MODEL XR200A WIRING DIAGRAM

MODEL XR200A WIRING DIAGRAM
MODEL XR200A WIRING DIAGRAM
Refer to the XR200A Installation Guide (LT-0482) for a complete description of wiring connections.
Refer to the XR200 Programming Manual (LT-0196) for complete programming instructions.
CAUTION
Danger of explosion if lithium battery is incorrectly replaced.
Replace only with DMP part number BT-0005 or equivalent
type. When discharged, disposal of used lithium battery is
non- hazardous per USEPA criteria. Disposal according to
local, state, and federal waste regulations.
s
s
DD, MPX
Selection
Form C Relays
AC wiring must be in conduit and exit out the left
side of the enclosure.
K4
Output Header J2
Relay Output 2
Use Model 305
Secondary Power Supply
1.2 Amps max. charging current.
Use only 12 VDC rechargable
batteries. DMP Model 367.
Replace every 3 to 5 years.
Protective
Earth Ground
22 GA. MIN
s
9
10
11
12
13
14
s
s
s
s
17
18
s
s
1
9
s
20
s
s
s
21
s
s
1k Ω 1k Ω
1k Ω 1k Ω
Z7 GND Z8
22
23
s
s
24
25
26
27
1k Ω 1k Ω
s
s
s
s
s
s
s
Model 690
100mA at 8 to 16 VDC.
ZONE EXPANDER
Model 715
7mA @ 12 VDC
Models 715-8, 715-16
20mA @ 12 VDC
ZONE EXPANDER
Model 714
s
1k Ω
s
s
1k Ω
s
s
s = Supervised Circuit
Black
s
Zones 9 and 10 and
Model 715 compatibility
identifier: A
Maximum operating
range:
8.8 VDC to 14.2 VDC.
3.3k Ω
Red
Red
Yellow
Green
s
28
s
s
Heat detectors,
pull stations, or
any other shorting
devices can be
connected to
zones 9 and 10.
Auxiliary Power
Total current 1.0 Amps
combined from Terminals
7, 11, 26, & 28.
s
Model 790 and 791
100mA at 8 to 16 VDC.
Tamper protection
when required for
Model 350A Attack
Resistant Enclosure.
Z9 + Z9 - Z10 + Z10 -
3.3k Ω
Keypads
Model 670, 770, and 771
100mA at 8 to 16 VDC.
Model 793
100 mA at 8 to 16 VDC.
16
1k Ω 1k Ω
Bell
Bell
12 VDC nominal
Total current 1.5 Amps max.
15
Z5 GND Z6
ZONE 7
RED
RED
s
BLACK
s
Maximum AC wire distance
With 16 gauge wire: 70 feet
With 18 guage wire: 40 feet
YELLOW
16 to 18 gauge wire
8
ZONE 3
7
Z3 GND Z4
ZONE 2
6
ZONE 1
5
BLACK
4
22 GA. MIN
3
GREEN
2
-B BELLGND RED YEL GRN BLK SMK GND Z1 GND Z2
22 GA. MIN
1
+B
22 GA. MIN
s
AC
Rear Tamper
J6
J16
Command
Processor
Reset
K7
K6
Relay Output 1
Use Model 305
AC
White/Orange
White/Yellow
White/Green
White/Blue
White/Violet
White/Gray
White
White/Black
Black
Front Tamper
J2 Output color code for
Model 430 Output Harness
ZONE 6
Battery Only Restart CR7
Primary Power
16VAC
40 - 100 VA
Output 3
Output 4
Output 5
Output 6
Output 7
Output 8
Output 9
Output 10
Ground
J2
ZONE 5
K2
ZONE 4
Answering
Machine
Bypass Relay
Use Model 305
Voltage Outputs
Wiring on terminals
5 through 22 must
exit to the right and
maintain a 1/4"
separation from the
AC and battery
positive wiring.
Ground Start
Relay
Use Model 305
Violet
Gray
Orange
Violet
Gray
Orange
J6 Interface Connector
Tamper Header J4
N/C
Com
N/O
N/C
Com
N/O
ZONE 10
Phone Jack Connector
Output 1
Output 1
Output 1
Output 2
Output 2
Output 2
Lithium
Battery
J11
ZONE 9
J12
ZONE 8
J3
s
1k Ω
Keyswitch Arming
Can be connected to any loop.
Disarm
s
Arm
1k Ω
ZONE
EXPANDER
Model 711/711E
7mA at 12 VDC
Models 714-8, 714-16
20mA @ 12 VDC
s
Power
Supervision
Relay
Refer to LT-0164 for a list of approved 4-wire
smoke detectors and power supervision relays.
s
s
s
s
s
s
s
s
3.3k Ω 3.3k Ω 3.3k Ω 3.3k Ω
Smoke
Detector
s
Ð+
s
s
s
s
s
1k Ω 1k Ω 1k Ω
s
1k Ω
7mA at
12 VDC
s
s
In all applications where more than one wire is
under a terminal, the wire must be cut, and not
looped around the screw terminal.
s
s
See the XR200A Installation Guide for a
list of approved 2-wire smoke detectors
for zones 9 and 10 and 715 Zone
Expanders.
1k Ω
WARNING!
Installation to be
performed by
authorized personnel.
ACN 087 480 279
LT-0468 (11/01)
Was this manual useful for you? yes no
Thank you for your participation!