- No category
advertisement
Service Manual
APC Smart-UPS
®
RT
3,000VA – 10,000VA 200-240 Vac
Tower/Rack Mount
Uninterruptible Power Supply
English
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
1
Table of Contents
1 Safety Precautions........................................................................................................................................... 3
2 Introduction to SURT...................................................................................................................................... 4
2.1
2.2
Key Points ........................................................................................................................................... 4
One-Line Diagram .............................................................................................................................. 4
2.3
2.4
2.5
Main Circuit Components ................................................................................................................... 4
Functional Description ........................................................................................................................ 5
Power Train Operation ........................................................................................................................ 5
2.6 Transistor-Level Diagrams ................................................................................................................. 6
3 User Interface ................................................................................................................................................ 11
3.1 Front Panel Display and Control Buttons ......................................................................................... 11
3.2
3.3
Terminal Mode.................................................................................................................................. 13
SmartSlot Accessories (Webcard)..................................................................................................... 15
4 Installation..................................................................................................................................................... 16
5 Component Replacements............................................................................................................................. 16
6 Troubleshooting ............................................................................................................................................ 17
6.1 Unit Setup ......................................................................................................................................... 17
6.2 Required Tools .................................................................................................................................. 17
6.3
6.4
6.5
Visual Inspections ............................................................................................................................. 17
Troubleshooting Flowchart ............................................................................................................... 18
Diode Checks .................................................................................................................................... 20
6.6 Documenting Failures ....................................................................................................................... 25
7 ECO's ............................................................................................................................................................ 25
8 Test After ECO's ........................................................................................................................................... 26
Appendix A. Fault codes on LED display & stored in EEPROM .................................................................... 28
Appendix B. ECO list as of October, 2005....................................................................................................... 33
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
2
1 Safety Precautions
Read and adhere to the following warnings when installing or servicing a UPS and/or battery packs.
Failure to observe these warnings may result in serious injury, death or damage to the equipment.
W ARNINGS
•
Do not attempt to install or service external batteries alone. A qualified electrician should perform the installation and servicing of external
batteries.
•
Disconnect charging source(s) BEFORE connecting or disconnecting battery terminals.
•
External batteries may retain lethal voltages after power has been disconnected and all switches are off.
•
Use extreme caution when making terminal connections. Do not allow cables to touch anything except the intended terminal.
P RACTICES Always wear:
•
Goggles or face shields
•
Acid-resistant, insulated gloves
•
Protective aprons
•
Protective overshoes or rubber boots
Always use:
•
Insulated tools
•
Rubber mats to cover batteries during servicing
•
Rubber mats or rubber stands on the floor
•
Adequate lifting devices
Remove:
•
Watches, rings, and other metal objects from your body
P RECAUTIONS
•
To avoid static build-up, service personnel should establish a grounding contact prior working on batteries.
•
Do not lay tools or metal parts on top of batteries.
•
Lead-acid batteries contain hazardous, toxic materials.
§ Do not open, alter or mutilate batteries. Internal materials may be harmful to the skin and eyes.
§ Do not dispose of batteries in a fire. There is danger of explosion.
•
Handle, transport and recycle batteries in accordance with local codes and regulations.
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
3
2 Introduction to SURT
2.1 Key Points
•
Double-conversion online topology
•
Inverter voltage is selectable through communication only: 200V, 208V, 220V, 230V, 240V.
•
Bypass “acceptable voltage” window changes with Inverter voltage setting.
•
Batteries must be connected to start UPS. After startup, batteries can be safely removed and replaced without interruption to the output.
•
Lynx2 (3kVA – 6kVA) has single battery (192V nominal) referenced to output Neutral.
•
Lynx3 (7.5kVA – 10kVA) has two battery strings (+192V and -192V nominal) managed independently and charged with separate chargers.
•
Lynx3 (7.5kVA – 10kVA) can accept single-phase or three-phase input voltage. In both cases, Bypass is only single-phase (“L1” and “N” inputs) so the input wiring must be sized to handle full-load current as singlephase.
2.2 One-Line Diagram
160 -284
VAC Input
Input
Filter
Section
Rectifier &
PFC
+/- DC Bus
Inverter
Output
Section
Bypass
Switch
Battery
Charger
240 VAC
Output
192 VDC
Battery
2.3 Main Circuit Components
The primary sections of the UPS are:
•
Input disconnect and filter stage
•
Input Power Factor Correction (PFC) power stage
•
Energy storage stage (dc bus capacitor bank)
•
Output power stage (inverter)
•
Bypass
•
Battery charger
•
Battery: 1 or 2 strings each connected to output Neutral
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
4
2.4 Functional Description
The control of power module and fault detection logic is uP based. The input filter stage contains input backfeed relays, input EMI filter, transient suppression, and battery select transfer relays. Input PFC power stage contains non-isolated power factor correcting AC/DC converters. PFC converter is split in two power sections – positive and negative boost stage – while operating on-line and in positive boost and buck boost power stage while operating on battery. This converter is capable of full power operation from 160 to 280 VAC line to neutral or from a nominal DC battery voltage of
192VDC. The output from this stage is a +/-395V center tapped dc bus. The energy storage stage is split DC bus capacitor handling seamless transitions from battery to line and vice versa as well as the low and high frequency power stages ripple. The inverter stage operates directly from +/- 395VDC bus and produces an AC output voltage of
200/208/220/230/240Vac (for NAM and EMEA) or 200Vac (for Japan). The output of the UPS is either connected through a pair of relays either to the inverter or to the input filtered line. The UPS contains 1 or 2 battery chargers, each rated
400W.
2.5 Power Train Operation
When operating on line, the input voltage is first rectified so two half wave rectified voltage waveforms are produced in reference to the Neutral. Positive line rectified signal is fed to positive boost PFC stage. This stage is a boost type converter which converts positive half rectified input signal into DC positive bus voltage of +395V, drawing the input current in phase with positive half cycle of the line current. The boost stage consists of an input choke, high frequency
IGBT switch, high frequency soft recovery diode and the output electrolytic capacitor. The positive boost stage is bypassed by a low power diode which serves as the boost converter protection in the case of sudden line overshoots and overvoltages or any other condition which causes input line peak voltage to be higher than DC bus capacitor voltage. The negative line rectified signal is fed to negative PFC stage. This stage is also boost type converter and operates in the same manner as the positive PFC boost stage. This stage converts negative line half rectified voltage to negative DC bus voltage of -395V. The bottom line is that when operating on line both PFC stages are operating as boost converters each processing half of the total output power per phase.
When operating on battery, the transfer relays connect the PFC to a DC voltage from the battery. The battery voltage is fed through a filter and inrush stage to both positive and negative PFC stages. The battery filter consists of chokes and two electrolytic capacitors. The function of the filter is to prevent high frequency ripple from PFC stage going back to battery and to provide differential mode filter for high frequency noise emanating from battery buses or cables (in case of external battery packs). The inrush stage as its name says during startup limits the battery inrush current. When the battery is connected to the input of the PFC stage, the battery filter capacitor and positive DC bus capacitor charging current is limited through two 50 ohm PTC resistors. When capacitors are charged to battery voltage inrush relays are switched into closed position bypassing the PTC resistors. The positive PFC stage operates as a DC/DC boost converter and converts battery voltage to DC bus voltage. The operation in this mode is the same as operation on line as described above, except that current drawn from battery is now DC current. The negative PFC stage operates as buck boost stage and converts battery voltage to negative DC bus voltage.
The output stage of the UPS consists of inverter with output filter and bypass relays. This stage is a DC/AC converter which function is to convert DC bus voltages into regulated output sine wave voltage. The inverter uses a neutral point clamp topology and consists of the top and bottom section. The top section converts positive DC bus voltage of 395V into positive half wave sine voltage and bottom portion converts negative DC bus voltage into negative half sinewave voltage.
The PWM control of inverter regulates the frequency and amplitude of the output AC voltage. The output filter consists of a smoothing choke and a filter capacitor. The filtered voltage is fed through a NO relay contact to the UPS output.
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
5
2.6 Transistor-Level Diagrams
Lynx2: 3kVA – 6kVA
Input 160-280Vac
BATTERY 192V
D22
L101
50 OHM
50 OHM
K1
LINE
BATTERY
K3 L8
D14
Q11
C6//C8
Q2//Q3
C12//C13
D23
Q12//Q13
L4+L5+L6
C27//C28
BATTERY
LINE
K4
Q6//Q7
L7
D19
Q4//Q5
D15
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
D24
Q14//Q15
Q16
6
Lynx II POWER TRAIN
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
7
Lynx3: 7.5kVA – 10kVA (interleaved PFC)
Input 160-280Vac
50/60Hz
BATTERY
+192V
LINE
50 OHM
50 OHM
BATTERY
NEUTRAL
BATTERY
-192V
LINE
BATTERY
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
8
Bypass
Inverter output
200-240Vac
50/60Hz
Lynx3 POWER TRAIN
Lynx3 PFC power board, 640-0761 – Circuit locations
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
9
Lynx3 INVERTER power board, 640-0762
SURT 3kVA-10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
10
3 User Interface
3.1 Front Panel Display and Control Buttons
The front panel contains status and diagnostic LEDs and two control buttons. Several of the LEDs comprise bar graphs that display status and diagnostic information according to the table below.
Load Smart-UPS RT Front Display Battery Charge
Indicator Description
Online The Online LED illuminates when the UPS is drawing utility power and performing double conversion to supply power to connected equipment.
On Battery The UPS is supplying battery power to the connected equipment.
Bypass
Fault
Overload
The Bypass LED illuminates indicating that the UPS is in bypass mode.
Utility power is sent directly to connected equipment during bypass mode operation. Bypass mode operation is the result of an internal UPS fault, an overload condition or a user initiated command either through an accessory or the manual bypass switch. Battery operation is not available while the
UPS is in bypass mode. Refer to Troubleshooting in this manual.
The UPS detects an internal fault.
Refer to Troubleshooting in this manual.
An overload condition exists. See Troubleshooting.
Replace
Battery
The battery is disconnected or must be replaced. See Troubleshooting.
Table 1. Front Panel LEDs.
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
11
Feature Function
Power On Press this button to turn on the UPS. (See below for additional capabilities.)
Power Off Press this button to turn off the UPS.
Cold Start
Self-Test
When there is no utility power and the UPS is off, press and hold the button to power up the UPS and connected equipment.
The UPS will emit two beeps. During the second beep, release the button.
Automatic: The UPS performs a self-test automatically when turned on, and every two weeks thereafter (by default). During the self-test, the UPS briefly operates the connected equipment on battery.
Manual: Press and hold the button for a few seconds to initiate the selftest.
Table 2. Front Panel Control Pushbuttons.
Diagnostic Utility
Voltage
The UPS has a diagnostic feature that displays the utility voltage applied to the UPS.
The UPS starts a self-test as part of this procedure. The selftest does not affect the voltage display.
Press and hold the button to view the utility voltage bar graph display. After a few seconds the five-LED, Battery Charge
display on the right of the front panel shows the utility input voltage.
Refer to the figure at left for the voltage reading (values are not listed on the UPS).
The display indicates the voltage is between the displayed value on the list and the next higher value.
Table 3. Front Panel Bar Graphs.
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
12
3.2 Terminal Mode
SURT can be configured in a number of ways: Network Management Card web interface, PowerChute ® Software,
Terminal Mode, or UPS-Link commands.
To access Terminal Mode, you will need:
- A computer with an RS-232 serial port
- A terminal application such as Hyperterminal
- An APC black cable 940-0024C (included with the UPS)
Make sure that no SmartSlot accessory is installed in the SmartSlot bay of the UPS. The SmartSlot prevents access to certain UPS communication features such as the Terminal Mode.
Using a standard APC serial cable (APC part number 940-0024C), connect the computer serial port to the back of the UPS.
Open a terminal program. Hyperterminal example:
From the Desktop, go to Start => Programs => Accessories => Communication
=>HyperTerminal.
The “Connection Description” dialog box appears. Enter a name for this connection and select any icon for it.
Click [OK]
The “Connect To” dialog box appears. In the “Connect using” drop-down list select the COM port you’re going to use to communicate with the UPS.
If you get a message that this port is used by another application then either use a different COM port or close the application using the intended port.
Click [OK]
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
13
In the communication settings dialog box, select the following settings:
Bits per second: 2400
Data bits: 8
Parity: Note
Stop bits: 1
Flow control: None
Click [OK]
Press the Enter key. The root terminal mode menu will appear, similar to the following:
To configure the UPS, press the 1 key. The UPS will chirp and the “UPS Settings” menu will appear.
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
14
To change a setting, press the corresponding key (not case-sensitive) and follow the instructions.
Please note that if no key is pressed for approximately 5 minutes, the Terminal Mode session will time out and you’ll have to press Enter and start from the root menu again.
3.3 SmartSlot Accessories (Webcard)
SURT models include a standard SmartSlot that is compatible with accessories used in other APC products.
Notes on “event log” entries in the AP9619 (NMC or “webcard”):
•
Almost all internal UPS faults are recorded as "Bad output voltage" regardless of whether or not the detected fault is related to the Inverter or Bypass. The NMC is not able to differentiate between the different UPS failure codes.
•
"Battery charger failure" could be a momentary battery overvoltage condition -- see if this alarm is cleared within 2 seconds in the log.
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
15
4 Installation
See User Manual included with the UPS for installation precautions and instructions.
Installation troubleshooting: Make sure:
• each battery string is above 175V (there are two battery modules per string)
• all battery modules are securely connected
• input AC is connected correctly, input phase_select switch set correctly to 1 or 3 (if exists)
• input breaker closed (if exists)
• output breakers on (if exist)
5 Component Replacements
Replacement boards:
SKU Power Board Control Board
SURT3000 0P7510 0P7603
SURT5000
SURT6000
SKU
SURT7500
0P7510
0P7516
0P7600
0P7606
PFC power Inverter power Main Control Aux Control Bias & I/O
0P7611 0P7621 0P7507
SURT8000 0P7611 0P7621 0P7608
SURT10000 0P7611 0P7621 0P7501
Battery modules (RBC44?) – one for Lynx2, two for Lynx3?
Bezels w/ stickers
Display PCB/bezel assemblies
Fan for Lynx2
Fan for Lynx3
Battery fuses: (515-1030A)
See ??? for optional PDU’s including H/W kit for Lynx2 output
0P7631
0P7631
0P7631
0P7641
0P7641
0P7641
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
16
6 Troubleshooting
Safety: Remove jewelry, pendants and wrist watches.
6.1 Unit Setup
Unpack the UPS and put it on a flat even surface (mind OSHA regulations). Check the packaging for any signs of damage.
Lynx2
Net Weight 120.00 lbs. ( 54.55 kg)
Shipping Weight 140.00 lbs. ( 63.64 kg)
Note:
Follow all environmental regulations. Discard old batteries in an environmentally friendly way. Be sure to deliver spent batteries to a recycling facility or ship to the manufacturer in the replacement battery packing material
.
6.2 Required Tools
•
Digital multimeter (for example, Fluke 87)
•
Power resistor to discharge capacitors
•
Serial communication cable (RS-232)
•
Communication software (for example, laptop and “Hyperterminal” software in Windows)
•
Phillips screwdriver
•
AC power supply
•
Load
6.3 Visual Inspections
Visual inspection is often overlooked but is one of the most important steps in diagnosing a problem. It can also save a lot of time.
Exterior
Check the packaging and exterior of the UPS for any physical damage
1. Plastic bezels
2. Fan guard & blades
3. Bent sheet metal
4. PDU breakers
Interior
Check all wiring, connections, and PCB components
1. Wire insulation broken
2. Burned components and/or burned marks on PCB
3. Daughter PCBs not tight in sockets
4. Components touching chassis or other components (esp. small heatsinks, power resistor leads)
5. Leads not clipped properly, solder-bridges (solder-side of PCB)
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
17
6.4 Troubleshooting Flowchart
Start
Visual inspection
(exterior)
Make sure all battery packs disconnected
Each
Battery pack
>84V?
Yes
No
Remove top panel,
Discharge all caps
Replace battery pack(s)
Visual inspection
(interior)
Diode checks OK?
No
Yes
Connect Battery,
Push ON-Switch
Repair & record failed parts
Brains on?
(Fan on)
Yes
No
(next page)
Troubleshoot
LPS
Lynx 2: Check
D781, D782, D776, D777,
D778, D779, Q712
Lynx 3: Check D704, D705,
D706, D707, D714, D718,
D722, Q704
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
18
(continued)
Fault displayed?
Yes
No
Disconnect SNMP cable from ctrl bd.
Send Y <SM>
Send 1...1 <PROG>
Send CTRL-U
Does unit cold start?
No
Yes
Apply AC input voltage
Check PFC:
Lynx 2: D716-k to J712: +400V
D715-a to J712: -400V
Lynx 3: PGND to +400V
PGND to -400V
Evaluate CTRL-U response and LED display.
See "SURT Faults Table"
+/-400V bus voltages OK?
No
Yes
Troubleshoot
PFC
Does unit go on-line ?
Yes
No
Troubleshoot input voltage sense and transfer relays
Troubleshoot
Inverter
Lynx2: Check Q708,
Q709, Q710, Q711,
Q726, Q727, D748,
D749, D723
Lynx3: Check IC903,
IC904
SURT
Faults
Table
Does unit stay on with all batteries disconnected?
Yes
No Troubleshoot
Charger
Lynx 2: Check Q705,
Q706, Q715, Q716,
Q717, Q718, D750,
D751
Lynx 3: Check
IC1403, IC1404,
IC1407, IC1408 collector-emitter and gate-emitter
Re-connect batteries
Lynx 2: Check Q730, Q731, F703,
F704, D736, D737, D738, D739.
Lynx 3: Check Q1407, Q1408,
F1401, F1402, D1406, D1407,
D1408, D1409
Does unit hold load on battery?
Yes
No
Apply ECO's
SURT
Faults
Table
Calibrate and Test unit
Record failure type, list all failed parts along with part markings
Done
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
19
6.5 Diode Checks
The following “good value” measurements were made with a functional board and a Fluke 87 DMM. These measurements are approximate and will vary depending on the meter used. See the power board diagram on the next page for Test Point locations.
Lynx2: 3kVA - 6kVA
+ Probe - Probe
Good
Value
Components checked If open If short
BATT BATTF zero
F701, F702 (battery fuses)
Both fuses bad, PFC probably has problem
OK
+VIN +400V 0.4V D716, D748 at least 1 part bad
VMID
-400V
-VIN
-VIN
INV_OUT
INV_OUT
VMID
-400V
+400V
VMID
INV_OUT
INV_OUT
0.8V charges
> 2V charges
> 2V
0.8V
Q706, Q715, Q716
D751, Q718, Q717
D750, Q715, Q716
Q705, Q718, Q717
VMID
+VIN
-VIN
B+
VMID
CHGR_SEC
0.45V Q709, Q710, D706
0.4V D715, D723
0.45V Q726, Q727, D707 zero RY704-normally closed
0.45V D738, D739 all parts bad all parts bad at least 1 part bad at least 1 part bad all parts bad at least 1 part bad
RY704 bad at least 1 part bad if < 2V, Q718 or Q717 bad if < 2V, Q715 or Q716 bad at least 1 part bad
OK
Q706 and
Q715/Q716 bad
At least D751 and 1
IGBT bad
At least D750 and 1
IGBT bad
Q705 and
Q718/Q717 bad at least 1 part bad
CHGR_SEC CHGR_L
CHGR_L
VMID
BATTF
LPS_FET
VMID +24V_SW
VMID
ZERO-
OFF_FET
ZERO-
OFF_FET
+15V_SW
B+
BATTF
0.45V D736, D737
0.45V D735
0.55V Q712
0.5V D782
0.5V D781
0.6V D731, TH701, TH702
0.85V Q728 at least 1 part bad
D735 bad
Q712 bad, check F705, Q729, D714, and output diodes
D782 bad, check Q712, F705, Q729, D715
D781 bad, check Q712, F705, Q729, D714
D731 bad, check TH701, TH702
Q728 bad, check MV703, GDT701
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
20
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
21
Lynx3: 7.5kVA through 10kVA
+ Probe - Probe
+BATT
-BATT
+VIN_P1
+VIN_P2
+BATTF
-BATTF
+400V
+400V
Good
Value
zero zero
Components checked
F1403, F1404,
F1405, F1406
If open
Fuses bad, +PFC probably has problem
Fuses bad, -PFC probably has problem
0.35V D903, IC903 (at least)
0.35V D905, IC904 (at least)
If short
D903, D905,
IC903, and/or IC904 bad
OK
OK
-400V
-400V
PGND
PGND
-VIN_N1
-VIN_N1
-VIN_N2
+VIN_P1
+VIN_P2
PGND
0.35V D902, IC903 (at least)
0.35V D904, IC904 (at least)
0.4V
0.4V
0.4V
IC903 (at least)
IC904 (at least)
IC903 (at least)
D902, D904,
IC903, and/or IC904 bad
IC903 and/or IC904 bad
-VIN_N2 PGND
-400V INV_OUT
INV_OUT +400V
INV_OUT
+Charger
Out
-400V
PGND
+400V
-Charger
Out
0.4V IC904 (at least)
0.35V
IC1407, IC1408
0.35V
Open IC1403, IC1404
0.55V Q1407, F1402
0.55V Q1408, F1401
IC1407 and/or IC1408
IC1403 and/or IC1404 bad
F1402 open, Q1407 probably bad
F1401 open, Q1408 probably bad
Q1407 bad
Q1408 bad
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
22
Lynx3 PFC power board, 640-0761
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
23
IC903, IC904 =
Lynx3 INVERTER power board, 640-0762
IC1403, IC1404 =
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
24
IC1407, IC408 =.
Notes:
Cold boot the unit and get the diagnostic information from the serial port before it gets cleared out. If the unit fails right away, read the display LED pattern and the failure code.
Initial power up (brains up) with batteries only
Check calibration of batteries (both strings), DC buses, firmware version, model #, serial number, etc.
Check fault history (^U command)
Cold-boot check calibration of DC buses, output AC voltage, etc.
AC-input check calibration of AC input voltage disconnect batteries to see if unit shuts down (indicates charger failure)
ON & OFF buttons, BYPASS switch, etc.
Startup with AC-input
Load: add/remove/calibration of watts & VA
AC input: add/remove with load
HF-OFF check
• Bypass switch
• 3phase input switch selection
• Lynx3 Battery voltage commands: ^J for +battery, ^K for –battery in PROG mode
• Once failed part is identified, try to determine if there were any manufacturing defects that might have caused the part to fail: Insufficient torque on mounting screw, leads not clipped, solder-bridge, parts touching other components, etc.
• In Terminal Mode, if Model = “??”, the EEPROM has probably become cleared or corrupted.
• “Overload” fault (ctrl-u = 02) is stored during factory testing (during production). Seeing this fault stored in a field unit does not necessarily mean the overload timeout happened at the customer’s site.
• “EQ charge” is normal in later versions of Lynx2 & Lynx3 firmware. If the battery voltage ever drops below 200V, the charger will go up to 235V for at least 5 minutes before settling back down to 218V.
EQ charge is also performed about once every 4 weeks.l
6.6 Documenting Failures
Int'l Stars, SIEBEL, or local spreadsheets. Make sure to record all relevant information about the diagnosis:
•
Reference designators of failed parts with date codes and vendor marks
•
PCB revisions, firmware revisions, accessories added, etc.
•
Recommend Corrective Actions and/or PCB revisions as needed.
7 ECO's
See ECO RMA database. For list as of this revision, see Appendix B.
•
Need table showing which PCB revision combinations can be used together (examples: 762x requires 763x or later, 1kVA change)
•
Need list of PCB revisions that are ok to ECO and send back to customers
•
Need table showing which PCB revisions need which ECO’s
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
25
8 Test After ECO's
(Final test fixture)
All calibration
Cold-boot
AC input: add/remove
Add load, check calibration of Voutput, Wout, VAout, DC buses, Vbatt, ...
AC input: add/remove
With AC input, disconnect batteries
HF-OFF check
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
26
Failure Analysis Report
& Corrective Action Plan
Customer
Customer location
Report date
Model
Unit s/n
Action Taken to Repair
RMA number
RMA date
PCB1 s/n
PCB2 s/n
Accessory1 s/n
Rev
Rev
Rev
Initial Assessment
Does the unit cold boot?
Does the unit indicate a fault?
Does unit operate online with no faults?
Is there any output?
Does unit switch to bypass?
Do all display leds work? ("A" in SM)
Does unit operate under 100% load?
Unit shut off after 9 min on battery standby?
Yes
___
___
___
___
___
___
___
___
No
___
___
___
___
___
___
___
___
Additional Information
Physical damage (deformed metal or plastic, loose connections, cut insulation, poor crimps, etc.)
Voltages: Pos Bus Neg Bus Vin Vout Charger (no batt) f/w rev
Command: Ctrl G*
Displays
Measured
Voltages
Measured
5V
Ctrl H*
12V
Shift L
-12V
Shift O
-15V
Shift B or ^J / ^K*
15V 24V b
Fault History
Ctrl U* n/a n/a
Vbat (list packs separately)
Repaired Unit - Measured and Calibrated Voltages
Voltages Pos Bus Neg Bus Vin Vout Charger (batteries disconnected)
Command Ctrl G* Ctrl H* Shift L Shift O Shift B or Shift J / K* (Lynx 3)
Displays
Measured
Corrective Actions to be Taken
Additional Notes
*in programming mode
Fault History
Ctrl U* n/a
2/14/2005
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
27
Appendix A. Fault codes on LED display & stored in EEPROM
Display LEDs show "1" for LED ON and "0" for LED OFF in the Battery capacity bar graph. For example, the following display indicates "Battery Capacitor
Soft Start Fault".
Notes
All values provided in UPS-Link terms. Overload test uses % power (watts) or % VA, whichever is greater.
The last fault(s) detected can be retrieved by sending the "Ctrl-U" command in Programming mode.
Fault Action Taken
Display
LEDs
Ctrl-
U
Auto-Recover from
FAILURE_BYPASS?
Battery Capacitor
Soft Start Fault
The unit immediately changes state to
UPS_FAILURE (less than 1ms)
0
1
1
0
0
11
Can't be in
FAILURE_BYPASS
Repair suggestion
Confirm battery voltage(s) above
165V and that +/-400V buses rise to within 15V(9V) of the battery bus(es) within 12 seconds and. If they don’t, check voltage after softstart PTCs, relay and relay drives.
Lynx2: TH701. TH702, RY702,
Q701, Q728, F701, F702.
Lynx 3: TH1401, TH1402,
TH1403, TH1404, RY1403,
RY1404, RY1405, RY1406,
RY1407, RY1408, Q1402, F1403,
F1404, F1405, F1406
Related
ECOs
BM934
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
28
Battery <-> Line
(PFC Input) Relay
Weld fault
No immediate action taken. State change will take place in the next AC line cycle (9ms @50Hz or 7ms @60Hz)
The UPS will transfer to
FAILURE_BYPASS or UPS_FAILURE state (See State Diagram.)
1
0
0
0
1
0D NO
Bypass Relay Fault
(Bypass relay is closed)
Bypass Relay Fault
(Output is off)
No immediate action is taken. Unit will change the state to UPS_FAILURE a half of an AC cycle later (10ms @ 50Hz or 8ms @ 60Hz)
0
1
0
0
1
Battery Charger
Fault(descent method)
No immediate action taken. State change will take place in the next AC line cycle (13.3ms @50Hz or 11.1ms
@60Hz) The UPS will transfer to
FAILURE_BYPASS or UPS_FAILURE state (See State Diagram.)
Battery Charger Fault
(hard limit)
0
1
0
1
0
DC Bus Overvoltage
Fault
DC Bus Overvoltage Fault will immediately turn-off the Inverter in hardware. The PFC will be turned off upon detection of this fault.
Case 1 (Inverter relay is closed): The
Inverter will be commanded off and new state will be set: UPS_FAILURE or
FAILURE_BYPASS. Should UPS transfer to FAILURE_BYPASS, output
Relay will be commanded to open and
Bypass Relay will be commanded to close immediately.
Case 2 (Inverter relay is open): UPS will transfer to UPS_FAILURE state at the closest AC line phase angle of 67.5 degrees (or in less than 18msec
@50Hz or 15msec @60Hz.)
0
1
0
0
0
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
0F
12
Can't be in
FAILURE_BYPASS
NO
Lynx3:
Confirm customer wiring to input terminal block (hardwired).
Input wires might be connected to Output terminal block by mistake.
Check Bypass contactor and drive
Lynx 2:
Check Q727, Q728, F703, F704,
D736, D737, D738, D739, Q730,
Q731
Lynx 3:
Check Q1407, Q1408, F1401,
F1402, D1406, D1407, D1408,
D1409
08
29
YES
Fan Fault
State transitions in the next AC line cycle (4ms @50Hz 3ms @60Hz)
Note: The UPS still tries to control the high/low speed mode selection for the fan.
Inverter Fault
(Hardware fault)
Inverter Fault
(Output voltage test)
The UPS commands an immediate turn off of the Inverter, the PFC and the
Charger. Next, the unit will enter either a FAILURE_BYPASS or
UPS_FAILURE state (See State
Diagram.) Upon setting the
FAILURE_BYPASS state the UPS will command the Bypass and the Backfeed relays to close. Upon setting
UPS_FAILURE state the UPS will command the Bypass and Backfeed relays to open. For either state the unit commands the Output Relay to open.Note: Normal UPS_FAILURE/
FAILURE_BYPASS procedure timings can not be applied in this case. The rest of hardware control operations (e.g.
PFC input relay control) will take place in the next AC line cycle. So, the timings specified will start from phase angle 0.
No immediate action is taken. All state transitions are taking place in the next
AC cycle. (20msec @50Hz, 17msec
@60Hz)
Logic Power Supply
Fault
Immediately switches in UPS_FAILURE state. (See Normal Behavior for
UPS_FAILURE State.)
0
0
1
1
0
0
0
0
0
1
1
1
0
0
0
10
06
0B
YES
NO
Check: Fan connections to control board (Lynx2 uses J5 only), fan guard is not pushed in, no foreign objects stuck in fan blades, fan frame not broken
Lynx 2: Check Q705, Q706, Q715,
Q716, Q717, Q718, D750, D751
Lynx 3: Check IC1403, IC1404,
IC1407, IC1408 collector-emitter and gate-emitter
Same as above
01
Can't be in
FAILURE_BYPASS
R544, R545 should be 10k TA107
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
30
High Output Voltage
High Output Voltage
(Extreme Overvoltage)
No immediate action is taken. The UPS will transfer to UPS_FAILURE or
FAILURE_BYPASS state (see State
Diagram) in the next AC line cycle.
(19msec @50Hz or 16ms @60Hz)
Output Relay Fault
(bypass relay is closed)
Output Relay Fault
(Transferring to inverter-on state)
Output Relay Fault
(Inverter is on)
Overload (Percent
LoadInverter is on)
No immediate action is taken. The UPS will transfer into UPS_FAILURE state in the next AC cycle (8ms @50Hz or 6ms
@60Hz.)
Overload
(Low output voltage)
Overload
(Percent Load
Bypass Relay is closed)
No immediate action is taken. All state transitions are taking place in the next
AC cycle (19msec @ 50Hz or 16msec
@60Hz.)The UPS will sound the beeper as long as the fault conditions are present.
Overtemperature
No immediate action is taken. All state transitions are taking place in the next
AC cycle (4msec @50Hz or 3msec
@60Hz.) The UPS will transfer to
FAILURE_BYPASS or UPS_FAILURE
(see State Diagram.)
1
0
0
0
0
0
0
1
0
1
0
0
0
1
1
Overload
LED
09 NO
0E
Can't be in
FAILURE_BYPASS
02
05
03
07
YES
YES
This fault is stored in ‘Ctrl-U’ during factory testing. It is not cleared before shipment.
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
31
PFC Failure
(Inverter on, hard limit detection)
PFC Failure
(Inverter on, delta detection)
PFC Failure
(Inverter off)
PFC Failure
(Charging up DC
Buses)
PFC Failure
(cold-boot)
No immediate action is taken. The UPS will transfer to FAILURE_BYPASS or
UPS_FAILURE state (see State
Diagram.) State transitions will take place at the closest phase angle of 67.5 degrees of AC line cycle.
Upon detection of this fault, the PFC is turned off immediately, state transitions are taking place in the next AC cycle
(8msec @50Hz or 6msec @60Hz.) The
UPS will transfer into
FAILURE_BYPASS or UPS_FAILURE state (see State Diagram.)
Upon detection of this fault, the UPS will immediately enter UPS_FAILURE state.
Short Circuit Same as overload above.
0
0
1
0
0
0A YES
Overload
LED
04
Can't be in
FAILURE_BYPASS
Lynx2:
Q708, Q709, Q710, Q711, Q726,
Q727, D748, D749, D723, DC bus and battery voltage feedback resistors, esp. R856, R857
Lynx3:
IC903, IC904, DC bus and battery voltage feedback resistors
Backfeed Relay Weld
No immediate action is taken. All state transitions are taking place in the next
AC cycle. (8msec @50Hz or 6msec
@60Hz) The UPS will transfer to
FAILURE_BYPASS or UPS_FAILURE
(see State Diagram.)
0
0
0
1
0
0C NO
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
32
Appendix B. ECO list as of October, 2005
Lynx2 modifications (Control board) – mirrored 180 degrees
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
33
Lynx3 modifications (Control board, top side)
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
34
Lynx3 modifications continued (Control board, bottom side) – mirrored 180 degrees
SURT 3kVA – 10kVA Service Manual
2005 American Power Conversion. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any retrieval system of any nature, without the written permission of the copyright owner. www.apc.com Rev 2005-2
35
advertisement
* Your assessment is very important for improving the workof artificial intelligence, which forms the content of this project
Related manuals
advertisement