FDUL221, FDUD29x, FDUD29x-E, RE6, REF8

Sinteso™
Test units and accessories
FDUL221, FDUD29x, FDUD29x-E, RE6, REF8, REF8-S, REF8-C, RE8, RE8-S, RE8-C, RE7T,
RE8ST, RE8STCO, RE8-CO, RE7T-x, RE10, FDUM29x, FDLU291, LE3, StabexHF
Test units to test detectors and detector lines forfire detection installations FS20
●
●
●
●
●
●
●
●
007228_o_en_-2016-04-20
Detector exchanger FDUD291 for the efficient installation and removal of Sinteso
point detectors
Detector exchanger and tester FDUD292 and intelligent detector tester FDUD293
for commissioning, maintenance, and troubleshooting of point detectors, alarm
sounders, and linear smoke detectors
Bluetooth extension kit FDUD29x-E for wireless communication between the
detector exchanger and tester FDUD292 and a mobile terminal
Line tester FDUL221 for diagnosing detector lines
Detector tester RE6 for use with environmentally-friendly test gas REF8, REF8-S,
REF8-C
Detector tester RE7T with hot air generator, RE8ST with smoke capsule RE8-S,
RE8ST-CO with smoke capsule RE8-S, capsule RE8-CO, and CO capsule
Detector tester RE10 for undertaking a function check on linear smoke detectors
Telescope rods FDUM291/292 for extending detector exchanger, detector
exchanger and tester, and other testers
Building Technologies
Control Products and Systems
Line tester FDUL221
Properties
●
●
●
●
●
●
●
4-line display with 20 characters per line
Menu-guided operation
Supply with battery or via network adapter
Possible to update the device software (firmware) via the MCL-USB adapter (radio)
FDUZ227 and via a PC
Environmentally friendly processing
Reusable materials
Electronic parts and synthetic materials can be easily separated
Function
Different functions can be called up, e.g.,:
● Number of devices found at A and B connection
● Line errors found, location of the line error
● Short-circuit, open line, ground fault with indication of which conductor/s
● Total resistance is too high and/or charge voltage at the line end is too low
● Data transmission fault due to line capacitance being too high
● Browsing from detector to detector with screen displaying type and serial number
● Display of branches and choice of branch for scrolling
● Activating the internal alarm indicator of the selected detector and recognizing the
connected alarm sounder
● Extended operation and functionality on PC with line tester software FXS2017
● The line tester software FXS2017 is included in the scope of delivery of the line tester
FDUL221.
Line tester software FXS2017
2
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
Use
The line tester FDUL221 is a universal device for the final testing of fully installed FDnet fire
detector lines if a control panel is not connected. The device is used to search for errors for
the electrician, installer, or service technician.
1 On/Off button
5 2x terminal strips for the detector line
2 USB connection
6 Network adapter
3 Connection of a loop or stub line
7 Display
4 Shielding
8 Battery compartment on the underside for
2x 9 V lithium batteries
Scope of delivery for FDUL221
Building Technologies
Fire Safety
3
007228_o_en_-2016-04-20
Detector exchanger FDUD291
Properties
●
●
●
Possible to exchange the detector without a ladder or scaffolding up to a room height of
8 m with the help of the telescope rods
Joint springs enable the point detectors to be inserted or removed at an angle
The point detector can be held in four rotational positions This makes it easier to work
efficiently
Specially developed springs hold the point detector in the detector exchanger
Compatible with
– Telescope rods FDUM291/292
– Previous straight connectors VR10/11/12/13
– MP/MT handles and straight connectors
Environmentally friendly processing
Reusable materials
●
Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
●
●
●
●
Function
121
57
1
390
2
1 Point detectors FDO, FDOOT, FDT, FDOOTC
Dimensioned drawing FDUD291
2 Joint springs of the FDUD291
Detector exchanger and tester FDUD292 and intelligent detector tester FDUD293
The detector exchanger and tester FDUD292 and the intelligent detector tester FDUD293
are universal tools for inserting and removing point detectors. The FDUD292 is used for
commissioning and maintenance, and the FDUD293 for maintenance of the FDnet devices.
The following devices are exceptions:
● Flame detector FDF2x1-9
● Line separators FDCL221 and FDCL221-M
● Radio gateway FDCW221
● Radio manual call point FDM273
● Neural radio fire detector FDOOT271
4
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
Properties
●
●
●
●
●
●
●
●
●
●
●
●
●
Function FDUD292
●
●
●
●
●
●
Function FDUD293
●
●
●
Efficient and environmentally-friendly checking of the detectors without gas
Possible to exchange the detector without a ladder or scaffolding up to a room height of
8 m with the help of the telescope rods
Flexible springs allow the point detectors to be inserted and removed at an angle
The point detector can be held in four rotational positions This makes it easier to work
efficiently
Specially developed springs hold the point detector in the detector exchanger and tester
Efficient operation thanks to alphanumerical display with backlight and keyboard
Clearly visible LED indicators for 'Test OK', 'Detector exchange recommended', 'Detector
exchange obligatory'
9 V battery operation
Compatible with
– Telescope rods FDUM291/292
– Previous straight connectors VR10/11/12/13
– MP/MT handles and straight connectors
Possible to update the device software (firmware) via the MCL-USB adapter (radio) and
via a PC
Environmentally friendly processing
Reusable materials
Electronic parts and synthetic materials can be easily separated
Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
Commissioning, maintenance, status checking, and testing of detectors with further
diagnosis information directly on site
Requesting parameters such as the bus address and changing detector settings
Efficient error search on the detector and the control panel, particularly during installation
Access levels with different functional scope
Efficient testing through communication with the 'Sinteso Test' smartphone app; only with
optional Bluetooth extension kit FDUD29x-E
Efficient installation and removal of the point detectors FDO, FDOOT, FDT, FDOOTC
Testing and triggering detectors
Efficient error search on the detector and the control panel, particularly during installation
Use
The test device and line device communicate either wirelessly or via the MC link
(Maintenance and Commissioning Link) with an adapter cable.
A wireless link is possible with the following line devices:
Device
Exceptions
All point detectors from the 'Sinteso™' product line: FDO,
FDOOT, FDT, FDOOTC
FDOOT271
All manual call points FDM
FDM231, FDM233, FDM234, FDM234H,
FDM273
All alarm sounders FDS
—
Building Technologies
Fire Safety
5
007228_o_en_-2016-04-20
A link via the adapter cable FDUD292-A is possible with the following line devices:
Device
Exceptions
All modules FDCI and FDCIO
FDCI221, FDCI223, FDCIO221
Linear smoke detector FDL
—
Radio gateway FDCW221
—
1 LEDs
8 Joint springs
2 Manual call point FDM
9 Keypad
3 Alarm sounder FDS
10 Modules FDC
4 Point detectors FDO, FDOOT, FDOOTC, FDT
11 Linear smoke detector FDL
5 Battery compartment on the rear
12 Adapter cable FDUD292-A
6 Adapter cable connection FDUD292-A
13 Radio gateway FDCW221
7 Display
6
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
Bluetooth extension kit FDUD29x-E
●
●
●
For connecting the detector exchanger and tester FDUD292 to a mobile terminal
Enables wireless data exchange between a detector exchanger and tester and a mobile
terminal
Compatible with detector exchanger and tester FDUD292
'Sinteso Test' Android app
'Sinteso Test' simplifies the process of comparing the data stored in the detection tree with
the device information for installed peripheral devices. 'Sinteso Test' is installed on a mobile
terminal – for example, a smartphone – and used alongside a detector exchanger and tester
FDUD292 and a Bluetooth extension kit FDUD29x-E.
The detector exchanger and tester FDUD292 with Bluetooth extension kit FDUD29x-E
installed sends the 'serial no.', or 'ID no.', of an installed peripheral device to 'Sinteso Test'.
'Sinteso Test' displays the data assigned to the 'serial no.', or 'ID no.', in the detection tree.
The detector exchanger and tester allows you to query the device information for the
installed peripheral device and compare this with data from the detection tree.
Building Technologies
Fire Safety
7
007228_o_en_-2016-04-20
Detector tester RE6
●
●
●
●
The detector tester RE6 is used together with a test gas can REF8, REF8-S, or REF8-C.
It is designed to test optical smoke detectors, ionization detectors, and CO detectors.
The detector tester is positioned over the detector for the testing process. Brief pressure
causes the test gas to flow into the measuring chamber of the detector and therefore
simulate the presence of fire aerosols. After a short period of time, the detector responds
and triggers the alarm.
REF8 and REF8-S are environmentally-friendly test gases and comply with strict
environmental regulations. They do, however, contain flammable substances. REF8 is
used for the temperature range 0…+40 °C and REF8-S for -20…+40 °C in dry and damp
conditions. REF8-S is mainly used for temperatures below 0 °C or for point detectors that
only trigger the alarm when there is a high level of smoke density or after longer signal
integration.
REF8-C is used to test the CO functionality of detectors with a CO sensor. REF8-C can
be used in dry and damp conditions at temperatures between -20 °C and +50 °C.
When transporting, e.g., in a car, we recommend protecting the detector tester and the test
gas cans from heat.
Please observe the notices on the detector tester for operation.
8
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
Detector tester RE7T – Solo461 heat detector tester kit
The heat detector tester kit consists of
● 1x heat detector tester
● 2x rechargeable batteries
● 1x charger with 12 V connection cable
● 2x mains cables AC 110/120-220/240 V.
The heat detector tester contains a hot air generator. The heat detector tester is positioned
over the detector for the function check. The hot air emitted heats the detector which triggers
this alarm.
In high rooms, detectors positioned at an angle can be reached and tested using adapters
and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.
The heat detector tester must not be used in electrical switching stations or areas where
there is a danger of explosion.
Building Technologies
Fire Safety
9
007228_o_en_-2016-04-20
Detector tester RE8ST – Testifire 1001-101 RT test kit
The test kit RE8ST consists of
● 1x Testifire 1001-101 tester
● 1x RE8-S smoke capsule
● 2x rechargeable batteries
● 1x charger with 12 V connection cable
● 2x mains cables AC 110/120-220/240 V
● 1x USB cable.
The detector tester contains a smoke capsule. The detector tester is positioned over the
detector for the function check. The smoke that is emitted triggers an alarm.
In high rooms, detectors positioned at an angle can be reached and tested using adapters
and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.
The detector tester must not be used in electrical switching stations or areas where there is
a danger of explosion.
10
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
Detector tester RE8STCO – Testifire 1001-101 ST test kit
The test kit RE8STCO consists of
● 1x Testifire 2001-101 tester
● 1x RE8-S smoke capsule
● 1x RE8-CO CO capsule
● 2x rechargeable batteries
● 1x charger with 12 V connection cable
● 2x mains cables AC 110/120-220/240 V
● 1x USB cable.
The detector tester contains a smoke capsule or CO capsule. The detector tester is
positioned over the detector for the function check. The smoke or gas that is emitted triggers
an alarm.
In high rooms, detectors positioned at an angle can be reached and tested using adapters
and telescope rods.
The adapter RE7T-A and telescope rods FDUM291/292 must be ordered separately.
The detector tester must not be used in electrical switching stations or areas where there is
a danger of explosion.
Building Technologies
Fire Safety
11
007228_o_en_-2016-04-20
Accessories and spare parts for RE7T/RE8ST/RE8STCO
RE7T-A – Solo719 adapter for FDUM29x
Mounting adapter for the detector testers RE7T, RE8ST, and RE8STCO on the telescope
rods FDUM291 and FDUM292
RE7T-B – Solo760 battery
Battery as spare part
RE7T-C – Solo725 charger
Charger as spare part for charging the batteries RE7T-B
RE8-S smoke capsule for RE8ST and RE8STCO
RE8-CO CO capsule for RE8STCO
12
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
Telescope rods FDUM291 and FDUM292
Properties
●
●
●
●
●
●
Light and robust yellow plastic pipes – non-conductive material.
Plastic sockets and friction bearings ensure that the pipes run into each other easily.
Quick spring-type locking mechanisms allow continuous adjustment of the length.
The pipes can be extended to their maximum length. A stop is used to prevent them from
extending further.
Previous testers can be used.
The telescope rods cannot be extended.
WARNING
Falling objects
Danger of injury
● Always wear a hardhat when working with telescope rods.
WARNING
Approaching or touching live lines
Electric shock
●
Building Technologies
Fire Safety
Only use testers with telescope rods in volt-free areas.
13
007228_o_en_-2016-04-20
FDUM291
●
●
●
●
●
●
Light telescope rod for all applications in rooms up to 5.5 m high
Flap closure for continuous adjustment of the length
Three-part telescope with tri-oval pipes as practical grip
Twisting the pipe in the opposite direction is not possible
Weight: 1.2 kg without tester fitted
Retracted length 1.6 m, extended length 4.2 m
●
●
●
●
●
Long and robust telescope rod for all applications in rooms up to 8 m high
Flip top closure for continuous adjustment of the length
Sturdy four-sided telescope with round pipes
Weight: 3.4 kg without tester fitted
Retracted length 2.1 m, extended length 7.3 m
FDUM292
1 Flip top closure
14
Building Technologies
Fire Safety
2 Flap closure
007228_o_en_-2016-04-20
Detector tester RE10, alarm test filter TF04
●
●
For undertaking a function check on the linear smoke detectors. The alarm test filter
TF04 is inserted into the detector tester in accordance with the type of detector to be
tested.
An alarm test filter is also included in the adjustment kit FDLU291.
For testing, the detector tester is held in front of the detector lens in the IR beam. The
detector responds after a few seconds.
Adjustment kit FDLU291
The adjustment kit is used for commissioning the linear smoke detector FDL241-9. The lens
of the linear smoke detector can be efficiently aligned to the reflector by one man.
Scope of delivery:
● Case with adjustment device
● Alarm test filter
● Visor
● Magnet
● Spiral cable
● MC link cable
● 9 V battery
● Suspension fixture with cable grippers and chain
Building Technologies
Fire Safety
15
007228_o_en_-2016-04-20
LE3 Test lamp
The test lamp LE3 is used to test the function of all flame detectors over distances up to
10 m. It is housed in a transportable case together with the required accessories. In addition,
the case enables the test lamp to be kept in a dust-free condition.
The quartz-halogen lamp used creates an intense ray of light. This helps to align the lamp on
the detector which is to be tested. During the detector test, the ray of light is modulated. The
luminous intensity can be set in accordance with the distance.
The power is supplied by a rechargeable battery. Since the color of the light depends on the
charge state of the battery, it must always be charged in buffer mode. A special charger is
available for this.
WARNING
Use of test lamps in areas at risk of explosion
Risk of explosion
●
Do not use the test lamp LE3 in areas at risk of explosion.
Test lamp Stabex HF
The test lamp Stabex HF is used to test the function of intrinsically safe flame detectors in
zone 1 or 2 areas at risk of explosion.
The lamp is used directly in front of the detector for the test. The ray of light must be pulsed
with the sliding switch at half-second intervals.
WARNING
Opening test lamps in areas at risk of explosion
Risk of explosion
●
16
Building Technologies
Fire Safety
Do not open the test lamp Stabex HF in areas at risk of explosion.
007228_o_en_-2016-04-20
Technical data
Line tester FDUL221
Supply voltage
Min. DC 10 V, max. DC 30 V
Battery or via
2x9V
Network adapter
AC 240 V / DC 24 V, 625 mA
Power consumption during measurement
Depends on the number of devices and the display backlight
Detector line voltage:
FDnet – FS20, AlgoRex
DC 32 V
FDnet – SIGMASYS
DC 28 V
Max. detector key figures (MK) per line
MK with network adapter
Min. 550
MK with battery
Min. 150
Operating temperature
-25…+40 °C
Storage temperature without battery
-30…+75 °C
Storage temperature with battery
-25…+60 °C
Air humidity (no condensation permitted)
≤95 % rel.
Detector exchanger and tester FDUD292, intelligent detector tester FDUD293
Supply voltage
DC 9 V
Alkali battery
Standard 9 V battery
Lithium manganese dioxide battery for temperatures below -10 °C
ULTRALIFE U9VL or U9VL-J
Capacity 950 – 1200 mAh
Operating current:
Ready – light on/off
2 mA / 42 mA
Communication – 3 LEDs + buzzer
95 mA
Operating temperature
-20…+40 °C
Storage temperature
-30…+75 °C
Storage temperature with battery
-25…+60 °C
Air humidity (no condensation permitted)
≤95 % rel.
Detector tester RE6
Operating temperature
REF8
0…+40 °C
REF8-S
-20…+40 °C
REF8-C
-20...+50 °C
Storage temperature
-20…+40 °C
Number of detector tests; dependent on detector type
Max. 400
Heat detector tester RE7T
Operating temperature
5...+45 °C
Storage temperature
-10…+50 °C
Air humidity (no condensation permitted)
≤95 % rel.
Voltage
Auto: DC 12 V
Mains: AC 110/120-220/240 V
Charging time
Approx. 1 hour per battery
Detector tester RE8ST/RE8STCO
Operating temperature
5...+45 °C
Storage temperature
-10…+50 °C
Building Technologies
Fire Safety
17
007228_o_en_-2016-04-20
Detector tester RE8ST/RE8STCO
Air humidity (no condensation permitted)
≤95 % rel.
Voltage
Auto: DC 12 V
Mains: AC 110/120-220/240 V
Charging time
Approx. 1 hour per battery
Adjustment kit FDLU291
Dimensions of the adjustment device
120 x 65 x 22 mm
Test lamp LE3
Power consumption
50 W
Modulation frequency
4 Hz
Max. distance for alarm activation
10 m
Measuring capacity with charged battery and max. distance
Number of detectors
~ 50
Operating and storage temperature
-20...+45 °C
Areas of use
Areas not at risk of explosion
Incandescent lamp
Halogen 12 V / 50 W
Battery
12 V / 7 Ah, lead, gas tight
Charging time
Min. 16 h
Mains connection charger
AC 220 / 240 V, 50…60 Hz
Dimensions
●
Test lamp
178 x 180 x 369 mm
●
Battery
153 x 103 x 67 mm
Test lamp Stabex HF
Max. distance for alarm activation
A few cm
Operating and storage temperature
-20…+40 °C
Explosion protection
II 2 G EEx ib e IIC T4
Ex approval
PTB 98 ATEX 2062
Areas of use
Zones 1 and 2
Protection category
IP65
Incandescent lamp
Halogen 2.8 V / 0.5 A
Battery
2x alkali batteries 1.5 V
Mono cell UM-1
18
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
FDUL221
Siemens Switzerland Ltd, Gubelstrasse 22
CH-6301 Zug
Technical data: see doc. 008250
FDUL221 - Line tester Sinteso. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 ; 2011/65/EU (RoHS): EN 50581 / EN 55024
The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoC: No.: CED-FDUL221
FDUD292
Siemens Switzerland Ltd, Gubelstrasse 22
CH-6301 Zug
Technical data: see doc. 007227
FDUD292 - Detector tester. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/53/EU (RED): EN 300 220-2 / EN 301 489-3 / EN 60950-1 ; 2011/65/EU (RoHS): EN 50581
The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoC: No.: CED-FDUD292-293
FDUD293
Siemens Switzerland Ltd, Gubelstrasse 22
CH-6301 Zug
Technical data: see doc. 009718
FDUD293 - Detector tester. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/53/EU (RED): EN 300 220-2 / EN 301 489-3 / EN 60950-1 ; 2011/65/EU (RoHS): EN 50581
The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoC: No.: CED-FDUD292-293
Siemens Switzerland Ltd, Gubelstrasse 22
CH-6301 Zug
Technical data: see doc. A6V10355605
FDUZ227 - Radio modem. Test equipment for use in fire detection and fire alarm systems installed in buildings.
FDUZ227
2014/53/EU (RED): EN 300 220-2 / EN 301 489-1 / EN 301 489-3 / EN 62479 ; 2011/65/EU (RoHS): EN 50581
The declared conformity can be seen in the EU Declaration of Conformity (DoC), which is obtainable via the Customer Support center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoC No.: CED-FDUZ227
LE3
Siemens Switzerland Ltd, Gubelstrasse 22
CH-6301 Zug
Technical data: see doc. 000252
LE3 - Test lamp. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/30/EU (EMC): EN 50130-4 / EN 61000-6-3 / EN 61010-1 / EN 55024 ; 2011/65/EU (RoHS): EN 50581
The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoC: No.: CED-LE3
STABEX HF
Siemens Switzerland Ltd, Gubelstrasse 22
CH-6301 Zug
Technical data: see doc. A6V10248358
STABEX HF - Stabex HF Hand lamp. Test equipment for use in fire detection and fire alarm systems installed in buildings.
2014/34/EU (ATEX): EN 60079-0 / EN 60079-7 / EN 60079-11 / EN 60079-31 ; 2011/65/EU (RoHS): EN 50581
The declared conformity can be seen in the EU Declaration of Conformity (DoC), which ist obtainable via the Customer Support Center:
Tel. +49 89 9221-8000 or http://siemens.com/bt/download
DoC: No.: CED-STABEX_HF
Building Technologies
Fire Safety
19
007228_o_en_-2016-04-20
Details for ordering
Type
Item number
Designation
Line tester
FDUL221
A5Q00004397
Line tester with line connection kit FDUL221A, power unit set FDUL221-B and carry case
1.567 kg
Accessories
–
A5Q00004142
Lithium manganese dioxide battery
9 V / 1.2 Ah
0.035 kg
Spare part
FDUL221-A
A5Q00008436
Line connection set
0.088 kg
FDUL221-B
A5Q00008437
Power unit set
0.292 kg
FDUL221-C
A5Q00008438
PC cable RS232 as spare part for FDUL221
with interface RS232
0.037 kg
Type
Item number
Designation
FDUD291
A5Q00003585
Detector exchanger
0.594 kg
Detector exchanger and tester FDUD292
A5Q00003357
Detector exchanger and tester incl. adapter
cable FDUD292-A
1.079 kg
Intelligent detector tester
FDUD293
A5Q00018261
Intelligent detector tester incl. adapter cable
FDUD292-A
1.079 kg
Accessories
–
A5Q00004142
Lithium manganese dioxide battery
9 V / 1.2 Ah
0.035 kg
Spare part
FDUD292-A
A5Q00004990
Adapter cable, audio stereo cable with
3.5 mm jack plug
0.040 kg
Type
Item number
Designation
FDUD29x-E
S54319-Z30-A1
Bluetooth extension kit
Detector exchanger
Bluetooth extension kit
Weight
Weight
Weight
0.028 kg
Type
Item number
Designation
Detector tester
RE6
BPZ:3680300001
Detector tester for smoke detectors
Weight
0.950 kg
Accessories
REF8
A5Q00011687
Test gas can
0.194 kg
REF8-S
A5Q00011688
Test gas can
0.186 kg
REF8-C
S54370-N2-A1
Test gas can CO
0.203 kg
Type
Item number
Designation
Detector tester
RE7T
S54312-F3-A1
Solo461 heat detector tester kit consisting of
tester, 2 batteries, charger, cable
2.800 kg
Accessories
RE7T-A
S54312-F3-A1
Solo719 adapter for FDUM29x
0.260 kg
Spare part
RE7T-B
S54370-N5-A1
Solo760 battery for RE7T
1.090 kg
RE7T-C
S54370-N6-A1
Solo725 charger for RE7T
1.210 kg
Type
Item number
Designation
RE8ST
S54370-S23-A1
Testifire 1001-101 ST test kit
3.470 kg
RE8STCO
S54370-S24-A1
Testifire 2001-101 STCO test kit
3.750 kg
RE8-S
S54370-N25-A1
TS3 smoke capsules (6 pieces)
0.079 kg
Detector tester
Capsule
Weight
Weight
RE8-CO
S54370-N22-A1
TS3 CO capsules (6 pieces)
0.077 kg
Accessories
RE7T-A
S54312-F3-A1
Solo719 adapter for FDUM29x
0.260 kg
Spare part
RE7T-B
S54370-N5-A1
Solo760 battery for RE7T 1
1.090 kg
RE7T-C
S54370-N6-A1
Solo726 charger for RE7T
1.210 kg
1)
1
Compatible with RE8ST and RE8STCO
20
Building Technologies
Fire Safety
007228_o_en_-2016-04-20
Type
Item number
Designation
Telescope rod
FDUM291
A5Q00004996
Telescope rod – three-part telescope with
tri-oval pipes; 1.6 m / 4.2 m
Weight
1.960 kg
Spare part
–
A5Q00009787
Lever with screw and nut –
0.023 kg
flip top closure
–
A5Q00009786
Adapter with lever, screw, and nut incl.
mounting and sleeve bolt
0.088 kg
–
A5Q00009788
Small flap with screw and nut – flap closure
0.015 kg
–
A5Q00009789
Large flap with screw and nut – flap closure
0.016 kg
Type
Item number
Designation
Telescope rod
FDUM292
A5Q00004997
Telescope rod – four-part telescope with
round pipes; 2.1 m / 7.3 m
4.480 kg
Spare part
–
A5Q00009787
Lever with screw and nut – flip top closure
0.023 kg
–
A5Q00009786
Adapter with lever, screw, and nut incl.
mounting and sleeve bolt
0.088 kg
Type
Item number
Designation
Detector tester
RE10
BPZ:3685190001
Detector tester for linear smoke detectors
0.345 kg
Alarm test filter for RE10
TF04
BPZ:4931090001
Alarm test filter – absorption 77 %
0.005 kg
Type
Item number
Designation
FDLU291
A5Q00004905
Adjustment kit for linear smoke detector
incl. case
Adjustment kit
Weight
Weight
Weight
0.840 kg
Type
Item number
Designation
Test lamp
LE3
BPZ:3669510001
Test lamp for flame detector incl. case and
charger, without battery
5.260 kg
Accessories
FA2003-A1
A5Q00019353
Battery 12 V / 7 Ah / VdS
2.293 kg
BPZ:3679630001
Halogen lamp 12 V / 50 W
0.395 kg
Type
Item number
Designation
Stabex HF
BPZ:4620910001
Test lamp for areas at risk of explosion
Spare part
Test lamp
Building Technologies
Fire Safety
Weight
Weight
0.175 kg
21
007228_o_en_-2016-04-20
Applicable documents
Document ID
Name
008331
List of compatibility (for 'Sinteso™' product line)
008164
Equipment overview Sinteso™ Detector system FD20
007227
Technical manual Detector exchanger and tester FDUD292
009718
Technical Manual Intelligent detector tester FDUD293
A6V10254740
Operating instructions Solo461 heat detector tester kit RE7T
A6V10387053
Installation RE8ST Testifire 1001-101 ST test kit, RE8STCO Testifire
2001-101 STCO test kit
A6V10260320
Operation RE7T-C Solo726 charger for RE7T-B
008250
Technical Manual Line tester FDUL221
A6V10395483
Line tester – operating instructions for electricians
A6V10424692
Installation, Commissioning Sinteso Test
A6V10405496
Installation Bluetooth extension kit FDUD29x-E
007016
Technical manual Linear smoke detector FDL241-9
000257
Operating instructions Test lamp LE3
Safety data sheets
A5Q00011687D
Safety data sheet REF8
A5Q00011688D
Safety data sheet REF8-S
A5Q00035329C
Safety data sheet REF8-C
MCL-USB adapter (radio) FDUZ227, see data sheet A6V10355605.
Issued by
Siemens Switzerland Ltd
Building Technologies Division
International Headquarters
Gubelstrasse 22
CH-6301 Zug
Tel. +41 41-724 24 24
www.siemens.com/buildingtechnologies
22
Building Technologies
Fire Safety
Document ID
007228_o_en_-Edition
2016-04-20
© Siemens Switzerland Ltd, 2007
Technical specifications and availability subject to change without notice.
007228_o_en_-2016-04-20
Manual FD20
Register 9
Download PDF