Wiring Diagram NOTES: AMC-103 JUMPER CONFIGURATION

Wiring Diagram NOTES: AMC-103 JUMPER CONFIGURATION
CLOSE
OPEN
CLS 1-2
CLS 1-3
OLS 1-2
EARTH
OLS 1-3
CLS: CLOSE LIMIT SWITCH (250VAC, 6A MAX)
OLS: OPEN LIMIT SWITCH (250VAC, 6A MAX)
TP: THERMAL PROTECTOR (250VAC, 6A MAX)
CAPACITOR
E
U
BL
ED
R
ACTUATOR
TERMINAL
STRIP
WHITE / RED
MOTOR
1
WHITE / BLUE
2
AMC-103
WHITE / BLACK
3
(L2) NEUTRAL
(L1) LINE (120vac)
G/F WHITE
4
HEATER (20W)
(L1) LINE (120vac)
CLS
2
NEUTRAL
SPAN
LINE
OPEN OUTPUT
COMMON
CLOSE OUTPUT
(+) 0-5V / 0-10V IN
(+) 4-20mA / 1-5V IN
SIGNAL GROUND
+ 12V OUT
+ 5V OUT
ZERO
WIPER
GROUND
DEADBAND
BLUE
WHITE
RED
RED
5
1
(SELECT 1 INPUT) (+)
3
BLUE
6
(-)
OLS
2
ORANGE
7
RED
WHITE
BLACK
1
3
3
BLACK
8
1K ohms Potentiometer
(POT-102)
2
1
9
10
11
DENOTES CUSTOMER
SUPPLIED ITEM
12
NOTES:
ACTUATOR SHOWN IN MID POSITION.
INCREASING SIGNAL ROTATES COUNTER CLOCKWISE.
FOR REVERSE ACTING (SEE NOTES).
WHEN CONVERTING A DIRECT ACTING ACTUATOR TO A
REVERSE ACTING ACTUATOR, TWO CHANGES IN WIRING
MUST BE MADE ON SERVO BOARD:
1-REVERSE THE RED AND BLACK POTENTIOMETER WIRES
CONNECTED ON THE SERVO BOARD.
2-REVERSE THE BLUE AND RED MOTOR OUTPUT WIRES
CONNECTED ON THE SERVO BOARD.
NOTE: DO NOT REVERSE THE INPUT SIGNAL POLARITY.
ALSO, MAKE SURE THAT BOTH WIRING CHANGES
ARE MADE - IF ONLY ONE IS MADE, THE ACTUATOR
WILL RUN TO EITHER FULL OPEN OR FULL CLOSE.
AFTER THE WIRING CHANGES HAVE BEEN MADE, REFER
TO CALIBRATION FOR SETTING THE ZERO AND SPAN.
INPUT SIGNAL
JUMPER CONFIGURATION
INPUT SIGNAL
RANGE
0-5V
0-10V
4-20mA
1-5V
Valve Solutions
ABZ Valves & Controls
Title:
JP1
JP2
Wiring Diagram
Parts:
ABZ 006 thru ABZ 009 Electric Actuator
120 VAC Single Phase (Modulating Service)
AMC-103 Servo Board
DWG No.
WS0609-A2H-X
Date
06-12-12
Drawn
BC
Checked
Approved
TP
TH
Revision
0