Blind actuator REG-K/2x(1x230)/10 Table of Contents 1

Blind actuator REG-K/2x(1x230)/10 Table of Contents 1
Chapter 8: Blind actuators
8.2 Blind actuator, 2-gang
Blind actuator REG-K/2x(1x230)/10
Art. No. 648229
Blind actuator REG-K/2x(1x230)/10Chapter 8:Blind actuatorsArt. No.648229As at 09/028.2Blind actuator, 2-gang
Blind actuator REG-K/2x(1x230)/10
B
+-
A
instabus
®
B
Colour
Article No.
light grey
648229
Bus
ON
L
T
1. Function
Prog.
RUN
Merten
EIB
The INSTABUS blind actuator REG-K/2x(1x230)/10 has
two channels (can be controlled individually by the
bus) for controlling blind/roller shutter motors with limit switches. The drives can be controlled in two directions (UP/DOWN, left/right or OPEN/CLOSED). A
maximum of 1 blind/roller shutter motor may be connected per channel.
Jalousieaktor
REG-K/2 x (1x230)/10
6482 29
AC 230V
µ 10A
A
B
2. Installation
Table of Contents
1.
Function
1
2.
Installation
1
3.
Technical Data
2
4.
Settings in the EIB Tool Software (ETS)
2
5.
Application overview
2
The INSTABUS blind actuator is a DIN rail mounted device (REG) and is mounted on a DIN rail according to
EN50022-35. A data rail is not required. The bus connection is carried out via the bus connecting terminal
supplied with the device. The cable cover is then
placed over the bus connecting terminal to guarantee
the safety clearance of the bus cable to the 230 V cables. A maximum of 4 core pairs can be connected to
the bus connecting terminal.
The cables to the blinds and the mains voltage are connected via plug-in terminals with a screw connection.
The cables can be screwed onto the plug-in terminal
before installing the device and then inserted at a later
date. The insertion of the terminal may not take place
under load. All the devices that are mounted next to
the blind actuator must at least be equipped with basic
insulation. It is displayed via two LEDs per channel
whether mains voltage is present at the blind for upward/downward movement. The green operating LED
only lights up if the application program has been loaded correctly into the device.
¼
½
Caution!
Switch off the mains voltage before connecting
the device to the load.
The switch outputs have bistable relays. The
switch contact of the outputs can become conductive due to strong vibrations during transport. Voltage may be present at the outputs
when the mains voltage is connected to the system! After commissioning, the outputs are moved to the required position by telegrams.
The minimum reversing time (pause on change
in direction) specified by the motor manufacturer must be observed for the connected motors.
If shorter reversing times are selected for the
blind actuator than those specifed for the motor,
it can lead to the motor being damaged.
The idle time (reversing time) of the blind actuator can
be set between 520 ms and 10.4 s in the latest application.
As at 09/02
1
Chapter 8: Blind actuators
8.2 Blind actuator, 2-gang
Blind actuator REG-K/2x(1x230)/10
Art. No. 648229
Connection example
3. Technical Data
Bus
+ -
External auxiliary supply:
Power supply from the
bus:
Insulation voltage:
Protection:
Switch contact:
Nominal voltage:
Nominal current:
Nominal capacity:
Service life
AC 230 V, 10 A at
cos ϕ = 1
Reversing time
(of the blind actuator)
Ambient temperature
Operation:
Storage:
Transport:
Max.humidity:
Environment:
Operating elements:
Display elements:
Connections
Bus:
Blind:
EC guidelines:
Dimensions:
Device width:
L2 L1 N PE
A
none
DC 24 V / approx. 5 mA
AC 4 kV AC
The switch contact must be
protected by a series-connected 10 A circuit-breaker.
4 x make contacts
AC 230 V, 50 to 60 Hz
10 A ohmic load,
10 A inductive load at
cos ϕ = 0.6
max. 2300 VA total output
of both motors
50,000 switching cycles
> 520 ms
(can be set between
520 ms and 10.4 s in the latest application)
-5° C to +45° C
-25° C to +55° C
-25° C to +70° C
93 %
The device is designed for
use at a height up to 2000
m above sea level
Programming button
Red LED for checking the
bus voltage and for entering the physical address
Green LED to indicate that
the application is running
Two LEDs per channel to indicate the switching direction of the blind outputs
L
C
D
B
M
1
L
C
D
E
M
1
40060150
A
Channel A
B
Bus coupler
C
UP
D
DOWN
E
Channel B
4. Settings in the EIB Tool Software (ETS)
Selection in the product database
Manufacturer:
Product family:
Product type:
Program name:
Media type:
Product name:
Order number:
Merten
4.5
Blind actuator
4.5.01 DIN rail mounted REG-K
2-gang blind/shutter
5210/2a
Twisted Pair
Blind actuator REG-K/2x(1x230)/10
648229
5. Application overview
The following application is available:
via two 1 mm pins for bus
connecting terminal
6-pole plug-in terminal with
screw connection for max.
2.5 mm
corresponds to low voltage
guideline 73/23/EEC;
corresponds to EMC guideline 89/336/EEC
90x72x65 mm (HxWxD)
4 modules = 72 mm
Application
Vers. Function
2-gang blind/shutter
5210/2a
2
Control of blinds with slat adjustment
Setting the slat adjustment period
or Control of roller shutters without
slat adjustment
Setting the max. operating time of the
blinds/roller shutters
Activating the safety function and parameterisation of the monitoring period
Setting the reversing time (pause on
change in direction)
Defining the setting for the safety position (top/bottom)
As at 09/02
2