Temperature / mA converter
9113B
– Input for RTD, TC and mA
– Active / passive mA output
– 1 or 2 channels
– Can be supplied separately or installed on power rail, PR type 9400
– SIL 2-certified via Full Assessment
Advanced features
• Configuration and monitoring by way of detachable display
front (PR 4501); process calibration and signal simulation.
• Copying of the configuration from one device to others of the
same type via the display front.
• TC inputs can use either the internal CJC or a terminal with a
built-in Pt100 sensor (PR 5910Ex, channel 1 / PR 5913Ex,
channel 2) for higher accuracy.
• The device automatically detects whether it must supply an
active or a passive current signal.
• Advanced monitoring of internal communication and stored
data.
• SIL 2 functionality is optional and must be activated in a menu
point.
Connections
Application
• The device can be mounted in the safe area and in zone 2 /
cl. 1 div. 2 and receive signals from zone 0, 1, 2 and zone 20,
21, 22 including M1 / Class I/II/III, Div. 1, Gr. A-G.
• Conversion and scaling of temperature (Pt, Ni and TC) and
active current signals.
• The 9113 has been designed, developed and certified for use
in SIL 2 applications according to the requirements of IEC
61508.
Technical characteristics
• 1 green and 2 red front LEDs indicate operation status and
malfunction.
• 2.6 kVAC galvanic isolation between input, output and supply.
Mounting
• The devices can be mounted vertically or horizontally without
distance between neighbouring units.
This page is automatically generated on the basis of information provided on www.prelectronics.com and affiliated websites. It is provided to you as a service and for information
purpose only. While we have attempted to maintain the information as accurately as possible, the page may contain errors or omissions for which we disclaim any and all liability
Environmental Conditions
Specifications range.......................................
Storage temperature......................................
Calibration temperature.................................
Relative humidity............................................
Protection degree...........................................
Installation in..................................................
-20°C to +60°C
-20°C to +85°C
20...28°C
< 95% RH (non-cond.)
IP20
Pollution degree 2 &
measurement / overvoltage
cat. II
109 x 23.5 x 104 mm
109 x 23.5 x 116 / 131 mm
250 g
265 g / 350 g
DIN EN 60715/35 mm
0.13...2.08 mm2 AWG 26...14
stranded wire
Screw terminal torque.................................... 0.5 Nm
Common specifications
Supply voltage...............................................
Fuse...............................................................
Max. power consumption...............................
Isolation voltage, test /working:
Input to any....................................................
Analog output to supply.................................
Status relay to supply.....................................
Communications interface.............................
Nom. 2 μA / 0 μA
0...20 mA
0...20 and 4...20 mA
Nom. 20 Ω + PTC 50 Ω
Programmable ON / OFF
Output specifications
Mechanical specifications
Dimensions (HxWxD).....................................
Dimensions (HxWxD) w/ 4501
/ 4511.............................................................
Weight approx................................................
Weight incl. 4501 / 4511 (approx.).................
DIN rail type...................................................
Wire size........................................................
Sensor error current: When
detecting / else...............................................
Current input: Measurement
range..............................................................
Current input: Programmable
measurement ranges.....................................
Input resistance, current
input...............................................................
Sensor error detection, current
input...............................................................
19.2...31.2 VDC
400 mA SB / 250 VAC
≤ 3.5 W (2 channels)
2.6 kVAC / 300 VAC
reinforced isolation
2.6 kVAC / 300 VAC
reinforced isolation
1.5 kVAC / 150 VAC
reinforced isolation
Communication enabler 4511
/ Programming front 4501
Min. 60 dB (0...100 kHz)
Signal / noise ratio.........................................
Average response time incl.
delay: Temperature input............................... ≤ 1 s
mA input......................................................... ≤ 0.4 s
Accuracy........................................................ Better than 0.1% of selected
range
EMC immunity influence................................ < ±0.5% of span
Extended EMC immunity: NAMUR
NE 21, A criterion, burst................................. < ±1% of span
Input specifications
Approvals
EMC............................................................... EN 61326-1
LVD................................................................ EN 61010-1
ATEX.............................................................. KEMA 07ATEX0148 X
IECEx............................................................. KEM 09.0052X
FM.................................................................. 3038279-C
INMETRO....................................................... NCC 12.1310 X
UL................................................................... UL 61010-1
GOST R......................................................... Yes
GOST Ex........................................................ Yes
DNV Marine.................................................... Stand. f. Certific. No. 2.4
SIL.................................................................. SIL 2 certified & fully assessed
acc. to IEC 61508
9113B-061814
RTD input....................................................... Pt10, Pt20, Pt50, Pt100,
Pt200, Pt250, Pt300, Pt400,
Pt500, Pt1000, Ni50, Ni100,
Ni120, Ni1000
Cable resistance per wire
(max.), RTD.................................................... 50 Ω
Sensor current, RTD...................................... Nom. 0.2 mA
Effect of sensor cable resistance
(3-/4-wire), RTD............................................. < 0.002 Ω / Ω
Sensor error detection, RTD.......................... Programmable ON / OFF
TC input: Thermocouple type......................... B, E, J, K, L, N, R, S, T, U,
W3, W5, LR
Cold junction compensation
(CJC) via ext. sensor in
connector 5910.............................................. 20...28°C ≤ ±1°C, -20...20°C /
28...70°C ≤ 2°C
CJC via internally mounted
sensor............................................................ ±(2.0°C + 0.4°C * Δt)
Δt =................................................................. Internal temperature-ambient
temperature
Sensor error detection, TC............................. Programmable ON or OFF
(only wire breakage)
Current output: Signal range......................... 0...20 mA
Programmable current ranges....................... 0...20 / 4...20 / 20...0 and
20...4 mA
Load (max.).................................................... 20 mA/600 Ω/12 VDC
Load stability, current output.......................... ≤0.01% of span/100 Ω
Sensor error indication, current
output............................................................. 0 / 3.5 / 23 mA / none
NAMUR NE 43 Upscale/Downscale.............. 23 mA / 3.5 mA
Output limitation, on 4...20
and 20...4 mA signals.................................... 3.8...20.5 mA
Output limitation, on 0...20
and 20...0 mA signals.................................... 0...20.5 mA
Current limit.................................................... ≤ 28 mA
2-wire 4…20 mA output: External
2-wire supply range........................................ 3.5...26 VDC
Signal range................................................... 4…20 mA
Max. load resistance [Ω]................................ (Vsupply - 3.5) / 0.023 A
Load stability, 4…20 mA output..................... ≤ 0.01% of span / 100 Ω
Effect of external 2-wire
supply voltage variation................................. < 0.005% of span / V
Max. voltage, status relay.............................. 110 VDC / 125 VAC
Max. current, status relay............................... 0.3 ADC / 0.5 AAC
Max. AC power, status relay.......................... 62.5 VA / 32 W
*of span.......................................................... = of the currently selected
measurement range
Download PDF