Compact Control Builder AC800M Configuration

Compact Control Builder AC800M Configuration
Compact Control Builder AC 800M
Configuration
Version 5.1.1
Power and productivity
for a better world
TM
Compact Control Builder AC 800M
Configuration
Version 5.1.1
NOTICE
This document contains information about one or more ABB products and may include a
description of or a reference to one or more standards that may be generally relevant to
the ABB products. The presence of any such description of a standard or reference to a
standard is not a representation that all of the ABB products referenced in this document
support all of the features of the described or referenced standard. In order to determine
the specific features supported by a particular ABB product, the reader should consult the
product specifications for the particular ABB product.
ABB may have one or more patents or pending patent applications protecting the intellectual property in the ABB products described in this document.
The information in this document is subject to change without notice and should not be
construed as a commitment by ABB. ABB assumes no responsibility for any errors that
may appear in this document.
In no event shall ABB be liable for direct, indirect, special, incidental or consequential
damages of any nature or kind arising from the use of this document, nor shall ABB be
liable for incidental or consequential damages arising from use of any software or hardware described in this document.
This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party nor used
for any unauthorized purpose.
The software or hardware described in this document is furnished under a license and
may be used, copied, or disclosed only in accordance with the terms of such license. This
product meets the requirements specified in EMC Directive 2004/108/EC and in Low Voltage Directive 2006/95/EC.
TRADEMARKS
All rights to copyrights, registered trademarks, and trademarks reside with their respective owners.
Copyright © 2003-2013 by ABB.
All rights reserved.
Release:
Document number:
April 2013
3BSE040935-511
TABLE OF CONTENTS
About This Book
General ............................................................................................................................13
Document Conventions ...................................................................................................14
Warning, Caution, Information, and Tip Icons................................................................14
Terminology.....................................................................................................................15
Section 1 - Basic Functions and Components
Introduction .....................................................................................................................17
Control Project Templates ...............................................................................................19
Program Organization Units, POU ..................................................................................19
System Firmware Functions ............................................................................................20
Hardware .........................................................................................................................22
Standard System Libraries with Hardware...........................................................23
Customized Hardware Types................................................................................25
Configuring the Controller ...................................................................................25
Basic Hardware ....................................................................................................28
Basic Library for Applications ........................................................................................28
Application Types and Instances .....................................................................................30
Types and Instances - Concept .............................................................................31
Define a Type in the Editor ..................................................................................32
Control Module Types, Function Block Types, and Diagram Types ...................41
Types in Applications...........................................................................................43
Types in User defined Library..............................................................................44
Modify Complex Types........................................................................................45
Diagram and Diagram Types................................................................................46
Decisions When Creating Types ..........................................................................53
3BSE040935-511
5
Table of Contents
Create and Connect Instances .............................................................................. 54
Function Block Execution.................................................................................... 59
Control Module Execution................................................................................... 62
Diagram Execution .............................................................................................. 63
Single Control Modules ....................................................................................... 65
FD Port
............................................................................................................ 67
Variables and Parameters ................................................................................................ 69
Variable and Parameter Concept .......................................................................... 71
Variables ............................................................................................................ 72
Variable Entry ...................................................................................................... 73
External Variables ................................................................................................ 81
Access Variables .................................................................................................. 82
Communication between Applications Using Access Variables ......................... 84
Communication in an Application Using Global Variables................................. 85
Communication Variables.................................................................................... 86
Control the Execution of Individual Objects ....................................................... 92
Link Variables in Diagrams ................................................................................. 96
Project Constants ................................................................................................. 96
I/O Addressing Guidelines................................................................................. 101
Connecting Variables to I/O Channels............................................................... 102
Extensible Parameters in Function Blocks ........................................................ 107
Keywords for Parameter Descriptions ............................................................... 108
Library Management ..................................................................................................... 109
Connect Libraries............................................................................................... 110
Create Libraries.................................................................................................. 114
Library States ..................................................................................................... 114
Library Password Protection.............................................................................. 115
Add Types to Libraries Used in Applications.................................................... 116
Add Customized Hardware Types to Library .................................................... 118
Device Import Wizard........................................................................................ 120
Additional Files for Libraries with Hardware.................................................... 121
Delete Hardware Types...................................................................................... 124
6
3BSE040935-511
Table of Contents
Type Usage for Hardware Types ........................................................................124
Hide and Protect Control Module Types, Function Block Types, Diagram Types, and Data
Types ..................................................................................................................126
Protect a Self-Defined Type ...............................................................................127
Task Control ..................................................................................................................129
Task Connections ...............................................................................................129
Task Execution ...................................................................................................133
Task Priority .......................................................................................................134
Interval Time ......................................................................................................136
Offset
...........................................................................................................137
Execution Time ..................................................................................................142
Overrun and Latency .....................................................................................................142
Overrun Supervision ..........................................................................................142
Latency Supervision...........................................................................................144
Task Abortion.....................................................................................................146
Load Balancing ..................................................................................................147
Non-Cyclic Execution in Debug Mode ..............................................................149
Task Analysis.................................................................................................................150
Exploring the Interface.......................................................................................151
Modifying Task Execution Time........................................................................155
Error and Warning Categories............................................................................155
Search and Navigation...................................................................................................157
Search and Navigation Dialog............................................................................158
Search Settings ...................................................................................................159
Symbol and Definition .......................................................................................161
References ..........................................................................................................163
Navigation to Editors .........................................................................................168
Search and Navigation Settings..........................................................................168
Search Data ........................................................................................................172
Reports
...........................................................................................................172
Analog Input and Output Signal Handling ....................................................................173
Backup Media................................................................................................................176
3BSE040935-511
7
Table of Contents
Compact Flash ................................................................................................... 177
Secure Digital .................................................................................................... 177
Adding CF Card or SD Card to Hardware......................................................... 178
Saving Cold Retain Values on Files................................................................... 179
Downloading the Application to Removable Media.......................................... 181
Configuration Load ............................................................................................ 181
Upgrading Controller Firmware using Backup Media ...................................... 182
Restoring Formatted CF Cards to Original Size ................................................ 186
Compiler Switches ........................................................................................................ 187
Settings
.......................................................................................................... 187
Reports .......................................................................................................................... 190
Difference Report............................................................................................... 190
Source Code Report ........................................................................................... 194
Reports Generated at Download ........................................................................ 197
Portability Verification....................................................................................... 200
Performance Management............................................................................................. 200
Project Documentation.................................................................................................. 202
Objects and Types .............................................................................................. 204
Editor Items........................................................................................................ 204
Used Types......................................................................................................... 205
Section 2 - Alarm and Event Handling
Introduction ................................................................................................................... 207
Alarms and Events ............................................................................................. 208
Alarm and Event Library ................................................................................... 209
Process Alarm and Event Generation............................................................................ 209
Process Alarms and Events................................................................................ 210
Detection of Simple Events ............................................................................... 218
Built-in Alarm and Event Handling in Other Libraries ..................................... 219
External Time Stamps (S800 I/O)...................................................................... 222
External Time Stamps (PROFINET IO) ............................................................ 222
External Time Stamps (INSUM) ....................................................................... 224
Choose Alarm Handling Method for INSUM Alarms....................................... 229
8
3BSE040935-511
Table of Contents
System Alarm and Event Generation ............................................................................230
Controller Generated System Alarms and System Simple Events.....................231
User Generated System Alarms .........................................................................232
Handling Alarms and Events.........................................................................................232
Simple Events.....................................................................................................233
System Alarms and Events.................................................................................233
Time Stamps.......................................................................................................234
Alarm and Event Communication .................................................................................237
Subscriptions ......................................................................................................237
Configuration of OPC AE Communication – Overview....................................237
Buffer Configuration ..........................................................................................239
Local Printers .....................................................................................................240
Print Format........................................................................................................240
Sending an Alarm to the Application.................................................................242
Condition State Example....................................................................................243
Inhibit Example..................................................................................................244
Simple Event Examples .....................................................................................247
Alarm and Event Functions ...........................................................................................251
System Diagnostics ............................................................................................251
Acknowledgement Rules – State Diagrams .......................................................252
Section 3 - Communication
Introduction ...................................................................................................................257
Communication Libraries ..............................................................................................258
COMLI Communication Library .......................................................................258
INSUM Communication Library .......................................................................258
MB300 Communication Library........................................................................263
MMS Communication Library...........................................................................264
MODBUS RTU Communication Library ..........................................................265
MODBUS TCP Communication Library...........................................................265
Modem Communication Library........................................................................265
Siemens S3964 Communication Library ...........................................................265
SattBus Communication Library........................................................................266
3BSE040935-511
9
Table of Contents
MTM Communication Library .......................................................................... 266
Serial Communication Library .......................................................................... 267
TCP and UDP Communication Libraries .......................................................... 269
Supported Protocols ...................................................................................................... 271
Control Network............................................................................................................ 272
Network Redundancy......................................................................................... 272
Statistics and Information on Communication .................................................. 273
Variable Communication............................................................................................... 274
Access Variables ................................................................................................ 274
Communication Variables.................................................................................. 274
StartAddr .......................................................................................................... 275
Reading/Sending Data................................................................................................... 278
Connection Methods .......................................................................................... 279
Communication Concepts.................................................................................. 281
Fieldbus Communication .............................................................................................. 284
MMS Communication................................................................................................... 287
Section 4 - Online Functions
Introduction ................................................................................................................... 289
Online Editors ............................................................................................................... 290
Diagram Editor in Test Mode and Online Mode ............................................... 292
Dynamic Display of I/O Channels and Forcing ............................................................ 294
Scaling Analog Signals ................................................................................................. 296
Supervising Unit Status................................................................................................. 296
Find Out What is Wrong by Using HWStatus................................................... 297
AllUnitStatus ..................................................................................................... 298
Binary Channels................................................................................................. 298
Supervising Communication Variable Status................................................................ 299
Supervising Communication Variable Using :Status Notation.......................... 300
Supervising Communication Variable Using GetCVStatus............................... 300
Understanding the Complete Status Code ......................................................... 302
Status Indications .......................................................................................................... 304
Acknowledge Errors and Warnings ................................................................... 306
10
3BSE040935-511
Table of Contents
Tasks ............................................................................................................................306
Interaction Windows......................................................................................................307
Status and Error Messages.............................................................................................309
Search and Navigation in Online and Test Mode ..........................................................310
Project Documentation ..................................................................................................314
Section 5 - Maintenance and Trouble-Shooting
Introduction ...................................................................................................................317
Backup and Restore .......................................................................................................317
Introduction ........................................................................................................317
Backup
...........................................................................................................318
Restore
...........................................................................................................319
Files for Separate Backup ..................................................................................319
Controller Configuration ...............................................................................................320
Controller Settings in Controllers ......................................................................320
Error Handler Log Entries..................................................................................324
Trouble-Shooting...........................................................................................................325
General
...........................................................................................................325
Log Files ...........................................................................................................326
Crash Dumps for Analysis and Fault-Localization ............................................341
Remote Systems Information .............................................................................342
Diagnostics for Communication Variables.........................................................345
Analysis Tools ....................................................................................................351
System Diagnostics ............................................................................................353
Trouble-Shooting Error Symptoms ....................................................................358
Error Reports .................................................................................................................360
Appendix A - Array, Queue and Conversion Examples
Arrays ............................................................................................................................361
SearchStructComponent.....................................................................................363
InsertArray .........................................................................................................367
SearchArray........................................................................................................368
Queues ...........................................................................................................................372
3BSE040935-511
11
Table of Contents
Conversion Functions.................................................................................................... 376
DIntToBCD........................................................................................................ 376
BCDToDInt........................................................................................................ 377
ASCII
.......................................................................................................... 378
ASCII Conversion.............................................................................................. 380
Appendix B - System Alarms and Events
General .......................................................................................................................... 387
OPC Server – Software ................................................................................................. 388
OPC Server – Subscription ........................................................................................... 390
Controller – Software .................................................................................................... 392
Controller – Hardware................................................................................................... 424
Alarms and Events Common for all Units......................................................... 426
Unit Specific Alarm and Events......................................................................... 430
INDEX
12
3BSE040935-511
About This Book
General
This manual describes how to use the basic programming and configuration
functions that can be accessed via the Project Explorer interface.
The libraries described in this manual conform to the IEC 61131-3 Programming
Languages standard, except for control modules and diagrams, which are not
supported by this standard.
•
Section 1, Basic Functions and Components, describes all the basic functions
that are available via system functions, Basic library, and commands in the
Control Builder interface. This section also describes the type and object
concept, and how variables and parameters are used.
•
Section 2, Alarm and Event Handling, describes the types in the Alarm and
Event library and how to use them to add alarm and event functions to objects
that do not have alarm functionality built into them.
•
Section 3, Communication, describes the types in the Communication libraries
and how to use them to establish communication between controllers.
•
Section 4, Online Functions, describes Control Builder functions in online
mode.
•
Section 5, Maintenance and Trouble-Shooting, describes Control Builder
maintenance functions. It also describes how to write an error report, the
location of various log files, how to read these log files, and how to fix some
common problems.
•
Appendix A, Array, Queue and Conversion Examples contains some examples
on how to use queues and arrays, and how to convert numbers from one format
to another.
•
Appendix B, System Alarms and Events describes system alarms and system
simple events from a controller perspective.
3BSE040935-511
13
Document Conventions
About This Book
Document Conventions
Microsoft Windows conventions are normally used for the standard presentation of
material when entering text, key sequences, prompts, messages, menu items, screen
elements, etc.
Warning, Caution, Information, and Tip Icons
This publication includes Warning, Caution, and Information where appropriate
to point out safety related or other important information. It also includes Tip to
point out useful hints to the reader. The corresponding symbols should be
interpreted as follows:
Electrical Warning icon indicates the presence of a hazard which could result in
electrical shock.
Warning icon indicates the presence of a hazard which could result in personal
injury.
Caution icon indicates important information or warning related to the concept
discussed in the text. It might indicate the presence of a hazard which could
result in corruption of software or damage to equipment/property.
Information icon alerts the reader to pertinent facts and conditions.
Tip icon indicates advice on, for example, how to design the project or how to use
a certain function
Although Warning hazards are related to personal injury, and Caution hazards are
associated with equipment or property damage, it should be understood that
operation of damaged equipment could, under certain operational conditions, result
in degraded process performance leading to personal injury or death. Therefore,
fully comply with all Warning and Caution notices.
14
3BSE040935-511
About This Book
Terminology
Terminology
The following is a list of terms associated with Compact Control Builder. The user
must be familiar with these terms before reading this manual. The list contains
terms and abbreviations that are unique to ABB or have a usage or definition that is
different from standard industry usage.
Term/Acronym
Description
Application
Applications contain program code to be compiled and
downloaded for execution in a controller.
Control Builder
A programming tool with a compiler for control software.
Control Builder is accessed through the Project Explorer
interface.
Control Module (Type)
A program unit that supports object-oriented data flow
programming. Control modules offer free-layout
graphical programming, code sorting and static
parameter connections. Control module instances are
created from control module types.
Firmware
The system software in the PLC.
Hardware Description
The tree structure in the Project Explorer, that defines
the hardware’s physical layout.
IndustrialIT
ABB’s vision for enterprise automation.
Interaction Window
A graphical interface used by the programmer to interact
with an object. Available for many library types.
MMS
Manufacturing Message Specification, a standard for
messages used in industrial communication.
OPC/DA
An application programming interface defined by the
standardization group OPC Foundation. The standard
defines how to access large amounts of real-time data
between applications. The OPC standard interface is
used between automation/control applications, field
systems/devices and business/office application.
3BSE040935-511
15
Terminology
About This Book
Term/Acronym
16
Description
Process Object
A process concept/equipment such as valve, motor,
conveyor or tank.
Project Explorer
The Control Builder interface. Used to create, navigate
and configure libraries, applications and hardware.
Type
A type solution that is defined in a library or locally, in an
application. A type is used to create instances, which
inherit the properties of the type.
3BSE040935-511
Section 1 Basic Functions and Components
Introduction
Control Builder is a programming tool that contains:
•
Compiler
•
Graphical programming editors that provide graphical representation of the
whole logic.
•
Programming editors for IEC-61131 languages
•
Standard libraries for developing controller applications
•
Standard hardware types (units) in libraries for configuring the controller
The Control Builder tool also includes system firmware and common functions such
as control system templates and task supervision. Most of the application
development can be accomplished using the basic functions and components
presented in this section.
This section is organized in the following manner:
•
Control Project Templates on page 19 describes the different templates that can
be used to create a project.
•
Program Organization Units, POU on page 19 introduces the Program
Organization Unit (POU) concept.
•
System Firmware Functions on page 20 describes firmware functions included
in the system, which can be used in any application.
•
Hardware on page 22 describes the standard libraries for hardware types.
•
Basic Library for Applications on page 28 describes the objects of the Basic
library, which can be included in any project.
3BSE040935-511
17
Introduction
18
Section 1 Basic Functions and Components
•
Application Types and Instances on page 30 introduces the very important,
object-oriented, types and objects concept. This subsection also describes how
to add user defined types and how to create objects (instances) from types.
•
Variables and Parameters on page 69 describes how to use parameters and
variables to store and transfer values in the control system.
•
Library Management on page 109 describes how to work with libraries.
•
Hide and Protect Control Module Types, Function Block Types, Diagram
Types, and Data Types on page 126 describes how to hide and protect objects
and types, using the Hidden and Protected attributes.
•
Task Control on page 129 describes how to set up tasks to control the execution
of the applications.
•
Overrun and Latency on page 142 describes how to configure latency control
for the tasks.
•
Task Analysis on page 150 describes the Task Analysis tool that detects the
possible task overrun/latency problems in an application before its download to
the controller.
•
Search and Navigation on page 157 describes how to use the search and
navigation function to find all instances of a type or to find out where a certain
variable is used.
•
Analog Input and Output Signal Handling on page 173 describes how to enable
over and under range for input and output objects.
•
Backup Media on page 176 describes how to use the Backup Media as a
removable storage.
•
Compiler Switches on page 187 describes how to use Compiler Switches to
control the behavior of compiler.
•
Reports on page 190 describes the function of the Difference Report and
Source Code Report.
•
Performance Management on page 200 describes how to gather information of
the applications using the Compiler Statistics tool.
3BSE040935-511
Section 1 Basic Functions and Components
•
Control Project Templates
Project Documentation on page 202 describes how to use the Project
Documentation function to document standard libraries, user defined libraries,
and applications in MS Word format.
Control Project Templates
A control project template sets up the necessary features required to build a project.
The project consists of system firmware functions, basic library functions,
application functions and a pre-set of hardware functions.
The Compact Control Builder provides the following project templates:
•
AC800M
Template for normal use, and for running applications.
•
EmptyProject
Template that requires a minimum configuration, with only the System folder
inserted. This template is rarely used.
•
SoftController
Template for developing software for simulating applications without a
controller.
Program Organization Units, POU
The IEC 61131-3 standard describes programs, function blocks, and functions as
Program Organization Units (POUs). The Control Builder also considers
control modules and diagrams as POUs. All these units are helpful in organizing the
control project into code blocks, minimizing code writing, and optimizing the code
structure and code maintenance.
A POU is an object type that contains an editor to write code and declare parameters
and variables.
All POUs can be repeatedly used in a hierarchical structure, except for diagrams and
programs that can only be a 'top-level' POU, inside an application.
1.
3BSE040935-511
Right-click the project name, and select Refresh Project.
19
System Firmware Functions
Section 1 Basic Functions and Components
System Firmware Functions
All system firmware functions are stored in the System folder, which is located at
the top of the library branch (in Project Explorer).
The System folder is not a library, even though it is always shown in the library
branch, together with the libraries (Basic library, Icon library, etc.)
The System folder contains fundamental IEC 61131-3 data types and functions,
along with other firmware functions, which can be used in firmware in the
controller. They are all protected and automatically inserted via the selected control
system templates.
The System folder cannot be changed, version handled or deleted from a control
project.
The system firmware functions that can be used in the application depends on the
Firmware version. To upgrade the Firmware, replace the BasicHWLib with the
latest version.
Table 1 contains the System firmware data types and functions. Refer the Control
Builder online help for more information and description.
20
3BSE040935-511
Section 1 Basic Functions and Components
System Firmware Functions
To access the detailed online help and how-to-do instructions for a system
firmware function, select the data type or function, and press the F1 key.
Table 1. System Function Overview
System Functions
Examples
Simple Data Types
bool, dint, int, uint, dword, word, real, etc.
Structured Data Types
time, Timer, date_and_time, etc.
Common Library Data
Types
Open structured data types like, BoolIO, DintIO,
DwordIO, RealIO, HWStatus, SignalPar, etc.
Bit String Operations
and, or, xor, etc.
Relational and Equality
Functions
Equal to, Greater than, etc.
Mathematical Functions
Trigonometric, Logarithmic, Exponential and
Arithmetic Functions.
Data Type Conversion
Conversion of bool, dint, etc.
String Functions
Handles strings like, inserts string into string,
deletes part of a string, etc.
Exception Handling
Functions for handling zero division detection
integer and real values.
Task Functions
SetPriority, GetPriority, etc,. Handles the priority of
the current task.
System Time Functions
Exchanging time information between different
systems.
Timer Functions
Functions to Start, Stop and Hold Timers.
Random Generation
Functions
Functions for generating random numbers or values.
Variable Handling Functions Reads and writes variable values.
Provides status information of communication
variables.
3BSE040935-511
21
Hardware
Section 1 Basic Functions and Components
Table 1. System Function Overview (Continued)
System Functions
Examples
Array Functions
Handles arrays.
Queue Functions
Handles queues.
Hardware
All hardware is defined as hardware types (units) in Control Builder. The hardware
types reflect the physical hardware in the system.
Hardware types are organized and installed as libraries. This makes it possible to
handle hardware types independently, with the following advantages:
•
Since the libraries are version handled, different versions of the same hardware
type exist in different versions of the library. This makes it easy to upgrade to
newer system versions and also allows coexistence of new and old hardware
units.
•
The new versions of a library (along with the hardware types) can be easily
delivered and inserted to the system.
A number of standard libraries with hardware types are delivered with the
system. A standard library is write protected and cannot be changed
•
22
Only used hardware types allocate memory in the controller.
3BSE040935-511
Section 1 Basic Functions and Components
Standard System Libraries with Hardware
Standard System Libraries with Hardware
The standard system libraries with hardware are delivered by the system. Table 2
describes the standard libraries with hardware.
Table 2. Standard system libraries with hardware
Library
Description
ABBDrvFenaCI871HwLib
Optional device for ABB drives, which enables the
connection of the drive to a PROFINET IO
network.
ABBDrvNpbaCI854HwLib
ABB Drive NPBA and subunits for PROFIBUS
ABBDrvRetaCI871HwLib
Optional device for ABB drives, which enables the
connection of the drive to a PROFINET IO
network.
ABBDrvFpbaCI854HwLib
ABB Drive FPBA and subunits for PROFIBUS DP
ABBDrvRpbaCI854HwLib
ABB Drive RPBA and subunits for PROFIBUS
ABBMNSiSCI871HWLIB
Motor control center solution that can be used in
PROFINET IO network.
ABBPnl800CI854HwLib
ABB Panel 800 for PROFIBUS
ABBProcPnlCI854HwLib
ABB Process Panel for PROFIBUS
BasicHWLib
Basic controller hardware types for AC 800M and
SoftController
CI853SerialComHwLib
RS-232C serial communication interface
CI854PROFIBUSHwLib
Communication interface PROFIBUS DP-V1
CI855Mb300HwLib
Communication interface MasterBus 300
CI856S100HwLib
Communication interface S100 I/O system and
S100 I/O units
CI857InsumHwLib
Communication interface INSUM
CI858DriveBusHwLib
Communication interface DriveBus
3BSE040935-511
23
Standard System Libraries with Hardware
Section 1 Basic Functions and Components
Table 2. Standard system libraries with hardware
Library
Description
CI865SattIOHwLib
Communication interface for remote I/O
connected via ControlNet
CI867ModbusTcpHwLib
Communication interface MODBUS TCP
CI868IEC61850HwLib
Communication interface IEC 61850
CI869AF100HwLib
Communication interface for AF 100
CI871PROFINETHwLib
Communication interface CI871
CI872MTMHwLib
Communication interface for MOD5-to-MOD5
CI873EthernetIPHWLib
Communication interface EtherNet/IP
ModemHwLib
Modem unit
PrinterHwLib
Printer unit
S200IoCI854HwLib
S200 adapter and S200 I/O units for PROFIBUS
S800CI830CI854HwLib
S800CI840CI854HwLib
S800CI801CI854HwLib
S800 adapters and S800 I/O units for PROFIBUS
S800IoModulebusHwLib
S800 I/O units for ModuleBus
S900IoCI854HwLib
S900 adapter and S900 I/O units for PROFIBUS
SerialHwLib
COMLIHWLib
ModBusHWLib
S3964HWLib
TCPHwLib
UDPHwLib
Hardware libraries for direct controller
communication with external hardware, using
different communication protocols
For a complete list of the hardware types in the standard libraries, see Control
Builder online help.
24
3BSE040935-511
Section 1 Basic Functions and Components
Customized Hardware Types
Customized Hardware Types
Customized hardware types can be created in user-defined libraries, using the
Device Import Wizard. This is useful when the hardware types found in the standard
system libraries or the Device Integration Library are not sufficient.
The Device Import Wizard imports a device capability description file (for example,
a *.gsd file), converts the file to a hardware type, and inserts the type into the userdefined library (See Create Libraries on page 114. Also see Device Import Wizard
on page 120 and Supported Device Capability Description Files on page 120).
In exceptional cases, it may be relevant to insert individual external customized
hardware types to a user-defined library (for example, to use a specific hardware
type, which have been converted and used in an earlier version of Control Builder).
The Source Code Report can be used to view the hardware types loaded in the
project. See Source Code Report on page 194.
Configuring the Controller
Before configuring the controller:
1.
Insert the libraries, which contain the hardware types (units) to be used in the
controller configuration, into the control project.
2.
Connect the libraries to the controller.
See Connect Libraries on page 110 for information on how to insert and connect
libraries.
Add Unit to Hardware in Controller Configuration
Perform the following steps to add a new hardware unit into the controller
configuration in Project Explorer:
1.
Make sure that the library, which contains the hardware type to be added, is
inserted to the project and connected to the controller.
2.
Right-click the unit to which a new hardware unit is to be added, and select
Insert Unit to open the Insert Unit dialog.
3BSE040935-511
25
Configuring the Controller
Section 1 Basic Functions and Components
Figure 1. Insert Unit dialog for inserting hardware in a controller configuration
.
It is not possible to select Insert Unit if the unit cannot contain any sub-units or if
no more positions are available.
3.
Expand the relevant library folder under Connected Libraries, and select the
hardware type to be included.
The Libraries in Project contains libraries that are added to the project but not
yet connected to the controller. If a unit is selected under Libraries in Project,
the option to connect the library to the controller appears.
4.
From the Position drop-down list, select a position for the hardware unit.
By default, the first available position is chosen. If no more positions are
available, the Position drop-down list is empty and the Insert button is
disabled.
26
3BSE040935-511
Section 1 Basic Functions and Components
5.
Configuring the Controller
For units supporting redundancy, check the Enable redundant mode check
box, and select a position for the backup unit.
Some redundant units have a fixed position offset. For these units, the backup
position is automatically calculated, and the user cannot change this position.
Click Previous or Next to navigate to another unit in the Project Explorer
hardware tree.
6.
In the Name field, enter a name for the unit. After the unit is inserted in the
hardware tree, this name appears along with the name of the selected type.
7.
Click Insert to apply the changes made.
8.
Click Close to close the dialog.
To rename the unit after it is inserted, right-click the unit, and select
Rename Unit.
Figure 2. Example of a hardware tree with a name for the AI820 unit
Replace Hardware in a Controller Configuration
Perform the following steps to replace a hardware unit in a controller configuration:
1.
Make sure that the library, which contains the hardware type to be added, is
inserted to the project and connected to the controller.
2.
Right-click on the unit to be replaced, and select Replace Unit to open the
Replace Unit dialog.
The Replace Unit dialog works in the same way as the Insert Unit dialog, except
that it is not possible to change the position of the unit in the Replace Unit dialog.
3BSE040935-511
27
Basic Hardware
Section 1 Basic Functions and Components
While the hardware unit is being replaced in a controller configuration, the system
retains the settings and connections, and also retains the units in the existing
subtrees. For example, replacing a CPU with a similar one can be done without any
connection loss or data loss.
Basic Hardware
The BasicHwLib contains standard system hardware types that are used when
configuring the AC 800M controller and SoftController. The standard system
hardware types are installed along with the Control Builder.
Only one version of BasicHwLib can be connected to a controller.
The BasicHwLib contains the following basic controller hardware:
•
•
•
•
•
•
•
•
Controllers (AC 800M and SoftController)
Compact Flash (CF) units
Secure Digital (SD) units
CPU units (PM8xx and CPU)
Ethernet links, serial Com ports, and PPP ports
ModuleBus
IP
IAC MMS
Basic Library for Applications
The Basic library contains basic building blocks for AC 800M control software. It
contains data types, function block types and control module types with extended
functionality, designed by ABB.
The contents inside the Basic library can be categorized as follows:
28
•
IEC 61131-3 Function Block Types.
•
Other Function Block Types.
•
Control Module Types.
3BSE040935-511
Section 1 Basic Functions and Components
Basic Library for Applications
For a complete list of data types, function block types, and control module types
in the Control Builder standard libraries, refer to the manual Compact 800
Engineering Compact Control Builder AC 800M Configuration (3BSE040935*)
Table 3. Basic Library Overview
Basic Functions
Examples
IEC 61131-3 Function Block Standard bistable function block types (SR, RS).
Types
Standard edge detection function block types
(R_TRIG, F_TRIG).
Standard counter function block types (CTU, CTD,
etc.)
Standard timer function blocks type (TP, TOn, etc.)
Other Function Block Types ACOF (Automatic Check Of Feedback) functions,
converters, pulse generators, detectors, system
diagnostics, timers, compares, etc.
Control Module Types
3BSE040935-511
Connection module for group start sequences
(GroupStartObjectConn), ControlConnection inputs
and outputs, Error Handler, Forced Signals, and
acknowledgment of ISP values for communication
variables.
29
Application Types and Instances
Section 1 Basic Functions and Components
Application Types and Instances
Types and instances form the basis of the application structure. This subsection
contains an overview of the following:
30
•
The type and instances concept, see Types and Instances - Concept on page 31.
•
The editors that are used to create and configure the types, see Define a Type in
the Editor on page 32.
•
Important differences between control module types, function block types, and
diagram types, see Control Module Types, Function Block Types, and Diagram
Types on page 41.
•
How to create types directly in an application, and how to create types in the
library for re-use in applications. See Types in Applications on page 43 and
Types in User defined Library on page 44.
•
How to create complex types so that they are flexible enough for future
upgrades, see Modify Complex Types on page 45.
•
What to consider and what to set up before creating types and using them, see
Decisions When Creating Types on page 53.
•
How to create objects from types and connect the object to the surrounding
application or type, see Create and Connect Instances on page 54.
•
Details about diagrams and diagram types, see Diagram and Diagram Types on
page 46.
•
How different objects are executed, see Function Block Execution on page 59,
Control Module Execution on page 62, and Diagram Execution on page 63.
•
How to use single control modules as containers for control modules, see
Single Control Modules on page 65.
3BSE040935-511
Section 1 Basic Functions and Components
Types and Instances - Concept
Types and Instances - Concept
Types are used to represent motors, valves, tanks, etc. that are located in a plant
area, and then turn them into manageable units in a control project (for example,
motor types, valve types, mixer types, and so on). Instances are created based on
each of these types.
A type is the source (the blue print) for a unit (motor, valve, tank, etc), while an
instance represents the unit(s) in libraries and applications. There is an inherited
mechanism between a type and all its instances, where all instances have the same
performance as the type, and changes performed in the type affect all instances
simultaneously.
A type is a generic solution, which can be used by many instances, and contains
programming code with variables, functions, connection parameters (textual and
graphical), graphical instances, and formal instances1.
Figure 3 shows the relationship between a type located in a library and two
instances created in an application.
type
If
A = 10then
B := A+1;
end_if;
Library
Application instance1
instance2
A
3
A
10
B
7
B
11
Figure 3. Relationship between a type and two instances.
The type contains the code, whereas each instance contains a list of computed
variable values. The instance does not contain any code; it uses the code inside the
type for manipulating its own local variable values.
1.
3BSE040935-511
Formal instances are instances of another type located inside a type. These, along with instances based on that
type are executed in applications.
31
Define a Type in the Editor
Section 1 Basic Functions and Components
A type is always static and cannot run by itself in applications. To execute the code
inside the type, an instance based on the type (an instance) must be created. The
instance executes the code located inside the type. To create an instance, point to a
type either in a library or in an application.
All instances based on the same type have the same characteristics, which means
they have equal access to everything in the type. An instance does not contain a
programming editor or code blocks; hence the code cannot be written inside an
instance. All logic must be created in the type.
The allocated memory for creating a type solution (for example, a motor type
solution that contains one motor type and 20 motor instances) is distributed mainly
on the programming code inside the type. Therefore, the cost (allocated memory)
for each new instance (motor) is very small, compared to the type itself. The
instance only needs to allocate memory for variables, as the code is located and
executed from the type. However, the number of instances are relevant for
considering the total CPU memory.
It is easier to update the application while working with newer version of types,
since the inherited mechanism takes care of changes that often concern hundreds of
instances. A code change (for example, declaring additional connection parameters)
can be done once for the type, and this change is inherited by all instances
simultaneously.
Control Builder also contains a number of structured data types. For more
information, refer to the Application Programming manual. A type described in this
sub-section is a function block type, a control module type, or a diagram type.
Define a Type in the Editor
Select the type from Project Explorer and open the corresponding Editor to declare
the necessary parameters for the type.
The editor of a type contains several declaration panes that can be opened from the
following tabs:
•
•
•
32
Parameters
Variables
Function Blocks
3BSE040935-511
Section 1 Basic Functions and Components
•
•
Define a Type in the Editor
Control Modules (only for diagram type editors)
Diagrams (only for diagram type editors)
Apart from the declaration panes, the editor contains:
•
Programming editor for programming the code using IEC-61131 languages
(see Figure 10).
•
Graphical editor called CMD Editor (only for control module types, see
Figure 13).
•
Graphical programming editor for FD (Function Diagram) (only in diagram
type editor, see Figure 12)
Declaration Pane for Parameters
To open the declaration pane for parameters, double-click the type (to open the
editor), and then select the Parameters tab.
Figure 4 shows the editor for My_MotorType, with the declaration pane for
parameters selected. These parameters can be used for connecting variables outside
the instance.
Figure 4. Declaration pane for creating connection parameters
Declaration Pane for Local Variables
To open the declaration pane for variables, double-click the type (to open the
editor), then select the Variables tab. If the editor is already open, simply select the
Variables tab.
Figure 5 shows the declaration pane for creating local variables inside the type. The
local variables can be used by the code inside the type.
3BSE040935-511
33
Define a Type in the Editor
Section 1 Basic Functions and Components
Figure 5. The declaration pane for creating local variables
Declaration Pane for External Variables
External variables are pointers to global variables. An instance can declare an
external variable locally and then use this variable to access the value in a global
variable located in the application. External variables and global variables are
discussed in External Variables on page 81.
Declaration Pane for Communication Variables
Communication variables are declared in top level Diagram editor, Program editor,
or top level Single Control Module editor. For details about communication
variables, see Communication Variables on page 86.
Figure 6 shows the declaration pane for communication variables in a Diagram
editor.
Figure 6. Declaration pane for communication variables
34
3BSE040935-511
Section 1 Basic Functions and Components
Define a Type in the Editor
Declaration Pane for Function Blocks
To open the declaration pane for function blocks, double-click the type (to open the
editor), and select the Function Blocks tab. If the editor is already open, simply
select the Function Blocks tab.
Figure 7 shows the declaration pane for declaring function blocks inside the type.
Figure 7. Declaration pane for creating function blocks inside a type
Enter the name of the function block in the Name column, and select the cell in the
Function Block Type column. Press CTRL+J to open a context menu with all
function block types available.
Connect all libraries with the required function blocks types to the application.
Only then, the available function block types are listed in the context menu
(CTRL+J)
Declaration Pane for Control Modules
To open the declaration pane for control modules, double-click the diagram or
diagram type (to open the editor), and select the Control Modules tab. If the editor
is already open, select the Control Modules tab.
Figure 8 shows the declaration pane for declaring control modules inside the
diagram or diagram type.
3BSE040935-511
35
Define a Type in the Editor
Section 1 Basic Functions and Components
Figure 8. Declaration pane for creating control modules inside a diagram type
Enter the name of the control module in the Name column, and select the cell in the
Control Module Type column. Press CTRL+J to open a context menu with all
control module types available.
Connect all libraries with the required control module types to the application.
Only then, the available control module types are listed in the context menu
(CTRL+J).
Declaration Pane for Diagrams
To open the declaration pane for diagrams, double-click the diagram type or
diagram (to open the editor), and select the Diagrams tab. If the editor is already
open, select the Diagrams tab.
Figure 9 shows the declaration pane for declaring diagrams inside the diagram type
or diagram.
Figure 9. Declaration pane for creating diagrams inside a diagram type
36
3BSE040935-511
Section 1 Basic Functions and Components
Define a Type in the Editor
Enter the name of the diagram in the Name column, and select the cell in the
Diagram Type column. Press CTRL+J to open a context menu with all diagram
types available.
Connect all libraries with the required diagram types to the application. Only
then, the available diagram types are listed in the context menu (CTRL+J).
Code Pane for Control Module Types and Function Block Types
The code pane in the editor for programs, control module types, function block
types, and single control modules supports five programming languages that
conforms to the IEC 61131-3 standard. The code pane is always active, and can be
accessed irrespective of which tab is selected (parameters, variables, function
blocks, etc.).
The code pane can be expanded using more code blocks for structuring the code.
These code blocks are then executed either in a predetermined order as decided by
the compiler (control modules), or from left to right (function blocks).
Figure 10 shows a part of the code pane of a control module type editor. This code
block uses Structured Text (ST) as the language. This editor contains two code
blocks: Control and Start_Code.
Code blocks
Figure 10. A code pane with two code blocks.
3BSE040935-511
Code pane
37
Define a Type in the Editor
Section 1 Basic Functions and Components
A brief description of code blocks in general and Start_ code blocks :
•
Code blocks are very useful for structuring the code. Dividing the
programming code into a number of code blocks, improves the overall code
structure and readability. Examples of code blocks are Control, Object Error,
Operators, etc.
Code block names cannot contain certain characters. See Online help for
information on characters that cannot be used in code block names.
•
There is no limit to the number of code blocks that can be created in a type.
Create only the required number of code blocks, since each code block affects
the memory consumption and the execution time of the type.
•
Start_
A code block with the prefix Start_ is always executed first in an application
and only once, at the application startup (after a warm and cold start, but not
after a power failure).
The Start_ code block is valid only for single control modules and control module
types.
This code block must be used for initiating alarm strings, converting project
constants to strings, etc.
However, there are some limitations while using the Start_ code block:
–
It is not suitable to place functions, function blocks, etc, in a Start_ code
block.
–
It is valid only for the code blocks in control modules, and not for the code
blocks in SFC (Sequential Function Chart).
–
The FirstScanAfterApplicationStart function must not be used in the
block.
–
Function blocks for communication must not be used in the block.
If the application contains a very large chunk of code that has to be run in the first
scan (for example, alarms in the Start_ code block), the execution time can be so
high that overrun occurs. This leads to the eventual shut-down of the controller.
38
3BSE040935-511
Section 1 Basic Functions and Components
Define a Type in the Editor
Code Block Context Menu
Right-click a code block tab to access the code block context menu.
Figure 11. Code block context menu
Graphical Code Pane for Diagram Types
The code pane in the editor for diagram type supports the FD (Function Diagram)
language. The FD code block in this editor allows mixing of functions, function
blocks, control modules and other diagrams, through graphical connections, to
create the logic. Variables and parameters can also be connected graphically. This
represents a complete graphical overview of the whole logic.
The FD code block is always active, and can be accessed irrespective of which tab is
selected in the declaration pane (parameters, variables, function blocks, control
modules or diagrams).
The logic created in the default FD code block can be expanded using optional ST
and SFC code blocks, which can be invoked in the FD code block or sorted
separately.
To open this editor, right-click the diagram type, and select Editor. Figure 12 shows
an example logic created in the FD code block of diagram type editor.
3BSE040935-511
39
Define a Type in the Editor
Section 1 Basic Functions and Components
Figure 12. Example logic created in the graphical code pane of diagram type editor
Graphical Editor - CMD Editor
The graphical editor, Control Module Diagram Editor (CMD Editor) is also a
combined editor for drawing and programming. The term ‘diagram’ refers to the
graphical view of control modules and connections.
Use this editor to create and edit control modules, code, and graphics, and to
connect variables and parameters.
To open the CMD Editor, right-click the control module type
and select CMD
Editor. Figure 13 shows part of the graphical editor (CMD Editor).
40
3BSE040935-511
Section 1 Basic Functions and Components
Control Module Types, Function Block Types, and
Figure 13. Graphical objects created in the CMD Editor.
The drawing functions in the CMD editor include basic auto shapes (lines,
rectangles, etc.), ready-to-use interaction instances (option buttons, check boxes,
etc.), and composite instances (trend graphs, string selectors, etc.). The graphical
instances are dynamic, that is, with changing variable values, the points move,
colors change, and numerical values are presented.
Control Module Types, Function Block Types, and Diagram Types
A type can be a control module type, a function block type or a diagram type. The
usage of different types can be mixed. For example, a control module can be created
inside a function block type (to add graphics), or a function block can be created
inside a control module type (to execute a list of basic functions). In a diagram type,
it is possible to create function blocks, control modules, and diagrams, to define the
entire logic.
3BSE040935-511
41
Control Module Types, Function Block Types, and Diagram Types
Section 1 Basic Functions and
Table 4. Differences between types
Property
Differences
Diagram Type
(supports mixing
Function Block Type Control Module Type function blocks, control
modules, and nested
diagrams)
Container POU
inside the
application
Programs, Diagrams
or Single Control
Modules
Diagrams or Single
Control Modules
Diagrams
Graphical
connections
between objects
Yes
Yes
Yes, including graphical
connection to
parameter/variable
objects.
Code sorting
No
Yes
Yes.
All code blocks, in control
modules inside the
diagram type, are sorted
together with the code
blocks outside the diagram
type in the container
Diagram.
Execution
42
Control modules are
Function blocks are
executed only once
executed from code.
Therefore, a function per scan.
block is executed once
or several times per
scan, or it is not
executed at all.
The execution order
shown in the diagram is
followed. Codeblocks from
control modules are sorted
into the diagrams
execution order according
to control module sorting
rules (writing into a
variable is sorted before a
read).
3BSE040935-511
Section 1 Basic Functions and Components
Types in Applications
Additionally, the following properties apply to function block types:
•
•
Parameter values on function block types are copied (except In_Out parameters
and parameters having by_ref attribute, see Function Block Execution on page
59).
Function block types are required when using extensible parameters (see
Extensible Parameters in Function Blocks on page 107).
The choice between control module types, function block types, and diagram types
depends on the context and environment. For guidelines about the use of control
modules, function blocks and diagrams, refer to the Application Programming
manual.
Types in Applications
Creating a type in an application is the quickest and easiest way to get started.
Before creating types in an application, no new libraries need to be created; use the
available methods like connect libraries, create user defined data types, and select
the object type to use (see Decisions When Creating Types on page 53). However, if
a type is created directly in an application, it can only be used inside that
application.
Figure 14. Types created under an application
To gain access to standard libraries (or user defined libraries), insert them into the
control project (see Library Management on page 109), and connect them to the
application. This allows the creation of instances in the application, from existing
types in the connected libraries.
3BSE040935-511
43
Types in User defined Library
Section 1 Basic Functions and Components
Types in User defined Library
The advantage of creating types inside a library, instead of creating them directly in
an application, is the possibility to re-use them in other applications. If the types are
created in a library, all the necessary functionality can be stored in this library. The
library can then be connected to any application.
If a new library is created, user defined types can be created in that library (Compact
Control Builder does not allow creation of types in a standard library).
Functionality from the
Control libraries
Type
Figure 15. A Type (MyControlLoop) created in MyTypeLib library. This example
shows a control loop created as a diagram type, while the components are readymade instances from the standard libraries
44
3BSE040935-511
Section 1 Basic Functions and Components
Modify Complex Types
Modify Complex Types
This subsection describes a use case where it is preferable to copy two types, instead
of keeping a single and very large type in a library.
Refuse Incinerator Type - Problem
In this example, assume that a plant area has two identical refuse incinerators.
A type solution like this is manageable if a Refuse Incinerator type is created in a
library with several underlying types. This type can then be re-used twice (as two
objects), in two separate applications, by connecting the library to each application.
The following are the examples of underlying types inside the Refuse Incinerator
type:
•
A Feeder type containing 10 conveyors.
•
A Combustion type.
•
An Ash Handling type.
•
A Flue Gas type.
After building the Refuse Incinerator type in the library, connect the library to both
Application_1 and Application_2. This helps in creating an Incinerator1 instance in
Application_1 and an Incinerator2 instance in Application_2.
If the Incinerator2 instance running in Application_2 suddenly needs an individual
change (for example, 20 conveyors instead of 10 conveyors), edit the library and
change the Feeder type inside the Refuse Incinerator type. But, changing anything
inside the Refuse Incinerator type affects both incinerators due to the type and
instance inherit mechanism.
By changing the Feeder type to include 20 conveyors, both the Incinerator instances
are changed suddenly to contain 20 conveyors, which is not the intended use.
3BSE040935-511
45
Diagram and Diagram Types
Section 1 Basic Functions and Components
Refuse Incinerator Type - Solution
To avoid the problem, once the type is ready, consider the possible individual
(instance) changes in the future. If an individual instance needs to be changed, copy
the type on the highest type level (in this example, Refuse Incinerator Type1 and
Refuse Incinerator Type2).
Create an Incinerator10 instance in Application_1, based on Refuse Incinerator
Type1, and then create an Incinerator20 instance in Application_2, based on the new
type copy, Refuse Incinerator Type2. This increases the memory consumption in the
controller, but allows individual changes. For example, the number of conveyors in
the feeder for one of the applications can be changed, without affecting the other.
Diagram and Diagram Types
Diagrams are created under an application, and diagram types (which can be reused
as instances in a diagram) are created under a library or under the same application
as the diagram.
The FD code blocks in diagrams and diagram types allow mixing of functions,
function blocks, control modules, and other diagrams, and graphically connect them
to achieve a particular logic.
Figure 16 shows the workflow for using diagrams and diagram types.
46
3BSE040935-511
Section 1 Basic Functions and Components
Diagram and Diagram Types
Figure 16. Workflow for using Diagrams and Diagram Types
3BSE040935-511
47
Diagram and Diagram Types
Section 1 Basic Functions and Components
Figure 17 shows the editor for a diagram POU under an application.
Figure 17. Editor for Diagram POU
The diagram editor consists of declaration pane and code pane. The code pane
contains a grid area where you add the objects and create graphical connections.
The editor for diagram type also looks similar.
The editor for a top level diagram (under the application) differs from a Program
editor in following ways:
•
The first code tab is always a FD language tab.
•
Additional code block tabs can be created, but only for ST and SFC.
•
Two additional tabs – Control Modules and Diagrams – are available in the
declaration pane.
The editor for a diagram type (under the application or library) differs from a
diagram editor in following ways:
48
•
There is a Parameter tab instead of a Communication Variables tab in the
declaration pane.
•
There are no I/O Address or Access Variables columns in the Variables tab.
3BSE040935-511
Section 1 Basic Functions and Components
Diagram and Diagram Types
The diagram editor or diagram type editor has one mandatory FD code block.
Only one FD code block is allowed within this POU. It is allowed to have several
optional ST and SFC code blocks in the diagram editor or diagram type editor.
Figure 18 shows the editor for a diagram after it is edited (to create an example
logic).
3BSE040935-511
49
Diagram and Diagram Types
Section 1 Basic Functions and Components
Figure 18. Editor for diagram POU with an example logic created
50
3BSE040935-511
Section 1 Basic Functions and Components
Diagram and Diagram Types
Characteristics of Diagrams and Diagram Types
The following are the main characteristics of diagrams and diagram types:
•
A diagram or diagram type can contain other diagrams (which are the instances
of other diagram types), in addition to functions, function blocks, and control
modules.
•
The objects inserted in the diagram editor or diagram type editor can be
connected graphically through ports, to create the logic.
•
The port of an object inserted in the diagram editor or diagram type editor can
be connected to variable by entering the name of the variable or by graphically
connecting the port to the variable object.
•
The FD code block in the editor also supports Split blocks and Join blocks to
work with objects having structured data types:
–
A Split block splits the structured data type variable, connected as its
input, to its components that are displayed as output connection ports.
These output connection ports can be connected to variables based on the
data types.
–
A Join block displays input connection ports, which are the components of
the structured data type, and these can be connected to variables. The
output connection port is connected to the structured data type variable.
Split and Join blocks does a copy of the variable in run-time. To avoid a copy,
create a variable and make the components visible, or do component connections
directly.
Split and Join blocks must not be used if the structured data type has components
with reverse attribute.
For the Split block, if reverse components are used, a change in the extracted
(split) data of a reverse component does not result in a change of this component
in the structured variable. For the Join block, if reverse components are used, it is
not possible to write to an out variable using Join, even if the attribute is reverse.
•
3BSE040935-511
The FD code pane supports creation of additional pages for adding more
objects and connects the objects graphically across pages. This helps to extend
the logic from the default page.
51
Diagram and Diagram Types
52
Section 1 Basic Functions and Components
•
The logic created in the FD code pane can be extended through connections to
other ST and SFC code blocks in the editor.
•
The FD logic can be extended across different applications by using
communication variables declared in the diagram editor. These variables
support cyclic communication between the top level diagrams, top level
single control modules and programs in different applications.
3BSE040935-511
Section 1 Basic Functions and Components
Decisions When Creating Types
Decisions When Creating Types
This subsection describes the decisions to be made about the types before
programming the code, and declaring parameters and variables. Many functions and
type solutions have been developed already, and the Control Builder helps to set up
and access these options before programming. Read more about design analysis in
the Application Programming manual.
The following decisions must be made before creating the types:
•
Whether there is a need to create instances in user defined type(s).
These types are based on other types located in external libraries. In that case,
those external libraries must be connected to the library or application.
•
Whether there is a need to create self-defined structured data types for passing
parameters through several layers of instances.
The data types are automatically connected to the library or application.
Structured data types are often useful in more complex type solutions, with a
deep hierarchical structure.
•
Whether a function block type or a control module type or a diagram type
should be used.
–
If the code is programmed in the Program POU1 only, select
function block types.
–
If a graphical editor is preferred for programming the code, and automatic
code sorting is also preferred, select control module types.
–
If a graphical editor is preferred for programming the code, and automatic
code sorting as well as mixing of functions, function blocks, control
modules and nested diagrams are also preferred, select diagram types.
This helps you to overcome the limitations when using a single type.
For information on how to access these methods, refer to the Control Builder
online help. Select one of the folders in Project Explorer and press F1.
1.
3BSE040935-511
See Program Organization Units, POU on page 19.
53
Create and Connect Instances
Section 1 Basic Functions and Components
Create and Connect Instances
An instance is a function block, control module or diagram, based on a type.
Each time a new instance is created, the Control Builder prompts for a type. The
type can be located in an inserted library (inserted into the control project), user
defined library, or directly in an application. In any case, a type and its location must
always be selected.
Once the type is selected, connect the connection parameters.
Figure 19 shows the creation of an instance (Pump10) based on My_MotorType,
which is a diagram type located in the application. The instance needs the location
(Application_1) and the type (My_MotorType).
54
3BSE040935-511
Section 1 Basic Functions and Components
Create and Connect Instances
Figure 19. Creating instance of a diagram type in Diagram editor
3BSE040935-511
55
Create and Connect Instances
Section 1 Basic Functions and Components
Connections Using Parameters
The instances can be connected either through graphics or through text, using the
parameters in their respective types.
Control Modules
For control modules (instances of control module types), graphical connections are
done directly in the Control Module Diagram (CMD) editor and textual connections
are implemented in the Connection editor.
Diagrams
For diagrams (which support instances of diagram types, function block types, and
control module types), both graphical connections and textual connections of
instances are done directly in the FD code block of the diagram editor.
Graphical Connections in CMD Editor
Graphical nodes and graphical connections in CMD editor connects the control
modules effectively.
The control module parameters, which can be graphically connected, contains
NODE in the beginning of the parameter description. This is the standard for all
control modules located inside the standard libraries.
Nodes for graphical connections can also be created for self-designed control
modules. Graphical connections are suitable for obtaining a comprehensive view of
main flows, for example, in a PID controller or for group start of several motors.
Figure 20 shows three graphical connections for group starting motors. The
modules are connected using the Graphical Connection function (located in the
CMD Editor).
56
3BSE040935-511
Section 1 Basic Functions and Components
Create and Connect Instances
2
1
3
Figure 20. Two motor instances that have been graphically connected with a Start
and Next instance located in the Group Start library. The circles symbolize the
connection nodes
Textual Connection for Control Modules
To open the Connections editor via the Connections entry, right-click the
control module (instance of control module type) and select Connections.
Parameters can be connected to the actual variables presented in the Connections
editor. Textual connection is the only way to connect parameters when the control
module is subordinate to a function block, since there are no surrounding graphics.
It is not possible to connect the same parameter both graphically and textually.
3BSE040935-511
57
Create and Connect Instances
Section 1 Basic Functions and Components
Connect an instance of Control Module in Connections Editor
The Connections editor is a parameter/variable interface between the instance and
its closest surrounding. The Connections editor displays the parameters that are
declared in the type, with reference to the control module instance, and connects the
surrounding parameters/variables to the instance.
If a control module instance is created in an application (see Figure 21), then the
application can be seen as the closest surrounding, and the variables in the
application must be connected to the instance.
If a control module instance is created in a type (located in a library), then the type
can be seen as the closest entity, and parameters/variables in the type must be
connected to the instance.
To connect the parameters to instances located several hierarchical layers away
(not the closest), use structured data types that simplifies the connections (instead
of passing corresponding parameters). For more information on structured data
types, refer to the Compact 800 Engineering Compact Control Builder AC 800M
Planning (3BSE044222*)
A Motor Type
FB1
OUT1
Name
Code
Application
motor object
appfb1
‘PumpMotor’
FB1
OUT1
appout1
Name
surrounding area
58
3BSE040935-511
Section 1 Basic Functions and Components
Function Block Execution
Figure 21. A control module instance connected to variables in an application. The
application is the ‘surrounding area’ with the variables appfb1, Name (initial value
‘PumpMotor’) and appout1 connected to the instance.
In Figure 21, the connection parameters for the motor instance connect the
parameters (FB1, Name and OUT1) to the variables (appfb1, appout1, Name; Name
has the initial value PumpMotor) that have been declared in the application.
Function Block Execution
There are three types of function block parameters: In, Out, and In_out.
The input and output parameters are passed by value, which means that the function
block creates copies of each variable value, before and after the function block is
executed. The In_Out parameters are passed by reference, which means only a
reference to the actual variable outside the function block is passed to and from the
function block.
Input parameters create a copy of each variable before the function block executes,
and the output parameters create a new copy after the function block is executed and
pass the new values to the surrounding variables outside the function block.
For complex data types and strings, a reference to the data instance can be passed in
the function block call. This is achieved by setting the attribute of the parameter to
by_ref.
surrounding area (Program or in a type)
before execution
var
Function block
var’
code
In
var’’
after execution
Out
var
Figure 22. In and Out parameters for a function block. This example illustrates how
In and Out parameters copies the variable (var).
3BSE040935-511
59
Function Block Execution
Section 1 Basic Functions and Components
Using by_ref on parameters enhances the performance. It takes a lot of execution
time to copy parameters in each scan.
60
3BSE040935-511
Section 1 Basic Functions and Components
Function Block Execution
There are some limitations when using by_ref:
•
It is not possible to connect expressions or literals to a reference parameter.
•
If a reference parameter is not connected in one invocation, it cannot be
connected in other invocation (if the instance has multiple invocations).
•
It is not possible to read or write the parameter from outside the function block
(except in the invocation). The example expressions like fb.par_in := 2; or k :=
fb.par_out; are not allowed for reference parameters.
By using by_ref, it is still possible to use init values, in which case the init value is
the default value. If the parameter is not connected, the default value is used.
The code generated for connecting by_ref parameter is identical to an in_out
parameter; but they differ in what is allowed inside the function block.
For example, it is not allowed to write onto an in parameter regardless of whether it
is a reference or value parameter. The ownership analysis detects that a variable is
read only if an in parameter by reference is used instead of in_out. It is therefore
preferable to use direction=in and attribute=by_ref (instead of in_out), if the
parameter is actually an in parameter.
The In_Out parameters are passed by reference, and only a reference to the actual
variable outside the function block is passed to and from the function block. The
local representation of the parameter does not exist inside the function block.
Performing operations on an In_Out parameter inside a function block means
performing operations directly on the actual variable connected to the function
block. See also Connecting Variables to I/O Channels on page 102.
Function block
code
varRef
In_Out
varRef
Figure 23. In_Out parameter for a function block. This example illustrates how the
In_Out parameter points as reference to the value in the variable varRef.
3BSE040935-511
61
Control Module Execution
Section 1 Basic Functions and Components
A structured data type having components with reverse attribute must not be used
for communication between function blocks. The components with reverse
attribute does not work as intended when used with function blocks.
Control Module Execution
Control modules provide data flow-driven execution, which makes the code design
much easier for solutions where several types and formal instances are needed. All
control modules communicate with each other, and can therefore determine when
each individual instance can send and receive information. A data flow-driven
design prevents possible mistakes, when trying to foresee the correct execution
order, since the compiler rearrange or sort all the code behind the scenes. This is
called code sorting.
Direction for Control Modules
In control module types, a parameter can have any of the following direction:
•
•
•
•
In
Out
In_out
Unspecified.
These control module parameters follow different access rules from the code inside
the control module and offer limitations to the methods used to connect them.
All of them are passed by reference, which means only a reference to the actual
variable outside the control module is passed to and from the Control module.
The rules governing their functioning are as follows:
62
•
Input parameters are read only.
•
Out, In_Out and Unspecified are read and edit.
•
Control modules on the same level can connect only In to Out.
•
A sub control module inside could only connect its In parameters to In
parameters in the surrounding control module and so on.
•
In_out must be connected to a variable (on any level). This is not the case if the
control module is used in FD code block in a diagram.
3BSE040935-511
Section 1 Basic Functions and Components
Diagram Execution
•
If the control module is used in FD code block in a diagram, the In_out
parameters can be connected to each other in FD code block. It is also possible
to connect one Out parameter to an In_Out parameter, and an In_Out to an In
parameter.
•
One Out can be connected to Several In parameters. But, it is not possible to
have multiple data connections from the same source on control module
parameters of structured data types that have reverse components. See Table 9.
•
A control module is allowed to write to an output parameter. An exception is
the case of output parameters that are of structured data type containing
components with the reverse attribute. It is an error if a control module writes
to a reverse component of an output parameter.
•
A control module is not allowed to write to an input parameter. An exception is
that it is allowed for a control module to write to a reverse component of an
input parameter.
These rules apply to connecting parameters to communication variables as well.
Communication Variable In should be connected to In parameters and the
corresponding for Out. The compiler (and check) warns if rules are broken.
Unspecified parameters can be used without limitations for compatibility reasons.
For more information on Code Sorting, see the Compact 800 Engineering
Compact Control Builder AC 800M Planning (3BSE044222*) manual.
Diagram Execution
The execution of the content in a diagram or diagram type is mainly configured
using the Data Flow Order of different invocations within the FD (Function
Diagram) code block. The Data Flow Order is a number that specifies the intended
order of execution. In the FD code block, the Data Flow Order is given to invoke
functions, function blocks, diagram instances, control modules, code blocks, split
blocks and join blocks.
Control modules in a diagram are sorted based on access of variables to enable both
forward and backward calculations and data flows to be executed in the same task
scan. Therefore code blocks in invoked control modules will not always be executed
in the order specified by the Data Flow Order.
3BSE040935-511
63
Diagram Execution
Section 1 Basic Functions and Components
The Structured Text and SFC code blocks can be defined without invoking them
from the FD code block. These code blocks are then sorted together with code
blocks of invoked control modules.
Direction for Diagram Types
In diagram types, a parameter can have any of the following direction:
•
•
•
In
Out
In_out
The diagram type parameters are shown as ports when the type is instantiated in the
diagram editor.
All of them are passed by reference, which means only a reference to the actual
variable outside the diagram type is passed to and from the diagram type.
The rules governing their functioning are as follows:
64
•
Each port has an attribute that determines if it is visible in the diagram or not.
•
Input ports are shown on the left side.
•
Output ports are shown on the right side.
•
In_out ports are normally shown on both sides with a connecting line through
the block. They can also be shown on the left side only, depending on the
FD Port property on the corresponding parameter declaration.
•
One Out can be connected to Several In parameters. But, it is not possible to
have multiple data connections from the same source on diagram type
parameters of structured data types that have reverse components. See Table 9.
•
A diagram type is allowed to write to an output parameter. An exception is the
case of output parameters that are of structured data type containing
components with the reverse attribute. It is an error if a diagram type writes to a
reverse component of an output parameter.
•
A diagram type is not allowed to write to an input parameter. An exception is
that it is allowed for a diagram type to write to a reverse component of an input
parameter.
3BSE040935-511
Section 1 Basic Functions and Components
Single Control Modules
These rules apply to connecting the parameters to communication variables as well.
Communication Variable In should be connected to In parameters and the
corresponding for Out. The compiler (and check) warns if rules are broken.
Single Control Modules
A special kind of control module type, the single control module, provides a way of
grouping graphical instances, variables, parameters, and control modules into a
single unit.
Compared to the previous discussions about types and instances, a single control
module can be considered as a hybrid of them both (see Figure 24). First of all,
create a single control module as an instance under the control module folder (not
the control module type folder) in an application.
Once a single control module is created, it starts acting as both a type and an
instance. It contains code, editors for declaring parameters, function blocks,
instance information, etc. just like a regular type or instance. A single control
module can never be reusable as a type that can be used to create many instances.
However, it can be copied to a new single control module, and then be modified.
3BSE040935-511
65
Single Control Modules
Application
Section 1 Basic Functions and Components
Single Control Module
Control Module Types
Control Modules
type
IfA = 10then
B:=A+1;
end_if;
object1
A
3
B
7
Figure 24. A single control module. This module is not reusable, hence intended to
be used only once for grouping instances into a single unit.
66
3BSE040935-511
Section 1 Basic Functions and Components
FD Port
Single control modules can be used as a framework and attach control module
instances inside, like an application does with instances. Figure 25 illustrates this,
where three single control modules (Transport, Heating, and Crushing) form the
framework for the control modules (Motor_1, etc.).
Figure 25. Single control modules form the framework for the control modules.
FD Port
The FD Port column appears in the editor for function block types, control module
types, and diagram types. This column is only significant for the types that are
instantiated in a Function Diagram (FD) code block.
The normal choice is Yes or No. The value specifies if the parameter shall be visible
when the function block type, control module type, or diagram type is instantiated in
an FD code block. The default value is Yes.
There are extra choices (Left or Right) for control module parameters with direction
unspecified and parameters with direction in_out. These choices are related to the
placement of the parameter port in the FD code block.
Unspecified parameters are placed on the left side by default, and in_out parameters
are placed on both sides by default.
3BSE040935-511
67
FD Port
Section 1 Basic Functions and Components
There are some types with structured parameters that are mostly output, but also
contain some input components. Such a parameter must be either an Unspecified
parameter (control module types only) or an In_Out parameter.
The following list of alternatives are available for parameters of direction
unspecified:
•
No - Not visible as a port. The parameter will be placed on the left side of the
object if the user decides to show it later on.
•
No Left - Not visible as a port. The parameter will be placed on the left side of
the object if the user decides to show it later on.
•
No Right - Not visible as a port. The parameter will be placed on the right side
of the object if the user decides to show it later on.
•
Yes - Visible as a port on the left side of the object.
•
Yes Left - Visible as a port on the left side of the object.
•
Yes Right - Visible as a port on the right side of the object.
The following list of alternatives are available for parameters of direction in_out:
68
•
No - Not visible as a port. The parameter will be placed on both sides of the
object if the user decides to show it later on.
•
No Left - Not visible as a port. The parameter will be placed on the left side of
the object if the user decides to show it later on.
•
No Right - Not visible as a port. The parameter will be placed on the right side
of the object if the user decides to show it later on. This is only available for
parameters of function block types.
•
Yes - Visible as a port on both sides of the object.
•
Yes Left - Visible as a port on the left side of the object.
•
Yes Right - Visible as a port on the right side of the object. This is only available
for parameters of function block types.
3BSE040935-511
Section 1 Basic Functions and Components
Variables and Parameters
It is not recommended to use a function block type parameter of direction in_out
with its FD Port property set to Yes Right. In this case, it is only possible to
connect this type of parameter to a variable, parameter, or
communication variable.
Therefore, it is recommended to use parameter with direction out and attribute
by_ref, instead of in_out with Yes Right option, so that this parameter can be
connected to input port of another object.
Variables and Parameters
Variables and parameters are the carriers of data throughout the system. This section
describes how to use parameters and variables in the best way possible:
•
Variable and Parameter Concept on page 71 gives an overview of variables and
parameters and how they are used.
•
Variables on page 72 gives an overview of the different variable types.
•
Variable Entry on page 73 describes how to declare variables.
•
External Variables on page 81 describes how to define external variables.
•
Access Variables on page 82 describes how to define and use access variables.
•
Communication between Applications Using Access Variables on page 84 and
Communication in an Application Using Global Variables on page 85 describe
how communicate between applications.
•
Communication Variables on page 86 describes how to define communication
variables.
•
Control the Execution of Individual Objects on page 92 describes how to use
variables and parameters to control the execution of objects.
•
Link Variables in Diagrams on page 96 describes the use of link variables for
graphical connections in diagram editor.
•
Project Constants on page 96 describes the use of project constants and how to
update them.
•
I/O Addressing Guidelines on page 101 describes the rules for addressing I/O
channels.
3BSE040935-511
69
Variables and Parameters
70
Section 1 Basic Functions and Components
•
Connecting Variables to I/O Channels on page 102 describes how to connect
I/O variables to I/O channels.
•
Extensible Parameters in Function Blocks on page 107 describes extensible
parameters (these can only be used in function blocks).
•
Keywords for Parameter Descriptions on page 108 describes keywords used in
description in editors to identify the function of a parameter.
3BSE040935-511
Section 1 Basic Functions and Components
Variable and Parameter Concept
Variable and Parameter Concept
Variables
Variables are used in Control Builder to store and compute values.
Variables are the carriers of values at object level, application level, and network
level:
•
Local variables – These are mainly used inside objects as carriers of local
values. They belong to the code and can only be accessed within the same
function block, control module, diagram or program.
•
Global variables – These are declared in the application and holds values that
can be accessed by any object (function block, control module, diagram or
program) in the application. However, to reach a global variable, each object
that intends to use a global variable must have declared a corresponding
External variable, see also External Variables on page 81).
•
Access variables and Communication variables are used as carriers for
communication between several applications and controllers in a network:
–
Access variables allow data exchange between controllers, that is, access
variables can be accessed by other controllers. See Communication
between Applications Using Access Variables on page 84.
–
Communication variables are used for cyclic communication between
top level diagrams, programs, and top level single control modules.
Communication variables support both inter application communication
and inter controller communication in a system network. For more
information, see Communication Variables on page 86.
All variables are defined by their names and data types. The data type (dint, bool,
real, string, and so on) defines the characteristics of the variable.
Parameters
Parameters cannot store any values, but the variables are assigned to parameters of
function blocks, control modules, diagrams and functions. Variables store the value
of the corresponding (connection) parameters.
3BSE040935-511
71
Variables
Section 1 Basic Functions and Components
Use parameters for connecting objects and to point to variable values that need to be
read into code blocks and written from code blocks.
When function blocks read from a variable and write to a variable, they use input
and output parameters that temporarily copy the variable value, before and after
execution. In this case, one may claim that parameters can temporarily hold a
value. See Function Block Execution on page 59 for more details.
Variables
Table 5 lists available variables in Control Builder.
Table 5. Variable types in Control Builder.
Variable type
Scope
Where to declare
Local variable
Object level. Can only be
accessed within the function
block, control module or
program in which it is
declared.
Application editor (for passing
parameters between control
modules) or,
Programs editor (for access in
the program).
Function block editor (for
access inside the function
block).
Control module editor (for
access inside the control
module).
Global variable
72
Application level. Can be
accessed from anywhere in
the code within an
application, except from
diagrams. An object that
intends to use a global
variable must declare an
external variable locally that
will point at the corresponding
global variable.
In the application editor. See
also Communication in an
Application Using Global
Variables on page 85.
3BSE040935-511
Section 1 Basic Functions and Components
Variable Entry
Table 5. Variable types in Control Builder. (Continued)
Variable type
Scope
Where to declare
Access variable
Network level. Variable that Access Variable editor of a
controller.
can be accessed by remote
systems for communication
between controllers. See also
Access Variables on page 82
and Communication between
Applications Using Access
Variables on page 84.
Communication
Variable
Project Level. Variable that
can be accessed by remote
systems for communication
between applications and
controllers. See
Communication Variables on
page 86
Editor for top level Diagram,
Program, or top level Single
Control Module.
Variable Entry
Control Builder helps the user to declare variables in applications, programs,
function block types and control module types. This section covers the entries:
Name, Data Type, Attributes, Initial Value and Description.
Name
It is recommended that variables are given simple and explanatory names, and that
they begin with a capital letter. Names consisting of more than one word should
have capital letters at the beginning of each new word. Examples of recommended
variable names are DoorsOpen, PhotoCell.
Certain names, however, are reserved by the system and cannot be used for other
purposes, for example true. An error message appears if such a word is used. For
naming guidelines and information on relevant tools, refer to the Compact 800
Engineering Compact Control Builder AC 800M Planning (3BSE044222*) manual.
3BSE040935-511
73
Variable Entry
Section 1 Basic Functions and Components
Data Types
A data type defines the characteristics of a variable type. There are both simple and
structured data types in Control Builder. A variable of simple data type contains a
single value, while a structured data type contains a number of components of
simple or structured data types.
Table 6 presents the most common simple data types and the initial value when the
variable is declared.
Table 6. Simple data types
Data type
Bytes allocated
by variable
Description
Initial value
(default)
bool
Boolean
4
False, 0
dint
Double integer
4
0
int
Integer
4
0
uint
Unsigned integer
4
0
10 bytes + string
length [n]
‘‘
string(1)
string
Character
word
Bit string
4
0
dword
Bit string
4
0
time
Duration
8
T#0s
date_and_time
Date and time of
day
8
1979-12-3100:00:00
real
Real number
4
0.0
(1) String length is 40 characters by default, but can be changed by entering string[n] as the data
type, where n is the string length. The number of bytes allocated for string[40] will be (40 +10)
50. The maximum string length is 140.
Comparison of variables of unsigned data types (uint, word, and dword) will not
work properly if the most significant bit is set. Internally, they are handled as
signed, where the most significant bit is used as the sign. This means that a word
variable with a value above 32767 will be considered to be smaller than a word
variable with a value below 32768.
74
3BSE040935-511
Section 1 Basic Functions and Components
Variable Entry
When declaring variables or parameters of the data type string, always define the
required length within square brackets (for example, string[20]), to minimize
allocated memory. If the string length is not defined, then Control Builder
automatically allocates memory for a 40 character string length.
Use variables of data type string with care. Strings occupy a great deal of
memory, and require much execution time to be copied or concatenated.
A structured data type contains a number of components of simple or structured data
type. For bidirectional communication using structured data types, a reverse
attribute must be set to indicate which components communicate in the opposite
direction (see also Bidirectional Communication Variable on page 90).
There are a number of predefined data types in Control Builder (for example
BoolIO and RealIO) that are structured data types. User-defined structured data
types can also be created, see Decisions When Creating Types on page 53.
The word “default” can be used as an initial value for a parameter in a control
module type or diagram type. This works for both simple and structured data
types. For a structured data type, the initial value “default” gives the default value
of the data types for all components.
This is useful when creating types; for input parameters of a structured data type
that do not have to be connected, and for output data types that do not have to be
connected.
More information is given in Control Builder online help. Search the index for
“structured data type”.
3BSE040935-511
75
Variable Entry
Section 1 Basic Functions and Components
Attributes
Attributes are used to define how variable values should be handled at certain
events, such as after cold restart, warm restart, etc. Variables that are supposed to
hold values over several downloads must for example, have a retain attribute in
order to keep their values after a warm start. Any of the attributes in Table 7, can be
given to a variable. For parameter attributes see Table 8.
Table 7. Variable attributes
Name
Description
no attribute
The variable value is not maintained after a restart, or a download of
changes. Instead, it is set to the initial variable value. If the variable
has no initial value assigned, it will be assigned the default data type
value, see Table 6 on page 74.
retain
The variable value is maintained after a warm restart, but not after a
cold restart. Control Builder sets retain on all variables by default. To
override this, the attribute field must be left empty in declaration pane.
coldretain
The variable value is saved on disk, and retained after warm or cold
restart.(1)
Coldretain overrides the retain attributes in a structured data type.
constant
The user cannot change the value online once assigned.
This attribute overrides the coldretain and retain attributes in a
structured data type.
76
hidden
The variable will be hidden for an OPC client connected to an OPC
server for AC 800M. This attribute is used for variable values not
necessary to a supervisory system.
nosort
This attribute suppresses the code sorting feature for control module
types. It is advisable not to use the nosort attribute if the user do not
know the data flow characteristics in detail.
state
This attribute will let the variable retain its old value between two
scans for control module types. The old and new value can be read by
adding :old and :new to the variable name.
3BSE040935-511
Section 1 Basic Functions and Components
Variable Entry
(1) When an application is downloaded the very first time, variables will get their initial data type
values, even though they have been declared with the attribute coldretain, and, that the controller
has done a cold restart. Hence, no variables can receive their coldretain values before they have
been stored on disk. Correspondingly, will variables that have been declared later on, contain their
initial values until they have been saved on disk.
Table 8. Parameter attributes
Name
Description
no attribute The parameter value is not maintained after a restart, or a download
of changes. Instead, it is set to the initial parameter value. If the
parameter has no initial value assigned, it will be assigned the default
data type value, see Table 6 on page 74.(1)
retain
The parameter value is maintained after a warm restart, but not after a
cold restart.(1)
coldretain
The parameter value is saved on disk, and retained after warm or cold
restart.(1)
Coldretain overrides the retain attributes in a structured data type.
hidden
The parameter will be hidden for an OPC client connected to an OPC
server for AC 800M. This attribute is used for variable values not
necessary to a supervisory system.
by_ref
This attribute is used for controlling the passed value. For in and out
parameters the value is usually copied into the called instance at the
invocation. But for non simple data types and strings it is time
consuming. In that case, a reference to the data instance is passed in
the function block call. This is achieved by setting the attribute of the
parameter to by_ref.
(1) These attributes are valid if the parameter is not connected, if connected it is the attributes of
connected variables.
It is possible to assign several attributes to a variable for example, retain, nosort,
and hidden can be assigned as (retain nosort hidden) attribute.
3BSE040935-511
77
Variable Entry
Section 1 Basic Functions and Components
An intermediate variable (a variable which is automatically generated when
making a graphical connection between function blocks) in FBD or LD is always
assigned the attribute retain (even if the parameters on both sides of the graphical
connection have the attributes coldretain).
In addition to the general attributes, the data type editor supports two special
attributes for the components (see Table 9).
Table 9. Special attributes for data types
Name
Description
displayvalue
This attribute is applicable for a component in a structured data
type, which is used in the FD code block of a diagram. In the
FD code block, the online value label is not shown for graphical
connections of structured data type. However, if one of the
components of the structured data type is marked with the
displayvalue attribute, the online value label is shown for this
component.
Note: The displayvalue attribute can be assigned to only one
component in a structured data type. It also possible to assign
this attribute through a combination of other attributes
(for example, coldretain displayvalue, nosort retain displayvalue,
and so on). In this case also, only one component can have this
type of attribute (with displayvalue).
If a nested structured variable is used, the displayvalue attribute
is needed on each level down to the value that should be
shown.
78
3BSE040935-511
Section 1 Basic Functions and Components
Variable Entry
Table 9. Special attributes for data types
reverse
The reverse attribute can be used while declaring sub elements
in a structured data type. This attribute is used when declaring
structured data types that are intended to represent a
connection between different program organization units in the
applications. The signals in the connection can pass data in
different directions, and the reverse attribute specifies that the
direction of this signal (component) is opposite to the normal
flow (forward or backward).
It is an error if a sub element of a structured data type has the
reverse attribute and the sub element itself is of a structured
data type containing a reverse attribute at any sub level in that
sub element.
The reverse attribute affects the usage of control module
parameters, diagram parameters and communication variables.
Note: All components that have the reverse attribute must be
placed consecutively in the data type editor.
Restrictions with reverse attribute for Split and Join blocks
in FD code block
In the FD code block in Diagram and Diagram Type POUs, the
Split and Join blocks must not be used for structured data types
with reverse components.
Restrictions with reverse attribute for function blocks
If structured data type is used for communication between
function blocks, ensure that the type does not contain any
reverse components.
Restrictions with reverse attribute for data exchange
between control modules or diagrams using Access
Variables
It is also not possible to write to out direction variables using
Access Variables in Structured Text, even if the attribute is
reverse.
3BSE040935-511
79
Variable Entry
Section 1 Basic Functions and Components
Attribute Example
The following example tries to illustrate how a variable will be handled, depending
on different attribute settings. Suppose the variable valveC has the attribute
coldretain, valveR has the attribute retain and valve has no attribute. Also, suppose
that these three variables have the initial value = True (see Figure 26 for the variable
declaration).
Figure 26. Three variables with different attributes settings
According to the attribute settings in Figure 26, the variables will be read or written
on different occasions in the given code example below, (read the comments under
each IF statement):
IF valveC THEN
(*Code in this position is only executed once after the very
first cold restart*)
valveC := false;
END_IF
IF valveR THEN
(*Code in this position is only executed once after a cold
restart*)
valveR := false;
END_IF
IF valve THEN
(*Code in this position is only executed once after a cold restart
and once after a warm restart*)
valve := false;
END_IF
Note that execution does not have to take place during the first scan after restart, for
example, when IF valve is embedded in another IF statement.
80
3BSE040935-511
Section 1 Basic Functions and Components
External Variables
Variables and parameters should have the attribute retain, unless they are written at
each scan. When a change has been made to the application, the entire application
will be (warm) restarted and in doing so, variables without the attribute retain will
be set to their initial values, and there is a chance that the change will not be totally
bumpless. It is recommended that In and Out parameters to function blocks always
have the attribute retain.
More information is given in Control Builder online help. Search the index for
“attribute”.
Initial Values
It is possible to give the variable an initial value, which will be assigned to the
variable the first time the application is executed. This setting overrides the default
data type value. Table 6 shows default initial values for the most common data
types.
Descriptions
The description field describes and provides information about the variable. A short
descriptive text may include an explanation of the cause of a condition or a simple
event, for example “Pump 1 is running”. Since the description is not downloaded to
the controller, the size of the description is irrelevant.
•
Diagrams and instances of diagram types
External Variables
External variables are not really variables, in the sense that they carry a value.
Instead, external variables work like parameters, that is, they point to a variable
value (in this case a global variable). In order for an object to reach a global variable
(located at the top of the application) it must use a pointer, or more specifically, an
external variable. By declaring an external variable inside an object, it is possible to
access global variables efficiently from a deep code design, without having to pass
variable values through parameters.
3BSE040935-511
81
Access Variables
Section 1 Basic Functions and Components
variable z
parameter z
parameter z
parameter z
value of z
variable z [global]
value of z
[external]
Figure 27. The variable z can be accessed deep down in the structure, using several
parameters. (Bottom): Using external (and global) variables, the variable z is
accessed directly, without having to use parameters.
Access Variables
Access variables are needed when the system works as a server. Allowed protocols
are MMS, COMLI, MODBUS TCP and SattBus. MMS and SattBus variables are
declared in the Access Variable Editor under the corresponding tab, COMLI and
MODBUS TCP variables under the Address tab. The variable name must be unique
within the physical control system.
Open the Access Variable Editor by right-clicking the ‘Access Variables’ icon under
the respective Controller and select Editor.
To limit the access to a variable, set the attribute to ReadOnly. If the attribute is
left blank, it is possible to both read and write.
82
3BSE040935-511
Section 1 Basic Functions and Components
Access Variables
MMS
MMS variables can only be accessed by name.
An MMS access variable name can be up to 32 characters long and contain letters,
digits and the characters dollar($) and underscore(_). However, an access variable
name cannot begin with a digit or the dollar ($) character.
All data types for single and structured variables are allowed, with the exception of
ArrayObject and QueueObject.
To limit the access to an MMS variable, set the Attribute to ReadOnly. If the
attribute is left blank, both read and write is possible.
SattBus
SattBus variables can be accessed in three ways:
•
Standard SattBus name such as Valve:
–
the name must consist of exactly five ASCII characters, but may not begin
with a percentage sign (%).
•
COMLI direct addressing (see Address ),
•
IEC 61131-3 standard representation for variables.
–
IEC61131-3 address must be entered under the COMLI tab
Allowed data types for a single variable are, bool, dint, int, uint, real or string.
Whereas a structured variable does not allow string data type.
Address
Address variables can be accessed in two ways only, either direct addressing with
capital X and the number for boolean, or capital R and the number for registers (R0R65535 for PA controller) beginning with a percentage sign or not, or according to
IEC 61131-3 standard representation for variables.
Allowed data types for a single variable are bool, dint, int, or uint, whereas
structured variables must all be of same data type. A structured variable is allowed
to contain more than 512 booleans and contain more than 32 components of integer
data type. Overlapping areas are not allowed.
3BSE040935-511
83
Communication between Applications Using Access Variables
Section 1 Basic Functions and
Example
An access variable name "X0" is defined and connected to a variable which contains
544 Boolean components at octal address 0-1037. The next available address is then
1040 to ensure that areas do not overlap.
At least one of the variables in the access variable table has to be defined. For
missing variables, requested data of boolean data type will be returned with the
value False and requested data of integer data type will be returned with the value
"0". Writing to undefined variables is ignored.
Communication between Applications Using Access Variables
Two applications may communicate with each other via variables, but these
variables must be declared as access variables (see, Access Variables on page 82).
This also applies when two applications are downloaded to the same controller (see
Figure 28).
Controller
Controller 1
Controller 2
Application
Application
Application 1
Application 2
Figure 28. Variables for communication between applications must always be
declared as access variables.
When transferring access variables, it is important to use the same data type range
for the client (dint), as for the server (dint).
It is, however, possible to connect variables with different ranges, such as a dint
variable on the server and an integer variable on the client.
84
3BSE040935-511
Section 1 Basic Functions and Components
Communication in an Application Using Global
As long as the variable values are within the range of an integer, this will work, but
once the value goes outside the integer range, it will not.
If an access variable is the only user of a variable that is connected to an I/O
channel, this variable is by default updated every second. To update this variable
with another interval, create a statement that involves the variable, but is never
executed.
A statement that is never executed, but still updates the variable x could look like
this:
if false then
x:=x;
end_if;
Connect this program to a task that executes with the desired interval. The
variable is updated every time the task is executed.
Communication in an Application Using Global Variables
In Programs
Global variables are declared at application level, in the Global Variables tab of the
application editor. They can be accessed directly, without any declaration in the
program editor. Variables that are not declared in the declaration pane in the
program editor are assumed to be global variables. A global variable can be used in
any program, without having external variables declared in a program.
In Function Blocks or Control Modules
In order to reach a global variable from either a function block type or a control
module type, each type must have either an external variable declared or a
parameter. Thus, the types access the global variable value by using an external
variable or a parameter to point at the global variable located in the application.
3BSE040935-511
85
Communication Variables
Section 1 Basic Functions and Components
Communication Variables
The communication variables are used for cyclic communication between top level
diagrams, top level single control modules, and programs, in the project that uses
MMS communication protocol.
Communication variables are declared in the Program editor, top level Single
Control Module editor, or top level Diagram editor. Communication variables
support both inter application communication and inter controller communication in
a project.
Communication variables are not supported in distributed applications. If an
application that contains communication variables is running in a controller, it is
not possible to download the same application to another controller.
A communication variable can be either a communication input variable or a
communication output variable.
If the direction of a communication variable is in in a POU, the POU can read the
variable, but cannot write to the variable. If the direction of a communication
variable is out in a POU, the POU can write to the variable and read the variable.
A communication variable can be either an elementary type or a structured data
type. It cannot be a generic or built-in type.
If a communication variable is of structured data type, it must not contain
components that are declared with the CONSTANT type qualifier and it must not
contain CONSTANT components at any sub-level of the variable.
Communication variables use a name based resolution to connect a communication
output variable to one or several communication input variables.
In a project, all communication output variables must be declared with unique
names.
Communication variables cannot be connected to the channels of an I/O unit.
Therefore an application code has to be entered to transfer values between
communication variables and local variables, which are connected to I/O.
86
3BSE040935-511
Section 1 Basic Functions and Components
Communication Variables
Declaration pane for communication variable
The declaration pane for communication variables consists of:
•
Name
The name of the communication variable. For communication output variables
(direction - out), the name must be unique on the project to resolve the
IP-address during compilation.
•
Data Type
•
Attributes
Possible attributes to specify are:
– retain
– coldretain
– hidden
– hidden retain
– hidden coldretain
If no attribute is specified when the communication variable is declared,
retain is filled in automatically by the editor.
•
Direction
The possible values are in or out. If no direction is specified when the
communication variable is declared, in is automatically filled in by the editor.
•
Initial Value
An initial value is assigned to the variable when the application is executed first
time. This setting overrides the default data type value.
•
ISP Value
Applicable only to communication input variables. This field defines the ISP
(Input Set as Predetermined) value to be set for the in variable. This value can
only be set for simple data types.
For structured data types, the ISP values can only be set in the data type for
each individual component (in the Data Type editor). Hence, it is not possible
to configure instance specific ISP values for structured data types.
3BSE040935-511
87
Communication Variables
Section 1 Basic Functions and Components
ISP could be used in a structured variable to detect communication failure or
bad quality, by using a Boolean Valid component with ISP set to false.
•
Interval Time
Communication cycle time for peer-to-peer communication. The possible
values are fast, normal, slow, very fast, and very slow. The default value is
normal.
The time interval (in milliseconds) for each of these cycle times is defined in
the hardware editor for IAC MMS in the Control Builder. The IAC MMS
object is located at position 5.1 under the controller object in the hardware tree
in Control Builder.
•
IP Address
Applicable to communication input variables, and also applicable for
communication output variables if bidirectional. This field defines the IP
address of the controller that contains the corresponding communication output
variable (with the same name) in any of its applications.
When no value for the IP address is entered, the editor automatically fills in the
default value auto. This means that the IP address is resolved during
compilation.
88
3BSE040935-511
Section 1 Basic Functions and Components
•
Communication Variables
Acknowledge Group
Applicable to communication input variables, and also applicable for output
variables if bidirectional. Acknowledge group is used to categorize the
communication variables in different groups for acknowledgement purpose
after their ISP values get latched. This avoids unexpected restart of
communication after fault detection. The possible settings are auto or a
group ID.
– auto - The communication resumes automatically after the error situation
is resolved. This is the default value.
– Specifying a group ID - This enables the communication variable for an
acknowledgement after fault detection. If a group ID is specified, the
acknowledgment is performed through the CVAckISP control module, for
a particular group or cascaded groups.The CVAckISP control module is
available in BasicLib.
A maximum of 32 Communication Variables can be grouped together with the
same group ID per application. This is also checked during application
compilation.
One control module instance of CVAckISP is used to reset all the latches in one
group of communication variables. If several such groups are to be reset
simultaneously, the control module instances of CVAckISP for each group may
be interconnected in a cascade configuration. The reset order is distributed to
all members in the configuration.
•
Description
User documentation of the variable.
Source and Sink for Communication Variables
The term ‘source’ is used for the POU that declares a communication output
variable. The term ‘sink’ is used for the POU that declares a communication input
variable.
If a sink is located in one application, a source can be located in any of the
following:
•
In the same application as the sink.
•
In another application but in the same controller as the sink.
3BSE040935-511
89
Communication Variables
•
Section 1 Basic Functions and Components
In another application and in another controller.
Multiple sinks can be linked to the same source.
For example, for every communication output variable with a unique name, there
can be multiple communication input variables with the same name as the
communication output variable. The communication input variables can reside in a
different POU, in a different application, or in a different controller.
There is no need to declare the location of the source (communication output
variable) while configuring the sink (communication input variable). This is because
the binding between them is based on the name of the communication variable.
The Control Builder checks whether the name of a communication output variable
is unique in the project, only during the download of the application. The download
is aborted if the variable name is not unique.
Unresolved Communication Variable
A communication input variable is unresolved if there is no communication output
variable (source) with the same name, during compilation.
The Control Builder allows the execution of an application that contains
unresolved communication variable. When a reconfiguration of the system is
done (for example, at a warm restart), the source can be created and the
unresolved communication variable becomes resolved.
A resolved communication variable does not become unresolved if the source is
removed. It gets unresolved the next time, when that particular application is
reconfigured.
Bidirectional Communication Variable
Bidirectional communication variables have communication in both directions and
can be configured for one-to-one connections only. These variables can be created
for structured data types only.
The configuration parameters that are used for the in variables can also be specified
for the out variables, if bidirectional. This allows the configuration of a
communication variable with a different communication setup in either directions
(for example, different interval times).
90
3BSE040935-511
Section 1 Basic Functions and Components
Communication Variables
Reverse attribute
For bidirectional communication using structured data types, a reverse attribute
must be set to indicate which components communicate in the opposite direction to
the in/out declaration of the communication variable.
The reverse attribute is configured in the data type editor.
The reverse attribute can only be set such that all in variables are located
consecutively and also all out variables are located consecutively in memory.
Hence, it is not possible to configure reverse for every other component in a data
type.
The reverse attribute can be set in both top level and sublevel of a structured data
type, but cannot be nested.
This means, the reverse attribute cannot be set for a structured data type component
Struct2 inside a structured data type Struct1. But, Struct2 can have reverse
components inside it.
For example, for a ControlConnection data type, which consists of one forward
structure and one backward structure, the reverse attribute is set on the whole
backward structure. All components in the backward structure inherits the reverse
attribute automatically.
Interval Time
Out of the five different cyclic categories (VerySlow, Slow, Normal, Fast, VeryFast),
the default interval time for a communication variable is Normal.
The interval time for a communication variable can be changed only when the
Control Builder is offline. The changes takes effect during the download.
The time interval (in milliseconds) for each cyclic category is defined using the
hardware editor for IAC MMS. The IAC MMS object is available at position 0.5.1
under the controller object. Position 5 contains the IP object.
Hardware Simulation with Communication Variables
It is possible to use hardware simulation for IAC.When using hardware simulation,
the communication variables use real communication and real copying of input
3BSE040935-511
91
Control the Execution of Individual Objects
Section 1 Basic Functions and Components
variables. This is also the case when downloading a simulated AC 800M to a Soft
Controller.
Application Download
The communication variable configuration is downloaded when the application is
downloaded to the controller. It is possible to download an unresolved In (or
bidirectional) communication variable, even though the communication will not
happen. To resolve an unresolved communication variable that already exists in a
controller, the new configuration with the Out variable must be downloaded.
When an out variable is removed, only in variables that are defined in applications
which are downloaded, shows communication variables as unresolved. Other
communication variables (in other applications) will timeout.
To support multi user engineering, all the affected controllers are reserved during
last step of the communication variable analysis, until the configuration is
downloaded.
Control the Execution of Individual Objects
Sometimes there is a need to execute specific sub function blocks and/or sub control
modules, with a time interval and priority different from the task connected to the
application. Depending on the requirement, this can be done in two ways:
1.
To create a new task and connect this task to all the following objects, read the
sub-section 'Using a Global Variable Connected to an External Variable on
page 92.
2.
To choose a new task for each individual object (and for that object only), read
the sub-section 'Using a Global Variable Connected to a Parameter on page 94.
Using a Global Variable Connected to an External Variable
Assume that the user has added a new task, for example SuperFast, to the other
tasks in the Project Explorer.
Steps to use global variable:
1.
92
Declare a global variable (for example Speed) of data type string, with the
attribute constant and the initial value 'SuperFast'.
3BSE040935-511
Section 1 Basic Functions and Components
Control the Execution of Individual Objects
2.
To reach objects that have been created in the application, start by declaring an
external variable in the type (open the type editor and select the external
variable tab).
3.
Declare an external variable with the same name, data type and attribute as the
global variable. In this example, an external variable called Speed of data type
string and with the attribute constant is used.
Finally, connect the new task SuperFast to the object by right-clicking the object
and selecting Task connection. Type the variable name Speed in the task field. All
the following objects that are created will have this task connection, that is,
SuperFast.
The advantages with this method of using a global variable connected to an external
variable (declared in the type) is that every following object will be connected to the
same task (SuperFast). If the user later on need to change the task connection for all
the objects (perhaps hundreds of objects), change only the initial value for the global
variable in the application (see Figure 29). The present task connection for all
objects will point, via the external variable to the task declared by the global
variable.
Tasks
SuperFast
Global variable
Speed initial value = ‘SuperFast’
Fast
type
External
variable = Speed
Normal
objects
Task connection = Speed
on the first created object.
Slow
Current task is SuperFast
for all following objects.
SuperSlow
Figure 29. All objects will have the same task connected (SuperFast), once the first
object has connected Speed.
3BSE040935-511
93
Control the Execution of Individual Objects
Section 1 Basic Functions and Components
Using a Global Variable Connected to a Parameter
Assume that the user has added a new task, for example SuperSlow, to the other
tasks in the Project Explorer.
The main advantage of this method, compared to the previous method with external
variables, is that the user can change the task connection on each following formal
instance, by simply connecting a parameter to a different global variable. (See
Figure 30).
For more information on formal instances, see Types and Instances - Concept on
page 31.
This method is based on declaring two global variables (for example, Slowly and
Learning) of the data type string, with the attribute constant, and the initial values
'SuperSlow' and ‘Slow’, respectively.
In order to reach the following objects that have been created in the application, start
by declaring a parameter in the type (open the type editor and select the parameter
tab). Declare a parameter, for example Sleepy, of data type string. Select the formal
instance (object) inside the type:
1.
Right-click the object and select Property > Task connection.
2.
Type Sleepy in the task field.
Every created object that is based on the type (containing the formal instance) can
be connected via the connection parameter Sleepy and one of the global variables
Slowly or Learning, located in the application.
94
3BSE040935-511
Section 1 Basic Functions and Components
Link Variables in Diagrams
Tasks
Global variables
SuperFast
Slowly with initial value = ‘SuperSlow’
Learning with initial value = ‘Slow’
Fast
type
Parameter = Sleepy
Normal
formal instance
Task connection = Sleepy
on the formal instance.
Slow
SuperSlow
object1
Sleepy connects = Slowly
object2
Sleepy connects = Learning
Current task is SuperSlow
Current task is Slow
Figure 30. Each object can be connected to a different task via the parameter Sleepy
declared in the type and task connected in the formal instance.
The advantage of this method is that the objects of the formal instance, located
inside the type can be connected to different tasks (global variables with a different
task name as init value).
Link Variables in Diagrams
For a graphical data connection in a diagram editor, it is possible to set a
link variable. A local variable of the same data type as the connected ports can be
used.
To create a link variable, right-click the required graphical connection to open the
context menu, and select Link Variable. Enter the name of the link variable.
3BSE040935-511
95
Project Constants
Section 1 Basic Functions and Components
The link variable name is not displayed in the graphics; it is only visible if you open
the Link Variable dialog.
Normally, link variables are not needed. The compiler auto-generates variables
when necessary. But, if it is needed to access the intermediate value via OPC, a link
variable is required. The declared link variables are available via OPC.
If an output port has multiple graphical connections, all these connections share the
same link variable (if any).
If a block has an in_out port that is graphically connected on both sides, both
connections share the same link variable (if any). This means that if several blocks
have graphically interconnected in_out ports and a link variable is set for one of the
graphical connections, the link variable is forwarded and set to all the graphical
connections in the in_out chain.
Project Constants
Project constants are declared at the top level of libraries and projects. They are
globally visible, and can be used wherever a constant value is permitted, for
example, in program code and for variable initialization. With project constants, it is
possible to create settings for an individual project, without having to modify any
source code, or having to introduce parameters which have to be passed on to all
concerned types.
Project constants are suitable to use for library items that the user wants to change.
Examples are, date and time formats, logical colors and logical names. Do not use
project constants to change the functionality of an object, for example, initial values
and comparisons in code.
Typically, project constants are declared in a library and given default values. They
are then used, for example, in code located inside types.
Project constants are allowed to have the same names as variables and parameters.
Control Builder will, however, choose the variable or parameter name if a name
conflict exists. This must be considered when adding, renaming or deleting
variables or parameters in an already running application.
Follow the naming convention, which says that project constants should begin
with the letter “c” (for example “cColors”). Use structured project constants, if
possible.
96
3BSE040935-511
Section 1 Basic Functions and Components
Project Constants
Note that project constants cannot be used to control the execution of function
blocks or control modules. Use a global variable or a parameter instead. For more
information see, Control the Execution of Individual Objects on page 92.
If a project constant connected to a retain parameter (or variable) is changed
online, then the change does not effect on existing instances until a cold restart is
performed.
Project constants declared at library level (user-defined libraries) can only be edited
and deleted from the library, that is, they cannot be deleted from the Project constant
dialog that is reach by right-click the control project folder (root object). To edit or
delete a library-declared project constant, right-click the library in Project Explorer
and select Project Constants.
Naming conflicts between project constants appears when the same project
constant name exists in more than one library at the same time.
The only way to avoid a naming conflict is either to delete one of the constants or
not using the constant at all. A type conflict can never be overridden.
Structured Project Constants
It is advisable to create one single structured project constant for an entire project or
library, where the project constant name is a concatenation of “c” and the project
name (or library name).
An example:
If the project name is “ACMEToothpaste”, the structured project constant should be
named “cACMEToothpaste”. Using a structured project constant makes sure that
there is little chance of conflict with variable and parameter names. Using a
structured project constant (“cACMEToothpaste”) enables the user to, for example,
use “Max” without causing problems due to a variable or parameter called “Max”,
since the full path to the project constant “Max” would be
“cACMEToothpaste.Max”.
Define only one project constant per library. This project constant can, and should,
be a structured project constant the concatenation of “c” and the library name in
3BSE040935-511
97
Project Constants
Section 1 Basic Functions and Components
which it is contained. For example, if the library name is “ACMEValveLib” the
(structured) project constant should be “cACMEValveLib”.
All project constants defined in libraries and projects must have been given
unique names.
Typical Use
There are two typical use cases for project constants:
1.
To satisfy the need for constant values in all project applications.
Some values might have to be constant throughout the entire project. To change
such a “constant” value, change it once. There is no need to change it at every
occurrence. For such cases, use a project constant. The project constant is
defined in one place only, and can be used throughout the project. Changes to
the project constant will be reflected throughout the project.
An example:
To be able to change the severity for all “High level alarms” in the entire
project, set up a project constant that defines the severity and use the project
constant in all alarm blocks in all applications. To change the severity, just
change the value of the project constant.
In this case, project constants should be defined on control project level, not in
a library.
2.
To be able to change library type solutions without having to make changes in
the library itself.
A method commonly used in control application engineering/programming is
to construct libraries, in which re-usable code is placed. It is good practice to
make the library as general as possible, to maximize its usefulness. The use of
project constants is an excellent solution for such situations.
Example 1: Easy Translation
Assume that the user has created a library that makes extensive use of text strings.
Instead of including strings (in the user’s native language) statically in the library,
use project constants. This allows another engineer to change the values of these
project constants and to translate the strings to another language.
98
3BSE040935-511
Section 1 Basic Functions and Components
Project Constants
For example, a project constant that was originally set to “Stop” can easily be
translated by a German engineer to “Halt”, simply by changing the value of the
project constant. This would not be the case if the user had typed “Stop” in the
library. Such string constants that are to be translated are best stored as a structured
project constant under the component .Settings.
The string “Stop” would, for example, be defined as the structured project constant
“cACMEValveLib.Settings.StopLabel” or, even more levels;
“cACMEValveLib.Settings.Labels.Stop”.
Example 2: Combination of Dynamic and Static String Constants
Consider the following function block, in Figure 31, that controls high alarms.
Signal is of RealIO type, Alarmlevel is of real type, and Message is of string type.
Signal
AlarmCond
Message
Alarm level
Figure 31. The function block AlarmCond located in the Alarm library.
Now, we want a “customized” message to be passed to Message, such as
High Level (> 75 ºC)
The message consists of five important elements that make up the message.
1.
“High Level”
2.
“(> “(note the spaces)
3.
75 (a value set by Alarm level)
4.
ºC (a value set by Signal.parameters.unit)
5.
“)”
All in all, three strings (1, 2, and 5) and two values (3 and 4).
3BSE040935-511
99
I/O Addressing Guidelines
Section 1 Basic Functions and Components
Defining these 3 strings locally would be poor design, since the strings would be
defined for every object that is created from the type. To create a dynamic
environment, use project constants, or, more specifically, structured project
constants.
In the example above, we actually have different string categories – “High Level”,
“(> “, and, “)”.
The first one is a (dynamic) string that a user may want to translate, depending on
target customer nationality, whereas the other two are static and independent of
language. This calls for two different views of project constant.
Using structured project constants, and the naming convention mentioned earlier in
this section, a defined structured project constant for “High Level” could be:
cACMEValveLib.Settings.HighLevelLabel.
As described in the first example (Example 1 above), we make use of the component
“Settings” in the structure. Underneath this component, we define the constants that
are to be translated, or changed, depending on circumstances.
Next, we define the structured project constant cACMEValveLib.Internal.Str1 and
cACMEValveLib.Internal.Str2 to contain “(> “and “)”. Note the component
“Internal”, which implies that components (constants) under this level are not to be
changed by the user. Of course, the user can use the structure
cACMEValveLib.Settings.Labels.HighLevel, as described earlier, if the user prefers
more levels.
I/O Addressing Guidelines
A good I/O variable structure is the key to being able to debug and change an
application. A good structure also makes the connection of the application to system
I/O easier to read and understand.
Below are some hints and tips to ensure that the I/O connections have a good
structure.
100
•
A good I/O connection structure requires a good application program structure,
and also a realistic translation of the process to be controlled, into the
application program.
•
Try to collect I/O of the same process object in the same controller, and even in
the same object in the application program.
3BSE040935-511
Section 1 Basic Functions and Components
•
I/O Addressing Guidelines
Try to divide the application program into process cells, with contents similar
to the real process.
These hints are basic rules for object-based programming for real processes, and
once the application has a good structure, it is easier to divide I/O signals into
groups or cells of the process.
3BSE040935-511
101
Connecting Variables to I/O Channels
Section 1 Basic Functions and Components
Connecting Variables to I/O Channels
Only one variable can be connected to each I/O signal, and vice versa. This is not a
problem for output signals, but for input signals it may be necessary to read the
same input signal from different programs, or even from different places in the same
program. This can be done by placing the connected IO variables in a common area,
for example, in the application. Then the variables can be read by the program(s).
Note that the result of an IO copying is different depending on whether the
parameter is IN or IN_OUT. An IN parameter will result in a copy of the value,
whereas an IN_OUT parameter will result in a reference to the current value. While
different tasks can copy the same I/O signal, a task with a higher priority may
update the signal value in the middle of a scan. See also Function Block Execution
on page 59.
If the same I/O signal must be read by different applications, the I/O copying must
be done from one of the applications. The copied value can then be moved to other
applications through ordinary communication services. See also Communication
between Applications Using Access Variables on page 84.
The address for a hardware unit is composed of the hardware tree position numbers
of the unit and its parent units, described from left to right and separated by dots.
For example, channel 1 on the I/O unit DO814 in Figure 32 has the address
Controller_1.0.11.1.1.
Figure 32 illustrates an example of a controller hardware position.
102
3BSE040935-511
Section 1 Basic Functions and Components
Connecting Variables to I/O Channels
Controller_1
Hardware pos. 0
Position 11
Unit 11.1
Channel 1
= Controller_1.0.11.1.1
Figure 32. An example of how IO channel addresses are created in a control project.
All I/O access is done via variables connected to I/O channels and these variables
are connected in the hardware configuration editor. The Connections tab displays all
channels that can be connected.
3BSE040935-511
103
Connecting Variables to I/O Channels
Section 1 Basic Functions and Components
I/O Data Types
Variables connected to I/O can be of any of the simple data types, bool, dint, dword
or real, or any of the system-defined I/O data types. For example, an IO unit input
can be connected to a variable of bool data type or a variable of BoolIO data type.
For applications that only require a simple channel value, it is enough to connect a
variable of simple data type. But for applications that need comprehensive
information like forcing IO channels, reading status, or validate analog channel
values, must connect variables that is of system defined (structured) IO data type.
It is possible to force I/O values, and display forced and non-forced values from
an engineering station, regardless of whether the channel is of a simple data type
or an I/O data type.
The user can always choose a variable that is of the simple data type bool, dint,
dword, or real, and connect it directly to the I/O channel, as long as the user is
content with a simple value in return. However, such a connection does not take
advantage of certain auxiliary signals which come with structured data types. A
predefined structured data type includes signals for I/O forcing, analog signal status,
maximum and minimum values, etc.
Always use In_Out parameters when writing to output I/O variables from a
function block. This will prevent unintentional overwriting of I/O variable
component values, such as scaling. Do not use Out parameters for this purpose.
Figure 33 presents as an example the available components inside the structured
data type BoolIO.
Figure 33. Components inside the structured data type BoolIO
A structured data type (for example, the BoolIO data type) contains four
components. Declare a local variable MyIOVar as a BoolIO data type, and then
104
3BSE040935-511
Section 1 Basic Functions and Components
Connecting Variables to I/O Channels
connect MyIOVar to an IO channel to automatically access these four component
values at the same time.
By declaring a structured data type, more information can be accessed from the
IO channel, which can be read/written in code.
Declaring MyIOVar as a simple data type, Bool, provides access to the channel
value. In other words, the user cannot read or write other values from the code.
When connecting a structured data type to an I/O channel, always connect the
data type (like MyIOVar). Do not try to connect one of the components inside
(like Value, I/O Value, Forced etc.) directly on the I/O channel.
Table 10 shows the (hardware editor) entries to different IO channels. The Type
column presents the IO channel data type in the hardware editor, whereas the
Variable column presents possible data type connections (simple, structured).
Table 10. Possible variable (data types) connections to IO channels.
Channel
Name
Type
Variable
IX, QX
Boolean. input (IX) and
output (QX)
BoolIO
bool, BoolIO
IW, QW
Non-boolean. input (IW) and RealIO
output (QW)
real, RealIO
IW, QW
Non-boolean. input (IW) and DintIO
output (QW)
dint, DintIO
IW, QW
Non-boolean. input (IW) and DwordIO
output (QW)
dword, DwordIO
IW0, QW0 (1)All Inputs, All Outputs
DwordIO
dword, DwordIO
IW0
Channel status
DwordIO
dword, DwordIO
IW0
UnitStatus
HWStatus dint, HWStatus
(1) ISP and OSP values are not set for variables connected to All Inputs/All Outputs!
For more information see also Access All Inputs and All Outputs on page 298.
See Figure 34 and the corresponding structured data types in Table 10.
3BSE040935-511
105
Connecting Variables to I/O Channels
IO channel of type boolIO.
Section 1 Basic Functions and Components
MyIOVar of BoolIO (correct connection).
Figure 34. A correct way of connecting IO variables. The structured data type
MyIOVar connected to an IO channel.
Example of I/O Channel Representation
The IO channel in Figure 34, IX0.11.1.1, interpreted from Table 10, gives the
following: IX is a Boolean input, whereas 0.11.1 represents the hardware address
and .1 represents the I/O channel.
Monitoring the Status for Hardware and I/O
UnitStatus is a hardware connection to individual hardware and I/O units in the
Project Explorer. The user can connect a variable to Unit Status by selecting the
Unit Status tab in the hardware editor.
If the user chooses to connect a variable to Unit Status this must be either of a dint
data type or of an HWStatus structured data type. The simple data type dint will
return one of the unit status value 0 (OK), 1 (Error) or 2 (Warning). Whereas, a
variable of HWStatus provides more extended unit status information. See the
contents inside the Unit Status tab in Figure 35.
106
3BSE040935-511
Section 1 Basic Functions and Components
Extensible Parameters in Function Blocks
Figure 35. The components available inside the HWStatus.
In addition to the Unit Status there is a 'collective' hardware connection,
AllUnitStatus, which contains errors and warnings regarding all hardware units
connected to the controller.
Similar to Unit Status, the user can choose to connect a variable of simple data type
dint or a variable of the structured data type HWStatus. The simple data type dint
will return one of the unit status value 0 (OK), 1 (Error) or 2 (Warning). Whereas, a
variable of HWStatus provides more extended unit status information.
Figure 36. The AllUnitStatus connection gives access to the status of all units.
.
For information about supervising IO channels and unit status in online mode, see
Supervising Unit Status on page 296.
Extensible Parameters in Function Blocks
Some function block types have extensible parameters, such as MMSRead,
COMLIRead, etc. This means that the number of input/output parameters is
changeable, and must be specified while declaring the function block in the function
block tab.
3BSE040935-511
107
Keywords for Parameter Descriptions
Section 1 Basic Functions and Components
The editor automatically inserts [1] when the user specifies a function block type
with extensible parameters. Change the number within the brackets to the required
number of parameters.
To see which function block types can have extensible parameters and the maximum
number of parameters for each type, see the Control Builder online help.
In the Function Block Diagram (FBD) and Ladder Diagram (LD) languages, a
maximum of 32 extensible parameters per function block can be shown.
There is no support for online values on Extensible Parameters. No such values
will be presented in online editors or in the project documentation and
consequently it is not recommended to trust these values.
Keywords for Parameter Descriptions
Types that are located in standard libraries contain keywords in the description
column for parameters. These keywords help the user to organize the parameters
and document the purpose of parameters.
Table 11. Type description keywords.
Keyword
Description
IN
The parameter direction is IN (read).
OUT
The parameter direction is OUT (write).
IN(OUT)
The parameter direction is both IN and OUT, but mainly IN (read).
OUT(IN)
The parameter direction is both IN and OUT, but mainly OUT (write).
NODE
Applies only to control modules. Used to indicate that the parameter has
a graphical connection.
EDIT
Applies only to IN parameters. The parameter, which must have a value,
is only read following changes to the application, warm restart or cold
restart.
Be careful not to connect a variable to a parameter with the keyword
EDIT. Use a literal instead.
108
3BSE040935-511
Section 1 Basic Functions and Components
Library Management
Library Management
From the user point of view, there are two main types of library:
•
Standard libraries, that are installed with the product. These are protected and
cannot be changed.
•
User-defined libraries, in which users can add their own types. Copies of
template types (data types, function block types, control module types, and
diagram types), from the standard libraries can be modified and also added into
the user-defined libraries.
The following operations are relevant to both library types:
•
Libraries must be inserted into the control project in which they are used, see
Insert Libraries into Control Projects on page 111.
•
A library that contains types for applications must be connected to all libraries
and applications that use types from the library. Libraries containing the
hardware types (units) used in the controller configuration have to be
connected to the controller. See Connect Library to Application, Library or
Controller on page 111.
•
A library can be disconnected from, an application, library or controller, see
Disconnect Libraries on page 113.
The following operations are relevant to non-standard libraries only, since standard
libraries are protected and cannot be changed:
•
A new library can be created, see Create Libraries on page 114.
•
The state of a library can be changed, see Library States on page 114.
•
The version of a library with hardware types can be changed, see Library
Password Protection on page 115.
•
Types can be added to a library with hardware types, as long as its state is
Open, see Add Types to Libraries Used in Applications on page 116 and Add
Customized Hardware Types to Library on page 118.
•
A library with hardware types can only be deleted if it is not connected to any
application, library or controller.
•
A library can be password-protected, see Library Password Protection on page
115.
3BSE040935-511
109
Connect Libraries
Section 1 Basic Functions and Components
Connect Libraries
In Project Explorer, libraries connected to a control project are stored in the
Libraries folder, while libraries connected to applications and libraries are stored in
the Connected Libraries folder, see Figure 37.
Figure 37. Libraries in Project Explorer
110
3BSE040935-511
Section 1 Basic Functions and Components
Connect Libraries
Insert Libraries into Control Projects
A library always has to be inserted into the control project before it can be
connected to an application or a controller. To connect a library to a control project:
1.
In Project Explorer, expand the Project folder.
2.
Select the Libraries/Hardware folder, right-click it and select Insert Library.
Connect Library to Application, Library or Controller
To connect a library to an application, a library or a controller:
1.
In Project Explorer, expand the corresponding Library, Application or
Controller folder.
2.
Select the corresponding Connected Libraries folder, right-click and select
Connect Library.
It is also possible to connect a library using drag-and-drop operation. Select the
library to be connected, and drag it to the required application, library, or
controller folder.
Replace Connected Library
A connected library can be replaced, for example, when the user wants to update to
a newer library version. Replacing to a newer version, results in that all instances of
a type in the new library will be used instead of the type in the old version.
To replace a connected library:
1.
In the corresponding Connected folder, right-click the library and select
Replace Library.
2.
Press the Yes button and select a library from the drop-down list in dialog box.
3.
Click the Replace button to confirm.
Library Usage
The Library Usage function displays the list of places where a library is used, and
where it is connected. For ordinary libraries the Library Usage function searches
applications and other libraries. For libraries with hardware, it searches controllers.
3BSE040935-511
111
Connect Libraries
1.
Section 1 Basic Functions and Components
Right-click the library and select Library Usage as inFigure 38. The Library
Usage dialog box is displayed with list of applications where the library is
connectedas in Figure 39.
Figure 38. Library Usage
112
3BSE040935-511
Section 1 Basic Functions and Components
Connect Libraries
Figure 39. Library Usage dialog showing connected Libraries
Disconnect Libraries
A library can only be removed if the library and its types are not used within the
project.
To remove a library from a control project:
•
In the Libraries/Hardware folder, right-click the library and select Remove.
The library is removed from the control project.
•
If the Library is in use the following dialog box displays.
•
Click Yes to see the Library Usage dialog box.
Libraries can be disconnected from both applications, libraries and controllers:
3BSE040935-511
113
Create Libraries
Section 1 Basic Functions and Components
•
In the corresponding Connected folder, right-click the library and select
Disconnect (Library). The library is disconnected, but it can be re-connected
at any time, since it is still inserted to the control project.
Create Libraries
To create a new library:
1.
In Project Explorer, right-click Libraries or Hardware and select New
Library... The New Library dialog box is displayed.
Figure 40. New Library dialog box
2.
Enter the name of the new library and click OK. The new library is created and
inserted into the control project.
Library States
A library is always in one out of three possible states:
•
Open
The contents of the library can be changed. This is the normal state for a library
when it is under development.
•
Closed
The contents of the library cannot be changed. However, the state can still be
changed back to Open.
Released
The contents of the library cannot be changed after it is set to released state.
New library versions cannot be made in Compact Control Builder. A library set to
released state cannot be changed again.
114
3BSE040935-511
Section 1 Basic Functions and Components
Library Password Protection
To change the library state:
1.
In Project Explorer, right-click the library and select Properties>State. The
State dialog box is displayed.
Figure 41. State dialog box
2.
Select the desired state and click OK. The library state is changed.
The library state can only change:
•
From Open to Closed or Released.
•
From Closed to Open or Released.
Library Password Protection
To password protect the libraries:
1.
Right-click the library and select Properties > Protection.
The Protection Properties dialog opens.
2.
Click Set Password. The Password dialog opens, see Figure 42.
3BSE040935-511
115
Add Types to Libraries Used in Applications
Section 1 Basic Functions and Components
Figure 42. Password dialog box
3.
Enter the new password and confirm it in the Verify new password field.
If the library is already password protected, you have to enter the old password
before entering a new one. A password may consist of both letters and digits. It
must be at least 6 characters long.
4.
Click OK. The library can now not be changed without entering the password.
Add Types to Libraries Used in Applications
Types can only be added if the library state is Open.
Follow the steps below to add the following functions in a library:
116
3BSE040935-511
Section 1 Basic Functions and Components
5.
Add Types to Libraries Used in Applications
To the library (see Figure 43), add the following:
a.
To connect another library to library, right-click the Connected Libraries
folder and select Connect Library.
Figure 43. Connecting a Library
b.
To add project constants to library, right-click the library folder and select
Project Constants.
Figure 44. Adding Project Constants
c.
3BSE040935-511
To add a type to the library, right-click the folder corresponding to the type
you want to add and select the command for creating a new type.
117
Add Customized Hardware Types to Library
Section 1 Basic Functions and Components
Figure 45. Adding a type
Add Customized Hardware Types to Library
For more information on working with types and project constants, see
Application Types and Instances on page 30.
Customized hardware types can only be added to the library if the library state is
Open. To add a customized hardware type to a library:
In Project Explorer, expand Libraries > Hardware.
Figure 46. Hardware with its libraries.
6.
118
Right-click Hardware types folder under your chosen library, and select
Insert/Replace Hardware Type(s).
3BSE040935-511
Section 1 Basic Functions and Components
Add Customized Hardware Types to Library
Figure 47. Inserting hardware types in library
7.
Browse and select the device capability description file (for example a *.gsd
file) you want to add as hardware and click Open. (See also Supported Device
Capability Description Files on page 120).
8.
The Device Import Wizard starts. Follow the instructions in the wizard.
In exceptional cases, it is possible to insert individual external customized hardware
types to a user-defined library, for example, a hardware type of a *.gsd file that have
been converted and used in an earlier version of Control Builder.
In this case, right-click the Hardware types folder under your chosen library and
select Insert/Replace Hardware Type(s) and browse to the hardware type (*.hwd
file) to be inserted. With Insert/Replace Hardware Type(s) it is also possible to
replace same hardware type.
If a hardware definition file (*.hwd) is re-imported with changed parameters,
Control Builder must be restarted so that the changes take effect.
If changes are made to existing *.hwd files, a new GUID is created for them to
coexist after the re-import.
3BSE040935-511
119
Device Import Wizard
Section 1 Basic Functions and Components
Device Import Wizard
You use this wizard to import a device capability description file. The wizard will
convert this file to a hardware type and insert the type into a user-defined library.
The appearance of some wizard dialog boxes will be different depending on the file
type to import.
Always complete the wizard, even if you are not finished. Then, you can reimport the file and continue where you left off.
When a wizard dialog box is displayed, relevant information is read from the
device capability description file. If it is large this may take a while, and a
progress bar will be shown.
•
You can import a new device capability description file, as described above
(Add Customized Hardware Types to Library on page 118).
•
You can change conversion settings for a previous import, as described in
Wizard on page 123.
•
When you receive an updated device capability description file, you may want
to replace the previous import. Import the new file the same way as the old one,
as described above.
For more information on the Device Import Wizard, refer to the online help.
Supported Device Capability Description Files
You can only import supported device capability description files. The following
files are supported:
•
PROFIBUS GSD files
•
PROFINET IO GSD files
•
Ethernet/IP and DeviceNet EDS files
For PROFIBUS GSD-files, *.gs? is the standard file extension. However, a file can
also have a different extension that specifies its language, for example, *.gse
(English) or *.gsg (German).
120
3BSE040935-511
Section 1 Basic Functions and Components
Additional Files for Libraries with Hardware
For PROFINET IO GSD files, *.xml is the standard file extension. PNIO uses
GSDML, an XML based markup language to describe the characteristics of the
PNIO devices.
For Ethernet/IP and DeviceNet, *.eds is the standard file extension. The wizard will
convert the EDS file to a hardware definition file (HWD File) and insert it as a
hardware type into the user-defined library.
You can only import PROFIBUS GSD-files with hardware types for CI854, and
not for CI851. (However, when you upgrade a previous system offering, any
included hardware types for CI851 will be upgraded as well.)
For more information on using Device Import Wizard for importing gsd, xml and
eds files into the Control Builder, refer to:
•
AC 800M, PROFIBUS DP, Configuration (3BDS009030*).
•
AC 800M, ProfiNet I/O, Configuration (3BDS021515*).
•
AC 800M, EtherNet/IP DeviceNet, Configuration
(9ARD000014*)
Additional Files for Libraries with Hardware
There are a number of files associated with libraries for hardware and hardware
types. For standard system libraries, it is not possible to perform any operation on
these type of files. For a user-defined library there are some files that can be
managed.
The file types, described below, are associated with the hardware definition and
cannot be changed or replaced.
File Types Associated with Hardware Types
To display the Additional Files dialog box for a hardware type:
1.
In Project Explorer, expand the library with the hardware type under
Libraries > Hardware.
2.
Under Hardware types for the library, right-click the hardware type and select
Files.
3BSE040935-511
121
Additional Files for Libraries with Hardware
Section 1 Basic Functions and Components
The only file type (in a user-defined library) that the user can perform any
operations on is the Help File. See Help File on page 123.
The file types, listed in Table 12, are associated with the hardware type and cannot
be modified by the user.
Table 12. File Types Associated with Hardware Types
File Type
Description
Firmware File
Firmware file for CPU or communication interface unit.
Update File
Update file for firmware; a download support file.
Firmware Idx File
Idx file for firmware, used when analyzing a crash dump.
Protocol Handler
Control Builder File
Protocol handler used by Control Builder.
Protocol Handler Controller Protocol handler used by controller.
File
Protocol Handler Idx File
Idx file for controller protocol handler, used when analyzing a
crash dump.
File Types Associated with Libraries
It is only possible to manage Additional files for a user-defined library.
To display the Additional Files dialog for a library with hardware types:
122
1.
In Project Explorer, browse Libraries > Hardware.
2.
Right-click the library and select Properties > Files.
3BSE040935-511
Section 1 Basic Functions and Components
Additional Files for Libraries with Hardware
The file types, listed in Table 13, are associated with the library.
Table 13. File Types Associated with Libraries
File Type
Description
Help File
A help file (of *.chm or *.hlp type) can be added, replaced, deleted
or extracted, See Help File on page 123
Import File
Import file is a device capability description file (for example a
*.gsd file) that has been added with the Device Import Wizard.
This type of file can be deleted (Delete button), or extracted
(Extract button) to a file on disk. By pressing the Wizard button it is
also possible to change the previous done settings. See Wizard .
Wizard
Settings for a previously added device capability description file can be changed.
1.
In Additional Files for a library, select the row with the device capability
description file (Import File) and press the Wizard button.
2.
In the displayed Device Import Wizard, define the new conversion settings.
Help File
A help file (of *.chm type) can be added, replaced, deleted or extracted for a
customized hardware type, as well as for a user-defined library.
Adding a help file to a customized hardware type or a user-defined library provides
access to the associated help file when you press F1on the user-defined library or on
the customized hardware type, in Project Explorer. For further information about
requirements on customized online help, see the Compact 800 Engineering
Compact Control Builder AC 800M Binary and Analog Handling (3BSE041488*)
manual.
To add a help file to a user-defined library or to a customized hardware type:
1.
In Additional Files dialog box, select the Help File row and press the Add
button.
Browse to the help file (of *.chm type) and click Open.
3BSE040935-511
123
Delete Hardware Types
Section 1 Basic Functions and Components
Replace and Delete
A help file that has been added can be replaced and deleted by selecting the row
with the help file and pressing Replace and Delete button respectively. It is also
possible to delete a device capability file (Import File) for a user-defined library.
Extract and Save a Copy of a File
A help file can be extracted and saved on disk by selecting the row with the help file
and press the Extract button (to the right of the grid). Browse to a place on disk and
save a copy of the file by pressing Save button.
In some exceptional cases there is a need to extract an individual customized
hardware type to a hardware definition file (*.hwd file). In this case, press the
Extract button under Hwd File.
Properties on Hardware Types
In Additional Files for a customized hardware type, it is possible to set a version
information text of maximum 18 character to the help file, by pressing the
Properties button.
Delete Hardware Types
A hardware type in a library can be removed.
It is not possible to remove a hardware type from a library, if it is used in any
hardware configuration.
1.
In Project Explorer, expand the library with the hardware type under
Libraries > Hardware.
2.
Under Hardware types for the library, right-click the hardware type and select
Remove.
Type Usage for Hardware Types
It is possible to display a list of which controller(s) that use(s) the hardware type
together with hardware tree position numbers.
1.
124
In Project Explorer, expand the library with the hardware type under
Libraries > Hardware.
3BSE040935-511
Section 1 Basic Functions and Components
2.
Type Usage for Hardware Types
Under Hardware types for the library, right-click the hardware type and select
Type Usage.
Figure 48. Type Usage for a selected hardware type.
3BSE040935-511
125
Hide and Protect Control Module Types, Function Block Types, Diagram Types, and Data Types
Hide and Protect Control Module Types, Function Block
Types, Diagram Types, and Data Types
When you create libraries with self-defined control module types, function block
types, diagram types, and data types, Control Builder provides you with two
protection features (attributes). These two attributes are called Hidden and
Protected, and can be set from Project Explorer.
Hidden
Setting the Hidden attribute will completely hide your code from other users. To
hide the code makes it easier to improve your type as often as you like. This is a
common situation when developing types that will be re-used over and over again in
different library solutions.
Protected
Setting your type to Protected will protect the internal type structure from being
seen. This means that only the type itself will be visible, and thus your type
definition will be protected from external exposure, as well as any attempt to
duplicate it. This is extra valuable when you create a type solution for re-use
engineering.
When a protected type is opened in an editor, only the parameter declaration is
visible (read-only). Other declarations like variables and function blocks are not
visible. Only code block tab is shown as a blank page, that is, the IEC 61131-3 logic
is protected. The complete type structure will still be protected from external
exposure.
The Hidden and Protected attribute can also be used for structured data types.
Override
After you have protected your types, you can always override the hidden and
protected attribute temporarily, while you work on improvements. The override
protection property can be set in Project Explorer.
126
3BSE040935-511
Section 1 Basic Functions and Components
Protect a Self-Defined Type
For self-made libraries with password protection, you must enter the password
before you make an override, see Library Password Protection on page 115
The protection cannot be overridden for Control Builder standard libraries. They
cannot be updated or changed by the user.
Protect a Self-Defined Type
To protect a self-defined type:
1.
In Project Explorer, right-click the type and select Properties > Protection
and Scope. A Protection and Scope window opens.
Figure 49. Protection and scope
2.
Check the desired protection radio button(s) and click OK.
Override Protection Attributes
To override protection for a library or application:
3BSE040935-511
127
Protect a Self-Defined Type
1.
Section 1 Basic Functions and Components
In Project Explorer, right-click the library (or application) and select
Properties > Protection. A Protection Properties window opens.
Figure 50. Protection properties
2.
128
Check the Override check box (see figure above) and click OK. The Override
feature will have impact in Project Explorer only.
3BSE040935-511
Section 1 Basic Functions and Components
Task Control
Task Control
A task is defined as an execution control element that is capable of starting, on a
periodic basis, the execution of a set of POUs (Programs, Function blocks, functions
etc.).
The Control Builder setup three tasks (Fast, Normal and Slow) by default, provided
that an AC 800M Control Project template has been selected. The tasks are
connected to their respective diagrams (one task per diagram). The tasks serve as
'work schedulers' for the diagrams and contain settings for interval time and priority.
However, setting interval time and priority is not enough; you must also tune your
tasks.
To learn how to tune tasks, see Compact 800 Engineering Compact Control
Builder AC 800M Planning (3BSE044222*) manual.
If a diagram does not have a task connected, it will run by the task connected to the
corresponding Application.
You may create and connect several tasks to a controller, but experience show that
more than five tasks in each controller makes it difficult to overview.
The Control Builder provides a Task Analysis tool that predicts the execution of an
application by the controller before loading it onto the controller. See Task Analysis
on page 150 for more information.
Task Connections
A task can be connected to a program, a function block, a control module or a single
control module, a diagram, and several tasks may execute in the same controller. An
application can also be connected to a task, and all POUs in an application execute
in this task, unless otherwise specified. A task can only execute POUs in one
application. Hence, POUs from different applications can not be connected to the
same task.
Do not re-connect tasks to applications unless it is necessary, as this might
disrupt the task execution during reconfiguration. Else change the parameters of
the connected task (to fit the needs).
3BSE040935-511
129
Task Connections
Section 1 Basic Functions and Components
Create a New Task
To create and configure a new task:
130
1.
Expand the Hardware tree, until you find Tasks.
2.
Right-click Tasks and select New Task. A ‘New Task’ window opens.
3.
Name the task.
4.
Click OK.
3BSE040935-511
Section 1 Basic Functions and Components
Task Connections
Figure 51. A new task has been created.
After the task has been created, it is time to configure the task with new properties.
5.
Right-click the new task (Superfast) and select Properties. A ‘Task Properties’
window opens.
Figure 52. A Task Properties window for configuring a task.
6.
Change the interval time to 40 ms and Priority to 1-Highest. Click Apply
followed by Close.
7.
Right-click Tasks and select Editor to view the new task. A ‘Task Overview’
window opens.
3BSE040935-511
131
Task Connections
Section 1 Basic Functions and Components
The Task Overview window lists all the tasks with each property settings. To change
the settings for a certain task:
8.
Select a task in the Task Overview window and open Tools > Task Properties.
Right-click a task directly in the hardware tree and select Properties to open the
Task Properties window directly.
Select Tools > Reset Max, to reset all tasks that appear in the editor.
Connect a Task to a Program
To connect the task SuperFast to Program1:
132
1.
Right-click Program1 and select Properties > Task Connection. A ‘Task
Connection’ dialog box opens.
2.
Select a task from the drop-down menu (here SuperFast) and click OK.
3BSE040935-511
Section 1 Basic Functions and Components
Task Execution
Figure 53. Program1 has changed task to Superfast.
Function Blocks with Different Task Connections
You can connect function blocks inside a program to a task different from the one
connected to the program, (right-click on the function block and select ‘Task
Connection’).
However, variables inside the function block that pass values to and from the
function block are controlled by the program task. The code in the function block
will run according to its task, but the parameters will be updated according to the
program task. This means, in practice, that the function block in a program can only
run at a slower, or a least at the same, speed as the program. However, if you use
external variables or connect I/O directly to the function block, there will be a direct
reference, independent of the task cyclicity of the function block.
To set-up specific time intervals and task priority different from the task connected
to the application whilst for example, designing libraries, can be done by declaring
and using global variables, or by using parameters.
For more information, see Control the Execution of Individual Objects on page
92.
Task Execution
There are four important task parameters that can be set to optimize program
execution:
•
Priority, which sets the execution order for tasks, see sub section Priority
below.
•
Interval time, sets the task intervals during the program is executed, see sub
section Interval Time on page 136.
3BSE040935-511
133
Task Priority
Section 1 Basic Functions and Components
•
Offset, a parameter that helps you to avoid unexpected delays in execution
when tasks are scheduled to execute at the same time. See sub section Offset on
page 137.
•
Execution time, for best real time behavior and communication performance,
avoid extensive continuous execution. See Execution Time on page 142 and
also Communication Considerations on page 140.
All POUs connected to a task execute with the same priority, interval time, offset,
and execution time.
Task Priority
There are six levels of priority: Time Critical, Highest, High, Normal, Low, and
Lowest, numbered from 0 to 5. The tasks are executed according to their priority,
where the time-critical task has the highest priority. A task with higher priority may
interrupt any task with lower priority, but a task cannot interrupt another task with
the same priority. There can only be one time-critical task. Such a task may interrupt
the execution at any point, while other tasks may only interrupt execution at defined
points.
An ordinary (non-time-critical) task can be interrupted:
•
at the start of any code block,
•
at backward jumps, for example for, while, repeat statements.
A time-critical task has special properties.
•
The task is not driven by the same scheduler as the rest of the tasks. Instead, the
task is driven from the system’s real-time clock (hence the high precision).
•
The tasks have high precision in execution time. The resolution is 1 ms.
•
A change to/from time-critical priority in Online mode is not possible.
•
A change to/from time-critical priority in Offline mode requires re-compilation
of the application.
Consider the following points, when using the time-critical priority.
•
134
Only one time-critical task per controller is allowed.
3BSE040935-511
Section 1 Basic Functions and Components
Task Priority
•
The execution time for a time-critical task (priority 0) must not exceed 100ms.
This restraint prevents the task from blocking other functions, for example
communication.
•
All functions cannot be called from the program connected to the task. You
cannot set time-critical priority if the code contains invalid instructions (this is
checked during compilation). The time-critical task interrupts execution at any
time, which means that execution might be interrupted mid-statement.
•
If a power failure occurs while the time-critical task is running, the execution of
the current code block is completed (assuming that it can be completed within
1 ms). For a warm start to be possible, no code block in the time-critical task
may take more than 1 ms to execute.
Task priorities 1–5 can be set by using the firmware function SetPriority. This
function is located in the System folder.
3BSE040935-511
135
Interval Time
Section 1 Basic Functions and Components
Interval Time
The interval time, during which the program is executed, is set in the Task
Properties dialog box. Default values are 50 ms (Fast), 250 ms (Normal) and 1000
ms (Slow). You can change these values at any time. For a time-critical task, the
interval time can be as short as 1 ms. The interval time of tasks of priority 1–5
cannot be less than 10 ms. The resolution is 1 ms.
If two tasks have the same priority, and they both wait for execution, the task with
the shortest interval time will be executed first.
All task intervals must be multiples of each other. The shortest interval is the
"time base".
Execution Example
Figure 54 shows two tasks executing in the same system. Task 1 and task 2 have
interval times of 30 and 200 ms, and execution times of 10 and 50 ms, respectively.
When the tasks have been assigned the same priority, the execution start time of task
1 is very much delayed. It also drops one execution.
Figure 54. Execution of two tasks with the same priority.
In Figure 55, task 1 has higher priority than task 2, and interrupts the execution of
task 2. Hence task 1 is not delayed much by task 2.
136
3BSE040935-511
Section 1 Basic Functions and Components
Offset
Figure 55. Execution of two tasks with different priorities.
Offset
The compiler will detect inappropriate offset settings.
The offset of each task must be equal or greater than the sum of the execution
times of all higher-priority tasks.
If your tasks are scheduled to execute at the same time you will receive a warning
during download. However, this compiler function is merely calculating theoretical
periodic executions, which means that it will not warn you for task collision caused
by, for example a too close offset time. Therefore, consider the compiler warning as
a first preliminary check provided to you and not as a guarantee that will prevent
task collisions.
Two tasks will be scheduled to start execution at the same time if the greatest
common divisor of the tasks interval times divides the difference in the tasks offsets.
Turning off Task Collision warnings
You can turn off the task collision warning from the Project Explorer.
1.
Right-click the Project item and select Settings > Compilation Warnings
from the context menu. A Compilation warnings dialog box will open.
2.
Click to clear Task Collisions check box and then OK.
3BSE040935-511
137
Offset
Section 1 Basic Functions and Components
When tasks are scheduled to execute at the same time, the task with the highest
priority will be executed first. If tasks have the same priority the task with the
shortest interval time will be executed first. Offset is a mechanism that can be used
to avoid unexpected delays in execution when tasks are scheduled to execute at the
same time.
Do not change task offset for a controller with a running application. This may
result in that the task executes one more time than expected.
In Figure 56 and Figure 57, the execution of two tasks with the same priority with
interval times of 50 ms and 100 ms is shown. When both tasks have a 0 ms offset
(Figure 56), the execution start time of task 2 is delayed, and the actual interval time
for task 2 is influenced by variations in the execution time of task 1.
Figure 56. No offset. The two tasks have the same priority, but different interval
times (50 and 100 ms).
If task 2 is assigned an offset, as in Figure 57, neither task is delayed, and the actual
interval time for task 2 will not be affected by task 1.
138
3BSE040935-511
Section 1 Basic Functions and Components
Offset
Figure 57. Offset is set on task 2. The two tasks have the same priority, but different
interval times (50 and 100 ms) and are thus executed at the requested times.
An application starts to execute by scheduling all tasks in the application to execute
at the same time. The task with highest priority is executed first, and if tasks have
the same priority, the task with the shortest interval time will be executed first.
Execution Synchronization
When a task has finished execution of the first scan after application start at time t,
the start of its next execution is synchronized to time 0 (the time the controller
started to execute).
t = n * (interval time) + d,
0  d < interval time
d is the time from the start of the current interval time, to when the task finished
execution in the current interval. The synchronization to time zero (0) implies that
the start of the next execution will be at the first start point after the current time.
If offset = 0, the task will be scheduled to execute at time (n + 1) * (interval time).
However, if the time to the start of the next execution, (interval time) - d, is less than
10 ms, the task will be scheduled to execute a time (n + 2) * (interval time).
If offset > 0, then if offset > d, the start of the next execution will be at a time
n * (interval time) + offset. If offset < d, the start of the next execution will be at a
time (n + 1) * (interval time) + offset. If the time to the start of the next execution is
less than 10 ms, the interval time will be added to the start time of the next
execution.
3BSE040935-511
139
Offset
Section 1 Basic Functions and Components
The same synchronization of execution time will be performed after a change in
interval time or offset.
Time critical task is not synchronized to time zero (0).
Communication Considerations
POU execution has higher priority than other functions, such as communication.
These functions are performed in the gaps between the execution of different tasks.
If several tasks with long execution times are executed immediately, one after the
other, the time gaps are few but long (see Figure 58).
Figure 58. The result of having no offset for three tasks with long execution times.
The gap (Ta+Tb) is the time available for the execution of other functions, for
example communication.
140
3BSE040935-511
Section 1 Basic Functions and Components
Offset
The offset mechanism can be used to make the time gaps more frequent (see
Figure 59).
Figure 59. The result of assigning offset to tasks 2 and 3, is that the time available
for the execution of other functions occurs more often (Ta).
The same processor handles communication and IEC 61131-3 code. This means
that you have to consider how much code you include in each task, when you tune
the tasks.
Assume that we have a task running code with an execution time of 500 ms and an
interval time of 1000 ms. This means a cyclic load of 50%
(load = execution time / interval time). But, this also means that no communication
can be performed during the 500 ms execution (since communication has lower
priority than the task).
Now, assume that we have divided the code into 4 tasks such that each one
corresponds to 125 ms of the execution time. The interval time is still 1000 ms,
hence the load is still 50%. But, if we set the offset for the 4 tasks to 0, 250, 500, and
750 ms, the result will be completely different. Now, code will be executed for
125 ms, after which there will be a pause when communication can be performed.
Following this, code will be executed for another 125 ms followed by another pause
when further communication can be performed. Hence, we still have the same cyclic
load, but the possibility for communication has increased considerably.
To conclude, try to tune your tasks using offsets before you change the priority.
Actually, the only time you have to change the priority, is when two tasks have so
much code that their execution cannot be “contained” within the same time slot, that
is, the total execution time exceeds the length of the time slot. It is then necessary to
specify which of the two tasks is most important to the system.
3BSE040935-511
141
Execution Time
Section 1 Basic Functions and Components
More information about task tuning can be found in the Compact 800
Engineering Compact Control Builder AC 800M Planning (3BSE044222*).
Execution Time
The maximum allowed execution time for time-critical tasks must not exceed
100ms. This is also recommended for the other tasks in the controller. The execution
time for each individual task should be kept feasible to 100 - 200ms.
The maximum allowed execution time does not include the first scan execution
time.
It is preferred to split the execution of a program or application into different tasks,
if the execution time is high and good real time behavior is needed. See
Communication Considerations on page 140.
Overrun and Latency
Overrun and Latency are two functions for supervising a task. Overrun checks if
each task finishes before it is supposed to start the next time, and detects if the task
runs for too long. Latency on the other hand, checks that a task starts on time (on
each cyclic start), and detects if the task starts too late.
The Overrun function is configured per controller via the Controller Settings dialog
box, while the Latency function is configured per task via the Task Properties
dialog box. Both Overrun and the Latency function uses the Error Handler to report
any errors.
Overrun Supervision
Overrun occurs when the execution of a task takes too long, that is, the task is still
executing when the next execution of the task is scheduled to start.
By setting the maximum number of consecutive overruns allowed (missed scans),
you can control when a fatal overrun error is considered to have occurred, and
consequently configure a controller reaction.
These reaction settings are:
•
•
142
Nothing,
Stop Application,
3BSE040935-511
Section 1 Basic Functions and Components
•
Overrun Supervision
Reset Controller.
In an AC 800M controller, load balancing and overrun supervision functions are
mutually exclusive, whereas the Load Balancing function is default. Hence, the
overrun supervision is turned off. For more information about load balancing and
cyclic load, see Load Balancing on page 147.
Configuring Overrun Supervision
Overrun supervision is set for each controller in the Controller Settings dialog box.
To select Overrun Supervision for a controller, follow these steps:
1.
Expand the Hardware tree until the controller (for example, Controller_1).
2.
Right-click the controller and select Properties > Controller Settings from
the pop-up menu. A ‘Controller Settings’ dialog box opens.
Figure 60. Controller Settings dialog box for a AC 800M controller.
3.
3BSE040935-511
Uncheck Load Balancing, (Enable overload compensation check box).
143
Latency Supervision
Section 1 Basic Functions and Components
4.
Select a reaction for Fatal Overrun from the Reaction drop-down menu, (Reset
Controller or Stop Application will activate the Limit field).
5.
Enter the number of consecutive overruns allowed in the Limit field, (number
of consecutive overruns before a fatal overrun is considered to have occurred).
6.
Use the tabs under Error Reaction to set-up actions for different error types and
severity. (For information on Error Reaction settings, see Controller Settings in
Controllers on page 320).
7.
Click OK.
If overrun errors occur, re-program the faulty task to decrease load.
Latency Supervision
Latency occurs when the execution of a task is delayed, that is, the task starts to
execute later than scheduled. The latency function will supervise your tasks (start on
time on each cyclic load), and detect if a task starts sooner or later than scheduled.
Latency is activated in the Task Properties dialog box, where you set the acceptable
latency in percent (accepted latency in percentage of the interval time). The lowest
accepted value for Latency Time is always 10 ms.
Configuring Latency Supervision
Latency supervision is set for each task in the Task Properties dialog box. To select
Latency Supervision for a task, follow these steps:
1.
144
Expand the Hardware tree, until you find Tasks.
3BSE040935-511
Section 1 Basic Functions and Components
2.
Latency Supervision
Right-click a task and select Properties from the pop-up menu. A ‘Task
Properties’ dialog box opens.
Enable
Latency supervision
check box
3.
Select Latency, (check Enable latency supervision check box).
4.
Enter latency percentage into the Accepted latency entry field. The actual used
latency time is shown to the right of the entry field (here 25 ms). The lowest
accepted latency time is 10 ms.
5.
Click Apply. Note how the actual latency time changes if the accepted latency
percentage exceeds 10 %.
6.
Click OK.
If latency error occurs, tune the tasks. Information about task tuning can be found
in the Compact 800 Engineering Compact Control Builder AC 800M Planning
(3BSE044222*).
3BSE040935-511
145
Task Abortion
Section 1 Basic Functions and Components
Latency Alarm Limit
A latency warning is issued if latency is above 70% of accepted latency. A system
alarm, actual latency in ms is generated, and added to the system log. A yellow
warning
is written to the Actual column of Latency alarm limit and “Latency
high alarm limit exceeded” is written in the Remark field of the task properties
dialog box.
Latency is measured on a periodic basic, the time from the start of one execution to
the start of next execution is measured. The latency is then calculated as the
difference between this value and the interval time. Latency can then be both
positive and negative. The maximum latency time is the absolute value of actual
latency.
If requested offset is 0 it is possible that actual offset is large, compared to actual
latency.
Example
Task A: Interval Time=150 ms, Offset=0 ms, Priority=4 - Low and
Execution Time=1 ms.
Task B: Interval Time=150 ms, Offset=0, Priority=3 - Normal and
Execution Time=17 ms.
In this case the actual offset of Task A is about 18 ms and actual latency vary from
-1 to +1 ms.
The execution of task A is delayed about 18 ms for each interval, which results in an
actual offset of 18 ms. This delay is repeated for each period which result in a small
actual latency, -1 to +1 ms.
If the interval time of Task A is changed to 50 ms the actual latency of Task A will
assume the values -18 ms, 0 ms, +18ms. Actual offset will assume the values 0 ms
and 18 ms.
Task Abortion
If a task is aborted, the corresponding application will be stopped. The following
criteria apply to a task abortion.
146
3BSE040935-511
Section 1 Basic Functions and Components
Load Balancing
Time-critical Tasks
Time-critical tasks (priority 0) are aborted when the execution time exceeds 300 ms.
Non Time-critical Tasks
Non-time-critical tasks (priority 1-5) are aborted when:
•
The execution time exceeds 10 seconds.
•
The execution time exceeds (100 * IntervalTime).
This means that if IntervalTime is set to 100 ms or higher (100 * 100 ms = 10
seconds), tasks will be aborted if they have not been executed within 10 seconds.
If IntervalTime has been set to <100 ms, tasks will be aborted if they are not
executed within (100 * IntervalTime).
Load Balancing
The cyclic load is the percentage of controller CPU power used for program
execution of application code. If the cyclic load exceeds 70% in the controller,
so-called load balancing is initiated automatically. The interval time for all tasks,
except the time-critical task, is then generally increased, to limit the cyclic load to
70%.
If the cyclic load then falls below 70% again, the interval time will normally be
decreased in all tasks, except for the time-critical task. However, the interval time
never falls below the original defined interval time.
3BSE040935-511
147
Load Balancing
Section 1 Basic Functions and Components
Whenever the interval time is changed due to load balancing, a SystemSimpleEvent,
expressed in percent (%) of the actual interval time, is generated, and added to the
system log.
Load balancing for the time-critical task is handled as follows (this differs from
non-time-critical tasks). The interval time for the time-critical task is increased,
whenever its execution time exceeds 50% of its interval time.
For example, if a time-critical task has an interval time of 100 ms, and the
execution time becomes 54 ms in an interval, then the new interval time becomes
108 ms. However, the interval time must be reset manually, after it has been
increased. The interval time of the time-critical task is never decreased
automatically, as for the other tasks.
Change the Requested Interval Time to its original value, or another suitable
value, in the Task Properties dialog box(in Online mode). Press Apply or OK to
bring the reset into effect.
Whenever the interval time is increased for the time-critical task, due to load
balancing, a SystemSimpleEvent, expressed as the actual interval time in ms, is
generated and added to the system log.
148
3BSE040935-511
Section 1 Basic Functions and Components
Non-Cyclic Execution in Debug Mode
Non-Cyclic Execution in Debug Mode
A task can be set up for non-cyclic execution. Use non-cyclic execution to simplify
the debugging of a program.
Debug Mode
Debug mode allows you to debug an application by halting the application running
in the controller, and executing the code one execution at the time.
Debug mode is enabled from the Task Properties dialog box(right-click the task in
Project Explorer, and select Properties).
When you have selected Enable debug mode, you can halt the cyclic execution of a
task by clicking Halt. When the task is halted, you can execute the task once by
clicking One Execution. (This is referred to as “non-cyclic execution”.)
Other tasks will not be affected if one task is set up for Debug mode, they will run in
normal cyclic execution mode.
To return to normal cyclic execution of the task, click Run.
A task in Debug mode is indicated in Project Explorer with a warning icon (a
yellow circle with a black exclamation point).
Functions based on the real-time clock (PID controllers, timers, etc.) cannot be
properly debugged in Debug mode.
Timer functions will take into account the actual time elapsed since started,
regardless if, for example, the task is halted in Debug mode.
3BSE040935-511
149
Task Analysis
Section 1 Basic Functions and Components
Task Analysis
The Control Builder provides a Task Analysis tool to predict the execution of tasks
in controllers before downloading the application to a controller.
The Task Analysis tool provides the following functions before the download of the
application:
•
Analyzes the task scheduling in the application.
•
Presents a graphical representation of how the tasks will execute with the
application.
•
Detects possible overload situations before the download of the application.
The tool detects problems such as task latency, task overrun and overload of
task execution.
•
Allows remedial actions by providing the option to change the execution time
of the tasks and view the updated analysis.
The update of the task execution time using the Task Analysis tool updates the
task for analysis only. The actual execution time of the task need to be changed by
updating the Task Values in the Task Properties dialog box in Control Builder.
The Task Analysis tool can be used before normal download. For initial download,
the execution time of the tasks is assumed to be 1ms for the analysis.
If the task configuration in the Control Builder project is changed before a normal
download, the Task Analysis dialog box automatically appears during the normal
download.
To open the Task Analysis dialog box in Control Builder in Offline mode or Online
mode, go to Tools > Task Analysis.
To enable/disable the Task Analysis function, go to Tools > Setup > Station >
Application Download, and edit the value in the EnableTaskAnalysisTool
text box to true or false. The default is true.
150
3BSE040935-511
Section 1 Basic Functions and Components
Exploring the Interface
Exploring the Interface
The Task Analysis dialog box displays a summary view, a detailed view, and the
status of the summary as shown in Figure 61.
Figure 61. Task analysis tool opened from Tools > Task Analysis
Summary view
This view lists the controllers to which the applications are downloaded. A circular
icon (for example, ) appears beside each controller indicating the various states.
The indications are:
•
Red icon: Error
•
Yellow icon: Warning
•
Green icon: Ok
3BSE040935-511
151
Exploring the Interface
Section 1 Basic Functions and Components
If the task execution contains errors or warnings, the description of the error or
warning is also displayed.
Detailed view
This view displays each controller (listed in Summary view) in a separate tab, as
shown in Figure 61.
Click each tab to open the graph showing the task execution of that controller. The
tasks are plotted on the graph with the Priority on the Y-axis and the Time
(task execution time) on the X-axis. Moving the cursor over each task name opens a
tooltip displaying its execution time, interval time, and offset.
Status
This is found at the bottom of the tool interface as shown in Figure 61. It displays
the total number of errors and warnings, and the icon (in red, yellow or green). This
helps to decide if it is safe to download the new application.
The significance of the indications are described below:
152
•
Red — the new application cannot be downloaded as there is a risk of
overloading the controller.
•
Yellow — the download of the new application may cause overloading of
controller. The user must, based on analysis, decide if it is feasible to go ahead
with the new application download.
•
Green — the new application is safe to be downloaded to the controller.
3BSE040935-511
Section 1 Basic Functions and Components
Exploring the Interface
Figure 62. Task Analysis tool with error and warning indications
Task Analysis During Download
If the task configuration in the Control Builder project is changed before the
download, the Task Analysis dialog box automatically appears during normal
download, with the additional options to accept or cancel the download (
and
icons). See Figure 63.
3BSE040935-511
153
Exploring the Interface
Section 1 Basic Functions and Components
If the Task Analysis dialog box shows errors, the
icon is not activated.
Accept
Reject
Execution Time = 1 ms
Figure 63. Task Analysis with additional options to accept or cancel the download
The execution time is fetched from the controller.
If a task is not running in the controller when the execution time is requested, the
tool uses 1ms as the execution time, and the
icon appears beside the
task name. See Figure 63. The
icon also appears if the task execution time is
modified for analysis.
154
3BSE040935-511
Section 1 Basic Functions and Components
Modifying Task Execution Time
Modifying Task Execution Time
The Execution Time of each task can be modified for analysis.
To modify the execution time of a task for analysis:
1.
On the detailed view in Task Analysis dialog box, open the tab screen of the
controller for which the task need to be changed.
2.
Click the
icon, or from the toolbar, select Tools > Settings.
The Task Settings ControllerName dialog box appears as shown in Figure 64.
Figure 64. Task settings
3.
Modify the execution times under New Execution Time column
corresponding to the task name, and click OK.
The graph is updated as per the new execution time, and the
beside the task name of the modified task.
icon appears
Error and Warning Categories
The errors and warnings that are displayed by the Task Analysis tool are generated
based on the following categories of analysis:
•
•
•
3BSE040935-511
Accepted latency
Task latency
Task overrun
155
Error and Warning Categories
•
•
•
•
Section 1 Basic Functions and Components
Interrupted execution
Cyclic load overload
Total load overload
First scan execution limit
Table 14 describes these categories and the corresponding reasons for errors and
warnings.
In the Task Analysis dialog box, these errors and warnings are displayed with
relevant messages that describe the problem.
Table 14. Categories of errors and warnings in Task Analysis tool
Category
Reason for Warning
Reason for Error
Accepted latency
An Accepted Latency value that is
set below 10% (default value) of the
Interval Time.
Task latency
The latency is detected and it is not The latency is detected and it is
within the Accepted Latency, but the not within the Accepted Latency,
latency supervision is disabled.
and the latency supervision is
enabled.
Task Gap
The time gap is too small (less than The time gap is too small (less
20% of the execution time of the
than 10% of the execution time of
task last executed) or <= 5ms.
the task last executed).
Task overrun
-
The overrun is detected, that is,
the task has not finished executing
one scan before the next cycle is
supposed to start.
Interrupted execution The task is interrupted by a higher prioritized task, and the task scan is
delayed.
Cyclic load overload
156
The task uses more than 50% of the The task uses more than 70% of
total cyclic load in the controller.
the total cyclic load in the
controller.
3BSE040935-511
Section 1 Basic Functions and Components
Search and Navigation
Table 14. Categories of errors and warnings in Task Analysis tool
Category
Reason for Warning
Total load overload
The total load in the controller is
above 70%.
Reason for Error
The total load in the controller is
above 98%.
Note: This check is relevant for
download using Load Evaluate Go
as well as for the download with
modified execution times.
First scan execution
limit
The load dependent first scan
execution time (LFST) is 90% of the
maximum Interval Time+Accepted
Latency.
The load dependent first scan
execution time (LFST) is more
than the maximum Interval
Time+Accepted Latency.
Tip: The duration of the first scan
execution time depends on the
cyclic load of the remaining tasks.
If the remaining tasks use L% CPU
load, the LFST = (FST*100)/(100-L).
Search and Navigation
The Search and Navigation function makes it possible for the user to search for
symbols (see Symbol and Definition on page 161) in a project, by using advanced
queries, for example, to find out where a certain variable is used in an application.
If a global variable and a data type in the application have the same name the
search data base will become faulty. This may results in that a symbol cannot be
found.
All symbols matching the search criteria are shown, together with definitions where
the symbols are declared. If a symbol is selected, all references where the selected
symbol is used in the project are also shown. By double-clicking on a definition, it is
possible to navigate to the editor where the symbol is declared. A double-click on a
reference shows the editor where the symbol is used.
3BSE040935-511
157
Search and Navigation Dialog
Section 1 Basic Functions and Components
A report that contains the last search result shown in the Search and Navigation
dialog box can also be generated (see Reports on page 172).
The Search and Navigation function is available in offline, online and test mode.
For information on search and navigation in online mode, see Search and
Navigation in Online and Test Mode on page 310.
Search and Navigation Dialog
The Search and Navigation dialog box mainly consists of Search settings, Symbol,
Definition and References. All Search settings are remembered and will be applied
next time the dialog box is used (until Control Builder is shut down).
The Search and Navigation dialog box can be accessed from Project Explorer,
context menus and editors:
158
•
In the Project Explorer, select Edit > Search.
•
Right-click a Project Explorer object (not Tasks) and select Search or
Alt+F12.
•
Select Edit > Search or right-click and select Search (or Alt+F12) in a POU
editor, a connection editor, a hardware editor or an access variable editor. These
editors also have a search tool bar button
that has the same function.
3BSE040935-511
Section 1 Basic Functions and Components
Search Settings
Search
settings
Symbol
Definition
Figure 65. The Search and Navigation dialog box
Search Settings
The Search part of the dialog box consists of the Search For: drop-down list, the
Search In: drop-down list, the Search Options radio buttons, the Max no of Hits edit
field and the Search button. Filter Result belongs to References (see Filter Result on
page 168) and the Rebuild button rebuild the Search data base (see Search Data on
page 172).
Search For:
In the Search For text field you enter the symbols to search for (see Symbol and
Definition on page 161). Search Options can be selected for the symbol text entered
in the Search For: text field. An empty text or an asterisk (*) character in the Search
For: text field search for all symbols. All symbols are case-insensitive, that is, a
search for the texts “my”, “My”, “mY” and “MY” gives the same search results.
3BSE040935-511
159
Search Settings
Section 1 Basic Functions and Components
Search Options
The default setting of Search Options is Match whole word. The Match substring
option searches for all symbols containing the entered text as a substring and the
Match prefix option searches for all symbols containing the entered text in the
beginning of the symbol names.
Max no of Hits:
The entered value in the Max no of Hits: field maximizes the number of symbols
that can be found at a search. The default value is 100.
Search In:
The selection in the Search In: drop-down list specifies where, in the project, you
want to search for the entered text symbol. An empty text field gives a search
through the whole project. Applications, Controllers or Libraries are selected if a
search after the Symbol is performed in all applications, all controllers or all
libraries respectively.
The text in the Search and Navigation Dialog on page 159,
Applications.Application_1.Diagram2 performs a search in Diagram2 of
Application_1.
In Controllers it is only possible to search for access variables and I/O channels as
symbols, since the search symbol has to be defined (declared) under Controllers,
in Project Explorer, to match the search criteria.
Select Search “In: Applications” (not Controllers) if you want to know in which I/O
unit a certain variable is connected.
Example
In the example below, see Figure 66, a search for the variable “start” is performed to
find out which I/O channel it is connected to. “start” is connected to channel 3 in
hardware on position 0.11.1. By double-clicking on I/O channel (3), in References
pane, you navigate to the I/O unit editor there “start” is connected.
160
3BSE040935-511
Section 1 Basic Functions and Components
Symbol and Definition
Figure 66. (Part of Search and Navigation dialog box at top) A search for “start”
variable in “Applications” to find out which I/O channel “start” is connected to.
(Part of Hardware Editor at bottom).
Search Button
A click on the Search button performs the search according to the settings. The
search result will be shown.
Always on Top
If Always on Top is checked, the Search and Navigation dialog box is placed in
front of all other Windows dialog boxes.
Symbol and Definition
The Symbol objects or the Definitions can be sorted in ascending or descending
order, by clicking on the corresponding title. A new click will toggle the sorting
order. The selected sorting order is remembered and will be used next time.
3BSE040935-511
161
Symbol and Definition
Section 1 Basic Functions and Components
Figure 67. The Symbol and Definition part of the Search and Navigation dialog.
Symbol
A symbol is an object, which can be search for in a project, by using the Search and
Navigation dialog box.
Examples of symbols are:
•
hardware channels, access variables, project constants, variables, global
variables, external variables, communication variables, parameters, extensible
parameters, diagrams, programs, function blocks, function block types, control
modules, control module types, single control modules, data types, functions,
Sequential Function Chart steps, Sequential Function Chart transitions,
Sequential Function Chart sequences, applications, controllers and libraries.
Examples of objects that are not symbols:
•
hardware types, tasks, task connections, comments, descriptions and language
statements in the code, labels in Instruction List code, code block names,
connected libraries.
A symbol can be selected by clicking on it, clicking on the definition of the symbol
or by using the arrow up/down keys on the keyboard.
Definition
The definition of a symbol is where the symbol is declared. The definition of a
variable is where in the project the variable is declared, for example in a program.
It is possible to navigate to the definition by double-click on it or by using the
context menu. The enter key on the keyboard can also be used. The editor where the
symbol is declared is shown with the symbol highlighted.
162
3BSE040935-511
Section 1 Basic Functions and Components
References
Definition Context Menu
Right-click a Definition to get the context menu selections.
•
Go To Definition in Editor navigates to the editor where the symbol is
declared.
•
Go To Definition in Project Explorer navigates to the location of the symbol
in Project Explorer.
•
Report... See Reports on page 172.
References
The References of a symbol is where in the project the symbol is used.
For example, a variable can be used/accessed by several code lines in several code
blocks, and as an actual parameter to a function call or function block call, or as a
parameter to a control module/single control module. The variable can also be used
(connected to) an I/O channel or an access variable.
Figure 68. The References part of the Search and Navigation dialog
In the example in Figure 68, the start symbol is used at two locations:
•
•
3BSE040935-511
function block OpenDoors, in Code code block of Diagram2.
in channel 3 of unit 1 at position 0 in Controller_1.
163
References
Section 1 Basic Functions and Components
It is possible to navigate to a reference by double-clicking it, or by using the context
menu. The enter key of the keyboard can also be used. The present editor is shown
with the symbol highlighted.
In the References pane, the project name always appears as the root.
Communication Variables are the only symbols that have references in different
projects.
If the communication variable that is being searched is present in another project,
the References pane displays this variable as part of another project only if the
other project also has been downloaded from the same workstation as the current
project.
References Context Menu
Right-click on a Reference to get the context menu selections.
164
•
Go To Reference in Editor navigates to the editor of the selected reference.
•
Go To Reference in Project Explorer navigates to the referenced object in the
Project Explorer.
•
The Search menu selection gives the user a possibility to initiate new searches
from the references pane. This is useful when a variable/parameter is connected
to a parameter of a control module, single control module, function block or
diagram type.
3BSE040935-511
Section 1 Basic Functions and Components
References
Figure 69. A search for Variable “AppVar1” in Applications.
In the example in Figure 69, Appvar1 is connected to a parameter SM1P1 of a
Single Control Module named SM1.
1.
In References, select SM1.SM1P1(1).
2.
Right-click and select Search.
The Search For: and Search In: text fields will be automatically updated
according to Figure 70. A new search is performed.
The Execute Search Instantly check box (see Execute Search Instantly on page
169) has to be checked. If it is not checked, the user must click the Search button.
3BSE040935-511
165
References
Section 1 Basic Functions and Components
Figure 70. A search for SM1P1 in SM1.
A new search can be done to follow parameter Par1 in single control module SM2.
166
3.
In References, select SM2.Par1(1).
4.
Right-click and select Search.
3BSE040935-511
Section 1 Basic Functions and Components
References
Figure 71. A search for parameter Par1 in SM1.
This example shows an easy way for the user to follow a parameter through a
control module hierarchy. The users only have to use the Search context menu to
follow the parameter downwards the control module hierarchy. It is also possible to
follow a parameter upwards a module/function block hierarchy.
Icons in References
The references are marked in blue and preceded by an icon.The icon can be any of
the following:
Icon
Description
The symbol is written.
The symbol is read.
The symbol is a function block/function block call.
The symbol is accessed by reference.
The symbol is a reference to a graphical connection.
3BSE040935-511
167
Navigation to Editors
Section 1 Basic Functions and Components
Filter Result
The Filter Result option makes it possible to show references with write access only,
or to show references with read access only.
The possible selections are read, write, I/O Channel Out and I/O Channel In. I/O
Channel Out shows references to output channels only, and Channel In shows
references to input channels only.
Navigation to Editors
It is possible to navigate to the following editors and dialogs:
– The POU editor
– The Connection editor (offline only)
– The Control Module Diagram editor
– The Hardware configuration editor
– The Access Variables editor
– The Project Constant dialog (offline only)
It is also possible to navigate to another project, if it is also displayed in the
References pane while searching communication variables.
l
When navigating to an editor or a dialog box, the window already can be active,
but minimized, as well as hidden behind other windows.
It is possible to navigate from a control module parameter or a single control
module parameter connection in the References to a Connection editor. However, if
the parameter connection is a graphical connection, Control Builder navigates to the
Control Module Diagram editor.
Search and Navigation Settings
The Search and Navigation settings dialog box has settings for executing the search
and editing of the search fields.
Select Tools > Setup > Station > Search and Navigation Settings to view the
Search and Navigation settings dialog box.
168
3BSE040935-511
Section 1 Basic Functions and Components
Search and Navigation Settings
Figure 72. The Search and Navigation settings dialog with default settings
Rebuild the Search Data when Opening Project
When this option is checked, Control Builder will rebuild search data when a new
project is loaded in the Control Builder. This check box is, by default, unchecked.
Rebuild the Search Data when Going to Online/Test Mode
When this option is checked, search data is rebuilt when Control Builder is entering
online mode or test mode. This setting ensures that the search data is consistent in
online and test mode compared to offline mode. This check box is, by default,
unchecked.
It is recommended to normally have this check box unchecked
Execute Search Instantly
When this option is checked, the Search and Navigation dialog box will instantly
perform a search when the dialog is accessed with the Search command, from a
menu or tool bar button, that is, the user do not have to press the Search button in
the dialog. The search is only performed if it is obvious what symbol to search for,
that is, both the Search For: and Search In: boxes in the Search and Navigation
dialog have to be filled in automatically. This check box is, by default, checked.
3BSE040935-511
169
Search and Navigation Settings
Section 1 Basic Functions and Components
Example:
Figure 73. Selection of the AC800MStatus and the Search option
1.
2.
In the code block, double click the AC800MStatus variable to select it.
Right click and select Search, or go to the toolbar and select Edit > Search (or
Alt-F12).
Figure 74. The search result after performing above steps.
170
3BSE040935-511
Section 1 Basic Functions and Components
Search and Navigation Settings
Allow editing of the Search Fields in Online/Test Mode
When this option is checked, it enables free editing in the Search field. It is
introduced since the strings in the search fields are very sensitive in this mode. A
single misplaced character ruins the search and the “search in” field is also case
sensitive. This check box is, by default, unchecked.
Iterative searches in Online/Test Mode
When this option is checked, the searches made in Online/Test mode are iterative,
and the search hits are presented in one pane. For details, see Search and Navigation
in Online and Test Mode on page 310.
This checkbox is, by default, checked.
3BSE040935-511
171
Search Data
Section 1 Basic Functions and Components
Search Data
The Search data base contains search data, that is, information about all symbols,
information about the definition of each symbol and information about all
references of each symbol.
It is possible to perform a manual rebuild of the Search data base. The Search data
base can be rebuilt in the following ways:
•
selecting Rebuild Search Data from the context menus of application,
controller and library.
•
selecting Tools > Rebuild all Search Data
•
clicking the Rebuild button in the Search and Navigation dialog
Reports
The search result can be transformed into a report by using Basic HTML Report.xslt,
that is by default installed together with Control Builder. The report contains the last
search result shown in the Search and Navigation dialog. All symbols, definitions
and references are included in the report. The symbols in the report are shown in the
same order as in the Search and Navigation dialog.
1.
Right-click on a Definition and select Report....
Figure 75. The Create Search and Navigation report dialog.
2.
172
Click Create Report button.
If the Open report with registered application is checked, the report will be
opened in a registered application. The Basic HTMLReport produces reports in
HTML format, that is, the report is opened in the registered Web browser.
3BSE040935-511
Section 1 Basic Functions and Components
Analog Input and Output Signal Handling
3.
Specify a directory to save the report in and enter a suitable file name.
4.
Click Save button to store the report file on disk.
It is possible to export the report to Microsoft Excel by using Export to Microsoft
Excel in the Internet Explorer context menu.
Analog Input and Output Signal Handling
Signals start and end in I/O units with I/O channels of the RealIO data type.
Between input and output I/O units, signals are handled in I/O function blocks of the
RealIO data type, or directly in various function blocks, or in control modules of the
ControlConnection data type.
Over and under range measurement
Signal objects of real type are equipped with an option to increase the signal range
with a fixed pre-selected factor of +-15% of the specified range. You can select
individual Signal Objects connected to variables of data type RealIO on the
controller and set the input parameter EnableOverUnderRange to true. The Signal
Object enabled with over and under range feature, displays the output parameter
OverUnderRangeEnabled as true to inform the surrounding code about the extended
range.
The default value on EnableOverUnderRange depends on a global project constant
from BasicLib. The default value for this project constant is false and Over and
Under range feature is disabled.
Input objects connected to I/O
To enable signal range extensions on input signals, in Project Explorer, click
connected controller > Hardware AC 800M >Editor > Settings. Set the Clamp
Analog in values as false. See Figure 76.
3BSE040935-511
173
Analog Input and Output Signal Handling
Section 1 Basic Functions and Components
Figure 76. Enabling over and under range for input objects.
174
3BSE040935-511
Section 1 Basic Functions and Components
Analog Input and Output Signal Handling
Output objects connected to I/O
To enable signal range extensions on output signals, in Project Explorer, click
connected controller > Hardware AC 800M >Editor > Settings. Set the Clamp
Analog out values as false. See Figure 77.
Figure 77. Enabling over and under range for output objects
3BSE040935-511
175
Backup Media
Section 1 Basic Functions and Components
Backup Media
The AC 800M controllers contain a card slot located at the front of the controller.
This card slot allows the restore of the saved configuration data and firmware data
from the backup media.
The supported backup media for AC 800M controllers are:
•
Compact Flash card (supported in all AC 800M controllers except PM891)
•
Secure Digital card (supported only in PM891)
The backup media cards are useful to save data in case of unpredictable power
supply and for transferring new or updated applications to other controllers.
For more information about the AC 800M controller, see the subsection ‘Product
Overview’ in the AC 800M Controller Hardware.
The card will be activated and read after a long controller reset (or power failure)
and your application(s) can be loaded into the new controller host without
performing a monitored application download from a Control Builder station.
The backup media does not support distributed applications; hence you cannot
use the memory card in a controller that run distributed applications.
An AC 800M configured as time master (CNCP order number 1) does not
transmit any clock synchronization messages if it starts from a backup media
image, and the time quality in the AC 800M is bad due to a discharged battery.
The time in the AC 800M has to be manually set using the function block SetDT
in order to have the clock synchronization in place.
176
3BSE040935-511
Section 1 Basic Functions and Components
Compact Flash
Compact Flash
Compact Flash (CF) is a portable memory card that can be easily inserted to the card
slot located at the front of AC 800M controllers (except PM891).
Specifications for Compact Flash Card
The following are the specifications for the CF card used in AC 800M controllers
(PM8xx, except PM891):
•
Formatted according to FAT16 or FAT32.
•
Minimum read speed – 8MB/second.
•
Minimum write speed – 6MB/second.
•
Same (or better) ambient temperature operative range compared to the PM8xx
that uses the card.
Recommended Compact Flash Cards
Only industrial type Compact Flash cards must be used with the AC 800M
controller.
The recommended industrial type CF cards are:
•
SanDisk Industrial Grade
•
SiliconSystems SiliconDrive
Secure Digital
Secure Digital (SD) is a portable memory card that can be easily inserted to the card
slot located at the front of the PM891 controller.
3BSE040935-511
177
Adding CF Card or SD Card to Hardware
Section 1 Basic Functions and Components
Specifications for Secure Digital Card
The specifications for the SD/SDHC card used in AC 800M controller (PM891):
•
Formatted according to FAT32.
•
Minimum read speed – 8MB/second.
•
Minimum write speed – 6MB/second.
•
Same (or better) ambient temperature operative range compared to the PM891
that uses the card.
SD/SDHC card formatted according to exFAT is not supported.
Adding CF Card or SD Card to Hardware
Ensure that BasicHwLib is inserted under Hardware and that it is connected to the
controller.
From the Project Explorer:
1.
Expand the Controllers item until you reach the CF Reader (or SD Reader)
item (see Figure 78).
2.
Right-click the CF Reader (or SD Reader) and select Insert Unit from the
context menu. A dialog opens.
3.
Select CF Card (or SD Card) in the dialog, and click Insert.
4.
Click Close.
Figure 78. The Controllers item expanded and the CF Card connected to the CF
Reader item.
178
3BSE040935-511
Section 1 Basic Functions and Components
Saving Cold Retain Values on Files
Saving Cold Retain Values on Files
The cold retain values used by the backup media can either be saved cyclically via
the settings in the hardware editor, or from the code via the function block
(SaveColdRetain).
Either way, these values are only saved on files located on the backup media. Thus,
not be confused with the cold retain values saved by Control Builder or OPC Server
during a download.
Read more about the SaveColdretain function block type in Control Builder
online help.
An OPC Server will not be able to give any data if the AC 800M starts to execute a
different version found at the backup media after the power is resumed. All OPC
quality in this case will be BAD, because the OPC Server has no way of finding the
correct description files. But, if the backup media has the last created version, then
the AC 800M continues to execute the last version, and the OPC server can generate
data.
Also note that cold retain values will not be saved on the backup media in case there
is an application version mismatch.
Setting Up Cyclic Save of Cold Retain Values
As mentioned earlier, saving cold retain values cyclic are one of two methods for a
single CPU configuration. The other method is saving cold retain values based on
process events, accomplished by calling the function block (SaveColdRetain) from
the code. You should typically decide one of these two methods. However, if you
run with a redundant CPU configuration, then you must read Cold Retain Values for
Redundant CPU Configuration on page 180.
This subsection will describe how to save cold retain values cyclic. Provided that
you have added the CF Card (or SD Card) to your Hardware tree, do the following:
1.
Double-click the CF Card (or SD Card) and select Settings tab in the
hardware editor.
2.
Set the cyclic interval time for saving cold retain values to file. The default
value is (60 min.). See Figure 79.
3BSE040935-511
179
Saving Cold Retain Values on Files
Section 1 Basic Functions and Components
Figure 79. Settings for Save cold retain values (default 60 min.).
To prevent CF card or SD card from saving additional cold retain values, you
must set the parameter Value to zero (0). Otherwise it will keep saving new
values to file. Setting the value to 0 would normally be the case before shipping
the backup media to a host control system.
3.
Close the hardware editor.
Cold Retain Values for Redundant CPU Configuration
If you have a redundant CPU configuration; you cannot save cold retain values
cyclic or by the function block.
However, you can always save cold retain values via the Tool menu in Control
Builder so that your cold retain values will be part of the application, thus be loaded
to the backup media.
To save cold retain values for a redundant CPU configuration in Control Builder,
first make sure your project is Online:
1.
In the Project Explorer menu bar select Tools > Save “ColdRetain” Values. A
‘Save “ColdRetain” Values’ dialog will open.
2.
Click Save. The cold retain values are saved with your application and you are
now ready to download to the CF card or SD card. These values will be
included when you download the next time to the CF or SD card.
If an AC 800M contains redundant communication interfaces on the CEX-bus,
then perform a download to the controller before creating the Compact Flash
image. Make sure that the project is not closed while creating the image and
before it goes offline, else the image is not completed.
180
3BSE040935-511
Section 1 Basic Functions and Components
Downloading the Application to Removable Media
Downloading the Application to Removable Media
Before you can download your application to the backup media, you must connect
an external Compact Flash Writer or Secure Digital Writer to your Control Builder
PC. The writer is normally connected to the PCs USB port.
It is not possible to download to removable media if the Difference Report is
enabled for the project. To check the Difference Report setting, right click the
project name, and select Settings > Difference Report.
From the Project Explorer, make sure your project is in offline mode and that the
Difference Report is not enabled. Then, do the following:
1. Insert a Compact Flash card or a Secure Digital card in the Writer slot.
2. Right-click controller and select Download to Removable Media from the
context-menu. A Backup Media dialog window will open.
3. Select Writer and click OK. The Control Builder will write the application to
the backup media.
In case the Control Builder source code files is to be placed on the CF/SD card, it
is recommended to zip these files into one single file before placing it on the card.
For a redundant CPU configuration, you need to write the same application twice
(two CF/SD cards, one in each CPU). Copy (in Windows Explorer) the
downloaded application (two folders) from the CF/SD card and paste them
temporarily on your local disk. Insert the next memory card into the Writer and
drag your two folders from the hard disk and drop them on the new CF memory
card.
Configuration Load
Configuration Load means to load a controller configuration, all applications and
their corresponding cold retain values from the backup media. After a configuration
load, the application can read all the critical process (cold retain) values that was
stored on the backup media (CF card or SD card).
If or when a control system is shuts down due to power failure, and no battery
backup in the controller is available, the backup media can re-boot the control
system with the latest and the most efficient cold retain values.
3BSE040935-511
181
Upgrading Controller Firmware using Backup Media
Section 1 Basic Functions and Components
In case of a redundant processor unit configuration, it is recommended to insert a
CF card or SD card in both CPUs.
Application Version Check
If the application version in the controller is not identical with the version in the
backup media or vice verse; a warning message will alert and no more cold retain
values can be saved.
Upgrading Controller Firmware using Backup Media
When a controller is started, or when a long reset is done, the execution starts in the
Boot Loader. While starting, the controller checks for any inserted CF card or SD
card. If a card is present, then the controller checks for valid firmware in it. If valid
firmware is found, it will be used for upgrading the current firmware.
Upgrading a controller’s firmware using a removable backup media, involves the
following steps:
1.
Loading a copy of the firmware (that is, a firmware image) onto the backup
media using Control Builder (refer Loading the Firmware Image to Removable
Media on page 182).
2.
Upgrading the controller firmware using the image on the backup media (refer
Upgrading Controller Firmware from a CF/SD card on page 186).
Loading the Firmware Image to Removable Media
Follow the steps given below for loading a firmware image from the Control Builder
to a removable backup media:
182
1.
Mount the backup media card (SD or CF card) on the card reader-writer of the
Control Builder PC. Make sure that no other program uses or accesses the card.
2.
Right-click on the controller object of the same type as the contoller to be
upgraded.
3.
From the context-menu, select Load Firmware to Removable Media. The
Load Firmware to Removable Media window appears.
3BSE040935-511
Section 1 Basic Functions and Components
4.
Upgrading Controller Firmware using Backup Media
The Load Firmware to Removable Media window displays details of the card
being used and the action that will be taken. The displayed details differ
depending on whether the media card is SD or CF. Click Yes to proceed or No
to cancel the operation.
Figure 80. Card details for PM865 PA/TP830
Figure 81. Card details for PM891
5.
On clicking Yes, a list of identified removable media appears. If the card is not
present in the list of removable media, then try the following:
–
3BSE040935-511
Unmount and then remount the media again.
183
Upgrading Controller Firmware using Backup Media
–
6.
Section 1 Basic Functions and Components
Make sure that the card is formatted in a file system. If not, use the
Windows format tool or Diskpart to format it in FAT or FAT32 file system.
Click the required removable media to select it, and then click Yes to proceed.
Either of the following cases will happen:
–
If the media used is CF, the Diskpart tool then formats the CF card to
FAT 16 with a maximum size of 2 GB (even if the size of the card is
greater). The progress of the Diskpart tool will be displayed in a command
prompt window. Upon completion the window closes automatically and
the firmware image is copied to the card
–
If the media is an SD card, then no formatting is required at this point. The
firmware image is copied to the card.
If the above operations are a success, then:
•
There will be four files on the card (see Figure 82 for CF card and Figure 83 for
SD card). If the media card is CF, then it has been formatted as FAT.
•
The file content.txt has been rewritten and the first row describes the selected
controller. Other rows remain either untouched or partly rewritten.
Figure 82. Firmware image files on CF card
184
3BSE040935-511
Section 1 Basic Functions and Components
Upgrading Controller Firmware using Backup Media
Figure 83. Firmware image files on SD card
If the operation is a failure, a message is displayed conveying the same. Further
information about the failure can be found in the Control Builder session log.
While Diskpart is formatting the CF card, it is possible that Windows may
discover the card as an unformatted disk. In such a case, the following dialogue
will be dislayed. Here, select Cancel. If not, there will be two program instances
trying to format the card at the same time.
Figure 84. Windows dialog for formatting unformatted disks
3BSE040935-511
185
Restoring Formatted CF Cards to Original Size
Section 1 Basic Functions and Components
Upgrading Controller Firmware from a CF/SD card
1.
Insert the CF card or SD card in the card reader slot of the CPU and Power-On.
2.
Perform a Controller Reset, by pressing and holding the INIT button till the
green Run LED starts flashing.
3.
Release the INIT button to start the loading firmware. The process to load the
Firmware starts, and the Run and the Battery LEDs indicate the progress.
At the end of the operation, the hardware reset starts the newly programmed system.
Restoring Formatted CF Cards to Original Size
In some cases the CF card used for copying the firmware from Control Builder, may
have a size of more than 2GB. During copying of the firmware, Diskpart will format
this card to FAT 16, and the size will be limited to 2GB. In such a case, to restore the
card to its full original size, follow the steps given below:
1.
Start the Diskpart tool by selecting Start > All Programs > Accessories >
Run and then type diskpart.exe. The Diskpart tool opens in the command
prompt. You can then procced with the commands written in bold in the
following steps.
2.
List all volumes to identify the actual media by using the list volume
command.
3.
Select the volume by its number or drive letter n by using the command
select volume n.
4.
Clean the selected volume using the command clean.
5.
Create a partition using create partition primary command.
6.
List all partitions to identify the partition by using list partition command.
7.
Select the partition by its number n by using the command select partition n.
8.
Activate the partition using the active command.
9.
Proceed to format the card with default settings using the format command.
10. When the format is complete, exit.
186
3BSE040935-511
Section 1 Basic Functions and Components
Compiler Switches
You may try the above steps in also cases where the card is shown as unformatted
and/or unreadable.
Compiler Switches
Compiler Switches are used to control the behavior of the compiler by setting
additionally language restrictions.
Global restrictions are valid for all code. Restrictions can be set to generate errors or
warnings at compilation. At compilation, errors and warnings are generated
according to these settings and global restrictions. These restrictions can be used to
stop the use of complex constructions in code, which might cause instabilities or
errors.
Global restrictions are combined as follows:
•
A global error always generate an error
•
A global warning generate a warning for applications.
It is possible to exclude a library from checking with user-defined compiler
switches. Only warnings can be excluded for a library, not errors.
If a library is excluded from a certain restriction, this restriction will not be
checked for any type belonging to that library.
If restrictions are changed, a re-compilation is required before the next download.
Restrictions are checked both at compilation and when checking the code.
Settings
Right-click the control project (root object) and select
Settings > Compiler Switches to open the Compiler Switches dialog.
The possible settings of compiler switches are described in Table 15.
3BSE040935-511
187
Settings
Section 1 Basic Functions and Components
Table 15. Compiler Switches
Switch
Description
Global
Simultaneous Execution in
SFC(1)
Simultaneous sequences in
SFC
A
Loops In ST
Loops in Structured Text (FOR,
WHILE, REPEAT and EXIT)
A
Nested IF or CASE
Nested IF and CASE
statements in Structured Text
A
Implicit Cast
Automatic conversion of data
types (e.g. integer to real)
A
Instruction List language
Instruction List
A
Ladder Diagram language
Ladder Diagram
A
Loops in Control Modules
Code sorting loops
E
SFC Language
Sequential Function Chart
Language
A
Force I/O from code
The compiler switch for forcing
I/O signals from code. It
restricts changes of the Forced
component in variables of one
of the data types BoolIO,
RealIO, DintIO and DwordIO
and results in either warning or
error when the switch is
activated.
A
Example: MyBoolIOVar.Forced
:= true; Not allowed since this
assignment directly affects the
“Forced” component.
188
3BSE040935-511
Section 1 Basic Functions and Components
Settings
Table 15. Compiler Switches (Continued)
Switch
Description
Global
Multiple calls to the same
Function Block
This switch defines if the
compiler should check if a POU
Type contains more than one
call to a specific Function Block
instance
W
None or multiple calls to
ExecuteControlModules
The ExecuteControlModules
function is called once in every
scan from a Function Block
Type that contains
ControlModule instances. This
switch decides if the compiler
checks that the call is made
correctly.
W
No forward flow between
blocks in FD
Verification of forward flow in
Function Diagram
W
(1) This switch does not affect the “sequence selection” functionality of SFC.
Notes to Table 15
“A”: - Allowed, Gives no error or warning
“W”: - Gives a compiler Warning if the rule is violated, acknowledge required
before download is allowed.
“E”: - Gives an compiler Error if the rule is violated, download is blocked.
The default settings are marked with boldface letters in the table.
“E & M’’ - Error and mandatory, same as "Error" but can not be changed by the
user.
See Control Builder online help for more specific information how to configure
compiler switches.
3BSE040935-511
189
Reports
Section 1 Basic Functions and Components
Reports
Difference Report
If the Difference Report function is enabled, the Difference Report Before
Download dialog displays (in the same dialog):
•
•
•
Differences
Source Code Report
Compilation Messages
Based on the information presented in the reports, you can either accept or reject the
changes, to continue with the download or cancel the download.
To enable/disable the function, right-click the control project folder (root object)
and select Settings > Difference Report. Difference report shows the difference
between data downloaded to the controller and the data present in Control Builder,
see Figure 85. The tree view to the left shows the parts of the application that have
changed. By clicking an item in the tree, you can display the present controller code
to the left, and the new code to the right. Differences are also indicated by colors
(the color coding is explained on the status bar at the bottom of the report window).
190
3BSE040935-511
Section 1 Basic Functions and Components
Difference Report
Figure 85. Difference Report Before Download
3BSE040935-511
191
Difference Report
Section 1 Basic Functions and Components
The Difference Report presents the differences found, under the Differences item in
the tree view.
Table 16. Categories under ‘Differences’ item
Category
ApplicationName
ControllerName
192
Displays Differences for...
•
Project Constants
•
Connected Libraries
•
Changed Types/Items
•
Instance Structure
•
Execution Order
•
Start Values
•
Main Source Units
•
Connected Applications
•
Connected Libraries
•
Hardware Types
•
Hardware
•
Tasks
•
Access Variables
•
Main Source Units
•
Foundation Fieldbus
– If an external configuration tool
like Fieldbus Builder FF is used,
the changed settings are
displayed
3BSE040935-511
Section 1 Basic Functions and Components
Difference Report
Table 16. Categories under ‘Differences’ item (Continued)
Category
Linked
Communication
Variables
System variable
VariableName
Displays Differences for...
•
Downloaded Controllers –
Communication variables in
downloaded controllers
•
Resolved Controllers –
Controllers where communication
variables will be resolved as a
result of the download
Changed System Variable
To reduce the compilation time during download of a project to a controller, it is
possible to exclude the start values from the difference report. The start value
analysis is enabled/disabled via Project > Settings > Difference Report.
History of Difference Report
The accepted Difference Reports could be accessed again after a download is
conducted. Select View Accepted Difference Reports from Tools menu to view the
list of reports with date and time of download.
Printing Difference Report as a PDF File
It is possible to print to a PDF-file instead of a printer if a PDF printer driver (Adobe
PDF or PDF995 or others) and the corresponding converter is installed.
To print the Difference Report as PDF File:
1.
3BSE040935-511
Select File > Print in the Difference Report.
193
Source Code Report
Section 1 Basic Functions and Components
2.
Select PDF995/Adobe PDF in the Print Dialog. Click OK.
3.
A Save As dialog displays. Enter the file name/folder and click Save.
4.
The PDF Viewer application is launched to display the difference report in PDF
format.
Source Code Report
The source code report shows the complete source code for the current project in the
Control Builder, and enables a review of the source code that is independent of
editors and user interfaces of the Control Builder.
194
3BSE040935-511
Section 1 Basic Functions and Components
Source Code Report
You perform the review by comparing the code presented in the report with the code
in the editors of the Control Builder, checking that the source codes correspond with
each other. If you find discrepancies, for example in the controller configuration,
you can try to compile and download again.
The main difference compared with the difference report is that the source code
report shows all source code from the different parts.
Figure 86. Source code report before download
The left part of the dialog displays a tree containing the different parts of the report
(see table below). To view the source code for a specific item, navigate the tree until
you find the item, and then double-click the item (or right-click the item and select
Show Source Code).
Table 17. Categories under ‘Source Code Report’ item
3BSE040935-511
Category
Displays Source Code for...
Project Constants
Project Constants
System Variable
VariableName
System Variable
195
Source Code Report
Section 1 Basic Functions and Components
Table 17. Categories under ‘Source Code Report’ item (Continued)
Category
Displays Source Code for...
Main Source Units for
Project
Main source units for project
ApplicationName
•
Connected Libraries
•
Types and Single
Instances
•
Instance Structure
•
Execution Order
•
ColdRetain and Instance
Specific Values
•
Main Source Units
•
Connected Applications
•
Connected Libraries
•
Hardware Types
•
Hardware
•
Tasks
•
Access Variables
•
Main Source Units
•
Downloaded Controllers
•
System Controllers
ControllerName
Linked Communication
Variables
Information about execution order and linked communication variables will be part
of the report, provided that a compilation has been performed.
Source code for protected types will not be displayed in the report. In the report, a
protected type is indicated by a padlock icon
. If the protected type is part of a
library, it is possible to override the protection by entering the password.
To print the source code for the whole project, select File > Print. To print the
source code for selected parts of the project, navigate the tree to the item you want
to print, right-click the item and select Print Source Code. Alternatively, you can
select File > Print, and select print range Selection in the Print dialog.
196
3BSE040935-511
Section 1 Basic Functions and Components
Reports Generated at Download
The source code report has a filter function to increase the readability of the
source code for Function Block Diagrams and Control Modules. This filter is by
default turned on (select Tools > Filter).
You can generate a source code report without compilation or download. See
Source Code Report Generated for Project in Control Builder on page 198.
You can also generate a source code report for the project in the controller. See
Source Code Report Generated for Project in Controller on page 198.
Reports Generated at Download
Difference Report and Source Code Report Generated at Download
For a description of the difference report and source code report generated when you
perform a download of a project from the Control Builder to the controller, see
Difference Report on page 190 and Source Code Report on page 194.
3BSE040935-511
197
Reports Generated at Download
Section 1 Basic Functions and Components
Source Code Report Generated for Project in Control Builder
To generate a source code report for the project in the Control Builder, without
performing any compilation or download, select Tools > Source Code Report.
Figure 87. Source code report generated without prior compilation
Source Code Report Generated for Project in Controller
A source code report for the project running in the controller can be generated
provided that:
198
•
A successful download to the controller, with difference report enabled, has
been performed.
•
The project in the Project Explorer is the same as the project in the controller.
3BSE040935-511
Section 1 Basic Functions and Components
Reports Generated at Download
To generate a source code report for the project in the controller, right-click the
controller in the Project Explorer and select Remote System, and then click Show
Downloaded Items. In the Downloaded Items dialog, click Source Code Report.
Figure 88. Source code report generated for project in controller.
3BSE040935-511
199
Portability Verification
Section 1 Basic Functions and Components
Portability Verification
This menu is located under the menu option Tools > Verify Portability in the
Project Explorer. This functionality verifies that the source code doesn't contain any
characters with an ASCII value above 127. If a project, containing characters with
ASCII values above 127, is moved between computers with different local system
settings it may result in errors when the Control Builder project is loaded.
Performance Management
The compiler statistics is a separate tool accessible from the tools menu in the
Control Builder as shown in Figure 89. When it is started, the currently opened
project in the Control Builder is compiled, and the collected information is saved in
XML format in the 'Results' subfolder of the working folder, which is presented in a
separate dialog, see Figure 90. Only information about compilable applications can
be gathered by the tool. If a project contains applications with errors, only statistics
of the correct applications is presented. In this case the statistics presented is taken
from a part of the project. One file is generated per application and it replaces old
ones if it previously exists for that application. The tool can also be started from a
Control Builder with no project loaded. In that case only information gathered from
previously generated files is displayed.
200
3BSE040935-511
Section 1 Basic Functions and Components
Performance Management
Figure 89. Compiler Statistics Tool
Figure 90. Compiler Statistics dialog
3BSE040935-511
201
Project Documentation
Section 1 Basic Functions and Components
The tool presents the following information:
•
The number of runtime instances of a type.
•
The number of sub-instances of a type and total number of instances caused by
the type.
•
The memory cost of one instance of the type, both including sub-instances and
without sub-instances.
•
The total memory cost for all instances of the type. Both including subinstances and without sub-instances.
•
The number of code blocks of the type.
•
The number of execution entities (Code calls) for all instances of the type, both
including sub-instances and without sub-instances.
•
The number of parameters passed by value of a type and the number of bytes
passed by value.
•
As above for all instances of the type, both including sub-instances and without
sub-instances.
Project Documentation
Project Documentation function generates documentation of libraries and
applications (in offline mode) for all the items in a selected project explorer folder.
This function can be used to make a reference book for a library, an application, a
controller, or a single object in a folder.
The project documentation function provides you with filter options while
documenting your control project. The filter helps you specify parts of the control
project and keeping the document size to a minimum. All documentation is
produced as Microsoft Word documents as default, hence Microsoft Office must be
installed.
All project documentation will be connected to a standard template. But you can
create templates of your own for the documentation.
A complete overview of a library, an application, a controller, or an object in these
folders can be exported to a file for printout from Project Explorer. However, it is
not possible to select a folder at the root level, for example the Libraries object
202
3BSE040935-511
Section 1 Basic Functions and Components
Project Documentation
folder. As an example, it is possible to filter out all ColdRetain variables and
Parameters in an application.
If the project documentation function is used in Online mode, the cold retain values
can also be obtained.
Printing Project Documentation
To print documentation, in Project Explorer:
1.
Right-click any object in the tree view and select Documentation. The
Documentation dialog box opens.
2.
Click More to filter information. The Editor Properties dialog box opens.
Figure 91. Editor Properties dialog for filter options.
The Editor Properties dialog box contains three main areas, which are represented
by tabs in the dialog, see Figure 91.
•
3BSE040935-511
Objects and Types,
203
Objects and Types
Section 1 Basic Functions and Components
•
Editor Items,
•
Used Types.
Objects and Types
This is the start level for filtering the contents of your application or library. As you
can see, all options have been selected by default. You adjust the filter setting by
exclude an option.
Editor Items
Figure 92. Editor Items tab for selecting items inside filtered types and objects.
After adjusting the filter settings for types and objects, another filtering can be done
per item. You can now specify which items to include/exclude for the previous
selected types and objects. The items are grouped under Declaration Pane and
Source code.
204
3BSE040935-511
Section 1 Basic Functions and Components
Used Types
Used Types
Used Types must
be checked.
Figure 93. Used Types dialog for printing used types only.
This filtering option selects types in a library that has an object (instance) in an
application or inside another library. The resulting documentation from this dialog
will only include the information for those types that have been matched as a
reference in the selected application or library (see the drop-down menus in
Figure 93).
In order to select a library or an application/library reference from the drop-down
menus, you must first check the Used Types check box.
3BSE040935-511
205
Used Types
206
Section 1 Basic Functions and Components
3BSE040935-511
Section 2 Alarm and Event Handling
Introduction
An important part of an automation system is to be able to supervise and interact
with the system. For this to be possible, information about the status of the
supervised processes must be made available to the operator. Both the operator and
the controllers need to be able to interact with the process.
This requires that information is transferred to and from the operator interface, in
the form of commands, alarms, and events.
Alarms and events are generated in three ways:
•
by using objects based on library types containing alarm and event functions,
•
by using objects especially made for alarm and event handling (based on the
types in the Alarm and Event library),
•
by hardware units throughout the system (system alarms).
This section describes how to add alarm and event handling when there are no builtin functions for this. For information on how to configure alarm and event handling
using objects that already contain alarm and event handling functions, refer to the
Compact 800 Engineering Compact Control Builder AC 800M Binary and Analog
Handling (3BSE041488*) manual, and to online help for the object in question.
This chapter describes the alarm handling functions in the Alarm and Event
library. Signal objects, process objects, and a number of control objects have
built-in alarm functionality that is similar to the functions described in this
section. For a description of built-in alarm functions, see the references above.
3BSE040935-511
207
Alarms and Events
Section 2 Alarm and Event Handling
Alarms and Events
Alarms and events inform the operator of the status of processes and systems. An
alarm represents a named state, also called an alarm condition (this is an OPC
standard term). Events give information about changes that is needed to analyze
various error situations. The OPC standard defines three kinds of events:
•
Condition-related events, which are created when an alarm state changes.
•
Simple events, which are created at occurrences like when a motor starts.
•
Tracking-related events, which are created at occurrences like an operator
action.
Alarms are usually presented to the operator in alarm lists, while events are
presented in event lists. Alarms and events can also be handled by various parts of
the system without the involvement of an operator, so that, for example, a process is
stopped when a certain alarm goes on. Alarms and events are collected from
controllers and other parts of the system, and transferred to subscribing OPC clients
(operator interfaces) using an OPC server, see Alarm and Event Communication on
page 237.
Alarms and events are often logged, for use in trouble-shooting and when tracing
the origins of an error, see Section 5, Maintenance and Trouble-Shooting.
There are two main types of alarms and events:
•
Process alarms and events are generated by changes in the alarm condition of a
monitored process signal, see Process Alarm and Event Generation on page
209.
•
System alarms and events are generated by a change in the status of the system
itself, for example by a hardware failure or by the application via function
block (SystemAlarmCond). See Detection of Simple Events on page 218 and
System Alarm and Event Generation on page 230.
Alarm and event handling also requires clock synchronization, in order for time
stamps to be reliable when trying to analyze a sequence of events. See Time Stamps
on page 234 and Sequence of Events (SOE) on page 222.
All alarms and events follow the OPC Alarm and Event specification.
208
3BSE040935-511
Section 2 Alarm and Event Handling
Alarm and Event Library
Alarm and Event Library
The Alarm and Event library contains function blocks and control modules for:
•
Creating alarms and events when a monitored signal of type bool changes,
•
Creating simple events with user-defined data, for use in, for example, batch
applications,
•
Printing alarms and events.
Additional Information
For examples of how to use components from the Alarm and Event library, see
Condition State Example on page 243. For details on how to use alarm and event
functions, see Alarm and Event Functions on page 251. This sub-section also
describes how to set up printers and print queues.
For a complete list of all objects in the Alarm and Event library, see the manual
Compact 800 Engineering Compact Control Builder AC 800M Binary and Analog
Handling (3BSE041488*).
Process Alarm and Event Generation
Process alarms and events can be generated using a number of objects based on
types in the Alarm and Event library.
•
The function block types AlarmCond and AlarmCondBasic, as well as the
control module types AlarmCondM and AlarmCondBasicM, can be used to
generate alarms and events each time there is a change in a monitored signal (of
type bool). See Process Alarms and Events on page 210.
The function block type AlarmCondBasic and the control module type
AlarmCondBasicM are versions of AlarmCond and AlarmCondM, which
consume less memory. These types do not allow inverting the monitored signal
and they support internal time stamps only.
•
•
3BSE040935-511
The function block type SimpleEventDetector can be used to generate a simple
event whenever a monitored signal of type bool changes. See Detection of
Simple Events on page 218.
The function block type DataToSimpleEvent can be used to create a simple
event and add user-defined data to it. Detection of Simple Events on page 218.
209
Process Alarms and Events
Section 2 Alarm and Event Handling
There are also system generated alarms and events, see System Alarm and Event
Generation on page 230.
Process Alarms and Events
Alarm condition-driven alarms and events are created when the monitored signal
changes, that is, when an alarm condition is fulfilled. This monitored signal must be
of type bool and is typically taken from another function block or module in the
system, or from an external device. The alarm condition function blocks and control
modules are state machines, which change from one state to another following a set
of configurable rules, whenever the monitored signal changes. This is defined as a
change in the alarm condition. Each time an alarm condition changes, an event is
created as well.
All alarm condition objects can be used in time-critical tasks.
AlarmCond and AlarmCondM
The two basic types for creating alarm conditions are the function block type
AlarmCond and the control module type AlarmCondM. The principle behind the
two is the same. Through parameters, it is possible to connect to the monitored
signal, add information to the alarm, provide other objects with status information,
and to control the behavior of the alarm condition. In Figure 94, the function block
type AlarmCond is used to illustrate the function of the different parameters.
210
3BSE040935-511
Section 2 Alarm and Event Handling
Process Alarms and Events
Signal
In parameters used for
the monitored signal
SignalID
UseSigToInit
Inverted
ExtTimeStamp
TransitionTime
Message
In parameters used
to add information
to the alarm
SrcName
AlarmCond
function block
CondName
Severity
Class
Out parameters for the
status of the alarm condition
EnCond
In parameters used to
control the behavior of
the alarm condition
DisCond
AckCond
FilterTime
CondState
Status
Error
EnDetection
AckRule
Figure 94. The function block AlarmCond.
3BSE040935-511
211
Process Alarms and Events
Section 2 Alarm and Event Handling
.
If you change the value of an Edit parameter, this change will not take effect until
after a warm or cold download.
The following alarm condition parameters are Edit parameters:
•
•
•
•
•
•
•
ExtTimeStamp,
SignalID,
UseSigToInit,
SrcName,
CondName,
Inverted,
AckRule.
The Description field in the parameter editor starts with EDIT if the parameter is
an Edit parameter.
The control module type AlarmCondM has similar functions and uses the same
parameters as the AlarmCond function block type.
For more information on parameters and their possible values, also see online
help and the Description column in the parameter editor.
Alarm Condition Types with Reduced Functionality
In applications where it is necessary to minimize memory consumption, the
function block type AlarmCondBasic and the control module type
AlarmCondBasicM offer an alternative to AlarmCond and AlarmCondM.
Basically, they are the same as their counterparts AlarmCond and AlarmCondM,
with the following differences:
212
•
They consume less memory.
•
They always use acknowledgement rule number 1 (AckRule=1).
•
It is not possible to invert the in signal, that is, the Inverted parameter cannot be
used.
•
External time stamps cannot be used, that is, the parameters ExtTimeStamp and
SignalID are not used.
•
Remote time stamps cannot be used, since the parameter TransitionTime cannot
be used.
3BSE040935-511
Section 2 Alarm and Event Handling
Process Alarms and Events
Select Signal to Monitor
The monitored signal can be internal (that is, reside in the controller), or external
(that is, reside outside the controller).
Which type of signal that is monitored is indicated by the parameter ExtTimeStamp.
If this parameter is True, the external signal indicated by the hardware address in the
parameter SignalID is monitored. If ExtTimeStamp is false, the parameter Signal is
used to connect to the monitored signal.
The parameter Inverted can be used to invert the in signal (True=invert signal).
UseSigToInit is used to indicate from where the initial value of the signal should be
taken (the state machine needs a start value). This parameter is only relevant when
the monitored signal is external. When UseSigToInit is True, Signal is used to get an
initial value.
Control the Behavior of the Alarm Condition
The following parameters can be used to control the behavior of an alarm condition:
•
AckRule determines which acknowledgement rule is used. The
acknowledgement rule decides the behavior of the alarm condition when an
alarm has been created. This parameter is an EDIT parameter (that is, it is used
for configuration purposes only, and cannot be changed without a restart) and it
cannot be changed from the code.
•
FilterTime determines how long the signal must deviate before a change is
considered to have taken place. The filter time should be set so that glitches do
not cause an alarm.
•
TransitionTime determines the time of the event occurrence when the Signal
change. If the value is equal the default value (the time) will be read inside this
FB instead
•
EnDetection enables detection when True. When this parameter becomes
False, the alarm condition goes to an inactive state and the signal is no longer
monitored. By setting this parameter to False, you will stop detection of new
alarms and leave existing alarms unacknowledged.
•
AckCond is used to acknowledge an alarm (True = acknowledge). It is normally
used to acknowledge alarms from simple devices such as push buttons.
3BSE040935-511
213
Process Alarms and Events
Section 2 Alarm and Event Handling
•
DisCond disables the alarm condition when True.
•
EnCond enables the alarm condition when True.
How the condition state changes when an alarm is acknowledged depends on the
value of the acknowledgement rule (AckRule) parameter. This parameter is available
in the AlarmCond and AlarmCondBasic function blocks, and in the AlarmCondM
and AlarmCondBasicM control modules.
The AckRule parameter is normally set to 1 (normal). It cannot be changed
online.
There are five acknowledgement rules:
•
AckRule = 1, “normal handling”, alarms must be acknowledged and inactive
before the “normal” state is resumed,
•
AckRule = 2, alarms need no acknowledgement,
•
AckRule = 3, alarms return to “normal” state on acknowledgement,
•
AckRule = 4, not used (reserved for future use),
•
AckRule = 5, alarms return to “normal” state when a sum system alarm is
acknowledged and returns to its normal state.
For more information about the different acknowledgement rules, see
Acknowledgement Rules – State Diagrams on page 252.
Alarm and Event Information
There are a number of parameters for adding information to alarms and events:
214
•
Message can be used to add a textual description of the alarm condition, for
example, “temperature low”.
•
SrcName identifies the alarm source, for example, “Motor101”.
•
CondName identifies the alarm condition, for example, “Level_High“.
•
Severity indicates the degree of severity, where 1 is the least severe, and 1000 is
the most severe level. This parameter is very useful when filtering alarms and
events.
•
Class can be used to classify the alarm (1-9999). This parameter is also useful
when filtering events,
3BSE040935-511
Section 2 Alarm and Event Handling
Process Alarms and Events
This information can be displayed in the operator interface and written to various
logs. It can also be used to sort and filter alarms and events.
Since the source name and the condition name identify the alarm, the combination
of the two must be unique within a controller. Any attempt to define an alarm
condition that results in a non-unique combination of source name and condition
name will result in an error (the Error parameter will become True). Also, a simple
event is generated.
If an OPC server detects a non-unique alarm (that is, two controllers have the same
combination of source name and condition name), a system simple event is
generated.
There are two alternatives for indicating the source of an alarm or event:
•
Leave the SrcName parameter empty. The Name parameter of the alarm owner
(see Alarm Owner Concept on page 218) will be used as the source name.
For a program or application to have a source name, you need to create a variable
called Name in the program or application. If the SrcName parameter is left
empty and the alarm owner is a program or application, the value of the Name
variable will be used as the source name.
•
Set the SrcName parameter to whatever source name you want to use.
All alarms belonging to the same alarm owner must have the same source name.
The condition name is normally the name of the alarm condition function block or
control module instance, for example Level_High, but could also be set via the
CondName parameter.
Condition names are case sensitive, that is, Level_High is not the same as
LEVEL_HIGH.
The same condition names should be used throughout the whole project, since it is
important that the operator has a limited set of condition names to deal with. Using
condition names in a consistent and structured manner also makes it easier to
understand the process.
For detailed information about source name and condition name restrictions and
syntax, see online help for the Alarm and Event library.
3BSE040935-511
215
Process Alarms and Events
Section 2 Alarm and Event Handling
The class parameter (Class) can be used to classify all alarms.
The default class is 9950 for all system alarms and system events. All other
numbers can be used as required. Possible values are 1-9999. The default value
can be changed by changing the CPU setting AE System AE class.
Status Information
There are three parameters that can be used to retrieve status information for an
alarm condition:
•
CondState indicates the state of the alarm condition (0-6, see below).
•
Error indicates an error in the alarm condition.
•
Status gives the status code from the latest execution.
If a parameter is outside its defined range, the Status parameter will take a
negative value or the value 703.
Alarm conditions are state machines, which change from one state to another
following fixed rules. The most important reason for an alarm condition to change is
a change in a monitored signal. The alarm condition (indicated by the parameter
CondState) also changes if:
216
•
an alarm is acknowledged,
•
an alarm is disabled,
•
an alarm is enabled,
•
auto-disable occurs.
3BSE040935-511
Section 2 Alarm and Event Handling
Process Alarms and Events
The condition state (CondState) parameter indicates the state of an alarm. An alarm
can be in one of seven states:
Integer value
State
0
Alarm condition not defined
1
Disabled
2
Enabled, Inactive, Acked - Idle
3
Enabled, Inactive, Unacked
4
Enabled, Active, Acked
5
Enabled, Active, Unacked
6
Enabled, AutoDisabled, Unacked
The CondState parameter can be used to pass the state of an alarm to other parts of
the software.
To see the state of all alarm conditions for a certain object in Project Explorer,
right-click the object and select Alarm Conditions from the context menu.
Autodisable
AC 800M controllers have a CPU parameter called AE Limit auto disable. This
setting controls the number of times an alarm can go on and off, without being
acknowledged. When the limit is reached, the alarm condition is automatically
disabled, and the state AutoDisabled is entered. The default setting is 3, and the
maximum setting is 127. If AE Limit auto disable is set to 0, autodisabling is turned
off and alarms can be activated an unlimited number of times.
An alarm that is in AutoDisabled state does not send any event (even though the
alarm condition changes), until it is acknowledged. See Acknowledgement
Rule 1 on page 252.
3BSE040935-511
217
Detection of Simple Events
Section 2 Alarm and Event Handling
Alarm Owner Concept
The alarm owner concept is important, since it is the key to manipulating the source
of an alarm. Not all objects in the Project Explorer tree hierarchy are alarm owners.
For an object (for example, a tank object) to be an alarm owner, it must fulfill two
criterias:
1.
It must have the attribute Alarm Owner set to True.
2.
It has to be the last link in an unbroken chain of alarm owners, all the way from
the program or application, down to this particular object. It must not be a sub
object to an object with the attributes hidden or protected.
The attribute "Sub Objects visible in PPA" will not affect the Alarm ownership.
If an object is not an alarm owner, or the alarm owner chain is broken, the system
looks further up in the hierarchy, until it finds an object on a higher level that is
directly above the origin of the alarm or event, and fulfills the above criteria.
This is the point of the alarm owner concept. By not setting the Alarm Owner
attribute for low-level objects, alarms and events can be connected to an object on a
level higher than their true origin. If no alarm owner is found, the program or
application itself becomes the alarm owner. The following objects are always alarm
owners:
•
•
Applications,
Programs.
Detection of Simple Events
A simple event detector generates a simple event each time there is a change in the
monitored signal. A simple event detector can be implemented by means of the
function block type SimpleEventDetector.
SimpleEventDetector can be used with internal, external or remote time stamps.
This function block type is connected to the monitored signal exactly the same way
as the function block type AlarmCond, that is, using the parameters Signal,
SignalID and UseSigToInit. See Select Signal to Monitor on page 213. It is also
possible to set the filter time (via a FilterTime parameter).
For SimpleEventDetector, the following applies:
If ExtTimeStamp is True, FilterTime is not used.
218
3BSE040935-511
Section 2 Alarm and Event Handling
Built-in Alarm and Event Handling in Other Libraries
The function block DataToSimpleEvent can be used to add data to a simple event.
See Simple Events on page 233.
For more information on how to configure these function blocks, see alarm and
event online help.
Built-in Alarm and Event Handling in Other Libraries
This section deals with alarm and event handling based on the Alarm and Event
library. However, alarm and event functions are built in to a number of other types in
the standard libraries that are delivered with Compact Control Builder.
This sub-section gives a short introduction to signal objects and to the built-in alarm
and event functions of process objects and control loops. It also describes the inhibit
and disable functions for these objects, since they are relevant to the interaction with
the types in the Alarm and Event library.
Alarm and Event Handling Using Signal Objects
The Signal Library contains types that can be used to create representations of
objects with an input or output signal, for example a temperature sensor. By using a
signal object, you can go to manual mode and set the value of the signal, as well as
supervise the signal and generate alarms when the signal deviates.
Never use types from the Signal Libraries to represent all I/O channels and if
used, types from SignalBasicLib should be taken. This will consume a lot of
memory and will result in poor performance. Use signal objects when there is a
real need to control and monitor an I/O signal. Signal objects normally represent
an object with a single signal.
For more information about the Signal Libraries, see online help and the manual
Compact 800 Engineering Compact Control Builder AC 800M Binary and Analog
Handling (3BSE041488*) manual.
Alarm and Event Handling in Control Loops and Process Objects
Alarm and event handling is built into a number of library types, such as control
loops and process objects. These alarms and events are handled the same way as
other process alarms and events.
3BSE040935-511
219
Built-in Alarm and Event Handling in Other Libraries
Section 2 Alarm and Event Handling
Alarms and events can be generated directly by those objects, each time the alarm
condition is fulfilled, or the object can generate a bool signal that can be connected
to an alarm condition object.
For a description of how to configure built-in alarm handling for various library
types, see online help for the type in question, and the Compact 800 Engineering
Compact Control Builder AC 800M Binary and Analog Handling
(3BSE041488*) manual.
Inhibit and Disable Alarms and Events
Sometimes there is a need for temporarily suspending alarm and event generation.
This can be done for all objects with built-in alarm handling:
•
Disable – the alarm condition is disabled, no alarms and events are generated,
nothing is sent, and no control action is taken (that is, the system does not act
upon the alarm condition).
Normally, the control action will be a boolean signal that causes a certain
reaction, for example, a signal that stops a motor. However, a control action could
also cause a more complex series of actions.
•
Inhibit – the control action itself is inhibited (that is, the system does not act
upon this alarm or event), while alarms and events are still presented to the
operator in the operator interface.
Inhibit is only available in the types listed under Inhibit Parameters on page 220.
Alarms and events can be disabled from the interaction windows and from OPC AE,
as well as from the application, via interaction parameters.
Inhibit Parameters
The inhibit function is present in the following standard library types.
•
220
Signal library
– SignalInReal
– SignalReal
– SignalInBool
– SignalBool
– SDLevelM
– SignalBoolCalcInM
3BSE040935-511
Section 2 Alarm and Event Handling
–
–
–
–
Built-in Alarm and Event Handling in Other Libraries
SignalInBoolM
SignalInRealM
SignalReadCalcInM
SignalSimpleInRealM
•
Standard Control library
– Level6CC
– Level4CC
– Level2CC
•
Supervision Basic library
– SDBool
– SDInBool
– SDInReal
– SDLevel
– SDOutBool
– SDReal
– SDValve
– InfoAlarmSDInReal
In these types, control actions are inhibited by setting a parameter InhXAct, where X
stands for the name of the condition, for example InhGTHAct (where GTH stands
for Greater Than High).
There are also parameters for indicating if the alarm condition (event generation)
has been inhibited or not.
Disable/Enable Parameters
The disable function is available in all types that contain built-in alarm handling. An
alarm condition is disabled by setting the EnableY parameter to False, where Y
stands for the name of the condition, for example EnableGTH (where GTH stands
for Greater Than High).
There are also parameters for indicating if the alarm condition has been disabled or
not.
There are additional parameters that affect the behavior of built-in alarm
conditions, for example AEConfigX. For more information on parameters, see
online help for the object in question (select and press F1).
3BSE040935-511
221
External Time Stamps (S800 I/O)
Section 2 Alarm and Event Handling
External Time Stamps (S800 I/O)
A special form of external time stamp is created by external units with Sequenceof-Event (SOE) support, such as DI831. A low level event is then time-stamped
by the I/O unit and sent to the controller to be dealt with. This triggers alarms or
simple events in the controller. The change of status is time-stamped with the low
level event time stamp.
Sequence of Events (SOE)
Some I/O modules add a low-level time stamp to an alarm or event when it detects a
change in a signal. Instead of using the time stamp created by the controller when it
detects a change in the monitored signal (that is, when the task is executed), the
controller simply adds the time stamp created by the I/O module. In this way, the
time stamp shows when the change actually occurred, instead of when it was
detected by the controller.
For this to work, the I/O module will have to support Sequence of Events (SOE).
SOE is currently supported on ModuleBus and PROFINET IO only. For
information on enabling/disabling and configuring SOE, see online help for S800
I/O.
External Time Stamps (PROFINET IO)
Sequence of Events (SOE) for PROFINET IO
Time stamped events are passed by PROFINET IO and CI871 through the controller
and are indicated in the AC 800M OPC Server. The timestamping is done by the
PNIO device. The PROFINET IO SOE is supported by use of the ABB SOE profile.
The following are the definitions and functions of ABB SOE Profile:
222
1.
Alarms from the PNIO device are converted into an External Event. These
External Events transferred through the AC 800M OPC-Server are indicated in
the EventList with their corresponding source address.
2.
The external event can be picked up from the IEC-61131 Application by a
Function block like alarm condition and converted to a process alarm.
3.
The time synchronization of PNIO device is done externally and not by the
CI871. It is the responsibility of the PNIO devices to get a time synchronization
3BSE040935-511
Section 2 Alarm and Event Handling
External Time Stamps (PROFINET IO)
managed (through access to the central time master in the system). The PNIO
device defines the information to be time stamped.
4.
3BSE040935-511
The ABB SOE profile is handled as a process alarm on PROFINET IO with a
vendor specific User Structure Identifier (USI).
223
External Time Stamps (INSUM)
5.
Section 2 Alarm and Event Handling
Once the SOE alarm is acknowledged (to ensure that it is not lost). The PNIO
device deletes the alarm only after receiving the acknowledgement from the
controller. The controller sends the acknowledgement after storing the alarm in
the non-volatile memory.
It is recommended to configure Function blocks as Alarm condition for process
signals only where the process values can be used as initial value in case of restart
behavior. Otherwise alarms can get frozen.
External Time Stamps (INSUM)
Creating an Application that Handles INSUM Alarms
All INSUM devices (MCU, Circuit Breaker) have supervision functions that can
report alarms. The different device types supervise and report specific alarm types.
The alarms are reported in specific Network Variables.
MCUs report the alarms in the Network Variable NVAlarmReport.
The user can decide if there should be a summary entry that tells that there are some
alarms (one or more) in the device. It is possible to have a separate summary alarm
for warnings and a separate alarm for trips.
This subsection discusses both methods, receiving INSUM alarms in the application
program, and generating alarm to the alarm lists. The user can decide to use either
methods or just one of them. For more information refer to Compact 800
Engineering Compact Control Builder AC 800M Binary and Analog Handling
(3BSE041488*) manual.
Receiving INSUM Alarms in the Application
To receive alarms in the application program the INSUMReceive function block is
used in the same way as when receiving other input network variables from an
INSUM device, choose the correct NVindex and data type. The data type should in
this case be NVAlarmReport (see also the MCUAlarmTrips/WarningsStructs
regarding how to interpret the bits).
The time stamp set by the INSUM device in the alarm variable is presented in the
two time fields of the NVAlarmReport. This time information is only correct if the
clock in the INSUM device is synchronized. The system software does not fill in
224
3BSE040935-511
Section 2 Alarm and Event Handling
External Time Stamps (INSUM)
these fields if the time stamp received from the INSUM device is incorrect. (See
below).
Generating Alarms for Alarm Lists
The controller system software generates alarms for the alarm and event lists in the
system, based on the updates of the INSUM alarm information if the parameter
Generate Alarms on the device is set to Enabled or Enabled Trip/Warning or
Enabled Detailed.
If the time stamp received from the INSUM device is correct (a valid time) this time
stamp is used for the generated alarm message. If it is not, the system software tags
the generated alarm message with the current controller time.
If the parameter Generate Alarms is set to disabled, alarm information can
anyway be sent to the alarm and event lists by the application. This can be done
by creating an AlarmCond function block and to connect information received
from an INSUM device to the parameter Signal and to set
External Time Stamp = FALSE.
In this case, the alarm messages are time stamped in the controller. If this time
accuracy is sufficient, this method is probably to be recommended because it is
easier to configure. No System Clock is needed in the INSUM system. If you let the
system software generate the alarms it can use the time stamp given by the INSUM
devices. If the INSUM System Clock is used this is a much more accurate time
stamp.
Summary Alarms, One Alarm Object Per Device
Generate Alarms = Enabled means that the system software internally (without
needing INSUMReceive) creates a subscription of the alarm variable from the
INSUM device. When this variable is updated from the INSUM system, the system
software evaluates the content.
If a bit (one or more) which is classified as an alarm (e.g. not the bit "Started1") is
set and no such bit previously was set, the system software generates one alarm
message.
If an alarm update is received with the change that no alarm classified bits are set
any more, the system software generates the alarm-off message.
3BSE040935-511
225
External Time Stamps (INSUM)
Section 2 Alarm and Event Handling
Summary Alarms, One Alarm Object For Warnings and One for Trips
Generate Alarms = Enabled Trip/Warning. The difference compared to the handling
for Enabled is that the system software generates one specific alarm message when
a warning bit is set and another alarm message when a trip bits are set.
226
3BSE040935-511
Section 2 Alarm and Event Handling
External Time Stamps (INSUM)
This means that there will be one alarm message for the first warning and one for
the first trip. To use this setting two AlarmCond blocks should be created for each
INSUM device, one for the warnings and one for the trips. If an alarm update is
received with the change that no warning bits are set there will be an alarm off
message for the warnings. The same applies for the trip bits.
Detailed Alarms
Generate Alarms = Enabled Detailed. The difference compared to the handling for
Enabled (see Summary Alarms, One Alarm Object Per Device on page 225) is that
for each alarm classified bit which is set (and previously was not set) the system
software generates one separate alarm message. If an alarm update is received with
the change that an alarm classified bit that previously was set now is reset, the
system software generates the alarm off message for that bit.
Using Enabled Detailed means that one AlarmCond block should be created for
each alarm type that the INSUM device sends. For a large INSUM configuration
where more than just a few alarm types per device should be supervised this
easily leads to a very large number of AlarmCond blocks.
Creating AlarmCond Blocks for Generated Alarms
The function block AlarmCond should be used to get descriptive messages in the
event and alarm list and get an association with an alarm object. AlarmCond is
associated with the alarm messages that the system generates by setting
ExternalTimeStamp=TRUE and to identify the alarm object with the parameter
SignalId.
Alarm Generation = Enabled
The SignalId should be a string that specifies the hardware position for the INSUM
device. This is done with the syntax C.G.D, where:
•
C is the position of the CI857,
•
G is the position of the INSUM Gateway and,
•
D is the position of the INSUM device. The position numbers are separated by
a dot '.'.
3BSE040935-511
227
External Time Stamps (INSUM)
Section 2 Alarm and Event Handling
Example:
•
The syntax 2.1.204 means the alarm for device #204 connected via Gateway #1
on CI857 #2.
Alarm Generation = Enabled Trip/Warning
The SignalId should be a string that in addition to the hardware position for the
INSUM device, also specifies a trip or a word.
This is done with the syntaxes C.G.D-T or C.G.D-W, where:
•
C, G and D as above,
•
T represents Trips and W represents Warnings.
Examples:
•
The syntax 2.1.204-W means a warning for device #204 connected via
Gateway #1 on CI857 #2.
•
The Syntax 2.1.204-T means a trip in device #204 connected via Gateway #1
on CI857 #2.
Alarm Generation = Enabled Detailed
The SignalId should be a string that, in addition to the hardware position for the
INSUM device, also specifies the alarm word and bit within the word. This is done
with the syntax C.G.D-X/B, where:
•
C, G, and D as above, and,
•
X is the word within NVAlarmRep (preceded by a dash “-”),
•
B is the bit within the word.
There are four words with warnings called W0-W3 and four words with trips called
T0-T3. The bits are numbered from 0 to 15. The word and the bit is separated by a
slash ‘/’.
Example:
The syntax 2.1.204-W1/3 means the alarm bit 3 in word W1 in device #204
connected via Gateway #1 on CI857 #2.
228
3BSE040935-511
Section 2 Alarm and Event Handling
Choose Alarm Handling Method for INSUM Alarms
Choose Alarm Handling Method for INSUM Alarms
This section contains some suggestions about choosing and handling INSUM
alarms. Whether to send alarms to alarm list or not:
•
•
If Alarms should be possible to view, but are not necessary to see in the Alarm
lists:
–
Set Generate Alarms = Disabled.
–
Do not create any AlarmCond blocks.
If the INSUM Alarms should be sent to the alarm list:
–
Use AlarmCond function blocks. See INSUM Alarms in Alarm Lists
below.
INSUM Alarms in Alarm Lists
Time stamping:
•
•
If local (in the INSUM devices) time stamping should be used:
–
Use a system clock in the INSUM system.
–
Set Generate Alarms = Enabled, Enabled Trip/Warning, Enabled Detailed
–
Use an AlarmCond block with External Time Stamp = TRUE.
If it is sufficient with time stamping in the application in the controller:
–
Set Generate Alarms = Disabled
–
Use an AlarmCond block with External Time Stamp = FALSE.
–
Connect it to the variable with the INSUM device information to be
supervised. The accuracy of this time stamping cannot be better than the
cycle time of the application where the AlarmCond is executed.
Separation of alarms in the alarm list:
•
3BSE040935-511
If the timing between different alarms within a device must be possible to see
in the alarm list than it is required to:
–
Set Generate Alarms = Enabled Detailed.
–
Use one AlarmCond per alarm type.
229
System Alarm and Event Generation
•
•
Section 2 Alarm and Event Handling
If it is sufficient to be able to identify the device than it is possible to:
–
Set Generate Alarms = Enabled.
–
Use one AlarmCond per INSUM device.
If it is sufficient to be able to identify the first warning and the first trip in a
device than it is possible to:
–
Set Generate Alarms = Enabled Trip/Warning
–
Use two AlarmCond blocks per INSUM device.
Number of devices:
•
•
If there are a lot of devices needing external time stamping than required for:
–
Use two (or one) AlarmCond per INSUM device.
–
Set Generate Alarms = Enabled Trip/Warning (or Enabled)
If there are a few devices that need external time stamping than it is possible to:
–
Use one AlarmCond per alarm type.
–
Set Generate Alarms = Enabled Detailed
System Alarm and Event Generation
System alarms and system simple events that are generated in a controller are
distributed to OPC alarm and event clients and locally connected printers, according
to the current system configuration.
All system alarms available in a controller can be located by printing all alarms (use
the PrintAlarms function block type and set the parameters to show the alarms you
want to see). They can also be displayed by and interacted with applications, by
means of the function block AttachSystemAlarm (this function block type retrieves
the alarm condition state and some other information for an alarm condition). When
units that are visible in Project Explorer (hardware units or program tasks) generate
system alarms or system simple events, a warning icon is displayed on the
corresponding unit.
230
3BSE040935-511
Section 2 Alarm and Event Handling
Controller Generated System Alarms and System Simple
System alarms and system simple events are used to draw attention to deviations
from normal system behavior. All system alarms and system simple events can be
sent to the OPC Alarm and Event Clients and even printed to the system log file,
depending on the current system configuration.
Controller Generated System Alarms and System Simple Events
Controller generated system alarms and system simple events are defined within the
controller. A list of all defined system alarms and system simple events within an
AC 800M controller can be found in Appendix B, System Alarms and Events.
Filter out system alarms from hardware units
The function is used to reduce the number of alarms generated from hardware units,
as important alarms tend to disappear in a crowd of alarms.
A example is when commissioning the system or a new part of an existing system,
there might be transmitters that are connected and disconnected and the system
generates a lot of underflow, overflow and channel error alarms.
The function is configured on the hardware object on the controller. Select
Controller > Hardware AC 800M >Editor > Settings, then select Filter out
system alarms from hardware units as shown in the Figure 95.
Figure 95. Filter out system alarms
3BSE040935-511
231
User Generated System Alarms
Section 2 Alarm and Event Handling
The parameter has five possible values:
Off: The filter function is shut off. The hardware status generates system alarms and
systems events for all status changes. This is the default setting.
Underflow: Underflow status changes will not generate any alarms.
Over- and underflow: Neither underflow nor overflow status changes generate
alarms.
Channel error: Channel error and IO warning will not generate system alarms or
events.
All: Alarms and events from all the status changes above are suppressed.
Even if the setting is set to filter out alarms, the errors and warnings will still be
visible in the hardware tree and the Unit Status tab in the hardware online editors.
The change to the filter is performed in offline mode and downloaded to the
controller to activate the change.
If the function is used during commissioning to decrease the number of alarms, it
might be crucial to shut off the filter before entering normal operation.
User Generated System Alarms
User generated system alarms can be defined in your applications via the function
block SystemAlarmCond.
Handling Alarms and Events
When implementing alarm and event handling, it is very important to create a good
system for:
232
•
classifying alarms and events,
•
setting the severity of different types of alarms,
•
indicating the source of an alarm or event,
•
naming alarm conditions.
3BSE040935-511
Section 2 Alarm and Event Handling
Simple Events
The most obvious reason for this is that you will be able to create an operator
environment in which the operator will quickly be alerted to various things that
require attention. The operator will also be able to quickly obtain additional
information and decide on the best course of action.
However, alarms and events are also logged, in order to be used for troubleshooting, and when analyzing things in order to improve performance of the plant.
This subsection describes:
•
How to send data in XML format, see Simple Events on page 233. This is
useful when creating batch records.
•
How to handle system alarms and events, see System Alarms and Events on
page 233.
•
Internal, remote, and external time stamps (Sequence of Events, SOE),
including time synchronization, see Time Stamps on page 234.
Simple Events
The DataToSimpleEvent function block is used to send data in XML format, for
example, to record data for batch processes.
For more information on how to use this function block, see online help. For
examples on how to use the DataToSimpleEvent function block, see Condition State
Example on page 243.
System Alarms and Events
The handling of system alarms and events is to a certain degree configurable. The
function block AttachSystemAlarm can be used to retrieve information on system
alarms and events, such as state, and whether the alarm has been disabled or
acknowledged.
The function block SystemAlarmCond can be used to retrieve system alarms and
events via the application.
3BSE040935-511
233
Time Stamps
Section 2 Alarm and Event Handling
Time Stamps
When an alarm or event is created, a time stamp can be added to it, showing the
exact time when the event occurred. There are three types of time stamp:
•
Internal Time Stamps, that are created by the controller.
•
Remote Time Stamps that are read from external communication partners via
the parameter TransitionTime.
•
External Time Stamps that are created by an I/O unit and transferred together
with the event.
The TransitionTime parameter (of type date_and_time) can be used to read a remote
time from a remote partner, via other protocols than MMS. The parameter is read
each time a change is detected in the monitored signal. If it is left unconnected, it
will have no effect.
When adding remote time stamps, it is possible to add any time. However,
settings in the operator interface might filter out alarms and events with times that
are outside the “normal” range (in the future or far back).
Internal time stamps simply show when the execution cycle in which the alarm was
created started. External and remote time stamps show the actual time at which the
alarm condition occurred in the external device or partner. All time stamps have a
resolution of 1 ms; however, it is the interval time of the task where the alarm
function block or module runs that determines the accuracy of the internal time
stamps. All alarm function blocks and modules in the same task are given the same
time stamp, if activated concurrently.
This is the point of using external and remote time stamps. Internal time stamps can
never be more accurate than the execution time of the task allows for. With external
or remote time stamps, the accuracy of the time-stamping mechanism in the external
or remote device (for example, an S800 I/O unit) sets the limit, something which
could seriously improve the accuracy of the time given in entries with external or
remote time stamps.
If external time stamps are to be used, the external time stamp parameter
(ExtTimeStamp) has to be set to True. When using external time stamps, there is also
234
3BSE040935-511
Section 2 Alarm and Event Handling
Time Stamps
a SignalId parameter that is used to indicate the source of the external alarm or
event.
External time stamps can only be created by external units with Sequence-ofEvent (SOE) support.
All time stamps use UTC (Coordinated Universal Time).
3BSE040935-511
235
Time Stamps
Section 2 Alarm and Event Handling
Clock Synchronization
For time stamps to be useful, the whole system must use the same time, that is, the
time must be synchronized. See also the Compact 800 Engineering Compact
Control Builder AC 800M Getting Started (3BSE041584*).
Depending on the type of controller, clock synchronization is possible by four
different protocols: CNCP, SNTP, MB 300 TS, and MMS Time Service. Clock
synchronization is set up in the controller hardware editor.
It is important to understand the difference between accuracy and resolution when
calculating how much a time stamp may deviate from the true system time:
•
Resolution is the number of decimals that are used to write the time. If the time
is given as, for example, 2004-02-19 19:43:22:633, the resolution might
be 1 ms (but could also be, for example, 0.5 ms).
•
Accuracy is a measure of how accurate a time stamp is, that is, how much it
may deviate from the true system time. If the accuracy is 1 ms, then
2004-02-19 19:43:22:633 actually means any time between
2004-02-19 19:43:22:632 and 2004-02-19 19:43:22:634.
For a more detailed, conceptual description of time synchronization, see the AC
800M Communication Protocols (3BSE035982*)
It is also important to understand that the accuracy deteriorates if a time stamp is
created in a unit that is supplied with the time from a controller, via ModuleBus.
The possible difference between the time stamps of two events that occurred at
exactly the same time, but in two different units in two different controllers, is the
sum of the accuracy of time synchronization in the network and two times the
accuracy of the ModuleBus time synchronization.
This means that the difference between external time stamps can be far greater than
the accuracy of time synchronization between controllers.
The highest accuracy is achieved by using the CNCP protocol, with an AC 800M
controller as master.
236
3BSE040935-511
Section 2 Alarm and Event Handling
Alarm and Event Communication
Alarm and Event Communication
Alarm and event information is communicated throughout the control network via
OPC servers, that is, a number of OPC Server for AC 800M. When the state of an
alarm condition changes, an event notification is sent to all subscribing OPC
servers, which then forward these notifications to their clients. Changes in alarms in
the OPC server are also forwarded to its clients. .
For detailed information on how to configure OPC Server for AC 800M, refer to
the AC 800M OPC Server (3BSE035983*) manual.
Subscriptions
An OPC server subscribes to event notifications from a control system. Each
controller compiles an internal list of all servers interested in various events.
Condition-related events are generated when alarm conditions change their state.
Simple events can be generated, for example, by the start of a motor. When an event
occurs, the control system sends event notifications to all servers on the subscription
list.
Configuration of OPC AE Communication – Overview
The whole system for transferring alarms and events, that is, controllers, OPC
servers, and OPC clients, must be configured so that there are no disturbances in the
alarm and event traffic.
There are several basic rules regarding system configuration:
•
A control system can send data or event notifications to one or two subscribing
OPC servers.
•
A maximum of seven OPC clients can subscribe to data or event notifications
from the same OPC server.
•
A maximum of four Ethernet links (two redundant) are supported via Ethernet
cards.
•
A maximum of four Point-to-Point Protocols (PPP) are supported via serial
cards.
3BSE040935-511
237
Configuration of OPC AE Communication – Overview
Section 2 Alarm and Event Handling
The OPC server must be configured to recognize the control systems it is to
communicate with. The OPC client must be configured to recognize the OPC
server(s) it is to communicate with. See Figure 96.
OPC Client 1
OPC Client 2
OPC Server 1
Panel 800
OPC Client 3
OPC Server 2
Control Systems:
Control Systems:
Subscr. list:
Control Systems:
Subscr. list:
Control System 1
Control System 2
Control System 1
Control System 2
OPC client 1
OPC client 2
Control System 1
Control System 2
Control System 3
Control System 4
OPC client 3
Control System 1
Control System 2
Control System 3
Control System 4
Subscr. list:
Subscr. list:
Subscr. list:
Subscr. list:
OPC server 1
OPC server 2
OPC server 1
OPC server 2
OPC server 2
OPC server 2
Figure 96. Example of a control network configuration.
Information about how to configure individual OPC servers is found in the
AC 800M OPC Server (3BSE035983*) manual, and in the online help, which can be
opened from the OPC server panel.
238
3BSE040935-511
Section 2 Alarm and Event Handling
Buffer Configuration
Buffer Configuration
Alarm and event handling requires a number of buffers. The memory for these
buffers must be allocated in the controllers. These settings have to be made in the
Settings tab for each controller CPU.
Table 18 describes the parameters in the Settings tab that need to be configured for
the buffer. See also System Diagnostics on page 251.
These settings affect the Available memory. For more information regarding
Available memory, refer to the Compact 800 Engineering Compact Control Builder
AC 800M Product Guide (3BSE041586*) manual.
For controller types with limited memory, the settings for the buffer configuration
should be carefully chosen or else the memory becomes full.
Table 18. Memory planning for buffer configuration
Parameter
Comment
AE Local printer event queue size
Each position allocates approximately 300
bytes of memory. The total memory need
for local printers is:
300 * AE Local printer event queue size *
AE Max number of local printer event
queues
AE Max number of local printer event
queues
The maximum number of event queues in
the controller
AE Event subscription queue size
Each position allocates approximately 300
bytes of memory. Total memory need for
subscribing OPC Servers are:
300 * AE Event subscription queue size *
AE Max number of event subscriptions
AE Max number of event subscriptions Number of subscribing OPC Servers
3BSE040935-511
239
Local Printers
Section 2 Alarm and Event Handling
Table 18. Memory planning for buffer configuration (Continued)
Parameter
Comment
AE Buffer size of low level event
Each position allocates 72 bytes of
memory. Total memory need for
Sequence of Events are:
72 * AE Buffer size of low level event
Set this setting to 2 if Sequence of Events
is not used
AE Max no of Name Value items
The maximum number of XML tagged
events
AE Max percent of log strings
The percentage of Name Value items that
are strings. Used to allocate memory for
Name Value item strings.
Local Printers
A local printer can be connected to the serial port of a controller, and print out event
lists and/or alarm lists as needed.
AC 800M
Buffer
Printer
Figure 97. Example of a controller and local printer configuration.
There can be only one local alarm/event printer connected to each controller.
Additional printers are invalid. There is limited data flow support for alarm/event
printers connected to controllers. Alarms and events that occur when the printer is
offline may not be printed when the printer goes online again. This applies to all
printers with direct connection to a controller.
Print Format
The print format for alarm conditions and events is governed by a special format
syntax.
The system supports the 8-bit ASCII character set (according to Windows). This
means that the serial and parallel printers must support the 8-bit character set.
240
3BSE040935-511
Section 2 Alarm and Event Handling
Print Format
The abbreviations used in these format strings are given in Table 19. The character
length of each field is given within parentheses..
Table 19. Abbreviations in format strings
Explanation of the identification
parameters
Abbreviation
Ti
Time stamp (MM-DD-HH:MI:SS)
Sr
Source name (maximum 30)
Co
Condition name (maximum 15)
Me
Message (maximum 70)
Cs
Condition state text (maximum 20)
Tt
Transition type text (maximum 20)
S
Severity (4)
C
Class(4)
The fields may be in any order.
Ti, Sr, Co, Me, Cs, and Tt have user-defined dynamic lengths. If the length of a
string is defined as longer than a presentation function that is already set, the
presentation is reduced accordingly
The text for the condition state originates from project constants such as
cAlarmCondStatetext.On1, cAlarmCondStatetext.Off1, and so on.
A maximum of 132 characters can be printed for each alarm/event.
Globally Defined Print Formats
Global print formats are defined in the project constants, which are categorized
based on alarm and event conditions or transitions:
•
3BSE040935-511
For Alarm Conditions
–
cPrintAlarmPres.AlarmCondFormat
–
cPrintAlarmPres.TimeFormat
241
Sending an Alarm to the Application
–
•
•
•
Section 2 Alarm and Event Handling
cPrintAlarmPres.FooterFormat
For Events
–
cPrintEventPres.CondEventFormat
–
cPrintEventPres.SmpEventFormat
–
cPrintEventPres.TimeFormat
For Alarm Condition State Texts
–
cAlarmCondStateText.Undefined
–
cAlarmCondStateText.On1
–
cAlarmCondStateText.Off1
–
cAlarmCondStateText.Acked
–
cAlarmCondStateText.Disabled
–
cAlarmCondStateText.Idle
–
cAlarmCondStateText.Autodisabled
For Event Transition Texts
–
cEventTransitionText.Undefined
–
cEventTransitionText.On1
–
cEventTransitionText.Off1
–
cEventTransitionText.Ack
–
cEventTransitionText.Disable
–
cEventTransitionText.Enable
–
cEventTransitionText.Autodisable
Sending an Alarm to the Application
Instead of sending your alarms to a local printer you can choose to only redirect the
alarm to the application. The function block PrintEvents contain two parameters; the
first parameter EventItem catch the values (Source Name, Condition name, Time
stamp, Severity etc.) and the second parameter EventItemText format these values
242
3BSE040935-511
Section 2 Alarm and Event Handling
Condition State Example
as if they was send to a printer and bring it to the application as well. Hence, these
values can then be sent and processed by your local code.
However, sending an alarm only to the application requires that you do not connect
the Channel parameter (leaving the Parameter field empty).
By sending an alarm to the application you can then redirect this information to
your cell phone. Every time an incoming alarm has a severity higher than 700,
you should be notified with a SMS.
Condition State Example
The following example shows how to use the condition state parameter (CondState)
to control a pump.
TEMP
energize
Start
AlarmCond
Signal
&
Stop
time
A
CondState
>
2
B
Blocking
Figure 98. Manipulating the condition state using I/O.
Figure 98 shows two alternative ways of stopping a pump when the temperature is
too high. The TEMP signal goes high when the temperature is too high.
3BSE040935-511
243
Inhibit Example
Section 2 Alarm and Event Handling
In alternative A, the TEMP signal is simply used to stop the pump (using the
blocking function, note that the TEMP input is inverted). There is no way to disable
this alarm. The pump is blocked as long as TEMP is high.
Alternative B uses an AlarmCond function block, which makes it possible to wait
for an action from the operator, before unblocking the pump. The blocking signal to
the pump does not go high until CondState > 2, that is, the alarm is enabled and not
idle (for a list of possible states, see Status Information on page 216). Once it has
gone high, it does not go low until Condstate => 1, that is, the alarm is disabled or
has returned to its idle state (this means that the alarm must be acknowledged by the
operator and TEMP must go low before the pump is unblocked, as long as
acknowledgement rule 1 is used).
Alternative B also makes it possible to disable the blocking function by simply
disabling the alarm condition.
This example has been simplified to illustrate a principle. In reality, it would not
be desirable to have a motor start when an alarm is acknowledged. Instead, the
operator would acknowledge the alarm, and then start the motor with a separate
command.
Inhibit Example
The below example shows how to implement the inhibit function for a motor M103
(see Figure 99):
•
An oil pressure sensor, P103, is used to stop the motor M103 if the oil pressure
is too low.
•
A SignalInReal object is used to supervise the sensor and a MotorUni is used to
control the motor.
•
The LTLLAct output from SignalInReal is connected to the PriorityCmd01 in
MotorUni. This means that the motor will be forced to stop when the oil
pressure is below the LL level. LTLLStat may be connected to a warning lamp
in a panel.
During start up of the equipment it is known that the oil pressure will be below the
limit, but it must be possible to start the motor. Therefore, the application logic will
set the EnableLL parameter in SignalInReal to False during start-up. This means
that LTLLAct will not be set, that is, the motor will not be stopped and no alarm is
244
3BSE040935-511
Section 2 Alarm and Event Handling
Inhibit Example
sent to the alarm list as long as the motor is starting up. LTLLStat will not be set and
the lamp will not be lit.
Suppose the operator, maybe for testing, wants to run the equipment at an oil
pressure below the LL level. He could then inhibit SignalInReal from the faceplate.
The motor will still run during the test, but an alarm will be sent to the alarm list.
LTLLStat will be set and the lamp will be lit.
3BSE040935-511
245
Inhibit Example
Section 2 Alarm and Event Handling
P103
M103
Figure 99. Example of how to implement inhibition of an alarm.
246
3BSE040935-511
Section 2 Alarm and Event Handling
Simple Event Examples
Simple Event Examples
The below examples show how to use the DataToSimpleEvent function block to
send simple event data, for example for a batch process, where data records should
be generated for the process at a number of points. There are three examples:
•
Simple Data on page 247,
•
Structured Data – Example 1 on page 249,
•
Structured Data – Example 2 on page 249.
Simple Data
Presume that an engineer wants to record three parameters in the process:
a temperature, a pressure and a stirring rate. Consequently, the engineer names
them:
varTEMP = “TEMP”
varPRESS = “PRESS”
varSTRAT = “STRAT”
These are the names the user wants to see on the screen when the recording is done,
but these names are not the same as the variable names. Instead, the names are
coupled to the extensible parameters in the Name field:
Name[1] = varTEMP
Name[2] = varPRESS
Name[3] = varSTRAT
During execution TEMP=300.2, PRESS=23.1, and STRAT=10. Temp and press are
real values (real) and STRAT is an integer, which causes no problem since Values is
of AnyType.
3BSE040935-511
247
Simple Event Examples
Section 2 Alarm and Event Handling
NestingLevel “1” is chosen and this is how it could look in Control Builder:
varTEMP = “TEMP”
tempValue := 300.2;
pressValue := 23.1;
My Log(SrcName := SrcName,
Message := Message,
Class := Class,
EventCode := thisNbrEvent
RecipePath := myLongPath,
Status => Status,
Name[1] := varTEMP,
Value[1] := tempValue,
NestingLevel[1] := 1,
Name[2] := varPRESS,
Value[2] := pressValue,
NestingLevel[2] := 1,
Name[3] := varSTRAT,
Value[3] := stratValue,
NestingLevel[3] := 1 );
In OPC Server for AC 800M, this will be encoded into an XML string.
<DATA_EV_LOG>
<TEMP Value=”300.2” type=”real”/>
<PRESS Value=”23.1” type=”real”/>
<STRAT Value=”10” type=”int”/>
</DATA_EV_LOG>
248
3BSE040935-511
Section 2 Alarm and Event Handling
Simple Event Examples
Structured Data – Example 1
An engineer wants to record data that belong together, that is, he or she wants to
create a structure named PHYS_DATA containing physical properties of an object,
in this case a tank.
The structure (PHYS_DATA) has no value in itself and the NestingLevel=1 when
PHYS_DATA is coupled to the first extensible parameter.
The next step is to give PHYS_DATA properties, and three components are created
in the following three extensible parameters:
height=4.1
length=3.0
depth=1.0
Since the parameters above are physical properties of PHYS_DATA, they are
assigned with NestingLevel=2. They are all floats.
In this case, the XML data in OPC Server for AC 800M will look like:
<DATA_EV_LOG>
<PHYS_DATA Value=”” type=””>
<height Value=”4.1” type=”real”/>
<depth Value=”3.0” type=”real”/>
<length Value=”1.0” type=”real”/>
</PHYS_DATA>
</DATA_EV_LOG>
Structured Data – Example 2
In this example, the engineer is in the same situation as in the previous example, but
now he or she also wants to record the recipe parameters in one of the batch objects.
The same procedure as in Example 1 is performed but a new parameter
“RecipePar” is added and NestingLevel=-1 is set. With NestingLevel=-1 it is
indicated that the recipe parameters to be fetched are placed on NestingLevel=1,
since the height, depth, and length values in the previous example were to be placed
on NestingLevel=2.
3BSE040935-511
249
Simple Event Examples
Section 2 Alarm and Event Handling
The recipe parameters are fetched in the controller and are:
heat=3.4
temp=349.4
heating=true
From a Control Builder view, this would look like:
structName := “PHYS_DATA”;
varHeight := “height”;
heightValue := 4.1;
varRecipe := “RecipePar”
LogThis(SrcName := SrcName,
Message := Message,
Severity := Severity,
Class := Class,
EventCode := thisNbrEvent,
RecipePath := myLongPath,
Status => Status,
Name[1] := structName,
Value[1] := EmptyValue,
NestingLevel[1] := 1,
Name[2] := varHeight,
Value[2] := heightValue,
NestingLevel[2] := 2,
Name[3] := varDepth,
Value[3] := depthValue,
NestingLevel[3] := 2,
Name[4] := varLength,
Value[4] := lengthValue,
NestingLevel[4] := 2,
Name[5] := varRecipe,
Value[5] := EmptyValue,
NestingLevel[5] := -1 );
250
3BSE040935-511
Section 2 Alarm and Event Handling
Alarm and Event Functions
The XML data will look as below. The last three parameters are fetched from a
Batch Object.
<DATA_EV_LOG>
<PHYS_DATA Value=”” type=””>
<height Value=”4.1” type=”real”/>
<depth Value=”3.0” type=”real”/>
<length Value=”1.0” type=”real”/>
</PHYS_DATA>
<RecipePar Value=”” type””/>
<heat Value=”3.4” type=”real”/>
<temp Value=”349.4” type=”real”/>
<heating Value=”true” type=”bool”/>
</DATA_EV_LOG>
Alarm and Event Functions
There are a number of functions that can be used to analyze and supervise alarm and
event handling:
•
The function block SystemDiagnostics contains a part that displays alarm and
event related information. See System Diagnostics on page 251.
•
For those who need detailed information about the alarm and event state
machine, there is a collection of state diagrams. See Acknowledgement Rules –
State Diagrams on page 252.
System Diagnostics
When in online mode, it is possible to view information regarding memory via the
interaction window of the function block SystemDiagnostics (located in the Basic
library).
The advanced mode of the interaction window displays system memory
information.
3BSE040935-511
251
Acknowledgement Rules – State Diagrams
Section 2 Alarm and Event Handling
There is also an Alarm and Event button which, if clicked, displays information
regarding:
•
Used amount of buffer size,
•
The number of:
•
a.
alarms in the controller,
b.
different condition names in the controller,
c.
local printer queues,
d.
subscribing OPC Servers.
The IP-addresses of the subscribing OPC Servers.
Acknowledgement Rules – State Diagrams
The control system handles four different condition state diagrams according to five
different acknowledgement rules.
Acknowledgement Rule 1
Rule number 1 uses three different state diagrams.
State 2
Inactive, Acked
State 4
Active, Acked
State 5
Active, Unacked
Figure 100. State diagram for enabled alarm conditions with AckRule 1, part 1.
In Figure 100 above, the alarm is in its normal state when it becomes active. It is
then acknowledged, and on becoming inactive it returns to its normal state.
252
3BSE040935-511
Section 2 Alarm and Event Handling
Acknowledgement Rules – State Diagrams
State 2
Inactive, Acked
State 3
Inactive, Unacked
State 5
Active, Unacked
Figure 101. State diagram for enabled alarm conditions with AckRule 1, part 2.
In Figure 101 above, the alarm is in its normal state when the alarm becomes active.
It then becomes inactive, and on being acknowledged returns to its normal state.
State 2
Inactive, Acked
State 5
Active, Unacked
State 3
Inactive, Unacked
State 6
Autodisabled
Figure 102. State diagram for enabled alarm conditions with AckRule 1, part 3.
3BSE040935-511
253
Acknowledgement Rules – State Diagrams
Section 2 Alarm and Event Handling
The third instance occurs when an alarm switches between active and inactive
without being acknowledged. In Figure 102, the alarm starts in its normal state and
becomes active. It then switches twice between active and inactive without being
acknowledged. When the alarm becomes inactive a third time it is automatically
placed in the Auto-disabled state. Whether the alarm is active or inactive in this state
is of no significance. When acknowledged the alarm returns to its normal state.
The default setting for auto-disable is three times. This can be changed through
the CPU setting AE Limit Auto Disable. If it is set to 0, there will be no autodisable function. There is also a system variable called AlarmAutoDisableLimit
which affects all process alarms with acknowledgement rule number 1
(AckRule=1).
Acknowledgement Rule 2
State 2
Inactive, Acked
State 4
Active, Acked
Figure 103. State diagram for enabled alarm conditions with AckRule 2.
Alarm conditions with AckRule 2 does not require acknowledgement and therefore
follow a different state diagram. When the alarm becomes active it switches to an
active and acknowledged state. On becoming inactive it returns to its normal state.
254
3BSE040935-511
Section 2 Alarm and Event Handling
Acknowledgement Rules – State Diagrams
Acknowledgement Rule 3
State 2
Inactive, Acked
State 5
Active, Unacked
Figure 104. State diagram for enabled alarm conditions with AckRule 3.
Regardless of the signal being monitored, alarm conditions with AckRule 3 changes
immediately to is normal state on acknowledgement. The alarm is no longer active
and disappears from the alarm list provided by an OPC client.
Acknowledgement Rule 4
Presently, Acknowledgement Rule 4 (AckRule 4) is reserved for future use.
Acknowledgement Rule 5
State 2
Inactive, Acked
State 4
Active, Acked
State 5
Active, Unacked
Figure 105. State diagram for enabled alarm conditions with AckRule 5, part 1.
AckRule 5 is used for so called sum system alarms. System alarms associated with
hardware units are typical examples of sum system alarms. They are used to indicate
several different errors that occur at the same time.
3BSE040935-511
255
Acknowledgement Rules – State Diagrams
Section 2 Alarm and Event Handling
There are two procedures for sum system alarms, that is, for AckRule 5. The first of
these is described in Figure 105 above. The sum system alarm is in its normal state
when it becomes active. Sum system alarms are used as a collection of errors and
Acknowledgement means that all errors are acknowledged. On becoming inactive it
returns to its normal state.
State 2
Inactive, Acked
State 3
Inactive, Unacked
State 5
Active, Unacked
Figure 106. State diagram for enabled alarm conditions with AckRule 5, part 2.
The second instance is shown in Figure 106 above. The sum system alarm is in its
normal state when it becomes active. It then becomes inactive, and on being
acknowledged returns to its normal state.
Any alarm can be disabled from any state, and when re-enabled placed in the
Inactive and Acked state. If the alarm state engine receives an incorrect Enable,
Disable or Acknowledgement request, the request is ignored.
256
3BSE040935-511
Section 3 Communication
Introduction
This section describes how to configure communication throughout your control
network. How to design your control network, and which protocol(s) to choose for
this is described in the AC 800M Communication Protocols (3BSE035982*).
This section is split into the following parts:
•
Communication Libraries on page 258 gives a brief overview of the
Communication standard libraries.
•
Supported Protocols on page 271 gives a brief overview of the protocols
supported by control builder.
•
Control Network on page 272 describes Control Network, which is used to
communicate between controllers, engineering stations, and external devices.
•
Variable Communication on page 274 describes variable communication
briefly, and contains references to more detailed information.
•
Reading/Sending Data on page 278 describes reading and sending data.
•
Fieldbus Communication on page 284 describes the supported fieldbus
protocols briefly.
3BSE040935-511
257
Communication Libraries
Section 3 Communication
Communication Libraries
The Communication libraries contains a number of libraries, one for each protocol,
with function block types for reading and writing variables from one system to
another. Typical communication function block types are named using the protocol
name and function, for example, COMLIRead or INSUMConnect.
All supported protocols are described in the AC 800M Communication Protocols
(3BSE035982*), which also contains general information about how to set up
communication in a control network. For detailed information on how to connect
and configure function block types and control module types, see the
corresponding online help (select the type and press F1).
COMLI Communication Library
The COMLI Communication library (COMLICommLib) contains function block
types and data types for COMLI communication.
COMLI function block types follow the IEC 1131 standard, but some divergences
occur. COMLI can be used for point-to-point or multidrop communication.
Communication takes place serially and asynchronously, based on the master/slave
principle, and in half duplex. Only address-oriented COMLI is supported on serial
channels.
INSUM Communication Library
The INSUM Communication library (INSUMCommLib) contains function block
types and data types for INSUM (Integrated System for User-optimized Motor
control) communication.
INSUM is a system for protection and control of motors and switchgear. AC 800M
controllers communicate with the INSUM system via TCP/IP, using the
communication interface CI857.
Usage and Status Information for INSUMConnect Function Block
To establish connection using INSUMConnect, set the value of the En_C parameter
to ‘true’, and specify the remote system with the CIPos and GWPos parameters. A
reference to the connection is inserted into the Id parameter so that this parameter
258
3BSE040935-511
Section 3 Communication
INSUM Communication Library
can be used by other function blocks communicating via the same connection (for
example, INSUMReceive and INSUMWrite function blocks).
The execution status of INSUMConnect is presented via the following parameters:
•
Valid
A "bool" parameter that indicates if the connection is working (true) or not
(false)
•
Error
A "bool" parameter that is true during one execution cycle, after the detection
of an error.
•
Status
A "dint" parameter that gives a value about the execution status of the function
block. A negative value means an error.
•
MsgStatus
A "INSUMGWMsgStatus" structure that contains status information about the
connection. This information is received from the gateway.
•
GWStatus
A "INSUMGWStatus" structure that contains status information about the
gateway. This information is collected by other means that just handles the
connection (for example, the supervision of the CI857 module).
Usage and Status Information for INSUMReceive Function Block
To activate cyclic reading of data through INSUMReceive, set the value of EN_R
parameter to ‘true’, and connect the Id parameter of INSUMReceive to the Id
parameter of an INSUMConnect function block.
The execution status of INSUMReceive is presented via the following parameters,
apart from the common paramters like Valid, Error, and Status (which are described
for INSUMConnect):
•
Ndr
A "bool" parameter that is set to ‘True’ during one execution cycle, after the
new data is received through the Rd parameter or any of the status parameters.
3BSE040935-511
259
INSUM Communication Library
•
Section 3 Communication
MsgStatus
An "INSUMDeviceMsgStatus" structure that contains status information about
the Network Variable subscription created by this INSUMReceive block. This
information is received from the gateway.
•
DeviceStatus
A "dint" value that contains status information about the INSUM device from
which the INSUMReceive block receives data. This information is received
from the Field Device List in the gateway.
Usage and Status Information for INSUMWrite Function Block
To run the write operation through INSUMWrite, set the value of the Req parameter
to ‘true’, and connect the Id parameter of INSUMWrite to the Id parameter of an
INSUMConnect function block.
The execution status of INSUMReceive is presented via the GWMsgStatus
parameter, apart from the common paramters like Error and Status (which are
described for INSUMConnect). The GWMsgStatus is a "dint" field that contains
status information about how the write operation is executed. This information is
received from the gateway.
The INSUM system consists of devices that are connected via a LonWorks network.
There are different device types for different types of equipment that can be
controlled and supervised. The device type used for motor control is called a Motor
Control Unit (MCU). The MCU is located in the motor starter module.
260
3BSE040935-511
Section 3 Communication
INSUM Communication Library
Network Variables in Motor Control Units (MCU)
The table shows Network Variables that are defined in the INSUM Motor Control
Unit.
Function/Object
NV name in MCU
in MCU
Dir.
Description
Current
Measurement
nvoCurrRep
In
Current information: A, % and Earth
current
TOL (Thermal
overload)
nvoCalcProcVal
In
Thermal capacity: % to Thermal
Overload
nvoTimeToTrip
In
Estimate of time until the motor will trip
due to thermal overload based on the
current load.
nvoTimeToReset
In
Remaining time until it is possible to
reset the MCU after a thermal overload
trip.
nviDesState
Out
Commands: Start, Stop etc
nvoCumRunT
In
Cumulated run hours
nvoMotorStateExt
In
Motor status: Running, Stopped, Alarm
etc
Contactor 1
nvoOpCount1
In
Number of switch cycles for contactor 1.
Contactor 2
nvoOpCount2
In
Number of switch cycles for contactor 2.
Contactor 3
nvoOpCount3
In
Number of switch cycles for contactor 3.
Control Access
nviCAPass
Out
Control access commands:
Local/Remote control of the device
nvoActualCA1
In
Feedback of Control access commands
Node
nvoAlarmReport
In
Alarmreport with Warning- and Trip
information
Voltage
Measurement
nvoVoltRep
In
Phase voltages and frequency
Motor Control
3BSE040935-511
261
INSUM Communication Library
Function/Object
NV name in MCU
in MCU
Power
Measurement
Section 3 Communication
Dir.
Description
In
Motor power: Active power, reactive
power and power factor
Out
General Purpose Output 1
In
Feedback of General Purpose Output 1
nviGpOut2
Out
General Purpose Output 2
nvoGpOut2Fb
In
Feedback of General Purpose Output 2
nvoGpIn1
In
General Purpose Input 1
nvoGpIn2
In
General Purpose Input 2
nvoPowRep
General Purpose nviGpOut1
I/O
nvoGpOut1Fb
Network Variables in Circuit Breakers
The table shows Network Variables that are defined in the INSUM Circuit Breakers.
Function/Object in
Circuit Breaker
NV name in Circuit
Breaker
Dir.
Description
Node
nvoNodeAlarmRep
In
Alarm report with Warning- and Trip
information
nviNodeCommand
Out
Commands: Open, Close etc
nvoNodeStatusRep
In
Circuit Breaker Status: Closed, Open,
Alarm etc
RMS Current
nvoAmpsCurrRep
In
Current information: A, % and Earth
current
Control Access
nviCAPass
Out
Control access commands:
Local/Remote control of the device
nvoCAOwner
In
Feedback of Control access commands
262
3BSE040935-511
Section 3 Communication
MB300 Communication Library
MB300 Communication Library
The MB300 Communication library (MB300CommLib) contains function block
types for MB300 communication. The MasterBus 300 (MB 300) protocol can be
used with AC 800M and AC 400. The CI855 communication interface unit for AC
800M is used to connect to AC 400 controllers via MasterBus 300.
Dataset communication between controllers connected to MasterBus 300 is handled
by three function blocks. A dataset consists of an address part and up to 24 elements
(32-bit values). Values can be a 32-bit integer, a 16-bit integer, a real or 32 booleans.
Each CI855 unit behaves as a unique node on the MasterBus 300 network it is
connected to, and has to be configured accordingly in the Control Builder hardware
tree.
3BSE040935-511
263
MMS Communication Library
Section 3 Communication
MMS Communication Library
The MMS Communication library (MMSCommLib) contains MMS data types,
function block types and control module types for establishing communication with
systems using the MMS protocol. MMS (Manufacturing Message Specification) is
used as a common application layer protocol. MMS defines communication
messages transferred between units, and has been specifically designed for
industrial applications.
MMS is the base protocol in Control Network. All communication between Control
Builders/OPC Servers and controllers uses MMS, for example, project download,
firmware download and online communication. Alarm and event handling also uses
MMS.
If the MMS Communication library is used, the communication between controllers
can be defined using access variables and function block types and/or control
module types from the MMS Communication library.
It is also possible to define the communication between controllers without using
MMSCommLib, by using the IAC feature and communication variables.
For more information on MMS communication, see the AC 800M Communication
Protocols (3BSE035982*).
264
3BSE040935-511
Section 3 Communication
MODBUS RTU Communication Library
MODBUS RTU Communication Library
The MODBUS RTU Communication library (ModBusCommLib) contains data
types and function block types for communication via the MODBUS protocol.
MODBUS can be used for point-to-point or multidrop communication.
Communication takes place serially and asynchronously, based on the master/slave
principle, and in half duplex. MODBUS slave communication is not supported, only
master communication.
MODBUS TCP Communication Library
The MODBUS TCP communication library (ModBusTCPCommLib) contains
function blocks types supporting the MODBUS TCP protocol. The types are used
for MODBUS TCP communication through Ethernet ports on CI867.
MODBUS is a request response protocol and offers services specified by function
codes and supports both master and slave functionality.
The master functionality provides the possibility to access registers and coils in
other MODBUS TCP devices for both write and read operations. It is also possible
for masters to retrieve status/diagnostic information from the slaves.
The slave functionality provides the possibility for other devices to access Access
Variables. Both read and write operations are possible.
Modem Communication Library
The Modem Communication library (ModemCommLib) contains function block
types used for serial communication over a modem. To use a modem connection, the
modem must be configured to a serial (Com) port and the COMLI protocol must be
added and configured (for more information, see Control Builder online help).
For more information about modem communication, see also the AC 800M
Communication Protocols (3BSE035982*).
Siemens S3964 Communication Library
The Siemens S3964 Communication library (S3964CommLib) contains function
block types to establish communication with a system supporting the Siemens
3964R protocol.
3BSE040935-511
265
SattBus Communication Library
Section 3 Communication
Siemens 3964R is a point-to-point protocol, which means that only one Siemens
system can be connected to each channel. The Siemens system requires an
Interpreter RK 512 unit.
SattBus Communication Library
The SattBus Communication library (SattBusCommLib) contains function block
types supporting SattBus. The types are used to communicate through Ethernet,
using the SattBus name-oriented model.
SattBus is only available for TCP/IP on Ethernet.
MTM Communication Library
The MOD5-to-MOD5 communication library, MTMCommLib, provides function
blocks to implement variable communication client in MOD5 controller to
AC 800M communication.
The MTMCommLib contains function block types.
The MOD5-to-MOD5 (MTM) protocol consists of request and response messages
that are exchanged each second.
The requests sent to other connected systems are determined by the control
application. The response sent at each second is determined by the requests received
at the previous second from other connected systems. The application programmer
accesses the protocol functions through standard function blocks.
The library uses the functions blocks MTMConnect, MTMReadCyc, MTMDefCyc,
and MTMDefERCyc to translate the request and to answer the MOD5 commands.
266
3BSE040935-511
Section 3 Communication
Serial Communication Library
Serial Communication Library
The Serial Communication library (SerialCommLib) contains function block types
for communication with external devices (for example printers, terminals, scanner
pens) via serial channels with user-defined protocols. You can write an application
which controls the characters sent and checks whether the correct answer is
received, using serial channel handling function blocks.
The following use cases help in understanding the libraries used in serial
communication.
Establishing a valid connection for serial communication
The prerequisites to establish a valid serial port connection for reading data from a
physical device or writing data to a physical device are:
•
Download the 61131-3 application that contains SerialCommLib and
SerialHWLib.
•
Instantiate the SerialConnect function block.
After the connection is established, the protocol is configured with the default
behavior (read and write messages ended by an EOM (End of Message)). The
default behavior is described by the parameters like En_C, Channel, Partner, Valid,
Error, Status, and ID, which are present in the function block.
If a malfunction of the connected CI853 communication module is detected, the
module can be replaced by a new one, and the connection to the serial port is
automatically reestablished.
Adding a CRC calculation to a message in serial communication
The prerequisites to add a CRC calculation to a message are:
•
Establish a valid connection to the serial port.
•
Instantiate the SerialSetup function block in the 61131-3 application.
After the CRC calculation is added, the settings of CRC remain intact even after a
disconnect operation.
3BSE040935-511
267
Serial Communication Library
Section 3 Communication
Enabling basic listening for serial communication
The prerequisites to enable the basic listening of serial communication data from a
device are:
•
Establish a valid connection to the serial port.
•
Instantiate the SerialListen function block in the 61131-3 application.
The input parameters for basic listening are message length, end of message, and
number of trailing characters.
After the basic listening is enabled, the string message (which is the output seen in
the Rd parameter) is received by the input device.
Enabling basic writing of serial communication data
The prerequisites to enable the basic writing of serial communication data to a
device are:
•
Establish a valid connection to the serial port.
•
Instantiate the SerialWrite function block in the 61131-3 application.
After the basic writing is enabled, the output is an acknowledgment from the Sd
parameter.
Example (Buffer handling)
A SerialListen function block is set up to read a specified message length of for
example 5 characters (MsgLength = 5).
While the Enable parameter has the value True and the buffer contains characters
the Ndr parameter will be True and 5 characters at a time will be passed to the Rd
parameter.
If an incoming message "012345678901234" has been received with a size of 15
characters (3x5) and is stored in the buffer the following will occur:
First scan: Rd = 01234 (012345678901234), Buffer = 5678901234
Second scan: Rd = 56789 (012345678901234), Buffer = 01234
Third scan: Rd= 01234 (012345678901234), Buffer is empty
There will be no fourth scan since the buffer is empty.
268
3BSE040935-511
Section 3 Communication
TCP and UDP Communication Libraries
If the message length is not a multiple of the MsgLength parameter the buffer will
keep the remaining characters until the number of characters in the buffer again is
greater than or equal to the MsgLength parameter value.
If an incoming message "0123456789012" has been received with a size of 13
characters (2x5+3) and is stored in the buffer the following will occur:
First scan: Rd = 01234 (0123456789012), Buffer = 56789012
Second scan: Rd = 56789 (0123456789012), Buffer = 012
There will be no third scan as the buffer does not contain at least 5 characters. The
buffer will retain these values until additional characters are added to the buffer and
it once again equals, or exceeds, 5 characters in length. At that time, the first 5
characters will be passed to the Rd parameter.
By setting the En_C parameter of the SerialConnect function block to value False
(disconnecting), the buffer of the serial channel will be cleared.
TCP and UDP Communication Libraries
The UDP communication library (UDPCommLib) and TCP communication library
(TCPCommLib) library provide function blocks that can be used to implement
protocols running on UDP or TCP.
The typical usage of these libraries is when the controller needs to communicate
with external equipment. Some examples are:
•
Communication with different road-infrastructure network nodes such as
variable speed signs, traffic direction and information signs.
•
Vision cameras – Many vision cameras implement the Telnet protocol (ASCII
TCP communication over standard port number 23).
•
Information server – The controller may function as both client and server on
the network. Example of server use is a SCADA application where a
supervisory system connects to different servers and collects information
periodically.
UDP communication does not establish a connection prior to sending/receiving. The
UDPCommLib supports broadcasting with which one node can send a message that
is received by many nodes.
3BSE040935-511
269
TCP and UDP Communication Libraries
Section 3 Communication
TCP is a point-to-point connection. Using TCPCommLib also ensures that the
messages are delivered without loss.
The only hardware configuration that is needed in Control Builder is to attach the
UDPProtocol and TCPProtocol hardware types (from UDPHwLib and TCPHwLib
respectively) under the IP position in the AC 800M controller harware tree.
270
3BSE040935-511
Section 3 Communication
Supported Protocols
Supported Protocols
Table 20 lists all supported protocols.
Table 20. Protocols supported by Control Builder
Protocol
Port/Interface
MMS on Ethernet
CN1, CN2 (TP830)
MMS on RS-232C (PPP)
COM3 (TP830), CI853
MasterBus 300
CI855
SattBus on TCP/IP
CN1 (TP830)
COMLI(1)
COM3 (TP830), CI853
Siemens 3964R(2)
MODBUS
COM3 (TP830), CI853
COM3 (TP830), CI853
MODBUS TCP on Ethernet(1)
Ch1, Ch2, CI867
IEC 61850
Ch1, CI868
PROFIBUS DP
CI854
DriveBus
CI858
INSUM
CI857
MOD5-to-MOD5
CI872
AF 100
CI869
PROFINET IO
CI871
EtherNet/IP
Ch1, CI873
UDP
Ch1, Ch2
TCP
Ch1, Ch2
(1)
(2)
(3)
3BSE040935-511
RTU(3)
Both master and slave
Master only
Master only
271
Control Network
Section 3 Communication
For more information on supported protocols, see the AC 800M Communication
Protocols (3BSE035982*).
Control Network
Control Network is a private IP network domain especially designed for industrial
applications. This means that all communication handling will be the same,
regardless of network type or connected devices. Control Network is scalable from a
very small network with a few nodes to a large network containing a number of
network areas with hundreds of addressable nodes (there may be other restrictions
such as controller performance).
Control Network uses the MMS communication protocol on Ethernet and/or
RS-232C to link workstations to controllers. In order to support Control Network on
RS-232C links, the Point-to-Point Protocol (PPP) is used.
For information on time stamps and clock synchronization within Control
Network, see the AC 800M Communication Protocols (3BSE035982*). Time
synchronization is also briefly described in Section 2, Alarm and Event
Handling.
Control Network, as well as other protocols and fieldbuses, is configured using
Control Builder (via the Project Explorer interface). Control Network settings are
specified in the parameter lists, accessed by right-clicking CPUs, Ethernet ports
and/or PPP connections.
The address of controller Ethernet ports should in some cases be set using the
IPConfig tool. See the Compact 800 Engineering Compact Control Builder
AC 800M Getting Started(3BSE041584*).
For information on communication parameter settings, see Control Builder
online help for the object in question. Select the object in Project Explorer, then
press F1 to display the corresponding online help topic.
Network Redundancy
The Redundant Network Routing Protocol (RNRP), developed by ABB, handles
alternative paths between nodes and automatically adapts to topology changes.
For more information on redundancy and RNRP, see the Automation System
Network manual.
272
3BSE040935-511
Section 3 Communication
Statistics and Information on Communication
Statistics and Information on Communication
Statistics concerning all MMS communication and Inter Application
Communication (IAC) in a system are displayed in the Remote System dialog.
Information can be viewed at any engineering station that is connected to the
network, by selecting Tools > Maintenance > Remote System, followed by Show
Remote Systems.
You can get the following MMS-related information:
•
Tools > Maintenance > Remote System > Show MMS Variables shows
which MMS variables are present in the selected remote system
•
Tools> Maintenance > Remote System > Show MMS Connections shows
all connections, including information on the type of connection, the
destination system, and a number of statistics.
The information regarding IAC (using communication variables) can be accessed
from Tools > Maintenance > Remote System > Show Diagnostics for
Communication Variables. See Diagnostics for Communication Variables on page
345.
There is also a function block type System Diagnostics that is stored in the Basic
library. This function block will (among other things) show Communication
variables, IAC, and Ethernet statistics.
For more information on the contents of the Remote System dialog and the
System Diagnostics function block type, see Control Builder online help.
3BSE040935-511
273
Variable Communication
Section 3 Communication
Variable Communication
Communication between applications uses access variables and communication
variables.
Access Variables
Access variables are defined in the access variable editor, which is displayed by
double-clicking Access Variables in the Controllers folder. The access variable
editor can also be displayed from the application editor, by double-clicking an
access variable field in the Access Variables column.
Access variables can use the MMS, COMLI, MODBUS TCP and SattBus protocols.
MMS and SattBus variables are declared in the Access Variable Editor under the
corresponding tab, COMLI and MODBUS TCP variables under the Address tab.
Paths to local variables are given using the syntax
ApplicationName.ProgramName.FunctionblockName.VariableName
Communication Variables
Communication variables are used for cyclic communication between top level
diagrams, programs and top level single control modules. These objects can exist in
the same application, the same controller, or in another controller. The name of the
communication variable must be unique on the project to resolve the IP-address
during compilation.
Communication variables behave differently depending on where the in and out
variables are placed:
•
In and out variables are in the same application and connected to the same
IEC 61131-3 task
–
274
In this case, the in and out variable represents the same physical memory
location; hence no communication is setup.
3BSE040935-511
Section 3 Communication
•
In and out variables are in the same application, but connected to different IEC
61131-3 tasks; or the in and out variables are in different applications in the
same controller
–
•
StartAddr
In this case, fast data copying is performed at each 61131-3 task scan for
the in variable. This type of IAC is called internal IAC, where the data is
copied between different memory locations, and this does not involve any
real communication. This is controlled by the task time, hence no external
communication is setup.
In and out variables are in different applications in different controllers
(external communication)
In this case, the actual external IAC occurs, and the client receives new values
based on the configured interval time. The protocol used is IAC_MMS, which
is based on User Datagram Protocol (UDP).
Five different interval time categories are used and these are configured on the
IAC_MMS hardware unit in Control Builder.
Communication variables are declared in the editor for diagrams, programs and top
level single control modules in Control Builder.
The communication using the declared communication variables happens only if
the IP and IAC MMS hardware types are inserted under the controller in the
hardware tree in Control Builder.
For more information about variable communication, see Variables and
Parameters on page 69.
StartAddr
All read and write function blocks have a StartAddr parameter. The StartAddr
identifies the first requested variable in the remote system.
Set a prefix and a start address via the StartAdr parameter. This sets the access
variable which identifies the memory area in the remote system from which data is
to be read or to which it is to be written.
For further information regarding memory addressing: see IEC 61131-3 Variable
Representation for IEC 61131-3 direct addressing and Access Variable Syntax for
direct addressing.
3BSE040935-511
275
StartAddr
Section 3 Communication
Example 1
You can read 16 bits from a subsystem, starting from the decimal address 64 (octal
address 100), as follows.
Connect a structured variable declared with 16 Boolean components to the Rd[1]
parameter in the COMLIRead function block. Then set the StartAddr parameter to:
Table 21. StartAddr parameter setting (16 bits)
Protocol
IEC 61131-3 Direct Addressing
Direct Addressing (Octal, 8# only)
MODBUS RTU/
MODBUS TCP
%IX8#100 (input)
%QX8#100 (output)
%IX10#64 (input)
%QX10#64 (output)
%IX16#40 (input)
%QX16#40 (output)
Not supported
COMLI
%MX8#100
%MX10#64
%MX16#40
%X100 or X100
Siemens 3964R
%MX8#100
%MX10#64
%MX16#40
%X100 or X100
Text in bold face indicates the most commonly used values.
If you exclude the base from the format it is assumed to be base 10. For example,
%MX64 is interpreted as %MX10#64.
Example 2
You can read a Register 45 from a subsystem, starting from the decimal address 45,
as follows:
276
3BSE040935-511
Section 3 Communication
StartAddr
Connect a structured variable declared with 16 Boolean components to the Rd[1]
parameter in the COMLIRead function block. Then set the StartAddr parameter to:
Table 22. StartAddr parameter setting (Register 45)
Protocol
IEC 61131-3 Direct Addressing
Direct Addressing (Octal, 8# only)
MODBUS RTU/
MODBUS TCP
%MW8#55
%IW8#55 (input)
%QW8#55 (output)
Not supported
%MW10#45
%IW10#45 (input)
%QW10#45 (output)
%MW16#2D
%IW16#2D (input)
%QW16#2D (output)
COMLI
%MW8#55
%R45 or R45
%MW10#45
%MW16#2D
Siemens 3964R
%MW8#55
%R45 or R45
%MW10#45
%MW16#2D
Text in bold face indicates the most commonly used values.
If you exclude the base from the format it is assumed to be base 10. For example,
%MW45 is interpreted as %MW10#45.
3BSE040935-511
277
Reading/Sending Data
Section 3 Communication
Reading/Sending Data
The communication libraries contain all types you need to set up communication for
the supported protocols. For most protocols, there are three main types:
Due to variations between various protocols, the name of individual types and
parameters may vary slightly between the different communication libraries.
However, the communication principles are still the same.
Communication function blocks should not be called more than once per scan.
Exceptions to this are stated explicitly in the corresponding online help. Do not
call communication function blocks in SFC, in IF statements, in CASE
statements, etc.
•
Connect Types
Connect types are used to initiate a communication channel and establish a
connection to a remote system with a unique node address in a network.
Connect types are used to open a communication channel. The identity of the
opened channel is communicated to the Read and Write types via an identity
parameter (the exact name of this parameter varies between protocols). For
example, MMSConnect is used by MMSRead and MMSWrite.
A connection is established when an enable parameter is set to true. This means
that a communication channel can be opened whenever needed. The identity of
the system to which a connection has been established is communicated to the
corresponding read and write types via an Id parameter.
Connect types have a built-in continuous supervisory function, which detects if
communication is interrupted after connection has been established.
g
The MMSWrite is used for communication between applications.
Communication between applications residing in different controllers is called
external, and is asynchronous. Communication between applications within the
same controller is called internal. The internal copy is synchronous or
asynchronous based on the amount of data copied.
The basic algorithm is based on how much data that can be copied synchronously
without disturbing the execution of 1131 tasks, that is the task latency must be
less than 2 ms. The total amount of data to be copied is about 800 bytes of
variable data. If the total of 800 bytes is exceeded the internal copy may affect the
task latency negatively and therefore the internal copy is executed
asynchronously.
278
3BSE040935-511
Section 3 Communication
Connection Methods
•
Read Types
Read types read data (often an access variable) from a target system. The
source system (the communication channel) is indicated by the Id parameter,
which is passed from the corresponding connect function block or control
module.
•
Write Types
Write types write data to a target system. The target system (the
communication channel) is indicated by the Id parameter, which is passed from
the corresponding connect function block or control module.
For some protocols, there are also additional types, such as types for cyclic reading
of data, data conversion, download of measuring ranges, etc.
Connection Methods
Function blocks from the communication libraries are used to read and write
variables from a remote system:
Figure 107. Function blocks in the communication libraries.
In the application program, a common Connect function block is used in a client
(master) to establish connection to a server (slave). The function blocks Read and
Write can then be used repeatedly. Refer to online help for a description of the
parameters concerned. Variables to be accessed must be declared in the server
Access variable editor.
To display the editor, right-click the Access Variables object and select Editor.
3BSE040935-511
279
Connection Methods
Section 3 Communication
Example 1:
Controller 2 (client) connects to Controller 1 (server) by means of a Connect
function block. Refer to online help for a description of how Partner and Channel
are specified for different communication protocols. Read and Write function blocks
with the same identity (ID) as the Connect block can then be used repeatedly.
As an example, Controller 2 has a Read function block in its application program
that sends a Read request to Controller 1 for an access variable named %R100. This
name must exist in the access variable list in Controller 1, which then reads the
value of Program1.A (%R100) and sends it to Controller 2. The value is then written
to the application variable named in Rd.
In the same way, the value of a variable in the Controller 1 access variable list can be
changed by means of a Write function block in Controller 2.
Controller 1 (server)
Controller 2 (client)
Connect
Access
variable
list
Partner
Channel
ID
%R100
Read
StartAddr
Program1.A
%R100
Rd
Write
ID
ID
StartAddr
Sd
Figure 108. Variable read by controller 2, from controller 1.
The function blocks ReadCyc and WriteCyc perform in a similar manner, but are
used to cyclically read or write to/from a server system with the interval specified by
the SupTime parameter.
280
3BSE040935-511
Section 3 Communication
Communication Concepts
Example 2:
Write and read requests are triggered by the Req parameter being set to True after
having been False for at least one scan. This problem can be avoided if two function
blocks are executed, one after the other. In this way, a request is always outstanding.
Additional requests triggered by the Req parameter will be ignored by the function
block, until the Done (or Ndr) parameter has become True.
Write
Done
Req
StartAddr
Write
• Req
Done
StartAddr
Figure 109. Resetting the Req parameter using two function blocks.
Communication Concepts
When setting up communication with external devices and other controllers, it is
also important to be familiar with the following:
•
The client/server concept (master/slave), see Client/Server Communication on
page 282,
•
The publisher/subscriber (also called subscriber/provider) concept, see
Publisher/Subscriber Communication on page 283.
•
There is also the choice between cyclic and asynchronous communication, see
Cyclic vs. Asynchronous Communication on page 284.
3BSE040935-511
281
Communication Concepts
Section 3 Communication
Client/Server Communication
The main principle of client/server communication is the following:
•
The client is the active party, which requests (reads) data from the server.
•
The server is a passive provider of information that simply answers to requests
from the clients.
Client/server communication could also be described as master/slave
communication. In that case, the client is the master, and the server is the slave.
Figure 110 shows the principle.
Server application
Function block
providing data
(server)
Data (sent on request)
(Communication Channel)
Request for data (cyclic or triggered)
Read function
block (client)
Client application
Figure 110. Client/server principle. The client reads data from the server. The
server sends data to the client when requested.
282
3BSE040935-511
Section 3 Communication
Communication Concepts
Publisher/Subscriber Communication
The main principle of publisher/subscriber communication is the following:
•
The publisher publishes (the publisher is also known as the provider) data
cyclically, in a pre-determined location.
•
The subscriber is a consumer of information, which subscribes to published
data.
Figure 111 shows the publisher/subscriber principle.
Publisher application
Function block
providing data
(server)
(Communication Channel)
Data (written cyclically)
Request for data (cyclic or triggered)
Data storage
(Communication Channel)
Read function
block (subscriber)
Data (sent on request)
Subscriber application
Figure 111. Publisher/subscriber principle. The publisher publishes data to a predefined location, which is read by the subscriber.
3BSE040935-511
283
Fieldbus Communication
Section 3 Communication
Cyclic vs. Asynchronous Communication
An important decision when setting up communication is whether communication
should be cyclic, that is, take place regularly, with a certain time interval, or
asynchronous, that is, take place when triggered by a certain event or condition.
Which method to use depends on things such as:
•
How much does the execution of communication code affect performance?
•
How often can a value be expected to change?
•
How important is it that a change in a certain value is communicated
immediately?
For more information about communication, performance and design, see
Application Programming manual.
For information on how to make part of your code execute with a different
interval, see Control the Execution of Individual Objects on page 92.
Fieldbus Communication
Fieldbuses offer communication on a dedicated bus, using a special fieldbus
communication protocol. Fieldbus devices often contain distributed code, which
means that they need to be set up not only from Control Builder, but also using a
fieldbus-specific configuration tool.
For detailed information on how to configure the fieldbuses, refer to the
corresponding, fieldbus-specific documentation. For detailed information on how
to configure communication with fieldbus devices, see the corresponding Control
Builder online help.
PROFIBUS DP
PROFIBUS (PROcess FIeld BUS) is a fieldbus standard, especially designed for
communication between systems and process objects. This protocol is open and
vendor independent. It is based on the standard EN 50 170. With PROFIBUS,
devices from different manufacturers can communicate without special interface
adjustments. PROFIBUS can be used for both high speed, time critical transmission
and extensive, complex communication tasks.
284
3BSE040935-511
Section 3 Communication
Fieldbus Communication
PROFIBUS has defined the three types of protocol: PROFIBUS FMS, DP and PA.
With AC 800M access to PROFIBUS DP and PA is supported.
PROFIBUS DP is connected to the controller via the CI854/CI854A communication
interface unit. The connection to PROFIBUS PA can be established by use of the
Linking Device LD 800P that links between PROFIBUS DP and PROFIBUS PA.
The original version of PROFIBUS DP, designated PROFIBUS DP-V0, has been
expanded to include version DP-V1 and DP-V2. With CI854/CI854A support for
DP-V1 and the acyclic services (toolrouting) is given. In addition CI854/CI854A
supports line and slave redundancy and CI854A supports master redundancy as
well.
The PROFIBUS DP-V0 configuration and parameter data for slave devices are
engineered in Control Builder and downloaded via CI854/CI854A.
PROFIBUS slave types are usually supplied with a *.gsd file. This file describes the
properties of the slave type. The *.gsd file must be converted with the Device Import
Wizard, in order to be used in the project.
PROFINET IO
PROFINET is a manufacturer-independent Fieldbus standard for applications in
manufacturing and process automation. PROFINET technology is described in fixed
terms in IEC 61158 and IEC 61784 as an international standard.
PROFINET IO uses Ethernet communication to integrate simple distributed I/O and
time-critical applications.
PROFINET IO describes a device model oriented to the PROFIBUS framework,
which consists of places of insertion (slots) and groups of I/O channels (subslots).
The technical characteristics of the field devices are described by the General
Station Description (GSD) on an XML basis. The PROFINET IO engineering is
performed in a way familiar to PROFIBUS. The distributed field devices are
assigned to the controllers during configuration.
The PROFINET IO is interfaced to the IEC 61131 controller AC 800M, using the
PROFINET IO module CI871.
PROFINET IO is based on IEEE 802.3. PROFINET IO uses Ethernet, TCP, UDP,
and IP as the basis for communication. It is designed to work with other IP-based
protocols on the same network.
3BSE040935-511
285
Fieldbus Communication
Section 3 Communication
The transmission of time-critical process data within the production facility, occurs
in the Real-Time (RT) channel.
DriveBus
The DriveBus protocol is used to communicate with ABB Drives and ABB
Special I/O units. DriveBus is connected to the controller via a CI858
communication interface unit.
Advant Fieldbus 100
Advant Fieldbus 100 (AF 100) is a high performance fieldbus, which is used for:
•
Communication between Advant Controllers.
•
Communication between Advant Controllers and S800 I/O Stations, AC 800M
controllers, and so on.
Advant Fieldbus 100 supports three transmission media:
•
Twisted pair (Twp)
•
Coaxial (RG59 and RG11)
•
Optical media.
An AF 100 bus can be built up with all the three media, where a part of one kind of
media is a specific segment.
The CI869 communication interface that is attached to the AC 800M controller
provides connectivity to other AC 800M, AC 160 or connectivity server over
AF 100. An AC 800M controller with the communication interface CI869 behaves
as an AF 100 station, receiving data from other AF 100 stations/devices. The CI869
has integrated Twisted Pair modems.
The Advant Fieldbus 100 supports two different kinds of communication:
•
Process data—Dynamic data used to monitor and control a process
•
Message transfer—Used for parameters, program loading, and diagnostic
purposes.
The protocols used by the supported fieldbuses are described in detail in the
AC 800M Communication Protocols (3BSE035982*).
286
3BSE040935-511
Section 3 Communication
MMS Communication
MMS Communication
How to Choose Function Block/Control Modules in MMSCommLib
MMSCommLib contains of function block types and control modules for different
communication purposes. See Figure 112 which types to be used at communication
between two controllers.
Figure 112. Function block types to be used at
3BSE040935-511
287
MMS Communication
288
Section 3 Communication
3BSE040935-511
Section 4 Online Functions
Introduction
When a controller project is in online mode and test mode, it is possible to inspect
the code while running it, and interact with the code. Furthermore, you can issue
operations to the controller. There are also functions to help the user to find online
errors and to document the control project.
The following functions are available in online mode and test mode:
•
Online editors, see Online Editors on page 290.
•
Dynamic display of I/O channels and forcing, see Dynamic Display of I/O
Channels and Forcing on page 294.
•
Scaling analog signals, see Scaling Analog Signals on page 296.
•
Unit status and channel status, see Supervising Unit Status on page 296.
•
Communication variable status, see Supervising Communication Variable
Status on page 299.
•
Hardware and task status indications, see Status Indications on page 304.
•
Tasks, see Tasks on page 306.
•
Interaction windows, see Interaction Windows on page 307.
•
Status and error messages, see Status and Error Messages on page 309.
•
Reports and analysis, see Search and Navigation in Online and Test Mode on
page 310.
•
Project documentation, see Project Documentation on page 314.
3BSE040935-511
289
Online Editors
Section 4 Online Functions
Online Editors
From the Project Explorer in online mode, you have access to editors similar to
those in offline mode, such as the application editor, diagram editor, program editor,
hardware configuration editor and function block editor. By using the online editors
the code currently running in the controller(s) can be inspected. Variable values and
parameters can be changed.
You can open one or several new online editor windows from the Project Explorer
by double-clicking on the Program Organization Unit (POU, see Application Types
and Instances on page 30) you want to view. You can also select the POU,
right click, and select Online Editor (or CMD Editor).
Figure 113. Part of Diagram editor in online mode
290
3BSE040935-511
Section 4 Online Functions
Online Editors
In online mode there are fewer menu entries in the menu bar than in the offline
editor. Edit and Insert are not available in online mode. The options available in
online menus are also somewhat different from those in offline mode. Columns in
the editor that are dimmed are not accessible.
An online editor window consists of a title row, menu bar, tool bar, and a status bar
at the bottom. The window is split into three panes, as follows.
•
In the upper declaration pane the variables and parameters of the POU are
displayed in forms that resemble Excel data sheets. Each sheet, with its tab, has
a unique appearance with respect to the number of columns and their names.
Select a tab to see its sheet, available columns and their names. See also Online
Change of Variable Values in the online help.
•
The middle code pane displays the various code blocks in the POU.
•
The lower description pane displays descriptions of the types and POUs.
It is possible for the user to enter editor settings in the Setup Editor dialog, using the
Tools > Setup menu.
From the online editor window you can activate the POU editor window using the
Tools > Edit Type menu or the Edit Type button
.
You can activate an online window for the POU parent via the Tools > View Parent
menu or the View Parent button
.
See the Control Builder online help for more information about the Setup Editor
dialog, Edit Type and View Parent.
To access filter select a column in the grid and select Tools > Filter or Filter button
.
From the 'Filter' dialog one can decide which rows to display or hide by selecting or
deselecting criteria items. The Criteria items can also be text filtered. An icon in the
column header informs shows an active filter on that column.
Alphabetical sorting of the column is possible by selecting Tools > Sort A to Z or
Sort Z to A, or by clicking the Sort A to Z /Sort Z to A button in toolbar
.
If column is not selected, Sort A to Z and Sort Z to A are disabled.
In offline Editor, when sorting the parameter column, a warning is presented which
informs that the parameter order might be changed.
3BSE040935-511
291
Diagram Editor in Test Mode and Online Mode
Section 4 Online Functions
Diagram Editor in Test Mode and Online Mode
In the diagram editor, in Test mode and Online mode, the current values are
displayed in labels. Double-click on label, the Set Value dialog box opens (See
Figure 114).
Figure 114. Set Value dialog
If the data type is bool, right click the displayed value (true or false) and set On or
Off (to toggle the value).
For graphical connections of structured data type, the online value label is not
shown. However, if one of the components is marked with the displayvalue attribute
in the data type editor (see Figure 115), a label is shown in the diagram editor.
Figure 115. Component marked as displayvalue
292
3BSE040935-511
Section 4 Online Functions
Diagram Editor in Test Mode and Online Mode
Figure 116. Graphical connections of structured data type
For example, in Figure 116, both are graphical connections of structured data type
but only the lower connection has a component marked as displayvalue.
The displayvalue attribute can be assigned to only one component in a structured
data type.
It is also possible to assign this attribute through a combination of other attributes
(for example, coldretain displayvalue, nosort retain displayvalue, and so on). In
this case also, only one component can have this type of attribute (with
displayvalue).
To view components in multilevel structures, the attribute displayvalue has to be set
on every level, that is. the attribute has to be set not only for the simple data type to
be viewed, but also for the sub-component the simple datat ype to be viewed
belongs to, and so on.
To view or change the components of a structured graphical connection, right-click
on the graphical connection and select Show Online Values from the context menu.
The Online Values dialog box opens (see Figure 117).
3BSE040935-511
293
Dynamic Display of I/O Channels and Forcing
Section 4 Online Functions
Figure 117. Online Values dialog box
It is possible to open several Online Value dialog boxes at the same time.
Tooltips are also available for online labels. This is useful if the online value is
large so that it cannot be displayed as a label along with the graphical connection,
or a truncated string value is displayed. Move the cursor over the graphical
connection or the truncated online value label (if it is displayed) to view the
tooltip that shows the whole value.
Dynamic Display of I/O Channels and Forcing
In test mode and online mode, you can use the hardware configuration editor for
dynamic online display of I/O channel values and forcing.
Forcing of I/O channels is performed in the hardware configuration editor under the
Status tab, or in the POU editor in online mode. All I/O channels that can be
connected to a variable in an application can also be forced in online mode, except
for channels such as UnitStatus on each I/O unit and AllUnitStatus on the current
controller (see Supervising Unit Status on page 296).
Normally, only channels with variable connections to application programs can be
forced. However, if no variable is connected, you have to change the parameter
Copy unconnected channels under the Settings tab for the current controller to
obtain a status update. The I/O channels you can copy are None, Inputs or Outputs,
or both the Inputs and Outputs.
294
3BSE040935-511
Section 4 Online Functions
Dynamic Display of I/O Channels and Forcing
When selected, the unconnected I/O channels are copied once a second so their
status is available in the Status tab like normally connected I/O channels.
Copy unconnected channels is for test purposes only and should never be selected
for a controller in a running plant, since it will increase CPU load.
Application programs requiring information about forcing and forced values, can
use the I/O data types when connecting variables to I/O channels. In this way, you
can use the Forced component (which indicates if the I/O channel is forced) and the
IOValue component (contains the value of the I/O channel) of the I/O data type.
When a channel is forced, all copying between the I/O value and the application
value stops. The forced value is different for inputs and outputs. For inputs, forcing
changes the variable value sent to the application. For outputs, forcing changes the
physical I/O channel value. In this way, the application can see both the Variable
(application) value and the Channel (I/O) value.
Forcing can be activated or deactivated using a check box in the Forced column for
the channel. The background of the forced Variable Value changes to yellow to
indicate forcing. To change the channel value, type in a new value for the Variable
Value. This value overrides the values for the channel.
Figure 118. I/O channel with the variable Photo_Cell forced to true.
More information is given in Control Builder the online help. Search the Index
for “I/O”.
3BSE040935-511
295
Scaling Analog Signals
Section 4 Online Functions
Scaling Analog Signals
It is possible to temporarily change the scaling values for analog signals in online
mode.
If scaling values for an analog signal are changed in online mode, the change will
be lost if you enter offline mode, make configuration changes and then perform a
download.
Supervising Unit Status
Each hardware unit has a UnitStatus channel that describes the current error status
of the unit. Both dynamic and static warnings and errors are collected in this
channel.
The data type, for the variable connected to the UnitStatus channel of the hardware
unit, can be either of dint data type or of HwStatus data type. If a variable of dint
data type is connected to the UnitStatus channel, the possible unit status values are:
0 (OK), 1 (Error), or 2 (Warning).
The HwStatus data type contains the same information as shown under the
Unit Status tab of the hardware configuration editor, that is, unit status information
and status message acknowledgement functions. These components will be
available by using the HwStatus data type as a variable connection to the UnitStatus
channel.
In the example below, see Figure 119, the DO814UnitStatus variable of dint data
type is connected to UnitStatus of DO814 (unit status is 0=OK!). The
DO810UnitStatus variable of HWStatus type is connected to UnitStatus of DI810
(HWState is 1, that is, unit status is Error).
296
3BSE040935-511
Section 4 Online Functions
Find Out What is Wrong by Using HWStatus
Figure 119. The UnitStatus connection gives access to the status of individual
hardware units.
Find Out What is Wrong by Using HWStatus
You cannot find out exactly what is wrong by using the simple data type dint, only
that something is wrong. Table 10 on page 105 shows that, in addition to using the
dint type, you can also use the data type HWStatus. By using the structured data type
HWStatus, instead of the simple data type dint, you may also find out what is wrong
with the unit.
Among other things, the structured data type HWStatus contains the component
ErrorsAndWarnings, which contains a bit pattern, representing the different errors
that may occur in the unit. Each bit in the word represents a unique error.
Figure 120 illustrate how the component ErrorsAndWarnings in HWStatus can be
accessed.
For example, the word takes the value of 16#80020000 (hexadecimal notation), if
the CPU battery suffers from low voltage.
For more information on error codes, see Control Builder online help.
By combining AC800MStatus.ErrorsAndWarnings with the bit pattern 800200001
and using the AND operator, it is possible to trigger an error (or warning) from the
hardware unit, together with the specific error code for “low CPU battery voltage”.
The result is assigned to the boolean variable BatteryLow. The ST code for this
condition is as follows:
(*Set the Boolean variable "BatteryLow" when AC 800M has low
battery*)
1.
3BSE040935-511
Typed in ST editor in hexadecimal notation as 16#80020000.
297
AllUnitStatus
Section 4 Online Functions
BatteryLow := (AC800MStatus.ErrorsAndWarnings AND
16#80020000) <>0;
In online mode it will be displayed as below in Figure 120.
I
Figure 120. The variable AC800MStatus (of HWStatus type) has been used to
access the component ErrorsAndWarnings.
AllUnitStatus
Each controller hardware object has one channel called AllUnitStatus, containing
the summarized status of all hardware units added to the controller. The most
serious unit status (dint) is forwarded up to the controller object, that is, the unit
status of the controller is error if one unit has an error, and one has a warning.
AllUnitStatus can be used in the same way as UnitStatus, that is, the variable
connected to AllUnitStatus can be of dint data type or of HWStatus data type.
Figure 121. The AllUnitStatus connection gives access to the status of all units for a
controller.
The variable connected to AllUnitStatus can be used in the application program, to
write different conditions depending on status value (see UnitStatus Example
Figure 120).
Binary Channels
Access All Inputs and All Outputs
Some units return a binary value, as a number of inputs divided on 8 or 16 channels.
Typically, this applies to different types of sensors. These values can be collected
via an overall channel, namely “All input”’. This means that, instead of reading all
298
3BSE040935-511
Section 4 Online Functions
Supervising Communication Variable Status
variable values from each channel, one variable can be connected to the channel
“All inputs” (IW0, see Table 10 on page 105), provided the variable is of dword data
type. This technique can also be used for digital outputs. However, for digital output
units, you must choose either to connect all individual channels or connect one
variable to the channel “All outputs” (QW0, see Table 10 on page 105). You cannot
use both methods simultaneously.
ISP and OSP values are not set for variables connected to All Inputs/All Outputs!
ISP/OSP (Input/Output Set as Predetermined) will not work when using the
channel "All Inputs" or "All Outputs". I/O values will be lost in an error situation.
Check Channel Status
There are two ways to check the channel status for an I/O unit. You can either use
the structured data type BoolIO, that is, read the component Status via BoolIO, or
you can connect a variable of type dword to the “Channel status” (IW0, see Table 10
on page 105).
The component Status in BoolIO only gives you the status for that connected
channel, whereas a variable of type dword that is connected to channel “Channel
status” will read the status for all channels, given with bit 0 equivalent to channel 1,
bit 1 equivalent to channel 2, etc. However, a variable of type BoolIO that is
connected to each channel contains more information, since the component Status is
a 32 bit dword, whereas AllChannel is a 16 bit dword. Connecting each channel to
BoolIO gives more information, but also more variables to connect.
Connecting a variable to AllChannel will give you less information, but only one
variable to connect.
Do not try to connect the component Status (inside BoolIO) directly to the
channel. You must connect BoolIO. For information about connecting structured
data types to IO channels, see I/O Data Types on page 104 and the variable
example given in Figure 33 on page 104.
Supervising Communication Variable Status
There are two methods to supervise the status of communication variables:
•
•
3BSE040935-511
Using the :status notation
Using the GetCVStatus function
299
Supervising Communication Variable Using :Status Notation
Section 4 Online Functions
Supervising Communication Variable Using :Status Notation
For communication variables, the status can be supervised using the :status
notation.
For example:
dword1:=CVMain:status;
In this example, the :status notation is used to obtain the status of the
communication variable, CVMain. The status appears as dword.
See also, Understanding the Complete Status Code on page 302.
Supervising Communication Variable Using GetCVStatus
For communication variables , the status can be supervised using the function,
GetCVStatus, which is available in the System library. But, the :status method has
better performance than the GetCVStatus function.
300
3BSE040935-511
Section 4 Online Functions
Supervising Communication Variable Using GetCVStatus
The GetCVStatus function accepts the communication variable as input, and
provides the complete status and extracted statuses through different output
parameters. These output parameters for extracted statuses can be connected to
variables to control the logic.
The available parameters for extracting the status are:
•
Quality – (dword) – The OPC quality of communication.
For GOOD, this parameter returns 16#C0.
For BAD, this parameter returns 0.
•
ManualAckRequired – (bool) – Whether manual acknowledgment is required
for the communication variable to restart the communication after failure.
This paramter returns true if manual acknowledgment is required, else it
returns false.
•
ServerIsSimulated – (bool) – Whether the controller that runs the server
application is either hardware simulated or Soft Controller.
This paramter returns true if the controller that runs the server application is
either hardware simulated controller or Soft Controller. Otherwise, it returns
false.
3BSE040935-511
301
Understanding the Complete Status Code
Section 4 Online Functions
Understanding the Complete Status Code
The displayed complete status code of a communication variable depends on:
•
The error (if any)
•
The discrete values for the following factors:
– Quality of communication
– Server is simulated or not
– Manual acknowledgment is required or not, after error is generated
To understand the complete status code, first convert it from hexadecimal to binary
(32 bits).
Table 23 describes the bit-wise description of the used bits in the binary status of
communication variable. Bit 0 is the least significant bit.
Table 23. Bit-wise description of communication variable status in binary code
Bit
Bit 5
Description
Not initialized. This bit is set in the following cases:
•
Initial download of application
•
Cold download of application
•
Restart of application after power-fail
•
Restart of application after short-reset
This is reset when:
•
First frame is received
•
Out variable is downloaded for internal IAC
Bit 6 and Bit 7
Quality of OPC (11 - GOOD, 00 - BAD)
Bit 8
The server is hardware simulated or it is a Soft Controller
Bit 12
Manual acknowledgment is required to restart
communication after error generation.
Bits that represent communication errors(1)
302
3BSE040935-511
Section 4 Online Functions
Understanding the Complete Status Code
Table 23. Bit-wise description of communication variable status in binary code
Bit
Description
Bit 16
The values are not communicated in time, but no timeout
have occurred. The OPC quality bits are still good (11).
This is used for external communication using IAC.
Bit 17
The values are not communicated in time, and a timeout
has occurred. The OPC quality bits are bad (00). This is
used for external communication using IAC.
Both Bit 16 and
Bit 17 are set
The IP address has not been resolved for the
communication variable.
Bit 18
The type does not match the type of the corresponding
out variable. This is used for both internal and external
communication using IAC.
Both Bit 16 and
Bit 18 are set
The corresponding out-variable is declared, but not
downloaded yet. This status is only relavent for internal
IAC and occurs only when the out variable has existed
and then has been removed.
Both Bit 17 and
Bit 18 are set
The communication is not configured.
Bit 16, Bit 17, and The task where the corresponding out variable is
Bit 18 are set
connected is not running. This is only relevant for internal
IAC.
Bit 19
General error code
Bits that represent protocol handling errors(1)
Bit 27
Wrong message type in the response message.
Bit 25 and Bit 27
are set
The out-variable cannot be found.
Bit 24, Bit 25, and The Initiate request was unsuccessful.
Bit 27 are set
Bit 26 and Bit 27
are set
3BSE040935-511
The protocol version between client and server does not
match.
303
Status Indications
Section 4 Online Functions
Table 23. Bit-wise description of communication variable status in binary code
Bit
Description
Bit 24, Bit 26, and The heap is full.
Bit 27 are set
Bit 25, Bit 26, and Permanent MMS error
Bit 27 are set
Bits 24 to 31are
set
Unspecified error
(1) The status represented by a single bit is different from the status when this bit is set as a
combination with other bits, in the same error category.
Status Indications
Status indications are not displayed in Test mode.
In the Project Explorer, dynamic status indications for the hardware units and tasks
are displayed as shown below.
Error
Warning
OK
Figure 122. Status indications of hardware and tasks in Project Explorer.
304
3BSE040935-511
Section 4 Online Functions
Status Indications
•
OK
No errors or warnings.
•
Error!
Hardware objects are marked with a red triangle icon if an error is detected in
the hardware, for example, if a hardware unit is missing.
The task is marked with a red triangle when a serious error has occurred, for
example, when a task is aborted as a consequence of too long execution time.
The error is described in the Remark field of the Task Properties dialog. See
Task Abortion on page 146 for more information.
•
Warning!
Hardware objects are marked with a warning icon if there is an overflow or
underflow at an analog channel, if the forcing of a channel is detected, or if an
unacknowledged fault disappears. The task icon is marked with a warning icon
if the task is not used (“Not in use”), in the case of overload, or when the task is
in debug mode and the task is halted, that is, non-cyclic mode (see Debug
Mode in the Compact 800 Engineering Compact Control Builder AC 800M
Getting Started(3BSE041584*) manual. The warning is described in the
Remark field of the Task Properties dialog. See Task Control on page 129 for
more information about tasks.
An error has higher priority than a warning, for example, an error is indicated if an
error occurs at the same time as channel forcing is detected.
A collapsed object folder shows status indications for all underlying objects, that is,
status indication is always forwarded up to the controller icon. It is not until an
object folder is fully expanded that you can be sure that status indications are shown
next to the unit they actually belong to. If, for example, a single task has a warning,
both its task folder icon and its controller icon are marked with a warning. Status
indications are displayed up to the controller level only.
3BSE040935-511
305
Acknowledge Errors and Warnings
Section 4 Online Functions
Acknowledge Errors and Warnings
Warnings concerning tasks do not have to be acknowledged.
All hardware unit errors and warnings have to be acknowledged by the user. Use the
status tab in the hardware editor to obtain information about the error or the
warning.
There is a possibility to acknowledge errors and warnings for all hardware
subobjects by right click the main hardware object (Hardware AC 800M in
Figure 122) and select Clear Latched Unit Status.
See Control Builder online help for more information about dynamic online display
of I/O channel values and forcing and how to acknowledge errors and warnings.
Tasks
Use the Task Overview dialog to display task information in online mode.
For each task, you can make changes to the Requested Interval Time, Offset,
Priority and Latency using the Task Properties dialog. The maximum encountered
intervals and the maximum encountered execution time can be reset.
It is not possible to change the task priority to/from 0 (Time-Critical priority) in
online mode.
Debug mode can be used, but for debugging only. Functions based on the real-time
clock (PID controllers, timers etc.) do not work properly when debug mode is used
(also, see Debug Mode in the Compact 800 Engineering Compact Control Builder
AC 800M Getting Started (3BSE041584*) manual.
If debug mode is used in a running plant, task execution will be stopped.
You can also select Always update output signals last in execution, or select
Always update output signals first in next execution.
For further basic information about tasks, see Task Control on page 129. For
Latency information, see Latency Supervision on page 144. See also Control
Builder online help for how to carry out task changes.
306
3BSE040935-511
Section 4 Online Functions
Interaction Windows
Interaction Windows
An interaction window contains the graphics of a control module and is only
accessible in online mode. An interaction window may contain both supervisory
features, such as signal status, and interactive features, such as push buttons. The
window can be accessed from:
•
A control module in the Project Explorer.
•
A function block in the Project Explorer. This is, however, only available under
the condition that at least one control module exists and is connected to the
selected function block type. By default, the first control module in the list will
appear in the interaction window (this can be changed in offline-mode by rightclicking on the type name in the Project Explorer and selecting Properties>
Set Interaction Window Control Module).
•
An online program editor containing a control module.
•
An online program editor containing a function block (compare with item 2
above).
•
From interaction window objects in a control module.
3BSE040935-511
307
Interaction Windows
Section 4 Online Functions
Figure 123. The left window is an interaction window activated from an application
window interaction object. The right window (supervision only) appears after
clicking the info interaction window button.
308
3BSE040935-511
Section 4 Online Functions
Status and Error Messages
Status and Error Messages
There are function block types, control module types and functions that contain a
parameter named Status. The Status parameter shows, in online mode and in test
mode, a status code that correspond to a status message. The status code changes
depending on the current state of the function block, control module or function.
There are function-specific status codes that are used within its range of application
only, for example, communication-specific status codes. Some status codes are
general and are used for most function blocks and control modules, and for
functions with a Status parameter.
The different status messages are described in Control Builder online help.
Function block types and control module types with a Status parameter also have an
Error parameter. The Error parameter is set to true if the Status parameter < 0, for
example, if Status is -35 (Maximum size limit has been exceeded). Status codes >1
is used as warnings and do not set the Error parameter.
Figure 124. A function block with Status parameter and Error parameter (operation
successful=1).
The Error and Status parameters can be used in the application program, for
example, a condition can be written in the program for a specific status code.
3BSE040935-511
309
Search and Navigation in Online and Test Mode
Section 4 Online Functions
Search and Navigation in Online and Test Mode
The Search and Navigation tool can be used to conduct simple searches and iterative
searches when the project is in Online mode or Test mode.
This functionality makes it possible to search for input/output of a certain signal as a
result of a single search, irrespective of name changes at parameter connections.
This means all information concerning reading and writing from the whole
Application/Controller(s) about a signal is found in the search.
The appearance of the Search and Navigation dialog in the Online mode and Test
mode depends on the setting of the following options in the Search and Navigation
Settings dialog box:
•
•
Allow editing of the Search Fields in Online/Test Mode
Iterative searches in Online/Test Mode
By default, the first option above is not set and the second option is set. See Search
and Navigation Settings on page 168.
Iterative Search
In Online mode or Test mode, if the option Iterative searches in Online/Test Mode
is set (the checkbox is checked) in the Search and Navigation Settings dialog, the
iterative search hits are directly presented in one pane – the References pane.
See Figure 125.
310
3BSE040935-511
Section 4 Online Functions
Search and Navigation in Online and Test Mode
Figure 125. Iterative search results for the variable AC800MStatus in Online mode
In Online mode or Test mode, if the option Iterative searches in Online/Test Mode
is not set (the checkbox is not checked) in the Search and Navigation Settings
dialog, the search hits are presented in two panes—the Symbol and Definition pane,
and the References pane. In this case, right click the symbol and select Iterative
Search to start its iterative search. See Figure 126.
It is also possible to search for another item in the window and obtain the new
results.
3BSE040935-511
311
Search and Navigation in Online and Test Mode
Section 4 Online Functions
Figure 126. Search results for the variable AC800MStatus in Online mode, with the
option for Iterative Search
After the Iterative Search option is selected (see Figure 126), the search results for
the selected symbol are replaced by new search results in the References pane,
which shows the header as References (iterative search).
General Considerations for Search in Online/Test Mode
The tree view in the References pane shows where the signal is read or written.
It is possible to navigate from the Search and Navigation dialog to the references of
a found symbol by double clicking a reference. Then a suitable editor is displayed
and the symbol is highlighted in the editor.
312
3BSE040935-511
Section 4 Online Functions
Search and Navigation in Online and Test Mode
The references are followed both upwards towards its first definition in a parent
node, and downwards to the leaves of the project structure, in order to cover all
usage. Every time a reference is followed, there is a new query to the search
database. By means of those user hidden repetitive queries, all relevant information
is collected from a single search.
There are following differences in online/test mode (compared to offline mode):
•
Search In: drop-downs can only contain search paths for objects that you can
see in online/test mode, for example, libraries cannot be searched.
•
References only show information concerning where the symbol is used, as can
be seen in online and test mode.The references tree (i.e. the tree presented in
the references pane of the Search and Navigation dialog) presents instance
paths in online mode and test mode.
•
It is only possible to navigate to online editors and to the Project Constant
dialog. The online editors that can be navigated to are the following:
– POU editor
– Connection editor
– Control Module Diagram editor
– Hardware configuration editor
– Access variables editor
– Diagram editor
In online mode, it is also possible to navigate from the Search and Navigation
function to the corresponding object in the Project Explorer.
3BSE040935-511
313
Project Documentation
Section 4 Online Functions
Project Documentation
Project Documentation in online mode is used to document (part of) the application
tree in online or test mode. You can select any application object, set the “tree
depth” in relation to the selected object, to document part of the tree only. You can
also use filter conditions for a more specific search. Unlike the offline mode, the
values of variables, parameters, etc. are included. For example, it is possible to filter
out all coldretain variables and parameters in an application. The output is a
Microsoft Word file, hence Microsoft Office must be installed.
All project documentation will be connected to a standard template.
1.
Enter online or test mode and select an application object in Project Explorer.
2.
Select File > Documentation Online... to open the Project Documentation
dialog.
Figure 127. The Documentation Online dialog.
314
3BSE040935-511
Section 4 Online Functions
3.
Project Documentation
See Control Builder online help for information about dialog settings and
selections.
See Project Documentation on page 202 for information about Project
Documentation in offline mode.
3BSE040935-511
315
Project Documentation
316
Section 4 Online Functions
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
This section provides important information for maintenance and trouble-shooting
Compact Control Builder products. It mainly advises you on how to maintain your
system, and how to collect information from a malfunctioning control system. The
latter information is particularly valuable if your supplier’s service department is to
be involved.
Introduction
Software maintenance and trouble-shooting includes the following activities:
•
Backup and Restore on page 317 gives a short overview of backup and restore.
•
Files for Separate Backup on page 320 describes how to configure handling
and logging of system alarms and events, using the Error Handler.
•
Trouble-Shooting on page 325 lists a number of error symptoms, and suggest
actions upon these.
•
Error Reports on page 360 describes how to write a complete error report, so
that the support engineers get a complete picture of an error situation.
Backup and Restore
Introduction
This function provides a backup of your project, and enables you to move a project
from one Control Builder station to another with the restore function. You can
choose to backup a complete project or select parts of the project.
3BSE040935-511
317
Backup
Section 5 Maintenance and Trouble-Shooting
Backup
Compact Control Builder suggest the current project in Project Explorer for backup,
or you can browse via a button to another project on your hard disk. Furthermore,
Control Builder suggests a destination folder, named Project Backup which will be
created next to the Project folder.
To Backup a project, select (in Project Explorer) Tools>Maintenance>Project
Backup. A Project Backup dialog window will open, (Figure 128).
Figure 128. Backup menu in Project Explorer.
318
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Restore
Complete Backup
This option includes all files that are needed to restore the project on another
computer.
Typical Backup
A Typical backup of a project includes all source code files that are needed to
restore the project on another computer. However, Retain, Cold Retain or Domain
files will not be included with this option.
Custom Backup
Advanced users may want to choose explicitly which files to back up. This option
provides a list of all files included in the project.
Restore
The restore function is used to install a backup, for example, after a disk crash, or
when moving a project to another system. You may decide to make a Complete,
Typical or Custom restore.
When you are restoring a complete project, all the project-related files are copied
from the backup folder to the project folder.
Files for Separate Backup
There are some settings files that are stored locally. These need to be backed up
separately:
•
OPC Server Configuration and System Setup Files
The OPC Server stores configuration files (*.cfg) and system setup files
(*.sys) on local disc. These files are stored in the OPC server working
directory and need to be manually copied to safe media on a regular basis. See
the AC 800M OPC Server (3BSE035983*) manual for more information.
•
Control Builder Settings File
Each Control Builder client saves its settings in the file systemsetup.sys.
This file is saved on local disk, in the Control Builder working directory, and
has to be manually backed up to safe media on a regular basis.
3BSE040935-511
319
Controller Configuration
Section 5 Maintenance and Trouble-Shooting
Controller Configuration
The Error Handler is used to configure controller behavior on system alarms and
events of different severities, and how different errors are logged.
Error Handler settings are made for each controller, in the Controller Settings
dialog. There are certain settings that cannot be changed (they are dimmed in the
dialog). You can add additional actions, but you cannot change the original settings.
•
Controller Settings in Controllers on page 320 describes how to configure the
Error Handler in a controller.
Errors can be reported from the code using the ErrorHandler function block type
or the ErrorHandlerM control module type. Using these types, errors identified by
the code can be handled in the same way as other errors. For more information on
how to configure the ErrorHandler(M) types, see corresponding online help.
The ErrorHandler(M) types should be used with care, since they can be used to
reset the controller.
Controller Settings in Controllers
Figure 129 shows the Controller Settings dialog for a AC 800M controller. It is
displayed by right-clicking the controller in Project Explorer and selecting
Properties > Controller Settings.
320
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Controller Settings in Controllers
Figure 129. Controller Settings dialog for an AC 800M controller.
If load balancing is enabled, overrun and latency supervision is automatically
disabled, see Overrun and Latency on page 142.
The default setting for a controller is that load balancing is enabled and overrun and
latency supervision disabled. If you disable load balancing overrun and latency
supervision is automatically enabled.
Fatal overrun settings are used only if overrun and latency supervision is enabled
(this part will be dimmed if load balancing is enabled, see Figure 129).
The Fatal Overrun part of the dialog lets you set how many overruns (missed scans)
that are allowed before a fatal error is considered to have occurred. The Reaction
setting is used to select which action the controller should take when a fatal overrun
3BSE040935-511
321
Controller Settings in Controllers
Section 5 Maintenance and Trouble-Shooting
error occurs. The options are Nothing, Stop Application, and Reset Controller (The
default option is Nothing). The default setting for the Limit is 10 interval cycles.
It is important to avoid configuring the error handler in such a way that a fatal
overrun error has two corresponding reactions, one that is set in the Fatal Overrun
part of the dialog (for example, Stop Application) and one that is set in the Error
Reaction dialog (for example, Controller Shutdown for the corresponding
severity). Note that severity Fatal and Critical always lead to a controller
shutdown.
If settings are inconsistent, you will receive a warning when trying to save the
new settings.
For a controller, the Error Reaction part lets the user set the following, see Table 24.
Table 24. Error Reaction. This part of the dialog is used to set controller actions at system alarms of
different severity.
Severity
Log
Event
Controller Shutdown
1 Low
Configurable for all
Configurable for all
Configurable for all
2 Medium
Always for system
diagnostics and
execution
Configurable for I/O
Configurable for all
Configurable for all
3 High
Always for system
diagnostics and
execution
Configurable for I/O
Always for system
diagnostics and
execution
Configurable for I/O
Configurable for all
4 Critical
Always
Always
Always
5 Fatal
Always
Always
Always
The above table shows controller reactions (fixed and configurable) when alarms of
different severities are received by the Error Handler in a controller.
322
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Controller Settings in Controllers
There are three tabs in the Error Reaction part of the dialog:
•
The System Diagnostics tab contains settings for system alarms generated by
the System Diagnostics module, for example, CEX module errors, protocol
handler errors.
•
The Execution tab contains settings for system alarms generated during
execution of IEC-61131 code, for example, latency errors, CRC check failures.
•
The I/O tab contains settings for I/O module errors.
The following definitions have been used for the severity of system errors when
designing error handling for different modules:
•
1 Low
Minor, of diagnostic or informative sort. Does not affect system integrity or the
functionality of the reporting module.
•
2 Medium
An error, such as I/O channel failure, communication failed, or similar, has
occurred. Does not affect system integrity, but affects functionality in the
reporting module.
•
3 High
Severe error, but not critical, for example I/O module failure. May affect
system integrity. Functionality in the reporting module is affected. Redundancy
may maintain the system integrity
•
4 Critical
A severe error has occurred, for example, a task has stalled, ModuleBus stalled,
I/O cluster down. Will affect system integrity, since the reporting module has
failed. Redundancy may maintain the safety of the system.
•
5 Fatal
Systematic software errors have been found. The whole reporting subsystem
has failed. Redundancy will not maintain the system integrity. This severity is
only used when there is no possibility to safely continue using a backup PM.
3BSE040935-511
323
Error Handler Log Entries
Section 5 Maintenance and Trouble-Shooting
Error Handler Log Entries
If an error of a certain severity is configured to be logged, it will generate a
Controller System log (see Controller System Log on page 336) entry with the
following general structure.
E yyyy-mm-dd hh:mm:ss:ms ErrorHandler PM: Error descr.(x,y,R)
•
Such an entry should be read according to the below table.
Table 25. How to read a log entry generated by the Error Handler.
Part
Description
E
Error
yyyy-mm-dd
Date
hh:mm:ss:ms
Time when error was time
stamped
ErrorHandler PM:
Error detected by
Allowed Value(s)
ErrorHandler PM:
=Processor Module
Error descr.
A text describing the error
x=error type
1 (System Diagnostics)
2 (Execution),
3 (I/O)
y=severity
1
2
3
4
5
ERS=action type
E (Event)
R (Reset)
S (System Alarm)
(x,y,ERS)
324
(Low)
(Medium)
(High)
(Critical)
(Fatal)
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Trouble-Shooting
The Online upgrade is not allowed when the changes are downloaded from
another engineering station.
During Online Upgrade, the valid signal of the control modules MMSReadxxxM
might drop just after the Online Upgrade switch, if there are other communication
ongoing (for example serial communication). For safe P2P communication it is
recommended to use MMSDefHI/MMSReadHI control modules.
This occurs while using the following control modules:
MMSDef128BoolM/MMSRead128BoolM
MMSDef64BoolM/MMSRead64BoolM
MMSDef16BoolM/MMSRead16BoolM
MMSDef2DintM/MMSRead2DintM
MMSDef2DwordM/MMSRead2DwordM
MMSDef2RealM/MMSRead2RealM
•
Trouble-Shooting
General
When a control system error occurs, it is important to investigate it as soon as
possible. In doing this, the possibility of finding and eliminating the problem will be
substantially increased. The reasons are:
•
The personnel involved will not have forgotten what happened.
•
The application software involved will not have been changed.
•
The systems involved will not have been changed (location, setup etc.).
•
You may need a work-around quickly, to be able to continue your work.
3BSE040935-511
325
Log Files
Section 5 Maintenance and Trouble-Shooting
•
Some errors only occur under very special circumstances and/or in special
hardware/software configurations. The person who reports the problem may
have the only installation/configuration where we know it could occur.
A well-described error, with all vital information included, will always increase
the probability of correcting the error quickly and effectively. Error Reports on
page 360 provides some hints when writing an error report.
The task of trouble-shooting is usually very difficult, and requires a great deal of
intuition and ability to draw conclusions from known facts. This subsection aims to
provide some guidelines on solving problems.
Here are some basic troubleshooting questions which should first be answered.
•
What is the problem?
•
Is it a known problem? Check the available information (for example, Release
Notes and Product Bulletins) and discuss it with colleagues.
•
Has the system worked previously (with the same hardware)? If so, the
problem may have occurred due to poor installation or due to setup problems.
•
Has anything been modified recently? The problem is often to be found in
modifications. If possible, revert to the previous state, and test.
•
Can the problem be linked to any special event?
•
Is it possible to reproduce the problem?
Log Files
The Industrial IT products described in this subsection have built-in logging
routines that continuously write to log files. Log files will contain important
information whenever a failure occurs during a programming session, or when a
controller is running. These files and the crash files (see section Crash Dumps for
Analysis and Fault-Localization on page 341) are very useful for troubleshooting
and contain crucial information for analyzing malfunctions.
System Log File
The system log is created the first time Control Builder is started (or if there is no
log file), and is used to store general information concerning Control Builder.
Examples of information logged are start/stop of Control Builder and changes in the
326
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Log Files
setup of Control Builder via the Tools menu. The System log can be read via the
menu entry Tools > Maintenance > Analysis > System Log. Figure 130 shows an
example of the system log.
Figure 130. An example of the system log
The path and file name of the System log are given in Table 26.
Table 26. The System log file path.
Denomination
Path/Note
Control Builder Path / File name
System Log
C:\ABB Industrial IT Data\Engineer IT Data(1)\
Compact Control Builder AC 800M\LogFiles\System.log
Note
Only one version of this file exists.
(1) The default working directory is shown.
Session Log Files
At start-up, Control Builder, OPC Server for AC 800M, MMS Server for AC 800M,
SoftController, automatically creates a session log file on the hard disk. These files
contain information generated during one session, that is, from the time the product
is started, until it is stopped. New files will be created upon each new start-up.
At start-up, information about hardware and software versions, and later,
information on system events, such as mode changes (Offline to Online, or vice
versa) and error print-outs, will be logged in the session log. Session logs are
continuously updated in a running system, and whenever a problem occurs it is a
3BSE040935-511
327
Log Files
Section 5 Maintenance and Trouble-Shooting
good idea to look at the logs to see if there are any printouts. It is possible to read
log files for the current session via the menus.
Session logs are saved from the previous nine sessions. It is important to save a
file containing information about a problem, with a new name, before it is
overwritten.
Ten successive start-ups will generate the following session log files; Session.log
(from last start-up), Session.log _bak1 (next to last), Session.log _bak2, etc to
Session.log _bak9 (the first start-up or oldest saved start-up). This means that when
you start-up the system a eleventh time Session.log _bak9 will be overwritten and
the previous Session.log will be renamed as Session.log _bak1 and a new
Session.log will be created.
You will lose the oldest saved file because all the files are pushed one step after
each start-up. This means that (_bak8) is pushed to (_bak9), (_bak7) to (_bak8)
etc and Session.log to (_bak1).
328
•
Session.LOG
•
Session.LOG_bak1
•
Session.LOG_bakn.......
•
Session.LOG_bak9
•
Session.LOG_bak9
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Log Files
The paths and file names of the session logs are given in Table 27.
Table 27. Session log file paths.
Denomination
Control
Builder
session log
Path/Note
Path / File name
C:\ABB Industrial IT Data\Engineer IT Data(1)\
Compact Control Builder AC 800M\LogFiles\Session.log
Note
Session log files stored from the last 9 sessions:
Session.log
Session.log_bak1, Session.log_bak2, Session.log_bakn....
Session.log_bak9
OPC Server
session log
Path / File name
C:\ABB Industrial IT Data\Control IT Data(1)\OPC Server for AC 800M\
LogFiles\Session.log
Note
Session log files are stored from the last 9 sessions:
Session.log
Session.log_bak1, Session.log_bak2, Session.log_bakn....
Session.log_bak9
3BSE040935-511
329
Log Files
Section 5 Maintenance and Trouble-Shooting
Table 27. Session log file paths. (Continued)
Denomination
MMS Server
session log
Path/Note
Path / File name
C:\ABB Industrial IT Data\Control IT Data(1)\ MMS Server for AC 800M\
Session.log
Note
Session log files are stored from the last 9 sessions:
Session.log
Session.log_bak1, Session.log_bak2, Session.log_bakn....
Session.log_bak9
SoftController Path / File name
session log
C:\ABB Industrial IT Data\Control IT Data(1)\ SoftController \ Session.log
Note
Session log files are stored from the last 9 sessions:
Session.log
Session.log_bak1, Session.log_bak2, Session.log_bakn....
Session.log_bak9
(1) The default working directory is shown.
330
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Log Files
OPC Server (Session.log) Example
The list example shows an extract from an OPC Server session log file and how to
interpret the given data in four separate error occurrences. Important information
has been highlighted with typeface bold.
E = error, AE = Alarm Event, DA = Data Access.
E 2003-11-07 11:11:54.867 On Unit= SubAlarmEvent ConnectionError172.16.0.11 OPC Server (6500) Connection error to AE subscribed
controller
E 2003-11-07 11:12:03.335 On Unit= SubDataAccess ConnectionError172.16.0.11 OPC Server (5500) Connection error to DA subscribed
controller
E 2003-11-07 11:12:04.913 Off Unit= SubAlarmEvent ConnectionError172.16.0.11 OPC Server (6500) Connection error to AE subscribed
controller
E 2003-11-07 11:12:27.398 Off Unit= SubDataAccess ConnectionError172.16.0.11 OPC Server (5500) Connection error to DA subscribed
controller
1.
The first event description tells us that the OPC server lost connection (On) to
controller for Alarm and Event subscription (and when this error occurred).
2.
The second event description tells us that the OPC server also lost connection
(On) to controller for Data and Access subscription.
3.
The third event description tells us that the OPC server regained connection
(Off) to controller for Alarm and Event subscription.
4.
The forth event description tells us that the OPC server regained connection
(Off) to controller for Data and Access subscription.
As you can see, letter (E) stands for error and it occurs both when error activates
(On) and when the same error is gone (Off).
3BSE040935-511
331
Log Files
Section 5 Maintenance and Trouble-Shooting
Control Builder Start Log
Control Builder creates a Start Log file for logging the last Offline to Online transfer
(in Test or Online mode). Information, such as warnings and error messages, will be
logged. The Start log is very useful when investigating errors that might occur
during or just after an Offline -> Online transition. Sometimes the Start log will give
a natural explanation of what at first looks like an error (for example, lost Cold
Retain values).
The nine latest Start logs are saved.
It is important to save a file containing information about a problem, with a new
name before it is overwritten. Furthermore, check that the date and time in the
Start log correspond with the time when the problem occurred.
The path and file name of the Control Builder start log, are given in Table 28.
Table 28. The Control Builder start log file path.
Denomination
Path/Note
Control Builder Path / File name
Start log
C:\ABB Industrial IT Data\Engineer IT Data(1)\
Compact Control Builder AC 800M\LogFiles\startlog.txt
Note
The nine latest Start log files are saved:
startlog.txt
startlog.txt_bak1,startlog.txt_bak2, startlog.txt_bakn....
startlog.txt_bak9
(1) The default working directory is shown.
332
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Log Files
Field Bus Parameter Log Files
During compilation and simulation, CI851, CI854 master parameters will be
automatically calculated.
The calculation is performed for all controllers in the project and for all masters
connected to the controllers. The result is sent to text files, which is stored in the
same place as the Control Builder log files. The text files have no backup, and are
replaced at every compilation and simulation.
The path and file name of the Field bus parameter log files, are given in Table 29.
Table 29. The Field bus parameter log files path.
Denomination
CI851
parameter log
file
CI854
parameter log
file
Path/Note
Path / File name
C:\ABB Industrial IT Data\Engineer IT Data(1)\
Compact Control Builder AC 800M\LogFiles\Profibus_DP_Calculation.txt
Path / File name
C:\ABB Industrial IT Data\Engineer IT Data(1)\
Compact Control Builder AC 800M\LogFiles\Profibus_DPV1_Calculation.txt
(1) The default working directory is shown.
3BSE040935-511
333
Log Files
Section 5 Maintenance and Trouble-Shooting
Device Import Wizard Log File
When Device Import wizard is used a log file is created. If any failure during the
import occurs, errors and/or warnings are written to the log file, together with a text
describing the error/warning.
For a successful creation of a hardware definition file the log file contains some
entries: date and time of use, version of wizard and parser component, contents of
the device description file and contents of the generated hardware definition file.
When the file size of a log file reaches 10MB it will be renamed next time the
Device Import Wizard is invoked and a new log file is created. If there are an backup
file at that time, it will be deleted.
Table 30. The Device Import Wizard log file path
Denomination
Device Import
Wizard log file
Path/Note
Path / File name
C:\ABB Industrial IT Data\Engineer IT Data(1)\
Compact Control Builder AC 800M\LogFiles\DIW.log
(1) The default working directory is shown
PROFINET configuration log file
The Control Builder creates a log file PROFINET_Configuration.txt during
download. This log file will have the result of the download compilation for the
current and previous configurations. The log file can store data upto 10 MB and is
stored in the LogFiles directory in Control Builder. The current compilation result is
stored at the end of the log file.
If the log file exceeds the maximum size of 10 MB, then the file is automatically
saved as PROFINET_Configuration1.txt and a new
PROFINET_Configuration.txt is created. A maximum of nine old log files will be
saved before the oldest file gets overwritten. The log file also contains internally
calculated data that are not available in the Control Builder.
334
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Log Files
Table 31. The Device Import Wizard log file path
Denomination
Path/Note
PROFINET
Configuration
log file
Path / File name
C:\ABB Industrial IT Data\Engineer IT Data(1)\
Compact Control Builder AC 800M\LogFiles\PROFINET_Configuration.txt
(1) The default working directory is shown
Control Builder System Information Report
The system information report is a list of hardware, software and setup information
for an engineering station. This information is generated by a menu command and
presented in a text editor.
To generate a new report perform either of these two alternatives.
•
Select menu Help > About Compact Control Builder AC 800M> List all
Information
•
In the Control Builder Setup Wizard, click Show Settings button.
This alternative generates almost the same information as the alternative above,
but fewer Environment variables are printed.
It is important to generate a new file containing information that was valid at the
time the problem occurred.
The path and file name of the Control Builder System information report file are
shown in Table 32.
Table 32. The Control Builder system information report file path.
Denomination
Path/Note
Control Builder Path / File name
System
C:\ABB Industrial IT Data\Engineer IT Data(1)\
information
Compact Control Builder AC 800M\LogFiles\ SystemInformation.txt
report
(1) The default working directory is shown.
3BSE040935-511
335
Log Files
Section 5 Maintenance and Trouble-Shooting
Heap Statistics Log
There is heap statistics log file for SoftController. Every time a message “memory
full” occurs (see Figure 131) in these products, the system software will
automatically generate a heap statistics log file containing information about the
content of the heap1.
If “memory full” occurs in a situation that cannot be explained as normal, then this
file should be included in an error report to your supplier’s service department.
When a system is unable to store more information in the heap, an error message
will be displayed. In most cases (more than 98%), this is due to an attempt to store
too much information in too small a heap. If this occurs for a product running on an
engineering station, increase the heap size for that product, using the Setup Wizard.
Figure 131. The “memory full” message.
The paths and file names of the heap statistics log files are given in Table 33
Table 33. The heap statistics log file path
Denomination
SoftController
heap statistics
log
Path/Note
Path / File name
C:\ABB Industrial IT Data\Control IT Data(1)\SoftController \heapstat.dat
Note
The file is intended to be stored and included in an error report.
Controller System Log
Controllers have a circular log buffer that can hold a certain amount of information,
normally all information that has been generated during the last 5 to 8 start-ups.
1.
336
A product, for example, a soft controller, uses a general memory area to store information. This area is called a
heap. In the engineering station this area does not necessarily reside in the RAM memory.
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Log Files
A lot of the information gathered in a controller log file can be of great assistance,
but a controller file is circular, which means that the last error often disguises more
important previous errors. This means that the original error can be hard to discover.
Therefore, you are advised to first save the log file to a safe location (no risk of
deleting history) and then fault-find your way back. After renaming the first
controller log file, it is safe to fetch as many controller log files as necessary.
The Controller System log is never deleted. Provided that the battery backup is
working properly, the information can be retained during a power failure. This
function makes it possible to restart a faulty system immediately to regain control of
the process, without losing vital information about the error.
You must first save the Controller system log file on a safe location before faultfinding; it is much more difficult to identifying the original error after several
startups.
The recommended way to access the Controller System log information is to fetch it
via Control Builder. Selecting Tools > Maintenance > Remote System… will
show a Remote System dialog, see Figure 132.
Figure 132. The Remote System dialog box.
3BSE040935-511
337
Log Files
Section 5 Maintenance and Trouble-Shooting
Enter the controller identity (the IP address) and click on the Show Controller Log
button to show the Controller System Log.
A redundant controller creates one log file for the primary unit and one for the
backup unit, hence two different log files.
The information will be shown in a text editor and also be stored in a file.
However, the first controller log can still be overwritten. The 'First-in-First-out'
principle is still valid for controller logs if you activate the ‘Show Controller Log’
function from the Project Explorer.
Figure 133 below, is an excerpt of the controller system log.
Figure 133. One section of the controller system log showing the actual firmware in
the controller.
The path and file name of the Controller System log file are given in Table 34.
Analyzing Controller Logs
During compile and download the logs are fetched, analyzed and saved if the
controllers configuration is empty and the logs contains crashes.
If the logs contains crashes then they are saved with following names:
Controller aa.bb.ccc.ddd yyyy-mm-dd-hh.mm.ss.ttt CPU.log
Controller aa.bb.ccc.ddd yyyy-mm-dd-hh.mm.ss.ttt BackupCPUlog
Controller aa.bb.ccc.ddd yyyy-mm-dd-hh.mm.ss.ttt CI.log
338
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Log Files
If controllers configuration is empty but none of the logs contain crash information,
then the files are stored with following names indicating that this was a download to
an empty controller:
Controller aa.bb.ccc.ddd (empty) CPU.log
Controller aa.bb.ccc.ddd (empty) BackupCPUlog
Controller aa.bb.ccc.ddd (empty) CI.log
aa.bb.ccc.ddd represents the IP-address.
yyyy-mm-dd-hh.mm.ss.ttt represents the current date and time.
The analysis is also done when logs are fetched through Remote System dialog. If
the logs contains crashes the file name includes date and time. If crashes are not
found in the logs, then they are saved with following default names:
Controller aa.bb.ccc.ddd CPU.log
Controller aa.bb.ccc.ddd BackupCPU.log
Controller aa.bb.ccc.ddd CI.log
aa.bb.ccc.ddd represents the IP-address.
Controller Logs Sent to Computers at Shutdown of Controller
At a controller shutdown, the Controller System log is automatically sent out on the
Control Network as a broadcast message. It is fetched and stored in the working
folder for the MMS Server on all computers running an MMS Server.
If the Controller System log, fetched via the Remote System dialog, after a
shutdown is empty due to a battery failure in the controller, the log will still be
present at all computers running an MMS Server. It is then possible to find it in
the following path:
C:\ABB Industrial IT Data\Control IT Data\MMS Server for AC 800M\
Controller aa.bb.ccc.ddd CPU.log
In this path you will also find the communication interface log file
(Controller aa.bb.ccc.ddd CI.log).
3BSE040935-511
339
Log Files
Section 5 Maintenance and Trouble-Shooting
Table 34. The controller system log and communication interface log file paths .
Denomination
Controller
System log
Primary CPU
Path/Note
Path / File name
All controllers:
C:\ABB Industrial IT Data\Engineer IT Data(1)\Compact Control Builder AC
800M\LogFiles\Controller aa.bb.ccc.ddd CPU.log
Note
aa.bb.ccc.ddd is the IP address of the controller. See Controller System
Log on page 336.
The nine latest Controller System logs are saved:
Controller aa.bb.ccc.ddd CPU.log
Controller aa.bb.ccc.ddd CPU.log_bak1,
Controller aa.bb.ccc.ddd CPU.log_bak2, etc
Controller aa.bb.ccc.ddd CPU.log_bak9
Controller
System log
Backup CPU
Path / File name
All controllers:
C:\ABB Industrial IT Data\Engineer IT Data(2)\Compact Control Builder AC
800M\LogFiles\Controller aa.bb.ccc.ddd BackupCPU.log
Note
aa.bb.ccc.ddd is the IP address of the controller. See Controller System
Log on page 336.
The nine latest Controller System logs are saved:
Controller aa.bb.ccc.ddd BackupCPU.log
Controller aa.bb.ccc.ddd BackupCPU.log_bak1,
Controller aa.bb.ccc.ddd BackupCPU.log_bak2, etc
Controller aa.bb.ccc.ddd BackupCPU.log_bak9
340
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Crash Dumps for Analysis and Fault-Localization
Table 34. The controller system log and communication interface log file paths (Continued).
Denomination
Communication
Interface log
Path/Note
Path / File name
All controllers:
C:\ABB Industrial IT Data\Engineer IT Data(1)\Control Builder M
Professional\LogFiles\Controller aa.bb.ccc.ddd CI.log
Note
aa.bb.ccc.ddd is the IP address of the controller. See Controller System
Log on page 336.
The nine latest Communication Interface logs are saved:
Controller aa.bb.ccc.ddd CI.log
Controller aa.bb.ccc.ddd CI.log_bak1,
Controller aa.bb.ccc.ddd CI.log_bak2, etc
Controller aa.bb.ccc.ddd CI.log_bak9
(1) The default working directory is shown.
(2) The default working directory is shown.
The Communication Interface log (Example, the log in CI867 and CI868) is not
battery protected. Hence, the log will be erased when the power to the controller
is cut.
Crash Dumps for Analysis and Fault-Localization
If a crash occurs (in Control Builder, OPC Server, SoftController, MMS Server
for AC 800M, two new files are generated at the same location as the session log
files. The first one is a dump file and the second is a rewritten session log file. These
two files contain crucial information that should be delivered to the support
personnel
3BSE040935-511
341
Remote Systems Information
Section 5 Maintenance and Trouble-Shooting
If a Control Builder crash occurs at 16:20 on the 19:th of May, then a dump file and
a rewritten session log file will look like:
ControlBuilderStd 2006-05-19 16.20.29.184.dmp
ControlBuilderStd 2006-05-19 16.20.29.184 Session.LOG
Remote Systems Information
A connected remote control system1 can be inspected and maintained from Control
Builder. This can be an important tool when troubleshooting the system.
Select Tools > Maintenance > Remote System to open the Remote System dialog,
see Figure 134.
Figure 134. Remote System dialog.
The “Show Remote System” function can only list nodes on the same physical
network! Thus, you must connect a Control Builder PC on the same Ethernet
network; you cannot Show Remote System on nodes beyond routers, subnetworks etc.
1.
342
Remote systems are controllers, OPC servers, and engineering stations connected to the same Control network
as your own local system.
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Remote Systems Information
The following remote system functions are available, see the Table 35 below. Click
on a button in the dialog to retrieve information.
Table 35. The available remote system dialog functions.
Menu Item
Function
Show Remote Systems
Shows a list of all addresses to the control
systems (including MMS process numbers)
connected to the same network as the requesting
system.
Show Downloaded Items
Shows information about controller configuration
and about the application(s) running in the
selected remote controller system, such as
application name, application status, compilation
date and time, compiling engineering station
identity, and the checksum of the application. You
can also remove a running application here.
You can also access the source code report from
the Show Downloaded Items dialog, see Source
Code Report Generated for Project in the Compact
800 Engineering Compact Control Builder
AC 800M Getting Started (3BSE041584*) manual.
Show Firmware Information
Shows information from a controller, such as unit
position, type of hardware unit, name and version
of the current firmware and firmware creation date.
Firmware can also be loaded to selected
controllers here.
Show MMS Variables
Shows all the MMS variables in the system.
Show Controller Log
Shows the Controller System log, described in the
section Controller System Log on page 336.
Show MMS Connections
Shows connection information about the remote
systems, such as IP address, server/client
function, identity of the connected system
(destination system), usage, and number and
maximum of transactions sent since connection
was established.
3BSE040935-511
343
Remote Systems Information
Section 5 Maintenance and Trouble-Shooting
Table 35. The available remote system dialog functions. (Continued)
Menu Item
Function
Show Controller Analysis
Shows the Controller Analysis dialog that is used
to:
•
Reset the Module Bus Fail Counters in the
selected controller.
•
Get the selected result/data from the
controller.
The user can obtain results for "Heap Statistics",
"Module Bus Fail Counters", "Module Bus I/O
Revisions", "Network Information" and "Thread
Execution".
The respective result, obtained from the controller
log, is saved to a new log file. The file name of the
new log contains the "Controller ID" and the
selected result. For example, 172.16.85.187_Heap
Statistics.log.
Show Diagnostics for
Communication Variables
Shows a diagnostic overview of the internal and
external communication using the communication
variables in the controller. For details, see
Diagnostics for Communication Variables on page
345.
The dialog displays:
•
Unresolved communication variables
•
Different counters for errors/warnings, cycle
times, and timeout.
•
Details about variable transaction in each
server connection and client connection.
•
Out variables of the selected node.
For further information, refer to Control Builder online help. Use the Help button
in the Remote System dialog, see Figure 134.
344
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Diagnostics for Communication Variables
Diagnostics for Communication Variables
The diagnostics tool for communication variables can be launched from the
Remote System dialog of the selected controller. Click Show Diagnostics for
Communication Variables in the Remote System dialog.
The first window that appears is the overview window. This window is a modeless
window, that is, it is possible to bring up and work in other windows in parallel.
Figure 135. Diagnostic Overview for Communication Variables dialog
The Diagnostic Overview for Communication Variables dialog contains three panes
that display information about the communication variables that are communicating
through the applications in the selected controller.
3BSE040935-511
345
Diagnostics for Communication Variables
Section 5 Maintenance and Trouble-Shooting
The information is cyclically updated. The update interval is set to 5 seconds.
Counters Pane
The first pane lists different counters for the communication variables in the
controller. Each column in the pane corresponds to a cycle time category of the
communication variables.
The counters display the following values corresponding to the cycle time category
in different columns:
•
Internal type errors–Type mismatch during communication between
applications within this controller.
•
External type errors–Type mismatch during communication with an application
in another controller.
•
Uncertains/Warnings–Variables that are not updated within the requested time
interval.
•
Timeouts–Variables that are not updated within the requested timeout interval.
•
Min Cycle Time–The lowest detected cycle time.
•
Max Cycle Time–The highest detected cycle time.
•
Average Cycle Time–The average cycle time.
In From and Out To Panes
The second pane "In From" contains information about the external client
connections with respect to communication variables in the selected controller. The
third pane "Out To" contains information about the external server connections with
respect to communication variables in the selected controller.
Each pane contains columns for:
346
•
Variables/s–An average value, calculated since last reset time.
•
Transactions–Number of transactions since last reset time.
•
Transactions/s–An average value, calculated since last reset time.
•
Max. Transactions/s–Maximum number of transactions per second since last
reset time.
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
•
Diagnostics for Communication Variables
Expected Transactions/s–Number of expected transactions per second from the
client. This column appears in the In From pane only.
The Last reset time shows the time when the Reset button was pressed.
Buttons
There are seven buttons in the overview:
•
Show Unresolved Variables–Click to open the Unresolved Variables dialog.
•
Show Out Variables–Click to open the Out Variables dialog.
•
Reset–Click to reset the information in the controller. New values will be
fetched.
•
Details–Click to open the Detailed Diagnostics dialog for the selected client
connection.
•
Overview–Click to open the Diagnostic Overview for the selected server or
client connection.
•
Help–Click to open the online help topic for the diagnostic tool.
•
Close–Click to close the window.
3BSE040935-511
347
Diagnostics for Communication Variables
Section 5 Maintenance and Trouble-Shooting
Show Unresolved Variables
Figure 136. Unresolved Variables dialog
The Unresolved Variables dialog displays the list of unresolved variables. Select the
variable and click Search to open the Search & Navigation tool for the selected
variable.
The Search works in Offline mode and when the setting "Iterative Search in
Online Mode" is set to false.
348
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Diagnostics for Communication Variables
Show Out Variables
Figure 137. The Out Variables dialog
The Out Variables dialog displays the list of out variables in the controller.
3BSE040935-511
349
Diagnostics for Communication Variables
Section 5 Maintenance and Trouble-Shooting
Details
Figure 138. Detailed Diagnostics dialog
The Detailed Diagnostics dialog displays the information for the different cycle time
groups in a selected client connection. The following values are shown:
•
Variables per second. An average value, calculated since last reset time.
•
Number of transactions since last reset time.
•
Transaction per second. An average value, calculated since last reset time.
•
Maximum number of transactions per second since last reset time.
•
Expected number of transaction per second. A value that is calculated at
compile time.
Click Overview to open the Diagnostic Overview (Figure 135) for the controller
that owns this client connection.
The information is cyclically updated. The interval is set to 5 seconds and it cannot
be changed.
350
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Analysis Tools
Analysis Tools
Control Builder Tools
The Control Builder Tools menu contains more useful tools for troubleshooting.
Note that a great deal of the information is only valuable for your supplier’s service
department.
Select Tools > Maintenance > Analysis to open the following menu items, see
Table 36.
For further information, refer to Control Builder online help.
Table 36. The menu items of the Analysis tool.
Menu Item
Function
Disable Double-buffering
Not useful for troubleshooting
Disable Information Zoom
Not useful for troubleshooting
Disable Clipping
Not useful for troubleshooting
Image Selector Info in Online Not useful for troubleshooting
Mode
Image Selector Information
Not useful for troubleshooting
Show control modules in
Online Mode
Not useful for troubleshooting
Write Variable Memory
Used for counting modules and instances.
Write Exported Variables
Not useful for troubleshooting
Write Variables in View
Not useful for troubleshooting
Start log
Shows the Control Builder Start log, described in
Control Builder Start Log on page 332.
System log
Shows the Control Builder System log, described in
System Log File on page 326.
3BSE040935-511
351
Analysis Tools
Section 5 Maintenance and Trouble-Shooting
Statistics for Application
The user can get the statistics about the application, for example, the number of
instances that exists in the application. This is useful when the maximum number of
instances has been exceeded. From the context menu of the selected application,
select Statistics as shown in Figure 139.
Figure 139. Obtaining statistics for the application
352
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
System Diagnostics
The maximum number of instances in an application is 65536. When this number is
exceeded, the following dialog is shown.
Figure 140. Error message shown at download, when an application has too many
instances.
System Diagnostics
System Diagnostics Function Block
The Basic library contains a function block type called System Diagnostics. You can
use this function block type to measure and display the following functions.
•
Cyclic load resulting from task execution,
•
Stop time and memory usage during a controller download,
A stop at each download occurs When a new application version is
downloaded. The length of this stop is mainly affected by the number of
variables marked as retain or cold retain. Each variable marked retain or
cold retain must keep the value at a download with warm restart. The
copying takes time and copying more values requires more time. The
attribute retain should only be set for variables if they really require such
an attribute, as this attribute increases the stop time during download of
program changes to the controller. When the new version of the
application has been created in the controller, the old application is
stopped (i.e start of stop time) then all values are copied from the old
application to the new. The new application version is then started (i.e end
of stop time). During the copying instances, the application exists in two
versions, one old and one new. This is the reason for the extra memory
needed.
•
Current memory in use,
•
Maximum memory used since the last cold start,
3BSE040935-511
353
System Diagnostics
Section 5 Maintenance and Trouble-Shooting
•
Alarm and event information,
•
Total CPU Load,
•
Ethernet statistics:
–
number of data packages sent,
–
number of sent data packages that were lost,
–
number of data packages received,
–
number of received data packages that were lost.
The System Diagnostics function block is, as default, located in one of the Diagram
folders of the Project Explorer tree, see Figure 141.
Figure 141. The System Diagnostics function block
Values can be updated either on command or cyclically using the Interaction
Window, which is opened by selecting the System Diagnostics function block, rightclicking, and then selecting Interaction Window.
The System Diagnostics Interaction window is only available in Test/Online
mode.
354
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
System Diagnostics
System Diagnostics Interaction Window.
The System Diagnostics Interaction window contains system memory and program
download information. The interaction windows can be displayed in two versions,
Simple and Advanced.
The values shown in Test mode are not those valid in Online mode. You cannot
use this information to check in advance which controller size you have to
purchase.
The Simple Interaction window contains the following information:
Table 37. The Simple Interaction window
Function
Description
System
Displays the TCP/IP address of the supervised system.
Cyclic load
Displays cyclic load due to task execution in percent.
Latest update
Displays the time of the last update.
Cyclic update
Cyclic update is activated by checking the check box.
Cyclic update interval is set in time format, for example 5 m
(5 minutes).
Total Load CPU
Shows the total CPU load for the controller. The total load
is available as a parameter of type dint, called
TotalSystemLoadPerCent.
Ethernet Statistics
By clicking the Ethernet button, you display Ethernet
statistics in a separate window.
This window shows the number of sent/received
packages, and how many of those that were lost. These
statistics are available as parameters. There are also
parameters for resetting the counters. See online help for
the SystemDiagnostics function block.
3BSE040935-511
355
System Diagnostics
Section 5 Maintenance and Trouble-Shooting
Click on the Advanced button, and the Advanced Interaction window will appear. It
contains the following additional information.
Table 38. The Advanced interaction window.
Function
Description
Memory size
The allocated heap size, see Figure 142.
Used memory
The part of the heap used in bytes and percent of the total
heap size.
Max used memory
The maximum part of the heap used in bytes and percent of
the total heap size.
Memory quota
The part of the total heap size available when program
changes are sent to the controller. If the memory quota is
exceeded an error icon is displayed.
Note. This setting is only used for a warning indication.
Stop time
Stop time during the last download.
Init peak memory
Memory used during initiation phase.
Used memory at
stop
The part of the heap used during the stop phase in bytes
and percent of the total heap size.
Max used memory at The maximum part of the heap used during the stop phase
stop
in bytes and percent of the total heap size.
Memory quota at
download
The part of the total heap size available when program
changes are sent to the controller. If the memory quota is
exceeded an error icon is displayed.
In the System Diagnostics function block, “Memory size” is the total physical
memory, minus executing firmware. This is sometimes also called the “heap”.
356
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
System Diagnostics
Memory usage is also displayed in the dialog “Heap Utilization” which can be
displayed for each controller. The available memory is called “Non-Used Heap” and
the rest is called “Used Shared Heap”.
Spare
(20-50%)
Available Memory
Max
Used
Shared
Heap
“Non-used heap”
Empty Project
Used
Shared
Heap
Memory Size
“Heap”
8-256 MB
RAM
Used by Firmware
Executing Firmware
Figure 142. Memory organization
3BSE040935-511
357
Trouble-Shooting Error Symptoms
Section 5 Maintenance and Trouble-Shooting
Trouble-Shooting Error Symptoms
Below are some examples of error symptoms and suggested measures.
Table 39. Examples of error symptoms and suggested measures.
Error Symptom
Measure
Control Builder fails.
1.Click OK.
2.Copy the two crash dump files (see Crash Dumps for
Analysis and Fault-Localization on page 341), the
Start Log and the Heap Statistics Log files (if there are
any).
3.Read the Session Log, and see if there is any
information that indicates the source of the problem.
4.Try to start Control Builder. If it starts, select
Help>About Compact Control Builder>List all
information in the Project Explorer and the Control
Builder System Information Report will be created.
5.Try to reproduce the fault, if possible. If the problem is
reproducible, export the project with all dependencies
and include the .afw file in the error report.
6.Check basic things, such as if the hard disk full.
7.If the fault appears during Offline to Online transfer,
and it is possible to reproduce the fault, check the
message written in the message pane, just prior to
fault occurrence. This will give a hint about what
operation (for example, sorting, compiling) and what
application is involved in the problem.
8.Make an error report and include the log files.
A Memory Full message appears. The
Heap Statistics log (SoftController)
states that the heap is full.
358
Increase the heap size in SoftController, see Heap
Statistics Log on page 336. Open Help > About and
check the amount of free memory. Free memory should
not be lower than 30%.
3BSE040935-511
Section 5 Maintenance and Trouble-Shooting
Trouble-Shooting Error Symptoms
Table 39. Examples of error symptoms and suggested measures. (Continued)
Error Symptom
Measure
A Too many instances in application
message appears.
1.Try to reduce your application, see Statistics for
Application on page 352.
The maximum number of above 65534
instances has been reached.
The MMS Server, OPC Server, or
SoftController fails.
1.Click OK.
2.Locate the two crash dump files (see Crash Dumps for
Analysis and Fault-Localization on page 341).
3.Read the Session Log, and see if there is any
information that points to the source of the problem.
4.Make an error report and include the log file.
The controller fails. The red F LED is lit,
and the green R LED is off.
1.Press the Init push-button on the controller until the
Run LED starts to blink. Note that the controller will be
empty if the red F LED is lit, that is, the application
program has been deleted.
2.Fetch the Controller System log and save it, see
Remote Systems Information on page 342.
3.Study the log, and find the marked reason for the stop
(normally, at the end of the log).
4.If an OPC Server for AC 800M is involved in
communication, check the OPC Server function.
5.Make an error report and include the saved log files.
6.Reload the application.
7.If possible, try to reproduce the problem. If the
problem is reproducible, backup the project.
Note that behavior similar to the example above is when
there is no firmware installed in the controller (for
example, when a new controller has been installed).
3BSE040935-511
359
Error Reports
Section 5 Maintenance and Trouble-Shooting
Error Reports
An error report contains information to the problem in question. A detailed report is
particularly valuable if your supplier’s service department is to be involved.
The following information should always be included in an error report.
•
Name of the person reporting the error (and the project, site, customer, etc.).
•
Product (including the type of product and version).
•
A listing of all information from the faulty system, such as the appropriate logs
and reports, see Log Files on page 326. The latter includes a great deal of
information such as software version and revision, setup, etc. If the fault
occurred during, or just after downloading a new version of the application
program, the Control Builder Start Log and the Control Builder Session Log
from the engineering station that performed the download should be included.
Whenever a problem involving I/O handling occurs, it is very important to
include a complete description of the I/O configuration.
•
A description of the problem. Add all information that could help solve the
problem, for example, what happened just before the error occurred, and other
important circumstances. If it is possible to reproduce the error, describe the
circumstances under which the error occurs. Sometimes it is advisable to create
a small application to demonstrate the error, and add it to the error report.
If several systems are involved, information about the system configuration must
be included (hardware type, etc.).
360
3BSE040935-511
Appendix A Array, Queue and Conversion
Examples
In this section you will find examples on how to handle arrays, queues, and some
examples on how to use bit conversion functions.
Arrays
It is possible to create a one-dimensional array with elements of any type, that is, the
elements can be a struct with variables of any type, or a single variable of any type.
Using PutArray and/or CopyArray, it is possible to build a tree structure of arrays.
Array elements are accessed direct via an index. A lower and upper boundary of the
index should be defined. The array must first be created using CreateArray.
The size of an array is limited to 65,524 components (variables of simple data type).
Example
In this example, there is a data type trec1 with the components b (bool), i (dint), and
st (string).
The following variables are also needed:
Name
Data Type
MyArray
ArrayObject
lrec
trec1
lrec1
trec1
lrec2
trec1
lrec3
trec1
Status
dint
FirstScan
bool
3BSE040935-511
Initial Value
TRUE
361
Arrays
Appendix A Array, Queue and Conversion Examples
Create and initialize an array with 20 array elements of the type trec1.
Use an IF – THEN statement for the CreateArray function and let it be controlled by
a variable, which is executed once during startup.
IF FirstScan THEN
FirstScan := false;
CreateArray(MyArray,1,20,lrec,status);
end_if;
Set up values for the different variables:
lrec1.b := TRUE
lrec1.i := 123
lrec1.st := A variable contaning the string 'Hello'
lrec2.b := FALSE
lrec2.i := 27
lrec2.st := A variable contaning the string 'BYE'
lrec3.b := TRUE
lrec3.i := 53
lrec3.st := A variable contaning the string 'BYE'
Set up the array contents:
PutArray (MyArray,1,lrec1,status);
PutArray (MyArray,2,lrec2,status);
PutArray (MyArray,3,lrec3,status);
362
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
SearchStructComponent
The array now contains the following:
1
b = TRUE
i = 123
st = 'Hello'
b = FALSE
2
3
i = 27
st = 'BYE
'
b = TRUE
i = 53
st = 'BYE '
b = Undef.
4
i = Undef.
st = Undef.
b = Undef.
20 i = Undef.
st = Undef.
SearchStructComponent
SearchStructComponent is a boolean function which searches for a specific part in a
record component. The corresponding components in Exrecord are scanned to find a
part in the component which matches the SearchComponent.
Variable = SearchStructComponent(Struct, SearchIndex,
SearchCount, SearchStruct, SearchComponent, FoundStruct,
Status)
Table 40.
3BSE040935-511
Parameter
Data type
Direction
Struct
AnyType
in_out
SearchIndex
dint
in_out
SearchCount
dint
in
SearchStruct
AnyType
in_out
SearchComponent AnyType
in_out
FoundStruct
AnyType
in_out
Status
dint
in_out
363
SearchStructComponent
Appendix A Array, Queue and Conversion Examples
The data type SearchComponent is either a single variable or a record containing a
couple of variables corresponding to a subset of the record component in Struct. The
SearchComponent could be either a boolean, integer, real or string data type or a sub
record which contains these data types. The SearchRecord shall consist of a variable
of SearchType and variables of the data types as the remaining variables in the
record component and at the same positions.
Figure 143. An example of the SearchComponent and a SearchRecord.
The SearchComponent may contain structured data types but the match is only
carried out on the boolean, integer, real and string data types. The variables in
SearchComponent of string data types must have the same length and content for a
match. The content of string is not case sensitive and the space characters are treated
as any other character. On match the whole record component is copied to
FoundStruct and the function returns true.
364
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
SearchStructComponent
Figure 144. The working principal of the SearchStructComponent.
The search starts in the index SearchIndex + 1 and ends at the first equivalent
component located or, if there are no more sub-records, in the last component of the
record.
A maximum number of record components given by SearchCount are scanned. The
component, in which a match occurs, is returned in FoundStruct and the index is
returned in SearchIndex.
Note that SearchIndex always points to the last record component that was scanned,
even if no matching occurs. This index can then be used in a repeated call to find all
occurrences of SearchComponent within the record.
3BSE040935-511
365
SearchStructComponent
Appendix A Array, Queue and Conversion Examples
Restrictions
The following data types in ExRecord will NOT be copied: QueueObject and
tObject.
The status returns:
366
•
(1 Success)
– The Search was successful
•
(- 5 ErrTypeMismatch)
– 1: Found sub-record was not of the same type as the structRecord.
– 2: SearchComponent was not a subset of SearchRecord
•
(- 6 ErrSizeMismatch)
– 1: SearchRecord was not of the same size as the StructRecord.
– 2: SearchComponent size is zero.
•
(-30 ErrInvalidPar)
– 1: SearchIndex was less than 0 or greater than the number of the Struct
minus one.
– 2: SearchCount was less or equal to zero.
– 3: SearchComponent has no valid components (i.e., boolean, real, integer
or string)
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
InsertArray
InsertArray
InsertArray(Array, Index, ArrayElement, Status)
Procedure: Inserts a new element in an array. All successive elements are moved one
step, and the last element overwritten. Inserts the contents of ArrayElement into the
record at position Index in the array Array. The records at position Index + 1 to
position LastIndex will be moved one position higher. The contents (even objects) of
the record at position LastIndex will be lost. Variables of the data type tObjects will
not be copied, unless the variable is an ArrayObject, then this array and its whole
tree structure of arrays will be copied into an identical tree structure. If the record at
position Index lacks some array in the tree structure, the array will be created.
Table 41.
3BSE040935-511
Parameter
Data type
Direction
Array
ArrayObject
in_out
Index
dint
in
ArrayElement
AnyType
in_out
Status
dint
in_out
367
SearchArray
Appendix A Array, Queue and Conversion Examples
SearchArray
SearchArray(Array, SearchIndex, SearchCount, SearchElement,
SearchComponent, FoundElement, Status)
This boolean function searches the array Array for a certain component in an array
element. All elements in the array are scanned to find an element with a component
(e.g. a string, or an entire record) that matches the search variable component.
The component SearchComponent in the element SearchElement is tested for
equality with corresponding components in each array element. The function
returns true if there is a find.
The search starts in the index SearchIndex + 1 and ends at the first equivalent
component located or if there are no more elements in the array to be scanned. A
maximum of number of array elements indicated by SearchCount are scanned. The
array element, in which a find occurs, is returned in FoundElement and the index for
the find is also returned in SearchIndex.
Note that SearchIndex always points to the last element that was scanned, even if no
find occurs. This index can then be used in a repeated call in order to find all
occurrences of SearchComponent within the array.
An error status is returned if:
•
the index SearchIndex points outside array limits.
•
the counter SearchCount is less then or equal to 0.
•
the element SearchElement is not of the same type as FoundElement.
•
the element SearchElement has a different size than FoundElement.
•
the SearchComponent is not a part of the element SearchElement.
368
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
SearchArray
Table 42.
Parameter
Data type
Direction
Array
ArrayObject
in_out
SearchIndex
dint
in_out
SearchCount
dint
in
SearchElement
AnyType
in_out
SearchComponent AnyType
in_out
FoundElement
AnyType
in_out
Status
dint
in_out
Example
Table 43. Data Type Definitions
3BSE040935-511
Name
Data Type
trec1
Struct
b
Boolean
i
dint
s
String
tSearchStruct
STRUCT
b
Boolean
SSR
tSearchSubRec
tSearchSubStruct
Struct
i
dint
s
String
369
SearchArray
Appendix A Array, Queue and Conversion Examples
Table 44. Variables
Name
Data type
Array
ArrayObject
HitBoolean
Boolean
HitRec
trec1
Lrec
trec1
Irec1
trec1
Irec2
trec1
Irec3
trec1
Status
dint
SearchRec
tSearchStruct
FirstScan
Boolean
Initial value
TRUE
Create and initialize an array with 20 array elements of type trec1.
The Create function may be in a Start_Code and in that case it is not necessary to
use the IF -THEN statement and Firstscan variable.
IF Firstscan THEN
Firstscan = false;
CreateArray(Array,1,20,lrec,status);
ENDIF;
Set up values for the different variables e.g. via interaction objects:
lrec1.b
lrec1.i
lrec1.s
lrec2.b
lrec2.i
lrec2.s
lrec3.b
lrec3.i
lrec3.s
370
<<<<<<<<<-
TRUE
123
"hello"
FALSE
27
"BYE"
TRUE
53
"BYE"
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
SearchArray
Set up array contents:
PutArray (Array,1,lrec1,status);
PutArray (Array,2,lrec2,status);
PutArray (Array,3,lrec3,status);
The array now contains the following:
Figure 145. An example of an Array.
Access the array by index:
Index = 3;
GetArray(Array,Index,lrec,status);
lrec now contains:
TRUE 53 "BYE "
Now access the array by searching. First set up the search component.
SearchRec.SSR.i = 27;
3BSE040935-511
371
Queues
Appendix A Array, Queue and Conversion Examples
SearchRec.SSR.s has its default value "BYE" Search a maximum of 10 array
elements for the search component. A find occurs where the integer element is 27
and the string element is "BYE", in this case at array index no 2. Start searching in
the first element number 1.
Index = 0;
IF SearchArray(Array,Index,10,SearchRec,SearchRec.SSR,
HitRec,Status) THEN
IF Status > 0 THEN
HitBoolean = HitRec.b;(Save Boolean content of hit element)
ENDIF;
ENDIF;
Queues
A queue may consist of elements of any type, that is, the elements could be a struct
with variables of any type, or a single variable of any type. Queue elements can be
accessed at both ends of the queue, that is, only the first and last element can be
accessed, but any element in the queue can be read. When using PutFirstQueue and
GetFirstQueue, the queue act as a stack. When using PutLastQueue and
GetFirstQueue, the queue will act as a FIFO queue. The size of the queue is not
dynamic, and has to be defined. The number of elements in the queue is dynamic.
The size of a queue is limited to 65,524 components (variables of simple data type).
372
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
Queues
Example 1
The following structured variable Item is needed:
Name
Data Type
Initial Value
b
bool
TRUE
i
dint
123
st
string
'Hello'
The following variables are needed:
Name
Data Type
data1
Item
data2
Item
Queue
QueueObject
Status
dint
FirstScan
bool
flag1
bool
flag2
bool
Initial Value
TRUE
Create and initialize an array with 10 elements of data type item:
3BSE040935-511
373
Queues
Appendix A Array, Queue and Conversion Examples
In an IF – THEN statement the CreateQueue function may be controlled by a first
scan variable.
if FirstScan then
FirstScan := false;
CreateQueue( Queue := Queue,
Size := 10,
QueueElement := data1,
Status := status );
end_if;
if flag1 then
PutLastQueue( Queue := Queue,
QueueElement := data2,
Status := status );
flag1 := false;
elsif flag2 then
GetFirstQueue( Queue := Queue,
QueueElement := data2,
Status := status );
flag2 := false;
end_if;
Example 2
The following parameters are needed:
374
Name
Data Type
Description
Size
dint
Max no. of elements in queue
InData
AnyType
In element, of same type as OutData
OutData
AnyType
Out element, of same type as InData
Put
bool
Put InData in queue on up edge
Get
bool
Get OutData from queue on up edge
Clear
bool
Clear contents of queue
Error
bool
Out: type or size of error
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
Queues
The following variables are needed:
Name
Data Type
Description
Queue
QueueObject
Queue object
PutState
bool state
GetState
bool state
Status
dint
Code block 1 called Start_name
(*CreateQueue*)
CreateQueue(Queue,Size,InData,status);
Error := status < 0;
Code block 2 (queue statement)
PutState := Put;
GetState := Get;
if PutState:NEW and not PutState:OLD then
PutLastQueue(Queue,InData,status);
Error := status < 0;
end_if;
if GetState:NEW and not GetState:OLD then
GetFirstQueue(Queue,OutData,status);
Error := status < 0;
end_if;
if Clear then
ClearQueue(Queue,status);
Error := false;
end_if;
3BSE040935-511
375
Conversion Functions
Appendix A Array, Queue and Conversion Examples
Conversion Functions
DIntToBCD
The DIntToBCD function converts an integer to a BCD value. An error status is
returned if overflow occurs and no BCD value is produced.
Example
The following variables are needed:
Name
Data Type
N
dint
BCD
dint
Status
dint
Convert an integer into a BCD value:
N = 12345 (N is 0 0 0 1 2 3 4 5)
N can be divided into eight four-bit nibbles, where each nibble represents one BCD
digit. The least significant nibble is 5, the next 4, etc. These nibbles can be written in
binary form as below:
0000 0000 0000 0001 0010 0011 0100 0101
All fourbit
nibbles
which is
equiv. to
00
000
000
000
000
010
010
001
101
000
101
BCD as
decimal
value
0
0
0
0
0
0
7
4
5
6
5
DIntToBCD ( N, BCD, Status ) ;
BCD now contains the value 74565.
376
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
BCDToDInt
BCDToDInt
BCDToDInt converts a BCD value to an integer. An error status is returned if the
BCD value is illegal (no integer value in these cases).
Example
The following variables are needed:
Name
Data Type
N
dint
BCD
dint
Status
dint
Convert the BCD value into an integer:
BCD = 74565
BCD as
decimal
value
0
0
0
0
0
0
7
4
5
6
5
BCD as
32-bit
pattern
00
000
000
000
000
010
010
001
101
000
101
BCD as
four-bit
nibbles
0000 0000 0000 0001 0010 0011 0100 0101
Each nibble represents one BCD digit. The least significant nibble is 5, the next 4,
etc. These nibbles can be written in decimal form as: 0 0 0 1 2 3 4 5.
BCDToDInt ( BCD, N, Status ) ;
N now contains the value 12345.
3BSE040935-511
377
ASCII
Appendix A Array, Queue and Conversion Examples
ASCII
ASCII character codes
ASCII (American Standards Committee for Information Interchange) originally
defined a set of codes for 128 characters and commands. Manufacturers later
extended the ASCII codes to provide another 128 characters.
ASCII is a method of coding characters and command sequences, which is
extensively used by manufacturers of peripheral equipment. Many devices transmit
information in ASCII code (for example bar-code readers, keyboards) and many
devices accept information in this form (for example VDUs and printers).
ASCII-coded strings allow for the transmission of non-printable characters and
control characters. ASCII character sequences can be used to change the mode of a
VDU display, or the character set of a printer.
Control Builder provides three procedures and one function manipulating ASCII
strings (ISO Latin-1 only). These are useful when a device requires ASCII-coded
information, and can be used to send ASCII-coded strings to printers, terminals etc.
Any ASCII character code may be used, thus it is possible to send control characters
and sequences to switch printers and VDUs into various display modes. (Bold,
Double Space, Reverse video etc.).
Before describing the procedures and functions available for ASCII strings, it is
useful to examine the way in which an integer is stored in the system memory.
Bit31
MSB
Bit0
Byte 3
LSB MSB
Byte 2
LSB MSB
Byte 1
LSB MSB
Byte 0
LSB
Figure 146. Integers are stored as four bytes in memory.
Integers are represented by a four-byte (32-bit) storage area. In normal usage, the
bits are used to store both the value and the sign of the integer. This 4-byte storage
space may also be used to store a series of values which represent an ASCII string.
Each ASCII character requires 1 byte of storage space. Therefore, it is possible to
store up to 4 ASCII characters in a single memory area reserved for an integer.
378
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
ASCII
The procedures below allow 1, 2 or 4 characters to be stored per integer.
Each ASCII character is coded with an integer value (in binary) between 0 and 255
(decimal). ASCII codes are normally represented as either their decimal equivalent,
or as a hexadecimal number. If the character is represented as a hexadecimal
number, then 2 digits are required for each character.
The hexadecimal digits, their decimal, and binary bit pattern equivalents are given in
the table below:
Table 45. ASCII code representatives
Hexadecimal digit
Decimal digit
Binary bit pattern
0
0
0000
1
1
0001
2
2
0010
3
3
0011
4
4
0100
5
5
0101
6
6
0110
7
7
0111
8
8
1000
9
9
1001
A
10
1010
B
11
1011
C
12
1100
D
13
1101
E
14
1110
F
15
1111
The letter capital “A” is represented by the ASCII code 6510 or 41HEX. Thus the
letter “A” is stored as a byte having the bit pattern 0100 0001.
3BSE040935-511
379
ASCII Conversion
Appendix A Array, Queue and Conversion Examples
ASCII Conversion
StringToASCIIStruct (String1, NoOfCharsPerDint, DintStruct, Status)
This procedure converts a string to an ASCIIStruct. An ASCIIStruct consists of any
number of integer components (see below).
The value of the parameter NoOfCharsPerDint determines how many ASCII
characters are stored within each ASCII record component. This value can be 1, 2, 4
or –1, –2, –4 only. A negative value means that the sequence of bytes is reversed.
NoOfCharsPerDint determines how many character codes are packed into the four
bytes available for the integer. If one character is stored per integer, then only the
first eight least significant bits of each integer are used for storage, if positive, or the
last eight, if negative.
DintStruct must be defined as follows: the type definition and its components can be
given any name, but the components must all be of integer data type. The number of
components (of integer type) should be decided based on the length of the string to
be converted, and also the number of characters which are to be stored in each
integer. The converted string may need to be transmitted to a peripheral device, so
the characteristics of this device should also be taken into account.
The maximum length for any string is 140 characters, and if this maximum is to be
stored in the minimum number of integer components, then this will require 35
integer components in the integer record (at four ASCII characters per integer). If
you anticipate the need to store this number of characters, then an integer record of
35 integer components should be defined.
Status returns an indication of the result of the operation.
380
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
ASCII Conversion
Storage with Different Character Packing Factors
When NoOfCharsPerDint is set to 1, each integer variable holds the value for one
ASCII character. Thus the character capital “A” is stored as decimal 65 in the
integer, as a bit pattern of 0100 (Nibble1) and 0001 (Nibble0).
Nibble1 Nibble0
Bit31
0 1 0 0 0 0 0 1
MSB
LSB
A
Byte 3
Byte 2
Byte 0
Figure 147. The ASCII code for “A” stored in an integer (packing = 1 character per
integer)
When NoOfCharsPerDint is set to 2, each integer variable stores the value for two
ASCII characters. The characters “AB” are stored as decimals 65 and 66 in the
integer. The value 65 for “A” is stored in the first byte of the integer, and that for “B”
in the second byte.
Nibble3 Nibble2 Nibble1 Nibble0
Bit31
0 1 0 0 0 0 1 0 0 1 0 0 0 0 0 1
MSB
LSB
B
A
Byte 3
Byte 2
Byte 1
Byte 0
Figure 148. The ASCII codes for “AB” stored in an integer (packing = 2 characters
per integer)
When NoOfCharsPerDint is set to 4, each integer variable contains the value for
four ASCII characters. The characters “ABCD” are stored as decimals 65, 66, 67
and 68 in the integer. The value 65 for “A” is stored in the first byte of the integer,
“B” in the second byte, “C” in the third byte, and “D” in the fourth byte.
Nibble7 Nibble6 Nibble5 Nibble4 Nibble3 Nibble2 Nibble1 Nibble0
Bit31
0 1 0 0 0 1 0 0 0 1 0 0 0 0 1 1
D
Byte 3
C
Byte 2
0 1 0 0 0 0 1 0 0 1 0 0 0 0 0 1
MSB
LSB
B
A
Byte 1
Byte 0
Figure 149. The ASCII codes for “ABCD” stored in an integer (packing = 4
characters per integer)
3BSE040935-511
381
ASCII Conversion
Appendix A Array, Queue and Conversion Examples
Definition of DintStruct type
The appropriate length of an integer struct to store ASCII code is defined by the
number of components required as follows.
Suppose we want to be able to store the maximum string length at a packing factor
of 4 characters per integer. A data type called, for instance, ASCIIMaxStringType,
should be defined consisting of 35 components which must be of integer data type
called, for example Chars1_4, Chars5_8 etc.
Usage
A string interaction is used to input the value of a string, (to a string variable called
String1), which is to be converted to ASCII code. The code is stored in an integer
struct called IntStruct which has 4 components (Comp1 to Comp4).
The procedure call:
StringToASCIIStruct(String1,1,IntStruct,Status1)
will write to the integer record components.
If the input string is “ABCD”, then the components will have the values 65, 66, 67
and 68, respectively. The literal value of 1 for the NoOfCharsPerDint determines
that there is to be one character code in each component.
If NoOfCharsPerDint had been set to 2, then the first integer component would have
the value 16961 (which is the decimal equivalent of 65 in the first byte and 66 in the
second), and the second component would have the value 17475, which is the
decimal equivalent of 67 in the first byte and 68 in the second. The other two bytes
in each integer component are set to 0000.
Unused components
NoOfCharsPerDint determines how many bits are allocated for storage (8 bits – 1
byte per character) for a component. For example, if NoOfCharsPerDint is set to 2,
then only the first two bytes are used in each component for data storage. The
remaining bytes are set to 0 (zero).
382
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
ASCII Conversion
This is illustrated below:
Bit31
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Null
Component1
Byte 3
Null
Byte 2
0 1 0 0 0 0 1 0 0 1 0 0 0 0 0 1
B
A
Byte 1
Byte 0
Bit31
Component2
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0 1 0 0 0 1 0 0 0 0 1 1
D
C
Null
Null
Byte 3
Byte 2
Byte 1
Byte 0
Bit31
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Null
Component3
Byte 3
0 0 1 0 0 0 0 0 0 0 1 0 0 0 0 0
Null
Space
Byte 2
Byte 1
Space
Byte 0
Bit31
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
Null
Component4
Byte 3
Null
Byte 2
0 0 1 0 0 0 0 0 0 0 1 0 0 0 0 0
Space
Byte 1
Space
Byte 0
Figure 150. The diagram shows four integer components of an integer record.
NoOfCharsPerDint has been set to 2, so that each component stores two ASCII
characters. The character string “ABCD” has been transferred to the struct.
3BSE040935-511
383
ASCII Conversion
Appendix A Array, Queue and Conversion Examples
Note the following
If there are two characters per integer, the allocated storage areas Byte 0 and Byte 1
contain either the code for the string character, or if there is no character available,
the code for a space (20HEX). Unused bit positions (Bytes 2 and 3 in this case)
contain zero.
Note:
•
Characters from the string to be transferred are read from the current pointer
position in the source string.
•
Space characters are inserted into the allocated storage areas within each
component. They are also inserted into all records to which no characters have
been transferred, for example, if the actual string requires less than the number
of components available for storage.
•
An error status is returned to the value of Status, if the string to be transferred is
longer than the storage space allocated. In this case, no transfer of any part of
the string occurs.
ASCIIStructToString(DIntStruct, NoOfCharacters, NoOfCharsPerDint, String1,
Status)
This procedure is the reverse of StringToASCIIStruct described above. It takes an
integer struct, which contains the codes for an ASCII string, and recreates the string
from the values in the components of the record. (See StringToASCIIStruct for full
details of the structure of the integer struct and the encoding method.)
The component values of the integer struct, DIntStruct are read and translated to the
value of the destination string, String1.
The value of the parameter NoOfCharacters determines how many ASCII
characters are read from the source record, DIntStruct, and the value of the
parameter NoOfCharsPerDInt informs the procedure how many characters are to be
expected in each integer component. Status returns an indication of the result of the
operation.
The DIntStruct parameter must be structured as an integer struct, that is, it must
have integer components only. (See details in StringToASCIIStruct.)
384
3BSE040935-511
Appendix A Array, Queue and Conversion Examples
ASCII Conversion
NoOfCharacters and NoOfCharsPerDInt may be variables, module parameters or
literals.
Usage
Suppose the integer struct DIntStruct from the previous example is to be converted
back to a string. The destination string is called String1 and the three characters are
to be copied. It is known that the original storage protocol defined 2 characters per
integer component.
The following code will perform the task:
ASCIIStructToString(DIntStruct,3,2,String1,Status2)
After execution the value of String1 value will be “ABC”.
Note
•
The number of characters per integer of the original record must be known,
only values of 1, 2, 4 or –1, –2, –4 are allowed.
•
The new output string will be inserted at the current pointer position in the
destination string.
•
An error status is reported as a value to Status if the generated string results in a
new string which is longer than the permitted length for the destination string.
3BSE040935-511
385
ASCII Conversion
386
Appendix A Array, Queue and Conversion Examples
3BSE040935-511
Appendix B System Alarms and Events
This section is divided in sub-sections for system alarms and system simple events
and it describes system alarms and system simple events from a controller
perspective. Additional information can also be found in the Control Builder online
help.
General
OPC Server
System alarms and system simple events generated within OPC server can be
divided in two general groups regarding to originating part of the OPC server
(source).
•
Software
•
Subscriptions
Controller
System alarms and system simple events generated within controller can be divided
in two general groups regarding to originating part of the controller (source).
•
Software generated system alarms and system simple events.
•
Hardware generated system alarms and system simple events.
3BSE040935-511
387
OPC Server – Software
Appendix B System Alarms and Events
OPC Server – Software
All system alarms and system simple events triggered by base code executing in
OPC Server belong to this group. This group is further divided into appropriate parts
uniquely identified by source name suffix.
•
_SWFirmware – for common base code
•
_SWDataAccess – for OPC Data Access specific code
•
_SWAlarmEvent – for OPC Alarm and Event specific code
The SrcName shall be automatically formed as:
SrcName = SystemIP address- SrcNameSuffix
Example: SrcName = 172.16.85.90:200-_SWFirmware
SrcNameSuffix = _SWFirmware
System Alarm HeapFull
SrcNameSuffix = _SWFirmware;
Condition name = HeapFull;
Message = "(1000) The Heap is full";
SeverityLevel = High;
SrcNameSuffix = _SWDataAccess
System Simple Event SaveColdRetainFailed
Generated when OPC Data Access server can not save cold retain files for an
application.
SrcNameSuffix = _SWFirmware;
Message = "(5000) Save Cold Retain failed for {1}";
{1} = The name of the application.
SeverityLevel = Medium;
388
3BSE040935-511
Appendix B System Alarms and Events
OPC Server – Software
SrcNameSuffix = _SWAlarmEvent
System Simple Event AlarmNotUnique
Generated when OPCAE server discover that there are two alarms with same
combination SouceName ConditionName defined in two different controllers.
SrcNameSuffix = _SWAlarmEvent ;
Message = "(6000) Alarm not unique {1}, {2}";
{1} = Source name of the alarm
{2} = Condition name of the alarm
SeverityLevel = Medium;
System Simple Event AlarmHandler overflow
Generated when an item in the EventHandler must be deleted because of overflow.
If there is space again in the EventHandler, the system initializes an AlarmSummary
and updates the missing information. The size of the EventHandler is limited by the
system variable MaxNoOfAlarms.
SrcNameSuffix = _SWAlarmEvent ;
Message = "(6001) AlarmHandler overflow. MaxNoOfAlarms exceeded";
SeverityLevel = Medium;
System Simple Event FailedToSubscribe
Generated when a try from OPC AE server to subscribe to a certain control system
was not successful. The corresponding control system name shall be concatenated to
this message.
SrcNameSuffix = _SWAlarmEvent;
Message = "(6002) Failed to subscribe on {1}";
{1} = The IP address of the control system.
SeverityLevel = Medium;
3BSE040935-511
389
OPC Server – Subscription
Appendix B System Alarms and Events
System Simple Event Overflow in queue to OPC client
Generated after an overflow of the event queue to an OPC client queue and when the
queue is filled less than 75% of the actual size. The system event is generated and
sent to the client to announce the overflow. On overflow the latest event is thrown
away. The size of every event queue to an OPC client queue is limited by the system
setting "Queue size".
SrcNameSuffix = _SWAlarmEvent;
Message = "(6003) Overflow in queue to OPC client";
SeverityLevel = Medium;
OPC Server – Subscription
OPC server can subscribe a number of controllers from both Data Access and Alarm
and Event part. Thus, each subscribed controller may have one or two system alarms
for its disposal, depending on number of subscription to controller from OPC server.
These system alarms must be created in a moment of corresponding connection i.e.
subscription establishing.
The SrcNameSuffix for Data Access subscriptions group is:
SrcNameSuffix = SubDataAccess
Example: SourceName = 172.16.85.90:22-SubDataAccess
The SrcNameSuffix for Alarm and Event subscriptions group is:
SrcNameSuffix = SubAlarmEvent
Example: SourceName = 172.16.85.90:22-SubAlarmEvent
The ConditionName for these system alarms is supposed to provide a unique
combination of SrcName and ConditionName (since SrcName is the same for whole
category). Thus, ConditionName has form that contains controller IP address.
Example: ConditionName = 172.16.85.90:2-ConnectionError
The following category of system alarms and system simple events handle errors
and warnings concerning connection towards subscribed controllers.
390
3BSE040935-511
Appendix B System Alarms and Events
OPC Server – Subscription
SrcNameSuffix = SubDataAccess
Each controller subscribed from Data Access should have one system alarm for its
disposal. Note that these system alarms shall be:
•
defined when a new subscription (connection) is established
•
activated when an error occurs on this connection
•
inactivated when all errors are corrected or disappeared
•
deleted when subscription is removed
Condition name has form that includes subscribed controller IP address. It is created
dynamically but last part is always the same: "-ConnectionError".
Example: Condition name = 10.46.37.121:2-ConnectionError.
System Alarm ConnectionError to DA subscription
SrcNameSuffix = SubDataAccess;
Condition name = -ConnectionError;
Message = "(5500) Connection error to DA subscribed controller";
Severity Level = Critical;
SrcNameSuffix = SubAlarmEvent
Each controller subscribed from Alarm and Event should have one system alarm for
its disposal. Note that these system alarms shall be:
•
defined when a new subscription (connection) is established
•
activated when an error occurs on this connection
•
inactivated when all errors are corrected or disappeared
•
deleted when subscription is removed
Condition name has form that includes subscribed controller IP address. It is created
dynamically but last part is always the same: "-ConnectionError".
Example: Condition name = "10.46.37.121:2-ConnectionError".
3BSE040935-511
391
Controller – Software
Appendix B System Alarms and Events
System Alarm ConnectionError to AE subscription
SrcNameSuffix = SubAlarmEvent;
Condition name = -ConnectionError;
Message = "(6500) Connection error to AE subscribed controller";
Severity Level = Critical;
Controller – Software
All system alarms and system simple events triggered by base code belongs to this
group.
This is important to note that system alarms and system simple events issued by
protocol specific code may belong to this group. Normally system alarms and
system simple events issued by protocol specific code are handled within 'Hardware
group'. Under certain circumstances when it is necessary to define errors or
warnings that are not cowered by HW state error handling, this group i.e.
corresponding dedicated SrcNameSuffix should be used. The following set of
source name suffixes are defined for this group.
•
_SWFirmware - for base code
•
_SW1131Task - for 1131 task execution specific code
•
_SWTargets - for HW and OS abstraction layer of the base code
•
_SWInsum-, _SWS100-, _SWMB300-, _SWProfibus-, _SWModbus- 1for
protocol specific code
SrcNameSuffix = _SWFirmware
System Alarm HeapFull
SrcNameSuffix = _SWFirmware;
Condition name = HeapFull;
Message = "(1000) The Heap is full";
SeverityLevel = High;
1.
392
System alarms and system simple events generated by respective communication protocol are described in the
online help function for respective protocol.
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
System Alarm ErrorHandler sum alarm
SrcNameSuffix = _SWFirmware
Condition name = ErrorHandler;
Message = "(1001) ErrorHandler sum alarm created";
SeverityLevel = Medium;
System Alarm Data transfer failed during FW-upgrade of Alarm&Event
This alarm is generated when Alarm&Event failed in the transfer of
Alarm&Event data from Primary CPU to Trainee CPU. It shows how many
items of different Alarm&Event data that failed. The consequence after
upgrade could be that inactive alarms disappear but active alarms will be
activated again.
SrcNameSuffix = _SWFirmware;
Condition name = HeapFull;
Message = "(1002) Alarm&Event failed in FW-upgrade. No of Static alarms =
{1}. No of Simple events = {2}. No of Dynamic alarms = {3}. No of SOEevents = {4}";
{1} = Number of failed items.
{2} = Number of failed items.
{3} = Number of failed items.
{4} = Number of failed items.
SeverityLevel = High;
System Simple Event EventNotificationLost
An event notification was lost. This can happen when the particular OPCServer or printer queue containing event notification is full. A system simple
event is generated when there is space again in this queue. After this the
missing information about alarms in the subscribing systems-OPC Servers is
updated, but this does not mean that all missed events are regenerated.
SrcNameSuffix = _SWFirmware;
Message = "(1010) Lost event notification(s) to {1}";
{1} = The remote systems (the OPC Servers) IP address when generated
event indicates full OPC-Server queue or with string "local printer" when
there is a lost event notification from a filled buffer in printer queue.
Severity Level = Medium;
3BSE040935-511
393
Controller – Software
Appendix B System Alarms and Events
System Simple Event Alarm definition failed
An attempt to define a process alarm in controller, or a system alarm in
controller or in OPC server was not successfully completed.
SrcNameSuffix = _SWFirmware;
Message = "(1011) Alarm definition failed for {1}, {2}";
{1} = Source name
{2} = Condition name
Severity Level = Low;
System Simple Event Undeclared External event
A low level event issued by external device is received, but no declaration was
found in applications.
SrcNameSuffix = _SWFirmware;
Message = "(1012) Undeclared external event; {1}";
{1} = Signal ID and new value delivered by low level event.
Severity Level = Medium;
System Simple Event Event notification(s) lost during firmware upgrade
Generated if events are lost during firmware upgrade
SrcNameSuffix = _SWFirmware;
Message = "(1014) Event notification(s) lost during firmware upgrade"
SeverityLevel = Medium
System Simple Event Alarm definition(s) failed during firmware upgrade
Generated if there are attempting to create alarms during firmware upgrade.
SrcNameSuffix = _SWFirmware;
Message = "(1015) Alarm definition(s) failed during firmware upgrade"
SeverityLevel = Medium
System Simple Event CommandedSwitchover
The system event below is issued when a commanded switchover has
successfully been executed.
394
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
SrcNameSuffix = _SWFirmware;
Message = "(1020) CPU Switchover was commanded";
SeverityLevel = Medium;
System Simple Event CommandedSwitchoverFailed
The system event below is issued when a commanded switchover has been
unsuccessfully executed.
SrcNameSuffix = _SWFirmware;
Message = "(1021) CPU Switchover command failed";
SeverityLevel = Medium;
System Simple Event Reset of backup CPU was commanded
The system event below is issued when a commanded reset of backup CPU has
successfully been executed.
SrcNameSuffix = _SWFirmware;
Message = "(1022) Reset of backup CPU was commanded";
SeverityLevel = Medium;
System Simple Event Reset of backup CPU command failed
The system event below is issued when a commanded reset of backup CPU has
unsuccessfully been executed.
SrcNameSuffix = _SWFirmware;
Message = "(1023) Reset of backup CPU command failed";
SeverityLevel = Medium;
System Simple Event Error found in DataToSimpleEvent
The system event below is generated during calls to DataToSimpleEvent
function block.
SrcNameSuffix = _SWFirmware;
Message = "(1030) AE setting NamValItem/LogStrings to low";
Message = "(1031) Error in FB parameters";
Message = "(1032) Data overflow in communication buffer";
SeverityLevel = Medium;
3BSE040935-511
395
Controller – Software
Appendix B System Alarms and Events
System Simple Event Reset of controller forces performed
System event generated from Access Management. Message when Override
Control has made a reset of controller forces.
SrcNameSuffix = _SWFirmware;
Message = "(1033) Reset of controller forces performed";
SeverityLevel = Medium;
System Simple Event Ack of event denied
System event generated from Access Management, when acknowledgement of
an alarm is denied.
SrcNameSuffix = _SWFirmware;
Message = "(1034) Acknowledge of event denied ({1}, {2})";
{1} = source name of the alarm
{2} = condition name of the alarm
SeverityLevel = Medium;
System Simple Event No configuration image found at compact flash card
The system event below is issued when a compact flash card, without a
configuration image, is detected during startup of controller.
SrcNameSuffix = _SWFirmware;
Message = ">(1040) No configuration image found at compact flash
card";
SeverityLevel = Medium;
System Simple Event Configuration image found at compact flash card is
corrupt
The system event below is issued when a compact flash card, with a corrupt
configuration image, is detected during startup of controller
SrcNameSuffix = _SWFirmware;
Message = "(1041) Configuration image found at compact flash is
corrupt";
SeverityLevel = Medium;
396
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
System Simple Event Configuration image found at compact flash does not
match controller
SrcNameSuffix = _SWFirmware;
Message = "(1042) Configuration image found at compact flash does not
match controller"
SeverityLevel = Medium
System Simple Event Configuration load is started from compact flash
SrcNameSuffix = _SWFirmware;
Message = "(1043) Configuration load is started from compact flash"
SeverityLevel = Medium
System Simple Event Configuration image found at compact flash has different
format
SrcNameSuffix = _SWFirmware;
Message = "(1044) Configuration image found at compact flash has
different format"
SeverityLevel = Medium
3BSE040935-511
397
Controller – Software
Appendix B System Alarms and Events
System Simple Event Configuration image found at compact flash does not
match controller
The system event below is issued when a compact flash card, with a
configuration image created for another type of CPU, is detected during startup
of controller.
SrcNameSuffix = _SWFirmware;
Message = "(1042) Configuration image found at compact flash does not
match controller"
SeverityLevel = Medium;
System Simple Event Configuration load is started from compact flash
The system event below is issued when a compact flash card, with a valid
configuration image, is detected during startup of controller.
SrcNameSuffix = _SWFirmware;
Message = "(1043) Configuration load is started from compact flash"
SeverityLevel = Medium;
System Simple Event Configuration image found at compact flash has not equal
format
The system event below is issued when a compact flash card, with a
configuration image created in a format not supported, is detected during
startup of controller.
SrcNameSuffix = _SWFirmware;
Message = "(1044) Configuration image found at compact flash has
different format"
SeverityLevel = Medium;
System Simple Event
SrcNameSuffix = _SWFirmware;
Message = “(1045) Write attempt to constant variable {1} of instance
{2}";
Severity Level = High;
398
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
System Simple Event
SrcNameSuffix = _SWFirmware;
Message = “(1046) System variable LogConstAbuse set to 0 since limit on
{1} messages reached";
Severity Level = High;
This message can occur on process alarms when the alarms have not executed yet.
For example, after an OLU. It should only occur temporarily and will disappear
when the execution has started and the alarm have changed state or when OPC/AE
clients (example PPA) are refreshed.
Message = “(1047) The message text is temporarily unavailable since the
alarm is issued before 1131 has been run.";
Severity Level = Medium;
3BSE040935-511
399
Controller – Software
Appendix B System Alarms and Events
SrcNameSuffix = _SW1131Task
System Alarm TaskAbort
SrcNameSuffix = _SW1131Task;
Condition name = TaskAbort;
Message = "(2000) Execution time too long in Task {1}";
{1} = Task name will be added to message, for example, "Execution time
too long in Task Fast"
Severity Level = Fatal;
System Simple Event Interval time in ordinary tasks inc
SrcNameSuffix = _SW1131Task;
Message = "(2001) Interval time in ordinary tasks increased {1}%";
{1} = The increase of the interval time in percent with the precision of one
decimal.
Severity Level = Medium;
System Simple Event Interval time in ordinary tasks dec
SrcNameSuffix = _SW1131Task;
Message = "(2002) Interval time in ordinary tasks decreased {1}%";
{1} = The decrease of the interval time in percent with the precision of
one decimal.
Severity Level = Medium;
System Simple Event Interval Time was changed
Only used for tasks executing at Time-Critical priority.
SrcNameSuffix = _SW1131Task;
Message = "(2003) Interval time changed to {1} ms. Task={2}";
{1} = New interval time ,
{2} = Name of the task.
Severity Level = Medium;
400
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
System Alarm Latency high in normal tasks
The alarm is activated when actual latency is 70 % of max latency.
SrcNameSuffix = _SW1131Task;
Message On = "(2004) Latency high in task {1}, {2} ms"
{1} = Name of the task,
{2} = Actual latency.
Message Off = "(2004) Latency high inactive "
Condition name = High Latency
SeverityLevel = Medium
System Alarm Latency high in time critical task
The alarm is activated when actual latency is 70 % of max latency.
SrcNameSuffix = _SW1131Task;
Message On = "(2005) Latency high in task {1}, {2} ms"
Message Off = "(2005) Latency high inactive "
{1} = Name of the task,
{2} = Actual latency.
Condition name = High Latency
SeverityLevel = Medium
SrcNameSuffix = _SWTargets
System Simple Event RCU error detected in the Primary CPU
SrcNameSuffix = _SWTargets;
Message = "(4000) Primary CPU: RCUError(0x{2})";
{2} = Content of the RCU Error Register in hexadecimal format.
Severity Level = High;
This event is issued from the RCU Driver if redundancy has been shut down due to
an internal error in the RCU Driver found at the end of synchronization.
System Simple Event
SrcNameSuffix = _SWTargets;
Message = “(4025) Failed to set RCU Driver state to
3BSE040935-511
401
Controller – Software
Appendix B System Alarms and Events
eRCUTakeoverPossible";
Severity Level = High;
This event is issued from the RCU Driver if redundancy has been shut down due to
an internal error in the RCU Driver found at the start of synchronization.
System Simple Event
SrcNameSuffix = _SWTargets;
Message = “(4026) Failed to set RCU Driver state to eRCUNormal";
Severity Level = High;
This event is issued from the RCU Driver if Online Upgrade has been suspended
due to an internal error in the RCU Driver.
System Simple Event
SrcNameSuffix = _SWTargets;
Message = “(4027) Failed to set RCU Driver state to eRCUOLU";
Severity Level = High;
System Simple Event RCU test error detected in the Primary CPU
SrcNameSuffix = _SWTargets;
Message = "(4001) Primary CPU: RCUTestError({2}, 0x{3})";
{2} = Test Number
1 = RCU Register test
2 = Log Parity test
3 = Log test
4 = Log Range test
5 = I O Emulation test
6 = CPU Bus Timeout test
{3} = The Error status is printed in hexadecimal format.
Severity Level = High;
System Simple Event Dual test error detected in the Primary CPU
SrcNameSuffix = _SWTargets;
Message = "(4002) Primary CPU: DualTestError({2}, 0x{3})";
{2} = The Dual Test status (see Table 46)
402
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
{3} = The Error status is printed in hexadecimal format.
Severity Level = High;
Table 46. Dual Test status.
Message
Description
CPUCEXBusMsgSendError
Failed to send test message to the Backup CPU
CPUCEXBusMessageError
Failed to receive test message from the Backup CPU
CheckpointTestError
Failed to upgrade memory of the Backup CPU
3BSE040935-511
403
Controller – Software
Appendix B System Alarms and Events
System Simple Event Backup CPU CEX-Bus test error detected in the Primary
CPU
SrcNameSuffix = _SWTargets;
Message = "(4003) Primary CPU: BkpCEXBusTestError({2}, 0x{3})";
{2} = The Test status (see Table 47)
{3} = The Error status is printed in hexadecimal format.
Severity Level = High;
Table 47. Test status from Backup CPU
Message
Description
CPUCEXBusMsgSendError
Failed to send test message to the Backup
CPU
CPUCEXBusMessageError
Failed to receive response message from the
Backup CPU
CEXBusTestError
Failed to test the CEX-Bus interface in the
Backup CPU
System Simple Event Error detected in the Primary CPU
SrcNameSuffix = _SWTargets;
Message = "(4004) Primary CPU: {2} in state {3}";
{2} = The name of the detected error (see Table 48)
{3} = The state when the error was detected.
Severity Level = High;
Table 48. The name of the detected error.
404
Message
Description
SDCError
RCU Service data channel error
RCUConnectorOpen
The RCU Link cable is not connected to the own CPU
RCUOtherConnectorOpen
The RCU Link cable is not connected to the peer CPU
RCUDrvErro
Failed when calling the RCU driver
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Table 48. The name of the detected error.
Message
Description
InitCommError
Failed to initialize interrupt handling with the peer CPU
InformCommParamError
Failed to inform other CPU about communication
parameters
GetCommParamError
Failed to get communication parameters from other
CPU
BkpCPUNotAlive
The Backup CPU is not alive
BkpCPUCEXBusError
Backup CPU not connected to the CEX-bus
BkpCPUIllegalExternalState Backup CPU has an illegal External state
Timeout
Backup CPU has not sent a response message within
a specified timeout time
CloningStartError
Failed to start cloning in state Upgrading
CloningNotCompletedError
Cloning not completed in state Unconfirmed
CloningError
Cloning failed in state Synchronized
BkpFirmwareError
Backup CPU’s firmware id not equal to Primary CPU’s
firmware id
System Simple Event A Backup CPU is recognized and started
SrcNameSuffix = _SWTargets;
Message = "(4005) Primary CPU: Backup CPU started";
Severity Level = Medium;
System Simple Event The system has reached the Synchronized state
The Backup CPU is ready to take-over if the Primary CPU fails
SrcNameSuffix = _SWTargets;
Message = "(4006) Primary CPU: Synchronized state";
Severity Level = Medium;
3BSE040935-511
405
Controller – Software
Appendix B System Alarms and Events
System Simple Event Switchover has occurred
SrcNameSuffix = _SWTargets;
Message = "(4007) Switchover to {2} has occurred";
{2} = "Lower CPU" or "Upper CPU"
Severity Level = Medium;
System Simple Event Report of Backup CPU error after a switchover
SrcNameSuffix = _SWTargets;
Message = "(4008) Primary CPU: {2} in {3}";
{2} = The error reported from the backup CPU
{3} = The position reported from the backup CPU
Severity Level = Medium;
System Simple Event The Backup CPU has stopped
SrcNameSuffix = _SWTargets;
Message = "(4009) Primary CPU: Backup CPU stopped ({2})";
{2} = Stop reason (seeTable 49)
Severity Level = High;
Table 49. Stop reason.
Message
Description
BkpCPUCEXBusError
Backup CPU not connected to the CEX bus
BkpHaltRequest
A Backup CPU problem has been detected in the Primary
CPU. The Backup CPU however seems fully alive
BkpCPUNotAlive
The Backup CPU has stopped or been removed without
reporting its status to the Primary CPU
Status sent from backup CPU
Backup CPU status received via the CEX bus
System Simple Event The Primary CPU has halted
SrcNameSuffix = _SWTargets;
Message = "(4010) Primary CPU: CPU halted";
Severity Level = High;
406
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
System Simple Event RCU error detected in the Backup CPU
SrcNameSuffix = _SWTargets;
Message = "(4020) Backup CPU: RCUError(0x{2})";
{2} = The contents of the RCU Error Register in hexadecimal format.
Severity Level = High;
System Simple Event RCU test error detected in the Backup CPU
SrcNameSuffix = _SWTargets;
Message = "(4021) Backup CPU: RCUTestError({2}, 0x{3})";
{2} = Test Number (see Table 50)
{3} = Error Status. in hexadecimal format.
Severity Level = High;
Table 50. Test Number
Test Number
Error Status
1
RCU Register test
2
Log Parity test
3
Log test
4
Log Range test
5
I/O Emulation test
6
CPU Bus Timeout test
System Simple Event Dual test error detected in the Backup CPU
SrcNameSuffix = _SWTargets;
Message = "(4022) Backup CPU: DualTestError({2}, 0x{3})";
{2} = Dual Test status (see Table 51)
{3} = Error Status. in hexadecimal format.
Severity Level = High;
3BSE040935-511
407
Controller – Software
Appendix B System Alarms and Events
Table 51. Dual Test status.
Message
Description
CPUCEXBusMsgSendError Failed to send test message to the Primary
CPU
CPUCEXBusMessageError
Failed to receive test message from the
Primary CPU
RCUDrvError
Failed when calling the RCU driver to set
threshold value for the Log Data Buffer
System Simple Event Error detected in the Backup CPU
SrcNameSuffix = _SWTargets;
Message = "(4023) Backup CPU: {2} in state {3}";
{2} = The name of the detected error (see Table 52)
{3} = The state when the error was detected.
Severity Level = High;
Table 52. The name of the detected error.
408
Message
Description
SDCError
RCU Service data channel error
RCUConnectorOpen
The RCU Link cable is not connected to the own
CPU
RCUOtherConnectorOpen
The RCU Link cable is not connected to the
peer CPU
RCUDrvError
Failed when calling the RCU driver
InitCommError
Failed to initialize interrupt handling with the
peer CPU
InformCommParamError
Failed to inform other CPU about
communication parameters
GetCommParamError
Failed to get communication parameters from
other CPU
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Table 52. The name of the detected error. (Continued)
Message
Description
EqualityCheckFailed
Memory upgrading of Backup CPU has failed
RCUMessageHaltReceived A Halt request has been received from the
Primary CPU
PrimCPUExitConnection
Primary CPU has exit connection
System Simple Event The Backup CPU has halted
SrcNameSuffix = _SWTargets;
Message = "(4024) Backup CPU: CPU halted";
Severity Level = High;
System Simple Event Stopped due to ModuleBus inaccessible from Backup
CPU
This event is issued from the MBTestMC unit if the Backup CPU has been stopped
due redundancy supporting modules on the module bus turned out to be inaccessible
from the Backup CPU.
SrcNameSuffix = _SWTargets;
Message = "(4030) Stopped due to ModuleBus inaccessible from Backup
CPU";
Severity Level = "High";
This event is issued from the RCU Driver if the Backup CPU has been halted due to
an overload situation in the redundancy control HW.
System Simple Event
SrcNameSuffix = _SWTargets;
Message = “(4028) RCU LDB overflow has occured in Backup/trainee
PM";
Severity Level = High;
3BSE040935-511
409
Controller – Software
Appendix B System Alarms and Events
This event is issued if the Backup CPU has been halted during start-up due to that it
uses the same MAC address as the Primary CPU. (This can happen if the original
Primary CPU unit has been removed from a redundant controller and the same unit
is later re-inserted as spare part in the same running controller.)
System Simple Event
SrcNameSuffix = _SWTargets;
Message = “(4042) Backup CPU has the same MAC Address as Primary
CPU";
Severity Level = High;
System Simple Event Switched over due to ModuleBus inaccessible from
Primary CPU
This event is issued from the MBTestMC unit if a switch-over occurred due to
redundancy supporting modules on the module bus turned out to be inaccessible
from the Primary CPU.
SrcNameSuffix = _SWTargets;
Message = "(4031) Switched over, ModuleBus inaccessible from Primary
CPU";
Severity Level = High;
Events from Network Interface Supervision
System Simple Event Backup CPU halted: Bad Network interface
This event is issued from the NIS primary task if the Backup CPU has been halted
due to both network interface in Backup CPU are not working properly.
SrcNameSuffix = _SWTargets;
Message = "(4040) Backup CPU halted: Bad Network interface";
Severity Level = High;
410
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Events from Checking of Available MAC address in Backup
System Simple Event No MAC address in Backup CPU
This event is issued to the primary PM if the backup PM has no MAC address.
SrcNameSuffix = _SWTargets;
Message = "(4041) No MAC address in backup PM";
Severity Level = High;
Events from Modulebus driver
System Simple Event Diverse pointer check
This event is issued from the check of pointers to the DPM which is used in all
accesses to read/write data to/from IO modules.
SrcNameSuffix = _SWTargets;
Message = "(4050) Fatal Error in diverse pointer check";
Severity Level = Fatal;
System Simple Event Failed to send message to queue
SrcNameSuffix = _SWTargets;
Message = "(4051) Mbus msgQ failed: control of Primary/Backup Leds
not run";
Severity Level = Low;
System Simple Event Null pointer
SrcNameSuffix = _SWTargets;
Message = "(4052) Null pointer check failed";
Severity Level = Fatal;
System Simple Event Failed to create message queue
SrcNameSuffix = _SWTargets;
Message = "(4053) Failed to create message queue";
Severity Level = High;
System Simple Event Test of RAM Error in MBM1 failed
3BSE040935-511
411
Controller – Software
Appendix B System Alarms and Events
SrcNameSuffix = _SWTargets;
Message = "(4054) Cyclic test of Ram Error in MBM1 failed";
Severity Level = Critical;
System Simple Event Runtime RAM Error in MBM1
SrcNameSuffix = _SWTargets;
Message = "(4055) Runtime Ram Error in MBM1";
Severity Level = Critical;
System Simple Event Diagnostic test of CRC32 calculator in FPGA failed
SrcNameSuffix = _SWTargets;
Message = "(4056) Cyclic test of CRC32 calculator failed in {1}";
{1} = Cause of failure. Example: checkFailed, timeout
Severity Level = Critical;
System Simple Event Switch PM is performed via errorHandler
SrcNameSuffix = _SWTargets;
Message = "(4057) Failure in SM detected by PM";
Severity Level = Critical;
System Simple Event Switch PM is performed via errorHandler due to Bus
Error
SrcNameSuffix = _SWTargets;
Message = "(4058) Try to switch PM due to Bus Error";
Severity Level = Critical;
System Simple Event CPU interface error in MBM1
SrcNameSuffix = _SWTargets;
Message = "(4059) CPU interface error in FPGA";
Severity Level = Critical;
Events from the MMU
System Simple Event Software errors
412
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
SrcNameSuffix = _SWTargets;
Message = "(4060) Software error detected by MMU";
Severity Level = Fatal;
System Simple Event Memory violation
SrcNameSuffix = _SWTargets;
Message = "(4061) Attempted write access in write-protected memory";
Severity Level = Fatal;
System Simple Event MMU checker error
SrcNameSuffix = _SWTargets;
Message = "(4062) Unexpected write in protected memory";
Severity Level = Critical;
System Simple Event DMA checker error
SrcNameSuffix = _SWTargets;
Message = "(4063) DMA Checker time. Test failed";
Severity Level = Critical;
System Simple Event Primary CPU: DMA memory violation
SrcNameSuffix = _SWTargets;
Message = "(4064) Primary CPU: DMA memory violation at {2}"
{2} = General fail address information
SeverityLevel = High
Events from FW Integrity Verification
Indication that FW CRC did not match original in primary PM.
SrcNameSuffix = _SWTargets;
Message = "(4070) FW Integrity Verification primary:CRC did not
match original";
Severity Level = Medium;
Indication that FW CRC did not match original in backup PM.
3BSE040935-511
413
Controller – Software
Appendix B System Alarms and Events
SrcNameSuffix = _SWTargets;
Message = "(4071) FW Integrity Verification backup:CRC did not match
original";
Severity Level = Medium;
Indication that FW CRC did not match in stand alone PM.
SrcNameSuffix = _SWTargets;
Message = "(4072) FW Integrity Verification standalone:CRC did not
match original";
Severity Level = Medium;
Address parameter failure in FW Integrity Verification.
SrcNameSuffix = _SWTargets;
Message = "(4073) FW Integrity Verification: Address parameter
failure";
Severity Level = Medium;
System Simple Event CRC error in FW Integrety Verification
SrcNameSuffix = _SWTargets;
Message = "(4074) FW Integrity Verification trainee CRC did not match
original"
SeverityLevel = Critical
Events from the Heap: Software Errors
SrcNameSuffix = _SWTargets;
Message = "(4080) Software error detected by Heap manager";
Severity Level = Fatal;
Events from the Heap: Memory Violation
SrcNameSuffix = _SWTargets;
Message = "(4081) Heap violation during allocation of an element";
Severity Level = Fatal;
414
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Message = "(4082) Heap violation during deallocation of an element";
Severity Level = Fatal;
Message = "(4083) Null element is deallocated in the heap";
Severity Level = Fatal;
Message = "(4084) Corrupt element is deallocated in the heap";
Severity Level = Fatal;
Message = "(4085) Corrupt elements are detected after a power fail";
Severity Level = Fatal;
Message = "(4086) The Protected Heap is out of memory";
Severity Level = Low;
Message = "(4087) The Shared Heap is out of memory";
Severity Level = Low;
Message = "(4093) The max boundary size of an element is exceeded in
the Shared Heap";
Severity Level = Medium;
Message = "(4094) The max boundary size of an element is exceeded in
the Protected Heap";
Severity Level = Medium;
Events from the Heap: Heap Checker Error
System Simple Event MemFree error - CPU Switch
SrcNameSuffix = _SWTargets;
Message = "(4088) Heap Checker detects a corrupt element during
deallocation of an element";
Severity Level = Critical;
System Simple Event MemFree error - no CPU Switch
SrcNameSuffix = _SWTargets;
Message = "(4089) Heap Checker detects a corrupt element during
deallocation of an element";
Severity Level = Fatal;
3BSE040935-511
415
Controller – Software
Appendix B System Alarms and Events
System Simple Event Synchronous heap check error - logging
SrcNameSuffix = _SWTargets;
Message = "(4090) Corrupt element during synchronous heap check";
Severity Level = Low;
System Simple Event Cyclic heap check error - CPU Switch
SrcNameSuffix = _SWTargets;
Message = "(4091) Corrupt element during cyclic heap check";
Severity Level = Critical;
System Simple Event Cyclic heap check error - no CPU Switch
SrcNameSuffix = _SWTargets;
Message = "(4092) Corrupt element during cyclic heap check";
Severity Level = Fatal;
System Simple Event Max boundary size exceeded in the Shared Heap
SrcNameSuffix = _SWTargets
Message = "(4093) The max boundary size of an element is exceeded in
the Shared Heap."
SeverityLevel = Medium
System Simple Event Max boundary size exceeded in the Protected Heap
SrcNameSuffix = _SWTargets
Message = (4094) The max boundary size of an element is exceeded in the
Protected Heap."
SeverityLevel = Medium
Events from Irq Supervisor
These messages are short (twelve characters) since most of them have to be printed
from interrupt context when an irq error has occurred, which means there is only a
very small time margin.
SrcNameSuffix = _SWTargets;
416
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Message = "(4100) Irq error. Unable to spawn Reset Irq Supervisor
thread";
Severity Level = Medium;
Message = "(4101) Irq error. MSCallout array full; not possible to add
SuperviseIrq; the IrqSupervision thread will be suspended";
Severity Level = Medium;
Message = "(4102) Irq error. Irq supervisor: Irq timed out; primary PM
will be shut down";
Severity Level = Medium;
Message = "(4103) Irq error. Irq supervisor: Irq timed out; backup PM
was shut down";
Severity Level = Medium;
Message = "(4104) Irq error. Irq supervisor: Irq timed out error in
standalone PM";
Severity Level = Medium;
Message = "(4105) Irq error. Unable to create a OS periodic timer, the
IrqSupervision thread will be suspended";
Severity Level = Medium;
Message = "(4106) Iirq error. Unable to raise thread priority, the
IrqSupervision thread will be suspended";
Severity Level = Medium;
Message = "(4107) Irq supervisor: Irq timed out; trainee PM was shut
down"
SeverityLevel = Medium
Events from CEX Bus Interrupt Handler
SrcNameSuffix = _SWTargets;
Message = "(4110) Hanging CEX IRQ: All CEMs on the upper CEX bus
segment are disabled";
Severity Level = Medium;
3BSE040935-511
417
Controller – Software
Appendix B System Alarms and Events
Message = "(4111) Hanging CEX IRQ: All CEMs on the lower CEX bus
segment are disabled";
Severity Level = Medium;
Message = "(4112) Hanging CEX IRQ: The upper PM has been shut
down";
Severity Level = Critical;
Message = "(4113) Hanging CEX IRQ: The lower PM has been shut
down";
Severity Level = Medium;
Message = "(4115) Invalid IRQ CEM {1}: All CEMs on this CEX bus
segment are disabled";
{1} = Module number of interrupting CEM
Severity Level = Medium;
Message = "(4116) Invalid IRQ CEM {1}: All CEMs on this CEX bus
segment are disabled";
{1} = Module number of interrupting CEM.
Severity Level = Medium;
Message = "(4117) Invalid CEX IRQ backup PM: The upper PM has
been shut down";
Severity Level = Medium;
Message = "(4118) Invalid CEX IRQ backup PM: The lower PM has
been shut down";
Severity Level = Medium;
Message = "(4119) Spurious CEX IRQ: {1} spurious IRQs since system
startup";
{1} = Number of spurious IRQ since start
Severity Level = Low;
Message = "(4120) Hanging CEX IRQ: All CEMs on the dir CEX bus
segment are disabled";
Severity Level = Medium;
Message = "(4121) Hanging CEX IRQ: All CEMs on the indir CEX bus
segment are disabled";
Severity Level = Medium;
418
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Message = "(4122) Hanging CEX IRQ: The PM has been shut down";
Severity Level = Critical;
Message = "(4123) Invalid IRQ CEM {1}: All CEMs on this CEX bus
segment are disabled";
{1} = Module number of interrupting CEM
Severity Level = Medium;
Message = "(4124) Invalid IRQ CEM {1}: All CEMs on this CEX bus
segment are disabled";
{1} = Module number of interrupting CEM
Severity Level = Medium;
Message = "(4125) Insufficient memory to create the Reset BC thread";
Severity Level = Medium;
Events from DMA Supervisor
SrcNameSuffix = _SWTargets;
Message = "(4126) Error in DMA Supervisor configuration";
Severity Level = Fatal;
Events from Internal Diagnostics Engine
SrcNameSuffix = _SWTargets;
Message = "(4130) Software error detected by Diagnostic Engine";
Severity Level = Medium;
Message = "(4131) Diagnostic Engine: FDRT deadline passed";
Severity Level = Medium;
Message = "(4132) Diagnostic Engine: Diurnal deadline passed";
Severity Level = Medium;
Events from RAMTest
SrcNameSuffix = _SWTargets;
Message = "(4133) RAMTest Primary Parity error self test;
Severity Level = Critical;
3BSE040935-511
419
Controller – Software
Appendix B System Alarms and Events
Message = "(4134) RAMTest Backup Parity error self test";
Severity Level = Critical;
Message = "(4135) RAMTest Standalone Parity error self test";
Severity Level = Critical;
Message = "(4136) RAMTest Primary Address line test 0x{1}";
{1} = Fail address
Severity Level = Critical;
Message = "(4137) RAMTest Backup Address line test 0x{1}";
{1} = Fail address
Severity Level = Critical;
Message = "(4138) RAMTest Standalone Address line test 0x{1}";
Severity Level = Critical;
{1} = Fail address
Message = "(4139) RAMTest Primary Internal error";
Severity Level = Fatal;
Message = "(4140) RAMTest Backup Internal error";
Severity Level = Fatal;
Message = "(4141) RAMTest Standalone Internal error";
Severity Level = Fatal;
Events from the RCU CRC Checker
SrcNameSuffix = _SWTargets;
Message = "(4142) Hardware error detected by RCU CRC Checker";
Severity Level = Critical;
Events from RAMTest
Message = "(4143) RAMTest Trainee Parity error self test"
SeverityLevel = = Critical
Message = "(4144) RAMTest Trainee Address line test 0x{1}"
{1} = Fail address
SeverityLevel = Critical
420
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Message = "(4145) RAMTest Backup Internal error"
SeverityLevel =Critical
Events from SSPActiveTest
Message = "(4146) SSP error detected by SSPActiveTest"
SeverityLevel = Fatal
Events from HWSetupVerification
These events are issued if HW Setup Verification detected an error in HW Setup.
The message also contains a test label, specifying the failing test.
SrcNameSuffix = _SWTargets;
Message = "(4150) HW Setup Verification in Primary: {1}";
{1} = Subtest strings used to specify the failing test method.
Severity Level = Medium;
Message = "(4151) HW Setup Verification in Backup: {1}";
Severity Level = Medium;
{1} = Subtest strings used to specify the failing test method.
Message = "(4152) HW Setup Verification in Standalone: {1}";
{1} = Subtest strings used to specify the failing test method.
Severity Level = Medium;
Message = "(4153) HW Setup Verification in Trainee: {1}"
{1} = Subtest strings used to specify the failing test method.
SeverityLevel = Critical
Events from EXTCLKSupervision
These events are issued from the EXTCLK Supervision if etiher the EXTCLK
frequency is or the FPGA divider is working incorrect.
SrcNameSuffix = _SWTargets;
Message = "(4160) EXTCLK Error Allowed range {1} us";
{1} = Sleep-time information
Severity Level = Medium;
3BSE040935-511
421
Controller – Software
Appendix B System Alarms and Events
Message = "(4161) EXTCLK Supervision Error: FATAL error";
Severity Level = Medium;
Events from HRESETSupervision
This event is issued from the Oscillator Supervision task if etiher the SPPL or
EXTCLK frequency is working incorrect.
SrcNameSuffix = _SWTargets;
Message = "(4170) HRESET Error asserted by {1}";
{1} = Strings used to specify the signals generating HRESET
Severity Level = High;
Events from Modulebus Driver
System Simple Event Comparision of CRC32 from SM and PM failed
SrcNameSuffix = _SWTargets;
Message = "(4180) MBM1 SM vs PM CRC32 failed, address 0x{1}";
{1} = Address (hexadecimal)
Severity Level = Low;
System Simple Event Failed to create SMDrv in Modulebus
SrcNameSuffix = _SWTargets;
Message = "(4181) Failed to create SMDrv From Modulebus";
Severity Level = Medium;
System Simple Event BusErrorIn interrupt routine
SrcNameSuffix = _SWTargets;
Message = "(4182) Bus Error In Modulebus ISR address 0x{1}";
{1} = Address (hexadecimal)
Severity Level = Critical;
System Simple Event BS Exception in MBM1scanner
SrcNameSuffix = _SWTargets;
Message = "(4183) BS EXCEPTION In MBM1 Scanner";
Severity Level = Critical;
422
3BSE040935-511
Appendix B System Alarms and Events
Controller – Software
Message = "(4184) Incoming safety header failure, address 0x{1}"
{1} = Address (hexadecimal)
SeverityLevel = Medium
Message = "(4185) Primary shutdown due to suspect SM"
SeverityLevel = Medium
Message = "(4186) No answer from SM address 0x{1}, error code 0x{2}"
SeverityLevel = Medium
Message = "(4187) Failure in safety IO, address 0x{1}, error code 0x{2}"
{1} = Address (hexadecimal)
{2} = Error code (hexadecimal)
SeverityLevel = Medium
Events from ModuleBus
System Simple Event
Message = "( (4901) Event overflow in module: {1}{2}"
{1} = Path to ModuleBus unit.
{2} = Unit number.
SeverityLevel = Medium
3BSE040935-511
423
Controller – Hardware
Appendix B System Alarms and Events
Controller – Hardware
Hardware generated system alarms are automatically available when the hardware is
configured. They may however be disabled.
All Hardware Units in the hardware configuration have one system alarm and one
system simple event each for its disposal. The intention is to have a sum alarm and a
sum event for different errors and warnings that can be detected on the hardware
unit.
.
Table 53. Parameters for Hardware Generated System Alarms and Events
Parameters Descriptions
424
Class
All hardware generated system alarms and events have the same
value of parameter 'Class' that is determined by the value of CPU
setting 'AE System AE class'.
Severity
Values of severity are defined through the CPU setting 'AE System
AE high severity' for hardware generated system alarms, respective
'AE System AE medium severity' for hardware generated system
simple events.
3BSE040935-511
Appendix B System Alarms and Events
Controller – Hardware
Table 53. Parameters for Hardware Generated System Alarms and Events
Parameters Descriptions
Message
The message contains reference to more detailed information,
because each alarm is a sum alarm that can indicate many different
errors on the unit. This information is given in the description of
Errors and Warnings in Control Builder.
The error code is stored in two 32 bit words first word is
ErrorsAndWarnings and the second is ExtendedStatus.
In each hardware generated system alarm or event message,
ErrorsAndWarnings and ExtendedStatus bit patterns are translated
into a text in the OPC-server. General status bits are translated into
a explaining text e.g. "I/O configuration error". Device specific bits
from ErrorsAndWarnings are translated into a text in the
OPC-server, if a matching text is available in the hardware definition.
Otherwise they are displayed as "Device specific bit xx" in the
message e.g. "Device specific bit 31". The same goes for
ExtendedStatus. If a matching text is not available in the hardware
definition, unit specific bits from ExtendedStatus are displayed as
"Extended status bit xx" in the message e.g. "Extended status bit 0".
The bits for every unit are explained later in this section.
Example
"Controller_1 (0000) I/O configuration error, Device specific bit 31,
Extended status bit 0"
If the Unit in this example is a PM865, "Device specific bit 31"=
"Battery low" and "Extended status bit 0" = "Backup CPU stopped"
In the controller log ErrorsAndWarnings and ExtendedStatus are
presented as HEX format.
Example:
"E 2004-03-08 10:25:06.677 On Unit= 2 HWError Controller_1
Errorcode=16#80004000 16#00000001 (0000) See HW-tree
3BSE040935-511
425
Alarms and Events Common for all Units
Appendix B System Alarms and Events
Table 53. Parameters for Hardware Generated System Alarms and Events
Parameters Descriptions
SrcName
The syntax for the source name in the SrcName parameter is
dynamically based on the IP address together with the
SrcNameSuffix that is the hardware unit address in the hardware
tree configuration.
Example: IP address (172.16.85.33) + SrcNameSuffix (2.5.101)
= "172.16.85.33-2.5.101".
CondName
All hardware generated system alarms have "HWError" as common
condition name in the CondName parameter.
AckRule
Ack Rule 5 is used for these system alarms,.
Alarms and Events Common for all Units
Table 54 lists those status bits that have the same meaning for all hardware units.
Note however that different units have different capabilities. A specific unit will
typically only be able to generate alarms and events for an assortment of the
common status bits.
Table 54. General status bit ErrorsAndWarnings
Bit
Status Bit
Value
0
ConnectionDown
16#00000001
Error
Alarm
High
Connection down
1
IoError
16#00000002
Error
Alarm
Medium
I/O error
2
ModuleMissing
16#00000004
Error
Alarm
High
Module missing
3
WrongModuleType
16#00000008
Error
Alarm
High
Wrong module
type
4
StatusChannelError
16#00000010
Warning
Alarm
Medium
Channel error
5
IoWarning
16#00000020
Warning
Event
Low
I/O warning
6
StatusUnderflow
16#00000040
Warning
Alarm
Low
Underflow
7
StatusOverflow
16#00000080
Warning
Alarm
Low
Overflow
8
StatusForced
16#00000100
Warning
Event
Low
Forced
426
Indication Generation Severity
Description
3BSE040935-511
Appendix B System Alarms and Events
Alarms and Events Common for all Units
Table 54. General status bit ErrorsAndWarnings (Continued)
Bit
Status Bit
Value
9
WatchdogTimeout
16#00000200
Error
Alarm
High
Watchdog timeout
10
DeviceFailure
16#00000400
Error
Alarm
High
Device failure
11
DeviceNotFound
16#00000800
Error
Alarm
High
Device not found
12
WrongDeviceType
16#00001000
Error
Alarm
High
Wrong device type
13
IOConnectError
16#00002000
Error
Alarm
Medium
I/O connection
error
14
IOConfigError
16#00004000
Error
Alarm
Medium
I/O configuration
error
15
HWConfigError
16#00008000
Error
Alarm
High
Hardware
configuration error
16
GeneralError 1
16#00010000
Error
–
–
–
16#00020000
Warning
–
–
–
18 RedWarningPrimary 2 16#00040000
Warning
Event
Low
Warning on
primary unit
RedWarningBackup 2 16#00080000
Warning
Event
Low
Warning on
backup unit
17
19
GeneralWarning
1
Indication Generation Severity
Description
20
RedErrorBackup 2
16#00100000
Warning
Alarm
Medium
Error on backup
unit
21
Reserved
16#00200000
–
–
–
–
22
DeviceSpecific10
16#00400000
3
3
3
3
23
DeviceSpecific9
16#00800000
3
3
3
3
24
DeviceSpecific8
16#01000000
3
3
3
3
25
DeviceSpecific7
16#02000000
3
3
3
3
26
DeviceSpecific6
16#04000000
3
3
3
3
27
DeviceSpecific5
16#08000000
3
3
3
3
28
DeviceSpecific4
16#10000000
3
3
3
3
3BSE040935-511
427
Alarms and Events Common for all Units
Appendix B System Alarms and Events
Table 54. General status bit ErrorsAndWarnings (Continued)
Bit
Status Bit
Value
Indication Generation Severity
Description
29
DeviceSpecific3
16#20000000
3
30
DeviceSpecific2
16#40000000
3
3
3
3
31
DeviceSpecific1
16#80000000
3
3
3
3
1
2
3
3
3
3
Used together with other status bits.
Used only if hte unit is configured as a redundant unit.
Depends on the specific hardware device ,defined within hardware definition file.
Table 55. General status bit ExtendedStatus
Bit
Status Bit
Value
0
ExtendedStatus1
16#00000001
1
1
1
1
1
ExtendedStatus2
16#00000002
1
1
1
1
2
ExtendedStatus3
16#00000004
1
1
1
1
3
ExtendedStatus4
16#00000008
1
1
1
1
4
ExtendedStatus5
16#00000010
1
1
1
1
5
ExtendedStatus6
16#00000020
1
1
1
1
6
ExtendedStatus7
16#00000040
1
1
1
1
7
ExtendedStatus8
16#00000080
1
1
1
1
8
ExtendedStatus9
16#00000100
1
1
1
1
9
ExtendedStatus10
16#00000200
1
1
1
1
10
ExtendedStatus11
16#00000400
1
1
1
1
11
ExtendedStatus12
16#00000800
1
1
1
1
12
ExtendedStatus13
16#00001000
1
1
1
1
13
ExtendedStatus14
16#00002000
1
1
1
1
14
ExtendedStatus15
16#00004000
1
1
1
1
15
ExtendedStatus16
16#00008000
1
1
1
1
16
ExtendedStatus17
16#00010000
1
1
1
1
428
Indication Generation Severity Description
3BSE040935-511
Appendix B System Alarms and Events
Alarms and Events Common for all Units
Table 55. General status bit ExtendedStatus (Continued)
Bit
Status Bit
Value
Indication Generation Severity Description
17
ExtendedStatus18
16#00020000
1
1
1
1
18
ExtendedStatus19
16#00040000
1
1
1
1
19
ExtendedStatus20
16#00080000
1
1
1
1
20
ExtendedStatus21
16#00100000
1
1
1
1
21
ExtendedStatus22
16#00200000
1
1
1
1
22
Reserved
16#00400000
–
–
–
–
23
PrimaryIncompatibleFW
2
16#00800000
Error
Alarm
High
Version of
the Running
Primary is
incompatible
24
BackupIncompatibleFW 2
16#01000000
Warning
Alarm
Medium
Version of
the Running
Backup is
incompatible
25
PrimaryNotPrefrdFW 2
16#02000000
Warning
Alarm
Medium
Version of
the Running
Primary is
not preferred
26
BackupNotPrefrdFW 2
16#04000000
Warning
Alarm
Medium
Version of
the Running
Backup is
not preferred
27
TimeouOnBackup 2
16#08000000
Warning
Alarm
Low
Watchdog
timeout on
backup
28
DeviceFailureBackup 2
16#10000000
Warning
Alarm
Low
Backup
device failure
3BSE040935-511
429
Unit Specific Alarm and Events
Appendix B System Alarms and Events
Table 55. General status bit ExtendedStatus (Continued)
Bit
29
Status Bit
SwitchoverInProgress
Value
2
16#20000000
30 ConfiguredAsRedundant 2, 3 16#40000000
UnitBPrimary 2
31
1
2
3
16#80000000
Indication Generation Severity Description
Warning
Event
Low
Switchover in
progress
-
-
-
Redundant
mode
enabled
-
-
-
Unit B acts
primary
Depends on the specific hardware device, defined within the hardware definition file.
Used only if the unit is configured as a redundant unit.
If this bit is set and bit 31 is not set, the text Unit A acts primary will be shown.
Unit Specific Alarm and Events
The status bit description of alarms and events specific to a hardware unit is
available along with the hardware type displayed under the hardware library.
To view the status bit description of alarms and events specific to a hardware unit:
1.
Go to Libraries > Hardware > HwLib folder, and expand the
Hardware Types folder.
2.
Right click the required hardware type and select Unit Specific Alarm and
Events (see Figure 151).
The status bit description of alarms and events is displayed in a separate window
(see Figure 152). This data can be used for supervising the unit status, see
Supervising Unit Status on page 296.
430
3BSE040935-511
Appendix B System Alarms and Events
Unit Specific Alarm and Events
Figure 151. Accessing the Unit Specific Alarm and Events option
Figure 152. Unit Specific Alarm and Events window for CI871 hardware type
3BSE040935-511
431
Unit Specific Alarm and Events
432
Appendix B System Alarms and Events
3BSE040935-511
INDEX
A
abort
tasks 146
access variables 82
accuracy 236
acknowledge
errors 306
warnings 306
acknowledgement rules 214, 252
add
message to alarm 214
to libraries 116
AF 100 286
alarm condition
name 214
alarm conditions 210
Alarm handling
INSUM 229
Alarm lists
INSUM 229
AlarmCond 210
parameters 211
AlarmCondBasic 212
AlarmCondBasicM 212
AlarmCondM 210
alarms
add message 214
classify 215
communication 237
condition name 214
disable 220
disable condition 214
enable 213
examples 243
in control loops 219
3BSE040935-511
inhibit 220
local printer 240
logging 232
severity 215
source name 214
state diagrams 252
status 216
subscribe to 237
system 230
all inputs 298
all outputs 298
all unit status 298
analog signals
scale 296
analysis tools 351
arrays
example 361
ASCII codes 378
ASCII conversion 380
asynchronous communication 284
attributes
Hidden 126
Protected 126
B
backup 317
individual files 319
BasicLib 28
buffer queues 239
buffers
configure 239
memory planning 239
C
CASE 188
433
Index
change
library state 115
channel status
check 299
check
channel status 299
classify
alarms 215
client/server 282
Closed 114
CNCP 236
codes
ASCII 378
COMLI 258
communication
alarm and event 237
client/server 282
cyclic vs. asynchronous 284
function blocks 279
libraries 258, 279
master/slave 282
modem 265
provider/subscriber 283
serial 267
statistics 274
using access variables 84
using global variables 85
variables 274
communication libraries
library 258
Communication Variables 86, 274
Diagnostics 345
complex types
modify 45
condition name
alarms 214
condition-related events 208
configure
buffers 239
Error Handler 320
434
OPC AE communication 237
connect
I/O channels 102
libraries 110
library 111
objects 54
to other system 278
Control Builder
start log 332
system information report 335
Control Builder start log
file path 332
control loops
alarms 219
control module types
AlarmCondBasicM 212
AlarmCondM 210
control modules
execution 62
single 65
Control Network 272
network areas 272
control project
insert library 111
remove library 113
controller logs
file paths 340
controller system log 336
controllers
system alarms 231
conversion
ASCII 380
conversion functions
example 376
conversions
ASCII 378
Coordinated Universal Time 235
crash dumps 341
create
library 114
3BSE040935-511
Index
objects 54
cyclic communication 284
D
data
read 278
send 278
data types 74
simple 74
debug mode 149
decisions
when creating types 53
declare
external variables 34
function blocks 35
parameter 33
types 32
variables 33
define
variables 73
development state
libraries 114
Device Import Wizard 120
DeviceNet EDS 120
Diagram and Diagram Types
Execution 63
Introduction 46
dialogs
Remote System 273
disable
alarm condition 214
alarms 220
events 220
disconnect
library 113
document conventions 14
download
reports 197
3BSE040935-511
E
EDIT parameters 212
editors
declare types 32
diagram 39
graphics 40
programming 37
enable
alarm detection 213
enter
variables 73
Error Handler
configure 320
log entries 324
error messages 309
Error Reaction
settings 322
error reports 360
errors
acknowledge 306
non-unique alarms 215
suggested actions 358
symptoms 358
Ethernet/IP EDS 120
events
communication 237
condition-related 208
disable 220
inhibit 220
logging 232
low level 222
simple 208
system 230
tracking-related 208
examples
alarm and event 243
arrays 361
conversion functions 376
queues 372
type protection 129
435
Index
execution
control for individual objects 92
control modules 62
control using external variables 92
control using parameter 94
debug mode 149
non-cyclic 149
EXIT 188
extensible parameters 107
external 81
external time stamps 234
external variables 81
declare 34
F
fatal overrun 321
fault localization
crash dumps 341
file paths
Control Builder start log 332
controller logs 340
heap statistics log 336
session logs 329
firmware functions 20
folders
System 20
FOR 188
function block types
AlarmCond 210
AlarmCondBasic 212
System Diagnostics 353
SystemDiagnostics 251
function blocks
communication 279
declare 35
functions 20
H
hardware
monitor 106
hardware status 297
heap 356
heap statistics log 336
file path 336
Heap Utilization 357
Hidden
attribute 126
I
I/O addressing 101
I/O channels
connect 102
force values 294
monitor 106
online mode 294
IAC MMS 275
IEC 61131-3 19
Implicit Cast 188
inhibit
alarms 220
events 220
initial values 81
Instruction List 188
INSUM
Alarm handling method 229
Alarm lists 229
INSUM Alarms 224
InsumCommLib 258
interaction windows 307
internal time stamps 234
interval time
tasks 136
intervals
tasks 136
G
K
graphical editor 40
keywords
436
3BSE040935-511
Index
in parameter descriptions 108
L
Ladder Diagram 188
latency 142, 144
latency supervision 321
libraries
add to 116
BasicLib 28
communication 258, 279
connect 110
connect to application 111
connect to library 111
create 114
disconnect 113
insert into control project 111
InsumCommLib 258
management 109
remove from control project 113
states 114
library management 109
library state
change 115
library states
Closed 114
Open 114
Released 114
load balancing 147, 321
Load Firmware 182
local printers 240
log
alarms and events 232
simple events 233
log entries
Error Handler 324
log files 326
Control Builder start log 332
controller system log 336
heap statistics 336
session 327
3BSE040935-511
system log 326
logging
alarms and events 232
Loops In ST 188
low level event 222
M
master
time synchronization 236
master/slave 282
MB 300 TS 236
MB300 263
memory size 356
MMS 264
MMS Time Service 236
ModBus 265
modem communication 265
monitor
hardware 106
I/O channels 106
MTMCommLib 266
N
Nested If or Case 188
network areas 272
network redundancy 272
non-cyclic execution 149
non-unique alarms
errors 215
number conversion
example 376
O
objects 30
connect 54
control execution 92
create 54
offset
tasks 137
online mode 106
437
Index
all inputs/outputs 298
all unit status 298
force I/O channels 294
hardware status 297
I/O channels 294
interaction windows 307
messages 309
project documentation 314
search and navigation 310
status indications 304
task overview 306
unit status 296
OPC AE communication
configure 237
OPC Server
session log example 331
OPC server
subscriptions 237
OPC Server for AC 800M 237
Open 114
open
code block menu 39
override
protection 127
type protection 126
overrun 142
overrun supervision 321
P
parameter
declare 33
parameters 69
AckCond 214
AckRule 213
AE Limit auto disable 217
AlarmCond 211
Class 215
CondName 214
CondState 216
DisCond 214
438
EDIT 212
EnCond 214
EnDetection 213
Error 216
extensible 107
ExtTimeStamp 213
FilterTime 213
Inhibit 220
Inverted 213
keywords 108
Message 214
Severity 215
Signal 213
SignalID 213
SrcName 214
Status 216
TransitionTime 234
UseSigToInit 213
POU 19
definition 19
printers
local 240
priorities
tasks 134
process alarms 209
PROFIBUS
DP-V1 284
PROFIBUS GSD 120
PROFINET IO 285
C871 285
GSD 285
PROFINET IO GSD 120
programming editor 37
project
insert library 111
remove library 113
project constants 96
structured 97
project documentation 202, 314
Protected
3BSE040935-511
Index
attribute 126
protection
example 129
override 127
override for types 126
Protocols
PROFINET IO 285
protocols
COMLI 258
MB300 263
MMS 264
ModBus 265
modem communication 265
SattBus 266
serial communication 267
Siemens S3964R 265
supported 271
provider/subscriber 283
publisher/subscriber 283
Q
queues
buffer 239
example 372
R
read
data 278
redundancy
network 272
Released 114
Remote System dialog 273
remote systems information 342
REPEAT 188
reports
at download 197
system information 335
resolution 236
restore 317
Reverse attribute 91
3BSE040935-511
RS-232C 272
RT 286
S
S3964R 265
SattBus 266
scale
analog signals 296
search and navigation 157
online mode 310
Secure Digital 177
self-defined types 127
send
data 278
Sequence-of-Events (SOE) 222
serial communication 267
session log
OPC server example 331
session log files 327
session logs
file paths 329
severity
alarms 215
SFC 188
Siemens
S3964R protocol 265
simple data types 74
simple events 208
log 233
Simultaneous Execution in SFC 188
single control modules 65
SNTP 236
Source Code Report 194
source name
alarms 214
start code blocks 39
state
libraries 114
state diagrams
alarms 252
439
Index
alarms,alarms
state diagrams 252
statistics
communication 274
status
alarms 216
indications 304
status messages 309
structured project constants 97
subscribe
to alarms 237
sum system alarms 255
supervise
hardware 106
I/O channels 106
unit status 296
supervision
latency 144
overrun 142
supported protocols 271
System alarms
List 231
system alarms
controller generated 231
sum 255
system alarms and events 230
System Diagnostics 273, 353
system diagnostics 251, 353
System folder 20
system information 335
system log file 326
T
Task Analysis 150
tasks 306
abort 146
execution 134
interval time 136
offset 137
priorities 134
440
time-critical 134
TCPCommLib 269
terminology 15
time stamps 234
external 234
internal 234
time synchronization 236
time-critical tasks 134
tools
analysis 351
tracking-related events 208
TransitionTime 234
trouble-shooting 325
symptoms and measures 358
type concept 30
types 30
document 202
in applications 43
in libraries 44
self-defined 127
U
UDPCommLib 269
unit status
supervise 296
UTC 235
V
variable communication 274
variables 69, 81
access 82
attributes 76
declare 33
define 73
initial values 81
list 72
W
warnings
acknowledge 306
3BSE040935-511
Index
WHILE 188
3BSE040935-511
441
Index
3BSE040935-511
442
Index
3BSE040935-511
443
Index
444
3BSE040935-511
ABB AB
Control Technologies
Västerås, Sweden
Phone: +46 (0) 21 32 50 00
e-mail: processautomation@se.abb.com
www.abb.com/controlsystems
ABB Automation LLC
Control Technologies
Abu Dhabi, United Arab Emirates
Phone: +971 (0) 2 4938 000
e-mail: processautomation@ae.abb.com
www.abb.com/controlsystems
ABB Automation GmbH
Control Technologies
Mannheim, Germany
Phone: +49 1805 26 67 76
e-mail: marketing.control-products@de.abb.com
www.abb.de/controlsystems
ABB China Ltd
Control Technologies
Beijing, China
Phone: +86 (0) 10 84566688-2193
www.abb.com/controlsystems
ABB S.P.A.
Control Technologies
Sesto San Giovanni (MI), Italy
Phone: +39 02 24147 555
e-mail: controlsystems@it.abb.com
www.abb.it/controlsystems
Copyright © 2003-2013 by ABB.
All rights reserved.
ABB Inc.
Control Technologies
Wickliffe, Ohio, USA
Phone: +1 440 585 8500
e-mail: industrialitsolutions@us.abb.com
www.abb.com/controlsystems
ABB Pte Ltd
Control Technologies
Singapore
Phone: +65 6776 5711
e-mail: processautomation@sg.abb.com
www.abb.com/controlsystems
Power and productivity
for a better worldTM
3BSE040935-511
Contact us
Was this manual useful for you? yes no
Thank you for your participation!