Ceracore UCS2 - Endress+Hauser Portal

Ceracore UCS2 - Endress+Hauser Portal
Technical Information
Ceracore UCS2
Pressure sensor element
Ceramic sensor with compensated sensor output signal
Application
Your benefits
• The pressure sensor element Ceracore UCS2 delivers
a pressure-proportional voltage signal
• Endress+Hauser offers support for the integration of
the Ceracore UCS2 into the customized application
• Dry capacitive ceramic sensor
TI901/P/00/en/08.08
• Basic ceramic material (99.9 % Al2O3)
- extremely high overload limit
- absolutely resistant to wear
- high temperature stability
- high long-term stability
- no hysteresis
- corrosion-resistant
• Active electronics
- sensor-specific signal conditioning
- high-accuracy pressure measurement with temperature stability
Ceracore UCS2
Function and system design
Measuring principle
The Ceracore UCS2 basic material is Al2O3 (99.9 %), a highly resistant ceramic material for many aggressive
gases and liquids. Cylindrical ceramic components (diaphragm, meter body) are bonded to form a highstrength, hermetically sealed pressure sensor element. With absolute pressure sensors, the vacuum of
3.0 x 10-6 mbar created in the production process between the diaphragm and the meter body remains permanently. This permits pressure measurements related to the vacuum. With gauge pressure sensors, the back of
the diaphragm is vented, i.e. this sensor measures the gauge pressure relative to the atmospheric pressure. Electrically, the sensor element represents a plate capacitor whose capacitance change is the dimension for the pressure change. The capacitive measuring process satisfies the highest requirements concerning resolution and
reproducibility. Together with the hysteresis-free behavior of the material Al2O3 , it is the basis for the excellent
specifications of the sensor. In addition, the Ceracore UCS2 is a dry measuring cell, i.e. there is no separating
diaphragm or filling fluid which could influence the measurement.
A further advantage of the capacitive ceramic sensor is its high overload resistance. After removal of the overload, it returns to the initial position without any damage or hysteresis.
Atmospheric pressure
Substrate
Gauge pressure cell
Cp electrode
Diaphragm
Pressure
Brazing preform
Absolute pressure cell
Counter electrode
Pressure
P01-UC2xxxxx-15-xx-xx-de-000
Input
Measured variable
Choice of gauge pressure or absolute pressure
Measuring range
Gauge pressure measurement 0.1 to 70 bar, absolute pressure measurement 0.2 to 70 bar
Output
Values dependent on installation
Zero point
0.50 V ± 0.05 V; applies to the respective lower range-value of the measuring range
Span
4.00 V ± 0.05 V
Characteristic curve
linear; max. non-linearity ≤0.2 % of span
Load
≥10 kΩ or ≤300 pF (with signal deviation <0.1 % of span)
Rise time
approx. 1 ms
Switch-on time
max. 10 ms
Long-term stability
max. 0.1 % of span per year
Output signal
0.5 to 4.5 V
2
Endress+Hauser
Ceracore UCS2
Power supply
Supply voltage
• 5 V DC stabilized, minimum 4.5 V / maximum 5.5 V
• Influence of supply voltage: no influence on linearity / proportional on lower range-value / proportional on
span, no influence on temperature compensation
Current consumption
Maximum 2 mA at a supply voltage of 5 V
Operating conditions: Installation
Orientation
Arbitrary. Operate the sensor system with the diaphragm pointing downwards. Otherwise observe the positiondependent zero point shift for small pressure ranges (≤ 400 mbar).
Weight
approx. 17 to 23 g, depending on measuring range
+5 VDCsupply
zero potential
output signal
+0,5...4,5
0.05
11
830003010E2
-100...100
mbar g
7.2
0.24...2.1
Æ 25
05 ±
+0.45
Æ 32.4 -0.15
R 1.
13.4
Dimensions
Electrical connection
reference
air hole
9.7
10.6
5
7.89...9.75
P01-UCS2xxxx-06-xx-xx-de-002
Operating conditions: Environment
Ambient temperature range
-40 °C to +125 °C (also applies to storage temperature)
Degree of protection
IP 00 as per DIN 60529 (IEC529); Climate class 3K3 DIN EN 60721-3-3
Operating conditions: Process
Reference operating conditions
As per DIN IEC 60770, T = 25 °C
Media
Gases and liquids
Material
Diaphragm: aluminum oxide ceramic Al2O3 (99.9 %)
Process temperature limits
-40 °C to +125 °C, compensation temperature -20 °C to +80 °C
Endress+Hauser
3
Ceracore UCS2
Thermal change
Thermal change of the lower range-value in the compensation temperature range: max. ±0.75 % of span, with
extended specification ±1 % of span
Thermal change of output span in the compensation temperature range: max. ±0.5 % of span. With measuring
ranges ≤0.4 bar ±0.8 % of span, with extended specification ±1 % of span
Limiting medium pressure
range
Overload limit: see "Ordering information" section, Overload influence: negligible
Vacuum resistance
UCS2 with nominal value 400 mbar up to 70 bar: 0 mbar abs
UCS2 with nominal value 200 mbar: 500 mbar abs (Version M in Ordering information)
UCS2 with nominal value 100 mbar: 700 mbar abs (Version L in Ordering information)
Ordering information
Ceracore UCS2
10
Sensor range; Overload (other measuring ranges and special versions on request)
A
B
C
D
E
F
G
H
I
J
L
M
N
O
P
R
S
T
U
V
20
0...100 mbar / 10 kPa/1.5 psi absolute; 4 bar/400 kPa/60 psi
0 to 200 mbar /20 kPa/3 psi absolute; 6 bar/600 kPa/ 90 psi
0 to 400 mbar /40 kPa/6 psi absolute; 6 bar/600 kPa/ 90 psi
0 to 1 bar /100 kPa/15 psi absolute; 10 bar/1 MPa/ 150 psi
0 to 2 bar /200 kPa/30 psi absolute; 18 bar/1.8 MPa/ 270 psi
0 to 4 bar /400 kPa/60 psi absolute; 25 bar/2.5 MPa/ 375 psi
0 to 10 bar /1 MPa/150 psi absolute; 40 bar/4 MPa/ 600 psi
0 to 20 bar /2 MPa/300 psi absolute; 40 bar/4 MPa/ 600 psi
0 to 40 bar /4 MPa/600 psi absolute; 60 bar/6 MPa/ 900 psi
0 to 70 bar /7 MPa/1050 psi absolute; 105 bar/10.5 MPa/ 1575 psi
0 to 100 mbar /10 kPa/1.5 psi relative; 4 bar/400 kPa/ 60 psi
0 to 200 mbar /20 kPa/3 psi relative; 6 bar/600 kPa/ 90 psi
0 to 400 mbar /40 kPa/6 psi relative; 6 bar/600 kPa/ 90 psi
0 to 1 bar /100 kPa/15 psi relative; 10 bar/1 MPa/ 150 psi
0 to 2 bar /200 kPa/30 psi relative; 18 bar/1.8 MPa/ 270 psi
0 to 4 bar /400 kPa/60 psi relative; 25 bar/5 MPa/ 375 psi
0 to 10 bar /1 MPa/150 psi relative; 40 bar/4 MPa/ 600 psi
0 to 20 bar /2 MPa/300 psi relative; 40 bar/4 MPa/ 600 psi
0 to 40 bar /4 MPa/600 psi relative; 60 bar/6 MPa/ 900 psi
0 to 70 bar /7 MPa/1050 psi relative; 105 bar/10.5 MPa/ 1575 psi
Calibration; Unit
A
1
2
3
UCS2 -
OEM Products
Endress+Hauser GmbH+Co.KG
Hauptstraße 1
79689 Maulburg, Germany
Tel.: +49 76 22 28 21 47
Fax: +49 76 22 28 20 49
E-Mail: oem@pcm.endress.com
www.envec.endress.com
TI901P/00/en/08.08
CCS/FM+SGML 6.0
see additional specification (special measuring ranges with extended specifications)
Sensor range; mbar/bar
Sensor range; kPa/MPa
Sensor range; psi
A
1
A
1
AAA