(3/8)
Flare
15.88(5/8)
3
7.5
50
5 ~ 48
-20 ~ 30
Hermetic Motor
GPT425DBA
1
42.5
12.05
Brushless
1
4,000
R410A
2,850(100.5)
Electronic Expension Valve
FVC68D
1,300
2
2
32
17
Propeller
2
60(1,000)
SIC-72FW-F1124-3
2
124
54
53
Flare
9.52(3/8)
Flare
15.88(5/8)
3
7.5
50
5~48
-20~30
Hermetic Motor
GPT425DAA
1
42.4
12.05 (at 60Hz)
Brushless
1
4,000
R410A
2,980(105.1)
Electronic Expansion Valve
FV50S
1,300
2
2
32
17
Propeller
2
60(1,000)
SIC-72FW-F1124-3
2
124
54
53
Flare
9.52(3/8)
Flare
15.88(5/8)
3
7.5
50
m
30
30
30
g/m
mm
mm
kg
kg
60
950 Χ 1,380 Χ 330
1,140 Χ 1,462 Χ 461
105
116
60
950 Χ 1,380 Χ 330
1,140 Χ 1,462 Χ 461
105
116
50
950 x 1,380 x 330
1,140 x 1,462 x 461
105
116
AHUW146A1
(HU141 U31)
AHUW166A1
(HU161 U31)
AHUW128A1
(HU123 U31)
Ø / V / Hz
A
A
1 / 220-240 / 50
28
28
1 / 220-240 / 50
28
28
3/380-415/50
11
11
Number of wires
3
3
5
Number of wires
4
4
4
Nominal Capacity and Nominal Input
* Capacity
* Power Input
* EER
COP
Cooling
Heating
Cooling
Heating
Cooling
Heating
kW
kW
kW
kW
W/W
W/W
Outdoor Unit
Technical Specification
Operation Range(Min.~Max.) Cooling
Outdoor Temperature
Heating
Compressor
Type
Model
Quantity
Displacement
Capacity
Compressor Motor
Type
Quantity
Rated Output
Refrigerant
Type
Charge
Control
Refrigerant Oil
Type
Charged Volume
Heat Exchanger
Quantity
Rows
Columns
FPI
Fan
Type
Quantity
Air Flow Rate
Fan Motor
Model
Quantity
Output
Sound Pressure
Cooling
Level
Heating
Liquid Piping
Type
Connection
Outer Diameter
Gas Piping
Type
Connection
Outer Diameter
Piping Length
Minimum
(Outdoor Unit ~
Standard
Indoor Unit)
Maximum
Height Difference
Maximum
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge
Dimensions
Unit(W x H x D)
Packed Unit(W x H x D)
Weight
Unit
Packed Unit
Electrical Specification
Power Supply
Maximum Running
Current
Wiring Connections
Cooling
Heating
For Power Supply
(Included Earth)
For Connection with
Indoor Unit (Included Earth)
Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
4 _ Air-to-Water Heat Pump
3. Specification
AHUW168A1
(HU163 U31)
* Capacity
* Power Input
* EER
COP
Cooling
Heating
Cooling
Heating
Cooling
Heating
15.5
14.0
4.65
3.24
3.33
4.32
16.8
16.0
5.09
3.81
3.30
4.20
AHUW148A1
(HU143 U31)
AHUW168A1
(HU163 U31)
°C DB
°C DB
EA
3
cm /Rev.
kW
EA
W
g(oz)
cc
EA
EA
EA
Fins/inch
EA
CMM(l/s)
EA
W
dB(A)±3
dB(A)±3
mm(inch)
mm(inch)
m
m
m
5~48
-20~30
Hermetic Motor
GPT425DAA
1
42.4
12.05 (at 60Hz)
Brushless
1
4,000
R410A
2,980(105.1)
Electronic Expansion Valve
FV50S
1,300
2
2
32
17
Propeller
2
60(1,000)
SIC-72FW-F1124-3
2
124
54
53
Flare
9.52(3/8)
Flare
15.88(5/8)
3
7.5
50
5~48
-20~30
Hermetic Motor
GPT425DAA
1
42.4
12.05 (at 60Hz)
Brushless
1
4,000
R410A
2,980(105.1)
Electronic Expansion Valve
FV50S
1,300
2
2
32
17
Propeller
2
60(1,000)
SIC-72FW-F1124-3
2
124
54
53
Flare
9.52(3/8)
Flare
15.88(5/8)
3
7.5
50
m
30
30
g/m
mm
mm
kg
kg
50
950 x 1,380 x 330
1,140 x 1,462 x 461
105
116
50
950 x 1,380 x 330
1,140 x 1,462 x 461
105
116
AHUW148A1
(HU143 U31)
AHUW168A1
(HU163 U31)
Ø / V / Hz
A
A
3/380-415/50
11
11
3/380-415/50
11
11
Number of wires
5
5
Number of wires
4
4
kW
kW
kW
kW
W/W
W/W
Technical Specification
Operation Range(Min.~Max.) Cooling
Outdoor Temperature
Heating
Compressor
Type
Model
Quantity
Displacement
Capacity
Compressor Motor
Type
Quantity
Rated Output
Refrigerant
Type
Charge
Control
Refrigerant Oil
Type
Charged Volume
Heat Exchanger
Quantity
Rows
Columns
FPI
Fan
Type
Quantity
Air Flow Rate
Fan Motor
Model
Quantity
Output
Sound Pressure
Cooling
Level
Heating
Liquid Piping
Type
Connection
Outer Diameter
Gas Piping
Type
Connection
Outer Diameter
Piping Length
Minimum
(Outdoor Unit ~
Standard
Indoor Unit)
Maximum
Height Difference
Maximum
(Outdoor Unit ~ Indoor Unit)
Additional Refrigerant Charge
Dimensions
Unit(W x H x D)
Packed Unit(W x H x D)
Weight
Unit
Packed Unit
Electrical Specification
Power Supply
Maximum Running
Current
Wiring Connections
Cooling
Heating
For Power Supply
(Included Earth)
For Connection with
Indoor Unit (Included Earth)
Note :
1. Capacities and power inputs are based on the following conditions:
* : Cooling conditions - Indoor Water Temperature 23°C/18°C; Outdoor Air Temperature 35°CDB/24°CWB
Heating conditions - Indoor Water Temperature 30°C/35°C; Outdoor Air Temperature 7°CDB/6°CWB
Standard piping length 7.5m
2. Wiring cable size must comply with the applicable local and national code.
3. The specification may be subject to change without prior notice for purpose of improvement.
Air-to-Water Heat Pump _ 5
Outdoor Unit
AHUW148A1
(HU143 U31)
Nominal Capacity and Nominal Input
3
4
Outdoor Unit
6 _ Air-to-Water Heat Pump
[Unit:mm]
Note
U4
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
1. Unit should be installed in compliance with the installation manual in
the product box.
Control Cover
Air discharge grill
Gas side service valve(mm)
Liquid side service valve(mm)
AHUW096A1 (HU091 U41)
4. Drawing
Outdoor Unit
Supporter
[Unit:mm]
Note
4. Electrical characteristics chapter should be considered for electrical
work and design. Especially the capacity of power cable and circuit
breaker for outdoor unit should be more than that of electrical
characteristics chapter.
3. All electrical components and materials to be supplied on the site
must comply with the local regulations or international codes.
2. Unit should be grounded in accordance with the local regulations or
applicable national codes.
1. Unit should be installed in compliance with the installation manual in
the product box.
Control Cover
Air discharge grill
Gas side service valve(mm)
Liquid side service valve(mm)
AHUW126A1 (HU121 U31)
AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31)
AHUW128A1 (HU123 U31)
AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)
4. Drawing
Air-to-Water Heat Pump _ 7
5. Wiring Diagram
Outdoor Unit
AHUW096A1(HU091 U41)
8 _ Air-to-Water Heat Pump
5. Wiring Diagram
AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31), AHUW166A1 (HU161 U31)
Outdoor Unit
Air-to-Water Heat Pump _ 9
5. Wiring Diagram
Outdoor Unit
AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31), AHUW168A1 (HU163 U31)
10 _ Air-to-Water Heat Pump
6. Piping Diagram
AHUW096A1 (HU091 U41), AHUW126A1 (HU121 U31), AHUW146A1 (HU141 U31)
AHUW166A1 (HU161 U31), AHUW128A1 (HU123 U31), AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)
INDOOR UNIT
OUTDOOR UNIT
EEV
LIQUID SIDE
Th2
3-Way
Service Valve
Th6
Th7
Th8
Indoor Unit
Plate Heat
Exchanger
Outdoor Unit
Heat Exchanger
Low Pressure
Switch
Th3
GAS SIDE
Th4
3-Way
Service Valve
Reversing Valve
Accumulator
Th5
COMPRESSOR
High Pressure
Switch
COOLING
HEATING
Description
Symbol
Meaning
Th1
Remote air temperature sensor
Th2
Inlet evaporator temperature sensor
Th3
Outlet evaporator temperature sensor
Th4
Compressor-suction pipe temperature
sensor
Th5
Compressor-discharge pipe temperature sensor
Th6
Condenser temperature sensor
Th7
Outdoor air temperature sensor
AHUW096A1
AHUW126A1
AHUW146A1
AHUW166A1
AHUW128A1
AHUW148A1
AHUW168A1
CN_ROOM
CN_ROOM
CN_ROOM
Indoor Unit
Outdoor
Unit
Th8*1
EEV
Condenser middle temperature sensor
Electronic Expansion Valve
Remarks
- Optional accessory (being sold separately)
- Not shown in diagram
CN_PIPE/IN
CN_PIPE/IN
CN_PIPE/IN
CN_PIPE/OUT
CN_PIPE/OUT
CN_PIPE/OUT
CN_TH3
CN_TH2
CN_TH2
- Th4 and Th5 are connected at 4 pin
type.
- Meaning is expressed based on Cooling mode.
CN_TH2
CN_TH1
CN_TH1
- Description is expressed based on
Cooling mode.
- Th6 and Th7 are connected at 4 pin
type.
CN_TH4
CN_TH3
CN_TH3
- Th8 is connected at 4 pin type.
- Only AHUW096A1 model is connected
at 3 pin type.
CN_EEV1
CN_EEV1
CN_EEV
- Adjusting mass flow rate of circulating
refrigerant
*1:Applied Model : AHUW128A1, AHUW148A1, AHUW168A1, AHUW096A1, AHUW126A1, AHUW146A1, AHUW166A1
Air-to-Water Heat Pump _ 11
Outdoor Unit
PCB Connector
Category
7. Performance Data
7.1 Cooling Operation
Model
AHUW096A1
(HU091 U41)
Model
AHUW126A1
(HU121 U31)
Model
Outdoor Unit
AHUW146A1
(HU141 U31)
Model
AHUW166A1
(HU161 U31)
LWT 7°C
Outdoor
Temperature TC
PI
20°C
30°C
35°C
40°C
45°C
6.58
6.47
6.21
5.79
5.15
1.54
2.17
2.41
2.86
3.03
LWT 7°C
Outdoor
Temperature TC
PI
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
7.39
7.10
6.91
6.38
5.75
1.57
2.20
2.44
2.89
3.09
8.21
7.73
7.51
6.97
6.35
1.60
2.23
2.47
2.93
3.15
8.55
8.15
8.04
7.37
6.75
1.61
2.25
2.52
2.96
3.20
9.05
8.78
9.00
7.96
7.35
1.63
2.28
2.65
3.00
3.26
9.29
9.20
9.02
8.32
7.27
1.64
2.30
2.71
3.03
3.06
9.33
8.68
7.18
2.74
3.06
2.87
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
15.57
14.29
14.87
4.53
4.59
5.89
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
20°C
30°C
9.54
12.82
2.00
4.19
11.04
13.15
2.34
4.25
12.55
14.07
2.68
4.40
14.06
15.45
3.03
4.44
15.56
15.38
3.37
4.21
17.07
16.02
3.72
3.98
35°C
40°C
45°C
11.65
11.17
9.37
4.48
4.89
5.24
12.53
11.61
10.39
4.65
5.02
5.37
13.40
12.68
11.41
4.75
5.18
5.51
14.44
13.43
12.43
4.77
5.25
5.64
14.50
13.31
13.46
4.00
4.39
5.77
14.97
13.77
14.16
4.28
4.49
5.83
LWT 7°C
Outdoor
Temperature TC
PI
20°C
30°C
35°C
40°C
45°C
10.63
13.36
12.15
11.65
9.35
2.51
4.58
4.90
5.34
5.73
LWT 7°C
Outdoor
Temperature TC
PI
20°C
30°C
35°C
40°C
45°C
13.64
13.72
12.48
11.96
10.17
4.17
4.84
5.18
5.64
6.11
LWT 10°C
LWT 13°C
LWT 15°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
12.16
13.83
13.17
12.21
10.56
2.83
4.65
5.08
5.49
5.87
13.69
14.91
14.20
13.43
11.78
3.15
4.81
5.20
5.66
6.01
15.22
16.42
15.35
14.28
13.00
3.47
4.85
5.22
5.74
6.14
16.75
16.50
15.50
14.28
14.22
3.79
4.76
4.69
5.15
6.28
18.28
17.19
16.06
14.78
14.72
4.11
4.67
5.02
5.26
6.21
16.71
15.34
15.23
5.32
5.38
6.15
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
14.84
14.36
13.68
12.68
11.06
4.26
4.91
5.37
5.80
6.10
16.03
15.63
14.88
14.08
11.96
4.36
5.08
5.49
5.98
6.10
17.23
17.30
16.17
15.03
12.86
4.45
5.12
5.51
6.06
6.09
18.43
17.58
16.10
15.21
13.75
4.55
5.18
5.07
5.54
6.09
19.62
18.31
17.11
15.74
14.43
4.64
5.23
5.63
5.67
6.13
17.80
16.34
15.10
5.73
5.80
6.17
LWT : Leaving Water Temperature
TC : Total Capacity (Averaged value, kW)
PI : Power Input(kW)
Notice : Measuring procedure follows EN-14511
Notice : Above table values may not be matched according to installation condition
12 _ Air-to-Water Heat Pump
LWT 18°C
7. Performance Data
Model
AHUW128A1
(HU123 U31)
Model
AHUW148A1
(HU143 U31)
Model
AHUW168A1
(HU163 U31)
LWT 7°C
Outdoor
Temperature TC
PI
20°C
30°C
35°C
40°C
45°C
12.80
12.33
11.94
11.45
8.59
3.49
4.00
4.46
4.72
4.55
LWT 7°C
Outdoor
Temperature TC
PI
20°C
30°C
35°C
40°C
45°C
13.40
12.70
12.30
11.79
8.59
3.97
4.44
4.95
5.24
4.55
LWT 7°C
Outdoor
Temperature TC
PI
20°C
30°C
35°C
40°C
45°C
11.23
13.75
12.50
11.99
8.59
2.92
4.83
5.17
5.64
4.55
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
13.98
13.39
13.02
12.07
9.92
3.55
4.06
4.56
4.91
4.65
15.16
14.45
14.10
13.34
10.24
3.62
4.15
4.66
5.06
4.18
15.95
15.16
14.33
13.70
10.46
3.66
4.20
4.56
5.04
3.87
17.13
16.18
14.60
14.00
11.20
3.73
4.28
4.02
5.10
3.90
17.92
16.86
15.83
14.47
12.15
3.77
4.33
4.66
5.16
3.93
16.43
14.93
12.82
4.69
5.23
3.95
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
14.64
13.80
13.23
12.26
9.92
4.04
4.51
5.00
5.39
4.65
15.88
14.89
14.15
13.39
10.24
4.12
4.60
5.05
5.49
4.18
16.70
15.62
14.77
13.71
10.46
4.17
4.67
5.06
5.54
3.87
17.94
16.67
15.50
14.42
11.20
4.24
4.75
4.65
5.66
3.90
18.76
17.37
16.31
14.90
12.15
4.29
4.81
5.17
5.73
3.93
16.93
15.38
12.82
5.21
5.81
3.95
LWT 10°C
LWT 13°C
LWT 15°C
LWT 18°C
LWT 20°C
LWT 22°C
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
TC
PI
13.43
14.94
14.26
13.22
9.92
3.57
4.91
5.36
5.77
4.65
15.56
16.12
15.35
14.52
10.24
4.22
5.01
5.48
5.95
4.18
16.98
16.92
16.20
15.04
10.46
4.65
5.08
5.50
6.02
3.87
18.66
18.05
16.80
15.53
11.20
4.85
5.17
5.09
5.57
3.90
19.78
18.81
17.72
16.18
12.15
4.98
5.23
5.62
5.64
3.93
18.33
16.83
12.82
5.67
5.71
3.95
LWT : Leaving Water Temperature
TC : Total Capacity (Averaged value, kW)
PI : Power Input(kW)
Outdoor Unit
Notice : Measuring procedure follows EN-14511
Notice : Above table values may not be matched according to installation condition
Air-to-Water Heat Pump _ 13
7. Performance Data
7.2 Heating Operation
Model
AHUW096A1
(HU091 U41)
Model
Outdoor Unit
AHUW126A1
(HU121 U31)
Model
AHUW146A1
(HU141 U31)
LWT 55°C
PI
TC
LWT 30°C
PI
TC
LWT 35°C
PI
TC
LWT 40°C
PI
TC
LWT 45°C
PI
TC
LWT 50°C
PI
TC
-15
7.55
3.20
6.98
3.15
6.13
3.27
5.85
3.19
5.66
3.44
-7
8.76
3.11
8.61
3.19
7.41
3.34
7.3
3.32
6.88
3.37
5.71
3.13
-2
6.83
1.94
6.55
2.12
6.13
2.32
5.99
2.33
5.88
2.54
5.41
2.65
2
7.13
1.95
6.87
2.07
6.48
2.30
6.35
2.31
6.29
2.57
6.08
2.60
7
9.29
1.98
9.00
2.20
8.43
2.42
8.25
2.44
7.69
2.62
7.37
2.70
10
9.81
2.06
9.71
2.20
9.27
2.35
9.12
2.49
8.11
2.58
7.47
2.61
15
10.34
1.82
10.17
1.82
9.71
2.09
9.44
2.31
8.67
2.59
7.00
2.33
18
10.64
1.85
10.49
1.92
10.03
2.16
9.63
2.35
9.00
2.66
6.71
2.16
Outdoor
Temperature
LWT 55°C
PI
TC
LWT 30°C
PI
TC
LWT 35°C
PI
TC
LWT 40°C
PI
TC
LWT 45°C
PI
TC
LWT 50°C
PI
TC
-15
10.13
4.22
9.40
4.10
8.31
4.36
7.95
4.24
7.60
4.75
-7
12.26
4.19
11.48
4.16
10.61
4.53
10.4
4.79
9.48
4.60
7.74
4.21
-2
8.93
2.53
8.65
2.85
8.24
3.05
8.10
3.09
7.94
3.30
7.27
3.54
Outdoor
Temperature
2
9.81
2.69
9.40
2.80
8.79
3.06
8.59
3.06
8.50
3.41
8.17
3.46
7
12.48
2.66
12.00
2.67
11.28
3.20
11.00
3.18
10.3
3.41
9.85
3.58
10
13.49
2.81
13.32
2.99
12.62
3.12
12.4
3.37
11.19
3.69
10.1
3.50
15
14.20
2.50
14.06
2.53
13.34
2.87
12.8
3.16
11.64
3.50
9.40
3.13
18
14.61
2.68
14.51
2.65
13.77
2.94
13.00
3.22
11.92
3.55
8.98
2.90
LWT 40°C
PI
TC
LWT 45°C
PI
TC
LWT 50°C
PI
TC
LWT 55°C
PI
TC
LWT 30°C
PI
TC
LWT 35°C
PI
TC
-15
11.75
4.97
10.86
4.90
9.54
5.08
9.10
4.97
8.81
5.34
-7
14.03
4.49
13.11
4.85
11.89
5.15
11.40
5.17
10.71
5.24
-2
10.62
3.01
10.19
3.30
9.54
3.61
9.32
3.63
9.14
3.95
8.42
4.13
2
11.09
3.04
10.69
3.22
10.09
3.58
9.88
3.59
9.78
4.00
9.46
4.04
7
14.46
3.08
14.00
3.15
13.12
3.77
12.80
3.80
11.97
4.08
11.50
4.20
10
15.11
3.17
14.94
3.39
14.27
3.63
14.10
3.83
12.49
3.97
11.60
4.06
15
15.93
2.81
15.65
2.81
14.96
3.21
14.50
3.56
13.35
4.00
10.90
3.62
18
16.38
2.85
16.15
2.95
15.44
3.31
14.80
3.63
13.87
4.10
10.40
3.35
Outdoor
Temperature
LWT : Leaving Water Temperature
TC : Total Capacity (Averaged value including defrost effect, kW)
PI : Power Input(kW)
Notice : Measuring procedure follows EN-14511
Notice : Above table values may not be matched according to installation condition
14 _ Air-to-Water Heat Pump
8.88
4.87
7. Performance Data
Model
AHUW166A1
(HU161 U31)
Model
AHUW128A1
(HU123 U31)
Model
Model
AHUW168A1
(HU163 U31)
LWT 50°C
PI
TC
LWT 55°C
PI
TC
LWT 35°C
PI
TC
LWT 40°C
PI
TC
-15
13.35
5.75
12.30
5.73
10.73
5.71
10.20
5.70
10.00
5.88
-7
15.93
5.96
14.80
5.61
12.56
5.34
12.10
5.42
11.83
5.84
9.98
5.51
-2
12.38
3.51
11.76
3.73
10.82
4.06
10.50
4.17
10.30
4.63
9.56
4.72
2
12.28
3.37
11.90
3.62
11.33
4.00
11.10
4.13
11.03
4.60
10.70
4.62
7
16.40
3.49
16.00
3.81
14.95
4.29
14.60
4.45
13.62
4.77
13.10
4.82
10
17.08
3.62
16.93
3.87
16.29
4.25
16.10
4.38
14.07
4.31
13.10
4.62
15
18.03
3.18
17.59
3.16
16.94
3.64
16.70
4.05
15.44
4.60
12.40
4.11
18
18.55
3.40
18.15
3.32
17.49
3.77
17.00
4.14
16.27
4.77
11.90
3.80
Outdoor
Temperature
LWT 30°C
PI
TC
LWT 35°C
PI
TC
LWT 40°C
PI
TC
LWT 45°C
PI
TC
LWT 50°C
PI
TC
LWT 55°C
PI
TC
-15
10.33
4.34
9.56
4.27
8.42
4.44
8.04
4.36
7.66
4.68
-7
12.42
4.32
11.66
4.31
10.49
4.54
10.02
4.61
9.37
4.58
7.73
4.23
-2
9.22
2.64
8.87
2.90
8.32
3.12
8.14
3.16
7.99
3.40
7.31
3.58
2
9.74
2.70
9.46
2.83
8.81
3.11
8.63
3.13
8.55
3.49
8.21
3.50
7
12.54
2.71
12.00
2.72
11.49
3.27
11.28
3.31
10.50
3.54
9.94
3.64
10
13.40
2.83
13.25
3.02
12.63
3.22
12.43
3.41
11.20
3.61
10.10
3.53
15
14.04
2.48
13.82
2.49
13.18
2.84
12.77
3.14
11.70
3.51
9.45
3.15
18
14.44
2.62
14.26
2.61
13.61
2.92
13.02
3.20
12.10
3.59
9.05
2.91
LWT 55°C
PI
TC
LWT 30°C
PI
TC
LWT 35°C
PI
TC
LWT 40°C
PI
TC
LWT 45°C
PI
TC
LWT 50°C
PI
TC
-15
12.04
5.09
11.11
5.07
9.74
5.17
9.29
5.12
8.82
5.26
-7
14.10
4.96
12.72
4.98
11.57
5.09
11.00
5.06
10.60
5.20
8.81
4.86
-2
10.88
3.14
10.38
3.36
9.60
3.64
9.34
3.69
9.18
4.00
8.40
4.14
2
11.06
3.09
10.89
3.28
10.10
3.60
9.90
3.66
9.83
4.07
9.43
4.05
7
14.40
3.16
14.00
3.24
13.37
3.82
13.16
3.92
12.30
4.20
11.46
4.22
10
15.21
3.26
15.06
3.49
14.46
3.79
14.26
3.95
12.90
4.04
11.55
4.06
15
15.86
2.80
15.53
2.80
14.89
3.21
14.56
3.56
13.40
4.02
10.85
3.62
18
16.32
2.92
16.02
2.94
15.38
3.31
14.87
3.64
14.10
4.14
10.43
3.35
Outdoor
Temperature
LWT 45°C
PI
TC
LWT 50°C
PI
TC
LWT 55°C
PI
TC
LWT 30°C
PI
TC
LWT 35°C
PI
TC
LWT 40°C
PI
TC
-15
14.09
5.96
12.98
5.98
11.37
6.01
10.83
6.02
10.10
5.92
-7
15.93
6.09
14.92
5.95
12.86
5.74
12.17
5.67
12.00
5.91
9.99
5.54
-2
12.72
3.74
12.08
3.92
11.04
4.20
10.69
4.29
10.50
4.63
9.57
4.74
2
12.61
3.60
12.22
3.82
11.55
4.15
11.33
4.26
11.30
4.73
10.75
4.64
7
16.40
3.71
16.00
3.81
15.56
4.42
15.41
4.62
14.40
4.95
13.09
4.84
10
17.49
3.83
17.34
4.10
16.73
4.51
16.53
4.65
15.20
4.69
13.11
4.64
15
18.05
3.19
17.61
3.18
16.95
3.66
16.68
4.07
15.50
4.62
12.36
4.13
18
18.57
3.42
18.17
3.34
17.50
3.79
17.04
4.16
16.30
4.79
11.91
3.82
Outdoor
Temperature
LWT : Leaving Water Temperature
TC : Total Capacity (Averaged value including defrost effect, kW)
PI : Power Input(kW)
Notice : Measuring procedure follows EN-14511
Notice : Above table values may not be matched according to installation condition
Air-to-Water Heat Pump _ 15
Outdoor Unit
AHUW148A1
(HU143 U31)
LWT 45°C
PI
TC
LWT 30°C
PI
TC
Outdoor
Temperature
8. Noise Criteria
Overall
Notes:
- Sound measured at 1m away with 1.5m height.
- Data is valid at free field condition.
- Data is valid at nominal operation condition.
- Reference acoustic pressure acoustic 0dB-20Pa.
- Sound level will vary depending on a range of factors such as
the construction(acoustic absorption coefficient) of particular
room in which the equipment is installed.
- The operating conditions are assumed to be standard.
1m
Microphone
1.5m
(dB(A)±3)
1Φ, 220-240V, 50Hz
Cooling
Heating
Model
AHUW096A1 (HU091 U41)
AHUW126A1(HU121 U31)
AHUW146A1(HU141 U31)
AHUW166A1(HU161 U31)
52
54
54
54
(dB(A)±3)
3Φ, 380-415V, 50Hz
Cooling
Heating
Model
52
53
53
53
AHUW128A1 (HU123 U31)
AHUW148A1 (HU143 U31)
AHUW168A1 (HU163 U31)
54
54
54
53
53
53
Sound pressure level
n Cooling(1Ø)
AHUW146A1(HU141 U31)
70
70
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
Approximate
Hearing
Threshold
NC-15
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
NC-55
50
NC-50
AHUW166A1(HU161 U31)
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-20
NC-15
10
125
250
500
1000
2000
4000
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-15
10
63
8000
Octave Band Center Frequency (Hz)
16 _ Air-to-Water Heat Pump
NC-65
60
NC-60
NC-55
50
NC-50
125
250
500
1000
2000
4000
8000
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-20
Octave Band Center Frequency (Hz)
80
63
NC-60
NC-20
10
63
NC-65
60
Octave Band Sound Pressure Level (dB re 20Pa )
80
Octave Band Sound Pressure Level (dB re 20Pa )
Octave Band Sound Pressure Level (dB re 20Pa )
AHUW126A1(HU121 U31)
80
20
Octave Band Sound Pressure Level (dB re 20Pa )
Outdoor Unit
AHUW096A1 (HU091 U41)
80
NC-20
NC-15
10
63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
8. Noise Criteria
n Heating(1Ø)
AHUW126A1(HU121 U31)
AHUW146A1(HU141 U31)
80
70
70
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-60
NC-55
50
NC-50
NC-15
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-20
10
63
NC-65
60
NC-65
60
NC-60
NC-55
50
NC-50
NC-15
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-20
10
63
Octave Band Sound Pressure Level (dB re 20Pa )
80
Octave Band Sound Pressure Level (dB re 20Pa )
Octave Band Sound Pressure Level (dB re 20Pa )
AHUW096A1 (HU091 U41)
80
NC-20
NC-15
10
63
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
AHUW166A1(HU161 U31)
Octave Band Sound Pressure Level (dB re 20µPa )
80
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
Outdoor Unit
NC-25
20
Approximate
Hearing
Threshold
NC-20
NC-15
10
63
125
250
500
1000
2000
4000
8000
Approximated SPL at specific distance : SPL[dB] = A + 20xLog(B/C)
where A[dB] : SPL at 1m distance
B[m] : 1m
C[m] : specific distance
Air-to-Water Heat Pump _ 17
8. Noise Criteria
n Cooling(3Ø)
AHUW148A1 (HU143 U31)
70
70
70
NC-65
60
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
Approximate
Hearing
Threshold
NC-60
NC-55
50
NC-50
NC-40
250
500
1000
2000
4000
NC-35
30
NC-30
Approximate
Hearing
Threshold
63
NC-55
50
NC-50
125
250
500
1000
2000
4000
NC-40
NC-30
63
8000
70
NC-60
NC-55
50
NC-50
NC-45
NC-40
NC-35
NC-30
NC-25
Approximate
Hearing
Threshold
NC-60
NC-55
50
NC-50
NC-15
125
250
500
1000
2000
4000
8000
Octave Band Center Frequency (Hz)
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-20
10
63
NC-65
60
NC-15
125
250
500
1000
2000
4000
500
1000
2000
4000
8000
NC-65
NC-60
NC-55
50
NC-50
NC-45
40
NC-40
NC-35
30
NC-30
NC-25
20
Approximate
Hearing
Threshold
NC-20
NC-15
10
8000
Octave Band Center Frequency (Hz)
Approximated SPL at specific distance : SPL[dB] = A + 20xLog(B/C)
where A[dB] : SPL at 1m distance
B[m] : 1m
C[m] : specific distance
18 _ Air-to-Water Heat Pump
250
60
NC-20
10
63
Octave Band Sound Pressure Level (dB re 20Pa )
70
Octave Band Sound Pressure Level (dB re 20Pa )
70
NC-65
NC-15
125
AHUW168A1 (HU163 U31)
AHUW148A1 (HU143 U31)
80
60
NC-20
Octave Band Center Frequency (Hz)
80
20
NC-25
10
80
30
NC-35
30
Octave Band Center Frequency (Hz)
n Heating(3Ø)
AHUW128A1 (HU123 U31)
40
NC-45
40
Approximate
Hearing
Threshold
NC-15
Octave Band Center Frequency (Hz)
Octave Band Sound Pressure Level (dB re 20Pa )
NC-60
NC-20
10
8000
NC-65
60
20
NC-25
20
NC-15
125
NC-45
40
NC-20
10
63
NC-65
60
Octave Band Sound Pressure Level (dB re 20Pa )
80
20
Outdoor Unit
AHUW168A1 (HU163 U31)
80
Octave Band Sound Pressure Level (dB re 20Pa )
Octave Band Sound Pressure Level (dB re 20Pa )
AHUW128A1 (HU123 U31)
80
63
125
250
500
1000
2000
4000
Octave Band Center Frequency (Hz)
8000
Part 3. Accessories
1. Dry Contact (PQDSA)
2. Remote Temperature Sensor (PQRSTA0)
3. PI485 (PMNFP14A0)
4. Sanitary Water Tank Kit(PHLTA/PHLTC)
5. Solar Thermal Kit(PHLLA)
1. Dry Contact (PQDSA)
1.1 Overview
LG Dry Contact is a solution for automatic control of air conditioning system at the ownerʼs behest.
In simple words, itʼs a switch which can be used to turn the unit On/Off after getting the signal from external sources like
key-in lock, door or window switch etc specially used in Hotel rooms.
Itʼs a small PCB that either can be fit inside the control box of Indoor unit or can be outside the unit in a plastic case if there
is no sufficient space inside the Indoor unit.
Apart from simple installation, it can also be linked to Central Controller via Indoor unit PI485 pcb. For this, all connecting
wires & an additional small pcb for looping is also provided along with Dry Contact.
Dry Contact can be used in two ways.
1. It can be used to actually turn On/Off the system on receiving the signal from the source.
In this case, user doesn't need to use remote controller anymore to turn On/Off the system.
However all the further settings like temperature, fan speed, mode etc can be done through remote controller only.
2. Other way is almost similar as above but in this case, after getting the On signal from the external source, user has to
turn On the system from remote controller only. Dry contact just activates the system.
However system can be turned Off directly from the external source. So only On mode is different here.
So in both of above conditions, system canʼt be operated without signal from external source which prevents unnecessary
use of system & facilitates its operation only when its required.
These settings can be selected from the remote controller whose details have been explained in the later part of this manual
So depending upon the requirement, Dry Contact offers a variety of applications to suit the customerʼs requirement in the
best possible way.
Power
Connector
Indoor PCB
Connector
Accessories
Dry Contact Controller
Connector
Air-to-Water Heat Pump _ 1
1. Dry Contact (PQDSA)
1.2 Part Description
1 CN-POWER : AC 220V Connector
2 CN-CC : Indoor PCB Connector
3 CN_DRY (L) : DRY CONTROLLER Connector
4 CN_DRY ( SIG ) : DRY CONTROLLER Connector
1
2
3
4
5
5 CN_DRY (ERROR CHECK) : ERROR Check Display Connector
6 CN_DRY( OPER STATE): Operation Display Connector
6
1.2.1 Accessory
Cable 1EA
(for Central controller)
Connecting PCB
(6871A30056A)
*for Central Controller
Dry contact
(For installation, 4EA)
Accessories
Cable 3EA
(for connecting with indoor unit)
Dry contact - 4EA
(For assembly the case)
User/Installation
Manual
[Structure of each cable]
NOTE
• These cable using for connection between Dry contact and Indoor unit.
• So before using these things Please check the connector type first and use cables on proper indoor unit.
2 _ Air-to-Water Heat Pump
1. Dry Contact (PQDSA)
1.3 Installation Guide
1.3.1 Step 1
Connect CN-CC with Indoor PCB by the cable(provided)
- Connection of Dry contact only
DRY CONTACT
PCB
Indoor
PCB
CN-CC
4
3
2
1
CN-CC
2 1
2 1
4
3
2
1
AC 220V
- Connection of Dry contact & LG Central Controller in case of single constant models.
Connection PCB
(6871A30056A)
DRY CONTACT
PCB
Indoor
PCB
CN-CC
4
3
2
1
CN-CC
2 1
2 1
4
3
2
1
AC 220V
S1
IC01A
OSC01B
L02D
L01D
C01A
BR1
PI485 PCB : Special purchase for
Central Control
(Ex : PHNFP14A0 or PSNFP14A0...)
SWITCH
U04Y
U02Y
LED1
LED01G
LED02G
LED03G
L1 2 3 4
ON
U03Y
C04Y
C03Y
TANS01Y
ZNR01Y
CN_COMM
* Single Only
- When you install single product this PCB have to add.
Accessories
Air-to-Water Heat Pump _ 3
1. Dry Contact (PQDSA)
1.3.2 Step 2
Connect CN_DRY with Control Unit. (Fix SUB PCB into the proper location.)
- To apply power source through PCB
DRY CONTACT
PCB
CN-CC
RY2
RY1
4
3
2
1
4
3
2
1
CN_DRY
Operation Display
Error Check Display
Dry contact
Controller
L
N
2 1
2 1
INPUT
AC 220V
LG does not
supply this section
- To apply power source directly to external source
DRY CONTACT
PCB
CN-CC
RY2
RY1
4
3
2
1
CN_DRY
4
3
2
1
Operation Display
Error Check Display
Dry contact
Controller
L
N
2 1
2 1
Accessories
INPUT
AC 220V
4 _ Air-to-Water Heat Pump
LG does not
supply this section
2. Remote Temperature Sensor (PQRSTA0)
2.1 Part Description
Remote temperature sensor can be installed any place a user wants to detect the temperature.
2.1.1 Remote Sensor
70mm
120mm
Remote Sensor
Connection Wire
2.1.2 Parts
Connection wire
15m(1EA)
Fixing screw for
Remote Sensor(2EA)
Installation Manual
Accessories
Air-to-Water Heat Pump _ 5
2. Remote Temperature Sensor (PQRSTA0)
2.2 Installation Method
2.2.1 How to use
1. After deciding where the remote temperature sensor is installed, decide
the location and height of the fixing screws.
(Interval between the screws : 60mm)
Fixing screws
60mm
2. Insert the connector of the connection wire into the space for the
connector in place of the room temperature sensor. (CN_ROOM)
3. Separately, set the option code of the attached controller on the indoor unit.
In detail, refer to "installer setting mode" in the owner's manual.
2.2.2 How to connect the remote temperature sensor and the connection wire
The Connection wire does not matter if you change the color of the wire because of non-polar
2.2.3 How to install the remote temperature sensor on the wall
Integrate the remote temperature sensor with the screws as the order of arrows.
Accessories
Fixing the
Remote Sensor
CAUTION
1. Choose the place where the average temperature can be measured for the place the indoor unit operates.
2. Avoid direct sunlight.
3. Choose the place where the cooling/heating devices do not affect the remote sensor.
4. Choose the place where the outlet of the cooling fan do not affect the remote sensor.
5. Choose the place where the remote sensor isnʼt affected when door is open.
6 _ Air-to-Water Heat Pump
3. PI485 (PMNFP14A0)
3.1 Part Description
L1 2 3 4
ON KSDO4H
1
2
3
4
5
6
7
8
9
10
11
h The location of parts might be different in case of PMNFP14A1.
PMNFP14A0 : For connecting 1 ~ 16 Indoor Units
PI485 GATEWAY(M)
1 CN_PWR: AC 220V Connector
2 +10V: DC 10V Terminal
3 GND: Ground
4 BUS_A: *RS-485 (+) Terminal
(Refer to note)
5 BUS_B: RS-485 (-) Terminal
6 CN_OUT: Outdoor Unit Connector
7 LED1:RS-485 Status LED
8 DIP Switch: Product Selection (Refer to the 「DIP Switch Configuration」)
9 LED01G, 02G, 03G: Communication Status LED
Accessories
10 Reset Switch: PI485(M) Reset
11 CN_DRY: DRY Contact
NOTE
RS-485 is one of the international interface standards for serial communication.
Air-to-Water Heat Pump _ 7
3. PI485 (PMNFP14A0)
3.2 Accessory Parts
L1 2 3 4
ON KSDO4H
Multi-V
PI485 : PMNFP14A0(1EA)
or PMNFP14A1(1EA)
or PGNFP14A0(1EA)
BRACKET (1EA)
MPS Multi
Multi-V
WIRE ASSY 1(1EA)
Accessories
Others : Tie Wrap (3 EA) - Cable Tie
Clamp (1 EA)
8 _ Air-to-Water Heat Pump
SCREW (4EA)
WIRE ASSY 2(1EA)
WIRE ASSY 3(1EA)
3. PI485 (PMNFP14A0)
3.3 Installation Guide
3.3.1 Installation Steps
1. 6 Connect CN_OUT with Outdoor Unit by the cable (provided)
2. 4 5 Connect RS-485 BUS_A(+) and BUS_(B)(-) with other network products (ex. Central Controller , IGateway.....)
3. 2 3 In case of using Simple Central Controller, connect VCC(+10V) and GND.
No need to connect otherwise.
4. 8 Select DIP Switch Configuration(Refer page 8)
5. 1 Connect CN_PWR with Outdoor PCB Power connector (Refer page 9, 10)
6. After Power is ON, check the Communication LED 9
- LED1G(Red)
• Normal : LED blinks for 5 times and then gets OFF
This process is repeated after every 3 minutes
• Error : Check the Indoor Unit's address & wiring connections
- LED2G(Yellow), LED3G(Orange)
• Normal : LED blinks continuously
• Error : Check the DIP Switch setting & wiring connections
7. 7 Check RS-485 Communication Status LED:
• Normal : LED's blinks 2 times in every 10~30 seconds
• Error : Check the wiring connections
8. Finally if all of the above steps are OK, then tie the cables by tie wraps & clamp
CAUTION
Install the PI485 after checking the hole for screw.
Accessories
Air-to-Water Heat Pump _ 9
4. Sanitary Water Tank Kit(PHLTA/PHLTC)
- Must be sued for communication of sanitary water tank and indoor unit
- PHLTA For 1phase Indoor model (AHNW**6**A1)
- PHLTC For 3phase Indoor model (AHNW**A**A1, AHNW**8**A1)
h PHRSTA0 : Sanitary water tank sensor (Thermistor) only
4.1 Part Description
1 Sensor (Thermister) : This sensor (PHRSTA0) can be supplied separately.
2 Sensor Adaptor
- It can be attached on the sanitary water tank
- Thermister is inserted in the sensor adaptor
- Connection 1/2"(12.7mm) BSP
3 MCCB (Circuit breaker) 40A
4 Magnetic switch
5 Installation manual
6 1 phase IDU model bracket (PHLTA only)
7 3 phase IDU model bracket (PHLTC only)
1
6
7
(PHLTA only)
(PHLTC only)
Accessories
5
3
2
10 _ Air-to-Water Heat Pump
4
5. Solar Thermal Kit(PHLLA)
- Must be used for communication of solar thermal component and indoor unit.
5.1 Model
- PHLLA : Sensorʼs limit temperature 100℃
5.2 Part Description
1 Sensor (Thermister)
2 Sensor Adaptor
- It can be attached on T type pipe fitting attatched in the pipe of solar thermal component
- Thermister is inserted in the sensor adaptor
- Connection 1/2"(12.7mm) BSP
3 T type pipe fitting (option)
1
2
3
Accessories
Air-to-Water Heat Pump _ 11
P/No.: 3828A20892W
Air Conditioner
20 Yeouido-dong, Yeongdeungpo-gu,
Yeouido P.O.Box 335 Seoul,
150-721, Korea.
http://www.lgeaircon.com
All rights reserved
Printed in Korea December / 2012
The specifications, designs, and
information in this brochure are subject to
change without notice.
The air conditioners manufactured by LG have received
ISO9001 certificate for quality assurance and ISO14001
certificate for environmental management system.