ZIP-USB-MP interface

Manual

Level converter USB/MP

Interface between USB and MPBus
ZIP-USB-MP
Content
Technical Data
Safety notes
Product features
Local connection on service socket
Local Connection on clamps
Connection MP-Bus
Connection UK24LON/ UK24EIB
Connection UK24MOD/ UK24BAC
www.belimo.com
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
2
2
2
4
4
5
6
7
1/8
ZIP-USB-MP
Manual
Technical Data
Ambient temperature
0 … +50° C, non-condensing
Non-operating temperature
-40 … +80° C
EMC
CE according to 2004/108/EG
Driver
Current version on Belimo website
Weight
160 g (with USB cable)
Safety notes
Only for connection to PC USB-Ports and Belimo 24V actuators (supplied with SELV
or US class 2 voltage) only
Product features
The ZIP-USB-MP is a potential-free interface between the USB port on a PC and the
BELIMO MP-Bus. It is used to connect the Belimo PC-Tool either to the MP-Bus or
directly to a parameterisable MFT actuator.
Power supply
Driver
The ZIP-USB-MP is supplied with voltage by the USB port.
The required driver is installed with the PC-Tool MFT-P.
If the driver has not been installed, this can be downloaded from the Belimo website
(Download section).
After installing the driver, the ZIP-USB-MP is shown as a virtual COM port on the PC.
Master mode – Monitor mode
Operating as MP-Master
– To parameterize actuators via the MP-Bus
– To select set points for simulating actuators via the MP-Bus
– To link sensors connected to the MP actuators
– To record graphic trends
In Master mode, an 18V carrier signal for the MP-Bus communication will be given out
of the ZIP-USB-MP. At this application no other MP master should be connected to the
MP-Bus (Bus collision).
www.belimo.com
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
2/8
ZIP-USB-MP
Manual
Product features
Master mode – Monitor mode
Operating as MP-Monitor
– To test MP communication with the MP-Monitor Tool (module of PC-Tool V3.x)
In MP-Monitor mode the carrier signal of the ZIP-USB-MP signal is switched off.
The Level converter behaves passively and listen is just listening on the MP-Bus.
Connection
USB
MP-Bus
The Connection happens via the USB 2.0 interface.
USB type B plug, connecting cable (1 m) with A to B plug enclosed


Wiring
1x 3-pol Weidmüller socket
1 x RJ12 socket
Weidmüller 3 Pin
RJ12 Socket
Pin1: MP-Bus
Pin 1: not connected
Pin 2: Enable
Pin 2: GND
Pin 3: Ground
Pin 3: not connected
Pin 4: MP
Pin 5: Enable
Pin 6: not connected
LED display
Enable: USB-ZIP-MP Master mode active
Data: Flashing at MP-communication
Initialized: Device is initialized from the PC (Windows)
3/8
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
www.belimo.com
ZIP-USB-MP
Manual
Local connection on service socket
Auto ● MOMA
~ T
Belimo
PC-Tool
RJ12
_
+
AC 24 V
DC 24 V
USB 2.0
ZK1-GEN
1
2
3
5
...
Local Connection on clamps
~ T
_
Belimo
PC-Tool
Auto ● MOMA
RJ11
+
AC 24 V
DC 24 V
2
5
ZK2-GEN MP
USB 2.0
GND
white/weiss = GND
blue/blau = not connected/nicht angeschlossen
green/grün = MP
1
~ T
_ +
U5/MP
Antrieb / Actuator
www.belimo.com
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
4/8
ZIP-USB-MP
Manual
Connection MP-Bus
Master mode
MP-Master
DDC Controller
UK...Gateway
Belimo
PC-Tool
Auto ● MOMA
RJ11
GND 24 V MP
ZK2-GEN
USB 2.0
Interupt connection/
Verbindung unterbrechen
GND
white/weiss = GND
blue/blau = not connected/nicht angeschlossen
green/grün = MP
MP
MP-Slave
Monitor mode
MP-Master
DDC Controller
UK...Gateway
Belimo
PC-Tool
Auto ● MOMA
RJ11
ZK2-GEN
GND 24 V MP
USB 2.0
GND
white/weiss = GND
blue/blau = not connected/nicht angeschlossen
green/grün = MP
MP
MP-Slave
Note: If working with an older
version of the ZIP-USB-MP, the
MO/MA switch has to get set
manually to MA (Master)
resp. MO (Monitor) mode.
5/8
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
www.belimo.com
ZIP-USB-MP
Manual
Connection UK24LON/ UK24EIB
Master /Monitor mode
By connecting the ZIP-USB-MP an enable signal will be sent to the gateway.
Thereby the gateway stops working in MP-Master mode.
UK24LON/EIB
MFT-H
USB 2.0
RJ11
ZK4-GEN
Note: If working with an older
version of the ZIP-USB-MP, the
MO/MA switch has to get set
manually to MA (Master)
resp. MO (Monitor) mode.
www.belimo.com
Power
0V 24V n.c.
MP-Com.
0V 24V Y U/MP
AC 24 V
DC 24 V
~T
Belimo
PC-Tool
Auto ● MOMA
LonTalk
a b
_
+
MP-Slave
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
6/8
ZIP-USB-MP
Manual
Connection UK24MOD/ UK24BAC
Master / Monitor mode
By connecting the ZIP-USB-MP an enable signal will be sent to the gateway.
Thereby the gateway stops working in MP-Master mode.
MP-Master
UK24MOD / BAC
Belimo
PC-Tool
Note: If working with an older
version of the ZIP-USB-MP, the
MO/MA switch has to get set
manually to MA (Master)
resp. MO (Monitor) mode.
7/8
Auto ● MOMA
ZK6-GEN
USB 2.0
MP
24 V
GND
MP-Slave
MP-Slave
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
MP-Slave
www.belimo.com
ZIP-USB-MP
www.belimo.com
Manual
T9-ZIP-USB-MP • en • v2.0 • 09.2013 • Subject to changes
8/8