DIN-C-SDR 480P-48 Compact DIN RAIL Power Supply with Parallel

Technical Data Sheet
Compact DIN RAIL Power Supply
480W 48V with Parallel Function
UNIT CODE
DESCRIPTION
C-SDR 480P 48
480 Watt, 48V, Single Output Compact DIN RAIL
Power Supply with PFC and Parallel Functions
SPECIFICATIONS
Input
Output
Agency Approvals
Universal AC Input
90 ~ 264VAC
+48VDC @ 0 ~ 10A
SE
PQ
M
IF
47
GL
..
Features at a Glance:
Environmentally friendly, compact and quiet
High efficiency 94% and high reliability
Current sharing up to 3840W (7+1)
Slim (86mm), Installed on DIN rail TS35 / 7.5 or 15
The C-SDR-480P Series is a 480W compact
industrial DIN rail power supply with PFC
and parallel functions, 94%+ efficiency in a
Working temperature ranging: -25ºC ~ +70ºC
slim 85mm design. A full input range
switcher with built in PFC function and 720W
Protections: Short circuit / Over load /
Over voltage / Over temperature
peak power capability for 3 seconds. Great
alone or C-SDR-480P can be connected with
LED indicator for power on
up to 7 additional units, in parallel, for a total
Cooling by fan-less natural (free air) convection
of 3,840 Watts. Great for scaled expansion.
Certified by UL, CUL, TUV and CE
Short circuit, overload, over voltage, and
Safety standards: UL508 (Industrial control equipment) over temperature protection.
Built-in: Active PFC function, PF>0.94, constant
current limiting circuit & DC OK relay contact
TUV EN60950-1 approved, EN61000-6-2 (EN50082-2)
Industrial immunity level, SEMI F47, GL approved
MTBF hours: 112.9Khrs MIL-HDBK-217F (25ºC)
3 year warranty
C-SDR-480P also fulfils the requirement of
EN61000-3-2 for harmonic current and
complies with GL and SEMI F47 for marine
and semi-conductor related use.
Case: 984A
Pricing 1~ 9 $ 338
10+ $ 307
25+ $ 289
Weight: 3.5 Lbs. (1.6 Kgs)
Dimensions: 3.4“ W x 4.9“ H x 5.0“ D
85.5*125.2*128.5mm (W*H*D)
Pollock Industries, Inc. 81 Butternut Road, White River, VT 05001
toll-free 1-866-665-5434
(603) 888-2467
sales@pollock.biz
Copyright © 2013 Pollock Industries, Inc.
All trademarks and service marks are the properties of their respective owners
Pollock Industries,
480W Single Output Industrial DIN RAIL with PFC and Parallel Function
SDR-480P series
¡½ Features :
¡ECurrent sharing up to 3840W(7+1)
¡ High efficiency 94% and low power dissipation
E
¡ 150% peak load capability
E
¡ Built-in active PFC function, PF>0.94
E
¡ Protections: Short circuit / Overload / Over voltage / Over temperature
E
¡ Cooling by free air convection
E
¡ Built-in constant current limiting circuit
E
¡ Can be installed on DIN rail TS-35/7.5 or 15
E
¡ UL 508(industrial control equipment)approved
E
¡ EN61000-6-2(EN50082-2) industrial immunity level
E
¡ Built-in DC OK relay contact
E
¡ 100% full load burn-in test
E
¡ 3 years warranty
E
SE
PQ
M
IF
47
GL
..
SPECIFICATION
OUTPUT
SDR-480P-24
SDR-480P-48
DC VOLTAGE
24V
48V
RATED CURRENT
20A
10A
CURRENT RANGE
0 ~ 20A
0 ~ 10A
RATED POWER
480W
480W
PEAK CURRENT
30A
15A
PEAK POWER Note.6
720W (3sec.)
RIPPLE & NOISE (max.) Note.2 100mVp-p
120mVp-p
VOLTAGE ADJ. RANGE
48 ~ 55V
¡Ó1.0%
24 ~ 28V
VOLTAGE TOLERANCE Note.3 ¡Ó1.2%
LINE REGULATION
¡Ó0.5%
LOAD REGULATION
¡Ó1.0%
SETUP, RISE TIME
1500ms, 150ms/230VAC
HOLD UP TIME (Typ.)
14ms/230VAC at full load
VOLTAGE RANGE
INPUT
¡Ó0.5%
¡Ó1.0%
Note.7 90 ~ 264VAC
FREQUENCY RANGE
47 ~ 63Hz
POWER FACTOR (Typ.)
0.94/230VAC
EFFICIENCY (Typ.)
94%
AC CURRENT (Typ.)
INRUSH CURRENT (Typ.)
5A/115VAC
40A/115VAC
3000ms, 150ms/115VAC at full load
127 ~ 370VDC
0.99/115VAC at full load
2.5A/230VAC
80A/230VAC
<0.6mA / 240VAC
LEAKAGE CURRENT
Normally works within 110 ~ 150% rated output power for more than 3 seconds and then shut down o/p voltage with auto-recovery
>150% rated power, constant current limiting with auto-recovery within 2 seconds and may cause to shut down if over 2 seconds
56 ~ 65V
29 ~ 33V
Protection type : Shut down o/p voltage with auto-recovery or re-power on to recovery
OVERLOAD
PROTECTION OVER VOLTAGE
105¢J ¡Ó5¢J (TSW : detect on heatsink of power switch)
OVER TEMPERATURE
Protection type : Shut down o/p voltage, recovers automatically after temperature goes down
DC OK REALY CONTACT RATINGS (max.) 60Vdc/0.3A, 30Vdc/1A, 30Vac/0.5A resistive load
FUNCTION
Please see the Function Manual
CURRENT SHARING
WORKING TEMP.
WORKING HUMIDITY
Note.5 -25 ~ +70¢J (Refer to "Derating Curve")
ENVIRONMENT STORAGE TEMP., HUMIDITY
TEMP. COEFFICIENT
VIBRATION
SAFETY STANDARDS
SAFETY &
EMC
(Note 4)
¡Ó0.03%/¢J (0 ~ 50¢J)
Component:10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6
UL508, TUV EN60950-1 approved
I/P-O/P:3KVAC
ISOLATION RESISTANCE
EMC EMISSION
I/P-O/P, I/P-FG, O/P-FG:>100M Ohms / 500VDC / 25¢J/ 70% RH
Compliance to EN55022 (CISPR22) Class B, EN61000-3-2,-3
EMC IMMUNITY
Compliance to EN61000-4-2,3,4,5,6,8,11, EN55024, EN61000-6-2 (EN50082-2), EN61204-3, heavy industry level, criteria A,
SEMI F47, GL approved
DIMENSION
PACKING
NOTE
-40 ~ +85¢J, 10 ~ 95% RH
WITHSTAND VOLTAGE
MTBF
OTHERS
20 ~ 95% RH non-condensing
I/P-FG:2KVAC
O/P-FG:0.5KVAC
O/P-DC OK:0.5KVAC
112.9Khrs min. MIL-HDBK-217F (25¢J)
85.5*125.2*128.5mm (W*H*D)
1.6Kg; 8pcs/13.8Kg/0.9CUFT
1. All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25¢J of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12" twisted pair-wire terminated with a 0.1uf & 47uf parallel capacitor.
3. Tolerance : includes set up tolerance, line regulation and load regulation.
4. The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets
EMC directives.
5. Installation clearances : 40mm on top, 20mm on the bottom, 5mm on the left and right side are recommended when loaded permanently with full power.
In case the adjacent device is a heat source, 15mm clearance is recommended.
6. 3 seconds peak power max. and the average output power should not exceed the rate power.
7. Derating may be needed under low input voltage. Please check the derating curve for more details.
File Name:SDR-480P-SPEC 2012-06-04
Pollock Industries, Inc. Toll-free 1-866-665-5434 (603) 888-2467 americool.com
MODEL
Pollock Industries,
480W Single Output Industrial DIN RAIL with PFC and Parallel Function
SDR-480P series
Mechanical Specification
Unit:mm
128.5
Case No.984A
125.2
TB2
+
1
2
DC OK
85.5
DC OK
+V ADJ
TB1
3
1
2
3
4
5
6
7
8
Terminal Pin No. Assignment (TB1)
35
Pin No.
1
2
3
Assignment
FG
AC/N
AC/L
Terminal Pin No. Assignment (TB2)
Pin No.
1,2
3,4
5,6
7
8
ADMISSIBLE DIN-RAIL:TS35/7.5 OR TS35/15
Assignment
DC OUTPUT +V
DC OUTPUT -V
Relay Contact
P+ (currene share)
P- (currene share)
Block Diagram
DC OK
I/P
EMI FILTER
&
RECTIFIERS
POWER
SWITCHING
PFC
CIRCUIT
RECTIFIERS
&
FILTER
+V
-V
O.C.P.
U.V.P.
FG
PFC
CONTROL
O.L.P.
PWM & PFC
CONTROL
DETECTION
CIRCUIT
O.V.P.
DC OK Relay Contact
Contact Close
PSU turns on / DC OK.
Contact Open
PSU turns off / DC Fail.
Contact Ratings (max.) 30V/1A resistive load.
Pollock Industries, Inc. 81 Butternut Road, white River, VT 05001
Toll-free 1-866-665-5434
(603) 888-2467 americool.com
File Name:SDR-480P-SPEC 2012-06-04
Pollock Industries,
480W Single Output Industrial DIN RAIL with PFC and Parallel Function
SDR-480P series
Peak Loading
(1)
(2)
720W
720W
480W
240W
50 sec.
3 sec.
15 sec. 3 sec.
Derating Curve
Output derating VS input voltage
100
150
90
For 3 sec. (typ.)
120
80
70
LOAD (%)
LOAD (%)
100
Continuous
80
60
60
50
40
-25
0
10
20
30
40
50
60
70 (VERTICAL)
90
100
AMBIENT TEMPERATURE (¢J)
110
135
155
230
264
INPUT VOLTAGE (V) 60Hz
Function Manual
1. Current sharing
(1)Parallel operation is available by connecting the units shown as below (P+,P- are connected mutually in parallel) :
(2)The voltage difference among each output should be minimized that less than 0.2V is required.
(3)The total output current must not exceed the value determined by the following equation (Output current at parallel operation)
=(The rated current per unit) x (Number of unit) x 0.9.
(4) In parallel operation 8 units is the maximum, please consult the manufacture for other applications.
(5) When in parallel operation, the minimum output load should be greater than 3% of total output load.
(Min. load > 3% rated current per unit x number of unit)
+
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
-
LOAD
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
+
- DC OK P+ P-
PSU
Pollock Industries, Inc. 81 Butternut Road, white River, VT 05001
Toll-free 1-866-665-5434
(603) 888-2467 americool.com
File Name:SDR-480P-SPEC 2012-06-04
Download PDF