DTZ1513 Three Phase Keypad Prepayment Energy Meter

DTZ1513 Three Phase Keypad Prepayment Energy Meter
DTZ1513 Three Phase Keypad Prepayment Energy
Meter with Plug-in Communication Module
Operation Manual
Shenzhen Inhemeter Co., Ltd
www.inhemeter.com
1 Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Content
1 INHE Keypad Prepayment Energy Meter Series ................................................................................5 2 Introduction ...............................................................................................................................................7 3 MCU Technical Parameter ....................................................................................................................16 3.1 Meter Outline Diagram (unit: mm) ............................................................................................20 3.2 Installation Diagram ....................................................................................................................21 3.4 Wiring Diagram ...........................................................................................................................22 3.5 Active/Reactive Measurement ..................................................................................................23 3.6 Meter Characteristics(direct connected) ................................................................................. 27 3.6.1 Active (reactive) Impulse Indicator (red LED)-marking 13, 14 ..................................29 3.6.2 Alarm Indicator(yellow LED)-Marking 12......................................................................29 3.6.3 Balance Credit Indicator(double color LED)-Marking 11 ...........................................29 3.6.4 Optical(infrared) Port-Marking 1 ....................................................................................30 4 LCD ..........................................................................................................................................................30 4.1 Auto-scrolling Display Mode ......................................................................................................32 4.2 Manual Scrolling Display Mode ................................................................................................33 4.3 Short Code Inquiry Display Mode ............................................................................................34 4.4 Keypad Operation Instructions .................................................................................................55 4.4.1 TOKEN Inputting..............................................................................................................55 4.4.2 Assignment Encryption Key Input Operation ..............................................................58 4.4.3 Technical Token ..............................................................................................................58 4.4.4 Special TOKEN ................................................................................................................59 4.4.5 Test TOKEN (non-specific meter TOKEN) ...................................................................60 4.4.6 Extended Function TOKEN ............................................................................................60 5 Measurement Function .........................................................................................................................60 5.1 Active/ Reactive/ Apparent Energy Measurement .................................................................60 5.2 Calculation of Active MD (Maximum demand) .......................................................................61 5.3 Electric Parameter Measurement .............................................................................................61 5.4 TOU Multi-tariff Measurement Function .................................................................................. 62 5.4.1 Daily Tariff ......................................................................................................................... 62 5.4.2 Weekly Tariff .....................................................................................................................64 5.4.3 Seasonal Tariff .................................................................................................................65 5.4.4 Holiday Tariff .....................................................................................................................66 5.4.5 Tariff Rate Table ...............................................................................................................66 5.4.6 Confirmation Valid Daily Tariff ........................................................................................ 67 5.4.7 Tariff Table Switching ...................................................................................................... 67 5.5 Step Tariff Measurement Function ...........................................................................................68 5.6 Tariff Data Settings ..................................................................................................................... 70 6 Special Functions ................................................................................................................................... 70 6.1 Load Cut off Function ................................................................................................................. 70 6.2 Zero Credit Power Off ................................................................................................................ 70 Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 2
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
6.3 Load Control Function ............................................................................................................... 71 6.4 Protection against Abnormal Grid Voltage and Phase Missing ...........................................73 6.4.1 Automatic Power Off .......................................................................................................73 6.4.2 Recovery of Power Supply ............................................................................................. 74 6.5 Anti-tamper against Cover Opening Function ........................................................................ 74 6.6 Prewarning & Warning Function ...............................................................................................75 6.6.1 Prewarning Function .......................................................................................................75 6.6.2 Warning Function .............................................................................................................75 6.7 Anti-over Purchasing Function .................................................................................................. 76 6.8 Anti-tamper for Reverse Power Consumption ........................................................................ 76 6.9 Bypass Tampering Disconnection ............................................................................................ 76 6.10 Neutral Loss Disconnection Function ................................................................................... 77 6.11 Energy Meter Overdraft Function (Optional)........................................................................ 77 6.12 Minimum Guaranteed Load Control Function (Optional) ................................................... 77 6.13 Over Current Threshold Disconnection Function (Optional) .............................................. 78 6.14 Special Time Power Guarantee Function ............................................................................. 78 6.15 Post Payment /Prepayment Mode Shift Function ................................................................79 6.16 TOU Multi-tariff / Step Tariff Shift Function in Credit(money) Settlement Mode
(expandable) ......................................................................................................................................79 6.17 Monthly Basic Power Consumption Setting (expandable) .................................................80 6.18 Parameters and Status Flag Configuration ...........................................................................80 6.19 Negative Balance Amount Display .........................................................................................82 6.20 Available Balance Amount Step Diagram Indication ...........................................................82 6.21 Not Available to Program or Modify Meter Number(Serial Number) after Delivery from
Factory ................................................................................................................................................83 6.22 Load Profile Record .................................................................................................................83 6.23 Available Days Indication (Optional) ......................................................................................84 6.24 Meter Display and Token Entry Function without Power (Optional) ..................................84 6.25 Monthly Energy Consumption Billing Date ...........................................................................85 6.26 Over Temperature Disconnection Function (Optional) ........................................................85 6.27 Magnetic Interference Disconnection Function (Optional) .................................................85 6.28 Remote Upgrading ...................................................................................................................85 6.29 Meter Running Status Inquiry Function .................................................................................85 6.30 Date Display Mode Shift Function .......................................................................................... 87 6.31 Real Time Clock Daylight Saving Time and Winter Time Automatic Shift ........................ 87 7 Historical Data Transfer & Storage and Event Recording Function .............................................. 88 7.1 13 Months Monthly Energy Consumption Data Recording ................................................. 88 7.2 45 Days Daily Energy Consumption Data Recording .......................................................... 88 7.3 Meter Tripping Event Recording .............................................................................................. 88 7.4 Power Failure/Off Event Recording .........................................................................................89 7.5 Special Event Recording ...........................................................................................................89 7.6 Electricity Purchasing Information ............................................................................................91 7.7 Technical TOKEN Usage Information ......................................................................................93 8 Communication port...............................................................................................................................95 Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 3
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
8.1 Optical (infrared) communication port .....................................................................................95 8.2 RS-485 Communication Port .................................................................................................... 97 8.3 TG4A0-01 Three-phase Meter GPRS/GSM Communication Module ................................ 97 8.4 TPDH0-01 Three Phase Meter PLC Communication Module .............................................98 8.5 TRGB0-01 Three-phase Meter RF Low Power-consumption Communication Module ...98 8.6 TZ0A0-01 Three-phase Meter Zig-bee Communication Module .........................................98 9 Security Rule ..........................................................................................................................................98 10 Fault Diagnosis ....................................................................................................................................98 11 Installation and Operation Instructions .............................................................................................99 12 Transport and Storage Instructions ...................................................................................................99 13 Warranty ............................................................................................................................................. 100 14 Annex Instructions ............................................................................................................................ 100 15 Detailed Order Specification ............................................................................................................ 101 16 INHEMETER SMARTtvend Management System ................................................................... 101 17 Pre-stored Energy and Preset Load Threshold Instruction ........................................................ 105 17.1 Power Pre-stored and Load Presetting Stipulation .......................................................... 105 17.2 Dealings to Pre-stored Energy ............................................................................................ 105 17.3 Load Threshold Pre-setting ............................................................................................... 106 18 Keypad Meter Mass Production Key Setting ................................................................................ 106 18.1 Customized SGC Code Setting ........................................................................................... 106 18.2 Inhe Default Key(SGC:999937)Setting ....................................................................... 107 Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 4
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
1 INHE Keypad Prepayment Energy Meter Series
INHEMETER keypad prepayment energy meter series include single & three phase keypad
prepayment meters; integrated & split keypad prepayment meters; energy deduction&money
deduction mode meters, multi-tariff TOU metering mode meters, monthly step-tariff mode meters;
cable, PLC and RF communication mode meters and DLMS certified replaceable communication
module single/three phase keypad prepayment meters; ANSI standard compliance split keypad
prepayment meters, common base type single phase keypad prepayment meter complying with
ESKOM installation requirements; three phase keypad prepayment metering box and single
phase keypad prepayment meter complying with PLN D3 009:2010.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 5
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Diagram:
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 6
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
2 Introduction
DTZ1513 Three Phase Four Wire (direct connected) Keypad prepayment Energy Meter with
Replaceable Communication Module has acquired STS(Standard Transfer Specification) test
certificate, which can accept 20 digits STS code inputting. The communication regulations
comply with DLMS requirements and have had DLMS test certificate. The meter can realize multi
tariff TOU metering of active, reactive and apparent energy , and hold different communication
module. It can be configured to AMI/AMR system by adding relevant concentrator and centralized
meter reading software, and also switch between prepayment/post payment (bill revenue
collection mode) according to actual usage. Under prepayment mode, it can be energy or money
deduction mode, monthly step tariff mode or multi tariff TOU metering mode. It is a preference for
smart metering grid. It adopts international standard IEC62053, IEC62055 and IEC62056; its
design and production comply with ISO9001.
According to usage requirement and site condition, users could choose different communication
module and add relevant concentrator and centralized meter reading software for configuration of
AMI/AMR system to realize functions of centralized meter reading, remote recharge/disconnect
control and etc.
DTZ1513 three phase keypad prepayment energy meter with replaceable communication module
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 7
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
complies with DLMS requirements and gets DLMS test certificate, which is the basic requirement
for compatibility of smart meter and remote meter reading control system.
Split keypad prepayment meter is consisted of two parts:
A: MCU: Metering and Control Unit-- MCU can be installed outdoors, in centralized meter box or
on telegraph pole.
B: CIU: Customer Interface Unit -- CIU is installed indoors, for users to get meter operation
parameters and load pre-purchased energy (credit).
C: Optional communication mode between MCU and CIU: pair cable, PLC and RF.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 8
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
AMI/AMR system configuration
AMR/AMR system is configured with DTZ1513 three phase keypad prepayment energy meter
with replaceable communication module , relevant concentrator, SMART vending/AMM system.
System composition diagram is as below:
This system has the functions below:
„ Remote meter reading
„ Remote recharge
„ Remote control
„ Remote tariff setting/ load threshold setting
„ Line loss analysis
„ Remote meter software upgrade
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 9
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Products order model Instruction:
S/N
Product
type
MCU
1
2
DTZ1513-M
BS410K2A)
Instruction
Three phase four wire keypad prepayment energy meter
with replaceable communication module (direct connected)
MCU
Replaceable communication module (optional)
TG4A0-01
Three phase meter GPRS/GSM communication module
((Simcom- SIM900,quadband)
TPDH0-01
Three phase meter PLC communication module (HT8560
central frequency 125kHz; PLC frequency range:
125±2.8kHz; PLC speed 550bps DPSK)
2.3
TRGB0-01
Three phase meter RF wireless communication module
(APPCON APC320N; port speed default value: 9600bps;
frequency 470 ~ 510MHz; programmable transmission
power ; AMR module APC920)
2.4
TZ0A0-01
Three phase meter ZigBee communication module (EM250
communication speed: 250kps, modulation mode O-QPSK;
2.1
2.2
Order
model
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 10
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Concentrator module HD3501-SB/ZigBee chip EM357)
3
Optional CIU
3.1
DDZ1513-C
IU-PLC
PLC communication CIU and single/three phase keypad
prepayment energy meter MCU compose split type keypad
prepayment energy meter
3.2
DDZ1513-C
IU-RF
RF communication CIU and single/three phase keypad
prepayment energy meter MCU compose split type keypad
prepayment energy meter
3.3
DDZ1513-C
IU-CABLE
Pair cable communication CIU and single/three phase
keypad prepayment energy meter MCU compose split type
keypad prepayment energy meter
4
Low voltage side data concentrator option
4.1
DJGZ22-IN
HE20
Low voltage PLC concentrator, upper communication
GPRS/GSM, lower communication PLC
4.2
DJGJ22-IN
HE20
Low
voltage
RF
wireless
concentrator,
upper
communication GPRS/GSM, lower communication RF
4.3
DJGT22-IN
HE20
Low voltage ZigBee concentrator, upper communication
GPRS/GSM, lower communication ZigBee
Theoretically, a PLC concentrator can read or control 1024 pieces PLC meters under the same low
voltage transformer. In real situation, only 100-600 pieces meters are installed under a low voltage
transformer. PLC meters produced by INHEMETER have relay function so the PLC
communication distance between meter and concentrator can reach 1,000m. The repeater
installed in special region can improve efficiency of meter reading. Please refer to “Low Voltage
PLC Concentrator Operation Manual” for details.
Meter circuit design, structure design and selection of components and materials are according to
the greater environment tolerance to guarantee the lasting and stable operation of meter. Metering
components take shielding and protection measures in structure design to resist interference of
external DC and AC magnetic field, over-voltage and high frequency electromagnetism field.
Energy meter is with good electromagnetism compatibility. These designs guarantee metering
reliability and stability. Therefore, no more calibration is needed in its life cycle.
Meter cover is made of fire retardant, flame resistant and heat deformation resistant polycarbonate
material. It can be recycled after the end of its life cycle to protect the environment. MCU cover is
double insulated and in compliance with dust and water protection standard IP54 (IEC60529).
MCU terminal is made of brass, and plated with nickel,the same as that for energy meter in
tropical areas. MCU has terminal cover and fastened by a sealing screw.
Keypad Prepayment Meter has two settlement modes: energy deduction mode and money
deduction mode
Energy Deduction Mode:
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 11
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
The meter will realize the prepayment control function through the actual energy recharged every
time.
Money Deduction Mode:
The Keypad Prepayment Meter can store the preset tariff (TOU tariff or step tariff). For every
purchase, the vending system will generate a TOKEN, according to the after-tax amount paid by
the user. Then the user input the TOKEN into the meter. The remaining credit will be displayed in
money. The amount will be deducted after 0.01 kWh is consumed, as per the preset tariff rate.
For meter without overdraft function, when the remaining amount becomes zero, the power
supply will be cut automatically.
Money settlement----TOU tariff application instruction:
The vending system will generate a TOKEN as per the after-tax amount paid by the user. Then
the user input the TOKEN into the Keypad Prepayment Meter. The amount will be deducted
according to the actual monthly consumed energy and agreed TOU tariff which is set by
communication port. When the remaining money becomes zero, the power supply will be cut
automatically. 4 tariff rates and 12 time shifts can be pre-programmed each day. Electricity price
will be adjusted according to time period to encourage electricity usage at offpeak period and
save at peak period.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 12
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Tariff Rate Structure:
Serial
No.
Tariff Rate
Tariff Code
Comments
1
P0
T1(TOU1)
Sharp Energy
Time Period
2
P1
T2(TOU2)
Peak Energy Consumption Time
Period
3
P2
T3(TOU3)
Off-peak Energy Consumption
Time Period
4
P3
T4(TOU4)
Valley Energy Consumption Time
Period
Consumption
Notes: P0, P1, P2, P3---Tariff Rate (unit: $); minimum unit: 0.0001
T1, T2, T3, T4---Tariff Code
Period Division:
Serial
No.
Period Starting Time
(HH:MM)
Tariff Rate / Tariff Code Option
TOU1
TOU2
TOU3
TOU1
1
2
3
4
5
6
7
8
9
10
11
12
Period Setting Example:
Serial
No.
Period Starting Time (HH:MM)
1
06:00
2
18:00
3
23:00
Tariff Rate / Tariff Code Option
TOU1
TOU2
TOU3
TOU4
√
√
√
Money Settlement----Step tariff application instruction:
The vending system will generate a TOKEN as per the after-tax amount paid by the user. Then
the user input the TOKEN code into the Keypad Prepayment Meter. The amount will be deducted
according to the monthly consumed energy and preset step tariff. When the remaining amount
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 13
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
becomes zero, the power supply will be cut automatically. Seven step tariff rates can be
programmed in one month. The energy can be saved through this rate change according to the
consumption.
Electricity Saving Policies
Electricity Price
Energy Consumption Monthly
Note 1:Basic Monthly Consumption can also be preset. Once set, the fixed consumption will be
deducted from the remaining amount from 00:00 of the first day of each month.
Note 2:Basic Consumption /kWh can also be preset.Once set, the fixed consumption will be
deducted from the remaining amount after one kWh is consumed.
S/N
1
2
Monthly Electricity
Consumption
Division
Step-Tariff Rate
Tariff Code
0 < Y ≤ E1
P0
T1
Y*P0
P1
T2
E1*P0+(Y-E1)*P1
E1 < Y ≤ E2
Billing Mode
3
E2 < Y ≤ E3
P2
T3
E1*P1+(E2-E1)*P1+(Y-E2)*P
2
4
E3 < Y ≤ E4
P3
T4
………
5
E4 < Y ≤ E5
P4
T5
………
6
E5 < Y ≤ E6
P5
T6
………
P6
T7
………
7
Note:
Y > E6
Y---Monthly Consumed Energy (unit: kWh)
E1, E2, E3, E4, E5, E6--- Monthly Electricity Consumption Division (unit: kWh)
P0, P1, P2, P3, P4, P5, P6--- Step Tariff Rate (unit: $): minimum unit: 0.0001
T1, T2, T3, T4, T5, T6, T7, T8---Tariff Code
Tariff Setting
Keypad prepayment energy meter sets or adjusts tariff through communication ports. In other
words, tariffs are set through AMI/AMR system or local communication port (optical
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 14
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
communication port, RS-485 communication port). Tariff setting has requirements on security
and must be set or adjusted by special module and controlled by TOKEN instead of pressing
buttons.
Tariff setting comes with tariff version no. and tariff activation date/time.
Energy meter can store two sets of tariff: one is in use now, which has been preset and activated
in the meter and its date of activation is prior to current date/time; another set of tariff will be
activated in due date/time and replace the current running tariff settings. When finish replacing
the tariff, energy meter will automatically delete the invalid tariff settings and get ready for next
standby tariff settings.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 15
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
3 MCU Technical Parameter
DTZ1513 Three phase keypad prepayment energy meters with plug-in communication module is
used to measure three phase four wire direct connected AC energy in the system of 50/60Hz
Item
specification
note
Technical Standard
IEC 62052-11 2003
IEC 62053-21 2003
IEC 62053-23 2003
IEC 62055-31 2005
IEC 62055-41 2007
IEC 62055-51 2007
IEC62056-21(IEC61107)
SANS 1524-1 2005
ESKOM SCSSCAAA9
BS5685-1997/ DIN 43857
Meter Type
Three phase four wire direct connected keypad prepayment
meter
Plug-in communication module (GPRS/GSM, PLC)
Money deduction mode (multi-tariff; step tariff as standby)
Normal display: remaining credit
Active Energy Metering
Direction
Forward and reverse consumption will be added to total active
energy;
Reverse energy is detected and meter alarms and cut off
power.
Anti-tamper Mode
Three circuits measurement mode.
Meter will be regarded as by-passing tampering condition by
measuring each phase line current, phase position and neutral
line current. Meter will give the unbalance tampering alarm if
the by-passing current deviation is beyond the default value,
STS Manufacturer Code
37
STS Test Certificate No.
STS-192、STS-194
Rated operating voltage
(Un)
3X220/380V;
Working frequency
50Hz±5Hz ;
Active
Accuracy
Measuring
Class 1.0
Reactive
Accuracy
Measuring
Class 2.0
Basic Current(Ib)
10A
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 16
Three Phase Keypad Prepayment Energy Meter
Item
Maximum
Current
(Plug-in Module Type)
specification
Working
note
100A
Starting Current
≤20mA
Threshold
Current for
Accurate Metering
120A
Shor-time Over current
3000A
Power Consumption
Voltage circuit each phase::<1.5W (or <4VA )@220V
Current circuit each phase : < [email protected] Base Reference
Current (Ib)
1000 imp/kWh
1000imp/kVarh
Meter Constant
Output of meter pulse
LED, photoelectric isolation
Upper threshold: 264V
Lower threshold: 150V
Working Voltage
68%--120%Un(programmable)
Note: meters will trip against abnormal voltage (programmable).
Maximum
withstand
voltage (48 hours)
500V
3X240/415V system
line-to-line voltage
No damage on meter, accurate metering
and normal working can be assured after
recovering to normal working voltage.
Short-time
voltage (1min)
withstand
600V AC
No damage on meter, accurate metering and normal working
can be assured after recovering to normal working voltage.
Breaker Device
Current Specification
10(100)A
Tripolar bistable latching relay 120A
Standard class of load switch: UC3(IEC62055-31)
Connecting 3000A, withstanding short-circuit current 6000A
27600VAX3 Maximum switching power of disconnection:
27600VAX3
DTS1513(MBS410K2A)
MCU with LCD, keypad and replaceable communication
module
Display /notice interface
With large screen, wide angle (≥120º), anti-ultraviolet function,
wide temperature range of LCD display mode, Digital display is
8 bits, IEC62056 display code encoding, visualized prompt
symbol, remaining credit bar indication, alarm/tip LED
indication, LCD screen with backlight instruction, user-friendly.
LCD size: 60.0mm*31.0mm
LCD visible display size: 55.4mm*22.0mm
LCD digit size (height*width): 12.0mmX4.5mm
Two display modes: auto-scroll (defaulted), manual scroll.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 17
Three Phase Keypad Prepayment Energy Meter
Item
(Plug-in Module Type)
specification
note
Display content is programmable. Default regular display item
is balance energy.
RWP (reading without power) function.
Working Environment:
Working Temperature:
Storage Temperature:
Humidity Requirement:
At the maximum temperature of 55℃, the relative humidity
range is : 0~95%
During the night:
100 % relative humidity (Maximum)
During the day:
25 % relative humidity
Less than 3500 meters area
Altitude
-25℃~+75℃
-40℃~+80℃
Lighting Protection
Built-in varistor protection
Meters can be used where severe lighting storms prevail.
Communication Port
Infrared communication
RS-485 communication port
Communication protocol
IEC62056-21
Communication modules
Selection
Please refer to the introduction of communication modules
Mode C
TG4A0-01
GPRS/GSM communication module; (Simcom- SIM900,
quadruple frequency)
TPDH0-01
PLC communication module; (HT8560 center frequency
125kHz;carrier frequency range: 125±2.8kHz;carrier
rate:550bps DPSK)
TRGB0-01
RF communication module; (APPCON APC320N; default port
rate: 9600bps; frequency: 470~510MHz; emission power is
programmable; centralized meter reading module APC920)
TZ0A0-01
Zigbee communication module (EM250 communication rate:
250kps, modulation mode: O-QPSK; concentrator module
HD3501-SB/ZigBee chip EM357)
Real-time Clock
Real-time clock with crystal timing
Crystal oscillator frequency: 32.768 kHz
Clock accuracy (support clock temperature compensation) :
±5ppm
Within reference temperature (23℃) and working voltage
range: clock accuracy ≤0.5s/d
Within working temperature range (-25℃~+75℃) and under
AC power supply or backup power supply mode: clock
accuracy≤1.0s/d
Real-time clock backup
battery
Columnar battery: 3.6 V lithium-ion battery
capacity
≥1200mAh
During grid power failure, the battery can support clock working
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 18
Three Phase Keypad Prepayment Energy Meter
Item
(Plug-in Module Type)
specification
note
more than 10 years.
Insulation performance
Class Ⅱ insulation envelope protection instruments, protection
grade 2 , double insulation
Pulse voltage
AC withstand voltage
Current pulse
6KV
4KV
Service rating 5kA
8/20μs
Withstand rating 30 kA,
4/10μs
IEC60060
1.2/50μs
Electromagnetic
compatibility
Electrostatic discharge
RF
electromagnetic
interference
resistance
test
Fast transient pulse test
RF
field
induction
conduction disturb
test
Surge immunity test
Standard: IEC 61000-4-2
Contact discharge : 8 kV
Air discharge: 15kV
Meter
normally.
Standard: IEC 61000-4-3
With current status: 80MHz to 2GHz 10
V/m
No current status: 80MHz to 2GHz 30V/m
Standard: IEC61000-4-4 under
current work condition
For current and voltage circuit: 4KV
For auxiliary circuit> 40V: 2KV
Meter
error
meets
the
requirement.
Meter
works
normally.
basic
Standard:IEC61000-4-6
under
basic
current work condition
Voltage level: 10V 150kHz to 80MHz
Standard: IEC 61000-4-5
Test voltage levels:
For current and voltage circuit:
For auxiliary loop:
1KV
works
4KV
Meter
error
meets
the
requirement.
Meter
works
normally.
Meter
error
meets
the
requirement.
Meter
works
normally.
Meter
normally.
works
Structure requirement
Cover and terminal layout
Comply with BS5685/DIN 43857
Cover protection class
IP54
Housing Material
Fire retardant, flame resistant, thermal deformation engineering
IEC60529-4 standard
plastic PC+GF
Inflaming retardant test :
pass 960°C glow wire test
(IEC60695-2-1)
Fire resistant test:UL94-V0 rated @1.5mm. No toxic gases
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 19
Three Phase Keypad Prepayment Energy Meter
Item
(Plug-in Module Type)
specification
note
emitted: Green Material
Physical
(LXWXH)
Dimension
Extended cover
300.0mm X 170.0mm X 85.0mm
Weight
Terminals:
About 1200g
Terminals layout complies with BS5685/ DIN 43857
Main terminal is the pressure-plate type; two screws for a wire.
The material is rust-proof.
Hole diameter: 9mm; hole depth: 30mm: hole distance: 20mm
Maximum Cable Cross Section: 35 mm2
Terminal material
Fire retardant, flame resistant, thermal deformation engineering
plastic PC+20%GF
Inflaming retardant test :
pass 960°C glow wire test
(IEC60695-2-1)
Fire resistant test:UL94-V0 rated @1.5mm. No toxic gases
emitted: Green Material
1)Two manufacturer seals on the top meter cover;
Sealing
2)Two terminal cover seals;
3) One seal on communication module
3.1 Meter Outline Diagram (unit: mm)
A: Extended terminal cover
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 20
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
3.2 Installation Diagram
(unit: mm)
Extended terminal cover
Pothook has two holes and the distance of which
is 10mm. The distance is adjustable.
3.3 Wiring Terminals (unit: mm)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 21
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Characteristic: pressure plate wiring mode is suitable for wires of different materials and
diameters, and it will not harm the wires.
3.4 Wiring Diagram
L1
L2
L3
N
Phase connections
L1(IN)
L2(IN)
L3(IN)
N(IN)
L1(OUT)
L2(OUT)
L3(OUT)
N(OUT)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 22
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
3.5 Active/Reactive Measurement
Phasor diagram under correct wiring
● Active power of three phase four wire multi-tariff prepayment meter :
P =P1+P2+P3
=UAIA cosφA+ UBIBcosφB+ UCIC cosφC
●
Active energy metering
EP =∫Pdt
=∫(UAIA cosφA+ UBIB cosφB+ UCICcosφC)dt
● Reactive power of three phase four wire meter :
Q =Q1+Q2+Q3
=UaIa sinφa+ UbIbsinφb+ UcIc sinφc
● Reactive metering of three phase four wire meter :
EQ =∫Qdt
=∫(UaIa sinφa+ UbIbsinφb+ UcIc sinφc)dt
Four quadrants metering vector diagram for active, reactive and apparent power of DTZ1513
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 23
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
three phase four wire energy meter .
Four quadrant active, reactive and apparent direction
1 quadrant
2 quadrant
3 quadrant
4 quadrant
Active
Direction
Forward
Reverse
Reverse
Forward
Reactive
Direction
Forward/inducti
ve
Forward/capacitive
Reverse/inductive
Reverse/capacitiv
e
Apparent
Direction
Forward
Reverse
Reverse
Forward
Error threshold (percentage): active power (class 1)
Error threshold indicated by percentage
Load Value
Power Factor
IEC62053-21
standard
Standard of
INHEMETER
0.02Ib≤I< 0.05 Ib
1
±1.5
±1.0
0.05Ib≤I< 0.10 Ib
1
±1.5
±1.0
0.10Ib≤I<Imax
1
±1.0
±0.6
0.02Ib≤I< 0.1Ib
0.5 lag
0.8 lead
±1.5
±1.5
±1.0
±1.0
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 24
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
0.1Ib≤I< 0.2Ib
0.5 lag
0.8 lead
±1.5
±1.5
±1.0
±1.0
0.2Ib≤I≤Imax
0.5 lag
0.8 lead
±1.0
±1.0
±0.6
±0.6
Active error diagram: active power (class 1)
COSΦ=1
Range of active error
COSΦ=0.5
Error threshold (percentage):
Load Value
Range of active error
reactive power (class 2.0)
sinФ
(Inductive or
Capacitive)
Error threshold indicated by percentage
IEC62053-23
Standard
Standard of
INHEMETER
0.02In≤I< 0.05 In
1
±2.5
±1.0
0.05In ≤ I ≤Imax
1
±2.0
±0.8
0.05In≤I< 0.1In
0.5
±2.5
±1.0
0.1In ≤ I ≤I max
0.5
±2.0
±0.8
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 25
Three Phase Keypad Prepayment Energy Meter
0.1In ≤ I ≤I
0.25
±7.0
(Plug-in Module Type)
±2.0
Reactive error diagram
SINΦ=1
SINΦ=0.5
Range of reactive error
Range of reactive error
Influence of voltage variation on accuracy performance:
For DTZ1513 energy meter, the working voltage variation has little influences to the meter active,
reactive measurement accuracy.
(Note: Voltage rang: 0.7-1.2XUn)
DTZ1513
Voltage and Accuracy influences distribution diagram
Influence of frequency variation on accuracy performance:
For DTZ1513 energy meter, the frequency variation has little influences to the meter active,
reactive measurement accuracy.
(Note: Frequency rang: 45Hz-65Hz)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 26
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
DTZ1513 Frequency and Accuracy influences distribution diagram
3.6 Meter Characteristics(direct connected)
DTZ1513 replaceable keypad prepayment energy meter :
1
1
15
14
13
12
11
Optical communication port
2
3
4
2
Meter cover seals (one on the right and one left)
5
3
Top cover
4
Bottom case
5
Plug-in communication module cover
7
6
Plug-in communication module cover seal
8
7
Terminal cover
8
Terminal cover seals(one on the right and one left)
9
RJ11 output line port(output line port for RS-485,
10
Keypad(4X3 12 keys)
11
Balance credit LED(two colors-red/green)
12
Alarm indicator(yellow)
13
Reactive impulse LED(red)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 6
10
etc )
9
14
Active impulse LED(red)
15
LCD
27
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
DTZ1513(MBS410K2A)
DTZ1513 plug-in module keypad prepayment energy meter when communication module
cover is open:
21
22
21 Plug-in communication module
23
22 Plug-in RTC battery
24
25
23 Sealed setting permission/MD reset button
24 Plug-in communication module cover electric
seal switch
25 Multi-tarrif backup key
DTZ1513 plug-in module keypad prepayment energy meter when terminal cover is open:
31
31
Main terminal screws (16)
32
Clamping screws for top cover and bottom casing
33
Terminal cover seal
34
Meter installation hole (one on the right and one
left)
32
35
Meter aux. terminal
33
34
35
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 28
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
41
42
41
Output port of external antenna of GPRS/GSM
42
RJ11 port: for RS485 port.
3.6.1 Active (reactive) Impulse Indicator (red LED)-marking 13, 14
Flashing frequency of these two red LED indicator indicates directly instant load of the meter, the
higher frequency indicating the higher load. Meanwhile, it can also be used as standard impulse
output to measure the accuracy of meter.
Active constant 1000imp/kWh means red LED flashes 1000 times for 1kWh.
Reactive constant 1000imp/kWh means red LED flashes 1000 times for 1kVarh.
3.6.2 Alarm Indicator(yellow LED)-Marking 12
The yellow LED indicator is on when: 0 credit, credit at power off alarm threshold, power off alarm
due to improper operation (like tampering)
3.6.3 Balance Credit Indicator(double color LED)-Marking 11
When the green LED indicator is on: credit more than alarm threshold
When the yellow LED indicator flashes: credit between pre-alarm and alarm, user needs to
recharge; otherwise power will be off.
When the red LED indicator flashes: credit less than alarm threshold, user needs to
recharge;otherwise power will be off.
When the red indicator is on: 0 credit, power is off under no over-draft permission or non-friendly
date/time. Recharge needs to be done to connect the electricity.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 29
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
3.6.4 Optical(infrared) Port-Marking 1
The optical port can be used to connect meter and portable devices (HHU and PC) by a optical
cable.In such a way operator can read and configure meter tariff. The port protocol complies with
C mode of IEC62056-21, and has safety levels and password control.
4 LCD
Meter adopts LCD display with large screen, wide visual angle(≥120º),anti -UV function and
wide temperature range;
LCD can display up to 8 digits. Digits can be programmed as following format:
8 integers;
7 integers + 1 decimal; or
6 integers + 2 decimals.
Meter adopts IEC62056 display code, visualized prompt symbol, bar indicator of available
electricity credit (balance energy/ amount) and LED indicator of alarm/ prompt. LCD has
Backlight.
LCD visual icon
Code
Figure
1
A : code display area, supporting OIBS code
display
B:current tariff indication(for multi-tariff/step tariff
deduction mode)
2
Bar indicator for balance credit
Happy & Sad
3
face
Relay status
4
Indication
indicator;
Smiley Face:Meter in Good Condition
Sad Face,:
Meter in Bad Condition
①
Relay connected
②
Relay disconnected
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 30
Three Phase Keypad Prepayment Energy Meter
Code
Figure
(Plug-in Module Type)
Indication
5
measured value unit
kWh: active energy
kW: active power
kVArh: reactive energy
kVAr: reactive power
V:
voltage
A:
current
kVA: apparent power
6
Currency icon: money deduction mode
7
Data display area: through combination, displaying
values:
① Measuring(metering) data、TOKEN input data
② Date: YY-MM-DD
③ Time: hh-mm-ss
8
Three phase prepayment meter phase voltage
indication
A: Phase mark disappears when corresponding
phase is lost
B: Phase mark flashes when the corresponding
phase has an alarm.
9
Lighting symbol: PLC communication state
① Flashing:normal PLC communication
②Displaying: abnormal PLC communication
Alarm symbol: for tampering, cover open,
10
11
② Displaying: with cover open event, the cover is
closed currently
② Flashing: with cover open event, the cover is
open currently
Battery icon: for battery status
Displaying: out of battery, need battery rechange
Disappear: normal battery
Energy meter will automatically start self-checking status when power on, LCD shows full display
at this time (as picture). After 2 seconds, energy meter enters into display mode of balance
amount.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 31
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Normal display (balance amount): energy meter with built-in relay connected and
electricity credit, it displays balance amount.
1
2
3
4
5
6
7
Mark
Name
Remark
NO.
1
Current tariff code
T2: tariff shift 2 or step tariff rate2; referring to multi-tariff function
introduction
2
Bar indicator
Balance credit
3
Meter status
Meter working status
4
Rely status
relay status
5
Quantity unit / currency unit
6
Main display data
Balance credit: 12107.6
7
Phase voltage/current status
Phase voltage is normal, no phase lost
Data of meter measuring, reading and recording can be achieved through the following 3
ways:
„ auto scroll display mode
„ manual scroll display mode
„ code inquiry mode
4.1 Auto-scrolling Display Mode
According to configurations of auto-scrolling display data/sequence/time, LCD sequentially
displays the data, and display time can be set as from 3 seconds to 99 seconds and autoscrolling display data can be programmable up to 10 items(through upper computer). For “Rocket
program”, factory setting only displays remaining amount.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 32
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
4.2 Manual Scrolling Display Mode
Under no code input condition, by pressing blue enter button, the meter will display certain data,
as setted display sequence order and time. Display time can be programmed from 3s to 99s,and
up to 20 items can be programmable. Therefore, under manual scrolling display mode, the
searchable data is auto scrolling display item plus keypad scrolling item(program through upper
computer).
For this program, factory setting of manual scrolling display is as follows:
Code
Code content
Display mode
170
Balance credit
000
Accumulative active energy
001
Tariff 1(T1) accumulative active
energy/step 0 accumulative active
energy
002
Tariff 2(T2) accumulative active
energy/step 1 accumulative active
energy
003
Tariff 3(T3) accumulative active
energy/step 2 accumulative active
energy
004
Tariff 4(T4) accumulative active
energy/step 3 accumulative active
energy
031
L1 voltage
032
L2 voltage
033
L3 voltage
034
L1 current
035
L2 current
036
L3 current
040
Combined phase active power
041
L1 active power
042
L2 active power
043
L3 active power
038
Date(DD-MM-YY)
039
Time(HH-MM-SS)
700
Meter address(first 6 digits)
Unit/Indication
Meter address(last 5 digits)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 33
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
4.3 Short Code Inquiry Display Mode
Input 3 digits code and press enter button through meter keypad, desired items can be queried.
Meter short code display:
Code content
Display
mode(example
)
Code
000
Accumulative active energy
001
Tariff 1(T1) accumulative
accumulative active energy
002
Tariff 2(T2) accumulative
accumulative active energy
003
Tariff 3(T3) accumulative
accumulative active energy
active
energy/step
2
004
Tariff 4(T4) accumulative
accumulative active energy
active
energy/step
3
005
Tariff 5(T5) accumulative
accumulative active energy
active
energy/step
4
006
Tariff 6(T6) accumulative
accumulative active energy
active
energy/step
5
007
Tariff 7(T7) accumulative
accumulative active energy
active
energy/step
6
008
Tariff 8(T8) accumulative
accumulative active energy
active
energy/step
7
009
Accumulative reverse active energy
010
Accumulative reactive energy(optional)
011
Tariff 1(T1) accumulative reactive energy
012
Tariff 2(T2) accumulative reactive energy
013
Tariff 3(T3) accumulative reactive energy
014
Tariff 4(T4) accumulative reactive energy
015
Tariff 5(T5) accumulative reactive energy
016
Tariff 6(61) accumulative reactive energy
017
Tariff 7(T7) accumulative reactive energy
018
Tariff 8(T8) accumulative reactive energy
019
Accumulative reverse reactive energy(quadrant 3 and
4)
020
Accumulative apparent energy(optional)
021
Tariff 1(T1) accumulative apparent energy
022
Tariff 2(T2) accumulative apparent energy
023
Tariff 3(T3) accumulative apparent energy
024
Tariff 4(T4) accumulative apparent energy
025
Tariff 5(T5) accumulative apparent energy
active
energy/step
active
Shenzhen Inhemeter Co., Ltd
Unit/Indi
cation
0
energy/step1
www: inhemeter.com 34
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
026
Tariff 6(T6) accumulative apparent energy
027
Tariff 7(T7) accumulative apparent energy
028
Tariff 8(T8) accumulative apparent energy
029
Accumulative reserve apparent energy
031
L1 voltage
032
L2 voltage
033
L3 voltage
034
L1 current
035
L2 current
036
L3 current
037
Frequency
038
Date(DD-MM-YY)
039
Time(HH-MM-SS)
040
Combined phase active power
041
L1 active power
042
L2 active power
043
L3 active power
050
Combined phase reactive power(optional)
051
L1 reactive power
052
L2 reactive power
053
L3 reactive power
060
Combined phase apparent power(optional)
061
L1 apparent power
062
L2 apparent power
063
L3 apparent power
070
Combined phase power factor
071
L1 power factor
072
L2 power factor
073
L3 power factor
074
L1 current voltage vector angle
075
L2 current voltage vector angle
076
L3 current voltage vector angle
077
L1L2 voltage angle
078
L L2L3 voltage angle
079
L1L3 voltage angle
080
N circuit current
110
Current daily active energy
Unit/Indi
cation
Current daily active deducted amount
111
Current daily tariff 1(T1) active energy/step 0 active
energy
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 35
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
Unit/Indi
cation
Current daily tariff 1(T1) active energy deducted
amount/step 0 active deducted amount
112
Current daily tariff 1(T2) active energy/step 1 active
energy
Current daily tariff 2(T2) active energy deducted
amount/step 1 active deducted amount
113
Current daily tariff 3(T3) active energy/step 2 active
energy
Current daily tariff 3(T3) active energy deducted
amount/step 2 active deducted amount
114
Current daily tariff 4(T4) active energy/step 3 active
energy
Current daily tariff 4(T4) active energy deducted
amount/step 3 active deducted amount
115
Current daily tariff 5(T5) active energy/step 4 active
energy
Current daily tariff 5(T5) active energy deducted
amount/step 4 active deducted amount
116
Current daily tariff 6(T6) active energy/step 5 active
energy
Current daily tariff 6(T6) active energy deducted
amount/step 5 active deducted amount
117
Current daily tariff 7(T7) active energy/step 6 active
energy
Current daily tariff 7(T7) active energy deducted
amount/step 6 active deducted amount
118
Current daily tariff 8(T8) active energy/step 7 active
energy
Current daily tariff 4(T4) active energy deducted
amount/step 3 active deducted amount
130
Current monthly active energy
Current active deducted amount
131
Current monthly tariff 1(T1) active energy/step 0 active
energy
Current monthly tariff 1(T1) active energy deducted
amount/step 0 active deducted amount
132
Current monthly tariff 2(T2) active energy/step 1 active
energy
Current monthly tariff 2(T2) active energy deducted
amount/step 1 active deducted amount
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 36
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
133
(Plug-in Module Type)
Unit/Indi
cation
Current monthly tariff 3(T3) active energy/step 2 active
energy
Current monthly tariff 3(T3) active energy deducted
amount/step 2 active deducted amount
134
Current monthly tariff 4(T4) active energy deducted
amount/step 3 active deducted amount
Current monthly tariff 4(T4) active energy deducted
amount/step 3 active deducted amount
135
Current monthly tariff 5(T5) active energy/step 4 active
energy
Current monthly tariff 5(T5) active energy deducted
amount/step 4 active deducted amount
136
Current monthly tariff 6(T6) active energy/step 5 active
energy
Current monthly tariff 6(T6) active energy deducted
amount/step 5 active deducted amount
137
Current monthly tariff 7(T7) active energy/step 6 active
energy
Current monthly tariff 7(T7) active energy deducted
amount/step 7 active deducted amount
138
Current monthly tariff 8(T8) active energy/step 7 active
energy
Current monthly tariff 8(T8) active energy deducted
amount/step 7 active deducted amount
139
Current monthly active MD
Current monthly MD date
Current monthly MD time
140
Current reactive power(optional)
150
Current apparent power(optional)
170
Balance credit
171
Accumulative recharged amount
172
Accumulative deducted amount
200
Load threshold
201
Allowed overload times
202
Over load power off recovery time
203
Min. guaranteed power supply load threshold
204
Over current power off threshold
205
Phase power unbalance power off threshold
206
Credit pre-alarm threshold
207
Credit alarm threshold
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 37
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
208
Billing date/time
209
Buzzer alarm interval
210
Excessive energy threshold
211
Overdraft threshold
212
Over voltage power off threshold
213
Low voltage power off threshold
214
Value of over temperature power off
215
Bypass tampering alarm threshold
230
Prepayment configuration status flag 1
231
Prepayment configuration status flag 2
240
Friendly time period(not allowing outage period)-starting
hour hour minute minute
241
Friendly time period(not allowing outage period)-ending
hour hour minute minute
242
Friendly weekend(not allowing outage period)
251
1st friendly holiday(date of not allowing outage
-YYMMDD)
252
2nd friendly holiday(date of not allowing outage
-YYMMDD)
253
3rd friendly holiday(date of not allowing outage
-YYMMDD)
254
4th friendly holiday(date of not allowing outage
-YYMMDD)
255
5th friendly holiday(date of not allowing outage
-YYMMDD)
256
6th friendly holiday(date of not allowing outage
-YYMMDD)
257
7th friendly holiday(date of not allowing outage
-YYMMDD)
258
8th friendly holiday(date of not allowing outage
-YYMMDD)
259
9th friendly holiday(date of not allowing outage
-YYMMDD)
260
10th friendly holiday(date of not allowing outage
-YYMMDD)
261
11th friendly holiday(date of not allowing outage
-YYMMDD)
262
12th friendly holiday(date of not allowing outage
-YYMMDD)
263
13th friendly holiday(date of not allowing outage
Shenzhen Inhemeter Co., Ltd
(Plug-in Module Type)
www: inhemeter.com Unit/Indi
cation
38
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
Unit/Indi
cation
-YYMMDD)
264
14th friendly holiday(date of not allowing outage
-YYMMDD)
265
15th friendly holiday(date of not allowing outage
-YYMMDD)
266
16th friendly holiday(date of not allowing outage
-YYMMDD)
267
17th friendly holiday(date of not allowing outage
-YYMMDD)
268
18th friendly holiday(date of not allowing outage
-YYMMDD)
269
19th friendly holiday(date of not allowing outage
-YYMMDD)
270
20th friendly holiday(date of not allowing outage
-YYMMDD)
300
Available electricity days
301
Total billing
302
Over load power off times
303
Meter status flag
1
304
Meter status flag
2
305
Meter status flag
3(cover opening event)
306
Meter status flag
4(grid event 1)
307
Meter status flag
5(grid event 2)
308
Meter status flag
6(grid event 3)
310
Accumulative trip times
311
Latest 1st trip date/time
Latest 1st trip recovery date/time
312
Latest 1st trip power off reason flag
1
Latest 1st trip power off reason flag
2
Latest 2nd trip date/time
Latest 2nd trip recovery date/time
313
Latest 2nd trip power off reason flag
1
Latest 2nd trip power off reason flag
2
Latest 3rd trip date/time
Latest 3rd trip recovery date/time
314
Latest 3rd trip power off reason flag
1
Latest 3rd trip power off reason flag
2
Latest 4th trip date/time
Latest 4th trip recovery date/time
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 39
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
315
(Plug-in Module Type)
Latest 4th trip power off reason flag
1
Latest 4th trip power off reason flag
2
Unit/Indi
cation
Latest 5th trip date/time
Latest 5th trip recovery date/time
316
Latest 5th trip power off reason flag
1
Latest 5th trip power off reason flag
2
Latest 6th trip date/time
Latest 6th trip recovery date/time
317
Latest 6th trip power off reason flag
1
Latest 6th trip power off reason flag
2
Latest 7th trip date/time
Latest 7th trip recovery date/time
318
Latest 7th trip power off reason flag
1
Latest 7th trip power off reason flag
2
Latest 8th trip date/time
Latest 8th trip recovery date/time
319
Latest 8th trip power off reason flag
1
Latest 8th trip power off reason flag
2
Latest 9th trip date/time
Latest 9th trip recovery date/time
320
Latest 9th trip power off reason flag
1
Latest 9th trip power off reason flag
2
Latest 10th trip date/time
Latest 10th trip recovery date/time
Latest 10th trip power off reason flag
1
Latest 10th trip power off reason flag
2
Grid power off event record
330
Accumulative times of grid power off events
331
Latest 1st grid power off date/time
Latest 1st grid power recovery date/time
332
Latest 2nd grid power off date/time
Latest 2nd grid power recovery date/time
333
Latest 3rd grid power off date/time
Latest 3rd grid power
334
recovery date/time
Latest 4th grid power off date/time
Latest 4th grid power recovery date/time
335
Latest 5th grid power off date/time
Latest 5th grid power recovery date/time
336
Latest 6th grid power off date/time
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 40
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
Unit/Indi
cation
Latest 6th grid power recovery date/time
337
Latest 7th grid power off date/time
Latest 7th grid power recovery date/time
338
Latest 8th grid power off date/time
Latest 8th grid power recovery date/time
339
Latest 9th grid power off date/time
Latest 9th grid power recovery date/time
340
Latest 10th grid power off date/time
Latest 10th grid power recovery date/time
Special event record
350
Accumulative event times
351/0
01
Latest 1st event occurring date
351/0
02
Latest 1st event occurring time
351/0
03
Lately 1st event index flag
351/0
04
Latest 1st event status flag
1(meter fault)
351/0
05
Latest 1st even status flag
2(cover opening)
351/0
06
Latest 1st even status flag
3(grid event 1)
351/0
07
Latest 1st even status flag
4(grid event 2)
351/0
08
Latest 1st even status flag
5(grid event 3)
352/0
01
Latest 2ndevent occurring date
352/0
02
Latest 2nd event occurring time
352/0
03
Latest 2nd event index flag
352/0
04
Latest 2nd event status flag
1(meter fault)
352/0
05
Latest 2nd even status flag
2(cover opening)
352/0
Latest 2nd event status flag
3(grid event 1)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 41
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
Unit/Indi
cation
06
352/0
07
Latest 2nd event status flag
4(grid event 2)
352/0
08
Latest 2nd event status flag
5(grid event 3)
353/0
01
Latest 3rdevent occurring date
353/0
02
Latest 3rd event occurring time
353/0
03
Latest 3rd event index flag
353/0
04
Latest 3rd event status flag
1(meter fault)
353/0
05
Latest 3rd event status flag
2(cover opening)
353/0
06
Latest 3rd event status flag
3(grid event 1)
353/0
07
Latest 3rd event status flag
4(grid event 2)
353/0
08
Latest 3rd event status flag
5(grid event 3)
354/0
01
Latest 4th event occurring date
354/0
02
Latest 4th event occurring time
354/0
03
Latest 4th event index flag
354/0
04
Latest 4th event status flag
1(meter fault)
354/0
05
Latest 4th event status flag
2(cover opening event)
354/0
06
Latest 4th event status flag
3(grid event 1)
354/0
07
Latest 4th event status flag
4(grid event 2)
354/0
08
Latest 4th event status flag
5(grid event 3)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 42
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
(Plug-in Module Type)
355/0
01
Latest 5thevent occurring date
355/0
02
Latest 5th event occurring time
355/0
03
Latest 5th event index flag
355/0
04
Latest 5th event status flag
1(meter fault)
355/0
05
Latest 5th event status flag
2(cover opening event)
355/0
06
Latest 5th event status flag
3(grid event 1)
355/0
07
Latest 5th event status flag
4(grid event 2)
355/0
08
Latest 5th event status flag
5(grid event 3)
356/0
01
Latest 6thevent occurring date
356/0
02
Latest 6th event occurring time
356/0
03
Latest 6th event index flag
356/0
04
Latest 6th event status flag
1(meter fault)
356/0
05
Latest 6th event status flag
2(cover opening event)
356/0
06
Latest 6th event status flag
3(grid event 1)
356/0
07
Latest 6th event status flag
4(grid event 2)
356/0
08
Latest 6th event status flag
5(grid event 3)
357/0
01
Latest 7thevent occurring date
357/0
02
Latest 7th event occurring time
357/0
03
Latest 7th event index flag
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com Unit/Indi
cation
43
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
(Plug-in Module Type)
357/0
04
Latest 7th event status flag
1(meter fault)
357/0
05
Latest 7th event status flag
2(cover opening event)
357/0
06
Latest 7th event status flag
3(grid event 1)
357/0
07
Latest 7th event status flag
4(grid event 2)
357/0
08
Latest 7th event status flag
5(grid event 3)
358/0
01
Latest 8th event occurring date
358/0
02
Latest 8th event occurring time
358/0
03
Latest 8th event index flag
358/0
04
Latest 8th event status flag
1(meter fault)
358/0
05
Latest 8th event status flag
2(cover opening event)
358/0
06
Latest 8th event status flag
3(grid event 1)
358/0
07
Latest 8th event status flag
4(grid event 2)
358/0
08
Latest 8th event status flag
5(grid event 3)
359/0
01
Latest 9th event occurring date
359/0
02
Latest 9th event occurring time
359/0
03
Latest 9th event index flag
359/0
04
Latest 9th event status flag
1(meter fault)
359/0
05
Latest 9th event status flag
2(cover opening event)
359/0
06
Latest 9th event status flag
3(grid event 1)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com Unit/Indi
cation
44
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
(Plug-in Module Type)
359/0
07
Latest 9th event status flag
4(grid event 2)
359/0
08
Latest 9th event status flag
5(grid event 3)
360/0
01
Latest 10th event occurring date
360/0
02
Latest 10th event occurring time
360/0
03
Latest 10th event index flag
360/0
04
Latest 10th event status flag
1(meter fault)
360/0
05
Latest 10th event status flag
2(cover opening event)
360/0
06
Latest 10th event status flag
3(grid event 1)
360/0
07
Latest 10th event status flag
4(grid event 2)
360/0
08
Latest 10th event status flag
5(grid event 3)
401/H
00
Last month active energy
401/H
01
Last month tariff 1(T1) active energy//step 0 active
energy
401/H
02
Last month tariff 2(T2) active energy//step 1 active
energy
401/H
03
Last month tariff 3(T3) active energy//step 2 active
energy
401/H
04
Last month tariff 4(T4) active energy//step 3 active
energy
401/H
05
Last month tariff 5(T5) active energy//step 4 active
energy
401/H
06
Last month tariff 6(T6) active energy//step 5 active
energy
401/H
07
Last month tariff 7(T7) active energy//step 6 active
energy
401/H
08
Last month tariff 8(T8) active energy//step 7 active
energy
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com Unit/Indi
cation
45
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
401/H
09
(Plug-in Module Type)
Unit/Indi
cation
Last month active maximum demand
Last month active maximum demand date
Last month active maximum demand time
401/H
10
Last month active deduction amount
401/H
20
Last month reactive energy;reactive energy under all
tariffs; reactive maximum demand; reactive deduction
amount
401/H
50
Last month apparent energy;apparent energy under all
tariffs; apparent maximum demand; apparent deduction
amount
402/H
00
Last 2nd month active energy
402/H
01
Last 2nd month tariff 1(T1) active energy//step 0 active
energy
402/H
02
Last 2nd month tariff 2(T2) active energy//step 1 active
energy
402/H
03
Last 2nd month tariff 3(T3) active energy//step 2 active
energy
402/H
04
Last 2nd month tariff 4(T4) active energy//step 3 active
energy
402/H
05
Last 2nd month tariff 5(T5) active energy//step 4 active
energy
402/H
06
Last 2nd month tariff 6(T6) active energy//step 5 active
energy
402/H
07
Last 2nd month tariff 7(T7) active energy//step 6 active
energy
402/H
08
Last 2nd month tariff 8(T8) active energy//step 7 active
energy
402/H
09
Last 2nd month active maximum demand
Last 2nd month active maximum demand date
Last 2nd month active maximum demand time
402/H
10
Last 2nd month active deduction amount
402/H
20
Last 2nd month reactive energy;reactive energy under
all tariffs; reactive maximum demand; reactive
deduction amount
402/H
Last 2nd month apparent energy;apparent energy under
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 46
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
50
(Plug-in Module Type)
Unit/Indi
cation
all tariffs; apparent maximum demand; apparent
deduction amount
403/H
00
Last 3rd month active energy
403/H
01
Last 3rd month tariff 1(T1) active energy//step 0 active
energy
403/H
02
Last 3rd month tariff 2(T2) active energy//step 1 active
energy
403/H
03
Last 3rd month tariff 3(T3) active energy//step 2 active
energy
403/H
04
Last 3rd month tariff 4(T4) active energy//step 3 active
energy
403/H
05
Last 3rd month tariff 5(T5) active energy//step 4 active
energy
403/H
06
Last 3rd month tariff 6(T6) active energy//step 5 active
energy
403/H
07
Last 3rd month tariff 7(T7) active energy//step 6 active
energy
403/H
08
Last 3rd month tariff 8(T8) active energy//step 7 active
energy
403/H
09
Last 3rd month active maximum demand
Last 3rd month active maximum demand date
Last 3rd month active maximum demand time
403/H
10
Last 3rd month active deduction amount
403/H
20
Last 3rd month reactive energy;reactive energy under
all tariffs; reactive maximum demand; reactive
deduction amount
403/H
50
Last 3rd month apparent energy;apparent energy under
all tariffs; apparent maximum demand; apparent
deduction amount
●
●
●
●
●
413/H
00
Last 13th month active energy
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 47
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
413/H
01
Last 13th month tariff 1(T1) active energy//step 0 active
energy
413/H
02
Last 13th month tariff 2(T2) active energy//step 1 active
energy
413/H
03
Last 13th month tariff 3(T3) active energy//step 2 active
energy
413/H
04
Last 13th month tariff 4(T4) active energy//step 3 active
energy
413/H
05
Last 13th month tariff 5(T5) active energy//step 4 active
energy
413/H
06
Last 13th month tariff 6(T6) active energy//step 5 active
energy
413/H
07
Last 13th month tariff 7(T7) active energy//step 6 active
energy
413/H
08
Last 13th month tariff 8(T8) active energy//step 7 active
energy
413/H
09
Last 13th month active maximum demand
Unit/Indi
cation
Last 13th month active maximum demand date
Last 13th month active maximum demand time
413/H
10
Last 13th month active deduction amount
413/H
20
Last 13th month reactive energy;reactive energy under
all tariffs; reactive maximum demand; reactive
deduction amount
413/H
50
Last 13th month apparent energy;apparent energy
under all tariffs; apparent maximum demand; apparent
deduction amount
451/d
00
Last day active energy
451/d
01
Last day tariff 1(T1) active energy//step 0 active energy
451/d
02
Last day tariff 2(T2) active energy//step 1 active energy
451/d
03
Last day tariff 3(T3) active energy//step 2 active energy
451/d
04
Last day tariff 4(T4) active energy//step 3 active energy
451/d
Last day tariff 5(T5) active energy//step 4 active energy
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 48
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
Unit/Indi
cation
05
451/d
06
Last day tariff 6(T6) active energy//step 5 active energy
451/d
07
Last day tariff 7(T7) active energy//step 6 active energy
451/d
08
Last day tariff 8(T8) active energy//step 7 active energy
451/d
10
Last day active deduction amount
452/d
00
Last 2nd day active energy
452/d
01
Last 2nd day tariff 1(T1) active energy//step 0 active
energy
452/d
02
Last 2nd day tariff 2(T2) active energy//step 1 active
energy
452/d
03
Last 2nd day tariff 3(T3) active energy//step 2 active
energy
452/d
04
Last 2nd day tariff 4(T4) active energy//step 3 active
energy
452/d
05
Last 2nd day tariff 5(T5) active energy//step 4 active
energy
452/d
06
Last 2nd day tariff 6(T6) active energy//step 5 active
energy
452/d
07
Last 2nd day tariff 7(T7) active energy//step 6 active
energy
452/d
08
Last 2nd day tariff 8(T8) active energy//step 7 active
energy
452/d
10
Last 2nd day active deduction amount
●
●
●
●
●
495/d
00
Last 45th day active energy
495/d
01
Last 45th day tariff 1(T1) active energy//step 0 active
energy
495/d
Last 45th day tariff 2(T2) active energy//step 1 active
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 49
Three Phase Keypad Prepayment Energy Meter
Code content
Display
mode(example
)
Code
02
(Plug-in Module Type)
Unit/Indi
cation
energy
495/d
03
Last 45th day tariff 3(T3) active energy//step 2 active
energy
495/d
04
Last 45th day tariff 4(T4) active energy//step 3 active
energy
495/d
05
Last 45th day tariff 5(T5) active energy//step 4 active
energy
495/d
06
Last 45th day tariff 6(T6) active energy//step 5 active
energy
495/d
07
Last 45th day tariff 7(T7) active energy//step 6 active
energy
495/d
08
Last 45th day tariff 8(T8) active energy//step 7 active
energy
495/d
10
Last 45th day active deduction amount
500
Recharge times
501
Last 1st recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
502
Last 2nd recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
503
Last 3rd recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
504
Last 4th recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
505
Last 5th recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
506
Last 6th recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
507
Last 7th recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
508
Last 8th recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
509
Last 9th recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
510
Last 10th recharge(recharge amount、TOKEN
value、TID code、recharge date/time)
511
Last 11th recharge(recharge amount、TOKEN value、
TID code、recharge date/time)
512
Last 12th recharge(recharge amount、TOKEN value、
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 50
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
Unit/Indi
cation
TID code、recharge date/time)
513
Last 13th recharge(recharge amount、TOKEN
value、TID code、recharge date/time)
514
Last 14th recharge(recharge amount、TOKEN
value、TID code、recharge date/time)
515
Last 15th recharge(recharge amount、TOKEN
value、TID code、recharge date/time)
520
Technical TOKEN input times
521
Latest 1st technical TOKEN input info.
522
Latest 2nd technical TOKEN input info.
523
Latest 3rd technical TOKEN input info.
524
Latest 4th technical TOKEN input info.
525
Latest 5th technical TOKEN input info.
526
Latest 6th technical TOKEN input info.
527
Latest 7th technical TOKEN input info.
528
Latest 8th technical TOKEN input info.
529
Latest 9th technical TOKEN input info.
600
In-use tariff version NO.
601
In-use tariff 1(T1) active energy rate//step tariff P0
602
In-use tariff 2(T2) active energy rate//step tariff P1
603
In-use tariff 3(T3) active energy rate//step tariff P2
604
In-use tariff 4(T4) active energy rate//step tariff P3
605
In-use tariff 5(T5) active energy rate//step tariff P4
606
In-use tariff 6(T6) active energy rate//step tariff P5
607
In-use tariff 7(T7) active energy rate//step tariff P6
608
In-use tariff 8(T8) active energy rate//step tariff P7
621
Tariff time period 1 starting HHMM Tx//monthly step
energy division E1
622
Tariff time period 2 starting HHMM Tx//monthly step
energy division E2
623
Tariff time period 3 starting HHMM Tx//monthly step
energy division E3
624
Tariff time period 4 starting HHMM Tx//monthly step
energy division E4
625
Tariff time period 5 starting HHMM Tx//monthly step
energy division E5
626
Tariff time period 6 starting HHMM Tx//monthly step
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 51
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
Unit/Indi
cation
energy division E6
627
Tariff time period 7 starting HHMM Tx//monthly step
energy division E7
628
Tariff time period 8 starting HHMM Tx//step tariff time
table
629
Tariff time period 9 starting HHMM Tx//next backup
month step energy division E1
630
Tariff time period 10 starting HHMM Tx//next backup
month step energy division E2
631
Tariff time period 11 starting HHMM Tx//next backup
month step energy division E3
632
Tariff time period 12 starting HHMM Tx//next backup
month step energy division E4
633
Tariff time period 13 starting HHMM Tx//next backup
month step energy division E5
634
Tariff time period 14 starting HHMM Tx//next backup
month step energy division E6
635
Tariff time period 15 starting HHMM Tx//next backup
month step energy division E7
636
Tariff time period 16 starting HHMM Tx
637
Tariff time period 17 starting HHMM Tx
638
Tariff time period 18 starting HHMM Tx
639
Tariff time period 19 starting HHMM Tx
640
Tariff time period 20 starting HHMM Tx
641
Tariff time period 21 starting HHMM Tx
642
Tariff time period 22 starting HHMM Tx
643
Tariff time period 23 starting HHMM Tx
644
Tariff time period 24 starting HHMM Tx
645
Next TOU shift date(multi-tariff mode)
646
Next TOU shift time(multi-tariff mode)
648
Next step tariff shift date(step tariff mode)
649
Next step tariff shift time(step tariff mode)
700
Energy meter NO.(meter address)
701
Energy meter impulse constant
702
Energy meter inserted software version NO.
703
Energy meter temperature measurement value
710
Key tpye
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 52
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
711
Key version
712
Tariff number
713
Organization code(SGC code)
714
STS software version
720
Energy meter installation position info.(longitude)
Future
definition and
no such item
now
721
Energy meter installation position info.(latitude)
Future
definition and
no such item
now
722
Energy meter installation position info.(altitude)
Future
definition and
no such item
now
730
Replaceable communication module type、version
731
GPRS/GSM module type info.
732
Signal quality(GPRS)
733
Connection status(GPRS)
741
PLC module info.
Future
definition and
no such item
now
751
Module number info.(RF)
Future
definition and
no such item
now
Unit/Indi
cation
Future
definition and
no such item
now
Future
definition and
no such item
now
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 53
Three Phase Keypad Prepayment Energy Meter
Code content
(Plug-in Module Type)
Display
mode(example
)
Code
761
Module number info.(Zigbee)
799
LCD full screen display check
Unit/Indi
cation
Special display symbol:
Display mode(example)
Data indication
Communication between CIU and MCU, please wait.
No display if no CIU
Failure of communication between CIU and MCU,
please wait!
No display if no CIU
Display: Cur_rEU
LCD flashes with Cur_rEU, which means reverse
current. Please check the wiring and electricity use?
Display: no_USEd
LCD displays no_USEd,which means the inquired item
is not in use.
Display: NULL
LCD displays NULL, which means the inquired item is
null and no data display.
Display: OUEr_Uol
LCD displays OUEr_Uol, which means energy meter
disconnects supply circuit due to over voltage in power
grid, and alternatively displays the voltage before
power-off. The energy meter will re-supply power
manually/automatically after voltage goes back to
normal.
Display: Lo_UoL
LCD displays Lo_UoL, which means energy meter
disconnects supply circuit due to too low the voltage in
power grid, and alternatively displays the voltage
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 54
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
before power-off. The energy meter will re-supply
power manually/automatically after voltage goes back
to normal.
4.4 Keypad Operation Instructions
The energy meter have 12 keys for Token entry and information
inquiry. When numbers are typed through keypad, LCD will
automatically display the input numbers and the current numbers of
tokens in the token area on the left upper corner. When exceeding four numbers, the meter will
automatically group four numbers, and separate every group by a dash. During the keypad
operation, all the irrelevant symbols will no longer display for the time being. As shown in the
picture, it is the status of inputting the token, and 10 numbers have been input. When press key,
meter will make “di” sound.
Numeric keys 0-9, which are used for input of token, the other two special key buttons
respectively are
red
for delete and blue
for confirmation.
: when the input token and the short token are wrong, the button can
The red delete button
be used to delete the digitals from right to left.
: After entering the token, press enter to confirm, the meter will load
The blue confirm button
the purchasing power or power purchasing amount. Otherwise, if there is an error with the input
token, there will be sound alarm, and LCD will have the corresponding error code accordingly.
If no other numbers have been entered, the confirmation key button will be used as manual
display button, and you can press the button to check the manual data display which has been
settled in advance.
4.4.1 TOKEN Inputting
4.4.1.1 Complete and acceptable TOKEN
After enter 20 digits TOKEN and confirm, LCD will display “Accept” if this TOKEN is correct and
accepted by the meter.
z keypad is locked up for 5 seconds for processing TOKEN.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 55
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Meter sound indication
Smile face
Display total credit (balance KWh) after 5 seconds .
z
z
z
S.N
Picture
Instruction
1
Display: connected
It is communicating with MCU, please waiting.
There is no display if meter without CIU
2
Display:Accept
Indicate the token has been accepted and the
recharging is successful.
3
Display:1002.90kWh
After recharge, the total balance is 1002.90kWh.
4.4.1.2. Incomplete TOKEN
If no number is input continuously within 30 seconds while inputting TOKEN code, it will be
regarded as overtime.
· TOKEN code will disappear from LCD.
· Display balance KWh/credit
4.4.1.3. Used Token
Once a TOKEN is accepted and processed by the meter, it will be rejected if input again. Meter
LCD will indicate “Used”.
z Keypad is locked up for 5 seconds and display “used”
z Meter sound alarm
z Sad face
4.4.1.4. Overdue Token
If the TOKEN is older than the oldest TOKEN that logged in meter record, it will be regarded as
“overdue” and rejected by the meter. Meter LCD will display “Old”.
z Keypad is locked up for 5 seconds and indicating “Old”
z Meter sound alarm
z Sad face.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 56
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
4. 4.1.5. The correct but rejected overflow token
Please refer to section 6.8 for anti-overflow function while recharge. The effective TOKEN code
will be rejected if total balance credit register capacity is more than preset value. LCD display will
indicate “Over- Crd”.
z Keypad is locked up for 5 seconds and indicating “Over Crd”
z Meter sound alarm
z Sad face.
4.4.1.6 Incorrect TOKEN
The TOKEN will be rejected by meter if number inputting is wrong, meter No. is inconsistent,
meter encryption key is incorrect, or random numbers are input for the purpose of tampering.
LCD display will indicate “Reject-1”.
z Display “ Reject-1”
z Meter sound alarm
z Sad face.
Instructions of rejected token types:
S.N
Cutline
Instruction
1
Meter TOKEN decoding verification error
TOKEN for recharge, load threshold modification,
encryption key shift are incorrect; or TOKEN is
inconsistent to meter number or meter encryption key.
2
Unsupported Token ,can not be decoded.
3
Meter encryption key type is DDTK, and does not
support recharge TOKEN.
4
TOKEN data is out of range and it is abnormal data
after decoding
5
Encryption replacement is illegal (error occurs when
other encryption key type is transfer to unique
encryption key.)
6
Used token
7
Overdue token
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 57
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Correct but rejected overflow token.
8
4.4.2 Assignment Encryption Key Input Operation
Meter assignment key need to be replaced when install & re-install meter, or meter use area and
power supply are changed, or prepayment management system vending encryption is refreshed,
or security target un-periodically change encryption. These security measures need to be
changed by inputting meter assignment encryption key. At the same time, vending system and
meter require assignment encryption key separately generated by the same vending encryption
key. Otherwise TOKEN from vending system will not be accepted by the meter.
Assignment encryption key has two groups of TOKEN(This first group of change encryption key
TOKEN and the second group of change encryption key TOKEN). Settings for the first group and
the second group will not be by sequence, user can input the first group or the second group at
first. But two groups of TOKEN must be input within 5 minutes together, otherwise, user has to
restart the input operation.
After inputting one group of TOKEN (accepted by meter correctly), the meter will indicate as
followings::
The 2nd group of change encryption key TOKEN is input and
accepted, please input the 1st group now.
The 1st group of change encryption key TOKEN is input and
accepted, please input the 2nd group now.
4.4.3 Technical Token
There are several TOKEN codes with special functions for keypad prepayment energy meter, that
is, technical Token, which can be applied for power off recovery due to tampering, record
clearance,meter load threshold setting, etc. These special TOKEN codes are generated
dispersedly according to each energy meter by vending Management System.
4.4.3.1 Tampering
clearance TOKEN
If power is cut off due to opening of terminal cover, the user must go to vending Management
Center to apply for tamper clearance TOKEN to have power supply recovered. After inputting
temper clearance TOKEN, the meter will recover from power failure to supplying power.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 58
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
4.4.3.2 Load threshold TOKEN
Load threshold can be changed by inputting load threshold TOKEN. If preset load threshold is
low as user load demand increases, which brings about frequent overload consumption or
overload power off, the user needs to go to Power Supply Management Department or Vending
Department to apply for additional requirement of power load, and a new load threshold TOKEN
will be provided after the application is permitted by Vending Department. Meter load
threshold setting will be revised by inputting new load threshold TOKEN.
4.4.3.3 Credit clearance TOKEN
If energy meter needs to be changed or maintained or user is changed, after confirming related
data, the user can input a KWh clearance TOKEN to reset remaining energy/credit. Built-in relay
will be disconnected to cut off power supply.
4.4.4 Special TOKEN
The following special TOKEN codes are special extended functions for keypad prepayment
energy meter made by INHEMETER.
4.4.4.1 Low credit pre-warning
threshold TOKEN
Balance KWh pre-warning threshold value and function can be set by inputting code:
the value of wich can be from 1 kWh to 999kWh.
4.4.4.2 Low credit warning
4547 8xxx,
threshold TOKEN
Balance KWh warning threshold value and function can be set by inputting code: 4547 9xxx,
the value of which can be set from 0kWh to 999kWh. If the setting value is zero, this function is
disabled.
As shown in section 6.7, pre-warning and warning function for meter of low credit.
4.4.4.3 Activation TOKEN after meter installation
Meter relay is in disconnection status since delivery from factory. After completion of installation,
20-digit special TOKEN should be input on the keypad to activate meter ( relay is
connected ). Meter relay is always in disconnection status before activation whether there is
presetting at factory, user recharging and remaining credit or not. Activation TOKEN can only be
used once in a meter. Once the meter is activated, it will not be restricted. Activation TOKEN will
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 59
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
be issued by INHEMETER.
The activation TOKEN: 1275-4194-1448-6450-5970
4.4.5 Test TOKEN (non-specific meter TOKEN)
There are some non-specific TOKEN for prepayment keypad meter which are used for meter
function test. Once the meter accept these TOKEN, the meter will do corresponding tests.
Function
TOKEN
Activate the disconnection device (internal latching
contactor)
0000
0000
0001
5099
7584
HMI test, which involves turning on all the LED’s,
displaying all segments on the LCD, and activating
the buzzer
0000
0000
0001
6777
4880
Display the total units counter
0000
0000
0002
0132
8896
Display the key revision number and key type
1844
6744
0738
4377
2416
Display the tariff index
3689
3488
1475
5332
2496
Display the power limit level
0000
0000
0012
0797
4400
Display the tamper state
0000
0000
0022
8172
8512
Display the instantaneous power
0000
0000
0044
2920
8064
Display the software version number
0000
0000
0087
2419
5840
Test all the above function(tests run sequentially)
5649
3153
7254
5031
3471
Every test (testing by sequence) will last for 2.5 seconds. If one test item operates
independently ,it will last 5 seconds. After the test, meter returns to normal working mode.
4.4.6 Extended Function TOKEN
The setting data of overdraw threshold and minimum guaranteed power consumption can be
transformed to TOKEN via vending system.
5 Measurement Function
5.1 Active/ Reactive/ Apparent Energy Measurement
DTZ1513 3P4W (direct connected) keypad prepayment energy meter with plug-in communication
module cumulatively measure and store 3P4W active/ reactive/ apparent energy; Active metering
unit is KWh, reactive metering unit is KVarh, apparent energy unit is kVah. The cumulative active/
reactive energy has already been cleared to zero at factory. Energy meter will adopt automatic
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 60
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
clearing mode if cumulative energy is greater than 999999.99kWh (or 999999.99kVarh/
999999.99kVah).
Measurement of reactive energy and apparent energy is optional for DTZ1513 energy meter and
can be done at the same time.
z Forward/reverse active energy is totaled into cumulative active energy. Cumulative
reverse active energy will be measured and displayed separately.
z Forward/reverse reactive energy measurement is totaled into cumulative reactive
energy. Cumulative reverse reactive power will be measured and displayed separately.
z Measurement/ display of active cumulative energy and cumulative active energy under
each tariff list
z Latest 45 days active power consumption and that under each tariff are recorded and
can be searched(or downloaded) .
z Latest 13months active power consumption and that under each tariff are recorded and
can be searched(or downloaded) .
z Active metering accuracy: Class 1.0
z Active energy display mode: 6+2, 6 digits of integer and 2 digits of decimal(factory
default setting)
z Reactive energy of each tariff and monthly reactive energy of 13 months can be
regarded as options
z Apparent energy of each tariff and monthly apparent energy of 13 months can be
regarded as options
5.2 Calculation of Active MD (Maximum demand)
DTZ1513 energy meter can record statistics of active MD in current billing period, and its
occurring date/time.
„ Billing period is one month and the starting date of billing period can be set, the range of
which is 1st day-27th day.
„ Demand calculation mode is sliding window method. Sliding time is 3 min and demand
calculation period is 15 min.
„ Calculate/display MD of current month and its occurring date/time
z Latest 13months MD and its occurring date/time are recorded and can be searched(or
downloaded) .
5.3 Electric Parameter Measurement
Phase voltage measurement/display: 3 digits of integer, 2 digits of decimal, unit: V, accuracy:
±1%
Current measurement/display: 3 digits of integer, 2 digits of decimal, unit: A, accuracy: ±1%
Power measurement/display: 2 digits of integer, 3 digits of decimal, unit: kW, accuracy: ±1%
Frequency measurement/display: 2 digits of integer, 2 digits of decimal, unit: Hz, accuracy: ±1%
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 61
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Power factor measurement/display: 1 digits of integer, 3 digits of decimal, unit: COSФ, accuracy:
±1%
Angle between phase current and phase voltage: 2 digits of integer, 2 digits of decimal, unit: Ф,
accuracy: ±1%
Angle between phase voltage: 2 digits of integer, 2 digits of decimal, unit: Ф, accuracy: ±1%
Note:Parameter measurement error except that of energy can be calculated through following
formula
Metering error (%) = (measured value-actual value)/ measured reference value *100%
Definition of measured reference value:
Voltage is rated voltage ; voltage measurement range is 0.6Um--1.2Um。
Current is maximum current ; current measurement range is 0.05Ib--Imax
5.4 TOU Multi-tariff Measurement Function
DTZ1513 three phase prepayment meter with plug-in communication module can measure
active/reactive energy with TOU function. Meter supports 8 tariffs and 24 time shifts.
Tariff shift is based on a daily tariff table as the basic unit. The meter can prestore up to 16 sets of
daily tariff table, and then based on the festival tariff table, seasonal tariff table, and weekly tariff
table to select the corresponding tariff table so as to realize tariff swift in different holidays,
seasons, and working days in the same week.
Tariff consists of the following basic units:
Sr/N
Basic unit
Number
of bytes
Note
1
8 tariffs
2
24 time shift per day
Daily TOU division
3
8 tariff rates
Tariff rate in each TOU
4
16 daily tariff
5
12 weekly tariff
6
12 seasonal tariff
7
50 holiday tariff
8
8 tariff rate tables
5.4.1 Daily Tariff
Daily tariff defines in every daily time shift to use with tariff rate code.
When a new day comes (at 00:00:00), meter will select a daily tariff according to program of
holiday tariff, seasonal tariff and weekly tariff.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 62
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Meter can store maximum 16 different daily tariffs.
Daily tariff includes the following information:
z Daily tariff table code.
z It is applied to the status data (1 valid, 0 invalid) for 8 tariff time shifts, and maximum 24
starting time (hh: mm). The information input will be valid from midnight to the specified time
at midnight.From 00:00 to 24:00, each time shift will start from the ending time of the last shift.
When it is 0 second of every minute, in accordance with the status data of present time shift
and tariff time shift in executed daily tariff table, the energy meter can define the tariff which is
for current time shift measurement, and calculate forward /reverse active energy
measurement from starting time to ending time within this time shift, and save them in the
corresponding register so as to realize the function of TOU measurement.
Daily Tariff Table(8 tariffs/24 time shifts)
16 Daily Tariff Tables
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 63
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Sample of Daily Tariff Table design:
Tariff code corresponding relations:
TOU1:00H
TOU2:01H
TOU3:02H
TOU4:03H
TOU5:04H
.
TOU12:0FH
Each daily tariff is 73 bytes.
The first byte of daily tariff code: 7XH X is daily tariff table code Range: 1-F
Daily tariff values are starting from the second byte. The basic unit of Daily tariff table is of every 3
bytes.
The unit of Daily tariff is hh:mm; Tariff code.(72 bytes unit in total)
12 Daily tariff in total is 16X73=1168 bytes.
The minimum time shift is 15 minutes, and should be larger than the setting of demand
calculation period.
5.4.2 Weekly Tariff
According to working day and weekend day, daily tariff codes for a week can be defined.Weekly
tariff defines effective day tariff table types on variety of occasions from Monday to Sunday. The
administrative department can store maximum 12 different weekly tariff tables. It can set different
daily tariff tables for every day of a week to differentiate each other (such as difference between
working day and weekend). It can also set the same daily tariff code to use the same type of tariff.
Weekly Tariff Table
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 64
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
There are 8 bytes for each weekly tariff. The first byte is the number of weekly tariff , while for
the last 7 bytes, each byte is in accordance with the number of daily tariff from Monday to
Sunday.
8X12=92 bytes in total.
5.4.3 Seasonal Tariff
Based on the cost of electricity generation and the anticipation on the electricity market, different
weekly tariff adopted in each season can be defined.Seasonal tariff defines the choices of weekly
tariff table in practical use. Energy administration department could define up to 12 seasonal
tariffs in different periods and situations. So the administration can work on the seasonal
differences of tariff shift. The seasonal tariff table is annually repeatable as the year factor is not
taken into consideration. The simplest situation is that there is only one weekly tariff number and
the unique tariff number is used from January 1st, (Seasonal tariff is like year time zone. State
Grid demands 2 time zones in a year.)
Seasonal Tariff Table
Starting from Jan.1st, the starting date (Month and Date) of each season is the ending date
(Month and Date) of the last season. Sequence in ascending order is MM/DD.
4X12=48 bytes in total.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 65
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
5.4.4 Holiday Tariff
In public holidays and festivals, the administration can select the particular daily tariff table in
special days. So the particular tariff forms holiday tariff.
Holiday tariff defines different daily tariff in public holidays and festivals. Meter can store up to 100
special days. For regular holidays (same day for every year, for example Jan 1st ), a special code
“A1H” can be set. In the host computer or HHU, MMDD can be set to show this day is valid for
every year. For the unfixed holidays (different day in different year, for example Easter Day or
Chinese Spring Festival), data should be input each year in the term of YYMMDD. Maximum 50
Festivals can be set in this type of meter as well as there are 50 tables in this meter. Estimated
validity period should be arranged and the time shifts of the festival tariff table should be modified
in practical use.
Holiday Tariff Table
Daily Tariff Table Serial
No. (71H-78H)
The basic unit is 5 bytes, the first byte is the number of holiday tariff, the second, third and fourth
bytes are respectively YY/MM/DD of the holidays. The fifth byte is the number of daily tariff, all
5X50=250 bytes in total.
5.4.5 Tariff Rate Table
Every tariff is in correspondence with a tariff rate. There are 8 tariffs. Tariff rate consists of tariff
number and price. All together is 8X5=40 bytes.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 66
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
5.4.6 Confirmation Valid Daily Tariff
At 00:00:00 each day, the energy meter will select proper daily tariff number from Holiday Tariff
table, Seasonal Tariff table and Weekly Tariff table, then the daily tariff table of that day can be
selected to RAM from ERROM. (For the energy meter which RAM is relatively small, time Daily
tariff table of the present and the next period can be put in). At 0 second each minute, the energy
meter will process the period of daily tariff, according to the present daily tariff table, to conduct
tariff measurement control. It can be referred as follow:
5.4.7 Tariff Table Switching
As the changes of resource and the energy supply, as well as electricity generation,transportation
and the electricity cost, tariff should be changed accordingly. Due to big quantity of energy meters
and the dispersion of locations, it’s impossible to modify the tariff for all meters at the same time.
In order to solve this problem, a set of spare tariff which is pre-stored in the meter is applied.
Utility can set activation date for the spare tariff. When the spare tariff is activated, meter will start
to use new seasonal, weekly, daily and holiday tariff. After activation, the previous tariff will be no
longer valid. In such way, utility can upload spare tariff to meters and on activation date all meters
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 67
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
will execute new tariff.
Spare tariff and its activation date will be saved temporarily in the meter, after activation, the old
tariff information will be deleted and meter will be able to accept another set of spare tariff.
5.5 Step Tariff Measurement Function
The step tariff rate consists of units as follow::
S/N.
Tariff Basic Unit
1
7 step tariffs
2
8 step tariffs
3
2 step tariffs
Byte
Remark
This rate is combined active rate
2X65=130
Energy:4 bytes; Unit Price: 4bytes; Code
Number: 1 byte
4
2 Seasonal Tariff
2X3=6
Step Tariff Table
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 68
Three Phase Keypad Prepayment Energy Meter
Shenzhen Inhemeter Co., Ltd
(Plug-in Module Type)
www: inhemeter.com 69
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
There is one set of spare Step Tariff table. It will activate on the appointed date;
The activation date and the new step tariff will be stored in the meter temporarily, after activation,
the old tariff information will be deleted and meter will be able to accept another set of spare tariff.
The new Step Tariff Table’s temporary memory is 136 bytes + the year and month of usage.
The step tariff is 272 bytes in total.
5.6 Tariff Data Settings
The tariff (holiday tariff, seasonal tariff, weekly tariff, daily tariff and spare tariff) can be
programmed by the tariff setting software organized by the R&D Center of INHEMETER. After
setting and confirmation, communication data module will be generated in accordance with
energy meter’s communication protocol, and data can be loaded to the meter through follows:
A. Infrared (HHU or PC) local setting
B. RS-485 communication port (HHU or PC) local settings
C. Remote batch setting
When it is not factory settings (such as on site modification or user preference):
A: To modify tariff and electricity rate by local communication, operator needs to turn on the
programming switch (with seal protection), which needs password authentication.
B: To modify tariff and electricity rate by remote communication, operator must go through
authorization and password authentication via data management center, it can also go through all
or selected meter type/meter No. to modify the tariff and electricity rate in batch mode. Meanwhile
meter must be allowed in remote programming mode.
6 Special Functions
6.1 Load Cut off Function
There is a built-in relay for DTZ1513 three phase four wire (direct connected) keypad prepayment
meter with replaceable communication module. According to user’s credit (balance amount),
tamper status, load control status and voltage of power supply, it can control the power.
Relay status indication on LCD
“
” It means built-in relay is connected, and power load is available.
“
”
It means built-in relay is disconnected, and power load is not available
Notice: If the relay status indication on LCD does not match the real status, it maybe malfunction,
and user should inform electricity management department to check.
6.2 Zero Credit Power Off
When remaining credit in the meter is zero (except overdraw, friendly data/time), the built-in relay
will output control signal immediately and control outside HV/LV breaker to disconnect, and
realize power off. After user recharging, meter will output automatic power supply recovery
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 70
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
information and control outside HV/LV breaker to connect, realize power recovery.
6.3 Load Control Function
DTZ1513 direct connected prepayment keypad energy meter has load control function and
complies with the load control algorithm method specially mentioned in SCSSCAAA9 item 7.7.2
of Eskom.
Notice: Meter load control function cannot be used to protect load security protection. It is
normally used to control the users average load upper threshold in a associated area. (mainly
concerned with grid security, cable loss reduction and power supply cable load limit). Load
connected to CT/PT means primary winding load (Transformation ration algorithm)
Automatic delay recovery mode after over load power off.
A. If one phase load is beyond load threshold value 132.000kWh (OBIS code 21.35.0 data
item), the alarm will sound and LED indicator will flash, and LCD on MCU/CIU will display
overload information, and switch to display on real time present overload phase power.
Above 2 LCD display by shift, which means it is in overload status and current load is 140.80kW.
B. If the consumption load is beyond load threshold for more than 45 seconds, the built-in relay
will cut off power at 45th second. After 150 seconds, the relay will connect automatically (power
supply will not work during the 150 seconds). And LCD on MCU/CIU will display remaining time
for power recovery (unit: second; it means remaining lock time. The remaining lock time will
reduce by a second interval).
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 71
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
If the user does not low down the consumption load, which is beyond threshold value, above
process will repeat (Power off- Delay recovery- Power off).
C. Within 30 minutes, if tripping occur for 5 times, meter will cut off power supply and last for 30
minutes. And power supply will automatically recover after 30 minutes. LCD will display remaining
lock time, it will reduce by one second interval. And LCD will display power at the last power off.
The recovery time after 5 tripping within 30 minutes can be programmable. Min. time period is
5minutes. It is default 30minutes at factory for this project.
Current load control threshold factory setting is : 22.000kWh
Notice: When overload tripping occurs constantly, the user should check the power consumption
load , and contact electricity company to modify load threshold.
Pressing key recovery mode:
If the configuration status flag 1 is set as key-pressing and no time interval recovery , the meter
will display the following symbols. If press the key, power will be recovered.
If times of overload power-off are more than allowed threshold value
D. If times of overload power-off are more than allowed threshold value which preset (check
TOKEN 201), the meter cannot recover power supply automatically after overload power-off. The
user should inform electricity company and apply for load threshold change TOKEN or tamper
record clearance TOKEN, and meter can recover power supply after TOKEN inputting.
Optional function: ① Overload is judged based on active power or apparent power which is
decided by meter prepayment status word. The default is active power at factory.
② Options for power supply recovery after overload power off: automatic
delay recovery or key-press immediate recovery.
③ Please check prepayment configuration instruction for more information.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 72
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
6.4 Protection against Abnormal Grid Voltage and Phase Missing
Keypad prepayment meter is designed for protection against voltage abnormity of grid and phase
missing so as to reduce damage to electronic appliances.
6.4.1 Automatic Power Off
A: Energy meter will automatically power off (cut off subscriber circuit), and indicate power-off
status and display corresponding phase voltage value when grid phase voltage is lower than <
threshold
value of voltage under condition of low voltage power-off, 213 >, and keeps the situation for 30
seconds; or grid phase voltage is higher than < threshold value of voltage under condition of
overvoltage power-off, 212 >, and keeps the situation for 3 seconds.
Lo_UoL: power off due to low voltage
108.00V: detected voltage before power off
OUEr_UoL: power off due to over voltage
306.70V: detected voltage before power off
Note: It’s programmable to set threshold value of grid phase voltage abnormity, and it’s available
to check threshold value by short code.
212: threshold value of voltage under condition of overvoltage power-off
213: threshold value of voltage under condition of low voltage power-off
B: when the grid missing one or two phases for 30 seconds, the meter will diagnose it as phase
missing. If status flag 231 has been set as trip when phase missing, the internal relay will
disconnect.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 73
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
6.4.2 Recovery of Power Supply
A: Automatic recovery of power supply:
If the voltage falls between 150V AC~264V for 5 minutes, energy meter would automatically
restore power supply.
B:Manual recovery of power supply:
If the voltage fall between 150V AC~264V, before the automatic restoration, user can connect the
power supply manually through the CIU.
Note: There will exist not more than ±3V error value in meter for above voltage range
determination due to such serious voltage deviation.Energy meter will cancel protection against
low voltage power-off if threshold value under condition of low voltage power-off set as zero;
Energy meter will cancel protection against high voltage power-off if threshold value under
condition of high voltage power-off set higher.
6.5 Anti-tamper against Cover Opening Function
Energy meter has activated anti-tamper against cover opening (terminal cover or upper
meter cover) function after delivery from factory.
6.5.1 Energy Meter will instantly power off once the terminal cover
or upper cover is opened under condition of power- on.
Energy meter shall recover power supply after upper cover and terminal cover are taken to
original position, and input corresponding TOKEN while meter still remains balance amount and
other problem is free.
6.5.2 Tripping at terminal cover opening under condition of
power-off(need to be activated)
Activation method:
Meter keeps continuous power supply for more than 2 hours after delivery from factory; or
accumulative power consumption with more than 1okWh.
Activation status: Terminal cover opening under condition of power-off, and tripping at recovery of
power supply. Meter will recover power supply only after subscriber takes back terminal cover to
original position, and input corresponding TOKEN while meter remains balance amount and other
problem is free.
Inactivation status: If terminal cover opening under condition of power-off, and meter will not
power off when power supply recovery ( terminal cover has been closed). Such activation will not
be applied when delivery from factory as it’s more convenient for electricity company to test and
install meters.
Cover opening indication icon:
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 74
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
① continuous lighting: there used to be cover opening event, and terminal cover has been
closed and built-in relay tripping.
② flashing: there used to be cover opening event, and terminal cover is still open.
Note: It’s decided by meter’s prepayment configuration flag to allow cover opening detection
under condition of power-off or power-on.
6.6 Prewarning & Warning Function
This function is applied to prompt subscriber that the balance amount is not sufficient, and
recharge is necessary; otherwise, meter will cut off power supply once balance amount uses up
soon later, and will bring subscriber inconvenience. Furthermore, this function provides
subscriber choices for settings. On the one hand, subscriber can reset threshold value of balance
amount for pre-warning/ warning according to actual situation; on the other hand, subscriber can
reset audible warning or not.
6.6.1 Prewarning Function
When balance amount is lower than threshold value for pre-warning(OBIS code C.51.12), meter
will sound warning and yellow LED indicator will flash, and icons
、
will alternatively flash
on LCD screen display to prompt subscriber to purchase electricity. It’s programmable to set
threshold value for pre-warning and its relevant function by inputting code: 4547 8xxx, available
value is from 1-999$. CIU screen will display “Accept” ,and indicate successful settings.
Prewarning threshold value for this project is: 30.00$
Warning symbols instructions:
„ Red warning indicator keeps continuous lighting ----- it means balance amount is lower
than 30$;
„ Red warning indicator flashes ----- It means balance amount is lower than 20$;
„ Red warning indicator flashes and sounds warning ----- It means balance amount is
lower than10$;
6.6.2 Warning Function
When balance amount is equal or lower than threshold value (display code 206), meter sounds
warning, yellow LED indicator keeps continuous lighting, and meter’s internal replay disconnects
to cut off power supply. Icons
、
will alternatively flash and icon
will display on
LCD screen. subscriber has to press blue key on meter keypad for recovery of power supply if
any inquiry. It’s programmable to set threshold value for warning by inputting code: 4547 9xxx,
available value is from 0-999$. CIU screen will display “Accept” ,and indicate successful settings.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 75
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Current warning threshold is: 0.00$
Note: Threshold value for warning must be lower than threshold value for pre-warning; there will
no corresponding warning or pre-warning if threshold value for warning or pre-warning is set as
zero. It’s very convenient for subscriber to programme the settings and relevant function.
6.7 Anti-over Purchasing Function
The meter can set maximum allowable credit (display code 210 data item). The TOKEN code will
be rejected if meter credit is more than allowable upper limit credit when recharge TOKEN is
effective. Recharge operation will only work normally when the sum of meter available credit and
purchase credit is less or equal to user maximum allowed upper limit credit.
Current maximum accumulative credit is: 999999.99$
6.8 Anti-tamper for Reverse Power Consumption
Meter will cut off power supply circuit when it detects reverse power consumption.
L line and N line are reverse in terminal connection. Meter will detect this event, and will
automatically cut off power supply if reversing event keeps over 60 seconds. Meter will
automatically recover power supply 5 minutes later when grid resumes work in proper way; or
press keypad to recover power supply within 5 minutes when grid resumes work in proper way ( it
will be invalid to press in the first minute, and valid since the second minute).
Note: It’s selected by prepayment configuration word to cut off power supply or not when reverse
power consumption event occurs.
Default setting at factory for this project: meter will cut off power supply circuit when
reverse power consumption event occurs.
6.9 Bypass Tampering Disconnection
When energy meter detects by pass tampering event, (over preset bypass threshold), power
supply would be disconnected.
Note: By pass tampering disconnection function is set by energy meter prepayment settings.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 76
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Current factory setting is disconnection when by pass tampering is detected
6.10 Neutral Loss Disconnection Function
When energy meter detects neutral loss, meter would disconnect power supply circuit.
Note: Neutral loss disconnection function is programmable by energy meter prepayment
configuration.
Current factory setting has neutral loss disconnection function
6.11 Energy Meter Overdraft Function (Optional)
Overdraft( default settings at factory will not allow overdraft): Meter will support overdraft.
Metering administration department or electricity utility can apply such function to subscribers
who have higher credit rating. Overdraft will be allowed when threshold is not zero(short code 211)
Overdraft amount is equal to threshold value( short code 211). Threshold value consists of six
integers and two decimals.When overdraft is allowed(threshold setting - short code 211), and
balance amount is lower than threshold for pre-warning or balance amount is zero which results
in power-off, subscriber can input short code 8989 8686 to activate overdraft function so as to
continue power supply until available overdraft amount become zero.
Note: Overdraft function is temporary measure for subscriber when it’s not convenient to
purchase electricity. subscriber should go to purchase electricity ASAP when overdraft is working.
Current factory setting has no overdraft function
6.12 Minimum Guaranteed Load Control Function (Optional)
Minimum guaranteed load control function (basic guaranteed load--energy meter does nott allow
this function in default setting). DTZ1513 three phase four wire (direct connected) keypad
prepayment energy meter could support minimum guaranteed load control function. For meter
management departments or vending utilities who have social responsibility and responsibility to
ensure users basic daily consumption, meter could be set with minimum guaranteed load control
function in local region or certain users. For users with minimum guaranteed load control function,
when credit balance is zero, if users’ load is lower than the setting minimum guaranteed load
threshold, the user could still on power, meter won’t cut off power supply until the load is over the
setting minimum guaranteed load limit. Meter would cut off power supply as it is over load limit
according to over load control function.
Current factory setting is no minimum guaranteed load control function
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 77
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
6.13 Over Current Threshold Disconnection Function (Optional)
When one- phase current is over threshold(100A)( check short code 204), the meter will sound
warning and yellow LED indicator will flash; meanwhile, LCD will display overload current
information, and timely shift to display present real-time current.
If current value keeps higher than threshold (100A)within 45 seconds, meter built-in relay will cut
off
power supply at the 45th second, and power-off will The last 150 seconds; then built-in relay will
automatically recover power supply(subscriber can not manually recover power supply within 150
seconds). Meanwhile, LCD will display remaining time information for recovery(unit: second; it
means locked remaining time. Remaining time will descend by interval of 1 second based on the
locking state). And LCD will timely shift the display for overload real-time current before power-off.
If subscriber doesn’t low down consuming current, and continue to allow current over threshold,
the process will repeat. Meter will automatically recover power supply after 30 minutes delaying
provided that overload current results in 5 times successive tripping within 30 minutes. subscriber
can not manually recover power supply during 30 minutes delaying. In the locking time, LCD will
display locked remaining time which will descend by interval of 1 minute; meanwhile, LCD will
display the current at the last time power- off .
It’s programmable to set delaying time for recovery after 5 times successive tripping; Minimum
setting value: 5 minutes; default value at factory: 30 minutes.
Current factory setting is : 0A, no request for this function!
Note: when meter suffers from successive tripping with overload current, subscriber should check
the current, and contact electricity company to modify threshold so as to keep subscriber’s
normal power consumption.
6.14 Special Time Power Guarantee Function
Energy meter has function of special time or day for friendly none-disconnection power supply.
Evening (or programmed time period) with none-disconnection power supply(optional): DTZ1513
three phase four wire (direct connected) keypad prepayment energy meter supports this function.
Metering administration department or electricity utility can apply this function to some specified
subscribers for social responsibility and people’s basic power consumption guarantee.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 78
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Special holiday/weekend with none-disconnection power supply(option): DTZ1513 three phase
four wire (direct connected) keypad prepayment energy meter supports this function. Metering
administration department or electricity utility can apply this function to some specified
subscribers for social responsibility and subscriber’s basic power consumption guarantee.
Time period with none-disconnection power supply:
240 starting time
241 ending time
Weekend with none-disconnection power
none-disconnection power supply each week
supply:
242
Holidays with none-disconnection
none-disconnection power supply.
supply:
25
power
refer
to
weekend
with
specified
holidays
with
6.15 Post Payment /Prepayment Mode Shift Function
DTZ1513 three phase four wire (direct connected) keypad prepayment energy meter
has function of shift between post-payment and prepayment. The shift is realized by prepayment
configuration word.
Prepayment configuration flag -item 230 can be programmed through optic commutation
port, RS-485 or AMI system to realize the shift after it’s allowed and authorized.
Prepayment metering(or shift from post-payment to prepayment); accumulative power
consumption keep the same, but built-in relay will disconnect circuit when balance amount is
zero.
Post-payment metering- billing settlement mode(or shift from prepayment to post-payment);
accumulative power consumption keep the same, but built-in relay will not disconnect circuit
when balance amount is zero.
6.16 TOU Multi-tariff / Step Tariff Shift Function in Credit(money)
Settlement Mode (expandable)
DTZ1513 three phase four wire (direct connected) keypad prepayment energy meter
is allowed to shift between TOU multi-tariff and stepped tariff in credit settlement mode. Such shift
will be realized through setting prepayment status word.
After permission as well as authorization, you can set the prepayment configuration status word
230 to realize such shift through optical communication port, RS485 communication port or AMI
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 79
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
system.
6.17 Monthly Basic Power Consumption Setting (expandable)
It’s programmable to set amount for Monthly Basic Power Consumption. If amount for actual
monthly power consumption is less than amount for Monthly Basic Power Consumption, meter
will automatically count electricity charge as amount for Monthly Basic Power Consumption(but
D-value between two kinds of amount will not be calculated to amount for actual monthly power
consumption. If amount for Monthly Basic Power Consumption is set as zero, this function
doesn’t work.
6.18 Parameters and Status Flag Configuration
DTZ1513 three phase four wire (direct connected) keypad prepayment energy meter has energy
meter prepayment parameters and status flag configuration function so as to maintain ideal
performance of energy meter.
This project three phase four wire (direct connected) keypad prepayment energy meter’s setting:
Display code
Default factory
setting
Data item content
200
Threshold for load control
201
Number of times for
threshold disconnection
202
Recovery time for overload power-off
203
Load
threshold
for
minimum
guaranteed power consumption
204
Current threshold for over current
disconnection
205
Disconnection
threshold
unbalance of phase power
206
Pre-warning threshold for balance
credit
207
Warning
credit
208
Billing date
209
Buzzer alarm interval
210
Overflow threshold
211
Overdraft threshold
212
Voltage threshold for over voltage
disconnection
threshold
for
Data
unit/implication
overload
when
balance
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 80
Three Phase Keypad Prepayment Energy Meter
213
Voltage threshold for low voltage
disconnection
214
Temperature threshold for
temperature disconnection
over
215
Warning threshold for by
tampering (6.25% 12.5%)
pass
230
Prepayment configuration status flag
1
231
Prepayment configuration status flag
2
(Plug-in Module Type)
Prepayment status flag configuration for this project is as follows:
Meter prepayment status flag 1 configuration instruction: Item 230
Prepayment status flag 1 configuration--Item 230
No.
Displays
Function
Instruction
0
-------1
Cover-open
detection
when power off
1: Cover-open detection when power off valid
(Activation required)
0: Cover-open detection when power off
invalid
1
------1-
Overload power recovery
mode
1: Press key manually restore
immediately
0: Overload power recover mode
2
-----1--
Power off disconnection
mode
1: Built-in relay disconnects when power off
0: Built-in relay not disconnects when power
off
3
----1---
Metering payment mode
1: Post payment mode
0: Prepayment mode
4
---1----
Overload detection mode
1: Apparent power
0: Active power
5
--1-----
Money settlement mode
1: Step tariff mode
0: Multi-tariff mode
6
- 1- - - - - -
Reverse
energy
disconnection or not
1: Reverse energy disconnection
0: Reverse energy no disconnection
7
1- - - - - - -
By
pass
tampering
disconnection or not
1: By pass tampering disconnection
0: By pass tampering no disconnection
power
Default factory setting meter prepayment status flag 1 for this project: 1100 0001
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 81
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Prepayment status flag 2 configuration--Item 231
Prepayment status flag 2 configuration--Item 231
No.
Displays
0
-------1
1
------1-
2
-----1--
3
----1---
Function
Phase loss power off
1: Loss phase disconnection;
0: Loss phase disconnection invalid
Reverse phase sequence
1: Reverse phase sequence disconnection;
0: Reverse phase sequence disconnection
invalid
power off
Payment deduction for
reactive energy
Magnetic interference power
off
Power off for
4
---1----
Instructions
over-temperature inside
1: Average amount deduction mode per hour;
0: real time reactive energy deduction mode
1: Magnetic field interference disconnection;
0: Magnetic field interference disconnection
invalid
1: Over temperature limit disconnection;
0: Over temperature limit disconnection
meter
5
--1-----
Date display mode
1: DDMMYY
0: YYMMDD
6
-1------
Daylight-saving time
1:valid 0:invalid
7
--------
Reserved
Default factory setting meter prepayment status character 2 configuration: 0010 0001
6.19 Negative Balance Amount Display
If balance amount is zero, and built-in relay suffers from breakdown, and still keeps
connected( subscriber continue to consume power); meter still makes normal measurement.
Under this situation, meter will display negative value for balance amount.
6.20 Available Balance Amount Step Diagram Indication
Energy meter LCD screen displays balance amount step digram indication
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 82
Three Phase Keypad Prepayment Energy Meter
①
②
③
Four bars are
lighting
Three bars are
lighting
Two bars are
lighting
(Plug-in Module Type)
④
One bar is
lighting
⑤
No bar is lighting,
framework of ladder
diagram is lighting/
Available amount( balance amount) indication according to pre-warning / warning
threshold( default at factory)
1 Four bars are lighting when available amount is more than pre-warning threshold, refer to
diagram①
2 Three bars are lighting when available amount is less than pre-warning threshold, but more
than warning threshold +(pre-warning threshold - warning threshold )/2, it prompts subscriber to
purchase electricity; refer to diagram ②
3 Two bars are lighting when available amount is less than warning threshold + (pre-warning
threshold -refer to diagram③.
4 One bar is lighting when available amount is less than warning threshold, but more than 1/2 of
warning threshold, it prompts subscriber to purchase electricity; refer to diagram ④.
5 None bar is lighting and framework of ladder digram is lighting when available amount is less
than 1/2 of waring threshold but not zero; it prompts subscriber to purchase electricity, otherwise
it will be power-off; refer to diagram ⑤.
6 None bar is lighting and framework of ladder digram is flashing when available amount is zero,
it means internal replay is disconnected and stops power supply(exceptions for overdraft,
minimum load power supply, evening/holidays power-on); refer to diagram⑤.
6.21 Not Available to Program or Modify Meter Number(Serial
Number) after Delivery from Factory
Meter cannot be programmed or modified when it’s on processing status after delivery from
Factory.
6.22 Load Profile Record
DTZ1513 three phase four wire (direct connected)keypad prepayment energy meter has
has load profile record:
record 8 channels, 1920 measurement values with time scale per channel. It’s convenient for
electricity company to check power consumption situation.
Time unit: hh: mm
Minimum time shift: 15minutes(00:15)
Max time shift: 1 day(24:00)
Record saving space details:
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 83
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Channel 1
channel 2
channel 4
15 mins
80 days
40 days
20 days
30 mins
160 days
80 days
40 days
60mins
320 days
160 days
80 days
120mins
640 days
320 days
160 days
Eight channels definitions as below,
Serial No.
Parameter
1
2
3
4
5
6
7
active power
8
Combined phase/separated
phase reactive energy
9
Combined phase/separated
phase apparent energy
Remark
reactive power
apparent power
power factor
Phase voltage
Phase current
Combined phase/separated
phase active energy
It’s available to read load profile record data through meter communication port.
6.23 Available Days Indication (Optional)
Meter can estimate available days for purchased electricity according to average load of
subscriber’s power consumption. It will display in available time item(display code 300), display
unit is dd:hh, Max indication time is 99 days 24 hours.
It adopts calculation based on balance amount and Maximum Demand. It adopts calculation by
last month MD when current month MD is zero; it adopts calculation by load threshold when last
month MD is zero.
6.24 Meter Display and Token Entry Function without Power
(Optional)
DDZ1513 single phase keypad prepayment energy meter has Power- off Display and TOKEN
Input functions.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 84
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Meter can display power consumption information (balance amount), or user can check relevant
information by inputting short code through keypad when meter is power off. But it’s not available
to check it by manual scroll display.
User can input TOKEN on meter keypad which include activation TOKEN, recharging TOKEN,
and technique TOKEN when meter is power off. But it’s available to operate meter state
exchange or relay connection/ disconnection, etc only after meter is power on.
6.25 Monthly Energy Consumption Billing Date
Meter can be programmed for monthly settlement day according to electricity company
requirement. Default setting is the last day of each month..
6.26 Over Temperature Disconnection Function (Optional)
When meter detects internal temperature over threshold( item 214: 95℃ default at factory), will
diagnose it as over temperature, and buzzer will sound warning. If this status keeps over
30seconds, meter will automatically cut off power supply; meter will automatically resume to
power on 5 minutes later or manually press keypad to resume power supply within 5 minutes if
internal temperature recovers as usual (lower than threshold). Root for over
temperature:overload or terminal connection trouble.
6.27 Magnetic Interference Disconnection Function (Optional)
When meter detects magnetic interference, it will display icon as below, and buzzer will be
alarming. Furthermore, meter will power off when it keeps detecting magnetic interference for 10
seconds; and meter will recover 5 minutes later after magnetic interference stops. Meter will
record that as event.
6.28 Remote Upgrading
DTZ1513 three phase four wire prepayment energy meter will realize on-line software upgrading
locally or remotely to supplement or improve meter functions.
6.29 Meter Running Status Inquiry Function
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 85
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
User can check running state of DTZ1513 three phase plug-in prepayment energy meter by
keypad, local communication port or remote communication method.
■ Meter Running Status Flag 1(shot code 303)
Sr.No.
0
1
2
3
4
Definition of running status flag
Remark
Without balance amount (balance
amount is zero).
Warning state
Pre-warning state
Relay state
Without balance amount (balance
amount is negative).
■ Meter Running Status Flag 2(meter fault event short code 304)
Sr.No.
0
1
2
3
4
5
6
Definition of running status flag
Remark
meter control circuit fault
Clock battery voltage is low
Internal register fault
Internal clock fault
Overdraft
Meter software upgrade
Meter clock calibration
■ Meter Running Status Flag 3(cover open counter event
Sr. No.
0
1
2
short code 305)
Definition of running status flag
Remark
Open meter terminal cover
Open meter cover
Open meter communication module
cover
■ Meter Running Status Flag 4(grid event 1 short code 306)
Sr. No.
0
1
Definition of running status flag
Remark
Active power reverse
Serious unbalance of current (more
than 6.5%)
■ Meter Running Status Flag 5 (grid event 2 short code 307)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 86
Three Phase Keypad Prepayment Energy Meter
Sr. No.
0
1
2
3
4
5
6
7
Definition of running status flag
(Plug-in Module Type)
Remark
Voltage loss
Low voltage
Over voltage
Current loss
Over current
Phase loss
Current loss
Neutral loss
■ Meter Running Status Flag 6(grid event 3 short code 308)
Sr. No.
Definition of running status flag
Remark
0
1
2
Reverse phase sequence for voltage
3
Three phases’ current are in
unbalance condition
4
5
6
Over demand
Reverse phase sequence for current
Three phases’ voltage are in
unbalance condition
Power factor is beyond the lower limit
Reverse split phase sequence for
active power
6.30 Date Display Mode Shift Function
DTZ1513 three phase keypad prepayment energy meter is capable of converting date display
mode through prepayment configuration status flag. The factory default display mode: YYMMDD
Upon permitted and authorized, through optical, RS485 communication port or AMI system,
meter prepayment configuration status flag 231 can be changed, and the date display mode can
be: DDMMYY
6.31 Real Time Clock Daylight Saving Time and Winter Time
Automatic Shift
DTZ1513 three phase keypad prepayment energy meter is capable of converting daylight saving
time and winter time. Upon permitted and authorized, through optical, RS485 communication port
or AMI system, once conversion date and time of daylight saving time and winter time is
configured, automatic conversion between them can be achieved.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 87
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
7 Historical Data Transfer & Storage and Event Recording
Function
7.1 13 Months Monthly Energy Consumption Data Recording
Meter will save The last 13 months monthly historical metering data,and it’s programmable for
monthly(billing) settlement date& time (freezing time). Default at factory for freezing time is 24:00
hour, end of each month.
A)Settlement(monthly) for power consumption at billing period; power consumption at different
tariff period.
B) Settlement(monthly) for amount at billing period; amount at different tariff period.
C) Settlement(monthly) for MD and it’s date & time .
D) Inquiry for 13 months monthly power consumption data and amount data by inputting short
code.
E) Monthly energy consumption inquiry code : 401-413
7.2 45 Days Daily Energy Consumption Data Recording
Meter will save recent 45 days daily power consumption data. Default settlement time is 00:00.
a) Power consumption on settlement day; power consumption by TOU
b) Consumption amount on settlement day; consumption amount by TOU
c) Check daily power consumption and corresponding amount data for 45 days by
inputting short code
d) Short coed for daily power consumption data inquiry : 451-- 495
7.3 Meter Tripping Event Recording
Meter will record last 20 power-off events, and user can check last 10 meter tripping events by
short code. Record content as below,
„ Accumulative tripping times
„ Tripping date/time
„ Recovery date/time after tripping
„ meter tripping reason flag 1
Sr. No.
Definition of Running state type flag
0
Balance amount is zero.
1
Warning
2
Over load
3
Over current
4
Un-activation
Shenzhen Inhemeter Co., Ltd
Remark
www: inhemeter.com 88
Three Phase Keypad Prepayment Energy Meter
5
Remote control
6
Fault by meter self-check
7
Neutral line failure
„
Sr. No.
meter tripping reason flag 2
Definition of running state type flag
0
Over voltage
1
Low voltage
2
Reverse
3
Open terminal cover
4
Open meter cover
5
Bypass tamper
6
Phase loss
7
Phase reverse
„
Sr. No.
0
1
(Plug-in Module Type)
Remark
meter tripping reason flag 3
Definition of running state type flag
Remark
Over temperature
Strong magnetic interference
7.4 Power Failure/Off Event Recording
Meter will record last 20 grid power-off events, and user can check last 10 grid power-off events.
Record content as below:
„ Grid power-off accumulative times
„ Date/time of Grid power-off occurrence
„ Recovery date/time after grid power-off
„ When grid power--off, energy meter can send this information to main station
management system automatically to achieve the automatic upload when power-off event
to solve problems in time.
7.5 Special Event Recording
Meter will record last 50 special events, and user can check last 10 special events by short
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 89
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
code(351-360). Record content as below,
„ 001-Occurrence date of special events
„ 002-Occurrence time of special events
„ 003-Event index of special events
Index No.
Definition of Event Status Flag
0
Meter control circuit fault
1
Low clock battery voltage
2
Internal register fault
3
Internal clock fault
4
Overdraft
5
Meter software upgrade
6
Meter clock calibration
Remark
7
„ 004-Special event status flag 2(cover open event), User can distinguish event types
according to it.
No.
Definition of Event Status Flag
0
Open terminal cover
1
Open meter cover
2
Open communication module cover
3
MD restoration
Remark
Special Event status flag 3(grid event 1). User can distinguish event types according to
„
it.
No.
Definition of Event Status Flag
0
Active power reverse
1
Serious unbalance of current (more
than 6.5%)
Remark
Special Event status flag 4(grid event 2). User can distinguish event types according to
„
it.
No.
0
1
2
3
4
5
6
7
Definition of Event Status Flag
Remark
Voltage loss
Low voltage
Over voltage
Current loss
Over current
Phase loss
Current loss
Neutral Loss
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 90
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Special Event status flag 5(grid event 3). User can distinguish event types according to
„
it.
No.
Definition of Event Status Flag
Remark
0
1
2
Reverse phase sequence for voltage
3
Three phases’ current are in
unbalance condition
4
5
6
Over demand
Reverse phase sequence for current
Three phases’ voltage are in
unbalance condition
Power factor is beyond the lower limit
Reverse split phase sequence for
active power
7.6 Electricity Purchasing Information
Meter will record last 15 purchasing and recharging events, and user can check last 15
purchasing and recharging events by short code. Record content as below,
b) Total recharging times
c) Recharging amount
d) Recharging TOKEN value
e) Corresponding TID code for recharging TOKEN
f) Recharging date/time
User can check last 10 recharging events.
Inquiry code as below,
Display
item code
Content
Display
method
Data unit/meaning
500
Accumulative
recharging times
XXXX
Four digits, Max. Record: 9999 times
501
Last recharging
event
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
502
Last
2nd
recharging events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
503
Last 3rd
recharging events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
504
Last
4th
recharging events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
505
Last5th recharging
events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
506
Last 6th
recharging events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 91
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
507
Last 7th
recharging events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
508
Last 8th
recharging events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
509
Last 9th
recharging events
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
510
Last 10th
recharging event
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
511
Last 11th
recharging event
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
512
Last 12th
recharging event
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
513
Last 13th
recharging event
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
514
Last 14th
recharging event
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
515
Last 15th
recharging event
display by 7
split screens
Recharging amount, TOKEN value, TID
code, Recharging date/time
Example (check last time recharging event, code 501):
Display No.
Example
Display Statement
1
The first screen:
Display recharging amount for this time( it shows
40.00kWh)
2
The second screen:
Display the first 7 digits of TOKEN for this
recharging(it show TOKEN as: 1162 4313 9811 8735
7405)
3
The third screen:
Display the middle 6 digits of TOKEN for this
recharging(it show TOKEN as: 1162 4313 9811 8735
7405)
4
The fourth screen:
Display the last 7 digits of TOKEN for this
recharging(it show TOKEN as: 1162 4313 9811 8735
7405)
5
The fifth screen:
Corresponding TID code for recharging TOKEN(it
shows 09968569)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 92
Three Phase Keypad Prepayment Energy Meter
Display No.
Example
(Plug-in Module Type)
Display Statement
The sixth screen:
Date for inputting recharging TOKEN(it shows 15th,
Dec, 2011)
6
The seventh screen:
Time for inputting recharging TOKEN(it shows 16:20)
7
7.7 Technical TOKEN Usage Information
Three phase prepayment keypad energy meter can record/ check the using information of last 10
technical TOKENS, and the using events can also be viewed via short codes. Recorded contents
as below:
„ Total using times of technical TOKEN
„ Technical TOKEN type
„ Technical TOKEN value
„ Using time and date of technical TOKEN
Energy meter can view the dealing events of last 10 technical TOKEN, the short codes show
below:
Display
item
code
Data item content
Display
method
Data item unit/ implication
520
Dealing times of
Technical TOKEN
XXXX
521
The last technical
TOKEN event
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
522
The
last
2nd
technical
TOKEN
events
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
523
The
last
3rd
technical
TOKEN
events
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
524
The
last
4th
technical
TOKEN
events
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
525
The
last
5th
technical
TOKEN
event
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
526
The
last
6th
technical
TOKEN
events
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
527
The
Display in 6
Technical TOKEN type, TOKEN value, the
last
7th
Shenzhen Inhemeter Co., Ltd
Four digits, 9999 at most
www: inhemeter.com 93
Three Phase Keypad Prepayment Energy Meter
technical
events
TOKEN
(Plug-in Module Type)
Screens
date and time of TOKEN entered
528
The
last
8th
technical
TOKEN
event
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
529
The
last
9th
technical
TOKEN
events
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
530
The
last
10th
technical
TOKEN
events
Display in 6
Screens
Technical TOKEN type, TOKEN value, the
date and time of TOKEN entered
Technical TOKEN type
Srr.
No.
Technical
TOKEN type
Technical TOKEN definition
1
00
Set Maximum Load
2
01
Clear Credit
3
02
Set Tariff Rate
4
03
Set Dispenser Key
5
05
Clear Tamper Condition
6
06
Phase Pwr. Unbal Limit
Display example (View the last technical dealing event, code No. 520)
Display
No.
Display Example
Display item description
1
The first screen
Display technical TOKEN type
Picture shows 01 which is the TOKEN for clearing
credit.
2
The second screen
Display the first 7 digits of technical TOKEN
(Picture shows TOKEN is:2531 3886 8909 4070
5121)
3
The third screen
Display the middle 6 digits of technical TOKEN
(Picture shows TOKEN is:2531 3886 8909 4070
5121)
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 94
Three Phase Keypad Prepayment Energy Meter
Display
No.
Display Example
(Plug-in Module Type)
Display item description
4
The fourth screen
Display the last 7 digits of technical TOKEN
(Picture shows TOKEN is:2531 3886 8909 4070
5121)
5
The fifth screen
Display TID of recharging TOKEN
(Picture shows 10744439)
6
The sixth screen
Display the date of TOKEN entered
(Picture shows 2011-12-15)
The sixth screen
Display the time of TOKEN entered
(Picture shows 16:20)
7
8 Communication port
Three phase four wire (direct connected) keypad prepayment energy meter consists of optical
(infrared) communication interface, RS-485 interface; PLC module, RF module, GPRS/GSM
module and Zig-bee module are optional. Main control unit and customer interface unit can make
up a split prepayment energy meter; or it can be configurable with concentrator and AMR
software as AMI/AMR system.
8.1 Optical (infrared) communication port
Meter optical (infrared) communication port works as the diagram shows below, it can read the
subscriber’s billing data, such as: total active (reactive/apparent) power consumption, max
demand, the historical monthly power consumption data of last 13 months, the daily power
consumption data of last 45 days and event record. It can also be used to program meter
processing parameters; for example, meter processing parameters and multi tariff/ Stepped
solutions can be set via code administration when it’s allowed. According to the different
requirements of customers, presetting at factory can be done or done by Electricity Company. It
can also be used to upgrade the meter embedded software.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 95
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Notice: The factory setting should be done before delivery.
Inhemeter provides following accessories.
Sr.
No.
Accessory
Name
1
Optical
communicati
on cable
2
3
HHU
:
C5000W
SMARTview
Material
Description
Communication cable between meter
and HHU or computer
Optical HHU,
communication
software.
with charger and
cable,
operation
INHEMETER
Smart
management system software
Shenzhen Inhemeter Co., Ltd
The operation manual for
optical communication cable
_V1.3_ English
Mobile data terminal user
manual
Mobile
data
terminal
introduction
meter
www: inhemeter.com 96
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
8.2 RS-485 Communication Port
RS-485 can be used to read the user’s billing data, such as: total active (reactive/apparent) power,
max demand, the historical total power and data of last 13 months, the daily using data of last 45
days and event record. It can also be used to set the energy meter operation parameters, for
example, the energy meter operation parameters and multi tariff/ TOU can be set via code
management. According to the different requirements of customers, the factory setting can be
done or done by Electricity Company. It can also be used to update the software. It can form a
AMI/AMR network via RS-485 port.
RJ11 port diagram
8.3 TG4A0-01 Three-phase Meter GPRS/GSM Communication
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 97
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Module
Please refer to attachment 1《SG4A0(TG4A0) Data sheet GPRS Single Phase(Three Phase)
Meter Replaceable Communication Module》
8.4 TPDH0-01 Three Phase Meter PLC Communication Module
Please refer to attachment 2《SPDH0(TPDH0) Data sheet PLC Single Phase(Three Phase)
Meter Replaceable Communication Module》
8.5 TRGB0-01 Three-phase Meter RF Low Power-consumption
Communication Module
Please refer to attachment 3《SRGB0(TRGB0) Data sheet RF Low Power-consumption
Wireless Single Phase(Three Phase)Meter Replaceable Communication Module》
8.6 TZ0A0-01 Three-phase Meter Zig-bee Communication Module
Please refer to attachment 4 《SZ0A0 ( TZ0A0 ) Data sheet RF Low Power-consumption
Wireless Single Phase(Three Phase)Meter Replaceable Communication Module》
9 Security Rule
Prepayment keypad energy meter can be installed outdoor, indoor and in switch board, but user
should pay more attention to wiring security and operation conveniences. Energy meter is
strengthened insulation-protection product, and button, panel, LCD and cover are safe in normal
use, and comply with safety and security rule. The safety protection is needed in installation and
operation. Naked conduct and interface is not permitted.
10 Fault Diagnosis
Prepayment energy meter has self-diagnosis function, and long life and adaptability have been
considered in design and manufacture. Fault may appear in some conditions because of
incorrect operation. Please deal with the faults in following table.
Sr.N
o.
1
Appearance
Error Description
Data memory error.
Shenzhen Inhemeter Co., Ltd
Reason or dealing method
Please contact power supply
company for maintenance.
www: inhemeter.com 98
Three Phase Keypad Prepayment Energy Meter
In LCD full screen, some character is not complete
or power indictor flashes, but no display in LCD.
2
(Plug-in Module Type)
It means LCD is broken;
manufacturer or agent should
replace the LCD.
3
LCD cannot display, power indictor and pulse
indictor do not flash.
①Power off or check following
items when power on
②Check wiring
③Check voltage
4
LCD and power indicator can work; pulse indictor
does not flash in power using.
①Check wiring.
②Current is less than 0.1%Ib.
5
LCD works and battery bar flashes.
Change battery.
11 Installation and Operation Instructions
1)
2)
3)
4)
5)
6)
7)
8)
Before installation, meter appearance, manufacturer mark, power company inspection
mark and seal should be checked. The energy meter can be installed inside the meter
box after confirmation.
Before wiring, please check the diagram on the meter terminal cover, and confirm input
and output cables are correspondence with the diagram on the cover. Copper cable or
copper joint is preferred.
In meter wiring, screw on every terminal should be unlocked first, and insert the cable;
the screw should be locked tightly and confirmed be touched well.
After confirm wiring is correct, meter cover should be fixed and special seal from Power
Company should be installed.
Pulling cable is not permitted when arranging cables, to avoid affecting fix on joint. Fix
the cable till it cannot move. Dust and water is not permitted to enter meter.
Supply power to meter and check its work condition. If it works well, record the data; if it
doesn’t work please check the installation, wiring and voltage.
Be careful in the whole meter installation process and avoid dropping or shocking.
In meter installation and operation, be careful about safety and avoid accident.
12 Transport and Storage Instructions
The product shall be transported and stored according to the related rules. No intense impact to
the product is allowable during transportation and unpacking.
The product shall be stored in original packing, the ambient temperature is -35℃~80℃, and the
relative humidity is not more than 100%, and no corrosive gas or harmful material is present.
Natural ventilation is good.
The product shall be stored on shelf in a warehouse and the stacking height shall not be more
than 8 layers.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 99
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
13 Warranty
If the meter does not meet the requirements of technical specifications according to the purchase
contract after leaving factory, and the user follows the manual instruction and manufacturer’s
sealing is in good condition, we furnish free maintenance or replace the defective meter within 24
months from the shipment.
14 Annex Instructions
There are related accessories attached (For each single meter packing) when meter delivery at
factory.
Sr.
No.
Accessory Name
Quantity
Remark
1
Meter MCU Unit
1
2
Meter CIU Unit
1
3
CIU cable
1
4
CIU Unit AA battery
4
5
User Operation Manual
1
6
Keypad meter identification card
1pcs
7
MCU Unit Serial No. Bar Code sticker
3pcs
8
Installation screw
1set
Not included
9
Sealing wire and sealing
1set
Not included
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 100
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
15 Detailed Order Specification
16
INHEMETER SMARTtvend Management System
SMARTvend: INHEMETER smart network power vending management system (Smart Vending
Anywhere) is introduced after years’ of experience of developing IC prepayment energy meter,
keypad prepayment energy meter, SMS prepayment energy meter power vending Management
system and after-payment power vending management mode. It uses B/S and C/S mixing
network construction and network data is under centralized management. Value added service,
various power vending, 7*24 power vending anywhere can be realized by co-operation with the
bank, the network companies, etc. It is mainly used to manage energy charge collection of
utilities, companies, schools and etc, and plays important role in automatic collection of energy
charges and load control. Smart Vending Anywhere System ( SVAS ) brings convenience,
efficiency and security for users and thus simplifies the complexity of management, reduces cost
and improves revenue collection. It can be used in prepayment / post-payment smart vending
system of energy meters, water meters, and gas meters.
SMARTvend System Features
z
Network- based system structure and operation mode;
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 101
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
z
Multi-method Billing and compatible with various billing solutions;
z Various power vending methods available, i.e. vending through internet, vending point,
agent, POS, ATM, SMS and scratch card;
z Multi-station or single station management for vending points; Vending points can be
centralized for control and vending authorization.
z Support many kinds of prepayment energy meter including IC card prepayment energy
meter and all STS certified keypad prepayment energy meter, SMS message prepayment
energy meter etc.
Abundant graphic statistics and analysis report forms;
z Multi-level management mode and digital certified authentication system to ensure system
security.
z Users are given rights according to position that can be done to each control point of each
module.
z Built-in third party data exchange port and can communicate with exterior system like
marketing system, AMR system closely.
z Desktop user-defined.
SMARTvend Structure
SMARTvend includes server application as following:
z Database Server: used for storage of business data.
z Web Server: used for providing HTTP service to connect vending points of utility company
and connection for bank payment collection, internet power vending, vending agency,
internet vending etc.
z Data Exchange Server: maintaining multi-layer system data exchange and data exchange
with different suppliers;
z Affair Handling Server: for affair handling, TOKEN generation and data encryption,
decryption etc;
z
Management Terminal: for system comprehensive maintenance and report analysis of client
side PC;
Notice: Above-mentioned server application can be grouped according to customer demand and
development condition; all service function operated in one server is supported as well.
Provide corresponding port for other systems:
z Power marketing system, power deployment automation EMS system, distribution
automation DMS system, superior measurement system, and other system.
z Telecommunication port: payment collection port provided by bank for ATM automatic and
internet power vending;
z Other System port: payment collection through agents like network company,
telecommunication company or scratch card
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 102
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
System Compatibility and Scalability
SMARTvend adopts unified power vending and revenue collection method,
compatible with IC prepayment energy meter, STS keypad prepayment energy meter, SMS
prepayment energy meter researched by Inhemeter, as well as STS keypad energy
meter made by different manufacturers. Meanwhile, it makes SMARTvend compatible
with prepayment energy meter with different types and different protocols, prepayment water
meter, prepayment hot water meter and gas meter by system’s third party extended interface
base.
Diversified Power Vending Module
SMARTvend SVAS provides various vending modes in order to bring convenience and efficiency
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 103
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
to users and reduce workload of vending personnel.
z ATM: Users purchase electricity from ATM self-help equipment. Recharge will be made by
connecting with bank system after safety certificate. ATM will read the card and print digit
code.
z PC recharge: Users enter online network vending website to purchase electricity(IC card
reader is needed for operation for IC prepayment energy meter). After paying and confirming
the payment on internet, vending management center will make safety authentication and
give vending instruction for printing digit code.
z POS, PDA recharge: Users enter network vending website by internet with handhold
computer for recharge (It can not recharge for IC prepayment energy meter).
z Agent vending: Banks or other agent vendors authorized by the utility provide vending
business for users.
z Recharge hall: Integrated petty charges recharge hall provide electricity vending business.
z Vending hall: Power supply system provides internal vending network.
z Scratch card: Telecom companies use their value added service to transfer the recharge
payment and give recharge instruction (It can not recharge for IC prepayment energy meter).
z SMS: Telecom companies use their value added service to transfer the recharge payment,
and after successful recharge transferring, recharge can be made by SMS. It is applicable for
SMS prepayment energy meter and STS keypad prepayment energy meter (It can not
recharge for IC prepayment energy meter).
SMARTvend Functions
SMARTvend has three versions: standard version, professional version and enterprise version.
Different version system contains different functions and supports different meter type.
Customers can choose according to their actual business requirement.
SMARTvend SVAS has following function modules:
1) Daily business processing module
Customer data maintenance, power consumption contact signing and canceling, petty charge
collection, power vending, meter exchange, card complement, card data maintenance, and
complementally bill printing.
2) Power vending network management module:
Contact signing or canceling of vending network, vending terminal management, vending
network reconciliation, vending network permission, commission payment, etc
3) Tempering module
Customer power off/power recovery, tempering charge collection, handling charge collection of
power off made by customers, etc
4) Charge collection module
Petty charge collection, capacitance increase charge collection, meter freezing charge collection
5) Reports outputting module
Account opening integrated report, vending integrated report, consumption integrated report,
tempering integrated report, vending network integrated report, charges integrated report, etc
daily report outputting, consumption and vending and other analyses report outputting
6) System management module
Company information management, department management, role permission management,
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 104
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
user management, electricity price management, system operation data management, data
management, data maintenance, data exchange management, etc,
7) Assistance module: Online assistance display
17 Pre-stored Energy and Preset Load Threshold Instruction
17.1 Power Pre-stored and Load Presetting Stipulation
For DTZ1513 three phase four-wire keypad prepayment energy meter:
z Pre-stored electricity:30.00kWh
z Load threshold :22.000kW
z Preset pre-warning alarm threshold:30.00kWh
z Preset alarm threshold:0.00kWh
17.2 Dealings to Pre-stored Energy
It aims to test before installation, check the circulation status after installation. There several
modes regarding pre-stored electricity. Detailed operation will refer to local practice.
A: After finishing the test before installation, installation operation and circulation status check
after installation, the pre-stored electricity can be reset to zero by installation worker before
officially handing over to users.
Carry-out ways: In the stage of installation, while registering user and meter information in the
power vending system, the system will generate the TOKEN code specialized in clearing up
power consumption credit. After finishing the circulation check status and before officially handing
over to users, installation workers will input this TOKEN code into keypad prepayment energy
meter to clear up power consumption credit (clear up pre-stored electricity).
B: After completing measurement meter testing, installation and inspection of electricity
circulation status after the installation, energy meter can be formally delivered to users in the prior
record by a meter installer residual value of the stored power to submit the sale of electricity
management system.
Specific carrying out ways: After completing measurement meter testing, installation and
inspection of power after the installation, energy meter can be formally delivered to users in the
prior by a meter installer record residual value of the stored charge and get the user to confirm it;
installer will record the pre-stored electricity meter to log on to the remaining value of the stored
power management system for the sale of electricity from the sale of electricity management
system in the user when the first purchase deducted.
C: Give the pre-stored power to users for free.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 105
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
Since the quantity of pre-stored electricity is not very big, then it can be given to users for free use
after energy meter test, installation and circulation statuses check.
D: The pre-stored power will be deducted with one time by power vending management system.
According to pre-stored power in the energy meter before delivery, power vending management
system will deduct it while users open an account and purchase the power.
17.3 Load
Threshold Pre-setting
The purpose of pre-set load threshold is to facilitate measurement test before installation of
energy meter. According to the user information and load threshold permitted by utilities, the
special load threshold TOKEN code will be generated by the power vending management system,
and then users input it into related energy meter to finish load threshold setting.
In the process of using the meter, if the actual load of users changes, then they can apply for load
threshold change anytime. If the application is authorized, the specific TOKEN code used for load
threshold will be generated by power vending management system, then users input this TOKEN
to the related meter and finish load threshold changes.
18 Keypad Meter Mass Production Key Setting
18.1 Customized SGC Code Setting
This project:SGC 600434,01,1
Energy meters are set according to the client’s requirement for SGC. A series of operation like
installation, power vending, recharging, etc. can be processed once the client receives the
products.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 106
Three Phase Keypad Prepayment Energy Meter
(Plug-in Module Type)
When leaving factory, Inhemeter keypad prepayment energy meter’s meter number, factory
setting and other information are given together with the whole batch. It’s convenient to import all
the information to customer vending management system.
18.2 Inhe Default Key(SGC:999937)Setting
Set with the default factory key (SGC: 999937)-key type is DDTK.
Key will be replaced as follows:
1) Inhemeter provides a authorization table with the SGC code: 999937 and manufacturer’s
information of Inhemeter as table 1.
2) Customer fill in the vending security module number, customer information (as table 2), submit
the table to the Key Management Center(KMC)and apply for a key file of the keypad prepayment
energy meters of Inhemeter, then update their security module.
3) Energy meters will be set with the SGC: 999937 of Inhemeter, and can be supplied to all
customers who have this requirement, key on the back plate is as the follow diagram.
SGC: 999937, 01, 1
CREDIT:
30.00kWh
POWER LIMIT: 15.180kW
METER NUMBER:
37 99000089 7
TYPE:
DDZ1513
1Phase 2 Wire
MFG. 2013 4) After customer receive energy meters from Inhemeter, they should generate 2 groups of
replace TOKEN codes as per new security modules, input them into the energy meters, so as to
change the default keys(DDTK)to unique keys (DUTK), the back plate has to be replaced too.
Shenzhen Inhemeter Co., Ltd
www: inhemeter.com 107
Three Phase Keypad Prepayment Energy Meter
Shenzhen Inhemeter Co., Ltd
(Plug-in Module Type)
www: inhemeter.com 108
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF