Operating Manual

FU 252

Signal converter for frequency - analog / serial

Product features:

Input frequency range from 0.1 Hz to 1 MHz for full scale analog output

Conversion time only 1 ms. (f > 2 kHz)

Analog output with +/- 10 V or 0 resp. 4 to 20 mA

Polarity of analog signal changes with change of the direction of rotation

Suitable for conversion of quadrature signals (A/B) as well as single-channel signals, with all HTL or TTL or RS422 formats and levels

Suitable for conversion of the sum, the difference or the ratio of two frequencies

RS232 or RS485 interface for serial readout of the input frequencies

Programmable digital filters and programmable linearization curves

Easy to set up by simple TEACH procedure, or by PC operator software motrona GmbH, Zeppelinstraße 16, DE - 78244 Gottmadingen, Tel. +49 (0) 7731 9332-0, Fax +49 (0) 7731 9332-30, [email protected], www.motrona.com

Version:

FU25201a_af_hk_04/2007

FU25202a_af_hk_10/2008

FU25202b_af_hk_10/2008

FU25202c_af_pp_07/2012

FU25202d_nw_09/2013

Fu25202e_oi/ag/04-2015

Fu252_02f_oi/ag/Aug-2015

Fu252_02g_oi/ag/Oct-15

Description:

First edition

Default settings "Frequency Control", "Input Filter", "Analog Mode"

Commissioning form, completion DIL2 positions 7+8

Correction in Description “Serial Value”

Small Corrections

- Supplemental note for 4.4 Analog output (Volt or mA instead “and”)

- Safety Instructions, Technical Specifications and Design updated

Some cross-references had to be changed resp. modulated

Page 1 : Subtitle changed (phrase was unclear)

Chapter 4.5 “Serial interface” RS232 or RS485 (instead of “and”)

Legal notices:

All contents included in this manual are protected by the terms of use and copyrights of motrona GmbH. Any reproduction, modification, usage or publication in other electronic and printed media as well as in the internet requires prior written authorization by motrona GmbH.

Fu252_02g_oi_e.doc / Apr-16 Page 2 / 36

Table of Contents

1.

SAFETY INSTRUCTIONS AND RESPONSIBILITY .......................................................................4

1.1.

General Safety Instructions ...................................................................................... 4

1.2.

Use according to the intended purpose ................................................................... 4

1.3.

Installation................................................................................................................ 5

1.4.

Cleaning, Maintenance and Service Notes ............................................................. 5

2.

COMPATIBILITY HINT ..............................................................................................................6

3.

INTRODUCTION .......................................................................................................................7

3.1.

Impulse input formats and input levels .................................................................... 7

3.2.

Operating range ........................................................................................................ 8

3.3.

Suitable encoders and sensors ................................................................................ 8

4.

TERMINAL ASSIGNMENTS AND CONNECTIONS ....................................................................9

4.1.

Example for use of TTL encoders ............................................................................. 9

4.2.

Example for use of HTL encoders ........................................................................... 10

4.3.

Proximity switches, photocells etc. ........................................................................ 10

4.4.

Analog output ......................................................................................................... 10

4.5.

Serial interface ....................................................................................................... 11

5.

DIL SWITCH SETTINGS .......................................................................................................... 12

5.1.

Basic mode of operation ........................................................................................ 12

5.2.

Impulse levels and symmetric / asymmetric input formats ................................... 13

5.3.

Analog output format ............................................................................................. 14

5.4.

Selecting the RS232 or the RS485 serial interface ............................................... 15

5.5.

Teach function, Test function, loading of default settings .................................... 15

6.

COMMISSIONING ................................................................................................................. 16

6.1.

Conversion of one only frequency (single or dual channel with direction signal) . 17

6.2.

Conversion and combination of two independent frequencies ............................ 17

7.

PC SETUP VIA OPERATOR SOFTWARE OS3.X ........................................................................ 18

8.

PARAMETER DESCRIPTION ................................................................................................... 20

9.

FREE PROGRAMMABLE LINEARIZATION ............................................................................... 27

10.

MONITOR FUNCTIONS .......................................................................................................... 29

11.

DATA READOUT VIA SERIAL INTERFACE ............................................................................... 31

12.

DIMENSIONS ........................................................................................................................ 32

13.

TECHNICAL SPECIFICATIONS ................................................................................................ 33

14.

INTERNAL REGISTERS AND SERIAL CODES .......................................................................... 34

15.

COMMISSIONING FORM ....................................................................................................... 36

Fu252_02g_oi_e.doc / Apr-16 Page 3 / 36

1. Safety Instructions and Responsibility

1.1. General Safety Instructions

This operation manual is a significant component of the unit and includes important rules and hints about the installation, function and usage. Non-observance can result in damage and/or impairment of the functions to the unit or the machine or even in injury to persons using the equipment!

Please read the following instructions carefully before operating the device and observe all safety and warning instructions! Keep the manual for later use.

A pertinent qualification of the respective staff is a fundamental requirement in order to use these manual. The unit must be installed, connected and put into operation by a qualified electrician.

Liability exclusion: The manufacturer is not liable for personal injury and/or damage to property and for consequential damage, due to incorrect handling, installation and operation. Further claims, due to errors in the operation manual as well as misinterpretations are excluded from liability.

In addition the manufacturer reserve the right to modify the hardware, software or operation manual at any time and without prior notice. Therefore, there might be minor differences between the unit and the descriptions in operation manual.

The raiser respectively positioner is exclusively responsible for the safety of the system and equipment where the unit will be integrated.

During installation or maintenance all general and also all country- and application-specific safety rules and standards must be observed.

If the device is used in processes, where a failure or faulty operation could damage the system or injure persons, appropriate precautions to avoid such consequences must be taken.

1.2. Use according to the intended purpose

The unit is intended exclusively for use in industrial machines, constructions and systems. Nonconforming usage does not correspond to the provisions and lies within the sole responsibility of the user. The manufacturer is not liable for damages which has arisen through unsuitable and improper use.

Please note that device may only be installed in proper form and used in a technically perfect

condition and in accordance to the Technical Specifications (see chapter 13 ). The device is not

suitable for operation in explosion-proof areas or areas which are excluded by the EN 61010-1 standard.

Fu252_02g_oi_e.doc / Apr-16 Page 4 / 36

1.3. Installation

The device is only allowed to be installed and operated within the permissible temperature range. Please ensure an adequate ventilation and avoid all direct contact between the device and hot or aggressive gases and liquids.

Before installation or maintenance, the unit must be disconnected from all voltage-sources.

Further it must be ensured that no danger can arise by touching the disconnected voltagesources.

Devices which are supplied by AC-voltages, must be connected exclusively by switches, respectively circuit-breakers with the low voltage network. The switch or circuit-breaker must be placed as near as possible to the device and further indicated as separator.

Incoming as well as outgoing wires and wires for extra low voltages (ELV) must be separated from dangerous electrical cables (SELV circuits) by using a double resp. increased isolation.

All selected wires and isolations must be conform to the provided voltage- and temperatureranges. Further all country- and application-specific standards, which are relevant for structure, form and quality of the wires, must be ensured. Indications about the permissible wire cross-

sections for wiring are described in the Technical Specifications (see chapter 13 ).

Before first start-up it must be ensured that all connections and wires are firmly seated and secured in the screw terminals. All (inclusively unused) terminals must be fastened by turning the relevant screws clockwise up to the stop.

Overvoltages at the connections must be limited to values in accordance to the overvoltage category II.

For placement, wiring, environmental conditions as well as shielding and earthing/grounding of the supply lines the general standards of industrial automation industry and the specific shielding instructions of the manufacturer are valid. Please find all respective hints and rules on www.motrona.com/download.html

--> “[General EMC Rules for Wiring, Screening and Earthing]”.

1.4. Cleaning, Maintenance and Service Notes

To clean the front of the unit please use only a slightly damp (not wet!), soft cloth. For the rear no cleaning is necessary. For an unscheduled, individual cleaning of the rear the maintenance staff or assembler is self-responsible.

During normal operation no maintenance is necessary. In case of unexpected problems, failures or malfunctions the device must be shipped for back to the manufacturer for checking, adjustment and reparation (if necessary). Unauthorized opening and repairing can have negative effects or failures to the protection-measures of the unit.

Fu252_02g_oi_e.doc / Apr-16 Page 5 / 36

2. Compatibility Hint

This product is a successor model of the thousandfold proven converter type FU251. The new product is suitable for a 100% replacement of the previous model, however some differences must be observed with DIL switch settings and parameter settings.

Some essential advantages of FU252 compared to FU251 are:

Maximum frequency 1 MHz (instead of 500 kHz)

Total conversion time in-out = 1 ms (this was no more assured with

FU251 after the modifications necessary for RoHS conformity)

Capability to accept even single-ended TTL input signals

(i.e. TTL input A only without inverted TTL signal /A)

The setting of the analog format (+/-10 V, 0 … 10 V or 0/4 … 20 mA) can be done by a supplementary DIL switch (no more PC required)

Enhanced auxiliary output 5 V / 250 mA for encoder supply

Fu252_02g_oi_e.doc / Apr-16 Page 6 / 36

3. Introduction

FU 252 is a small and low-cost, but highly performing converter for industrial applications, where one frequency or two different frequencies need to be converted into an Analog signal or a serial data format. The unit has been designed as a compact module with 12 screw terminals and a 9-position SUB-D connector (female). The housing is suitable for standard DIN rail mounting.

3.1. Impulse input formats and input levels

The input site provides channels A and B and also the inverted lines /A and /B. All inputs are designed for use with either HTL level or TTL level, with either single-ended format or differential format (RS422).

The unit can convert the following formats to Analog and serial: a. Quadrature signals with a 90

phase displacement. Polarity of the Analog output and sign of the serial data depend on the direction given by the A/B phase. b. Single channel impulses on channel A. Input B sets the polarity of the output (LOW = negative, HIGH = positive). In case of open (unconnected) inputs, please note:

Open NPN inputs are evaluated as HIGH state

Open PNP inputs are evaluated as LOW state

Open RS422 inputs may cause problems, therefore please set unused inputs to HTL by

means of the appropriate DIL switch c. Fully independent frequencies on both channels A and B. The output signal can represent the sum, the difference, the product or the ratio of the two input frequencies.

a.

b.

c.

A

B

A and B, quadrature 90°

A

B

-

+

A=impulse, B=static polarity select

A

B

A and B: independant frequencies

Fu252_02g_oi_e.doc / Apr-16 Page 7 / 36

3.2. Operating range

The full scale frequency (i.e. the input frequency where the Analog output reaches 10 V or

20 mA) can be set in a range from –1 MHz to +1 MHz. The operating range of the unit can be assigned to any frequency window inside this frequency range.

A “zero output frequency” can be set to guarantee defined operation of the converter with low input frequencies.

For applications with unstable input frequencies, the unit provides programmable digital filters for smoothing of the output signal.

3.3. Suitable encoders and sensors

The FU252 converter can accept the following impulse sources:

Quadrature encoders with HTL level output (10 – 30 V) and either PNP or NPN or Push-

Pull or NAMUR characteristics, using A and B outputs wit 90° displacement

Single channel impulse sources like proximity switches or photocells, providing HTL level at PNP or NPN or Namur characteristics

TTL / RS422 quadrature encoders with output lines A, /A ,B and /B

Symmetric single channel sources with TTL / RS422 output, providing differential signals (e.g. A and /A)

Asymmetric single channel sources wit TTL level (without inverted signals, e.g. A only)

In general, HTL encoders will be supplied from the same source as the converter itself.

For supply of TTL encoders, the unit provides an auxiliary output of 5.5 volts

(stabilized, max. 250 mA).

Fu252_02g_oi_e.doc / Apr-16 Page 8 / 36

4. Terminal Assignments and Connections

We recommend connecting the Minus wire of the power supply to earth potential.

Please observe that, under poor earthing and grounding conditions, multiple earth connections of screens and GND terminals may cause severe problems. In such cases it may be better to have only one central earthing point for the whole system.

GND terminals 4, 6 and 12 are connected internally.

Under nominal conditions the current consumption of the unit is approx. 70 mA (aux. output

unloaded, see section 13 “Technical Specifications”). Lower input voltage and load of the aux.

output will increase the consumption accordingly.

Current output 0-20mA / 4-20mA Voltage output +/-10V

TTL: input /A HTL: n.c.

TTL: input /B HTL: n.c.

TTL: input A HTL: input A

TTL: input B HTL: input B

FU 252

Control

Aux. output 5.5V

(max. 250 mA)

GND ( - ) for analogue signals

Supply +18...30 VDC

(typ. 70 mA)

GND ( - )

GND ( - )

4.1. Example for use of TTL encoders

If applicable, the encoder can be supplied from the FU252 converter. Where the encoder is already supplied from a remote source, we recommend fully differential operation, with no

GND connection between encoder and converter (see figures a. and b.)

TTL encoder

FU 252

+

A

A

A

A

11 (+5.5V)

8

9

B

B

-

B

B

2

3

12 (GND)

Screen

TTL encoder

+

A

A

B

B

-

FU 252

11 (+5.5V)

A

A

8

9

B

B

2

3

12 (GND)

Screen

Fu252_02g_oi_e.doc / Apr-16 Page 9 / 36

4.2. Example for use of HTL encoders

The encoder may be supplied from the same source as the converter, or from another source.

HTL encoder

+24V

+

Screen

FU 252

A

9

B

GND

3

12 (GND)

4.3. Proximity switches, photocells etc.

These connections are fully similar to a HTL incremental encoder. With single channel operation, input B remains unconnected or can be used to select the output polarity. With use of two independent frequencies for forming sum, difference or ratio, input B is used for the second input frequency.

To use sensors with 2-wire NAMUR characteristics:

set the inputs to HTL and NPN

connect the positive wire of the sensor to the corresponding input and the negative wire to GND.

4.4. Analog output

The unit provides a +/-10V voltage output and a 0 - 20mA / 4 – 20 mA current output at a resolution of 14 bits, i.e. the voltage output operates in steps of 1.25 mV and the current output operates in steps of 2.5 µA.

The nominal load of the voltage output is 2 mA and the current output accepts loads between zero and 270 ohms.

The Analog ground uses a separate terminal, which however internally is connected to the GND potential of the power supply.

Screen

1

+/- 10V

(Imax = 2 mA)

Voltage out

4

GND

Current out

7

20 mA

(R = 0 - 270 ohms)

Important note: “Voltage out” and “Current out” cannot be used together.

Please do never connect mA and V simultaneously!

The calibration depends on “Analog output format” (see chapter

5.3

)

Fu252_02g_oi_e.doc / Apr-16 Page 10 / 36

4.5. Serial interface

The unit provides selectively a RS232 resp. RS485 interface, however only one of the two can be used at a time. Serial communication allows to read out conversion results and to set parameters and variables by PC, according to need.

+5V

GND int.

RS485

T+

T-

R+

R-

TxD

RxD

RS232

Sub-D-9 (female on unit site)

GND

TxD

RxD

PC

Please connect only pins 2, 3 and 5 !

FU 252

120 Ohms

120 Ohms

T+

T-

R+

R-

120 Ohms

120 Ohms

RS485- Bus

( 4- wire )

T+

T-

R+

R-

FU 252

120 Ohms

T-

T+

120 Ohms

FU 252

( 2- wire )

Fu252_02g_oi_e.doc / Apr-16 Page 11 / 36

5. DIL Switch Settings

There is one 8-position switch located on the top side (DIL1), and another 8-position switch is located on the bottom side of the unit (DIL2). These switches provide major settings of the desired properties of the unit.

Changes of switch settings will become active only after cycling the power supply of the unit!

Positions 7 and 8 of switch DIL2 are for internal factory use only and must both be set to OFF at any time during normal operation

Teach button

Top side

Switch DIL1

Bottom side

Swit ch DIL2

5.1. Basic mode of operation

Positions 2, 3 and 4 of switch DIL1 on the top side allow setting the following operation modes:

DIL1

1 2 3 4 5 6 7 8

Setting example:

Quadrature input A / B / 90° on on on on on off on off on on off off off on on off on off off off on off off off

Mode of operation

Channel A only

Ratio A : B

Sum A + B

Quadrature A / B / 90°

Channel B only

Product A x B

Difference A - B

A = impulse, B = direction / sign

Fu252_02g_oi_e.doc / Apr-16 Page 12 / 36

5.2. Impulse levels and symmetric / asymmetric input formats

Positions 5 and 7 of DIL1 together with positions 3 to 6 of DIL2 allow setting of all imaginable combinations of levels and formats.

All subsequent tables use the following definitions:

„0“ = switch OFF, „1“ = switch ON and

„x“ = position not important

Switch settings refer to impulse inputs A / B only, but the

Control Input (terminal 10) provides always HTL / PNP format, i.e. you must apply a positive voltage 10 – 30 volts to activate the function

Where you use 2-wire sensors with NAMUR characteristics, connect the positive pole of the sensor to the corresponding input terminal, and the negative pole to GND

Where subsequently you read (A) or (B), this indicates that the inputs expect asymmetric signals and you will not need the corresponding inverted signals

Where however you read (A and /A) or (B and /B), this indicates that the inputs expect symmetric differential signals according to RS422 standard, i.e. it is mandatory to apply also the inverted signals

5.2.1. Standard settings

If you just use encoders or sensors according to common industrial standards, and if also all input signals should have the same level, you just can use one of the following three standard settings and do not need to consider all further alternatives of switch settings.

DIL1 DIL2 Input Characteristics Encoder Type

5 6 7 3 4 5 6

0

0 0 0 0 0

Asymmetric HTL input (A, B),

10 - 30 V level, NPN (switching to -) or

Push-Pull or NAMUR characteristics

1

0 0

0 0 0

Asymmetric HTL input (A, B),

10 - 30 V level, PNP (switching to +) or

Push-Pull characteristics

Symmetric TTL signals or

0

1

0 0 0 0

RS422 signals (A, /A), (B, /B)

(differential, including inverted signal)

Standard HTL encoders,

Proximity switches,

Photo switches etc.

PNP Proximity switches,

Photo switches etc.

Standard TTL encoders providing A, /A, B, /B output channels

Fu252_02g_oi_e.doc / Apr-16 Page 13 / 36

5.2.2. Settings for special applications

Where you find that the standard settings shown before are not suitable for your application, please go through the following setting options and find out the input levels and characteristics you need.

DIL1 DIL2

5 6 7 3 4 5 6

Characteristics of input A Characteristics of input B

x

x

x

x

x

x

x

x

0

0

0

0

0

0

0

1

0

1

1

0

1

0

1

0

TTL level (A)

HTL level (A and /A)

TTL level (A)

TTL level (A and /A)

TTL level (B)

HTL level (B and /B)

TTL level (B and /B)

TTL level (B)

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

x

0

0

0

1

1

1

1

1

1

1

1

1

1

0

0

0

0

1

1

1

0

1

1

0

0

1

1

0

0

1

1

0

1

0

1

0

1

0

1

0

HTL level NPN (A)

HTL level NPN (A)

HTL level NPN (A)

HTL level PNP (A)

HTL level PNP (A)

HTL level PNP (A)

TTL level (A and /A)

TTL level (A)

TTL level (A and /A)

TTL level (A)

HTL level PNP (B)

TTL level (B and /B)

TTL level (B)

TTL level (B and /B)

TTL level (B)

HTL level NPN (B)

HTL level NPN (B)

HTL level NPN (B)

HTL level PNP (B)

HTL level PNP (B)

5.3. Analog output format

The desired output format of the Analog output can be set by positions 1 and 2 of switch DIL2.

DIL2 Output format

1 2

0 0

Voltage 0 … +10 V

0 1

1 0

1 1

Voltage +/- 10 V

Current 4 – 20 mA

Current 0 – 20 mA

With this setting the format depends on the parameter „Analog

Mode“ which can be set by PC. Since the factory default setting of parameter “Analog Mode” is “1”, the format will be a 0 …

+10 V output under default conditions.

Fu252_02g_oi_e.doc / Apr-16 Page 14 / 36

5.4. Selecting the RS232 or the RS485 serial interface

Position 1 of switch DIL1 selects between the RS232 interface and the RS485 interface. All

connection details have already been explained in section 4.5

.

DIL1 / 1 Serial Interface

0

RS232 interface is active (RS485 is switched off)

1

RS485 interface is active (RS232 is switched off)

5.5. Teach function, Test function, loading of default settings

Positions 6 and 8 of switch DIL1 allow to set the following functions:

DIL1 Function

6 8

x 0

Unit returns to the factory default parameters after power-down

x 1

Unit always keeps the parameters according to customer setting

0 x

Push button and yellow LED operate in TEACH mode (see chapter 7 )

1 x

Push button and yellow LED operate in TEST mode, Teach is disabled (see chapter 7 )

After successful commissioning, please make sure to set positions

6 and 8 to “ON”. Otherwise, cycling of the power supply or touching the push button inadvertently would result in overwriting your parameter settings.

Fu252_02g_oi_e.doc / Apr-16 Page 15 / 36

6. Commissioning

With all basic applications, you can use the Teach feature for commissioning of the unit.

Extended functions need a PC for setup and are described under section 7.

As a first step it is advisable to check the input frequencies by means of the LED marked

“Status”. DIL switch 6 must be set to ON for this test.

When you press the TEACH button one time, the yellow LED will be lit when the unit detects a frequency on input A. The LED will be OFF when no input frequency can be detected.

When you press the TEACH button once more, you can also check input B (if applicable). With all operation modes using two independent frequencies, again the yellow LED will be lit when a frequency has been detected on input B.

With operation modes using input B to define the direction and polarity (quadrature or static), the yellow LED will indicate that the actual input signals provide positive output (LED on) or negative output (LED off). Where you like to get the other polarity, you must change the information of direction on A/B inputs

The TEACH function can only be used when the DIL switches are set for operations with one input frequency only (i.e. A only, B only, quadrature A/B or A = impulse and B = direction).

You must switch over to combined operations A + B, A - B, A x B or A : B only after you have successfully run the Teach function for both channels. Parameter „Teach-Mode“ will determine if or if not an automatic re-scaling will apply after switch-over.

Fu252_02g_oi_e.doc / Apr-16 Page 16 / 36

6.1. Conversion of one only frequency

(single channel or dual channel with direction signal)

Make sure that the DIL switches are set according to the encoder you use, and that position 6 of switch DIL1 is OFF (Teach function active).

 Self-test: Upon power up, both front LED’s must be lit first, and the yellow status LED must switch off after the self-test has been concluded successfully (approx.1 s).

 Scaling of the Analog output with use of the Teach function:

Press the Teach button one time. The status LED will blink in a slow sequence while the unit waits for setting of the minimum frequency. Please make your encoder now generate the frequency where you expect your Analog output to be zero (in general this will be 0 Hz at standstill)

 Press the Teach button again. This stores your minimum frequency definition, the LED will blink in a fast sequence and the unit waits for setting of the maximum frequency. Please move your encoder now at a speed where you expect full scale Analog output.

 Press the teach button once more. This stores your maximum frequency definition and the

LED will switch off. After this Teach procedure, your Analog output is set to a 0 – 10 volts range between the minimum and the maximum input frequency.

6.2. Conversion and combination of two independent frequencies (A + B, A - B, A x B, A : B)

In principle, the Teach procedure is the same as described under 6.1. However, we must first teach every of the two channels A and B separately.

 Set the DIL switch to “Channel A only” (see

5.1

) and teach the minimum and the maximum

frequency for channel A like shown before.

 Now set the DIL switch to “Channel B only” and run the teach procedure for minimum and maximum frequency of channel B.

 Finally, set the DIL switch according to the combination of the frequencies that you desire.

The unit is able to automatically re-scale the output swing in a way that you receive full scale output when the result of the A/B calculation reaches the maximum

(see parameter “Teach Mode”).

Please observe that minimum and maximum frequency settings for inputs A and B must never be “0” when you intend to use the ratio function A : B !

Fu252_02g_oi_e.doc / Apr-16 Page 17 / 36

7. PC Setup via Operator Software OS3.x

You can apply the full set of functions when you use a PC and our operator software OS3.x for setup of the unit (at this time the actual version is OS3.2).

You can download this software and full instructions, free of charge, from our homepage www.motrona.com

Connect your PC to the converter, using a serial RS232 cable like shown in section 4.5

of this

manual. Make sure, the cable only uses pins 2, 3 and 5. Pins 2 and 3 must be crossed.

Run the OS3.x software and you will see the following screen:

In case your text and color fields remain empty and the headline says „OFFLINE“, you must verify your DIL switch setting and the serial settings of the unit. To access serial settings, please select „COMMS“ from the menu bar.

Fu252_02g_oi_e.doc / Apr-16 Page 18 / 36

Ex-factory, all motrona units use the following serial default settings:

Unit No. 11, Baud rate 9600, 1 start/ 7 data/ parity even/ 1 stop bit

If the serial settings of your unit should be unknown, you can run the „SCAN“ Function from the „TOOLS“ menu to find out.

On the left side of your screen you find the Edit window with all parameters.

Under „INPUTS“ you find some soft keys allowing to switch ON or OFF of the Control commands. Indicator boxes in the RS column signal if the corresponding command is set by serial communication. Indicator boxes in the PI/O column indicate if the same command is set by hardware input.

Under OUTPUTS you can get information about the state of the unit. The indicator boxes

„Status A“ and „Status B“ especially serve to check the input frequencies:

Status A will be lit while a frequency is detected on input A

(except with operating mode „B single“)

Status B will be lit while a frequency is detected on input B

(except with operating modes „A single“, „A/B_dir“ and „A/B_90“)

The color bar in the “Output Value” field indicates the actual percentage of the output signal in a range of +/- 100 %.

The Control keys allow Read-out, Transmission and saving of parameter settings.

For enduring memorization of parameters entered by keypad, you should press the ENTER key every time you have completed one line.

Optionally you can also use the soft keys „Transmit“ or „Transmit All“ for temporary storage of your last setting or all previous settings (storage until next power-down), and finally use the „Store EEProm“ key when you like to have an enduring storage of all settings transmitted before.

Fu252_02g_oi_e.doc / Apr-16 Page 19 / 36

8. Parameter Description

General Setting:

Direction

Filter A/B

Linearisation Mode

Parameter

Register Setting (.8):

Multiplier

Divisor

Offset

Read-out from (:8)

Description

These operands allow converting the result to the desired engineering units.

This conversion affects the numeric value for serial read out from register (:8) only, but not the scaling of the Analog output.

With settings Multiplier = 1,0000

Divisor = 1,0000

Offset = 00000 the readout from register < :8 > equals to the percental result

(xxx.xxx%) where 100,000% has been defined by the TEACH minimum and TEACH maximum settings

Multiplier

=

Measuring result in % of full scale

x

+

Offset

Divisor

When you set “Divisor” to 0, this will completely skip all calculations.

This step is advisable when you need very fast response with the shortest conversion time possible.

This parameter allows inversion of the polarity of the Analog output.

(Important only with operating modes A/B (2x90

) or A = Impulse and B

= direction.

0 = no inversion

1 = output inverted

Digital filter for smoothing the Analog output with combined modes

(calculations from A and B)

00 = Filter off (immediate response to changes of the input signal)

01 = Filter with time constant 1,563 ms

02 = Filter with time constant 3,125 ms

03 = Filter with time constant 6,250 ms etc.

12 = Filter with time constant 3200 ms (slow response)

Please note:

These time constants are valid for sampling time settings of 1 ms. and higher sampling times will correspondingly increase the time constant

0 = Linearisation OFF, parameters P1 to P16 are irrelevant.

1 = Linearisation in a range from 0% to 100 %

2 = Linearisation over full range –100% to +100%

See example under section 9 „Linearisation“

Fu252_02g_oi_e.doc / Apr-16 Page 20 / 36

Channel A Setting

Sampling Time A

Wait Time A

Filter A

Reset Value A

Parameter

Frequency Control

Input Filter

*) This Parameter is only relevant when remarkable Sampling

Times are used. It determines the way how the unit responds to gaps within one sampling period.

Description

Frequency control and response characteristics to frequency gaps for channels A and B. This setting is taken as a 4 bit binary value.

Range 00 – 15, default setting 10 (only to be changed in special case)*

Programmable hardware filter for the impulse inputs

0 = no filtering

1 – 3 : filter low – medium - high

Time base for measuring the frequency on input A

Range 0 – 9,999 seconds

Setting 0 provides a sampling time of 750 µs

Zero setting time for missing frequency on input A.

Range 0.01 – 9.99 seconds

The Analog signal goes to zero when no input impulse appears during the Wait Time.

Example:

With setting 0,01 s all frequencies <100 Hz will produce zero output

Digital filter for smoothing the Analog output with unstable frequencies on input A.

00 = Filter off (immediate response to changes of the input signal)

01 = Filter with time constant 1.563 ms

02 = Filter with time constant 3.125 ms

03 = Filter with time constant 6.250 ms etc.

07 = Filter with time constant 100 ms (slow response)

Please note:

These time constants are valid for sampling time settings of 1 ms. and higher sampling times will correspondingly increase the time constant

Range -1 100 000,0 to +1 100 000,0

Input A will be overwritten by this simulated frequency value, if the control input is active and the “Reset A” function has been assigned to the control input.

Sampling Time

Input A : Bit0 = 1, Bit1 = 0. Input B : Bit2 = 1, Bit 3 = 0

Input A : Bit0 = 0, Bit1 = 1. Input B : Bit2 = 0, Bit 3 = 1

Fu252_02g_oi_e.doc / Apr-16 Page 21 / 36

Parameter

Channel B Setting

Sampling Time B

Wait Time B

Filter B

Reset Value B

Analog Setting

Teach Minimum A

Teach Maximum A

Teach Minimum B

Teach Maximum B

Description

Time base for measuring the frequency on input B

Range 0 – 9,999 seconds

Setting 0 provides a sampling time of 750 µs

Zero setting time for missing frequency on input B.

Range 0.01 – 9.99 seconds

The Analog signal goes to zero when no input impulse appears during the Wait Time.

Example:

With setting 0,01 s all frequencies <100 Hz will produce zero output

Digital filter for smoothing the Analog output with unstable frequencies on input B.

00 = Filter off (immediate response to changes of the input signal)

01 = Filter with time constant 1.563 ms

02 = Filter with time constant 3.125 ms

03 = Filter with time constant 6.250 ms etc.

07 = Filter with time constant 100 ms (slow response)

Please note:

These time constants are valid for sampling time settings of 1 ms. and higher sampling times will correspondingly increase the time constant

Range -1 100 000,0 to +1 100 000,0

Input B will be overwritten by this simulated frequency value, if the control input is active and the “Reset B” function has been assigned to the control input.

These two couples of settings define your minimum and maximum input frequency for input A and input B (if applicable), where your Analog output moves between 0 V and 10 V.

This is how you can enter your minimum and maximum settings:

either by operating the Teach pushbutton, like described already in

section 6.1

or by entering the frequency settings directly by keyboard to the parameter field of your screen, without using the TEACH function

Fu252_02g_oi_e.doc / Apr-16 Page 22 / 36

Parameter

Teach Mode

Description

This parameter is only important when your application provides a combination of the two inputs (e.g. A + B). The setting determines how to scale the total result of the selected A/B calculation

Teach Mode = 0: The unit will automatically calculate a new “full scale” output, resulting from the expected maximum values that can come up with the combined result from A and B *)

Teach Mode = 1: The total result will use the same scaling as applied to

input channel A *)

Teach Mode = 2: Before calculating the combination result, the channel B frequency will be pre-scaled using the conversion parameters „Multiplier“ and „Divisor“ , so that a direct compare between two frequencies of different scaling can take place.

Analog Mode:

Determines which Analog output format should be used (see 5.3

):

V V mA mA

Min.

Max.

Encoder

Min.

Max.

Encoder

Min.

Max.

Encoder

Min.

Max.

Encoder

Output Mode = 0

-10V ... 0 ... +10V

Output Mode = 1

0 ... +10V

Output Mode = 2

4 ... 20 mA

Output Mode = 3

0 ... 20 mA

Analog Offset: Parameter to shift the zero position of the Analog output over the full range of +/- 9999 mV resp. +/-19,998 mA (if applicable). Normal setting is 0.

Analog Gain: Allows setting the maximum swing of the Analog output.

Setting 1000 results in a full scale signal of 10 volts or 20 mA, setting 500 will reduce the signal to 5 volts etc.

*) Example: Provided you have set both inputs A and B to a range of 0 … 10 kHz for a 0 … 10 volts output, and after this you switch over to the sum mode A + B:

Teach Mode = 0 would allow to apply the full frequency range of 10 kHz to each of the inputs at the same time, because the automatic re-scaling function has set a full range scale of 20 kHz for the expected maximum of the sum A + B.

Teach Mode = 1 would reach the full-scale output already with a sum of A + B = 10 kHz, because only the 10 kHz / 10 volts scaling of input A will apply

Fu252_02g_oi_e.doc / Apr-16 Page 23 / 36

Parameter

Serial

Communication:

Serial Unit No.:

Serial Baud Rate:

Serial Format:

Serial Protocol:

Description

With RS 485 applications it is necessary to attach a specific address to each unit, since up to 32 units can be connected to the same bus. You can choose any address number between 11 and 99.

The address must however not contain a “0“ because these numbers are reserved for collective addressing.

Setting

0*

1

2

3

4

5

Setting

0*

1

2

3

4

5

6

# data bits

7

7

7

7

7

7

* = Factory setting

Parity even even odd odd none none

Baud Rate

9600

4800

2400

1200

600

19200

38400

# stop bits

1

2

1

2

1

2

8

9

6

7

8

8

8

8 even odd none none

1

1

1

2

* = Factory setting

Determines the sequence of characters sent, when you use the serial output for cyclic data transmission under timer control

(xxxxxxx is the measuring value transmitted).

Serial Protocol = 0 :

Serial Protocol = 1 :

Setting “1” will suppress transmission of the unit number, therefore the transmission cycle is shorter than with setting “0”

Unit No.

1 1 +/- X X X X X X LF CR

+/- X X X X X X LF CR

Fu252_02g_oi_e.doc / Apr-16 Page 24 / 36

Parameter

Serial Timer:

Serial Value:

Description

This register determines the cycle time in seconds for cyclic transmission when the Printer Mode is switched on.

Range 0.001 to 99.999 seconds.

With setting “0” all cyclic transmission is switched off and the unit will only send data upon request (PC mode *)

Sets the code of the register of which the content should be sent with cyclic transmission.

Setting range 00 – 09 (corresponds to register codes :0 to :9) and 10 - 19 (corresponds to register codes ;0 to ;9)

For clarification of register codes see sections 10

and 11 .

Input Setting:

Input Configuration:

Input Function:

*) The serial port of the unit can operate in either “PC-Mode“ or in

“Printer Mode“.

With “PC-Mode“, the unit receives a request string and responds with a corresponding data string. For details of the protocol see separate description

“SERPRO“.

With “Printer Mode“ the unit sends data without any request and under Timer control as described subsequently.

As soon as the unit receives a character, it automatically switches over to PC

Mode and operates according to protocol. When for a period of 20 s no character has been received, the unit switches automatically back to

“Printer Mode“ and starts cyclic data transmission again.

Sets the switching characteristics of the „Control“ input (terminal 10):

0 = function „active HIGH“, 1 = function „active LOW“

Selects the function of the “Control” input (terminal 10):

0 = no control function

1 = Replaces the frequency applied to input A by a fixed frequency value as set under parameter „Reset Value A“

2 = Replaces the frequency applied to input B by a fixed frequency value as set under parameter „Reset Value B“

3 = Replaces the result of the combination A / B by a fixed value as set under parameter „Reset Value A/B“

4 = Freezes the actual frequency value of input A

5 = Freezes the actual frequency value of input B

6 Freezes both frequencies A and B

7 = Starts a serial transmission of the defined register value

Fu252_02g_oi_e.doc / Apr-16 Page 25 / 36

Parameter

Both Channel Setting:

Multiplier:

Divisor:

Offset:

Linearisation Setting:

P1_x to P16_x:

P1_y to P16_y:

Description

These settings provide a final scaling of the calculation result from the combined operation modes A / B

Interpolation points for linearization (initial values)

Interpolation points for linearization (substitute values)

(For clarification see section 9 )

Fu252_02g_oi_e.doc / Apr-16 Page 26 / 36

9. Free Programmable Linearization

This programmable feature allows the user to convert a linear input signal to a non- linear

Analog output. There are 16 programmable x/y coordinates available, which can be set in any desired distance over the full conversion range. Between two coordinates, the unit uses linear interpolation. Therefore it is advisable to use more coordinates in a range with strong curves and only a few coordinates where the curvature is less.

To specify your desired linearization curve, you must first set the „Linearisation Mode“ register to either 1 or 2.

Use registers P1(x) to P16(x) to specify the coordinates on the x-axis. These are the Analog output values that the unit normally would generate according to the actual input frequency.

These settings must be in % of full scale.

Now enter the attached values to registers P1(y) to P16(y). These are the values that the Analog output will generate instead of the x- values, i.e. P2(y) will substitute P2(x) etc.

x-registers must use continuously increasing settings, i.e. P1(x) must have the lowest and P16(x) must have the highest setting

All entries use a percental format of xx.xxx% full scale.

Setting 000.000% means zero output and setting 100.000% means full scale output.

With Linearisation Mode set to 1, it is a must to set P1(x) to 0% and

P16(x) to 100%. Linearisation is defined in the positive range only and the negative range will be a mirror image of the positive range with reference to zero.

With Linearisation Mode set to 2, it is a must to set P1(x) to –100% and P16(x) to +100%. This enables the user to set curves which are not symmetric to the zero position. y y

P1(x)= -100%

P1(y)= 95%

*) Output mode = 0

P8(x)= 0%

P8(y)= 80%

P1(x)= 0%

P1(y)=10%

P16(x)=100%

P16(y)= 80% x x

*)

P16(x)=+100%

P16(y)= -60%

Linearisation Mode = 1 Linearisation Mode = 2

Fu252_02g_oi_e.doc / Apr-16 Page 27 / 36

You can visualize your curve on the PC screen or by means of an external oscilloscope.

For this, select TOOLS, then TEST and there „Analog Voltage Function“. The unit will now simulate a repeating frequency course over the full range and generate the Analog signal accordingly. When you use the Scope function of the operator software, you must set the serial code to „:1” to record the Analog output.

Fu252_02g_oi_e.doc / Apr-16 Page 28 / 36

10. Monitor Functions

The monitor function of the OS3.2 PC software allows to display some important data on the PC screen with a continuous refresh cycle.

Select „Monitor“ from the „Tools“ menu to open the basic view of the monitor window. Click to

“Define” to open the definition window. You will find a list with all accessible parameters and actual values, where however the texts may be unfounded.

With FU252, only the following register codes make sense:

C1 C2 Description

: 8 Actual conversion result in % of full-scale, format xxx.xxx % *)

: 9 Actual frequency on input A in Hz, resolution 0.1 Hz, format xxx xxx.x Hz

; 1 Actual frequency on input B in Hz, resolution 0.1 Hz, format xxx xxx.x Hz

; 3 Actual output voltage of the Analog output, scaling 0 … 10 000 millivolts

*) In accordance to the applied conversion scaling see chapter 8 .

Fu252_02g_oi_e.doc / Apr-16 Page 29 / 36

Click to the Status field, next to the desired register code (where you read ON or OFF). Now you can toggle this position between ON and OFF by touching any key.

Set all of the register codes to ON which you afterwards would like to trace on the monitor.

Switch all unused register codes to OFF.

To change the text shown with the register code, click to the corresponding text field. The same text will now appear in the “Text Editor” window below the parameter window. Rename the text according to your desire and press ENTER to store the new text in the corresponding monitor line.

When all desired codes have been set to ON and the texts have been renamed according to need, click OK. Where, besides the display data on the screen, you also like to record all data to a file on your hard disc, click first to „Store to File“ and set the corresponding check box.

After starting the monitor, you will see the following window where all values are updated continuously:

Fu252_02g_oi_e.doc / Apr-16 Page 30 / 36

11. Data Readout via Serial Interface

All register codes from section 10 are also available for serial readout by PC or PLC. For

communication the FU252 converter uses the Drivecom Protocol according to ISO 1745. All protocol details can be found in our manual SERPRO_2a.doc which is available for download from our homepage www.motrona.com

To request for a data transmission you must send the following request string to the converter:

EOT AD1 AD2 C1 C2 ENQ

EOT = control character (Hex 04)

AD1 = unit address, High Byte

AD2 = unit address, Low Byte

C1 = register code, High Byte

C2 = register code, Low Byte

ENQ = control character (Hex 05)

The following example shows the request string for readout of the actual frequency of input A

(code :9) from a unit with unit address 11:

ASCII Code:

Hex Code:

EOT

04

1

31

1

31

:

3A

9

39

ENQ

05

Binary Code: 0000 0100 0011 0001 0011 0001 0011 1010 0011 1001 0000 0101

After a correct request, the unit will respond:

STX C1 C2 x x x x x x x ETX BCC

STX = control character (Hex 02)

C1 = register code, High Byte

C2 = register code, Low Byte xxxxx = readout data

ETX = control character (Hex 03)

BCC = block check character

For all further details see SERPRO_2a.doc.

Fu252_02g_oi_e.doc / Apr-16 Page 31 / 36

12. Dimensions

40 mm (1.575’’)

91mm (3.583’’)

74 mm (2.913’’)

Front view

Side view Top view

Fu252_02g_oi_e.doc / Apr-16 Page 32 / 36

13. Technical Specifications

Power supply:

Connections:

Encoder supply:

Connector type:

Output voltage:

Output current:

Incremental Input: Signal levels:

HTL characteristic:

HTL internal resistance:

Channels:

Frequency:

Measurement accuracy:

Control Input:

Input voltage:

Protection circuit:

Ripple:

Consumption:

Analog outputs:

Application:

Signal levels:

Pulse time:

Voltage:

Current:

Resolution:

Accuracy:

Resolution per bit:

Reaction time

(standard operation):

Reset time (in case of a sudden interruption):

Housing:

Ambient temperature:

Failure rate:

Conformity and standards:

Material:

Mounting:

Dimensions (w x h x d):

Protection class:

Weight:

Operation:

Storage:

MTBF in years:

EMC 2004/108/EC:

Guideline 2011/65/EU:

18 … 30 VDC reverse polarity protection

≤ 10 % at 24 VDC approx. 75 mA at 24 V (unloaded encoder supply) screw terminals, 1.5 mm² / AWG 16

+ 5.5 VDC / +/- 5 % max. 250 mA

RS422: Differential voltage > 1 V

TTL: LOW: 0 … 0.5 V / HIGH: 2.5 … 5.3 V

HTL: LOW: 0 … 3 V / HIGH: 10 … 30 V

NPN / PNP

Ri ≈ 4.75 kOhm

A, /A, B, /B max. 1 MHz at RS422 and TTL symmetrical max. 200 kHz at HTL and TTL asymmetrical

0.02 % +/- 1 digit proximity switches or control commands

LOW < 3 V / HIGH >10 V min. 5 ms

- /+ 10 V (external load max. 5 kOhm)

0/4 … 20 mA (burden max. 270 Ohm)

14 Bit

0.1%

1.25 mV / 2,5 µA depends on sampling time and frequency; approx. 1 ms (fin > 2 kHz); 1/f in (fin < 1 kHz)

5 ms (without average), 700 ms (max. average) plastic

35 mm top hat rail (according to EN 60715)

40 x 79 x 91 mm / 1.5748 x 3.1102 x 3.5827 inch

IP20 approx. 190 g

0 °C … +45 °C / +32 … +113 °F (not condensing)

-25 °C … +70 °C / -13 … +158 °F (not condensing)

75.2 a (long-term usage at 60 °C / 140 °F )

EN 61000-6-2, EN 61000-6-3, EN 61000-6-4

RoHs-conform

Fu252_02g_oi_e.doc / Apr-16 Page 33 / 36

14. Internal Registers and Serial Codes

Commands:

# Name

7 FreezeBoth

8 FreezeB

9 FreezeA

10 ResetBoth

11 ResetB

12 ResetA

13 ActivateData

14 StoreEEProm

65

66

67

68

61

Code

62

63

64

Parameters:

# Menu

0 Register-Setting(:8)

1

2

3 General-Setting

4

5

6

7

8 Channel-A-Setting

9

10

11

12 Channel-B-Setting

13

14

15

16 Analog-Setting

17

18

19

20

21

22

23

TeachMaxA

TeachMinB

TeachMaxB

TeachMode

AnalogMode

AnalogOffset

AnalogGain

24 Reserved

25 Serial-Communication SerialUnitNo.

26 SerialBaudRate

27

28

29

30

SerialFormat

SerialProtocol

SerialTimer

SerialValue

Name

Multiplier

Divisor

Offset

Direction

FilterAB

LinearisationMode

FrequencyControl

InputFilter

SamplingTimeA

WaitTimeA

FilterA

ResetValueA

SamplingTimeB

WaitTimeB

FilterB

ResetValueB

TeachMinA

CmdBit

0040

0020

0010

0008

0004

0002

1000

0001

SerStatus

Yes

Yes

Yes

Yes

Yes

Yes

Yes

Yes

BusStatus

No

No

No

No

No

No

No

No

E0

90

91

92

30

31

32

Code

00

01

02

46

11

08

D2

D3

Min Max

-1000000 1000000

0 1000000

-1000000 1000000

0

0

0

0

0

1

12

2

15

3

33

09

D6

0

1

0

9999

999

7

D7 -10000000 10000000

34 0 9999

10

D8

1

0

999

7

D9 -10000000 10000000

03 -10000000 10000000

04 -10000000 10000000

05 -10000000 10000000

06 -10000000 10000000

12 0 2

07 0 3

47

48

-9999

0

9999

10000

0

0

0

0

0

0

0

9999

99

6

99999

19

9

1

ExtStatus

Yes

Yes

Yes

Yes

Yes

Yes

No

No

Default

10000

0

0

10

0

0

0

0

0

100

0

100

0

0

0

0

0

10000

0

10000

0

1

0

1000

1000

11

0

0

0

0

0

Fu252_02g_oi_e.doc / Apr-16 Page 34 / 36

# Menu

31 Input-Setting

32

33 Both-Channel-Setting

34

35

60

61

62

63

64

65

66

67

43

44

45

46

47

48

49

50

51

52

53

54

55

56

57

58

59

36 Linearisation-Setting

37

38

39

40

41

42

A7

A8

A9

B0

B1

B2

B3

B4

B5

B6

A0

A1

A2

A3

A4

A5

A6

B7

B8

B9

C0

C1

C2

C3

C4

C5

C6

C7

C8

C9

D0

D1

Code

E2

E3

13

14

15

Name

InputConfiguration

InputFunction

Multiplier

Divisor

Offset

P4(y)

P5(x)

P5(y)

P6(x)

P6(y)

P7(x)

P7(y)

P8(x)

P8(y)

P9(x)

P1(x)

P1(y)

P2(x)

P2(y)

P3(x)

P3(y)

P4(x)

P9(y)

P10(x)

P10(y)

P11(x)

P11(y)

P12(x)

P12(y)

P13(x)

P13(y)

P14(x)

P14(y)

P15(x)

P15(y)

P16(x)

P16(y)

Default

0

0

10000

10000

0

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

Min Max

0 1

0 7

-1000000 1000000

1 1000000

-1000000 1000000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

-100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

100000

Fu252_02g_oi_e.doc / Apr-16 Page 35 / 36

15. Commissioning Form

Date:

Operator:

Software:

Serial No.:

General Setting

Input

Direction:

Linearisation Mode:

Frequency Control:

Sampling Time::

Wait Time:

Filter

Reset Value:

Analog Setting

Teach Minimum:

Teach Maximum

Serial Communication

Teach Mode

Analog Mode

Serial Unit No

Input Setting:

Both Channel Setting:

Serial Baud Rate

Serial Format

Input Configuration

Multiplier:

Linearization

P01_X:

P02_X:

P03_X:

P04_X:

P05_X:

P06_X:

P07_X:

P08_X:

DIL Switch 1

P01_Y:

P02_Y:

P03_Y:

P04_Y:

P05_Y:

P06_Y:

P07_Y:

P08_Y:

Channel A

Analog Offset

Analog Gain

Divisor:

P09_X:

P10_X:

P11_X:

P12_X:

P13_X:

P14_X:

P15_X:

P16_X:

Channel A

Filter A/B:

Input Filter:

-

-

-

-

Serial Protocol

Serial Timer

Serial Value

Unit: FU252

Offset:

P09_Y:

P10_Y:

P11_Y:

P12_Y:

P13_Y:

P14_Y:

P15_Y:

P16_Y:

Channel B

Channel B

Input Function 0

DIL Switch 2

-1- -2- -3- -4- -5- -6- -7- -8- -1- -2- -3- -4- -5- -6- -7- -8-

OFF OFF

Fu252_02g_oi_e.doc / Apr-16 Page 36 / 36