SC200 Handbook - NANA Power Inc
SC200 System Controller
Operation Handbook
Issue: IPN 997-00012-50G
Issue Date: May 2011
Eaton Corporation
Telecommunications Power Solutions
www.eaton.com/telecompower
[email protected]
The product discussed in this literature is subject to terms and conditions outlined in Eaton selling policies. The
sole source governing the rights and remedies of any purchaser of this equipment is the relevant Eaton selling
policy.
No warranties, express or implied, including warranties of fitness for a particular purpose or merchantability, or
warranties arising from course of dealing or usage of trade, are made regarding the information,
recommendations and descriptions contained herein.
In no event will Eaton be responsible to the purchaser or user in contract, in tort (including negligence), strict
liability or otherwise for any special, indirect, incidental or consequential damage or loss whatsoever, including but
not limited to damage or loss of use of equipment, plant or power system, cost of capital, loss of power, additional
expenses in the use of existing power facilities, or claims against the purchaser or user by its customers resulting
from the use of the information, recommendations and descriptions contained herein.
The information contained in this literature is subject to change without notice.
Subject to the right to use its equipment, Eaton Corporation does not convey any right, title or interest in its
intellectual property, including, without limitation, its patents, copyrights and know-how.
No part of this literature may be reproduced or transmitted in any form, by any means or for any purpose other
than the Purchaser’s personal use, without the express written permission of Eaton Corporation.
®
®
TM
TM
TM
TM
TM
Eaton , Matrix, Powerware , Intergy , CellSure , SiteSure , PowerManagerII and DCTools are trade
names, trademarks, and/or service marks of Eaton Corporation or its subsidiaries and affiliates. Unless otherwise
noted, brands, product names, trademarks or registered trademarks are the property of their respective holders.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
About This Guide


About This Guide
Scope
This guide covers operation of the SC200 system controller with embedded software Version 3.0
or later.

See SC200 Identity Information on page 14 to determine the version of the embedded software.
Audience
This guide is intended for use by:

Installers competent in:




installing and commissioning dc power systems
safe working practices for ac and dc powered equipment
the relevant local electrical safety regulations and wiring standards
Operators and maintenance staff competent in:


operation of dc power systems
safe working practices for ac and dc powered equipment
Related Information

PowerManagerII Online Help

DCTools Online Help

SiteSure-3G Installation and Operation Guide – IPN 997-00012-51

CellSure Installation Guide – IPN 997-00012-20
Reporting Problems with this Guide
Please use this email address to report any problems you find in this guide:
Eaton DC Product Marketing Communications
EMAIL:
[email protected]
For Further Information and Technical Assistance
For further information and technical assistance see Worldwide Support on page 115.
Third Party Software
Software code in the SC200 system controller includes the following third party software:
Eric Young is the author of the parts of the library
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
i
SC200 Handbook
ii
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Table of Contents


Table of Contents
About This Guide
Scope ........................................................................................................................................... i
Audience..................................................................................................................................... i
Related Information .................................................................................................................. i
Reporting Problems with this Guide ...................................................................................... i
For Further Information and Technical Assistance .............................................................. i
Third Party Software................................................................................................................. i
Chapter 1
General Description
Overview ................................................................................................................................... 1
SC200 System Controller ......................................................................................................... 2
Input/Output Board ................................................................................................................ 2
Connections............................................................................................................................... 3
Compatible Software ............................................................................................................... 4
Chapter 2
SC200 Operation
Overview ................................................................................................................................... 5
Starting the SC200 .................................................................................................................... 6
Main Screen Shortcut Keys............................................................................................................. 6
SC200 Operation using the Keypad and Screen................................................................... 6
Soft Keys ........................................................................................................................................... 7
Navigation Keys .............................................................................................................................. 7
Main Menu Navigation .................................................................................................................. 8
Sub-menu Tabs ................................................................................................................................ 9
Changing a Configuration Setting using the Keypad ............................................................... 10
Keypad Access Security ................................................................................................................ 10
Display Settings ............................................................................................................................. 11
Main Screen Parameters ............................................................................................................... 11
Display Time-out ........................................................................................................................... 12
Alarm Indicators ............................................................................................................................ 12
SC200 Operation Using a PC/Laptop ................................................................................. 13
SC200 Identity Information ................................................................................................... 14
SC200 Internal Clock .............................................................................................................. 14
Language Options .................................................................................................................. 16
Language selection ........................................................................................................................ 16
SC200 Firmware Upgrade ..................................................................................................... 17
Configuration File .................................................................................................................. 17
Backup and Restore ............................................................................................................... 18
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
iii
SC200 Handbook
Chapter 3
System Operation
Overview .................................................................................................................................. 19
Voltage Control ....................................................................................................................... 20
Float Voltage ................................................................................................................................... 20
Active Voltage Control (AVC) ..................................................................................................... 21
Battery Current Limit (BCL) ......................................................................................................... 21
Battery Test ..................................................................................................................................... 22
Equalize ........................................................................................................................................... 24
Fast Charge ..................................................................................................................................... 25
Temperature Compensation ......................................................................................................... 27
Rectifiers ................................................................................................................................... 28
Identify a Rectifier.......................................................................................................................... 29
Rectifier Comms Lost Alarm ........................................................................................................ 30
Rectifier Shutdown ........................................................................................................................ 30
Low Voltage Disconnect (LVD) ............................................................................................ 32
Typical LVD Arrangements.......................................................................................................... 33
LVD Operation ............................................................................................................................... 34
LVD Setup ....................................................................................................................................... 35
Smart Alarm Disconnect ............................................................................................................... 38
Alarms ...................................................................................................................................... 39
Types of Alarms ............................................................................................................................. 39
Active Alarm Indications .............................................................................................................. 40
Common Alarm Parameters ......................................................................................................... 41
System Alarm Configuration ....................................................................................................... 42
System Overload Alarm ................................................................................................................ 42
Smart Alarms .................................................................................................................................. 44
Batteries .................................................................................................................................... 49
Batteries Configuration ................................................................................................................. 50
Battery Mid-point Monitoring (MPM) ........................................................................................ 50
Battery Time Remaining ............................................................................................................... 54
Reverse Battery Detection ............................................................................................................. 58
Generator Control Option ...................................................................................................... 60
Configuration ................................................................................................................................. 61
Input/Output (I/O) ................................................................................................................ 62
Identify an I/O Board.................................................................................................................... 62
Analog System Values ................................................................................................................... 63
Analog Inputs ................................................................................................................................. 63
System States .................................................................................................................................. 65
Digital Inputs .................................................................................................................................. 66
Digital Outputs............................................................................................................................... 67
Data Logging ........................................................................................................................... 68
Event Log ........................................................................................................................................ 68
Data Log .......................................................................................................................................... 69
PC Log ............................................................................................................................................. 70
iv
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Table of Contents
Chapter 4
Communications
Overview ................................................................................................................................. 71
Communications Options ..................................................................................................... 72
Direct (USB) Communications ............................................................................................. 72
Ethernet Communications .................................................................................................... 72
DCTools or PowerManagerII Communications Setup (if required) ....................................... 73
Communication via Web Browser .............................................................................................. 74
Communication via a Network Management System using SNMP....................................... 75
Modbus-TCP Communications ................................................................................................... 77
Serial (RS232) Communications ........................................................................................... 78
PSTN Modem Communications .................................................................................................. 78
GSM Modem Communications ................................................................................................... 80
Serial Server.................................................................................................................................... 83
Communications Security ..................................................................................................... 83
Serial Communications (USB/RS232/Ethernet) Security ........................................................ 84
Web Access Security ..................................................................................................................... 85
CSP ........................................................................................................................................... 86
Chapter 5
Maintenance
Overview ................................................................................................................................. 87
Troubleshooting ..................................................................................................................... 88
Replacing the System Controller or I/O Board.................................................................. 92
Appendix A
Specifications
SC200 system controller ........................................................................................................ 93
IOBGP-00, -01 I/O Board ...................................................................................................... 93
Appendix B
Appendix C
Alarm Descriptions
Connector Pin-outs
System Controller Connector Pin-outs .............................................................................. 101
I/O Board (IOBGP-00, -01) Connector Pin-outs............................................................... 103
Appendix D
Appendix E
System Event Types
SC200 Mappings
I/O Board Mapping ............................................................................................................. 109
Digital Output (Relay) Activation...................................................................................... 111
Equipment Incident Report
Worldwide Support
Index
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
v
SC200 Handbook
vi
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Chapter 1
General Description


C
h
a
General Description
p
t
e
r
1
Overview
Topic
Page
SC200 System Controller
2
Input/Output Board
2
Connections
3
Compatible Software
4
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
1
SC200 Handbook
SC200 System Controller
The SC200 system controller is an advanced control and monitoring solution which provides a
full suite of communications options, including built-in Ethernet interface, Web server, and
SNMP agent.
Alarm notifications may be by SNMP traps, SMS text messaging, dial-out to PowerManagerII
remote monitoring software, or relay contact closures.











Power on LED (green)
Minor alarm LED (yellow)
Critical/Major alarm LED (red)
Color LCD
Soft keys (2)
Navigation keys (4)
USB 1.1 connector (12Mb/s)
Retaining screw
Power and system
communications connector
RS232 connector
Ethernet connector and
status LEDs
The SC200 is supplied pre-configured with either a default configuration file, or with one
factory customized for a particular application. Some configuration file changes can be made
with the keypad, or all settings can be changed via a PC connected to the USB interface (see
details on page 17).
For connector pin-outs see details on page 101. See Troubleshooting on page 88 for details of
SC200 alarm LEDs.
Input/Output Board
The input/output (I/O) board provides the I/O interfaces and connections for the SC200
system controller.
The I/O board includes a range of sense inputs for dc power system control and monitoring. It
also allows real time data collection from building services and other external devices, and relay
outputs for alarm signals or control of external devices.
2
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
General Description
The I/O functions are:
Sensors:
Current - 3, Bus voltage - 1, Temperature - 2, Battery Mid-point - 4
Input/Output:
Digital inputs: 4 pre-defined system functions, 6 user-defined
Relay outputs: 6 (one also used as Monitor OK alarm)
LVD contactor outputs: 2








For input and output specifications see details on page 93. For connector pin-outs see details on
page 103.
Bus voltage sense input - XH9
Power/Comms OK LED (green)
Digital inputs D1-D6 (6 user defined) - XH15A,
XH15B
Digital (relay) outputs RY1-RY6 (6) - XH16-XH21
LVD contactor 2 status LED (green)
LVD contactor 2 connector - XH5
LVD contactor 1 status LED (green)








LVD contactor 1 connector - XH4
LVD power input connector - XH8
Power and RXP comms input - YH11
Current sense inputs (3) - XH6
Temperature sense inputs (2) - XH7
Battery Mid-point Monitoring sense inputs - XH12
DC power system digital inputs (4 pre-defined:
Load Fuse Fail, Battery Fuse Fail, AC Distribution
Fan Fail, AC Distribution MOV Fail) - YH3
See Troubleshooting on page 88 for details of I/O board LED signals.
Connections
The following diagram shows the connections between the SC200, the I/O board, the other dc
power system components and external devices.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
3
SC200 Handbook










SC200 system controller
I/O board
Voltage feed module
USB communications
Ethernet communications
RS232 communications
Digital relay outputs (6) to external devices and/or
alarm indication system

Digital inputs (6) from external voltage-free switches
or relay contacts

Connection to additional I/O board(s) and/or
SiteSure-3G I/O module(s)

Connection to dc common bus

Connection to dc live bus
Communications to rectifiers
DC power system digital inputs (Load Fuse Fail,
Battery Fuse Fail, AC Distribution Fan Fail, AC
Distribution MOV Fail)

Connections for battery mid-points (4)






Connection for temperature sensors (2)
Connection for current sensors (3)
Connection for LVD contactor and auxiliary switch
Connection for LVD contactor and auxiliary switch
Bus voltage sense and LVD power connections
I/O and system controller power and RXP comms
connections
For connector pin-outs see details on page 103. For input and output specifications see details on
page 93.
Compatible Software
The following software is compatible with the SC200 system controller:
4

DCTools Configuration Software. Latest version is available free from
www.powerquality.eaton.com/downloads.

PowerManagerII Remote Control and Monitoring Software. Contact your Eaton dc product
supplier for further information (see Worldwide Support on page 115).

Recommended web browsers: Microsoft Internet Explorer 8 (IE6 is compatible but with
reduced performance), Mozilla Firefox 3.0.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Chapter 2
SC200 Operation


C
h
SC200 Operation
a
p
t
e
r
2
Overview
Topic
Page
Starting the SC200
6
SC200 Operation using the Keypad and Screen
6
SC200 Operation Using a PC/Laptop
13
SC200 Identity Information
14
SC200 Internal Clock
14
Language Options
16
SC200 Firmware Upgrade
17
Configuration File
17
Backup and Restore
18
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
5
SC200 Handbook
Starting the SC200
When dc power is applied to the SC200 (via the RXP connector YS11) the start-up sequence
begins.


Approx.
120s

Start-up screen
Main screen
Menu screen
The values shown are
configurable, see details on page
11. All active Critical, Major,
Minor and Warning alarms are
displayed.
See navigation details on page 8.
If Logon is required see Keypad
Access Security on page 10.
Main Screen Shortcut Keys
Key
Function
From the Main Screen go directly to the Alarms screen.
From the Main Screen go directly to the Settings screen.
From the Main Screen go directly to the Control Processes screen.
From the Main Screen go directly to the Analogs screen.
SC200 Operation using the Keypad and Screen






6
LCD
Soft key 1 label
Soft key 1
Navigation keys (Up - Down Left - Right)
Soft key 2
Soft key 2 label
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200 Operation
Soft Keys
The function of the soft keys is indicated by the corresponding labels on the LCD screen. The
following table shows the most common labels and key functions.
Label
Key function
Go to menu screen. See details on page 8.
Go back to parent menu screen.
Go to sub-menu or configuration screen*.
Save a new configuration setting*.
Ignore a new configuration setting*.
* See Changing a Configuration Setting on page 10.
Navigation Keys
Key
Function

Move up/down in the menu screen. See details on page 8.

Move up/down in a list (hold to go to the top or bottom of the list).

Select options in a configuration screen.

Increase/decrease a value in a configuration screen.

Move left/right in the menu screen. See details on page 8.

Move left/right between tabs in Rectifiers, Alarms, Battery or Settings
menus.

Move left/right between segments of a multiple segment value in a
configuration screen.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
7
SC200 Handbook
Main Menu Navigation
At each menu screen press Enter to access the associated configuration menu screen(s).
These menus have multiple configuration menu screens. See details on page 9.
8
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200 Operation
Sub-menu Tabs
The following menu screens have sub-menus accessed via tabs at the top of the screens.
Rectifiers Sub-menus

List of registered
rectifiers.
Rectifier settings.
Alarms Sub-menus

List of active alarms.
Alarm settings.
Battery Sub-menus

Battery settings.
LVD settings.
Mid-point monitoring
settings.
Settings Sub-menus

SC200 settings.
Registered
input/output boards.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
9
SC200 Handbook
Changing a Configuration Setting using the Keypad
For the configuration settings that can be changed using the keypad, the keys have the
following functions.
Press to change the setting or activate a control process.
Press to change the value. Hold key to change at a faster rate.
Use these keys for values with multiple segments (for example an IP address).
Press to save the new value.
Or
Press to leave the value unchanged.
Keypad Access Security
This feature prevents accidental or unauthorized changes to settings from the SC200 keypad.
All access to change an SC200's settings will be lost if:


All communications are disabled (see S3P Access on page 84 and HTTP/HTTPS
Access on page 85), and

Keypad access is Read Only, or PIN Protected and the keypad access PIN is lost.
The SC200 will continue to function, but no configuration changes can be made.
Contact your Eaton dc product supplier or Eaton for advice (see Worldwide Support
on page 115).
► To use DCTools/Web to enable/disable keypad access

In DCTools/Web go to Communications > Front Panel.

Set Access to:



Unprotected - keypad access is allowed to view and change parameters, or
Read Only - keypad access is allowed to view parameters only, or
PIN Protected - keypad access is allowed to view and change parameters if the correct 4digit number is typed in the Access PIN field. Otherwise, Read Only access is allowed.
► To use the SC200 when access is set to PIN Protected

At the Main Screen press Menu. The Logon screen appears.

If the Access PIN is not known then press Skip to use the SC200 with Read Only access.

If the Access PIN is known:



10
Use the Left and Right keys to access each digit position. Use the Up and Down keys to
change the digits.
When the correct digits are entered, press Logon.
Keypad access will return to PIN Protected mode when the display returns to the Main
Screen.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200 Operation
Display Settings
► To change the display contrast

Use the keypad to go to: Settings > Setup > Contrast > Edit.
► To change the display language

See Language Options on page 16.
► To change the display orientation (horizontal/vertical)
Either:

Use the keypad to go to: Settings > Setup > Orientation > Edit.

Select the required orientation (vertical, horizontal-left or horizontal-right). Press Save.
Or:

In DCTools/Web go to: Configuration > Communications > Front Panel.

Select the required orientation (vertical, horizontal-left or horizontal-right). Click Save
Changes.

The functions of the navigations keys also change to suit the new display orientation.
Main Screen Parameters
The parameters displayed on the SC200 main screen are configurable.
To be updated.
(default parameters are Bus Voltage and Rectifier Current).


Top value
Bottom value
► To change the parameters displayed on the main screen
Either:



Use the keypad to go to: Settings > Setup > Top Value and/or Bottom Value > Edit.
Select the required parameters (see Note 1) for Top Value and/or Bottom Value.
If Analog Input is selected then also select a value for Top Value Index and/or Bottom
Value Index. See Note 2.
Or:



In DCTools/Web go to: Configuration > Communications > Front Panel.
Select the required parameter (see Note 1) for Top Value and/or Bottom Value.
If Analog Input is selected then also select a value for Top Value Index and/or Bottom
Value Index. See Note 2.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
11
SC200 Handbook
Notes:
1
The parameters available are: Bus Voltage, Rectifier Current, Load Current, Battery Current,
Battery Temperature, Load Power, System Power, or Analog Input.
2
If Analog Input is selected then also select a value for Top Value Index and/or Bottom Value
Index. This value is the number of the AI from the Analog Inputs table. To view the table in
DCTools/Web go to: Analog Inputs.
Display Time-out
If there is no keypad activity for 60 seconds the display will go back to the main screen.
Alarm Indicators
Visual indicators
Power on LED (green)
Minor Alarm LED (yellow)
Critical/Major Alarm LED (red)
???
The system value cannot be displayed because of a failed, disconnected or
unconfigured sensor.
Audible indicator

One beep – indicates an invalid key press

Three beeps every 2 seconds – refer to the alert message on the display

One beep every 2 seconds – Minor alarm is active

Continuous sound – Critical/Major alarm is active

Critical/Major alarms always override Minor alarms.
► To stop the audible indicator

Press any key

The audible indicator will restart at the next active alarm or alert message.
► To enable/disable the audible alarm indicator
Either:

Use the keypad to go to: Alarms > Alarm Settings > Audible Alarms > Edit.

In DCTools/Web go to: Alarms > Alarm Configuration.
Or:

12
When Disabled, the audible indicator will still indicate an invalid key press.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200 Operation
SC200 Operation Using a PC/Laptop
DCTools is configuration software for editing a system controller's configuration file (on-line)
and monitoring the operation of Eaton's dc power systems. It is available free from
www.powerquality.eaton.com/downloads.
DCTools can be run on a PC/laptop connected to the SC200's USB port.

DCTools can also be run on a remote PC/laptop connected to the SC200's RS232 serial port (via a
modem) or Ethernet port. For remote PC/laptop connection details see Communications Options
on page 72.
Before you start you will need:

The latest version of DCTools available from www.powerquality.eaton.com/downloads.

A PC/laptop with USB port and USB A/B cable (RadioShack 55010997, Jaycar WC7700, or
equivalent).
► To connect a PC/laptop to the SC200:
1 Download the latest version of DCTools from www.powerquality.eaton.com/downloads.
2
Install DCTools on the PC/laptop.
3
Connect a USB A/B cable from a USB port on the PC/laptop to the USB port on the SC200.

4
DCTools will now connect to the SC200.

5
See the diagram on page 2 for location of the USB port.
If connection is not successful refer to DCTools Help (press F1) or Troubleshooting on page
88.
For details of the SC200 control and monitoring functions available via DCTools see System
Operation on page 19.

For help using DCTools press F1.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
13
SC200 Handbook
SC200 Identity Information
The following identity information is stored in the SC200.
Parameter
Description
Where to find:
Serial Number
The SC200 serial number (factory set). SC200: Info
Software Version The version of the embedded
(App Version)
software in the SC200 (factory set).
DCTools/Web:
Configuration > Identity
If required, the following site specific information can be stored in the SC200 to assist site
management.
Parameter
Description
Where to find:
System
Manufacturer
The manufacturer of the dc power
system.
System Type
The dc power system model number.
System Serial
Number
The dc power system serial number.
System Location
Location of dc power system at the
site.
Site Name
Name of the site.
Site Address
Address of the site.
Site Notes
Any notes relevant to site access,
location or other matters.
Contact
Contact name, phone number, and so
on.
Configuration
Name
Reference name of the configuration
file in the SC200.
DCTools/Web:
Configuration > Identity
SC200 Internal Clock
The SC200 has a battery-backed clock for time stamping of log entries and Control Processes.
The time and date is factory set. It can also be set manually using a web browser or can be
synchronized (either to a PC clock using DCTools or to an SNTP reference time server).
14
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200 Operation
► To view the SC200 time
Either:

Use the keypad to go to: Info.

This time is set to Universal Coordinated Time (UTC). DCTools, Web and PowerManagerII
convert local PC time to/from UTC for the SC200. For practical purposes UTC is equivalent
to Greenwich Mean Time (GMT).
Or:

In DCTools go to: Configuration > Identity.

This time is set to the SC200 time adjusted to the time zone set in the PC.
Or:

In Web go to: Configuration > Time.

This time is set to the SC200 time adjusted to the time zone set in the PC.
► To set the time
1 Connect to the SC200 via a web browser. (See Ethernet Communications on page 72.)
2
Go to Configuration > Time.
3
Click on the time-date field to select the text.
4
Select the time or date text to be changed and type the correct time/date.
5
Press Enter on the keyboard. Then select Apply in the Changes window.
Time Synchronization
If required, the SC200 time can be synchronized either to the internal time of a PC or laptop, or
to a reference time server using SNTP protocol (SC200 must have access to the server).
► To synchronize the SC200 time using DCTools or PowerManagerII
1 Ensure the time on the PC is correct before synchronizing.

PowerManagerII can be set to automatically synchronize SC200 clocks.
2
Connect to the SC200 with DCTools/PowerManagerII. (See Communications Options on page
72.)
3
Go to Configuration >Identity > Time Synchronization
4
Click Synchronize to synchronize the SC200 time to the PC/laptop time.

DCTools, Web and PowerManagerII convert local PC time to/from UTC for the SC200.
► To synchronize the SC200 time using SNTP

For more information on SNTP, including a list of public SNTP servers, visit www.ntp.org
http://www.ntp.org.

Ensure that your network has an internal SNTP server or allows access to an external server. It
may be necessary to configure access through your network's firewall.
1
Connect to the SC200 via DCTools/Web.
2
Either:
In DCTools go to Configuration > Configuration > SNTP, or
In Web go to Configuration > Time > SNTP.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
15
SC200 Handbook
3
Set the following parameters:

Primary Address
IP address of primary SNTP server.
Backup Address
IP address of backup SNTP server.
UDP Port
Assigned by the time server administrator.
Poll Interval
The time between synchronizations.
The time will update a few seconds after any SNTP parameter change.
Language Options
The SC200 system controller language default is English. Text on the LCD and web pages (see
details on page 74) can be shown in other languages by loading the appropriate Translation File
(SC200-xx-Vyyy.icp) into the SC200.
Contact Eaton for available Translation Files (see Worldwide Support on page 115).

This process does not change the language in DCTools.
► To add a new SC200 display/web page language:
1 Obtain the appropriate Translation File (SC200-xx-Vyyy.icp) from Eaton.
2
Save the file.
3
Connect to the SC200 via an Ethernet connection. See Communications Options on page 72.
4
Open a web browser and browse to the SC200 IP address.
5
Go to Tools > Firmware Upgrade.
6
Click on Browse and select the Translation File (SC200-xx-Vyyy.icp).
7
Click on Next then follow the prompts to add the language.
Language selection
An SC200 can hold multiple language files and any of these can be selected for the LCD and
Web pages.
► To see which languages are loaded into an SC200
Either:

On the SC200 keypad go to: Settings > Language > Edit.

Connect to the SC200 via an Ethernet connection. See Communications Options on page
72.
On the Log On web page, there is a flag icon for each language option available.
Or:

► To select a new language for the Web pages

On the Log On web page, click on the flag icon for the language you require.

16
The web pages will change to this language.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200 Operation
► To select a new language for the SC200 display
Either:


On the SC200 keypad go to: Settings > Language > Edit.
Select the required language and press Save.
Or:





In DCTools/Web go to Communications > Front Panel.
Type the two letter language code in the Language Code field.
This code is the "xx" in the file name of the Translation File (SC200-xx-Vyyy.icp). For
example: zh = Chinese. Clear the Language Code field (blank entry) to revert to English.
Click Apply Changes. The display language will change.
The message "Waiting for database to become available for update ..." may display for a few
seconds.
If an incorrect or unavailable language code is used the display language will remain/revert to
English.
SC200 Firmware Upgrade
If required, the embedded software (firmware) in the SC200 can be upgraded from a PC/laptop
via a web browser.
► To use a web browser for a Firmware Upgrade
1 Connect to the SC200 via a web browser. (For details see Ethernet Communications on
page 72.)
2
Check the SC200 internal clock shows the correct time. If necessary set the correct time. See
SC200 Internal Clock on page 14.
3
Go to Tools.
4
Select Firmware Upgrade: Launch.
5
Select the file (*.icp). Click Next, then click Proceed.
Configuration File
The operational settings of the dc power system are stored in a configuration file loaded into the
SC200 system controller.
The SC200 is supplied pre-loaded with a configuration file. If this configuration file has been
customized for the site then no further configuration changes will be necessary.
Otherwise, it is important that the settings of this configuration file are checked and changed as
required for site-specific conditions. In particular, settings that may affect the performance and
life expectancy of the battery must be checked and set according to the battery manufacturer’s
recommendations.
Some settings in the configuration file can be edited using the system controller's keypad (see
details on page 6), or all settings can be edited using a PC/laptop with DCTools/Web (see
details on page 13) or remotely, see Communications Options on page 72.
The configuration file settings in the SC200 can be saved to (Backup) or loaded from (Restore) a
PC/laptop using DCTools/Web. See Backup and Restore on page 18.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
17
SC200 Handbook
Backup and Restore
The configuration file settings in the SC200 can be saved to (Backup) or loaded from (Restore) a
PC/laptop using DCTools/Web.
Backup and Restore can be used to:

Load a standard (master) configuration file into an SC200 for customization.

Copy a customized configuration file from one SC200 to others (at similar sites).

Save a copy of a customized configuration file. This is recommended in case the SC200 has
to be replaced.
► To use DCTools for Backup and Restore
1 Connect to the SC200 with DCTools. See Communications Options on page 72.
2
In DCTools go to File > ICE Backup/Restore and follow the prompts.

The saved file does not include site specific settings including Site Identity, IP Address, S3P
Address, battery characterization data.
► To use a web browser for Backup
1 Connect to the SC200 via a web browser. For details see Ethernet Communications on page
72.
2
Go to Tools.
3
Select Backup Tool.
4
Select the file type:


5
System Snapshot (*.dcs): Configuration file including site specific settings.
Configuration (*.dcc): Configuration file without site specific settings - Site Identity, IP
Address, S3P Address, battery characterization data).
Click Proceed to Backup the configuration.
► To use a web browser for Restore
1 Connect to the SC200 via a web browser. For details see Ethernet Communications on page
72.
2
Go to Tools.
3
Select Restore Tool.
4
Select the file type:



5
18
System Snapshot (*.dcs): Configuration file including site specific settings.
Configuration (*.dcc): Configuration file without site specific settings - Site Identity, IP
Address, S3P Address, battery characterization data).
Fragment (*.dcf): Restore part of a configuration file (such as battery characterization
data).
Click Next, and then select a file name to Restore a configuration.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Chapter 3
System Operation


C
h
System Operation
a
p
t
e
r
3
Overview
Topic
Page
Voltage Control
20
Rectifiers
28
Low Voltage Disconnect (LVD)
32
Alarms
39
Batteries
49
Generator Control Option
60
Input/Output (I/O)
62
Data Logging
68
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
19
SC200 Handbook
Voltage Control
The output voltage of the rectifiers is controlled by a number of control processes. The
following diagram shows the various control processes, measured values and operating values
that determine the rectifier output voltage.

If ac fails then any active control process stops. No control process can start until the ac supply is
restored.
Float Voltage
Configuration
Set the following parameter.
Parameter
Description
Where to find:
Float Voltage
Set to the voltage required to maintain optimum
battery charge (at the nominal ambient
temperature*) as specified by the battery
manufacturer. The bus voltage may be adjusted
above or below this value by the System Control
Processes.
SC200: Control Processes >
Voltage Control > Float
Voltage


20
*This is the same as the Reference
Temperature used by Temperature
Compensation. See details on page 27.
DCTools/Web:
Control Processes > Voltage
Control
The system voltage is limited by maximum and minimum values. The values are viewable in
DCTools/Web at Control Processes > Voltage Control. These values are not configurable.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Active Voltage Control (AVC)
Active Voltage Control maintains a constant float voltage under varying load current by
monitoring the bus voltage and adjusting the rectifier output voltage to compensate for any
voltage drop. This prevents undercharging the batteries during high load demand.
► To enable Active Voltage Control

Use the SC200 keypad to go to: Control Processes > Voltage Control > AVC.
Or, in DCTools/Web go to: Control Processes > Voltage Control > Active Voltage Control.


Active Voltage Control is normally enabled. Only disable if there are particular reasons.
Information
The following information is available about AVC.
Parameter
Description
Where to find:
State
Indicates if AVC is active or inactive.
Target Voltage
AVC will set the Base Voltage to attempt to
maintain the bus voltage to this value.
Voltage Offset
The difference between the Base Voltage and the
Target Voltage.
DCTools/Web:
Control Processes > Active
Voltage Control
Battery Current Limit (BCL)
Battery Current Limit automatically limits the battery recharge current to:

Prevent excessive battery charge current in under-loaded systems

Minimize gas release in VRLA batteries

Reduce the load on a standby generator.
Two current limit values can be set (both are a percentage of the C10 rating of the battery):
Battery Current Limit (Normal Limit): BCL value for use when utility ac is available.
Engine Run Limit (optional):

BCL value for use when ac is supplied by a standby
generator. This reduces the load on the generator
and allows a smaller generator to be used.
Engine Run Limit is activated by a signal from an ac standby generator.
► To enable BCL

Use the SC200 keypad to go to: Control Processes > Battery Current Limit.

Or, in DCTools/Web go to: Control Processes > Battery Current Limit.
► To activate Engine Run BCL

Connect a voltage free relay contact (that will operate when the standby generator starts) to
a Digital Input.

In DCTools/Web go to Digital Inputs.

Configure the selected Digital Input and set Function to Engine Run.

In DCTools/Web go to Control Processes > Battery Current Limit and set the Engine Run
Limit.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
21
SC200 Handbook
Information
The following information is available about BCL.
Parameter
Description
Where to find:
State
Indicates if BCL is active or inactive.
SC200: Control Processes >
Battery Current Limit.
DCTools/Web:
Control Processes > Battery
Current Limit
Engine Run State
Indicates if Engine Run BCL is active.
DCTools/Web:
The bus voltage adjustment made by Battery
Control Processes > Battery
Current Limit is applied to the Operating
Current Limit
Voltage to produce the Target Voltage. Target
Voltage is used as the input to the AVC function.
Voltage Offset
Configuration
Set the following parameters.
Parameter
Description
Where to find:
Battery Capacity
Set to the rated 10 hour capacity of the installed
battery strings. Zero means no battery is
installed.
SC200: Battery > Battery >
Battery Capacity
Current Limit
BCL maintains the battery current below this
value, which is a percentage of the installed C10
Battery Capacity.
Engine Run Limit
The Battery Current Limit setting when Engine
Run is active. BCL maintains the battery current
below this value when the engine run digital
input is active (engine run is enabled). This limit
is expressed as a percentage of the installed C10
Battery Capacity.
DCTools/Web: Batteries
DCTools/Web: Control
Processes > Battery Current
Limit
Battery Test
Battery Test is a preventative maintenance tool that monitors the discharge capabilities to
ensure that the condition of the battery has not deteriorated over time.
The SC200 temporarily reduces the output voltage of the rectifiers to just below the bus voltage
for a set duration. The battery then supplies power to the load. A battery test passes if the
battery voltage remains above a predetermined level for the duration of the test.
Battery Tests can be scheduled to occur at regular intervals, and/or can be started/stopped
manually, and/or can be started by an external relay contact or switch.

Battery Test does NOT function during a Fast Charge or Equalize, or during the lock-out period
after an ac supply failure.

If a Digital Input has the function "Start Battery Test" then a Battery Test will start when the
Digital Input becomes active.
► To enable Battery Test (or to start or stop a test manually)

Use the SC200 keypad to go to: Control Processes > Battery Test.

22
Or, in DCTools/Web go to: Control Processes > Battery Test
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
► To use an external relay contact to activate a Battery Test (optional)

Connect a voltage free relay contact or switch to any Digital Input.

In DCTools/Web go to Digital Inputs.

Configure the selected Digital Input and set Function to Start Battery Test.
Information
The following information is available about Battery Test.
Parameter
Description
State
Indicates if Battery Test is disabled, locked-out, active
or inactive.
Next Start Time
The start time of the next scheduled Battery Test.

Where to find:
Time shown on SC200 is UTC. Time on PC
running DCTools/Web is local time. See SC200
SC200: Control Processes >
Internal Clock on page 14.
Battery Test
The time to the end of the currently active Battery Test. DCTools/Web: Control
Processes > Battery Test
Battery Test
The time remaining until a Battery Test can be started.
Lockout Remaining Battery Tests cannot be started within 48 hours of an ac
supply failure.
Remaining Time
Voltage Offset
The adjustment to the bus voltage being applied due to
the Battery Test. While a Battery Test is running, the
rectifiers are turned down to force the battery to carry
the load.
Configuration
Set the following parameters.
Parameter
Description
First Start Time
The date and time that the first battery test cycle will
occur. Subsequent tests will occur at every Battery Test
Interval after that.
Interval
The time between scheduled battery tests. The interval
period begins at the start of a battery test. Zero disables
scheduled battery tests. Zero also disables the 48 hour SC200: Control Processes >
lockout following an ac supply failure, allowing an
Battery Test
immediate manual test.
DCTools/Web: Control
Processes > Battery Test
The maximum time a Battery Test process will be
active. The battery test will pass if the bus voltage
remains above the Battery Test Termination Voltage
for the duration of the test.
Test Duration
Termination
Voltage
Where to find:
If the bus voltages drops below this value during a
Battery Test, then the test fails.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
23
SC200 Handbook
Equalize
Equalize charges batteries at a higher voltage after they have been fully charged to ensure that
all individual cell voltages are the same, that electrolyte is distributed evenly, and that sulfate
crystal buildup on the plates is reduced.
Equalize can be scheduled to occur at regular intervals and/or can be started/stopped
manually.


Refer to the battery manufacturer's instructions before using Equalize.
If a Digital Input has the function "Start Equalize" then a manual equalize cycle will start when
the Digital Input becomes active.
If Equalize cannot start at the scheduled time (for example when there is no ac supply) then its
state will be Pending and it will start as soon as conditions allow. Use Stop Equalize to cancel a
Pending Equalize.
► To enable Equalize (or to start or stop Equalize manually)

Use the SC200 keypad to go to: Control Processes > Equalize.

Or, in DCTools/Web go to: Control Processes > Equalize.
► To use an external relay contact to activate an Equalize (optional)

Connect a voltage free relay contact or switch to any Digital Input.

In DCTools/Web go to: Digital Inputs.

Configure the selected Digital Input and set Function to Start Equalize.
Information
The following information is available about Equalize.
Parameter
Description
State
Indicates if Equalize is Disabled, Active, Inactive
or Pending.
Next Start Time
The start time of the next scheduled Equalize.

24
Where to find:
Time shown on SC200 is UTC. Time on
PC running DCTools/Web is local time.
See SC200 Internal Clock on page 14.
Remaining Time
The time to the end of the currently active
Equalize.
Voltage Offset
The adjustment to the bus voltage being applied
due to the Equalize.
SC200: Control Processes >
Equalize
DCTools/Web: Control
Processes > Equalize
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Configuration
Set the following parameters.
Parameter
Description
Where to find:
First Start Time
The date and time that the first scheduled
Equalize will occur. Subsequent Equalize will
occur at every Equalize Interval after that.
Interval
The time between scheduled Equalize. The
interval period begins at the start of an Equalize.
Zero disables scheduled Equalizes.
Duration
The duration of a scheduled Equalize. Use the
value recommended by the battery
manufacturer.
Equalize Voltage
The bus voltage maintained during an Equalize
cycle. Use the value recommended by the battery
manufacturer. The bus voltage is further
adjusted by Temperature Compensation.

SC200: Control Processes >
Equalize
DCTools/Web: Control
Processes > Equalize
Equalize may also be used to trigger the Generator Enable alarm. See details on page 60.
Fast Charge
After an ac supply failure, Fast Charge automatically increases the float voltage of the power
system to recharge the batteries as quickly as possible.
Enable Fast Charge if the site experiences frequent ac supply failures.

Fast Charge does NOT function during a Battery Test, Equalize or if the battery current sensor
fails.

If Fast Charge is used then Battery Current Limit (BCL) should also be used. See Battery Current
Limit on page 21 for details.
If Fast Charge cannot start at the scheduled time (for example when there is no ac supply) then
its state will be Pending and it will start as soon as conditions allow. Use Stop Fast Charge to
cancel a Pending Fast Charge.
► To enable Fast Charge (or to stop Fast Charge manually)

Use the SC200 keypad to go to: Control Processes > Fast Charge.

Or, in DCTools/Web go to: Control Processes > Fast Charge.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
25
SC200 Handbook
Information
The following information is available about Fast Charge.
Parameter
Description
State
Indicates if Fast Charge is Disabled, Active,
Inactive or Pending.
Ah Discharged
The current level of battery discharge. A Fast
Charge cycle is started if this value is above the
Ah Threshold.

Where to find:
See also Reset Battery State.
Maximum Time
Remaining
The maximum time to the end of the currently
active Fast Charge.
Voltage Offset
The adjustment to the bus voltage being applied
due to the Fast Charge.
SC200: Control Processes >
Fast Charge
DCTools/Web: Control
Processes > Fast Charge
Configuration
Set the following parameters.
Parameter
Description
Voltage Threshold
If the bus voltage drops below this value during
an ac supply failure, then Fast Charge starts when
the ac supply is restored. Fast charge can also be
started based on the Ah Threshold.
Ah Threshold
If Ah Discharged exceeds this value during an ac
supply failure, then Fast Charge starts when the
ac supply is restored. The threshold is given as a
percentage of installed C10 battery capacity. Fast
charge can also be started based on the Voltage
Threshold.
Maximum
Duration
The maximum duration of a Fast Charge as
recommended by the battery manufacturer.
Recharge
Percentage (%)
The ratio of ampere-hours recharged to the
ampere-hours discharged. Fast Charge stops
either when the Ah recharged equals the Ah
discharged x Fast Charge Recharge Percentage, or
after Maximum Duration.
Fast Charge
Voltage
The bus voltage maintained during a Fast Charge.
Battery Capacity
The rated 10 hour capacity of the installed
battery strings. Zero means no battery is
installed.

26
Where to find:
SC200: Control Processes >
Fast Charge
DCTools/Web: Control
Processes > Fast Charge
Fast Charge may also be used to trigger the Generator Enable alarm. See details on page 60.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Temperature Compensation
As the ambient temperature of a battery drops (or rises) the voltage required to maintain full
charge increases (or decreases). Temperature Compensation automatically varies the float
voltage to cancel the effects of changing temperature.
Enable Temperature Compensation for optimum battery life and battery capacity over a wider
temperature range.

Temperature Compensation does NOT function during a Battery Test.
► To enable Temperature Compensation

Use the SC200 keypad to go to: Control Processes > Temp. Compensation > Enable.

Or, in DCTools/Web go to: Control Processes > Temperature Compensation.
Information
The following information is available about Temperature Compensation.
Parameter
Description
Where to find:
State
Indicates if Temperature Compensation is active
or inactive.
Voltage Offset
The adjustment to the bus voltage being applied
due to the Temperature Compensation. Offset is
zero when the battery temperature equals the
reference temperature.
SC200: Control Processes >
Temp. Compensation >
Enable
Battery
Temperature
The temperature measured by the battery
temperature sensor.
DCTools/Web: Control
Processes > Temperature
Compensation
SC200: Analogs > Battery
Temperature
DCTools/Web: Batteries
Configuration
Set the following parameters.
Parameter
Description
Where to find:
Cells Per String
The number of 2V cells per battery string (for
example: 24 in a 48V nominal system).
SC200: Battery > Battery
DCTools/Web: Batteries
Slope
Bus voltage adjustment rate. Use the value
recommended by the battery manufacturer.
Reference Temp
The temperature where no voltage adjustment is
applied. Refer also to Float Voltage on page 20.
SC200: Control Processes >
Temp. Compensation >
Enable
Upper Limit
No additional voltage adjustment is made above
this temperature.
Lower Limit
No additional voltage adjustment is made below
this temperature.
DCTools/Web: Control
Processes > Temperature
Compensation
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
27
SC200 Handbook
Rectifiers
The SC200 registers all rectifier modules as they are inserted into the dc power system.
Information
The following information is available from rectifiers.
Parameter
Description
State
Registered - communicating with the SC200.
Un-registered - there is a rectifier compatibility or
communications problem.
Serial Number
(S/N)
Rectifier serial number.
AC Voltage
The ac voltage measured by the rectifier (single-phase
rectifiers only).
Phase Voltages
The ac phase voltages measured by the rectifier (threephase rectifiers only).
Voltage
Rectifier's dc output voltage.
Current
Rectifier's output current.
Heatsink Temp
The measured rectifier heatsink temperature.
Max Power (Limit)
Rectifier's maximum output power (factory set).
Power
Rectifier output power as a percentage of Max. Power
Limit.
Max Current Limit
The maximum current limit value of the rectifier.

28
Where to find:
Adjust Rectifier Current Limit to set a lower
operating current limit.
Status
Information about rectifier alarms.
Type
Rectifier manufacturer's model number.
Software Version
Version of rectifier embedded software.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200: Rectifiers > Enter
(Use Left and Right keys to
scroll to other rectifiers)
DCTools/Web: Rectifiers
DCTools/Web: Rectifiers
SC200: Rectifiers > Enter
(Use Left and Right keys to
scroll to other rectifiers)
System Operation
Common Rectifier Configuration
The following parameters (common to all rectifiers) can be configured.
Parameter
Description
Where to find:
Rectifier (DC)
Current Limit
The output current limit of the rectifier. If set to zero,
then the output current limit is maximum.
AC Rectifier
Current Limit
The input current limit of the rectifier. If set to zero,
then the input current limit is maximum.
Rectifier Current
Share
Current Share ensures that the total output power of
the power system is evenly shared between all
rectifiers.
SC200: Rectifiers > Rect.
Settings
DCTools/Web: Rectifiers
Set to Enabled unless there is a specific reason to
disable.
OVSD Set Point
Over Voltage Shut Down. A rectifier will shut down if
its output voltage exceeds this value.

Recommended value is 59.2V for 48V nominal
systems, 28.6V for 24V nominal systems.
Ramp Up Slope
The ramp-up slope of the rectifier, as a percentage of
the rectifier rated current.
Enable Rectifier
Shutdown
Set to Enabled to allow rectifier shut down.
Start Up Delay
The delay from ac turn-on before the rectifier output
turns on.


DCTools/Web: Rectifiers
Load Based Rectifier Shutdown is not available
with APR48-3G, EPR48-3G, APR24-3G and
CR48-3G rectifiers.
See Voltage Control on page 20 for details of the rectifier's output voltage control.
Identify a Rectifier
The rectifier's registration number does not correspond to a physical position in the dc power
system.
► To identify a rectifier
Either:

On SC200 keypad go to: Rectifiers > Rectifier number. Press Enter.


The rectifier details screen appears. Use
to scroll to other rectifiers.
All LEDs on the selected rectifier will flash for 60 seconds, or press Esc to stop.
Or:

In DCTools/Web go to: Configuration > RXP > RXP Devices.

DCTools: select Identify Device or Web: click on Start Identifying.

All LEDs on the selected rectifier will flash for 60 seconds.

Rectifier serial numbers are printed on a label on the front of each rectifier.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
29
SC200 Handbook
Rectifier Comms Lost Alarm
When a rectifier is removed (or a fault interrupts rectifier communications), the SC200 will
display an alert message and sound an alert alarm (if Audible Alarms are enabled). After the
Alarm Recognition Period, a Rectifier Comms Lost alarm will activate.

A Multiple Rectifier Comms Lost alarm will activate (after the Alarm Recognition Period) if
more than one rectifier is affected.
► To prevent a Rectifier Comms Lost alarm when a rectifier is removed
Press any key within the Alarm Recognition Period, to cancel the alert.
Rectifier Shutdown
Manual Rectifier Shutdown
► To shut down a rectifier

In DCTools/Web go to: Rectifiers > Configuration.

Set Rectifier Shutdown to Enabled.

In the Rectifiers table select the Shutdown check box (DCTools) or click Shutdown (Web).

The rectifier will shut down and the yellow LED will be on.

The SC200 will restart any shutdown rectifiers if: ac has failed, or more than one rectifier has
failed, or the bus voltage is below the Low Load threshold, or Rectifier Shutdown is disabled.

Shutdown rectifiers will restart if Load Based Rectifier Shutdown is enabled.
Rectifier Restart
► To restart all shutdown rectifiers

Use the SC200 keypad to go to: Rectifiers > Rect. Settings (tab) > Restart All Rectifiers.
Or

In DCTools/Web go to: Rectifiers. Click Restart All Rectifiers.
► To restart individual rectifiers

In DCTools/Web go to: Rectifiers.

For each rectifier clear the Shutdown check box (DCTools) or click Startup (Web).
The rectifier(s) will then resume normal operation.

30
The SC200 will restart any shutdown rectifiers if: ac has failed, or more than one rectifier has
failed, or the bus voltage is below the Low Load threshold, or Rectifier Shutdown is disabled.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Load Based Rectifier Shutdown

Load Based Rectifier Shutdown is not available with APR48-3G, EPR48-3G, APR24-3G and
CR48-3G rectifiers.
If Load Based Rectifier Shutdown (LBRS) is enabled then the SC200 automatically shuts down
rectifiers when the total load current is significantly less than the total rectifier capacity.
This raises the average load on the remaining rectifiers which will then operate at a higher
efficiency. This results in a decrease in system power consumption.
The run time of all rectifiers is recorded and balanced to ensure even aging.
The SC200 will progressively restart rectifiers if the load increases.


Rectifiers shut down by LBRS will have the yellow LED on.

The SC200 will automatically restart all rectifiers if ac supply has failed, or more than one rectifier
has failed, or the bus voltage is below the Low Load threshold, or Battery Test / Equalize / Fast
Charge are active.
At least two rectifiers will always be on to maintain N+1 rectifier redundancy. Therefore, LBRS
has no effect in dc power systems with only one or two rectifiers.
► To enable Load Based Rectifier Shutdown

Use the SC200 keypad to go to: Control Processes > Load Based Rectifier Shutdown.


Or, in DCTools/Web go to: Rectifiers > Load Based Rectifier Shutdown
Ensure that Rectifier Start Up Delay is less than 30 seconds. See information on page 29. LBRS
will not function correctly if the start up delay is more than 30 seconds.
LBRS Info SC200
Information
The following information is available about Load Based Rectifier Shutdown.
Parameter
Description
Where to find:
State
Indicates if LBRS is Enabled or Disabled.
SC200: Control Processes >
LBRS
DCTools/Web: Rectifiers >
Load Based Rectifier
Shutdown
Run Time
The run time of each rectifier
DCTools/Web: Rectifiers
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
31
SC200 Handbook
Configuration
The following parameters must be configured to set Load Based Rectifier Shutdown.
Parameter
Description
Reset Run Time
Sets the run time of all rectifiers to zero.
High Threshold
LBRS restarts all rectifiers if the load is more
than this percentage of the total rectifier capacity.
Typical: 80%.
Low Threshold
LBRS shuts down rectifiers if the load is less than SC200: Control Processes >
this percentage of the total rectifier capacity.
LBRS
Typical: 60%.
DCTools/Web: Rectifiers >
The time interval in minutes that the SC200 Load Based Rectifier
will cycle rectifiers when the LBRS process Shutdown
Interval
Where to find:
is active.
Restart All
Rectifiers
Press to temporarily restart all rectifiers shut
down by LBRS.

Disable LBRS to permanently restart all
rectifiers.
Low Voltage Disconnect (LVD)
Low Voltage Disconnects may be connected either as load disconnect or battery disconnect
depending on the dc power system model. They have two purposes:

to protect a VRLA battery from deep discharge and premature failure, and/or

to reduce the load on a battery under discharge so that high priority equipment operates
for a longer time after an ac supply failure.
The SC200 has 16 independent LVD control channels (LVD 1 to LVD 16). Each channel can
control one or more of up to 16 contactors, with coil voltages from 12V to 48V nominal.

There are two contactor connectors on an IOBGP input/output board. Additional contactors are
controlled by additional IOBGP-01 input/output boards. If required, refer to the dc power system
Installation and Operation Guide for details on how to connect additional IOBGP-01 input/output
boards to the SC200.
LVD Disconnect Modes
The LVD control channels can have any combination of the following modes of operation:
1
Voltage Based Disconnect: The LVD control channel will disconnect its contactor(s) based
on the bus voltage.
2
AC Timer Based Disconnect: The LVD control channel will disconnect its contactor(s) after
a specified period of ac supply failure.
3
Smart Alarm Disconnect: The LVD control channel will disconnect its contactor(s)
according to the state of a specified Smart Alarm. See Smart Alarm Disconnect on page 38.

32
CAUTION: An unnecessary LVD disconnection may occur if the Smart Alarm uses a sensor
or other input device which becomes faulty or disconnected.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
If Chained to Previous is enabled, the LVD control channel will only disconnect its contactor(s) if
one of its disconnect conditions is True, and the preceding control channel has been
disconnected for the Recognition Time.

Chained to Previous does not apply to LVD 1.
LVD Default and Custom Configuration
If factory-fitted in the dc power system, the LVD contactors will be characterized and the LVD
control channels will have default configuration settings for Voltage Based Disconnect. Custom
configuration will only be necessary if:

contactors are connected to the dc power system on site (see LVD Characterization on page
34 and LVD Setup on page 35)

different disconnect conditions are required (see LVD Configuration on page 37).
Typical LVD Arrangements
The simplest use of an LVD is a single battery disconnect contactor.
The following diagram shows a typical arrangement of two LVDs. This arrangement allows
lower priority loads to be disconnected first (contactor controlled by control channel LVD 1),
either at a specified battery voltage or a specified time interval after an ac supply failure. This
then prolongs battery power for the highest priority loads (contactor controlled by control
channel LVD 2). The battery will be disconnected when the battery voltage reaches its
minimum preset voltage.

Contactor controlled by
LVD 1 - low priority load
disconnect (disconnects
first).

Contactor controlled by
LVD 2 - battery
disconnect (only
disconnects after LVD 1)

Connections to high
priority loads (for example
transmission equipment).

Connections to low
priority loads.

Connection to the SC200
system controller via the
I/O board.
More complex arrangements with up to 16 contactors and a selection of disconnection criteria,
are possible with the SC200 system controller. The exact arrangement(s) used in a particular
Eaton dc power system will be described in the Installation and Operation Guide.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
33
SC200 Handbook
Characterization
If auxiliary contacts are fitted to the LVD contactor(s)*, then the LVD Characterization process
determines the optimum operating voltages to suit the contactor(s) coil voltage. These values
are stored in the SC200 and on the I/O board.
An LVD Characterization Error alarm will be activated if the SC200 detects that the
characterization values stored in the SC200 and on the I/O board are different. This happens
when:

The SC200 is replaced. To clear the alarm, on the SC200 select Use IOB Values.

The I/O Board is replaced. To clear the alarm, on the SC200 select Use SC Values.

Both the SC200 and the I/O Board are replaced. In this case, re-characterize the
contactor(s).

When a contactor is re-characterized it will disconnect and re-connect several times. Refer to
Maintenance in the dc power system Installation and Operation Guide for full instructions.
Factory-fitted contactors will be characterized at the factory. If an existing contactor is replaced,
characterize the new contactor from the SC200.

In this case, there will be no LVD Characterization Error alarm.
LVD Operation
► To allow access to LVD functions from the SC200 keypad

In DCTools/Web go to: Control Processes > LVD.


Select the Allow Front Panel LVD Control check box.
If the check box is cleared LVD functions can only be accessed using DCTools/Web.
► To manually connect or disconnect an LVD control channel

Use the SC200 keypad to go to: Battery > LVDs > LVD 1 - LVD 16 > Details > Manual Control.

Select Connect or Disconnect to connect or disconnect the channel (and all mapped
contactors).


34
The contactor(s) will remain in the selected state until another state or Auto is selected.
Select Auto to return the LVD control channel to automatic operation.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Information
The following information is available about LVD control channels and contactors.
Parameter
Description
Where to find:
LVD Control
Channel State
Connected: all of the channel's disconnect
conditions are false. All mapped contactors are
connected (contacts closed).
Disconnected: one of the channel's disconnect
conditions is true. All mapped contactors are
disconnected (contacts open).
Manual: The LVD is under manual control from
the SC200 keypad (see previous section).
No Contactors: there are no contactors mapped
to this channel.
Idle: The LVD has not yet connected or
disconnected.
LVD Control
Channel Inhibited
Indicates if the LVD cannot change state due to
the Inhibit Period.
Contactor State
Disabled: contactor cannot be operated
SC200: Battery > LVDs
DCTools/Web: Control
Processes > LVD
Connected: contactor is connected (contacts
closed)
Disconnected: contactor is disconnected
(contacts open)
Failed: contactor is not connected to the I/O
board or is faulty.
Conflict: two contactors are mapped to the same
I/O board connector.
Not Characterized: the contactor must be
characterized (see details on page 34).
LVD Setup
Use the following procedures to enable or add an LVD control channel.

For SC200s upgraded from software v2.57 or earlier only:
The software upgrade preserves the original LVD1 and LVD2 alarms (for backwards
compatibility). However, these alarms will not operate with LVD 3 or higher. Before adding LVD
3, 4 and so on., enable and configure the generic LVD alarms (LVD Manual, LVD Fail, LVD
Disconnected, LVD Characterization) and disable the specific LVD1 and LVD2 alarms.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
35
SC200 Handbook
► To Enable (Add) an LVD control channel using the SC200 keypad

Control and configuration of LVDs and contactors is only available from the SC200 keypad if
Allow Front Panel LVD Control is TRUE. See LVD Operation on page 34.
1
Go to: Battery > LVDs.
2
If there are no LVD control channels (LVD 1, LVD 2, ...) listed then go to Step 4.
3
For each LVD control channel select Details. Note the contactors operated by each channel.

The contactor numbers (1-1, 1-2, ...) indicate the existing IOB Number - IOB Connector
Number combinations.
4
Go to: Battery > LVDs > Add LVD.
5
From the list of registered I/O boards, select a board connected to a contactor to be
operated by this LVD control channel. Select Next.
6
For IOBGP I/O boards (see Input/Output Board on page 2) select:


1, if the contactor is connected to XH4
2, if the contactor is connected to XH5.
Warning: Do not select an existing IOB Number - IOB Connector Number combination (see
Step 3). This will cause a conflict.
7
Select Next.
8
Select contactor type:


9
Normally Open if contacts are open when coil voltage is zero.
Normally Closed if contacts are closed when coil voltage is zero.
Characterize the contactor (see LVD Characterization on page 34).
10 To add additional contactors to the LVD control channel, go to Battery > LVDs > LVD x >
Add Contactor. Repeat Steps 5-9.
► To Enable an LVD control channel using DCTools/Web
1 In DCTools/Web go to: Control Processes > LVD. Expand the Logical LVDs table:
2
Select a spare LVD control channel and configure as required. See LVD Configuration on
page 37.
3
Expand the Physical Contactors table.
4
Select and configure the contactor(s) to be operated by the LVD control channel. See
Contactor Configuration on page 38.
General Configuration Settings
36
Parameter
Description
Where to find:
Inhibit Period
The minimum time an LVD stays connected or
SC200: Battery > LVDs
disconnected before it can change state. Does not DCTools/Web: Control
apply to manual operation.
Processes > LVD
Allow Front Panel
LVD Control
Disables LVD control from the system controller
front panel.
DCTools/Web: Control
Processes > LVD
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Control Channel Configuration
Parameter
Description
Where to find:
Voltage Based
Disconnect
If Enabled, the LVD will disconnect if the bus
voltage has been below the Disconnect Voltage for
the Recognition Time and reconnect if the bus
voltage has been above the Reconnect Voltage for
the Recognition Time.
Disconnect Voltage See Voltage Based Disconnect.
Reconnect Voltage* See Voltage Based Disconnect.
Recognition Time
See Voltage Based Disconnect and Chained To
Previous.
AC Timer Based
Disconnect
If Enabled, then during an ac supply failure the
LVD will disconnect after the AC Timer Delay,
even if the Disconnect Voltage has not been
reached.
AC Timer Delay
See AC Timer Based Disconnect.
SC200: Battery > LVDs >
LVD x > Settings
DCTools/Web: Control
Processes > LVD > Logical
LVDs
Smart Alarm Based If Enabled, the LVD will disconnect when the
Disconnect
Smart Alarm specified by Smart Alarm Index
becomes active.

See Smart Alarm Disconnect on page 38.
Smart Alarm Index
See Smart Alarm Based Disconnect.
Chained To
Previous
(Chaining)
If Enabled, the LVD channel will only disconnect
if one of its disconnect conditions is true and the
preceding LVD channel has been disconnected
for the Recognition Time. This applies in reverse
when reconnecting.


Does not apply to LVD 1.
* If the LVD channel operates contactors used as a load-disconnect, ensure the Reconnect Voltage
is set higher than the expected open-circuit recovery voltage of the discharged batteries.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
37
SC200 Handbook
Contactor Configuration
Parameter
Description
LVD Num
Set to the number of the LVD control channel
that will operate this contactor.

Enable
Where to find:
In DCTools/Web, number is from first
column of the Logical LVDs table.
Set to Enabled for this contactor to be operated
(connected and disconnected).

IOB Number
(On IOB)
If a connected contactor (contacts closed)
is Disabled, it will remain connected
unless the coil is disconnected from the
I/O board or the I/O board loses power.
SC200: See LVD Setup on
page 35.
DCTools/Web: Control
Processes > LVD > Physical
Contactors
Set to the number of the I/O board from the I/O
Board to Serial Number Mapping table.

IOB LVD Number
(LVD Connector)
For IOBGP I/O boards, set to:

1, if the contactor is connected to XH4

2, if the contactor is connected to XH5.

Type
See I/O Board Mapping on page 109.
See Input/Output Board on page 2.
Set according to the type of contactor:

Normally Open if contacts are open
when coil voltage is zero.

Normally Closed if contacts are closed
when coil voltage is zero.
SC200: Battery > LVDs >
LVD x > Contactors (x-1, x-2,
...) > Edit
DCTools/Web: Control
Processes > LVD > Physical
Contactors
Smart Alarm Disconnect
An LVD control channel can be set to disconnect if a specified Smart Alarm becomes active. For
example, a battery LVD can be set to disconnect if the battery temperature is too high, or a load
LVD can be set to disconnect when Ah Discharged exceeds a defined value.

An unnecessary LVD disconnect may occur if Smart Alarm Disconnect uses a sensor
which becomes faulty or disconnected.

38
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
► To configure a Smart Alarm Disconnect
1 In DCTools/Web go to: Alarms > Smart Alarms. Configure a Smart Alarm as described on
page 45.
2
Note the SA Number (first column of the Smart Alarm States table).
3
Go to: Control Processes > LVD.
4
For the required LVD control channel:


Set Smart Alarm Index to the SA Number (first column of the Smart Alarm States table).
Set Smart Alarm based Disconnect to Enabled.
The LVD control channel will disconnect its contactor(s) if the Smart Alarm becomes active.

Except, if Chained to Previous is enabled then the preceding LVD control channel must be
disconnected first.
Alarms
An SC200 supplied with a standard configuration file (see details on page 17) has a standard set
of alarms configured and enabled. This will be sufficient for standard dc power system
operation.
For specific alarm arrangements all SC200 alarms can be individually enabled or disabled and
are configurable.
Types of Alarms
The SC200 provides five types of alarms:
Alarm type
Description
Configuration
System alarms
Generated by the operating values of dc power See details on page 42.
system (voltages, currents, temperatures, and
so on) and the operation of power system
modules (rectifiers, circuit breakers, fuses, and
so on). The SC200 system alarms are listed in
Alarm Descriptions on page 97.
Analog Input
(AI) High alarms
Activated when the input value of an AI is
above the alarm threshold.
See details on page 63.
Analog Input
(AI) Low alarms
Activated when the input value of an AI is
below the alarm threshold.
See details on page 63.
Digital Input (DI) Activated when a DI is in its active state.
alarms
See details on page 66.
Smart Alarms
See details on page 44.
Software simulation of logic gates to allow the
logical combination of other alarms, time
schedules and/or system values.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
39
SC200 Handbook
Active Alarm Indications
All alarms have a configured Severity:
Critical
Major
Minor
Warning
Control
The Severity determines how an active alarm is indicated:
Severity
Alarm indications
Details
SC200 Major alarm LED will turn on.
See details on page 12.
SC200 Minor alarm LED will turn on.
See details on page 12.
If the SC200 audible indicator is enabled, it will
sound until a key is pressed.
See details on page 12.
The alarm name and severity icon will be
displayed on the SC200 main screen.
See details on page 6.
The Event Log will record the alarm activation.
See details on page 68.
If configured, an SMS text message will be sent to
one or more cell phones.
See details on page 82.
If configured, PowerManagerII control and
monitoring software will be notified by modem
callback. PowerManagerII can initiate various
actions when it receives an alarm notification.
Refer to the
PowerManagerII online
Help.
In DCTools/Web (if connected), the alarm name
and severity icon will be displayed in the Alarms
list on the System page.
See DCTools screen on
page 13, Web screen on
page 74.
If configured, an SNMP Trap will be sent to a
network management system (NMS).
See details on page 75.
If configured, a note will be displayed on the
SC200 and included in the SNMP trap (if used).
Refer to the alarm's
configuration details.
If configured, one or two digital outputs (relays)
will be operated.
Refer to the alarm's
configuration details.
►
► To view a list of active alarms

Use the SC200 keypad to go to: Alarms.

40
Or, in DCTools/Web go to System.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Common Alarm Parameters
The following parameters are common to multiple alarms.
Parameter
Description
Where to find:
Enable Audible
Alarm Indication
Enable or disable the audible alarm indicator.
Alarm Recognition
Period
All alarms (except those listed below) are
activated only after the alarm condition is
present for this period.

These alarms have individual recognition SC200: Alarms > Alarm
Settings > Global Settings
periods: AC Fail, System Overload,
DCTools/Web: Alarms >
Generator Fail.

These alarms do not have recognition
periods: Battery Test Fail, Configuration
Error, Generator Enable, Missing
Hardware, Standby Mode, String Fail,
Unknown Hardware, Unmapped IOB
Found, and all LVD alarms.
Alarm Configuration
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
41
SC200 Handbook
System Alarm Configuration
The following system alarm parameters can be configured.
Parameter
Description
Where to find:
Severity
Set to the required alarm priority. This
determines how the alarm is indicated. See
details on page 40.
If set to Disabled then the alarm will not activate.
DO Mapping A
If required, select a digital output (relay) that
will be operated when the alarm is active.
DO Mapping B
If required, select a second digital output (relay)
that will be operated when the alarm is active.
Send Trap
An SNMP Trap will be sent for this alarm, if Send
Trap is True and the alarm's Severity matches the DCTools/Web: Alarms >
Alarm States
setting of the SNMP Trap Level (see details on
page 76).
Notes
Type any required description. When the alarm
is active the text will be displayed on the SC200
and included in the SNMP trap (if used).
Recognition Period
The following alarms have individual
recognition periods: AC Fail, System Overload,
Generator Fail.

High or Low
Threshold
SC200: Alarms > Alarm
Settings > System Alarm.
Select an alarm.

Use
to scroll
to other alarms.
All other system alarms either use the
standard Alarm Recognition Period or do
not have a recognition period. See details
on page 41.
SC200: Alarms > Alarm
The following alarms have a high or low
threshold: High Float, Low Float, High Load,
Low Load, Battery Temperature High, Battery
Temperature Low.
Settings > System Alarm.
Select an alarm.
The alarm will be activated if the measured
value is above or below this value, as applicable.
DCTools/Web: Alarms >
Alarm Configuration
Enable High Float
Tracking
If enabled, the High Float alarm threshold will
be increased when the operating voltage is
increased by a voltage control process.
Enable Low Float
Tracking
If enabled, the Low Float alarm threshold will be
decreased when the operating voltage is
decreased by a voltage control process.

Use
to scroll
to other alarms.
The following system alarms have particular configuration settings:

System Overload alarm. See details on page 42.

Battery Mid-point monitoring. See details on page 50.
System Overload Alarm
The System Overload alarm activates if the total system load exceeds a percentage of the
installed rectifier capacity for a specified period. This indicates that additional rectifiers need to
be installed. This is useful at sites where there is ongoing installation of additional load
equipment.
42
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
► To enable System Overload

In DCTools/Web go to: Alarms > Alarm States. Enable and configure System Overload alarm.
See System Alarm Configuration on page 42.

Go to: Alarms > Alarm Configuration. Configure the System Overload alarm parameters. See
details on page 43.
Information
The following information is available about System Overload.
Parameter
Description
Where to find:
System Power
The output power of the system as a percentage
of the total nominal power the system is capable
of supplying.
SC200: Analogs
DCTools/Web: Analog
Inputs
Configuration
Set the following parameters.
Parameter
Description
Where to find:
System Overload
alarm parameters
See System Alarm Configuration on page 42.
DCTools/Web: Alarms >
Alarm States
System Overload
Threshold
The System Overload alarm activates if the load
is above this threshold continuously for the
System Overload Recognition Period. Measured as a
percentage of total rectifier capacity.
System Overload
Recognition Period
The System Overload alarm activates if the load
is above the threshold continuously for this time.
It is normally set to several hours so that the
alarm does not operate during a normal battery
recharge.
System Overload
Type
The System Overload alarm can be based on
either Total Capacity or Redundancy.
If the system overload type is based on Total
Capacity then the alarm will trigger when the
load is above the System Overload Threshold for
the System Overload Recognition Period.
DCTools/Web: Alarms >
Alarm Configuration
If the system overload type is Redundancy then
the alarm will trigger when the load is above the
total current capacity of the system minus the
current capacity of the largest rectifier, for the
System Overload Recognition Period.

An alarm will always activate if the
system overload type is set to
Redundancy when there is only one
rectifier installed.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
43
SC200 Handbook
Smart Alarms
Smart Alarms are a software simulation of logic gates to allow the logical combination of other
alarms, time schedules and/or system values. Up to 32 Smart Alarms can be configured.
A single Smart Alarm is the equivalent of a multi-input AND, OR or XOR logic gate. More
complex logic arrangements are created by using one Smart Alarm as an input into another. For
example:
Two input AND gate:
SAx = Sa AND Sb
Three input OR gate:
SAy = Sa OR Sb OR Sc
Multi-gate logic:
SAz = SAx OR NOT Sd

One input is Smart Alarm SAx (output
from another gate). The other input is
negated. This is available with Alarm
Sources only.
Key:
SAx, SAy, SAz are Smart Alarms (entered in the Smart Alarms table).
Sa, Sb, Sc, Sd are the Sources (entered in the Alarm Sources, Schedule Sources or System Value
Sources tables).
Smart Alarms also have optional activation and deactivation delays. When activated they can
cause alarm indications (unless Severity is set to Control) and can activate one or two digital
outputs (in the same way as other alarms).

44
For more information and application examples contact your Eaton DC product supplier and
request Eaton Application Note AN0106, SC200 Version 3 Advanced Alarm Features.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Sources
The inputs to Smart Alarms are called Sources.
Sources can be any combination of:

Alarm Sources (up to 64):
System Alarms, Analog Input High alarms, Analog Input Low alarms, Digital Input
alarms, Other Smart Alarms


Time Schedules (up to 20)


Alarm Sources can either use the alarm’s recognition period,or be triggered immediately.
Alarm Sources can also be triggered either when the source alarm becomes active or when it
becomes inactive.
Time schedules can repeat for a fixed number of times, or indefinitely.
System Values (up to 20):
Bus Voltage, Rectifier Current, Load Current, Battery Current, Battery Temperature, Load
Power, System Power, Ah Discharged, Number Of Rectifiers Failed, Number Of Rectifiers
Comms Lost.

System Value Sources are active either when the system value is above or below a defined
threshold value.
Configuration
Information
The following information is available about Smart Alarms and Sources.
Parameter
Description
Where to find:
Smart Alarm State
The present state of the Smart Alarm. If Enabled
and active, this will be the alarm's Severity. If
Disabled, or Enabled but inactive, the state is
shown as "-".
DCTools/Web: Alarms >
Smart Alarms > Smart
Alarm States
Source Triggered
The present state of the source:
= Enabled and active
"-" = Disabled, or Enabled but inactive.
= There is an invalid dependency, or the
source Index is invalid.
Next Activation
The date and time this schedule will next
activate.
Schedule End
The date and time this schedule will activate for
the last time.
DCTools/Web: Alarms >
Smart Alarms > Sources
DCTools/Web: Alarms >
Smart Alarms > Schedule
Sources
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
45
SC200 Handbook
► To create a Smart Alarm
1 Determine the equivalent logic gate arrangement for the Smart Alarm.

2
Smart Alarms can be regarded as logic gates. Each gate (AND, OR or XOR) is an entry in
the Smart Alarm States table. The gate inputs are entries in the Alarm Sources, Scheduled
Sources or System Value Sources tables.
Configure the Smart Alarm(s):


In DCTools/Web go to: Alarms > Smart Alarms.
Expand the Smart Alarm States table and configure a Smart Alarm and configure the
following parameters.

To change a setting, double-click and select from drop down list or edit the text.
Parameter
Setting
Name
Type the name of the alarm.
Severity
Set to the required alarm priority. This determines how the alarm is indicated.
See details on page 40.
If set to Disabled then the alarm will not activate.
46
Operator
Determines how the sources will be logically combined (AND, OR or XOR).
Recognition Period
The alarm will activate when the logical combination of the sources has been
true for this period.
Deactivation
Recognition Period
The alarm will deactivate when the logical combination of the sources has been
false for this period.
Digital Output
Mapping A
If required, select a relay that will be operated when the alarm is active.
Digital Output
Mapping B
If required, select a second relay that will be operated when the alarm is active.
Send Trap
An SNMP Trap will be sent for this alarm, if Send Trap is True and the alarm's
Severity matches the setting of the SNMP Trap Level (see details on page 76).
Trap Origin
Sent in the Trap Origin field.
Group
Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online
help for details.
Notes
Type any required description. When the alarm is active the text will be
displayed on the SC200 and included in the SNMP trap (if used).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
► To configure the Source(s) for a Smart Alarm
Configure the following parameters for the source(s) for each Smart Alarm.

Every Smart Alarm must have at least one Source assigned to it.
Alarm Sources
Parameter
Setting
SA Num
Type the number (from the Smart Alarm States table) of the Smart Alarm for
which this source is an input.
Status
Set to Enabled.
Logic
Set to either:
Trigger When
Source Is

EQUAL - the Alarm Source will become active when the source
alarm is Triggered or Active.

NOT - the Alarm Source will become active when the source alarm
is Inactive.
Set to either:

Triggered - the Alarm Source will become active immediately
when the conditions for this alarm become true (or false when Logic
is set to NOT). The alarm does not have to be Enabled.


Do not use Triggered when Type is set to Smart Alarm.
Active - the Alarm Source will become active when the alarm
becomes active (or inactive when Logic is set to NOT), after the
alarm recognition time, and only if the alarm is Enabled.
Type
Set to the appropriate source type: System Alarm, Analog Input High, Analog
Input Low, DI, Smart Alarm.
Index
Identify the alarm:

Source Type = System Alarm:
DCTools - type the alarm number from the Alarm States table.
Web - select the name of the system alarm from the list.

Source Type = AI High/AI Low - type the alarm number from the
Analog Input High Alarms or the Analog Input Low Alarms table.

Source Type = DI - type the alarm number from the Digital Input
Alarms table.

Source Type = Smart Alarm - type the alarm number from the Smart
Alarm States table.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
47
SC200 Handbook
Scheduled Sources
Parameter
Setting
SA Num
Type the number (from the Smart Alarm States table) of the Smart Alarm for
which this source is an input.
Status
Set to Enabled.
First Date / Time
Set to the date and time for the first activation of the Schedule Source.
Duration
Set the time the Schedule Source will be active.
Interval
Set the time between activations.
Number of
Activations
Set the number of activations.

If set to zero then there is no limit to the number of activations.
System Value Sources
Parameter
Setting
SA Num
Type the number (from the Smart Alarm States table) of the Smart Alarm for
which this source is an input.
Status
Set to Enabled.
System Value
Set to the required value (Bus Voltage, Rectifier Current, Load Current, Battery
Current, Battery Temperature, Load Power, System Power, Ah Discharge, Number Of
Rectifiers Failed, Number Of Rectifiers Comms Lost).
Threshold Type
Set to either:

High - the System Value Source will be true when the System
Value goes above the Threshold.

Low – the System Value Source will be true when the System Value
goes below the Threshold.
Threshold
The System Value Source will be true when the System Value goes above or
below (depending on the Threshold Type) this value.
Hysteresis
Determines when an active System Value Source will become false:
If Threshold Type is set to Low the System Value Source will become false when
the System Value goes above Threshold + Hysteresis.
If Threshold Type is set to High the System Value Source will become false when
the System Value goes below Threshold - Hysteresis.
Latched Smart Alarm
A Smart Alarm can be latched so that once it become active it must be cleared manually.
► To Create a latched Smart Alarm
1 Configure a Smart Alarm with the following parameter settings:
48
Operator:
OR
Severity:
Select the level for the required alarm indications (see
details on page 40).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Set other parameters as required (see details on page 45).
2
3
Configure an Alarm Source with the following parameter settings:
SA Num:
The number of the Smart Alarm configured in step 1.
Status:
Enabled
Logic:
EQUAL
Trigger When Source Is:
Active
Type:
Smart Alarm
Index:
The number of the Smart Alarm configured in step 1.
Configure a second source (Alarm Source, Schedule Source or System Value Source) with the
following parameter settings:
SA Num:
The number of the Smart Alarm configured in step 1.
Status:
Enabled
Set other parameters as required (see details on page 45).
The Smart Alarm will activate when the source (configured in step 3) becomes active. The Smart
Alarm will then remain active until it is manually cleared (see next), even if the source is
deactivated.
► To Clear a latched Smart Alarm
Either:

Use SC200 keypad to go to: Alarms. Select the active alarm. Press Details > Clear.
Or:

In DCTools/Web go to: Alarms > Smart Alarms. Click the Clear button.
Batteries
The following information is available about the batteries connected to the dc power system.
Parameter
Description
Battery Charge
State

Charge - the battery current is above
the Battery State Threshold.

Discharge - the battery current is below
-1 * Battery State Threshold.

Floating - the battery current is between
± Battery State Threshold.

Unavailable - the battery current is not
available.

Where to find:
DCTools/Web: Batteries
See SC200 or DCTools/Web displays
??? or N/A on page 89.
Battery
Temperature
The temperature measured by the battery
temperature sensor.
Ah Discharged
The current level of battery discharge.

SC200: Battery > Battery
See also Reset Battery State.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
49
SC200 Handbook
Batteries Configuration
The following battery parameters must be configured.
Parameter
Description
Cells Per String
The number of 2V cells per battery string (for
example: 24 in a 48V nominal system).
Battery Capacity
Set to the rated 10 hour capacity of the installed
battery strings.
Battery State
Threshold
Used to determine the Battery Charge State. See
Battery Charge State on page 49.
Battery Type
An optional text field for the name or type of
battery.
Battery Current
Sensor Fail
Recognition Period
Where to find:
SC200: Battery > Battery
(tab)
DCTools/Web: Batteries
DCTools/Web: Batteries
An optional battery current sensor fail delay.
Set if momentary battery current sensor fail
conditions stop battery related control processes.
Battery Mid-point Monitoring (MPM)
Battery Mid-point Monitoring provides a cost-effective method for the early detection of
internal battery faults. The voltages of the two halves of a battery string are measured and the
system controller generates an alarm signal if a voltage imbalance is detected.
A voltage imbalance is an indication that one or more cells has an internal fault. Further
investigation can then isolate the faulty cell(s) and action can be taken to correct the problem
and prevent a total battery failure.
To connect Battery Mid-point Monitoring see details in the dc power system installation guide.
If a String Fail alarm is generated see Troubleshooting on page 88.
To ensure reliable operation Mid-point Monitoring operates only when the battery is in float
charge and after a configurable lockout period since the last battery discharge, Fast Charge,
Equalize or Battery Test.
50
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
► To enable Battery Mid-point Monitoring (MPM)

1
If any of the mid-point monitoring analog inputs are used for Reverse Battery Detection (see
details on page 58) then they are not available for MPM.
Connect the mid-point monitoring sense wires to the batteries. Refer to the dc power
system Installation and Operation Guide.

There are four mid-point monitoring analog inputs on an IOBGP input/output board (for four
battery strings). Up to 20 additional battery strings can be monitored if additional IOBGP
input/output boards are connected. Refer to the dc power system Installation and Operation
Guide for details on how to connect additional IOBGP input/output boards to the SC200.
2
In DCTools/Web go to Batteries.
3
Set Cells Per String to the number of 2V cells per string (for example: 24 for 48V nominal
system).
4
Expand the Mid-point Monitoring table.
5
Set MPM Enable to Enabled and check the configuration settings (see details on page 53).
6
Go to Analog Inputs and Enable the mid-point monitoring analog inputs (one per battery
string) as required.

7
Battery strings 1-4 will be connected to IOB Number 1, IOB AI Numbers 2-5. Battery strings
5-8 will be connected to IOB Number 2, IOB AI Numbers 2-5. And so on, as required up to
string 24.
Go to Alarms > Alarm States. Enable and configure the String Fail alarm. See System Alarm
Configuration on page 42.
► To clear a String Fail alarm
1 In DCTools/Web go to Batteries > Mid-point Battery Monitoring (expand the table).
2
Click on Clear String Fail.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
51
SC200 Handbook
Information
The following information is available about Battery Mid-point Monitoring.
Parameter
Description
MPM State
Disabled: MPM is Disabled.
Where to find:
Unable To Start: MPM is Enabled but either: Cells
per String is zero; the bus voltage sensor has
failed; ac supply has failed; the battery is in
discharge state; Fast Charge, Equalize or Battery
Test is active; or the battery fuse has failed.
Locked Out: MPM is within the MPM Lockout
Period. No String Fail alarm will become active in
this period.
Converging: MPM is outside the MPM Lockout
Period but is within MPM Convergence Period.
Stable: MPM is outside the MPM Convergence
Period.
Time In This State
The time period MPM has been in the current
state.
Current MPM
Threshold
When MPM state is Converging this value is
between MPM Start Threshold and MPM Stable
Threshold. When MPM state is Stable this value is
the MPM Stable Threshold.
Reference Voltage
The calculated mid-point reference voltage (50%
of the bus voltage for even number of cells).
String State
OK: MPM is in the state Converging or Stable and
the string's Imbalance is below the current
threshold.
SC200: Battery > MPM
DCTools/Web: Batteries >
Mid-point Monitoring
Unavailable: The MPM is not in state Converging
or Stable, or the string's mid-point voltage is
unavailable.
Pending Fail: The string's Imbalance is above the
current threshold, but has not yet been so
continuously for the String Fail Recognition
Period.
Fail: The string's Imbalance has been above the
Current MPM Threshold for longer than the String
Fail Recognition Period. This will activate a String
Fail alarm.
Not Configured: No analog input is mapped to
this string.
52
Mid-point Voltage
Shows the mid-point voltage reading for the
string or N/A if no analog input channel is
mapped to this string.
Imbalance
The percentage imbalance of the Mid-point
Voltage.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Configuration
Set the following parameters.
Parameter
Description
Where to find:
String Fail alarm
parameters
See System Alarm Configuration on page 42.
DCTools/Web: Alarms >
Alarm States
MPM Enable
Enable/disable Mid-point Monitoring.
MPM Lockout
Period*
Time from when MPM is able to start until the
start of the MPM Convergence Period.
MPM Convergence Time from the end of the MPM Lockout Period
Period*
until MPM State is Stable. During this period the
Current MPM Threshold is calculated using linear
interpolation between Start Threshold and Stable
Threshold and the MPM State is defined as
Converging. After this period the MPM State is
defined as Stable and the MPM Stable Threshold
applies.
String Fail
Recognition Period
If the mid-point Imbalance percent of a battery
string exceeds the MPM Threshold for this period
of time the String State is set to Fail and the String
Fail alarm is activated.
MPM Start
Threshold*
Mid-point Imbalance percent threshold at the
start of the MPM Convergence Period.
MPM Stable
Threshold*
Mid-point Imbalance percent threshold after the
convergence period.
SC200: Battery > MPM >
Settings
DCTools/Web: Batteries >
Mid-point Monitoring
* A dynamic alarm threshold is used to give the best possible battery fault detection:
1
After the end of a discharge, Fast Charge or Equalize cycle, MPM does not start until the
end of the MPM Lockout Period, to ensure the system is in float charge.
2
At this point, the battery cell voltages are expected to be widely spread, so the alarm
threshold is set high (MPM Start Threshold).
3
The alarm threshold is then progressively reduced over the MPM Convergence Period.
4
After the end of the MPM Convergence Period, cell imbalance is assumed to be stable, and a
fixed threshold is used (MPM Stable Threshold).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
53
SC200 Handbook
Battery Time Remaining
The SC200 obtains characterization data from every full battery discharge, to a specified end
voltage.
During a battery discharge, the SC200 uses this characterization data to calculate an estimated
time until the battery will reach the specified end voltage.

If a battery disconnect LVD is fitted then the end voltage will usually be the voltage at which the
LVD disconnects the battery.

Battery Time Remaining is designed for a constant power load. The accuracy of the time
remaining calculation will be reduced if the dc power system is connected to a predominantly
resistive (constant current) load.

The time remaining calculation will not be correct if a non-essential load is disconnected during
the battery discharge.
The following information is available about Battery Time Remaining.
Parameter
Description
Battery Time
Remaining*
During a battery discharge, this is the estimated time
until the battery voltage will be equal to the End
Voltage, at the present battery current. Time Remaining
will be re-calculated if the load current varies during
discharge (for example, when a load disconnect LVD
operates).
Estimated State of
Charge (SOC)*

54
Where to find:
SC200: Menu > Controls >
Batt Time Remaining
DCTools/Web: Batteries
The estimated charge left in the battery (Ah).
*Values of Battery Time Remaining and SOC are only available during a discharge and if the
battery has been characterized. The values will be N/A when the Battery Charge State is
Floating or Charge, or if the battery has not been characterized. See Battery Characterization.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Configuration


It will take at least 10 hours to characterize a battery.

When a battery is characterized it is discharged. The bus voltage will gradually
reduce to the battery end voltage. Ensure that this will not affect the operation of
any equipment connected to the dc power system.
Use the following procedure to configure Battery Time Remaining for the first time, or if a
previously characterized battery is changed.

Battery Characterization is not necessary if a previously saved battery characterization data file is
available. Refer to Characterization Data Management on page 58. Only use characterization data
for an identical type and size of battery.
► To configure Battery Time Remaining
1 Check that all battery strings are connected and all LVD contactors (if any) are connected.

2
During a battery characterization, LVD contactor disconnection is inhibited. If any LVD
contactor is configured to connect during a battery discharge then set it to Manual Connect to
prevent operation during the battery characterization.
Check that all battery strings are fully charged.

When a battery is fully charged, the Battery Charge State will be Float and Ah Discharged
will be zero. See Batteries on page 49.
3
Check that all battery parameters are set to the correct values. See Batteries Configuration
on page 50.
4
Check that the load current is at least 2% of the C10 capacity of the batteries (Battery
Capacity) and 150% of the Battery State Threshold. See Batteries Configuration on page 50.

5
Either, in DCTools/Web go to Batteries > Battery Time Remaining, or use the SC200 keypad
to go to Battery. Set End Voltage to the voltage per cell when the battery is regarded as fully
discharged.

6
If the load current is less than 10% of the C10 capacity of the batteries, then Battery
Characterization will take longer than 10 hours.
In general set the end voltage to the same value as for the LVD Disconnect Voltage (see LVD
Configuration on page 37). End Voltage must be at least 0.02V/Cell above the Minimum
System Voltage (per cell). The Minimum System Voltage is viewable in DCTools/Web at
Control Processes. It is not configurable.
Enable Battery Current Limit (see details on page 21).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
55
SC200 Handbook
► To Characterize the Battery
1
Either:



2
If "Characterize" is not present on the SC200 or the "Characterize" button is inactive in
DCTools/Web, then check all configuration settings. In DCTools/Web, the hover text will
indicate why the characterization cannot start.
Or, use Automatic Characterization to start a characterization automatically when all
conditions are correct and stable:
In DCTools/Web go to: Battery > Battery Time Remaining.
Set Automatic Characterization to Enabled and set Automatic Characterization Delay to the
required time that the conditions must be stable.
The characterization process will take at least 10 hours, depending on the load current.

3
Manually start a Characterization:
On the SC200 go to: Battery > Characterize > Start.
Or, in DCTools/Web go to: Battery > Battery Time Remaining. Click Characterize.
During characterization the rectifier output voltage is varied to maintain a constant power
discharge.
When the characterization has finished, the Characterization Result will be Updated.

If any other Characterization Result is shown, refer to BTR Operation on page 57.
4
The rectifiers will return to float voltage and the battery will start to recharge. If required,
start a manual Equalize (see details on page 24) to reduce the battery recharge time.
5
Restore any changed LVD operation back to the original settings. If no longer required,
disable Battery Current Limit.
Battery Time Remaining is now operational. During any battery discharge an estimate of time
remaining will be displayed.
56
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Operation
The following information is available about Battery Time Remaining.
Parameter
Description
Time Remaining
During a battery discharge, this is the estimated
time until the battery voltage will be equal to the
End Voltage, at the present battery current. Time
remaining will be re-calculated if the load
SC200: Battery
current varies during discharge (for example,
DCTools/Web: Batteries
when a load disconnect LVD operates).

Where to find:
Time Remaining is only available when
Battery Time Remaining State is Active.
Battery State Of
Health
The approximate battery capacity measured
during the last battery characterization, as a
percentage of the configured Battery Capacity.
State
Inoperative: The battery characterization data is
not loaded, End Voltage is below the
characterization end point, or the bus voltage or
battery current is unavailable.
DCTools/Web: Batteries
Inactive: Battery Charge State is Float or Charge.

See Battery Charge State on page 49.
Characterizing: Battery characterization is in
progress.
Active: The battery has been characterized and
Battery Charge State is Discharge.

See Battery Charge State on page 49.
Lowest End
Voltage
The end voltage used for the last battery
characterization.
Characterization
Result
Not Yet Run: The battery has not been
characterized since the last restart of the SC200.
Active: The SC200 is collecting the
characterization data.
Complete: The SC200 has collected the
characterization data and is updating its
database.
SC200: Battery
DCTools/Web: Batteries >
Battery Time Remaining
Updated: The SC200 has updated its database.
Sensor Failed: Data from the last
characterization was not saved because the bus
voltage sensor failed or the battery current
became unavailable.
Not Fully Charged: Characterization did not
start because the battery was not fully charged
when discharge started.
Unstable Battery Current Pending: The battery
current has varied more than the tolerance for an
accurate characterization. Characterization will
continue if the battery current is in tolerance
within one minute. Otherwise, data from this
discharge will not be saved.
Unstable Battery Current: Data from the last
characterization was not saved because the
battery current varied more than the tolerance,
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
57
SC200 Handbook
for more than one minute.
Voltage Step Detected: Data from the last
characterization was not saved because of a
change in the bus voltage (possibly caused by a
load disconnect).
Canceled: Data from the last characterization
was not saved because the characterization was
stopped manually.
Characterization Data Management
Battery characterization data can be saved to file for later use. This is useful if several sites use
batteries of the same type and size. However, characterization of each battery will provide the
most accurate estimate of Time Remaining.
► To save characterization data to a file
1 In Web go to Batteries > Battery Time Remaining.
2
When the battery characterization is completed, click on Characterization Data: Download.
3
Click Save. Type a file name (*.dcf) and browse to the required location. Click Save.
► To load battery characterization data into the SC200
Use Web to restore the *.dcf (configuration fragment) file previously saved. Refer to Backup and
Restore on page 18.
Reverse Battery Detection
If Reverse Battery Detection is enabled and a battery is connected with the incorrect polarity, the
SC200 will:

activate a Wrong Battery Polarity alarm, and

prevent any LVD from connecting.

58
Reverse Battery Detection uses the battery mid-point monitoring (MPM) analog inputs on an
IOBGP input/output board. Any of the mid-point monitoring analog inputs used for Reverse
Battery Detection are not available for MPM (see details on page 50).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
► To enable Reverse Battery Detection
1 Before the batteries are connected to the dc power system, connect the mid-point
monitoring sense wires to the battery sides of the battery fuses/disconnect devices (leave
the fuses/disconnect devices open). Refer to the dc power system Installation and
Operation Guide.

There are four mid-point monitoring analog inputs on an IOBGP input/output board (for four
battery fuses/disconnect devices). Up to 20 additional battery fuses/disconnect devices can be
connected if additional IOBGP-01 input/output boards are connected. Refer to the dc power
system Installation and Operation Guide for details on how to connect additional IOBGP-01
input/output boards to the SC200.
In DCTools/Web go to Analog Inputs and for each mid-point monitoring analog inputs
used (one per battery fuses/disconnect devices) set the following parameters.
2

To change a setting, double-click and select from drop down list or edit the text.
Parameter
Setting
Status
Set to Enable.
Name
Set to: Battery Polarity Detect 1, Battery Polarity Detect 2, ...
Function
Set to Reverse Battery Detection.
Units
Set to Volts.
IOB Number
Set to 1 for battery fuses/disconnect devices 1-4.
Set to 2 for battery fuses/disconnect devices 5-8.
...
IOB AI Number
Set to 2 for battery fuses/disconnect devices 1, 5, 9 ...
Set to 3 for battery fuses/disconnect devices 2, 6, 10 ...
...
Gain
Set to 1.
Offset
Set to 0.
Group
Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online
help for details.
Wrong Battery Polarity Alarm
If Reverse Battery Detection is connected and enabled, the SC200 will activate a Wrong Battery
Polarity alarm if it detects that one or more of the batteries are connected with the wrong
polarity.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
59
SC200 Handbook
Generator Control Option
Generator Control is used to delay the start of standby ac generators until the batteries are
partially discharged (rather than immediately after the ac supply fails). This can save fuel by
preventing generators running during short ac supply failures. It can also be used to control a
generator in a hybrid power system (cyclic charge/discharge).
Generator Control uses a digital output (relay) which is connected in series with the generator
run signal of the generator controller. The relay is controlled by the Generator Enable alarm. The
relay contacts interrupt the generator run signal until the Generator Enable alarm is active.
The Generator Enable alarm is activated when the ac supply fails and either the Fast Charge or
Equalize control process starts (depending on the setting of the Generator Start Trigger).
The Generator Enable alarm stays active (and the generator running) until the ampere-hours
recharged is enough for the battery to be fully charged, or until the maximum fast charge
duration is reached.
A Generator Fail alarm is activated if the SC200 does not detect that the ac supply is present
(rectifiers have turned on) after the Generator Fail Alarm Recognition Period following Generator
Enable becoming active.
Single line diagram






60
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
AC utility supply
Generator
AC change-over switch
Rectifiers
Generator control panel
Normally open (NO) relay
contacts on I/O board
interrupt Generator Run
signal.
System Operation
Typical operation
AC Supply
Battery Discharge
Generator Run
Generator Fuel
Savings




AC supply failure. Battery starts to discharge.
AC supply restored. Battery begins to recharge. Battery discharge did not reach the Ah Threshold. Generator
Enable was not active (relay contacts did not close) so the generator did not run.
AC supply failure. Battery starts to discharge.
Battery discharge reaches the Ah Threshold. Generator Enable becomes active and the relay contacts close.
The Generator Run circuit is completed allowing the generator to start. Battery begins to recharge.

Battery recharge is complete. Generator Enable becomes inactive and the relay contacts open. The
Generator Run circuit is interrupted causing the generator to stop. Battery begins to discharge.

AC supply restored. Battery begins to recharge. Battery discharge did not reach the Ah Threshold. Generator
Enable was not active (relay contacts did not close) so the generator did not run.
Configuration
1
In DCTools/Web go to Alarms > Alarm States (expand the Alarms table).

See Alarms on page 39.
2
Set the Severity of the Generator Enable alarm to enable it.
3
In the Alarm DO Mapping A column select a spare digital output (relay).
4
In DCTools/Web go to Digital Outputs and configure the digital output as Active State
Energized. See Digital Outputs on page 67.
5
Connect from the normally open (NO) contacts of the digital output relay on the I/O board
to the generator run circuit.
6
Go to Control Processes > Generator Control.
7
Set Generator Start Trigger to either Fast Charge Only or Fast Charge and Equalize as required.
8
Go to Control Processes > Fast Charge.
9
Check that Fast Charge is enabled, and check the following configuration settings.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
61
SC200 Handbook
Parameter
Description
Where to find:
Battery Capacity
Set to the rated 10 hour capacity of the installed
battery strings.
SC200: Battery > Battery
Ampere-Hour
Threshold
DCTools/Web: Batteries
If Ah Discharged is above this value, then the
Generator Enable alarm will be active. The
threshold is given as a percentage of installed
C10 battery capacity.
Generator Enable alarm can also be triggered
based on the Voltage Threshold.
Voltage Threshold
If the bus voltage drops below this value then
Generator Enable alarm will be active. Generator
Enable alarm can also be triggered based on the
Ampere-Hour Threshold.
Recharge
Percentage
The ratio of ampere-hours recharged to the
ampere-hours discharged. Fast Charge stops
either when the Ah recharged equals the Ah
discharged x Fast Charge Recharge Percentage,
or after Maximum Duration.
Maximum
Duration
The maximum duration of a Fast Charge as
recommended by the battery manufacturer.
Generator Fail
Alarm Recognition
Period
A Generator Fail alarm is activated after this time
if Generator Enable is active but the SC200 does
not detect that the ac supply is present (rectifiers
have turned on).
SC200: Control Processes >
Fast Charge
DCTools/Web: Control
Processes > Fast Charge
SC200: Alarms > Alarm
Settings > System Alarms >
Generator Fail
DCTools/Web: Alarms >
Alarm Configuration
Input/Output (I/O)
The following section describes the I/O functions available with a single IOBGP I/O board.

Also see I/O Board Mapping on page 109.
Optional SiteSure-3G input/output (I/O) modules or additional IOBGP I/O boards can be
connected to the SC200 to provide additional I/O to monitor and control external devices. For
details refer to the SiteSure-3G Installation Guide (see Related Information on page i).
Identify an I/O Board
Input/Output (I/O) boards and SiteSure-3G modules are referenced by their serial numbers.
► To identify a particular I/O board or SiteSure-3G module
Either:

On SC200 keypad go to: Settings > IOBs and select a module or board. Press Enter.


62
The I/O board details screen appears. Use
to scroll to other I/O boards.
The Power-on LED on the selected I/O board or SiteSure-3G module will flash for 60
seconds (or press Esc to stop).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Or:

In DCTools/Web go to: Configuration > RXP > RXP Devices.

DCTools: select Identify Device or Web: click on Start Identifying.

The Power-on LED on the selected I/O board or SiteSure-3G module will flash for 60
seconds.
Analog System Values
The SC200 provides access to the following system analog values.
Parameter
Description
Bus Voltage
The average of all analog inputs configured as Bus
Voltage. Otherwise, the system bus voltage is
determined from the rectifier output voltages.
Load Current
The sum of any analog inputs configured as Load
Current. Otherwise, if Battery Current is available, the
Load Current is calculated as Rectifier Current - Battery
Current. Otherwise it is unavailable.
Battery Current
The sum of any analog inputs configured as Battery
Current. Otherwise, if Load Current is available, the
Battery Current is calculated as Rectifier Current - Load
Current. Otherwise it is unavailable. If positive, the
battery is being charged.
Battery
Temperature
The average of all analog inputs configured as Battery SC200: Analogs
Temperature.
DCTools/Web:
The sum of any analog inputs configured as Rectifier Analog Inputs >
System Values
Current. Otherwise, if there are Battery and Load
Currents, the Rectifier Current is calculated as Battery
Current + Load Current. Otherwise, Rectifier Current is
determined as the sum of all reported rectifier output
currents.
Rectifier Current
Where to find:
Load Power
The power being supplied to the load. Load Current x
Bus Voltage.
System Power
The output power of the system as a percentage of
the total nominal power of the registered rectifiers.
AC Voltage
The average of the ac voltage measured by singlephase rectifiers.
Or, if 3-phase rectifiers are fitted then the average of
the ac phase voltages is shown.
Analog Inputs
The analog inputs (AI) monitor variable dc voltages (bus voltage sense, general purpose analog
inputs, current sensors or temperature sensors). See Specifications on page 93 for details.
Generally, the system analog inputs (as indicated by the "Function" field) are configured at the
factory and do not need to be changed.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
63
SC200 Handbook
► To configure an analog input
1 In DCTools/Web go to Analog Inputs. Expand the Analog Inputs table.

The table shows the maximum number of analog inputs. The actual number of analog inputs
available depends on the number of I/O boards or modules connected.
Select an Analog Input. The analog inputs are mapped to specific I/O connectors and are of
three types (voltage/general purpose, current or temperature). See mapping tables on page
109.
2

If needed, more than one analog input can be mapped to the same connector so that the sensor
can trigger more than one Analog Input High and/or Low Alarm. In this case, no more than
one analog input can be assigned to a system function.
Configure the following parameters to suit the application.
3

To change a setting, double-click and select from drop down list or edit the text.
Parameter
Setting
Status
Set to Enabled.
Name
Type the name of the input or use the default value.
Function
Set to User Defined. Or to a particular system function if the input is to be
associated with that function.
Units
Select the units to match the type of analog value.
IOB Number
The number of the I/O board or module.

IOB AI Number
Generally, do not change this mapping. See point 2.
The number of the AI on the I/O board or module.

Generally, do not change this mappings. See point 2.
Gain
A scaling factor applied to the raw measured value.
Offset
A fixed value added to the raw measured value (after any Gain is applied).
Group
Set to 0 unless using Groups in PowerManagerII. Refer to PowerManagerII
online help.
Analog Input High and Low Alarms
Any analog input that is Enabled in the Analog Inputs table can activate a high and/or low alarm.

The Alarm Recognition Period (see details on page 41) applies to analog input alarms.
Configure the following parameters in the Analog Input High Alarms and/or Analog Input Low
Alarms tables to suit the application.

64
To change a setting, double-click and select from drop down list or edit the text.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Parameter
Setting
Severity
Set to the required alarm priority. This determines how the alarm is indicated.
See details on page 40.
If set to Disabled then the alarm will not activate.
Threshold
An analog input high/low alarm is activated if the scaled input is greater
than/less than or equal to this value.
Hysteresis
The amount of hysteresis applied to the input before an active alarm is
deactivated.
Digital Output
Mapping A
If required, select a relay that will be operated when the alarm is active.
Digital Output
Mapping B
If required, select a second relay that will be operated when the alarm is active.
Send Trap
An SNMP Trap will be sent for this alarm, if Send Trap is True and the alarm's
Severity matches the setting of the SNMP Trap Level (see details on page 76).
Notes
Type any required description. When the alarm is active the text will be
displayed on the SC200 and included in the SNMP trap (if used).
System States
The SC200 monitors the following system states to provide an overview of the dc power
system's operation. States displayed will depend on the dc power system model.
Name
Description
Where to find:
Fan
Indicates if any digital input with Function set to
"ACD Fan Fail" is active (only used in systems
with ac distribution fans).
Cabinet Fan
Indicates if any digital input with Function set to
"Cabinet Fan Fail" is active (only used in systems
with cabinet fans).
Mains Fail
Indicates if any digital input with Function set to
"AC Fail" is active.
MOV Fail
Indicates if any digital input with Function set to
"MOV Fail" is active (only used in systems with
MOV surge protection).
Load Fuse Fail
Indicates if any digital input with Function set to
"Load Fuse Fail" is active.
Battery Fuse Fail
Indicates if any digital input with Function set to
"Battery Fuse Fail" is active.
Phase Fail
Indicates if any digital input with Function set to
"Phase Fail" is active.
SC200: Digitals
DCTools/Web: Digital
Inputs
Notes:
1
See the related Alarm Descriptions on page 97.
2
A value of Unavailable indicates that a System State is not configured for this dc power
system.
3
A value of Missing indicates that the I/O board has been disconnected or is faulty, or the
connector mapping is incorrect.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
65
SC200 Handbook
Digital Inputs
The input/output (I/O) board is fitted with a number of configurable digital inputs (DI) which
can monitor external voltage-free relay contacts or switches. See Input/Output Board on page 2
for details.
► To configure a digital input
1 In DCTools/Web go to Digital Inputs. Expand the Digital Inputs table.
2
Digital Input 1-6 are available for configuration.


Digital Input 7-10 (on I/O board 1) are used for system alarms.
If additional I/O boards and/or SiteSure-3G modules are connected there will be more
configurable Digital Inputs. See details in the dc power system installation guide.
The last four digital inputs are the pre-assigned Digital System States (see details on page
65). Do not change these settings.
3
Select a configurable Digital Input.
4
Configure the following parameters to suit the application.

To change a setting, double-click and select from drop down list or edit the text.
Parameter
Setting
Status
Set to Enabled.
Name
Type the name of the input.
Function
Set to User Defined.
IOB Number
The number of the I/O board (or SiteSure-3G module if connected). Do not
change.
IOB DI Number
The number of the DI on the I/O board (or SiteSure-3G module if connected).
Do not change.
Active State
Select the state of the input that will activate the DI.
Group
Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online
help for details.
Digital Input Alarms
Any digital input that is Enabled in the Digital Inputs table can activate an alarm.
Configure the following parameters in the Digital Input Alarms table to suit the application.

66
To change a setting, double-click and select from drop down list or edit the text.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
Parameter
Setting
Severity
Set to the required alarm priority. This determines how the alarm is indicated.
See details on page 40.
If set to Disabled then the alarm will not activate.
Recognition Period
The alarm will activate only after the digital input is active for this period.
Deactivation
Recognition Period
The alarm will deactivate only after the digital input is inactive for this period.
Digital Output
Mapping A
If required, select a relay that will be operated when the alarm is active.
Digital Output
Mapping B
If required, select a second relay that will be operated when the alarm is active.
Send Trap
An SNMP Trap will be sent for this alarm, if Send Trap is True and the alarm's
Severity matches the setting of the SNMP Trap Level (see details on page 76).
Notes
Type any required description. When the alarm is active the text will be
displayed on the SC200 and included in the SNMP trap (if used).
Digital Outputs
The input/output (I/O) board is fitted with a number of digital outputs (relays) which can
control external equipment or alarm systems. See Input/Output Board on page 2 for details.
Digital outputs are operated by a mapping from a digital input alarm (see details on page 66),
an analog input high or low alarm (see details on page 63), or a system alarm (see details on
page 39).
► To manually control a digital output
Either:

In DCTools/Web go to Digital Outputs:



Expand the Digital Outputs table.
In the Control State column of the required digital output, select Active or Inactive.
Or, use the SC200 keypad to go to Digital Outputs:


Select the required digital output. Press Edit.
Select Active or Inactive. Press Save.

The DO Manual alarm (if enabled) will activate.

The corresponding digital output will Energize or De-Energize, as selected in the Active
State column of the Digital Outputs table.

While Active or Inactive is selected, the DO will not be operated by any active alarms mapped
to it. Set Control State back to Automatic to allow mapped alarms to operate the digital output.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
67
SC200 Handbook
► To set the state of a digital output from PowerManagerII

In DCTools, set the Group of one or more digital outputs to a non-zero value.

Only digital outputs with a non-zero Group are visible in PowerManagerII

In PowerManagerII select the SiteManager group item.

Click on the Realtime tab.

From the drop down list beside the digital output select Active Manual or Inactive Manual.

The DO Manual alarm (if enabled) will activate.

The corresponding digital output will Energize or De-Energize, according to its Active State.

While Active Manual or Inactive Manual is selected, the DO will not be operated by any active
alarms mapped to it. Set Control State back to Automatic to allow mapped alarms to operate the
digital output.
► To configure a digital output
1 In DCTools/Web go to Digital Outputs. Expand the Digital Outputs table.
2
Select a Digital Output (1-6*).

3
Other Digital Outputs will be available if additional I/O boards and/or SiteSure-3G modules
are connected. See details in the dc power system installation guide.
Configure the following parameters to suit the application.

To change a setting, double-click and select from drop down list or edit the text.
Parameter
Setting
Control State
Set to Automatic.
Status
Set to Enabled.
Name
Type the name of the output.
IOB Number
The number of the I/O board (or SiteSure-3G module). Do not change.
IOB DO Number
The number of the DO on the I/O board (or SiteSure-3G module). Do not
change.
Active State
Select the state of the output when the DO is active*.
Group
Set to 0 unless using Groups in PowerManagerII. See PowerManagerII online
help for details.

* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board
loses power or loses communication with the SC200.
Data Logging
The SC200 has the following data logging functions.
Event Log
The Event Log records every system event. See System Event Types on page 107 for a
description of event log entries.

68
The most recent Event Log entries are shown by the SC200 web view, on the Log screen. See
Communication via Web Browser on page 74.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
System Operation
► To view and save the Event Log

To view the log entries, either:


In DCTools go to: Controller Log > Data Log , or
In Web go to Logs > Log Management and click Event Log (CSV): Download to view the
log entries in a new browser window.

Wait for the log entries to download from the SC200.

To save the log to a file, either:



In DCTools click on Save to File ... , or
In Web go to File > Save As...
Type a file name, select a file type, and browse to a location to save the file.
► To configure the size of the Event Log

Either:



In DCTools go to: Controller Log > Configuration, or
In Web go to Logs > Event Log Config.
Type the required number of Event Log entries (up to 10,000). Memory will be allocated for
at least this number of entries. When the memory is full the oldest record will be overwritten.
► To clear the Event Log

In Web go to Logs > Log Management or in DCTools go to Controller Log > Configuration >
Log Management.

Click Clear Logs.

This will also clear the Data Log.
Data Log
The Data Log records several system parameters (AC Voltage, Bus Voltage, Load Current,
Rectifier Current, Battery Current, Battery Temperature) at specified intervals. The rate of
recording increases (interval is reduced) when the bus voltage differs from the float voltage by
more than a specified value.
Data log entries are also written whenever a system event occurs (as for the Event Log).
► To view and save the Data Log

To view the log entries, either:


In DCTools go to: Controller Log > Event Log , or
In Web go to Logs > Log Management and click Data Log (CSV): Download to view the log
entries in a new browser window.

Wait for the log entries to download from the SC200.

To save the log to a file, either:



In DCTools click on Save to File ... , or
In Web go to File > Save As...
Type a file name, select a file type, and browse to a location to save the file.
► To configure the Data Log

Either:



In DCTools go to: Controller Log > Configuration, or
In Web go to Logs > Data Log Config.
The following parameters must be configured.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
69
SC200 Handbook
Parameter
Description
Where to find:
Normal Interval
The time between each data log record when the Bus
Voltage differs from the Float Voltage by less than the
Off-Normal Offset Voltage.
Off-Normal
Interval
The time between each log record when the Bus
Voltage differs from the Float Voltage by more than the Web: Logs > Data Log
Data Log Off-Normal Offset Voltage.
Config
Off-Normal Offset
Voltage
The Off Normal Log Interval will apply when bus
voltage is outside the range: Float Voltage ± OffNormal Offset Voltage. Off-normal condition
transitions are recognized within 10 seconds.
DCTools: Controller Log >
Configuration > Data Log
Config
Maximum Number Memory will be allocated for at least this number of
of Log Entries
Data Log entries (up to 10,000). When the memory is
full the oldest record will be over-written.
► To clear the Data Log

In Web go to Logs > Log Management or in DCTools go to Controller Log > Configuration >
Log Management.

Click Clear Logs.

This will also clear the Event Log.
PC Log
The PC Log allows a continuous streaming of system data (Bus Voltage, Load Current, Battery
Current, Battery Temperature, Rectifier Current, Load Power, System Power) from the SC200
directly into a specified file.
► To configure and activate the PC Log
1 In DCTools go to PC Log.
70
2
At File Name, click on the button to type a file name, select a file type, and browse to a
location to save the file.
3
Select the required interval between log entries (from 5s to 60 minutes).
4
Click on Start to begin the log.
5
Click on Stop to end the log.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Chapter 4
Communications


C
h
Communications
a
p
t
e
r
4
Overview
Topic
Page
Communications Options
72
Direct (USB) Communications
72
Ethernet Communications
72
Serial (RS232) Communications
78
Communications Security
83
CSP
86
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
71
SC200 Handbook
Communications Options
The SC200 system controller has a standard USB interface, a standard RS232 serial interface
(XS1) and an Ethernet 10BaseT interface (XS31) for communication with a local or remote PC or
laptop, or a Network Management System (NMS). See the diagrams on page 2 for locations of
these connectors.
The standard communications options for an SC200 system controller are described in the
following sections. For other communications options contact your Eaton dc product supplier
or Eaton (see Worldwide Support on page 115).
Direct (USB) Communications
See SC200 Operation Using a PC/Laptop on page 13.
Ethernet Communications
Connections



SC200 system controller
PC/laptop with:

PowerManagerII and/or DCTools (see details on page 73), and/or

Web browser (see details on page 74), and/or

Network Management System using SNMP (see details on page 75), and/or

Building management System using Modbus-TCP (see details on page 77).
Communications network. Protocol: TCP/IP
MAC Address
► To view the MAC Address of the SC200
Either:

Use the SC200 keypad to go to: Info
Or:


72
In DCTools/Web go to: Configuration > Communications > Ethernet
The Media Access Control (MAC) address is the SC200’s unique Ethernet address assigned by the
manufacturer.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Communications
SC200 Setup

The network administrator must assign a unique IP address to each SC200 to be connected to the
TCP/IP network.
► To configure an SC200 for Ethernet communications from the keypad

Go to Settings > Setup

Enter the IP Address, Subnet Mask and Gateway Address assigned by the network
administrator.

If required, set HTTP Access to Enabled for web browser access, or set HTTPS Access to
Enabled for secure web access.
► To configure an SC200 for Ethernet communications using DCTools

Connect using USB (see details on page 13).

In DCTools go to Configuration > Communications.

Under Ethernet, type the IP Address, Subnet Mask and Gateway Address assigned by the
network administrator.

If required, under HTTP (Web), set HTTP Access to Enabled for web browser access, or set
HTTPS Access to Enabled for secure web access.
DCTools or PowerManagerII Communications Setup (if required)
► To connect to the SC200 with DCTools or PowerManagerII:
1 Install DCTools/PowerManagerII on the PC/laptop.
2
Double-click the DCTools/PowerManagerII icon to open the connection manager.
3
Go to Connection > New to open a new connection dialog box.
4
Enter:
Connection Name:
<as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Ethernet
S3P Address:
0 (0 = Broadcast, 1-65279 = individual address)
Server IP Address:
Allocated by network administrator
Server Port:
Allocated by network administrator
Telnet
Cleared
5
Press OK. DCTools/PowerManagerII will now connect to the SC200.
6
See System Operation on page 19 for details of the SC200 control and monitoring functions
available via DCTools.

7
For help using DCTools press F1.
If required, access to the SC200 via DCTools or PowerManagerII can be password
controlled. See Write Access Password on page 84.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
73
SC200 Handbook
Communication via Web Browser
The SC200 system controller has an in-built web server. This allows a PC/laptop with a
standard web browser to control and monitor the SC200 via an IP network.
► To connect to the SC200 with web browser:
1 Set up Ethernet communications and connect the SC200 to the IP network. See Ethernet
Communications on page 72.
2
Open a web browser window.

3
Type the IP Address of the SC200 into the address bar of the browser.

If HTTPS Access has been enabled and you wish to use secure web communication (see details
on page 85) then type "https://" before the IP Address.
4
The SC200 web server Log On page will appear.
5
If required, type a Logon ID and Password. Otherwise select Default User.

6
74
Recommended web browsers: Microsoft Internet Explorer 8 (IE6 is compatible but with
reduced performance), Mozilla Firefox 3.0.
Administration of Logon IDs and Passwords is available in DCTools/Web. See Web Access
Security on page 85.
Click Log On. The SC200 web system page will be displayed.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Communications
7
Go to the Forms for details of the SC200 control and monitoring functions available via the
web.
8
To change a setting click the text field, type the new value, then press Enter on the PC
keyboard. Then click Apply in the Changes window.

9
Hold the mouse pointer over any field for help.
Click Log Off (top right of window) to log out.
Communication via a Network Management System using SNMP
The SC200 system controller can be configured to allow access by a Network Management
System (NMS), and/or to send alarms as SNMP traps to up to eight different SNMP trap
receivers on an NMS.
► To allow NMS access to the SC200
1 Set up Ethernet Communications (see details on page 72).
2
In DCTools/Web go to Configuration > Communications > SNMP.
3
Set the following parameters:
SNMP Access:
Disabled: NMS access to the SC200 is not allowed.
All: the NMS has full access to the SC200.
Read Only: the NMS has read only access to the
SC200.
V3 Only: SNMP v3 access is allowed.
Read Community,
Write Community:
Do not change the default settings unless requested by
the network administrator.
Authentication Password
(SHA):
Only used with SNMP v3. Set if the NMS requires an
authentication password.
Privacy Password (DES):
Only used with SNMP v3 and if an authentication
password is set. Set if the NMS uses encryption.
System Object ID:
This is a unique Object Identifier that allows the NMS
to identify the type of device (in this case a power
system) on the network.
Objects are named in the
iso.org.dod.internet.private.enterprises (1.3.6.1.4.1)
sub-tree for enterprise-specific objects. The default
Object Identifier for an SC200-based dc power system
is: 1.3.6.1.4.1.1918.2.13
A network administrator can specify a new Object
Identifier within the (1.3.6.1.4.1) sub-tree, if required.
Do not enter the sub-tree integers 1.3.6.1.4.1 into the
System Object ID field.
► To send alarms as SNMP traps
1 Set up Ethernet Communications (see details on page 72).
2
In DCTools go to Configuration > Communications > SNMP.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
75
SC200 Handbook
3
Set the following parameters:
System Object ID:
See: To Allow NMS Access to a SC200 on page 75.
Trap Version:
Set to SNMP V1, V2, V3 as required.
Trap Format:
Set to Eaton or X.733 as appropriate .
"Eaton" format uses different trap numbers according
to the alarm source. X.733 format uses a single trap
number for all alarm sources.
Enable Generic Traps, Trap Configure as appropriate.
Repeat and Trap Repeat
Rate
4
For each SNMP trap receiver (up to 8) , configure the following parameters.
Parameter
Configuration Guidelines
Name
Type the name of the SNMP trap receiver (20 bytes maximum).

Level
This allows 20 ASCII characters, but less for languages with multi-byte
characters.
SNMP Trap Level – controls reporting of specific events for each receiver:

Select All Alarms And Warnings to receive Critical, Major and Minor
alarms, and Warnings. (Typically Warnings are status messages such
as Equalize Active.)

Select Minor And Above to receive Critical, Major and Minor alarms.

Select Major And Above to receive only Critical and Major alarms.

Select Critical Only to receive only Critical alarms.

Select Disabled to disable notifications to the receiver.

76
To prevent an SNMP Trap for an individual alarm, set Send Trap to False
in the alarm's configuration.
IP Address
IP address of the trap receiver assigned by the network administrator.
Port
The default setting is 162. Do not change this setting, unless requested by
the network administrator.
Trap
Community
A form of password. Use public, unless the network administrator has
assigned a new password.
Mode
Select:

Normal Traps for sending traps to any network management system,
except PowerManagerII

Acknowledged Summary Trap for sending traps to PowerManagerII
only
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Communications
Modbus-TCP Communications
Modbus-TCP* Connections



The SC200 only accepts one Modbus-TCP connection at a time, on the reserved Modbus-TCP port
of 502.

SC200 system controller
Communications network. Protocol: TCP/IP
PC/laptop with Building Management System
using Modbus-TCP.
SC200 Setup
1 Setup Ethernet Communications (see details on page 72).
2
Set the following Modbus-TCP* parameters:
Parameter
Description
Where to find:
Modbus Access
Set to Enabled.
SC200: Settings > Modbus
Address
Set to 1 for Modbus-TCP.
DCTools/Web:
Configuration >
Communications > Remote
Access Protocols > Modbus

* The SC200 also supports Modbus-RTU via the RS232 serial port (XS1). For details request
Application Note AN0107 from your Eaton dc product supplier.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
77
SC200 Handbook
Diagnostics
The following diagnostic information is available.
Parameter
Description
Where to find:
Bus Message Count Number of messages. Does not include messages
with bad CRC.
Bus
Communication
Error Count
Number of CRC errors.
Slave Exception
Error Count
Number of exception errors.
Slave Message
Count
Number of messages to the SC200.
Slave No Response
Count
Number of messages received for which no
response was sent.
Bus Character
Overrun Count
Number of messages received with more than
256 characters.

DCTools/Web:
Communications > Modbus
> Diagnostics
All counts are since the last SC200 restart or since counter was reset.
Serial (RS232) Communications
The parameters of the RS232 serial port can be configured, if required for a specific RS232
device. However, for most applications use the default settings.
Parameter
Description
Where to find:
Baud Rate
Default: 19200
Parity
Default: None
SC200: Settings > Serial Port
Settings
Stop Bits
Default: One
DCTools/Web:
Configuration >
Communications > Serial >
Port Settings
PSTN Modem Communications
Connections




78
The PC modem may be external to the PC (as shown) or internal.
SC200 system controller
PC/laptop with PowerManagerII and/or DCTools.


PSTN modem
PSTN network.
RS232 modem cable (straight-thru). If access to
XS1 is restricted use a DB9 ribbon cable extension
(Farnell part number 869-6411).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Communications
SC200 Setup

Not all modems are suitable. If your modem does not operate correctly check the modem setup
string. Contact your Eaton dc product supplier or Eaton for further assistance. See Worldwide
Support on page 115.
► To enable modem communications
1 Connect to the SC200 with DCTools (see details on page 13).
2
Go to Communications.
3
Click on + to expand Serial. Configure the following settings:
Enable Modem:
Enabled
Modem Power Reset:
Optional. If this is enabled, then the SC200 will attempt
to reset a non-operating modem by turning its power
supply off and on using digital output 2.
Modem Set Up String:
The string sent to the modem on reset.
The modem AT command should not be included as it
is automatically sent. The Auto-Answer Rings
parameter is also sent, so it does not need to be
included here. For complete details of appropriate
commands, consult your modem documentation.
Modem Auto Answer Rings: Number of rings before an incoming call is answered.
Setting this parameter to zero disables incoming calls
(the modem can still be used for alarm reporting).
4
If the SC200 is to report alarms to PowerManagerII then click on + to expand
PowerManager Callback. Configure the following settings:
Alarm Report:
Select the type of event(s) that will initiate the dial-out
process.
Report Maximum Retries:
Set to the number of times the SC200 is to try to connect
with a remote modem, if the first attempt fails.
After this number of retries the SC200 will try the next
number in the Dial Out Numbers table.

Dialing will stop if none of the numbers in the Dial
Out Number Table connect.
Report Retry Interval:
Set to the required interval between retries.
Dial Out Number(s):
Type the telephone number(s) to be called.

Consult the modem documentation for appropriate
dial modifiers.
DCTools or PowerManagerII Communications Setup
► To connect to the SC200 with DCTools or PowerManagerII:
1 If not already installed, install the PC modem (hardware and software) according to the
manufacturer's instructions.
2
Install DCTools/PowerManagerII on the PC/laptop.
3
Double-click the DCTools/PowerManagerII icon to open the Connection Manager window.
4
Go to Connection > New to open a new connection dialog box.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
79
SC200 Handbook
5
Enter:
Connection Name:
<as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Select the COM port used by the modem (if external) or the
modem name.
S3P Address:
0 (0 = Broadcast, 1-65279 = individual address)
Phone Number:
The number of the PSTN line used by the modem.
Modem Logon:
Clear if a logon script is not required for the modem.
Select if a logon script is required. Click Logon Script to define.
For more details, see DCTools/PowerManagerII online help
(press F1).
6
Press OK. DCTools/PowerManagerII will now connect to the SC200.
7
See System Operation on page 19 for details of the SC200 control and monitoring functions
available via DCTools.

8
For help using DCTools press F1.
If required, access to the SC200 via DCTools or PowerManagerII can be password controlled.
See Write Access Password on page 84.
GSM Modem Communications
Connections






80
The PC modem may be external to the PC (as shown) or internal.
SC200 system controller
Optional:
PC/laptop with PowerManagerII and/or DCTools.

SMS text capable GSM cell phone or SMS-Email
Gateway (if available)



SMS text message "P" or "p"
RS232 modem cable (straight-thru). If access to
XS1 is restricted use a DB9 ribbon cable extension
(Farnell part number 869-6411).
GSM modem
Power status text messages
Alarm text messages
Modem
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Communications
SC200 Setup

Not all modems are suitable. If your modem does not operate correctly check the modem setup
string. Contact your Eaton dc product supplier or Eaton for further assistance. See Worldwide
Support on page 115.
► To enable modem communications
1 Connect to the SC200 with DCTools (see details on page 13).
2
Go to Communications.
3
Click on + to expand Serial. Configure the following settings:
Enable Modem:
Enabled
Modem Power Reset:
Optional. If this is enabled, then the SC200 will attempt
to reset a non-operating modem by turning its power
supply off and on using digital output 2.
Modem Set Up String:
The string sent to the modem on reset.
The modem AT command should not be included as it
is automatically sent. The Auto-Answer Rings
parameter is also sent, so it does not need to be
included here. For complete details of appropriate
commands, consult your modem documentation.
Modem Auto Answer Rings: Number of rings before an incoming call is answered.
Setting this parameter to zero disables incoming calls
(the modem can still be used for alarm reporting).
4
If the SC200 is to report alarms to PowerManagerII then click on + to expand
PowerManager Callback. Configure the following settings:
Alarm Report:
Select the type of event(s) that will initiate the dial-out
process.
Report Maximum Retries:
Set to the number of times the SC200 is to try to connect
with a remote modem, if the first attempt fails.
After this number of retries the SC200 will try the next
number in the Dial Out Numbers table.

Dialing will stop if none of the numbers in the Dial
Out Number Table connect.
Report Retry Interval:
Set to the required interval between retries.
Dial Out Number(s):
Type the telephone number(s) to be called.

Consult the modem documentation for appropriate
dial modifiers.
DCTools or PowerManagerII Communications Setup
► To connect to the SC200 with DCTools or PowerManagerII:
1 If not already installed, install the PC modem (hardware and software) according to the
manufacturer's instructions.
2
Install DCTools/PowerManagerII on the PC/laptop.
3
Double-click the DCTools/PowerManagerII icon to open the Connection Manager window.
4
Go to Connection > New to open a new connection dialog box.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
81
SC200 Handbook
5
Enter:
Connection Name:
<as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Select the COM port used by the modem (if external) or the
modem name.
S3P Address:
0 (0 = Broadcast, 1-65279 = individual address)
Phone Number:
The number of the PSTN line used by the modem.
Modem Logon:
Clear if a logon script is not required for the modem.
Select if a logon script is required. Click Logon Script to define.
For more details, see DCTools/PowerManagerII online help
(press F1).
6
Press OK. DCTools/PowerManagerII will now connect to the SC200.
7
See System Operation on page 19 for details of the SC200 control and monitoring functions
available via DCTools.

8
For help using DCTools press F1.
If required, access to the SC200 via DCTools or PowerManagerII can be password controlled.
See Write Access Password on page 84.
SMS Text Messaging Setup (if required)

For additional information see Application Note AN0112. To receive application notes see
Worldwide Support on page 115.
► To enable SMS alarm messages
1 Connect to the SC200 with DCTools/Web.
2
Go to Configuration > Communications > Serial.
3
Click on  to expand SMS Notifications.
4
For each cellphone to receive SMS alarm messages set the Phone Number and other details
as required.
5
Type the required Prefix string if alarm messages are to be sent to an email address.

This requires a GSM-Email Gateway connected to the GSM network. Contact the GSM
network operator for details of the Prefix string required at the beginning of the SMS message.
► To check the dc power system status using SMS
1 From any cellphone write a SMS (text) message starting with "P" or "p" (any following
characters are ignored).
2
Send the message to the SC200 GSM modem telephone number.
The SC200 will reply with a dc power system status message. This will include: Number of
active alarms, bus voltage, load current, ac voltage, battery current, battery temperature, battery
time remaining (if available).
82
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Communications
Serial Server
The SC200's Serial Server function makes the SC200's RS232 port available to any software via
Ethernet. For example, use Serial Server to connect DCTools to a CellSure Battery Controller
(CBC) connected to the SC200.

For information refer to the CellSure Installation Guide (see Related Information on page i).
► SC200 Setup
1 Configure the SC200 for Ethernet communications. See details on page 72.
2
Either:



On the SC200 keypad go to Settings > Setup > Serial Server. Select Enabled.
Or:
Use DCTools/Web to go to Configuration > Communications > Remote Access Protocols >
Serial Server.
Set Access to Enabled.
DCTools or PowerManagerII Setup

Use similar settings for other software.
1
Install DCTools/PowerManagerII on the PC/laptop.
2
Double-click the DCTools/PowerManagerII icon to open the connection manager.
3
Go to Connection > New to open a new connection dialog box.
4
Enter:
5
Connection Name:
<as required>
Comms Enabled:
True
Protocol:
S3P
Connect Using:
Local Network
S3P Address:
0 (0 = Broadcast, 1-65279 = individual address)
Server IP Address:
The IP Address of the SC200. Allocated by network
administrator.
Server Port:
15000
Telnet
Cleared
Press OK. DCTools/PowerManagerII will now connect to the device connected to the
SC200's RS232 port.
Communications Security
SC200 settings cannot be changed if:


All communications are disabled (see S3P Access on page 84 and HTTP/HTTPS
Access on page 85), and

Keypad access (see details on page 10) is Read Only, or PIN Protected and the
keypad access PIN is lost.
In this situation the SC200 will continue to function, but no configuration changes can
be made. Contact your Eaton dc product supplier or Eaton for advice (see Worldwide
Support on page 115).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
83
SC200 Handbook
Serial Communications (USB/RS232/Ethernet) Security
S3P Access
S3P is the serial communications protocol used by the SC200 to communicate with DCTools or
PowerManagerII via the USB, RS232 or Ethernet port.

S3P Protocol is not used by the web server.
► To Enable/Disable S3P access

On the SC200 keypad go to Settings > Setup > S3P. Select Enabled or Disabled.
Or:
1
Connect to the SC200 with a web browser (see details on page 72).
2
Go to Configuration > Communications > Remote Access Protocols > S3P.
3
Set Access to Enabled or Disabled.
Write Access Password
The Write Access Password prevents unauthorized changes to the SC200 configuration (using
DCTools or PowerManagerII).

When a Write Access Password is set serial communications access to the SC200 (using DCTools
or PowerManagerII) is read only. The password must be entered before any setting can be
changed.

If a Write Access Password is lost, clear it from the SC200 keypad and type a new password in
DCTools, or change it via the Web.
► To set a Write Access Password
1 Connect to the SC200 with DCTools/Web (see details on page 72).
2
Go to Configuration > Communications > Remote Access Protocols > S3P
3
Type a password into the Write Access Password field.

4
Passwords are case sensitive, maximum 32 characters.
Click the Apply Changes button.
► To clear or change a Write Access Password
1 Connect to the SC200 with DCTools/Web (see details on page 72).
2
Go to Configuration > Communications > Remote Access Protocols > S3P
3
Type a new password into the Write Access Password field or leave the field blank for no
password control.
4
Click the Apply Changes button.
5
DCTools only: Type the old password.
► To clear a Write Access Password from the SC200
1 Use SC200 keypad to go to Settings > Setup > Clear Write Access Password
2

84
Press Enter.
The password is now permanently cleared. If required, reset the password with DCTools/Web.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Communications
Web Access Security
Server Access
Access to the SC200 web server can be disabled or set for secure access using Secure Sockets
Layer (SSL) protocol.

SSL is a protocol for transmitting encrypted data over the Internet. URLs that require an SSL
connection start with https: instead of http:. If the network is insecure, Eaton recommends that
you disable HTTP Access.
► To change access to the web server
Set the following parameters as required.
Parameter
Description
Where to find:
HTTP Access
Enable to allow un-encrypted access to the SC200
web server.
Disable to prevent un-encrypted access to the
SC200 web server.
HTTPS Access
SC200: Settings > Setup
Enable to allow encrypted access to the SC200
web server.

DCTools/Web:
Communications > HTTP
HTTPS access will be slower than HTTP (Web)
because of the encryption process.
Disable to prevent encrypted access to the SC200
web server.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
85
SC200 Handbook
User Setup
► To setup specific users and control their access levels
For each user, set the following parameters as required.

If there are no active users then web access is disabled. Use DCTools to set up an active user.
Parameter
Description
User Name
This is not used in the login process (except for
"Default User"). It is displayed at the top-right of
the Web view screen.
Logon ID*
The logon name of the user.
Password*
The password of the user.

Read
Where to find:
Lost passwords cannot be recovered. If a
password is lost then set a new password.
Allows the user to view configuration settings
only.
DCTools/Web:
Allows the user to change configuration settings. Communications > HTTP
(Web)
Allows the user to download configuration or
snapshot files.
Write
Backup
Restore
Allows the user to upload configuration or
snapshot files.
Execute
Commands
Allows the user to stop and start control
processes.
Upgrade Firmware
Allows the user to upgrade firmware.
Edit User List
Allows the user to edit the user list and change
user access settings.

*Leave both fields blank to allow Default User (anonymous) log on.
CSP
These are parameters for specific protocols. Contact Eaton for further details.

86
If these protocols are not used then leave the parameters at their default values.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Chapter 5
Maintenance


C
h
Maintenance
a
p
t
e
r
5
Overview

The dc power system contains hazardous voltages and hazardous energy levels. Before
undertaking any maintenance task refer to the Warnings in the dc power system
installation guide.

If a maintenance task must be performed on a "live" system then take all necessary
precautions to avoid short-circuits or disconnection of the load equipment, and follow any
"live-working" instructions applicable to the site.

Only perform the maintenance tasks described in the Maintenance chapter. All other tasks
are classified as Servicing. Servicing must only be performed according to specific
instructions and only by personnel authorized by Eaton. This includes disassembly and/or
servicing of any modules.

For further information on Servicing contact your local Eaton dc product supplier, or refer
to the contact details on page 115.

Topic
Page
Troubleshooting
88
Replacing the System Controller or I/O Board
92
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
87
SC200 Handbook
Troubleshooting
Use the table to troubleshoot minor installation and operational problems. For additional
assistance see contact details on page 115. Return items for replacement or repair with a
completed Equipment Incident Report on page 113.
Problem
Possible Cause
Required Action
SC200 displays a dc power
system alarm message.
SC200 LCD is blank and
green Power On LED is off.
RXP/power cable is
disconnected from the SC200.
Connect cable from connector YS11 to the
dc power system voltage feed module
(see Connections on page 3). Wait for
start-up to complete.
The ac supply is off and the
batteries are not connected
because the Low Voltage
Disconnect (LVD) has
disconnected.
None. The power system including the
SC200 will return to normal operation
when the ac supply is within its specified
voltage range.
Faulty Voltage Feed Module
(VFM) or faulty SC200.
Replace faulty unit.
SC200 is in start-up mode
Wait for start-up to complete. See
Starting the SC200 on page 6.
Faulty SC200
Replace faulty SC200.
SC200 Red LED or Yellow
LED is on.
An alarm is active.
Check the type of alarm on the LCD or
with DCTools/Web or PowerManagerII. See
Alarm Descriptions on page 97.
Unable to change settings
from SC200 keypad.
Keypad access is set to Read
Only or PIN Protected.
See Keypad Access Security on page 10.
Rectifier does not shutdown
when LBRS is enabled.
Load Based Rectifier Shutdown
is not available with APR48-3G,
EPR48-3G, APR24-3G and
CR48-3G rectifiers.
See Load Based Rectifier Shutdown on
page 31.
Monitor OK relay (RLY6) is
de-energized.
An active alarm, digital input or Check relay mapping. See Digital
analog input is mapped to this
Outputs on page 67.
relay.
SC200 LCD is blank and
green Power On LED is on.
Incorrect battery or load
current readings.
88
See Alarm Descriptions on page 97.
Problem with power or
communications to I/O board.
Check all connections (see Connections
on page 3).
SC200 or I/O board software
corrupt or hardware fault.
Replace faulty unit.
Bus voltage sense polarity is
incorrect.
Check the bus voltage sense polarity and
correct if necessary.
Incorrectly configured shunt
inputs.
Check shunt mapping and gain is correct.
Current is within the Battery
State Threshold. See details on
page 50.
None, normal operation.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Maintenance
Problem
Possible Cause
Required Action
SC200 or DCTools/Web
displays ??? or N/A
Failed, disconnected or
unconfigured sensor.
Replace, connect or configure sensor.
Faulty or disconnected voltage
feed module.
Replace or connect voltage feed module.
Incorrect I/O board mapping.
Check I/O board mapping. See details on
page 109.
DCTools connection
problem (Target Failed to
Respond error)
Connection problem
Refer to following communications
problems.
Modem/RS232
communications problem.
Incorrect, disconnected or faulty Check an RS232 straight-thru cable is
cable.
plugged into XS1 and the modem.
Replace faulty cable.
Access to RS232 connector XS1
is restricted.
Use a DB9 ribbon cable extension (Farnell
part number 869-6411).
Incorrect communications
settings.
See PSTN Modem Communications on
page 78 or GSM Modem
Communications on page 80.
Incorrect modem setup string.
Refer to the AT command section in the
modem's manual.
Modem not powered or other
modem problem.
Refer to the modem's manual.
Incompatible modem.
Contact your Eaton dc product supplier
or Eaton for advice. See Worldwide
Support on page 115.
Password required to change
settings.
See Write Access Password on page 84.
Serial communications are
disabled
S3P Access is disabled.
Set S3P Access to Enabled. See details in
the System Controller Operation
Handbook.
Ethernet communications
problem
Incorrect, disconnected or faulty Check a network patch cable is connected
cable.
from XS31 to a live network outlet.
Replace faulty cable.
Ethernet link is not active.
On the Ethernet connector (XS31) check:
Yellow LED is continuously lit to show
link is active.
Green LED flashes to show traffic is
reaching the SC200.
See the diagrams on page 2 for position
of the Ethernet connector.
Incorrect communications
settings.
See Ethernet Communications on page
72.
SC200 serial communications
are disabled.
Check S3P Access is enabled. See details
on page 84.
Password required to change
settings (using DCTools or
PowerManagerII).
See Write Access Password on page 84.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
89
SC200 Handbook
Problem
Web communications
problem
Possible Cause
Required Action
Ethernet communications
problem.
See previous entry.
Cannot connect to web server.
Check IP address and other settings in
SC200 are correct. Check correct IP
address is used in web browser address
bar. See Ethernet Communications on
page 72.
Check HTTP Access or HTTPS Access is
enabled. See Web Access Security on
page 85.
Cannot log on to web server.
Incorrect Logon ID or Password, or no
active users setup.
Use DCTools to set up an active user. See
Web Access Security on page 85.
Web communications lost
(Comms Lost error message).
Check that the SC200 is operating.
Check the Ethernet communications
connections. See previous entry.
Check web browser type and version. See
Compatible Software on page 4.
USB communications
problem
Lost Logon ID and/or
Password.
Use DCTools to set up a new Logon ID
and/or Password. See Web Access
Security on page 85.
Default User log on is not
available.
Default User is not setup or not active.
A user cannot change settings,
Backup or Restore, Execute
Commands, Upgrade
Firmware, or Edit User List.
Check the user's access levels. See Web
Access Security on page 85.
Use DCTools to set up a Default User. See
Web Access Security on page 85.
Incorrect, disconnected or faulty Check a USB A/B cable is plugged into
cable.
the USB port and a PC USB port.
Replace faulty cable.
90
SC200 serial communications
are disabled.
Check S3P Access is enabled. See details
on page 84.
DCTools not installed on PC or
wrong version.
Install latest version of DCTools.
Download from
www.powerquality.eaton.com/downloa
ds.
Password required to change
settings.
See Write Access Password on page 84.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Maintenance
Problem
Possible Cause
Required Action
SC200 time/date is incorrect Time/date is different on SC200 None. Time shown on SC200 is UTC.
compared to DCTools/Web.
Time on PC running DCTools/Web is
local time.
String Fail Alarm
Time needs to be set.
See SC200 Internal Clock on page 14.
SC200 time can be set, but is
incorrect when SC200 restarts.
Internal battery is dead. Return SC200 for
service. (If removed, the battery must be
disposed of according to the
manufacturer's instructions.)
The Battery Mid-point
See Battery Mid-point Monitoring in the
Monitoring system has detected dc power system installation guide.
a voltage imbalance in one of
the battery strings.
A Battery Mid-point Monitoring Check the sense wires.
sense wire is disconnected.
I/O board Power/Comms
OK LED is off
I/O board is not powered or
faulty.
Check connection to YH3 on I/O board.
See Connections on page 3.
Replace I/O board if faulty.
I/O board Power/Comms
OK LED is flashing.
I/O board is responding to an
Identify command from the
SC200.
None, this is normal operation. See
details on page 62.
LVD Status LED(s) (on I/O
board) are on.
LVD contactor is energized.
None, this is normal operation.
LVD Status LED(s) are off
LVD contactor is de-energized.
(I/O board Power On LED is
on).
None, this is normal operation.
LVD Status LED(s) flashing.
The contactor is in the wrong
state (SC200 internal state does
not match signal from contactor
auxiliary switch).
Check the electrical and mechanical
operation of the contactor and auxiliary
switch.
LVD Type setting is incorrect.
Check LVD Type setting.
LVD settings incorrect.
Check LVD is enabled and set to correct
values. See details on page 37.
LVD contactor(s) not
operating.
Check all wiring and connectors. See
Connections on page 3.
Check that the LVD manual control is set
to AUTO. See details on page 34.
Check that the contactor is correctly
configured and mapped to the I/O
board. See details on page 38.
Contactor is disconnected.
Check the control and dc power cables
are connected. See details on page 3.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
91
SC200 Handbook
Problem
Possible Cause
Required Action
System has no dc output
(rectifiers are on).
Load fuse or disconnect device
open.
Check for open fuse or disconnect device.
LVD contactor has disconnected Use DCTools/Web to check LVD is enabled
the load.
and set to correct values. (LVD status
LED on the I/O board is on when
contactor is energized.)
Check that the I/O board is connected
(Power LED is on).
Check that the LVD control and power
cables connections on page 3.
Check the connections from the load bus
to the LVD.
System has no battery input
Battery disconnect device or
fuse open.
Check for open battery disconnect device
or fuse.
LVD has disconnected the
battery because ac supply is off
and the battery is fully
discharged.
None. The battery will be automatically
reconnected when the ac supply is
restored.
LVD contactor is open.
Use DCTools/Web to check LVD is enabled
and set to correct values. (LVD status
LED on the I/O board is on when
contactor is energized.)
Check that the I/O board is connected
(Power LED is on).
Check that the LVD control and power
cables are connected. See Connections on
page 3.
Check the connections from the battery
bus to the LVD.
Replacing the System Controller or I/O Board
The SC200 system controller or the I/O board can be replaced without switching off the dc
power system and disconnecting the equipment it powers.
The specific procedures depend on the system configuration. Refer to the dc power system
Installation and Operation Guide.
92
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Appendix A
Specifications


A
p
Specifications
p
e
n
d
i
x
A
SC200 system controller
Communications
USB
RS232
Ethernet
External modem options
Version:
1.1 (12Mbits/s)
Connector:
USB B (female)
Interface:
RS232 (DTE)
Connector:
DB9M
Interface:
10baseT
Connector:
RJ45
Protocols:
TCP/IP, SNMP, S3P over IP,
http (Web), https (secure Web),
SNTP, Modbus-TCP, Serial
Server
MAC Address:
See details on page 72.
Web browser:
Microsoft Internet Explorer 8
(IE6 is compatible but with
reduced performance), Mozilla
Firefox 3.0.
Type:
PSTN or GSM
Operation:
Dial in/Dial out on alarm*
* Can operate as a backup for Ethernet communications.
IOBGP-00, -01 I/O Board
The following specifications apply to a single IOBGP-00, -01 I/O board connected to the SC200
system controller.
Digital Outputs/Alarm Relays (IOBGP)

Number of Digital Outputs/Relays
6 (one also used for Monitor OK alarm)*
Contact Arrangement
One changeover contact per relay
Contact Rating
0.1A @ 60V dc maximum
Connectors
Screwless terminal blocks
Wire Size
0.5 - 2.0mm2 [20 - 14 AWG]
Isolation
Relay connections are isolated to 500V dc from all
other circuitry, earth and system common.
* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board
loses power or loses communication with the SC200.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
93
SC200 Handbook
Battery Mid-point Monitoring
Number of Strings
Standard:
Maximum:
4
24 (with additional IOBGP-01 I/O
boards)
Range
–35V to +35V
Resolution
<30mV
Accuracy
±0.5% at 25°C [77°F], ±1% over rated temperature
range
Digital Inputs (IOBGP)
Number of Digital Inputs
6
Connectors
Screwless terminal blocks
Wire Size
0.5 - 2.0mm2 [20 - 14 AWG]
Input Types
Voltage-free switch or relay contacts only
Input Range
Live Bus to Live Bus + 5V
Input Common
Same bus as used for current shunts (Live bus is
standard)
Input Protection
Protected against damage from short circuit to live
or common bus
Temperature Sense Inputs (IOBGP)
Number of Temperature Sense Inputs
2
One only connected as standard. Second input available
(requires additional temperature sensor).
Range
2.53V to 3.43V (-20 to +70°C [-4 to +158°F])
Resolution
< 0.01V (< 1°C [1.8°F])
Accuracy
±1°C [1.8°F] at 25°C [77°F], ±2°C [3.6°F] over rated
temperature range
Maximum Cable Length
20m (65 feet)
Connector
RJ45
Current Sense Inputs (IOBGP)
94
Number of Current Sense Inputs
3
Range
–50 to +50mV
Resolution
<50µV
Accuracy
±0.5% at 25°C [77°F], ±1% over rated temperature
range
Connector
RJ45
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Specifications
Bus Voltage Sense Input (IOBGP)
Number of Bus Voltage Sense Inputs
1
Range
–60V to +60V
Resolution
30mV
Accuracy
±0.5% at 25°C [77°F], ±1% over rated temperature
range
Connector
MTA156 (2-way)
Low Voltage Disconnect (IOBGP)
Number of contactor connections
2 per IOBGP I/O board
Number of LVD channels
16
Contactor Type
Normally Open (NO) with auxiliary contacts only.
Contactor Coil Voltage (nominal)
12V, 24V or 48V
Maximum Hold-in Current
1.2A (per contactor)
Connector
MTA156 (4-way)
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
95
SC200 Handbook
96
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Appendix B
Alarm Descriptions


A
p
p
Alarm Descriptions
e
n
d
i
x
B
AC Fail
All rectifiers report ac supply failure or a digital input with Function set to "AC Fail"
is active.
ACD Fan Fail
The ac distribution cooling system or fan controller has failed (indicated by an active
digital input with Function set to "ACD Fan Fail".
Auxiliary Sensor Fail
An I/O board has an analog input with Function User Defined and the input is either
out of range or unavailable.
Battery Current Limit
Battery Current Limit (BCL) is active. See Battery Current Limit on page 21.
Battery Fuse Fail
A battery fuse has blown or a battery disconnect device has operated (indicated by
an active digital input with Function "Battery Fuse Fail").
Battery Temperature
High
The analog input with Function set to "Battery Temperature" has a value above the
Battery Temperature High Threshold.
This alarm indicates either thermal runaway of the batteries or that the batteries are
operating at a temperature that may cause reduced battery life.
Battery Temperature
Low
The analog input with Function set to "Battery Temperature" has a value below the
Battery Temperature Low Threshold.
This alarm indicates a risk to the standby power system battery as lower
temperatures reduce the battery capacity.
Battery Test
The Battery Test control process is active. See Battery Test on page 22.
Battery Test Fail
The batteries do not have the required capacity or are not fully charged. See Battery
Test on page 22.
Cabinet Fan Fail
A cabinet fan has failed (indicated by an active digital input with Function set to
"Cabinet Fan Fail").
Configuration Error
One of the following is true:

The Rectifier Current Limit is set higher than the Maximum Current Limit of all
the registered rectifiers. See details on page 29.

The OVSD Set Point is out of the range of any registered rectifiers. See details on
page 29.

More than one digital output are mapped to the same relay on an I/O board or
SiteSure-3G Module. See details on page 67.


An LVD contactor is in Conflict state. See details on page 38.

Smart Alarm Based Disconnect is Enabled, but the corresponding Smart Alarm is
Disabled. See details on page 38.
A Smart Alarm source has an invalid Source Triggered setting.
DO Manual
A digital output is set to manual control (control state is set to Active or Inactive). See
Digital Outputs on page 67.
Equalize
The Equalize control process is active. See Equalize on page 24.
Fast Charge
The Fast Charge control process is active. See Fast Charge on page 25.
Generator Enable
The Generator Control process is active and Ah Discharged has exceeded the AmpereHour Threshold or the bus voltage is below the Voltage Threshold. See Generator Control
on page 60.
Generator Fail
Generator Enable is active but the SC200 has not detected that the ac supply is present
(rectifiers have not turned on) after the Generator Fail Alarm Recognition Period.
High Float
The bus voltage is above its normal range (set by the High Float Threshold).
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
97
SC200 Handbook
High Load
The bus voltage is higher than the safe range for the load and/or battery (set by the
High Load Threshold).
In Discharge
Battery Charge State is Discharge (see details on page 49).
Load Fuse Fail
A load fuse has blown or a load disconnect device has operated (indicated by an
active digital input with Function "Load Fuse Fail").
Low Float
The bus voltage is below its normal range (set by the Low Float Threshold).
Low Load
The bus voltage is lower than the safe range for the load and/or battery (set by the
Low Load Threshold).
LVD Characterization Error
An LVD contactor must be characterized. See Low Voltage Disconnect on page 34.
LVD Disconnected
An LVD contactor has disconnected the battery or load. See Low Voltage Disconnect
on page 34.
LVD Fail
An LVD contactor is faulty or the control cable from the I/O board is disconnected.
See Low Voltage Disconnect on page 34.
LVD Manual
An LVD is set to MANUAL CONNECT or MANUAL DISCONNECT. See Low
Voltage Disconnect on page 34.
Missing Hardware
The SC200 has lost communication with a mapped I/O board or SiteSure-3G
module. Or, an input or output is mapped to an invalid I/O board or SiteSure-3G
module. See I/O Board Mapping on page 109.
MOV Fail
One or more MOV cartridges have failed and must be replaced (indicated by an
active digital input with Function set to "MOV Fail").
Multiple Rectifier
Comms Lost
More than one rectifier has lost communications. See also Rectifier Comms Lost on
page 98.
Multiple Rectifier Fail
Multiple rectifiers are faulty or their ac supply has failed without causing partial or
total ac supply failure.
Partial AC Fail
A digital input with Function set to "Phase Fail" is active, or more than 20% of singlephase rectifiers are reporting ac supply failure, or all 3-phase rectifiers are reporting
loss of the same phase.
Rectifier Comms Lost
Normally this alarm indicates that a rectifier has been removed during routine
maintenance. However, faulty rectifier communications or losing the rectifier
communications bus can also trigger this alarm. If removing multiple rectifiers
triggers this alarm, reset it from the keypad before it triggers an external alarm.
Rectifier Current Limit
Rectifier(s) in current limit.
Rectifier Fail
A rectifier is faulty or its ac supply has failed without causing partial or total ac
supply failure.
Rectifier No Load
The total rectifier current is less than 2% of the maximum system output current or is
less than 2A.
Rectifier Over
Temperature
Rectifier(s) operating in temperature turndown mode, because of high ambient
temperature or low ac supply voltage.
Sensor Fail
The current, temperature or voltage sensing system is faulty, or the I/O board
mapping is incorrect.
Standby Mode
The SC200 is on but inactive. Another system controller controls the dc power
system. If the other system controller fails or is disconnected then the SC200 in
Standby Mode will become active (after a short delay).
String Fail
There is a voltage imbalance in one of the battery strings. See Battery Mid-point
Monitoring on page 50.
98
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Alarm Descriptions
System Overload
The power system is operating close to its maximum capacity and more rectifiers are
needed. The System Overload threshold is configurable. See System Overload Alarm
on page 42.
Unknown Hardware
The SC200 has detected an unknown type of device on the RXP bus. Contact your
Eaton DC product supplier for advice.
Unmapped IOB Found
An I/O board or SiteSure-3G module is connected to the SC200, but its serial number
is not in the I/O Board to Serial Number Mapping table. See I/O Board Mapping on
page 109.
Wrong Battery Polarity
An analog input with Function set to "Reverse Battery Detect" has a value above the
Bus Voltage.
This alarm indicates the battery is connected with wrong polarity. See Reverse
Battery Detection on page 58.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
99
SC200 Handbook
100
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Appendix C
Connector Pin-outs


A
p
p
Connector Pin-outs
e
n
d
i
x
C
System Controller Connector Pin-outs
Connector
Type
Purpose
XS1
DB9M
RS232 Serial Interface
XS31
YS11
USB
RJ45
RJ45
USB B
Ethernet Interface
RXP System
Communications
USB Serial Interface
Pin
Description
1
-
2
RD (Receive Data)
3
TD (Transmit Data)
4
DTR (Data Terminal Ready)
5
Common (Ground)
6
-
7
RTS (Request to Send)
8
-
9
-
1
Rx
2
Rx
3
Tx
4
-
5
-
6
Tx
7
-
8
-
1
+24/48V (System bus voltage)
2
+24/48V (System bus voltage)
3
-
4
RS485-A
5
RS485-B
6
-
7
0V
8
0V
1
VCC (+5 V dc)
2
Data -
3
Data +
4
Ground
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
101
SC200 Handbook
1
1
8
RS232 D9M and RJ45 connector pin-outs
102
RJ45 plug pin-outs
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
8
Connector Pin-outs
I/O Board (IOBGP-00, -01) Connector Pin-outs
See input and output specifications on page 93.
Connector
Type
Purpose
XH4
MTA
156
LVD 1 Interface
XH5
XH6
XH7
XH8
XH9
XH12A
XH15A
MTA
156
RJ45
RJ45
LVD 2 Interface
Current Sense Inputs
Temperature Sense Inputs
MTA
156
LVD Power
MTA
156
Bus Voltage Sense Input
MTA
156
Battery Mid-point
Monitoring sense inputs
Digital inputs D1-D3
Pin
Description
1
Coil -
2
Coil +
3
LVD 1 auxiliary switch
4
Auxiliary switch common
1
Coil -
2
Coil +
3
LVD 2 auxiliary switch
4
Auxiliary switch common
1
Current Input 1 Common
2
Current Input 1
3
+12V out
4
Current Input 2 Common
5
Current Input 2
6
0V out
7
Current Input 3 Common
8
Current Input 3
1
-
2
-
3
-
4
Temp Sense 1+
5
Temp Sense 1-
6
-
7
Temp Sense 2+
8
Temp Sense 2-
1
Bus live
2
Common
1
Controller reference (Live)
2
Controller sense (Com)
1
String 1 Mid-point
2
String 2 Mid-point
3
String 3 Mid-point
4
String 4 Mid-point
1
D1 input
2
0V
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
103
SC200 Handbook
Connector
Type
XH15B
Digital inputs D4-D6
XH16/XH17
Digital relay outputs 1-2
XH18/XH19
Digital relay outputs 3-4
XH20/XH21
YH3
104
Purpose
Digital relay outputs 5-6*
RJ45
DC power system digital
inputs
Pin
Description
3
D2 input
4
0V
5
D3 input
6
0V
1
D4 input
2
0V
3
D5 input
4
0V
5
D6 input
6
0V
1
Relay 1 normally closed (NC)
2
Relay 1 normally open (NO)
3
Relay 1 Common (COM)
4
Relay 2 normally closed (NC)
5
Relay 2 normally open (NO)
6
Relay 2 Common (COM)
1
Relay 3 normally closed (NC)
2
Relay 3 normally open (NO)
3
Relay 3 Common (COM)
4
Relay 4 normally closed (NC)
5
Relay 4 normally open (NO)
6
Relay 4 Common (COM)
1
Relay 5 normally closed (NC)
2
Relay 5 normally open (NO)
3
Relay 5 Common (COM)
4
Relay 6 normally closed (NC)
5
Relay 6 normally open (NO)
6
Relay 6 Common (COM)
1
Load Fuse Fail
2
Battery Fuse Fail
3
+12V out
4
AC Distribution Fan Fail
5
AC Distribution MOV Fail
6
0V out (system live - protected)
7
-
8
System common - protected
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Connector Pin-outs
Connector
Type
Purpose
YH11
RJ45
RXP System
Communications

Pin
Description
1
+24/48V (System bus voltage)
2
+24/48V (System bus voltage)
3
-
4
RS485-A
5
RS485-B
6
-
7
0V
8
0V
* Digital Output 6 is also used as the Monitor Fail alarm relay. It will de-energize if the I/O board
loses power or loses communication with the SC200.
1
8
1
8
RJ45 connector pin-outs
RJ45 plug pin-outs
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
105
SC200 Handbook
106
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Appendix D
System Event Types


A
p
p
System Event Types
e
n
d
i
x
D
Event Type
Description
Additional Event
Information
AI High Activation
An analog input high threshold
alarm has become active.
Analog input number
(DCTools) or name (Web).
AI High Deactivation
An analog input high threshold
alarm has become inactive.
Analog input number
(DCTools) or name (Web).
AI Low Activation
An analog input low threshold
alarm has become active.
Analog input number
(DCTools) or name (Web).
AI Low Deactivation
An analog input low threshold
alarm has become inactive.
Analog input number
(DCTools) or name (Web).
Alarm Activation
An alarm has become active.
Alarm number (DCTools) or
name (Web).
Alarm Deactivation
An alarm has become inactive.
Alarm number (DCTools) or
name (Web).
Clock Change From
The clock was changed to this new
Event Log Time from the old
Event Information time. When the
clock is changed, two event log
entries are recorded. The first is
the Clock Change To event and
the second is the Clock Change
From event.
Clock Change To
The clock was changed to the new
Event Information time from the
old Event Log Time. When the
clock is changed, two event log
entries are recorded. The first is
the Clock Change To event and
the second is the Clock Change
From event.
Configuration Change
The configuration database was
changed.
DI Activation
A digital input alarm has become
active.
Digital input number
(DCTools) or name (Web).
DI Deactivation
A digital input alarm has become
inactive.
Digital input number
(DCTools) or name (Web).
DO Control Activation
A digital output has been
manually activated.
Digital output number
(DCTools) or name (Web).
DO Control
Deactivation
A digital output has been
manually deactivated.
Digital output number
(DCTools) or name (Web).
Logs Cleared
The event and data logs have been
cleared.
Rectifier Restart
A rectifier was started manually.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
107
SC200 Handbook
Event Type
Description
Additional Event
Information
This excludes events where a
rectifier starts due to Load-Based
Rectifier Shutdown or after the
removal of a fault condition.
108
Rectifier Shutdown
A rectifier was shut down
manually. This excludes events
where a rectifier shuts down due
to Load-Based Rectifier Shutdown
or a fault condition.
Start Up
Records when the controller
started running.
Smart Alarm Activation A smart alarm has become active.
Smart Alarm number
(DCTools) or name (Web).
Smart Alarm
Deactivation
Smart Alarm number
(DCTools) or name (Web).
A smart alarm has become
inactive.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Appendix E
SC200 Mappings


A
p
SC200 Mappings
p
e
n
d
i
x
E
The SC200 uses mappings to allow it to associate internal functions, alarms and physical I/O
devices.

A default mapping is set at the factory before delivery. Usually this default mapping will not need
to be changed.
I/O Board Mapping
The serial numbers of an I/O board and SiteSure-3G modules, and the physical connectors on
the board/modules are mapped to logical numbers in the SC200. This allows the physical
inputs and outputs (including LVD contactors) to be recognized by the SC200.
I/O Board serial number mapping
Each I/O board serial number must be mapped to a logical IOB Number.
Usually, I/O board serial number mappings only need to be changed if:

The I/O board is changed or added. See details on page 92.

The SC200 is changed and/or a new configuration file is loaded into the SC200. See details
on page 92.

This mapping is not included in configuration files and must be set if an SC200 is changed or
loaded with a new configuration file. Input/output, sensors and most voltage control processes are
only available if this mapping is set.
► To map I/O boards
Either:

Use the SC200 keypad to go to: Settings > IOBs. The serial numbers of registered
input/output boards are displayed.

Select an unmapped Input/Output board (identified as New). Press Enter. Identity
information is displayed and the I/O board LED will flash.

Press Map and select an unused IOB Number (or one marked as Missing, if replacing an
I/O board). Press Enter.
Or:

In DCTools/Web go to: Configuration > RXP

Copy the I/O board serial number(s) from the RXP Devices table to the I/O Board to Serial
Number Mapping table to map an IOB Number to each I/O board (overwrite an existing
serial number if required).

If multiple SiteSure-3G modules are installed use the I/O board Identify function to physically
identify each board. See details on page 62.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
109
SC200 Handbook
I/O connector mapping
Each I/O connector (analog input, digital input and digital output) on an I/O board must be
mapped to a logical IOB Number and IOB AI, IOB DI or IOB DO Number.
► To map I/O connectors
See Analog Inputs on page 63, Digital Inputs on page 66 and Digital Outputs on page 67.
The following tables show the default connector mappings:
Analog
Input
Name
Function*
IOB
Number
IOB AI
Number
Connector
1
IOBGP 1 Bus Voltage
Bus Voltage
1
1
XH9
2
IOBGP 1 Mid-point 1
Battery Mid-point
1
2
XH12A
3
IOBGP 1 Mid-point 2
Battery Mid-point
1
3
XH12A
4
IOBGP 1 Mid-point 3
Battery Mid-point
1
4
XH12A
5
IOBGP 1 Mid-point 4
Battery Mid-point
1
5
XH12A
6
Battery Current
Battery Current
1
6
XH6
7
Current 2
User Defined
1
7
XH6
8
Current 3
User Defined
1
8
XH6
9
Battery Temperature
Battery
Temperature
1
9
XH7
10
Temperature 2
User Defined
1
10
XH7
Digital
Input
Name
Function*
IOB
Number
IOB DI
Number
Connector
1
Digital Input 1
User Defined
1
1
XH15A
2
Digital Input 2
User Defined
1
2
XH15A
3
Digital Input 3
User Defined
1
3
XH15A
4
Digital Input 4
User Defined
1
4
XH15B
5
Digital Input 5
User Defined
1
5
XH15B
6
Digital Input 6
User Defined
1
6
XH15B
7
Load Fuse Fail
Load Fuse Fail
1
7
YH3
8
Battery Fuse Fail
Battery Fuse Fail
1
8
YH3
9
ACD Fan Fail
ACD Fan Fail
1
9
YH3
10
MOV Fail
MOV Fail
1
10
YH3
* Function is an internal analog or digital input value used by the SC200 for voltage control
processes, and/or to generate System States, and/or to generate system alarms.
110
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
SC200 Mappings
Digital
Output
Name
IOB
Number
IOB DO
Number
Connector
1
Summary Non Urgent
1
1
XH16
2
Low/High Load
1
2
XH17
3
Rectifier Fail
1
3
XH18
4
AC Fail
1
4
XH19
5
Load/Batt Disconnect
1
5
XH20
6
IOBGP 1 RY6/Mon OK
1
6
XH21

Digital outputs are activated by mappings from alarms (see Digital Output (Relay) Mapping on
page 111) or by a test (see Digital Outputs on page 67).
LVD connector mappings
For details refer to LVD Configuration on page 37.
Digital Output (Relay) Activation
Any alarm can activate one or two digital outputs (A and B).
► To map digital outputs

See System Alarms on page 42, Smart Alarms on page 44, Analog Inputs on page 63,
Digital Inputs on page 66 and Digital Outputs on page 67.
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
111
SC200 Handbook
112
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Equipment Incident Report
EQUIPMENT INCIDENT REPORT
Please enter as much information as you can. Send the completed form, together with the item for repair to your nearest
authorized service agent. NOTE: Only one fault to be recorded per form.
For further information contact your local Eaton dc product supplier or Eaton (see contact details on page 115). Or
email: [email protected]
Date: ________________
Customer Information
Company: _______________________________________________________________________
Postal Address: _______________________________________________________________________
_______________________________________________________________________
Return Address: _______________________________________________________________________
(Not PO Box)
_______________________________________________________________________
Telephone: _______________
Fax: _______________
Email: _________________
Contact Name: _______________________________________________________________________
Location of Failure
Product code: ___________
Serial number: __________
Document number: _____________
System type installed in: _________________________
Serial number: _____________
Site name or location: __________________________________________________________
Fault discovered
Failure source
Delivery
Unpacking
Installation
Initial test
Operation after _____ years
Other _______________
Design
Manufacturing
Documentation
Transportation
Installation
Handling
______________
Effect on system operation
None
Minor
Major
_______________________
INFORMATION (fault details, circumstances, consequences, actions)
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
Internal use only.
Reference No: __________ RMA: __________ NCR: __________ Signature: _________________ Date: _______________
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
113
INFORMATION continued (fault details, circumstances, consequences, actions)
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
______________________________________________________________________________________
SG/03 ISS06
114
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Worldwide Support


Worldwide Support
For product information and a complete listing of worldwide sales offices, visit Eaton's website
at: www.eaton.com/telecompower or email: [email protected]
For technical support contact either your local Eaton dc product representative, the closest
office from the following list, telephone (+64) 3 343-7448, or email
[email protected]
Australia:
1300 877 359
Canada:
1-800-461-9166
Central America:
+52 55 9000 5252
China:
+86-571-8848-0166
+86-571-8848-0366
Europe / Middle East / Africa:
+44-1243-810-500
Hong Kong / Korea / Japan:
+852-2745-6682
India:
+91-11-4223-2325
New Zealand
0800 DC Power (0800 327-693)
Singapore / South East Asia:
+65 6825 1668
South America:
+54-11-4124-4000
South Pacific:
+64-3-343-7448
Taiwan:
+886-2-6600-6688 or free call 0800-038-168
United States of America (Toll Free):
1-800-843-9433 - option 2 - option 6
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
115
SC200 Handbook
116
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Index


Index
B
?
Battery • 49
??? on SC200 Display • 12, 89
Ah Discharged • 26, 49
Battery Capacity • 49
A
Battery Charge State • 49
AC Rectifier Current Limit • 29
Battery Current • 11, 63, 88, 109
AC Supply
Battery Current Sensor Fail • 49
AC Fail Alarm • 41, 65, 97
Battery Fuse Fail Alarm • 65, 97, 109
AC Voltage • 28, 63
Battery Fuses • 92
ACD Fan Fail Alarm • 65, 97, 109
Battery Temperature • 11, 27, 49
Low AC Threshold • 28
Battery Temperature High Alarm • 41, 97
ACD Fan Fail Alarm • 65, 97, 109
Battery Temperature Low Alarm • 41, 97
Active Voltage Control • 20, 21
Battery Test • 20, 21, 22, 25, 27
Ah Discharged • 26, 49
Battery Test Alarms • 97
Alarms • 39
Cells Per String • 27, 49
Alarm Configuration • 39, 41
CellSure • 83
Alarm Descriptions • 97
Equalize • 20, 22, 24
Alarm Tracking • 42
Fast Charge • 20, 22, 25
Analog Input Alarms • 39, 63
In Discharge Alarm • 98
Audible Alarm Indication • 12, 40
Mid-Point Monitoring (MPM) • 50, 94
Digital Input Alarms • 39, 66
Number of Cells • See Cells Per String
LEDs (SC200) • 2, 12, 88
Reverse Polarity • 58, 99
LVD Status LED • 2, 91
String Fail Alarm • 50, 51, 91, 98
Mappings • 109
Temperature Compensation • 20, 27
Monitor OK Alarm • 2, 88
Temperature Sensor • 2, 3, 63, 94, 109
Rectifier Alarms • 97
Time Remaining • 54
Battery Circuit Breakers • 92
Rectifier Comms Lost Alarm • 30, 98
Battery Fuse Fail Alarm • 65, 97, 109
Relays • See Digital Outputs (Relays)
Battery Current Limit (BCL) • 20, 21, 25
SC200 Alarms • 12, 39, 88
Severity • 40
Battery Current Limit Alarm • 97
Smart Alarms • 44
Engine Run BCL • 21
Sound • See Audible Alarm Indication
BCL • See Battery Current Limit (BCL)
System Alarms • 39, 97
Browsers (recommended) • 4
System Overload Alarm • 41, 42, 99
Bus Voltage • 63
Bus Voltage Sense • 2, 21, 109
Analog Inputs • 11, 63
Analog Input Alarms • 39, 63
High Load Alarm • 41, 98
Mappings • 109
Low Load Alarm • 41, 98
Audible Alarm Indication • 12, 40
Auxiliary Sensor Fail Alarm • 97
C
AVC • See Active Voltage Control
Cabinet Fan Fail Alarm • 97
Cells Per String • 27, 49
CellSure • 83
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
117
SC200 Handbook
Characterization of LVD • 34
Data Log • 69
Circuit Breakers
Event Log • 68
Battery Circuit Breakers • 92
PC Log • 70
Battery Fuse Fail Alarm • 65, 97, 109
System Event Types • 107
Load Circuit Breakers • 92
DCTools • 4, 13, 72, 78, 80
Load Fuse Fail Alarm • 65, 98, 109
N/A (in DCTools/Web) • 89
Communications • 72, 93
Software Versions • 4
Browsers (recommended) • 4
Target Failed to Respond Error • 89
Communications Options • 72
Write Access Password • 84, 89
Connector • 2, 3
Digital Inputs • 66, 94, 109
CSP • 86
Connectors • 2, 3, 103
DCTools • 4, 13, 72, 78, 80
Digital Input Alarms • 39, 66
Ethernet Communications • 72, 89
Mappings • 109
GSM Modem Communications • 80, 89
System States • 65
HTTP/HTTPS • 85
Digital Outputs (Relays) • 40, 67, 93
Loss of Communications • 83
Connectors • 2, 3, 103
MAC Address • 72
Relay Mapping • 41, 66, 67, 111
Modbus • 77
Remote Control State • 67
Problems • See Troubleshooting
Test Digital Outputs • 67
PSTN Modem Communications • 78, 89
Display Settings • 11
Security • 83
Language • 16
Serial Server • 83
SNMP • 75
E
USB Communications • 13, 90
Email Alarm Messages • 82
Web Access Security • 85, 90
Engine Run BCL • 21
Web Server • 74, 90
Equalize • 20, 22, 24
Write Access Password • 84, 89
Equalize Active Alarm • 97
Configuration File • 17, 39
Ethernet
Backup and Restore • 18
Connector • 2, 3
Changing a Configuration Setting • 10
Ethernet Communications • 72, 89
Contrast • See Display Settings
MAC Address • 72
Control • See Voltage Control
Problems • See Troubleshooting
CSP • 86
Event Log • 68
Current
System Event Types • 107
Battery Current • 11, 63, 88, 109
Load Current • 11, 63, 88
F
No Load Alarm • 98
Fast Charge • 20, 22, 25
Rectifier Current • 6, 11, 63
Fast Charge Active Alarm • 97
Current Limit
Battery Current Limit (BCL) • 20, 21, 25
Rectifier Current Limit • 29
Float Voltage • 20, 28
High Float Alarm • 41, 97
Low Batt Temp Alarm • 41, 98
Current Sense • 2, 3, 63, 94, 109
Function • 65, 66
Fuse
D
Battery Fuses • 92
Data Logging • 68
118
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Index
Load Fuses • 92
Display Settings • 11
Language • 16
LEDs
G
LEDs (SC200) • 2, 12, 88
Generator
Generator Control Option • 60
LVD Status LED • 2, 91
Generator Enable Alarm • 97
Power On LED • 2, 91
Generator Fail Alarm • 41, 60, 97
Troubleshooting • 88
Load Circuit Breakers • 92
GSM Modem Communications • 80, 89
Load Fuse Fail Alarm • 65, 98, 109
H
Load Current • 11, 63, 88
Heatsink Temperature • 28
Load Fuse Fail Alarm • 65, 98, 109
Load Fuses • 92
High Float Alarm • 41, 97
High Load Alarm • 41, 98
Load Power • 11, 63
Horizontal/Vertical Setting of Display • See
Display Settings
Load-Based Rectifier Shutdown • 31
Locate Rectifier • See Identify a Rectifier
HTTP/HTTPS • 85
Log • See Data Logging
Logon (SC200) • 10
I
Logon ID (Web) • 85
Identify a Rectifier • 29
Low AC Threshold • 28
Low Batt Temp Alarm • 41, 98
Identify an I/O Board • 62
Low Load Alarm • 41, 98
Identity Information • 14
Low Voltage Disconnect (LVD) • 34
In Discharge Alarm • 98
Characterization of LVD • 34
Input/Output (I/O) Board
Connectors • 2, 3, 103
Additional I/O • See SiteSure-3G I/O module
LVD Alarms • 98, See Troubleshooting
Analog Inputs • 11, 63
LVD Status LED • 2, 91
Connections to other system components • 3
Mappings • 109
Connector Pin-outs • 103
Problems • 91
Description • 2
LVD • See Low Voltage Disconnect (LVD)
Digital Inputs • 66, 94, 109
I/O Board Mapping • 109
Identify an I/O Board • 62
M
LVD Status LED • 2, 91
MAC Address • 72
Power On LED • 2, 91
Main Screen • 6, 11
Main Screen Items • 11
Repair and Return • 113
Replacing the Input/Output Board • 92
Mains Fail Alarm • See AC Fail Alarm
Mappings • 109
Internal Clock • 14, 91
Mid-Point Monitoring (MPM) • 50, 94
String Fail Alarm • 50, 51, 91, 98
K
Missing Hardware Alarm • 98
Keypad
Modbus • 77
Keypad Access Security • 10, 88
Modem (PSTN, GSM) • See Communications
Monitor OK Alarm • 2, 88
L
MOVs
Language • 16
MOV Fail Alarm • 65, 98, 109
LCD • 6, 88
MPM • See Mid-Point Monitoring (MPM)
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
119
SC200 Handbook
Multiple Rectifier Comms Lost Alarm • 98
Ramp Up Slope • 29
Multiple Rectifier Fail Alarm • 98
Rectifier Alarms • 97
Rectifier Comms Lost Alarm • 30, 98
N
Rectifier Current • 6, 11, 63
N/A (in DCTools/Web) • 89
Rectifier Current Limit • 29
Network Management System (NMS) • See
SNMP
Registration • 28
No Load Alarm • 98
Restart Rectifier(s) • 30
Number of Cells • See Cells Per String
Serial Number • 28, 29
Repair and Return • 113
Shutdown • 29, 30, 88
O
Start Up Delay • 29
Output Voltage and Current • 20, 28, 63
System Overload Alarm • 41, 42, 99
Over Voltage Shut Down (OVSD) • 29
System Power • 11, 63
Voltage Control • 20
Relays • See Digital Outputs (Relays)
P
Monitor OK Alarm • 2, 88
Partial AC Fail Alarm • 98
Relay Mapping • 41, 66, 67, 111
Password
Remote Control State • 67
Web Access Security • 85, 90
Repair and Return • 113
Write Access Password • 84, 89
PC Log • 70
Restart Rectifier(s) • 30
PC/Laptop (Connection via USB) • See USB
Communications
RS232 • 78
Reverse Polarity • 58, 99
Connector • 2, 3
Polarity
Modem (PSTN, GSM) • See Communications
Reverse Polarity • 58, 99
Serial Server • 83
Power
Load Power • 11, 63
S
System Power • 11, 63
PowerManagerII • 4, 40
SC200 system controller
Problems • See Troubleshooting
??? on SC200 Display • 12, 89
Protection • See Security
Alarm Descriptions • 97
PSTN Modem Communications • 78, 89
Changing a Configuration Setting • 10
Configuration File • 17, 39
R
Connections to other system components • 3
Ramp Up Slope • 29
Connector Pin-outs • 101, 103
Rectifiers
Description • 2
AC Rectifier Current Limit • 29
Display Settings • 11
Heatsink Temperature • 28
Firmware Upgrade • 17
Identify a Rectifier • 29
Identity Information • 14
Load Power • 11, 63
Internal Clock • 14, 91
Load-Based Rectifier Shutdown • 31
Keypad • 6, 88
Locate Rectifier • See Identify a Rectifier
Language • 16
Output Voltage and Current • 20, 28, 63
LEDs (SC200) • 2, 12, 88
Over Voltage Shut Down (OVSD) • 29
Main Menu • 8
Problems • See Troubleshooting
Main Screen • 6, 11
Mappings • 109
120
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
Index
N/A (in DCTools/Web) • 89
Temperature Compensation • 20, 27
Problems • See Troubleshooting
Temperature Sensor • 2, 3, 63, 94, 109
Repair and Return • 113
Test Digital Outputs • 67
Replacing the System Controller • 92
SC200 Alarms • 12, 39, 88
Text Messaging (SMS) • See GSM Modem
Communications
Security • See Keypad Access Security
Time • See Internal Clock
Startup • 6
Time Remaining • 54
Transient Voltage Protection
Security • 83
MOV Fail Alarm • 65, 98, 109
Keypad Access Security • 10, 88
Web Access Security • 85, 90
Translation • 16
Write Access Password • 84, 89
Troubleshooting • 88
Repair and Return • 113
Sensor Fail Alarm • 98
Servicing • 113, 115
Auxiliary Sensor Fail Alarm • 97
Technical Assistance • 115
Serial Server • 83
Servicing • 113, 115
Severity • 40
U
Shutdown • 29, 30, 88
Unknown Hardware Alarm • 99
USB
Load-Based Rectifier Shutdown • 31
Over Voltage Shut Down (OVSD) • 29
Connector • 2, 3
Restart Rectifier(s) • 30
Problems • See Troubleshooting
SiteSure-3G I/O module • 62
USB Cable • 13
Smart Alarms • 44
USB Communications • 13, 90
SMS Text Messaging • See GSM Modem
Communications
V
SNMP • 75
SNTP • See Internal Clock
Vertical/Horizontal Setting of Display • See
Display Settings
Software Versions • 4
Voltage (Bus) • 63, See Bus Voltage Sense
Sound • See Audible Alarm Indication
Voltage Control • 20
Specifications • 93
Active Voltage Control • 20, 21
Standby Mode • 98
Bus Voltage Sense • 2, 21, 109
Start Up Delay • 29
Voltage Feed Module • 3
String Fail Alarm • 50, 51, 91, 98
System Alarms • 39, 97
W
System Overload Alarm • 41, 42, 99
Web
System Power • 11, 63
Browsers (recommended) • 4
System States • 65
Language • 16
Web Access Security • 85, 90
T
Web Server • 74, 90
Target Failed to Respond Error • 89
Write Access Password • 84, 89
Technical Assistance • 115
Temperature
Battery Temperature • 11, 27, 49
Battery Temperature High Alarm • 41, 97
Battery Temperature Low Alarm • 41, 97
Heatsink Temperature • 28
Copyright © 2007-2011 Eaton Corporation. All Rights Reserved.
IPN 997-00012-50G
May 2011
121