ABB TZIDC Data Sheet

Data Sheet 10/18-0.22-EN Rev. I
TZIDC
Electro-Pneumatic Positioner
Contents
Measurement made easy
Compact, well-proven, and
flexible
HART protocol
Wide operating temperature range
— -40 ... 85 °C (-40 ... 185 °F)
For 4 … 20 mA two-wire technology
Low operating cost
Easy to commission, “single pushbutton” operating
philosophy
Compact design
Mechanical position indicator
Well-proven technology
ATEX, FM, CSA, GOST and IECEx approvals
Robust and environmentally ruggedized
For SIL2 safety loops
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
10/18-0.22-EN
Contents
1
2
3
4
5
6
7
8
9
Data Sheet
Description ........................................................................................................................................................... 3
1.1
Pneumatics ..................................................................................................................................................... 3
1.2
Operation ........................................................................................................................................................ 3
1.3
Communication .............................................................................................................................................. 3
1.4
Inputs and outputs .......................................................................................................................................... 3
1.5
Modular design ............................................................................................................................................... 3
Mounting versions............................................................................................................................................... 5
2.1
To linear actuators in accordance with the standard ..................................................................................... 5
2.2
To rotary actuators in accordance with the standard ..................................................................................... 5
2.3
Integral mounting to control valves ................................................................................................................ 5
2.4
Special actuator-specific mounting ................................................................................................................ 5
Operation .............................................................................................................................................................. 7
3.1
General ........................................................................................................................................................... 7
3.2
Operator panel ............................................................................................................................................... 8
Communication ................................................................................................................................................... 9
4.1
DTM ................................................................................................................................................................ 9
4.2
LKS adapter (RS-232 interface converter) ..................................................................................................... 9
4.3
FSK Modem ................................................................................................................................................... 9
Specifications .................................................................................................................................................... 10
5.1
Input.............................................................................................................................................................. 10
5.2
Output ........................................................................................................................................................... 10
5.3
Travel............................................................................................................................................................ 10
5.4
Air supply ...................................................................................................................................................... 10
5.5
Transmission data and influences ................................................................................................................ 10
5.6
Environmental capabilities............................................................................................................................ 11
5.7
Housing ........................................................................................................................................................ 11
5.8
Safety Integrity Level .................................................................................................................................... 11
5.9
Options ......................................................................................................................................................... 12
5.10 Accessories .................................................................................................................................................. 12
Ex relevant specifications ................................................................................................................................ 13
6.1
ATEX ............................................................................................................................................................ 13
6.2
IECEx ........................................................................................................................................................... 14
6.3
FM/CSA ........................................................................................................................................................ 16
Electrical connections ...................................................................................................................................... 22
7.1
TZIDC with remote sensor ........................................................................................................................... 23
7.2
TZIDC for external remote sensor ................................................................................................................ 24
Dimensions ........................................................................................................................................................ 25
Ordering information......................................................................................................................................... 28
9.1
Accessories .................................................................................................................................................. 31
Electro- Pneu mat ic Po sition er
TZIDC
for 4 ... 20 mA two-wir e tec hnol ogy
2
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
1
10/18-0.22-EN
Description
Change from one to two c ol umns
The TZIDC is an electronically configurable positioner with
communication capabilities designed for mounting to pneumatic linear
or rotary actuators. It features a small and compact design, a modular
construction, and an excellent cost-performance ratio.
Fully automatic determination of the control parameters and
adaptation to the final control element yield considerable time savings
and an optimal control behavior.
1.1
Pneumatics
a
An I/P module with subsequent pneumatic amplifier is used to control
the pneumatic actuator. The well-proven I/P module proportionally
converts the permanent electrical setpoint signal from the CPU into a
pneumatic signal used to adjust a 3/3-way valve.
The air flow for pressurizing or depressurizing the actuator is
continuously adjusted. As a result, excellent control is achieved.
When reaching the set point, the 3/3-way valve is closed in center
position to minimize the air consumption.
Four different pneumatics versions are available: for single-acting or
double-acting actuators, each with “fail-safe” or “fail-freeze” function.
1.1.1
“Fail-safe” function
If the electrical power supply fails, the positioner output 1 is
depressurized, and the pneumatic actuator’s return spring moves the
valve to the defined safe position. In case of a double-acting actuator
the second output 2 is additionally pressurized.
1.1.2
“Fail-freeze” function
If the electrical power supply should fail, the positioner output 1 (and
2, if applicable) is closed and the pneumatic actuator stops (“freezes”)
the valve in the current position. If compressed air supply should fail,
the positioner depressurizes the actuator.
1.2
Operation
The positioner has a built-in operating panel providing a 2-line LCD
and 4 pushbuttons for optimal local configuration, commissioning and
operational monitoring.
Alternatively, the appropriate configuration program and the available
communication option can be used.
1.3
Communication
The standard TZIDC model has a local communication interface (LKS
connector). Additionally, a “HART communication” option for
communication via the 20 mA signal is available. Both
communications are based on the HART Protocol.
1.4
Inputs and outputs
In addition to its input for the analog position set point the TZIDC
positioner is equipped with a digital input which can be used to
activate various protective functions in the device via the process
control system. A digital output allows you to output collective alarms
or fault messages.
1.5
Modular design
q
TheTZIDC basic model can be enhanced at any time by retrofitting
optional equipment. Option modules for analog or digital position
feedback or a shutdown-module can be installed. Additionally, a
mechanical position indicator, proximity switches or 24 V
microswitches are available for indicating the position independently
of the mother board function.
Change from one to two c ol umns
3
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
Basic model
Fig. 1: TZIDC schematic diagram
Basic model
1 LKS plug
2 Setpoint signal 4 ... 20 mA
3 Digital input
4 Digital output DO
5 Supply, 1.4 ... 6 bar (20 ... 90 psi)
6 Exhaust
7 I/P module with 3/3-way valve
8 Position sensor (optional up to 270° rotation angle)
10/18-0.22-EN
Optional upgrades
Optional upgrades
9 Plug module for analog feedback (4 ... 20 mA)
10 Plug-in module for safety shutdown (forced depressurization)
11 Plug module for digital feedback
12 Installation kit for mechanical position indicator
13 Installation kit for digital feedback with proximity switches
14 Installation kit for digital feedback with 24 V microswitches
IMPORTANT (NOTE)
With optional upgrades either the “Installation kit for digital feedback with proximity switches” (13) or the “Installation
kit for digital feedback with microswitches 24 V” (14) can be used.
In both cases, the “mechanical position indicator” (12) must be installed.
4
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
2
Change from one to two c ol umns
2.1
Mounting versions
To linear actuators in accordance with the
standard
Lateral attachment is in accordance with DIN / IEC 534 (lateral
attachment to NAMUR). The required attachment kit is a complete set
of attachment material, but does not include the screwed pipe
connections and air pipes.
2.2
10/18-0.22-EN
To rotary actuators in accordance with the
standard
This attachment is designed for mounting according to the standard
VDI/VDE 3845. The attachment kit consists of a console with
mounting screws for mounting on a rotary actuator. The adapter for
coupling the positioner feedback shaft to the actuator shaft has to be
ordered separately. Screwed pipe connections and air pipes have to
be provided on site.
2.3
Integral mounting to control valves
The TZIDC positioner featuring standard pneumatic action is available
as an option for integral mounting.
The required holes are found at the back of the device.
The benefit of this design is that the point for mechanical stroke
measurement is protected and that the positioner and actuator are
linked internally. No external tubing is required.
2.4
Special actuator-specific mounting
In addition to the mounting methods described above, there are
special actuator-specific attachments.
Please contact us for details.
Change from one to two c ol umns
5
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
Fig. 2: Mounting options
1 Mounting to linear actuators acc. to DIN / IEC 534
2 Mounting to rotary actuators to VDI / VDE 3845
6
10/18-0.22-EN
3
4
Integral mounting to control valves
Integral mounting to control valves by using an adapter panel
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
3
10/18-0.22-EN
Operation
Change from one to two c ol umns
A
The total range of parameters includes:
- Operating parameters
- Adjustment parameters
- Monitoring parameters
- Diagnosis parameters
- Maintenance parameters
Digital input
For the digital input, one of the following safety options can be
selected. You may use the operator’s panel or configuration program
to select an option.
- No function (default)
- Move to 0 % position
- Move to 100 % position
- Hold previous position
- disable local configuration
- Disable local configuration and operation
- Disable any access (no local or remote access via a PC)
The selected function is activated once the 24 V DC signal is no
longer applied (< 11 V DC).
3.1.1
3.1.2
3.1
General
Microprocessor-based position control in the TZIDC provides for
optimal results. The positioner features high-precision control
functions and high operational reliability. Due to their elaborate
structure and easy accessibility, the device parameters can be quickly
adapted to the respective application.
Operating parameters
The following operating parameters can be set manually if required:
Setpoint Signal
Signal min. 4 mA, max. signal 20 mA (0 ... 100 %)
freely selectable for split-range operation
min. range 20 % (3.2 mA)
recommended range > 50 % (8.0 mA)
Action (setpoint signal)
Increasing: Setpoint Signal 4 ... 20 mA = position 0 ... 100 %
Decreasing: Setpoint Signal 20 ... 4 mA = position 0 ... 100 %
Characteristic curve (travel = f {setpoint signal})
Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 or freely
configurable with 20 reference points.
Travel limit
The positioning travel, i.e. the stroke or angle of rotation, can be
reduced as required within the full range of 0 ... 100 %, provided that
a minimum value of 20 % is observed.
Shut-off function
This parameter can be set separately for each end position. When the
respective configured limit value is exceeded, the shut-off function
causes immediate travel of the actuator until reaching the set end
position.
When the shut-off value is set to “0”, the position is further controlled,
even in the respective end position.
Travel time prolongation
This function can be used to increase the max. travel time for full
travel. This time parameter can be set separately for each direction.
IMPORTANT (NOTE)
This function can only be used with the pneumatics with the
safety function “fail-safe”.
Switching points for the position
This parameter allows you to define two position limits for signaling
(see option “Module for digital position feedback”).
Digital output
The alarms generated in the TZIDC positioner can be polled via the
digital output as a collective alarm.
The desired information can be selected via the operator panel or
remotely via the configuration program.
The output can be set to “active high” or “active low”, as required.
Adjustment parameters
The TZIDC positioner has a special function for automatic adjustment
of the parameters.
Additionally, the control parameters can be set automatically (in
adaptive control mode) or manually to optimally adapt them to the
process requirements.
Tolerance band
Upon reaching the tolerance band, the position is slowly re-adjusted
until the dead band has been reached.
Dead band (sensitivity)
When reaching the dead band, the position is held. The factory setting
for this parameter is 0,1 %.
Actuator spring action
Selection of the sensor shaft rotating sense (looking into the open
case), if the valve is moved to the safe position by the actuator spring
(actuator is depressurized via Y1 / OUT1).
For double-acting actuators the actuator spring action corresponds to
pressurizing the pneumatic output (OUT2).
Display 0 ... 100 %
Adjusting the display (0 ... 100%) according to the direction of action
for opening or closing the valve.
3.1.3
Monitoring parameters
B
Various functions for permanent operational monitoring are
implemented in the TZIDC operating program. The following states
will be detected and indicated, e.g.:
- 4 ... 20 mA setpoint signal out of range
- position out of the adjusted range
- positioning time-out (adjustable time parameter)
- position controller inactive
- counter limits (settable in the diagnosis phase) exceeded
While automatic commissioning is in progress, the current state is
continuously indicated on the integrated LCD.
During operation, the LCD shows the most important process
variables:
- current position (in %),
- malfunctions, alarms, messages (as code)
Access to extended monitoring parameters is possible via HART
communication and the DTM.
7
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
3.1.4
Diagnosis parameters
10/18-0.22-EN
3.2.1
Single-button commissioning
The diagnosis parameters of the TZIDC program inform the operator
about the operating conditions of the valve.
From this information the operator can derive which maintenance
works are required, and when.
Additionally, limit values can be defined for these parameters. When
they are exceeded, an alarm is reported.
The following values are e.g. determined:
- Number of movements performed by the valve
- Total travel
The diagnosis parameters and limit values can be called up, set, and
reset via HART communication, using the configuration program.
Commissioning the TZIDC positioner is especially easy. The standard
Autoadjust function for automatic adaptation of the device parameters
can be started by simply pressing a single front panel button, and
without knowing parameterization details.
Depending on the selected actuator type (linear or rotary), the
displayed zero position is automatically adapted:
- for linear actuators counter-clockwise (CTCLOCKW)
- for rotary actuators clockwise (CLOCKW).
Besides this standard function, a customized “Autoadjust” function is
available. The function is launched either via the operator’s panel or
HART communication.
3.2
3.2.2
Operator panel
The TZIDC positioner’s operator panel with four pushbuttons allows
for
- operational monitoring
- manual control
- configuration
- fully automatic commissioning
The operator panel is protected by a cover which avoids unauthorized
access to the operating elements.
Display
The information indicated by the 2-line LC display is permanently
updated and adapted during operation, to inform the operator in an
optimal way.
During control operation (control with or without adaptation) the
following TZIDC data can be called up by pressing the pushbuttons
briefly:
- Up button:
Current setpoint (mA)
- Down button:
Temperature in device
- Up + Down buttons:
Current control deviation
Change from one to two c ol umns
Change from one to two c ol umns
Fig. 3: TZIDC with removed cover, view of the operator panel
Change from one to two c ol umns
8
Fig. 4: TZIDC operating elements and display
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
Kommuni kati on
4
Change from one to two c ol umns
4.1
10/18-0.22-EN
Communication
DTM
The DTM (Device Type Manager) for TZIDC is based on the
FDT / DTM technology (FDT 1.2) and can be integrated in a process
control system or loaded in a PC with the DSV401 (SMART VISION)
program. This allows you to work with the same user interface in the
commissioning phase, during operation, and for service tasks for
monitoring the device, setting parameters, and uploading data.
Communication is based on the HART protocol. It occurs via a local
interface connection (LKS) or in frequency-modulated mode using an
FSK-modem connected at any chosen point of the 20 mA signal line.
Communication has no effect on operation. Newly set parameters are
saved in the non-volatile memory directly upon the download into the
device, and become active immediately.
4.2
LKS adapter (RS-232 interface converter)
You can easily connect your TZIDC positioner to a PC, e.g., in the
workshop or in the commissioning phase, by using the positioner’s
LKS adapter (LKS = local communication interface).
An RS-232 interface converter adapts the signals on the serial PC
port to the level of the positioner’s LKS.
4.3
Fig. 5: Local communication via LKS adapter
1 TZIDC
3 Controller
2 LKS adapter
FSK Modem
The FSK modem establishes a digital frequency-modulated
communication (Frequency Shift Keying) with the TZIDC positioner.
Tapping is possible at any chosen point of the 20 mA signal line.
We recommend that you use an electrically isolated FSK modem. It is
bus-compatible when used with isolating amplifiers. Even connecting
explosion-protected field devices is possible, on condition that the
FSK modem is run outside the hazardous area.
Fig. 6: HART communication with FSK modem via 20 mA signal line
1 TZIDC
3 Controller
2 FSK modem
Change from one to two c ol umns
9
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
5
10/18-0.22-EN
Specifications
Change from one to two c ol umns
5.1
Input
5.4
Setpoint signal (two-wire technology)
Nominal range
4 ... 20 mA
Split range configuration between 20 ... 100 %
of the nominal range
Max.
50 mA
Min.
3.6 mA
Starting at
3.8 mA
Load voltage at 20 mA
9.7 V
Impedance at 20 mA
485 Ω
Digital input
Control voltage
Current
5.2
Air capacity
0 ... 5 V DC
logical switching state "0"
11 ... 30 V DC
logical switching state "1"
max. 4 mA
0 ... 6 bar (0 ... 90 psi)
5.0 kg/h = 3.9
Nm3/h
= 2.3 sfcm
13 kg/h = 10 Nm3/h = 6.0 sfcm
at 6 bar (90 psi) supply pressure
Output function
For single or double-acting
actuators, air is vented from
actuator or actuator is blocked in
case of (electrical) power failure
Shut-off values
End position 0 % = 0 ... 45 %
End position 100 % = 55 ... 100 %
Digital output (control circuit to DIN 19234 / NAMUR)
Supply voltage
5 ... 11 V DC
Current > 0.35 mA ... < 1.2 mA
Switching state logical "0"
Current > 2.1 mA
Switching state logical "1"
Effective direction (configurable) normally logical "0" or logical "1"
Travel limit
Travel time prolongation
Dead band time limit
10
1.4 ... 6 bar (20 ... 90 psi)
Air consumption
5.5
< 0.03 kg/h / 0.015 scfm (independent
of supply pressure)
Transmission data and influences
Decreasing
Increasing setpoint signal 0 ... 100 %
Increasing pressure at output
Increasing setpoint signal 0 ... 100 %
Decreasing pressure at output
Action (setpoint signal)
Increasing
Signal 4 ... 20 mA = Position 0 ... 100 %
Decreasing
Signal 20 ... 4 mA = Position 0 ... 100 %
Characteristic curve (travel = f {setpoint signal})
Linear, equal percentage 1:25 or 1:50 or 25:1 or 50:1 and freely
configurable with 20 reference points
Deviation
< 0.5 %
Tolerance band
0,3 ... 10%, adjustable
Dead band
0,1 ... 10%, adjustable
Resolution (A/D conversion)
> 16,000 steps
Sample rate
20 ms
Influence of ambient temperature
< 0.5% per 10 K
Reference temperature
20 °C
Influence of vibration
< 1 % to 10 g and 80 Hz
Seismic vibration
Meets requirements of DIN/IEC 68-3-3 Class III for strong and
strongest earthquakes
Travel
Rotation angle
Used range
Supply pressure
Output Y1
Increasing
at 1.4 bar (20 psi) supply pressure
5.3
free of oil, water and dust to DIN/ISO
8573-1. Pollution and oil content
according to Class 3 (purity: max.
particle size = 5 µm, max. particle density
= 5 mg / m3; oil content: max.
concentration = 1 mg / m3; pressure dew
point: 10 K below operating temperature)
IMPORTANT (NOTE)
Do not exceed the maximum operating pressure of the
actuator!
Output
Compressed air output
Range
Air supply
Instrument air
25 ... 120° (rotary actuators,
optional 270°)
25 ... 60 ° (linear actuators)
Min. and max. limits, freely
configurable between 0 ... 100 %
of total travel (min. range
> 20 %)
Range of 0 ... 200 s, separately
for each direction
Setting range 0 ... 200 s
(monitoring parameter for control
until the deviation reaches the
dead band)
Influence of mounting orientation
Not measurable
Complies with the following directives
- EMC directive 2004/108/EC from December 2004
- EC Directive for CE conformity marking
Communication
- HART protocol 5.9
- Local connector for LKS (not in explosion protection area)
- HART communication via 20 mA signal line with (optional) FSK
modem
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
5.6
Environmental capabilities
Ambient temperature
For operation, storage and
transport:
When using proximity switches
SJ2-S1N (NO):
Relative humidity
Operational (with closed housing
and air supply switched on):
Transport and storage:
5.7
-40 ... 85 °C (-40 ... 185 °F)
-25 ... 85 °C (-13 ... 185 °F)
95 % (annual average),
condensation permissible
75 % (annual average), noncondensing
Housing
Material / Degree of protection
Aluminum with ≤ 0.1 % copper, protection class IP 65 (optional IP
66) / NEMA 4X
Surface / Color
Electrostatic dipping varnish with epoxy resin, stove-hardened.
Case varnished black, RAL 9005, matte, housing cover Pantone
420.
Electrical connections
Screw terminals:
Max. 1.0 mm2 (AWG 17) for options
Max. 2.5 mm2 (14 AWG) for bus connector
10/18-0.22-EN
5.8
Safety Integrity Level
IMPORTANT (NOTE)
Applies to applications with single-acting and depressurizing
pneumatics.
The positioner TZIDC / TZIDC-200 and the emergency shutdown
module for meet the requirements regarding:
- functional safety acc. to IEC 61508
- explosion protection (depending on the model)
- electromagnetic compatibility in accordance with EN 61000
Without the input signal, the pneumatic module in the positioner vents
the drive and the installed spring in it moves the valve in a
predetermined end position (OPEN or CLOSED).
SIL specific safety-related characteristics:
Device
SFF
PFDav
λdd + λs
λdu
TZIDC / TZIDC-200 as
shutdown module
TZIDC / TZIDC-200 with
supply current 0 mA
94 %
1.76 * 10-4
718 FIT
40 FIT
94 %
1.76 * 10-4
651 FIT
40 FIT
For details refer to the Management Summary in the SIL-Safety
Instructions 37/18-79XA.
IMPORTANT (NOTE)
Do not expose the terminals to strain.
Four thread combinations for cable entry and pneumatic
connection
- Cable: thread 1/2-14NPT, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread G 1/4
- Cable: thread G 1/2, air pipe: thread Rc 1/4
(Optional: With cable gland(s) and pipe plugs if necessary)
Weight
1,7 kg (3,75 lb)
Mounting orientation
Any
11
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
5.9
Options
Module for analog position feedback 1)
Signal range
4 ... 20 mA (configurable split ranges)
Supply, 2-wire circuitry
24 V DC (10 ... 30 V DC)
48 V DC (20 ... 48 V DC, no ignition
protection)
Characteristic curve
(configurable)
Rising or falling
Deviation
<1%
IMPORTANT (NOTE)
Without a signal from the positioner (e.g., “no power” or
“initializing”) the module sets the output to > 20 mA (alarm
level)
Module for digital position feedback
Two switches for digital position feedback (position adjustable within
the range of 0 ... 100 %, ranges cannot overlap)
1)
Current circuits acc. to DIN 19234 / NAMUR
Supply voltage
5 ... 11 V DC
Signal current < 1.2 mA
Switching state logical “0“
Signal current > 2.1 mA
Switching state logical “1“
Direction of action
normally logical “0“ or logical “1“
(configurable)
Module for the emergency shutdown function 2)
24 V DC (20 ... 30 V DC) (galvanically
Supply voltage
isolated from input signal)
Safe position is activated when Voltage < 5 V
SIL
See "Safety Integrity Level"
A separate 24 V DC signal is normally applied to the emergency
shutdown module, which connects through the signal from the
microprocessor to the I/P module.
When the 24 V DC signal is interrupted, the I/P module executes the
respective safety function, depending on the mechanical construction.
The positioner output 1 is depressurized, and the valve is moved to
the safe position. In case of a double-acting actuator the second
output 2 is additionally pressurized.
IMPORTANT (NOTE)
The emergency shutdown module can only be used with
pneumatics with the safe position “fail-safe”.
The emergency shutdown module works independently of the mother
board, i.e. all information from the final control element is available in
the supervisory process control system at any time.
1)
2)
10/18-0.22-EN
The module for analog position feedback and the module for
digital position feedback plug in separate slots and can be used
together.
The module for the emergency shutdown function uses the same
space as the module for analog feedback and the module for
analog or digital feedback and cannot be plugged in and run
together with any of them.
Digital position feedback with proximity switches
Two proximity switches for independent position signaling, Switching
points adjustable between 0 ... 100 %
Current circuits acc. to DIN 19234 / NAMUR
Supply voltage
Signal current < 1.2 mA
Signal current > 2.1 mA
5 ... 11 V DC
Switching state logical “0“
Switching state logical “1“
Direction of action (logical state)
Proximity switch
< Lim. 1
SJ2-SN (NC)
SJ2-S1N (NO)
0
1
Position
> Lim. 1
< Lim. 2
1
0
> Lim. 2
1
0
0
1
IMPORTANT (NOTE)
When using proximity switch SJ2_S1N (NO), the TZIDC
positioner may only be used at an ambient temperature range
-25 ... 85 °C (-13 ... 185 °F).
Digital position feedback with 24 V microswitches
Two microswitches for independent position signaling. Switching
points can be adjusted from 0 ... 100 %.
Voltage
max. 24 V AC / DC
Load rating
max. 2 A
Contact surface
10 µm Gold (AU)
Mechanical position indicator
Indicator disk in enclosure cover linked with positioner feedback
shaft.
IMPORTANT (NOTE)
These options are also available for retrofitting by Service.
5.10 Accessories
Mounting material
- Attachment kit for linear actuators to DIN/IEC 534 / NAMUR
- Attachment kit for part-turn actuators to VDI / VDE 3845
- Attachment kit for integral mounting to control valves
- Attachment kit for actuator-specific attachment upon request
Pressure gauge block
- With pressure gauges for supply and output pressure.
- Pressure gauges with housing ø 28 mm
- Aluminum connection block in black
- Installation material in black for mounting to TZIDC
Filter regulator
All metal version in brass, varnished black, bronze filter element,
(40 µm) , with condensate drain.
max. pre-pressure 16 bar (232 psi), output adjustable to 1.4 ... 6 bar
(20 ... 90 psi).
IMPORTANT (NOTE)
The filter regulator may only be installed in combination with
the pressure gauge block (accessory).
PC adapter for communication
LKS adapter for plug-in connection to TZIDC
FSK modem for HART communication
PC software for remote configuration and operation
DAT200 Asset Vision Basic with DTM for TZIDC on CD-ROM
Change from one to two c ol umns
12
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
6
Ex relevant specifications
Change from one to two c ol umns
6.1
6.1.1
ATEX
Current circuit
Plug-in module for digital
position feedback
(terminal +51 / -52 or
+41 / -42)
ATEX Ex i
Designation:
Type Examination Test
Certificate:
Type:
Device class:
Standards:
Device class:
Standards:
II 2 G
Temperature class
T4
T5
T6 1)
1)
10/18-0.22-EN
II 2 G Ex ia IIC T6 resp. T4 Gb
II 2 G Ex ib IIC T6 resp. T4 Gb
II 2 D Ex ia IIIC T51°C resp. 70°C
Db
TÜV 04 ATEX 2702 X
Plug-in module for analog
position feedback
(terminal +31 / -32)
Intrinsically safe equipment
II 2 G
EN 60079-0:2009
EN 60079-11:2007
II 2D
EN 60079-0:2009
EN 61241-11:2006
Plug-in module for
shutdown contact input
(Terminal +51 / -52) or
+85 / -86)
Ta
Ambient temperature range
-40 ... 85 °C
-40 ... 50 °C
-40 ... 40 °C
Optional interface to
remote sensor
(Terminal X2-2: +Uref
X3-2: GND
X3-1: Signal
When using the plug-in module for "Digital Feedback" in Temperature Class T6, the
maximum permissible ambient temperature range is -40 ... 35 °C.
II 2 D
Housing surface
temperature
T81 °C
T61 °C
T51 °C
Ta
Ambient temperature range
(II 2 D)
-40... 70 °C
-40 ... 50 °C
-40 ... 40 °C
Ex ia or Ex ib type of ignition
protection
IIC:
L0 = 5mH
C0 = 2 µF
Electrical data
In intrinsically safe explosion protection types Ex ib IIC/Ex ia IIC or Ex
iaD, only for connection to a certified intrinsically safe circuit.
Current circuit
Signal circuit
(terminal +11 / -12)
Contact input
(terminal +81 / -82)
Switch output
(terminal +83 / -84)
Mechanical digital
feedback
(terminal limit1 +51 / -52
or limit2 +41 / -42)
Electrical data
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 6.6 nF
Li negligibly small
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 4.2 nF
Li negligibly small
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 500 mW
Ci = 4.2 nF
Li negligibly small
For max. values, see EC type
examination test certificate number
PTB 00 ATEX 2049 X
Proximity switches manuf. by Pepperl
& Fuchs
Electrical data
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 500 mW
Ci = 3.7 nF
Li negligibly small
Maximum values:
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 6.6 nF
Li negligibly small
Ui = 30 V
Ii = 320 mA
Pi = 1.1 W
Ci = 3.7 nF
Li negligibly small
Maximum values:
U0 = 5.4 V
I0 = 74 mA
P0 = 100 mW
Ci negligibly small
Li negligibly small
Local communication
interface (LKS)
IIB:
L0 = 5mH
C0 = 10 µF
Only for connection to a programmer
outside the potentially explosive
area.
(See special conditions)
Special Requirements
•
The local communication interface (LKS) may only be operated at
Um ≤ 30 V DC outside the potentially explosive area.
•
•
•
•
•
•
Variants with special certification confirming that they meet the
requirements for the "flameproof enclosure" type of ignition
protection may not be used as "intrinsically safe", if they have
been previously used as a flameproof type of ignition protection.
When used with gases from group IIA and a temperature class of
T1 for auxiliary power, the TZIDC positioner may only be used
outdoors or inside sufficiently ventilated buildings.
The gas supplied must be kept sufficiently free of air and oxygen
to prevent an ignitable atmosphere from forming.
The equipment may only be used as a II 2 D type device in areas
where the level of mechanical hazard is "low".
Cable and wire entries that meet the requirements of EN 6124111 for Category II 2 D as well as the ambient temperature range
must be used.
Prevent electrostatic charging due to propagating brush discharge
when the equipment is used for applications involving combustible
dust.
13
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
6.1.2
ATEX Ex n
Designation:
Declaration of conformity:
Type:
Device class:
Standards:
II 3 G
Temperature class
T4
T6
Electrical data
Current circuit
Signal circuit
(terminal +11 / -12)
Contact input
(terminal +81 / -82)
Switch output
(terminal +83 / -84)
Mechanical digital feedback
(terminal limit1 +51 / -52 or
limit2 +41 / -42)
Plug-in module for digital
position feedback
(terminal +51 / -52 or +41 / 42)
Plug-in module for analog
position feedback
(terminal +31 / -32)
Plug-in module for shutdown
contact input
(Terminal +51 / -52) or
+85 / -86)
6.2
IECEx
II 3 G Ex nA IIC T6 or T4 Gc
TÜV 02 ATEX 1943 X
"n" type of protection
II 3 G
EN 60079-15:2010
EN 60079-0:2009
Designation:
Ta
Ambient temperature range
-40 ... 85 °C
-40 ... 50 °C
Standards:
Electrical data
U = 9.7 V DC
I = 4 ... 20 mA, max. 21.5 mA
U = 12 ... 24 V DC; 4 mA
U = 11 V DC
U = 5 to 11 V DC
U = 5 ... 11 V DC
U = 10 ... 30 V DC
I = 4 ... 20 mA, max. 21.5 mA
Certificate No.:
Issue No.:
Type:
Type and
designation
Temperature class
T4
T6 1)
1)
Ex ia IIC T6 or T4 Gb
Ex ib IIC T6 or T4 Gb
Ex nA IIC T6 or T4 Gc
IECEx TUN 04.0015X
5
Intrinsic safety "i" or "n" type of
protection
IEC 60079-0:2011
IEC 60079-11:2011
IEC 60079-15:2010
TZIDC Ex ia IIC or Ex ib IIC
Ambient temperature range
-40 ... 85 °C
T4
-40 ... 40 °C
T6 1)
When using the plug-in module for "Digital Feedback" in Temperature Class T6, the
maximum permissible ambient temperature range is -40 ... 35 °C.
6.2.1
IECEx i
Electrical data for a TZIDC designated as Ex ia IIC or Ex ib IIC With
the intrinsically safe Ex ib IIC / Ex ia IIC types of ignition protection,
only for connection to a certified intrinsically safe circuit.
Electrical data
Signal circuit
(terminal +11 / -12)
U = 20 ... 30 V DC
Special Requirements
• Devices may only be connected to circuits in zone 2 if they are
suitable for operation in zone 2 potentially explosive atmospheres
and for the conditions prevailing at the installation location
(manufacturer's declaration or certificate from an inspection
authority).
• For the "digital feedback with proximity switches" circuit, external
measures must be implemented to prevent the rated voltage from
being exceeded by more than 40 % in the event of transient
disturbances.
• It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the purpose of
carrying out repairs. Note: It is considered very unlikely that a
potentially explosive atmosphere would be present in zone 2 at
the same time that installation or maintenance/repair work was
being carried out.
• Only non-flammable gases may be used for the pneumatic
auxiliary power.
• Only use suitable cable entries which meet the requirements of
IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may
only be operated at an ambient temperature range
from -25 ... 85 °C.
14
10/18-0.22-EN
Contact input
(terminal +81 / -82)
Switch output
(terminal +83 / -84)
Local communication
interface (LKS)
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 W
Ci = 6.6 nF
Li negligibly small
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 W
Ci = 4.2 nF
Li negligibly small
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 500 mW
Ci = 4.2 nF
Li negligibly small
Only for connection to a
programmer outside the potentially
explosive area.
(See Special conditions)
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
The following modules may be operated as an option:
Electrical data
Plug-in module for digital
position feedback
(terminal +51 / -52 or +41 / 42)
Plug-in module for analog
position feedback
(terminal +31 / -32)
Plug-in module for shutdown
contact input
(terminal +51 / -52 or +85 / 86)
6.2.2
1.1.3
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 500 mW
Ci = 3.7 nF
Li negligibly small
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 mW
Ci = 6.6 nF
Li negligibly small
Maximum values:
Ui = 30 V
li = 320 mA
Pi = 1.1 mW
Ci = 3.7 nF
Li negligibly small
10/18-0.22-EN
Special Requirements
• Devices may only be connected to circuits in zone 2 if they are
suitable for operation in zone 2 potentially explosive atmospheres
and for the conditions prevailing at the installation location
(manufacturer's declaration or certificate from an inspection
authority).
• For the "digital feedback with proximity switches" circuit, external
measures must be implemented to prevent the rated voltage from
being exceeded by more than 40 % in the event of transient
disturbances.
• It is only permissible to connect, disconnect, and switch live
circuits during installation or maintenance, or for the purpose of
carrying out repairs. Note: It is considered very unlikely that a
potentially explosive atmosphere would be present in zone 2 at
the same time that installation or maintenance/repair work was
being carried out.
• Only non-flammable gases may be used for the pneumatic
auxiliary power.
• Only use suitable cable entries which meet the requirements of
IEC 60079-15.
• If the SJ2_S1N (NO) proximity switch is used, the positioner may
only be operated in an ambient temperature range
from -25 ... 85 °C.
IECEx n
Electrical data
Signal circuit
(terminal +11 / -12)
Contact input
(terminal +81 / -82)
Switch output
(terminal +83 / -84)
U = 9.7 V DC
I = 4 ... 20 mA, max. 21.5 mA
U = 12 ... 24 V DC; 4 mA
U = 11 V DC
The following modules may be operated as an option:
Electrical data
Plug-in module for digital
position feedback
(terminal +51 / -52 or +41 / 42)
Plug-in module for analog
position feedback
(terminal +31 / -32)
Plug-in module for shutdown
contact input
(Terminal +51 / -52) or
+85 / -86)
U = 5 ... 11 V DC
U = 10 ... 30 V DC
I = 4 ... 20 mA, max. 21.5 mA
U = 20 ... 30 V DC
15
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
6.3
6.3.1
FM/CSA
6.3.2
CSA International
Certificate:
Class 2258 02
Class 2258 04
1052414
PROCESS CONTROL
EQUIPMENT –
For Hazardous Locations
PROCESS CONTROL
EQUIPMENT – Intrinsically
Safe, Entity – For Hazardous
Locations
Class I, Div 2, Groups A, B, C and D;
Class II, Div 2, Groups E, F, and G,
Class III, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
Input rated
30 V DC; max. 4 ... 20 mA
Max output pressure
90 psi
Max. ambient
85 Deg C
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F and G
Class III, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
intrinsically safe with entity parameters of:
Terminals 11 / 12
V max = 30 V
I max = 104 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 81 / 82
V max = 30 V
I max = 110 mA
Ci = 4.2 nF
Li = 0 uH
Terminals 83 / 84
V max = 30 V
I max = 90 mA
Ci = 4.2 nF
Li = 0 uH
Terminals 31 / 32
V max = 30 V
I max = 110 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 41 / 42 and 51 / 52
V max = 30 V
I max = 96 mA
Ci = 3.7 nF
Li = 0 uH
Terminals Limit2 41 / 42 and
V max = 15.5 V
Limit1 51 / 52
I max = 52 mA
Ci = 20 nF
Li = 30 uH
When installed per installation Drawing No 901064
Temperature Code
Temperature Code
Max. Ambient
Max. Ambient
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or
optional features.
• Local communication interface LKS shall not be used in
hazardous location.
• Each pair of conductors of each intrinsic safety circuit
shall be shielded..
16
10/18-0.22-EN
CSA Certification Record
Certificate:
Class 2258 04
1649904 (LR 20312)
PROCESS CONTROL
EQUIPMENT – Intrinsically
Safe, Entity – For Hazardous
Locations
Class I, Div 1, Groups A, B, C and D;
Class II, Div 1, Groups E, F, and G,
Class III, Div 1, Enclosure Type 4X:
Model TZIDC, P/N V18345-x0x2x2xx0x Intelligent Positioner
Input rated
30 V DC; max.4 ... 20 mA
Output pressure
Max. 90 psi
Intrinsically safe with entity parameters of:
Terminals 11 / 12
V max = 30 V
I max = 104 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 81 / 82
V max = 30 V
I max = 110 mA
Ci = 3.7 nF
Li = 0 uH
Terminals 83 / 84
V max = 30 V
I max = 96 mA
Ci = 3.7 nF
Li = 0 uH
Terminals 31 / 32
V max = 30 V
I max = 110 mA
Ci = 6.6 nF
Li = 0 uH
Terminals 41 / 42 and 51 / 52
V max = 30 V
I max = 96 mA
Ci = 3.7 nF
Li = 0 uH
Terminals Limit2 41 / 42 and
V max = 15.5 V
Limit1 51 / 52
I max = 52 mA
Ci = 20 nF
Li = 30 uH
When installed per installation Drawing No 901064
Temperature Code
T4
Max. Ambient
85 Deg C
IMPORTANT (NOTE)
• The "x" in P/N denotes minor mechanical variations or
optional features.
• Local communication interface LKS shall not be used in
hazardous location.
• Each pair of conductors of each intrinsic safety circuit
shall be shielded.
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
6.3.3
10/18-0.22-EN
FM Approvals
TZIDC Positioner, Model V18345-a0b2c2de0f
IS/I,II,III/1/ABCDEFG/T4 Ta = 85 °C – 901064/7/4; Enity;
NI/I/2/ABCD/T4 Ta = 85 °C;
S/II,III/2/FG/T4 Ta =85 °C; Type 4XMax Enity Parameters: Per Control
Drawings
a = Case/mounting – 1, 2, 3, 4 or 9
b = Input/communication port – 1 or 2
c = Output/safe protection – 1, 2, 4 or 5
d = Option modules for analog or digital position feedback – 0, 1, 3
or 5
e = Mechanical kit (proximity swiches) for digital position feedback
(option) – 0, 1 or 3
f = Design (varnish/coding) – 1 or 2
17
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
Change from one to two c ol umns
6.3.4
18
FM Control Document
10/18-0.22-EN
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
10/18-0.22-EN
19
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
20
10/18-0.22-EN
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
10/18-0.22-EN
21
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
7
Electrical connections
Fig. 7: Screw terminals, overview
1 Module for analog position feedback
2 Module for digital feedback or service switch of emergency
shutdown module
3 Module for digital feedback or terminals for emergency
shutdown module
4 Digital position feedback, either proximity switches or 24 V
microswitches
Fig. 8: Pin configuration
A Basic model
B Options
22
10/18-0.22-EN
5
6
7
8
9
Digital position feedback, either proximity switches or 24 V
microswitches
Digital output DO
Digital input
Signal 4 ... 20 mA
Grounding screw
1
2
3
4
5
6
7
8
Analog input
Digital input
Digital output DO
Digital feedback
Analog feedback
Proximity switches
Microswitches
Emergency shutdown module
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
7.1
10/18-0.22-EN
TZIDC with remote sensor
In the case of the "TZIDC with remote sensor" design, the components are supplied in two housings, which together form one harmonized unit.
Housing 1 (control unit) contains the electronics and pneumatics along with the following options (where applicable):
• Analog position feedback
• Digital position feedback
• Shutdown module
Housing 2 (remote sensor) contains the position sensor and is suitable for mounting on linear and part-turn actuators.
The following options can be installed if required:
• Optical position indicator
• Mechanical feedback contacts (proximity switch or microswitch design)
The two housings can be or are connected to a shielded 3-wire cable. The maximum cable length is 10 m.
For Housing 1 (control unit) an attachment kit is available for pipe and wall mounting (see Accessories).
Fig. 9:
1
2
3
4
TZIDC with remote position sensor
Housing 1 (control unit)
Setpoint signal
Connecting cable
Housing 2 (remote sensor)
5
6
7
8
Pneumatic output 2
Pneumatic output 1
Air supply
Pneumatic actuator
23
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
7.2
10/18-0.22-EN
TZIDC for external remote sensor
In the case of the TZIDC design for remote sensor, the positioner is supplied without position detection.
The housing (control unit) contains the electronics and pneumatics along with the following options (where applicable):
• Analog position feedback
• Digital position feedback
• Shutdown module
The TZIDC designed for the remote sensors can be connected to any position sensor (4 ... 30 kΩ, with open circuit detection 4 ... 18 kΩ). The
maximum length of the shielded 3-wire cable is 10 m.
Fig. 10:
1
2
3
4
24
TZIDC for remote sensors
Housing (control unit)
Setpoint signal
Connecting cable
Remote sensor
5
6
7
8
Pneumatic output 2
Pneumatic output 1
Air supply
Pneumatic drive
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
8
10/18-0.22-EN
Dimensions
All dimensions in mm (inch)
Fig. 11: Top view
Fig. 12: Front and rear views
A Tap hole M8 (10 mm low)
B Tap hole M6 (8 mm low)
C
D
Tap hole M5 x 0.5 (air vents for direct mount)
Sensor shaft (larger than scale)
25
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
10/18-0.22-EN
Fig. 13: side view (from left to right)
A Pneumatic connections, NPT 1/4"-18 or G1/4"
Mounting to linear actuators to DIN / IEC 534
Fig. 14: Mounting drawings
26
Mounting to rotary actuators to VDI / VDE 3845
*) Dimensions A and B are dependent on the rotary actuator
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
10/18-0.22-EN
Fig. 15: Positioner TZIDC with pressure gauge block and filter regulator
27
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
Bes tell ang aben
9
10/18-0.22-EN
Ordering information
Main Code
Variant
1-6
7
TZIDC Electro-Pneumatic Positioner, intelligent, configurable, with
V18345 X
indicator and operator panel
Case / Mounting
1
Case made of aluminium, varnished, for mounting to linear actuators
acc. DIN / IEC 534 / NAMUR or to rotary actuators acc. VDI / VDE 3845
Case made of aluminium, varnished, with mechanical position indicator,
2
for mounting to linear actuators acc. DIN / IEC 534 / NAMUR or to rotary
actuators acc. VDI / VDE 3845
Case made of aluminium, varnished, for integral mounting to control
3
valves (see dimensional drawing)
Case made of aluminium, varnished, with mechanical position indicator,
4
for integral mounting to control valves (see dimensional drawing)
Case made of aluminium, varnished, for mounting to rotary actuators
5
acc. VDI / VDE 3845 with extended rotation angle up to 270°
Case made of aluminium, varnished, with mechanical position indicator,
6
for mounting to rotary actuators acc. VDI / VDE 3845 with extended
rotation angle up to 270°
SRemote sensor control unit
7
1)
Input / Communication Port
Input 4 ... 20 mA, two-wire, with connector plug for LKS adapter
Input 4 ... 20 mA, two-wire, with connector plug for LKS adapter and FSK module for
HART communication
Explosion Protection
Without
ATEX II 2 G Ex ib IIC T6 resp. T4 Gb
FM / CSA
ATEX II 3 G Ex nA IIC T6 resp. T4 Gc
IECEx Ex ib IIC T6 resp. T4 Gb
IECEx Ex nA IIC T6 resp. T4 Gc
ATEX II 2 G Ex ia IIC T6 resp. T4 Gb
ATEX II 2 D Ex ia IIIC T51°C resp. 81°C Db
GOST Russia - Ex II 2 G EEx ib II C T6
GOST Russia - 0 Ex iA IIC T6
GOST Russia - Ex iaD 21 T5
IECEx ia IIC T6 resp. T4 Gb
Output / Safe Position (in case of an electrical power failure)
Single acting, fail safe
Single acting, fail freeze
Double acting, fail safe
Double acting, fail freeze
Connections
Cable: Thread 1/2-14 NPT, air pipe: Thread 1/4-18 NPT
Cable: Thread M20 x 1.5, air pipe: Thread 1/4-18 NPT
Cable: Thread M20 x 1.5, air pipe: Thread G 1/4
Cable: Thread G 1/2, air pipe: Thread Rc 1/4
Continued on next page
1) With standard characteristic curve, if delivered without remote sensor
2) Not for integral mounting
28
Add. Code
8
9
10
11
12
13
14
15
16
XX
X
X
X
X
X
X
X
X
X
XX
0
0
0
0
0
0
0
1
2
0
1
2
4
5
6
7
8
B
E
F
K
2)
2)
1
2
4
5
2
5
6
7
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
10/18-0.22-EN
Main Code.
Variant
1-6
7
8
9
10
11
TZIDC Electro-Pneumatic Positioner, intelligent, configurable, with
V18345 X X X X X
indicator and operator panel
Option Modules for Analog or Digital Position Feedback
Without
Plug-in module for analog position feedback, signal range 4 ... 20 mA, two-wire
Plug-in module for digital position feedback
Plug-in module for shutdown function
Plug-in module for analog position feedback, signal range 4 ... 20 mA, two-wire, and
digital position feedback
Plug-in module for analog position feedback, signal range 4 ... 20 mA, two-wire, and
shutdown module
Plug-in module for analog position feedback, 48 V DC
Optional Mechanical Kit for Digital Position Feedback
Without
Mechanical kit for digital position feedback with proximity switches SJ2-SN (NC or logical 1)
Mechanical kit for digital position feedback with proximity switches SJ2-S1N (NO or logical 0)
Mechanical kit for digital position feedback with 24 V AC / DC microswitches (change-over contacts)
Add. Code
12
13
14
15
16
XX
X
X
X
X
X
XX
0
5) 1
6) 3
7) 5
0
0
0
0
0
1
3
3) 4
5
3) 6
4) 7
Design (Varnish / Coding)
Standard
Special version for Chemical Industries
Sprache der Dokumentation
German
Italian
Spanish
French
English
Swedish
Finnish
Polish
Portuguese
Russian
Czech
Dutch
Danish
Greek
Latvian
Hungarian
Estonian
Bulgarian
Romanian
Slovak
Lithuanian
Slovenian
SIL2 - Declaration of Conformity
SIL2 - Declaration of Conformity
Certificate of Compliance
Certificate of compliance with the order acc. EN 10204-2.1 (DIN 50049-2.1) with item description
Test report 2.2 acc. EN 10204 (DIN 50049-2.2)
Continued on next page
3)
4)
5)
6)
7)
8)
9)
1
8) E
M1
M2
M3
M4
M5
M7
M8
M9
MA
MB
MC
MD
MF
MG
ML
MM
MO
MP
MR
MS
MU
MV
9)
CS2
CF2
CF3
Not for FM / CSA Version
Not for explosion protected version
Only for model with mechanical position indicator, no IECEx
Only for model with mechanical position indicator and only for ambient temperature range -25 ... 85 °C, no IECEx
Not for explosion protected version and only for model with mechanical position indicator
Details on request
With single acting, fail safe pneumatic only
29
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
10/18-0.22-EN
Main Code.
Variant
TZIDC Electro-Pneumatic Positioner, intelligent, configurable, with
indicator and operator panel
Inspection Certificate
Inspection certificate 3.1 acc. EN 10204
Device Identification Label
Stainless steel 11.5 x 60 mm (0.45 x 2.36 in.)
Sticker 11 x 25 mm (0.43 x 0.98 in.)
Special Option Cable Gland
With cable gland
Remote Sensor
Basic unit
Basic unit with position indicator
Remote Sensor Temperature Range
Extended ambient temperature range -40 ... 100 °C (-40 ... 212 °F)
Remote Sensor Vibration Resistance
Advanced vibration range 2 g @ 300 Hz
Remote Sensor Protection Class
Protection class IP 67
Remote Sensor Cable
5 m cable enclosed
10 m cable enclosed
10) Only with remote sensor control unit
30
Add. Code
1-6
7
8
9
10
11
12
13
14
15
16
XX
V18345
X
X
X
X
X
X
X
X
X
X
XX
CBA
MK1
MK3
ZG1
10)
10)
RS
RD
10)
RT
RV
10)
RP
10)
10)
R5
R6
Electro-Pneumatic Positioner TZIDC
for 4 ... 20 mA two-wire technology
9.1
10/18-0.22-EN
Accessories
Accessories
Mounting bracket
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 80/20 mm
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 80/30 mm
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 130/30 mm
EDP300 / TZIDC Mounting bracket for rotary actuators (mounting to VDI / VDE 3845), dimension A/B = 130/50 mm
Lever
EDP300 / TZIDC Lever 30 mm
EDP300 / TZIDC Lever 100 mm
Adapter
EDP300 / TZIDC Adapter (shaft coupler) for rotary actuators (mounting to VDI / VDE 3845)
EDP300 / TZIDC Form - locking shaft adapter
Pressure gauge block
TZIDC Pressure gauge block, 0.6 MPa, single acting, G 1/4 connection
TTZIDC Pressure gauge block, 0.6 MPa, single acting, Rc 1/4 connection
TZIDC Pressure gauge block, 0.6 MPa, single acting, NPT 1/4 connection
TZIDC Pressure gauge block, 0.6 MPa, double acting, G 1/4 connection
TZIDC Pressure gauge block, 0.6 MPa, double acting, Rc 1/4 connection
TZIDC Pressure gauge block, 0.6 MPa, double acting, NPT 1/4 connection
Filter regulator
TZIDC Filter regulator, brass, connections thread G 1/4, incl. material for mounting to pressure gauge block
TTZIDC Filter regulator, brass, connections thread 1/4-18 NPT, incl. material for mounting to pressure gauge block
Attachment kit
EDP300 / TZIDC Attachment kit for linear actuators, stroke 10 ... 35 mm
EDP300 / TZIDC Attachment kit for linear actuators, stroke 20 ... 100 mm
EDP300 / TZIDC Attachment for remote sensor control unit (for wall or pipe mounting)
EDP300 / TZIDC Attachment kit for Fisher 1051-30, 1052-30
EDP300 / TZIDC Attachment kit for Fisher 1061 size 130
EDP300 / TZIDC Attachment kit for Fisher 471
EDP300 / TZIDC Attachment kit for Fisher 657 / 667 Size 10 ... 90 mm
EDP300 / TZIDC Attachment kit for Fisher Gulde 32/34
EDP300 / TZIDC Attachment kit for Gulde DK
EDP300 / TZIDC Attachment kit for Keystone 79U/E-002(S) ... 79U/E-181(S)
EDP300 / TZIDC Attachment kit for Masoneilan CAMFLEX II, VARIMAX, MINITORK II
EDP300 / TZIDC Attachment kit for Masoneilan VariPak 28000 series
EDP300 / TZIDC Attachment kit for MaxFlo MaxFlo
EDP300 / TZIDC Attachment kit for NAF 791290
EDP300 / TZIDC Attachment kit for NAMUR stroke 100 ... 170 mm
EDP300 / TZIDC Attachment kit for NELES BC6-20, B1C6-20, BJ8-20, B1J8-20
EDP300 / TZIDC Attachment kit for Valves Nuovo Pignone, lever for linear stroke, length 150 ... 250 mm
EDP300 / TZIDC Attachment kit for Samson 241, 271, 3271
EDP300 / TZIDC Attachment kit for Samson 3277
EDP300 / TZIDC Attachment kit for Schubert&Salzer GS 8020 / 8021 / 8023
EDP300 / TZIDC Attachment kit for SED SED stroke 100 mm
EDP300 / TZIDC Mounting Kit Uhde Type 4 Stroke 400 mm cropped
Order number
319603
319604
319605
319606
7959151
7959152
7959110
7959371
7959364
7959358
7959360
7959365
7959359
7959361
7959119
7959120
7959125
7959126
7959381
7959214
7959206
7959195
7959177
7959344
7959161
7959147
7959144
7959163
7959140
7959207
7959339
7959146
7959210
7959145
7959136
7959200
7959141
7959500
n
31
ABB Limited
Process Automation
Salterbeck Trading Estate
Workington, Cumbria
CA14 5DS
UK
Tel:
+44 (0)1946 830 611
Fax:
+44 (0)1946 832 661
ABB Inc.
Process Automation
125 E. County Line Road
Warminster, PA 18974
USA
Tel:
+1 215 674 6000
Fax:
+1 215 674 7183
Note
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB does not accept any
responsibility whatsoever for potential errors or
possible lack of information in this document.
We reserve all rights in this document and in the
subject matter and illustrations contained therein.
Any reproduction, disclosure to third parties or
utilization of its contents - in whole or in parts – is
forbidden without prior written consent of ABB.
Copyright© 2013 ABB
All rights reserved
3KXE341001R1001
ABB Automation Products GmbH
Process Automation
Schillerstr. 72
32425 Minden
Germany
Tel:
+49 551 905-534
Fax:
+49 551 905-555
Sales
www.abb.com
Service
Software
10/18-0.22-EN Rev. I 12.2013
Contact us
Download PDF