Bosch D296, D297 Beam Smoke Detectors Installation Instructions

Below you will find brief information for Beam Smoke Detectors D296, Beam Smoke Detectors D297. The D296 (24 VDC) and D297 (12 VDC) Long-range Beam Smoke Detectors have a separate transmitter and receiver. Internal pointability provides coverage flexibility without brackets. Automatic signal synchronization and range adjustment reduce installation costs. Selectable sensitivity and alarm response time provide installation flexibility.

PDF Download
Document
Bosch Beam Smoke Detectors D296, D297 Installation | Manualzz

Advertisement

Advertisement

Advertisement

Key features

  • Internal pointability
  • Automatic signal synchronization
  • Range adjustment
  • Selectable sensitivity
  • Alarm response time
  • Remote indicator plate
  • Remote test and indicator plate
  • Test cable
  • Sensitivity Test filters

Frequently asked questions

The maximum spacing between the beam paths is 60 ft (18.3 m).

Connect a VOM to the voltage monitor contacts on the D306 or D307 if used. If you do not have a D306 or D307 connected to the detector, remove the receiver access door and measure the reference voltage using the supplied test cable.

Remove the access cover and press the setup button to initiate a reset of the reference voltage.

The D296 operates at 18.0 VDC to 32.0 VDC, while the D297 operates at 10.2 VDC to 15.0 VDC.

Remove power from the receiver for at least 1 sec., then reapply power.

Use the Sensitivity Test Kit supplied with the detector to check detector sensitivity only during installation. For field testing, order and use a D308 Test Kit.