PFL40-1500/2000 Portable Cable Fault

PFL40-1500/2000 Portable Cable Fault
PFL40 SERIES
Portable Cable Fault Location and High Voltage Test Solutions
PFL40-1500/2000
Portable Cable Fault Location
and High Voltage Test Solutions
DESCRIPTION
The prime objective of any cable fault location system is to
provide quick, effective, accurate and safe fault location,
thereby reducing system outages and “customer minutes
lost.”
The “new” family of compact Megger cable fault locating
systems is designed to meet this criterion. These new
systems are seen as a valuable extension to our existing
range of CFL instruments and capabilities.
The standard system comes as a mobile compact system
that can be further customised by the customer to meet
local requirements. All systems offer the facility to
undertake cable testing; cable and fault diagnosis;
prelocation of cable faults; fault conditioning; pinpoint
location using acoustic methods.
■
Compact, portable fault locating systems
■
DC testing to 40 kV
■
Proof/burn up to 34 kV
■
8/16/34 kV, 1500 Joules surge output
■ 2000 Joules surge output optional
■ 4-kV range optional
■
A.R.M. (Arc Reflection Method)
■
Impulse current (current impulse)
■
Voltage decay (optional)
■
Integrated TDR
DC Testing (0-40 kV DC)
Used to prove the integrity of and to identify and confirm
fault conditions in cable networks with a test voltage up to
40 kV and a current of 25 mA. The variable output voltage
can also be used to test sheaths requiring 5 or 10-kV test
voltages. The operator selectable over-current trip levels
provide protection to the system under test in the event of
the cable under test breaking down.
Fault Pre-location
After identifying the type of fault, pre-location of the fault
position can be determined using the following methods:
■
In TDR mode, a real time trace and a stored trace can
be viewed simultaneously on the colour display,
allowing comparison and difference measurements to
be determined.
Standard Scope of Supply
TDR — The Time Domain Reflectometer offers:
■ Menu driven operation
■
User definable table of standard cable types
■
All pulse echo modes
■
Transient analyses methods of prelocation
In basic mode, the TDR features auto-ranging, auto
distance to fault and operator assist functions that guide
the operator through the fault locating process.
■
In the A.R.M. mode, faults are stablised by creating a
temporary “bridge” to earth. During this condition, a
standard pulse echo measurement is taken into what is
basically a short circuit fault.
■
ICE and Voltage Decay methods are both transient
analysis methods of pre-location which utilise either a
linear coupler or voltage divider. During a breakdown at
the point of fault, transients are generated that oscillate
both back to the TDR and far end of the cable. In ICE
mode, a surge generator (34 kV) max is used to
generate the breakdown; in voltage decay the dc source
(40 kV) max is used.
PFL — Portable Fault Locator provides:
■ D.C. testing
■
Fault conditioning
■ Proof/Burn
■ A.R.M. (Arc Reflection Method)
■
Fault pre-location using:
■ A.R.M. (Arc Reflection Method)
■ ICE (Impulse Current)
■ Voltage Decay
■
Acoustic pinpoint fault location
■
Ground Safety Interlock
The TDR is used to pre-locate cable faults using pulse
echo, arc reflection, impulse current (ICE) and the
optional voltage decay method.
PFL40 SERIES
Portable Cable Fault Location and High Voltage Test Solutions
Fault Conditioning
Fault conditioning is used to stabilise unstable, flashing or
high resistance faults. The Megger Fault Locator system
incorporates both A.R.M. and Proof/Burn modes.
■
■
Proof/Burn
Using the available 40 kV dc output and following a
breakdown of the cable under test, a high current is
applied, stabilising the fault condition. This allows
easier and quicker prelocation and pinpointing of the
unstable faults.
A.R.M.
Not widely thought of as a fault condition method, the
A.R.M. method stabilises faults by creating a temporary
“bridge” to earth, enabling standard pulse echo
techniques of prelocation to be used.
Acoustic pinpoint fault location
Accurate acoustic pinpoint fault location is achieved with
the powerful 8/16/34 kV (4 kV optional) surge generator
(thumper) which comes in either 1500 Joules or 2000
Joules (optional) configurations.
Additional accuracy can be achieved by using the Megger
MPP1001 or MPP1002 Acoustic and Electromagnetic
pinpointer, which shows direction and distance to fault.
Pinpoint Fault Location
Surge:
0 – 8/16/34 kV, (4 kV optional)
1500 Joules each range (2000 Joules optional)
Impulse Sequence : Adjustable 2 – 12 seconds
Single Shot
Cables
HV: 15m of 70kV 1-phase EPR
System Supply: 15m, 8mm2
Earth: 15m, 8mm2
Environmental
Operating Temperature: -20° to +50°C (-4° to 122°F)
Storage Temperature: -20° to +70°C (-4° to 122°F)
Elevation: 1500m (5000 ft)
Derate voltages at higher altitudes
Humidity: 50 to 95% RH non-condensing
Supply Mains: Universal 100 to 260 V (50/60 Hz)
IP Rating
IP54 (with top/back flaps closed)
Weight
149 kg
Dimensions
965 mm H x 536 mm W x 503 mm D
ORDERING INFORMATION
SPECIFICATIONS
Testing
DC testing: 0 – 40 kV Imax 25 mA (negative to earth)
Resolution: 1 mA
Trip: Adjustable current trip
Metering: Analog and digital metering of current and voltage
Pre-location
MTDR
Range: 60 m – 50 km
Pulse width: 40, 80, 160, 320, 640 ns 1, 2, 5, 10 µs, and auto
Display: 8 in., full VGA, color
Cursors: Dual independent
Gain:
Selectable, x1, 2, 3, 4, 5, 10, 20, 50, 100, and auto
Input:
Impedance 50 Ω
Inputs:
1 pulse echo, 1 current impulse/voltage decay
1 serial, 2 parallel (printer/USB memory device)
Ports:
Software Included COMLink for downloading trace
Item
Cat. No.
40 kV dc, 8/16/34 kV @ 1500 Joule surge
PFL40-1500
40 kV dc, 8/16/34 kV @ 2000 Joule surge
PFL40-2000
Included Accessories
PFF40 with integral MTDR1
PFL
High-voltage shielded output cable, 15 m
Supply cable, 7 m
17032-17
Flexible earth cable, 15 m
19265-15
Wheel kit and
Handle assembly
36306
36409
Earth rod
23462-1
Interlock shorting plug
10226-1
Cable bag
18313
Instruction manual
High Voltage Prelocation
A.R.M.: 8/16/34 kV (4 kV optional)
ICE:
8/16/34 kV (4 kV optional)
Voltage decay: 0 – 40 kV
Fault Conditioning
A.R.M.: 8/16/34 kV (4 kV optional)
Proof/burn: 0 – 40 kV
0 – 4 kV, 240 mA (optional)
0 – 8 kV, 120 mA
0 – 16 kV, 60 mA
0 – 34 kV, 30 mA
UK
Archcliffe Road, Dover
CT17 9EN England
T +44 (0) 1 304 502101
F +44 (0) 1 304 207342
UKsales@megger.com
UNITED STATES
4271 Bronze Way
Dallas, TX 75237-1019 USA
T 1 800 723 2861 (USA only)
T +1 214 333 3201
F +1 214 331 7399
USsales@megger.com
36566
AVTMPFL40
Optional Accessories
Earth monitor/ground safety interlock
36724
4-kV stand-alone surge capability
36727
Stand-alone battery supply
36726
Voltage decay coupler
36569
Stand-alone cable reel assembly
CBL100HV
Rack mounted cable reel assembly
CBL125H
Pinpointer/Receiver
MPP1002
OTHER TECHNICAL SALES OFFICES
Norristown USA, Sydney AUSTRALIA,
Toronto CANADA, Trappes FRANCE,
Kingdom of BAHRAIN, Mumbai INDIA,
Johannesburg SOUTH AFRICA, and
Conjure THAILAND
ISO STATEMENT
Registered to ISO 9001:2000 Cert. no. 10006.01
PFL40_SERIES_DS_en_V02
www.megger.com
Megger is a registered trademark
Information subject to change
without notice