GUTOR-Technical Data Sheet PXP-WEB

Technical Data Sheet
PXP AC UPS System
> PXP 1000 5-160 kVA single phase
> PXP 3000 5-160 kVA three phase
Technical data PXP
UPS input
Rectifier input voltage Rectifier input voltage tolerance Rectifier input frequency Rectifier current total harmonic distortion Rectifier input power factor Inrush current
Bypass input voltagePXP 1000 PXP 3000 Bypass input frequency 3x380 / 400 / 415 V
-10 /+15 %
41 – 70 Hz (auto detection)
<5 % @ 100 % load
typical 0.96 – 0.98
≤8 – 10IN
1x220 / 230 / 240 V +/-10 %
3x380 / 400 / 415 V +/-10 %
50 / 60 Hz + / -8 %
Battery circuit
Battery voltage Battery operating range Float voltage at -10 % line power Boost voltage at nominal line power Boost charge time Charging current limitation 400 VDC
335 – 540 VDC
programmable within battery operating range
programmable within battery operating range
1– 24h programmable
programmable
UPS output
Nominal UPS ratings at 0.8 lagging PF 5, 10, 15, 20, 30, 40, 50, 60, 80, 100, 120,
140, 160 kVA
Output voltage
PXP 1000
1x220 / 230 / 240 V (other voltages optional)
PXP 3000 3x380 / 400 / 415 V (other voltages optional)
Voltage tolerance:
static within 0 –100 % load +/-1 %
dynamic for 0 –100 % or 100 – 0 % +/- 5 %
regulation time to +/-1 % <60 ms
regulation time to +/- 3 % <20 ms
Overload:
Inverter 230 % / 60 ms, 150 % / 1 min, 125 % / 10 min
Bypass 1000 % / 100 ms, 150 % / 1 min, 125 % / 10 min
Frequency 50 / 60 Hz
Frequency stability, free running <0.01 %
Synchronization range 0.5 / 1 / 2 / 4 / 6 / 8 % programmable
Slew rate single phase systems 0.25 / 0.5 / 1 Hz/s programmable
Slew rate three phase systems 0.25 / 0.5 / 1 / 2 / 4 / 6 Hz / s programmable
Wave form sinusoidal
Admissible output crest factor 3
Distortion factor:
Linear load <2 %
Non-linear load according to IEC 62040-3 <5 %
Allowable power factor 0.8 lag – 0.8 lead
General data
Ambient temperature range for storage from -30 to +80 °C
Ambient temperature range for operation from -10 to +40 °C (100 % nominal load)
Altitude above sea level <1000 m without load de-rating
Allowable air humidity <95 % (non condensing)
Noise level standard n+1 fan system 55 – 65 dBA depending on type
Degree of protection IP20 according to IEC 60529
Paint
pebble gray, RAL 7032 structured
Standards:
Safety IEC / EN 62040-1
EMC IEC / EN 62040-2
Performance IEC / EN 62040-3
UPS classification VFI-SS-111 acc. to IEC 62040-3
Conformity CE-Label
Efficiency up to 94 % depending on type
Cooling forced ventilation (two speed) with n+1
­redundant monitored fans
Data subject to changes
Specification PXP
Typical single-line drawing
N*
N*
Battery asymmetry supervision
Diode for reverse polarity protection
Up to 3 sensors for temperature dependent battery charging voltage (recommended for Valve Regulated Lead Acid (VRLA) battery)
Optional features – UPS output
Standard configuration
Static bypass switch EN
Rectifier input switch
Fixed charging voltage I-V characteristic
PFC rectifier (supplies 100 % AC load @ 0.8 PF and
charges ­battery with 20 % of nominal power)
Rectifier line power backfeed protection
Battery capacity test (full discharge with current load)
Human-machine interface with additional LEDs for direct
alarm display
Ground terminal
Bottom cable entry
N+1 monitored two-speed fans
Digital input
Emergency Power Off (EPO)
2 configurable inputs
Digital (NO / NC relay)
Common alarm
Battery operation
Static bypass switch On
Optional features – UPS input
Other input voltages:
3x190, 208, 220, 230, 440, 460, 480, 500, 525, 600, 660, 690 V
Rectifier input MCCB
Without isolation transformer on rectifier line power � T001
Without isolation transformer on bypass line power � T501
Bypass stabilizer with isolation transformer
Bypass mains backfeed protection
Optional features – Battery circuit
Battery fuse in UPS
Battery fuse box
Battery MCCB in UPS
Battery MCCB box (for non-hazardous areas or hazardous areas
zone 1/2 Ex de IIC)
Battery temperature alarm
Battery monitor (programmable battery data)
Other output voltages:
1x110, 115, 120, 127, 254, 265, 277 V
3x190, 200, 208, 220, 230, 440, 460, 480, 500, 525,
600, 660, 690V
Without isolation transformer on inverter output � T002
Analog meters 72x72 mm or 96x96 mm (directly beside of HMI):
Rectifier mains (voltage, current, frequency)
Bypass mains (voltage, current, frequency)
Battery (voltage, current)
Inverter output (voltage, current, frequency, PF, kVA, kW)
Others on request built in distribution
Digital outputs (NO / NC relay output):
Operational indications
Battery not connected
Normal operation
Static bypass operation
Manual bypass operation
Boost charge
Float charge
Inverter asynchronous
Fail-safe alarms:
Rectifier line power fault
Bypass line power fault
Battery discharged
Fan failure
Rectifier fault
Inverter fault
Static bypass switch fault
Over temperature
Battery ground fault
More individual operation status indications or fail-safe
alarms on request (maximum 19 relays in total)
Optional features – Communication
Network management card (NMC) for WEB browser based
­monitoring
MODBUS RS-485, IEC 61850
Other interfaces are available on request
Optional features – Other alarms
DC ground fault alarm
AC ground fault alarm
Optional features – General
Ambient temperature maximum +55°C
Allowable altitude up to 4000 m above sea level
Air filters at air inlet
Other colors
Space heaters
Panel lighting
Top cable entry
Protection up to IP52
Cabinet height 2300 mm (standard 1900 mm)
Additional options are available on request
Human-machine interface (front panel)
The front panel includes a comprehensive and flexible human-machine interface. It is divided into three sections:
Control and display consists of an LC display,
­indication LEDs for operating modes, and
push buttons to navigate through the display
menus and control the UPS. The user can
access measurement data and s­ ystem information
via display ­menus, including the event and
alarm logs.
Mimic indicates the current operational status
of the system and its components. It clearly shows
the power path currently supplying the load and
the availability of the other supplies.
Alarm indication for the system alarms, as well
as for external signals which can be flexibly assigned
to LEDs for visualization.
Settings accessible via display menu
Auto start
Auto boost charge
Set date / time
Charge mode
Bypass operation
Battery capacity test
Battery monitor test (optional)
Display settings
Menu language
Measurements accessible via display menu
Offices
GUTOR Electronic LLC
Brazil > Canada > China > Germany > India
Hardstrasse 72 – 74
Japan > Malaysia > Mexico > Russia > Saudi Arabia
5430 Wettingen
United Arab Emirates > USA
Switzerland
P +41 (0)56 437 34 34
F +41 (0)56 437 34 44
gutor.info@schneider-electric.com
www.gutor.com
Q410.104 Rev. 5
AC rectifier line power input voltage, current and frequency
AC bypass line power input voltage, current and frequency (optional)
AC output voltage, current and frequency
Load in kVA, kW and % of nominal rating
Battery voltage and current
Battery capacity % and expected runtime
Total system status in parallel / redundant operation
3 temperature measurements (with optional sensors)
Runtime and switchover statistics
Maximum and minimum voltages and currents
Time-stamped event log (operation mode changes and alarms)
Download PDF