ec1000_energy_box_ds_en

ec1000_energy_box_ds_en
NRGence™ Energy Intelligence Solutions
Energy Box
EC1000
The EC1000 Energy Box is the latest evolution of NRGence™ - ATEN's energy intelligence solutions. It is the
intelligent, cost effective solution to monitor ATEN's Energy PDUs - to ensure safe and effective energy-saving
power management.
The EC1000 Energy Box has four Energy Sensor ports to connect to four Energy PDU modules and four
Environment Sensor ports for external sensors to monitor environmental conditions. Each environmental sensor
can provide measured readings of temperature, humidity, and differential pressure from separate areas of a data
room, giving a wide range of monitoring and protection you need.
The Energy Box allows power and environmental data to be monitored and displayed at the rack or remotely for
easy viewing and maintenance. The Energy Box is a standalone unit with Over IP monitoring that is controlled by
Web GUI or ATEN's eco Sensors software.
The EC1000 Energy Box features real-time status, system logs, threshold alerts, and event notifications. The
EC1000 logs power and environmental conditions according to customizable minimum/maximum thresholds set
for electrical current, temperature, humidity, and differential pressure.
Remote monitoring offers secure access with 128bits SSL encryption, and customizable account policies for user
management. Remote authentication supports RADIUS and additional management interfaces including HTTP,
HTTPS, and SNMPv1&v2&v3 (Read, Write, Trap). Event notifications can be monitored via Syslog/SMTP/SNMP trap
and audible alarms for real-time local and remote alerting.
When used in conjunction with ATEN's Energy PDUs* and eco Sensors Energy Management Software*, the
EC1000 allows you to conveniently upgrade your cabinet with remote energy management functionality to make
your server room go green quickly and cost-effectively.
* ATEN series of low cost Energy PDUs (PE1216/PE1324) and energy management software – eco Sensors are available at
www.aten.com.
EC1000 front view
1
EC1000 rear view
NRGence™ Energy Intelligence Solutions
Features
Operation
•Space saving 1U rack mounting with front and rear mounting
•4 RJ-45 Energy Sensor Ports to monitor four Energy PDU currents (0A to 32A per port)
•4 RJ-11 Environment Sensor Ports to monitor temperature, humidity, and differential pressure*
•Maximum Amperage Monitor [email protected]~240V (Energy Box)
•3 digit 7 segment front panel LED displays current/sensor/IP address information
•Threshold monitoring for:
◊ Current
◊ Temperature*
◊ Humidity*
◊ Differential pressure*
•Threshold alerting through:
◊ Local: audible alarm and LED lights
◊ Remote: SMTP/SNMP trap/Syslog
Management
•Front panel LED indicators for current, temperature*, humidity*, differential pressure*, and IP address information at
the Energy Box
•Remote real-time current, temperature*, humidity*, and differential pressure* monitoring and management
•Management through eco Sensors Energy Management Software or 3r party SNMP manager
•Supports name assignment for individual Energy PDUs
•Event Logging – 128 line event log
•Syslog support
•F/W upgradable
Remote Access
•Remote management via TCP/IP using built in 10/100Mbps Ethernet port
•Management via built in browser based GUI
•Network Interfaces: TCP/IP, UDP, HTTP, HTTPS, SSL, SMTP, DHCP, NTP, DNS, 10Base-T/100Base-TX, auto sense, Ping
•Supports SNMP Manager V1, V2, V3
Security
•Strong security features include password protection and advanced encryption technologies – utilizing 128 bit SSL
•RADIUS authorization and authentication
* Requires external sensors
2
NRGence™ Energy Intelligence Solutions
Benefits
Real-time Monitoring
The EC1000 monitors the electrical current of 4 Energy PDU's, along with room
temperature, humidity, and differential pressure using environmental sensors.
Early Warning
Notification
The EC1000 allows administrators to set custom thresholds. When levels exceed
the user defined thresholds, designated recipients can receive alarm notifications
via SMTP email, SNMP traps, or Syslog alerts. An audio alarm and flashing lights
can also be set to alert administrators locally.
External Authentication
Support
The EC1000 supports login authorization management from external sources via
RADIUS.
Cost-effective Energy
Management
Using NRGence™ Energy PDUs and an EC1000 Energy Box utilized by the intuitive
and user-friendly eco Sensors management software- allows you to remotely and
continuously monitor environment and power status, to optimize data center
energy management by utilizing automated power analysis reports.
Temperature
Sensor
Remote Monitoring
and Management
Network
Humidity
Sensor
Up to 4 sensors
Up to 4 Energy PDUs
3
NRGence™ Energy Intelligence Solutions
Specifications
Function
EC1000
Energy PDU Connections
4
Port Selection
Connectors
Switches
Pushbutton
Energy Sensor
4 x RJ-45 Female
Environment Sensor
4 x RJ-11 Female
Power
1 x DC Jack
LAN
1 x RJ-45 Female
Reset
1 x Semi-recessed Pushbutton
Selection
1 x Selection Pushbutton
PDU Status
4 (Orange)
Sensor Status
4 (Green)
Energy/Environment/IP
LEDs
3 (Green)
Selection
1 digit 7-segment (Orange)
Current/Sensor/IP Address
3 digit 7-segment (Orange)
Power
LAN
1 (Blue)
10M/ 100Mbps
Link
1 (Orange/Green)
1 (Green)
100–240V; 50/60Hz; 0A to 32A (per port)
Monitoring Range
LED Display Resolution 0.1A
Precision: ±[email protected] ~ 1A, ±1%@ >1A
Power Consumption
DC 5.3 V
Operating Temp.
Environment
Storage Temp
Humidity
Physical Properties
0–50°C
-20–60°C
0–80% RH, Non-condensing
Housing
Metal
Weight
0.59 kg
Dimensions (L x W x H)
20.00 x 7.59 x 4.20 cm
Optional Equipments
Environment Sensors
Sensors are optional accessories. You can use the EC1000 Energy Box without sensors. However, if you want to have
complete energy management of your data center with the full use of the EC1000 Energy Box, you need to use eco
Sensors software* and install 4 sensors for each of the PDU rack locations to generate a complete energy-efficient data
and chart.
Part No.
EA1140
EA1240
EA1340
Sensor
Temperature
Temperature / Humidity
Differential Pressure / Temperature
* Please see www.aten.com for more details.
ATEN International Co., Ltd.
4
3F., No.125, Sec. 2, Datong Rd., Sijhih District., New Taipei City 221, Taiwan
Phone: 886-2-8692-6789 Fax: 886-2-8692-6767 www.aten.com E-mail: [email protected]
Publish Date: 11/2016 V3.0
© Copyright 2016 ATEN® International Co., Ltd.
ATEN and the ATEN logo are trademarks of ATEN International Co., Ltd.
All rights reserved. All other trademarks are the property of their
respective owners.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement