Universal converter
9116B
– Input for RTD, TC, Ohm, potentiometer, mA and V
– Supply for 2-wire transmitters
– Active / passive mA output and relay output
– Can be supplied separately or installed on power rail, PR type 9400
– SIL 2-certified via Full Assessment
Advanced features
• Configuration and monitoring by way of detachable display
front (PR 4501); process calibration, signal and relay
simulation.
• Advanced relay configuration, e.g. setpoint, window, delay,
sensor error indication and power monitoring.
• Copying of the configuration from one device to others of the
same type via PR4501.
• Reduced Uo Ex data < 8.3 V for active input signals.
• TC inputs with internal CJC or external CJC for higher
accuracy.
• The device automatically detects whether it must supply an
active or a passive current signal.
Connections
Application
• 9116B can be mounted in the safe area and in zone 2 / cl. 1
div. 2 and receive signals from zone 0, 1, 2 and zone 20, 21,
22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
• Conversion and scaling of temperature, voltage,
potentiometer and linear resistance signals.
• Power supply and signal isolator for 2-wire transmitters.
• Monitoring of error events and cable breakage via the
individual status relay and/or a collective electronic signal via
the power rail.
• The 9116 has been designed, developed and certified for use
in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 1 red front LED indicate operation status and
malfunction. 1 yellow LED indicates relay status.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
185 g
200 g / 285 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
Screw terminal torque.................................... 0.5 Nm
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Isolation voltage, test /working:
Input to any....................................................
Analog output to supply.................................
Status relay to supply.....................................
Communications interface.............................
19.2...31.2 VDC
1.25 A SB / 250 VAC
≤ 3.5 W
2.6 kVAC / 300 VAC
reinforced isolation
2.6 kVAC / 300 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
Communication enabler 4511
/ Programming front 4501
Min. 60 dB (0...100 kHz)
Signal / noise ratio.........................................
Response time (0...90%, 100...10%):
Temperature input (programmable)............... 1...60 s
mA / V input (programmable)......................... 0.4...60 s
Accuracy........................................................ Better than 0.1% of selected
range
Auxiliary supplies for 9116B1:
2-wire supply (terminal 54...52)...................... 28...16.5 VDC / 0...20 mA
Auxiliary supplies for 9116B2:
2-wire supply (terminal 54...52)...................... 22...16.5 VDC / 0...20 mA
Input specifications
Output specifications
Current output: Signal range......................... 0...20 mA
Programmable current ranges....................... 0...20 / 4...20 / 20...0 and
20...4 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span/100 Ω
Sensor error indication, current
output............................................................. 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Output limitation, on 4...20
and 20...4 mA signals.................................... 3.8...20.5 mA
Output limitation, on 0...20
and 20...0 mA signals.................................... 0...20.5 mA
Current limit.................................................... ≤ 28 mA
2-wire 4…20 mA output: External
2-wire supply range........................................ 3.5...26 VDC
Signal range................................................... 4…20 mA
Max. load resistance [Ω]................................ (Vsupply - 3.5) / 0.023 A
Load stability, 4…20 mA output..................... ≤ 0.01% of span / 100 Ω
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Relay output: Relay functions........................ Setpoint, Window, Sensor
error, Power and Off
Hysteresis, in % of span/display
range.............................................................. 0.1...25 / 1...25
ON and OFF delay......................................... 0...3600 s
Sensor error reaction..................................... Break / Make / Hold
Max. voltage................................................... 250 VAC / 30 VDC
Max. current................................................... 2 AAC / 2 ADC
Max. AC power.............................................. 500 VA / 60 W
Max. voltage, status relay.............................. 110 VDC / 125 VAC
Max. current, status relay............................... 0.3 ADC / 0.5 AAC
Max. AC power, status relay.......................... 62.5 VA / 32 W
*of span.......................................................... = of the currently selected
measurement range
Approvals
EMC............................................................... EN 61326-1
LVD................................................................ EN 61010-1
ATEX.............................................................. KEMA 10ATEX0053 X
IECEx............................................................. KEM 10.0022X
FM.................................................................. 3038267-C
INMETRO....................................................... NCC 12.1309 X
UL................................................................... UL 61010-1
GOST R......................................................... Yes
GOST Ex........................................................ Yes
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
9116B-061814
RTD input....................................................... Pt10, Pt20, Pt50, Pt100,
Pt200, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100,
Ni120, Ni1000
Cable resistance per wire
(max.), RTD.................................................... 50 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Programmable ON / OFF
Short circuit detection, RTD........................... Yes
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC) via ext. sensor in
connector 5910.............................................. 20...28°C ≤ ±1°C, -20...20°C /
28...70°C ≤ 2°C
CJC via internally mounted
sensor............................................................ ±(2.0°C + 0.4°C * Δt)
Δt =................................................................. Internal temperature-ambient
temperature
Sensor error detection, TC............................. Programmable ON or OFF
(only wire breakage)
Current input: Measurement
range.............................................................. 0...20 mA
Current input: Programmable
measurement ranges..................................... 0...20 and 4...20 mA
Input resistance, current
input............................................................... Nom. 20 Ω + PTC 50 Ω
Sensor error detection, current
input............................................................... Loop break 4...20 mA
Voltage input: Measurement
range.............................................................. 0...10 VDC
Programmable measurement ranges,
VDC................................................................ 0/0.2...1, 0/1...5, 0/2...10 VDC
Input resistance, voltage
input............................................................... Nom. >10 MΩ