Digital indicator for panel mounting Model DI10

Digital indicator for panel mounting Model DI10
Accessories
Digital indicator for panel mounting
Model DI10
WIKA data sheet AC 80.06
Applications
■■ Machine building and plant construction
■■ Test benches
■■ Level measurement
■■ General industrial applications
Special features
■■ Suitable for 4 ... 20 mA current loops
■■ Min/Max value memory
■■ Linearisation with up to 10 programmable points
■■ 2 optional potential-free switch contacts
■■ Minimal mounting depth: 25 mm without plug-in terminal
Digital indicator model DI10
Fig. top: for panel mounting
Fig. bottom: for wall mounting
Description
The model DI10 digital indicator, with its small mounting
depth, is ideal for mounting in applications with limited
mounting space. As a result of this small insertion depth, it
can be used in applications where other indicators would be
too large.
The digital indicator is suitable for industry-standard 4 ... 20 mA
current loop signals. The power supply for the display comes
directly from the current loop, so no additional power supply is
needed.
The display is parameterised through a logically-structured
menu which enables intuitive operation. The settings can be
made using the control keys on the front.
linearised with up to 10 programmable points. The display
time can be varied between 0.1 and 10 seconds. In order
to prevent unintentional changes by the operator within the
menu system, a programming lock can be activated.
The retrieval of the Min/Max values is made through the
simple operation of the control keys.
Two PhotoMOS outputs are available as options, with adjustable hysteresis independent of each other.
For convenient installation outside of electrical panels, the
display is also available in a practical wall-mount enclosure,
which offers an ingress protection of IP 65.
The parameterisation enables the setting of the indication
range and an offset. In addition, a sensor signal can be
WIKA data sheet AC 80.06 ∙ 01/2016
Page 1 of 4
Specifications
Model DI10
Display
Principle
7-segment LED, red, 4-digit
Indication range
-1999 ... 9999
Character size
Display rate
Memory
Input
14 mm
0.1 ... 10 sec
Flash memory (independent of power supply), data retention > 100 years
Number and type
1 x 4 ... 20 mA current input
Measuring time
0.1 ... 10.0 sec
Accuracy
Voltage drop
Power supply
Electrical connection
{Switching output}
Number and type
{}
± 0.3 % of the measuring span ± 1 digit
approx. DC 5.1 V, max. 150 mW
{approx. DC 8.0 V for the option with two switching outputs, max. 200 mW}
Not required, since the digital indicator is powered from the 4 ... 20 mA loop
screw terminals, conductor cross-section up to 2.5 mm²
2 PhotoMOS outputs, galvanically isolated
max. AC/DC 30 V, max. 0.4 A
Items in curved brackets are optional extras for an additional price.
Case
Material
PC polycarbonate, black
Dimensions
3.8" x 1.9" x 1.6" (96 x 48 x 41 mm) (W x H x D) including screw terminals
Ingress protection
Weight
Mounting
{Wall-mount enclosure}
Front: IP 65; Rear: IP 00
approx. 0.11 lbs. (50 g)
Screw elements for wall thicknesses up to 3 mm
Material
ASA, black, PG gland
Dimensions
160 x 90 x 60 mm (W x H x D)
Ingress protection
Weight
Mounting
{}
IP 65
approx. 300 g
Fixing holes for screws
Items in curved brackets are optional extras for an additional price.
Permissible ambient conditions
Operating temperature
32 ... 140 °F (0 ... 60 °C)
Relative humidity
0 ... 80 % mean annual relative humidity, non-condensing
Storage temperature
-4 ... 176 °F (-20 ... +80 °C)
CE conformity
EMC directive
Safety regulations
Page 2 of 4
2004/108/EC, EN 61326 emission (group 1, class B) and interference immunity (industrial application)
EN 61010
WIKA data sheet AC 80.06 ∙ 01/2016
Dimensions in mm
Panel-mount unit
45
Panel cutout
92
Wall-mount unit
Display and operating elements
1
P
5
1
2
3
4
5
7-segment display
Window of dimensions
Up key [UP]
Down key [DOWN]
Program key [P]
l/min
4
3
WIKA data sheet AC 80.06 ∙ 01/2016
2
Page 3 of 4
Designation of terminal connectors
S1
11
Internal bridge within instrument
S2
12
13
14
1
2
3
4
5
IB
+ Irel
+ Iin
- Iin
IB
{4-pin terminal block}
5-pin terminal block
Plug connector for switching outputs:
Screw terminal for signal input:
11
1
2
IB
+ Irel
3
+ Iin
internal bridge within instrument
Measuring signal current input (only in conjunction with switch outputs)
Current measuring signal
5
IB
internal bridge within instrument
12
13
14
Switching output S1
4
Switching output S2
- Iin
Current measuring signal
{} Items in curved brackets are optional extras for an additional price.
Scope of delivery
■■ Digital indicator model DI10
■■ Sealing
■■ Mounting screws (for panel mounting)
■■ Operating instructions
Order no.
Model
Panel-mount unit
Wall-mount unit
Without switching outputs
14019785
14024082
With 2 switching outputs
14019786
14024084
Ordering information
To order, the order number is sufficient. Other options require additional specification.
Page 4 of 4
WIKA data sheet AC 80.06 ∙ 01/2016
WIKA Instrument, LP
1000 Wiegand Blvd.
Lawrenceville, GA 30043
Tel: 888-WIKA-USA • 770-513-8200
Fax:770-338-5118
[email protected]
www.wika.com
01/2016 US
© 2016 WIKA Alexander Wiegand SE & Co. KG, all rights reserved.
The specifications given in this document represent the state of engineering at the time of publishing.
We reserve the right to make modifications to the specifications and materials.
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement