no minimum order required - PEI

150 WATTS
DC4-150 SERIES
Features
RoHS Compliant
Advanced SMT Design
36-72 VDC Input Range
4242 VDC Reinforced Insulation
2 Year Warranty
One to Four Outputs
Fits 1U Applications
Compact 3.8" x 6.0" x 1.3" Size
Size and Pin compatible with REL-150 Series
EN 60950-1 ITE Certification
EN 60601-1 Medical Certification
Optional Chassis and Cover
NO MINIMUM ORDER REQUIRED
OUTPUT SPECIFICATIONS
Total Output
Power at 50oC
Output Voltage
Centering
(50% load)
100W
150W
Output
Output
Output
Output
Output Voltage Output
Adjust Range
Load
Output
Regulation
Output
1:
2:
3:
4:
1:
1:
2:
(2001
Model)
Output 3:
Output 4:
INPUT SPECIFICATIONS
Input Voltage Range 36-72 VDC
Input Under-Voltage
Lockout
Turn-On Voltage
Turn-Off Voltage
Input Overvoltage
Shutdown
Maximum Input
Current
Reflected Ripple
Current
Efficiency
29.0-35.0 VDC
28.0-34.0 VDC
77.0-85.0 VDC
6A
5%
82% Typ., Full Power, 48VDC,
varies by model
0.5%
change)
(4001-5
Models)
Source
Regulation
Cross
Regulation
Output Noise
Convection Cooled
300 LFM Forced Air
+/-0.5%
+/-5.0%
+/-5.0%
+/-5.0%
95 - 105%
Outputs
1-4:
Outputs
2-4:
Outputs
1-4:
None
5.0%
change)
(10-100%load
(10-100%load
8.0%
(20-100%loadchange)
6.0%
(20-100%loadchange)
5.0%
(10-100%loadchange)
5.0%
(10-100%loadchange)
0.5%
5.0%
1.0%
Turn on
Overshoot
Transient
Outputs 1 - 4
Response
Voltage
5.0%
Deviation
Recovery Time 500MicroS
Load Change 50% to 100%
Output 1: 110% to 150%
Output
Overvoltage
Protection
Output
110-160% rated Pout, cycle on/off, auto
Overpower
recovery
Protection
Start Up Time 5 Seconds
ENVIRONMENTAL SPECIFICATIONS
Ambient Operating
0 o C to + 70o C
Derating:
See
Power Rating Chart
Temperature Range
Ambient Storage Temp.
- 40o C to + 85o C
Range
Temperature Coefficient
Outputs 1 - 4: 0.02% /oC
SAFETY SPECIFICATIONS
GENERAL SPECIFICATIONS
Underwriters UL 60950-1 First Edition UL
Laboratories 60601-1 First Edition
File
E137708/
E140259
Dielectric Strength
Reinforced Insulation 4242 VDC, Primary to
Secondary, 1 Sec.
Basic Insulation 2121 VDC, Primary to
Ground, 1 Sec.
Operational Insulation
707 VDC, Secondary to
CB Report per IEC
Ground, 1 Sec.
60950-1(2001)
First
Power Good Signal
Logic high with input voltage
Edition
All National
above Vin min.
Deviations CB Report per IEC
Remote
Sense
250mV compensation of
60601-1(1988) Second Edition
output
cable losses.
A1, A2
Mean Time Between
100,000 Hours min.,
Failures
MIL-HDBK-217F, 25oC, GB
UL
CAN/CSA-C22.2 No.
Weight
1.60 Lbs. Chassis and Cover
Recognition 60950-1-03
0.90 Lbs. Open Frame
Mark For
CAN/CSA-C22.2 No.
Maximum Output Power vs. Ambient
Canada File 601-1-M90
with
Temperature
updates
1
and
2
E137708/
E140259
EN 60950-1:2001
EN
60601-1/A2:1995
Notes
Consult factory for alternate output configuration.
Consult factory for positive, negative or floating
outputs.
Refer to Application Information for complete
output power ratings.
All specifications are maximum at 25C unless
otherwise stated and are subjected to change
without notice.
Specify optional chassis and cover, power good or
reverse input protection when ordering.
MODEL LISTING
DC4-150-4001 +3.3V/15A (1)
+5V/8A
DC4-150-4002 +5V/15A(1)
+3.3V/8A
DC4-150-4003 +5V/15A(1)
+3.3V/8A
DC4-150-4004 +5V/15A (1)
-5V/8A
DC4-150-4005 +5V/15A(1)
-5V/8A
DC4-150-4006 +5V/15A (1)
+24V/3A
DC4-150-4007 +5V/15A (1)
DC4-150-3001 +5V/15A (1)
+24V/3A
+12V/4A
DC4-150-3002 +5V/15A (1)
DC4-150-2001 +3.3V/15A (1)
+15V/3A
+5V/8A
DC4-150-2002
DC4-150-2003
DC4-150-2004
DC4-150-2005
DC4-150-1001
+12V/5A
+24V/3A
-12V/5A
-15V/5A
+5V/15A (1)
+5V/15A(1)
+12V/7.5A
+15V/5A
2.5V/30A(2)
DC4-150-1002 3.3V/30A(2)
DC4-150-1003 5V/30A(2)
DC4-150-1004
DC4-150-1005
DC4-150-1006
DC4-150-1007
DC4-150-1008
12V/12.5A
15V/10.0A
24V/6.3A
28V/5.4A
48V/3.1A
+12V/2A
+12V/2A
+15V/2A
+12V/2A
+15V/2A
+12V/2A
-12V/2A
-12V/2A
-15V/2A
-12V/2A
-15V/2A
-12V/2A
+15V/2A
-15V/2A
-12V/3A
-15V/2A
DC4-150 SERIES MECHANICAL SPECIFICATIONS
APPLICATIONS INFORMATION
1. Rated 12A with convection cooling.
2. Rated 20A maximum with convection cooling.
3. Total power must not exceed 100 watts with
convection cooling on open frame models.
4. Total power must not exceed 150 watts with
13. This product is intended for use as a
professionally installed component within
information technology and medical
equipment.
14. Remote sense terminals may be used to
compensate for cable losses up to 250mV. The
use of a twisted pair is recommended as well
as a decoupling capacitor (0.1 0 10MicroF) and
a capacitor of 100MicroF/amp connected
across the load.
15. This power supply has been safety approved
and final tested using a DC
dielectric strength test. Please consult factory
before performing AC dielectric strength test.
16. Maximum screw penetration into bottom
chassis mounting holes is .100 inches.
17. Maximum screw penetration into side chassis
mounting holes is .250 inches.
18. To meet emissions specifications, all four
mounting hole ground pads must
be electrically connected to a common metal
chassis. Chassis/cover option recommended.
19. Total current from Outputs 3 & 4 must not
exceed 3 amps with convection cooling.
20. Total current from Outputs 1 & 2 must not
exceed 15 amps with convection cooling.
21. Semiconductor case temperatures must not
exceed 110C.
300LFM forced air cooling on open frame
models.
5. Total power must not exceed 85 watts with
convection cooling and chassis/cover option.
6. Total power must not exceed 150 watts with
300LFM forced air cooling and chassis/cover
option.
7. Each output can deliver its rated current but
total output power must not exceed maximum
power as determined by the cooling method
state above.
8. Sufficient area must be provided around
convection cooled power supplies to allow
natural movement of air develop.
9. 300 linear feet per minute of airflow must be
maintained one inch above any point of the
heatsink in the direction shown when forced air
cooling is required.
10. A minimum load of 10% is required on output
one to insure proper regulation of remaining
outputs.
11. Peak to peak output ripple and noise is
measured directly at the output
terminals of the power supply, without the use
CONNECTOR SPECIFICATIONS
of the probe ground lead or retractable tip, 20
.156 friction lock header
MHz bandwidth.
mates with Molex
12. This product was type tested and safety
09-50-3061 or equivalent
certificated using the the dielectric strength test P1 DC Input
crimp terminal housing with
voltages listed in Table V of UL 60601-1. In
Molex 2478 or equivalent
consideration of clause 20.4g, care must be
crimp terminal.
taken to insure the voltage applied to a
6-32 screw down terminal
reinforced insulation does not over stress basic P2 DC Output(Single) mates with #6 ring tongue
insulation. Secondary to ground capacitors may
terminal. (10 in-lb max)
need to be removed prior to performing a
.156 friction lock header
dielectric strength type test on the end product.
mates with Molex
It is highly recommended that the DC test
09-50-3141 or equivalent
P2 DC Output(Multiple)
voltages listed in DVB.1. Annex DVB are not
crimp terminal housing with
exceeded during a production-line dielectric
Molex 2478 or equivalent
strength test of the assembled end product.
crimp terminal.
Please consult factory for further information.
.187 quick disconnect
G Ground
terminal.
.100 breakaway header
mates with Molex
50-57-9006 or equivalent
P3 P.G./Sense(Single)
crimp terminal housing with
Molex type 71851 or
equivalent crimp terminal.
.100 breakaway header
mates with Molex
P.G./Sense(Multiple) 22-55-2061 or equivalent
P3
crimp terminal housing with
Molex type 70058 or
equivalent crimp terminal.
RECOMMENDED AIR FLOW DIRECTION
1.Optimum 2.Good 3.Fair
Download PDF