Technical Bulletin
M12 Field Connector
4-Conductor Molded Cordset
l5-Conductor Molded Cordset
l
l
Revision 5.2
156 Auriesville Road
Fultonville, NY 12072
Phone: 518-922-5315 or 800-833-0081
www.anderson-negele.com
Field Wireable Connector Assembly
Shown With
Cap Removed
Thread
sealing tape
CABLE
REQUIREMENTS
—2 conductor, stranded, 18-24
AWG, shielded with ground.
Retaining Ring
Sleeve
Compression
Ring
Transmitter
Red
Black
Document 1142
Anderson Instrument Co., Inc.
LOOP +
LOOP -
Pressing Screw
Seal
Grommet -2 included choose one to accommodate cable OD
O-Ring
Key
Pin 1
Pin 2
To install the Receptacle tighten until
metal to metal contact is made.
When done properly the O-Ring
should no longer be visible.
Pin 4
Pin 3
Pin 2 - Black
(-PWR)
DETAIL
Receptacle End
Pins 3, 4 and 5 not used on 2-wire devices
1. Insert cable through Pressing Screw,
Compression Ring, Seal Grommet, and
Sleeve as shown below.
2. Strip back 1-1/4” of outer sheathing, cut off
any excess wires, shield and ground. Strip off
1/4” insulation from remaining two wires. It is
not necessary or recommended to tin the
wires.
3. Orient Connector end so that center pin
connecting screw is horizontal facing right
Pin 1 - Red
(+PWR 9-30 VDC)
Center Pin
Screw (Reference)
DETAIL
Connector End
4. Wire LOOP+ (red) wire to top-right terminal, and
LOOP- (black) wire to top-left terminal. No
connection is made to the center and bottom
terminals.
5. Screw on the Sleeve. Hand-tighten only.
6. Press the Seal Grommet into the Sleeve and handtighten the Pressing Screw.
7. Use a wrench to tighten the Pressing Screw
another 3/4 turn. Do not over-tighten!
Attaching The Connector To The Transmitter
To install connector, simply line up key, press
into receptacle, and hand-tighten the
Molded Cord Set - 5-Conductor, Grounded
Loop+(red) wire Pin 1
Loop- (black) wire Pin 2
P/N: 42117H0025
42117H0050
42117H0100
Receptacle
Transmitter
Shield (bare) wire
Note: Blue, Black and Grey not used
on 2 wire devices.
Ground shield connected to nut.
+ LOOP
- LOOP
Molded Cord Set - 4-Conductor
*Dielectric Grease
P/N: 5662400000
Loop+ (red) wire Pin 1
Loop- (black) wire Pin 2
*In wet or corrosive environments it is recommended that the receptacle pins be coated with USDA
approved dielectric grease to minimize possibility of corrosion.
Rev. 5.2
Doc 1142
P/N: 42117K0025
42117K0050
42117K0100
Shield (clear or bare) wire
Note: Green and White not used
on 2 wire devices.
Ground shield NOT connected to nut.
Page 1
Molded Cordset - 4-Conductor
Molded End Black
14mm
HEX
0.168
2”
Part Number
42117K0025
42117K0050
42117K0100
SPECIFICATIONS
Connector:
Contact Carrier Material/Color:
Molded Head Material/Color:
Contact Material/Plating:
Coupling Nut:
Shielding Sleeve:
Rated Current:
Rated Voltage:
Outer Cable Jacket Material/Color:
Conductor Insulation Material:
Number of Conductors:
Drain Shield:
Temp Range:
Protection Class:
5 Pin Eurofast Style Female
Pur/Black
Pur/Black
Brass/Gold
14mm HEX
N/A
4.0 A
250V
PVC/Black
PVC
4 x 24 AWG - Pin 4 Not Used
24 AWG Drain / Foil Shield
-40C to +80C
Meets NEMA 1, 3, 4X, 6P and IEC IP68, 69k
Length
25 ft
50 ft
100 ft
NOTE:
Pin 4 not Connected.
For best EMI protection drain shield
should be grounded at junction.
Molded Cordset - 5-Conductor
Molded End Blue
14mm
HEX
0.168
2”
Part Number
42117H0025
42117H0050
42117H0100
SPECIFICATIONS
Connector:
Contact Carrier Material/Color:
Molded Head Material/Color:
Contact Material/Plating:
Coupling Nut:
Shielding:
Rated Current:
Rated Voltage:
Outer Cable Jacket Material/Color:
Conductor Insulation Material:
Number of Conductors:
Drain Shield:
Temp Range:
Protection Class:
Rev. 5.2
5 Pin Eurofast Style Female
Pur/Black
Pur/Blue
Brass/Gold
14mm HEX
100% Shield coverage
4.0 A
250V
PVC/Black
PVC
5 x 24 AWG - Pin 4 Not Used
24 AWG Drain wire / Foil Shield
-40C to +80C
Meets NEMA 1, 3, 4X, 6P and IEC IP68, 69k
Doc 1142
Length
25 ft
50 ft
100 ft
NOTE:
Drain shield connected to coupling. Additional
grounding not required or recommended.
Page 2