XP Predator R410A 6.5 - 12 Ton

XP Predator R410A 6.5 - 12 Ton
528195-YTG-H-0213
®
TECHNICAL GUIDE
®
Description
ASHRAE 90.1 COMPLIANT
YORK® Predator® units are convertible single packages with a
common footprint cabinet and common roof curb for all 6-1/2
through 12-1/2 ton models. All units have two compressors with
independent refrigeration circuits to provide 2 stages of cooling.
The units were designed for light commercial applications and
can be easily installed on a roof curb, slab, or frame.
R-410A
XP SERIES
6-1/2 THRU 12-1/2 TON
60 Hertz
All Predator® units are self-contained and assembled on rigid
full perimeter base rails allowing for 3-way forklift access and
overhead rigging. Every unit is completely charged, wired,
piped, and tested at the factory to provide a quick and easy field
installation.
All units are convertible between side and down airflow.
Independent economizer designs are used on side and down
discharge applications, as well as all tonnage sizes.
Predator® XP units are available in the following configurations:
heat pump and heat pump with electric heat. Electric heaters
are available as factory-installed options or field-installed
accessories.
Tested in accordance with:
6-1/2 THROUGH 10 TON
12-1/2 TON
FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE
528195-YTG-H-0213
Table of Contents
Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Table of Contents . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Nomenclature . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Features and Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Guide Specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Capacity Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Sound Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43
Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 45
Economizer Options . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
Component Location
Heat Pump
SimplicityTM Control
board w/screw connectors for T-stat wiring and
network connection
Terminal block
for hi-voltage
connection
Disconnect location
(optional disconnect switch)
Filter access
(2” or 4” filter options)
Filter drier (solid core)
Condenser
section
Second Model
Nameplate Inside
Control Door
Slide-out motor and
blower assembly for
easy adjustment and
service.
Dual stage cooling for maximum
comfort (7-1/2 12-1/2 Only)
Compressor #2
Access (High-Eff
Compressor)
Base Rails w/ Forklift Slots (3 Sides)
& Lifting Holes
Belt-drive
blower
motor
Roof curbs in eight- and
fourteen-inch heights. Roof
curbs for transitioning from
Sunline™ footprint to the
XP series footprint are also
available (field installed
accessory)
Toolless
Door Latch
2
Side entry power
and control wiring
knockouts
Compressor #1 Access
(High-Eff Compressor)
Slide-out drain pain
with steel 3/4” NPT,
Female Connection
Johnson Controls Unitary Products
528195-YTG-H-0213
Nomenclature
6.5-12.5 Ton York® Model Number Nomenclature
X P 090 C00 A 2 A AA 6 0 1 2 4 A
Product Category
Product Style
X = HP, Single Pkg., R-410A
A = Style A
B = Style B
C = Style C
Product Identifier
Configuration Options (not required for all units)
These four digits will not be assigned until a quote is requested, or an order placed.
P = 11.0 EER HP
SS Drain Pan
CPC Controller, DFS, APS
Johnson Controller, DFS, APS
Nominal Cooling Capacity
Honeywell Controller, DFS, APS
078 = 6.5 Ton
090 = 7.5 Ton
102 = 8.5 Ton
120 = 10.0 Ton
150 = 12.5 Ton
Novar Controller, DFS, APS
Simplicity Intellicomfort II Controller
Simplicity Intellicomfort II Controller w/Simplicity®LINC
IntelliSpeed with VFD
IntelliSpeed, VFD and Manual Bypass
IntelliSpeed, VFD Ready (for customer-provided, field-installed drive)
Heat Type and Nominal Heat Capacity
2" Pleated Filters, MERV 7
C00 = Cooling Only. No heat installed
4" Pleated Filters, MERV 13
BAS Ready Economizer (2-10 V.D.C. Actuator without a Controller)
Electric Heat Options
Shipping Bag
Any Combination of Additional Options that Don’t Have an Option Code Pre-assigned
E09 = 9 KW
E18 = 18 KW
E24 = 24 KW
E36 = 36 KW
E54 = 54 KW
Product Generation
6 = Sixth Generation
Additional Options
Airflow
A = Std. Motor
B = Std. Motor/Econo./Barometric Relief (Downflow
Only)
C = Std. Motor/Econo./Power Exhaust (Downflow Only)
D = Std. Motor/Motorized Damper (Downflow Only)
E = Std. Motor/Horizontal Economizer (No Baro.)
F = Std. Motor/Slab Econo./Power Exhaust
(Downflow Only)
G = Std. Motor/Slab Econo./Barometric Relief
(Downflow Only)
N = Hi Static
P = Hi Static/Econo./Barometric Relief
(Downflow Only)
Q = Hi Static/Econo./Power Exhaust
(Downflow Only)
R = Hi Static/Motorized Damper (Downflow Only)
S = Hi Static/Horizontal Economizer (No Baro.)
T = Hi Static/Slab Econo./Power Exhaust
(Downflow Only)
U = Hi Static/Slab Econo./Barometric Relief
(Downflow only)
Voltage
2 = 208/230-3-60
4 = 460-3-60
5 = 575-3-60
AA = None
AB = Phase Monitor
AC = Coil Guard
AD = Dirty Filter Switch
AE = Phase Monitor & Coil Guard
AF = Phase Monitor & Dirty Filter Switch
AG = Coil Guard & Dirty Filter Switch
AH = Phase Monitor, Coil Guard & Dirty Filter Switch
RC = Coil Guard, Shipping Bag & American Flag
TA = Technicoat Condenser Coil
TJ = Technicoat Evaporator Coil
TS = Technicoat Evaporator & Condenser Coils
EA = ElectroFin Condenser Coil
EJ = ElectroFin Evaporator Coil
ES = ElectroFin Cond & Evap Coils
ZZ = If desired option combination is not listed above, ZZ will be assigned and configuration options will be
located in digits 15-18.
Installation Options
A = No Options Installed
B = Option 1
C = Option 2
D = Options 1 & 2
E = Option 3
F = Option 4
G = Options 1 & 3
H = Options 1 & 4
J = Options 1, 2 & 3
K = Options 1, 2, & 4
L = Options 1,3 & 4
M = Options 1, 2, 3, & 4
N = Options 2 & 3
P = Options 2 & 4
Q = Options 2, 3, & 4
R = Options 3 & 4
S = Option 5
T = Options 1 & 5
U = Options 1, 3, & 5
V = Options 1, 4, & 5
W = Options 1, 3, 4, & 5
X = Options 3 & 5
Y = Options 4 & 5
Z = Options 3, 4 & 5
Options
1 = Disconnect
2 = Non-Pwr'd Conv. Outlet
3 = Smoke Detector S.A.
4 = Smoke Detector R.A.
5 = Pwr'd Conv. Outlet
Johnson Controls Unitary Products
3
528195-YTG-H-0213
Features and Benefits
Standard Features
• High Efficiency – High efficiency units reach as high as
11.5 EER. These efficiencies exceed all legislated
minimum levels and provide low operating costs.
• Service Friendly – The Predator® incorporates a number
of enhancements which improve serviceability.
The motor and blower slide out of the unit as a common
assembly. This facilitates greater access to all the indoor
airflow components, thus simplifying maintenance and
adjustment.
Service time is reduced through the use of hinged,
toolless panels. Such panels provide access to frequently
inspected components and areas, including the control
box, compressors, filters, indoor motor & blower, and the
heating section. The panels are screwed in place at the
factory to prevent access by children or other
unauthorized persons. It is recommended that the panels
be secured with screws once service is complete.
Service windows have been placed in both condenser
section walls. Rotation of the cover allows easy access to
the condenser coils for cleaning or inspection.
The unit control board utilizes flash codes to aid in
diagnosis of unit malfunctions. Unique alarm codes quickly
identify the source of the unit alarm.
All units use the same standard filter size. This
standardization removes any confusion on which filter
sizes are needed for replacement.
The non-corrosive drain pan slides out of the unit to permit
easy cleaning. The drain pan is accessed by removing the
drain pan cover plate on the rear of the unit. Once the plate is
removed, the drain pan slides out through the rear of the unit.
All Predator® units have a second model nameplate
located inside the control access door. This is to prevent
deterioration of the nameplate through weathering.
• Environmentally Aware – For improved Indoor Air
Quality, A combination of foil faced and elastometric
rubber insulation is used exclusively throughout the units.
• Convertible Airflow Design – The side duct openings
are covered when they leave the factory. If a side supply/
return is desired, the installer simply removes the two side
duct covers from the outside of the unit and installs them
over the down shot openings. No panel cutting is required.
Convertible airflow design allows maximum field flexibility
and minimum inventory.
• System Protection - Suction line freezestats are supplied
on all units to protect against loss of charge and coil frosting
when the economizer operates at low outdoor air
temperatures while the compressors are running. Every unit
has solid-core liquid line filter-driers and high and lowpressure switches. Internal compressor protection is
standard on all compressors. Crankcase heaters are
standard on reciprocating compressors. Scroll compressors
do not require crankcase heaters. Phase Monitors are
standard on units with scroll compressors. This accessory
monitors the incoming power to the unit and protects the
unit from phase loss and reversed phase rotation.
•
Advanced Controls - Simplicity® control boards have
standardized a number of features previously available
only as options or by utilizing additional controls.
•
Low Ambient - An integrated low-ambient control
allows all units to operate in the cooling mode down to
0F outdoor ambient without additional assistance.
Optionally, the control board can be programmed to
lockout the compressors when the outdoor air temperature is low or when free cooling is available.
The Simplicity® control board used in this product
will effectively operate the cooling system down to
0°F when this product is applied in a comfort cooling
application for people. An economizer is typically
included in this type of application. When applying
this product for process cooling applications (computer rooms, switchgear, etc.), please reference
applications bulletin AE-011-07 or call the applications department for Unitary Products @ 1-877UPG-SERV for guidance. Additional accessories
may be needed for stable operation at temperatures
below 30° F.
•
Anti-Short Cycle Protection - To aid compressor life,
an anti-short cycle delay is incorporated into the standard controls. Compressor reliability is further ensured
by programmable minimum run times. For testing, the
anti-short cycle delay can be temporarily overridden
with the push of a button.
•
Fan Delays - Fan on and fan off delays are fully programmable. Furthermore, the heating and cooling fan
delay times are independent of one another. All units
are programmed with default values based upon their
configuration of cooling and heat.
•
Safety Monitoring - The control board monitors the
high and low-pressure switches, the freezestats, the
gas valve, if applicable, and the temperature limit
switch on gas and electric heat units. The unit control
board will alarm on ignition failures, compressor lockouts and repeated limit switch trips.
•
Nuisance Trip Protection and Strikes - To prevent
nuisance trouble calls, the control board uses a “three
times, you’re out” philosophy. The high and low-pressure switches and the freezestats must trip three times
within two hours before the unit control board will lock
out the associated compressor.
•
On Board Diagnostics - Each alarm will energize a
trouble light on the thermostat, if so equipped, and
flash an alarm code on the control board LED. Each
high and low-pressure switch alarm as well as each
freezestat alarm has its own flash code. The control
board saves the five most recent alarms in memory,
and these alarms can be reviewed at any time.
Alarms and programmed values are retained through
the loss of power.
• Reliable – From the beginning – All units undergo
computer automated testing before they leave the factory.
4
Johnson Controls Unitary Products
528195-YTG-H-0213
•
•
•
•
•
Units are tested for refrigerant charge and pressure, unit
amperage, and 100% functionality. For the long term – All
Predator® units are painted with a long lasting, powder
paint that stands up over the life of the unit. The paint
used has been proven by a 1000 hour salt spray test.
Flexible Placement – All models and configurations
share the same cabinet/footprint and thus the same roof
curb. You have the flexibility to set one curb and choose
the correct tonnage size and heating option after the
internal loads have been determined.
To further simplify planning and installation, Predator® XP
cabinets are designed to fit your roof. With the optional
roof curb, the unit ductwork is designed to fit around 24”
on-center joists or between 48” on-center joists.
The drain pan can be rotated to drain to either the front or
the rear of the unit. Additionally, the drain pan can be
fitted to drain through the roof curb. As it is sometimes
difficult to have a level installation, the drain pan features
a generous slope to ensure proper drainage.
Full Perimeter Base Rails – The permanently attached
base rails provide a solid foundation for the entire unit and
protect the unit during shipment. The rails offer forklift
access from 3 sides, and rigging holes are available so that
an overhead crane can be used to place the units on a roof.
Easy Installation – Electric utility knockouts are supplied in
the unit underside as well as the side of the unit. A clearly
identified location is provided to mount a field supplied
electrical disconnect switch. Utility connections can be
made quickly and with a minimum amount of field labor.
All units are shipped with 2” throw-away filters installed.
Wide Range of Indoor Airflows – All indoor fan motors
are belt-drive type providing maximum flexibility to handle
most airflow requirements. For high static applications,
factory installed alternate indoor fan motors are available.
With the optional indoor fan motor, all units can supply
nominal airflow at a minimum of 1.5” ESP.
Warranty - All models include a 1-year limited warranty
on the complete unit. Compressors and electric heater
elements each carry a 5-year warranty.
Factory Installed Options
YORK® offers several equipment options factory installed, for
the Predator®line.
• Optional Factory Installed Economizers - Predator units
offer a variety of optional factory installed economizers
with low leak dampers. The outdoor air enthalpy sensor
enables economizer operation if the outdoor enthalpy is
less than the setpoint of the economizer logic module. See
economizer options section to determine the correct
economizer for your application.
• Downflow Economizer - (With barometric relief) The economizer is provided with a single enthalpy input.
The economizer is 2% low leakage type, and is shipped
installed and wired. The installer needs only to
assemble and mount the outdoor air hood (Provided).
The economizer has spring return, fully modulating
damper actuators and is capable of introducing up to
100% outdoor air. As the outdoor air intake dampers
open, the return air dampers close. The changeover
from mechanical refrigeration to economizer operation is
Johnson Controls Unitary Products
•
•
•
•
regulated by the standard single enthalpy input. There is
an optional input dual dry bulb available. To meet
regulated air standards, the economizer control accepts
an optional CO2 input for demand ventilation. With
single enthalpy input, the economizer control monitors
outdoor air. The dual enthalpy kit provides a second
input used to monitor the return air. With a dual input kit
installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
• Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizers only.
• BAS Ready Economizer -(With barometric relief) The economizer is provided with an actuator that
requires a 0-10V DC input from an external source (i.e.,
field installed building automation system controller).
Power exhaust options are available. The economizer is
2% low leakage type with spring return and fully
modulating dampers capable of introducing up to 100%
outside air. Also include 2” pleated filters.
• Slab Economizer for Energy Recovery Ventilators(With barometric relief and Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type, and is shipped
installed and wired. The economizer has spring return,
fully modulating damper actuators and is capable of
introducing up to 100% outdoor air. As the outdoor air
intake dampers open, the return air dampers close. The
changeover from mechanical refrigeration to
economizer operation is regulated by the standard
single enthalpy input. There is an optional input dual dry
bulb available. To meet regulated air standards, the
economizer control accepts an optional CO2 input for
demand ventilation.With single enthalpy input, the
economizer control monitors outdoor air. The dual
enthalpy kit provides a second input used to monitor the
return air. With a dual input kit installed, the economizer
control compares the values of the two enthalpy or
temperature inputs and positions the dampers to
provide the maximum efficiency possible.
Power Exhaust (Downflow only) - This accessory
installs in the unit with a down flow economizer.
Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly
with an outdoor air hood and filters. The outdoor air
dampers open to the preset position when the indoor fan
motor is energized. The damper has a range of 0% to
100% outdoor air entry. Factory installed option or field
installed accessory.
Alternate Indoor Blower Motor - For applications with
high static restrictions, units are offered with optional
indoor motors that provide higher static output and/or
higher airflow, depending upon the installer’s needs.
Stainless Steel Drain Pan - An optional rust-proof
stainless steel drain pan is available to provide years of
trouble-free operation in corrosive environments.
5
528195-YTG-H-0213
• Electric Heaters - The electric heaters range from 9kW to
54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All heaters are
intended for single point power supply.
• IntelliSpeed™ Supply Fan Control Option (ASHRAE
90.1 compliant, section 6.4.3.10) - Units configured with
the IntelliSpeed™ Supply Fan Option will contain a VFD
for variable volume supply fan operation. This option
allows the supply fan RPM to vary based on the number
of compressors or heating stages energized. The
economizer's minimum position will also be configurable
to vary based on the supply fan VFD frequency output.
• Disconnect Switch - For heat pump units with electric
heat, a HACR breaker sized to the unit is provided. For
heat pump units, a switch sized to the largest electric heat
available for the particular unit is provided. Factory
installed option only.
• Convenience Outlet - (Non-Powered/Powered) - This
option locates a 120V single-phase GFCI outlet with cover,
on the corner of the unit housing adjacent to the
compressors. The “Non-powered” option requires the
installer to provide the 120V single-phase power source and
wiring. The “Powered” option is powered by a stepdown
transformer in the unit. Factory installed option only.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment. Available
for both the supply and/or return air.
Factory installed smoke detectors in the return air, may be
subjected to freezing temperatures during "off" times due
to out side air infiltration. These smoke detectors have an
operational limit of 32 °F to 131°F. Smoke detectors
installed in areas that could be out side those limitations
will have to be moved to prevent having false alarms.
• Filters – 2” Pleated MERV 7 or 4” Pleated MERV 13 are
available to meet LEED requirements. A 2” Throwaway is
shipped as standard.
• Phase Monitors - Designed to prevent unit damage. The
phase monitor will shut the unit down in an out-of phase
condition. (Standard on units with Scroll Compressors.)
• Coil Guard - Customers can purchase a coil guard kit to
protect the condenser coil from damage. Additionally, this
kit stops animals and foreign objects from entering the
space between the inner condenser coil and the main
cabinet. This is not a hail guard kit.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters. Factory installed option or
field installed accessory.
• Technicoat Condenser Coils - The condenser coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
6
• Technicoat Evaporator Coil - The evaporator coils are
coated with a phenolic coating for protection against
corrosion due to harsh environments.
• ElectroFin® E-coat Condenser Coils - The condenser
coils are coated with an epoxy polymer coating to protect
against corrosion.
• ElectroFin® E-coat Evaporator Coils - The evaporator
coils are coated with an epoxy polymer coating to protect
against corrosion.
Control Options
• BAS - Building Automation System Controls Simplicity®
INTELLI-Comfort II™ Control - The York® Simplicity®
INTELLI-Comfort II™ control is factory installed. It includes
a supply air sensor, a return air sensor, and an outside air
sensor. There are provisions for a field installed dirty filter
indicator switch, an air-proving switch, an Outside Air
Humidity sensor, a Return Air Humidity sensor, an Inside
IAQ sensor, and an Outside Air IAQ sensor. Construction
mode operation, 365-day real time clock with 7 day
programming plus holiday scheduling is built-in. Two
different modes of demand ventilation are achieved through
the INTELLI-Comfort II™ using CO2 sensors. It uses an
inside CO2 sensor to perform Demand Ventilation. It can
also use an Outside CO2 sensor to perform Differential
Demand Ventilation. It uses a Patented Comfort Ventilation
algorithm to provide comfortable ventilation air
temperature. The patented economizer-loading algorithm
will protect the equipment when harsh operating conditions
exist. Humidity in the occupied space or return duct can be
monitored and controlled via humidity sensors and the onboard connection for hot gas re-heat system. It uses the
INTELLI-Start™ algorithm to maximize energy savings by
recovering the building from the Unoccupied Setpoints to
the Occupied Setpoints just in time for the Occupied Time
Period to begin. The Simplicity® INTELLI-Comfort II™
balances space temperature, ventilation air temperature,
CO2 and humidity for ultimate comfort.
• Simplicity® INTELLI-Comfort II™ Control - The York®
Simplicity® INTELLI-Comfort II™ control is factory
installed. It includes all the features of the INTELLIComfort II™ control with an additional control to translate
communications from MODBUS to the BACnet MSTP
protocol.
• Novar® BAS Control - The Novar® building automation
system controller is factory installed. Incudes supply air
sensor, return air sensor, dirty filter indicator switch, and
air proving switch.
• Johnson Controls BAS Control - The Johnson Control
YK-UNT-1126 building automation system controller is
factory installed. Includes supply air sensor, return air
sensor, dirty filter indicator switch, and air proving switch.
• CPC BAS Control - The Computer Process Controls
Model 810-3060 ARTC Advanced Rooftop building
automation system controller is factory installed. Includes
supply air sensor, return air sensor, dirty filter indicator
switch and air proving switch.
• Honeywell BAS Control - The Honeywell W7750C
building automation system controller is factory installed.
Includes air supply sensor, return air sensor, dirty filter
indicator switch, and air proving switch.
Johnson Controls Unitary Products
528195-YTG-H-0213
• York Commercial Comfort System (YCCS) - Provides
rooftop system integration for YCCS single zone and
change-over bypass systems.
Field Installed Accessories
YORK® offers several equipment accessories for field
installation, for the Predator® line.
• Downflow Economizer - (With barometric relief) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
control accepts an optional CO2 input for demand
ventilation. With single enthalpy input, the economizer
control monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
• Horizontal Economizer - (Without barometric relief) All features of the downflow economizer exist except you
must order the duct mount barometric relief separately.
You must order a 1EH0408 if you are installing a
power exhaust. You can order a 1RD0411 Barometric
Relief for horizontal flow economizer.
• Slab Economizer for Energy Recovery Ventilator(Without barometric relief or Fresh Air Hood) - The
economizer is provided with a single enthalpy input. The
economizer is 2% low leakage type. The economizer has
spring return, fully modulating damper actuators and is
capable of introducing up to 100% outdoor air. As the
outdoor air intake dampers open, the return air dampers
close. The changeover from mechanical refrigeration to
economizer operation is regulated by the standard single
enthalpy input. There is an optional input dual dry bulb
available. To meet regulated air standards, the economizer
control accepts an optional CO2 input for demand
ventilation.With single enthalpy input, the economizer control
monitors outdoor air. The dual enthalpy kit provides a
second input used to monitor the return air. With a dual input
kit installed, the economizer control compares the values of
the two enthalpy or temperature inputs and positions the
dampers to provide the maximum efficiency possible.
You can order 1EH0409 Barometric Relief/FA Hood for
field installations without an ERV.
• Dual Enthalpy Control, Accessory - This kit contains
the required components to convert a single enthalpy
economizer to dual enthalpy.
• Barometric Relief Damper - Zero to 100% capacity
barometric relief dampers for use with horizontal flow, or
field installed slab economizers.
• Power Exhaust - This accessory installs in the unit with a
down flow economizer. Power exhaust plugs into the
connector in the unit bulkhead. You must purchase
1EH0408 barometric relief when applying to a
horizontal flow application.
Johnson Controls Unitary Products
• Manual Outdoor Air Damper - Like the motorized outdoor
air damper, each manual outdoor air damper includes a
slide-in damper assembly with an outdoor air hood and
filters. Customers have a choice of dampers with ranges of
0% to 100% or 0% to 35% outdoor air entry.
• Motorized Outdoor Air Damper - The motorized outdoor
air damper includes a slide-in/plug-in damper assembly with
an outdoor air hood and filters. The outdoor air dampers
open to the preset position when the indoor fan motor is
energized. The damper has a range of 0% to 100% outdoor
air entry. Factory installed option or field installed accessory.
• Smoke Detectors - The smoke detectors stop operation
of the unit by interrupting power to the control board if
smoke is detected within the air compartment.
• CO2 Sensor - Senses CO2 levels and automatically
overrides the economizer when levels rise above the
preset limits.
• Dirty Filter Switch - This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally high
pressure drop across the filters.
• Coil Guard - Field installed decorative wire coil guard.
• Hail Guard - This kit includes a sloped hood which installs
over the outside condenser coil and prevents damage to
the coil fins from hail strikes. Field installed accessory only.
• Electric Heaters - The electric heaters range from 9 kW
to 54kW and are available in all the voltage options of the
base units. All heaters are dual staged. All units include
an adapter panel for easy installation of the electric
heaters. Necessary hardware and connectors are
included with the heaters. All heaters are intended for
single point power supply.
• Low Limit / Compressor Lockout Kit
• Compressor Lockout (CLO): To prevent mechanical
(compressorized) operation of the unit during cold
outdoor conditions where there is a risk of returning
liquid refrigerant back to the compressors.
• Low Limit Control (LLC): To prevent the supply air
from dropping below a specified setpoint by utilizing the
units first stage heating means when there is a demand
for cooling during cold outside conditions.
• Metal Frame Filter Kit - Metal frame with polyester filter
medium.
• Permanent Filters - Permanent filters are available.
• Roof Curbs - The roof curbs have insulated decks and are
shipped disassembled The roof curbs are available in 8” and
14” heights. For applications with security concerns, burglar
bars are available for the duct openings of the roof curbs.
• Roof Curb Transition - Single Piece Adapter (10” High) Roof curbs for transitioning from Sunline™ units to
Predator® units. Fits 7.5 to 12.5 Sunline™ roof curbs only.
• Burglar Bars - Mount in the supply and return openings
to prevent entry into the duct work.
• Thermostat - The units are designed to operate with 24volt electronic and electro-mechanical thermostats. All
units (with or without an economizer) operate with twostage heat/two-stage cool or two-stage cooling only
thermostats, depending upon unit configuration.
7
528195-YTG-H-0213
Accessories
Part Number
1RC0470
1RC0471
1RC0472
1BD0408
2TP04520925
2TP04521825
2TP04522425
2TP04523625
2TP04525425
2TP04520946
2TP04521846
2TP04522446
2TP04523646
2TP04525446
2TP04520958
2TP04521858
2TP04522458
2TP04523658
2TP04525458
2TP04540925
2TP04541825
2TP04542425
2TP04543625
2TP04540946
2TP04541846
2TP04542446
2TP04543646
2TP04540958
2TP04541858
2TP04542458
2TP04543658
1FA0413
1FA0414
2MD04702724
2MD04703324
2EE04705924
2EE04706024
2EE04705724
2EE04705824
2PE04703225
2PE04703246
2PE04703258
2EC04700924
1EH0407
1RD0411
1EH0408
1EH0409
2AQ04700424
2AQ04700324
2SD04700824
2SD04700924
2SD04701024
2MK04700624
1CG0419
1CG0424
1CG0427
1HG0411
1HG0415
1FL0402
1FL0423
2DF0401
1FF0414
1FF0415
8
Description
Roof Curb, 8" Height
Roof Curb, 14" Height
Roof Curb, Transition (7.5 T through 12.5 T)
Burglar Bars, Downflow
Electric Heat 9kW 230V
Electric Heat 18kW 230V
Electric Heat 24kW 230V
Electric Heat 36kW 230V
Electric Heat 54kW 230V
Electric Heat 9kW 460V
Electric Heat 18kW 460V
Electric Heat 24kW 460V
Electric Heat 36kW 460V
Electric Heat 54kW 460V
Electric Heat 9kW 575V
Electric Heat 18kW 575V
Electric Heat 24kW 575V
Electric Heat 36kW 575V
Electric Heat 54kW 575V
Electric Heat 9kW 230V, 42" Tall Cabinet
Electric Heat 18kW 230V, 42" Tall Cabinet
Electric Heat 24kW 230V, 42" Tall Cabinet
Electric Heat 36kW 230V, 42" Tall Cabinet
Electric Heat 9kW 460V, 42" Tall Cabinet
Electric Heat 18kW 460V, 42" Tall Cabinet
Electric Heat 24kW 460V, 42" Tall Cabinet
Electric Heat 36kW 460V, 42" Tall Cabinet
Electric Heat 9kW 575V, 42" Tall Cabinet
Electric Heat 18kW 575V, 42" Tall Cabinet
Electric Heat 24kW 575V, 42" Tall Cabinet
Electric Heat 36kW 575V, 42" Tall Cabinet
Manual Outside Air Damper 0-35%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Manual Outside Air Damper 0-100%, Downflow (Incl. Hood, Damper & Filters, No Barometric Relief)
Motorized Damper, Downflow (Incl. Hood, Damper & Filter, no Barometric Relief)
Motorized Damper, Horizontal (Incl. Hood, Damper & Filter, no Barometric Relief)
Economizer, Downflow (Incl. Barometric Relief & All Hoods)
Economizer, Horizontal (Incl. Dampers & Hoods, no Barometric Relief)
Economizer, Slab, Downflow (Incl. Dampers only no Hoods or Barometric Relief), 50” Tall Cabinet
"Downflow Economizer, Slab type for ERV (no Barometric Relief or FA hood)", 42" Tall Cabinet
Power Exhaust, Downflow, 230V (For Units with Economizer only)
Power Exhaust, Downflow, 460V(For Units with Economizer only)
Power Exhaust, Downflow, 580V (For Units with Economizer only)
Dual Enthalpy Control (Use with Single Enthalpy Economizer)
Hood Kit, Downflow Economizer (Included with all Downflow Economizers)
Barometric Relief Kit, Ductmount for Horizontal Application (Incl. Damper & Hood)
Barometric Relief Kit, Ductmount for Horizontal Application w/Power Exhaust (Incl. Damper & Hood)
Barometric Relief / Hood Kit, for Field Installed Slab Econ. w/o ERV (Incl. Barometric Relief & FA Hood)
CO2 Detector Unit Mount
CO2 Detector Space Mount
Smoke Detector for Supply (All Gen 5 units with 2" & 4" Filters)
Smoke Detector for Return (All Gen 5 units with 2" & 4" Filters)
Smoke Detector for Supply and Return (All Gen 5 units with 2" & 4" Filters)
Low Limit / Compressor Lockout Kit
Coil Guard (Electric / Electric & HP models), 8-1/2 and 10 Ton
Coil Guard (Electric / Electric and HP models), 12-1/2 Ton
Coil Guard (Electric / Electric & HP Models), 6-1/2 and 7-1/2 Ton
Hail Guard Kit
Hail Guard Kit, 42" Tall Cabinet
Permanent Filter Kit
Permanent Filter Kit, 42" Tall Cabinet
Dirty Filter Switch
2” only Metal Filter Frame Kit, 50” Tall Cabinet
2” only Metal Filter Frame Kit, 42" Tall Cabinet
Johnson Controls Unitary Products
528195-YTG-H-0213
Guide Specifications
GENERAL
Units shall be manufactured by York International Unitary
Products in an ISO 9001 certified facility. YORK® Predator®
units are convertible single packages with a common footprint
cabinet and common roof curb for all 6-1/2 through 12-1/2 ton
models. All units have two compressors with independent R410a refrigeration circuits to provide 2 stages of cooling. The
units were designed for light commercial applications and can
be easily installed on a roof curb, slab, or frame. All Predator®
units are self-contained and assembled on rigid full perimeter
base rails allowing for 3-way forklift access and overhead
rigging. Every unit is completely charged with R-410a, wired,
piped, and tested at the factory to provide a quick and easy
field installation. All units are convertible between side and
down airflow. Independent economizer designs are used on
side and down discharge applications, as well as all tonnage
sizes. Predator® units are available in the following
configurations: heat pump and heat pump with electric heat.
Electric heaters are available as factory-installed options or
field-installed accessories.
DESCRIPTION
Units shall be factory assembled, single package (Heat Pump),
designed for outdoor installation. They shall have built in field
convertible duct connections for down discharge supply/return or
horizontal discharge supply/return and be available with factory
installed options or field installed accessories. The units shall be
factory wired, piped and charged with R-410a refrigerant and
factory tested prior to shipment. All unit wiring shall be both
numbered and color coded. The cooling performance shall be
rated in accordance with DOE and AHRI test procedures. Units
shall be CSA certified to ANSI Z21.47 and UL 1995/CAN/CSA No.
236-M90 standards.
UNIT CABINET
Unit cabinet shall be constructed of galvanized steel with
exterior surfaces coated with a non-chalking, powder paint
finish, certified at 1000 hour salt spray test per ASTM-B117
standards. Indoor blower sections shall be insulated with up to
1” thick insulation coated on the airside. Either aluminum foil
faced or elastometric rubber insulation shall be used in the
unit’s compartments and be fastened to prevent insulation from
entering the air stream. Cabinet doors shall be hinged with
toolless access for easy servicing and maintenance. Full
perimeter base rails shall be provided to assure reliable transit
of equipment, overhead rigging, fork truck access and proper
sealing on roof curb applications. Disposable 2” filters shall be
furnished and be accessible through hinged access door. Fan
performance measuring ports shall be provided on the outside
of the cabinet to allow accurate air measurements of evaporator
fan performance without removing panels or creating bypass of
the coils. Condensate pan shall be slide out design, constructed
of a non corrosive material, internally sloped and conforming to
ASHRAE 62-B9 standards. Condensate connection shall be a
minimum of ¾” I.D. female and be rigid mount connection.
Johnson Controls Unitary Products
INDOOR (EVAPORATOR) FAN ASSEMBLY
Fan shall be a belt drive assembly and include an adjustable
pitch motor pulley. Job site selected brake horsepower shall not
exceed the motors nameplate horsepower rating plus the service factor. Units shall be designed to operate within the service
factor. Fan wheel shall be double inlet type with forward curve
blades, dynamically balanced to operate smoothly throughout
the entire range of operation. Airflow design shall be constant
volume. Bearings shall be sealed and permanently lubricated
for longer life and no maintenance. Entire blower assembly and
motor shall be slide out design.
OUTDOOR (CONDENSER) FAN ASSEMBLY
The outdoor fans shall be of the direct drive type, discharge air
vertically, have aluminum blades riveted to corrosion resistant
steel spider brackets and shall be dynamically balanced for
smooth operation. The outdoor fan motors shall have permanently
lubricated bearings internally protected against overload
conditions and staged independently. A cleaning window shall be
provided on two sides of the units for coil cleaning.
REFRIGERANT COMPONENTS
Compressors:
a. Shall be fully hermetic type, direct drive, internally
protected with internal high-pressure relief and over
temperature protection. The hermetic motor shall be
suction gas cooled and have a voltage range of + or –
10% of the unit nameplate voltage.
b. Shall have internal spring isolation and sound muffling to
minimize vibration and noise, and be externally isolated
on a dedicated, independent mounting.
Coils:
a. Evaporator and condenser coils shall have aluminum
plate fins mechanically bonded to seamless internally
enhanced copper tubes with all joints brazed. Special
Phenolic coating shall be available as a factory option.
b. Evaporator and condenser coils shall be of the direct
expansion, draw-thru design.
Refrigerant Circuit and Refrigerant Safety Components shall
include:
a. Independent fixed-orifice
expansion devices.
or
thermally
operated
b. Solid core filter drier/strainer to eliminate any moisture or
foreign matter.
c. Accessible service gage connections on both suction
and discharge lines to charge, evacuate, and measure
refrigerant pressure during any necessary servicing or
troubleshooting, without losing charge.
d. The unit shall have two independent refrigerant circuits,
equally split in 50% capacity increments.
9
528195-YTG-H-0213
Unit Controls:
a. Unit shall be complete with self-contained low-voltage
control circuit protected by a resettable circuit breaker on
the 24-volt transformer side.
b. Unit shall incorporate a lockout circuit which provides
reset capability at the space thermostat or base unit
should any of the following standard safety devices trip
and shut off compressor:
c. Loss-of-charge/Low-pressure switch.
• High-pressure switch.
• Freeze-protection thermostat, evaporator coil. If any of
the above safety devices trip, an LED (light-emitting
diode) indicator shall flash a diagnostic code that
indicates which safety switch has tripped.
d. Unit shall incorporate “AUTO RESET” compressor over
temperature, over current protection.
e. Unit shall operate with conventional thermostat designs
and have a low voltage terminal strip for easy hook-up.
f. Unit control board shall have on-board diagnostics and
fault code display.
g. Standard controls shall include anti-short cycle and low
voltage protection, and permit cooling operation down to
0 ºF.
h. Control board shall monitor each refrigerant safety switch
independently.
i. Control board shall retain last 5 fault codes in nonvolatile memory, which will not be lost in the event of a
power loss.
ELECTRIC HEATING SECTION (IF EQUIPPED)
An electric heating section, with nickel chromium elements,
shall be provided in a range of 9 thru 54 KW, offering two states
of capacity all sizes. The heating section shall have a primary
limit control(s) (automatic reset) to prevent the heating element
system from operating at an excessive temperature. The Heating Section assembly shall slide out of the unit for easy maintenance and service. Units with Electric Heating Sections shall be
wired for a single point power supply with branch circuit fusing
(where required).
UNIT OPERATING CHARACTERISTICS
Unit shall be capable of starting and running at 125 ºF outdoor
temperature, exceeding maximum load criteria of AHRI Standard 340/360. The compressor, with standard controls, shall be
capable of operation down to 0 ºF outdoor temperature.
ELECTRICAL REQUIREMENTS - All unit power wiring shall
enter unit cabinet at a single factory provided location and be
capable of side or bottom entry to minimize roof penetrations
and avoid unit field modifications. Separate side and bottom
openings shall be provided for the control wiring.
STANDARD LIMITED WARRANTIES - Compressor – 5 Years,
Elect. Heat Elem. – 5 Years, Parts – 1 Year
10
FACTORY INSTALLED OPTIONAL OUTDOOR AIR (Shall be
made available by either/or):
• ELECTRONIC ENTHALPY AUTOMATIC ECONOMIZER
– Outdoor and return air dampers that are interlocked and
positioned by a fully-modulating, spring-return damper
actuator. The maximum leakage rate for the outdoor air
intake dampers shall not exceed 2% when dampers are
fully closed and operating against a pressure differential
of 0.5 IWG. A unit-mounted potentiometer shall be
provided to adjust the outdoor and return air damper
assembly to take in outdoor air to meet the minimum
ventilation requirement of the conditioned space during
normal operation. During economizer operation, a mixedair temperature control shall modulate the outdoor and
return air damper assembly to prevent the supply air
temperature from dropping below 55 ºF. Changeover from
compressor to economizer operation shall be provided by
an integral electronic enthalpy control that feeds input into
the basic module. The outdoor intake opening shall be
covered with a rain hood that matches the exterior of the
unit. Water eliminator/filters shall be provided.
Simultaneous economizer/compressor operation is also
possible. Dampers shall fully close on power loss.
Available with barometric relief or power exhaust.
• MOTORIZED OUTDOOR AIR DAMPERS – Outdoor and
return air dampers that are interlocked and positioned by
a 2-position, spring-return damper actuator. The
maximum leakage rate for the outdoor air intake dampers
shall not exceed 2% when dampers are fully closed and
operating against a pressure differential of 0.5 IWG. A
unit-mounted potentiometer shall be provided to adjust
the outdoor and return air damper assembly to take in the
design CFM of outdoor air to meet the ventilation
requirements of the conditioned space during normal
operation. Whenever the indoor fan motor is energized,
the dampers open up to one of two pre-selected positions
– regardless of the outdoor air enthalpy. Dampers return
to the fully closed position when the indoor fan motor is
de-energized. Dampers shall fully close on power loss.
ADDITIONAL FACTORY INSTALLED OPTIONS
• ALTERNATE INDOOR BLOWER MOTOR – For
applications with high restrictions, units are available with
optional indoor blower motors that provide higher static
output and/or higher airflow.
• CONVENIENCE OUTLET (POWERED/NON-POWERED)–
Unit can be provided with an optional 120VAC GFCI outlet
with cover on the corner of the unit housing the compressors.
• ELECTRIC HEAT - Electric Heaters range from 9 kW to
54 kW and are available in all the voltage options of the
base unit.
• PHASE MONITOR - Designed to prevent damage in outof-phase condition.
• COIL GUARD - Designed to prevent condenser coil
damage.
• BAS CONTROLS - Include supply air sensor, return air
sensor, dirty filter indicator and air proving switch.
Johnson Controls Unitary Products
528195-YTG-H-0213
• DIRTY FILTER SWITCH – This kit includes a differential
pressure switch that energizes the fault light on the unit
thermostat, indicating that there is an abnormally highpressure drop across the filters.
• BREAKER – An HACR breaker can be factory installed
on heat pumps or heat pumps with electric heat.
• DISCONNECT SWITCH - A disconnect can be factory
installed on a cooling only units sized for the largest
electric heat available.
• SMOKE DETECTOR – A smoke detector can be factory
mounted and wired in the supply and/or return air
compartments.
OTHER PRE-ENGINEERED ACCESSORIES AVAILABLE
• ROOF CURB - 14” and 8” high, full perimeter knockdown
curb, with hinged design for quick assembly.
• BAROMETRIC RELIEF DAMPER – (Unit mounted –
Downflow, Duct Mounted – Horizontal) – Contains a rain
hood, air inlet screen, exhaust damper and mounting
hardware. Used to relieve internal air pressure through
the unit during economizer operation.
• ECONOMIZER (Downflow and Horizontal flow)
• POWER EXHAUST – (Unit mount – Downflow, Duct
mount – Horizontal flow)
• DUAL ENTHALPY KIT - Provides a second input to
economizer to monitor return air.
Johnson Controls Unitary Products
11
528195-YTG-H-0213
Physical Data
XP078-150 Physical Data
Component
Models
XP078
XP090
XP102
XP120
XP150
6.5
7.5
8.5
10
12.5
Gross Capacity @ AHRI A point (Mbh)
80000
94000
104000
122000
155000
AHRI net capacity (Mbh)
78000
90000
100000
117000
148000
EER
11.5
11.0
11.0
11.2
11.0
IEER
12.0
12.3
12.4
11.4
12.5
IPLV
12.4
12.4
12.4
12.4
11.9
Nominal CFM
2600
2800
3300
3750
4200
System power (KW)
6.78
8.15
9.10
10.45
13.60
R-410A
R-410A
R-410A
R-410A
R-410A
Nominal Tonnage
AHRI COOLING PERFORMANCE
Refrigerant type
Refrigerant charge (lb-oz)
System 1
14-2
9-8
13-8
12-14
16-0
System 2
12-10
9-0
13-0
12-12
16-0
47°F capacity rating (Mbh)
75.0
90.0
94.0
102.0
144.0
System power (KW) / COP
6.2 / 3.35
7.6 / 3.35
7.8 / 3.35
8.6 / 3.30
13.2 / 3.2
17°F capacity rating (Mbh)
43.0
55.0
57.0
58.0
87.0
System power (KW) / COP
5.7 / 2.20
7.0 / 2.25
7.3 / 2.25
7.8 / 2.20
11.9 / 2.05
-
-
-
-
-
Length
89
89
89
89
119-7/16
Width
59
59
59
59
59
Height
50-3/4
42
50-3/4
50-3/4
50-3/4
1080
920
1135
1135
1400
Scroll
Scroll
Scroll
Scroll
Scroll
2
2
2
2
2
50 / 100
50 / 100
50 / 100
50 / 100
50 / 100
29.0
23.8
29.0
29.0
47.5
2
2
2
2
2
AHRI HEATING PERFORMANCE
HSPF (Btu/Watts-hr)
DIMENSIONS (inches)
OPERATING WT. (lbs.)
COMPRESSORS
Type
Quantity
Unit Capacity Steps (%)
CONDENSER COIL DATA
Face area (Sq. Ft.)
Rows
Fins per inch
16
20
20
16
15
Tube diameter (in.)
3/8
3/8
3/8
3/8
3/8
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
13.2
Circuitry Type
Refrigerant control
EVAPORATOR COIL DATA
Face area (Sq. Ft.)
13.2
10.6
13.2
13.2
Rows
4
3
4
4
4
Fins per inch
15
15
15
15
15
Tube diameter
3/8
3/8
3/8
3/8
3/8
Circuitry Type
Split-face
Split-face
Split-face
Split-face
Split-face
TXV
TXV
TXV
TXV
TXV
Refrigerant control
12
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078-150 Physical Data (Continued)
Models
Component
XP078
XP090
XP102
XP120
XP150
6.5
7.5
8.5
10
12.5
2
2
2
2
4
Nominal Tonnage
CONDENSER FAN DATA
Quantity of Fans
Fan diameter (Inch)
24
24
24
24
24
Type
Prop
Prop
Prop
Prop
Prop
Drive Type
Direct
Direct
Direct
Direct
Direct
2
2
2
2
4
1/3
1/3
1/3
1/3
1/3
Quantity of motors
Motor HP each
No. speeds
1
1
1
1
1
RPM
850
850
850
850
850
Nominal total CFM
6800
6800
6800
6800
14000
BELT DRIVE EVAP FAN DATA
Quantity
Fan Size (Inch)
Type
1
1
1
1
1
15 x 15
12 x 12
15 x 15
15 x 15
15 x 15
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Centrifugal
Motor Sheave
VL40
VL44
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower Sheave
AK84
AK71
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A54
A52
A49
A49
A56
A54
A56
A54
A54
BX55
Motor HP each
1-1/2
2
1-1/2
3
2
3
2
3
3
5
RPM
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
56
56
56
56
56
56
56
56
56
184T
Frame size
FILTERS
4 - (24 x 20 x 2)1,2 4 - (24 x 16 x 2)1,2 4 - (24 x 20 x 2)1,2 4 - (24 x 20 x 2)1,2 4 - (24 x 20 x 2)1,2
Quantity - Size
4 - (24 x 20 x 2)3
4 - (24 x 16 x 4)3
4 - (24 x 20 x 4)3
4 - (24 x 20 x 2)3
4 - (24 x 20 x 4)3
1. 2 In. Throwaway, Standard, MERV (Minimum Efficiency Reporting Value) 3.
2. 2 In. Pleated, Optional, MERV 7.
3. 4 In. Pleated, Optional, MERV 13.
XP078-150 Unit Limitations
Unit Limitations
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Model
XP
XP
XP
XP
XP
Johnson Controls Unitary Products
Unit Voltage
Applied Voltage
Outdoor DB Temp
Min
Max
Max (°F)
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
208/230-3-60
187
252
125
460-3-60
432
504
125
575-3-60
540
630
125
13
528195-YTG-H-0213
Capacity Performance
XP078-150 Cooling Capacities
XP078 (6.5 Ton)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
1625
1950
2275
2600
2925
3250
14
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
107.3
99.2
91.1
81.6
112.8
104.3
95.7
85.8
83.3
118.3
109.4
100.4
90.0
87.4
123.8
114.4
105.1
94.2
91.5
117.9
108.2
97.1
94.2
121.3
111.3
99.9
97.0
4.8
4.7
4.7
4.6
4.8
4.8
4.7
4.7
4.6
4.9
4.8
4.8
4.7
4.7
4.9
4.9
4.8
4.8
4.7
4.9
4.8
4.8
4.7
4.9
4.9
4.8
4.8
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
99.2
90.3
81.5
75.1
102.7
93.5
84.4
77.8
76.7
106.2
96.8
87.3
80.4
79.3
109.8
100.0
90.2
83.1
82.0
100.9
91.1
83.9
82.7
101.9
91.9
84.7
83.5
6.2
6.1
6.1
6.1
6.2
6.2
6.1
6.1
6.1
6.2
6.2
6.1
6.1
6.1
6.2
6.2
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.1
6.0
6.0
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Input
Return Dry Bulb (°F)
Capacity1
(MBh)
(kW)2
90
85
80
75
70
65
75°F
47.0
38.9
30.7
103.2
5.5
57.9
49.8
41.7
33.5
94.7
5.4
68.8
60.7
52.6
44.5
36.4
86.3
5.4
81.6
70.5
61.8
53.7
45.5
37.4
78.4
5.3
53.0
43.7
34.4
107.7
5.5
65.2
55.9
46.6
37.3
98.9
5.5
77.4
68.1
58.8
49.5
40.2
90.1
5.4
85.8
78.4
69.1
59.8
50.5
41.2
81.8
5.4
83.3
81.9
72.6
63.3
54.0
44.7
80.0
5.4
58.9
48.5
38.0
112.3
5.5
72.5
62.0
51.5
41.1
103.1
5.5
86.0
75.5
65.1
54.6
44.1
93.9
5.5
90.0
86.3
76.5
66.0
55.6
45.1
85.2
5.4
87.4
86.7
80.3
69.8
59.4
48.9
83.4
5.4
64.9
53.3
41.6
116.8
5.6
79.7
68.1
56.5
44.8
107.2
5.5
94.5
82.9
71.3
59.7
48.0
97.6
5.5
94.2
94.2
83.8
72.2
60.6
48.9
88.7
5.4
91.5
91.5
88.0
76.4
64.7
53.1
86.7
5.4
85.1
72.4
59.7
47.0
109.4
5.5
102.9 88.1
75.4
62.6
49.9
99.6
5.5
97.1
97.1
90.5
77.8
65.1
52.4
90.5
5.4
94.2
94.2
92.5
79.8
67.1
54.3
88.5
5.4
90.6
76.7
62.9
49.1
111.6
5.5
111.3 93.3
79.5
65.6
51.8
101.6
5.5
99.9
99.9
97.3
83.5
69.6
55.8
92.3
5.4
97.0
97.0
97.0
83.2
69.4
55.6
90.2
5.4
95°F
44.1
36.5
28.8
92.8
7.0
54.5
46.8
39.1
31.4
84.1
7.0
64.8
57.1
49.4
41.7
34.0
75.4
7.0
75.1
71.1
60.4
52.7
45.0
37.3
69.4
6.9
49.6
40.5
31.4
95.7
7.0
60.8
51.7
42.7
33.6
86.8
7.0
72.1
63.0
53.9
44.9
35.8
77.8
7.0
77.8
75.1
66.0
57.0
47.9
38.8
71.6
6.9
76.7
76.1
67.0
57.9
48.9
39.8
71.9
6.9
55.0
44.5
34.1
98.7
7.0
67.2
56.7
46.3
35.8
89.4
7.0
79.4
68.9
58.5
48.1
37.6
80.2
7.0
80.4
79.1
71.6
61.2
50.7
40.3
73.8
6.9
79.3
79.0
72.7
62.2
51.8
41.3
74.1
6.9
60.4
48.6
36.7
101.6
7.0
73.5
61.7
49.9
38.1
92.1
7.0
86.7
74.9
63.1
51.2
39.4
82.6
7.0
83.1
83.1
77.2
65.4
53.6
41.8
76.0
6.9
82.0
82.0
78.4
66.5
54.7
42.9
76.3
6.9
79.6
66.6
53.6
40.6
92.9
7.0
89.3
80.7
67.7
54.7
41.7
83.3
6.9
83.9
83.9
80.9
67.9
54.9
41.9
76.6
6.9
82.7
82.7
80.9
67.9
54.9
41.9
77.0
6.9
85.7
71.4
57.2
43.0
93.7
6.9
91.9
86.5
72.3
58.1
43.9
84.0
6.9
84.7
84.7
84.7
70.5
56.2
42.0
77.3
6.9
83.5
83.5
83.5
69.3
55.1
40.8
77.7
6.9
90
45.6
56.2
66.8
78.4
51.3
63.0
74.7
81.8
80.0
56.9
69.8
82.7
85.2
83.4
62.6
76.6
90.6
88.7
86.7
82.4
96.1
90.5
88.5
88.1
101.6
92.3
90.2
39.9
51.2
62.6
69.4
46.0
57.3
68.7
71.6
71.9
52.1
63.4
74.8
73.8
74.1
58.2
69.5
80.8
76.0
76.3
75.7
82.4
76.6
77.0
81.9
84.0
77.3
77.7
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
37.7
29.7
48.3
40.4
32.5
58.9
51.0
43.1
35.2
70.8
61.1
53.2
45.3
42.1
32.9
53.8
44.6
35.5
65.6
56.4
47.2
38.0
76.8
67.6
58.4
49.2
79.0
69.8
60.6
51.4
46.5
36.0
59.4
48.9
38.5
72.2
61.8
51.3
40.9
82.7
74.0
63.6
53.1
82.9
76.5
66.0
55.6
50.9
39.2
64.9
53.2
41.5
78.9
67.2
55.5
43.7
88.7
80.5
68.8
57.1
86.7
83.2
71.4
59.7
69.5
56.6
43.8
84.4
71.5
58.7
45.8
90.5
85.7
72.9
60.0
88.5
86.7
73.8
61.0
74.1
60.1
46.1
89.9
75.9
61.9
47.9
92.3
91.0
77.0
62.9
90.2
90.2
76.2
62.2
105°F
33.2
25.5
43.5
35.8
28.1
53.9
46.2
38.5
30.8
67.0
55.6
47.9
40.2
37.0
28.0
48.3
39.3
30.3
59.7
50.7
41.7
32.7
70.0
61.0
52.0
43.0
70.8
61.8
52.8
43.8
40.8
30.5
53.1
42.8
32.5
65.5
55.2
44.9
34.6
73.0
66.4
56.1
45.8
73.5
67.3
57.0
46.7
44.6
33.0
57.9
46.3
34.7
71.3
59.7
48.1
36.5
76.0
71.8
60.2
48.6
76.3
72.8
61.2
49.6
62.8
49.8
36.9
76.3
64.2
51.3
38.3
76.6
74.6
61.6
48.7
77.0
75.2
62.3
49.3
67.6
53.3
39.0
81.4
68.7
54.4
40.1
77.3
77.3
63.0
48.7
77.7
77.7
63.3
49.0
65
37.4
40.0
42.3
42.7
45.1
45.3
48.0
47.1
48.1
48.9
48.2
32.5
34.0
34.8
35.5
36.4
37.0
38.0
35.7
36.3
34.4
34.7
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078 (6.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1625
1950
2275
2600
2925
3250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
86.5
77.9
69.4
63.7
88.8
80.0
71.2
65.4
67.1
91.1
82.1
73.1
67.1
68.9
93.4
84.2
74.9
68.8
70.6
84.9
75.6
69.4
71.2
85.6
76.2
69.9
71.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
35.6
48.0
60.5
63.7
42.4
53.8
65.3
65.4
67.1
49.3
59.7
70.1
67.1
68.9
56.1
65.5
74.9
68.8
70.6
71.9
75.6
69.4
71.2
78.2
76.2
69.9
71.8
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
29.9
22.2
80.1
8.7
40.3
32.6
24.9
71.7
8.6
50.7
43.0
35.3
27.6
63.3
8.6
62.9
50.7
43.0
35.3
27.6
58.0
8.6
33.5
24.6
81.8
8.7
44.9
36.0
27.1
73.2
8.6
56.4
47.4
38.5
29.6
64.6
8.6
64.9
55.9
47.0
38.1
29.2
59.2
8.6
65.5
56.5
47.6
38.7
29.8
62.4
8.5
37.0
26.9
83.5
8.6
49.5
39.4
29.2
74.7
8.6
62.0
51.9
41.7
31.6
65.9
8.6
66.8
61.2
51.0
40.9
30.7
60.4
8.6
68.1
61.9
51.7
41.5
31.4
63.7
8.5
40.5
29.2
85.2
8.6
54.1
42.8
31.4
76.2
8.6
67.7
56.3
45.0
33.6
67.3
8.6
68.8
66.5
55.1
43.7
32.3
61.6
8.6
70.6
67.2
55.8
44.4
33.0
65.0
8.5
59.0
46.1
33.2
76.8
8.6
72.0
60.7
47.8
35.0
67.8
8.6
69.4
68.2
55.3
42.4
29.5
62.1
8.6
71.2
69.5
56.6
43.7
30.8
65.5
8.5
63.8
49.4
35.0
77.4
8.6
76.2
65.1
50.7
36.3
68.3
8.6
69.9
69.9
55.5
41.1
26.7
62.6
8.6
71.8
71.8
57.4
43.0
28.6
66.0
8.5
90
30.4
44.8
58.3
58.0
38.8
50.4
61.9
59.2
62.4
47.3
55.9
65.5
60.4
63.7
55.7
61.5
67.3
61.6
65.0
68.0
67.8
62.1
65.5
74.5
68.3
62.6
66.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
26.7
19.0
37.1
29.4
21.7
47.5
39.8
32.1
24.4
58.0
45.8
38.1
30.4
30.0
21.1
41.5
32.6
23.8
53.0
44.2
35.3
26.5
59.2
50.9
42.0
33.2
60.2
51.3
42.5
33.6
33.3
23.2
45.9
35.9
25.9
58.6
48.6
38.6
28.6
60.4
56.0
46.0
36.0
62.6
56.5
46.4
36.4
36.5
25.4
50.3
39.2
28.0
64.1
53.0
41.8
30.7
61.6
61.1
49.9
38.8
65.0
61.6
50.4
39.3
55.2
42.4
29.5
67.6
57.3
44.4
31.6
62.1
61.8
49.0
36.2
65.5
63.8
51.0
38.1
60.0
45.5
31.0
68.3
61.5
47.0
32.5
62.6
62.6
48.1
33.6
66.0
66.0
51.5
37.0
65
22.7
24.3
24.7
26.0
26.4
27.6
28.1
23.3
25.3
19.1
22.5
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
15
528195-YTG-H-0213
XP090 (7.5 Ton)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
1875
2250
2625
3000
3375
3750
16
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
116.6
107.8
99.0
93.7
120.7
111.7
102.6
97.0
93.4
124.9
115.5
106.1
100.3
96.6
129.1
119.4
109.6
103.7
99.8
120.8
111.0
104.9
101.1
122.3
112.3
106.2
102.3
5.8
5.7
5.6
5.5
5.8
5.7
5.6
5.6
5.6
5.8
5.7
5.6
5.6
5.6
5.8
5.7
5.6
5.6
5.6
5.7
5.7
5.6
5.6
5.7
5.7
5.6
5.6
48.6
62.9
77.2
93.7
53.8
69.3
84.8
97.0
93.4
59.0
75.7
92.4
100.3
96.6
64.1
82.1
100.0
103.7
99.8
87.0
106.1
104.9
101.1
91.9
112.3
106.2
102.3
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
103.4
95.0
86.6
79.0
106.3
97.7
89.0
81.3
81.1
109.3
100.4
91.5
83.6
83.4
112.2
103.1
94.0
85.8
85.6
103.5
94.4
86.2
86.0
104.0
94.8
86.5
86.3
7.3
7.2
7.2
7.1
7.3
7.3
7.2
7.1
7.1
7.4
7.3
7.2
7.1
7.1
7.4
7.3
7.2
7.2
7.2
7.3
7.3
7.2
7.2
7.3
7.3
7.2
7.2
43.0
56.8
70.5
79.0
47.7
62.6
77.6
81.3
81.1
52.3
68.4
84.6
83.6
83.4
56.9
74.3
91.6
85.8
85.6
79.7
93.2
86.2
86.0
85.2
94.8
86.5
86.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Input
Return Dry Bulb (°F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
40.0
31.5
110.0
6.5
54.3
45.7
37.2
101.4
6.5
68.6
60.0
51.5
42.9
92.8
6.4
85.2
74.6
66.1
57.5
48.9
86.4
6.3
44.0
34.1
113.5
6.5
59.5
49.6
39.8
104.7
6.5
75.0
65.1
55.3
45.5
95.8
6.4
91.3
81.0
71.2
61.4
51.5
89.2
6.3
93.4
85.1
75.3
65.4
55.6
87.2
6.3
47.9
36.8
117.1
6.6
64.6
53.5
42.5
108.0
6.5
81.3
70.2
59.2
48.1
98.8
6.4
97.5
87.3
76.3
65.2
54.1
92.0
6.4
96.6
91.8
80.7
69.6
58.6
90.0
6.4
51.8
39.5
120.7
6.6
69.7
57.4
45.1
111.2
6.5
87.7
75.4
63.0
50.7
101.8
6.4
103.7 93.7
81.4
69.1
56.7
94.8
6.4
99.8
98.4
86.1
73.8
61.5
92.7
6.4
73.9
60.7
47.6
112.2
6.5
92.8
79.6
66.5
53.3
102.7
6.5
104.9 99.9
86.8
73.6
60.5
95.6
6.4
101.1 100.4 87.2
74.1
60.9
93.5
6.4
78.0
64.0
50.0
113.1
6.5
97.9
83.9
69.9
55.9
103.5
6.5
106.2 106.2 92.2
78.2
64.2
96.4
6.4
102.3 102.3 88.3
74.3
60.3
94.3
6.4
95°F
34.8
26.5
95.4
8.2
48.5
40.3
32.0
87.7
8.1
62.3
54.0
45.8
37.5
79.9
8.1
79.0
66.6
58.4
50.1
41.9
74.0
8.0
38.2
28.8
97.6
8.2
53.2
43.8
34.4
89.7
8.2
68.1
58.7
49.3
39.9
81.8
8.1
81.3
72.4
63.0
53.6
44.2
75.7
8.0
81.1
74.8
65.4
56.0
46.6
75.4
8.0
41.7
31.1
99.9
8.3
57.9
47.3
36.7
91.8
8.2
74.0
63.4
52.8
42.2
83.7
8.1
83.6
78.2
67.6
57.0
46.5
77.5
8.1
83.4
80.8
70.2
59.6
49.0
77.1
8.1
45.2
33.4
102.1
8.3
62.5
50.8
39.0
93.8
8.2
79.9
68.1
56.3
44.6
85.6
8.1
85.8
84.0
72.2
60.5
48.7
79.2
8.1
85.6
86.8
75.0
63.3
51.5
78.8
8.1
67.0
54.2
41.4
93.9
8.2
85.5
72.7
59.9
47.2
85.6
8.2
86.2
85.3
72.5
59.7
47.0
79.3
8.1
86.0
86.5
73.8
61.0
48.2
78.9
8.1
71.4
57.6
43.8
94.0
8.3
91.1
77.3
63.5
49.7
85.7
8.2
86.5
86.5
72.8
59.0
45.2
79.4
8.1
86.3
86.3
72.5
58.7
45.0
79.0
8.1
90
45.8
59.8
73.8
86.4
50.7
65.9
81.2
89.2
87.2
55.6
72.1
88.5
92.0
90.0
60.5
78.2
95.8
94.8
92.7
83.4
99.7
95.6
93.5
88.6
103.5
96.4
94.3
37.5
53.1
68.7
74.0
43.7
58.8
73.9
75.7
75.4
49.8
64.5
79.2
77.5
77.1
56.0
70.2
84.4
79.2
78.8
75.2
85.1
79.3
78.9
80.1
85.7
79.4
79.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
37.4
29.0
51.4
43.0
34.6
65.4
57.0
48.6
40.2
82.1
70.6
62.2
53.8
41.1
31.5
56.3
46.7
37.1
71.5
61.9
52.3
42.7
86.3
76.7
67.1
57.5
87.2
80.0
70.3
60.7
44.8
34.0
61.2
50.4
39.6
77.7
66.8
56.0
45.2
90.5
82.8
72.0
61.1
90.0
86.3
75.5
64.6
48.5
36.5
66.1
54.1
42.1
83.8
71.7
59.7
47.7
94.8
88.8
76.8
64.8
92.7
92.6
80.6
68.5
70.4
57.4
44.5
89.1
76.2
63.2
50.2
95.6
92.6
79.6
66.7
93.5
93.4
80.5
67.5
74.7
60.8
46.9
94.5
80.6
66.7
52.8
96.4
96.4
82.5
68.6
94.3
94.3
80.4
66.5
105°F
31.2
23.2
45.1
37.0
29.0
58.9
50.9
42.9
34.8
74.0
62.0
54.0
45.9
34.5
25.3
49.6
40.4
31.2
64.7
55.5
46.3
37.1
75.7
67.6
58.4
49.2
75.4
69.1
59.9
50.7
37.7
27.4
54.1
43.8
33.4
70.5
60.2
49.8
39.4
77.5
73.3
62.9
52.5
77.1
74.8
64.5
54.1
41.0
29.5
58.7
47.1
35.6
76.3
64.8
53.3
41.7
79.2
78.9
67.4
55.8
78.8
80.6
69.1
57.5
62.7
50.2
37.7
80.1
69.0
56.5
44.1
79.3
79.1
66.7
54.2
78.9
79.8
67.3
54.8
66.7
53.3
39.8
83.9
73.2
59.8
46.4
79.4
79.4
65.9
52.5
79.0
79.0
65.6
52.1
65
45.4
47.9
51.1
50.3
53.8
52.7
56.5
53.7
54.6
54.7
52.6
37.9
40.0
41.5
42.2
43.7
44.3
46.0
41.7
42.3
39.1
38.7
Johnson Controls Unitary Products
528195-YTG-H-0213
XP090 (7.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
1875
2250
2625
3000
3375
3750
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
87.4
80.3
73.3
68.9
89.0
81.7
74.5
70.1
69.6
90.5
83.2
75.8
71.3
70.8
92.0
84.6
77.1
72.5
72.0
84.3
76.9
72.4
71.8
84.1
76.7
72.2
71.7
9.1
9.1
9.0
8.9
9.2
9.1
9.0
9.0
9.0
9.2
9.1
9.0
9.0
9.0
9.2
9.1
9.1
9.0
9.0
9.2
9.1
9.0
9.0
9.2
9.1
9.1
9.0
32.0
49.4
66.9
68.9
39.7
55.0
70.3
70.1
69.6
47.4
60.6
73.7
71.3
70.8
55.1
66.1
77.1
72.5
72.0
70.6
76.9
72.4
71.8
75.1
76.7
72.2
71.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
27.6
19.8
79.5
10.1
41.6
33.8
26.0
73.0
10.0
55.6
47.8
40.0
32.2
66.6
9.9
68.9
57.4
49.6
41.7
33.9
63.9
9.9
30.7
21.7
80.3
10.1
46.0
37.0
28.1
73.8
10.0
61.3
52.4
43.4
34.4
67.3
9.9
70.1
62.9
53.9
44.9
35.9
64.5
9.9
69.6
63.3
54.4
45.4
36.4
63.9
9.9
33.7
23.6
81.1
10.1
50.4
40.3
30.1
74.5
10.0
67.1
56.9
46.8
36.6
68.0
9.9
71.3
68.3
58.2
48.1
37.9
65.2
9.9
70.8
68.9
58.7
48.6
38.4
64.6
9.9
36.8
25.5
81.9
10.1
54.8
43.5
32.2
75.3
10.1
72.8
61.5
50.2
38.9
68.7
10.0
72.5
73.8
62.5
51.2
39.9
65.9
9.9
72.0
74.4
63.1
51.8
40.5
65.2
9.9
58.4
46.2
34.0
74.8
10.1
74.8
65.3
53.1
41.0
68.2
10.0
72.4
73.0
60.8
48.6
36.4
65.4
10.0
71.8
73.0
60.8
48.7
36.5
64.8
10.0
62.0
48.9
35.9
74.2
10.1
76.7
69.2
56.1
43.0
67.7
10.0
72.2
72.2
59.1
46.0
33.0
65.0
10.0
71.7
71.7
58.6
45.5
32.5
64.3
10.0
90
25.8
45.8
65.4
63.9
35.7
51.2
66.7
64.5
63.9
45.5
56.6
68.0
65.2
64.6
55.4
62.0
68.7
65.9
65.2
66.0
68.2
65.4
64.8
70.0
67.7
65.0
64.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
23.8
16.5
38.2
30.6
23.0
52.3
44.7
37.1
29.5
63.9
52.7
45.1
37.5
26.9
18.1
42.4
33.7
24.9
57.9
49.2
40.4
31.7
64.5
58.1
49.3
40.6
63.9
57.6
48.8
40.1
30.1
19.8
46.7
36.8
26.8
63.6
53.7
43.8
33.8
65.2
63.4
53.5
43.6
64.6
62.9
53.0
43.0
33.2
21.5
50.9
39.9
28.8
68.7
58.2
47.1
36.0
65.9
65.9
57.6
46.6
65.2
65.2
57.1
46.0
54.1
42.2
30.3
68.2
61.6
49.8
37.9
65.4
65.4
55.0
43.1
64.8
64.8
54.4
42.5
57.3
44.6
31.9
67.7
65.1
52.4
39.7
65.0
65.0
52.3
39.6
64.3
64.3
51.6
38.9
65
29.9
31.8
31.3
33.6
33.1
35.5
34.9
31.2
30.6
26.9
26.2
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
17
528195-YTG-H-0213
XP102 (8.5 Ton)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
2125
2550
2975
3400
3825
4250
18
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
120.9
113.7
106.4
96.7
126.2
118.6
110.9
100.9
100.3
131.4
123.5
115.5
105.1
104.4
136.7
128.4
120.1
109.3
108.6
132.2
123.6
112.5
111.8
136.0
127.2
115.7
115.0
6.2
6.1
6.0
5.9
6.2
6.1
6.0
6.0
5.9
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.0
6.2
6.1
6.0
6.0
6.3
6.2
6.1
6.1
58.3
69.9
81.4
96.7
62.1
78.1
94.1
100.9
100.3
65.9
86.3
106.8
105.1
104.4
69.7
94.6
119.5
109.3
108.6
101.6
123.3
112.5
111.8
108.6
127.2
115.7
115.0
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
116.2
105.1
94.0
87.9
120.4
108.9
97.4
91.1
91.1
124.5
112.6
100.7
94.2
94.2
128.7
116.4
104.1
97.4
97.4
118.8
106.3
99.4
99.4
121.3
108.4
101.4
101.4
7.8
7.8
7.8
7.7
7.8
7.8
7.8
7.7
7.7
7.9
7.9
7.8
7.7
7.7
7.9
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
7.9
7.9
7.8
7.8
46.9
64.7
82.5
87.9
56.5
73.1
89.7
91.1
91.1
66.1
81.5
96.9
94.2
94.2
75.7
89.9
104.1
97.4
97.4
96.9
106.3
99.4
99.4
103.9
108.4
101.4
101.4
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Input
Return Dry Bulb (°F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
45.7
36.0
118.6
7.0
60.2
50.5
40.8
109.4
6.9
74.6
65.0
55.3
45.6
100.2
6.9
94.3
79.3
69.6
59.9
50.2
92.3
6.8
51.0
39.8
123.3
7.0
67.0
55.8
44.7
113.7
7.0
83.0
71.8
60.7
49.5
104.2
6.9
99.3
87.7
76.5
65.4
54.3
96.0
6.8
100.5 89.7
78.6
67.5
56.3
95.7
6.8
56.2
43.6
128.0
7.0
73.7
61.2
48.6
118.1
7.0
91.3
78.7
66.1
53.5
108.1
6.9
104.3 96.1
83.5
70.9
58.3
99.6
6.9
104.6 98.3
85.8
73.2
60.6
99.3
6.9
61.5
47.5
132.7
7.1
80.5
66.5
52.5
122.4
7.0
99.6
85.6
71.5
57.5
112.1
7.0
109.3 104.5 90.4
76.4
62.4
103.3
6.9
108.6 106.9 92.9
78.9
64.9
103.0
6.9
86.1
70.7
55.3
125.5
7.1
106.7 91.0
75.5
60.1
115.0
7.0
112.5 110.1 94.7
79.2
63.8
105.9
6.9
111.8 111.0 95.5
80.1
64.7
105.6
6.9
91.8
74.9
58.1
128.6
7.1
113.8 96.4
79.5
62.7
117.8
7.0
115.7 115.7 98.9
82.1
65.2
108.6
7.0
115.0 115.0 98.2
81.4
64.5
108.2
7.0
95°F
39.8
29.8
107.5
8.9
54.7
44.7
34.7
97.2
8.8
69.6
59.6
49.5
39.5
86.8
8.8
87.9
71.6
61.6
51.5
41.5
80.7
8.7
44.9
33.3
111.4
8.9
61.5
49.9
38.3
100.6
8.9
78.1
66.5
54.9
43.3
89.9
8.8
91.1
79.9
68.3
56.7
45.1
83.5
8.7
90.8
79.2
67.6
56.0
44.4
85.1
8.8
50.0
36.8
115.2
9.0
68.3
55.1
41.9
104.0
8.9
86.6
73.4
60.2
47.0
92.9
8.9
94.2
88.2
75.0
61.8
48.6
86.4
8.8
94.1
87.5
74.3
61.0
47.8
88.0
8.8
55.0
40.2
119.0
9.0
75.1
60.3
45.5
107.5
9.0
95.2
80.4
65.6
50.8
96.0
8.9
97.4
96.6
81.8
67.0
52.2
89.2
8.8
97.4
95.7
80.9
66.1
51.3
90.9
8.8
80.7
64.4
48.2
109.5
9.0
101.8 85.9
69.7
53.4
97.8
8.9
99.4
99.0
82.8
66.5
50.3
90.9
8.8
99.4
98.6
82.3
66.1
49.9
92.6
8.8
86.2
68.6
50.9
111.6
9.0
108.4 91.4
73.8
56.1
99.7
8.9
101.4 101.4 83.8
66.1
48.4
92.6
8.9
101.4 101.4 83.8
66.1
48.5
94.4
8.9
90
52.6
67.3
82.0
92.3
59.3
75.6
91.9
96.0
95.7
66.0
83.9
101.8
99.6
99.3
72.7
92.2
111.8
103.3
103.0
99.2
114.8
105.9
105.6
106.2
117.8
108.6
108.2
44.1
62.6
81.1
80.7
56.2
71.1
86.0
83.5
85.1
68.4
79.7
91.0
86.4
88.0
80.5
88.3
96.0
89.2
90.9
95.4
97.8
90.9
92.6
102.5
99.7
92.6
94.4
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
42.8
32.9
57.4
47.6
37.7
72.1
62.3
52.4
42.5
91.1
75.4
65.6
55.7
47.9
36.6
64.2
52.9
41.5
80.5
69.2
57.8
46.4
95.2
83.8
72.4
61.0
95.7
84.5
73.1
61.7
53.1
40.2
71.0
58.1
45.2
89.0
76.1
63.2
50.3
99.2
92.2
79.3
66.4
99.3
92.9
80.0
67.1
58.3
43.8
77.8
63.4
49.0
97.4
83.0
68.5
54.1
103.3 100.5 86.1
71.7
103.0 101.3 86.9
72.5
83.4
67.6
51.8
104.3 88.4
72.6
56.8
105.9 104.5 88.7
72.9
105.6 104.8 88.9
73.1
89.0
71.8
54.5
111.1 93.9
76.7
59.4
108.6 108.6 91.3
74.1
108.2 108.2 91.0
73.7
105°F
37.9
28.3
52.5
42.4
32.3
67.1
56.5
46.4
36.3
80.7
68.6
58.5
48.4
43.5
31.8
59.4
47.6
35.9
75.2
63.5
51.7
40.0
83.5
77.0
65.3
53.5
85.0
73.3
61.6
49.8
49.2
35.3
66.3
52.9
39.4
83.4
70.4
57.0
43.6
86.4
85.5
72.1
58.7
87.9
81.4
67.9
54.5
54.8
38.8
73.2
58.1
43.0
91.5
77.4
62.3
47.2
89.2
93.9
78.9
63.8
90.9
89.4
74.3
59.2
78.8
62.2
45.6
95.6
82.9
66.3
49.7
90.9
93.3
76.7
60.1
92.6
91.9
75.3
58.7
84.4
66.3
48.2
99.7
88.4
70.3
52.2
92.6
92.6
74.6
56.5
94.4
94.4
76.3
58.2
65
45.9
49.7
50.3
53.5
54.2
57.3
58.1
57.1
57.3
56.8
56.5
38.3
41.8
38.1
45.2
41.1
48.7
44.1
43.5
42.1
38.4
40.1
Johnson Controls Unitary Products
528195-YTG-H-0213
XP102 (8.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
2125
2550
2975
3400
3825
4250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
98.9
89.2
79.6
73.4
102.3
92.4
82.4
76.0
79.1
105.8
95.5
85.1
78.5
81.8
109.2
98.6
87.9
81.1
84.4
100.3
89.4
82.5
85.9
101.9
90.9
83.9
87.3
10.0
9.9
9.8
9.7
10.0
9.9
9.8
9.8
9.8
10.1
10.0
9.9
9.8
9.8
10.1
10.0
9.9
9.8
9.9
10.0
9.9
9.9
9.9
10.1
10.0
9.9
9.9
41.2
60.4
79.6
73.4
55.9
69.1
82.4
76.0
79.1
70.7
77.9
85.1
78.5
81.8
85.4
86.6
87.9
81.1
84.4
93.9
89.4
82.5
85.9
101.1
90.9
83.9
87.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
36.0
26.8
90.2
11.1
50.3
40.1
30.0
81.3
11.0
64.5
53.4
43.3
33.2
72.4
10.9
73.4
65.6
55.4
45.3
35.2
66.2
10.8
42.2
30.3
93.3
11.1
57.3
45.4
33.5
84.1
11.0
72.3
60.5
48.6
36.7
74.9
10.9
76.0
74.1
62.3
50.4
38.5
68.5
10.8
79.1
67.5
55.6
43.7
31.8
73.1
10.8
48.4
33.8
96.4
11.2
64.3
50.6
37.0
86.9
11.0
80.1
67.5
53.8
40.2
77.3
10.9
78.5
82.7
69.1
55.5
41.8
70.7
10.8
81.8
75.3
61.6
48.0
34.4
75.6
10.9
54.6
37.3
99.5
11.2
71.3
55.9
40.5
89.7
11.1
87.9
74.5
59.1
43.7
79.8
10.9
81.1
91.3
75.9
60.6
45.2
73.0
10.9
84.4
83.1
67.7
52.3
37.0
78.0
10.9
76.9
60.0
43.0
91.0
11.1
89.4
79.9
63.0
46.0
81.0
11.0
82.5
87.6
70.7
53.7
36.8
74.0
10.9
85.9
85.2
68.3
51.3
34.4
79.1
10.9
82.6
64.1
45.6
92.3
11.1
90.9
85.4
66.8
48.3
82.1
11.0
83.9
83.9
65.4
46.8
28.3
75.1
10.9
87.3
87.3
68.8
50.3
31.8
80.3
11.0
90
44.1
58.2
72.4
66.2
59.4
67.2
74.9
68.5
73.1
74.8
76.1
77.3
70.7
75.6
90.2
85.0
79.8
73.0
78.0
91.0
81.0
74.0
79.1
92.3
82.1
75.1
80.3
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
31.8
25.3
48.0
37.8
27.6
62.0
50.4
40.2
30.0
66.2
66.2
52.3
42.2
40.8
28.8
55.1
43.1
31.1
69.4
57.4
45.4
33.4
68.5
68.5
59.2
47.2
73.1
61.6
49.6
37.6
49.9
32.3
62.2
48.4
34.6
76.9
64.5
50.6
36.8
70.7
70.7
66.1
52.3
75.6
69.2
55.3
41.5
58.9
35.9
69.4
53.7
38.0
79.8
71.5
55.8
40.2
73.0
73.0
73.0
57.4
78.0
76.8
61.1
45.5
75.1
57.8
40.5
81.0
76.9
59.6
42.3
74.0
74.0
64.6
47.3
79.1
78.5
61.2
43.9
80.8
61.8
42.9
82.1
82.1
63.4
44.4
75.1
75.1
56.2
37.2
80.3
80.3
61.3
42.4
65
32.0
35.2
25.5
38.5
27.7
41.7
29.8
30.0
26.6
18.3
23.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
19
528195-YTG-H-0213
XP120 (10 Ton)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
2500
3000
3500
4000
4500
5000
20
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
143.9
137.2
130.5
121.6
147.9
141.0
134.1
124.9
127.2
151.8
144.7
137.7
128.2
130.6
155.8
148.5
141.3
131.6
134.0
144.4
137.4
128.0
130.4
140.3
133.5
124.4
126.7
7.2
7.0
6.9
6.9
7.2
7.0
6.9
6.9
6.8
7.2
7.0
6.9
6.9
6.8
7.2
7.1
6.9
6.9
6.8
7.1
7.0
7.0
6.9
7.2
7.1
7.0
7.0
59.2
79.6
100.1
121.6
65.7
88.3
110.9
124.9
127.2
72.3
97.0
121.7
128.2
130.6
78.9
105.7
132.5
131.6
134.0
107.3
133.0
128.0
130.4
109.0
133.5
124.4
126.7
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
130.2
121.9
113.6
106.1
133.6
125.1
116.5
108.8
112.8
137.0
128.2
119.4
111.6
115.7
140.4
131.4
122.4
114.3
118.5
128.7
119.9
112.0
116.1
126.1
117.4
109.7
113.7
9.3
9.1
8.9
8.9
9.4
9.2
9.0
8.9
8.9
9.4
9.2
9.0
8.9
8.9
9.4
9.2
9.0
9.0
8.9
9.3
9.0
9.0
8.9
9.3
9.1
9.0
9.0
62.5
78.8
95.1
106.1
68.9
86.2
103.6
108.8
112.8
75.2
93.6
112.0
111.6
115.7
81.6
101.0
120.5
114.3
118.5
108.2
118.9
112.0
116.1
115.3
117.4
109.7
113.7
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Input
Return Dry Bulb (°F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
48.0
36.8
137.1
8.3
68.4
57.3
46.1
129.6
8.1
88.9
77.7
66.6
55.4
122.0
7.9
112.1 92.0
80.8
69.7
58.5
113.8
7.9
53.3
40.8
140.7
8.3
75.9
63.4
51.0
133.0
8.1
98.4
86.0
73.5
61.1
125.3
7.9
118.6 101.9 89.5
77.0
64.6
116.9
7.9
117.6 105.2 92.7
80.3
67.8
120.0
7.8
58.6
44.9
144.4
8.3
83.3
69.6
55.8
136.5
8.1
108.0 94.2
80.5
66.8
128.6
7.9
125.1 111.8 98.1
84.4
70.6
119.9
7.9
125.8 115.3 101.6 87.8
74.1
123.2
7.8
63.9
48.9
148.1
8.3
90.7
75.7
60.7
139.9
8.1
117.5 102.5 87.5
72.5
131.8
8.0
131.6 121.7 106.7 91.7
76.7
123.0
7.9
134.0 125.4 110.4 95.4
80.4
126.3
7.9
92.1
76.8
61.5
136.6
8.2
120.4 104.1 88.8
73.5
128.7
8.0
128.0 123.0 107.8 92.5
77.2
120.0
8.0
130.4 126.0 110.7 95.5
80.2
123.3
7.9
93.4
77.8
62.3
133.2
8.3
123.4 105.7 90.1
74.5
125.5
8.1
124.4 124.4 108.8 93.2
77.6
117.0
8.0
126.7 126.7 111.1 95.5
79.9
120.2
8.0
95°F
51.8
41.1
119.6
10.6
68.1
57.4
46.7
112.1
10.4
84.4
73.7
63.0
52.2
104.5
10.2
106.1 94.4
83.7
73.0
62.3
97.9
10.1
56.3
43.7
122.6
10.6
73.6
61.1
48.5
114.9
10.4
91.0
78.4
65.8
53.3
107.1
10.2
108.8 100.5 87.9
75.3
62.8
100.3
10.1
110.9 98.4
85.8
73.2
60.6
105.1
10.2
60.8
46.4
125.6
10.6
79.2
64.8
50.3
117.7
10.4
97.6
83.1
68.7
54.3
109.7
10.2
111.6 106.6 92.1
77.7
63.3
102.8
10.1
114.7 104.3 89.9
75.4
61.0
107.7
10.2
65.3
49.0
128.6
10.6
84.7
68.4
52.2
120.5
10.4
104.2 87.9
71.6
55.3
112.4
10.2
114.3 112.6 96.3
80.0
63.8
105.2
10.2
118.5 110.3 94.0
77.7
61.4
110.2
10.2
90.9
73.7
56.5
117.9
10.5
110.8 94.6
77.4
60.1
110.0
10.3
112.0 111.2 93.9
76.7
59.5
103.0
10.2
116.1 112.0 94.8
77.5
60.3
107.9
10.2
97.1
78.9
60.8
115.3
10.5
117.4 101.3 83.2
65.0
107.5
10.3
109.7 109.7 91.5
73.3
55.2
100.7
10.2
113.7 113.7 95.6
77.4
59.2
105.5
10.2
90
60.8
79.2
97.6
113.8
67.3
87.3
107.2
116.9
120.0
73.8
95.3
116.9
119.9
123.2
80.3
103.4
126.5
123.0
126.3
107.8
126.0
120.0
123.3
112.1
125.5
117.0
120.2
53.1
73.0
92.9
97.9
63.1
81.1
99.0
100.3
105.1
73.2
89.2
105.2
102.8
107.7
83.3
97.3
111.4
105.2
110.2
103.1
109.5
103.0
107.9
108.8
107.5
100.7
105.5
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
49.9
38.9
68.3
57.3
46.4
86.7
75.7
64.8
53.8
109.1 93.2
82.3
71.3
54.8
42.3
74.8
62.2
49.7
94.7
82.2
69.7
57.2
113.7 101.2 88.7
76.2
114.3 101.8 89.2
76.7
59.7
45.6
81.2
67.2
53.1
102.8 88.7
74.6
60.5
118.3 109.2 95.1
81.0
120.3 109.8 95.7
81.6
64.6
49.0
87.7
72.1
56.4
110.8 95.2
79.5
63.9
123.0 117.2 101.5 85.9
126.3 117.8 102.2 86.5
91.5
75.2
59.0
115.6 99.3
83.1
66.8
120.0 117.1 100.8 84.6
123.3 119.0 102.8 86.5
95.3
78.4
61.5
120.4 103.5 86.6
69.8
117.0 117.0 100.2 83.3
120.2 120.2 103.3 86.4
105°F
45.8
35.3
62.4
51.9
41.3
79.0
68.5
57.9
47.4
97.9
84.3
73.7
63.2
50.6
38.0
68.5
56.0
43.5
86.5
73.9
61.4
48.9
100.3 91.0
78.4
65.9
101.5 88.9
76.4
63.8
55.4
40.8
74.7
60.1
45.6
94.0
79.4
64.9
50.4
102.8 97.7
83.1
68.6
105.9 95.5
80.9
66.4
60.1
43.6
80.8
64.3
47.7
101.5 84.9
68.4
51.8
105.2 104.3 87.8
71.3
110.2 102.0 85.5
68.9
85.7
68.4
51.0
104.5 90.3
73.0
55.7
103.0 102.5 85.2
67.8
107.9 103.8 86.4
69.1
90.6
72.5
54.4
107.5 95.7
77.6
59.5
100.7 100.7 82.6
64.4
105.5 105.5 87.4
69.2
65
60.4
63.7
64.2
66.9
67.6
70.2
70.9
68.3
70.2
66.4
69.6
52.6
53.3
51.3
54.0
51.9
54.7
52.4
50.5
51.8
46.3
51.1
Johnson Controls Unitary Products
528195-YTG-H-0213
XP120 (10 Ton) (Continued)
Air on
Evaporator Coil
CFM
2500
3000
3500
4000
4500
5000
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
109.0
102.2
95.4
89.6
111.7
104.7
97.7
91.8
97.4
114.3
107.1
100.0
93.9
99.6
116.9
109.6
102.3
96.1
101.9
107.1
100.0
93.9
99.6
104.6
97.7
91.7
97.3
11.8
11.6
11.5
11.3
11.8
11.6
11.5
11.3
11.4
11.8
11.6
11.4
11.3
11.4
11.8
11.6
11.4
11.3
11.4
11.7
11.5
11.4
11.5
11.7
11.5
11.4
11.5
43.6
67.1
90.6
89.6
57.4
76.0
94.5
91.8
97.4
71.2
84.8
98.4
93.9
99.6
85.0
93.6
102.3
96.1
101.9
97.9
100.0
93.9
99.6
102.3
97.7
91.7
97.3
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
39.8
29.5
98.4
13.1
56.7
46.4
36.0
92.4
12.9
73.6
63.3
52.9
42.5
86.4
12.7
89.6
74.2
63.8
53.4
43.0
81.4
12.6
44.9
32.4
100.7
13.1
63.4
50.9
38.4
94.5
12.9
82.0
69.5
57.0
44.5
88.4
12.7
91.8
81.5
68.9
56.4
43.9
83.2
12.6
92.0
79.5
67.0
54.5
42.0
89.6
12.7
49.9
35.3
102.9
13.0
70.1
55.5
40.8
96.6
12.9
90.4
75.7
61.1
46.4
90.3
12.7
93.9
88.8
74.1
59.5
44.8
85.1
12.5
97.0
86.6
72.0
57.3
42.7
91.6
12.7
55.0
38.2
105.2
13.0
76.8
60.1
43.3
98.7
12.8
98.7
82.0
65.2
48.4
92.3
12.7
96.1
96.1
79.3
62.5
45.7
86.9
12.5
101.9 93.8
77.0
60.2
43.4
93.6
12.7
80.5
63.1
45.6
96.3
12.9
98.2
86.0
68.6
51.2
90.0
12.7
93.9
93.9
76.4
59.0
41.6
84.8
12.6
99.6
95.5
78.1
60.6
43.2
91.3
12.8
84.2
66.1
48.0
93.9
13.0
97.7
90.1
72.0
53.9
87.8
12.8
91.7
91.7
73.6
55.5
37.4
82.7
12.6
97.3
97.3
79.2
61.1
43.0
89.1
12.8
90
36.1
61.3
86.4
81.4
53.3
70.8
88.4
83.2
89.6
70.5
80.4
90.3
85.1
91.6
87.6
89.9
92.3
86.9
93.6
92.8
90.0
84.8
91.3
93.9
87.8
82.7
89.1
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
32.0
23.6
51.1
40.8
30.6
68.3
58.0
47.8
37.6
81.4
64.0
53.8
43.6
39.2
26.7
58.3
45.9
33.4
77.5
65.0
52.5
40.1
83.2
71.9
59.5
47.0
82.6
70.1
57.6
45.1
46.3
29.7
65.6
50.9
36.1
86.8
72.0
57.3
42.5
85.1
79.9
65.1
50.4
88.1
77.8
63.1
48.3
53.5
32.7
72.9
55.9
38.8
92.3
79.0
62.0
44.9
86.9
86.9
70.8
53.7
93.6
85.5
68.5
51.5
75.3
57.7
40.2
90.0
81.8
64.2
46.7
84.8
84.8
67.7
50.2
91.3
87.3
69.8
52.2
77.7
59.6
41.6
87.8
84.5
66.5
48.4
82.7
82.7
64.6
46.6
89.1
89.1
71.0
52.9
65
33.4
34.5
32.6
35.6
33.5
36.7
34.4
32.6
34.7
28.5
34.9
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
21
528195-YTG-H-0213
XP150 (12.5 Ton)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
3125
3750
4375
5000
5625
6250
22
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
163.7
158.9
154.2
145.0
169.7
164.7
159.8
150.3
147.7
175.7
170.5
165.4
155.6
152.9
181.6
176.3
171.0
160.9
158.1
180.7
175.3
164.9
162.0
185.0
179.5
168.8
165.9
9.7
9.5
9.4
9.3
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.7
9.5
9.4
9.3
9.4
9.6
9.5
9.4
9.4
9.6
9.5
9.4
9.4
70.7
95.0
119.4
145.0
77.1
103.5
129.9
150.3
147.7
83.5
112.0
140.4
155.6
152.9
89.9
120.4
150.9
160.9
158.1
125.2
159.2
164.9
162.0
129.9
167.4
168.8
165.9
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
155.1
148.5
141.8
133.3
160.4
153.5
146.6
137.8
135.3
165.6
158.5
151.4
142.3
139.8
170.8
163.5
156.2
146.8
144.2
167.7
160.2
150.5
147.9
171.8
164.1
154.2
151.5
11.6
11.5
11.4
11.3
11.6
11.6
11.5
11.3
11.4
11.7
11.7
11.6
11.4
11.5
11.8
11.7
11.7
11.5
11.5
11.7
11.6
11.5
11.5
11.7
11.6
11.5
11.5
64.1
89.6
115.1
133.3
71.2
99.2
127.1
137.8
135.3
78.4
108.8
139.2
142.3
139.8
85.5
118.4
151.3
146.8
144.2
125.0
157.7
150.5
147.9
131.6
164.1
154.2
151.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Input
Return Dry Bulb (°F)
Capacity1
(MBh)
(kW)2
85
80
75
70
65
75°F
58.2
45.7
159.4
10.6
82.6
70.1
57.6
153.7
10.5
106.9 94.4
81.9
69.4
148.0
10.4
137.7 121.3 108.8 96.4
83.9
139.1
10.3
63.4
49.7
165.0
10.7
89.8
76.1
62.3
159.1
10.6
116.2 102.4 88.7
75.0
153.2
10.5
145.4 131.7 118.0 104.2 90.5
144.0
10.3
147.7 135.9 122.2 108.4 94.7
141.5
10.4
68.5
53.6
170.6
10.7
97.0
82.0
67.1
164.5
10.6
125.5 110.5 95.5
80.6
158.4
10.5
153.2 142.1 127.1 112.1 97.2
148.9
10.4
152.9 146.6 131.6 116.7 101.7
146.3
10.4
73.7
57.5
176.2
10.7
104.2 88.0
71.8
169.9
10.6
134.7 118.5 102.3 86.1
163.6
10.5
160.9 152.4 136.2 120.0 103.8
153.8
10.4
158.1 157.3 141.1 124.9 108.7
151.2
10.4
108.5 91.8
75.2
174.2
10.6
140.3 123.6 107.0 90.3
167.7
10.6
164.9 160.6 144.0 127.3 110.6
157.7
10.4
162.0 161.6 145.0 128.3 111.6
154.9
10.5
112.8 95.7
78.5
178.4
10.7
145.8 128.7 111.6 94.5
171.8
10.6
168.8 168.8 151.7 134.6 117.5
161.5
10.4
165.9 165.9 148.8 131.7 114.6
158.7
10.5
95°F
51.2
38.3
147.3
13.0
76.7
63.8
51.0
140.1
12.9
102.2 89.4
76.5
63.6
133.0
12.8
131.3 111.2 98.3
85.4
72.6
126.1
12.6
56.6
42.0
152.0
13.0
84.6
70.0
55.4
144.6
12.9
112.5 97.9
83.3
68.7
137.2
12.8
136.5 121.9 107.3 92.7
78.1
130.1
12.7
135.3 121.8 107.2 92.6
78.0
128.0
12.7
62.0
45.7
156.7
13.1
92.4
76.1
59.8
149.0
13.0
122.9 106.5 90.2
73.9
141.4
12.9
141.6 132.6 116.2 99.9
83.6
134.1
12.7
139.8 132.5 116.2 99.8
83.5
131.9
12.8
67.4
49.4
161.3
13.1
100.3 82.3
64.2
153.5
13.0
133.2 115.1 97.1
79.0
145.7
12.9
146.8 143.3 125.2 107.1 89.0
138.1
12.8
144.2 143.2 125.1 107.1 89.0
135.9
12.8
106.2 87.3
68.5
157.5
13.0
141.1 122.2 103.4 84.6
149.5
12.9
150.5 148.7 129.9 111.1 92.2
141.7
12.8
147.9 147.3 128.5 109.7 90.8
139.4
12.8
112.0 92.4
72.8
161.6
13.0
148.9 129.3 109.7 90.1
153.3
12.9
154.2 154.2 134.6 115.0 95.4
145.4
12.8
151.5 151.5 131.9 112.3 92.7
143.0
12.8
90
67.4
92.3
117.2
139.1
74.2
101.3
128.5
144.0
141.5
80.9
110.4
139.8
148.9
146.3
87.7
119.4
151.1
153.8
151.2
125.1
158.4
157.7
154.9
130.7
165.8
161.5
158.7
58.0
86.8
115.6
126.1
67.7
96.2
124.8
130.1
128.0
77.3
105.7
134.0
134.1
131.9
86.9
115.1
143.2
138.1
135.9
122.1
148.3
141.7
139.4
129.1
153.3
145.4
143.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
85°F
54.7
42.0
79.6
67.0
54.3
104.6 91.9
79.2
66.5
134.5 116.3 103.6 90.9
60.0
45.8
87.2
73.0
58.9
114.4 100.2 86.0
71.9
140.9 126.8 112.6 98.5
141.5 128.9 114.7 100.5
65.3
49.6
94.7
79.1
63.4
124.2 108.5 92.9
77.2
147.4 137.3 121.7 106.0
146.3 139.6 123.9 108.3
70.6
53.4
102.3 85.1
68.0
134.0 116.8 99.7
82.6
153.8 147.8 130.7 113.6
151.2 150.3 133.1 116.0
107.3 89.6
71.8
140.7 122.9 105.2 87.4
157.7 154.7 136.9 119.2
154.9 154.5 136.7 119.0
112.4 94.0
75.7
147.4 129.0 110.7 92.3
161.5 161.5 143.2 124.8
158.7 158.7 140.3 122.0
105°F
47.7
34.5
73.7
60.6
47.5
99.8
86.7
73.6
60.5
124.4 104.1 91.0
77.9
52.8
37.8
81.3
66.4
51.5
109.9 95.0
80.1
65.2
129.0 114.1 99.1
84.2
128.0 114.9 100.0 85.1
57.9
41.2
88.9
72.2
55.5
120.0 103.3 86.5
69.8
133.5 124.0 107.3 90.6
131.9 125.0 108.2 91.5
63.0
44.5
96.5
78.0
59.5
130.1 111.5 93.0
74.5
138.1 134.0 115.4 96.9
135.9 135.0 116.5 97.9
102.6 83.1
63.5
137.9 118.8 99.3
79.8
141.7 139.7 120.1 100.6
139.4 139.0 119.5 100.0
108.6 88.1
67.6
145.7 126.0 105.5 85.1
145.4 145.4 124.9 104.4
143.0 143.0 122.5 102.1
65
78.2
84.3
86.4
90.4
92.6
96.4
98.9
101.4
101.2
106.4
103.6
64.8
69.3
70.2
73.8
74.8
78.4
79.4
81.1
80.5
83.9
81.6
Johnson Controls Unitary Products
528195-YTG-H-0213
XP150 (12.5 Ton) (Continued)
Air on
Evaporator Coil
CFM
3125
3750
4375
5000
5625
6250
WB
(°F)
Total
Capacity1
(MBh)
Total
Input
(kW)2
90
77
72
67
62
77
72
67
62
57
77
72
67
62
57
77
72
67
62
57
72
67
62
57
72
67
62
57
139.5
131.8
124.1
118.9
143.6
135.7
127.8
122.4
120.6
147.7
139.6
131.5
125.9
124.1
151.8
143.5
135.1
129.4
127.6
147.4
138.8
133.0
131.0
151.3
142.5
136.5
134.5
14.4
14.2
14.1
14.0
14.4
14.3
14.1
14.0
14.1
14.5
14.3
14.1
14.1
14.1
14.5
14.3
14.2
14.1
14.1
14.4
14.2
14.1
14.1
14.4
14.2
14.2
14.2
52.0
84.1
116.1
118.9
64.1
93.3
122.5
122.4
120.6
76.2
102.5
128.8
125.9
124.1
88.3
111.7
135.1
129.4
127.6
119.1
138.8
133.0
131.0
126.5
142.5
136.5
134.5
Temperature of Air on Condenser Coil
Sensible Capacity (MBh)
Total
Total
Return Dry Bulb (°F)
Capacity1
Input
(MBh)
(kW)2
85
80
75
70
65
115°F
44.1
30.8
131.7
15.8
70.7
57.4
44.1
123.5
15.6
97.4
84.0
70.7
57.4
115.3
15.4
117.5 97.0
83.7
70.3
57.0
111.7
15.4
48.9
33.7
135.2
15.8
78.1
62.9
47.6
126.8
15.6
107.2 92.0
76.8
61.6
118.4
15.4
121.5 106.2 91.0
75.8
60.6
114.7
15.4
120.6 108.1 92.8
77.6
62.4
113.3
15.4
53.7
36.6
138.8
15.8
85.4
68.3
51.2
130.1
15.6
117.1 100.0 82.9
65.8
121.5
15.4
125.4 115.4 98.3
81.2
64.1
117.8
15.4
124.1 117.4 100.3 83.2
66.1
116.3
15.4
58.5
39.5
142.3
15.9
92.7
73.7
54.8
133.5
15.6
127.0 108.0 89.0
70.0
124.6
15.4
129.4 124.6 105.7 86.7
67.7
120.8
15.4
127.6 126.8 107.8 88.8
69.8
119.2
15.4
98.9
78.8
58.6
137.3
15.7
134.7 115.3 95.2
75.0
128.1
15.5
133.0 130.6 110.4 90.2
70.1
124.2
15.5
131.0 130.7 110.5 90.3
70.1
122.6
15.5
105.2 83.8
62.5
141.1
15.7
142.5 122.7 101.3 80.0
131.7
15.5
136.5 136.5 115.2 93.8
72.5
127.6
15.5
134.5 134.5 113.2 91.8
70.5
126.0
15.5
90
47.4
81.4
115.3
111.7
62.4
90.4
118.4
114.7
113.3
77.3
99.4
121.5
117.8
116.3
92.2
108.4
124.6
120.8
119.2
116.2
128.1
124.2
122.6
123.9
131.7
127.6
126.0
Sensible Capacity (MBh)
Return Dry Bulb (°F)
85
80
75
70
125°F
40.6
27.0
67.8
54.2
40.6
95.0
81.4
67.8
54.2
110.5 89.9
76.4
62.8
45.1
29.5
74.8
59.3
43.7
104.6 89.1
73.5
58.0
114.0 98.4
82.9
67.3
113.3 101.2 85.6
70.1
49.6
32.1
81.9
64.4
46.9
114.2 96.7
79.2
61.7
117.4 106.9 89.4
71.9
116.3 109.9 92.4
74.9
54.1
34.6
89.0
69.5
50.0
123.8 104.4 84.9
65.5
120.8 115.3 95.9
76.4
119.2 118.6 99.1
79.7
95.3
74.5
53.7
128.1 111.9 91.0
70.2
124.2 121.5 100.7 79.8
122.6 122.3 101.5 80.6
101.7 79.5
57.3
131.7 119.4 97.2
74.9
127.6 127.6 105.4 83.2
126.0 126.0 103.8 81.6
65
49.2
51.8
54.6
54.4
57.4
57.0
60.2
59.0
59.8
61.0
59.4
1. These capacities are gross ratings. For net capacity, deduct air blower motor, MBh = 3.415 x kW. Refer to the appropriate Blower
Performance Table for the kW of the supply air blower motor.
2. These ratings include the condenser fan motors (total 1 kW) and the compressor motors but not the supply air blower motor.
Johnson Controls Unitary Products
23
528195-YTG-H-0213
XP078-150 Heating Capacities
XP078-150
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
1950
70
80
55
078
(6.5)
XP
2600
70
80
55
3250
70
80
55
2250
70
80
55
090
(7.5)
XP
3000
70
80
55
3750
70
80
55
2550
70
80
55
102
(8.5)
XP
3400
70
80
55
4250
70
80
24
Capacity1 &
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
10.1
4.10
4.8
4.95
0.9
5.54
13.4
3.63
8.0
4.45
4.3
5.07
13.8
3.25
8.5
4.11
4.6
4.69
17.4
5.0
15.4
6.1
13.0
6.9
20.1
4.4
18.0
5.5
15.9
6.4
21.2
4.0
19.1
5.1
16.7
5.9
9.4
4.9
12.2
6.1
11.1
6.9
14.9
4.3
17.7
5.6
16.6
6.4
17.2
4.0
20.0
5.2
18.9
6.1
21.7
4.30
16.4
5.15
12.5
5.74
25.0
3.83
19.6
4.65
15.8
5.27
25.3
3.45
20.0
4.30
16.2
4.89
29.3
5.2
27.3
6.3
24.9
7.1
32.0
4.6
29.9
5.7
27.7
6.6
33.0
4.2
31.0
5.3
28.6
6.1
22.3
5.1
25.1
6.3
24.0
7.1
27.8
4.5
30.6
5.8
29.4
6.6
30.1
4.2
32.9
5.4
31.8
6.3
33.3
4.50
28.0
5.35
24.1
5.94
36.6
4.03
31.2
4.85
27.4
5.47
36.9
3.65
31.6
4.50
27.7
5.09
41.1
5.4
39.1
6.5
36.7
7.3
43.8
4.9
41.8
5.9
39.6
6.8
44.9
4.4
42.9
5.5
40.5
6.3
35.1
5.3
37.9
6.5
36.8
7.3
40.6
4.7
43.4
6.0
42.3
6.8
42.9
4.4
45.7
5.6
44.6
6.5
44.8
4.70
39.5
5.55
35.7
6.14
48.1
4.22
42.7
5.05
39.0
5.67
48.5
3.85
43.2
4.70
39.3
5.29
53.0
5.6
51.0
6.7
48.6
7.5
55.7
5.1
53.6
6.1
51.5
7.0
56.7
4.6
54.7
5.7
52.3
6.5
48.0
5.5
50.8
6.7
49.7
7.5
53.5
4.9
56.3
6.2
55.1
7.0
55.8
4.6
58.6
5.9
57.5
6.7
56.4
4.89
51.1
5.75
47.2
6.33
59.7
4.42
54.3
5.24
50.5
5.86
60.0
4.05
54.7
4.90
50.9
5.48
64.9
5.9
62.8
6.9
60.4
7.7
67.6
5.3
65.5
6.3
63.3
7.2
68.6
4.8
66.6
5.9
64.2
6.7
60.8
5.7
63.7
6.9
62.5
7.7
66.3
5.2
69.1
6.4
68.0
7.2
68.6
4.8
71.4
6.1
70.3
6.9
68.0
5.09
62.7
5.94
58.8
6.53
71.3
4.62
65.9
5.44
62.1
6.06
71.6
4.24
66.3
5.10
62.4
5.68
76.7
6.1
74.7
7.1
72.3
7.9
79.4
5.5
77.3
6.6
75.2
7.4
80.5
5.1
78.5
6.1
76.1
6.9
73.7
5.9
76.5
7.1
75.4
7.9
79.2
5.4
82.0
6.6
80.8
7.4
81.5
5.0
84.3
6.3
83.2
7.1
79.5
5.29
74.2
6.14
70.4
6.73
82.8
4.82
77.4
5.64
73.7
6.26
83.2
4.44
77.9
5.29
74.0
5.88
88.6
6.3
86.6
7.4
84.2
8.1
91.3
5.7
89.2
6.8
87.1
7.6
92.3
5.3
90.3
6.3
87.9
7.1
86.5
6.1
89.4
7.3
88.2
8.2
92.0
5.6
94.8
6.8
93.7
7.6
94.3
5.2
97.1
6.5
96.0
7.3
91.1
5.49
85.8
6.34
81.9
6.93
94.4
5.02
89.0
5.84
85.2
6.46
94.7
4.64
89.5
5.49
85.6
6.08
100.5
6.5
98.4
7.6
96.0
8.4
103.2
5.9
101.1
7.0
98.9
7.8
104.2
5.5
102.2
6.6
99.8
7.3
99.4
6.3
102.2
7.5
101.1
8.4
104.9
5.8
107.7
7.0
106.6
7.8
107.2
5.4
110.0
6.7
108.9
7.5
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078-150 (Continued)
Size
(Tons)
Model
Air Over Evaporator
Coil
CFM
DB (°F)
55
3000
70
80
55
120
(10)
XP
4000
70
80
55
5000
70
80
55
3750
70
80
55
150
(12.5)
XP
5000
70
80
55
6250
70
80
Capacity1 &
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
kW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
MBH
KW
Outdoor Temperature (°F @ 72% RH)
-10
0
10
20
30
40
50
60
51.3
5.35
40.6
6.49
37.7
7.24
52.4
4.68
41.8
5.83
39.0
6.59
52.1
3.49
41.5
4.63
38.6
5.38
26.2
8.0
22.8
9.5
19.5
10.7
34.3
7.2
30.9
8.7
27.6
9.9
36.3
6.8
32.9
8.3
29.6
9.5
63.5
5.59
52.8
6.73
50.0
7.48
64.6
4.92
54.0
6.07
51.2
6.83
64.4
3.73
53.7
4.87
50.8
5.62
45.3
8.4
41.9
9.9
38.7
11.1
53.4
7.6
50.1
9.1
46.7
10.3
55.5
7.2
52.0
8.7
48.8
9.9
75.7
5.83
65.0
6.97
62.2
7.72
76.8
5.16
66.2
6.31
63.4
7.07
76.6
3.97
65.9
5.11
63.0
5.86
64.5
8.8
61.0
10.3
57.8
11.5
72.6
8.0
69.2
9.5
65.8
10.7
74.6
7.6
71.1
9.1
67.9
10.3
87.9
6.07
77.2
7.21
74.4
7.96
89.1
5.40
78.4
6.55
75.6
7.31
88.8
4.21
78.1
5.35
75.2
6.11
83.6
9.2
80.2
10.7
76.9
11.9
91.7
8.4
88.3
9.9
85.0
11.1
93.7
8.0
90.3
9.5
87.0
10.7
100.1
6.31
89.4
7.45
86.6
8.20
101.3
5.65
90.6
6.79
87.8
7.55
101.0
4.45
90.3
5.59
87.4
6.35
102.7
9.6
99.3
11.1
96.1
12.3
110.8
8.8
107.5
10.3
104.1
11.5
112.8
8.4
109.4
9.9
106.2
11.1
112.3
6.55
101.6
7.69
98.8
8.44
113.5
5.89
102.8
7.03
100.0
7.79
113.2
4.70
102.5
5.84
99.6
6.59
121.9
10.0
118.4
11.5
115.2
12.7
130.0
9.2
126.6
10.7
123.2
11.9
132.0
8.8
128.5
10.3
125.3
11.5
124.5
6.79
113.8
7.93
111.0
8.68
125.7
6.13
115.0
7.27
112.2
8.03
125.4
4.94
114.7
6.08
111.8
6.83
141.0
10.4
137.6
11.9
134.3
13.1
149.1
9.6
145.7
11.1
142.4
12.3
151.1
9.2
147.7
10.7
144.4
11.9
136.7
7.03
126.1
8.17
123.2
8.92
137.9
6.37
127.2
7.51
124.4
8.28
137.6
5.18
126.9
6.32
124.0
7.07
160.1
10.8
156.7
12.3
153.5
13.5
168.2
10.0
164.8
11.5
161.5
12.7
170.2
9.6
166.8
11.1
163.6
12.3
1. These capacities do not include the supply air blower motor heat. For net capacity, add motor heat, MBh = 3.415 x
kW.
Johnson Controls Unitary Products
25
528195-YTG-H-0213
Airflow Performance
XP078-150 Side Duct Application
XP078 (6.5 Ton) Side Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
441
470
500
529
558
587
616
645
674
FS4
0.44
552
0.48
571
0.54
591
0.60
612
0.68
635
0.78
658
0.88
683
1.00
710
1.14
737
0.54
0.59
0.66
0.73
0.82
0.92
1.02
1.14
1.27
639
654
669
686
705
725
746
768
792
Standard 1.5 HP & Drive
0.63
719
0.72
785
0.69
730
0.79
795
0.76
743
0.87
806
0.85
756
0.96
819
0.94
771
1.05
832
1.04
788
1.16
847
1.15
806
1.28
863
1.27
825
1.41
879
1.40
846
1.55
897
0.81
0.89
0.97
1.07
1.17
1.29
1.41
1.55
1.70
859
870
882
894
906
918
931
943
956
0.99
1.09
1.18
1.29
1.40
1.51
1.63
1.76
1.89
Hi Static 2 HP & Drive
920
1.16
966
1.25
932
1.25
978
1.35
944
1.35
990
1.44
956
1.45 1002 1.55
968
1.56 1014 1.66
980
1.68 1026 1.77
992
1.80 1038 1.89
1005 1.92 1051 2.02
1018 2.06 1064 2.15
1018 1.35
1030 1.44
1042 1.54
1054 1.64
1066 1.75
1078 1.87
1090 1.99
1103 2.12
1116 2.25
FS4
1066
1078
1090
1102
1114
1126
1138
1151
-
1.43
1.53
1.62
1.73
1.84
1.95
2.07
2.20
-
Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x .932.
Field Supplied Drive.
XP090 (7.5 Ton) Side Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
779
0.37
840
0.58
809
0.52
870
0.73
842
0.69
903
0.90
879
0.87
939
1.08
918
1.08
979
1.28
960
1.30 1020 1.50
1004 1.54 1065 1.74
1050 1.79 1111 2.00
1099 2.07 1159 2.27
1149 2.36 1209 2.56
898
928
961
998
1037
1079
1123
1169
1218
1268
0.76
0.91
1.08
1.26
1.46
1.68
1.92
2.18
2.45
2.74
955
985
1018
1054
1093
1135
1179
1226
1274
1324
Standard 1.5 HP & Drive
0.92 1010 1.07 1065
1.07 1040 1.22 1095
1.24 1073 1.39 1128
1.42 1110 1.57 1165
1.63 1149 1.77 1204
1.85 1191 1.99 1246
2.09 1235 2.23 1290
2.34 1281 2.49 1336
2.62 1330 2.76 1385
2.91 1380 3.05 1435
1.21
1.36
1.52
1.71
1.91
2.13
2.37
2.63
2.90
3.19
1120
1150
1183
1220
1259
1301
1345
1391
1440
1490
Hi Static 3 HP & Drive
1.34 1176 1.46 1233 1.59 1292
1.48 1206 1.61 1263 1.74 1321
1.65 1239 1.78 1296 1.91 1355
1.84 1275 1.96 1332 2.09 1391
2.04 1315 2.16 1371 2.29 1430
2.26 1356 2.39 1413 2.51 1472
2.50 1400 2.62 1457 2.75 1516
2.75 1447 2.88 1504 3.01 1562
3.03 1495 3.15 1552 3.28 1611
3.32 1545 3.44
3 HP & Field Supplied Drive
1.72
1.87
2.04
2.22
2.43
2.65
2.89
3.14
3.42
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP102 (8.5 Ton) Side Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
632
0.23
684
0.44
639
0.32
691
0.53
646
0.41
698
0.62
654
0.50
706
0.71
663
0.60
714
0.81
673
0.71
724
0.93
684
0.84
735
1.05
696
0.98
747
1.19
709
1.14
761
1.35
724
1.31
776
1.52
740
1.50
792
1.71
734
741
748
756
765
774
785
798
811
826
842
0.65
0.74
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
783
790
797
805
813
823
834
846
860
874
890
Standard 2 HP & Drive
0.84
830
1.03
876
0.93
837
1.12
883
1.02
844
1.21
890
1.11
852
1.30
898
1.21
861
1.40
907
1.32
871
1.51
917
1.45
882
1.63
928
1.59
894
1.78
940
1.75
907
1.93
953
1.92
922
2.11
968
2.11
938
2.30
984
1.21
1.30
1.39
1.48
1.58
1.69
1.82
1.96
2.12
2.29
2.48
921
928
936
943
952
962
973
985
999
1013
1029
1.39
1.48
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
966
972
980
987
996
1006
1017
1029
1043
1057
1073
Hi Static 3 HP & Drive
1.56 1009 1.74 1051 1.91
1.65 1015 1.83 1058 2.00
1.74 1023 1.92 1065 2.09
1.83 1031 2.01 1073 2.18
1.93 1039 2.11 1082 2.28
2.05 1049 2.22 1091 2.39
2.17 1060 2.34 1102 2.52
2.31 1072 2.48 1115 2.66
2.47 1086 2.64 1128 2.81
2.64 1100 2.82 1143 2.99
2.83 1116 3.01 1159 3.18
3 HP & Field Supplied Drive
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
26
Johnson Controls Unitary Products
528195-YTG-H-0213
XP120 (10 Ton) Side Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
646
654
663
673
684
696
709
724
740
757
776
795
816
2 HP & Field Supplied Drive
0.41
698
0.62
748
0.50
706
0.71
756
0.60
714
0.81
765
0.71
724
0.93
774
0.84
735
1.05
785
0.98
747
1.19
798
1.14
761
1.35
811
1.31
776
1.52
826
1.50
792
1.71
842
1.71
809
1.92
859
1.94
827
2.15
877
2.19
847
2.40
897
2.45
868
2.66
918
0.82
0.92
1.02
1.13
1.25
1.39
1.55
1.72
1.92
2.13
2.35
2.60
2.86
797
805
813
823
834
846
860
874
890
908
926
946
967
1.02
1.11
1.21
1.32
1.45
1.59
1.75
1.92
2.11
2.32
2.55
2.79
3.06
844
852
861
871
882
894
907
922
938
955
974
993
1014
Standard 2 HP & Drive
1.21
890
1.39
936
1.30
898
1.48
943
1.40
907
1.58
952
1.51
917
1.69
962
1.63
928
1.82
973
1.78
940
1.96
985
1.93
953
2.12
999
2.11
968
2.29 1013
2.30
984
2.48 1029
2.51 1001 2.69 1046
2.74 1020 2.92 1065
2.98 1040 3.16 1085
3.25 1061 3.43
-
1.57
1.66
1.76
1.87
2.00
2.14
2.29
2.47
2.66
2.87
3.10
3.34
-
980
987
996
1006
1017
1029
1043
1057
1073
1091
1109
-
1.74
1.83
1.93
2.05
2.17
2.31
2.47
2.64
2.83
3.04
3.27
-
Hi Static 3 HP & Drive
1023 1.92 1065 2.09
1031 2.01 1073 2.18
1039 2.11 1082 2.28
1049 2.22 1091 2.39
1060 2.34 1102 2.52
1072 2.48 1115 2.66
1086 2.64 1128 2.81
1100 2.82 1143 2.99
1116 3.01 1159 3.18
1134 3.22 1176 3.39
1152 3.45
3 HP & Field Supplied Drive
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP150 (12.5 Ton) Side Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
6000
6200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
673
684
696
709
724
740
757
776
795
816
839
862
886
912
939
967
0.71
0.84
0.98
1.14
1.31
1.50
1.71
1.94
2.19
2.45
2.73
3.03
3.34
3.67
4.02
4.39
724
735
747
761
776
792
809
827
847
868
890
914
938
964
990
1018
3 HP & Field Supplied Drive
0.93
774
1.13
823
1.32
871
1.05
785
1.25
834
1.45
882
1.19
798
1.39
846
1.59
894
1.35
811
1.55
860
1.75
907
1.52
826
1.72
874
1.92
922
1.71
842
1.92
890
2.11
938
1.92
859
2.13
908
2.32
955
2.15
877
2.35
926
2.55
974
2.40
897
2.60
946
2.79
993
2.66
918
2.86
967
3.06 1014
2.94
940
3.14
989
3.34 1037
3.24
964
3.44 1012 3.64 1060
3.55
988
3.76 1037 3.95 1084
3.89 1014 4.09 1063 4.28 1110
4.23 1041 4.44 1089 4.63 1137
4.60 1068 4.80 1117 4.99 1165
Hi Static 5 HP & Drive
1.51
1.63
1.78
1.93
2.11
2.30
2.51
2.74
2.98
3.25
3.53
3.82
4.14
4.47
4.82
5.18
917
928
940
953
968
984
1001
1020
1040
1061
1083
1106
1131
1156
1183
1211
1.69
1.82
1.96
2.12
2.29
2.48
2.69
2.92
3.16
3.43
3.71
4.01
4.32
4.65
5.00
5.36
962
973
985
999
1013
1029
1046
1065
1085
1106
1128
1151
1176
1201
1228
1256
Standard 3 HP & Drive
1.87 1006 2.05 1049 2.22 1091
2.00 1017 2.17 1060 2.34 1102
2.14 1029 2.31 1072 2.48 1115
2.29 1043 2.47 1086 2.64 1128
2.47 1057 2.64 1100 2.82 1143
2.66 1073 2.83 1116 3.01 1159
2.87 1091 3.04 1134 3.22 1176
3.10 1109 3.27 1152 3.45 1194
3.34 1129 3.52 1172 3.69 1214
3.61 1150 3.78 1193 3.95 1235
3.89 1172 4.06 1215 4.23 1257
4.18 1195 4.36 1238 4.53 1281
4.50 1220 4.67 1263 4.85 1305
4.83 1246 5.01 1289 5.18 1331
5.18 1272 5.35 1315 5.53 1358
5.54 1300 5.72
5 HP & Field Supplied Drive
2.39
2.52
2.66
2.81
2.99
3.18
3.39
3.62
3.86
4.13
4.41
4.70
5.02
5.35
5.70
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
Johnson Controls Unitary Products
27
528195-YTG-H-0213
XP078-150 Bottom Duct Application
XP078 (6.5 Ton) Bottom Duct
Air Flow
(CFM)
1800
2000
2200
2400
2600
2800
3000
3200
3400
1.
2.
3.
4.
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
445
486
530
567
605
645
686
729
772
FS4
0.63
559
0.71
589
0.84
624
0.91
653
1.02
685
1.16
719
1.31
757
1.49
797
1.70
839
0.66
0.76
0.90
0.98
1.10
1.24
1.39
1.57
1.77
Standard 1.5 HP & Drive
648
0.69
730
0.72
674
0.79
753
0.83
705
0.94
781
0.99
729
1.04
801
1.09
758
1.16
826
1.21
788
1.29
854
1.36
822
1.46
885
1.53
858
1.64
917
1.73
897
1.84
953
1.93
799
820
846
867
889
915
943
972
1005
0.75
0.87
1.03
1.14
1.27
1.43
1.60
1.81
2.03
875
898
924
944
965
988
1013
1038
1066
Hi Static 2 HP & Drive
0.89
937
0.99
984
1.05
1.02
960
1.13 1007 1.18
1.19
988
1.31 1034 1.35
1.31 1007 1.41 1055 1.47
1.45 1028 1.55 1075 1.60
1.60 1051 1.71 1099 1.75
1.77 1076 1.88 1123 1.93
1.96 1102 2.07 1149 2.11
2.16 1130 2.27 1177 2.31
FS4
1038
1061
1088
1108
1128
1151
1176
1203
1230
1.08
1.21
1.39
1.50
1.63
1.80
1.97
2.16
2.36
1086
1109
1137
1156
1178
1201
1225
1252
1.11
1.25
1.42
1.54
1.67
1.83
2.00
2.19
Blower performance includes gas heat exchangers and 2" filters. See STATIC RESISTANCE table for additional applications.
See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
kW = BHP x .932.
Field Supplied Drive.
XP090 (7.5 Ton) Bottom Duct
Air Flow
(CFM)
2000
2200
2400
2600
2800
3000
3200
3400
3600
3800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
1.5 HP & Field Supplied Drive
805
0.46
879
0.68
842
0.62
916
0.84
885
0.81
959
1.02
933
1.01 1007 1.23
985
1.24 1059 1.46
1040 1.49 1114 1.71
1097 1.77 1171 1.98
1157 2.06 1231 2.28
1219 2.38 1293 2.60
1282 2.72 1356 2.93
953
990
1033
1081
1132
1187
1245
1305
1367
1430
Standard 1.5 HP & Drive
0.86 1027 1.03 1101
1.02 1064 1.19 1138
1.21 1107 1.38 1181
1.41 1155 1.58 1229
1.64 1206 1.81 1281
1.90 1261 2.06 1336
2.17 1319 2.34 1393
2.47 1379 2.63 1453
2.78 1440 2.95 1515
3.12 1504 3.29 1578
1.19
1.35
1.53
1.74
1.97
2.22
2.49
2.79
3.11
3.45
Hi Static 3 HP & Drive
1177 1.34 1254 1.49 1333
1214 1.50 1291 1.65 1370
1257 1.68 1334 1.83 1413
1305 1.89 1382 2.04 1461
1356 2.12 1433 2.27 1512
1411 2.37 1488 2.52 1567
1469 2.64 1546 2.80 1625
1529 2.94 1606 3.09 1685
1590 3.26 1667 3.41
3 HP & Field Supplied Drive
1.65
1.81
1.99
2.20
2.43
2.68
2.96
3.25
-
1414
1451
1495
1542
1594
1649
1706
1766
-
1.82
1.98
2.17
2.37
2.60
2.85
3.13
3.43
-
1499
1536
1579
1627
1679
1734
1791
-
2.02
2.18
2.36
2.57
2.80
3.05
3.33
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP102 (8.5 Ton) Bottom Duct
Air Flow
(CFM)
2200
2400
2600
2800
3000
3200
3400
3600
3800
4000
4200
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
662
0.53
717
0.68
677
0.63
732
0.78
693
0.75
748
0.90
712
0.88
767
1.03
733
1.03
788
1.18
757
1.20
811
1.36
782
1.40
837
1.55
810
1.61
865
1.76
841
1.85
896
2.00
874
2.11
928
2.26
909
2.38
963
2.53
770
784
801
819
841
864
890
918
948
981
1016
0.83
0.93
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
Standard 2 HP & Drive
821
0.96
870
1.09
835
1.06
885
1.19
852
1.18
901
1.31
871
1.31
920
1.44
892
1.46
941
1.59
915
1.64
964
1.77
941
1.83
990
1.96
969
2.04 1018 2.18
999
2.28 1049 2.41
1032 2.54 1082 2.67
1067 2.81 1117 2.95
918
933
949
968
989
1012
1038
1066
1097
1130
1164
1.22
1.32
1.44
1.57
1.72
1.89
2.09
2.30
2.54
2.80
3.07
Hi Static 3 HP & Drive
965
1.35 1010 1.47 1055 1.59
979
1.44 1025 1.57 1069 1.69
996
1.56 1041 1.68 1085 1.80
1014 1.69 1060 1.81 1104 1.94
1036 1.84 1081 1.97 1125 2.09
1059 2.02 1104 2.14 1149 2.26
1085 2.21 1130 2.33 1174 2.45
1113 2.43 1158 2.55 1203 2.67
1143 2.66 1189 2.78 1233 2.91
1176 2.92 1222 3.04 1266 3.16
1211 3.20 1256 3.32 1301 3.44
3 HP & Field Supplied Drive
1098
1112
1129
1148
1169
1192
1218
1246
1276
1309
-
1.71
1.81
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
28
Johnson Controls Unitary Products
528195-YTG-H-0213
XP120 (10 Ton) Bottom Duct
Air Flow
(CFM)
2600
2800
3000
3200
3400
3600
3800
4000
4200
4400
4600
4800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
2 HP & Field Supplied Drive
693
0.75
748
0.90
712
0.88
767
1.03
733
1.03
788
1.18
757
1.20
811
1.36
782
1.40
837
1.55
810
1.61
865
1.76
841
1.85
896
2.00
874
2.11
928
2.26
909
2.38
963
2.53
946
2.68 1000 2.83
985
3.00 1040 3.15
1026 3.33
-
801
819
841
864
890
918
948
981
1016
1053
1092
-
1.04
1.17
1.33
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
-
Standard 2 HP & Drive
852
1.18
901
1.31
949
1.44
996
871
1.31
920
1.44
968
1.57 1014
892
1.46
941
1.59
989
1.72 1036
915
1.64
964
1.77 1012 1.89 1059
941
1.83
990
1.96 1038 2.09 1085
969
2.04 1018 2.18 1066 2.30 1113
999
2.28 1049 2.41 1097 2.54 1143
1032 2.54 1082 2.67 1130 2.80 1176
1067 2.81 1117 2.95 1164 3.07 1211
1104 3.11 1154 3.24 1202 3.37
1143 3.43
3 HP & Field Supplied Drive
Hi Static 3 HP & Drive
1.56 1041 1.68 1085
1.69 1060 1.81 1104
1.84 1081 1.97 1125
2.02 1104 2.14 1149
2.21 1130 2.33 1174
2.43 1158 2.55 1203
2.66 1189 2.78 1233
2.92 1222 3.04 1266
3.20 1256 3.32 1301
-
1.80
1.94
2.09
2.26
2.45
2.67
2.91
3.16
3.44
-
1129
1148
1169
1192
1218
1246
1276
1309
-
1.92
2.06
2.21
2.38
2.58
2.79
3.03
3.28
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
XP150 (12.5 Ton) Bottom Duct
Air Flow
(CFM)
3200
3400
3600
3800
4000
4200
4400
4600
4800
5000
5200
5400
5600
5800
Available External Static Pressure - IWG1
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
757
782
810
841
874
909
946
985
1026
1069
1114
1161
1210
1260
3 HP & Field Supplied Drive
1.20
811
1.36
864
1.40
837
1.55
890
1.61
865
1.76
918
1.85
896
2.00
948
2.11
928
2.26
981
2.38
963
2.53 1016
2.68 1000 2.83 1053
3.00 1040 3.15 1092
3.33 1081 3.48 1133
3.69 1124 3.84 1177
4.06 1169 4.21 1222
4.45 1216 4.60 1268
4.86 1264 5.01 1317
5.28 1315 5.43 1367
1.50
1.69
1.91
2.14
2.40
2.68
2.98
3.29
3.63
3.98
4.35
4.74
5.15
5.57
915
941
969
999
1032
1067
1104
1143
1184
1228
1273
1319
1368
1418
1.64
1.83
2.04
2.28
2.54
2.81
3.11
3.43
3.76
4.12
4.49
4.88
5.29
5.71
964
990
1018
1049
1082
1117
1154
1193
1234
1277
1322
1369
1418
-
Standard 3 HP & Drive
1.77 1012 1.89 1059
1.96 1038 2.09 1085
2.18 1066 2.30 1113
2.41 1097 2.54 1143
2.67 1130 2.80 1176
2.95 1164 3.07 1211
3.24 1202 3.37 1248
3.56 1241 3.69 1287
3.90 1282 4.02 1328
4.25 1325 4.38 1372
4.62 1370 4.75 1417
5.01 1417 5.14 1463
5.42 1465 5.55 1512
5 HP & Field Supplied Drive
2.02
2.21
2.43
2.66
2.92
3.20
3.49
3.81
4.15
4.50
4.87
5.26
5.67
-
1104
1130
1158
1189
1222
1256
1294
1333
1374
1417
1462
1509
-
2.14
2.33
2.55
2.78
3.04
3.32
3.62
3.93
4.27
4.62
5.00
5.38
-
Hi Static 5 HP & Drive
1149 2.26 1192 2.38
1174 2.45 1218 2.58
1203 2.67 1246 2.79
1233 2.91 1276 3.03
1266 3.16 1309 3.28
1301 3.44 1344 3.56
1338 3.74 1381 3.86
1377 4.05 1420 4.18
1418 4.39 1461 4.51
1461 4.74 1505 4.87
1506 5.12 1550 5.24
1553 5.51 1596 5.63
-
1. Blower performance includes 2” filters. See STATIC RESISTANCE table for additional applications.
2. See RPM SELECTION table to determine desired motor sheave setting and to determine the maximum continuous BHP.
3. kW = BHP x 0.932.
RPM Selection
Size
(Tons)
Model
078
(6.5)
XP
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
XP
XP
XP
XP
HP
1.5
2.0
1.5
3
2
3
2
3
3
5
Max
BHP
1.73
2.30
1.73
3.45
2.30
3.45
2.30
3.45
3.45
5.75
Johnson Controls Unitary Products
Motor
Sheave
VL40
VL44
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Blower
Sheave
AK84
AK71
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
6 Turns
Open
NA
NA
N/A
N/A
N/A
N/A
N/A
N/A
N/A
1052
5 Turns
Open
576
790
897
1088
735
880
785
880
880
1095
4 Turns
Open
618
843
945
1147
775
928
821
928
928
1136
3 Turns
Open
661
887
991
1205
815
972
858
972
972
1175
2 Turns
Open
702
936
1035
1265
851
1016
901
1016
1016
1216
1 Turn
Open
748
989
1079
1312
889
1067
940
1067
1067
1272
Fully
Closed
792
1041
1126
1365
930
1110
980
1110
1110
N/A
29
528195-YTG-H-0213
Additional Static Resistance
Size
(Tons)
Model
090 (7.5)
XP
078 (6.5)
102 (8.5)
120 (10)
150 (12.5)
XP
CFM
Economizer1 2
4” Filter1
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
1900
2100
2300
2500
2700
2900
3100
3300
3500
3700
3900
4100
4300
4500
4700
4900
5100
5300
5500
5700
5900
6100
6300
0.07
0.09
0.11
0.13
0.16
0.18
0.20
0.22
0.24
0.27
0.29
0.31
0.30
0.35
0.02
0.02
0.04
0.11
0.18
0.25
0.31
0.37
0.43
0.49
0.54
0.58
0.65
0.69
0.74
0.78
0.82
0.86
0.89
0.93
0.96
0.98
1.01
0.10
0.11
0.12
0.14
0.15
0.16
0.18
0.19
0.20
0.21
0.23
0.24
0.25
0.26
0.12
0.13
0.14
0.16
0.17
0.19
0.20
0.22
0.26
0.27
0.29
0.32
0.35
0.38
0.41
0.44
0.47
0.51
0.55
0.58
0.62
0.67
0.71
9
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.05
0.06
0.07
0.08
0.09
0.10
0.12
0.13
0.15
0.17
0.19
0.21
0.23
0.25
0.28
0.30
0.33
0.35
0.38
0.41
0.44
0.47
0.50
Electric Heat kW1
18
24
36
0.06
0.07
0.08
0.07
0.08
0.09
0.08
0.09
0.10
0.09
0.10
0.11
0.10
0.12
0.13
0.11
0.13
0.14
0.13
0.15
0.16
0.14
0.17
0.18
0.16
0.19
0.20
0.18
0.21
0.22
0.20
0.23
0.24
0.22
0.25
0.26
0.24
0.28
0.29
0.26
0.30
0.31
0.06
0.07
0.08
0.07
0.08
0.09
0.08
0.09
0.10
0.09
0.10
0.11
0.10
0.12
0.13
0.11
0.13
0.14
0.13
0.15
0.16
0.14
0.17
0.18
0.16
0.19
0.20
0.18
0.21
0.22
0.20
0.23
0.24
0.22
0.25
0.26
0.24
0.28
0.29
0.26
0.30
0.31
0.29
0.33
0.34
0.31
0.35
0.37
0.34
0.38
0.40
0.37
0.41
0.43
0.40
0.44
0.46
0.43
0.47
0.49
0.46
0.50
0.53
0.49
0.53
0.56
0.53
0.56
0.59
54
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.10
0.11
0.13
0.14
0.16
0.18
0.20
0.22
0.24
0.26
0.28
0.31
0.34
0.37
0.40
0.43
0.46
0.49
0.53
0.56
0.59
0.62
0.65
1. Deduct these values from the available external static pressure shown in the respective Blower Performance
Tables.
2. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the
resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer
operation.
30
Johnson Controls Unitary Products
528195-YTG-H-0213
Drive Selection
1.
Determine side or bottom supply duct Application.
2.
Determine desired airflow.
3.
Calculate or measure the amount of external static pressure.
4.
Using the operating point determined from steps 1, 2 & 3, locate this point on the appropriate supply air blower performance
table. (Linear interpolation may be necessary.)
5.
Noting the RPM and BHP from step 4, locate the appropriate motor and, or drive on the RPM selection table.
6.
Review the BHP compared to the motor options available. Select the appropriate motor and, or drive.
7.
Review the RPM range for the motor options available. Select the appropriate drive if multiple drives are available for the
chosen motor.
8.
Determine turns open to obtain the desired operation point.
Example
1.
2600 CFM
2.
1.6 iwg
3.
Using the supply air blower performance table below, the following data point was located: 1268 RPM & 1.95 BHP.
4.
Using the RPM selection table below, Size X and Model Y is found.
5.
1.95 BHP exceeds the maximum continuous BHP rating of the 1.5 HP motor. The 2 HP motor is required.
6.
1268 RPM is within the range of the 2 HP drives.
7.
Using the 2 HP motor and drive, .5 turns open will achieve 1268 RPM.
Airflow Performance
Example Supply Air Blower Performance
Air Flow
(CFM)
2200
2400
2600
2800
Available External Static Pressure - IWG
0.2
0.4
0.6
0.8
1.0
1.2
1.4
1.6
1.8
2.0
RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP RPM BHP
804
835
869
906
0.50
0.66
0.84
1.03
1.5 HP & Field Supplied Drive
866
0.71
925
0.90
982
897
0.87
956
1.06 1013
931
1.05
990
1.24 1047
968
1.25 1027 1.43 1084
1.06
1.22
1.40
1.60
1038
1069
1103
1139
Standard 1.5 HP & Drive
1.21 1092 1.35 1147
1.37 1124 1.51 1178
1.55 1158 1.69 1212
1.75 1194 1.89 1249
1.48
1.64
1.82
2.02
1203
1234
1268
1304
Alternate 2 HP & Drive
1.61 1259 1.73 1317
1.77 1290 1.90 1348
1.95 1324 2.07 1382
2.14 1361 2.27
-
1.87
2.03
2.21
-
Table X: RPM Selection
Size
(Tons)
Model
HP
X
Y
1.5
2
Max
BHP
1.73
2.30
Johnson Controls Unitary Products
Motor
Sheave
1VM50
1VM50
Blower
Sheave
AK74
AK64
6 Turns
Open
N/A
N/A
5 Turns
Open
897
1039
4 Turns
Open
945
1094
3 Turns
Open
991
1150
2 Turns
Open
1035
1207
1 Turn
Open
1079
1256
Fully
Closed
1126
1308
31
528195-YTG-H-0213
Altitude/Temperature Correction Factors
Air
Temp.
40
50
60
70
80
90
100
0
1.060
1.039
1.019
1.000
0.982
0.964
0.946
1000
1.022
1.002
0.982
0.964
0.947
0.929
0.912
2000
0.986
0.966
0.948
0.930
0.913
0.897
0.880
3000
0.950
0.931
0.913
0.896
0.880
0.864
0.848
4000
0.916
0.898
0.880
0.864
0.848
0.833
0.817
Altitude (Ft.)
5000
0.882
0.864
0.848
0.832
0.817
0.802
0.787
6000
0.849
0.832
0.816
0.801
0.787
0.772
0.758
7000
0.818
0.802
0.787
0.772
0.758
0.744
0.730
8000
0.788
0.772
0.757
0.743
0.730
0.716
0.703
9000
0.758
0.743
0.729
0.715
0.702
0.689
0.676
10000
0.729
0.715
0.701
0.688
0.676
0.663
0.651
1.100
1.050
Correction Factor
1.000
Sea Level
0.950
1000 ft
0.900
2000 ft
3000 ft
0.850
4000 ft
0.800
5000 ft
0.750
6000 ft
7000 ft
8000 ft
0.700
9000 ft
10000 ft
0.650
0.600
40
50
60
70
80
90
100
Air Temperature (ºF)
Electric Heat Minimum Supply Air
Size
(Tons)
32
Model
078
(6.5)
XP
090
(7.5)
XP
102
(8.5)
XP
120
(10)
XP
150
(12.5)
XP
Voltage
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
208/230-3-60
460-3-60
600-3-60
9
1950
1950
1950
2250
2250
2250
2550
2550
2550
-
Minimum Supply Air (CFM)
Heater kW
18
24
36
1950
1950
1950
1950
1950
1950
1950
1950
1950
2250
2250
2250
2250
2250
2250
2250
2250
2250
2550
2550
2550
2550
2550
2550
2550
2550
2550
3000
3000
3000
3000
3000
3000
3000
3000
3000
3750
3750
3750
3750
3750
3750
3750
3750
3750
54
3500
3000
3500
4000
3750
3750
Johnson Controls Unitary Products
528195-YTG-H-0213
Indoor Blower Specifications
Motor
Size
(Tons)
Model
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
XP
XP
XP
XP
XP
HP
RPM
Eff.
SF
Frame
1-1/2
2
1-1/2
3
2
3
2
3
3
5
1725
1725
1725
1725
1725
1725
1725
1725
1725
1725
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.8
0.87
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
1.15
56
56
56
56
56
56
56
56
56
184T
Motor Sheave
Datum Dia.
Bore (in.)
(in.)
2.4 - 3.4
7/8
2.8 - 3.8
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
3.4 - 4.4
7/8
4.3 - 5.3
1-1/8
Blower Sheave
Datum Dia.
Bore (in.)
(in.)
8.1
1
6.7
1
7.0
1
5.7
1
8.5
1
7.0
1
8.0
1
7.0
1
7.0
1
6.7
1
Model
VL40
VL44
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VM50
1VP56
Model
AK84
AK71
AK74
AK61
AK89
AK74
AK84
AK74
AK74
BK77
Belt
A54
A52
A49
A49
A56
A54
A56
A54
A54
BX55
Power Exhaust Specifications
Model
Voltage
2PE04703225
2PE04703246
2PE04703258
208/230-1-60
460-1-60
575-1-60
HP
3/4
3/4
3/4
Motor
RPM1
1075
1075
1050
QTY
1
1
1
Motor
FLA
5
2.2
1.5
LRA
7.8
3.4
2.9
CFM @
0.1 ESP
3800
3800
3800
Fuse Size
MCA
6.3
2.8
1.9
10
5
4
1. Motors are multi-tapped and factory wired for high speed.
Electric Heat Multipliers
Voltage
Nominal
kW Capacity Multipliers1
Applied
208
230
460
575
240
480
600
0.75
0.92
0.92
0.92
1. Electric heaters are rated at nominal voltage. Use this table to determine the electric heat
capacity for heaters applied at lower voltages.
Sound Performance
Indoor Sound Power Levels
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Model
CFM
ESP
(IWG)
Blower
RPM
BHP
Rating1
Sound
dB (A)
63
Sound Power, dB (10-12) Watts
Octave Band Centerline Frequency (Hz)
125
250
500
1000
2000
4000
8000
XP
2600
0.6
812
1.14
74
71
73
73
71
69
65
65
60
XP
3000
0.6
854
1.47
77
74
76
76
74
72
68
68
63
XP
3400
0.6
872
1.65
80
77
79
79
77
75
71
71
66
XP
4000
0.6
959
2.29
83
80
82
82
80
78
74
74
69
XP
5000
0.6
1132
3.74
87
84
86
86
84
82
78
78
73
1. These values have been accessed using a model of sound propagation from a point source into the hemispheric/free field. The dBA values
provided are to be used for reference only. Calculation of dBA values cover matters of system design and the fan manufacture has no way
of knowing the details of each system. This constitutes an exception to any specification or guarantee requiring a dBA value of sound data
in any other form than sound power level ratings.
Johnson Controls Unitary Products
33
528195-YTG-H-0213
Outdoor Sound Power Levels
Size
(Tons)
078
(6.5)
090
(7.5)
102
(8.5)
120
(10)
150
(12.5)
Model
Sound Rating1
dB (A)
125
Octave Band Centerline Frequency (Hz)
250
500
1000
2000
4000
8000
XP
83
88.0
82.5
81.5
78.0
73.0
69.0
62.0
XP
83
89.5
83.5
82.0
78.0
72.5
68.0
60.5
XP
83
89.0
84.5
81.5
78.0
72.5
68.5
70.5
XP
83
89.5
83.5
81.0
78.0
72.0
68.5
70.5
XP
84
90.0
84.5
81.5
77.5
72.0
68.5
61.5
1. Rated in accordance with AHRI 270 standard.
34
Johnson Controls Unitary Products
528195-YTG-H-0213
Electrical Data
XP078-150 Standard Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
15.1
1.5
6.2
5.5
0.0
230
13.5
88.0
15.1
1.5
6.2
5.5
0.0
460
6.0
44.0
9.3
0.8
3.1
2.2
0.0
575
4.9
34.0
7.7
0.6
2.4
1.8
0.0
208
15.6
83.1
21.4
1.5
6.2
5.5
0.0
230
15.6
83.1
21.4
1.5
6.2
5.5
0.0
460
6.9
41
9.7
0.8
3.1
2.2
0.0
575
5.4
33
7.5
0.6
2.4
1.8
0.0
208
16.7
120
26.0
1.5
8.2
5.5
0.0
230
16.7
120
26.0
1.5
8.2
5.5
0.0
460
8.7
60
13.5
0.8
4.1
2.2
0.0
575
6.7
42
10.5
0.6
3.6
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
Stages
Amps
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18
25.5
9
18
24
34
9
18
24
34
9
18
24
34
6.8
13.5
18
25.5
9
18
24
34
9
18
24
34
9
18
24
34
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
39.6
63.2
86.4
102.0
128.1
39.6
66.6
93.7
111.7
141.8
18.2
31.7
45.3
54.3
69.3
14.6
25.5
36.3
43.5
55.5
44.3
67.9
91.1
106.8
132.8
44.3
71.4
98.4
116.5
146.5
20.2
33.8
47.3
56.3
71.3
15.8
26.6
37.4
44.6
56.6
48.8
72.4
95.6
111.2
137.3
48.8
75.8
102.9
120.9
151.0
25.3
38.8
52.3
61.4
76.4
19.9
30.7
41.5
48.7
60.8
45.1
68.7
91.9
107.5
133.6
45.1
72.1
99.2
117.2
147.3
20.4
33.9
47.5
56.5
71.5
16.4
27.3
38.1
45.3
57.3
49.8
73.4
96.6
112.3
138.3
49.8
76.9
103.9
122.0
152.0
22.4
36.0
49.5
58.5
73.5
17.6
28.4
39.2
46.4
58.4
54.3
77.9
101.1
116.7
142.8
54.3
81.3
108.4
126.4
156.5
27.5
41.0
54.5
63.6
78.6
21.7
32.5
43.3
50.5
62.6
1
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
50
50
70
70
90
100
110
110
150
150
50
50
70
80
100
100
125
125
150
150
20
25
35
35
50
50
60
60
70
80
15
20
30
30
40
40
45
50
60
60
50
60
70
80
100
100
110
125
150
150
50
60
80
80
100
110
125
125
150
175
25
25
35
40
50
50
60
60
80
80
20
20
30
30
40
40
45
50
60
60
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
110
125
150
175
175
30
35
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
35
528195-YTG-H-0213
XP078-150 Standard Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
1.5
8.2
5.5
0.0
230
16.0 110.0 24.9
1.5
8.2
5.5
0.0
460
7.8
52.0
12.1
0.8
4.1
2.2
0.0
575
5.7
38.9
8.9
0.6
3.6
1.8
0.0
208
23.1
160
36.0
1.5
10.9
5.5
0.0
230
23.1
160
36.0
1.5
10.9
5.5
0.0
460
12.2
87
19.0
0.8
5.3
2.2
0.0
575
8.7
62
13.5
0.6
4.1
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
47.2
94.0
109.7
135.7
151.1
47.2
101.3
119.4
149.4
149.4
23.3
50.3
59.3
74.4
74.4
17.6
39.3
46.5
58.5
58.5
68.9
115.7
131.3
157.4
157.4
68.9
123.0
141.0
171.1
171.1
36.0
63.0
72.0
87.1
87.1
26.1
47.7
54.9
67.0
67.0
52.7
99.5
115.2
141.2
158.0
52.7
106.8
124.9
154.9
154.9
25.5
52.5
61.5
76.6
76.6
19.4
41.1
48.3
60.3
60.3
74.4
121.2
136.8
162.9
162.9
74.4
128.5
146.5
176.6
176.6
38.2
65.2
74.2
89.3
89.3
27.9
49.5
56.7
68.8
68.8
1
Model
kW
Stages
Amps
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18
25.5
40.6
18
24
34
54
18
24
34
54
18
24
34
54
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
1
Max Fuse2/ Max Fuse3 /
Breaker3 Breaker
Size w/
Size
Pwr Exh
(Amps)
(Amps)
60
60
100
100
110
125
150
150
175
175
60
60
110
110
125
125
150
175
150
175
30
30
60
60
60
70
80
80
80
80
20
25
40
45
50
50
60
70
60
70
90
90
125
125
150
150
175
175
175
175
90
90
125
150
150
150
175
200
175
200
45
50
70
70
80
80
90
90
90
90
30
35
50
50
60
60
70
70
70
70
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
36
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078-150 Hi Static Motor - Without Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
15.1
1.5
8.2
5.5
0.0
230
13.5
88.0
15.1
1.5
8.2
5.5
0.0
460
6.0
44.0
9.3
0.8
4.1
2.2
0.0
575
4.9
34.0
7.7
0.6
3.6
1.8
0.0
208
15.6
83.1
21.4
1.5
10.9
5.5
0.0
230
15.6
83.1
21.4
1.5
10.9
5.5
0.0
460
6.9
41
9.7
0.8
5.3
2.2
0.0
575
5.4
33
7.5
0.6
4.1
1.8
0.0
208
16.7
120
26.0
1.5
10.9
5.5
0.0
230
16.7
120
26.0
1.5
10.9
5.5
0.0
460
8.7
60
13.5
0.8
5.3
2.2
0.0
575
6.7
42
10.5
0.6
4.1
1.8
0.0
078
(6.5)
090
(7.5)
102
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18
25.5
9
18
24
34
9
18
24
34
9
18
24
34
6.8
13.5
18
25.5
9
18
24
34
9
18
24
34
9
18
24
34
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
41.6
65.2
88.4
104.0
130.1
41.6
68.6
95.7
113.7
143.8
19.2
32.7
46.3
55.3
70.3
15.8
26.7
37.5
44.7
56.7
49.0
72.6
95.8
111.5
137.5
49.0
76.1
103.1
121.2
151.2
22.4
36.0
49.5
58.5
73.5
17.5
28.3
39.1
46.3
58.3
51.5
75.1
98.3
113.9
140.0
51.5
78.5
105.6
123.6
153.7
26.5
40.0
53.5
62.6
77.6
20.4
31.2
42.0
49.2
61.3
47.1
70.7
93.9
109.5
135.6
47.1
74.1
101.2
119.2
149.3
21.4
34.9
48.5
57.5
72.5
17.6
28.5
39.3
46.5
58.5
54.5
78.1
101.3
117.0
143.0
54.5
81.6
108.6
126.7
156.7
24.6
38.2
51.7
60.7
75.7
19.3
30.1
40.9
48.1
60.1
57.0
80.6
103.8
119.4
145.5
57.0
84.0
111.1
129.1
159.2
28.7
42.2
55.7
64.8
79.8
22.2
33.0
43.8
51.0
63.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
50
60
70
80
90
100
110
110
150
150
50
60
70
80
100
110
125
125
150
150
25
25
35
35
50
50
60
60
80
80
20
20
30
30
40
40
45
50
60
60
60
70
80
80
100
110
125
125
150
150
60
70
80
90
110
110
125
150
175
175
25
30
40
40
50
60
60
70
80
80
20
20
30
35
40
45
50
50
60
70
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
35
35
45
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
37
528195-YTG-H-0213
XP078-150 Hi Static Motor - Without Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
1.5
10.9
5.5
0.0
230
16.0 110.0 24.9
1.5
10.9
5.5
0.0
460
7.8
52.0
12.1
0.8
5.3
2.2
0.0
575
5.7
38.9
8.9
0.6
4.1
1.8
0.0
208
23.1
160
36.0
1.5
16.1
5.5
0.0
230
23.1
160
36.0
1.5
16.1
5.5
0.0
460
12.2
87
19.0
0.8
8.1
2.2
0.0
575
8.7
62
13.5
0.6
6.0
1.8
0.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
13.5
18
25.5
40.6
18
24
34
54
18
24
34
54
18
24
34
54
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
49.9
96.7
112.4
138.4
154.5
49.9
104.0
122.1
152.1
152.1
24.5
51.5
60.5
75.6
75.6
18.1
39.8
47.0
59.0
59.0
74.1
120.9
136.5
162.6
162.6
74.1
128.2
146.2
176.3
176.3
38.8
65.8
74.8
89.9
89.9
28.0
49.6
56.8
68.9
68.9
55.4
102.2
117.9
143.9
161.4
55.4
109.5
127.6
157.6
157.6
26.7
53.7
62.7
77.8
77.8
19.9
41.6
48.8
60.8
60.8
79.6
126.4
142.0
168.1
168.1
79.6
133.7
151.7
181.8
181.8
41.0
68.0
77.0
92.1
92.1
29.8
51.4
58.6
70.7
70.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
100
110
125
125
150
150
175
175
60
70
110
110
125
150
175
175
175
175
30
30
60
60
70
70
80
80
80
80
20
25
40
45
50
50
60
70
60
70
90
100
125
150
150
150
175
175
175
175
90
100
150
150
150
175
200
200
200
200
50
50
70
70
80
80
90
100
90
100
35
35
50
60
60
60
70
80
70
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
38
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078-150 Standard Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
15.1
1.5
6.2
5.5
10.0
230
13.5
88.0
15.1
1.5
6.2
5.5
10.0
460
6.0
44.0
9.3
0.8
3.1
2.2
5.0
575
4.9
34.0
7.7
0.6
2.4
1.8
4.0
208
15.6
83.1
21.4
1.5
6.2
5.5
10.0
230
15.6
83.1
21.4
1.5
6.2
5.5
10.0
460
6.9
41
9.7
0.8
3.1
2.2
5.0
575
5.4
33
7.5
0.6
2.4
1.8
4.0
208
16.7
120
26.0
1.5
8.2
5.5
10.0
230
16.7
120
26.0
1.5
8.2
5.5
10.0
460
8.7
60
13.5
0.8
4.1
2.2
5.0
575
6.7
42
10.5
0.6
3.6
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
6.8
13.5
18
25.5
9
18
24
34
9
18
24
34
9
18
24
34
–
6.8
13.5
18
25.5
–
9
18
24
34
–
9
18
24
34
–
9
18
24
34
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
49.6
73.2
96.4
112.0
138.1
49.6
76.6
103.7
121.7
151.8
23.2
36.7
50.3
59.3
74.3
18.6
29.5
40.3
47.5
59.5
54.3
77.9
101.1
116.8
142.8
54.3
81.4
108.4
126.5
156.5
25.2
38.8
52.3
61.3
76.3
19.8
30.6
41.4
48.6
60.6
58.8
82.4
105.6
121.2
147.3
58.8
85.8
112.9
130.9
161.0
30.3
43.8
57.3
66.4
81.4
23.9
34.7
45.5
52.7
64.8
55.1
78.7
101.9
117.5
143.6
55.1
82.1
109.2
127.2
157.3
25.4
38.9
52.5
61.5
76.5
20.4
31.3
42.1
49.3
61.3
59.8
83.4
106.6
122.3
148.3
59.8
86.9
113.9
132.0
162.0
27.4
41.0
54.5
63.5
78.5
21.6
32.4
43.2
50.4
62.4
64.3
87.9
111.1
126.7
152.8
64.3
91.3
118.4
136.4
166.5
32.5
46.0
59.5
68.6
83.6
25.7
36.5
47.3
54.5
66.6
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
60
80
80
100
110
125
125
150
150
60
60
80
90
110
110
125
150
175
175
25
30
40
40
60
60
60
70
80
80
20
25
30
35
45
45
50
50
60
70
60
70
80
90
110
110
125
125
150
150
60
70
90
90
110
125
150
150
175
175
30
30
40
45
60
60
70
70
80
80
25
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
35
40
45
50
60
60
70
70
90
90
30
30
35
40
50
50
60
60
70
70
39
528195-YTG-H-0213
XP078-150 Standard Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
1.5
8.2
5.5
10.0
230
16.0 110.0 24.9
1.5
8.2
5.5
10.0
460
7.8
52.0
12.1
0.8
4.1
2.2
5.0
575
5.7
38.9
8.9
0.6
3.6
1.8
4.0
208
23.1
160
36.0
1.5
10.9
5.5
10.0
230
23.1
160
36.0
1.5
10.9
5.5
10.0
460
12.2
87
19.0
0.8
5.3
2.2
5.0
575
8.7
62
13.5
0.6
4.1
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
–
13.5
18
25.5
40.6
–
18
24
34
54
–
18
24
34
54
–
18
24
34
54
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
57.2
104.0
119.7
145.7
163.6
57.2
111.3
129.4
159.4
159.4
28.3
55.3
64.3
79.4
79.4
21.6
43.3
50.5
62.5
62.5
78.9
125.7
141.3
167.4
167.4
78.9
133.0
151.0
181.1
181.1
41.0
68.0
77.0
92.1
92.1
30.1
51.7
58.9
71.0
71.0
62.7
109.5
125.2
151.2
170.5
62.7
116.8
134.9
164.9
164.9
30.5
57.5
66.5
81.6
81.6
23.4
45.1
52.3
64.3
64.3
84.4
131.2
146.8
172.9
173.9
84.4
138.5
156.5
186.6
186.6
43.2
70.2
79.2
94.3
94.3
31.9
53.5
60.7
72.8
72.8
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
70
110
110
125
150
150
175
175
175
70
70
125
125
150
150
175
175
175
175
35
35
60
60
70
70
80
90
80
90
25
25
45
50
60
60
70
70
70
70
100
100
150
150
150
150
175
175
175
175
100
100
150
150
175
175
200
200
200
200
50
50
70
80
80
80
100
100
100
100
35
40
60
60
60
70
80
80
80
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
40
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078-150 Hi Static Motor - With Powered Convenience Outlet
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
13.5
88.0
15.1
1.5
8.2
5.5
10.0
230
13.5
88.0
15.1
1.5
8.2
5.5
10.0
460
6.0
44.0
9.3
0.8
4.1
2.2
5.0
575
4.9
34.0
7.7
0.6
3.6
1.8
4.0
208
15.6
83.1
21.4
1.5
10.9
5.5
10.0
230
15.6
83.1
21.4
1.5
10.9
5.5
10.0
460
6.9
41
9.7
0.8
5.3
2.2
5.0
575
5.4
33
7.5
0.6
4.1
1.8
4.0
208
16.7
120
26.0
1.5
10.9
5.5
10.0
230
16.7
120
26.0
1.5
10.9
5.5
10.0
460
8.7
60
13.5
0.8
5.3
2.2
5.0
575
6.7
42
10.5
0.6
4.1
1.8
4.0
078
(6.5)
090
(7.5)
102
(8.5)
Johnson Controls Unitary Products
Electric Heat Option
Model
kW
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
None
E09
E18
E24
E36
6.8
13.5
18.0
25.5
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
9.0
18.0
24.0
34.0
–
6.8
13.5
18
25.5
–
9
18
24
34
–
9
18
24
34
–
9
18
24
34
–
6.8
13.5
18
25.5
–
9
18
24
34
–
9
18
24
34
–
9
18
24
34
MCA1
(Amps)
MCA1
w/Pwr
Exh
(Amps)
51.6
75.2
98.4
114.0
140.1
51.6
78.6
105.7
123.7
153.8
24.2
37.7
51.3
60.3
75.3
19.8
30.7
41.5
48.7
60.7
59.0
82.6
105.8
121.5
147.5
59.0
86.1
113.1
131.2
161.2
27.4
41.0
54.5
63.5
78.5
21.5
32.3
43.1
50.3
62.3
61.5
85.1
108.3
123.9
150.0
61.5
88.5
115.6
133.6
163.7
31.5
45.0
58.5
67.6
82.6
24.4
35.2
46.0
53.2
65.3
57.1
80.7
103.9
119.5
145.6
57.1
84.1
111.2
129.2
159.3
26.4
39.9
53.5
62.5
77.5
21.6
32.5
43.3
50.5
62.5
64.5
88.1
111.3
127.0
153.0
64.5
91.6
118.6
136.7
166.7
29.6
43.2
56.7
65.7
80.7
23.3
34.1
44.9
52.1
64.1
67.0
90.6
113.8
129.4
155.5
67.0
94.0
121.1
139.1
169.2
33.7
47.2
60.7
69.8
84.8
26.2
37.0
47.8
55.0
67.1
Stages Amps
1
2
2
2
1
2
2
2
1
2
2
2
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
–
1
2
2
2
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
18.9
37.5
50.0
70.8
21.7
43.3
57.7
81.8
10.8
21.7
28.9
40.9
8.7
17.3
23.1
32.7
2
Max Fuse2/ Max Fuse3 /
Breaker
Breaker3
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
60
70
80
90
100
110
125
125
150
150
60
70
80
90
110
125
125
150
175
175
30
30
40
40
60
60
70
70
80
80
20
25
35
35
45
45
50
60
70
70
70
80
90
90
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
30
35
45
45
60
60
70
70
80
90
25
25
35
35
45
45
60
60
70
70
70
80
90
100
110
125
125
150
150
175
70
80
90
100
125
125
150
150
175
175
40
40
50
50
60
70
70
70
90
90
30
30
40
40
50
50
60
60
70
70
41
528195-YTG-H-0213
XP078-150 Hi Static Motor - With Powered Convenience Outlet (Continued)
Size
(Tons)
Volt
Compressors
(each)
RLA LRA
MCC
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Exh
Motor
Pwr
Conv
Outlet
FLA
FLA
FLA
FLA
208
16.0 110.0 24.9
1.5
10.9
5.5
10.0
230
16.0 110.0 24.9
1.5
10.9
5.5
10.0
460
7.8
52.0
12.1
0.8
5.3
2.2
5.0
575
5.7
38.9
8.9
0.6
4.1
1.8
4.0
208
23.1
160
36.0
1.5
16.1
5.5
10.0
230
23.1
160
36.0
1.5
16.1
5.5
10.0
460
12.2
87
19.0
0.8
8.1
2.2
5.0
575
8.7
62
13.5
0.6
6.0
1.8
4.0
120
(10)
150
(12.5)
Electric Heat Option
Model
kW
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
None
E18
E24
E36
E54
13.5
18.0
25.5
40.6
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
18.0
24.0
34.0
54.0
–
13.5
18
25.5
40.6
–
18
24
34
54
–
18
24
34
54
–
18
24
34
54
MCA
(Amps)
MCA1
w/Pwr
Exh
(Amps)
59.9
106.7
122.4
148.4
167.0
59.9
114.0
132.1
162.1
162.1
29.5
56.5
65.5
80.6
80.6
22.1
43.8
51.0
63.0
63.0
84.1
130.9
146.5
172.6
173.5
84.1
138.2
156.2
186.3
186.3
43.8
70.8
79.8
94.9
94.9
32.0
53.6
60.8
72.9
72.9
65.4
112.2
127.9
153.9
173.9
65.4
119.5
137.6
167.6
167.6
31.7
58.7
67.7
82.8
82.8
23.9
45.6
52.8
64.8
64.8
89.6
136.4
152.0
178.1
180.4
89.6
143.7
161.7
191.8
191.8
46.0
73.0
82.0
97.1
97.1
33.8
55.4
62.6
74.7
74.7
1
Stages Amps
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
–
2
2
2
2
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
37.5
50.0
70.8
112.7
43.3
57.7
81.8
129.9
21.7
28.9
40.9
65.0
17.3
23.1
32.7
52.0
2
Max Fuse2/ Max Fuse3 /
Breaker
3
Breaker
Size w/ Pwr
Size
Exh
(Amps)
(Amps)
70
80
110
125
125
150
150
175
175
175
70
80
125
125
150
150
175
175
175
175
35
35
60
60
70
70
90
90
90
90
25
25
45
50
60
60
70
70
70
70
100
110
150
150
150
175
175
200
175
200
100
110
150
150
175
175
200
200
200
200
50
50
80
80
80
90
100
100
100
100
40
40
60
60
70
70
80
80
80
80
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
42
Johnson Controls Unitary Products
528195-YTG-H-0213
Typical Wiring Diagrams
XP078-150 Typical Wiring Diagrams
Typical XP078-120 Heat Pump with/without Electric Heat Wiring Diagram
Johnson Controls Unitary Products
43
528195-YTG-H-0213
Typical XP150 Heat Pump with/without Electric Heat Wiring Diagram
44
Johnson Controls Unitary Products
528195-YTG-H-0213
Weights and Dimensions
XP078-150 Unit Weights
Unit 4 Point Load Weight
Unit 6 Point Load Weight
FRONT
FRONT
LEFT
LEFT
B
C
B
A
A
D
C
E
F
D
Y
X
FRONT
LEFT
Size
Weight (lbs.)
Center of Gravity
Model
Shipping Operating
X
Y
(Tons)
078
XP
1085
1080
38
25
(6.5)
090
XP
925
920
38
23
(7.5)
102
XP
1140
1135
38
25.5
(8.5)
120
XP
1140
1135
38
25.5
(10)
150
XP
1405
1400
51
25.5
(12.5)
4 Point Load Location (lbs.)
A
B
C
D
A
6 Point Load Location (lbs.)
B
C
D
E
F
262
195
266
357
184
150
124
169
204
250
206
153
240
322
144
117
97
152
184
225
281
209
275
369
197
160
133
175
211
259
281
209
275
369
197
160
133
175
211
259
258
347
456
339
164
198
243
319
260
216
XP078-150 Unit Accessory Weights
Unit Accessory
Economizer
Power Exhaust
Electric Heat1
Weight (lbs.)
Shipping
Operating
90
85
40
35
49
49
1. Weight given is for the maximum heater size available
(54KW).
Johnson Controls Unitary Products
45
528195-YTG-H-0213
XP078-150 Unit Dimensions
XP078-120
See detail A for drain location
XP150
See detail A for drain location
46
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078-150 Unit Physical Dimensions
Unit Model Number
078
090
102
120
150
A
50 3/4
42
50 3/4
50 3/4
50 3/4
B
89
89
89
89
119 1/2
Dimension (in.)
C
D
30 3/16
24 3/16
22 1/8
18 3/16
30 3/16
24 3/16
30 3/16
24 3/16
30 3/16
24 3/16
E
17 3/16
15 3/16
17 3/16
17 3/16
17 3/16
F
6 3/16
6 3/16
6 3/16
6 3/16
6 3/16
Detail A
5-3/8
3/4” FPT
XP078-150 Unit Clearances
Direction
Top1
Front
Rear
Distance (in.)
72
36
36
Direction
Right
Left
Bottom2
Distance (in.)
12
36
0
1. Units must be installed outdoors. Over hanging structure or shrubs should not obscure condenser air discharge outlet.
2. Units may be installed on combustible floors made from wood or class A, B or C roof covering materials.
XP078-150 Unit Bottom Duct Openings
Johnson Controls Unitary Products
47
528195-YTG-H-0213
XP078-150 Unit Electrical Entry
Disconnect Swith Cover
Power Entry Ø 2-1/2
Control Entry Ø 7/8
Power Entry Ø 2-1/2
Convenience Outlet Cover
Convenience Outlet
Power Entry Ø 7/8
FRONT
XP078-120 Unit Side Duct Openings
18-1/4
Dot Plugs
A
Return
Air
Supply
Air
D
B
2-31/32
5-5/32
C
31-11/16
48
Johnson Controls Unitary Products
528195-YTG-H-0213
XP150 Unit Side Duct Openings
Dot Plugs
18-1/4
A
D
B
5-5/32
2-7/8
C
31-5/8
Side Duct Dimensions
Unit Model Number
078
090
102
120
150
A
28 1/4
27 3/4
28 1/4
28 1/4
28 1/4
Dimension (in.)
B
C
18 1/16
28 1/4
12 1/16
27 1/2
18 1/16
28 1/4
18 1/16
28 1/4
18 1/16
28 1/4
D
18 1/4
16
18 1/4
18 1/4
18 1/4
XP078-150 Unit Left Duct Opening
30-3/8
4-5/16
Johnson Controls Unitary Products
49
528195-YTG-H-0213
XP078-150 Unit Accessory Dimensions
XP078-150 Roof Curb
RIGHT
80-5/8
INSULATED DECK UNDER
CONDENSER SECTION
20
SUPPLY
20
6
RETURN
2 TYP.
30
INSULATED DECK UNDER
COMPRESSOR SECTION
50-1/2
FRONT
8 or 14
XP078-150 Transition Roof Curb
2 TYP
50-1/2
30-1/2
23 4
80-5/8
26
RETURN
SUPPLY
10
76-5/8
94
FRONT
50
59-1/4
64-1/4
RIGHT
Johnson Controls Unitary Products
528195-YTG-H-0213
XP078-150 Economizer Assembly
58 1/4
88 1/4
39 1/2
or
47 1/2
Outside Air
Intake Hood
35 3/4
Relief Hood for
Power Exhaust or
Barometric Relief
26
Johnson Controls Unitary Products
25 3/4
26
30 1/4
51
528195-YTG-H-0213
Economizer Options
Economizer Usage
Application
Cabinet Height
Description
Model
Bottom Return
All
Downflow economizer with barometric relief
2EE04705924
Side Return
All
Horizontal economizer without barometric relief
2EE047060241
42"
Slab Economizer, 42” tall cabinet
2EE047058242
50"
Slab Economizer, 50” tall cabinet
2EE047057242
ERV or End Return
1. Barometric relief must be ordered separately and installed in duct work.
2. Barometric relief or fresh air hood not included. Must be ordered separately.
Factory Installed Downflow Economizer
2EE04705924
Fresh Air Hood
2EE04705924
2EE04705924
2EE04705924
Fresh Air Damper Return Air Damper
Barometric Relief Damper
2EE04705924
Barometric Relief Hood
Field Installed Downflow Economizer W/Power Exhaust
2EE04705924
Fresh Air Hood
52
2EE04705924
2EE04705924
Fresh Air Damper Return Air Damper
2PE047032XX
Power Exhaust
2EE04705924
Barometric Relief Damper
2EE04705924
Barometric Relief Hood
Johnson Controls Unitary Products
528195-YTG-H-0213
Field Installed Horizontal Economizer W/Power Exhaust
2EE04706024
Return Air Damper
Field Installed
Duct Work
2EE04706024
Fresh Air Damper
2PE047032XX
Power Exhaust
1EH0408
Barometric
Relief Damper
1EH0408
Barometric
Relief Hood
2EE04706024
Fresh Air Hood
Slab Economizer Downflow W/Power Exhaust
1EH0409
Fresh Air Hood
2EE04705X24
Slab Economizer
2PE047032XX
Power Exhaust
1EH0409 Barometric
Relief Damper
Johnson Controls Unitary Products
1EH0409 Barometric
Relief Hood
53
Slab Economizer End Return W/Power Exhaust
1EH0409
Fresh Air Hood
Field Installed
Duct Work
2EE04705X24
Slab Economizer
1EH0409
Barometric Relief Hood
1EH0409
Barometric Relief Damper
Subject to change without notice. Printed in U.S.A.
Copyright © 2013 by Johnson Controls, Inc. All rights reserved.
Johnson Controls Unitary Products
5005 York Drive
Norman, OK 73069
2PE047032XX
Power Exhaust
528195-YTG-H-0213
Supersedes: 528195-YTG-G-1012