CHQ MODULES INSTALLATION INSTRUCTIONS
Hochiki Europe (UK) Ltd
CHQ MODULES INSTALLATION INSTRUCTIONS
Products Covered: CHQ SZM (Single Zone Monitor), CHQ-DIM (Dual Input Monitor)
Introduction
The CHQ "Smart-Fix" Range of Modules consists of the following models:
CHQ-DZM
CHQ-DIM
CHQ-DIM(SCI)
CHQ-DZM(SCI))
Dual Zone Monitor
Dual Input Module
CHQ-DIM/DIN
CHQ-DZM/DIN
CHQ-DIM/DIN(SCI)
CHQ-DZM/DIN(SCI)
CHQ-DRC
CHQ-MRC
CHQ-DRC(SCI)
CHQ-MRC(SCI)
Dual Relay Controller
Mains Relay Controller
CHQ-DRC/DIN
CHQ-MRC/DIN
CHQ-DRC/DIN(SCI)
CHQ-MRC/DIN(SCI)
CHQ-DSC
CHQ-SZM
CHQ-DSC(SCI)
CHQ-SZM(SCI)
Dual Sounder Controller
Single Zone Monitor
CHQ-DSC/DIN
CHQ-SZM/DIN
CHQ-SZM/DIN(SCI)
CHQ-DSC/DIN(SCI)
Note: (SCI) indicates Module incorporates a short-circuit isolator. DIN indicates Module housing is designed to fit
standard “Top Hat” DIN Rail.
Components
Standard "Smart-Fix" Modules (including (SCI) versions) are supplied as two individual components (see Fig 1 & 2). DIN
versions are supplied as one unit (see Fig 3).
Fig 1
"Smart-Fix" CHQ Module (Back Plate inc PCB Component)
(Note: configuration of Wiring Terminal blocks differs between
models)
Fig 2
CHQ-LID Transparent Module Lid
(Supplied with four screws and acrylic retaining
washers)
Setting the Loop Address
‰
‰
‰
The analogue address of the Module is set using the first 7
switches of the 8-bit DIL switch, which in the case of the
Standard CHQ is located through the cut-out section on the
top of the PCB cover. On the DIN version, this switch is
located on the edge of the PCB behind the clear door (see
Fig 3).
The switches are numbered 1 to 8 (left to right) and each
switch should be in the UP position for “ON” and DOWN for
“OFF” and should be set using a small-tipped screwdriver or
similar.
Refer to the Address Chart (Fig 10) on page 4 for a quick
reference on addresses.
Fig 3
(continued on page 4)
Page 1
DIN Rail Mountable CHQ
2-3-0-778/ISS1/APR07
Hochiki Europe (UK) Ltd
CHQ-DIM DUAL INPUT MONITOR
This device is a loop-powered module designed to interface to a variety of inputs, such as, door contacts, sprinkler flow/door
switches and plant equipment fault contacts, this module is particularly suited to applications where a fast response is required
to the input change.
Setting Contact Monitoring
Both volt free input contacts can be configured to
be either N/O or N/C, by setting the 2-bit DIL switch
(see Fig 4).
DIL Switch Bit 1 = INPUT 1
DIL Switch Bit 2 = INPUT 2
ON = Normally Closed (N/C)
OFF = Normally Open (N/O)
LOOP CONNECTIONS
S = Cable Screen (if required)
- = Loop Negative (-ve)
+ = Loop Positive (+ve)
Fig 4
Order codes
Transmission method
Loop:-Operating voltage
Quiescent current
Current consumption whilst polling
Current consumption with inputs active
Current in short-circuit
Maximum short-circuit current (Loop)
Input line resistance
CHQ-DIM
Weights &
CHQ-DIM(SCI)
Dimensions
CHQ-DIM/DIN
CHQ-DIM/DIN(SCI)
Colour and enclosure material
1
CHQ-DIM / CHQ-DIM(SCI) / CHQ-DIM/DIN /CHQ-DIM/DIN(SCI)*1
Digital communication using ESP
17 - 41 VDC
280μA
22mA ± 20 %
4.3mA (Both inputs active)*2
8mA (CHQ-DIM/DIN(SCI))
1A (CHQ-DIM/DIN(SCI))
ON threshold <50Ω, OFF threshold >100KΩ
324g
L=157mm x W=127mm x D=35mm (CHQ Module plus Lid)
327g
D=79mm (CHQ Module plus Lid plus CHQ-BACKBOX)
110g
(add 235g to module weight when using CHQ-BACKBOX)
113g
CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS
* Fire alarm control panel compatibility required for these products.
Page 2
2
* Note: - Add 85μA per input for normally closed contact monitoring
2-3-0-778/ISS1/APR07
Hochiki Europe (UK) Ltd
CHQ-SZM SINGLE ZONE MONITOR is a loop-powered module that provides a single fully monitored input for the
connection of up to six Hochiki conventional smoke or heat detectors, OR one Hochiki beam detector, or any number of
conventional call points, the unit also contains an output for remote fire indication.
Note: The end of line device (EOL) is supplied
with the unit – do NOT discard in error! The EOL
device MUST be fitted at the last detector on the
zone, note the polarity.
Fig 5
C = -ve
L = +ve
Part number TE-RH-E
Order codes
Transmission method
Loop:-Operating voltage
Quiescent current
Current consumption whilst polling
Current in short-circuit
Maximum short-circuit current (Loop)
E.O.L device
Zone voltage
Zone resistance
Zone capacitance
Detectors per zone
CHQ-SZM
CHQ-SZM(SCI)
CHQ-SZM/DIN
CHQ-SZM/DIN(SCI)
Colour and enclosure material
Weights &
Dimensions
1
CHQ-SZM / CHQ-SZM(SCI) / CHQ-SZM/DIN / CHQ-SZM/DIN(SCI) *
Digital communication using ESP
17 - 41 VDC
260μA
22 mA ± 20 %
8mA (CHQ-SZM/DIN(SCI))
1A (CHQ-SZM/DIN(SCI))
TE-RH-E (polarity conscious)
15.3V - 17.1V
50Ω (Max)
0.3μF (Max)
Number of conventional detectors per zone
DCA, DFB, DFE – No limit
SLG, SLK, SLR, SIF, SIH, SIJ, DCC, DCD, DFJ – 6 max
SPB-ET or SRA-ET– Only one and no other detectors
HF-24 – Only one and no other detectors
Conventional Call Points – No limit
325g
L=157mm x W=127mm x D=35mm (CHQ Module plus Lid)
328g
D=79mm (CHQ Module plus Lid plus CHQ-BACKBOX)
111g
(add 235g to module weight when using CHQ-BACKBOX)
114g
CHQ Module & CHQ-BACKBOX White ABS, DIN Module Green ABS
* Fire alarm control panel compatibility required for these products.
This module does not support any line continuity options; therefore, if manual Call Points are to be interfaced then these
should be connected first.
Page 3
2-3-0-778/ISS1/APR07
Hochiki Europe (UK) Ltd
Installation – "Smart-Fix" Version
Set analogue address before installation (see page 1). The
fixing surface should be dry and stable.
‰ Hold the back plate up against the fixing surface and
mark the position of the four corner fixing holes.
‰ Determine which cut-out sections along the top and
bottom edges of the module require removing to
accommodate the cables being used.
‰ Remove cut-outs by scoring with a sharp knife before
breaking off with pliers or snips.
‰ Mount the back plate using appropriate fixings (not
supplied) for the fixing surface.
‰ Terminate and connect field wiring as per the wiring
diagrams on pages 2 & 3 (and the terminal block
indications on the product label).
The transparent lid (CHQ-LID) is supplied with four screws
and eight retaining washers.
‰ Push the screws through one of the retaining washers
and then through the holes in the lid from front to back,
pushing another retaining washer onto the end inside
the lid.
‰ Screw the lid onto the back plate; do not over tighten
the screws as this could damage the unit.
Note, a white plastic version of the lid is available (sold
separately – CHQ-LID(WHT)).
Installation – "Smart-Fix" with Back Box
For those installations requiring glanded cables, a module
back box (CHQ-BACKBOX) is available (sold separately).
Fig 10
This features ten knock-out cable entries (glands are not supplied). Ensure glands used conform to IP67, if such ingress
protection is required. The CHQ-BACKBOX is mounted on the fixing surface; the CHQ Module is then fitted to the top of
the back box. Finally the CHQ-LID is added creating a sealed enclosure. For further details refer to the CHQ-BACKBOX
Instructions (2-3-0-800).
Installation – DIN Version
Set analogue address before installation (see page 1) and write loop address in space provided on door label.
‰ Clip onto an appropriate DIN Rail, which should be mounted within an approved enclosure with the loop connections
at the bottom of the unit.
‰ Terminate and connect field wiring as per the wiring diagrams on pages 2 & 3 (and the terminal block indications on
the product label).
‰ To comply with EMC regulations, these products must be fitted in a protective enclosure.
‰ Suitable anti-static precautions must be taken when handling these products.
Status LEDs
Refer to the table below for Status LED indications:
CHQ-DIM (all variants)
Dual Input Module
CHQ-SZM (all variants)
Single Zone Monitor
Green LED flashes each time the unit is polled by the
fire alarm control panel and is continuously illuminated
when either input is active.
Amber LED is continually illuminated when unit
detects short-circuit fault.
Hochiki Europe (UK) Ltd
Grosvenor Road, Gillingham Business Park,
Gillingham, Kent, ME8 0SA, England
Telephone: +44(0)1634 260133
Facsimile: +44(0)1634 260132
Email: sales@hochikieurope.com
Web: www.hochikieurope.com
Page 4
Hochiki Europe (UK) Ltd. reserves the right to alter
the specification of its products from time to time
without notice. Although every effort has been made
to ensure the accuracy of the information contained
within this document it is not warranted or
represented by Hochiki Europe (UK) Ltd. to be a
complete and up-to-date description. Please check
our web site for the latest version of this document.
2-3-0-778/ISS1/APR07