Below you will find brief information for packaged air conditioner APH450PG. This document is a service manual for the APH450PG packaged air conditioner. It contains a variety of information including installation of the unit, troubleshooting, exploded views, and parts list. The document is intended for qualified technicians and should not be used by anyone without proper training.
Advertisement
Advertisement
PACKAGED AIR CONDITIONER
A P H 4 5 0 P G
SERVICE
Manual
AIR CONDITIONER
1. Pre c a u t i o n s
CONTENTS
2. Product Specifications
3. Operating Instructions and
I n s t a l l a t i o n
4. Disassembly and Reassembly
5. Tro u b l e s h o o t i n g
6. Exploded Views and Parts List
7. Block Diagrams
8. PCB Diagrams
9. Wiring Diagrams
10. Schematic Diagrams
1. Precautions
1) Turn off the the power.
Be sure to turn off the power before attempting to repair the unit such as the disassembly of the unit.
2) Be careful of electric shock
When checking the circuit with the power connected in unavoidable circumstances, take special care not to touch the live parts. There is a danger of electric shock.
3) Use of appropriate parts
Be sure to use the genuine parts of the relevant model when it is necessary to replace parts. (Replace parts instead of repairing with regard to the malfunctioning of electric contact areas.
Never attempt to modify the unit. It is extremely dangerous for the consumer to attempt to repair the unit on his(her) own.)
4) Use of proper tools
Use appropriate tools for repair, and use measuring equipment after accurate calibration. Using worn tools may result in problems, including poor contact and poor connection.
5) Avoid damage to electric wire or electric cord.
Check the electric cord or electric wire for any damage during repair.
Be sure to replace it if damaged.
6) Avoid intermediate connection of the electric cord.
Never attempt to make an intermediate connection by cutting the middle area of the electric cord or make a connection to the power receptacle as it is very dangerous, causing problems or fire.
7) Checking of insulation
Be sure to check the insulation resistance after completion of the assembly work.
(Check whether the insulation resistance of the electric wire and grounding terminal is over 30M
Ω
by using the insulation resistance tester, and then connect the power source.)
8) Checking of grounding
Check the grounding condition, and perform repair if poorly grounded.
9) Checking of installation condition
Check the installation condition of the unit, and perform repair if there is any defective area.
If the unit remains in an unstable installing condition, install it at a new site.
10) Be careful of children
As the repair of the unit involves a lot of dangerous elements, do not allow children to approach nearby during repair work.
Cleaning
Turn off the sub power switch separately installed.
No connection with the power receptacle
Upon completion of the repair, clean the air conditioner and surrounding area, and inform the customer of completion of the repair.
Samsung Electronics
1-1
2. Product Specifications
2-1 Table
ITEM
Power source
Capacity
(Cooling/Heating)
Aux. heater
Power consumption
E.E.R (Cooling/Heating)
Running current (C/H)
Noise level (C/H)
Moisture removal
Air circulation
Dimension
(Net/Packed)
Weight(Net/Packed)
Piping box
Refrigerant type
Refrigerant quantity
Compressor type
Protective device
Refrigerant piping size
Drain piping size
Loading Q’ty (20’/40’)
Width
Height
Depth
Note: (1) The data are measured at the following conditions.
Model
ø/V/Hz kcal/h
BTU/h
Watt/h
W kcal/Wh
A dBA l/hr m 3 /h mm mm mm kg kg inch mm set
Indoor air temperature
Outdoor air temperature
DB
WB
DB
WB
Indoor unit
APH450PG
Outdoor unit
3 / 380 / 50
11,250 / 12,200
45,000 / 48,800
3,000
5,000 / 4,700
2.25 / 2.60
9 / 8.7
53 / 54
5.8
1,920
590 / 704
1,810 / 1,925
420 / 600
75 / 85
63
14
R-22
4.8
Reciprocating
4,800
930 / 1,200
1,240 / 1,370
385 / 540
123 / 133
Internal thermostat (CM)
High pressure switch
Gas : 3/4”, Liquid : 3/8”
I.D 18 I.D 16
12 / 24
Cooling
27.0˚C(80.6˚F)
19.0˚C(66.2˚F)
35.0˚C(95.0˚F)
24.0˚C(75.2˚F)
APH450PG
Heating
20.0˚C(68.0˚F)
12.0˚C(53.6˚F)
7.0˚C(44.6˚F)
6.0˚C(42.8˚F)
Samsung Electronics
2-1
2-2 Dimensions
420
Unit : mm
385
2-2
590
930
Samsung Electronics
3. Operating instructions and Installation
3-1 Operating Instructions
Operation Operation of auto cool, auto heat, cool, heat, fan
Operation of turbo, cool, heat, fan
Function selection
Main switch operation
Operation of remote controller
Auto cool mode
Auto heat mode
Cool mode
Heat mode
Fan mode
C o n t rol of fan motor step according to current temperature
C o n t rol of fan motor step according to current temperature
C o n t rol of cool according to the diff e rence between curre n t and desired temperature
C o n t rol of cool according to the diff e rence between curre n t and desired temperature
Operation of indoor fan motor only
Fan speed selector mode
Manual 3-step
Auto
High, medium, low
C o n t rol of fan motor step according to current temperature
Airflow selector mode
Convenience function
Left-right turn
Turbo operation
Convenience reservation
Turbo-operating compressor and powerful operating fan m o t o r ( 3 0 m i n u t e s )
R e s e rve function which is off after on time of 1, 2, 3, 4, or 5 h o u r s
LED display function
Function selector
Selection of fan speed
Selection of airflow
Current temperature
Desired temperature
Fan speed diagram
Convenience reservation
Current time
Auto cool, auto heat, cool, heat, turbo, fan lamp
Low, medium, high lamp
Left-right lamp
Indoor temperature display
Desired temperature display
Low, medium, high, turbo lamp
Reserve lamp and reserve time display
Current time display
Samsung Electronics
3-1
3-2 Key type and functions
3-2-1 PANEL key type and functions
Key name Key operating function
On/off
Mode selection
Fan speed selection
Start and end of operation
- ON 1 time = operation start, ON again = operation end.
- No continued operation
Change of the operation mode
- Each time the button is pressed(ON), the mode is changed in the following order:
“auto
→ cool
→ fan”(standard=auto)
- No continued operation
Setting of the indoor fan motor speed
- Each time the button is pressed ON, the mode is changed in the following order:
“low
→ medium
→ high”(standard=high)
Increase the desired temperature(current time) Temperature(time) setting(up)
Temperature(time) setting(down)
- Temperature: When pressing the button(ON) one time, the desired temperature is increased by the unit of 1°C.(18°C- 30°C)
- Time: When pressing the button(ON) one time, the time is increased by 1 minte.
If the “on” button is pressed continuously, the time is increased by 10 minutes.
- One short, and continued operation
Decrease the desired temperature (cur rent time)
- Temperature: When pressing the button(ON) one time, the desired temperature is decreased by the unit of 1°C. (18°C - 30°C)
Change of display
- Time: When pressing the button(ON) one time, the time is decreased by 1 minute.
If the “on” button is pressed continuously, the time is decreased by 10 minutes.
- One short, and continued operation
The temperature and current time can be changed.
- If the “on” key is pressed 1 time, current temperature and desired temperature are displayed.
- If the “on” key is pressed 1 time, current time is displayed.
The hours of 1,2,3,4 and 5 is selected whenever one time of on is performed.
Brief reservation
Heater on/off selection If the switch is selected to the on direction, the heater is operating at the heater operation condition.
The heater is not operating when the switch is selected to the off position.
* Operating functions
Fan Speed adjustment
Fan Speed display
Time/Temperature display
Operating Light
Remote control
Sensor On/Off Button
Key type
TACT
TACT
TACT
TACT
TACT
TACT
TACT
SLIDE
3-2
Time/Temperature
Selection
Time or Temperature adjustment
Operating
Mode Selection
Timer adjustment
Auxiliary Heater
Switch (option)
Power Light
Samsung Electronics
3-3 Accessory Parts List
3-3-1 Connection Parts
No.
Part Name
Connecting pipe
1
3/8”
(ø9.52mm)
Q’ty
1
Connecting pipe
2
1
3/4”
(ø19.05mm)
Heater cable (3 strand)
3
1
Remarks
Option
(Piping box)
Protection tube
4 1
5
Connecting wire (7 strand)
6
Wire of sensor (2 strand)
7
Power cable
8
Drain hose
9
Finishing tape
10
Insulation tape
11
Insulation tube for indoor unit piping connection
1
1
1
1
2
1
1
Piping box
3-3-2 Others
No.
Part Name
Leg holder for indoor unit
1
Q’ty
4
Remarks
Piping box
Screw
TH M4 X 12 4
2
3
4
TH M4 X 25
Cable clamp 12N
8N
Indoor unit fixing holder
6N
4
2
3
1
Option(Piping box)
1
5
Leg holder for outdoor unit
4
6
Insulation rubber bottom
7
Cable tie
8
Putty
9
Pipe band
10
Rubber cabi slot
11
Rubber cabi hole
12
Drain plug out
4
5
3
3
1
1
1
Piping box
Samsung Electronics
3-3
3-4 Installation
3-4-1 Selection of Installation Place
3-4-1(a) Indoor Unit
• Install the unit at a place close to the wall facing the outside as it is necessary to perform piping connection with the outdoor unit.
- It is effective to install the unit at a window side to ensure uniform distribution of indoor temperature .
• Install the unit at a place where there is no obstacle against the wind around the air inlet and air outlet.
• Install the unit horizontally at a stable, rigid place.
(When installing the unit at a place subjected to vibration, noise may occur. )
• Avoid a place near the door which is frequented by people.
• Avoid a place subject to direct sunlight.
Top view
Side view
Above 50cm
Above 20cm
3-4-1(b) Outdoor Unit
• Place free from the risk of combustible gas leakage.
• Place which can bear the weight of the unit.
• Place which can bear the fixing strength of the outdoor unit.
• Avoid a place subject to oil (including machine oil).
• Avoid a saline place.
• Avoid a place subject to sulfide gas (hot spring zone).
(When installing the unit at such special environmental conditions, it may cause machine trouble. When it is unavoidable to use such places. It re q u i res special m a i n t e n a n c e . )
Above 100cm
• A place where the discharge air and noise of the outdoor unit do not disturb the neighborh o o d .
(Take special care not to cause any inconvenience to your neighbors when installing the unit on the borderline with your neighborh o o d . )
• A place where strong wind does not head against the air outlet of the outdoor unit.
(If a strong wind heads directly against the air outlet at the time of cool operation, a safety device can be operated.)
• Do not install the outdoor unit at an unstable place such as outer wall of an apartment or building.
The outdoor unit may fall down, causing severe personal or property damage or loss.
* If there is any unavoidable reason to install the unit at such a place, take the following measures against the wind;
1. When installing the unit at a roadside concentrated with buildings, install it parallel with the ro a d .
2. Install the unit so that the air outlet faces toward the wall at a place such as rooftop, which may be subjected to s t rong wind.
Wall
* The outdoor unit should be installed in accordance with the service space.
Strong wind
Roof top
Above 15cm
Above 50cm
Above 15cm
Space for piping and wiring
The air inlet faces toward the wall.
Above 50cm
Space for piping and wiring
Above 30cm
Above 15cm
The air outlet faces toward the wall.
3-4
Samsung Electronics
Operating instructions and Installation
3-4-2 Electrical Work
The electrical work should be performed by a specialist qualified for the work.
• Use the three phase power supply, and be sure to install the sub power distributing board for exclusive use with the unit(separately purchased by the user).
* Avoid octopus-type wiring as it can cause a drop in voltage, thus resulting in poor performance of the automatic control circ u i t .
• Be sure to install circuit breaker (separately purchased by the user).
• Be sure to connect the grounding wire .
Electric power spec
Power
Ampere of breaker
Knife switch
Switch
Fuse
Size of grounding wire
Min. size of electric wires from/to the indoor/outdoor unit
CAUTION
3phase 4wires 380V
50 A
25 A
25 A
2.5 mm
0.75 mm
2
2
• Be sure to use the wires, and switches or fuses of power distribution board are qualified and fulfill the specification.
• Be sure to install knife switch or circuit breaker on the power distribution board.
• The electrical and grounding work should be performed as per “ technical specification of electrical facilities ” and “ specification of internal wiring ”.
• Be sure to connect main electrical input wires with bolted connectors using compressed terminal.
Applicable voltage 380V 342V ~ 418V
When connecting 3Phase 4wires 380V AC
1. Remove cover of electric box on side panel of outdoor unit.
2. Connect electric input wires (R,S,T,N) to each terminal (R,S,T,N) of the electric box on outdoor unit re s p e c t i v e l y.
3 . Connect electric wires to each terminal on indoor and outdoor unit re s p e c t i v e l y.
OUTDOOR SIDE
1:Thin Brown
2:Sky
3:Brown
4:Black
5:Thin sky
6:Dark Black
Knife switch or automatic circuit breaker
Wire of sensor
Indoor/outdoor unit connecting wire
Power cable
Inoor unit
Heater cable
CAUTION
• Be sure to connect electrical wires correctly, if not it can cause a trouble.
* Be sure to fix wires from/to the indoor and outdoor unit on the piping insulated.
Avoid wires contact to bare pipe or valve directly without any insulated spacer.
* Must be use the approval wire according to IEC or EN requirement.
Samsung Electronics
3-5
Operating instructions and Installation
3-4-3 Installation Method
3-4-3(a) Installation Procedures
1 . Open the inlet grille, and remove the flare nut.
2. Bend the connection pipe to an appropriate length using the spring bender depending upon the installation place.
- Allowable pipe length : Maximum 25m
- Allowable pipe drop distance : Maximum 15m
- Make no more than ten bending points on the pipe
• When the pipe length is in excess of the standard pipe length of 5m, add the refrigerant
(R-22) of 50g for each additional 1m.
CAUTION
• If the pipe is lengthened, the performance of the unit is degraded, and the service life is shortened.
Therefore, the pipe length should be as short as possible (less then 15m).
Outdoor unit
Indoor unit
Outdoor unit
Indoor unit
3. Install the high pre s s u re pipe to the heat exchanger liquid pipe, and the low pre s s u re pipe to the heat exchanger gas pipe respectively using the flare nut, taking care not to cause any leakage of re f r i g e r a n t .
4. Be sure to insulate the pipe with appropriate insulation material.
5. Insert the drain hose into the drain pipe, and connect them by tying them to the cable tie to prevent any water leakage.
6. After completion of the installation, check the connecting area for any gas leakage.
7. Wind a finish tape when the wiring of the refrigerant pipe, the unit, and the drain piping are comp l e t e d .
Outdoor unit checking area
Indoor unit checking area
3-6
Samsung Electronics
Operating instructions and Installation
3-4-3(b) Connection of Refrigerant Piping
Flare Processing
1. Cut the pipe using the pipe cutter.
Oblique Roughness Burr
2. Insert the flare nut into the pipe, and then perform the flare pro c e s s i n g .
Outer Diameter
ø 9.52mm
ø 19.05 mm
A ( out / in)
1.7 / 1.0 (mm)
2.2 / 1.5 (mm)
• Unproper flaring
Inclined Surface damaged
Cracked Uneven thickness
Pipe Bending
1. Perform bending of the pipe using the bender which has a specified bending radius.
2. Be sure to take full care to perform bending of the pipe successfully at one time.
Bending and unbending the pipe more than twice makes the bending work increasingly diff i c u l t .
3. You may use the spring inserted into the gas pipe instead of the bender to bend the pipe.
4. When you bend the pipe using the spring, hold the pipe with both hands to prevent any distortion, and secure a minimum bending radius of more than 100mm.
Spring
Tightening of Connection Parts
• Align the center of the connection piping, and tighten the flare nut by turning it with hand. Then tighten it again using the spanner in the direction as shown in the figure .
Remarks Outer Diameter
ø 9.52mm
ø 19.05mm
Tightening Torque
400 kg • cm
700kg • cm
Final Torque
450 kg • cm
750kg • cm
Samsung Electronics
3-7
Operating instructions and Installation
3-4-3(c) Drilling a Hole in the Wall
• Drill a hole of 70mm in diameter to the outside.
• The drilling should be done at a distance of less than 150mm from the floor facing the indoor unit.
ø70mm
Less than
150mm
3-4-3(d) Drain Hose
• Extend the drain hose to the drain hose connected to the drain pan, and fix it with the tape or a cable tie to prevent separation. Then make a covering of it so that water can not flow outward l y.
Piping Material
Insulator
Vinyl Chloride(Outer diameter ø 16mm)
Foamed Polyethylene
Drain pan
Insulation
Band
Drain hose
Indoor and outdoor connection
CAUTION
1. As the draining is of natural drain type, make the drain hose direct downward.
2. If there is any foreign substance in the drain plate, it may clog the drain pipe.
Therefore, be sure to remove the foreign substance inside after installation.
3. After completion of installation, be sure to pour water into the drain pan, and then check the draining condition.
(There is no problem in draining when the draining is completed within 20 seconds.)
• In heating and deice operation, condensed water may be generated.
Install drain line as following procedure.
1. Insert the drain plug into base hole.
2. And then connect drain hose to drin plug.
Hole
Base
Drain plug
Drain hose
3-4-3(e) Rat-prevention Cover
• The piping of this unit can be connected to the left and rear side.
• When you hit the area for piping connection slightly with a hammer, a hole is made.
- If there is any reason to change connection, fill in hole with ruber cabi slot.
Holes for piping connection (2 points)
3-8
Samsung Electronics
Operating instructions and Installation
3-4-3(f) Indoor Unit
In order to install drain hose through wall, adjust height (max. 150mm) of the indoor unit using leg holder.
Fixing to the floor
• When using the leg holder of the indoor unit.
1. Lie down the unit on flat floor.
2 . Insert the leg holders into screwed holes and then fasten them clockwise.
3 . Turn the unit right and adjust horizontal line of it.
* Mis-alignment of the unit can cause vibration and n o i s e .
Leg holder of the indoor unit
Fixing to the wall
• When using fixing holder of the indoor unit.
1 . Fix the holder using long screw bolts on wall.
2 . Fix the unit using two screw bolts or four anchor bolts.
(Size of the screw hole on the holder is ø4.5mm
and size of the bolt is ø6mm.)
Fixing holder of the indoor unit
3-4-3(g) Outdoor Unit
When using the anchor bolt
1 . Fix the unit on a flat, rigid floor using the anchor bolt.
(Anchor bolt : M10 x 4 points - separately purc h a s e d )
Anchor bolt fixing dimensions
Unit:mm
A 840
B 415
When using the leg holder of the outdoor unit
1 . Insert the foot holder (4EA).
2 . Remove the nut fastened to the leg holder, and then insert the leg holder into the hole of the outdoor unit leg.
3 . Fix the unit securely with the nut.
Nut
Outdoor unit leg
Leg holder
Foot holder
Samsung Electronics
3-9
Operating instructions and Installation
3-4-3(h) Air Purge
• Be sure to perform the air purge of the indoor unit, and piping using the refrigerant of the outdoor unit at the time of installation.
Open the cap of the valve(B), and valve(A).
OUTDOOR UNIT
Gas side
Liquid side
Open the valve cock of the valve(B) by approximately 45°. After an elapse of 10 seconds, close the valve cork.
Check the connection piping for leakage.
Not
Ieaking
Leaking
• Close the nut for the connection piping again.
Proceed to h when there is no leakage.
• If it is necessary to perform repair due to continuous leakage of gas, discharge the refrigerant gas, and repair the leaking area.
Then revacuum and refill the refrigerant.
Flare nut
Valve cock
Cap
Needle valve cap
Indoor unit
* Open the needle cap of the valve(A), and press the needle valve for 3 seconds to drain the gas out.
Repeat this procedure three times.
Open the valve cock of valve(B) and valve(A) completely.a
Close the cap of each valve.
Liquid side
3-Way valve
Gas side
Outdoor unit
3-Way valve
Check the valve for leakage.
3-10
Samsung Electronics
Operating instructions and Installation
3-4-3(i) Refrigerant Charging
Air purge(at the time of new installation only)
Close the gas pipe side valve by turning it clockwise.
Connect the pressure gauge to the low pressure side service valve, and then open the gas pipe side valve again.
Connect it to the refrigerant filling tank.
(Turn the tank upside down : Fill the refrigerant in liquid form.)
Start cooling operation.
Check the pressure of the pressure gauge.
Check whether the low pressure side is within the range of 4.5~5.5kg/cm2G
(outside temperature 35°C).
Open the tank and refill the refrigerant until arriving at the proper pressure.
(Refill the refrigent slowly checking the pressure.)
Stop operation.
Close the gas pipe side valve, and loosen the pressure gauge connected.
Then open the gas pipe side valve again.
Tighten the cap of each valve using a specified tool.
OUTDOOR UNIT
Gas pipe side
Liquid pipe side
Samsung Electronics
3-11
Operating instructions and Installation
3-4-4 Check and Test Operation
3-4-4(a) Check
• Be sure to check the following again after completion of installation.
1. Check the piping connection area for any gas leakage.
Outdoor connection area
Indoor connection area
2. Is the drain hose properly connected?
3. Is the insulation of the piping in good condition?
Insulation
Drain hose Indoor and outdoor connection
4. Is grounding properly made?
3-12
Samsung Electronics
Operating instructions and Installation
3-4-4(b) Test Operation
• After checking, read the owner’s instructions care f u l l y, and perform a test operation.
Then deliver the unit to the customer.
(When delivering the unit, be sure to read carefully and follow the contents of the owner ’ s i n s t ru c t i o n s . )
CAUTION
1. Be sure to check whether the service valve is opened before attempting to perform the test operation.
2. Never attempt to start test operation by force pressing the electronic contactor as it is very dangerous.
(This is very dangerous as the protective device does not work.)
3. Be sure to perform the test operation after installation.
It is easy to start the test operation in winter if you increase the sensor temperature to
23°C ~ 25°C by holding the indoor temperature sensor. (Cooling operation)
Temperature Sensor
Samsung Electronics
3-13
4. Disassembly and Reassembly
4-1 Indoor Unit
No
1
Parts
Indoor unit
Procedure Remarks
2 Inlet grille
1) Open the inlet grille and remove the connection ring.
3 Main PCB
1) Separate the PCB connect wire after separating the control box cover.
2) Separate the connection wire to separate the front cover and duct.
3) The main PCB should be separated by turn over the mountain tab.
Samsung Electronics
4-1
Disassembly and reassembly
No
4
Parts
Front cabi
Procedure
1) The front cabi should be separated by giving strength downward after loosening 2 screws at the lower end.
Remarks
5 Plate top 1) The plate top should be separated by loosening screws.
4-2
Samsung Electronics
No
6
Parts
Ass’y grille out
Procedure
1) First loosen screws at left and right sides of grille out.
Disassembly and reassembly
Remarks
2) Then the ass’y grille out should be separated by giving strength upward (
↑
).
7 Ass’y Blower in 1) First loosen the 4 screws at left and right sides.
2) Then the ass’y duct should be separated by lifting it.
Samsung Electronics
4-3
Disassembly and reassembly
No
8
Parts
Evaporator
Procedure
1) First separate the cover after loosening the screws fixed at evap cover R.
Remarks
2) Then separate the 3 screws fixed at cabinet
BKT of evaporator BKT.
3) Evaporator should be separated by flinging ahead.
4-4
Samsung Electronics
No
9
Parts
Motor
Procedure
1) When the ass’y duct should be separated from the motor, the 2 bracket should be separated first.
Disassembly and reassembly
Remarks
2) Then the bolts fixed at the blower and motor shaft should be separated.
3) Then the screws binding the holder top blower and duct should be separated.
4) The duct of one side should be separated as the picture shows after loosening the upper binder.
5) The binder of the motor and the duct should be separated.
Samsung Electronics
4-5
Disassembly and reassembly
No Parts Procedure
6) Then the motor should be separated.
Remarks
7) The bracket fixed at the motor should be separated.
10 Panel PCB 1) Should be separated after loosening the insulating material and binders at the back of the front side.
4-6
Samsung Electronics
4-2 Outdoor Unit
No
1
Parts
Outdoor unit
Procedure
1) Packaged air conditioner outdoor unit
Remarks
2) The binders of the front side should be separated.
3) The flank and the binders should be separated from each other.
2 Control box 1) Connect distributed wires in the control box.
Samsung Electronics
4-7
5. Troubleshooting
First,
Second,
Third,
Troubleshooting
Items to be checked first
Check the corrective actions in the case of occurrence of self-diagnosis mode
When the trouble is not related to the 1st or 2nd items above, check the troubled area in detail in accordance with the fault analysis method by symptom.
5-1 Items to be checked first
1 ) Is the supply voltage appro p r i a t e ?
The supply voltage: should be AC 187V-AC 253V/60Hz
2) Is the connecting wire between the indoor unit and outdoor unit appro p r i a t e ?
Be sure to check whether the cables for the indoor unit and outdoor unit are securely connected by the same terminal number.
3) When any claim occurs according to the contents of the table below, it is not related the trouble of the air-conditioner at all.
No.
Operation of air-conditioner Description
1 The compressor does not operate even though the desired temperature is set lower than
The compressor operation is delayed for 3 minutes for the protection of it during the restart of compressor. It operates normally after 3 minutes room temperature (during the cooling operation) delay even at the initial operation.
2 The hot wind does not come out even though the In order to prevent the discharging of cool wind, the room fan motor desired temperature is set higher than the room operates only when the temperature of indoor heat exchanger is kept temperature. (heating operation) higher than a constant one.
3 The wind quantity is not controlled during the automatic (cooling/heating) turbo operation.
The wind quantity is set by the micom during the automatic turbo operation.
4 The temperature can not be set during the automatic (cooling/heating) turbo blowing operation.
The desired temperature is set automatically during the automatic turbo operation. The wind blowing operation is simply the operation mode for the circulation of indoor air.
5-2 Self-diagnosis and corrective actions
Cause No.
1
Temperature display
E1
2
3
4
5
E5
E6
E7
EL
Short of indoor temperature sensor
Open of Indoor temperature sensor
Short of indoor heat exchanger sensor
Open of indoor heat exchanger sensor
Short of outdoor heat exchanger sensor
Open of outdoor heat exchanger sensor
Short of heater temperature sensor
Open of heater temperature sensor
When the electrical heater is over heated
Corrective actions
Check of departure of indoor temperature sensor
Check of PCB open/short
Check of indoor exchanger sensor departure
Check of PCB open/short
Replacement of sensor
Check of outdoor exchanger sensor departure
Check of PCB open/short
Replacement of sensor
Check of heater wiring diagram
Check of sensor attachment location
Check of heater temperature sensor departure
Check of PCB open/shore
Replacement of sensor
Samsung Electronics
5-1
5-3 Fault Analysis by Symptom
5-3-1 No Power (No display)
1) Checkpoints
(1) Is the voltage of the power source normal?(AC 187V - AC 253V)
(2) Is the power line in good contact?
(3) Check the power fuse(F701, F702) and PCB fuse(F101) for open.
(4) A re the primary and secondary sides of the power-trans in good contact with the connector?
(5) Is the output voltage of REG1(KA7812) normal?(DC 11.5V - DC 12.5V)
(6) Is the output voltage of REG2(KA 7805) normal?(DC 4.5V - DC 5.5V)
2) Checking pro c e d u res(after checking the checkpoints of clause 1)
Turn off the power, and then turn it on in 5 seconds.
Is the room temperature displayed on the temperaturre indicator, the display lamp turned on, and the panel shutter down when pressing the on/off button.
N
Is the voltage or the power trans AC 18V-21V secondary side(CN11) normal?
Y
Is the output voltage of REG1 and REG2 normal?
(REG1=12V, REG2=5V)
Y
Is the output wave at the MICOM(IC1) pin (No. 33~40) a square wave?
Y
Is the output wave at IC2 pin No. 11~18 a square wave?
Y
N
N
Check and replace the power trans.
Remove the shorted parts of the power terminal.
Replace the defective parts.
(D101-104, REG1, REG2)
N
Check and replace the MICOM(IC1).
N
Then it is normal operation.
Check and replace the IC2.
Y
Is the harness between the main PCB and panel PCB well connected?
Y
LED display or panel PCB defective.
N
Reassemble or replace the harness after checking it.
5-2
Samsung Electronics
Troubleshooting
5-3-2 When the Indoor Fan Motor does not Operate.
1) Checkpoints
(1) Is the voltage of the power source normal?(AC 187V-AC 253V)
(2) Is the indoor fan connector (CN71) in good contact?
(3) Is the starting condensor of the fan motor in good contact with the terminal?
(4) Is the resistance at both ends of the relay coil approximately 400
Ω
?
2) Checking pro c e d u res(after checking the checkpoints of clause 1)
Turn off the power, and then turn it on in 5 seconds.
Operate the on/off button, and operation mode key, and place it in the “FAN” position.
Does the airflow volume of the indoor fan motor change when converting into high, medium, and low by the FAN speed key?
N
Do the RY6(high), RY3(medium), and RY4(low) operate when converting into high medium and low by the FAN speed key.
N
Is the resistance at both ends/of the relay(RY 3, 4, 6) coil approximately 400
Ω
?
Y
Is it “high” when checking the output wave for airflow at the MICOM(IC1) pin No. 55, 56, and 53?
Y
Is the voltage at both ends of the relay for each airflow at the time of selecting the fan speed(high/medium/low) DC
12V?
Y
Is the voltage at both ends/of indoor fan motor AC 187V~253V?
Y
Y
N
N
N
Then the indoor fan motor is norm a l .
Then the relay is normal.
N
Then replace the relay when resistance is 0¥ or i
~
.
Check the resistance level after t u rning off the power.
Then check and replace the MICOM(IC1).
Is it low when checking the output wave for each airflow at the IC3 pin No. 11, 12, and 13?
Y
Then check the wiring harness for open.
N
Then check and replace the IC3.
Check and replace the indoor fan motor.
Samsung Electronics
5-3
Troubleshooting
5-3-3 When the Compressor Does not Operate
1) Checkpoints
(1) Is the voltage of the power source normal?(AC 187V - AC 253V)
(2) Is the desired temperature set at a higher level than the current temperature at the time of “Cool” o p e r a t i o n ?
(3) Is the power-in good contact with the comp. connector(GT 1, 2, 3, 4, 5)?
(4) Check the wirings of the outdoor and indoor unit for a wrong connection or poor contact.
(5) Isn’t the compressor in a 3-minute stand-by state?
2) Checking pro c e d u res(after checking the checkpoints of clause 1)
Turn off the power, and then turn it on in 5 seconds.
Check whether the relay(RY1) is turned on and the compressor is operated in 3 minutes after starting the
“COOL” operation by activating the on/off button and operation made key.
N
Is the resistance at both ends/of the re l a y ( RY 1) coil approximately 400
Ω
?
Y
Is it “high” when checking the output wave of the MICOM
(IC1) pin No. 6?
Y
Is the voltage at both ends/of the relay(RY1) coil DC 12V?
Y
Is the voltage at both ends/of the electronic contactor coil
AC 187V~253V?
Y
Is the voltage at both ends/of the electronic contactor terminal AC 187V~253V?
Y
Replace the compressor.
Y
Then the compressor and relay are norm a l .
N
N
Replace the relay when the resistance is 0
Ω
or
∞
.
Check and measure the resistance value after turning off the power.
Then check and replace the
MICOM (IC1).
N
N
Is it “low” when checking the output wave of the IC 3
No. 16.
Y
N
Then check and replace the IC 3
Then check the wiring of indoor and Then check the wiring of indoor and or open.
N
Then check and replace the electronic contactor
5-4
Samsung Electronics
Troubleshooting
5-3-4 When the remote control does not operate
1) Checkpoint
The sounds “beep” when it receives the signal of the remote contro l .
2) Checking pro c e d u re s
Turn off the lower, and then turn it on in 5 seconds.
Is room temperature displayed on the temperature indicator and does the operation start when pressing the on/off button on the panel?
Y
Does the indoor unit sound a “beep”, and stop when pressing the on/of button on the remote control?
N
Is the panel PCB connector properly connected to the main PCB connector?
Y
Is the voltage of the battery over DC 2.5V?
Y
Is the unit normally operated when pressing the on/off button after replacing the bettery?
Y
Is the receiving wave of the MICOM(IC1)
No.24 a square wave?
Y
Check and replace the MICOM(IC1).
N
Y
N
N
N
Refer to the checkpoint when the power is not supplied.
Then it is in normal operation.
Repair and replace the panel harness as required.
Then replace the battery.
Then replace the remote control.
N
Then replace the receiver module.
Samsung Electronics
5-5
5-4 PCB Inspection
5-4-1 Inspection Precautions
1 . Be sure to check whether the AC sub power switch is removed when removing the main PCB or panel PCB.
2 . Do not hold the outside of the main PCB or panel PCB with the hand or aply excessive force to it.
3 . When connecting or removing the connector to the main PCB or panel PCB, do not pull the lead w i re, but hold the entire assembly with the hand.
5-4-2. Inspecting procedures
1 . When there is any trouble with the main PCB or panel PCB, check the connector for a poor connection, and the PCB or copper-clad pattern for separation.
2. The PCB is composed of the following two parts;
• Main PCB: The main PCB is composed of the micom and peripheral circuit, relay drive sensor drive circuit, DC 5V power circuit, DC 12V power circuit and buzzer drive circ u i t .
• Panel PCB: The panel PCB is composed of the LED display key and remote contro l .
5-4-3. Detailed inspection procedures
NO Procedures
1 Turn off the sub power switch, and then check PCB fuse.
2 1. Apply the supply voltage
2. When power lamp and LED display operate after pressing the on/off button, it is not related to items
1)~4).
Checking method
1) Is the fuse blown?
Cause of trouble
1) Overvoltage?
2) Indoor fan motor short?
Check the supply voltage
1) Is the voltage between both ends/of the trans connector “AC187V~AC253V”
(GT6, GT7)
1) Power cord faulty, poor connection of indoor and outdoor unit, fuse blown, wrong wiring of power cables.
2) Voltage between both terminals of the CN 2) Power trans faulty.
11 AC15V~ AC22V Power circuit faulty.
3) Is the voltage between both terminals of 3) Power circuit faulty load short.
the REG1 (KA 7812) out and GND DC 12V?
4) Is the voltage between both terminals of the REG2 (KA7805) out and GND DC 5V?
4) Power circuit faulty, load short.
1) The compressor does not operate.
1) The relay(RY1) for driving the electronic contractor does not operate.
2) Electronic contactor faulty.
3 Set the unit to “COOL” operation mode by the “ON/OFF” button and mode selector key.
1. Cool operation
2. Set the desired temperature at a sufficiently lower level than the current temperature.
4 Set the unit to “HEAT” operation mode by the “ON/OFF” button and mode selector key.
1. Heat operation
2. Set the desired temperature at a sufficiently lower level than the current temperature.
5 Set the unit to “HEAT” operation mode by the “ON/OFF” button and mode selector key.
1. Heat operation
2. Set the desired temperature at a sufficiently lower level than the current temperature.
1) The compressor does not operate. 1) The relay(RY1) for driving the electronic contactor does not operate.
2) Electronic contactor faulty.
1) Is the voltage between the com terminal 1) Indoor fan motor faulty.
and the high, medium, and low terminal of 2) Starting condenser faulty.
the indoor fan motor connector
AC187V~AC253V? (When selecting each fan speed)
2) The indoor fan motor does not turn.
5-6
Samsung Electronics
6. Exploded Views and Parts List
6-1 Indoor Unit
6-1
Samsung Electronics
■ PART LIST
No CODE-NO DESCRIPTION
PLATE-TOP
ASS’Y-CABI IN
ASS’Y-BASE IN
ASS’Y-DRAIN PART
ASS’Y-CABI FRONT
“
ASS’Y-CABI FRONT IN
DECORATION-LOW
COVER-CONTROL
“
ASS’Y-CONTROL PANEL
“
BRAND-SAMSUNG
KNOB-A
KNOB-B
DECORATION-DIE
BRACKET-DECO LOW
FILTER-PRE
ASS’Y-GRILLE IN
BASKET-PEMOCON
BASKET-GRILL LF
BASKET-GRLL RH
GRILLE INLET UP
GRILLE INLET LOW
ASS’Y-GRILLE OUT
GRILLE OUTLET
DECO UP
HOLDER OUT GRILL
HOLDER-BLADE UP
BLADE-V
LINK-BLADE V
CAM BLADE
ASS’Y-MOTOR SWING
HOLDER-BLADE LOW
ASS’Y BLADE H
HOLDER-BLADE
BLADE-H
ASS’Y BLOWER IN
HOLDER-TOP BLOWER
ASS’Y-CASE DUCT R
COVER-BELL MOUTH
ASS’Y CASE DUCT L
BRACKET-MOTOR IN
ASS’Y-MOTOR IN
BLOWER
CASE-CONTROL
TRANS-POWER
ASS’Y-PCB MAIN
CSVER-CONTROL CASE
ASS’Y-EVAP IN
COVER-EVAP R
ASS’Y-TUBE INLET PART
ASS’Y COLLECTOR IN
HOLDER-THERMISTOR
ASS’Y ELEC HEATER
39
40
41
42
43
34
35
36
37
38
30
31
32
●
33
44
45
46
47
48
49
25
26
27
28
29
21
22
23
24
16
17
18
19
20
●
10
11
12
13
14
15
●
5
6
7
8
9
3
4
1
2
●
DB61-30501A
DB74-10079A
DB92-10007B
DB67-90005A
DB61-30108A
DB61-30109A
DB64-10035A
DB64-10036A
DB92-10298A
DB64-10034A
DB64-50075A
DB61-40034A
DB61-40235A
DB66-30156A
DB66-60026A
DB68-70001A
DB95-20065E
DB61-40234A
DB92-20017A
DB61-40037A
DB70-10271A
DB90-10561A
DB90-20171B
DB91-90012C
DB90-40113F
DB90-40113D
DB90-10175A
DB64-50076A
DB63-10027A
DB63-10432A
DB93-40232T
DB93-40232V
DB64-30011D
DB64-50019A
DB64-50020A
DB64-50069A
DB66-30070A
DB94-30143C
DB61-40233A
DB90-40112B
DB63-10431A
DB90-40112A
DB61-30507A
DB95-20136E
DB67-50003A
DB61-10023A
DB26-10070A
DB93-10519A
DB63-10033A
DB96-40164B
DB63-10430A
DB96-10559A
DB96-50083A
DB61-40052A
DB91-20081A
Samsung Electronics
SPECIFICATION
SECC-P, -, -, -, -, SC-94445T
AP-1100, L1810590°ø363
SAH-2017, 2517, SECC-P(20/20)
AP-1604CR, -
Heater only model
Non heater model
SA-165CH, LAMINATED
ABS, -, -, -
ABS, -, -, -
EPS
Heater only model
Non Heater model
KOAL, T1.6, W11.5, L70, BLK, -
ABS, CR, SAH-165CH, -
ABS, CR, SAH-165CH, -
ABS, GRY, SAH-165CH, -
SECC-P(20/20), T2.0, SC-4
PE, T0.3, AP-110
SAH-165CH, -
SAH-2016/2516
SC-9444ST, SAH-165CH
SC-94445T, SAH-165CH
ABS, SAH-2016/2516
ABS, SAH-2016/2516
AP-1100, -
ABS, SAH-2016/2516
ABS, SAH-2016/2416
SECC-P(20/20), BLK
SGCCM, T1, -, L564
PC ABS, T3, 5, -
PC ABS, T2, 12, -, -, -
POM
516RPM M2LA49ZR32, -
SGCCM, T1, -, L564
SAH-2016/2516
ZN-DC1, -, -, SAH-165CH
SECC-P, T0.5, 230, -
APH450PG, 6uF
SGCCM, T2.0, -, AP-1100
AP-1100, T0.8
SGCCM, T0.8, -, -, M, AP-1100
AP-1100, T0.8
SGCCM, T2.0, -, AP-1100
APH450PG
ABS, -, -
ABS, -, -, BLK, -, -
DC17, AC230, -, -, -, DC17, DC0.6A
ABS, -, BLK, -, -
APH450PG
SGCCM, T0.8, -, -, L749 W 77
AP-1300, 1.2/850/900/950/1000
AP-1604CR, -
ABS, -, WHT, -
APH450PG
Exploded Views and Parts List
Q’TY
1
4
1
1
2
1
5
1
2
1
1
1
1
1
1
1
1
1
1
1
(1)
1
1
2
1
1
1
1
1
(1)
1
1
(1)
1
1
(1)
1
1
1
1
1
-
1
1
1
-
2
1
3
1
-
1
1
1
4
REMARKS
Option
Option
16~20 ASS’Y
21~29 ASS’Y
31, 32 ASS’Y
33~39 ASS’Y
Heater only
6-2
6-2 Outdoor Unit
6-2-1 Outdoor Unit
6-3
Samsung Electronics
■ PART LIST
No
CODE-NO DESCRIPTION
1
2
3
DB90-10565A
DB63-30028C
DB67-50067A
6
7
4
5
8
DB95-20137F
DB95-20137G
DB90-30028E
DB61-40088A
DB93-40693A
DB93-40696A
9 DB93-40272A
10 DB67-30025A
11 DB99-10114A
12 DB99-10115A
13 DB90-10071B
14 DB90-10085B
15 DB72-50556A
16 DB95-10068A
17 DB73-10008A
18 DB90-10369D
19 DB96-30277A
20 DB96-30278A
21 DB98-20057A
22 DB63-30110C
23 DB67-90017B
ASSY-CABI OUT AIR
GUARD-INLET
FAN-PROPELLER
ASSY-MOTOR OUT
ASSY-MOTOR OUT
ASSY-MOUNT MOTOR OUT
HOLDER-FRAME
ASSY-CONTROL OUT
“
PARTITION
ASSY-BASE OUT
ASSY VALVE 3/8" CHECK
ASSY-4 WAY V/V
ASSY-CABI OUT LW SD
ASSY-CABI OUT UP SD
INSU SOUND
ASSY-COMP
GROMMET-MOUNT
ASSY-CABI OUT B
ASSY-COND UP
ASSY-COND LOW
ASSY-PLATE TOP
SCREEN-GUARD
HANDLE
SPECIFICATION
WELD GUARD FAN
SC-91438T, -
AS+GF20, D495, 4BLADE
AP-1100, OSM-6508SRC
AP-1100, OSM-6508SRC WIRE
APE-1600CR, -
SGCC1, T1.6, -, -
Heater only model
Non-heater model
T1, -, 389.17°ø1239.46
AP-3508, M8 WELD BOLT
APH450PG
APH450PG
SECC-P(20/20), T0.8
SECC-P(20/20), T0.8
T12, W940, L380
CRNQ-0500-TFD
BROWN
AP-1004/1604CR, -
1.7 WAVE
1.7 WAVE
AP-1004/1604CR, -
P.E.H 100%, T2.5, -, -
ABS, -, SC-90073R
Samsung Electronics
Exploded Views and Parts List
Q’TY
1
1
1
1
1
1
(1)
(1)
1
1
1
1
1
1
2
1
1
1
1
1
4
1
1
1
REMARKS
6-4
Exploded Views and Parts List
6-2-2 ASS’Y CONTROL BOX
■ Parts List
No
4
5
6
1
2
3
CODE NO
DB93-40419A
2501-001098
DB34-90089A
DB65-40022A
DB34-90090A
DB47-90121A
Description
ASS'Y CONTROL BOX OUT
CAPACITOR OUT
MAGNET-CONTACTOR
TERMINAL BOARD
MAGNET-CONTACTOR
FILTER-NOISE
Specification
SGCC-M, Z(Z=22)
450VAC 4uF
42AF35AL
600V 35, 15A
42AF35ALPM
PC4-F05
Q’ty
1
1
1
1
2
1
Remark
Heater only
6-5
Samsung Electronics
6-3 Remote Control
2
1
5
3
4
6
3
4
1
2
5
6
■ Parts List
No CODE NO
DB93-30026K
DB61-10022A
DB61-10011A
DB73-20013A
DB93-10509A
DB64-40008J
DB63-10081A
Description
ASS’Y-REMOCON
CASE-REMOCON(UPP)
CASE-REMOCON(LW)
RUBBER(BT)
ASS’Y-REMOCON PCB
WINDOW-REMOCON
COVER BATTERY
Specification
AR-H60
ABS
ABS
NBR
APH450PG
PC T1.5
ABS
Samsung Electronics
1
1
1
1
1
1
Q’ty
1
Remark
6-6
7. Block Diagrams
7-1 Micro Computer Block Diagram
Time condensor
Real temperature perception sensor(R-TH)
Evaporating temperature perception sensor
Condensing temperature perception sensor
Over heat perception sensor
Remote control receiver
Lamp examiner
REMOTE CONTROLLER
On/Off
Left-right turn
Fan Speed selectorhigh, medium, low
Function selector
Heat
Cool
Fan
Turbo
Temperature control: low, high
INDOOR CONTROL PANEL
A/D transformer
Temperature controller
Compressor controller
Heater controller
Indoor fan controller
Outdoor fan controller
Left-right motor controller
4-way valve controller
Buzzer controller
Reset circuit
Oscillator circuit
Indoor indicators
•Temperature lamp
•Cooling lamp
•Heating lamp
•Low-medium-high turbo lamp
•Timer lamp
•Power lamp
•Mode selector lamp: Auto, Heat, cool, fan
•Outdoor unit motion lamp
•Defrosting lamp
•Lamp to indicate desired temperature
•Lamp to indicate present temperature
•Timer lamp to indicate reservation
•Lamp to indicate present time
•Turbo lamp
Operation of room switches
•On/Off
•Temperature(time) - high, temperature(time) - low
•Function selector
•Convenience reservation
•Fan selector selector
•Change indicator
•Selector of Heater On/Off
Workload operation
•Indoor fan motor - low, medium, high, turbo
•Left-right motor
•Compressor
•Outdoor fan motor
•4-way valve
Electric circuit(DC+5V)
Electric circuit(DC+12V)
Electric transformer
Electric power input
Samsung Electronics
7-1
7-2 Refrigerating Cycle Block Diagram
INDOOR UNIT
Allowavle pipe length:Maximum 25m
Allowable pipe drop distance:Maximum 15m
OUTDOOR UNIT
Check valve
Capillary tube
3-way valve
Liquid side
Heat exchanger
(Evaporator)
Capillary tube
Heat exchanger
(Condenser)
Gas side
3-way valve
Compressor
4-way valve
High
Pressure switch
Cooling
Heating
Gas leak check point
* Amount of refilling per extension length of 1m;
When extending the pipe length by more than 5m, 50g of R-22 refrigerant should be re f i l l e d per extension length of 1m.
Refrigerating cycle temperature and pressure
Operating Condition
Cooling
Heating
Standard
Max over load
Low temp
Standard
Max over load
Deice
STD Pressure
(kg/cm2G)
(GAS SIDE)
4.5~5.5
6.5~7.5
3~4
18.5~20.5
-
-
Piping Temp.(˚C)
T1
40~45
50~55
30~35
32~36
36~40
28~32
T2
9~12
14~18
1~4
65~75
70~80
40~45
20
27
20
DB
27
32
21
Indoor
UseTemp. Condition (°C)
Outdoor
-
-
-
WB
19
23
16
7
21
2
DB
35
43
21
6
16
1
WB
24
26
16
7-2
Samsung Electronics
8. PCB Diagrams
8-1 Ass’y Main PCB (Code No : DB93-10519A, B)
8-1
Samsung Electronics
PCB Diagrams
■ PARTS LIST
DESIGN LOCATION
-
SK1, SK4
F701, F702
F101
VAR1
RY1-RY8, RY11
C701
C702
CN11
CN41
CN44
CN91
CN92
CN93
CN71
IC1
IC2
IC3, IC5
IC4
Q601
Q401
-
REG1
REG2
D101-D105
D907
X1
X2
BZ61
C102
C103
C104
C501
C105, C109, C201, C202
C401-C407
C901, C902
C903
R201, R201
R401, R403, R413-R415
R501, R502, R601, R901
R902
R402
R405, R406, R411
R404
R408~R410, R912
R602
R903-R911
R407
Samsung Electronics
DB47-90118A
DB47-90011A
2802-000103
DE30-20013A
DE30-20013A
2401-000725
2401-000710
2401-000303
2401-003107
2201-000144
2201-000176
2401-000353
2001-000042
2001-000065
CODE NO
DE62-30031A
DE47-30019A
3601-001094
DB47-90053A
DB47-90014A
3501-001042
2306-000111
2301-000133
3711-000880
3711-000940
3711-002662
3711-000577
3711-001084
3711-001154
3711-000357
DB61-40240
DB09-10138A
DE13-20009A
DE13-20017A
1003-000217
0504-000201
0501-000398
DB47-90036A
DB47-90037A
Description
HEAT SINK(L)
SPARK-KILLER
FUSE
FUSE
VARISTOR
RELAY
C-FILM
C-FILM
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
FUSE HOLDER
IC-MCU (M1COM)
IRESET IC
IC-LINEAR
IC-DRIVE
TR-SWITCHING
TR-GENERAL
C-VOLT REG
IC-VOLT REG
SCREW TAPPING
DIODE-RECT
DIODE-SW
RESONATOR
CRISTAL
BUZZER
C-ELECT
C-ELECT
C-ELECT
C-ELECT
C-CERAMIC
C-CERAMIC
C-CERAMIC
R-CARBON
R-CARBON
Specification
AL6063 T16.8 W23.5 L30
ESQ-1201
FST 250V 5A 20mm
FST 250V 2.0A 20mm
INR1-D471-SVC471D-10A
UT205-12S 250V3A
CF 912 M 630V T 104J
CF 912 M 630V T 103J
SMW250-03 RED
SMW250-06 BLUE
JSW250-02 WHT
SMW250-10 WHT
SMW250-08 WHT
SMW250-09 WAT
YW396-09A WHT
FH-51H 7.5A
MB89635R-435
KA7533 DIP
KID65003AP
ULN2981
R1002
KSC935Y
KA7812
KA7805
PH 3 L6 AB FEFZY
1N4007 1000V 1A
1N4148 1.2V 4.0NS T
10MHz CST10MTW-TF
32, 768KHE
CBE2220BA
CE 04 C 35V T 222-M
CE 04 C 25V T 222-M
CE 04 C 25V 101-M
CE 04 C 16V 470-M
CK 0A 50V T 104-Z
CK OA 50V T 103-Z
CK OA 50V T 101-Z
RD 1/4 T 102-J
RD 1/4 T 103-J
APH450PG Remark
1
16
1
1
1
1
1
5
1
1
1
1
1
1
1
2
1
2
3
1
1
1
1
1
1
1
1
6
2
1
1
1
1
1
1
2
11
2
1
2001-000047
2004-001136
2001-000588
2001-00036
2001-001172
2003-000160
2004-000616
R-CARBON
R-METAL
R-CARBON
R-CARBON
R-CARBON
R-METAL OXIDE
R-METAL
RD 1/4 T 222-J
RD 1/4 T 682-F
RD 1/4 T 332-J
RD 1/4 T 330-J
RD 1/2 T 620-J
RS 1T 121-J
RS 1/4 243-F
1
4
1
2
1
9
1
8-2
8-2 Ass’y Panel PCB(Code No : DB93-10520A, B)
8-3
Samsung Electronics
■ PART LIST
DESIGN LOCATION
SW9
CN1
CN2
CN3
CN4
CN6
R1
C1
-
C2
D1-05
LE1
-
SW1-SW4, SW6-SW8
CODE NO
2001-000065
2401-003107
2201-000144
DB32-50023A
DB47-90011A
DB07-10050A
DE07-20142A
DB34-90082A
3408-000326
3711-000570
3711-001111
3711-001147
3710-000193
3711-000940
Description
R-CARBON
C-ELECT
C-CERAMIC
MODULE REMOCON
DIODE SW
LED LAMP
LED DISPIAY
SW-TACT
SW-SLIDE
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
CONNECTOR-WAFER
Specifition
RD 1/4 T 103-J
CE 04 C 16V 470-M
CK OA 50V T 104-Z
TSOP-1238 TB1
1N4148 1.2V
LTL-4212 RED T P10.0
SSG-9405T-01
KPT-1115D
-
SMAW250-10-WHT
SMAW250-08-WHT
SMAW250-09-WHT
BH250-04R WHT
YFAW205-304R WHT
PCB Diagrams
1
1
1
1
1
Q’TY Remark
1
7
4
1
1
1
1
1
Samsung Electronics
8-4
9. Wiring Diagrams
9-1 Indoor Unit
Samsung Electronics
M A R K
S K 1 , 4
VA R 1
F M
RTH ROOM
H T H
E T H
S W I N G
N A M E
S PARK KILLER
VA R I S T O R
INDOOR FAN MOTOR
T H E R M I S T O R
O V E R H E AT SENSOR
E VA P. SENSOR
SWING MOTOR
RY 1
RY 2
RY 3
RY 4
COMPRESSOR DRIVE RELAY
SWING MOTOR DRIVE RELAY
FAN MOTOR DRIVE RELAY ( H I G H )
FAN MOTOR DRIVE RELAY ( M I D )
RY 5 FAN MOTOR DRIVE RELAY ( L O W )
RY 6 FAN MOTOR DRIVE RELAY ( T U R B O )
RY 7
RY 8
OUTDOOR FAN DRIVE RELAY
4 WAY V/V DRIVE RELAY
RY 1 1
H E AT E R
H E ATER DRIVE RELAY
P. T.C. HEAT E R
9-1
9-2 Outdoor Unit
9-2
N O T E
5 2 C
A P H 4 5 0 P G
N A M E
MAGNETIC SWITCH COMP
5 2 C 1
TB 1, 2
MAGNETIC SWITCH ETH
TERMINAL BLOCK
TH 1
C H
S P K
2 0 S
THERMISTOR CONDENSER
CRANK CASE HEAT E R
S PARK KILLER
4 - WAY VA LV E
C 1 , 2
N . F. B
6 3 H
FM1, 2
N / F
C A PACITOR OUT
CIRCUIT BREAKER 25A
HIGH-PRESSURE SWITCH
FAN MOTOR OUT
NOISE FILT E R
* USE 25AMPS TIME DELAY FUSE OR CIRCUIT BREAKER
Samsung Electronics
Application date Page
U P D A TE LOG SHEET
Part# Note(Cause & Solution) S/Bulletin#
Use this page to keep any special servicing information. (Service Bulletin, etc.)
If only parts number changes, Just change parts number directly on parts list.
And if you need more information, please see the service bulletin
Copyright
®œ 1995 by Samsung Electronics Co., Ltd.
All rights reserved.
This manual may not, in whole or in part, be copied, photocopied, reproduced, translated, or converted to any electronic or machine readable from without prior written permission of
Samsung Electronics Co., Ltd.
SyncMaster 17GLi/CMG7387L Service
Manual
First edition June 1995.
Tr a d e m a r k s
Samsung is a registered trademark and
SyncMaster 17GLi/CMG7387L and
MacMaster
Cable Adapter are trademark of Samsung
Electronics Co., Ltd.
Macintosh, Centris, Quadra, Duo Dock, and
Power Macintosh are trademark of Apple computer, Inc.
All other trademarks are the property of their respective owners.
10. Schematic Diagrams
10-1 Indoor Unit
Samsung Electronics
10-1