SMB600 Surface Mounting Kit for Use with 400 or 500 Series

I56-444-05
INSTALLATION AND MAINTENANCE INSTRUCTIONS
SMB600 Surface Mounting Kit for Use with
400 or 500 Series Detectors with
6”/152.4mm Dia. Base, 400 Series
Direct-Wire Detectors and Sounder Bases
3825 Ohio Avenue, St. Charles, Illinois 60174
1-800-SENSOR2, FAX: 630-377-6495
www.systemsensor.com
GENERAL DESCRIPTION
The SMB600 Surface Mounting Kit allows System Sensor
detectors to be surface mounted when the junction box
intended to be used is not of adequate size.
FIGURE 1:
The kit consists of the following parts:
Qty.Description
1
Plastic surface mount base
2
#6 x 1″ sheet metal screws
2
#8-32 x 1⁄2″ screws
2
Plastic anchors
ALIGNMENT RIBS
JUNCTION BOX MOUNTING INSTRUCTIONS
1.Read and follow the installation instructions appropriate
for the detector head, or other device, to be used with
the SMB600.
11/2″
max.
2.Pull the wires through the 1.3″/33mm dia. hole in the
bottom of the base. The SMB600 must be mounted to a
UL listed junction box (see Figure 3).
C0522-01
FIGURE 2:
3.Using the two #8-32 screws supplied, mount the
6″/152.4mm dia. mounting base, direct wire
mounting bracket, or sounder base to the surface
mount base.
NOTE:
ALIGNMENT RIB
When using the B402, B404, or B406 with the
surface mount base, the 4 alignment ribs
(see Figure 1) must be cut off flush or below
the top edge of the surface mount base
(see Figure 2).
CUT OFF
RIBS (4)
C0523-00
4.Wire the 6″/152.4mm dia. mounting base or detector
per installation instructions.
FIGURE 3:
SMB600
C0524-00
1
I56-444-05
06-10
SURFACE WIRING MOUNTING INSTRUCTIONS
6. Mount the base, using the supplied screws, in the
SMB600 Surface Mounting Adaptor Kit.
1. Read the installation instructions appropriate for the
detector head to be used and determine the number of
wires used.
NOTE: When using the B402, B404, or B406 with the surface mount base, the 4 alignment ribs (see Figure
1) must be cut off flush or below the top edge of
the surface mount base (see Figure 2).
2. Drill out the appropriate holes using the drill centers
provided on the sides of the adaptor (see Figure 4).
Do not use conduit larger than 1/2″ to connect to the
SMB600.
7. Plug the detector head into its mounting base and rotate
clockwise.
3. Mount the adaptor on the ceiling using the 2 keyholes
and appropriate screws or bolts (not included). The
screws or bolts must be long enough to go through the
adaptor (5/32″ or 4mm) and still fasten securely to the
ceiling.
8. Test the system as indicated in the detector instruction
manual.
4. Pull wiring and conduit through the drilled hole(s). Attach
nut(s) (not included) to conduit fitting and tighten.
5. Wire detector base using the instructions included with
the base.
FIGURE 4. DRILL CENTERS:
DRILL
CENTERS (4)
C0525-00
2
I56-444-05
©2016 System Sensor. 06-10
Download PDF