DMG700
31100124
GB DIGITAL MULTIMETER
G
B
I271 I GB F E 01 13
LOVATO ELECTRIC S.P.A.
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. 035 4282111
FAX (Nazionale): 035 4282200
FAX (International): +39 035 4282400
E-mail [email protected]
Web www.LovatoElectric.com
DMG700
D
Available in German at www.LovatoElectric.com/I271D.pdf
CZ
Available in Czech at www.LovatoElectric.com/I271CZ.pdf
PL
Available in Polish at www.LovatoElectric.com/I271PL.pdf
RU
Available in Russian at www.LovatoElectric.com/I271RU.pdf
WARNING!
– Carefully read the manual before the installation or use.
– This equipment is to be installed by qualified personnel, complying to current standards, to avoid damages or safety hazards.
– Before any maintenance operation on the device, remove all the voltages from measuring and supply inputs and short-circuit the CT input terminals.
– The manufacturer cannot be held responsible for electrical safety in case of improper use of the equipment.
– Products illustrated herein are subject to alteration and changes without prior notice. Technical data and descriptions in the documentation are accurate, to
the best of our knowledge, but no liabilities for errors, omissions or contingencies arising there from are accepted.
– A circuit breaker must be included in the electrical installation of the building. It must be installed close by the equipment and within easy reach of the
operator. It must be marked as the disconnecting device of the equipment:
IEC/EN 61010-1 § 6.11.2.
– Clean the instrument with a soft dry cloth; do not use abrasives, liquid detergents or solvents.
INDEX
Page
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Keyboard functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Measurement viewing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2
Table of display pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Display page navigation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3
Energy meters page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Hour counters page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Trend graph page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Counters page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
User pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4
Main menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Password access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Settings lock. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
Expandability . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
Additional resources. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
Communication channels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6
Inputs, outputs, internal variables, counters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Limit thresholds . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Boolean logic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Remote-controlled variables. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
7
Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Tariffs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Setting of parameters (set-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8
Table of parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9
Commands menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Wiring test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Technical characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Terminal arrangement. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Mechanical dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Wiring diagrams. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
INTRODUCTION
The DMG700 multimeter has been designed to combine the maximum possible easiness of operation together with a wide choice of advanced functions. The
flush-mount 96x96mm housing combines modern design of the front panel with tool-less mounting of the device body and the expansion capability of the rear
panel, where it is possible to mount plug-in
EXP series modules. The graphic backlight LCD display offers a user-friendly interface. The rich variety of functions, makes the DMG series multimeters the ideal
choice for a wide range of applications.
1
31100124
I271 I GB F E 01 13
DESCRIPTION
– Flush-mount housing, 96x96mm
– Graphic LCD display, 128x80 pixels, white backlight, 4 levels of grey
– 4 keys for viewing and setting
– Easy and fast navigation
– Compatible with LV, MV, HV applications
– Texts for measurements, setup and messages in 5 languages
– Reading of more than 160 electrical parameters
– Expansion bus for maximum 4 plug-in modules EXP series
– Advanced programmable I/O functions
– True RMS measurements
– Continuous (gapless) sampling
– High accuracy
– Sealable terminal covers
– Settings lock through sealable dip-switch.
KEYBOARD FUNCTIONS
MENU key - Used to enter or exit from viewing and setting menus.
s and t keys - Used to scroll display pages, to select among possible choices and to modify settings (increment-decrement).
key - Used to rotate through sub-pages, to confirm a choice, to switch between viewing modes.
MEASUREMENT VIEWING
– The s and t keys allow to scroll the pages of viewed measurements one by one. The page being viewed is written in the title bar.
– Some of the readings may not be shown, depending on the programming and the wiring of the device (for instance, if programmed-wired for a three-phase
without neutral system, L-N voltage page is not shown).
– For every page, the
key allows to rotate through several sub-pages (for instance to show the highest/lowest peak for the selected readings).
– The sub-page viewed is indicated in the status bar on the bottom of the display by one of the following icons:
• IN = Instantaneous value - Actual instantaneous value of the reading, shown by default every time the page is changed.
• HI = Highest peak - Highest peak of the instantaneous value of the relative reading. The HIGH values are stored and kept even when auxiliary power is
removed. They can be cleared using the dedicated command (see commands menu).
• LO = Lowest peak - Lowest value of the reading, stored from the time the DMG is powered-on. It is resetted using the same command used for HI values.
• AV = Average value - Time-integrated value of the reading. Allows showing measurements with slow variations. See integration menu in setup chapter.
• MD = Maximum Demand - Maximum peak of the integrated value. Stored in non-volatile memory and it is resettable with dedicated command.
• GR = Graphic bars - Shows the measurements with graphic bars.
Example of display page with numeric indication
1 - Unit of measure
2 - Measurement
3 - Title bar
4 - Phase indication
5 - Sub-page indication
Example of display page with bar-graphs
1 - Unit of measure
2 - Measurement
3 - Phase indication
4 - HI-LO markers
– The user can define to which page and sub-page the display must return to after a period of time has elapsed without any keystroke.
– If needed, it is possible to set the multimeter so that the display will remain always in the position in which it has been left.
– To set these functions see menu M02 – Utility.
2
G
B
31100124
TABLE OF DISPLAY PAGES
I271 I GB F E 01 13
Selection with s and t
Selection with
N°
PAGE
1
PHASE-TO-PHASE VOLTAGES - V(L1-L2), V(L2-L3), V(L3-L1), V(LL)EQV
HI
LO
SUB PAGES
AV
2
PHASE-TO-NEUTRAL VOLTAGES - V(L1-N), V(L2-N), V(L3-N), V(L-N)EQV
HI
LO
AV
3
PHASE AND NEUTRAL CURRENTS - I(L1), I(L2), I(L3), I(N)
HI
LO
AV
MD
GR
4
ACTIVE POWER - P(L1), P(L2), P(L3), P(TOT)
HI
LO
AV
MD
GR
5
REACTIVE POWER - Q(L1), Q(L2), Q(L3), Q(TOT)
HI
LO
AV
MD
GR
6
APPARENT POWER - S(L1), S(L2), S(L3), S(TOT)
HI
LO
AV
MD
7
POWER FACTOR - PF(L1), PF(L2), PF(L3), PF(EQ)
HI
LO
AV
8
FREQUENCY-ASYMMETRY - F, ASY(VLL), ASY(VLN), ASY(I)
HI
LO
AV
9
PH-PH VOLTAGE HARMONIC DISTORTION - THD-V(L1-L2), THD-V(L2-L3), THD-V(L3-L1)
HI
LO
AV
10
PH-N VOLTAGE HARMONIC DISTORTION - THD-V(L1), THD-V(L2), THD-V(L3)
HI
LO
AV
GR
11
CURRENT HARMONIC DISTORTION - THD-I(L1), THD-I(L2) THD-I(L3)
HI
LO
AV
GR
12
ENERGY METERS - kWh+(TOT), kWh-(TOT), kvarh+(TOT), kvarh-(TOT), kVA(TOT)
13
ENERGY TARIFFS
14
TREND GRAPH
15
HOUR COUNTER - Hr(TOT), Hr(Partial)
16
EXPANSION MODULES
17
18
GR
G
B
GR
GR
GR
GR
PARTIAL
TAR1
...
TAR4
COUNTERS
CNT1
...
CNT4
LIMIT THRESHOLDS
LIM1
...
LIM8
19
BOOLEAN LOGIC
BOO1
...
BOO8
20
ALARMS
ALA1
...
ALA8
21
INFO-REVISION-SERIAL NO.
MODEL, REV SW, REV HW, Nº SERIES / INTERNAL TEMPERATURE
22
LOGO
23
(USER-DEFINED PAGE 1)
24
(USER-DEFINED PAGE 2)
25
(USER-DEFINED PAGE 3)
26
(USER-DEFINED PAGE 4)
NOTE: Some of the pages listed above may not be available if the function that they must view is not enabled.
For instance, if no alarm is programmed, then the Alarm page will not be shown.
DISPLAY PAGE NAVIGATION
Phase-Phase voltages
IN = Instantaneous value
HI = Highest value
LO = Lowest value
AV = Average value
GR = Graphic bars
HI = Highest value
LO = Lowest value
AV = Average value
GR = Graphic bars
HI = Highest value
LO = Lowest value
AV = Average value
MD = Max demand
Phase voltages
IN = Instantaneous value
Phase-Neutral currents
IN = Instantaneous value
(continued)
3
31100124
ENERGY METERS PAGE
– The Energy meters page shows the following meters simultaneously:
• active energy, imported and exported
• reactive energy, imported and exported (inductive / capacitive)
• apparent energy.
– The main page shows the total meters. Pressing key
, the display moves to sub-page with partial meters (clearable by the user).
– To clear energy meters, it is necessary to access the commands menu.
I271 I GB F E 01 13
1 - Total / Partial indication
HOUR COUNTERS PAGE
– The page for hour counters shows the following simultaneously:
• total hour counter (counts the power-on time of the device)
• partial hour counter (counts how long a programmable condition occurred)
– To clear hour counters, it is necessary to access the commands menu.
– The hour counters page can be completely hidden if the general hour counter enable has been set to OFF (see hour counter menu).
TREND GRAPH PAGE
– The trend graph page allows to show the changes in the time domain of one measurement selectable among the following:
• average equivalent voltage
• average total active power
• average total reactive power
• average total apparent power.
– The default measurement is the Average total active power. To change the measurement, enter the dedicated parameter in the Trend sub-menu.
– It is possible to see, on the graph, the history of the last 96 values of the integrated measurement, each corresponding to a integration time interval.
– The default time interval is equal to 15 minutes, so the graph depth in time is equal to 24h.
– With the default factory setting, the trend graph shows the active power demand variation of the last day.
– Consumption data is lost when auxiliary power is removed from the DMG device or when the settings in the setup menu are changed.
– When the maximum storing capacity is exceeded, the newest data overwrites the oldest, so that the most recent data is always shown.
– The vertical full-scale is calculated automatically, depending on the rated data programmed in M01 menu - General.
1 - Time scale.
Indicates the time in the past to which
the measurements are referred.
2 - Vertical scale.
Can be autoranging or fixed
by the user.
3 - Measurement viewed on graph
COUNTERS PAGE
– The counters page displays CNT1…4 counters.
– It is possible to count the number of times an input is activated, or a limit has been overcame etc. The count condition is defined by Counter source
parameters.
– For every counter, it is possible to define a description and a unit of measure with a free text, for instance litres, kg, etc.
– It is possible to define a conversion factor between the number of pulse counts and the measurement shown on display. This function can be obtained by
specifying a multiply and a divide factor. For instance, setting the multiplier k to 3, for every pulse count, the value shown will be increased 3 fold. If instead,
a divider is set to 10, then the value will be increased by one only after 10 pulses have been applied to the input. With a combination of multiply and divide
factor, any ratio between counts and measurement can be achieved.
– If the counter has no divide factor, the screen indicates the count with whole numbers only, otherwise it is displayed with two decimals.
– The counters can be cleared by means of commands menu or by means of the Reset source signal, defined by dedicated parameters.
1 - Unit of measure (free text)
2 - Count
3 - Description (free text)
4 - No. of the selected counter
USER PAGES
– The user can create a maximum of
4 customised display pages.
– Each of these pages can view
4 measurements, freely chosen among the available readings of the DMG700.
– The title of the page can be freely programmed by the user, allowing, for instance, indicating the part of the plant supervised by the multimeter.
– The user pages are placed in a position so they can be easily reached starting from the first page, by pressing button s.
– Like all other pages, it is possible to set the multimeter to return automatically to the user page after a time has elapsed without keystrokes.
– To define the user page, see the dedicated menu M15 in the parameter set-up chapter.
4
G
B
31100124
MAIN MENU
– The main menu is made up of a group of graphic icons (shortcuts) that allow rapid access to measurements and settings.
– Starting from normal viewing, press MENU key. The main menu screen is displayed.
– Press s t to select the required function. The selected icon is highlighted and the central part of the display shows the description of the function.
– Press
to activate the selected function.
– If some functions are not available, the relevant icon will be disabled, that is shown in light grey.
–
G
B
etc. - Shortcuts that allow to jump to the first page of that group. Starting from that page it is still possible to move
I271 I GB F E 01 13
forward-backward in the usual way.
–
- Open the password entry page, where it is possible to specify the numeric codes that unlock protected functions (parameter setting, commands
menu, etc.).
–
- Access point to the set-up menu for parameter programming.
–
- Access point to the commands menu, where the authorised user can execute some clearing-resetting actions.
1 - Voltage readings
7 - Trend graph
2 - Current readings
8 - Hour readings
3 - Power readings
9 - Expansion modules
4 - Frequency - Asymmetry
10 - Set-up menu
5 - Harmonic Analysis
11 - Commands menu
6 - Energy meters
12 - Password entry
PASSWORD ACCESS
– The password is used to enable or lock the access to the setting menu (set-up) and to commands menu.
– For brand-new devices (factory default), the password management is disabled and the access is free.
If instead the passwords have been enabled and defined, then to get access it is necessary to enter the password first, specifying the numeric code through
the keypad.
– To enable password management and to define numeric codes, see set-up menu.
– There are two access levels, depending on the code entered:
• User-Level access - Allows clearing of recorded values but not editing of parameter set-up.
• Advanced access level - Same rights of the user access plus parameter setting.
– From normal viewing, press MENU to recall the main menu, select the password icon and press .
– The display shows the screen in the figure.
Keys s t change the selected digit.
Key
confirms the digit and moves to the next.
Enter numeric code, then move on the key icon.
If the password code entered matches the User access code or the Advanced access code, then the relevant unlock message is shown.
Once unlocked the password, the access rights last until:
• The device is powered off.
• The device is reset (after quitting the set-up menu).
• The timeout period of two minutes elapses without any keystroke.
– To quit the password entry screen, press MENU key.
–
–
–
–
–
SETTINGS LOCK
– On the DMG700 there are two DIP switches that are used to lock the access to parameter settings and / or to reset operations (commands menu).
– This DIP switches are placed in a way that they become unaccessible once the sealable terminal covers are mounted.
– To change switch position:
• Remove power supply to DMG700 and remove terminal covers (if mounted) and the 8-pole terminal block
• Using a small flat screwdriver, move the switches in the required position.
• Re-mount terminal blocks and terminal covers.
– The multimeter is supplied with the switches in unlocked position.
SW
POS
SW1
OFF
Parameter settings allowed
ON
Parameter settings locked
SW2
DESCRIPTION
OFF
Commands menu access allowed
ON
Commands menu access locked
5
31100124
I271 I GB F E 01 13
EXPANDABILITY
– Thanks to expansion bus, the DMG700 can be expanded with EXP series modules.
– It is possible to connect a maximum of 4 EXP… modules.
– The supported EXP modules can be grouped in the following categories:
• Communication modules.
• Digital I/O modules.
– To insert an expansion module:
• Remove the power supply to DMG700.
• Remove terminal covers and the 8-pole terminal block.
• Remove the protection cover of one of the expansion slots.
• Insert the upper hook of the module into the fixing hole.
• Rotate the module body downwards, inserting the connector on the bus.
• Push until the bottom clip snaps into place.
• Re-install the terminal block and transparent terminal covers.
– There is no sequence for module insertion.
1
2
3
G
B
4
CLICK!
WARNING!
When the EXP module is installed on a DMG series multimeter, it is mandatory to install the sealable terminal covers supplied with the multimeter.
– When a DMG700 is powered on, it automatically recognises the EXP modules that have been mounted.
– If the system configuration has changed with respect to the last saved, (one module has been added or removed) the base unit asks the user to confirm the
new configuration. In case of confirmation, the new configuration will be saved and will become effective; otherwise the mismatch will be shown at every
subsequent power-on of the multimeter.
– The current system configuration is shown in the dedicated page of the display (expansion modules), where it is possible to see the number, the type and the
status of the modules.
– The I/O numbering is shown under each module.
– The status (energised/de-energised) of every single I/O and communication channel is highlighted in reverse.
1 - No. and status of communication channel
2 - Type of the expansion module
3 - Numbering and status of the I/Os
ADDITIONAL RESOURCES
– The expansion modules provide additional resources that can be used through the dedicated setup menus.
– The set-up menus related to the expansions are always accessible, even if the expansion modules are not physically fitted.
– Since it is possible to add more than one module of the same typology (for instance two communication interfaces), the set-up menus are multiple, identified
by a sequential number.
– The following table indicates how many modules of each group can be mounted at the same time.
TYPE OF MODULE
CODE
FUNCTION
MAX No.
COMMUNICATION
EXP10 10
USB
2
EXP10 11
RS232
DIGITAL I/O
EXP10 12
RS485
EXP10 00
4 INPUTS
EXP10 01
4 STATIC OUTPUTS
2
EXP10 02
2 INPUTS +
2 ST. OUTPUTS
4
EXP10 03
2 RELAYS
4
2
COMMUNICATION CHANNELS
– The DMG700 supports a maximum of 2 communication modules, indicated as COMn. The communication setup menu M07 is thus divided into two sections
(n=1 and n = 2) of parameters for the setting of the ports.
– The communication channels are completely independent, both for the hardware (physical interface) and for the communication protocol.
– The two channels can communicate at the same time.
6
31100124
I271 I GB F E 01 13
INPUTS, OUTPUTS, INTERNAL VARIABLES, COUNTERS
– The inputs and outputs of the expansion modules are identified by a code and a sequence number. For instance, the digital inputs are identified by code INPx,
where x is the number of the input. In the same way, digital outputs are identified by code OUTx.
– The sequence number of I/Os is simply based on their mounting position, with a progressive numbering from left to right. For instance the input INP1 is the
first input terminal of the leftmost module, while the subsequent inputs will be named INP2, INP3 and so on.
– The DMG700 supports a maximum of 8 digital inputs and 8 outputs that will thus be numbered INP1…8 and OUT1…8. For every I/O, there is a dedicated
setting menu that allows to specify functionality and properties.
– In a similar way, there are some internal bit-variables (markers) that can be associated to the outputs or combined between them. For instance, it is possible
to apply some limit thresholds to the measurements done by the multimeter (voltage, current, power, etc.). In this case, an internal variable named LIMx will
be activated when the measurements go out of limits defined by the user through the dedicated setting menu.
– Finally, it is possible to manage up to 4 counters (CNT1..CNT4) that can count pulses coming from an external source (through a digital input INPx) or the
number of times that a certain condition has occurred. For instance, defining a limit threshold LIMx as the count source, it will be possible to count how
many times one measurement has exceeded a certain limit.
– The following table groups all the I/O and the internal variables managed by the DMG700.
Cod.
DESCRIPTION
Range (x)
INPx
Digital inputs
1...8
OUTx
Digital outputs
1...8
LIMx
Limit thresholds
1...8
BOOx
Boolean logic
1...8
REMx
Remote-controlled variables
1...8
ALAx
Alarms
1...8
PULx
Energy count pulses
1...5
CNTx
Counters
1...4
– The status of each I/O or internal variable can be shown on the display in the dedicated page.
LIMIT THRESHOLDS (LIM)
– The LIMn thresholds are internal variables whose status depends on the out-of-limits of one particular measurement set by the user (e.g. total active power
higher than 25kW) among all those measured.
– To make the setting of the thresholds easier, since the limits can span in a very wide range, each of them can be set using a base number and a multiplier
(for example: 25 x 1k = 25000).
– For each LIM, there are two thresholds (upper and lower). The upper threshold must always be set to a value higher than the lower threshold.
– The meaning of the thresholds depends on the following functions:
Min function: the lower threshold defines the trip point, while the upper threshold is for the resetting. The LIM trips when the selected measurement is less
than the Lower threshold for the programmed delay. When the measured value becomes higher than the upper setpoint, after the delay, the LIM status is
reset.
Max function: the upper threshold defines the trip point, while the lower threshold is for the resetting. The LIM trips when the selected measurement is more
than upper threshold for the programmed delay. When the measured value decreases below the lower setpoint, after the delay, the LIM status is reset.
Max+Min function: both thresholds are for tripping. When the measured value is less than lower or more than upper setpoints, then, after the respective
delays, the LIM will trip. When the measured value returns within the limits, the LIM status will be immediately reset.
– Trip denotes either activation or de-activation of the LIM variable, depending on “Normal status” setting.
– If the LIM latch is enabled, the reset can be done only manually using the dedicated command in the commands menu.
– See set-up menu M08.
1 - Status of the limit variable
2 - Value of measurement
3 - Function
4 - Type of measurement
5 - Upper threshold
6 - Threshold delay
7 - Lower threshold
BOOLEAN LOGIC (BOO)
– It is possible to create max. 8 internal variables named BOO1..8, whose status depends on the Boolean logic combination of limit thresholds, inputs, outputs, etc.
– The operands (INP, LIM etc) can be combined between each other with the following Boolean operators: AND, OR, EXOR, AND NOT, OR NOT, EXOR NOT.
– Every Boolean variable is the result of max
4 operands combined with 3 logic operations.
– Example: if one wants the Boolean variable BOO1 to be activated when the limits LIM1, LIM2 and LIM3 are all active or when the input INP1 is active, BOO1
must programmed as the combination of LIM2 AND LIM3 AND LIM4 OR INP1.
– It is not necessary to use all 4 operands for one Boolean variable. If for instance, one wants BOO2 to be active when INP1 or INP2 are active, then it is
possible to program BOO2 settings with the combination INP1 OR INP2, leaving the following logic operations set to --- (no operation).
– The BOOLEAN LOGIC page displays, for every variable BOO1..8, the status of the single operands that are involved in the logic operation and the final result,
that is the status of the selected Boolean variable.
1 - Operand 1
2 - Logic operation 1
3 - Operand 2
4 - Operand status 1
5 - Status of the resulting variable
REMOTE-CONTROLLED VARIABLES (REM)
– DMG700 can manage up to 8 remote-controlled variables (REM1…REM8).
– These are variables which status can be modified by the user through the communication protocol and used in combination with outputs, Boolean logic, etc.
– Example: using a remote variable (REMx) as a source for an output (OUTx), it will be possible to freely energise or de-energise one relay through the
supervision software. This allows to use the DMG700 relays to drive lighting or similar loads.
– Another possible use of REM variables is to enable/disable other functions remotely, inserting them into a Boolean logic in AND with inputs or outputs.
7
G
B
31100124
I271 I GB F E 01 13
ALARMS (ALA)
– The user can define a maximum of 8 programmable alarms (ALA1…ALA8).
– For each alarm, it is possible to define the source that is the condition that generates the alarm, and the text of the message that must appear on the screen
when this condition is met.
– The condition that generates the alarm can be, for instance, the overcoming of a threshold. In this case, the source will be one of the limit thresholds LIMx.
– If instead, the alarm must be displayed depending on the status of an external digital input, then the source will be an INPx.
– With the same criteria, it is possible to also link complex conditions to an alarm, resulting from the logic combination of inputs, limits, etc. In this case,
Boolean logic variables BOOx must be used.
– For every alarm, the user can define a free message that will appear on the alarm page.
– It is also possible to define a priority for the alarm. If it is a simple indication, then the priority can be set to low. In this case the icon that follows the
message will be the ‘info’ symbol.
– If instead, the alarm must indicate a more critical situation, by setting its priority to High, the message will be displayed with the warning icon, and when the
alarm becomes active, the display page will move automatically on the Alarms screen.
– When several alarms are active at the same time, they are displayed sequentially, and their total number is shown on the status bar.
– To reset one alarm that has been programmed with latch, use the dedicated command in the commands menu.
– For alarm programming and definition, refer to set-up menu M09.
1 - Alarm no. / total alarm count
TARIFFS
– For the energy billing, the DMG700 can manage 4 different tariffs in addition to the total and partial energy meters.
– The tariff selection is made by external digital inputs, and is thus conditioned by the use of an EXP expansion module provided with digital inputs. To select
among the 4 tariffs, the two input functions TAR-A and TAR-B must be used. Their binary combination selects the tariff as shown in table:
TAR-A
TAR-B
TARIFF
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
– If the synchronise input for the power integration is used, then the tariff change becomes active when the sync signal triggers it; otherwise the tariff change
takes place immediately when the status of the selected inputs changes.
– The tariffs, each with 5 meters (active energy imported/exported, reactive imported/exported, apparent) are shown on a dedicated page, following the totalpartial energy screen.
– If the DMG is equipped with a communication port, then it is possible to select the active tariff through the dedicated command via Modbus protocol (see
technical instruction for Modbus protocol).
1 - Active tariff
2 - Viewed tariff
PARAMETER SETTING (SET-UP)
– From normal viewing, press MENU to recall the main menu, then select icon
and press
to open the set-up menu screen.
– The display will show the table below, with the parameters grouped in sub-menus with a function-related criteria .
– Select the required menu with s t keys and confirm with .
– To quit set-up and go back to the readings viewing, press MENU.
8
G
B
31100124
I271 I GB F E 01 13
– The following table lists the available sub-menus:
Code
Sub-menu
Description
M01
GENERAL
Detailed data of the installation
M02
UTILITY
Language, backlight, display pages, etc.
M03
PASSWORD
Access codes enabling
M04
INTEGRATION
Readings integration time
M05
HOUR COUNTER
Hour counter enabling
M06
TREND GRAPH
Trend graph reading and scale
M07
COMMUNICATION (COMn)
Communication ports
M08
LIMIT THRESHOLDS (LIMn)
Limit thresholds on readings
M09
ALARMS (ALAn)
Alarm messages
M10
COUNTERS (CNTn)
General counters
M11
ENERGY PULSING (PULn)
Energy pulse count
M12
BOOLEAN LOGIC (BOOn)
Boolean logic variables
M13
INPUTS (INPn)
Digital inputs
M14
OUTPUTS (OUTn)
Digital outputs
M15
USER PAGES (PAGn)
User-defined pages
G
B
– Select the sub-menu and press
to show the parameters.
– Each parameter is shown with code, description and current setting value.
1 - Parameter code
2 - Parameter description
3 - Current setting value
4 - Selected parameter
– To modify the setting of one parameter, select it and then press .
– If the Advanced level access code has not been entered, it will not be possible to enter editing page and an access denied message will be shown.
– If instead the access rights are confirmed, then the editing screen will be shown.
1 - Selected parameter
2 - Minimum possible setting
3 - Graph bar of the value-range
4 - New value entered
5 - Maximum possible setting
6 - Factory default setting
– When the editing screen is displayed, the parameter setting can be modified with s and t keys. The screen shows the new setting, a graphic bar that
shows the setting range, the maximum and minimum values, the previous setting and the factory default.
– Pressing simultaneously s and t, the setting is set to factory default.
is used to move the cursor along the text string.
– During the entry of a text string, keys s and t are used to select the alphanumeric character while
Pressing keys s and t simultaneously will move the character selection straight to ‘A’.
– Press MENU to go back to the parameter selection. The entered value is stored.
– Press MENU again to save all the settings and to quit the set-up menu. The multimeter executes a reset and returns to normal operation.
– If the user does not press any key for more than 2 minutes, the multimeter leaves the setu-p automatically and goes back to normal viewing.
PARAMETER TABLE
UdM
Default
Range
P01.01
M01 - GENERAL
CT primary
A
5
1-10000
P01.02
CT secondary
A
5
5
P01.03
Rated voltage
V
Aut
Aut / 50-500000
P01.04
VT usage
OFF
OFF-ON
P01.05
VT primary
V
100
50-500000
P01.06
VT secondary
V
P01.07
Type of wiring
100
50-500
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
L1-N
P01.01 – CT primary winding rated current.
P01.02 – CT secondary winding rated current. For DMG700 fixed to 5A.
P01.03 – System rated voltage. Leaving to Aut the multimeters automatically adapts bar-graph full scale.
P01.04 – Set to ON if VT are used. If set to OFF, the following two parameters will be ignored.
P01.05 – VT primary winding rated voltage.
P01.06 – VT secondary winding rated voltage.
P01.07 – Set this parameter according to the used wiring diagram. See wiring diagrams on last pages of the manual.
9
31100124
I271 I GB F E 01 13
M02 - UTILITY
Default
Range
English
English
Italiano
Francais
Espanol
Portoguese
%
50
0-100
High backlight level
%
100
0-100
Low backlight level
%
30
0-50
P02.05
Low backlight delay
sec
30
5-600
P02.06
Default page return
sec
60
OFF / 10-600
P02.07
Default page
VL-L
VL-L / VL-N ...
P02.08
Default sub-page
INST
INST / HI / LO /
AVG / MD /GRAPH /
1-8
P02.09
Display update time
0.5
0.1 - 5.0
P02.01
Language
P02.02
Display contrast
P02.03
P02.04
UdM
sec
P02.06 – If set to OFF the display always remains in the page where the user left it. If set to a time delay, after that time the display page goes back to page set
in P02.07.
P02.07 – Number of the page to which the display returns automatically after time specified by P02.06 has elapsed from the last keystroke.
P02.08 – Sub-page type to which the display returns after P02.06 has elapsed.
M03 - PASSWORD
Default
Range
Enable passwords
OFF
OFF-ON
P03.02
User level password
1000
0-9999
P03.03
Advanced level password
2000
0-9999
P03.01
UdM
P03.01 – If set to OFF, password management is disabled and the access to setup parameters and command menu is allowed.
P03.02 – When P.03.01 enabled, value to be specified to get user access. Refer to Password Access chapter.
P03.03 – Like P03.02, but referred to advanced access.
M04 - INTEGRATION
Default
Range
Shift
Fixed / Shift
Sync. / Bus
min
15
1-60
min
15
1-60
Voltage integration time
min
1
1-60
Frequency integration time
min
1
1-60
P04.01
Integration mode
P04.02
Power integration time
P04.03
Current integration time
P04.04
P04.05
UdM
P04.01 – Selection of average reading calculation method:
Fixed = Readings are integrated for the set time. Every time the integration time elapses, the Average value is updated with the result of the last integration.
Shift = The instantaneous values are integrated for a period of time equal to 1/15th of the set time. Every time this interval elapses, the oldest value is replaced
with the new one just calculated. The average value is updated every 1/15th of the time set, considering a time-sliding window that groups the last 15 calculated
values, with a total length equal to integration time setting.
Sync = Like fixed mode, but the integration intervals are started by an external digital input programmed with Synchronisation function.
Bus = Like fixed mode, but the integration intervals are started by synchronising messages on the serial bus.
P04.02 – Average readings integration time, used for active, reactive and apparent power.
P04.03, P04.04, P04.05 – Readings integration time (AVG) for the corresponding measurements.
Default
Range
P05.01
M05 - HOUR COUNTER
Hour counter enable
UdM
ON
OFF-ON
P05.02
Partial hour counter enable
ON
OFF-ON- INPxLIMx-BOOx
P05.03
Channel number (x)
1
1-8
P05.01 – If set to OFF the hour counters are disabled and the hour meter page is not shown.
P05.02 – If set to OFF, the partial hour counter is not incremented. If ON, time is incremented as long as DMG is powered. If set to an internal variable (INPxLIMx-BOOx), time increments only while a programmed condition occurs.
P05.03 – Number of the channel (x) of the variable eventually used in the previous parameter. Example: If the partial hour counter must count the time during
which one measurement is above a certain threshold, e.g. defined by LIM3, then it is necessary to program LIMx in the previous parameter and channel 3 in this
parameter.
M06 - TREND GRAPH
P06.01
Trend graph measurement
P06.02
Autorange
P06.03
Full scale value
P06.04
Full scale multiplier
P06.01 – Selects the reading to be shown on trend graph page.
P06.02 – Choice between automatic range or fixed range defined by the user.
P06.03 – Full scale range value. The unit of measure is the one defined by the selected reading.
P06.04 – Full scale value multiplier.
10
UdM
Default
Range
kW (tot)
AVG
VL-L (eq) AVG
kW (tot) AVG
kvar (tot) AVG
kVA (tot) AVG
ON
OFF-ON
1000
0-1000
x1
x1 - x1k - x1M
G
B
31100124
M07 - COMMUNICATION
P07.n.02 Serial speed
I271 I GB F E 01 13
UdM
P07.n.01 Serial node address
bps
P07.n.03 Data format
Default
Range
01
01-255
9600
1200
2400
4800
9600
19200
38400
8 bit - n
G
B
8 bit, no parity
8bit, odd
8 bit, even
7 bit, odd
7 bit, even
P07.n.04 Stop bits
1
1-2
P07.n.05 Protocol
Modbus RTU
Modbus RTU
Modbus ASCII
Note: This menu is divided into 2 sections, for comm channels COM1..2
P07.n.01 – Serial address (node number) for the communication protocol.
P07.n.02 – Serial communication speed.
P07.n.03 – Data format. Can be set to 7 bits only for ASCII protocol.
P07.n.04 – Number of stop bits.
P07.n.05 – Communication protocol selection.
Default
Range
P08.n.01 Reference measurement
M08 - LIMIT TRESHOLDS
UdM
OFF
OFF- (measures)
P08.n.02 Function
Max
Max - Min - Min+Max
P08.n.03 Upper threshold
0
-9999 - +9999
P08.n.04 Multiplier
x1
/100 - x10k
P08.n.05 Delay
sec
0
0.0 - 600.0
0
-9999 - +9999
x1
/100 - x10k
0
0.0 - 600.0
P08.n.09 Normal status
OFF
OFF-ON
P08.n.10 Latch
OFF
OFF-ON
P08.n.06 Lower threshold
P08.n.07 Multiplier
P08.n.08 Delay
sec
Note: This menu is divided into 8 sections, for limit thresholds LIM1..8
P08.n.01 – Defines which measurements of the multimeter must be compared with limits.
P08.n.02 – Function of the limit threshold.
It can be:
Max = LIMn active when the measurement is higher than P08.n.03. P08.n.06 is the reset threshold.
Min = LIMn active when the measurement is lower than P08.n.06. P08.n.03 is the reset threshold.
Min+Max = LIMn active when the measurement is higher than P08.n.03 or is lower than P08.n.06.
P08.n.03 and P08.n.04 – Used to define the upper threshold, that is made up by the value set in P08.n.03 multiplied by P08.n.04.
P08.n.05 – Trip delay on upper threshold.
P08.n.06, P08.n.07, P08.n.08 – Like above, referred to lower threshold.
P08.n.09 – Allows to invert the status of the limit LIMn.
P08.n.10 – Defines if the threshold remains latched and thus needs to be reset manually (ON) or if it resets automatically (OFF).
M09 - ALARMS
P09.n.01 Alarm source
P09.n.02 Channel number (x)
P09.n.03 Latch
Default
Range
OFF
OFF-LIMx-INPx-BOOx
1
1-8
OFF
OFF-ON
P09.n.04 Priority
Low
Low - High
P09.n.05 Text
ALAn
(Text - 16 char)
Note: This menu is divided into 8 sections, for alarms ALA1..8
P09.n.01 – Signal that generates the alarm. It can be the overcoming of a limit threshold (LIMx), the activation of an external alarm (INPx), one Boolean logic
condition (BOOx).
P09.n.02 – Channel number (x) referred to the previous parameter.
P09.n.03 – Defines if the alarm remains latched and has to be reset manually (ON) or if it automatically resets (OFF).
P09.n.04 – If the alarm has high priority, when it is activated the display page automatically switches on the alarm page, and the alarm is shown with the
Warning icon. If instead the priority level is low, the page does not change and shown with the information icon.
P09.n.05 – Free text of the alarm. Max 16 characters.
11
31100124
M10 - COUNTERS
P10.n.01 Count source
Range
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.02 Channel number (x)
1
1-8
P10.n.03 Multiplier
1
1-1000
P10.n.04 Divider
I271 I GB F E 01 13
Default
1
1-1000
P10.n.05 Counter description
CNTn
(Text - 16 chars)
P10.n.06 Unit of measure
Umn
(Text - 6 chars)
P10.n.07 Reset source
OFF
OFF-ON-INPx-LIMx-BOOx
1
1-8
P10.n.08 Channel number (x)
Note: This menu is divided into 4 sections, for counters CNT1..4
P010.n.01 = Signal that causes the increment of the counter (on rising edge). It can be the power-on of the multimeter (ON), the overcoming of a limit threshold
(LIMx), the activation of an external input (INPx), one logic combination (BOOx).
P010.n.02 = Number of the channel (x) referred to previous parameter.
P010.n.03 = Multiplying factor. The pulse count is multiplied by this coefficient before being displayed.
P010.n.04 = Dividing factor. The pulse count is divided by this coefficient before being displayed. If different from 1, then the value is displayed with 2 decimals.
P10.n.05 = Description of the counter. Free text 16 characters.
P10.n.06 = Unit of measure of the counter. Free text 6 characters.
P10.n.07 = Signal that causes the clearing of the counter. As long as this signal is activated, the counter remains at value 0.
P10.n.08 = Number of the channel (x) referred to previous parameter.
M11 - PULSES
Default
Range
P11.n.01 Measurement source
kWh+
kWh+,kWh-,kvarh+,kvarh-,kVAh
P11.n.02 Count unit
100
10/100/1k/10k
P11.n.03 Pulse duration
0.1
0.01-1.00
Note: This menu is divided into 5 sections, for energy count pulses PUL1..5
P11.n.01 = Type of energy to which the pulse is linked to.
P11.n.02 = Quantity of energy for each pulse. (e.g. 10Wh, 100Wh, 1kWh, etc.).
P11.n.03 = Pulse duration.
M12 - BOOLEAN LOGIC
P12.n.01 Operand 1
P12.n.02 Channel number (x)
Default
Range
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
1
1-8
P12.n.03 Logic operator 1
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.04 Operand 2
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.05 Channel number (x)
1
1-8
P12.n.06 Logic operator 2
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.07 Operand 3
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.08 Channel number (x)
1
1-8
P12.n.09 Logic operator 3
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.10 Operand 4
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
1
1-8
P12.n.11 Channel number (x)
Note: This menu is divided into 8 sections, for Boolean variables BOO1..8
P12.n.01 = First operand of the Boolean logic.
P12.n.02 = Number of the channel (x) referred to previous parameter.
P12.n.03 = Logic operation between first and second operands.
P12.n.04 = Second operand.
From P12.n.05 to P12.n.11 – (as given above).
M13 - INPUTS
UdM
Default
Range
OFF
OFF - ON - LOCK SYNC - TAR-A TAR-B
C01...C08
P13.n.01 Input function
P13.n.02 Normal status
OFF
OFF-ON
P13.n.03 ON delay
sec
0.05
0.00 - 600.00
P13.n.04 OFF delay
sec
0.05
0.00 - 600.00
Note: This menu is divided into 8 sections, for digital inputs INP1..8
P13.n.01 = Input function:
OFF – Input disabled
ON – Input enabled, used as a source for counters, Boolean logic, etc.
LOCK – Settings lock. Does not allow access to both levels.
SYNC – Synchronisation for power/energy integration.
TAR-A, TAR-B – Energy tariff selection. See Energy tariffs chapter.
C01…C08 – When this input is activated (edge-triggered), the corresponding command of the commands menu is executed.
P13.n.02 = Normal status of the input. Allows to invert the INPn activation logic.
P13.n.03 – P13.n.04 = Delay on activation – deactivation of the input. Allow to filter the input status to avoid bouncing.
12
G
B
31100124
M14 - OUTPUTS
UdM
Default
Range
OFF
OFF-ON-SEQ-LIMxBOOx-ALAx-PULxREMx
P14.n.01 Output function
P14.n.02 Channel number (x)
I271 I GB F E 01 13
P14.n.03 Idle status
1
1-8
OFF
OFF-ON
G
B
Note: This menu is divided into 8 sections, for digital outputs OUT1..8
P14.n.01 = Function of the output:
OFF – Output disabled
ON – Output always enabled
SEQ – Output enabled in case of wrong phase sequence
LIMx – BOOx – ALAx – PULx – REMx – Output linked to the status of the programmed variable. Allows to connect the status of an output to the status of a limit
threshold, a Boolean variable, an alarm, etc.
P14.n.02 = Number of the channel (x) referred to previous parameter.
P14.n.03 = Normal status of the output. Allows to reverse the logic of the output function.
M15 - USER-DEFINED PAGES
Default
Range
OFF
OFF - ON
P15.n.01 Page enabling
P15.n.02 Title
PAGn
(Text - 16 char)
P15.n.03 Measurement 1
OFF
OFF- (measurements)
P15.n.04 Measurement 2
OFF
OFF- (measurements)
P15.n.05 Measurement 3
OFF
OFF- (measurements)
P15.n.06 Measurement 4
OFF
OFF- (measurements)
Note: This menu is divided into 4 sections, for user pages PAG1..4
P15.n.01 = Enables user page PAGn.
P15.n.02 = Title of the user page. Free text, 16 chars.
P15.n.03, P15.n.04, P15.n.05, P15.n.06 = Measurement that will be shown in the four frames of the user page.
COMMANDS MENU
– The commands menu allows executing some occasional operations like reading peaks resetting, counters clearing, alarm reset, etc.
– If the Advanced level password has been entered, then the commands menu allows executing the automatic operations useful for the device configuration.
– The following table lists the functions available in the commands menu, divided by the access level required.
Code
COMMAND
ACCESS LEVEL
User
DESCRIPTION
Advanced
C.01
RESET HI-LO
l
l
Clears of HI and LO peaks of all readings
C.02
MAX DEMAND RESET
l
l
Clears of Max Demand of all readings
C.03
PARTIAL ENERGY METER RESET
l
l
Clears partial Energy meters
C.04
PARTIAL HOUR COUNTERS RESET
l
l
Clears partial hour counters
C.05
RESET COUNTERS
l
l
Clears counters
C.06
RESET TARIFFS
l
l
Clears tariff Energy meters
C.07
RESET ALARMS
l
l
Clears alarms with latch
C.08
RESET LIMITS
l
l
Clears limit thresholds with latch
C.11
TOTAL ENERGY METER RESET
l
Clears total, partial and tariff energy meters
C.12
TOTAL HOUR COUNTERS RESET
l
Clears total hour counters
C.13
PARAMETERS TO DEFAULT
l
All set-up parameters are reset to factory default value
C.14
PARAMETERS BACKUP
l
Saves a backup copy of all set-up parameters
C.15
PARAMETERS RESTORE
l
Restores the set-up parameters to backup values
C.16
WIRING TEST
l
Carries out the wiring test in order to check proper wiring
of the DMG. See wiring test chapter.
– Once the required command has been selected, press
executed.
– To cancel the command execution press MENU.
– To quit commands menu press MENU.
to execute it. The device will prompt for a confirmation. Pressing
again, the command will be
13
31100124
I271 I GB F E 01 13
WIRING TEST
– The wiring test allows to verify if the connection of the DMG device has been done properly.
– To be able to execute the test, the device must be connected to an active plant, with the following conditions:
• three-phase system with all phases present (V > 50VAC PH-N)
• current flowing in each phase > 1% of the CT primary.
• positive flow of energies (that is a normal plant where the inductive load draws power from the grid).
– To launch test execution, enter commands menu and select the required command per commands menu instructions.
– The test allows to verify the following points:
• reading of the three phases
• phase sequence
• voltage imbalance
• reverse polarity of one or more CT
• mismatch between voltage and current phases.
– If the test does not succeed, the display shows the reason of the failure.
– If instead the test succeeds, then the condition is stored in the non-volatile memory, and a message that states the test successfully completed is shown in
the information page.
1 - Test sequence
2 - Test result
14
G
B
31100124
GB
TECHNICAL CHARACTERISTICS
Ambient conditions
Auxiliary supply
100 - 440V~
110 - 250V
Operating temperature
-20...+60°C
Storage temperature
-30...+80°C
90 - 484V~
93,5 - 300V
Relative humidity
<80% (IEC/EN 60068-2-70)
Maximum pollution degree
2
Measurement category
III
Overvoltage category
3
Altitude
≤2000m
Climatic sequence
Z/ABDM (IEC/EN 60068-2-61)
690V~ phase-phase
400V~ L-N
Shock resistance
15g (IEC/EN 60068-2-27)
Vibration resistance
0.7g (IEC/EN 60068-2-6)
UL rating
600V~ phase-phase
347V~ L-N
Insulation
Measurement range
20 - 830V~ L-L
10 - 480V~ L-N
Rated impulse withstand voltage Uimp
9.5kV
Power frequency withstand voltage
5.2kV
Frequency range
45 - 66Hz
Auxiliary supply and voltage input connections
Method of measuring
True RMS value
Type of terminal
Screw (removable)
Method of connection
Single-phase, two-phase, three-phase with or
without neutral or balanced three-phase system.
Number of terminals
4 for voltage inputs
2 for Aux supply
Rated voltage Us ∂
I271 I GB F E 01 13
Operating voltage range
Frequency
Power consumption/dissipation
Immunity time for microbreakings
45 - 66Hz
3.9VA 3.4W max
≥50ms
Voltage inputs
Type of input
Maximum rated voltage Ue
Three phase + neutral
Current inputs
Rated insulation voltage Ui
690V~
Conductor cross section (min… max)
0.2…2.5 mm² (24...12 AWG)
Rated current Ie
5A~
Tightening torque
0.5 Nm (4.5 lbin)
Measuring range
0,010 - 6A~
Current input connections
Type of input
Shunt supplied by an external current transformer
(low voltage). Max. 5A
Type of terminal
Screw (fixed)
Number of terminals
6 for external CT connection
Measuring method
Overload capacity
G
B
True RMS value
Conductor cross section (min… max)
0.2…4 mm² (26...10 AWG)
Tightening torque
0.8 Nm (7 lbin)
+20% Ie
Overload peak
50A for 1 second
Burden (per phase)
≤ 0.6W
Housing
Material
Polyamide RAL7035
Version
Flush mount per IEC 61554
Degree of protection
IP54 on front
IP20 housing and terminals
Weight
480g
Accuracy
Measuring conditions
Temperature
+23°C ±2°C
Voltage (phase to neutral)
± 0.5% (50…480V~) ±0.5 digit
Voltage (phase to phase)
± 0.5% (80…830V~) ±0.5 digit
Current
± 0.5% (0.1…1.2In) ±0.5 digit
Active Energy
Class 1 (IEC/EN 62053-21)
Reactive energy
Certifications and compliance
Certifications
cULus
Class 2 (IEC/EN 62053-23)
UL marking
Auxiliary supply and voltage input
0.05%/°K per V, A, W
Current Input
Use 60°C/75°C copper (Cu) conductor only
AWG Range: 24 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 4.5lb.in
AWG Range: 26 - 10 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 7lb.in
“For use on a flat surface of a Type 1 Enclosure”
Additional errors
Temperature
Compliant with standards
IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/ EN 61000-6-4,
UL508, CSA C22.2 N°14
∂ Auxiliary supply connected to a line with a phase-neutral voltage ≤300V.
15
31100124
I271 I GB F E 01 13
INSTALLATION
– DMG700 is designed for flush-mount installation according to IEC 61554.
– Insert the device into the panel cutout, making sure that the gasket is properly positioned between the panel and the device front frame.
– From inside the panel, for each of the four fixing clips, position the clip in one of the two grooves then press on the clip end until it snaps into the second
groove.
– Push the clip forward pressing on its side and making it slide in the grooves until it presses completely against the internal surface of the panel.
TAC
–
–
–
–
Repeat the same operation for the four clips.
In case it is necessary to dismount the multimeter, lift the central lever of the clip in order to release it, then pull it backwards until it slips off.
For the electrical connection see the wiring diagrams in the dedicated chapter and the requirements given in the technical characteristics table.
Once the wiring is completed, it is possible to mount the terminal covers supplied with the instrument. These terminal covers are sealable, making instrument
tampering and/or the access to the screw terminals impossible.
– To install the terminal covers, insert the side hooks in place and apply a light pressure until they snaps in. Be aware of the match between the terminal block
and the proper terminal cover.
– The locking of the terminal covers must be done inserting the proper wire in the side eyelets and applying the seal.
TERMINAL ARRANGEMENT
MECHANICAL DIMENSIONS
53.2
92
92
61.5
16
19
96
99.5
96
G
B
31100124
WIRING DIAGRAMS
3-phase connection with or without neutral
P01.07 = L1-L2-L3-N L1-L2-L3
2-phase connection
P01.07 = L1-N-L2
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
I271 I GB F E 01 13
N
CT2
G
B
L
O
A
D
L2
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
-A1
CURRENT
VOLTAGE
+
A2
AUX SUPPLY
Single-phase connection
P01.07 = L1-N
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
VOLTAGE
Balanced 3-phase connection with or without neutral
P01.07 = L1-L2-L3-N-BIL L1-L2-L3-BIL
CT1
CT1
L1
L1
L
O
A
D
N
L
O
A
D
L2
L3
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
I1
VOLTAGE
S1 S2
S1 S2
I2
I3
CURRENT
--
+
A1
A2
AUX SUPPLY
3-phase without neutral ARON connection
P01.07 = L1-L2-L3
V1 V2 V3 VN
I1
L
O
A
D
CT2
L3
I3
L1
L2
CT3
L3
L
O
A
D
100...440VAC
110...250VDC
100...440VAC
110...250VDC
AUX SUPPLY
S1 S2
I2
CT1
CT1
L2
+
A2
S1 S2
CURRENT
3-phase without neutral ARON connection
P01.07 = L1-L2-L3
L1
-A1
S1 S2
VOLTAGE
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
-A1
CURRENT
+
A2
AUX SUPPLY
3-phase connection with neutral via VT
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3-N
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
CURRENT
3-phase connection without neutral via VT
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
CT2
L2
CT3
L3
L
O
A
D
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
TV
V1 V2 V3 VN
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
--
A1
+
TV
V1 V2 V3 VN
A2
AUX SUPPLY
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
NOTES
1. Recommended fuses: Aux supply and voltage measurement inputs: F1A (fast)
2. S2 terminals are internally jumpered.
17
31100124
I MULTIMETRO DIGITALE
LOVATO ELECTRIC S.P.A.
I271 I GB F E 01 13
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. 035 4282111
FAX (Nazionale): 035 4282200
FAX (International): +39 035 4282400
E-mail [email protected]
Web www.LovatoElectric.com
DMG700
D
Available in German at www.LovatoElectric.com/I271D.pdf
CZ
Available in Czech at www.LovatoElectric.com/I271CZ.pdf
PL
Available in Polish at www.LovatoElectric.com/I271PL.pdf
RU
Available in Russian at www.LovatoElectric.com/I271RU.pdf
ATTENZIONE!!
– Leggere attentamente il manuale prima dell’utilizzo e l’installazione.
– Questi apparecchi devono essere installati da personale qualificato, nel rispetto delle vigenti normative impiantistiche, allo scopo di evitare danni a persone o
cose.
– Prima di qualsiasi intervento sullo strumento, togliere tensione dagli ingressi di misura e di alimentazione e cortocircuitare i trasformatori di corrente.
– Il costruttore non si assume responsabilità in merito alla sicurezza elettrica in caso di utilizzo improprio del dispositivo.
– I prodotti descritti in questo documento sono suscettibili in qualsiasi momento di evoluzioni o di modifiche. Le descrizioni ed i dati a catalogo non possono
pertanto avere alcun valore contrattuale.
– Un interruttore o disgiuntore va compreso nell’impianto elettrico dell’edificio. Esso deve trovarsi in stretta vicinanza dell’apparecchio ed essere facilmente
raggiungibile da parte dell’operatore. Deve essere marchiato come il dispositivo di interruzione dell’apparecchio:
IEC/EN 61010-1 § 6.11.2.
– Pulire lo strumento con panno morbido, non usare prodotti abrasivi, detergenti liquidi o solventi.
INDICE
PAG.
Introduzione . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
Descrizione . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Funzione dei tasti frontali . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Visualizzazione delle misure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Tabella delle pagine del display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Navigazione fra le pagine del display . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20
Pagina contatori di energia . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pagina contaore . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pagina grafico trend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pagina contatori . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Pagine utente . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
Menu principale . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Accesso tramite password . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Blocco impostazioni . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Espandibilità . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Risorse aggiuntive . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Canali di comunicazione. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Ingressi, uscite, variabili interne, contatori. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Soglie limite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Logica Booleana . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Variabili da remoto . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Allarmi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Tariffe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Impostazione dei parametri (set-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Tabella dei parametri . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Menu comandi . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Test di collegamento. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Caratteristiche tecniche . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Installazione . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Disposizione morsetti. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Dimensioni meccaniche . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Schemi di connessione . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
INTRODUZIONE
Il multimetro DMG700 è stato progettato per unire la massima semplicità di utilizzo con una ampia scelta di funzioni avanzate. In esecuzione per montaggio a
pannello con dimensioni standard 96x96mm, il DMG700 unisce il moderno design del frontale alla praticità di montaggio e alla possibilità di espansione sul
retro, dove è possibile alloggiare moduli della serie EXP. Il display grafico retroilluminato LCD consente una interfaccia utente chiara ed intuitiva. La ricca
dotazione di funzioni fa dei multimetri serie DMG la soluzione ideale per un campo di applicazioni molto ampio.
18
I
31100124
I271 I GB F E 01 13
DESCRIZIONE
– Esecuzione da incasso 96x96mm.
– Display LCD grafico 128x80 pixel, retroilluminato, 4 livelli di grigio.
– 4 tasti per visualizzazione ed impostazione.
– Navigazione rapida e semplice.
– Compatibile con reti BT, MT e AT.
– Testi per misure, impostazioni e messaggi in 5 lingue.
– Più di 160 grandezze elettriche misurate.
– Bus di espansione per max 4 moduli plug-in serie EXP.
– Funzioni di I/O avanzate programmabili.
– Misure in vero valore efficace (TRMS).
– Acquisizione continua (gapless).
– Elevata accuratezza.
– Coprimorsetti piombabili.
– Blocco impostazioni tramite interruttore piombabile.
FUNZIONE DEI TASTI FRONTALI
Tasto MENU – Serve per entrare o uscire dai vari menu sia di visualizzazione che di impostazione.
Tasti s e t - Servono per lo scorrimento fra le pagine video, per la selezione fra le possibili scelte presentate a display e per la modifica di impostazioni
(incremento/decremento).
Tasto
- Serve per lo scorrimento delle sotto-pagine, per confermare una scelta effettuata e per passare da una modalità all’ altra di visualizzazione.
VISUALIZZAZIONE DELLE MISURE
– I tasti s e t consentono di scorrere le pagine di visualizzazione misure una per volta. La pagina attuale è riconoscibile tramite la barra del titolo.
– Alcune delle misure potrebbero non essere visualizzate in funzione della programmazione e del collegamento dell’apparecchio (ad esempio se programmato
per un sistema senza neutro le misure riferite al neutro non vengono visualizzate).
– Per ogni pagina, il tasto
consente di accedere a delle sotto-pagine (ad esempio per visualizzare i valori massimi e minimi registrati per la misura
selezionata).
– La sottopagina visualizzata correntemente è indicata in basso a sinistra da una delle seguenti icone:
• IN = Valore istantaneo - Valore istantaneo attuale della misura, visualizzato di default ogni volta che si cambia pagina.
• HI = Valore massimo istantaneo - Valore più alto misurato dal multimetro per la relativa misura. I valori HIGH vengono memorizzati e mantenuti anche in
assenza di alimentazione. Possono essere azzerati tramite apposito comando (vedere menu comandi).
• LO = Valore minimo istantaneo - Valore più basso misurato dal multimetro dal momento della messa in tensione. Viene resettato con lo stesso comando
usato per i valori HI.
• AV = Valore integrato - Valore della misura integrato (mediato) nel tempo. Consente di vedere una misura con variazioni lente. Vedere menu Integrazione.
• MD = Massimo valore integrato - Valore massimo del valore integrato (max demand). Rimane memorizzato in memoria non volatile ed è resettabile con
apposito comando.
• GR = Barre grafiche - Visualizzazione delle misure tramite barre grafiche.
Esempio di pagina con indicazioni numeriche
1 - Unità di misura
2 - Misura
3 - Titolo pagina
4 - Indicazione fasi
5 - Indicazione sottopagina
Esempio di pagina Barre grafiche
1 - Unità di misura
2 - Misura
3 - Indicazione fasi
4 - Indicatori HI-LO
– L’utente ha la possibilità di specificare su quale pagina e su quale sottopagina il display deve ritornare automaticamente dopo che è trascorso un tempo senza
che siano premuti dei tasti.
– Volendo è anche possibile programmare il multimetro in modo che la visualizzazioni resti sempre nella posizione in cui è stata lasciata.
– Per l’impostazione di queste funzioni vedere menu M02 – Utilità.
19
I
31100124
TABELLA DELLE PAGINE DEL DISPLAY
I271 I GB F E 01 13
Selezione con s e t
Selezione con
N°
PAGINE
1
TENSIONI CONCATENATE - V(L1-L2), V(L2-L3), V(L3-L1), V(LL)EQV
HI
LO
SOTTOPAGINE
AV
2
TENSIONI DI FASE - V(L1-N), V(L2-N), V(L3-N), V(L-N)EQV
HI
LO
AV
3
CORRENTI DI FASE E DI NEUTRO - I(L1), I(L2), I(L3), I(N)
HI
LO
AV
MD
GR
4
POTENZA ATTIVA - P(L1), P(L2), P(L3), P(TOT)
HI
LO
AV
MD
GR
5
POTENZA REATTIVA - Q(L1), Q(L2), Q(L3), Q(TOT)
HI
LO
AV
MD
GR
6
POTENZA APPARENTE - S(L1), S(L2), S(L3), S(TOT)
HI
LO
AV
MD
7
FATTORE DI POTENZA - PF(L1), PF(L2), PF(L3), PF(EQ)
HI
LO
AV
8
FREQUENZA - ASIMMETRIA - F, ASY(VLL), ASY(VLN), ASY(I)
HI
LO
AV
9
DISTORSIONE ARMONICA TENSIONI L-L - THD-V(L1-L2), THD-V(L2-L3), THD-V(L3-L1)
HI
LO
AV
GR
10
DISTORSIONE ARMONICA TENSIONI L-N - THD-V(L1), THD-V(L2), THD-V(L3)
HI
LO
AV
GR
HI
LO
AV
GR
GR
GR
GR
GR
11
DIST. ARMONICA CORRENTE - THD-I(L1), THD-I(L2) THD-I(L3)
12
CONTATORI DI ENERGIA - kWh+(TOT), kWh-(TOT), kvarh+(TOT), kvarh-(TOT), kVA(TOT)
13
TARIFFAZIONE ENERGIA
14
GRAFICO TREND
15
CONTAORE - Hr(TOT), Hr(Parziale)
16
MODULI ESPANSIONE
17
CONTATORI
CNT1
...
18
SOGLIE LIMITE
LIM1
...
LIM8
19
LOGICA BOOLEANA
BOO1
...
BOO8
20
ALLARMI
ALA1
...
ALA8
21
INFO-REVISIONI-Nº SERIE
MODELLO, REV SW, REV HW, Nº SERIES / TEMPERATURA INTERNA
22
LOGO
23
(PAGINA UTENTE 1)
24
(PAGINA UTENTE 2)
25
(PAGINA UTENTE 3)
26
(PAGINA UTENTE 4)
PARZIALE
TAR1
...
TAR4
I
CNT4
NOTA: Alcune delle pagine elencate sopra potrebbero non essere visualizzate, se la funzione visualizzata non è abilitata. Ad esempio se non viene programmato
alcun allarme, la corrispondente pagina non viene visualizzata.
NAVIGAZIONE FRA LE PAGINE DISPLAY
Tensioni concatenate
IN = Valore istantaneo
HI = Valore massimo
LO = Valore minimo
AV = Valore medio
GR = Barre grafiche
HI = Valore massimo
LO = Valore minimo
AV = Valore medio
GR = Barre grafiche
HI = Valore massimo
LO = Valore minimo
AV = Valore medio
MD = Max demand
Tensioni di fase
IN = Valore istantaneo
Correnti di fase e neutro
IN = Valore istantaneo
(continua)
20
31100124
PAGINA CONTATORI DI ENERGIA
– Nella pagina contatori di energia vengono visualizzati contemporaneamente:
• energia attiva importata ed esportata
• energia reattiva importata ed esportata (induttiva / capacitiva)
• energia apparente.
– La pagina principale visualizza i contatori totali. Tramite il tasto
è possibile accedere alla sotto-pagina con i contatori parziali (azzerabili dall’utente).
– Per l’azzeramento dei contatori è necessario accedere al menu comandi.
I271 I GB F E 01 13
1 - Indicazione Totali / Parziali
PAGINA CONTAORE
– Nella pagina contaore vengono visualizzati:
• contatore totale (conta il tempo di alimentazione dell’apparecchio)
• contaore parziale (conta il tempo per cui una condizione programmabile è verificata)
– Per l’azzeramento dei contatori è necessario accedere al menu comandi.
– La pagina contaore può essere disabilitata completamente se l’abilitazione generale contaore viene impostata su OFF (vedere menu Contaore).
I
PAGINA GRAFICO TREND
– La pagina trend consente di visualizzare un grafico con l’andamento nel tempo di una misura definita dall’utente, selezionabile fra:
• tensione equivalente integrata
• potenza attiva totale integrata
• potenza reattiva totale integrata
• potenza apparente totale integrata
– Di default, la misura visualizzata è la potenza attiva totale integrata. Per modificare la misura, agire sull’apposito parametro nel menu di impostazioni Trend.
– E’ possibile rappresentare sul grafico gli ultimi 96 valori della misura integrata, ciascuno corrispondente ad un intervallo di tempo di integrazione.
– L’intervallo di tempo di default è 15 minuti, cosicché il grafico ha la possibilità di visualizzare l’andamento della misura selezionata nelle ultime 24 ore.
– Con le impostazioni di fabbrica quindi il grafico trend ha la possibilità di visualizzare l’andamento dei consumi di potenza attiva nelle ultime 24 ore.
– I dati dei consumi vengono azzerati quando si disalimenta l’apparecchio oppure quando si agisce sul menu impostazioni.
– Superata la capacità massima di visualizzazione, i nuovi dati sostituiscono i più vecchi, secondo una logica di memorizzazione circolare.
– Il fondoscala verticale viene calcolato automaticamente in funzione dei dati nominali inseriti nel menu impostazioni Generale.
1 - Scala dei tempi.
Indica il tempo nel passato al quale si
riferiscono le misure.
2 - Scala verticale.
Può essere automatica o fissa.
3 - Misura rappresentata
Measurement viewed on graph
PAGINA CONTATORI
– Nella pagina contatori vengono visualizzati i conteggi CNT1…4.
– E’ possibile contare il numero di volte che un ingresso viene attivato, oppure un limite viene superato ecc. La condizione è definita dai parametri Sorgente di
conteggio.
– Per ciascun contatore è possibile definire una descrizione ed una unità di misura tramite un testo libero, ad esempio litri, mc, ecc.
– Inoltre si può definire un coefficiente di conversione fra il numero di impulsi conteggiati e la misura mostrata sul display. Questa funzione si ottiene
specificando un coefficiente moltiplicativo ed uno frazionario. Ad esempio impostando k moltiplicativo = 3, per ogni impulso letto verrà incrementato di 3 il
valore indicato a display. Se invece si programma un coefficiente frazionario = 10, la misura visualizzata verrà incrementata solo dopo 10 impulsi applicati
all’ingresso. Con la combinazione di k moltiplicativo e frazionario si può ottenere qualsiasi rapporto di conversione.
– Se il contatore non ha alcun coefficiente frazionario, allora la sua visualizzazione sarà solo con numeri interi. Altrimenti verranno visualizzate due cifre
decimali.
– I contatori possono essere azzerati tramite il menu comandi, oppure tramite il segnale Sorgente di reset definito dagli appositi parametri.
1 - Unità di misura del contatore
2 - Conteggio
3 - Descrizione (libera) del contatore
4 - Nr. delcontatore selezionato
PAGINE UTENTE
– L’utente ha la possibilità di creare un numero massimo di 4 pagine personalizzate.
– Queste pagine possono contenere 4 misure ciascuna scelte liberamente fra quelle disponibili sul DMG700.
– Il titolo della pagina utente può essere specificato liberamente dall’utente, dando ad esempio indicazione della parte di impianto servita dal multimetro.
– Le pagine utente sono posizionate in modo da poter essere raggiunte facilmente partendo dalla prima pagina premendo il tasto s.
– Come per tutte le altre pagine, è poi possibile programmare il multimetro per posizionare il display su una delle pagine utente dopo che per un certo tempo
non sono stati premuti dei tasti.
– Per l’impostazione delle pagine utente vedere l’apposito menu M15 nel capitolo impostazione parametri.
21
31100124
MENU PRINCIPALE
– Il menu principale è costituito da un insieme di icone grafiche che permettono l’accesso rapido alle misure ed alle impostazioni.
– Partendo dalla visualizzazione misure normale, premere il tasto MENU. Il display visualizza il menu rapido.
– Premere s t per selezionare la funzione desiderata.
L’icona selezionata viene evidenziata e la scritta nella parte centrale del display indica la descrizione della funzione.
– Premere
per attivare la funzione selezionata.
– Se alcune funzioni non sono disponibili la corrispondente icona sarà disabilitata, cioè visualizzata in colore grigio.
I271 I GB F E 01 13
–
ecc. - Agiscono come scorciatoie che consentono di velocizzare l’accesso alle pagine di visualizzazione misure, saltando
direttamente al gruppo di misure selezionato, partendo dal quale ci si potrà spostare avanti e indietro come di consueto.
–
- Impostazione del codice numerico che consente l’accesso alle funzioni protette (impostazione dei parametri, esecuzione di comandi).
–
- Punto di accesso alla programmazione dei parametri (set-up). Vedere il capitolo dedicato.
–
- Punto di accesso al menu comandi, dove l’utente abilitato può eseguire una serie di azioni di azzeramento e ripristino.
1 - Visualizzazione tensioni
7 - Grafico trend
2 - Visualizzazione correnti
8 - Visualizzazione contatore
3 - Visualizzazione potenze
9 - Moduli di espansione
4 - Frequenza - asimmetria
10 - Impostazioni set-up
5 - Analisi armonica
11 - Menu comandi
6 - Contatori di energia
12 - Inserimento password
ACCESSO TRAMITE PASSWORD
– La password serve per abilitare o bloccare l’accesso al menu di impostazione ed al menu comandi.
– Per gli apparecchi nuovi di fabbrica (default), la password è disabilitata e l’accesso è libero. Se invece le password sono state abilitate, per ottenere l’accesso
bisogna prima inserire il relativo codice di accesso numerico.
– Per abilitare l’uso delle password e definire i codici di accesso fare riferimento al capitolo impostazione parametri.
– Esistono due livelli di accesso, a seconda del codice inserito:
• Accesso livello utente - consente l’azzeramento dei valori registrati ma non la modifica delle impostazioni dell’apparecchio.
• Accesso livello avanzato - stessi diritti dell’utente con in più la possibilità di alterare le impostazioni.
– Dalla normale visualizzazione misure, premere MENU per richiamare il menu principale, quindi selezionare l’icona password e
premere .
– Compare la finestra di impostazione password in figura:
Con i tasti s t si cambia il valore della cifra selezionata.
Con il tasto
si conferma la cifra e ci si sposta a rotazione sulle successive.
Inserire la password, quindi spostarsi sull’icona della chiave.
Quando la password inserita corrisponde alla password livello Utente o livello Avanzato, compare il relativo messaggio di sblocco.
Una volta sbloccata la password, l’accesso rimane abilitato fino a che:
• L’apparecchio viene disalimentato.
• L’apparecchio viene resettato (in seguito all’uscita dal menu impostazioni).
• Trascorrono più di 2 minuti senza che l’operatore tocchi alcun tasto.
– Con il tasto MENU si abbandona l’impostazione password e si esce.
–
–
–
–
–
BLOCCO IMPOSTAZIONI
– Sul DMG700 sono disponibili due dip-switch che consentono di bloccare l’accesso alle impostazioni e alle operazioni di reset (menu comandi).
– Questi dip switch sono posizionati in modo da diventare inaccessibili una volta montati i coprimorsetti piombabili.
– Per posizionare i dip switch:
• togliere l’alimentazione al DMG700 e rimuovere entrambi i coprimorsetti (se montati) e la morsettiera estraibile a 8 poli
• con l’ausilio di un piccolo cacciavite a lama piatta, posizionare I dip switch nella configurazione voluta.
• riposizionare morsettiere e coprimorsetti.
– L’apparecchio viene fornito con i dip-switch configurati in posizione di accesso consentito.
SW
POS
SW1
OFF
Accesso ai parametri consentito
ON
Accesso ai parametri bloccato
SW2
22
DESCRIZIONE
OFF
Accesso a menu comandi consentito
ON
Accesso a menu comandi bloccato
I
31100124
I271 I GB F E 01 13
ESPANDIBILITÀ
– Grazie al suo bus di espansione, il DMG700 può essere espanso con dei moduli aggiuntivi della serie EXP.
– E’ possibile collegare ad un DMG700 un massimo di 4 moduli EXP….
– I moduli EXP… supportati dal DMG700 si dividono nelle seguenti categorie:
• moduli di comunicazione
• moduli di I/O digitale
– Per inserire un modulo di espansione:
• togliere l’alimentazione al DMG700
• rimuovere il coprimorsetto e la morsettiera estraibile a 8 poli
• rimuovere uno dei coperchi protettivi degli slot di espansione
• inserire il gancio superiore del modulo nella apposita feritoia
• ruotare il modulo verso il basso inserendo il connettore sul bus
• premere fino a che l’apposita clip sul lato inferiore del modulo si aggancia a scatto
• Re-installare la morsettiera e il coprimorsetto trasparente.
– L’ordine di inserimento dei moduli è libero.
1
2
3
I
4
CLICK!
ATTENZIONE!
Quando vengono installati dei moduli EXP… su dei multimetri della serie DMG, è obbligatorio installare i coprimorsetti piombabili forniti con il multimetro.
– Quando un DMG700 viene alimentato, riconosce automaticamente i moduli EXP ad esso collegati.
– Se la configurazione del sistema è diversa rispetto all’ultima rilevata (è stato aggiunto o rimosso un modulo) l’unità base chiede all’utente di confermare la
nuova configurazione. In caso di conferma la nuova configurazione verrà salvata e diventerà effettiva, altrimenti ad ogni messa in tensione verrà segnalata la
discordanza.
– La configurazione attuale del sistema è visualizzata nella apposita pagina del display (moduli espansione), dove si vedono il numero, il tipo e lo stato dei
moduli collegati.
– La numerazione degli I/O viene elencata sotto ogni modulo.
– Lo stato (attivato/disattivato) degli I/O e dei canali di comunicazione viene evidenziato con la scritta in negativo.
1 - Nr. e stato del canale di comunicazione
2 - Tipo dei moduli di espansione
3 - Numerazione e stato degli I/O
RISORSE AGGIUNTIVE
– I moduli di espansione forniscono delle risorse aggiuntive che possono essere sfruttate tramite gli opportuni menu di impostazione.
– I menu di impostazione che riguardano le espansioni sono disponibili anche se i moduli non sono fisicamente presenti.
– Dato che è possibile aggiungere più moduli della stessa tipologia (ad esempio due interfacce di comunicazione) i relativi menu di impostazione sono multipli,
identificati da un numero progressivo.
– Di seguito una tabella che indica quanti moduli di ogni tipo possono essere montati contemporaneamente.
TIPO DI MODULO
CODE
FUNCTION
MAX No.
COMUNICAZONE
EXP10 10
USB
2
EXP10 11
RS232
I/O DIGITALI
EXP10 12
RS485
EXP10 00
4 INGRESSI
2
EXP10 01
4 USCITE STATICHE
2
EXP10 02
2 INGRESSI +
2 USCITE ST.
4
EXP10 03
2 RELE’
4
CANALI DI COMUNICAZIONE
– Al DMG700 è possibile connettere al massimo 2 moduli di comunicazione, denominati COMn. Il menu di impostazione comunicazioni M07 prevede quindi
due sezioni (n=1 e n=2) di parametri per l’impostazione delle porte di comunicazione.
– I canali di comunicazione sono completamente indipendenti, sia dal punto di vista hardware (tipo di interfaccia fisica) che dal punto di vista del protocollo di
comunicazione.
– I canali di comunicazione possono funzionare contemporaneamente.
23
31100124
I271 I GB F E 01 13
INGRESSI, USCITE, VARIABILI INTERNE, CONTATORI
– Gli ingressi e le uscite digitali forniti dai moduli di espansione sono identificati da una sigla e da un numero progressivo. Ad esempio gli ingressi digitali sono
denominati INPx, dove x rappresenta il numero dell’ingresso. Allo stesso modo, le uscite digitali sono denominate OUTx.
– La numerazione degli ingressi / uscite si basa semplicemente sulla posizione di montaggio dei moduli di espansione, con una numerazione progressiva da
sinistra a destra. Ad esempio l’ingresso INP1 è il primo morsetto di ingresso del modulo più a sinistra, mentre i successivi preseguendo verso destra
saranno INP2, INP3 ecc.
– Per il DMG700 sono previsti un massimo di 8 ingressi digitali e di 8 uscite, che saranno quindi denominati INP1…INP8 e OUT1…OUT8. Per ciascun I/O
esiste un menu di impostazione che consente di specificarne la funzione e le proprietà.
– Allo stesso modo degli ingressi/uscite, esistono delle variabili interne (bit) che possono essere associate alle uscite o combinate fra loro. Ad esempio si
possono applicare delle soglie limite alle misure effettuate dal multimetro (tensione, corrente etc.). In questo caso la variabile interna, denominata LIMx, sarà
attivata quando la misura risulta essere fuori dai limiti definiti dall’utente tramite il relativo menu di impostazione.
– Infine è possibile gestire fino a 4 contatori (CNT1…CNT4) che possono conteggiare impulsi provenienti dall’esterno (quindi da ingressi INPx) oppure il
numero di volte per cui si è verificata una determinata condizione. Ad esempio definendo una soglia LIMx come sorgente di conteggio, sarà possibile contare
quante volte una misura ha superato un certo valore.
– Di seguito una tabella che raccoglie tutti gli I/O e le variabili interne gestiti dal DMG700.
Cod.
DESCRIZIONE
Range (x)
INPx
Ingressi digitali
1...8
OUTx
Uscite digitali
1...8
LIMx
Soglie limite
1...8
BOOx
Combinazioni Booleane
1...8
REMx
Variabili da remoto
1...8
ALAx
Allarmi
1...8
PULx
Impulsi di conteggio energia
1...5
CNTx
Contatori
1...4
– Lo stato di ciascun I/O e variabile interna può essere visualizzato sul display nella apposita pagina di stato I/O.
SOGLIE LIMITE (LIM)
– Le soglie limite LIMn sono delle variabili interne il cui stato dipende dalla fuoriuscita dai limiti definiti dall’utente da parte di una misura fra quelle effettuate
dal multimetro (esempio: potenza attiva totale superiore a 25kW).
– Per velocizzare l’impostazione delle soglie, che possono spaziare in un range estremamente ampio, ciascuna di esse va impostata con un valore base + un
coefficiente moltiplicativo (esempio: 25 x 1k = 25000).
– Per ogni LIM sono disponibili due soglie (superiore ed inferiore). La soglia superiore deve essere sempre impostata ad un valore maggiore di quella inferiore.
– il significato delle soglie dipende dalle seguenti funzioni:
Funzione Min: con la funzione Min la soglia inferiore è d’intervento quella superiore di ripristino. Quando il valore della misura selezionata è sotto il limite
inferiore, dopo il ritardo si ha l’attivazione della soglia. Quando il valore della misura è maggiore della soglia superiore, dopo il ritardo si ha il ripristino.
Funzione Max: con la funzione Max la soglia superiore è d’intervento quella inferiore di ripristino. Quando il valore della misura selezionata è maggiore della
superiore, dopo il ritardo si ha l’attivazione della soglia. Quando il valore della misura è minore della soglia inferiore, dopo il ritardo si ha il ripristino.
Funzione Min+Max: con la funzione Min+Max le soglie inferiore e superiore sono entrambe d’intervento. Quando il valore della misura selezionata è minore
della soglia inferiore o maggiore della soglia superiore, dopo i rispettivi ritardi si ha l’intervento dell’uscita. Quando il valore della misura rientra nei limiti si
ha il ripristino immediato
– L’intervento può significare eccitazione o diseccitazione del limite LIMn a seconda dell’impostazione.
– Se il limite è impostato con memoria, il ripristino è manuale e può essere effettuato tramite il comando apposito nel menu comandi.
– Vedere il menu di impostazione M08.
1 - Stato variabile limite
2 - Valore della misura
3 - Funzione
4 - Tipo di misura
5 - Soglia superiore
6 - Ritardo su soglia
7 - Soglia inferiore
LOGICA BOOLEANA (BOO)
– E’ possibile creare un massimo di 8 variabili interne denominate BOO1…8 il cui stato dipende dalla combinazione logica Booleana di soglie limite, ingressi,
uscite etc.
– Gli operandi (INP, LIM ecc.) possono essere combinati fra loro con le seguenti operazioni logiche Booleane: AND, OR, EXOR, AND NOT, OR NOT, EXOR NOT.
– Ogni variabile Booleana è il risultato della combinazione di massimo 4 operandi legati fra loro da tre operazioni logiche.
– Esempio: se desideriamo che la variabile BOO1 venga attivata quando sono attivi i limiti LIM2, LIM3 e LIM4 oppure quando è attivo l’ingresso INP1, dovremo
programmare BOO1 come la combinazione di LIM2 AND LIM3 AND LIM4 OR INP1.
– Non è necessario utilizzare tutti i 4 operandi per una combinazione logica. Se ad esempio vogliamo solo che BOO2 sia attivo quando è attivo INP1 oppure
INP2, è possibile programmare i parametri di BOO2 come la combinazione INP1 OR INP2, lasciando le successive operazioni logiche impostate su
--- (nessuna operazione).
– La pagina display LOGICA BOOLEANA visualizza , per ciascuna variabile BOO1..8, lo stato dei singoli operandi che sono coinvolti nella operazione logica ed il
risultato finale, cioè lo stato della variabile Booleana selezionata.
1 - Operando 1
2 - Operazione logica 1
3 - Operando 2
4 - Stato operando 1
5 - Stato variabile booleana risultante
VARIABILI DA REMOTO (REM)
– DMG700 ha la possibilità di gestire un massimo di 8 variabili comandate da remoto (REM1…REM8).
– Si tratta di variabili il cui stato può essere modificato a piacere dall’utente tramite il protocollo di comunicazione e che possono essere utilizzate in
abbinamento alle uscite, alla logica Booleana etc.
– Esempio: usando una variabile remota (REMx) come sorgente di una uscita (OUTx) sarà possibile attivare e disattivare liberamente un relè tramite il software
di supervisione. Questo consentirebbe di utilizzare i relè di uscita del DMG700 per comandare dei carichi ad esempio illuminazione o altro.
– Un altro utilizzo delle variabili REM può essere quello di abilitare o disabilitare determinate funzioni da remoto, inserendole in una logica Booleana in AND con
ingressi o uscite.
24
I
31100124
I271 I GB F E 01 13
ALLARMI (ALA)
– L’utente ha la possibilità di definire un massimo di 8 allarmi programmabili (ALA1…ALA8).
– Per ciascun allarme è possibile stabilire la sorgente, cioè la condizione che genera l’allarme ed il testo del messaggio che deve comparire sul display quando
questa condizione si verifica.
– La condizione che genera l’allarme può essere ad esempio il superamento di una soglia. In questo caso la sorgente sarà una delle soglie limite LIMx.
– Se invece l’allarme deve essere visualizzato in conseguenza dell’attivazione di un ingresso digitale esterno, allora la sorgente sarà un INPx.
– Con lo stesso criterio è possibile abbinare ad un allarme anche condizioni complesse risultanti dalla combinazione logica Booleana di ingressi, soglie, etc. In
questo caso si utilizzeranno le variabili Booleane BOOx.
– Per ciascun allarme l’utente ha la possibilità di definire un messaggio liberamente programmabile che comparirà sulla pagina stato allarmi.
– E’ poi possibile definire una priorità di allarme. Se si tratta di una semplice indicazione, allora la priorità può essere impostata come bassa. In questo caso
l’icona che accompagna l’allarme sarà l’icona di informazione.
– Se invece l’allarme deve indicare una situazione più importante, impostando la sua priorità su alta, sarà possibile indicare il messaggio con l’icona di
attenzione e far sì che al verificarsi dell’allarme la pagina del display si sposti automaticamente sulla pagina visualizzazione allarmi.
– In caso di presenza contemporanea di più allarmi essi vengono mostrati a rotazione e ne viene indicato il numero totale.
– Per azzerare un allarme che è stato programmato con memoria, utilizzare l’apposito comando nel menu comandi.
– Per la definizione degli allarmi vedere menu di impostazione M09.
1 - Nr. allarme / totale allarmi
I
TARIFFE
– Per il conteggio dell’energia, il DMG700 ha la possibilità di gestire 4 tariffe indipendenti oltre alla totale e alla parziale.
– La selezione delle tariffe avviene tramite degli ingressi digitali esterni, ed è quindi condizionata all’installazione di un modulo di espansione EXP fornito di
ingressi digitali.
Per selezionare le 4 tariffe sono disponibili le due funzioni di ingresso TAR-A e TAR-B.
La loro combinazione binaria effettua la selezione come da tabella:
TAR-A
TAR-B
TARIFFA
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
– Se viene utilizzato l’ingresso di sincronismo per l’intervallo di integrazione, allora il cambio tariffa viene effettuato in concomitanza con il sincronismo,
altrimenti il cambio di tariffa avviene al momento del cambio di configurazione degli ingressi.
– I conteggi delle tariffe, ciascuno con i
5 contatori di energia (attiva importata ed esportata, reattiva importata ed esportata, apparente) sono visualizzati su una apposita pagina, consecutiva a quella
dei contatori totali e parziali .
– Se il DMG è fornito di interfaccia di comunicazione, è possibile selezionare la tariffa attiva tramite un apposito comando sul protocollo Modbus (vedere
istruzione tecnica protocollo Modbus).
1 - Tariffa attiva
2 - Tariffa visualizzata
IMPOSTAZIONE DEI PARAMETRI (SET-UP)
– Dalla normale visualizzazione misure, premere MENU per richiamare il menu principale, quindi selezionare l’icona
e premere
per accedere al
menu impostazioni.
• Viene visualizzata la tabella in figura, con la selezione dei sotto-menu di impostazione, nei quali sono raggruppati tutti i parametri secondo un criterio legato
alla loro funzione.
• Selezionare il menu desiderato tramite i tasti s t e confermare con
• Per uscire e tornare alla visualizzazione misure premere MENU.
25
31100124
I271 I GB F E 01 13
– Nella seguente tabella sono elencati i sottomenu disponibili
Code
Sottomenu
Descrizione
M01
GENERALE
Dati caratteristici dell’impianto
M02
UTILITA’
Lingua, luminosità, pagine
M03
PASSWORD
Abilitazione protezione accesso
M04
INTEGRAZIONE
Tempi di integrazione misure
M05
CONTAORE
Abilitazione contaore
M06
GRAFICO TREND
Definizione misura e scala
M07
COMUNICAZIONE (COMn)
Porte di comunicazione
M08
SOGLIE LIMITE (LIMn)
Soglie sulle misure
M09
ALLARMI (ALAn)
Messaggi di allarme
M10
CONTATORI (CNTn)
Contatori generici
M11
IMPULSI (PULn)
Impulsi di conteggio energia
M12
LOGICA BOOLEANA (BOOn)
Combinazioni logica Booleana
M13
INGRESSI (INPn)
Ingressi digitali
M14
USCITE (OUTn)
Uscite digitali
M15
PAGINE UTENTE (PAGn)
Pagine personalizzate
I
– Selezionare il sotto-menu e premere il tasto
per visualizzare i parametri.
– Tutti i parametri sono visualizzati con codice, descrizione, valore attuale.
1 - Codice parametro
2 - Descrizione parametro
3 - Valore attuale
4 - Parametro selezionato
– Se si vuole modificare il valore di un parametro, dopo averlo selezionato premere .
– Se non è stata immessa la password livello Avanzato, non sarà possibile accedere alla pagina di modifica, e verrà visualizzato un messaggio di accesso negato.
– Se invece si ha l’accesso, verrà visualizzata la pagina di modifica.
1 - Parametro selezionato
2 - Minimo valore possibile
3 - Barra grafica valore-range
4 - Nuovo valore impostato
5 - Massimo valore possibile
6 - Valore di default di fabbrica
– Quando si è in modalità modifica, il valore può essere modificato con i tasti s e t. Vengono visualizzati anche una barra grafica che indica il range di
impostazione, i valori minimi e massimi possibili, il valore precedente e quello di default.
– Premendo contemporaneamente s e t l’impostazione viene riportata al valore di default di fabbrica.
si sposta il cursore all’interno del testo. Premendo
– Durante l’impostazione di un testo, con i tasti s e t si seleziona il carattere alfanumerico e con
contemporaneamente s e t la selezione alfanumerica si posiziona direttamente sul carattere ‘A’.
– Premere MENU per tornare alla selezione parametri. Il valore immesso rimane memorizzato.
– Premere di nuovo MENU per salvare i cambiamenti ed uscire dalla impostazione. Il multimetro esegue un reset e ritorna in funzionamento normale.
– Se non vengono premuti tasti per 2 minuti consecutivi, il menu set-up viene abbandonato automaticamente e il multimetro torna alla visualizzazione normale.
TABELLA PARAMETRI
UdM
Default
Range
P01.01
M01 - GENERALE
Primario TA
A
5
1-10000
P01.02
Secondario TA
A
5
5
P01.03
Tensione nominale
V
Aut
Aut / 50-500000
P01.04
Utilizzo TV
OFF
OFF-ON
P01.05
Primario TV
V
100
50-500000
P01.06
Secondario TV
V
P01.07
Tipo di collegamento
100
50-500
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
L1-N
P01.01 – Corrente nominale del primario dei TA.
P01.02 – Corrente del secondario dei TA. Fisso a 5A per DMG700.
P01.03 - Tensione nominale dell’impianto. Lasciando su Aut il multimetro adegua automaticamente la scala delle barre grafiche.
P01.04 – Programmare ad ON se vengono utilizzati dei TV. Se programmato ad OFF i successivi due parametri vengono ignorati.
P01.05 – Tensione nominale primario TV.
P01.06 – Tensione nominale secondario TV.
P01.07 – Impostare concordemente allo schema di collegamento utilizzato. Vedere Schemi di collegamento alla fine del manuale.
26
31100124
I271 I GB F E 01 13
M02 - UTILITA’
Default
Range
English
English
Italiano
Francais
Espanol
Portoguese
%
50
0-100
%
100
0-100
Intensità retroilluminazione display bassa
%
30
0-50
P02.05
Tempo passaggio a retroilluminazione bassa
sec
30
5-600
P02.06
Ritorno a pagina di default
sec
60
OFF / 10-600
P02.07
Pagina di default
VL-L
VL-L / VL-N ...
P02.08
Sotto-pagina di default
INST
INST / HI / LO /
AVG / MD /GRAPH /
1-8
P02.09
Tempo di aggiornamento display
0.5
0.1 - 5.0
P02.01
Lingua
P02.02
Contrasto LCD
P02.03
Intensità retroilluminazione display alta
P02.04
UdM
sec
P02.06 – Se impostato ad OFF il display rimane sempre nella pagina dove è stato lasciato dall’utente. Se impostato ad un valore, dopo questo tempo il display
ritorna alla pagina impostata con P02.07.
P02.07 – Numero della pagina alla quale il display ritorna automaticamente una volta che è trascorso il tempo P02.06 dall’ultima pressione di un tasto.
P02.08 – Tipo di sotto-pagina alla quale il display torna dopo trascorso P02.06.
M03 - PASSWORD
Default
Range
Utilizzo password
OFF
OFF-ON
P03.02
Password livello Utente
1000
0-9999
P03.03
Password livello Avanzato
2000
0-9999
P03.01
UdM
P03.01 – Se impostato ad OFF, la gestione delle password è disabilitata e l’accesso alle impostazioni e al menu comandi è libero.
P03.02 – Con P03.01 attivo, valore da specificare per attivare l’accesso a livello utente. Vedere capitolo Accesso tramite password.
P03.03 – Come P03.02, riferito all’accesso livello Avanzato.
M04 - INTEGRAZIONE
Default
Range
Scorr.
Fisso / Scorrevole
Sincronismo / Bus
min
15
1-60
min
15
1-60
Tempo di integrazione tensioni
min
1
1-60
Tempo di integrazione frequenza
min
1
1-60
P04.01
Modo integrazione
P04.02
Tempo integrazione potenze
P04.03
Tempo integrazione correnti
P04.04
P04.05
UdM
P04.01 – Selezione della modalità di calcolo delle misure integrate.
Fisso = Le misure istantanee vengono integrate per il tempo impostato. Ad ogni scadenza del tempo, la misura integrata viene aggiornata con il risultato
dell’ultima integrazione.
Scorrevole = Le misure istantanee vengono integrate per un tempo = 1/15 del tempo impostato. Ad ogni scadenza di questo intervallo viene sostituito il valore
più vecchio con il nuovo calcolato. La misura integrata viene aggiornata ogni 1/15 del tempo impostato, considerando una finestra scorrevole nel tempo che
comprende gli ultimi 15 valori calcolati, di lunghezza totale equivalente al tempo impostato.
Sincronismo = Come modalità fisso, ma gli intervalli di integrazione sono scanditi da un ingresso digitale esterno programmato con la funzione sincronismo.
Bus = Come modalità fisso, ma gli intervalli di integrazione sono scanditi da messaggi di sincronismo inviati sul bus seriale.
P04.02 – Tempo integrazione misure AVG (media) per le potenze attiva, reattiva ed apparente.
P04.03, P04.04, P04.05 – Tempo integrazione misure AVG (media) per le relative grandezze.
Default
Range
P05.01
M05 - CONTAORE
Abilitazione generale contaore
UdM
ON
OFF-ON
P05.02
Abilitazione contaore parziale
ON
OFF-ON- INPxLIMx-BOOx
P05.03
Numero canale (x)
1
1-8
P05.01 – Se OFF i contaore sono disabilitati e la pagina di misura dei contaore non viene visualizzata.
P05.02 – Se OFF il contaore parziale non viene incrementato. Se ON viene incrementato quando il multimetro è alimentato. Se abbinato ad una delle variabili
interne (LIMx-INPx-BOOx) viene incrementato solo quando questa condizione è vera.
P05.03 – Numero del canale (x) della variabile interna eventualmente usato nel parametro precedente. Esempio: Se il contaore parziale deve contare il tempo per
cui una misura è oltre una certa soglia, definita dal limite LIM3, programmare LIMx nel parametro precedente e specificare 3 in questo parametro.
M06 - GRAFICO TREND
P06.01
Misura per pagina trend
P06.02
Autorange scala
P06.03
Valore fondo scala
P06.04
Moltiplicatore fondo scala
UdM
Default
Range
kW (tot)
AVG
VL-L (eq) AVG
kW (tot) AVG
kvar (tot) AVG
kVA (tot) AVG
ON
OFF-ON
1000
0-1000
x1
x1 - x1k - x1M
P06.01 – Seleziona la misura da visualizzare sul grafico Trend.
P06.02 – Decide se la scala verticale si adatta automaticamente ai valori visualizzati oppure se viene definita fissa dall’utente.
P06.03 – Valore di fondo scala definito dall’utente. L’unità di misura diventa quella della misura selezionata.
P06.04 – Moltiplicatore del valore di fondo scala.
27
I
31100124
M07 - COMUNICAZIONE
UdM
P07.n.01 Indirizzo seriale nodo
I271 I GB F E 01 13
P07.n.02 Velocità seriale
bps
P07.n.03 Formato dati
Default
Range
01
01-255
9600
1200
2400
4800
9600
19200
38400
8 bit - n
8 bit, no parity
8bit, odd
8 bit, even
7 bit, odd
7 bit, even
P07.n.04 Bit di stop
1
1-2
P07.n.05 Protocollo
Modbus RTU
Modbus RTU
Modbus ASCII
Nota: questo menu è diviso in 2 sezioni, per i canali di comunicazione COM1..2
P07.n.01 – Indirizzo seriale (nodo) del protocollo di comunicazione.
P07.n.02 – Velocità di trasmissione della porta di comunicazione.
P07.n.03 – Formato dati. Impostazioni a 7 bit possibili solo per protocollo ASCII.
P07.n.04 – Numero bit di stop.
P07.n.05 – Scelta del protocollo di comunicazione.
M08 - SOGLIE LIMITE
I
Default
Range
P08.n.01 Misura di riferimento
UdM
OFF
OFF- (misure)
P08.n.02 Funzione
Max
Max - Min - Min+Max
P08.n.03 Soglia superiore
0
-9999 - +9999
P08.n.04 Moltiplicatore
x1
/100 - x10k
P08.n.05 Ritardo
sec
0
0.0 - 600.0
0
-9999 - +9999
x1
/100 - x10k
0
0.0 - 600.0
P08.n.09 Stato a riposo
OFF
OFF-ON
P08.n.10 Memoria
OFF
OFF-ON
P08.n.06 Soglia inferiore
P08.n.07 Moltiplicatore
P08.n.08 Ritardo
sec
Nota: questo menu è diviso in 8 sezioni, per le soglie limite LIM1..8
P08.n.01 – Definisce a quale delle misure del multimetro applicare la soglia limite.
P08.n.02 – Definisce il funzionamento della soglia limite. Può essere:
Max = LIMn attivo quando la misura supera P08.n.03. P08.n.06 è la soglia di ripristino.
Min = LIMn attivo quando la misura è inferiore a P08.n.06. P08.n.03 è la soglia di ripristino.
Min+Max = LIMn attivo quando la misura è superiore a P08.n.03 oppure inferiore a P08.n.06.
P08.n.03 e P08.n.04 – Definiscono la soglia superiore, che è data dal valore di P08.n.03 moltiplicato per P08.n.04.
P08.n.05 – Ritardo di intervento sulla soglia superiore.
P08.n.06, P08.n.07, P08.n.08 – come sopra, riferiti alla soglia inferiore.
P08.n.09 – Permette di invertire lo stato del limite LIMn.
P08.n.10 – Definisce se la soglia rimane memorizzata e va azzerata manualmente (ON) o se si ripristina automaticamente (OFF).
M09 - ALLARMI
P09.n.01 Sorgente allarme
P09.n.02 Numero canale (x)
P09.n.03 Memoria
Default
Range
OFF
OFF-LIMx-INPx-BOOx
1
1-8
OFF
OFF-ON
P09.n.04 Priorità
Low
Bassa - Alta
P09.n.05 Testo
ALAn
(testo - 16 char)
Nota: questo menu è diviso in 8 sezioni, per gli allarmi ALA1..8
P09.n.01 – Segnale che provoca l’allarme. Può essere il superamento di una soglia (LIMx), l’attivazione di un ingresso esterno (INPx), una condizione logica
Booleana (BOOx).
P09.n.02 – Numero del canale x riferito al parametro precedente.
P09.n.03 – Definisce se l’ allarme rimane memorizzato e va azzerato manualmente (ON) o se si ripristina automaticamente (OFF).
P09.n.04 – Se l’allarme ha priorità alta, al suo verificarsi provoca lo spostamento automatico del display sulla pagina allarmi e viene visualizzato con l’icona di
attenzione. Se invece è impostato su priorità bassa, la pagina non cambia e viene visualizzato con l’icona di informazione.
P09.n.05 – Testo libero dell’allarme. Max. 16 caratteri.
28
31100124
M10 - CONTATORI
Default
Range
P10.n.01 Sorgente conteggio
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.02 Numero canale (x)
1
1-8
P10.n.03 Moltiplicatore
1
1-1000
I271 I GB F E 01 13
P10.n.04 Divisore
1
1-1000
P10.n.05 Descrizione del contatore
CNTn
(Testo - 16 caratteri)
P10.n.06 Unità di misura
Umn
(Testo - 6 caratteri)
P10.n.07 Sorgente di reset
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.08 Numero canale (x)
1
1-8
Nota: questo menu è diviso in 4 sezioni, per i contatori CNT1..4
P010.n.01 = Segnale che provoca l’incremento del conteggio (sul fronte di salita). Può essere la messa in tensione del multimetro (ON), il superamento di una
soglia (LIMx), l’attivazione di un ingresso esterno (INPx), una condizione logica Booleana (BOOx).
P010.n.02 = Numero del canale x riferito al parametro precedente.
P010.n.03 = K moltiplicativo. Gli impulsi contati vengono moltiplicati per questo valore prima di essere visualizzati.
P010.n.04 = K frazionario. Gli impulsi contati vengono divisi per questo valore prima di essere visualizzati. Se diverso da 1, il contatore viene visualizzato con 2
cifre decimali.
P10.n.05 = Descrizione del contatore. Testo libero 16 caratteri.
P10.n.06 = Unità di misura del contatore. Testo libero 6 caratteri.
P10.n.07 = Segnale che provoca l’azzeramento del conteggio. Fino a che questo segnale è attivo il conteggio rimane al valore zero.
P10.n.08 = Numero del canale x riferito al parametro precedente.
M11 - IMPULSI
Default
Range
P11.n.01 Misura sorgente
kWh+
kWh+,kWh-,kvarh+,kvarh-,kVAh
P11.n.02 Unità di conteggio
100
10/100/1k/10k
P11.n.03 Durata impulso
0.1
0.01-1.00
Nota: questo menu è diviso in 5 sezioni, per gli impulsi di conteggio energia PUL1..5
P11.n.01 = Tipo di energia alla quale è legato l’impulso.
P11.n.02 = Quantità di energia per ogni impulso (esempio 10Wh, 100Wh, 1kWh ecc.).
P11.n.03 = Durata dell’impulso.
M12 - LOGICA BOOLEANA
P12.n.01 Operando 1
Default
Range
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.02 Numero canale (x)
1
1-8
P12.n.03 Operazione logica 1
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.04 Operando 2
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.05 Numero canale (x)
1
1-8
P12.n.06 Operazione logica 2
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.07 Operando 3
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.08 Numero canale (x)
1
1-8
P12.n.09 Operazione logica 3
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.10 Operando 4
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
1
1-8
P12.n.11 Numero canale (x)
Nota: questo menu è diviso in 8 sezioni, per le variabili Booleane BOO1..8
P12.n.01 = Primo operando della logica Booleana.
P12.n.02 = Numero del canale riferito al parametro precedente.
P12.n.03 = Operazione logica fra il primo ed il secondo operando.
P12.n.04 = Secondo operando.
Da P12.n.05 a P12.n.11 – (come sopra).
M13 - INGRESSI
UdM
P13.n.01 Funzione ingresso
P13.n.02 Stato riposo
Default
Range
OFF
OFF - ON - LOCK SYNC - TAR-A TAR-B
C01...C08
OFF
OFF-ON
P13.n.03 Ritardo ON
sec
0.05
0.00 - 600.00
P13.n.04 Ritardo OFF
sec
0.05
0.00 - 600.00
Nota: questo menu è diviso in 8 sezioni, per gli ingressi INP1..8
P13.n.01 = Funzione ingresso:
OFF – Ingresso disabilitato
ON – Ingresso abilitato, usato come sorgente per contatori, logica Booleana, ecc.
LOCK – Blocco impostazioni – impedisce l’accesso ad entrambi i livelli.
SYNC – Sincronismo per integrazione potenza.
TAR-A, TAR-B – Selezione tariffa energie. Vedere capitolo tariffazione.
C01…C08 – Quando questo ingresso viene attivato (sul fronte di salita), viene esguito il corrispondente comando del menu comandi.
P13.n.02 = Stato a riposo dell’ingresso. Permette di invertire la logica di attivazione.
P13.n.03 – P13.n.04 = Ritardi di attivazione – disattivazione dell’ingresso. Permettono di filtrare lo stato per evitare rimbalzi.
29
I
31100124
M14 - USCITE
UdM
P14.n.01 Funzione di uscita
Default
Range
OFF
OFF-ON-SEQ-LIMxBOOx-ALAx-PULxREMx
P14.n.02 Numero canale (x)
P14.n.03 Stato a riposo
1
1-8
OFF
OFF-ON
I271 I GB F E 01 13
Nota: questo menu è diviso in 8 sezioni, per le uscite OUT1..8
P14.n.01 = Funzione della uscita:
OFF – Uscita disabilitata
ON – Uscita sempre abilitata
SEQ – Uscita attivata in caso di errata sequenza fasi
LIMx – BOOx – ALAx – PULx – REMx – Uscita abbinata allo stato della variabile programmata. Permette di portare su di una uscita lo stato di una soglia, di una
combinazione Booleana, di un allarme, ecc.
P14.n.02 = Numero di canale (x) riferito al parametro precedente.
P14.n.03 = Stato a riposo dell’uscita. Permette di invertire la logica di funzionamento dell’uscita.
M15 - PAGINE UTENTE
P15.n.01 Abilitazione pagina
P15.n.02 Titolo
Default
Range
OFF
OFF - ON
PAGn
(testo 16 char)
P15.n.03 Misura 1
OFF
OFF-(tutte le misure)
P15.n.04 Misura 2
OFF
OFF-(tutte le misure)
P15.n.05 Misura 3
OFF
OFF-(tutte le misure)
P15.n.06 Misura 4
OFF
OFF-(tutte le misure)
Nota: questo menu è diviso in 4 sezioni, per le pagine utente PAG1…PAG4
P15.n.01 = Abilita la pagina utente PAGn.
P15.n.02 = Titolo della pagina utente. Testo libero.
P15.n.03, P15.n.04, P15.n.05, P15.n.06 = Misure che verranno visualizzate nei quattro riquadri della pagina utente.
MENU COMANDI
– Il menu comandi permette di eseguire operazioni saltuarie quali azzeramenti di misure, contatori, allarmi, ecc.
– Se è stata immessa la password per accesso avanzato, allora tramite il menu comandi è anche possibile effettuare delle operazioni automatiche utili ai fini
della configurazione dello strumento.
– Nella seguente tabella sono riportate le funzioni disponibili con il menu comandi, divise a seconda del livello di accesso necessario.
Code
COMANDO
LIVELLO ACCESSO
Utente
DESCRIZIONE
Avanzato
C.01
RESET HI-LO
l
l
Azzera i valori di picco HI e LO di tutte le misure
C.02
AZZERAMENTO MAX DEMAND
l
l
Azzera i valori Max demand di tutte le misure
C.03
AZZERAMENTO ENERGIE PARZIALI
l
l
Azzeramento dei contatori di energia parziali
C.04
AZZERAMENTO CONTAORE PARZIALI
l
l
Azzeramento dei contaore parziali
C.05
AZZERAMENTO CONTATORI
l
l
Azzeramento contatori
C.06
AZZERAMENTO TARIFFE
l
l
Azzeramento contatori tariffe
C.07
AZZERAMENTO ALLARMI
l
l
Azzeramento allarmi con memoria
C.08
AZZERAMENTO LIMITI
l
l
Azzeramento soglie limite con memoria
C.11
AZZERAMENTO ENERGIE TOTALI
l
Azzeramento dei contatori di energia totali, parziali e tariffe
C.12
AZZERAMENTO CONTAORE TOTALI
l
Azzeramento dei contaore totali
C.13
PARAMETRI A DEFAULT
l
Ripristina tutte le impostazioni ai valori di default di fabbrica
C.14
BACKUP PARAMETRI
l
Salva una copia di sicurezza (backup) delle impostazioni
C.15
RIPRISTINO PARAMETRI
l
Ricarica le impostazioni dalla copia di sicurezza
C.16
TEST COLLEGAMENTO
l
Esegue il test per verificare la correttezza del collegamento
del DMG. Vedere capitolo Test collegamento
– Una volta selezionato il comando desiderato, premere
per eseguirlo. Lo strumento chiederà una conferma. Premendo nuovamente
eseguito.
– Per annullare l’esecuzione di un comando selezionato premere MENU.
– Per abbandonare il menu comandi premere MENU.
30
il comando verrà
I
31100124
I271 I GB F E 01 13
TEST DI COLLEGAMENTO
– Il test di collegamento consente di verificare se l’installazione del multimetro è stata effettuata correttamente.
– Per poter eseguire il test, il multimetro deve essere inserito in un impianto attivo con le seguenti condizioni:
• sistema trifase con presenza di tutte le fasi (V > 50VAC L-N)
• corrente minima circolante su ciascuna fase> 1% del fondo scala del TA impostato
• verso positivo delle energie (cioè in un comune impianto dove il carico induttivo assorbe energia dalla fornitura)
• Per lanciare l’esecuzione del test, entrare nel menu comandi e selezionare il comando appropriato secondo le istruzioni del capitolo Menu comandi.
– Il test consente di verificare i seguenti punti:
• lettura delle tre tensioni
• sequenza delle fasi
• sbilanciamento delle tensioni
• inversione della polarità di uno o più TA
• scambio delle fasi fra tensioni/correnti
– Se il test non viene superato, il display visualizza la ragione dell’errore.
– Se il test viene superato, la condizione viene memorizzata nella memoria non volatile ed un messaggio che attesta l’esito positivo viene visualizzato nella
pagina informazioni.
1 - Sequenza dei controlli
2 - Esito del test
I
31
31100124
I
CARATTERISTICHE TECNICHE
Condizioni ambientali
Alimentazione ausiliaria
Tensione nominale Us ∂
I271 I GB F E 01 13
Limiti di funzionamento
100 - 440V~
110 - 250V
Temperatura d’impiego
-20...+60°C
Temperatura di stoccaggio
-30...+80°C
90 - 484V~
93,5 - 300V
Umidità relativa
<80% (IEC/EN 60068-2-70)
Inquinamento ambiente massimo
Grado 2
Categoria di misura
III
Categoria dì sovratensione
3
Altitudine
≤2000m
Sequenza climatica
Z/ABDM (IEC/EN 60068-2-61)
690V~ fase-fase
400V~ fase-neutro
Resistenza agli urti
15g (IEC/EN 60068-2-27)
Resistenza alle vibrazioni
0,7g (IEC/EN 60068-2-6)
Dati d’impiego UL
600V~ fase-fase
347V~ fase-neutro
Isolamento
Campo di misura
20 - 830V~ fase-fase
10 - 480V~ fase-neutro
Tensione nominale di tenuta a impulso Uimp
9,5kV
Tensione di tenuta a frequenza d’esercizio
5,2kV
Campo di frequenza
45 - 66Hz
Connessioni circuito alimentazione/misura tensioni
Tipo di misura
Vero valore efficace (TRMS)
Tipo di morsetti
A vite (estraibili)
Modalità di collegamento
Linea monofase, bifase, trifase con o senza neutro e
trifase bilanciato
N° morsetti
4 per controllo tensione
2 per alimentazione
Frequenza
45 - 66Hz
Potenza assorbita/dissipata
3,9VA 3,4W max
Tempo di immunità alla microinterruzione
≥50ms
Ingressi voltmetrici
Tipo di ingresso
Tensione nominale Ue max
Trifase + neutro
Ingressi amperometrici
Tensione nominale d’isolamento Ui
690V~
Sezione conduttori (min...max)
0,2...2,5 mm2 (24...12 AWG)
Corrente nominale Ie
5A~
Coppia di serraggio morsetti
0,5 Nm (4,5 lbin)
Campo di misura
0,010 - 6A~
Connessioni circuito misura correnti
Tipo di ingresso
Shunt alimentati mediante trasformatore di corrente
esterno (bassa tensione) 5A max.
Tipo di morsetti
A vite (fissi)
N° morsetti
6 per connessioni TA esterni
Sezione conduttori (min...max)
0,2...4 mmq (26...10 AWG)
Coppia di serraggio morsetti
0,8 Nm (7 lbin)
Tipo di misura
Limite termico permanente
Limite termico di breve durata
Autoconsumo (per fase)
Valore efficace (RMS)
+20% Ie
50A per 1 secondo
≤ 0,6W
Contenitore
Materiale
Poliammide RAL 7035
Esecuzione
Da incasso secondo IEC 61554
Grado di protezione
IP54 frontale
IP20 contenitore e morsetti
Peso
480g
Accuratezza
Condizioni di misura
Temperatura
+23°C ±2°C
Tensione di fase
± 0,5% (50…480V~) ±0,5 digit
Tensione concatenata
± 0,5% (80…830V~) ±0,5 digit
Corrente
± 0,5% (0,1…1,2In) ±0,5 digit
Energia attiva
Classe 1 (IEC/EN 62053-21)
Energia reattiva
Omologazioni e conformità
Omologazioni
cULus
Classe 2 (IEC/EN 62053-23)
UL marking
Circuito alimentazione/misura tensioni:
0,05%/°K per V, A, W
Circuito misura correnti:
Use 60°C/75°C copper (Cu) conductor only
AWG Range: 24 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 4.5lb.in
AWG Range: 26 - 10 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 7lb.in
“For use on a flat surface of a Type 1 Enclosure”
Errori addizionali
Temperatura
Conformi a norme
IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/ EN 61000-6-4,
UL508, CSA C22.2 N°14
∂ Alimentazione ausiliaria prelevata da un sistema con tensione fase-neutro ≤300V.
32
I
TAC
I
– Ripetere l’operazione per le quattro clips.
– Nel caso si renda necessario smontare l’apparecchio, sollevare l’aletta centrale delle clips in modo da liberare il millerighe, quindi farle scorrere indietro sulle
guide fino a sfilarle.
– Per i collegamenti elettrici fare riferimento agli schemi di connessione riportati nell’apposito capitolo e alle prescrizioni riportate nella tabella delle
caratteristiche tecniche.
– Una volta terminata i collegamenti elettrici, è possibile posizionare i coprimorsetti in dotazione. Questi coprimorsetti sono sigillabili, impedendo la
manomissione dello strumento e l’accesso ai morsetti di collegamento.
– Per montare i coprimorsetti inserire i ganci nell’apposita sede ed esercitare una lieve pressione fino a che si agganciano. Attenzione all’abbinamento fra la
morsettiera ed il relativo coprimorsetto.
– Il blocco si ottiene inserendo l’apposito filo e sigillo nell’occhiello ricavato agli angoli esterni del coprimorsetto.
DISPOSIZIONE MORSETTI
DIMENSIONI MECCANICHE
53.2
99.5
96
19
92
92
96
31100124
I271 I GB F E 01 13
INSTALLAZIONE
– DMG700 è destinato al montaggio da incasso secondo IEC 61554.
– Inserire il multimetro nel foro del pannello dalla parte frontale, accertandosi che la guarnizione sia posizionata correttamente fra il pannello e la cornice dello
strumento.
– Dall’interno del quadro, per ciascuna delle quattro clips di fissaggio, posizionare la clip in una delle due guide laterali, premendo successivamente sullo
spigolo della clip in modo da agganciare a scatto anche la seconda guida.
– Spingere la clip in avanti facendo pressione sulle sue pareti laterali e facendole scorrere sulle guide fino che le apposite alette deformabili premono al
massimo possibile contro la superficie interna del pannello.
61.5
33
31100124
SCHEMI DI CONNESSIONE
Connessione trifase con o senza neutro
P01.07 = L1-L2-L3-N L1-L2-L3
Connessione bifase
P01.07 = L1-N-L2
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
I271 I GB F E 01 13
N
CT2
L
O
A
D
L2
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
-A1
CURRENT
VOLTAGE
+
A2
AUX SUPPLY
Connessione monofase
P01.07 = L1-N
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
VOLTAGE
Connessione trifase bilanciata con o senza neutro
P01.07 = L1-L2-L3-N-BIL L1-L2-L3-BIL
CT1
I
CT1
L1
L1
L
O
A
D
N
L
O
A
D
L2
L3
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I2
I3
I1
VOLTAGE
CURRENT
--
+
A1
A2
AUX SUPPLY
Connessione ARON 3 fasi senza neutro
P01.07 = L1-L2-L3
V1 V2 V3 VN
L
O
A
D
CT2
L3
I3
L1
L2
CT3
L3
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
-A1
CURRENT
+
A2
AUX SUPPLY
Connessione trifase con neutro mediante TV
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3-N
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
CURRENT
Connessione trifase senza neutro mediante TV
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
CT2
L2
CT3
L3
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
TV
V1 V2 V3 VN
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
NOTE
1. Fusibili raccomandati: Alimentazione ausiliaria e ingresso misura tensione: F1A (rapido)
2. I morsetti S2 sono internamente connessi fra di loro.
34
L
O
A
D
100...440VAC
110...250VDC
100...440VAC
110...250VDC
AUX SUPPLY
S1 S2
I2
CURRENT
CT1
CT1
L2
+
A2
S1 S2
I1
Connessione ARON 3 fasi senza neutro
P01.07 = L1-L2-L3
L1
-A1
S1 S2
VOLTAGE
--
A1
+
TV
V1 V2 V3 VN
A2
AUX SUPPLY
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
L
O
A
D
31100124
F MULTIMETRE NUMERIQUE
I271 I GB F E 01 13
LOVATO ELECTRIC S.P.A.
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. 035 4282111
FAX (Nazionale): 035 4282200
FAX (International): +39 035 4282400
E-mail [email protected]
Web www.LovatoElectric.com
DMG700
D
Available in German at www.LovatoElectric.com/I271D.pdf
CZ
Available in Czech at www.LovatoElectric.com/I271CZ.pdf
PL
Available in Polish at www.LovatoElectric.com/I271PL.pdf
RU
Available in Russian at www.LovatoElectric.com/I271RU.pdf
ATTENTION !
– Lire attentivement le manuel avant l’installation ou toute l’utilisation.
– Ces appareils doivent être installés par un personnel qualifié en respectant les normes en vigueur relatives aux installations pour éviter tout risque pour le
personnel et le matériel.
– Avant toute intervention sur l’appareil, couper ses entrées de mesure et l’alimentation auxiliaire de l’appareil et court-circuiter le secondaire des
transformateurs de courant.
– Le fabricant ne peut être tenu responsable de la sûreté électrique en cas de mauvaise utilisation de l’appareil.
– Les produits décrits dans cette publication peuvent à tout moment être susceptibles d’évolutions ou de modifications. Les descriptions et les données y
figurant ne peuvent en conséquence revêtir aucune valeur contractuelle.
– Dans l’installation électrique de l’édifice, il faut prévoir un interrupteur magnétothermique, situé à proximité de l’appareil et d’accès facile. Il doit être marqué
comme le dispositif de sectionnement de l’appareil :
IEC/EN 61010-1§ 6.11.2.
– Nettoyer l’appareil avec un tissu propre et ne pas employer les produits abrasifs, les détergents liquides ou les dissolvants.
SOMMAIRE
PAGE
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Fonction des touches avant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Affichage des mesures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36
Tableau des pages de l’afficheur . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Navigation entre les pages de l’afficheur . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Page compteurs d’énergie . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Page compteur d’heures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Page graphique de tendance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Page compteurs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Pages utilisateur. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
Menu principal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Accès par mot de passe . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Verrouillage des paramétrages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
Extensibilité . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Ressources additionnelles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Canaux de communication . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40
Entrées, sorties, variables internes, compteurs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Seuils limite . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Logique booléenne . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Variable à distance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 41
Alarmes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Tarifs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Réglage des paramètres (set-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 42
Tableau des paramètres . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Menu Commandes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
Test de connexion. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 48
Caractéristiques techniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 49
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Disposition des bornes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Dimensions mécaniques . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50
Schémas de connexion . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51
INTRODUCTION
Le multimètre DMG700 a été projeté pour unir la plus grande simplicité d’emploi à un large choix de fonctions avancées. Dans l’exécution à montage sur
panneau de taille standard 96x96mm, le DMG700 associe le design moderne de la partie avant à la praticité de montage et à la possibilité d’extension à l’arrière
où vous pouvez insérer des modules de la série EXP.
L’afficheur graphique rétroéclairé LCD présente une interface utilisateur claire et intuitive. Grâce à la grande quantité de fonctions disponibles, les multimètres de
la série DMG sont la solution idéale pour un très large domaine d’application.
35
F
31100124
I271 I GB F E 01 13
DESCRIPTION
– Exécution à encastrer 96x96mm.
– Afficheur LCD graphique, 128x80 pixels, rétroéclairé, 4 niveaux de gris.
– 4 touches d’affichage et de paramétrage.
– Navigation rapide et simple.
– Compatible avec les réseaux BT, MT et AT.
– Textes pour mesures, paramétrages et messages dans 5 langues.
– Plus de 160 grandeurs électriques mesurées.
– Bus d’extension pour max 4 modules plug-in série EXP.
– Fonctions avancées d’E/S programmables.
– Mesures en valeur efficace vraie (TRMS).
– Saisie continue (gapless).
– Précision élevée.
– Couvre-bornes plombables.
– Verrouillage des paramétrages à l’aide d’un interrupteur plombable.
FONCTION DES TOUCHES FRONTALES
Touche MENU - Elle permet d’entrer et de quitter les menus d’affichage et de programmation.
Touches s et t - Elles permettent de parcourir les pages-écrans, de sélectionner les différentes options affichées et de modifier les paramètres
(augmenter/réduire).
Touche
- Elle permet de parcourir les sous-pages, de confirmer un choix effectué et de passer d’un mode d’affichage à l’autre.
AFFICHAGE DES MESURES
– Les touches s et t permettent de faire défiler les pages d’affichage des mesures une par une. Le nom de la page courante apparaît dans la barre de titre.
– Certaines mesures pourraient ne pas être affichées selon la programmation et le type de branchement de l’appareil (par exemple, s’il est programmé pour un
système sans neutre, les mesures se référant au neutre ne sont pas affichées).
– Dans chaque page, la touche
permet d’accéder aux sous-pages (par exemple pour afficher les valeurs maximum et minimum enregistrées pour la
mesure sélectionnée).
– La sous-page courante est indiquée en bas à gauche par l’une des icônes suivantes :
• IN = Valeur instantanée - Valeur instantanée actuelle de la mesure, affichée par défaut chaque fois que vous changez de page.
• HI = Valeur maximum instantanée - Valeur la plus élevée mesurée par le multimètre pour la mesure relative. Les valeurs HIGH sont enregistrées et
maintenues même en cas de coupure de courant. Vous pouvez les remettre à zéro à l’aide de la commande appropriée (voir menu Commandes).
• LO = Valeur minimum instantanée - Valeur la plus basse mesurée par le multimètre dès la mise sous tension. Vous pouvez la remettre à zéro à l’aide de la
commande utilisée pour les valeurs HI.
• AV = Valeur intégrée - Valeur de la mesure intégrée (moyennée) au cours du temps. Elle permet de voir une mesure avec des variations lentes. Voir le
menu Intégration.
• MD = Valeur maximum intégrée - Valeur maximum de la valeur intégrée (demande maximum). Elle reste enregistrée dans la mémoire rémanente ; vous
pouvez la remettre à zéro à l’aide d’une commande appropriée.
• GR = Barres graphiques - Affichage des mesures à l’aide de barres graphiques.
Exemple de page avec indications numériques
1 - Unité de mesure
2 - Mesure
3 - Titre de page
4 - Indication de phase
5 - Icônes d’état
Exemple de page graphique à barres
1 - Unité de mesure
2 - Mesure
3 - Indication de phase
4 - Indicateurs HI-LO
– Vous pouvez spécifier sur quelle page et quelle sous-page l’afficheur doit revenir automatiquement après un délai durant lequel aucune touche n’est enfoncée.
– Vous pouvez aussi programmer le multimètre de sorte que l’affichage reste sur la dernière position courante.
– Pour définir ces fonctions, voir le menu M02 – Utilitaire.
36
F
31100124
TABLE DES PAGES DE L’AFFICHEUR
I271 I GB F E 01 13
Selection avec s et t
Selection avec
N°
PAGE
1
TENSIONS PHASE-PHASE - V(L1-L2), V(L2-L3), V(L3-L1), V(LL)EQV
HI
LO
SOUS-PAGE
AV
2
TENSIONS DE PHASE - V(L1-N), V(L2-N), V(L3-N), V(L-N)EQV
HI
LO
AV
3
COURANTS DE PHASE ET DE NEUTRE - I(L1), I(L2), I(L3), I(N)
HI
LO
AV
MD
GR
4
PUISSANCE ACTIVE - P(L1), P(L2), P(L3), P(TOT)
HI
LO
AV
MD
GR
5
PUISSANCE REACTIVE - Q(L1), Q(L2), Q(L3), Q(TOT)
HI
LO
AV
MD
GR
6
PUISSANCE APPARENTE - S(L1), S(L2), S(L3), S(TOT)
HI
LO
AV
MD
7
FACTEUR DE PUISSANCE - PF(L1), PF(L2), PF(L3), PF(EQ)
HI
LO
AV
8
FREQUENCE - ASYMETRIE - F, ASY(VLL), ASY(VLN), ASY(I)
HI
LO
AV
9
DISTORTION HARMONIQUE TENSIONS L-L - THD-V(L1-L2), THD-V(L2-L3), THD-V(L3-L1)
HI
LO
AV
GR
10
DISTORTION HARMONIQUE TENSIONS L-N - THD-V(L1), THD-V(L2), THD-V(L3)
HI
LO
AV
GR
11
CDISTORTION HARMONIQUE COURANT - THD-I(L1), THD-I(L2) THD-I(L3)
HI
LO
AV
GR
12
COMPTEURS D’ENERGIE - kWh+(TOT), kWh-(TOT), kvarh+(TOT), kvarh-(TOT), kVA(TOT)
13
TARIFICATION ENERGIE
14
GRAPHE A TENDANCE
15
COMPTEUR HORAIRE - Hr(TOT), Hr(Partial)
16
MODULES D’EXTENSION
17
18
GR
GR
GR
GR
PARTIAL
TAR1
...
TAR4
COMPTEURS
CNT1
...
CNT4
SEUILS DE LIMITE
LIM1
...
LIM8
19
LOGIQUE BOOLE
BOO1
...
BOO8
20
ALARMES
ALA1
...
ALA8
21
IINFO-REVISIONS-MATRICULE
MODEL, REV SW, REV HW, Nº SERIES / TEMPERATURE INTERNE
22
LOGO
23
(PAGE UTILITAIRE 1)
24
(PAGE UTILITAIRE 2)
25
(PAGE UTILITAIRE 3)
26
(PAGE UTILITAIRE 4)
F
NOTA: Certaines pages listées ci-dessus ne pourront pas être disponibles si la fonction qu’elles doivent afficher n’est pas activée. Par exemple, si aucune alarme
n’a été défini, alors la page d’alarme ne sera pas visualisée.
NAVIGATION SUR LES PAGES DE L’AFFICHEUR
Tensions phase-phase
IN = Valeur instantanée
HI = Valeur maxi
LO = Valeur mini
AV = Valeur moyenne
GR = Graphiques à barres
HI = Valeur maxi
LO = Valeur mini
AV = Valeur moyenne
GR = Graphiques à barres
HI = Valeur maxi
LO = Valeur mini
AV = Valeur moyenne
MD = Max demand
Tensions de phase
IN = Valeur instantanée
Courant de phase et neutre
IN = Valeur instantanée
(suite)
37
31100124
PAGE COMPTEURS D’ENERGIE
– Cette page affiche simultanément :
• l’énergie active importée et exportée
• l’énergie réactive importée et exportée (inductive/capacitive)
• l’énergie apparente.
– La page principale affiche les compteurs totaux. La touche
permet d’accéder à la sous-page des compteurs partiels (que vous pouvez remettre à zéro).
– Pour remettre à zéro les compteurs, accédez au menu Commandes.
I271 I GB F E 01 13
1 - Indication Total/Partiel
PAGE COMPTEUR HORAIRE
– Cette page affiche :
• le décompte des heures total (il compte le temps d’alimentation de l’appareil)
• le décompte des heures partiel (il compte le temps durant lequel une condition programmable se vérifie)
– Pour remettre à zéro ces compteurs, accédez au menu Commandes.
– Vous pouvez désactiver complètement cette page en prédisposant l’activation générale du compteur d’heures sur OFF (voir le menu Compteur horaire).
PAGE GRAPHIQUE DE TENDANCE
– Cette page permet d’afficher un graphique indiquant la progression au cours du temps d’une mesure définie par l’utilisateur que vous pouvez sélectionner
parmi :
• tension équivalente intégrée
• puissance active totale intégrée
• puissance réactive totale intégrée
• puissance apparente totale intégrée.
– Par défaut, l’appareil affiche la puissance active totale intégrée. Pour modifier l’affichage, utilisez le paramètre approprié du menu Tendance.
– Sur le graphique, vous pouvez représenter les 96 dernières valeurs de la mesure intégrée dont chacune correspond à un intervalle de temps d’intégration.
– L’intervalle de temps par défaut est 15 minutes, de sorte que le graphique puisse afficher la progression de la mesure sélectionnée dans les dernières 24
heures.
– Avec les paramètres d’usine, le graphique affiche donc la progression des consommations de puissance active des dernières 24 heures.
– Les données des consommations sont remises à zéro quand vous éteignez l’appareil ou quand vous agissez sur le menu de programmation.
– Quand la capacité maximum d’affichage est dépassée, les nouvelles données remplacent les plus vieilles, selon une logique de mémorisation en boucle.
– Le fond d’échelle verticale est calculé automatiquement en fonction des données assignées insérées dans le menu M01 - Général.
1 - Echelle des temps.
Indique le temps dans le passé les
mesures se rapportent.
2 - Echelle verticale.
Peut être automatique ou fixe.
3 - Mesure visualisée
PAGE COMPTEURS
– La page compteurs affiche les décomptes CNT1…4.
– Vous pouvez compter le nombre de fois qu’une entrée est activée ou quand une limite est dépassée, etc. La condition est définie par les paramètres Source
décompte.
– Pour chaque compteur, vous pouvez définir une description et une unité de mesure à l’aide d’un texte libre, p. ex. litres, m3, etc.
– Vous pouvez par ailleurs définir un coefficient de conversion entre le nombre d’impulsions comptées et la mesure inscrite sur l’afficheur. Pour ce faire,
spécifiez un coefficient multiplicatif et un fractionnaire. Par exemple, si vous définissez k multiplicatif = 3, pour chaque impulsion lue, la valeur indiquée sur
l’écran sera multipliée par 3. En revanche, si vous programmez un coefficient fractionnaire = 10, la mesure affichée sera augmentée seulement après 10
impulsions appliquées à l’entrée. Avec la combinaison de k multiplicatif et fractionnaire, vous pouvez obtenir un rapport de conversion quelconque.
– Si le compteur n’a aucun coefficient fractionnaire, l’affichage présentera seulement des nombres entiers. Sinon, il y a deux chiffres décimaux.
– Vous pouvez remettre à zéro les compteurs à l’aide du menu Commandes ou en définissant les paramètres appropriés du signal Source RAZ.
1 - Unité de mesure (personnalisable) du compteur
2 - Comptage
3 - Description (personnalisable) du compteur
4 - Nombre du compteur choisi
PAGES UTILISATEURS
– Vous pouvez créer un nombre maximum de
4 pages personnalisées.
– Ces pages peuvent contenir 4 mesures chacune choisies librement parmi celles disponibles sur le DMG700.
– Vous pouvez librement nommer la page en indiquant par exemple la partie de l’installation servie par le multimètre.
– Vous pouvez accéder facilement aux pages utilisateur à partir de la première page en enfonçant la touche s.
– Comme toutes les autres pages, vous pouvez programmer le multimètre pour positionner l’afficheur sur l’une des pages utilisateur après un délai durant
lequel aucune touche n’est enfoncée
– Pour la définition des pages utilisateur, voir le menu M15 dans le chapitre Réglage des paramètres.
38
F
31100124
I271 I GB F E 01 13
MENU PRINCIPAL
– Le menu principal comprend des icônes d’état graphiques (raccourcis) qui permettent un accès rapide aux mesures et réglages.
– A partir de la visualisation normale, appuyez sur la touche MENU et le menu s’affiche.
– Appuyez sur s ou t pour sélectionner la fonction requise. L’icône sélectionnée est mis en évidence et la description de la fonction vient visualisée sur l’afficheur.
– Appuyez sur
pour actionner la fonction choisie.
– Si certains fonctions ne sont pas disponibles, l’icône correspondant sera désactivé et sera visualisé en couleur gris clair.
–
etc - Ces raccourcis qui permettent l’accès rapide aux pages de visualisation mesures et de passer rapidement à la
primaire page du groupe de mesures choisi. Il est toujours possible déplacer en avant ou en arrière comme d’habitude.
–
- Permet d’ouvrir la page de mot de passe où il est possible insérer le code numérique qui débloque les fonctions protégées (réglage des paramètres,
exécuter des commandes).
–
- Point d’accès au réglage des paramètres (set-up). Consultez la section dédiée.
–
- Point d’accès au menu commandes, où l’utilisateur autorisé peut exécuter un certain nombre d’opérations de mettre à zéro ou réinitialiser.
1 - Visualisation tensions
7 - Graphique à tendance
2 - Visualisation courants
8 - Visualisation compteur horaire
3 - Visualisation puissances
9 - Modules d’extension
4 - Fréquence - asymétrie
10 - Réglages (Set-up)
5 - Analyse harmonique
11 - Menu commandes
6 - Computeurs energie
12 - Insérer mot de passe
ACCÉS PAR MOT DE PASSE
– Le mot de passe est utilisé pour activer ou verrouiller l’accès au menu réglage (set-up) et menu commandes.
– Pour les nouveaux appareils (par défaut ), la gestion de mot de passe est désactivé et l’accès est libre.
Au contraire, si les mots de passe ont été activés et définis, puis à obtenir l’accès, il est nécessaire d’entrer le code d’accès numérique.
– Pour activer la gestion des mots de passe et de définir les code numériques, consulter la section réglage des paramètres (set-up).
– Il y a deux niveaux d’accès, selon le code validé:
• Accès niveau utilisateur - permet la remise à zéro des valeurs enregistrées mais pas les réglages de l’appareil.
• Accès niveau avancé - les mêmes droits de l’utilisateur et aussi la possibilité de changer les réglages.
– Lors de l’affichage des mesures, appuyez sur MENU pour rappeler le menu principal, sélectionner l’icône mot de passe et appuyez sur
– La fenêtre saisir mot de passe est affichée comme de suite:
F
.
Les touches s t changent le chiffre du code chiosi.
Le touche
confirme le chiffre et se déplace au suivant.
Saisissez le mot de passe, puis déplacez sur l’icône de clé.
Si le mot de passe saisi correspond au mot de niveau utilisateur ou niveau avancé, le message de déblocage est visualisé.
Après le déblocage, l’accès reste active jusqu’au:
• L’appareil est hors alimenté.
• L’appareil est réinitialisé (après avoir quitté le menu réglages).
• Le délai d’interruption de session de deux minutes s’écoule sans aucune activation des touches.
– On quitte l’affichage du mot de passe en appuyant sur la touche MENU.
–
–
–
–
–
VERROUILLAGE DES PARAMÉTRAGES
– Le DMG700 est pourvu de deux micro-interrupteurs permettant de bloquer l’accès aux paramétrages et aux opérations de réinitialisation (menu Commandes).
– Ces micro-interrupteurs sont positionnés de sorte à être inaccessibles quand les cache-bornes plombables sont montés.
– Pour positionner les micro-interrupteurs :
• couper le courant au DMG700, puis retirez les deux couvre-bornes (s’ils sont montés) et le bornier extractible à 8 pôles
• à l’aide d’un petit tournevis à lame plate, positionnez les micro-interrupteurs dans la configuration voulue.
• remettez en place le borniers et les cache-bornes.
– L’appareil est fourni avec les micro-interrupteurs configurés en position d’accès autorisé.
SW
POS
SW1
OFF
Accès aux paramètres admis
ON
Accès aux paramètres bloqué
SW2
DESCRIPTION
OFF
Accès au menu Commandes admis
ON
Accès au menu Commandes bloqué
39
31100124
I271 I GB F E 01 13
EXTENSIBILITE
– Grâce à son bus d’extension, le DMG700 peut être étendu avec des modules additionnels de la série EXP…
– Vous pouvez brancher au maximum 4 modules EXP à un DMG700.
– Les modules EXP supportés par le DMG700 sont partagés en catégories :
• modules de communication
• modules d’E/S numérique
– Pour insérer un module d’extension :
• mettez le DMG700 hors tension
• retirez le couvre-borne et le bornier extractible à 8 pôles
• retirez l’un des couvercles de protection des emplacements d’extension.
• Insérez le crochet supérieur du module dans la fente appropriée
• tournez le module vers le bas en insérant le connecteur sur le bus
• enfoncez jusqu’à ce que s’enclenche la patte située au bas du module
• Remettez en place le bornier et le couvre-borne.
– L’ordre d’insertion des modules est libre.
1
2
3
4
CLICK!
F
ATTENTION !
Quand vous installez des modules EXP sur des multimètres de la série DMG, vous devez obligatoirement monter les cache-bornes plombables fournis avec le
multimètre.
– Quand un DMG700 est mis sous tension, il reconnaît automatiquement les modules EXP qui y sont reliés.
– Si la configuration du système est différente par rapport à la dernière configuration relevée (un module a été ajouté ou retiré), l’unité de base vous demande
de confirmer la nouvelle configuration. Si vous la confirmez, elle sera enregistrée et deviendra effective, sinon l’incohérence sera signalée à chaque mise sous
tension.
– La configuration actuelle du système apparaît dans la page relative (modules d’extension) qui indique le numéro, le type et l’état des modules reliés.
– La numérotation des E/S est indiquée sous chaque module.
– L’état (activé/désactivé) des E/S et des canaux de communication est mis en surbrillance.
1 - Nb et état de voie de communication
2 - Type des modules d’extension
3 - Numération et état des E/S
RESSOURCES ADDITIVES
– Les modules d’extension fournissent des ressources additionnelles que vous pouvez utiliser à l’aide des menus de programmation.
– Les menus de programmation concernant les extensions sont disponibles même si les modules ne sont pas présents physiquement.
– Comme vous pouvez ajouter plusieurs modules du même type (par exemple deux interfaces de communication), les menus de programmation relatifs sont
multiples, identifiés par un numéro progressif.
– Le tableau suivant indique combien de modules de chaque type vous pouvez monter simultanément.
TYPE DE MODULE
REF
FONCTION
Nb MAXI
COMMUNICATION
EXP10 10
USB
2
EXP10 11
RS232
E/S NUMERIQUES
EXP10 12
RS485
EXP10 00
4 ENTREES
EXP10 01
4 SORTIES STATIQUES
2
EXP10 02
2 ENTREES +
2 ST. OUTPUTS
4
EXP10 03
2 RELAIS
4
2
CANAUX DE COMMUNICATION
– Au DMG700, vous pouvez brancher au maximum 2 modules de communication, nommés COMn. Le menu Communications M07 prévoit donc deux sections
(n=1 et n=2) de paramètres pour prédisposer les ports de communication.
– Les canaux de communication sont complètement indépendants, aussi bien du point de vue matériel (type d’interface physique) que du protocole de
communication.
– Les canaux de communication peuvent fonctionner simultanément.
40
31100124
I271 I GB F E 01 13
ENTREES, SORTIES, VARIABLES INTERNES, COMPTEURS
– Les entrées et les sorties numériques fournies par les modules d’extension sont identifiées par un sigle et un numéro progressif. Par exemple, les entrées
numériques sont nommées INPx, où x représente le numéro de l’entrée, tandis que les sorties numériques sont nommées OUTx.
– La numérotation des entrées/sorties se base simplement sur la position de montage des modules d’extension, avec une numérotation progressive de gauche
à droite. Par exemple, l’entrée INP1 est la première borne d’entrée du module la plus à gauche tandis que les bornes suivantes seront, de gauche à droite,
INP2, INP3 etc.
– Pour le DMG700 , on a prévu au maximum 8 entrées numériques et 8 sorties, qui seront donc nommées INP1…INP8 et OUT1…OUT8. Pour chaque E/S, il
existe un menu de programmation permettant de spécifier sa fonction et ses propriétés.
– Comme pour les entrées/sorties, il existe des variables internes (bits) qui peuvent être associées aux sorties ou entre elles. Par exemple, vous pouvez
appliquer des seuils limite aux mesures effectuées par le multimètre (tension, courant, etc.). Ainsi la variable interne nommée LIMx sera activée quand la
mesure dépassera les limites que vous aurez définies dans le menu de programmation.
– Pour finir, vous pouvez gérer jusqu’à 4 compteurs (CNT1..CNT4) pouvant compter des impulsions venant de l’extérieur (donc d’entrées INPx) ou bien le
nombre de fois où se vérifie une condition déterminée. Par exemple, si vous définissez le seuil LIMx comme source de décompte, vous pourrez savoir
combien de fois une mesure a dépassé une certaine valeur.
– Le tableau ci-dessous montre toutes les E/S et les variables internes gérées par le DMG700.
Cod.
DESCRIPTION
INPx
Entrées numériques
Range (x)
1...8
OUTx
Sorties numériques
1...8
LIMx
Seuils de limite
1...8
BOOx
Logique Boole
1...8
REMx
Variables à commande à distance
1...8
ALAx
Alarmes
1...8
PULx
Impulsion de comptage énergie
1...5
CNTx
Compteurs
1...4
– L’état de chaque E / S ou variable interne peut être visualisé à la page d’état E/S.
SEUILS DE LIMITE (LIM)
– Les seuils limite LIMn sont des variables internes dont l’état dépend du dépassement des limites définies par l’utilisateur de la part d’une mesure parmi celles
effectuées par le multimètre (exemple : puissance active totale supérieure à 25kW).
– Pour accélérer la programmation des seuils, dont la plage peut être très vaste, il faut définir chacune d’entre elles avec une valeur base + un coefficient
multiplicatif (exemple : 25 x 1k = 25000).
– Pour chaque LIM, deux seuils sont disponibles (supérieur et inférieur). Le seuil supérieur doit avoir une valeur plus grande que le seuil inférieur.
– Le sens des seuils dépend des fonctions suivantes :
Fonction Min : avec la fonction Min, le seuil inférieur est celui de déclenchement tandis que le seuil supérieur est celui de rétablissement. Quand la valeur de
la mesure sélectionnée est au-dessous de la limite inférieure, le seuil s’active au terme du retard. Quand la valeur de la mesure dépasse le seuil supérieur,
celle-ci est rétablie au terme du retard.
Fonction Max : avec la fonction Max, le seuil supérieur est celui de déclenchement tandis que le seuil inférieur est celui de rétablissement. Quand la valeur de
la mesure sélectionnée dépasse le seuil supérieur, celui-ci s’active au terme du retard. Quand la valeur de la mesure est inférieure au seuil inférieur, celle-ci
est rétablie au terme du retard.
Fonction Min+Max : avec la fonction Min+Max, les seuils inférieur et supérieur sont tous deux de déclenchement. Quand la valeur de la mesure sélectionnée
est inférieure au seuil inférieur ou supérieure au seuil supérieur, au terme des retards respectifs, la sortie déclenche. Quand la valeur respecte les limites, le
rétablissement est immédiat.
– Le déclenchement peut signifier excitation ou désexcitation de la limite LIMn selon le réglage.
– Si la limite est définie avec une mémoire, le rétablissement est manuel et il peut être effectué à l’aide de la commande appropriée du menu Commandes.
– Voir le menu de programmation M08.
1 - Etat variable imite
2 - Valeur de mesure
3 - Fonction
4 - Type de mesure
5 - Seuil haut
6 - Retard au seuil
7 - Seuil bas
LOGIQUE BOOLE (BOO)
– Vous pouvez créer 8 variables internes au maximum nommées BOO1…8 dont l’état dépend de la combinaison logique booléenne de seuils limite, entrées,
sorties etc.
– Les opérandes (INP, LIM etc.) peuvent être associés entre eux avec les opérations logiques booléennes suivantes : AND, OR, EXOR, AND NOT, OR NOT,
EXOR NOT.
– Chaque variable Booléenne est le résultat de la combinaison de 4 opérandes au maximum liés entre eux par des opérations logiques.
– Exemple : si vous voulez que la variable BOO1 soit activée quand les limites LIM2, LIM3 et LIM4 sont activées ou quand l’entrée INP1 est activée, vous devez
programmer BOO1 comme la combinaison de LIM2 AND LIM3 AND LIM4 OR INP1.
– Il n’est pas nécessaire d’utiliser les
4 opérandes pour une combinaison logique. Par exemple, si vous voulez que BOO2 seulement soit activé quand INP1 ou INP2 est activé, vous pouvez
programmer les paramètres de BOO2 avec la combinaison INP1 OR INP2, en laissant les opérations logiques suivantes définies sur --- (aucune opération).
– La page LOGIQUE BOOLEENE affiche, pour chaque variable BOO1..8, l’état de chaque opérande impliqué dans l’opération logique et le résultat final, c’est-àdire l’état de la variable booléenne sélectionnée.
1 - Opérande 1
2 - Opération logique 1
3 - Opérande 2
4 - Etat opérande 1
5 - Résultat de l’état variable booléenne
VARIABLES A DISTANCE (REM)
– DMG700 peut gérer jusqu’à 8 variables commandées à distance (REM1…REM8).
– Il s’agit de variables que vous pouvez modifier à votre gré à travers le protocole de communication et que vous pouvez associer aux sorties, à la logique
booléenne, etc.
– Exemple : si vous utilisez une variable à distance (REMx) comme source de sortie (OUTx), vous pourrez activer et désactiver librement un relais à l’aide du
logiciel de supervision. Vous pourrez ainsi utiliser les relais de sortie du DMG700 pour commander des charges par exemple éclairage ou autre.
– Une autre utilisation des variables REM est d’activer ou désactiver certaines fonctions à distance en les insérant dans une logique booléenne en AND avec
des entrées et des sorties.
41
F
31100124
I271 I GB F E 01 13
ALARMES (ALA)
– Vous pouvez définir jusqu’à 8 alarmes programmables (ALA1…ALA8).
– Pour chaque alarme, vous pouvez établir la source c’est-à-dire la condition qui engendre l’alarme et le texte du message qui doit apparaître sur l’afficheur
quand cette condition se vérifie.
– La condition qui engendre l’alarme peut être, par exemple, le dépassement d’un seuil. Dans ce cas, la source sera l’un des seuils limite LIMx.
– En revanche, si l’alarme doit s’afficher après l’activation d’une entrée numérique externe, la source sera alors INPx.
– Avec le même critère, vous pouvez aussi associer à une alarme des conditions complexes résultant de la combinaison logique booléenne d’entrées, seuils,
etc. Dans ce cas, vous utiliserez les variables booléennes BOOx.
– Pour chaque alarme, vous pouvez définir un message librement programmable qui apparaîtra dans la page d’état des alarmes.
– Vous pouvez aussi définir une priorité d’alarme. S’il s’agit d’une simple indication, alors la priorité peut être définie comme basse. Dans ce cas, l’icône qui
accompagne l’alarme sera l’icône d’information.
– En revanche, si l’alarme doit indiquer une situation plus importante, en définissant une priorité élevée, le message sera affiché avec l’icône d’attention et
quand l’alarme se vérifiera, la page d’affichage des alarmes apparaîtra automatiquement sur l’afficheur.
– En cas de présence simultanée de plusieurs alarmes, elles sont affichées à rotation et leur nombre total apparaît sur l’afficheur.
– Pour réarmer une alarme qui a été programmée avec la mémoire, utilisez la commande appropriée du menu Commandes.
– Pour définir des alarmes, voir le menu de programmation M09.
1 - Nombre d’alarme / total d’alarmes
TARIFS
– Pour le décompte de l’énergie, le DMG700 peut gérer 4 tarifs indépendants outre les tarifs total et partiel.
– La sélection des tarifs se produit à travers les entrées numériques externes, elle est donc conditionnée à l’installation d’un module d’extension EXP pourvu
d’entrées numériques. Pour sélectionner les 4 tarifs, vous disposez des deux fonctions d’entrée TAR-A et TAR-B. Leur combinaison binaire effectue la
sélection comme indiqué dans le tableau :
TAR-A
TAR-B
TARIF
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
– Si vous utilisez l’entrée de synchronisme pour l’intervalle d’intégration, alors le changement de tarif sera effectué en même temps que le synchronisme, sinon
le changement de tarif se produit lors du changement de configuration des entrées.
– Les décomptes des tarifs, chacun avec les
5 compteurs d’énergie (active importée et exportée, réactive importée et exportée, apparente) sont affichés dans une page appropriée, suivant celle des
compteurs totaux et partiels.
– Si le DMG est pourvu d’une interface de communication, vous pouvez sélectionner le tarif actif à l’aide de la commande appropriée sur le protocole Modbus
(voir les instructions techniques du protocole Modbus).
1 - Tarif active
2 - Tarif visualisé
REGLAGES DES PARAMÈTRES (SET-UP)
– En mode d’affichage normal des mesures, enfoncez MENU pour rappeler
le menu principal, sélectionnez l’icône
et enfoncez
pour accéder au menu de programmation.
• La page ci-dessous apparaît avec les sous-menus de programmation où sont regroupés tous les paramètres selon un critère lié à leur fonction.
• Sélectionnez le menu voulu à l’aide des touches s et tpuis confirmez avec .
– Pour quitter la page et revenir à l’affichage des mesures, enfoncez MENU.
42
F
31100124
I271 I GB F E 01 13
– La table suivante indique la liste des sous-menu disponibles.
Code
Sous-Menu
Description
M01
GENERAL
Données caract. l’installation
M02
UTILITE
Langue, luminosité, pages…
M03
MOT DE PASSE
Activation protection accès
M04
INTEGRATION
Temps intégration mesures
M05
COMPTEUR HORAIRE
Activation décompte des heures
M06
GRAPHE DE TENDANCE
Définition mesure et échelle
M07
COMMUNICATION (COMn)
Ports de communication (DMG210)
M08
SEUILS DE LIMITE (LIMn)
Seuils sur les mesures
M09
ALARMES (ALAn)
Messages d’alarme
M10
COMPTEURS (CNTn)
Compteurs généraux
M11
IMPULSIONS (PULn)
Impulsions décompte énergie
M12
LOGIQUE BOOLE (BOOn)
Combinaisons logique booléenne
M13
ENTREES (INPn)
Entrées numériques
M14
SORITES (OUTn)
Sorties numériques
M15
PAGE UTILISATEUR (PAGn)
Pages personnalisées
– Sélectionnez le sous-menu et enfoncez
pour voir tous les paramètres.
– Tous les paramètres sont accompagnés de leur code, description et valeur courante.
1 - Code paramètre
2 - Description paramètre
3 - Valeur courante
4 - Paramètre chiosi
– Pour modifier la valeur d’un paramètre, sélectionnez-le puis enfoncez .
– Si vous ne saisissez pas le mot de passe du niveau Avancé, vous ne pourrez pas accéder à la page de modification et un message d’accès refusé s’affichera.
– En revanche si vous êtes autorisé à l’accès, la page de modification apparaît.
1 - Paramètre sélectionné
2 - Valeur mini possible
3 - Graphique à barre valeur-gamme
4 - Nouvelle valeur programmée
5 - Valeur maxi possible
7 - Valeur de défaut
– Quand vous êtes en mode modification, vous pouvez modifier la valeur à l’aide des touches s et t. Vous verrez aussi une barre graphique indiquant la
plage de réglage, les valeurs minimum et maximum possibles, la valeur précédente et la valeur par défaut.
– Si vous enfoncez simultanément s et t, le paramètre est ramené à la valeur par défaut prédisposée en usine.
déplace le curseur à l’intérieur du texte.
– Pendant la définition d’un texte, les touches s et t permettent de sélectionner un caractère alphanumérique et
En enfonçant simultanément s et t, la sélection alphanumérique se positionne directement sur le caractère ‘A’.
– Enfoncez MENU pour revenir à la sélection des paramètres. La valeur entrée reste mémorisée.
– Enfoncez de nouveau MENU pour enregistrer les changements et quitter le mode programmation. Le multimètre se réinitialise et se met en fonctionnement
normal.
– Si vous n’enfoncez aucune touche pendant
2 minutes consécutives, le menu de définition des paramètres disparaît de l’afficheur et le multimètre revient à l’affichage normal.
TABLE DES PARAMETRES
UdM
Default
Range
P01.01
M01 - GENERAL
Primaire TI
A
5
1-10000
P01.02
CT secondary
A
5
5
P01.03
Tension assignée
V
Aut
Aut / 50-500000
P01.04
Utilisation TP
OFF
OFF-ON
P01.05
Primaire TP
V
100
50-500000
P01.06
Secondaire TP
V
P01.07
Type de connexion
100
50-500
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
L1-N
P01.01 – Courant assigné du primaire des TI.
P01.02 – Courant du secondaire des TI. Fixe à 5A pour DMG700.
P01.03 – Tension assignée de l’installation. En laissant sur Aut, le multimètre ajuste automatiquement l’échelle des barres graphiques.
P01.04 – Programmez-le sur On si vous utilisez des TP. S’il est programmé sur OFF, les deux paramètres suivants sont ignorés.
P01.05 – Tension assignée primaire TP.
P01.06 – Tension assignée secondaire TP.
P01.07 – A définir selon le schéma de connexion utilisé. Voir les schémas de connexion à la fin du manuel.
43
F
31100124
I271 I GB F E 01 13
M02 - UTILITE
Default
Range
English
English
Italiano
Francais
Espanol
Portoguese
%
50
0-100
%
100
0-100
Intensité basse rétroéclairage afficheur
%
30
0-50
P02.05
Temps de passage à rétroéclairage bas
sec
30
5-600
P02.06
Retour à la page par défaut
sec
60
OFF / 10-600
P02.07
Page par défaut
VL-L
VL-L / VL-N ...
P02.08
Sous-page par défaut
INST
INST / HI / LO /
AVG / MD /GRAPH /
1-8
P02.09
Temps de mise à jour afficheur
0.5
0.1 - 5.0
P02.01
Langue
P02.02
Contraste LCD
P02.03
Intensité haute rétroéclairage afficheur
P02.04
UdM
sec
P02.06 – S’il est défini sur OFF, l’afficheur reste toujours sur la dernière page rappelée par l’utilisateur. S’il est défini sur une valeur, au terme du délai indiqué,
l’afficheur revient à la page définie avec P02.07.
P02.07 – Numéro de la page sur laquelle l’afficheur revient automatiquement au terme du délai P02.06 après la dernière pression d’une touche.
P02.08 – Type de sous-page sur laquelle l’afficheur revient au terme du délai P02.06.
M03 - MOT DE PASSE
Default
Range
Utilisation mots de passe
OFF
OFF-ON
P03.02
Mot de passe niveau Utilisateur
1000
0-9999
P03.03
Mot de passe niveau Avancé
2000
0-9999
P03.01
UdM
P03.01 – S’il est défini sur OFF, la gestion des mots de passe est désactivée et l’accès aux paramétrages et au menu Commandes est libre.
P03.02 – Si P03.01 est actif, spécifiez une valeur pour activer l’accès au niveau utilisateur. Voir le chapitre Accès par mot de passe.
P03.03 – Comme P03.02, pour l’accès au niveau Avancé.
M04 - INTEGRATION
Default
Range
Décalage
Fisse / Décalage
Synchr. / Bus
min
15
1-60
min
15
1-60
Temps intégration tensions
min
1
1-60
Temps intégration fréquence
min
1
1-60
P04.01
Mode d’intégration
P04.02
Temps intégration puissances
P04.03
Temps intégration courants
P04.04
P04.05
UdM
P04.01 – Sélection du mode de calcul des mesures intégrées.
Fixe = Les mesures instantanées sont intégrées pendant le temps défini. Au terme de chaque délai, la mesure intégrée est mise à jour avec le résultat de la
dernière intégration.
Décalage = Les mesures instantanées sont intégrées pendant un délai = 1/15 du temps défini. Au terme de chaque délai, la valeur la plus vieille est remplacée
par la nouvelle valeur calculée. La mesure intégrée est mise à jour tous les 1/15 du temps défini, en considérant une fenêtre décalée dans le temps comprenant
les 15 dernières valeurs calculées, de longueur totale équivalent au temps défini.
Synchronisme = Comme pour le mode fixe mais les intervalles d’intégration sont cadencés par une entrée numérique externe programmé avec la fonction
synchronisme.
Bus = Comme le mode fixe mais les intervalles d’intégration sont cadencés par des messages de synchronisme envoyés au bus série.
P04.02 – Temps d’intégration des mesures AVG (moyenne) pour les puissances active, réactive et apparente.
P04.03, P04.04, P04.05 – Temps d’intégration des mesures AVG (moyenne) pour les grandeurs relatives.
Default
Range
P05.01
M05 - COMPTEUR HORAIRE
Activation générale décompte des heures
UdM
ON
OFF-ON
P05.02
Activation décompte des heures partiel
ON
OFF-ON- INPxLIMx-BOOx
P05.03
Numéro canal (x)
1
1-8
P05.01 – S’il est sur OFF, les décomptes des heures sont désactivés et la page de mesure des compteurs horaires n’est pas affichée.
P05.02 – S’il est sur OFF, le compteur d’heures partiel est arrêté. S’il est sur On, le décompte des heures se vérifie quand le multimètre est sous tension. S’il est
associé à l’une des variables internes (LIMx-INPx-BOOx), le décompte des heures ne démarre que lorsque cette condition se vérifie.
P05.03 – Numéro du canal (x) de la variable interne éventuellement utilisée dans le paramètre précédent. Exemple : si le décompte des heures partiel doit
compter le temps durant lequel la mesure dépasse un certain seuil défini par la limite LIM3, programmez LIMx pour le paramètre précédent et spécifiez 3 pour
ce paramètre.
M06 - GAPHE DE TENDANCE
P06.01
Mesure pour page graphique de tendance
P06.02
Plage automatique
P06.03
Valeur fond d’échelle
P06.04
Multiplicateur fond d’échelle
UdM
Default
Range
kW (tot)
AVG
VL-L (eq) AVG
kW (tot) AVG
kvar (tot) AVG
kVA (tot) AVG
ON
OFF-ON
1000
0-1000
x1
x1 - x1k - x1M
P06.01 – Sélectionne la mesure à afficher sur le graphique de tendance.
P06.02 – Indique si l’échelle verticale s’adapte automatiquement aux valeurs affichées ou si elle est fixe (prédisposition de l’utilisateur).
P06.03 – Valeur de fond d’échelle définie par l’utilisateur. L’unité de mesure devient la mesure sélectionnée
P06.04 – Multiplicateur de la valeur de fond d’échelle.
44
F
31100124
M07 - COMMUNICATION
P07.n.02 Vitesse série
I271 I GB F E 01 13
UdM
P07.n.01 Adresse série noeud
bps
P07.n.03 Format de données
Default
Range
01
01-255
9600
1200
2400
4800
9600
19200
38400
8 bit - n
8 bit, no parity
8bit, odd
8 bit, even
7 bit, odd
7 bit, even
P07.n.04 Bits d’arrêt
1
1-2
P07.n.05 Protocole
Modbus RTU
Modbus RTU
Modbus ASCII
Nota : Ce menu est partagé en 2 sections pour les canaux de communication COM1..2
P07.n.01 – Adresse série (nœud) du protocole de communication.
P07.n.02 – Vitesse de transmission du port de communication.
P07.n.03 – Format de données. Définitions à 7 bits possibles seulement pour le protocole ASCII.
P07.n.04 – Nombre de bits d’arrêt.
P07.n.05 – Choix du protocole de communication.
Default
Range
P08.n.01 Mesure de référence
M08 - SEUILS DE LIMITE
UdM
OFF
OFF- (mesures)
P08.n.02 Fonction
Max
Max - Min - Min+Max
P08.n.03 Seuil supérieur
0
-9999 - +9999
P08.n.04 Multiplicateur
x1
/100 - x10k
P08.n.05 Retard
sec
0
0.0 - 600.0
0
-9999 - +9999
x1
/100 - x10k
0
0.0 - 600.0
P08.n.09 Etat au repos
OFF
OFF-ON
P08.n.10 Mémoire
OFF
OFF-ON
P08.n.06 Seuil inférieur
P08.n.07 Multiplicateur
P08.n.08 Retard
sec
F
Nota : Ce menu est partagé en 8 sections pour les seuils limite LIM1..8
P08.n.01 – Définit sur quelles mesures du multimètre il faut appliquer le seuil limite.
P08.n.02 – Définit le fonctionnement du seuil limite qui peut être :
Max = LIMn actif quand la mesure dépasse P08.n.03. P08.n.06 est le seuil de rétablissement.
Min = LIMn actif quand la mesure est inférieure à P08.n.06. P08.n.03 est le seuil de rétablissement.
Min+Max = LIMn actif quand la mesure dépasse P08.n.03 ou est inférieure à P08.n.06.
P08.n.03 et P08.n.04 – Définissent le seuil supérieur donné par la valeur P08.n.03 multipliée par P08.n.04.
P08.n.05 – Retard de déclenchement sur le seuil supérieur.
P08.n.06, P08.n.07, P08.n.08 – Comme
ci-dessus mais pour le seuil inférieur.
P08.n.09 – Permet d’inverser l’état de la limite LIMn.
P08.n.10 – Définit si le seuil reste enregistré et doit être rétabli manuellement (ON) ou s’il rétablit automatiquement (OFF).
M09 - ALARMES
P09.n.01 Source alarme
P09.n.02 Numéro canal (x)
P09.n.03 Mémoire
Default
Range
OFF
OFF-LIMx-INPx-BOOx
1
1-8
OFF
OFF-ON
P09.n.04 Priorité
Low
Basse - Haute
P09.n.05 Texte
ALAn
(Texte - 16 caractères)
Nota : Ce menu est partagé en 8 sections pour les alarmes ALA1..8
P09.n.01 – Signal provoquant l’alarme due, par exemple, au dépassement d’un seuil (LIMx), à l’activation d’une entrée externe (INPx), à une condition logique
booléenne (BOOx).
P09.n.02 – Numéro du canal (x) se référant au paramètre précédent.
P09.n.03 – Définit si l’alarme reste mémorisée et doit être réarmée manuellement (ON) ou si elle est rétablie automatiquement (OFF).
P09.n.04 – Si l’alarme a une priorité élevée, quand elle se vérifie, l’afficheur passe automatiquement à la page des alarmes et montre l’icône d’alarme. Si la
priorité est basse, la page ne change pas et l’icône d’information apparaît sur l’afficheur avec l’alarme.
P09.n.05 – Texte libre de l’alarme composé de 16 caractères au maximum.
45
31100124
M10 - COMPTEURS
Default
Range
P10.n.01 Source décompte
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.02 Numéro canal (x)
1
1-8
P10.n.03 Multiplicateur
1
1-1000
I271 I GB F E 01 13
P10.n.04 Diviseur
1
1-1000
P10.n.05 Description compteur
CNTn
(Texte - 16 caractères)
P10.n.06 Unité de mesure
Umn
(Texte - 6 caractères)
P10.n.07 Source RAZ
OFF
OFF-ON-INPx-LIMx-BOOx
1
1-8
P10.n.08 Numéro canal (x)
Nota : Ce menu est partagé en 4 sections pour les compteurs CNT1..4
P010.n.01 = Signal, entraînant l’activation du décompte (sur le front de montée), dû par exemple à la mise sous tension du multimètre (ON), au dépassement
d’un seuil (LIMx), à l’activation d’une entrée externe (INPx), à une condition logique booléenne (BOOx).
P010.n.02 = Numéro du canal (x) se référant au paramètre précédent.
P010.n.03 = K multiplicatif. Les impulsions décomptées sont multipliées par cette valeur avant d’être affichées.
P010.n.04 = K fractionnaire. Les impulsions décomptées sont divisées par cette valeur avant d’être affichées. Si différent de 1, le compteur est affiché avec 2
chiffres décimaux.
P10.n.05 = Description du compteur. Texte libre composé de 16 caractères.
P10.n.06 = Unité de mesure du compteur. Texte libre composé de 16 caractères.
P10.n.07 = Signal provoquant la remise à zéro du décompte. Tant que ce signal est actif, le décompte reste sur la valeur 0.
P10.n.08 = Numéro du canal (x) se référant au paramètre précédent.
M11 - IMPULSIONS
Default
Range
P11.n.01 Source mesure
kWh+
kWh+,kWh-,kvarh+,kvarh-,kVAh
P11.n.02 Unité de décompte
100
10/100/1k/10k
P11.n.03 Durée impulsion
0.1
0.01-1.00
Nota : Ce menu est partagé en 5 sections pour les impulsions de décompte énergie PUL1..5
P11.n.01 = Type d’énergie à laquelle est liée l’impulsion.
P11.n.02 = Quantité d’énergie pour chaque impulsion (ex. 10Wh, 100Wh, 1kWh, etc.).
P11.n.03 = Durée de l’impulsion.
M12 - LOGIQUE BOOLE
Default
Range
P12.n.01 Opérande 1
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
1
1-8
P12.n.03 Opérateur logique 1
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.04 Opérande 2
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.02 Numéro canal (x)
P12.n.05 Numéro canal (x)
1
1-8
P12.n.06 Opérateur logique 2
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.07 Opérande 3
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.08 Numéro canal (x)
1
1-8
P12.n.09 Opérateur logique 3
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.10 Opérande 4
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
1
1-8
P12.n.11 Numéro canal (x)
Nota : ce menu est partagé en 8 sections pour les variables booléennes BOO1..8
P12.n.01 = Premier opérande de la logique Booléenne.
P12.n.02 = Numéro du canal (x) se référant au paramètre précédent.
P12.n.03 = Opération logique entre le premier et le second opérande.
P12.n.04 = Second opérande.
A partir de P12.n.05 à P12.n.11 – (comme ci-dessus).
M13 - ENTREES
UdM
P13.n.01 Fonction entrée
P13.n.02 Etat repos
Default
Range
OFF
OFF - ON - LOCK SYNC - TAR-A TAR-B
C01...C08
OFF
OFF-ON
P13.n.03 Retard ON
sec
0.05
0.00 - 600.00
P13.n.04 Retard OFF
sec
0.05
0.00 - 600.00
Nota : Ce menu est partagé en 8 sections pour les entrées INP1..8
P13.n.01 = Fonction entrée :
OFF – Entrée désactivée
ON – Entrée activée, utilisée comme source pour compteurs, logique Booléenne, etc.
LOCK – Verrouillage des paramètres. Empêche l’accès aux deux niveaux.
SYNC – Synchronisme pour intégration puissance.
TAR-A, TAR-B – Sélection tarif énergie. Voir chapitre Tarifs.
C01…C08 – Quad cette entrée est activée (sur le front de montée), la commande correspondante du menu Commandes est exécutée.
P13.n.02 = Etat au repos de l’entrée. Permet d’inverser la logique d’activation.
P13.n.03 – P13.n.04 = Retard d’activation – désactivation de l’entrée. Ils permettent de filtrer l’état pour éviter des rebonds.
46
F
31100124
M14 - SORTIES
UdM
Default
Range
OFF
OFF-ON-SEQ-LIMxBOOx-ALAx-PULxREMx
P14.n.01 Fonction de sortie
P14.n.02 Numéro canal (x)
I271 I GB F E 01 13
P14.n.03 Etat au repos
1
1-8
OFF
OFF-ON
Nota : Ce menu est partagé en 8 sections pour les sorties OUT1..8
P14.n.01 = Fonction de la sortie :
OFF – Sortie désactivée
ON – Sortie toujours activée
SEQ – Sortie activée en cas d’ordre des phases erroné
LIMx – BOOx – ALAx – PULx – REMx – Sortie associée à l’état de la variable programmée. Permet de mettre sur une sortie l’état d’un seuil, d’une combinaison
Booléenne, d’une alarme, etc.
P14.n.02 = Numéro de canal (x) se référant au paramètre précédent.
P14.n.03 = Etat au repos de la sortie. Permet d’inverser la logique de fonctionnement de la sortie.
M15 - PAGES UTILISATEUR
Default
Range
P15.n.01 Activation page
OFF
OFF - ON
PAGn
(texte à 16 caractères)
P15.n.03 Mesure 1
OFF
OFF-(toutes mesures)
P15.n.04 Mesure 2
OFF
OFF-(toutes mesures)
P15.n.05 Mesure 3
OFF
OFF-(toutes mesures)
P15.n.06 Mesure 4
OFF
OFF-(toutes mesures)
P15.n.02 Titre
Nota : Ce menu est partagé en 4 sections pour les pages utilisateur PAG1..4
P15.n.01 = Active la page utilisateur PAGn.
P15.n.02 = Titre de la page utilisateur. Texte libre.
P15.n.03, P15.n.04, P15.n.05, P15.n.06 = Mesures qui seront affichées dans les quatre cadrans de la page utilisateur.
MENU COMMANDES
– Le menu Commandes permet d’exécuter des opérations occasionnelles (remise à zéro des mesures, compteurs, alarmes, etc.).
– Si vous avez saisi le mot de passe pour l’accès avancé, vous pouvez à l’aide du menu Commandes effectuer des opérations automatiques utiles pour
configurer l’appareil.
– Le tableau suivant montre les fonctions disponibles dans le menu Commandes, partagées selon le niveau d’accès nécessaire.
Code
COMMANDE
NIVEAU ACCES
Utilisateur
F
DESCRIPTION
Avancé
C.01
RAZ HI-LO
l
l
Remet à zéro les valeurs de crête HI et LO de toutes les mesures
C.02
RAZ MAX DEMAND
l
l
Remet à zéro les valeurs Demande maximum de toutes les mesures
C.03
RAZ ENERGIE VALEURS PARTIELLES
l
l
Remet à zéro les compteurs d’énergie partielle
C.04
RAZ COMPTEURS HORAIRES PARTIELS
l
l
Remet à zéro les compteurs d’heures partiels
C.05
RAZ COMPTEURS
l
l
Remet à zéro les compteurs
C.06
RAZ TARIFS
l
l
Remet à zéro les compteurs de tarifs
C.07
RAZ ALARMES
l
l
Réarme les alarmes avec mémoire
C.08
RAZ LIMITES
l
l
Remet à zéro les seuils limite avec mémoire
C.11
RAZ ENERGIE VALEURS TOTALAUX
l
Remet à zéro les compteurs d’énergie totaux, partiels, tarifs
C.12
RAZ COMPTEURS HORAIRES TOTAUX
l
Remet à zéro les compteurs d’heures totaux
C.13
PARAMETRES DE DEFAUT
l
Rétablit tous les paramètres sur les valeurs par défaut
C.14
PARAMETRES DE SECOURS
l
Enregistre une copie de sauvegarde des paramètres
C.15
REARMEMENT PARAMETRES
l
Prend les paramétrages dans la copie de sauvegarde
C.16
TEST DE CONNEXION
l
Exécute l’essai pour vérifier que le DMG est relié correctement.
Voir le chapitre Test de connexion.
– Après avoir sélectionné la commande voulue, enfoncez
pour l’exécuter. L’appareil demandera une confirmation. Enfoncez de nouveau
sera exécutée.
– Pour annuler l’exécution d’une commande sélectionnée, enfoncez MENU.
– Pour quitter le menu commandes, enfoncez MENU.
, la commande
47
31100124
I271 I GB F E 01 13
TEST DE CONNEXION
– Le test de connexion permet de vérifier si l’installation du multimètre a été effectuée correctement.
– Pour pouvoir exécuter le test, le multimètre doit être inséré dans une installation active avec les conditions suivantes :
• système triphasé, présence de toutes les phases (V > 50VAC L-N)
• courant minimum circulant sur chaque phase > 1% du fond d’échelle du TI défini
• sens positif des énergies (à savoir dans une installation courante où la charge inductive absorbe l’énergie du réseau).
– Pour lancer l’exécution du test, entrez dans le menu commandes et sélectionnez la commande appropriée selon les instructions du chapitre Menu
Commandes.
– Le test permet de vérifier les points suivants :
• lecture des trois tensions
• ordre des phases
• déséquilibrage des tensions
• inversion de polarité d’une ou plusieurs TI
• échange des phases entre tensions/courants.
– Si le test donne un résultat négatif, l’afficheur montre la raison de l’erreur.
– Si le test est mené à bien, la condition est enregistrée dans la mémoire rémanente et un message attestant le résultat positif apparaît dans la page des
informations.
1 - Séquence des contrôles
2 - Résultat de l’essai
F
48
31100124
F
CARACTERISTIQUES TECHNIQUES
Environnement
Alimentation auxiliaire
100 - 440V~
110 - 250V
Température de fonctionnement
-20...+60°C
Température de stockage
-30...+80°C
90 - 484V~
93,5 - 300V
Humidité relative
<80% (IEC/EN 60068-2-70)
Degré de pollution maxi
2
Catégorie de mesure
III
Catégorie de surtension
3
Hauteur
≤2000m
Séquence climatique
Z/ABDM (IEC/EN 60068-2-61)
690V~ phase-phase
400V~ ph-n
Résistance aux chocs
15g (IEC/EN 60068-2-27)
Résistance aux vibrations
0.7g (IEC/EN 60068-2-6)
Catégorie d’emploi selon UL
600V~ phase-phase
347V~ ph-n
Isolement
Plage de mesure
20 - 830V~ ph-ph
10 - 480V~ ph-n
Tension assignée de tenue aux chocs Uimp
9,5kV
Tension de tenue à fréquence industrielle
5,2kV
Plage de fréquence
45 - 66Hz
Connexions circuit alimentation/mesure tensions
Type de mesure
Valeur efficace vraie RMS
Type de bornes
A vis (extractibles)
Modalité de connexion
Ligne monophasée, biphasée, triphasée avec
ou sans neutre et triphasée équilibrée
Nombre de bornes
4 pour contrôle tension
2 pour alimentation
Tension assignée Us ∂
I271 I GB F E 01 13
Limites de fonctionnement
Fréquence
Puissance absorbée/dissipée
Temps d’immunité à la micro-interruption
45 - 66Hz
3,9VA 3,4W max
≥50ms
Entrées de tension
Type d’entrée
Tension assignée Ue max
Triphasé + neutre
Entrées ampérométriques
Tension assignée d’isolement Ui
690V~
Section conducteurs (mini...maxi)
0,2…2,5 mm² (24...12 AWG)
Courant assigné Ie
5A~
Couple de serrage bornes
0,5 Nm (4,5 lbin)
Plage de mesure
0,010 - 6A~
Connexions circuit mesure courants
Type d’entrée
Shunt alimentés par un transformateur de courant
externe (basse tension). 5A max.
Type de bornes
A vis (fixes)
Nombre de bornes
6 pour connexion TI externes
Section conducteurs (mini...maxi)
0,2…4 mm² (26...10 AWG)
Couple de serrage bornes
0,8 Nm (7 lbin)
Type de mesure
Surchage permanente
Courant dynamique de brève durée
Charge (par phase)
Valeur efficace vraie RMS
+20% Ie
F
50A pendant 1 seconde
≤ 0,6W
Boîtier
Matière
Polyamide RAL7035
Version
A encastrer selon IEC 61554
Degré de protection
IP54 frontal
IP20 boîtier et bornes
Poids
480g
Précision
Conditions de mesure
Température
+23°C ±2°C
Tension phase-neutre
± 0,5% (50…480V~) ±0,5 digit
Tension entre phase
± 0,5% (80…830V~) ±0,5 digit
Courant
± 0,5% (0,1…1,2In) ±0,5 digit
Energie active
Classe 1 (IEC/EN 62053-21)
Energie réactive
Certifications et conformité
Certifications
cULus
Classe 2 (IEC/EN 62053-23)
UL marking
Circuit alimentation/mesure tensions
0,05%/°K pour V, A, W
Circuit mesure courants
Use 60°C/75°C copper (Cu) conductor only
AWG Range: 24 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 4.5lb.in
AWG Range: 26 - 10 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 7lb.in
“For use on a flat surface of a Type 1 Enclosure”
Erreurs additionnelles
Température
Conformes aux normes
IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/ EN 61000-6-4,
UL508, CSA C22.2 N°14
∂ Alimentation auxiliaire prélevée par un système à tension phase-neutre ≤300V.
49
31100124
I271 I GB F E 01 13
INSTALLATION
– Le DMG700 est destiné au montage à encastrer selon IEC 61554.
– Insérez le multimètre dans le perçage du panneau sur la partie avant en veillant à ce que le joint soit positionné correctement entre le panneau et le cadre de
l’appareil.
– A l’intérieur du cadre, pour les quatre pattes de fixation, positionnez la patte dans l’un des deux guides latéraux puis appuyez sur l’angle de la patte pour
l’accrocher au second guide.
– Poussez la patte en avant en faisant pression sur ses parois latérales et en les faisant glisser sur les guides jusqu’à ce que les ailettes déformables s’appuient
bien contre la surface interne du panneau.
TAC
– Répétez l’opération pour les quatre pattes.
– Si vous devez démonter l’appareil, soulevez l’ailette centrale des pattes pour les libérer, puis faites-les glisser vers l’arrière sur les guides pour les désenfiler.
– Pour les branchements électriques, reportez-vous aux schémas de connexion du chapitre approprié et aux prescriptions figurant dans le tableau des
caractéristiques techniques.
– Après avoir terminé les branchements électriques, vous pouvez remettre en place les cache-bornes et les sceller pour empêcher la manipulation de l’appareil
et l’accès aux bornes de connexion.
– Pour monter les cache-bornes, insérez les crochets dans le logement approprié et exercer une légère pression jusqu’à ce qu’ils s’enclenchent. Veillez à mettre
le bon couvre-borne sur la borne appropriée.
F
– Insérez le fil et le sceau dans l’œillet situé aux angles externes du cache-borne pour le plombage.
DISPOSITION DES BORNES
DIMENSIONS D’ENCOMBREMENT
53.2
92
92
61.5
50
19
96
99.5
96
31100124
SCHEMAS DE CONNEXION
Connexion triphasée avec ou sans le neutre
P01.07 = L1-L2-L3-N L1-L2-L3
Connexion biphasée
P01.07 = L1-N-L2
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
I271 I GB F E 01 13
N
CT2
L
O
A
D
L2
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
-A1
CURRENT
VOLTAGE
+
A2
AUX SUPPLY
Connnexion monophasée
P01.07 = L1-N
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
VOLTAGE
Connexion triphasée équilibrée avec ou sans le neutre
P01.07 = L1-L2-L3-N-BIL L1-L2-L3-BIL
CT1
CT1
L1
L1
L
O
A
D
N
L
O
A
D
L2
L3
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
I1
VOLTAGE
S1 S2
S1 S2
I2
I3
CURRENT
--
+
A1
A2
AUX SUPPLY
Connexion ARON 3 phases sans le neutre
P01.07 = L1-L2-L3
V1 V2 V3 VN
I1
L
O
A
D
CT2
L2
L3
I3
F
L1
L2
CT3
L3
L
O
A
D
100...440VAC
110...250VDC
100...440VAC
110...250VDC
AUX SUPPLY
S1 S2
I2
CT1
L1
+
A2
S1 S2
CURRENT
Connexion ARON 3 phases sans le neutre
P01.07 = L1-L2-L3
CT1
-A1
S1 S2
VOLTAGE
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
-A1
CURRENT
+
A2
AUX SUPPLY
Connexion triphasée avec le neutre par TP
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3-N
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
CURRENT
Connexion triphasée sans le neutre par TP
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
CT2
L2
CT3
L3
L
O
A
D
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
TV
V1 V2 V3 VN
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
--
A1
+
TV
V1 V2 V3 VN
A2
AUX SUPPLY
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
NOTA
1. Fusibles recommandées : Alimentation auxiliaire et entrée de tension : F1A (rapide).
2. Les bornes S2 sont liés internement ensemble.
51
31100124
E MULTÍMETRO DIGITAL
LOVATO ELECTRIC S.P.A.
I271 I GB F E 01 13
24020 GORLE (BERGAMO) ITALIA
VIA DON E. MAZZA, 12
TEL. 035 4282111
FAX (Nazionale): 035 4282200
FAX (International): +39 035 4282400
E-mail [email protected]
Web www.LovatoElectric.com
DMG700
D
Available in German at www.LovatoElectric.com/I271D.pdf
CZ
Available in Czech at www.LovatoElectric.com/I271CZ.pdf
PL
Available in Polish at www.LovatoElectric.com/I271PL.pdf
RU
Available in Russian at www.LovatoElectric.com/I271RU.pdf
¡ATENCIÓN!
– Leer detenidamente el manual antes del uso y la instalación.
– Estos aparatos deben ser instalados por personal cualificado y de conformidad con las normativas vigentes en materia de equipos de instalación a fin de
evitar daños personales o materiales.
Antes de efectuar cualquier intervención en el instrumento, desconectar la tensión en las entradas de medición y alimentación y cortocircuitar los
transformadores de corriente.
– El fabricante declina cualquier responsabilidad relacionada a la seguridad eléctrica en caso de uso impropio del dispositivo.
– Los productos descritos en este documento pueden ser modificados o perfeccionados en cualquier momento. Por tanto, las descripciones y los datos aquí
indicados no implican algún vínculo contractual.
– La instalación eléctrica del edificio debe contar con un interruptor o disyuntor. Éste debe estar colocado muy cerca del aparato, en una ubicación de fácil
acceso para el operador. Debe estar marcado como dispositivo de interrupción del aparato: IEC/EN 61010-1 § 6.11.2.
– Limpiar el instrumento con un paño suave, evitando el uso de productos abrasivos, detergentes líquidos o disolventes.
INDICE
PAG.
Introducción . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Descripción . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Función de las teclas frontales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Visualización de las medidas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Tabla de las páginas de la pantalla . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Navegación por las páginas de la pantalla . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Página contadores de energía . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Página cuentahoras . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Página gráfico trend . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Página contadores . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Páginas usuario . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Menú principal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Acceso con contraseña . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Bloque configuración . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
Expansibilidad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Recursos adicionales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Canales de comunicación. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Entradas, salidas, variables internas, contadores. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Valores de umbral . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Lógica Booleana . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Variables de remoto . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
Alarmas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Tarifas. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Configuración de los parámetros (set-up) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Tabla de los parámetros . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Menú mandos . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 64
Test de conexión. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65
Características técnicas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 66
Instalación . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Disposición terminales . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Dimensiones mecánicas. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67
Esquemas de conexión. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 68
INTRODUCCIÓN
El multímetro DMG700 ha sido diseñado para combinar la máxima simplicidad de uso con una amplia selección de funciones avanzadas. En la versión para
montaje en panel de tamaño estándar 96x96mm, DMG700 combina el diseño moderno del frente con la practicidad de colocación y la posibilidad de expansión
trasera, donde es posible colocar los módulos de la serie EXP. La pantalla gráfica LCD hace que la interfaz usuario sea clara e intuitiva. La gran variedad de
funciones de los multímetros serie DMG permite su uso en un campo de aplicaciones sumamente amplio.
52
E
31100124
I271 I GB F E 01 13
DESCRIPCIÓN
– Versión empotrable 96x96mm.
– Pantalla gráfica LCD de 128x80 pixeles, retroiluminada, con 4 tonalidades de gris.
– 4 teclas para la visualización y configuración.
– Navegación rápida y simple.
– Compatible con redes BT, MT y AT.
– Textos para medidas, configuración y mensajes en 5 idiomas.
– Más de 160 parámetros eléctricos medidos.
– Bus de expansión para máx 4 módulos plug-in serie EXP.
– Funciones de I/O avanzadas programables.
– Medidas en verdadero valor eficaz (TRMS).
– Adquisición continua (gapless).
– Elevada precisión.
– Cubrebornes precintables.
– Bloque configuración mediante interruptor precintable.
FUNCIÓN DE LAS TECLAS FRONTALES
Tecla MENÚ - Sirve para entrar o salir de los diferentes menús de visualización y configuración.
Teclas s y t - Sirven para pasar las páginas de vídeo, para seleccionar las diferentes opciones visualizadas y para modificar los parámetros
(aumentar/disminuir los valores).
Tecla
- Sirve para pasar las subpáginas, para confirmar una selección efectuada y para pasar de un modo de visualización a otro.
VISUALIZACIÓN DE LAS MEDIDAS
– Las teclas s y t permiten pasar las páginas de visualización una por una. La página actual se reconoce por la barra del título.
– En base a la programación y conexión del aparato, es posible que algunos parámetros no se visualicen (por ejemplo si está programado para un sistema sin
neutro, no se visualizarán los parámetros relacionados a este último).
– En cada página, la tecla
permite acceder a las subpáginas correspondientes (por ejemplo para visualizar los valores máximos y mínimos registrados
para el parámetro seleccionado).
– La subpágina visualizada en el momento está indicada abajo a la izquierda con uno de los siguientes iconos:
• IN = Valor Instantáneo - Valor Instantáneo actual del parámetro, visualizdo por defecto cada vez que se cambia de página.
• HI = Valor máximo instantáneo - Valor más alto medido por el multímetro para el parámetro correspondiente. Los valores HIGH quedan memorizados y
guardados, incluso en caso de corte de alimentación. Es posible ponerlos a cero mediante el mando correspondiente (véase Menú mandos).
• LO = Valor mínimo instantáneo - Valor más bajo medido por el multímetro desde la puesta en tensión. El mismo se restablece con el mismo mando
utilizado para los valores HI.
• AV = Valor integrado - Valor promedio del parámetro a lo largo del tiempo. Permite observar un parámetro con variaciones lentas. Véase menú
Integración.
• MD = Máximo valor integrado - Máximo alcanzado por el valor integrado (max demand). Queda guardado en la memoria no volátil y puede restablecerse
con el mando correspondiente.
• GR = Barras gráficas - Visualización de las medidas mediante barras gráficas.
Ejemplo de página con indicaciones numéricas
1 - Unidad de medida
2 - Medida
3 - Titulo página
4 - Indicación fases
5 - Indicación subpágina
E
Ejemplo de página con Gráficos de Barras
1 - Unidad de medida
2 - Medida
3 - Indicación fases
4 - Indicadores HI-LO
– El usuario puede especificar la página y subpágina de la pantalla a la que desea retornar automáticamente una vez transcurrido un determinado lapso de
tiempo sin pulsar alguna tecla.
– Si lo desea, también es posible programar el multímetro de manera que la visualización permanezca en la posición en que se se ha dejado.
– Para configurar estas funciones véase el menú M02 – Utilidades.
53
31100124
TABLA DE LAS PÁGINAS DE LA PANTALLA
I271 I GB F E 01 13
Selección con s y t
Selección con
N°
PÁGINAS
1
TENSIONES ENTRE FASES - V(L1-L2), V(L2-L3), V(L3-L1), V(LL)EQV
HI
LO
SUBPÁGINAS
AV
2
TENSIONES DE FASE - V(L1-N), V(L2-N), V(L3-N), V(L-N)EQV
HI
LO
AV
3
CORRIENTE DE FASE Y NEUTRO - I(L1), I(L2), I(L3), I(N)
HI
LO
AV
MD
GR
4
POTENCIA ACTIVA - P(L1), P(L2), P(L3), P(TOT)
HI
LO
AV
MD
GR
5
POTENCIA REACTIVA - Q(L1), Q(L2), Q(L3), Q(TOT)
HI
LO
AV
MD
GR
6
POTENCIA APARENTE - S(L1), S(L2), S(L3), S(TOT)
HI
LO
AV
MD
7
FACTOR DE POTENCIA - PF(L1), PF(L2), PF(L3), PF(EQ)
HI
LO
AV
8
FRECUENCIA - ASIMETRÍA - F, ASY(VLL), ASY(VLN), ASY(I)
HI
LO
AV
9
DISTORSIÓN ARMÓNICA TENSIONES L-L - THD-V(L1-L2), THD-V(L2-L3), THD-V(L3-L1)
HI
LO
AV
GR
10
DISTORSIÓN ARMÓNICA TENSIONES L-N - THD-V(L1), THD-V(L2), THD-V(L3)
HI
LO
AV
GR
HI
LO
AV
GR
11
DIST. ARMÓNICA CORRIENTE - THD-I(L1), THD-I(L2) THD-I(L3)
12
CONTADORES ENERGÍA - kWh+(TOT), kWh-(TOT), kvarh+(TOT), kvarh-(TOT), kVA(TOT)
13
TARIFAS ENERGÍA
14
GRÁFICO TREND
15
CUENTAHORAS - Hr(TOT), Hr(Partial)
16
MÓDULOS DE EXPANSIÓN
17
18
GR
GR
GR
GR
PARCIAL
TAR1
...
TAR4
CONTADORES
CNT1
...
CNT4
VALORES DE UMBRAL
LIM1
...
LIM8
19
LÓGICA BOOLEANA
BOO1
...
BOO8
20
ALARMAS
ALA1
...
ALA8
21
INFO-REVISIONES-Nº SERIE
MODEL, REV SW, REV HW, Nº SERIE / TEMPERAURA INTERNA
22
LOGOTIPO
23
(PÁGINA USUARIO 1)
24
(PÁGINA USUARIO 2)
25
(PÁGINA USUARIO 3)
26
(PÁGINA USUARIO 4)
NOTA: Certaines pages listées ci-dessus ne pourront pas être disponibles si la fonction qu’elles doivent afficher n’est pas activée. Par exemple, si aucune alarme
n’a été défini, alors la page d’alarme ne sera pas visualisée.
NAVEGACIÓN ENTRE LAS PÁGINAS VÍDEO
Tensione entre fases
E
IN = Valor instantáneo
HI = Valor máximo
LO = Valor mínimo
AV = Valor medio
GR = Barras gráficas
HI = Valor máximo
LO = Valor mínimo
AV = Valor medio
GR = Barras gráficas
HI = Valor máximo
LO = Valor mínimo
AV = Valor medio
MD = Max demand
Tensiones de fase
IN = Valor instantáneo
Corriente de fase y neutro
IN = Valor instantáneo
(sigue)
54
31100124
I271 I GB F E 01 13
PÁGINA CONTADORES DE ENERGÍA
– En la página de los contadores de energía se visualizan juntos los valores de:
• energía activa consumida y generada
• energía reactiva consumida y generada (inductiva/capacitiva)
• energía aparente
– La página principal presenta los contadores totales. Mediante la tecla
es posible acceder a la subpágina de los contadores parciales (que el usuario
puede poner a cero).
– Para poner a cero los contadores es necesario acceder al menú de mandos.
1 - Indicación Totales / Parciales
PÁGINA CUENTAHORAS
– En la página cuentahoras se visualizan:
• cuentahoras total (cuenta el tiempo de alimentación del aparato)
• cuentahoras parcial (cuenta el tiempo durante el cual ocurre una determinada condición programable)
– Para poner a cero los contadores es necesario acceder al menú de mandos.
– La página cuentahoras puede inhabilitarse por completo si la habilitación general cuentahoras está configurada en OFF (véase menú Cuentahoras).
PÁGINA GRÁFICO TREND
– La página Trend permite visualizar un gráfico con la evolución temporal de un parámetro seleccionado por el usuario entre los siguientes:
• tensión equivalente integrada
• potencia activa total integrada
• potencia reactiva total integrada
• potencia aparente total integrada
– Por defecto, el parámetro visualizado es la potencia activa total integrada. Para establecer otro parámetro, variar el mismo en el menú de configuración Trend.
– En el gráfico es posible representar los últimos 96 valores de la medida integrada, cada uno de los cuales correspondiente a un intervalo temporal de integración.
– El intervalo temporal predefinido es de 15 minutos, de manera que el gráfico pueda visualizar la evolución del parámetro seleccionado durante las últimas
24 horas.
– Por tanto, con la configuración de fábrica el gráfico puede visualizar la evolución del consumo de potencia activa durante las últimas 24 horas.
– Los datos sobre los consumos se ponen a cero cuando se desconecta la alimentación del aparato o cuando se modifica el menú Configuraciones.
– Una vez superada la capacidad máxima de visualización, los nuevos datos sustituyen los anteriores siguiendo una lógica de memorización circular.
– El fondo de escala vertical se calcula automáticamente en base a los datos nominales ingresados en el menú M01 - General.
1 - Escala de tiempos.
Indica el tiempo pasado al que se
refieren las medidas.
E
2 - Escala vertical.
Puede ser automática o fija.
3 - Mesure visualisée
Parámetro representado
PÁGINA CONTADORES
– En la página contadores se visualizan los cómputos CNT1…4.
– Es posible contar la cantidad de veces que se activa una entrada, se supera un límite, etc. La condición se define en los parámetros Fuente de conteo.
– Para cada contador es posible definir una descripción y una unidad de medida con un texto libre (litros, m3, etc.).
– También se puede definir un coeficiente de conversión entre la cantidad de pulsos contados y la medición visualizada en pantalla. Esta función se obtiene
especificando un coeficiente multiplicador y uno fraccionario. Por ejemplo, si se configura el k
multiplicador = 3, por cada pulso leído el valor visualizado será aumentar 3 veces en pantalla. En cambio, si se programa un coeficiente fraccionario = 10, el
valor visualizado aumentará sólo cada 10 pulsos aplicados en la entrada. Combinando los k multiplicador y fraccionario es posible obtener cualquier relación
de conversión.
– Si el contador no presenta algún coeficiente fraccionario, su visualización se realizará solamente con números enteros. De lo contrario se visualizarán dos
cifras decimales.
– Los contadores pueden ponerse a cero desde el menú de mandos o mediante la señal Fuente de reajuste definida en los parámetros correspondientes.
1 - Unidad de medida del contador
2 - Cómputo
3 - Description (personnalisable) du compteur
4 - N. del contador seleccionado
PÁGINAS USUARIO
– El usuario tiene la posibilidad de crear una cantidad máxima de 4 páginas personalizadas.
– Estas páginas pueden contener 4 parámetros cada una, seleccionados libremente entre los disponibles en DMG700.
– El título de la página usuario puede elegirse libremente, por ejemplo indicando la parte de instalación servida por el multímetro.
– Las páginas usuario se ubican de manera que puedan ser localizadas fácilmente a partir de la primera, pulsando la tecla s.
– Al igual que todas las otras páginas, también es posible programar el multímetro para que la pantalla vuelva a una de las páginas usuario tras un
determinado lapso de tiempo de inactividad de las teclas.
– Para configurar las páginas usuario, véase el menú M15 en el capítulo de configuración parámetros.
55
31100124
MENÚ PRINCIPAL
– El menú principal consta de un conjunto de iconos gráficos que agilizan el acceso a las medidas y configuraciones.
– Desde la visualización normal de los parámetros pulsar la tecla MENÚ. La pantalla visualiza el menú rápido.
– Pulsar s t para seleccionar la función deseada. Se destacará el icono seleccionado y se visualizará la descripción de la función en el centro de la pantalla.
– Pulsar
para activar la función seleccionada.
– Si alguna función está inhabilitada, el icono correspondiente se visualizará de color gris.
I271 I GB F E 01 13
–
etc - Sirven para simplificar y agilizar el acceso a las páginas de visualización de parámetros, dado que llevan
directamente al grupo de medidas seleccionado y desde allí es posible avanzar o retroceder como de costumbre.
–
- Configuración del código numérico que permite acceder a las funciones protegidas (configuración de parámetros, ejecución de mandos).
–
- Punto de acceso a la configuración de los parámetros (set-up). Véase el capítulo específico.
–
- Punto de acceso al menú de mandos, donde el usuario habilitado puede ejecutar una serie de acciones de puesta a cero y restablecimiento.
1 - Visualización Tensiones
7 - Gráfico trend
2 - Visualización Corrientes
8 - Visualización cuentahoras
3 - Visualización Potencias
9 - Módulos de expansión
4 - Frecuencia - asimetria
10 - Configuraciónes (Set-up)
5 - Análisis armónico
11 - Menú mandos
6 - Contadores de energia
12 - Ingreso contraseña
ACCESO CON CONTRASEÑA
– La contraseña sirve para habilitar o impedir el acceso al menú de configuración y al menú de mandos.
– En los aparatos recién salidos de fábrica, la contraseña está inhabilitada por defecto y el acceso es libre. En cambio, si se han habilitado las contraseñas,
para poder acceder a dichos menús es necesario ingresar el código numérico correspondiente.
– Para habilitar el uso de las contraseñas y crear los códigos de acceso consúltese el capítulo configuración parámetros.
– Existen dos niveles de acceso que dependen del código ingresado:
• Acceso nivel usuario - Permite poner a cero los valores registrados, pero no modificar la configuración del aparato.
• Acceso nivel avanzado - Asigna los mismos derechos del usuario y además permite modificar la configuración.
– Desde la visualización normal de los parámetros pulsar la tecla MENÚ para abrir el menú principal, luego seleccionar el icono contraseña y pulsar .
– Se abrirá la ventana de configuración contraseña ilustrada en la figura:
Con las teclas s t se cambia el valor de la cifra seleccionada.
Con la tecla
se confirma la cifra y se va a las siguientes.
Ingresar la contraseña y desplazarse al icono de la llave.
Cuando la contraseña ingresada corresponde a la del nivel Usuario o a la del nivel Avanzado, se visualiza el mensaje de desbloqueo correspondiente.
Una vez aceptada la contraseña, el acceso permanece habilitado hasta que:
• El aparato se desconecta de la alimentación.
• El aparato se restablece (cuando se sale del menú configuración).
• Transcurren más de dos minutos sin que se pulse alguna tecla.
– Con la tecla MENÚ se cierra la ventana de configuración contraseña y se sale.
–
–
–
–
–
BLOQUEO CONFIGURACIÓN
– DMG700 presenta dos microinterruptores que permiten impedir el acceso a la configuracion y a las operaciones de reajuste (menú mandos).
– Estos microinterruptores están colocados de manera que no pueda accederse a los mismos tras haber montado los cubrebornes precintables.
– Para utilizar los microinterruptores:
• Desconectar la alimentación de DMG700, extraer los dos cubrebornes (si están montados) y la clema extraíble de 8 polos.
• Sirviéndose de un pequeño destornillador plano, poner los microinterruptores en la posición deseada.
• Colocar nuevamente la clema y los cubrebornes.
– El aparato se entrega con los microinterruptores posicionados para permitir el acceso.
SW
POS
SW1
OFF
Acceso a los parámetros consentido
ON
Acceso a los parámetros impedido
SW2
56
DESCRIPCIÓN
OFF
Acceso al Menú Mandos consentido
ON
Acceso al Menú Mandos impedido
E
31100124
I271 I GB F E 01 13
EXPANSIBILIDAD
– Gracias a su bus de expansión, DMG700 puede expandirse con los módulos adicionales de la serie EXP.
– DMG700 puede conectarse a un máximo de 4 módulos EXP….
– Los módulos EXP… aceptados por DMG700 pueden ser de las siguientes categorías:
• módulos de comunicación.
• módulos de I/O digitales.
– Para colocar un módulo de expansión:
• Desconectar la alimentación de DMG700.
• Retirar el cubrebornes y la clema extraíble de 8 polos.
• Extraer una de las tapas protectoras de las ranuras de expansión.
• Introducir el gancho superior del módulo en la ranura correspondiente.
• Girar el módulo hacia abajo introduciendo el conector en el bus.
• Presionar hasta que se enganche la pinza colocada en el lado inferior del módulo.
• Volver a instalar la clema y el cubrebornes transparente.
– El orden de aplicación de los módulos no es importante.
1
2
3
4
CLICK!
¡ATENCIÓN!
Cuando se instalan módulos EXP… arriba de los multímetros de la serie DMG, es imprescindible instalar los cubrebornes precintables que se entregan con el
multímetro.
– Cuando un DMG700 recibe alimentación, reconoce automáticamente los módulos EXP conectados al mismo.
– Si la configuración del sistema no es igual a la última detectada, porque se ha agregado o extraído un módulo, la unidad básica pide al usuario que confirme
la nueva configuración. Si se da la confirmación, la nueva configuración se guardará y quedará efectiva, de lo contrario a cada puesta en tensión se señalará
dicha discordancia.
– La configuración actual del sistema se visualiza en la página video correspondiente (módulos de expansión), donde se halla el número, el tipo y el estado de
los módulos conectados.
– La numeración de las entradas y salidas está indicada debajo de cada módulo.
– El estado (activado/desactivado) de las entradas y salidas de los canales de comunicación está indicado con la inscripción en negativo.
E
1 - N. y estado del canal de comunicación
2 - Tipo de módulos de expansión
3 - Numericación y estado de las I/O
RECURSOS ADICIONALES
– Los módulos de expansión proveen recursos adicionales que pueden utilizarse mediante los correspondientes menús de configuración.
– Los menús de configuración relativos a las expansiones pueden visualizarse aunque los módulos no se encuentren materialmente presentes.
– Dada la posibilidad de agregar varios módulos del mismo tipo (por ejemplo dos interfaces de comunicación), los menús de configuración son numerosos y
están identificados por un número progresivo.
– A continuación presentamos una tabla que indica cuántos módulos de cada tipo pueden instalarse juntos.
TIPO MÓDULO
COMUNICACIÓN
I/O DIGITALES
CODE
FUNCTION
MAX No.
EXP10 10
USB
2
EXP10 11
RS232
EXP10 12
RS485
EXP10 00
4 ENTRADAS
2
EXP10 01
4 SALIDAS ESTÁTICAS
2
EXP10 02
2 ENTRADAS +
2 SALIDAS EST.
4
EXP10 03
2 RELÉS
4
CANALES DE COMUNICACIÓN
– En DMG700 puede conectarse un máximo de 2 módulos de comunicación, denominados COMn. El menú de configuración comunicaciones M07 presenta
entonces dos secciones de parámetros (n=1 y n=2) para la configuración de los puertos de comunicación.
– Los canales de comunicación son completamente independientes, tanto desde el punto de vista hardware (tipo de interfaz material) como desde el punto de
vista del protocolo de comunicación.
– Los canales de comunicación pueden funcionar simultáneamente.
57
31100124
I271 I GB F E 01 13
ENTRADAS, SALIDAS, VARIABLES INTERNAS, CONTADORES
– Las entradas y las salidas digitales presentes en los módulos de expansión están identificadas mediante una sigla y un número progresivo. Por ejemplo, las
entradas digitales se denominan INPx, donde X representa el número de la entrada. De manera análoga, las salidas digitales se denominan OUTx.
– La numeración de las entradas y salidas se basa simplemente en la posición de instalación de los módulos de expansión, considerándolas progresivamente
de izquierda a derecha. Por ejemplo, la entrada INP1 es el primer borne de entrada del módulo más a la izquierda, mientras que los siguientes prosiguiendo
hacia la derecha serán INP2, INP3, etc.
– Para DMG700 se ha previsto un máximo de 8 entradas digitales y de 8 salidas, que entonces se denominarán INP1…INP8 y OUT1…OUT8. Para cada I/O hay
un menú de configuración que permite especificar su función y propiedades.
– Al igual que las entradas/salidas, existen algunas variables internas (bits) que pueden asociarse a las salidas o combinarse entre las mismas. Por ejemplo, es
posible aplicar umbrales límite a las medidas tomadas por el multímetro (tensión, corriente, etc.). En este caso, la variable interna se denomina LIMx y se
activará cuando la medición no se encuentre entre los límites definidos por el usuario mediante el menú de configuración correspondiente.
– Por último, es posible controlar hasta 4 contadores (CNT1…CNT4) para contar los pulsos procedentes del exterior (por tanto de entradas INPx) o la cantidad
de veces en que se presenta una determinada condición. Por ejemplo, si definimos un umbral LIMx como fuente de cómputo, será posible contar cuántas
veces una medición ha superado un determinado valor.
– A continuación presentamos una tabla con todas las I/O y las variables internas controladas por DMG700.
Cod.
DESCRIPCIÓN
INPx
Entradas digitales
Range (x)
1...8
OUTx
Salidas digitales
1...8
LIMx
Valores de umbral
1...8
BOOx
Lógica Booleana
1...8
REMx
Variables de remoto
1...8
ALAx
Alarmas
1...8
PULx
Pulsos de cómputo energía
1...5
CNTx
Contadores
1...4
– El estado de cada I/O y sus variables internas puede verse en pantalla, en la página de estado I/O.
ALORES DE UMBRAL (LIM)
– Los valores de umbral LIMn son variables internas cuyo estado depende de la superación de los límites definidos por el usuario por parte de una de las
mediciones efectuadas por el multímetro (ejemplo: potencia activa total superior a 25kW).
– Para agilizar la configuración de los umbrales, que pueden variar dentro de un rango sumamente amplio, cada uno de los mismos debe configurarse con un
valor básico + un coeficiente multiplicador (ejemplo: 25 x 1k = 25000).
– Cada LIM tiene a disposición dos umbrales: uno superior y uno inferior. El umbral superior tiene que configurarse siempre a un valor mayor que el inferior.
– El significado de los umbrales depende de las siguientes funciones:
Función Mín: Con la función Mín, el umbral inferior provoca la activación y el superior la restablece. Cuando el valor del parámetro seleccionado es menor al
límite inferior, tras el retardo se activa el umbral. Cuando el valor del parámetro seleccionado es mayor al límite superior, tras el retardo se obtiene el
restablecimiento.
Función Máx: Con la función Máx, el umbral superior provoca la activación y el inferior la restablece. Cuando el valor del parámetro seleccionado es mayor
al límite superior, tras el retardo se activa el umbral. Cuando el valor del parámetro seleccionado es menor al límite inferior, tras el retardo se obtiene el
restablecimiento.
Función Mín+Máx: Con la función Mín+Máx, los umbrales inferior y superior provocan la activación. Cuando el valor del parámetro seleccionado es menor al
límite inferior o mayor al límite superior, tras los respectivos retardos se obtiene la activación de la salida. Cuando el valor del parámetro seleccionado vuelve
dentro de los límites se obtiene el restablecimiento inmediato.
– La activación puede ser una excitación o desexcitación del límite LIMn según la configuración.
– Si el límite está configurado con memoria, el restablecimiento es manual y puede ser efectuado mediante el mando correspondiente en el menú de mandos.
– Véase el menú de configuración M08.– Véase el menú de configuración M08.
1 - Estado variable límite
2 - Valor de la medida
3 - Función
4 - Tipo de medida
5 - Umbral superior
6 - Retardo en umbral
7 - Umbral inferior
LÓGICA BOOLEANA (BOO)
– Se puede crear un máximo de 8 variables internas denominadas BOO1…8, cuyo estado depende de la combinación lógica Booleana de umbrales límite,
entradas, salidas, etc.
– Los operandos (INP, LIM, etc.) pueden combinarse entre sí mediante las siguientes operaciones lógicas Booleanas: AND, OR, EXOR, AND NOT, OR NOT,
EXOR NOT.
– Cada variable Booleana es el resultado de la combinación de un máximo de 4 operandos relacionados entre sí mediante tres operaciones lógicas.
– Ejemplo: Si queremos que la variable BOO1 se active al activarse los límites LIM2, LIM3 y LIM4 o cuando se activa la entrada INP1, tendremos que
programar BOO1 como la combinación de LIM2 AND LIM3 AND LIM4 OR INP1.
– No es necesario utilizar los 4 operandos en una sola combinación lógica. Por ejemplo, si sólo queremos que BOO2 se active al activarse INP1 o INP2, es
posible programar los parámetros de BOO2 como la combinación INP1 OR INP2, dejando las otras operaciones lógicas configuradas con
--- (ninguna operación).
– La página vídeo LOGICA BOOLEANA presenta, por cada variable BOO1..8, el estado de cada uno de los operandos involucrados en la operación lógica y el
resultado final, es decir el estado de la variable Booleana seleccionada.
1 - Operando 1
2 - Operac. lógica 1
3 - Operando 2
4 - Estado operando 1
5 - Estado variable booleana resultante
VARIABLES DE REMOTO (REM)
– DMG700 puede aceptar hasta un máximo de 8 variables controladas de manera remota (REM1…REM8).
– Se trata de variables cuyo estado puede ser modificado a voluntad por el usuario mediante el protocolo de comunicación y que pueden utilizarse en
combinación con las salidas, la lógica Booleana, etc.
– Ejemplo: Si se usa una variable remota (REMx) como fuente de una salida (OUTx), es posible activar y desactivar un relé libremente mediante el software de
supervisión. Esto permite de utilizar los relés de salida DMG700 para controlar algunas cargas como por ejemplo la iluminación.
– Otro empleo de las variables REM puede ser la de habilitar o inhabilitar determinadas funciones desde una posición remota, introduciéndolas en una lógica
Booleana AND con entradas o salidas.
58
E
31100124
I271 I GB F E 01 13
ALARMAS (ALA)
– El usuario puede definir una cantidad máxima de 8 alarmas programables (ALA1…ALA8).
– Por cada alarma es posible establecer la fuente, es decir la condición que provoca la alarma, y el texto del mensaje que se visualizará en pantalla al
presentarse dicha condición.
– Por ejemplo, una condición que provoca la alarma puede ser la superación de un umbral. En este caso, la fuente será uno de los valores de umbral LIMx.
– En cambio, si la alarma deba visualizarse como consecuencia de la activación de una entrada digital externa, la fuente será una INPx.
– Con el mismo criterio también es posible asociar a una alarma algunas condiciones complejas que resulten de una combinación lógica Booleana de entradas,
umbrales, etc. En este caso utilizaremos las variables Booleanas BOOx.
– Por cada alarma, el usuario tiene la posibilidad de definir un mensaje de libre programación que se visualizará en la página de estado alarmas.
– También es posible definir el nivel de prioridad de una alarma. Si se trata de una simple indicación, la prioridad de la alarma puede configurarse como baja.
En ese caso, el icono asociado a la alarma será un icono de información.
– En cambio, si la alarma debe indicar una situación más urgente de resolver, al configurar la prioridad como alta el mensaje de la alarma estará acompañado
por el icono de Atención y la pantalla visualizará automáticamente la página de alarmas.
– Si se presentan varias alarmas a la vez, las mismas se muestran de manera consecutiva y se indica la cantidad total.
– Para borrar una alarma que había sido programada con memoria es necesario servirse del mando específico que se halla en el menú de mandos.
– Para la definición de las alarmas véase el menú de configuración M09.
1 - N. Alarma / Total alarmas
TARIFAS
– Para contar la energía, DMG700 puede controlar 4 tarifas independientes además de los valores total y parcial.
– La selección de las tarifas se realiza mediante entradas digitales externas, por tanto se requiere la instalación de un módulo de expansión EXP con entradas
digitales. Para seleccionar las 4 tarifas se utilizan las dos funciones de entrada TAR-A y TAR-B.
Su combinación binaria permite la selección como se indica en la siguiente tabla:
TAR-A
TAR-B
TARIFA
OFF
OFF
1
ON
OFF
2
OFF
ON
3
ON
ON
4
– Si se utiliza la entrada de sincronismo para el intervalo de integración, el cambio de tarifa es efectuado contemporáneamente al sincronismo, de lo contrario
el cambio se produce al cambiar la configuración de las entradas.
– Cada uno de los cómputos de las tarifas presenta 5 contadores de energía (activa consumida y generada, reactiva consumida y generada, aparente) y se
visualizan en una página específica que sigue a la de los contadores totales y parciales.
– Si el DMG cuenta con interfaz de comunicación, es posible seleccionar la tarifa activa mediante un mando específico en el protocolo ModBus (véase
instrucción técnica protocolo ModBus).
1 - Tarifa activa
2 - Tarifa
E
CONFIGURACIÓN DE LOS PARÁMETROS (SET-UP)
– Desde la visualización normal de los parámetros pulsar la tecla MENÚ para abrir el menú principal, luego seleccionar el icono
y pulsar
para
acceder al menú configuración.
– Entonces se visualiza la tabla ilustrada en la figura, con la selección de los submenús de configuración que contienen todos los parámetros clasificados
según su función.
.
– Seleccionar el submenú deseado mediante las teclas s t y confirmar con
– Para salir del menú y volver a la visualización de los parámetros pulsar MENÚ.
59
31100124
I271 I GB F E 01 13
– En la siguiente tabla pueden verse los submenús disponibles.
Code
Submenú
Descripción
M01
GENERAL
Datos concernientes la instalación
M02
UTILIDADES
Idioma, Brillo, Páginas Vídeo
M03
CONTRASEÑA
Habilitación protección acceso
M04
INTEGRACIÓN
Tiempos de integración medidas
M05
CUENTAHORAS
Habilitación cuentahoras
M06
GRÁFICO TREND
Definición parámetro y escala
M07
COMUNICACIÓN (COMn)
Puertos de comunicación
M08
VALORES DE UMBRAL (LIMn)
Umbrales de los parámetros
M09
ALARMAS (ALAn)
Mensajes de alarma
M10
CONTADORES (CNTn)
Contadores generales
M11
PULSOS (PULn)
Pulsos de cómputo energía
M12
LÓGICA BOOLEANA (BOOn)
Combinaciones lógica Booleana
M13
ENTRADAS (INPn)
Entradas digitales
M14
SALIDAS (OUTn)
Salidas digitales
M15
PÁGINAS USUARIO (PAGn)
Páginas personalizadas
– Seleccionar el submenú y pulsar la tecla
para visualizar los parámetros.
– Todos los parámetros se visualizan con su código, descripción y valor actual.
1 - Código parámetro
2 - Descripción parámetro
3 - Valor actual
4 - Parámetro seleccionado
– Si se desea modificar el valor de un parámetro, tras haberlo seleccionado pulsar .
– Si no se ha ingresado la contraseña de nivel avanzado no será posible acceder a la página de modificación y se visualizará un mensaje de negación de acceso.
– Si por el contrario se obtiene el acceso, se visualizará la página de modificación.
1 - Parámetro seleccionado
2 - Mínimo valor posible
3 - Barra gráfica valor-alcance
4 - Nuevo valor configurado
5 - Máximo valor posible
6 - Valor predefinido
– En la página de modificación es posible variar los valores con las teclas s y t. También se visualiza una barra gráfica que indica el alcance de
configuración, los valores mínimos y máximos posibles, el valor anterior y el predefinido.
– Si se pulsan simultáneamente las teclas s y t, la configuración vuelve a ser la predefinida en fábrica.
se desplaza el cursor sobre el texto. Al
– Durante el ingreso de un texto, con las teclas s y t se selecciona el carácter alfanumérico, mientras que con
pulsar simultáneamente s y t, la selección alfanumérica presenta directamente la letra ‘A’.
– Pulsar MENÚ para volver a la selección de parámetros. El valor ingresado permanece memorizado.
– Pulsar nuevamente la tecla MENÚ para guardar las modificaciones y salir de la configuración. El multímetro realiza un reajuste y vuelve al estado de
funcionamiento normal.
– Si no se pulsa alguna tecla durante 2 minutos consecutivos, el menú de configuración (Setup) deja de visualizarse automáticamente y el multímetro vuelve a
la pantalla normal.
TABLA DE PARÁMETROS
UdM
Default
Range
P01.01
M01 - GENERAL
Primario TC
A
5
1-10000
P01.02
Secundario TC
A
5
5
P01.03
Tensión nominal
V
Aut
Aut / 50-500000
P01.04
Uso TT
OFF
OFF-ON
P01.05
Primario TT
V
100
50-500000
P01.06
Secundario TT
V
P01.07
Tipo de conexión
100
50-500
L1-L2-L3-N
L1-L2-L3-N
L1-L2-L3
L1-L2-L3-N BIL
L1-L2-L3 BIL
L1-N-L2
L1-N
P01.01 – Corriente nominal del circuito primario de los TC.
P01.02 – Corriente del circuito secundario de los TC. Fijo en 5A para DMG700.
P01.03 – Tensión nominal de la instalación. Dejándolo en Aut, el multímetro adapta automáticamente la escala de las barras gráficas.
P01.04 – Poner en ON si se utilizan TT. Si se pone en OFF, los dos parámetros que siguen serán ignorados.
P01.05 – Tensión nominal primario TT.
P01.06 – Tensión nominal secundario TT.
P01.07 – Configurar de conformidad con el esquema de conexión utilizado. Véanse los Esquemas de conexión al final del manual.
60
E
31100124
I271 I GB F E 01 13
M02 - UTILIDADES
Default
Range
English
English
Italiano
Francais
Espanol
Portoguese
%
50
0-100
%
100
0-100
Intensidad retroiluminación pantalla baja
%
30
0-50
P02.05
Tiempo cambio a retroiluminación baja
sec
30
5-600
P02.06
Retorno a página predefinida
sec
60
OFF / 10-600
P02.07
Página predefinida
VL-L
VL-L / VL-N ...
P02.08
Subpágina predefinida
INST
INST / HI / LO /
AVG / MD /GRAPH /
1-8
P02.09
Tiempo de actualización pantalla
0.5
0.1 - 5.0
P02.01
Idioma
P02.02
Contraste LCD
P02.03
Intensidad retroiluminación pantalla alta
P02.04
UdM
sec
P02.06 – Si se pone en OFF, en pantalla se visualiza siempre la última página utilizada por el usuario. Si se ingresa un valor, éste indica el tiempo tras el cual la
pantalla retornará a la página programada en P02.07.
P02.07 – Número de la página a la que retorna automáticamente la pantalla una vez transcurrido el tiempo P02.06 desde la última pulsación de una tecla.
P02.08 – Tipo de subpágina a la que retorna la pantalla una vez transcurrido el tiempo P02.06.
M03 - PASSWORD
Default
Range
Uso contraseña
OFF
OFF-ON
P03.02
Contraseña nivel Usuario
1000
0-9999
P03.03
Contraseña nivel Avanzado
2000
0-9999
P03.01
UdM
P03.01 – Si se pone en OFF, la gestión de la contraseña está inhabilitada y el acceso a la configuración y al menú de mandos es libre.
P03.02 – Con P03.01 activado, valor a ingresar para acceder al nivel usuario. Véase capítulo Acceso con contraseña.
P03.03 – Igual que P03.02, pero en referencia al acceso al nivel Avanzado.
M04 - INTEGRACIÓN
Default
Range
Var.
Fijo / Variable
Sincronismo / Bus
min
15
1-60
min
15
1-60
Tiempo de integración tensiones
min
1
1-60
Tiempo de integración frecuencia
min
1
1-60
P04.01
Modo integración
P04.02
Tiempo integración potencias
P04.03
Tiempo integración corrientes
P04.04
P04.05
UdM
P04.01 – Selección del modo de cálculo de las medidas integradas.
Fijo = Las mediciones instantáneas son integradas durante el tiempo programado. Cada vez que termina el tiempo, la medición integrada se actualiza con el
resultado de la última integración.
Variable = Las mediciones instantáneas son integradas durante un tiempo equivalente a 1/15 del tiempo programado. Cada vez que termina este intervalo, el
valor más viejo es reemplazado por el nuevo resultado del cálculo. La medición integrada se actualiza cada 1/15 del tiempo programado, considerando un
alcance que se desplaza en el tiempo, dura el tiempo programado y comprende los últimos 15 valores calculados.
Sincronismo = Igual que el modo Fijo, pero los intervalos de integración son definidos por una entrada digital externa programada con la función sincronismo.
Bus = Igual que el modo Fijo, pero los intervalos de integración son definidos por mensajes de sincronismo enviados por el bus de serie.
P04.02 – Tiempo integración medidas AVG (promedio) para las potencias activa, reactiva y aparente.
P04.03, P04.04, P04.05 – Tiempo integración medidas AVG (promedio) para los respectivos parámetros.
Default
Range
P05.01
M05 - CUENTAHORAS
Habilitación general cuentahoras
UdM
ON
OFF-ON
P05.02
Habilitación cuentahoras parcial
ON
OFF-ON- INPxLIMx-BOOx
P05.03
Número canal (x)
1
1-8
P05.01 – Con este parámetro en OFF, los cuentahoras están inhabilitados y no se visualiza la página de los cuentahoras.
P05.02 – Con este parámetro en OFF, el cuentahoras parcial no se incrementa. Con este parámetro en ON, el incremento ocurre cuando el multímetro recibe
alimentación. Al asociarse a una de las variables internas (LIMx-INPx-BOOx) se incrementa sólo cuando esta condición es efectiva.
P05.03 – Número del canal (X) de la variable interna usada eventualmente en el parámetro anterior. Ejemplo: Si el cuentahoras parcial debe contar el tiempo
durante el cual un parámetro supera un determinado umbral definido por el límite LIM3, es necesario programar LIMx en el parámetro anterior y configurar este
parámetro con el valor 3.
M06 - GRÁFICA TREND
P06.01
Medida para página trend
P06.02
Autoalcance escala
P06.03
Valor de fondo de escala
P06.04
Multiplicador de fondo de escala
UdM
Default
Range
kW (tot)
AVG
VL-L (eq) AVG
kW (tot) AVG
kvar (tot) AVG
kVA (tot) AVG
ON
OFF-ON
1000
0-1000
x1
x1 - x1k - x1M
P06.01 – Selecciona la medida a visualizar en el gráfico Trend.
P06.02 – Establece si la escala vertical tiene que adaptarse automáticamente a los valores visualizados o si será definida fija por el usuario.
P06.03 – Valor de fondo de escala definido por el usuario. La unidad de medida se aplica a la medida seleccionada.
P06.04 – Multiplicador del valor de fondo de escala.
61
E
31100124
M07 - COMUNICACIÓN
UdM
P07.n.01 Dirección serial nudo
I271 I GB F E 01 13
P07.n.02 Velocidad serial
bps
P07.n.03 Formato datos
Default
Range
01
01-255
9600
1200
2400
4800
9600
19200
38400
8 bit - n
8 bit, no parity
8bit, odd
8 bit, even
7 bit, odd
7 bit, even
P07.n.04 Bit de stop
1
1-2
P07.n.05 Protocolo
Modbus RTU
Modbus RTU
Modbus ASCII
Nota: Este menú se subdivide en 2 secciones, para los canales de comunicación COM1..2
P07.n.01 – Dirección serial (nodo) del protocolo de comunicación.
P07.n.02 – Velocidad de transmisión del puerto de comunicación.
P07.n.03 – Formato datos. Configuraciones a 7 bits posibles sólo para el protocolo ASCII.
P07.n.04 – Número bit de stop.
P07.n.05 – Selección del protocolo de comunicación.
Default
Range
P08.n.01 Medida de referencia
M08 - VALORES DE UMBRAL
UdM
OFF
OFF- (misure)
P08.n.02 Función
Max
Max - Min - Min+Max
P08.n.03 Umbral superior
0
-9999 - +9999
P08.n.04 Multiplicador
x1
/100 - x10k
P08.n.05 Retardo
sec
0
0.0 - 600.0
0
-9999 - +9999
x1
/100 - x10k
0
0.0 - 600.0
P08.n.09 Estado de reposo
OFF
OFF-ON
P08.n.10 Memoria
OFF
OFF-ON
P08.n.06 Umbral inferior
P08.n.07 Multiplicador
P08.n.08 Retardo
sec
Nota: Este menú se subdivide en 8 secciones, para los valores de umbral LIM1..8
P08.n.01 – Determina el parámetro del multímetro al cual aplicar el valor de umbral.
P08.n.02 – Determina el funcionamiento del valor de umbral. Puede ser:
Máx = LIMn activo cuando el parámetro supera el valor de P08.n.03. P08.n.06 es el umbral de restablecimiento.
Mín = LIMn activo cuando el parámetro es inferior al valor de P08.n.06. P08.n.03 es el umbral de restablecimiento.
Mín+Máx = LIMn activo cuando el parámetro supera el valor de P08.n.03 o es inferior al valor de P08.n.06.
P08.n.03 y P08.n.04 – Determinan el umbral superior, que es el resultado del valor de P08.n.03 multiplicado por el de P08.n.04.
P08.05 – Retardo de intervención en el umbral superior.
P08.n.06, P08.n.07, P08.n.08 – Igual que el anterior pero respecto del umbral inferior.
P08.n.09 - Permite invertir el estado del límite LIMn.
P08.n.10 – Determina si el umbral debe quedar memorizado y hay que restablecerlo manualmente (ON) o si se restablece automáticamente (OFF).
E
M09 - ALARMAS
P09.n.01 Fuente alarma
P09.n.02 Número canal (X)
P09.n.03 Memoria
Default
Range
OFF
OFF-LIMx-INPx-BOOx
1
1-8
OFF
OFF-ON
P09.n.04 Prioridad
Low
Baja - Alta
P09.n.05 Texto
ALAn
(texto - 16 car.)
Nota: Este menú se subdivide en 8 secciones, para las alarmas ALA1..8
P09.n.01 – Señal que provoca la alarma. Puede ser la superación de un umbral (LIMx), la activación de una entrada externa (INPx) o una condición lógica
Booleana (BOOx).
P09.n.02 – Número del canal X referido al parámetro anterior.
P09.n.03 – Determina si la alarma debe quedar memorizada y hay que borrarla manualmente (ON) o si se restablece automáticamente (OFF).
P09.n.04 – Si la alarma tiene una prioridad alta, al presentarse provoca la visualización automática de la página de alarmas y se presenta también el icono de
atención. En cambio, si la prioridad configurada es baja, la pantalla no cambia de página y se presenta con el icono de información.
P09.n.05 – Texto libre de la alarma. Máx. 16 caracteres.
62
31100124
M10 - CONTADORES
P10.n.01 Fuente cálculo
Range
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.02 Número canal (X)
1
1-8
P10.n.03 Multiplicador
1
1-1000
P10.n.04 Divisor
I271 I GB F E 01 13
Default
1
1-1000
P10.n.05 Descripción del contador
CNTn
(Texto - 16 caracteres)
P10.n.06 Unidad de medida
Umn
(Texto - 6 caracteres)
P10.n.07 Fuente de reajuste
OFF
OFF-ON-INPx-LIMx-BOOx
P10.n.08 Número canal (x)
1
1-8
Nota: Este menú se subdivide en 4 secciones, para los contadores CNT1..4
P010.n.01 = Señal que provoca el incremento de la cuenta (en el frente anterior). Puede ser la puesta en tensión del multímetro (ON), la superación de un
umbral (LIMx), la activación de una entrada externa (INPx) o una condición lógica Booleana (BOOx).
P010.n.02 = Número del canal X referido al parámetro anterior.
P010.n.03 = K multiplicador. Los pulsos contados se multiplican por este valor antes de visualizarse en pantalla.
P010.n.04 = K fraccionario. Los pulsos contados se dividen por este valor antes de visualizarse en pantalla. Si no equivale a 1, el contador presenta 2 cifras
decimales.
P10.n.05 = Descripción del contador. Texto libre de 16 caracteres.
P10.n.06 = Unidad de medida del contador. Texto libre de 6 caracteres.
P10.n.07 = Señal que provoca la puesta a cero del conteo. El conteo permanece en cero mientras esta señal está activada.
P10.n.08 = Número del canal X referido al parámetro anterior.
M11 - PULSOS
Default
Range
P11.n.01 Fuente medida
kWh+
kWh+,kWh-,kvarh+,kvarh-,kVAh
P11.n.02 Unidad de conteo
100
10/100/1k/10k
P11.n.03 Duración pulso
0.1
0.01-1.00
Nota: Este menú se subdivide en 5 secciones, para los pulsos de energía PUL1..5
P11.n.01 = Tipo de energía a la que corresponde el pulso.
P11.n.02 = Cantidad de energía por pulso (ejemplo: 10Wh, 100Wh, 1kWh, etc.).
P11.n.03 = Duración del pulso.
M12 - LÓGICA BOOLEANA
P12.n.01 Operando 1
Default
Range
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.02 Número canal (X)
1
1-8
P12.n.03 Operación lógica 1
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.04 Operando 2
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.05 Número canal (X)
1
1-8
P12.n.06 Operación lógica 2
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.07 Operando 3
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
P12.n.08 Número canal (X)
1
1-8
P12.n.09 Operación lógica 3
---
- - - - AND - OR - EXOR - AND NOT OR NOT - EXOR NOT
P12.n.10 Operando 4
OFF
OFF-LIMx-INPx-OUTx-REMx-BOOx
1
1-8
P12.n.11 Número canal (X)
E
Nota: Este menú se subdivide en 8 secciones, para las variables Booleanas BOO1..8
P12.n.01 = Primer operando de la lógica Booleana.
P12.n.02 = Número del canal referido al parámetro anterior.
P12.n.03 = Operación lógica entre el primero y el segundo operando.
P12.n.04 = Segundo operando.
De P12.n.05 a P12.n.11 – Iguales a los anteriores.
M13 - ENTRADAS
UdM
P13.n.01 Función entrada
P13.n.02 Estado reposo
Default
Range
OFF
OFF - ON - LOCK SYNC - TAR-A TAR-B
C01...C08
OFF
OFF-ON
P13.n.03 Retardo ON
sec
0.05
0.00 - 600.00
P13.n.04 Retardo OFF
sec
0.05
0.00 - 600.00
Nota: Este menú se subdivide en 8 secciones, para las entradas INP1..8
P13.n.01 = Función entrada:
OFF – Entrada inhabilitada
ON – Entrada habilitada que se utiliza como fuente para los contadores, la lógica Booleana, etc.
LOCK – Bloqueo configuración – Impide el acceso a ambos niveles.
SYNC – Sincronismo para integración potencia.
TAR-A, TAR-B – Selección tarifa energías. Véase capítulo Tarifas energía.
C01…C08 – Cuando se activa esta entrada en el frente anterior se ejecuta el mando del menú mandos correspondiente.
P13.n.02 = Estado de reposo de la entrada. Permite invertir la lógica de activación.
P13.n.03 – P13.n.04 = Retardos de activación o desactivación de la entrada. Permiten filtrar el estado para evitar cambios bruscos.
63
31100124
M14 - SALIDAS
UdM
Default
Range
OFF
OFF-ON-SEQ-LIMxBOOx-ALAx-PULxREMx
P14.n.01 Función de salida
P14.n.02 Número canal (X)
1
1-8
P14.n.03 Estado de reposo
OFF
OFF-ON
I271 I GB F E 01 13
Nota: Este menú se subdivide en 8 secciones, para las salidas OUT1..8
P14.n.01 = Función de la salida:
OFF - Salida inhabilitada
ON – Salida siempre habilitada
SEQ – Salida activada en caso de error de secuencia fases
LIMx – BOOx – ALAx – PULx – REMx – Salida asociada al estado de la variable programada. Permite llevar a una salida el estado de un umbral, de una
combinación Booleana, de una alarma, etc.
P14.n.02 - Número del canal (X) referido al parámetro anterior.
P14.n.03 = Estado de reposo de la salida. Permite invertir la lógica de funcionamiento de la salida.
M15 - PÁGINAS USUARIO
Default
Range
OFF
OFF - ON
P15.n.01 Habilitación página
P15.n.02 Título
PAGn
(texto 16 caracteres)
P15.n.03 Medida 1
OFF
OFF - (todas medidas)
P15.n.04 Medida 2
OFF
OFF - (todas medidas)
P15.n.05 Medida 3
OFF
OFF - (todas medidas))
P15.n.06 Medida 4
OFF
OFF - (todas medidas)
Nota: Este menú se subdivide en 4 secciones, para las páginas de usuario PAG1...PAG4.
P15.n.01 = Habilita la página usuario PAGn.
P15.n.02 = Título de la página usuario. Texto libre.
P15.n.03, P15.n.04, P15.n.05, P15.n.06 = Medidas que se visualizarán en los cuatro recuadros de la página usuario.
MENÚ MANDOS
– El menú de mandos permite efectuar operaciones ocasionales como la puesta a cero de parámetros, contadores, alarmas, etc.
– Si se cuenta con la contraseña para el nivel avanzado, mediante el menú de mandos también es posible efectuar algunas operaciones automáticas que sirven
para configurar el instrumento.
– En la tabla que sigue se indican las funciones disponibles en el menú de mandos, subdivididas en base al nivel de acceso necesario.
Cód.
MANDO
NIVEL ACCESO
Usuario
DESCRIPCIÓN
Avanzado
C.01
RESET HI-LO
l
l
Pone a cero los valores de pico HI y LO de todos los parámetros
C.02
PUESTA A CERO MÁX DEMAND
l
l
Pone a cero los valores Max demand de todos los parámetros
C.03
PUESTA A CERO ENERGÍAS PARCIALES
l
l
Pone a cero los contadores de energía parciales.
C.04
PUESTA A CERO CUENTAHORAS PARCIALES
l
l
Pone a cero los cuentahoras parciales
C.05
PUESTA A CERO CONTADORES
l
l
Pone a cero los contadores
C.06
PUESTA A CERO TARIFAS
l
l
Pone a cero los contadores tarifas
C.07
BORRADO ALARMAS
l
l
Borra las alarmas con memoria
C.08
RPUESTA A CERO LÍMITES
l
l
Puesta a cero valores de umbral con memoria
C.11
PUESTA A CERO ENERGÍAS TOTALES
l
Pone a cero los contadores de energía totales, parciales y tarifas.
C.12
PUESTA A CERO CUENTAHORAS TOTALES
l
Pone a cero los cuentahoras totales
C.13
PARÁMETROS PREDEFINIDOS
l
Restablece los valores predefinidos de fábrica para todos los parámetros
C.14
COPIA SEGURIDAD PARÁMETROS
l
Guarda una copia de seguridad (backup) de las configuraciones
C.15
RESTABLECIMIENTO PARÁMETROS
l
Recarga las configuraciones de la copia de seguridad
C.16
TEST CONEXIÓN
l
Realiza la prueba para verificar que la conexión del DMG sea correcta.
Véase capítulo Test conexión
– Una vez seleccionado el mando deseado, pulsar
para ejecutarlo. El instrumento solicitará una confirmación. Al pulsar nuevamente
mando.
– Para anular la ejecución de un mando seleccionado, pulsar el botón MENÚ.
– Para salir del menú mandos, pulsar MENÚ.
64
se ejecutará el
E
31100124
I271 I GB F E 01 13
TEST DE CONEXIÓN
– El test de conexión permite comprobar si la instalación del multímetro ha sido efectuada correctamente.
– Para poder efectuar el test, el multímetro tiene que colocarse en una instalación activa con las siguientes condiciones:
• sistema trifásico con todas las fases presentes (V > 50VAC L-N)
• corriente mínima circulante en cada fase > 1% del fondo de escala del TC configurado
• sentido positivo de las energías (es decir una instalación común donde la carga inductiva absorbe energía de la red de suministro)
– Para iniciar la ejecución del test, acceder al menú de mandos y seleccionar el mando apropiado en base a las instrucciones del capítulo menú de mandos.
– El test permite verificar las siguientes condiciones:
• lectura de las tres tensiones
• secuencia de las fases
• desequilibrio de las tensiones
• inversión de polaridad de uno o varios TC
• intercambio de fases entre tensiones/corrientes
– Si no se supera el test, en pantalla se visualiza la causa del error.
– Si en cambio se supera el test, la condición se guarda en la memoria no volátil y se presenta un mensaje de resultado positivo en la página Información.
1 - Secuencia de los controles
2 - Resultado del test
E
65
31100124
E
CARACTERÍSTICAS TÉCNICAS
Condiciones ambientales
Alimentación auxiliar
Tensión nominal Us ∂
I271 I GB F E 01 13
Límites de empleo
100 - 440V~
110 - 250V
Temperatura de funcionamiento
-20...+60°C
Temperatura de almacenamiento
-30...+80°C
90 - 484V~
93,5 - 300V
Humedad relativa
<80% (IEC/EN 60068-2-70)
Grado de contaminación máxima
2
Categoría de medición
III
Categoría de sobretensión
3
Altitud
≤2000m
Secuencia climática
Z/ABDM (IEC/EN 60068-2-61)
690V~ fase-fase
400V~ fase-neutro
Resistencia a los golpes
15g (IEC/EN 60068-2-27)
Resistencia a las vibraciones
0,7g (IEC/EN 60068-2-6)
Datos de empleo UL
600V~ fase-fase
347V~ fase-neutro
Aislamiento
Tensión nominal de aislamiento Ui
690V~
Campo de medición
20 - 830V~ fase-fase
10 - 480V~ fase-neutro
Tensión nominal soportada
de impulso Uimp
9,5kV
Campo de frecuencia
45 - 66Hz
Verdadero valor eficaz (TRMS)
Tensión de soportada a frecuencia
industrial
5,2kV
Tipo de medición
Modo de conexión
Línea monofásica, bifásica, trifásica con o sin neutro y
trifásica equilibrada
Frecuencia
45 - 66Hz
Potencia consumida/disipada
3,9VA 3,4W max
Tiempo de inmunidad a micro cortes
≥50ms
Entradas de tensión
Tipo de entrada
Tensión nominal Ue max
Trifásica + neutro
Entradas de corriente
Conexiones circuito alimentación/medida tensiones
Tipo de bornes
De tornillo (extraíbles)
N° terminales
4 para control tensión
2 para alimentación
Corriente nominal Ie
5A~
Campo de medición
0,010 - 6A~
Sección conductores (mín...máx)
0,2...2,5 mm2(24...12 AWG)
Tipo de entrada
Shunts alimentados con transformador de corriente
periférico (baja tensión) 5A máx.
Par de ajuste terminales
0,5 Nm (4.5 LBin)
Tipo de medición
Valor eficaz (RMS)
Tipo de bornes
De tornillo (fijos)
Sobrecarga permanente
+20% Ie
N° terminales
6 para conexiones TC externos
Intensidad termica de corta duración
50A por 1 segundo
Sección conductores (mín...máx)
0,2...4 mm2 (26...10 AWG)
Carga (por fase)
≤ 0,6W
Par de ajuste terminales
0,8 Nm (7 LBin)
Conexiones circuito medición corrientes
Caja
Precisión
Condiciones de medición
Temperatura
Material
Poliamida RAL 7035
+23°C ±2°C
Versión
Empotramiento según IEC61554
Tensión de fase
± 0,5% (50…480V~) ±0,5 digit
Grado de protección
Tensión compuesta
± 0,5% (80…830V~) ±0,5 digit
IP54 frente
IP20 caja y terminales
Corriente
± 0,5% (0,1…1,2In) ±0,5 digit
Peso
480g
Energía activa
Classe 1 (IEC/EN 62053-21)
Homologaciones y conformidad
Energía reactiva
Classe 2 (IEC/EN 62053-23)
Homologaciones
cULus
0,05%/°K per V, A, W
UL marking
Circuito alimentación/medición tensiones
Use 60°C/75°C copper (Cu) conductor only
AWG Range: 24 - 12 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 4.5lb.in
AWG Range: 26 - 10 AWG stranded or solid
Field Wiring Terminals Tightening Torque: 7lb.in
“For use on a flat surface of a Type 1 Enclosure”
Errores adicionales
Temperatura
Circuito medición corrientes
Conforme a normas
IEC/EN 61010-1, IEC/EN 61000-6-2, IEC/ EN 61000-6-4,
UL508, CSA C22.2 N°14
∂ Alimentación auxiliar conectada a una línea con tensión fase-neutro ≤300V.
66
E
TAC
– Repetir la operación con las cuatro pinzas.
– Si en el futuro fuera necesario desmontar el aparato, levantar la aleta central de las pinzas de manera que se suelte el milrayas, y luego hacerlas deslizar
hacia atrás hasta extraerlas por completo.
– Para efecuar las conexiones eléctricas remitirse a los esquemas de conexión del capítulo correspondiente y a las instrucciones de la tabla de características
técnicas.
– Una vez efectuadas las conexiones eléctricas es posible colocar los cubrebornes proporcionados con el equipamiento. Estos cubrebornes pueden precintarse
para impedir la adulteración del instrumento y el acceso a los terminales de conexión.
– Para colocar los cubrebornes, introducir los ganchos en el sitio correspondiente y ejercer una ligera presión hasta que queden asegurados. Prestar atención
a la combinación de la clema con el cubrebornes correspondiente.
– El precintado se logra introduciendo el hilo y el precinto en el anillo formado por los ángulos exteriores del cubrebornes.
DISPOSICIÓN TERMINALES
E
DIMENSIONES MECÁNICAS
53.2
99.5
96
19
92
92
96
31100124
I271 I GB F E 01 13
INSTALACIÓN
– DMG700 se instala mediante empotramiento, de conformidad con IEC 61554.
– Introducir el multímetro en la escotadura del panel, cerciorándose de que la junta quede bien colocada entre el panel y el marco del instrumento.
– Desde el interior del cuadro, colocar cada una de las pinzas de fijación en una de las dos guías laterales, presionando luego sobre la arista de la pinza de
manera que se enganche a presión también la segunda guía.
– Empujar la pinza hacia adelante haciendo presión sobre sus paredes laterales, haciéndolas deslizar a lo largo de las guías hasta que las aletas deformables
queden bien apretadas contra la superficie interna del panel.
61.5
67
31100124
ESQUEMAS DE CONEXIÓN
Conexión trifásica con o sin neutro
P01.07 = L1-L2-L3-N L1-L2-L3
Conexión bifásica
P01.07 = L1-N-L2
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
I271 I GB F E 01 13
N
CT2
L
O
A
D
L2
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
-A1
CURRENT
VOLTAGE
+
A2
AUX SUPPLY
Conexión monofásica
P01.07 = L1-N
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
VOLTAGE
Conexión trifásica equilibrada con o sin neutro
P01.07 = L1-L2-L3-N-BIL L1-L2-L3-BIL
CT1
CT1
L1
L1
L
O
A
D
N
L
O
A
D
L2
L3
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
V1 V2 V3 VN
S1 S2
I1
VOLTAGE
S1 S2
S1 S2
I2
I3
CURRENT
--
+
A1
A2
AUX SUPPLY
Conexión ARON trifásica sin neutro
P01.07 = L1-L2-L3
V1 V2 V3 VN
I1
L
O
A
D
CT2
L3
I3
L1
L2
CT3
L3
L
O
A
D
100...440VAC
110...250VDC
100...440VAC
110...250VDC
AUX SUPPLY
S1 S2
I2
CT1
CT1
L2
+
A2
S1 S2
CURRENT
Conexión ARON trifásica sin neutro
P01.07 = L1-L2-L3
L1
-A1
S1 S2
VOLTAGE
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
-A1
CURRENT
+
A2
AUX SUPPLY
V1 V2 V3 VN
S1 S2
S1 S2
S1 S2
I1
I2
I3
VOLTAGE
CURRENT
E
Conexión trifásica con neutro mediante TT
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3-N
Conexión trifásica sin neutro mediante TT
SET TV = P01.04, P01.05 e P01.06 - P01-07 = L1-L2-L3
CT1
CT1
L1
L1
CT2
L2
CT3
L3
L
O
A
D
CT2
L2
CT3
L3
N
100...440VAC
110...250VDC
-A1
+
A2
AUX SUPPLY
100...440VAC
110...250VDC
TV
V1 V2 V3 VN
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
NOTA
1. Fusibles aconsejados: Alimentación auxiliar y entrada de medida tensión: F1A (rápido)
2. Los terminales S2 están conectados internamente entre sí
68
--
A1
+
TV
V1 V2 V3 VN
A2
AUX SUPPLY
VOLTAGE
S1 S2
S1 S2
S1 S2
I1
I2
I3
CURRENT
L
O
A
D
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement