INTERACTIVE INSTALLATION AND SAFETY

INTERACTIVE INSTALLATION AND SAFETY
Please read these
instructions carefully
before installing
This will ensure an easy
start and a great first
customer experience with
TS4 installation
INTERACTIVE
INSTALLATION AND SAFETY MANUAL
FOR TS4: SMART MODULES AND RETROFIT
CLICK TO CONTINUE
It is highly recommended to
view in full screen mode
THE INTERACTIVE MANUAL
ON THIS SIDE:
You’ll see clarification, additional
information, and links for external
This manual contains action buttons, designated to help
you navigate around and find the most relevant
information for your installation
Next
Goes to the next page
Back
Goes to the previous page
Home
Goes to the product selection page
CLICK TO CONTINUE
pages
READ THIS FIRST
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
LETHAL VOLTAGE MAY BE PRESENT IN ANY PV INSTALLATION
•
•
This manual contains important instructions for installation and
maintenance of the Tigo Energy® product models TS4-L, TS4-O,
TS4-S, TS4-M, TS4-R-M, TS4-R-S, TS4-R-O, ES-GTWY-020,
Cloud Connect, Cloud Connect Advanced and related Tigo Energy
software applications.
Risk of electric shock, do not remove cover, disassemble, or repair,
no user serviceable parts inside. Refer servicing to qualified
service personnel.
•
Before installing or using the Tigo Energy® System, please read all
instructions and warning markings on the Tigo Energy products,
appropriate sections of your inverter manual, photovoltaic (PV)
module installation manual, and other available safety guides.
•
Failure to adhere to these instructions may result in injury or death,
damage to the system or voiding the factory warranty.
•
To reduce risk of fire and shock hazard, install this device with
strict adherence to National Electric Code (NEC) ANSI/NFPA 70
and/or local electrical codes. When the photovoltaic array is
exposed to light, it supplies a DC voltage to the Tigo Energy®
Module Maximizer™. The Module Maximizers and Smart Modules
start in the “ON” state and their output voltage may be as high as
the PV module open circuit voltage (Voc) when connected to the
module. The installer should use the same caution when handling
electrical cables from a PV module with or without the Tigo Energy
Module Maximizer attached.
•
Installation must be performed by trained professionals only. Tigo
Energy does not assume liability for loss or damage resulting from
improper handling, installation, or misuse of products.
•
Remove all metallic jewelry prior to installing the Tigo Energy
Module Maximizers or Smart Modules to reduce the risk of
contacting live circuitry. Do not attempt to install in inclement
weather.
•
Do not operate the Tigo Energy Module Maximizers or Smart
Modules if they have been physically damaged. Check existing
cables and connectors, ensuring they are in good condition and
appropriate in rating. Do not operate Tigo Energy Module
Maximizers or Smart Modules with damaged or substandard wiring
or connectors. Tigo Energy Module Maximizers must be mounted
on the high end of the PV module back-sheet or racking system,
and in any case above ground.
•
Do not connect or disconnect under load. Turning off the Inverter
and/or the Tigo Energy products may not reduce this risk. Internal
capacitors within the inverter can remain charged for several
minutes after disconnecting all power sources. Verify capacitors
have discharged by measuring voltage across inverter terminals
prior to disconnecting wiring if service is required.
•
Service Personnel: Check the voltage of the array after activating
the Tigo Energy® PV-Safe™ function on the MMU prior to
performing service.
•
Always assume Module Maximizers and Smart Modules are in
“ON” state, or may turn on when restarting.
GUIDE:
TS4 PLATFORM: BASE
Long Strings
This manual covers the installation steps for the Tigo TS4 family of
products, both integrated and add-on versions.
Optimization
Rapid Shutdown
Monitoring
WHERE TO BUY:
CLICK HERE
Module integrated TS4
Add-on TS4-R
TS4 PLATFORM: COVER SELECTION
GUIDE:
Long Strings
The TS4 covers contain your module level electronics:
Optimization
Rapid Shutdown
TS4-L*
TS4-O
Monitoring
WHERE TO BUY:
CLICK HERE
TS4-S
TS4-M
*TS4-L is available only for the module integrated TS4
ORDERING INFORMATION:
COMMUNICATION
Cloud Connect Kit comes with:
1 Gateway
The Cloud Connect is your data logger and safety control unit.
The Gateway is an antenna that communicates with your smart
modules or add-on devices.
It is always recommended to install communication accessories, to
utilize the full potential of your TS4, however it is only mandatory in
order to enable monitoring and safety features, such as Rapid
Shutdown.
1 Power supply: 2 different options:
1. Wall Outlet
2. DIN Rail
Additional Gateways available separately
Select your model of Cloud Connect:
Cloud Connect and Gateway
Cloud Connect Advanced
and Gateway
WHERE TO BUY:
CLICK HERE
REMINDER:
When using TS4-O and TS4 -L, Cloud
Connect is only required where rapid
shutdown and/or monitoring
capabilities are needed
TABLE OF CONTENTS
1. System Overview
& Product Description
2. Installing Cloud Connect
(CC)
5. Configuring the
System Online
6. Commissioning
3. Installing Gateways (GTWY)
7. Rapid Shutdown
4. Installing and Mapping
8. Connecting Modbus
Accessories
1. SYSTEM OVERVIEW: TS4-B (TS4 BASED MODULES)
DESIGN RULES:
1 CLOUD CONNECT:
Gateway (GTWY)
- Up to 7 GTWYs and 360 PV modules
- All Smart Modules in the same string
must be assigned to the same CC
1 GTWY:
- Up to 120 PV modules
- Modules must be within 10m-15m
(33-50 ft.) from the GW, depending on
Next Gateway
roof topology and material
For further information CLICK HERE
Internet
Inverter
Cloud Connect
(CC)
CC AND GTWY CALCULATOR:
For the number of CCs and GTWYs
required for your project CLICK
Tigo’s Monitoring
Software for
Systems
Management
Smart Module
Powered by Tigo
HERE
DESIGN RULES:
1. SYSTEM OVERVIEW: TS4-R
1 CLOUD CONNECT:
Gateway (GTWY)
- Up to 7 GTWYs and 360 PV modules
- All Smart Modules in the same string
must be assigned to the same CC
1 GTWY:
- Up to 120 PV modules
- Modules must be within 10m-15m
(33-50 ft.) from the GW, depending on
Next Gateway
roof topology and material
For further information CLICK HERE
Internet
Inverter
Cloud Connect
(CC)
CC AND GTWY CALCULATOR:
For the number of CCs and GTWYs
required for your project CLICK
Tigo’s Monitoring
Software for
Systems
Management
TS4-R with
Monitoring, Safety
and/or Optimization
HERE
1. SYSTEM OVERVIEW & PRODUCT DESCRIPTION
TS4-M: MONITORING: The TS4-M provides continuous
system-wide monitoring for fleets to make customer support
and fleet workflow on track
Diodes
Monitoring
TS4-S: SAFETY: The TS4-S provides the necessary safety
and monitoring services required by municipalities
Diodes
Monitoring
Safety
TS4-O: OPTIMIZATION: In addition to safety, monitoring, and
PV2.0 synchronization, TS4-O optimizes each PV module
when its performance is affected by shade or mismatch
Diodes
Monitoring
Safety
Optimization
TS4-L: LONG STRINGS: The TS4-L is the complete Smart
Module solution. It is ideal for systems requiring fully optimized
performance at the module level, monitoring, safety, and longer
strings CLICK HERE to see the TS4-L string sizing info.
Diodes
Monitoring
Safety
Optimization
Long Strings
MORE INFORMATION:
Click here to learn more, watch a
video and see the TS4 platform
datasheet.
WHERE TO PLACE:
2. INSTALLING THE CLOUD CONNECT (CC)
- On a wall or beam
OPTIONAL
Emergency Push Button
Wired Ethernet
connection option
1
- Out of direct sunlight
159.5mm (6.28”)
90.2mm (3.55”)
- Next to the inverter
3 CONNECTIONS:
-+
1. Internet connection, using one of the
options:
•
Ethernet Port
•
Built in Wi-Fi
•
Wi-Fi connection is
configured using the
Tigo SMART app
2. Power supply: 2 options:
G■BA
57.5mm (2.26”)
OPTIONAL
Wi-Fi Antenna*
As an Internet
connection and / or
for commissioning
with a smartphone
-+BA --++
RS485
For 3rd party
devices
Gateway
Plug in GTWY(s)
cable after all the
GTWY(s) are
connected in
series (next page)
Power Supply
24Vdc input
2
3
For Rapid Shutdown,
install CC on the same
AC panel as the
inverter
*In case CC is mounted in a metal enclosure, extend this antenna out of the box in order to
use Wi-Fi as an Internet connection
•
DIN Rail Power Supply
•
Wall Socket Power Supply
•
CLICK HERE for details
3. GTWY
•
More on RS485 cables in the
next page
Complete CC menu options in 7.
Commissioning
CLICK HERE for Tigo SMART app
guide
INSTALLATION:
3. INSTALLING GATEWAYS (GTWY)
1. Connect all GTWY cables before
powering ON Cloud Connect
2. Mount GTWY on back of PV
module using provided bracket, or
50ft (15m)
bolt to the racking system
3. Powering ON Cloud Connect and
preform GTWY test from the Tigo
SMART App
RS-485 communication cable is
recommended: 2 x twisted pair,
Gateway attaches to module frame
using provided bracket
Locate Gateway near center of array
or each sub-array
sunlight resistant of direct burial.
MORE INFORMATION
• Gateway Hardware Guide
• Gateway Placement Guide
• Communication Cable Guide
Connect multiple Gateways in series and leave terminating resistor only in final Gateway.
TABLE OF CONTENTS
1. System Overview
& Product Description
2. Installing Cloud Connect
(CC)
5. Configuring the
System Online
6. Commissioning
3. Installing Gateways (GTWY)
7. Rapid Shutdown
4. Installing and Mapping
8. Connecting Modbus
Accessories
1. SYSTEM OVERVIEW: TS4-B (TS4 BASED MODULES)
DESIGN RULES:
1 CLOUD CONNECT:
Gateway (GTWY)
- Up to 7 GTWYs and 360 PV modules
- All Smart Modules in the same string
must be assigned to the same CC
1 GTWY:
- Up to 120 PV modules
- Modules must be within 10m-15m
(33-50 ft.) from the GW, depending on
Next Gateway
roof topology and material
For further information CLICK HERE
Internet
Inverter
Cloud Connect Advanced
(CCA)
CC AND GTWY CALCULATOR:
For the number of CCs and GTWYs
required for your project CLICK
Tigo’s Monitoring
Software for
Systems
Management
Smart Module
Powered by Tigo
HERE
DESIGN RULES:
1. SYSTEM OVERVIEW: TS4-R
1 CLOUD CONNECT:
Gateway (GTWY)
- Up to 7 GTWYs and 360 PV modules
- All Smart Modules in the same string
must be assigned to the same CC
1 GTWY:
- Up to 120 PV modules
- Modules must be within 10m-15m
(33-50 ft.) from the GW, depending on
Next Gateway
roof topology and material
For further information CLICK HERE
Internet
Inverter
Cloud Connect Advanced
(CCA)
CC AND GTWY CALCULATOR:
For the number of CCs and GTWYs
required for your project CLICK
Tigo’s Monitoring
Software for
Systems
Management
TS4-R with
Monitoring, Safety
and/or Optimization
HERE
1. SYSTEM OVERVIEW & PRODUCT DESCRIPTION
TS4-M: MONITORING: The TS4-M provides continuous
system-wide monitoring for fleets to make customer support
and fleet workflow on track
Diodes
Monitoring
TS4-S: SAFETY: The TS4-S provides the necessary safety
and monitoring services required by municipalities
Diodes
Monitoring
Safety
TS4-O: OPTIMIZATION: In addition to safety, monitoring, and
PV2.0 synchronization, TS4-O optimizes each PV module
when its performance is affected by shade or mismatch
Diodes
Monitoring
Safety
Optimization
TS4-L: LONG STRINGS: The TS4-L is the complete Smart
Module solution. It is ideal for systems requiring fully optimized
performance at the module level, monitoring, safety, and longer
strings CLICK HERE to see the TS4-L string sizing info.
Diodes
Monitoring
Safety
Optimization
Long Strings
MORE INFORMATION:
Click here to learn more, watch a
video and see the TS4 platform
datasheet.
2. INSTALLING THE CLOUD CONNECT ADVANCED
(CCA)
WHERE TO PLACE:
- On a wall or beam
Network
Wired Ethernet and
Wi-Fi connections
OPTIONAL
Connect an External Switch
for PV-Safe
1
- Next to the inverter
- Out of direct sunlight
3 CONNECTIONS:
1. Internet connection, using one of the
options:
•
Ethernet Port
•
Built in Wi-Fi
•
Wi-Fi connection is
configured using the
Tigo SMART app
2. Power supply: 2 options:
GBA
RS485
For 3rd party
devices
Wireless Capabilities
Use Wi-Fi for your
Internet connection and
for commissioning with
a smartphone
-+BA
GBA
RS485
For 3rd party
devices
Gateway
Plug in GTWY(s)
cable after all the
GTWY(s) are
connected in
series (next page)
-+
Power Supply
24Vdc input
2
3
For Rapid Shutdown,
install CC on the same
AC panel as the
inverter
*In case CC is mounted in a metal enclosure, extend this antenna out of the box in order to
use Wi-Fi as an Internet connection
•
DIN Rail Power Supply
•
Wall Socket Power Supply
•
CLICK HERE for details
3. GTWY
•
More on RS485 cables in the
next page
Complete CC menu options in 7.
Commissioning
CLICK HERE for Tigo SMART app
guide
3. INSTALLING GATEWAYS (GTWY)
Installation:
1. Connect all GTWY cables before
powering on Cloud Connect
50ft (15m)
2. Install GTWY on back of PV
module using provided bracket or
bolt to the racking system
3. Power on Cloud Connect and perform
Gateway test from Tigo SMART App
Gateway attaches to module frame
using provided bracket
Locate Gateway near center of array
or each sub-array
RS-485 communication cable is recommended.
2 twisted pair, sunlight resistant or direct burial
More Information:
• Gateway Hardware Guide
• Gateway Placement Guide
• Communication Cable Guide
Connect multiple Gateways in series and leave terminating resistor only in final Gateway.
4. INSTALLING & MAPPING: TS4-R
1
Mount the optimizer
on the top right corner
of the PV module
3
Connect the long output cables of the
optimizers in series to form strings, as
you would with standard PV modules
2
Connect the PV
cables from the
module to the short
leads of the TS4-R
TEMPLATES:
4. INSTALLING & MAPPING
Create your site map using Tigo’s
1
string list template
To view and download, CLICK HERE
Remove 1 barcode sticker from
the TS4 junction box or add-on
Another option is to first map your
site online (see next page). At the
end, you’ll be able to download a
2
Place the sticker on the map, string
list or construction drawing, in the
exact position you are going to
place modules in the field or on the
roof.
physical map of your system to help
map the barcodes
NOTE:
If you’re installing 50 modules or less
and don’t need an exact physical
position you may skip the mapping
Place PV modules in a way
matches the map you made using
barcodes.
3
step and go straight to
commissioning
MAKE SURE you take the junction
Also record the serial numbers of
box’s label or the TS4-R label, NOT
the GTWY(s)
the module’s
5. CONFIGURE THE SYSTEM ONLINE
CLICK HERE
http://installations.tigoenergy.com/
1
Click on
3
Follow the wizard instructions
2
** For smart module systems with less than 50 panels, this step can be done after the physical installation
6. COMMISSIONING
CC MENU:
To commission the Tigo equipment there are 3 simple steps that need to be
completed:
1. Status
1.1. Modules
1. NETWORK TEST
1.1.1. Signal
2. GATEWAY TEST
1.1.2. Voltage
3. DISCOVERY
1.1.3. Power
For systems with multiple Cloud Connect units, these tests need to be
performed on each individual Cloud Connect .
1.2. Date / Time
Network and Gateway tests can run at the same time on different CCs.
However, Discovery must be initiated on Cloud Connects one by one, making
sure GTWY discovery stage is complete before moving to the next one.
1.4.Version
This may take several minutes to several hours depending on the size of the
system.
Note: The discovery process can be initiated for
sites with more than 50 Smart Modules only after the
online configuration of the system has been
completed and downloaded by the Cloud Connect.
1.3. Unit ID
1.5. Config (internal use only)
2. Control
2.1. Discovery
2.2. Modules ON
2.3. Push Data
2.4. Restart
.
This step requires an Internet connection.
2.5. Gateway Test
2.6. Replace GW
To Commission the system using your smartphone, download the Tigo SMART app
and follow its instructions. CLICK HERE to view the manual.
2.7. H/W Test (internal use only)
3. Network
VERIFY RAPID SHUTDOWN FUNCTIONALITY
3.1. Display IP
Verify rapid shutdown functionality after the discovery process is
completed.
3.2. Test
Switch off the AC main and make sure voltage drops below 30V
within 10 seconds. Power the system on after testing using:
3.4. Set Proxy
3.3. Configure
3.5. Renew
2. Control -> 2.2. Modules ON
Click for description
7. RAPID SHUTDOWN
TS4-L, TS4-O, and TS4-S with Kaco Blueplanet Smart Inverter and Gateway are a solution to meet NEC 2014 690.12
Rapid Shutdown requirements, when combined with a DC disconnect at the inverter.
When Rapid Shutdown is initiated, the voltage across PV conductors will drop below 30V within 10 seconds at the
module level.
Rapid Shutdown is activated by taking 2 simple actions.
To activate rapid shutdown (with most inverters order of actions doesn’t matter):
1. Switch off DC disconnect as well to disconnect capacitors.
2. Switch OFF AC main to deactivate system.
In the inverter’s box you’ll find 2 red labels to mark the Rapid Shutdown equipment. Place one sticker next to the
inverter’s DC switch and the other on the AC main breaker. Both labels must be visible!
Only a properly installed, configured, and tested system will perform Rapid Shutdown properly.
CLICK HERE for more info about Rapid Shutdown
8. CONNECTING MODBUS DEVICES (OPTIONAL)
INSTALLATION:
1. Verify device settings for AC
meter, inverter, etc. in its own
installation manual
2. Connect devices to RS-485 port
on CC or CCA (note: similar
devices can be connected in
series)
3. Contact Tgo Tech Support to
G■BA
activate a connected device
To
GTWY
To
Modbus device
1.408.402.0802 ext. 2
00800.CALL.TIGO(2255.8446)
support@tigoenergy.com
RECOMMENDED SETTINGS:
• 9600 baud rate
• 8 bits data
• 1 stop bit
GBA
To
GTWY
To
Modbus device
• No parity
TECHNICAL SPECIFICATIONS – SMART MODULE WITH TS4-B1500 BASE
TS4 COVERS
ELECTRICAL RATINGS
DIODES
TS4-D
MONITORING
TS4-M
SAFETY
TS4-S
OPTIMIZATION
TS4-O
LONG STRINGS
TS4-L
INPUT @ STC
Rated DC Input Power
375W
375W
375W
375W
375W
Maximum DC Input Voltage (VOC)
90V
52V
52V
52V
52V
Maximum Short Circuit Current (I SC)
12A
12A
12A
10A
10A
Operating Voltage
0-80V
16-48V
16-48V
16-18V
16-48V
Output Power Range
0-375W
0-375W
0-375W
0-375W
0-375W
Output Voltage Range
0-VOC
0-VOC
0-VOC
0-VOC
0-VOC
Communication Type
N/A
802.15.4
2.4GHz
802.15.4
2.4GHz
802.15.4
2.4GHz
802.15.4
2.4GHz
Rapid Shutdown Verified
(NEC 2014 690.12)
Need additional
RS device
Need additional
RS device
Yes
Yes
Yes
Impedance Matching Capability
No
No
No
Yes
Yes
Output Voltage Limit
No
No
No
No
Yes
Maximum System Voltage
1000/1500V
1000/1500V
1000/1500V
1000/1500V
1000/1500V
Maximum Series Fuse Rating
15A
15A
15A
15A
15A
OUTPUT
TECHNICAL SPECIFICATIONS – RETROFIT UNIT WITH TS4-R1500 BASE
TS4-R
ELECTRICAL RATINGS
MONITORING
TS4-R-M
SAFETY
TS4-R-S
OPTIMIZATION
TS4-R-O
INPUT @ STC
Rated DC Input Power
375W
375W
375W
Maximum DC Input Voltage (VOC)
52V
52V
52V
Maximum Short Circuit Current (I SC)
12A
12A
10A
Operating Voltage
16-48V
16-48V
16-18V
Output Power Range
0-375W
0-375W
0-375W
Output Voltage Range
0-VOC
0-VOC
0-VOC
Communication Type
802.15.4
2.4GHz
802.15.4
2.4GHz
802.15.4
2.4GHz
Rapid Shutdown Verified
(NEC 2014 690.12)
Need additional RS
device
Yes
Yes
Impedance Matching Capability
No
No
Yes
Output Voltage Limit
No
No
No
Maximum System Voltage
1000/1500V
1000/1500V
1000/1500V
Maximum Series Fuse Rating
15A
15A
15A
OUTPUT
TECHNICAL SPECIFICATIONS
MECHANICAL SPECIFICATIONS – TS4-B and TS4-R
Mechanical
Ambient Temperature Range
-40ºC to +85ºC (-40ºF to +185ºF)
Storage Temperature Range
-40ºC to +85ºC (-40ºF to +185ºF)
Cooling Method
Natural Convection
Dimensions (with cover)
152.5 x 108 x 25 (mm)
Weight
550 g (1.20 lb.)
Environmental Rating
IP65/67, NEMA 3R
Cabling
Cabling Type
PV1-F, PV wire
Cable Length
1.0 m/other lengths on request
Connector
MC4 compatible/MC4/H4
UV Resistance
500 hr with UBV light between
300-400nm @ 65C
Maximum String Voltage
1000V UL / IEC
Outer Cable Diameter
6.25 ± 0.25 mm (600V), 7.15 ± 0.25 mm (1000V)
Wire Cross Section
4.0mm2 (12AWG)
YOU’RE GOOD TO GO!
For more details on designing and installing solutions
powered by Tigo, please visit:
•
Tigo Academy
•
Agora
Or contact us at:
•
support@tigoenergy.com
•
1.408.402.0802 #2
GOOD LUCK!
Tigo Customer Care