Quarterly Progress Report

DE-EE0002896
Final Technical Report
Project Title:
Recovery Act: Development of a Very Dense Liquid Cooled
Compute Platform
Award Number:
DE-EE0002896
Project Period:
January 31, 2010 to December 31, 2012
Post-Novation Period: May 1, 2012 to December 31, 2012
Technical Contact:
Phil Hughes
3350 Scott Boulevard
Santa Clara, CA 95054
Ph 415 613 9264
Fax 408 327 8101
phil@clusteredsystems.com
Business Contact:
Robert Lipp
3350 Scott Boulevard
Santa Clara, CA 95054
Ph 408 234 6655
Fax 408 327 8101
bob@clusteredsystems.com
Recipient Organization:
Clustered Systems Company, Inc.
3350 Scott Boulevard #30-01
Santa Clara, CA 95054
Partners:
Emerson-Cooligy (Subrecipient and cost-sharing partner)
800 Maude Avenue
Mountain View, CA 94043
California Energy Commission (cost-sharing partner)
Grant Award Number: PIR-10-058
Intel Corporation (cost-sharing source-processors)
SLAC National Accelerator Laboratory (install/testing
space)
Date:
March 31, 2013
Page 1 of 37
DE-EE0002896
Acknowledgment:
This report is based upon work supported by the U. S. Department of Energy under Award No.
DE-EE0002896 and Co-sponsored by the California Energy Commission Under Grant Award
No. PIR-10-058
Disclaimer:
This report was prepared as an account of work sponsored by an agency of the United States
Government. Neither the United States Government, nor any agency thereof, nor any of their
employees, makes any warranty, express or implied, or assumes any legal liability or
responsibility for the accuracy, completeness, or usefulness of any information, apparatus,
product, or process disclosed, or represents that its use would not infringe privately owned
rights. Reference herein to any specific commercial product, process, or service by trade name,
trademark, manufacturer, or otherwise does not necessarily constitute or imply its endorsement,
recommendation, or favoring by the United States Government or any agency thereof. Any
findings, opinions, and conclusions or recommendations expressed in this report are those of
the authors and do not necessarily reflect those of the United States Government or any agency
thereof.
Document Availability: Reports are available free via the U.S. Department of Energy (DOE)
Information Bridge Website: http://www.osti.gov/bridge
Reports are available to DOE employees, DOE contractors, Energy Technology Data Exchange
(ETDE) representatives, and Informational Nuclear Information System (INIS) representatives
from the following source:
Office of Scientific and Technical Information
P.O. Box 62
Oak Ridge, TN 37831
Tel: (865) 576-8401
FAX: (865) 576-5728
E-mail: reports@osti.gov
Website: http://www.osti.gov/contract.html
Page 2 of 37
DE-EE0002896
Contents
Acknowledgment:............................................................................................................................ 2
Disclaimer: ...................................................................................................................................... 2
List of Tables ............................................................................................................................... 5
List of Figures .............................................................................................................................. 5
List of Acronyms .......................................................................................................................... 6
Executive Summary ........................................................................................................................ 7
Introduction ..................................................................................................................................... 9
System Overview ........................................................................................................................ 9
Cooling Technology .................................................................................................................... 9
Electronic Sub-Systems ............................................................................................................ 10
Background ................................................................................................................................... 10
Accomplishment, Results and Discussion ................................................................................... 12
Program Modifications .............................................................................................................. 12
Complete System Overview ...................................................................................................... 14
System Components ................................................................................................................. 15
Compute Blade ...................................................................................................................... 15
Active Plane ........................................................................................................................... 16
Power Distribution Blade ....................................................................................................... 17
Chassis .................................................................................................................................. 18
PCIe Switch ........................................................................................................................... 19
Power Supply......................................................................................................................... 19
Liebert XDS System .............................................................................................................. 20
Technology Development Highlights ............................................................................................ 22
Micro-Channel Cold Plate ..................................................................................................... 22
Cold Plate Thermal Interface (TIM) ....................................................................................... 24
Blade Installation Mechanisms .............................................................................................. 25
SLAC Installation .......................................................................................................................... 26
SLAC Installation Measured Results ........................................................................................ 27
Exploration of maximum coolant temperature performance ................................................. 28
Design Repeatability .............................................................................................................. 29
Power Conversion Loss ........................................................................................................ 30
Overall Power and Cooling Efficiency ................................................................................... 30
Power Consumption Variation with Temperature ................................................................. 31
Publications: .................................................................................................................................. 32
Patents: ..................................................................................................................................... 32
Page 3 of 37
DE-EE0002896
Benefits Assessment .................................................................................................................... 32
Commercialization ........................................................................................................................ 34
Conclusions................................................................................................................................... 35
Recommendations ........................................................................................................................ 35
Acknowledgements ....................................................................................................................... 35
References .................................................................................................................................... 36
Appendices ................................................................................................................................... 37
Data Sheets ........................................................................................................................... 37
Page 4 of 37
DE-EE0002896
List of Tables
Table 1 Temperature Cycle .......................................................................................................... 28
Table 2 Power Supply Efficiency .................................................................................................. 30
Table 3 Cooling Water Temperature Computation ...................................................................... 30
Table 4 Coefficients for deriving kilowatts required per ton of cooling ........................................ 31
Table 5 Efficiency Calculation ...................................................................................................... 31
Table 6 U.S. Data Center Energy Usage ..................................................................................... 33
List of Figures
Figure 1 - Rack Illustration .............................................................................................................. 9
Figure 2 - Actual PUE vs Quoted vs Fan Power .......................................................................... 11
Figure 3 - Power Use in an Air Cooled Server ............................................................................. 11
Figure 4 - Power Use in a Refrigerant Cooled Server ................................................................. 12
Figure 5 - 100KW Rack Overview ................................................................................................ 14
Figure 6 - SLAC Rack Installation ................................................................................................ 14
Figure 7 - Server Blade Picture .................................................................................................... 15
Figure 8 - Active Plane (PCIe Switch) Picture.............................................................................. 17
Figure 9 - Chassis Front Picture ................................................................................................... 18
Figure 10 - Chassis Rear Picture ................................................................................................. 18
Figure 11 - Active Plane Cold Plates Picture ............................................................................... 19
Figure 12 - Chassis Cold Plate Plumbing Overview .................................................................... 19
Figure 13 - SLAC Rack Configuration .......................................................................................... 20
Figure 14 - SLAC Installation Showing the Rack and XDS System ............................................ 20
Figure 15 - Micro-channel Close-up View .................................................................................... 22
Figure 16 - Server Cold Plate Assembly Bottom ......................................................................... 23
Figure 17 - Server Cold Plate Assembly Top ............................................................................... 24
Figure 18 - Server Cold Plate with TIM ........................................................................................ 24
Figure 19 – Close-up of Server Blade Installation Mechanism .................................................... 25
Figure 20 - Generic Rack Cooling Circuit ..................................................................................... 27
Figure 21 - CPU Temperature Margin .......................................................................................... 29
Figure 22 - Power Variation with Temperature ............................................................................ 31
Page 5 of 37
DE-EE0002896
List of Acronyms
CPU – Central Processing Unit
DCIE – Data Center Infrastructure Efficiency
DIMM – Dual In-line Memory Module
Exaflop – 1018 floating point calculations/sec
GbE – Gigabit Ethernet
HPC – High Performance Computing
PDU – Power Distribution Unit
PCB – Printed Circuit Board
PCIe Peripheral Control Interface
Petaflop – 1015 floating point calculations/sec
PUE – Power Usage Effectiveness
R134a – refrigerant number R134a
SKU – Stock Keeping Unit
Teraflop – 1012 floating point calculations/sec
TIM – Thermal Interface Material
VAC – Volts, Alternating Current
VDC – Volts, Direct Current
xU (or xRU) – number of Rack Units (1.75”) where x = the number of units
Page 6 of 37
DE-EE0002896
Executive Summary
The objective of this project was to design and develop a prototype very energy efficient highdensity compute platform with 100% pumped refrigerant liquid cooling using commodity
components and high volume manufacturing techniques.
We believe that we have surpassed our goal. Testing at SLAC has indicated that we achieved a
DCIE of 0.93 against our original goal of 0.85. This number includes both cooling and power
supply and was achieved employing some of the highest wattage processors available. This
figure of merit is superior even to those of companies such as Google and Facebook who claim
a DCIE of around 0.89 using free air cooling with low power processors.
In fact, our relative performance is even better when the non IT load (i.e. server fans and power
conversion) is included with the overhead rather than the IT load as it is today. The US average
DCIE of 0.55 becomes 0.42 and a free air facility, only 0.80. Clustered’s DCIE, after factoring in
power conversion to 12VDC, is 0.90.
If the IT industry had our technology, the U.S. could maintain the same compute capacity it has
today while releasing only 50% of the CO2 into the atmosphere.
In another development, a senior fellow at one CPU manufacturer voiced the opinion that our
technology could bring forward the delivery of Exaflop computing by a full year.
This project included the development of a fundamentally new cooling architecture based upon
pumped refrigerant liquid cooling and encompassed both infrastructure and equipment. The
design comprehends mechanisms for heat transfer from the servers’ internal components to
ultimate dissipation of the heat to the ambient environment. It is powerful enough for HPC (High
Performance Computing) applications and cost effective for general enterprise applications. It is
relatively insensitive to its environment, thus does not require an expensive conditioned
environment.
Energy consumption throughout the entire power and cooling chain has been reduced.
Refrigerant touch cooling allows all the power hungry fans to be eliminated, reduces pumping
energy costs and can use warm water for cooling, virtually eliminating the energy cost of a
chiller. Bulk n+1 redundant 97% efficient rectifiers take 480VAC input and output 380VDC for
distribution to on-blade power conversion units, significantly reducing power distribution losses.
Virtual I/O reduces the number of high power networking components.
The elimination of air as coolant enables extreme density. This aids inter-processor
communication which is very important for HPC, and reduces real estate requirements by up to
90%. Being insensitive to its environment, warehouse style space can be substituted for far
more expensive data center accommodation, dropping building costs from around $250 to $80
per square foot.
Page 7 of 37
DE-EE0002896
We can pack 392 CPUs in 6 chassis into one standard 48U data center rack. Our target was
300-400 CPUs. In most applications however, we expect a power supply and network gear to
replace one chassis leaving space for 320 CPUs.
The SLAC system has 256 CPUs in 4 chassis. Predicted performance is 47 petaflops. The
system is installed in a non-controlled environment in a cage just off the loading dock of Building
950, not in a data center. A Liebert XD pumped refrigerant platform connected to the building’s
centralized cold water system supplies the coolant.
Besides the results of tests described herein, the compute platform is undergoing long term
performance and reliability testing.
The SLAC installation is also at the core of our commercialization efforts as they will evaluate it
under real loads and conditions and report on the outcomes. They will allow us to bring visitors
to observe the system in use and describe their experience with it.
In order to promote a transition to our technology, Clustered Systems Company will offer
customers the option of licensing the technology or purchasing the key elements of the design
from us, namely the flexible cold plates and the super compliant TIM.
The data center world is a conservative one with low risk generally the highest priority. This
means there is a general reluctance by data center managers to adopt the latest technologies
for energy savings. It is not only secondary to their mission, but often hardly on the radar.
Our recommendations mainly reflect this situation and suggest ways to overcome this obstacle
without additional investment. These include specifying true DCIEs (i.e. counting server fans
and power conversion as infrastructure load) of over 0.9 for future DoE server system
purchases, adding a liquid cooling option to your “DC Pro” calculator, and using your “bully
pulpit”. Finally, improved server proximity will open up new interconnect techniques. These
should be studied and as recognized interconnect experts, Clustered Systems wishes to be
included in any such RFPs.
Page 8 of 37
DE-EE0002896
Introduction
System Overview
Figure 1 - Rack Illustrationshows the rack as conceived. It is 48U tall, 800mm wide and
1200mm deep.
It has space for six 8U chassis, each containing 16 double height blades. In many cases we
expect that 2U of rack space will be used for external switches and 6U for power supplies,
replacing one chassis.
The rack is powered with 3 phase 480VAC. N+1 redundant power
converters rated at 115KW rectify the incoming AC to 380VDC that is
distributed to the individual chassis in the system. One circuit breaker
and eight fuses are provided for each chassis in a PDU blade.
The cooling system is fully interoperable with Liebert, Inc.’s XD
pumped refrigerant system.
Cooling Technology
Most electronics systems, including servers, today consist of a
baseboard (motherboard) with multiple components mounted upon it.
Manufacturing variances cause differences in the height and coplanarity of identical components in the same locations on different
Figure - Rack Illustration
boards. Using a single cold plate to touch all of these is problematic
as even the smallest gaps create an enormous resistance to the flow of heat.
The workaround has been to use cooling blocks mounted on individual hot components.
Coolant is supplied from a manifold in the server rack or chassis but as the servers have to be
removed for servicing, liquid connectors must be used. These can leak and cause havoc with
the electronics.
Clustered Systems’ has developed a contact cooled (touch) system that relies on flexible cold
plates covered with a highly compliant and thermally conductive Thermal Interface Material
(TIM). Heat is moved from the components to a common plane via heat risers mounted on the
hot components. These can be made from simple aluminum blocks. It is thence removed by a
refrigerant liquid circulating through a cold plate and TIM combination that is pressed down on
the risers and conforms to the uneven surfaces of the plane.
The cold plate and TIM are permanently installed in a chassis, totally eliminating the need for
connectors. Servers can be removed without breaking a liquid connection.
The server blade has a slot in the rear that accepts a cold plate. As the blade is inserted, pins in
the lid guide the cold plate through the blade above the components but under the lid. After the
blade is inserted and locked into position, the cover is cranked down, pressing the cold plate
against the heat risers. This force causes the TIM to conform to the various heights and
positions of the heat risers, creating a thermally conductive path between the heat risers and the
cold plate.
Page 9 of 37
DE-EE0002896
The surface area of the heat risers is designed to be large to minimize thermal impedance. Low
pressure is required to avoid a large overall force that might damage the components. Pressure
of 0.5psi will compress the Clustered Systems TIM over 75% in thickness. This pressure is
considerably lower than commercially available TIMs that typically require over 15psi for about
25% compression.
Clustered Systems had to develop this conformable TIM as no commercially available TIMs met
the requirements for this application.
Electronic Sub-Systems
System development required development of six custom PCBs. Four of these boards interface
the Intel JP2600JF motherboards used in the compute blade

User interface and Ethernet connector at blade front (Headlight)

PCIe switch blade interface and power conversion at rear of blade (Hitch)

Bridge board, connecting Hitch to the motherboard (Crankshaft)

PCIe and Gigabit Ethernet switch blade at the rear of the chassis

Adapter board, providing interface between Hitch and the switch blade.

40 port PCIe switch support board (housed in separate chassis)
The PCIe switch blade provides virtual I/O for improved performance, lower cost and power
reduction. The last board is used in the 40 port PCIe switches that provide network interface
between the compute platform and the outside world.
Background
Electricity consumed in data center and telecom systems is over 2 percent of the U.S. total and
growing rapidly. Historically, the energy used to provide cooling for data centers is upwards of
45% of the total facility power. Over the last several years, there have been significant efforts to
improve the energy used for IT cooling by making small improvements to the cooling equipment
and the control of air movement. However, moving air is energy intensive because air circuits
have a low specific heat and density, and high thermal resistance at the gas to solid boundary.
Hot and cold air can also mix in unpredictable ways; and air is simply incompatible with high
density, high power systems that are required for HPC.
Improvements to increase the cooling power of air cooling systems has meant pushing air
through ever decreasing gap sizes, but the required energy is becoming unacceptably large.
The net result is that more energy is wasted in the support of a CPU than is used to run it.
Unfortunately, the most common standard for measuring data center efficiency, PUE, includes
the server fan energy as part of the compute load instead of the cooling overhead. This greatly
distorts the final efficiency calculation, hiding a major source of energy consumption.
Server fan load varies from 5% to over 30% of the server compute power depending on a
number of factors from power density to fan size to ambient temperature. The chart below
illustrates the hidden cost of ignoring fan energy.
Page 10 of 37
DE-EE0002896
Actual PUE vs Quoted PUE vs Fan Power
2.20
2.00
Actual PUE
Quoted PUE=1
1.80
Quoted PUE=1.1
1.60
Quoted PUE=1.2
Quoted PUE=1.3
1.40
Quoted PUE=1.4
1.20
1.00
0%
5%
10%
15%
20%
25%
30%
Fan Power
Figure - Actual PUE vs Quoted vs Fan Power
A further examination of the entire energy consumption cycle warrants further examination.
Figure - Power Use in an Air Cooled Servershows where the energy is consumed in a typical
high performance air cooled server. As can be seen, it requires 815W into a data center facility
to run the 300W core consisting of two CPUs and 8 DIMMs.
Figure - Power Use in an Air Cooled Server
Page 11 of 37
DE-EE0002896
Figure shows the same server as cooled by the Clustered System’s compute platform
developed under this program. By making improvements in cooling the entire power train and
adopting I/O sharing, total incoming power is reduced by almost 50%.
Figure - Power Use in a Refrigerant Cooled Server
Accomplishment, Results and Discussion
The project demonstrates the power of touch based refrigerant cooling as applied to blade
servers. Reduced energy consumption, very high density and the ability to support high power
processors have been demonstrated. The latest developments in server interconnect, I/O
virtualization and power distribution and conversion were incorporated to further reduce energy
consumption.
Program Modifications
Learnings and budget limitations during the program led to several changes in the program
development deliverables.
We originally were planning on delivering two complete racks to SLAC outfitted with custom
motherboards and two 10GbE switches. The system was to be connected either directly to the
chilled water system originating from SLAC cooling towers without further cooling by a chiller, or
from downstream waste cooling water from the return line of other equipment that had used the
water once for cooling.
Mid program we shut down our motherboard development due to technical issues and opted to
use a recently released Intel motherboard. Although a difficult switch mid program, it ended up
Page 12 of 37
DE-EE0002896
being a wise choice as we now have a much more commercially acceptable solution with the
Intel board. Originally we had planned to develop a custom server card that contained the power
and networking interface as there was no suitable motherboard available when we started.
However, our chosen vendor stumbled in the development of this card and it was significantly
behind schedule and in danger of not being functional in a timely manner for this project.
Coincidently, Intel completed development of the S2600JF motherboard and in mid project we
decided we could more expeditiously complete the project using the Intel board and only
develop the much simpler interface boards around it. The basic S2600JF board was designed
for a 1U application rather than a blade application and a few of the components are too tall for
our application. As Intel was interested in a SKU suitable for blades, they had already designed
a modified design that fit our application.
During initial architectural design, our Ethernet switch board vendor advised us they could build
a fully PCIe compatible switching system for the same cost as our originally planned hybrid
PCI/10GbE system. This had the potential for improved system performance, increased
networking flexibility and lower energy consumption, so we proceeded down that path.
Budget constraints at SLAC led to some uncertainty as to where the system would be located.
Eventually the LCLS group took ownership. The building was not reasonably amenable to our
plans for connecting it to cooling tower water or return water. Physical limitations on the LCLS
building in the SLAC campus led to cooling the system using building chilled water. We
regretted having to give up these options as operating it without a chiller over the two year test
period would have saved energy and provided a demonstration of the power and versatility of
our cooling technology. However, in compensation, we now have the ability to control the
temperature of the refrigerant going to the system to fully and rapidly demonstrate its cooling
operating range and flexibility.
LCLS did not need the full computing power of proposed system so it was scaled down to a
single rack. We went ahead with a second rack comprising a single chassis, power supply and
switches that we installed in our lab. We were limited by budget overruns due to additional costs
incurred primarily labor for fine tuning the design, and did not have sufficient funds to fully
populate this second rack. This in-house rack aids our commercialization effort by giving us a
unit we can demonstrate to prospective customers in our own facility. It also is a vehicle for
further evaluation and system improvements under our control.
Page 13 of 37
DE-EE0002896
Complete System Overview
The final fully configured product as initially conceived is shown in Figure 6
Figure - 100KW Rack Overview
The system installed at SLAC varies somewhat from this illustration in that only four chassis
were installed to make room for the additional switches seen at the top of Figure 5.
Figure - SLAC Rack Installation
Page 14 of 37
DE-EE0002896
System Components
Compute Blade
There are 16 compute blade enclosures in each chassis.
Figure - Server Blade Picture
Configuration and Motherboard
The compute blade contains two identical and independent server sections within one
enclosure.
Each server section comprises an Intel S2600JF half width motherboard connected to a rear
mounted custom power/networking interface card a by a small connector card, and a further
connection in the front to a custom front panel mounted interface card and a hard disk. These
enclosures are mounted vertically in the chassis.
The CPUs are Intel E5-2680 2.7GHz 8 core 130W XEON processors. There are 2 CPUs and 8
4 GB DIMMs on each motherboard. The maximum power dissipation for each compute blade is
approximately 1KW.
Heat Risers
Note the large silver colored blocks over the CPUs and other hot components. These are
simple blocks of aluminum mounted on the components using the existing conventional heat
sink mounting mechanisms. They conduct heat from these components to a common plane for
Page 15 of 37
DE-EE0002896
heat removal by a cold plate. The DIMMs are jacketed with conventional DIMM heat removal
jackets slightly modified such that the top has a flat planar area to thermally interface to the cold
plate. Note that the DIMMs, as the tallest components, set the height of the plane that all the
risers are designed to.
Safety and Hot Swap
This hot swap enclosure has mechanisms for safely engaging and disengaging the blade from
the system, mechanically insuring the enclosure cannot be inserted nor removed while powered
on. Additionally, an electrical interlock prevents the card from being powered up until the
cooling system is engaged; and assures power is off prior to removal.
Network Interface
The system contains no conventional midplane or backplane. To avoid obsolescence, all the
electrical components are removable. The power/networking interface plugs directly into
chassis-mounted removable rear power distribution strips and removable active plane
networking cards.
The power/networking card plugs converts 380VDC to 12VDC as the primary local power
source for the blade. Conversion efficiency is about 96%.
This same card further extends the motherboard PCIe signals to two active plane cards via dual
50 pair high speed differential signal connectors. Management 1GbE signals are also carried
across the same connectors.
The power/networking card is connected to the motherboard by a small custom bridge card
carrying PCIe and control signals and dual 12V power connectors.
Active Plane
Figure shows the PCIe switch card developed for this application mounted in its blade carrier.
The 16 connectors on the bottom provide connectivity to the front CPU blades. The 8 PCIe
connectors on the top are for cabling to other switch blades and switches. Two 1GbE sockets
provide external management connectivity. High performance inter-processor communication
can occur over these active planes without protocol translation, saving energy and improving
performance.
Page 16 of 37
DE-EE0002896
Figure - Active Plane (PCIe Switch) Picture
There are four slots for active planes in the rear of each chassis. A minimum of two are
required for full network connectivity from the rear. The cards are inserted horizontally into the
chassis, orthogonal to the compute blades. This permits full interconnect between all the
motherboards in that horizontal row. An external switch provides connectivity between rows and
between chassis.
Power Distribution Blade
The PDU blade was designed and supplied by Panduit, Inc. Although not a formal member of
the development team, they agreed to develop and build this blade at no cost to us.
The PDU blade controls power to the chassis. It has a 50A breaker supplying power to a fuse
panel contained within. Eight fused circuits distribute power via rear connectors to two power
distribution strips and thence to the compute blades and active planes.
It is shown on the left of the picture of the chassis below.
Page 17 of 37
DE-EE0002896
Chassis
Figure 9 shows the front of a single chassis with one empty slot and one CPU blade partially removed.
Figure - Chassis Front Picture
Figure 10 shows the chassis rear illustrating how an active plane card is inserted. The plumbing
manifolds distribute the refrigerant to the blades.
Figure - Chassis Rear Picture
Page 18 of 37
DE-EE0002896
Figure 11 is a picture of a set of rear cold
plates. The fluid enters the bottom plate
where it flows to the end and returns
through the top plate. The return is also
shown in the picture above where it
protrudes from the left side.
Figure - Active Plane Cold Plates Picture
Figure 12 illustrates the complete
chassis plumbing. The two rows of
16 server blade cold plates are on
the left. The two pairs of rear cold
plates is on the right.
Figure - Chassis Cold Plate Plumbing Overview
PCIe Switch
A 40 port PCIe switch was custom developed for us by OneStop Systems. Two of these are
installed in each rack to provide connectivity between blades and as a virtual I/O uplink to the
outside world.
These switches also contain the processors for configuration of the PCIe network. The first
level of switching occurs on the active planes that connect all 16 blades on a row and provide 8
uplinks to the switches. All these signals are connected in a Fat Tree configuration by the
switches. The switches also have two slots for insertion of a standard Ethernet or Infiniband
network card that converts from PCIe to the relevant protocol providing a virtual I/O for uplinks
to an external network. This saves energy and is potentially a cheaper and more flexible
solution than the current state of the art systems.
The switches currently provide the dynamic virtual I/O function for only 32 blades. Limitations in
the PCIe protocol are currently limiting full implementation of this feature. Work is continuing at
Clustered Systems and OneStop Systems to fully implement full functionality as we believe it
will be an attractive feature for commercialization.
Power Supply
The DC power supply was developed by Emerson Network Power in an informal arrangement.
Emerson modified the form factor and size of a product in development to meet our needs. This
480VAC to 380VDC unit is about 97% efficient..
Page 19 of 37
DE-EE0002896
Figure 13 shows the SLAC installation. The rack was built by Liebert, Inc. as a partner in this
project.
The components of this rack from the top down are:

GbE switch with 2ea 10GbE optical uplinks

Emerson 115KW 380VDC power supply

2ea fully configured chasses

2ea OneStop Systems 40 port PCIe switches

2ea fully configured chasses
Figure - SLAC Rack
Configuration
Liebert XDS System
The XDS is installed adjacent
to the rack (Figure 14). As a
partner in this project, Liebert
modified one of their standard
XDS systems for compatibility
with our system. In particular,
they added the sidecar to the
right of their standard system
and made the system fully
redundant.
During normal operation, nearly
50% of the refrigerant volume
of the system comprises
refrigerant gas boiling off the
cold plates. However, when
the system is off, refrigerant will
settle to the lowest and/or
coldest spots in the system. A
Figure - SLAC Installation Showing the Rack and XDS System
standard Liebert installation
requires a minimum of 20KW loading to maintain the proper distribution of gas and liquids in the
Page 20 of 37
DE-EE0002896
system. However, in our case the system must be able to be turned off completely. Extra
refrigerant storage was added to provide proper functionality over all loads. The sidecar is
essentially no more than a large refrigerant storage tank to provide this function.
Page 21 of 37
DE-EE0002896
Technology Development Highlights
Several critical technologies needed to be developed for this project:

Vertically mounted micro-channel cold plate

Conformable thermal interface

Blade installation mechanisms
Micro-Channel Cold Plate
We developed a micro-channel cold plate on an earlier product that is currently in production
and commercially available. This earlier product incorporated these cold plates for cooling 1U
servers. They were mounted horizontally on the tops of these servers with large manifolds on
either side to distribute and collect the refrigerant. They were made from extruded aluminum
using mass production facilities and technologies developed for the automotive industry. The
aluminum is flexible and will conform to some extent to an uneven surface.
Figure 15 shows an end-on view of such an
extrusion approximately to scale. The extrusion is
100mm wide by 2mm thick and is cut to length as
required.
This application required 160mm wide cold plates
mounted vertically in the chassis. They could be
connected only to a rear manifold to distribute
and collect the refrigerant. The front had to
remain thin to slide into the narrow slot in the
server.
160mm micro-channel extrusions are generally
beyond the state of the art for commercial
applications. We therefore opted to make the
cold plate from two side-by-side 75mm wide
pieces with a small space between them. The
first plate sources the refrigerant from a manifold
and the second side returns the refrigerant to an
isolated portion of the same manifold. Rather
than retool a new extrusion, for this first limited
deployment, we decided to machine our current
material down from 100mm to 75mm
Figure - Micro-channel Close-up View
The primary challenge was how to connect the
front end of the plates such that the assembly
remained thin enough to slide into the narrow slot
in the rear of the server and maintain continuity
of the channels without intermixing between
channels. If a simple manifold was used, bubbles
Page 22 of 37
DE-EE0002896
from refrigerant heating on the sourcing path would all rise to the top of the manifold, leading to
dry out and ineffective cooling on the upper half of the return manifold.
We solved this problem by developing a technology to butt soldering extrusions end-to-end. The
cold plate sections are mitered to terminate in 45 degree angles. A third piece is doubled
mitered into a wedge shape and placed between them. These three pieces are plated and
tinned and soldered together in a temperature controlled press. The other ends are soldered
into the refrigerant distribution manifold. Special jigs and techniques were developed to assure
an accurate quality solder joint and limit solder flow to unwanted areas such as the microchannel tubes. As a final quality check, all plates are subject to over-pressure, flow and vacuum
tests prior to the next level of assembly.
Figure is a picture of the top of the cold plate prior to TIM installation. The left end (rear) is
finished with a manifold that, in turn, connects to chassis supply and return manifolds.
Figure - Server Cold Plate Assembly Bottom
Page 23 of 37
DE-EE0002896
Figure is a picture of the top of the cold plate prior to TIM installation. It is covered with a low
friction HDMW plastic. Note the right side (front) is finished with a guide rail that aligns the plate
when it is slipped into the server. It also pre-aligns the plate in the proper position in the chassis
to receive the server during installation.
Figure - Server Cold Plate Assembly Top
The 6” wide by 21” long cold plates are mounted vertically two-high in 16 slots in each chassis.
The rear of the cold plates are permanently brazed to a common manifold that sources the
refrigerant liquid through the bottom pipes and takes away the liquid/gas combination emerging
from the top pipe.
Cold Plate Thermal Interface (TIM)
A conformal thermal interface is next installed on the cold plate. It is designed to be readily
removable in case of wear or damage.
Figure 18 shows the TIM installed on a cold plate over an aluminum base. Note the brown
Figure - Server Cold Plate with TIM
Page 24 of 37
DE-EE0002896
plastic edge guards that are attached to the TIM that secure it to the side of the cold plate.
Metal aluminum tape over the TIM and guide rail finishes off the unit preventing undue
movement and covering all edges that might catch the serve during the installation or removal
procedures. The conformability of the TIM is illustrated in the picture by the apparent creases
and dents in the surface. These are purely cosmetic in nature and come about in the
manufacture and use of these units. They have no measurable effect on operation.
The TIM comprises a proprietary thermal grease inside a containing sleeve. The sleeve is
compound material comprising a thin strong thermally conductive plastic coating over a metal
layer.
The thermal grease mixture was co-developed with Dow-Corning Corporation with further
amendments and processing at Clustered Systems to achieve the appropriate properties. In
particular, the material must flow and conform to the irregular surface of the components and
heat risers it comes in contact. A large area of thermal contact is required for high thermal
conductivity from the components to the TIM and thus the cold plate. It needs a thermal
conductance approaching 2 w/m-k. The viscosity must be low enough to quickly conform to
pressures as low as 0.1PSI but must be sufficiently thixotropic such that it will never sag or run
when placed vertically or possibly damaged by abuse. Lastly, as the material is used in
relatively large quantities it must be very inexpensive compared to most commercially available
compounds.
Blade Installation Mechanisms
The blade enclosure has a number of features for easy and safe operation. The blade is
Inclined
Slot
Release
Lever Lock
Power
Switch
Screw
Mechanism
Figure – Close-up of Server Blade Installation Mechanism
Page 25 of 37
DE-EE0002896
designed to be hot swappable. Circuitry on the rear power interface board needs to be enabled
and disabled to control the 380VDC. It is imperative that the blade cannot be inserted or
removed when the power is on or when the engagement mechanisms are not set properly.
Additionally, the cold plate must be in contact and properly seated on the heat risers to conduct
heat when the server is turned on.
The blade lid is the key operating component for operating the blade cooling system. The cold
plate is held up against the lid at all times. When the blade is inserted in the chassis, the lid is
held high above the heat risers. After insertion, the lid is lowered, pressing the cold plate against
the heat risers. This is accomplished by a screw mechanism in the front of the blade which
draws the lid forward and back. Inclined slots in the lid engage pins in the blade base that
control the height depending on the relative position of the lid. As the lid moves forward, it
descends; it ascends when the direction is reversed.
Multiple interlocks, both mechanically and electrically are incorporated.

Pins on the rear of the lid prevent the blade from being inserted or removed unless the
lid is in the “high” position.

Bars on the screw mechanism lock the release levers in place and prevent blade
extraction unless the lid is in the “high” position.

Two redundant switches turn off the electrical power to the blade when the screw
mechanism is not in the locked position, preventing both removal when electrically “hot”
or powering the server when the cold plates are not engaged.
SLAC Installation
Finally installed in late December, the system was charged with refrigerant in mid-January. Due
to a quality problem at one of our suppliers, population of the rack was not completed until early
March and test software loaded mid March. This revealed a secondary problem with the
network adapter cards. Twenty seven of them would not communicate via the backplane. We
resolved this by adding cables to connect the front Ethernet connector to an external switch.
This allowed all the servers to communicate with the management system and upload the test
software.
Page 26 of 37
DE-EE0002896
Figure - Generic Rack Cooling Circuit
Figure illustrates how Clustered’s rack connects to the rest of the cooling system. In the case of
the SLAC installation, the “Heat Transfer to Ambient” is another heat exchanger that interfaces
with the building chilled water supply. The controls available to us were a) water pump speed
and b) a flow valve on the building chilled water circuit. Both had to be manually operated. We
ran tests over two days. Compute load was supplied by using “Prime95” in torture test mode.
Data was collected using power, temperature and flow loggers loaned by PG&E as well as the
internal temperatures of the various components as reported by the servers’ BMCs (Baseboard
Management Controller).
SLAC Installation Measured Results
On the first day, we did an operating range check by allowing the refrigerant temperature to
climb to about 60oC and observing at what temperature the CPU would begin to reduce its clock
speed.
Page 27 of 37
DE-EE0002896
Exploration of maximum coolant temperature performance
Table Temperature Cycle
Refrigerant
Return
Motherboard BMC
Temp
Inlet Temp Temp
17.0
17.3
18.5
20.0
22.5
26.2
29.0
31.0
35.8
41.3
53.4
57.5
55.2
47.0
48.9
44.5
30.7
24.6
21.5
19.8
18.9
18.3
17.9
36
37
38
39
41
44
47
50
53
58
68
74
75
71
70
71
63
54
48
45
43
41
40
31
32
32
33
35
38
41
43
46
50
58
66
67
65
64
64
56
49
44
40
38
36
35
P1
P1 VR Thermal
Temp Margin
44
46
46
49
52
55
56
57
60
66
76
82
82
80
78
79
72
64
58
54
52
50
49
-53
-51
-50
-44
-41
-38
-38
-39
-34
-26
-12
-12
-15
-19
-21
-20
-32
-39
-44
-47
-48
-49
-50
P2
Thermal
Margin
-53
-51
-50
-44
-41
-38
-38
-38
-34
-26
-12
-12
-15
-19
-21
-20
-32
-39
-44
-46
-48
-49
-50
DIMM 1
LAN NIC Thermal
Temp
Margin
34
34
35
36
39
42
45
47
51
56
66
72
71
65
67
63
53
47
43
41
39
38
37
-41
-40
-40
-39
-36
-34
-31
-29
-26
-22
-14
-6
-4
-7
-8
-8
-16
-23
-28
-32
-35
-36
-37
This table shows a typical server (#5). Measurements were made over a two hour time period at
5 minute intervals. The highest coolant temperature is highlighted in yellow. All temperatures
are in oC. All but the refrigerant temperature were logged using Intel management software.
Table column headings are as follows:
Refrigerant Return Temp – Temperature of the cooling refrigerant as it exits the rack
Motherboard Inlet Temp – Temperature sensor on the motherboard
BMC Temp – Baseboard Management Controller chip temperature
P1 VR Temp – Processor 1 Voltage Regulator temperature
P1 Thermal Margin – Processor 1 thermal margin
P2 Thermal Margin – Processor 2 thermal margin
LAN NIC Temp – NIC chip temperature
DIMM 1 Thermal Margin – DIMM #1 thermal margin
Page 28 of 37
DE-EE0002896
The temperature of the CPU is reported as a margin as Intel does not release the maximum
allowable junction temperature. The more negative, the better. When a CPU heats up enough
to force the margin to zero, the BIOS reduces its power consumption (throttles performance) to
avoid overheating. As can be seen, the margin disappears at approximately 60 oC. The key here
is that full performance is maintained to 60oC.
In practice it is not recommended to run a server continuously at such elevated temperatures.
While the semiconductor components may survive, the ancillary components, such as
electrolytic capacitors, may dry out and fail.
Design Repeatability
0
-5
-10
-15
-20
-25
-30
-35
-40
C001
C005
C009
C013
C017
C021
C025
C029
C033
C037
C041
C045
C049
C053
C057
C061
C065
C069
C073
C077
C081
C085
C089
C093
C097
C101
C105
C109
C113
C117
C121
C125
Temperature Margin oC
CPU Temperature Margin @ 40oC
Server Number
Figure - CPU Temperature Margin
Here we took a simultaneous sample of all 122 active servers. Of the 128 total, two had power
connection problems that could not be repaired in time and four were not brought up due to an
oversight by the systems administrator. As can be seen about 10% of the servers had
significant excursion from the -30oC margin.
The servers with zero margin have blocked inlet metering devices to the cold plates. This was
due to debris from the SLAC installation process blocking refrigerant flow. This will be
eliminated in future by installing a filter in the inlet manifold to each chassis.
Investigating the cause of the less significant excursions needs further work. Possible causes
include blade and TIM manufacturing variances, CPU power differences and possibly debris
restricting refrigerant flow through the metering devices.
As all the cold plates, TIMs and servers were prototypes assembled by hand, such variations in
performance would be expected.
Page 29 of 37
DE-EE0002896
Power Conversion Loss
We attached a flow meter and temperature sensors to the chilled water supply and return, and a
power meter to the 480VAC to 380VDC converter (Courtesy PG&E). We then varied the
refrigerant temperature slowly over four hours in order to detect any possible temperature
related anomalies. There were none.
Table Power Supply Efficiency
Delta T
37.84
Average
GPM
BTU
Calculated kW Actual kW
7.02 131,152
38.44
39.22
Powr Supply Efficiency
98%
As can be seen, the power supply was even more efficient than specified in Emerson’s literature
(97%) even at 40% of full load (note however that the stated accuracy of the power meter was
+/-1% and the flow meter about the same).
Overall Power and Cooling Efficiency
As it was too time consuming to set up measurements for the refrigerant and water pumps, we
relied on earlier measurements reported by Lawrence Berkeley Laboratories. We also used
their curve for chiller and economizer power requirements.
In this computation we assume that the system will be run with 40oC refrigerant temperature.
This implies that the cooling water temperature must be about 85 oF as shown in Table .
Table Cooling Water Temperature Computation
Refrigerant feed
Refrigerant feed
XDP HX drop
Water to ambient
Ambient
40
o
104
o
10
o
9
o
85
o
C
Recommendation
F
F
Data Sheet
F
F
Target
The total power required by the Liebert XDP is 0.81kW. This is capable of cooling 160kW, so we
pro rate this to 0.33kW.
The cooling water pump is assumed to be compliant with ASHRAE’s 90.1-2008 Chapter 11
rules which specify 0.022kW per GPM.
Finally, the heat rejection to ambient is calculated using a model chiller as defined in Appendix
B of LBNL document “Demonstration of Rack-Mounted Computer Equipment Cooling
Solutions”, by H. Cole 2010.
The 3 term polynomial equation used derives the kW/ton has the coefficients shown in Table
Page 30 of 37
DE-EE0002896
Table Coefficients for deriving kilowatts required per ton of cooling
T
3
Coefficient
0.00000628
T2
-0.00105494
1
0.04389858
T0
0.10162531
T
The efficiency is thus:
Table Efficiency Calculation
System power
Power conversion
Refrigerant Pump
Water Pump
Cooling Plant
kW
38.44
0.79
0.33
0.64
0.77
Total power
Efficiency
PUE
40.97
94%
1.07
Measured
Measured
Reported (LBNL)
Computed
Computed (LBNL)
Power Consumption Variation with Temperature
There was a fairly good correlation between the refrigerant return temperature and the power
consumed by the unit even though the power difference was less than 10%. The power
consumption leading the refrigerant temperature can be explained by its low flow rate.
Figure - Power Variation with Temperature Over a Two Hour Test Cycle
Page 31 of 37
DE-EE0002896
Publications:
These are being prepared in anticipation of announcing the placing in service of the rack at
SLAC. They will be accompanied by additional collateral



“Survey of liquid cooling systems” paper written, seeking publisher
“Data Center in a Box” Paper written, seeking publisher
“High Density Rack Cooling – choices” seeking publisher
Patents:
USPTO Application No. 13448353 “COLD PLATE WITH REDUCED BUBBLE EFFECTS” was
filed for work done under this contract.
Benefits Assessment
The results showed a true PUE of 1.07 for our system.
According to the Uptime Institute's 2012 Data Center Survey, the global average of
respondents' largest data centers is between 1.8 and 1.89.
As an example of state of the art, Google quotes an average PUE for its data centers of 1.12.
http://www.google.com/about/datacenters/efficiency/internal/index.html However, even though it
claims to include all sources of overhead in its calculations, it does not appear to include AC-DC
power conversions in the servers and the energy consumed by moving air through the servers.
Energy Star labeling requires a minimum internal power supply efficiency of 85% at 50% of
rated load. This is from the AC input to the 12VDC output. Fans consume an additional 10-20%
of the total server load.
If we generously assume a 90% power supply efficiency and 10% fan load as a state of the art
example, only about 79% of the input power is actually delivered to the compute elements
(motherboard) of the server. The true PUE is then not 1.12, but:
PUEGoogle = (1.12 / 0.9) / (1.0 – 0.1) = 1.38
A similar argument could be used on the global average with less efficient subsystems to
produce a true:
PUEglobal average = (1.85 /.85) / (1.0 -0.2) = 2.72
The measured PUE of 1.07 for our system includes the first stage of AC-DC conversion from
480VAC to 380VDC. We have a second stage on the board of 380VDC-12VDC. To make a
comparable calculation we need to add that efficiency into the calculation:
PUEClustered = 1.07 / 0.96 = 1.11
According to a report by Jonathan Koomey, data centers in the U.S consumed about 2% of the
total electricity in the country.
According to the EPA, 3,856 billion kWh were consumed in the U.S. in 2011. If we assume
similar numbers for the two years, approximately 77 billion Kwh were consumed by U.S. data
centers in 2011. Each billion Kwh generates an average of 1.22 million pounds of CO 2 per EPA
data (eGRID2012). If 50% of data centers adopted technology such as herein described, about
Page 32 of 37
DE-EE0002896
50 million pounds less of CO2 and other greenhouse gases would not be released into the
atmosphere every year – just in the U.S.
Table U.S. Data Center Energy Usage
Total US Energy Generation 2011
DC Energy Consumed (Koomey 2010) %
Data Center Portion
CO2 per MMWH (EGRID 2012)
Data Center Portion
3,856
MMWh
2%
77
1.22
94
MMWh
lbs/MWh
Mlbs
Other secondary but nonetheless important benefits of our system include:

The design is very high density. Greater density offers:
o
shorter inter-processor wire lengths which require less driver power while speeding
communication, improving compute throughput, a very important factor in HPC.
o
a smaller footprint; data center buildings can be made much smaller resulting in less
material input (especially cement, the manufacture of which produces large
quantities of CO2) and cost. In addition, they are also much simpler.

Complex air handling systems replaced by simple plumbing.

Considerably reduced cooling energy as liquid requires much less energy to circulate and is
a much more efficient heat remover; these energy savings combined with the elimination of
complex, ongoing air management processes result in greatly decreased operational
expenses.

Energy savings through equipment upgrade could be repurposed to run more computers,
postponing the need to build new data centers.
In summary, our system uses only 34% of the energy consumed by the global data
center average and 73% of the energy of the best of breed.
Page 33 of 37
DE-EE0002896
Commercialization
The technology is positioned as an open system cooling architecture that will accept any
mechanically compliant designs. An OEM might decide to make a totally proprietary design for
both front and rear blades or follow an as yet to be defined standard and make units compatible
with others’ products.
We have only recently focused heavily on commercialization. Even so, we have attracted a
large data center Infrastructure OEM to evaluate out technology. So far, they have bought a
rack and two chassis plus a couple of blades and are proceeding with evaluation.
Intel has also introduced us to a few OEMs. Feedback from them is our technology will be
useful for generations emerging in 2014.
A Europe based company has designed an adapter for our blades so we can populate a single
blade with 8 dense form factor (DFF) GPU boards.
These however are just part of the picture. Our strategy, as a small company with limited
resources is based upon three tactics:
a) Contact end customers to drive demand
b) Increase our visibility through our web presence and guerrilla marketing
c) Approach second tier OEMs and VARs to offer unique advantage
d) Work with Intel, AMD, nVidia, etc. to gain access to larger OEMs
e) Attempt to influence legislation favoring increased energy savings
In the short term, we may also make copies of the SLAC installation for early adopters.
We offer our customers the option of either a royalty bearing license to our technology or to
purchase the core technology items from us. These include the cold plates and TIMs.
The SLAC installation is at the core of our commercialization efforts. They are using it not only
for real ongoing number crunching for their large R&D compute needs, but are providing
independent testing and validation of the system and will be writing a series of reports on the
system. They are allowing us to invite prospective customers to view the system. This will be an
invaluable sales tool.
We have installed a chassis with one rack in our showroom/laboratory to showcase the product
and customer evaluation. As opposed to the SLAC installation that is being actively used by
SLAC as part of their data processing facilities, this system is available for customers to
evaluate in great detail. We can run their programs on it and demonstrate in real time its
performance.
A website has already been established (www.clusteredsystems.com) and profiles established
on Linked in and Facebook.
A comprehensive set of data sheets and white papers have been prepared.
Page 34 of 37
DE-EE0002896
Conclusions
The project has been a total success in its cooling and power supply aspects. The stated goals
were exceeded and additional benefits of the technology were discovered. These include very
high density that can cut capital expenditure by 50%, and the flexibility of the cold plate system.
We believe that we can double the cooling capacity to 200kW per rack, making it suitable for
GPU intensive computing.
We are disappointed that the work on the I/O virtualization and processor-to-processor
communication was not finished prior to the end of the contract. However, we are working with
our supplier to complete the work and install it at SLAC.
We have noted considerable resistance to change in the Data Center facilities community. This
is due to multiple considerations including fear of job loss, lack of understanding and resistance
to change what is good enough (even though very expensive and unreliable).
The many expert Data Center designers whose whole experience has been with air cooling will
find that their cooling skill set would no longer be needed. Most facilities personnel have not had
a strong grounding in basic physics and properties of matter, hence are skeptical of the claims
made by the liquid cooling community. Finally, change is resisted because nobody wants to be
first, resulting in a “Catch 22” situation.
Recommendations
1) The DoE should specify that PUEs for any new HPC project should not exceed 1.15.
This would help develop the market, not just for Clustered Systems but for any company
with a viable liquid cooling solution.
2) Energy calculations for liquid cooled systems should be added to the DoE “DC Pro”
program.
3) The orthogonal switch architecture, while it has been used for several years in network
switches and routers is new to the compute space. This can introduce a new degree of
architectural flexibility, enabling higher speeds due to increased server density, different
interconnect topologies and even improve software defined networking. DoE should
solicit proposals along these lines.
4) DoE must use its “bully pulpit” for liquid cooling promotion.
5) Fund additional development in the cooling of GPUs in the Clustered architecture.
Acknowledgements
We would like to thank our partners and their employees whose participation in this project
helped make it a success:
California Energy Commission – additional funding
Intel Corporation – CPUs, motherboards and technical assistance
Emerson Network Power – custom rack, modified XDP and bulk 380VDC power supplies
One Stop Systems – PCIe switches and boards
Panduit Corporation – PDU development and manufacture
PG&E – for the loan of thermal, power and flow data loggers
Dow Corning Company – custom thermal grease formulations and technical support
SLAC National Accelerator Laboratory – system installation and evaluation
Page 35 of 37
DE-EE0002896
The many small machine and metal worker shops that gave us invaluable advice and support
including California Machining, Spacesonics, Eclipse Metal Fabrication, Sematech, etc.
References
http://uptimeinstitute.com/2012-survey-results
http://www.google.com/about/datacenters/efficiency/internal/index.html
Jonathan Koomey http://www.analyticspress.com/datacenters.html
http://www.energystar.gov/ia/partners/downloads/V5_0_Computer_Clarification.pdf?d5d9-e03b
ASHRAE’s 90.1-2008 Chapter 11
Appendix B of LBNL document “Demonstration of Rack-Mounted Computer Equipment Cooling
Solutions”, by H. Cole 2010
Page 36 of 37
DE-EE0002896
Appendices
Data Sheets
Page 37 of 37
ExaBlade XCS-3000 100kW Blade Rack
XCS-3000 Overview
The ExaBlade XCS-3000 is a very dense, very
energy efficient, blade product family. This
blade power and cooling platform uses
Clustered Systems’ phase-change Touch
Cooling™ technology. The power and cooling
overhead is so low that it is an excellent choice
for any multi-server application.
It supports up to 192 dual CPU server boards
in 96 dual board blades, 24 network switch
blades, plus power distribution and cooling.
Alternately, power supplies and switches may
be substituted for one or more chassis to
provide a fully integrated Super Node in a
single rack.
All electrical and electronic components and
boards are readily replaceable, ensuring a
multi-generational platform life.
The figure on the right illustrates a XCP-R3006
rack fully populated with six XCP-C3000
chassis, each outfitted with 16 XCP-CB3014
blades comprising two Intel S2600JP server
boards.
Standard configurations
Standard configurations support 1.2KW/blades
(>100KW total) power and cooling.
XCP-3080 Configuration




80ea 8U cooled front blade slots
20ea 1U cooled rear network blade slots
2ea 1U slots for network switches
1ea 6U 105KW 480VAC-to-380VDC
bulk power supply
XCP-3096 Configuration
 96ea 8U cooled front blade slots
 24ea 1U cooled rear network blade slots
Target Applications
The XCS-3000 is ideal for hosting High
Performance Computing, Cloud Computing,
Routing and Switching, Storage Systems, or
combinations thereof.
Clustered Systems has partnered with leading
hardware and software vendors to offer
complete turn-key systems.
Cooling System
The platform is cooled by Clustered Systems’
Touch Cooling™ technology. The XCS-3000
can be configured to cool up to 2.4KW per
blade and up to 200KW per rack.
Two cold plates cool each front blade position.
Pumped R134a refrigerant carries away the
heat via highly efficient refrigerant phase
change. One cubic centimeter of refrigerant
can carry off the same amount of heat as 5.5
liters of air using only a small fraction of the
pumping energy.
The thermal resistance between the hot chips
and cold plate is designed to be very low.
Often the returning refrigerant can be re-cooled
by ambient air without the use of a chiller.
Typically, cooling overhead is 5%-10% of IT
load. Chips dissipating up to 300W each can
be accommodated and cooled.
XGS-3000 100kW Blade Rack
The system is plug compatible with Liebert
Inc.’s XDP and XDC pump/heat-exchanger
/chiller units.

Eliminates power waste associated with
air movement; 20% to 50% energy
savings in the data center
Front Blade Slots

All connections are permanent,
hermetic and virtually leak proof.
These 16 slots per chassis are designed to
house compute servers, line cards or disk
drives. Each has two built-in cold plates
capable of providing effective cooling in excess
of 1.2KW. Special thermal pads are mounted
to the cold plates. The cold plates slip into slots
in the rear of the blades upon blade
installation, whereupon mechanisms then
clamp the cold plates down upon the hot active
components
Rear Blade Slots
These are orthogonally mated to the front
blades without an intermediate backplane or
mid-plane. They provide interconnect between
the front blades and external network(s). As
they are field removable, they may also contain
active components, unlike conventional blade
products which require the chassis to be
dismantled to extract the mid-plane. Each slot
has a cold plate above it.
Availability
Available now.
Companion Products
Clustered Systems offers the following
introductory products for the XCS-3000:

XCP-C3000-s – standard blade chassis
mechanical enclosure that may be
loaded with subsystems of choice.

XCP-C3000-g – 2.4KW/blade chassis
version for GPU subsystems

XCP-PS3105-e 105KW 480VAC380VDC Emerson power supply

XCP-PB3001 – Chassis level PDU

XCP-CB3014 – Dual Intel S2600JF
blade

XCP-CD3042 – Intel S2600JF and dual
Intel PHI 7100 blade

XCP-CB3082P – Intel S2600CP GPU
controller blade

XCP-CB3082G – Octal Intel Xeon PHI
5100 blade

XCP-NBR3024 – a 24 port PCIe rear
mounted switch blade

XCP-SP3040 – a 40 port external PCIe
switch and I/O virtualization engine

XCP-CB3000X – standard front blade
mechanical enclosure that may be
loaded with subsystems of choice.

XCP-NBR3000X – standard rear blade
mechanical enclosure that may be
loaded with subsystems of choice.
Bulk Power Supply (3080 only)
Provision is made in the rack for a 6U high
unit. A 105KW 480VAC-to-380VDC rectifier
unit is available as an add-in to the XCS-3000.
Eliminating intermediate conversion and
distribution steps can cut energy consumption
by 10%.
Cable raceways are installed on each chassis.
Up to 1.2KW (2.4KW) 380VDC is available to
each blade. An interface module in each blade
converts from 380VDC to 12VDC blade power.
Serviceabilty
The XCS-3000
is designed to be highly
service friendly. All electronics, including
backplanes are field removable making it very
easy to execute a total system upgrade in situ.
Other benefits

Quiet! (no fans in blade chassis)

Room neutral, deployable anywhere
2
XGS-3000 100kW Blade Rack
Feature Summary
Rack Standard
Height
Width
Depth
Enclosure Style
Rack Style
Number of Chassis Per Rack
Chassis Height
Number of Front Slots Per Chassis
Inside Height of front blade slots
Inside Width of front blade slots
Inside Depth of front blade slots
Number of rear slots per Chassis
Inside Height of rear blade slots
Inside Width of rear blade slots
Inside Depth of front blade slots
Doors
Side panels
Construction Material
ROHS Compliance
Leveling Feet
Rack Hole Type
Gross Weight (when fully outfitted with blades)
Coolant
Type
Refrigerant ingress connection
Refrigerant egress connection
EIA-310-D, EIA-310-E Compliant
48U, 84 in (2134 mm)
31.5 in (800 mm)
47.2 in (1200 mm)
Rectangular
Free Standing
6
8U (13.95 in)
16
13.58 in (340mm)
1.6 in (40.6mm)
29.9 in (759mm)
4
1.5 in (38.1mm)
27.1 in (688 mm)
7 in (177.8 mm)
Optional lockable front & rear doors
Included
Powder coated steel
Optional
Supplied
N/A
4000lbs
R134a
2ea 7/8” Quick Connect male
2ea 1¼” Quick Connect male
© 2013 Clustered Systems Company, Inc.
Bldg 30-01, 3350 Scott Boulevard, Santa Clara, CA 95054
www.clusteredsystems.com
info@clusteredsystems.com
Tel +1-408-327-8100 Fax +1-408-327-8101
3
ExaBlade XCP-C3000 Chassis
XCP-C3000-x Overview
The XCP-C3000 is a member of Clustered
Systems’ XCS-3000 ExaBlade product family. The
XCS-3000 is an open platform that accepts any
mechanically conforming device. This very dense,
energy efficient blade power and cooling platform
uses Clustered Systems’ phase-change Touch
Cooling™ technology.
The XCP-C3000 is designed to be mounted in a
XCP-R3006 rack along with other chassis, power
supplies or switches.
All electrical and electronic components and
boards are readily replaceable, ensuring a multivendor compatibility and multi-generational
platform life.
The XCP-C3000 Blade Chassis comprises the
mechanical support, power distribution and cooling
for 16 XCP-CB30xx blades in the front and 4 XCPNBR30xx orthogonal active plane cards in the
rear. The active planes are typically networking
cards providing the first layer of switching in a
larger system.
The chassis has built-in power distribution with the
leftmost slot reserved for a PDU blade.
Two versions are available, the –s version that
powers and cools up to 1200W per blade slot, and
the –g version that powers and cools up to 2400W
per blade slot.
Pumped R134a refrigerant carries away the heat
via highly efficient refrigerant phase change. One
cubic centimeter of refrigerant can carry off the
same amount of heat as 5.5 liters of air using only
a small fraction of the pumping energy. Operation
is completely silent.
The thermal resistance between the hot chips and
cold plate is designed to be very low. Often the
returning refrigerant can be re-cooled by ambient
air without the use of a chiller. Typically, cooling
overhead is 5%-10% of IT load. Chips dissipating
up to 300W each can be accommodated and
cooled.
Chassis Components



16ea 8U cooled vertical front blade slots
1ea 8U uncooled vertical front PDU blade
slot
4ea 1U cooled horizontal rear blade slots
Cooling
The system is plug compatible with Liebert Inc.’s
XDP and XDC pump/heat-exchanger/chiller units.
Chasses are factory installed in the XCP-R3006
rack. Refrigerant is distributed to each chassis in
the rack via fixed flow regulators sized to the
chassis application. Refrigerant connections to
each chassis are permanently and hermetically
sealed by brazing to minimize the possibility of
leaks and consequential refrigerant loss. All
connections within each chassis are likewise
permanently and hermetically sealed.
Front Blade Slots
These are designed to house compute servers,
line cards or disk drives. Each has two built-in cold
plates capable of providing effective cooling in
excess of 1.2KW. Special thermal pads are
mounted to the cold plates. The cold plates slip
into slots in the rear of the blades upon blade
installation, whereupon mechanisms then clamp
the cold plates down upon the hot active
components
The figure above illustrates a XCP-3000-s fully
populated with sixteen XCP-3014 blades and a
PDU blade.
Rear Blade Slots
Rear blades directly mate to the front blades
without an intermediate backplane or mid-plane.
They provide interconnect between the front
blades and external network(s). As they are field
removable, they may also contain active
components, unlike conventional blade products
which require the chassis to be dismantled to
extract the mid-plane. Each slot has a cold plate
for cooling.
Chassis Power Distribution:
Cable raceways are provided with each chassis.
Up to 1.2KW (2.4KW) is available to each blade. A
PDU blade distributes the power to the individual
blades.
.
Feature Summary
Chassis Height
Chassis Depth
Chassis Width (mounting clearance)
Number of Front Server Slots
Number of Front PDU Slots
Inside Height of front blade slots
Inside Width of front blade slots
Inside Depth of front blade slots
Number of rear blade slots
Inside Height of rear blade slots
Inside Width of rear blade slots
Inside Depth of rear blade slots
Construction Material
ROHS Compliance
Coolant
Power/Cooling Option
Power Distribution
Rear Blade power / cooling
Front Blade power / cooling options
8U (13.95 in)
38.6 in (980.3mm)
28.7 in (728.8mm)
16
1
13.58 in (340mm)
1.58 in (40.1mm)
29.9 in (759mm)
4
1.5 in (38.1mm)
27.1 in (688mm)
7 in (177.8mm)
Zinc coated steel
Optional
R134a
20KW / 40KW
380VDC
400W
1200W / 2400W
© 2013 Clustered Systems Company, Inc.
Bldg 30-01, 3350 Scott Boulevard, Santa Clara, CA 95054
www.clusteredsystems.com
info@clusteredsystems.com
Tel +1-408-327-8100 Fax +1-408-327-8101
XCP-3014 Dual Intel S2600JP Blade
ExaBlade XCP-3014 Dual Intel S2600JF Blade
Overview
The XCP-CB3014 is a member of Clustered
Systems’ XCS-3000 blade product family. This
very dense, energy efficient blade power and
cooling platform uses Clustered Systems’ phasechange Touch™ Cooling technology.
The XCP-CB3014 Quad Socket Compute Blade
has the highest power density of any available
blade server. It is designed to plug into the XCPC3000 Blade Chassis. It contains two independent
dual socket Intel S2600JF server boards and two
optional hard drives. All communication to and
from each board is carried over two rear PCIe ports
and two 1GbE ports, one on the front panel and one
in the rear.
The external PCIe network is configured to provide
shared memory operation, very low latency interprocessor communication and I/O virtualization.
This approach also cuts energy usage by about 8%.
A 380VDC power connector provides power for
each board.
CPU and Memory
Each server board supports two of Intel’s Xeon EP26xx processors and eight DIMMs.
System Interconnect
The rear of each server has two high speed
connectors for redundant system interconnect.
Each carries a 4 lane PCIe 2.0 link plus a single
1GbE connection.
These connectors plug into a chassis mounted
Network Blade, such as the XCP-NBR3024, a 24
Port PCIe switch. This in turn connects to an
external XCP-SP3040, a 40 Port PCIe network
switch. This latter switch has a controller to
configure the PCIe network and provide I/O
virtualization facilities.
The rear Ethernet connection may be passed on to
an external management network.
Front Panel
USB, VGA and 1GbE ports are brought to the front
panel from each server and multiple LED indicator
lights provide system and server status.
Hard Disk Drive
Each server board supports a 2.5” form factor hard
disk drive.
Cooling
Cooling is supplied by the blade chassis using
Clustered Systems’ Touch Cooling™ technology.
Power and cooling will support full CPU turbo
mode of 3.1GHz and 135W power dissipation.
Power
Each server board connects to a 380VDC power
supply via a connector on the rear of the blade.
This voltage is converted to lower voltages in the
blade. This approach eliminates the need for heavy
cabling or bus bars and lowers resistance losses.
As a bulk 380VDC power supply may be directly
connect to native 480VAC, several intermediate
conversion stages are eliminated, resulting in about
10% energy savings.
Safety
At high DC voltages, measures must be taken to
ensure personnel safety and to prevent arcing
which may cause connector erosion or overheating.
The XCP-CB3014 contains one electrical and two
mechanical interlocks that prevent removal of a
powered board, and prevent power being applied to
the boards unless the blade is properly seated and
the cold plate is in position to cool the boards.
Each Blade
Form Factor
13.55” high x 1.57” wide x 29.9” deep
Weight
28 pounds
Number of Server Boards
2
Each Server Board Slot
Server Board
Intel Server Board S2600JF (“Jefferson Pass”)
Front Panel
Connectors:1GbE, VGA, 2ea. USB
Switches: Reset, Power, Selected
LEDs: Power, Status, ID, High Voltage, Network Activity
Rear I/O
2ea PCIe x4 Gen 2
2ea 1GbE management network
1ea 380VDC power connector
Hard Disk
2.5” Form Factor, 7200 RPM, 160GB, SATA 3Gb
Power input
380VDC, 1.3A
Cooling System
Clustered Systems Touch Cooling™ technology
Remote Management
IPMI 2.0 interface
© 2013 Clustered Systems Company, Inc.
Bldg 30-01, 3350 Scott Boulevard, Santa Clara, CA 95054
www.clusteredsystems.com
info@clusteredsystems.com
Tel +1-408-327-8100 Fax +1-408-327-8101
XCP-3014 Dual Intel S2600JP Blade
ExaBlade XCP-SP3040 External PCI Switch
Overview
The XCP-SP3040 Switch is a PCIe 2.0
x4 switch containing two independent 24
port switches in a 1U high box. 20 ports
from each switch terminate to external
PCIe connectors in the rear while the
other four connect to the COM module
and optional I/O module.
Intel® I/O Expansion
Module An Intel® I/O Expansion
Modules slot in the front enables
external connectivity via dual10G
Ethernet, or any other I/O type
compatible with the Intel® I/O
Expansion Module format, including
InfiniBand, SATA, etc.
COM Module
Applications
Each switch has a COM module for
control and configuration.
The XCP-SP3040 interconnects with,
and controls the XCP-NBR-3024 Switch
Blade. It provides switching and access
to an external network.
The COM module performs network
discovery and configuration functions
for the switch network. This information
is shared with other interconnected
switches to provide a unified platform
for blade-to-blade communication.
PCIe Switch Network
The PCIe switch network comprises all
the interconnected switch blades and
external switches. Every server
connected to the network has access to
every other server through PCIe packet
switching.
Power and Cooling
The box is powered by 120 VAC and is
air cooled.
References
Intel® I/O Expansion Modules
http://www.intel.com/products/server/io/index.htm
Features
Each Blade
Form Factor
1U high x 26” wide x 30” deep
PCIe 2.0 connections
40
Intel® I/O Expansion
Modules slots
1
Power input
120 VAC, 200W
© 2013 Clustered Systems Company, Inc.