FIRERAY 5000-UL Reflective Beam Smoke Detector

Fire Alarm Systems | FIRERAY 5000-UL Reflective Beam Smoke Detector
FIRERAY 5000-UL Reflective Beam Smoke
Detector
www.boschsecurity.com
The Fireray5000‑UL Linear Smoke Detector covers
distances between 26.25 ft and 330 ft (8 m and
100 m). A reflective prism allows for the accurate
detection of smoke particles within the given distance
range.
For ranges between 26.25 ft and 164 ft (8 m and
50 m), one prism is sufficient. For ranges between
164 ft and 330 ft (50 m and 100 m), four prisms are
required. The additional prisms are included in the
FRay5000‑LR‑Kit Long Range Kit.
Key application areas are large halls such as historical
buildings, churches, museums, shopping centers,
factory halls, warehouses, etc.
The Fireray5000‑UL Linear Smoke Detector is suitable
for use in areas where point-type detectors are not
effective
The Fireray5000-UL Linear Smoke Detector can be
upgraded with one additional FRAY5000-HEADUL Detector Head. The system controller can control
two detectors. Each head can be programmed
separately.
u
Extended monitoring range
u
Up to 2 detectors per system controller
u
Two pairs of fire and fault relays (one per detector)
u
Transmitter and receiver integrated into a compact
housing
u
Integral LASER alignment
Functions
The transmitter emits an invisible infrared light beam
(850 nm) that is focused through a lens. The light
beam is reflected by the prism mounted opposite and
returned to the transmitter/receiver combination.
If the IR beam is obscured by smoke and the signal
received drops below the selected threshold (standard
10 s, adjustable), the detector triggers a fire alarm and
the alarm relay closes.
The sensitivity can be adjusted according to the
environmental conditions. The default settings of 25%
(sensitive), 35% and 50% (non-sensitive) can be
changed in steps of 1%. Each detector can be adjusted
individually. The standard setting is 35%.
The alarm relay can be set to auto-reset or latched
mode.
The LEDs indicate three different operating states:
• Alarm
• Fault
• Operation
You can control and set all parameters via the system
controller and LCD display for each detector head.
2 | FIRERAY 5000-UL Reflective Beam Smoke Detector
Slow changes in the operating states (e. g. component
aging, optics contamination, etc.) do not cause false
alarms, but are compensated by the automatic gain
control. Every 15 minutes, the system state is
compared with a default reference value and in the
case of a deviation, is corrected automatically
to 0.17 dB/h. If the compensation limit is reached,
"Fault" the fault signal is indicated.
If the IR beam is obscured within 2 s and the
obscuration is more than 87% and lasts for 10 seconds
and above (operator changeable), the fault relay
switches. Faults may be caused by an obstacle in the
beam path, by the covering of the reflector, etc. As
soon as the fault cause is removed, the fault relay is
cleared and after 5 s, the detector is automatically
reset to standard operation. The fire panel must be
reset separately.
The system has an alarm output, which is a relay with
a potential‑free change-over contact.
Certifications and approvals
Installation for smoke plume
Pos.
Description
A
Ceiling
B
C
Heat accumulation
D
IR beam
• Since the smoke from a fire does not simply rise
straight up, but rather spreads like a mushroom cloud
(depending on air current and accumulation), the
monitoring range is much greater than the diameter
of the IR beam.
• The lateral detection on either side of the beam is
24.6 ft (7.5 m).
• Country-specific Standards and guidelines on
planning must be observed.
Region
Certification
USA
UL
UROX.S3417 Fireray5000-UL
FM
3037125 Fireray5000-UL
CSFM
see our website
NYCMEA
22-08-E Fireray5000-UL
MSFM
2243 Fireray5000-UL
Detector arrangement
The detectors must be arranged according to the
following distances:
ULC
UROXC.S3417 Fireray5000-UL
X1
Distance from the ceiling
1 ft to 2 ft (0.3 m to
0.6 m)
X2
Horizontal distance detector/wall
min. 1.6 ft (0.5 m)
X3
Horizontal distance between two
detectors under gable roofs
Canada
Installation/configuration notes
• For connection to FPA-1000 and any UL-listed 24V
control panel.
• The line of sight between the detector and the
reflector always has to be clear and may not be
interfered by moving objects (e. g. overhead crane).
• Heat accumulation under the roof may prevent smoke
from rising up to the ceiling. Thus, the detector must
be mounted below the expected heat accumulation.
Accordingly, the benchmark values for X1 specified in
the table have to be exceeded.
• The mounting surface for the detector must be firm
and vibration-free. Metal supports that may be
affected by heat or cold are unsuitable for the
installation.
• The detector and the reflector are usually installed at
the same height and aligned with one another. The
wide angle of the IR beam allows for an easy
adjustment and for a reliable long-term stability.
• The detector must be mounted in a position where
the detector’s optical system is not exposed to direct
sunlight or artificial light. Normal ambient light has no
influence on the IR beam and the analysis.
Example: Gable roof, 10° roof pitch
X3 = 30 ft + (30 ft x 10%)
X3 = 30 ft + 3 ft
X3 = 33 ft
Positioning the detectors on flat ceilings
1.6 ft (0.5 m) < X2 < 30 ft (9.1 m)
60 ft (18.25 m)
30 ft
(9.1 m)
30 ft
(9.1 m)
X2
X1
1 ft (0.3 m)
< X1 <
2 ft (0.6 m)
60 ft (18.25 m)
60 ft (18.25 m)
3 | FIRERAY 5000-UL Reflective Beam Smoke Detector
Positioning the detectors under a shed roof
60 ft (18.25 m)
X1
60 ft (18.25 m)
Alarm relay (contact load)
100 mA @ 36 V
Fault relay (contact load)
100 mA @ 36 V
Mechanics
X1
Φ
X1
LED indicators for
X1
X2
1.6 ft
(0.5 m)
• Alarm
Flashes red every 10 s
• Fault
Flashes yellow every 10 s
• Operation
Flashes green every 10 s
Dimensions (W x H x D)
Positioning the detectors under a gable roof
X3
• Detector
5.3 x 5.3 x 5.3 in
(135 x 135 x 135 mm)
• Prism reflector
3.9 x 3.9 x 0.4 in
(100 x 100 x 10 mm)
• Control unit
7.9 x 9.3 x 3.2 in
(200 x 235 x 81 mm)
X3
X1
10°
1 ft (0.3 m) < X1 < 2 ft (0.6 m)
Housing
• Color
Light gray/black
• Material
C6600, non-flammable
Weight
• Detector
1.1 lbs (500 g)
• Prism reflector
0.22 lbs (100 g)
Parts included
• Control unit
2.2 lbs (1000 g)
Qty.
Components
Environmental conditions
1
Fireray5000‑UL Linear Smoke Detector:
compact device with integrated transmitter and receiver
Protection class as per EN 60529
IP 54
Reflective prism
Permissible operating
temperature
-22°F to 131°F (-20°C to 55°C)
1
1
Control unit
32°F to 100°F (0°C to 37.8°C)
1
Installation kit
Permissible operating
temperature, UL Listed
Installation
1.6 ft (0.5 m) < X2 < 24.6 ft (7.5 m)
X2
X2
Technical specifications
Planning
Electrical
Permissible distance detectorreflector
Min. 26.25 ft (8 m) – max. 164 ft
(50 m)
•with FRay5000‑LR‑Kit Long
Range Kit
Min. 164 ft (50 m) – max. 330 ft
(100 m)
Lateral detection
(on either sides of the light beam)
Max. 30 ft (9.1 m) (heed local
guidelines!)
Connectable detectors per
system controller
1 or 2
Operating voltage
14 V DC (-10%) to 36 V DC
(+10%)
Current consumption
• In standby (1 detector head)
≤ 6 mA @ 36 V DC
• In standby (2 detector heads)
≤ 8,5 mA @ 36 V DC
• In alignment mode (with 1 or 2
detector heads)
≤ 37 mA @ 36 V DC
Reset control by power disruption
>5s
Special features
Optical wavelength
Tolerance of the axial deviation
850 nm
4 | FIRERAY 5000-UL Reflective Beam Smoke Detector
• Detector
± 0.3°
• Reflective prism
± 5.0°
FRAY5000-CMOUNT Ceiling Mount
Ordering information
Ceiling Pendant Mount for FRay5000-50-UL Reflective
Beam Smoke Detector prism and FRAY5000-BR
Universal Bracket Accessory for FRay5000 (not
available in APR).
FIRERAY 5000-UL Reflective Beam Smoke Detector
Order number FRAY5000-CMOUNT
Reflective linear smoke detector with one detector
head and one prism, range min. 26.25ft - max. 164ft
(for ranges between 164 ft and 330 ft four prisms are
required), comply with UL
Order number FIRERAY5000-UL
Accessories
FRAY5000-HEAD-UL Detector Head
additional detector head
Order number FRAY5000-HEAD-UL
FRay5000-LR-Kit Long Range Kit
3 additional prisms for Fireray5000-EN and
Fireray5000-UL, for ranges between 164 ft and 328 ft
(50 m and 100 m)
Order number FRay5000-LR-Kit
FRAY5000-BR Universal Bracket Accessory for
FRay5000
universal bracket for Fireray5000 detector head or
prism plate (FRAY5000-1PRISM or FRAY5000-4PRISM)
Order number FRAY5000-BR
FRAY5000-1PRISM Prism Plate for 1 prism
prism plate for 1 prism, for use with universal bracket
FRAY5000-BR
Order number FRAY5000-1PRISM
FRAY5000-4PRISM Prism Plate for 4 prism
prism plate for 4 prism, for use with universal bracket
FRAY5000-BR
Order number FRAY5000-4PRISM
FRAY5000-DETBOX Detector Back Box
Detector Back Box for FRay5000-50-UL Reflective
Beam Smoke Detector. Requires FRAY5000-PLATE
Cover Plate (sold separately, not available in APR).
Order number FRAY5000-DETBOX
FRAY5000-PLATE Cover Plate for Detector Back Box
Cover Plate for FRAY5000-DETBOX Detector Back Box
(sold separately, not available in APR).
Order number FRAY5000-PLATE
FRAY5000-CTRBOX Controller Back Box for FRay5000
FRay-5000 Reflective Beam Detector Controller Back
box with knock-outs (not available in APR).
Order number FRAY5000-CTRBOX
FRAY5000-TRIM Trim Plate for FRay5000 Controller
Back Box
Semi Flush Trim Plate for use with FRAY5000-CTRBOX
Controller Back Box for FRay5000 (sold separately, not
available in APR).
Order number FRAY5000-TRIM
5 | FIRERAY 5000-UL Reflective Beam Smoke Detector
Represented by:
Europe, Middle East, Africa:
Bosch Security Systems B.V.
P.O. Box 80002
5600 JB Eindhoven, The Netherlands
Phone: + 31 40 2577 284
emea.securitysystems@bosch.com
emea.boschsecurity.com
Germany:
Bosch Sicherheitssysteme GmbH
Robert-Bosch-Ring 5
85630 Grasbrunn
Germany
www.boschsecurity.com
© Bosch Security Systems 2016 | Data subject to change without notice
13228175627 | en, V8, 02. Aug 2016
North America:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
onlinehelp@us.bosch.com
www.boschsecurity.us
Asia-Pacific:
Robert Bosch (SEA) Pte Ltd, Security Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Download PDF