95-7700-1 Q7770A RapidLink Dial

95-7700-1 Q7770A RapidLink Dial
Q7770A RapidLink™
DIAL-UP NETWORK ADAPTER
PRODUCT DATA
FEATURES
• High performance communications protocol provides
for faster communication of data to your LONWORKS
network.
• Serial EIA-232 interface connects host processors to
LONWORKS networks.
• A fixed 115,200 baud rate is supported on serial the
EIA-232 port to support direct local connections.
• On-board modem support with baud rate up to 56K bps
to support remote dial-up connections.
• Uses LONWORKS network protocol.
• Integral FT-3150® smart transceiver.
BEFORE INSTALLATION
The RapidLink Dial-Up Network Adapter provides local
access to LONWORKS® Bus (E-bus) from a PC through an
industry standard EIA-232 interface (previously called RS232) or dial-up remote access through an on-board 56K bps
modem. All of the RapidLink connections are located on the
rear panel of the device. The RapidLink Dial-up Network
Adapter interfaces with the LCBS family of controllers (i.e.
Excel 10, Excel 15 and Q7300 / T7300 series of controllers,
any third party controllers supported by LCBS family of
controllers). It can be used with LONSPEC™ 4.6.5,
LONSTATION™ Multi-Site 4.6.0, and RapidZone 3.0.0 or new
versions of this software packages.
The RapidLink Dial-up Network Adapter requires input power
of 9 to 24 Vac or Vdc and at least 250 mA. RapidLink should
be connected with UL Class 2 wiring only. The input power
can be connected through the screw terminal connector
supplied with RapidLink. The E-Bus network connector on the
RapidLink is orange colored and located on the rear of the
RapidLink enclosure. The mating connector is also a screw
terminal type.
• LONWORKS communicates through a 78-kilo-baud
transformer-coupled transceiver.
• 9 to 24 Vac or Vdc Class 2 power input using a mating
connector with removable screw terminals.
• Automatic dial-out using on-board modem for
transferring alarm information to a central station
(When used in conjunction with XL15A Building
Manager).
• Easy migration for existing systems through one to
one replacement of existing LON® transceiver and
external modem with RapidLink and upgrading
LONSPEC, LONSTATION and XL15A firmware to 4.6.5,
4.6.0 and 2.4.61 (or later versions) respectively.
• Easy wall mounting or tabletop operation.
• Fast installation - No switches to configure.
• Easy to read labels to guide installation of wiring.
RapidLink has LEDs that indicate activity on the serial,
modem, and E-Bus. RapidLink has an LED indicating that the
device is powered and an LED indicating that the E-Bus
Service switch, located on the front panel, is being pressed.
RapidLink also provides a Reset switch on the front panel.
The RapidLink enclosure has provisions for both wall
mounting and tabletop operation.
® U.S. Registered Trademark
Copyright © 2004 Honeywell International Inc.
All Rights Reserved
95-7700-1
Q7770A RAPIDLINK™
SPECIFICATIONS
The RapidLink Dial-up Network Adapter is a one-piece,
externally wired communication device. RapidLink can be
hardwired to the LonWorks network. The on-board 56K bps
modem provides for communication to the remote site as well
as allowing an Excel15A Building Manager to dial out alarms
to LonStation. The EIA-232 serial port provides for local
access to the E-Bus.
Model Number: Q7770A1001
Supported Application(s):
LONSPEC Version 4.6.5 and above.
LONSTATION Multi-Site version 4.6.0 and above.
RapidZone Version 3.0.0 and above.
Input Operating Voltage: 9 to 24 Vac or Vdc.
Operating Input Current (Typical): 120 mA.
Power Supply: 9 to 24 Vac or Vdc Class 2 power supply only
using removable screw terminals.
Temperature:
Operating: +32°F to +100°F (0°C to +38°C).
Storage: -40°F to +185°F (-40°C to +85°C).
Humidity (non-condensing):
Operating: 25 to 95% RH at 50°C.
Storage: 95% maximum at 50°C.
Dimensions:
7-1/2 in. L x 5-7/16 in. W x 1-3/16 in. H.
190 mm L x 138 mm W x 46 mm H.
System Processor: Ubicom™ IP2022 RISC Processor.
Neuron Transceiver:
Echelonfl Neuron FT-3150 Smart Transceiver.
Approvals: UL, cUL, FCC, CE.
Modem Connection: On-board Modem supports remote
connection with connection speeds of up to 56 Kbps.
Approved PC Side Modem: US Robotics 56K external V.90.
Modem Connector Type: RJ-11.
Modem Dip Switch Settings: None.
Network (E-Bus) Connector: Weidmuller - 2-conductor BLA.
Available Accessories:
5000591-001 RapidLink U.S. Accessory Kit. 12 Vac, 250 mA
(120 Vac, 60 Hz Main Outlet) Class 2-power supply;
telephone line cable; serial cable; E-Bus mating connector.
Bus Polarity: Polarity insensitive.
E-Bus Service Interface: Service Switch and LED.
IMPORTANT
• Using the RapidLink Dial-up Network Adapter for
alarm dial-out on systems with W7760A Excel 15A
Controllers requires upgrading W7760A firmware to
version 2.4.61.
• Obtain firmware upgrades from Honeywell TAC.
Serial Port EIA-232 (Formerly RS-232).
Serial Port Bit Rate: 115200 bps.
Serial Connector Type: Female DB-9.
Power Polarity: Polarity insensitive.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or
phone:
1. Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1885 Douglas Drive North
Minneapolis, Minnesota 55422-4386
In Canada–Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive, Scarborough, Ontario M1V 4Z9.
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
95-7700–1
2
Q7770A RAPIDLINK™
RAPIDLINK OVERVIEW (FIG. 1 THROUGH 3)
SERVICE
E-BUS PWR RESET
M22087
Fig. 1. RapidLink (front view).
POWER AC/DC IN
9V-24 250mA
CLASS 2 WIRING
NETWORK
E-BUS
M22088
POWER
Fig. 2. RapidLink (rear view).
POWER SUPPLY SECTION
9V - 24V C/DC
REGULATOR - 5V,
3,3V, 2.6V
RESET SWITCH
EIA RS232
IP2022
120MHz
PROCESSOR
POWER LED
E-BUS LED
RS232 LED
NEURON3150
PROCESSOR
E-BUS
SERVICE LED
SERVICE SWITCH
MODEM
128KB SRAM
MODEM + DAA SECTION
MODEM LED
M22089
Fig. 3. RapidLink (internal view).
3
95-7700–1
Q7770A RAPIDLINK™
Table 1. RapidLink Interface.
Interface
Function
Service Switch
Pressing the Service Switch results in a Neuron Service Request for RapidLink.
While pressed, the Service LED should be at maximum intensity.
Reset Switch
The Reset Switch is recessed to prevent accidental reset.
Pressing the Reset Switch results in a circuit hardware reset and a RapidLink firmware restart.
Unregulated AC/DC Two-position, locking black connector connects RapidLink to a Class 2-power source.
The provided mating plug is a Weidmuller part number 1730700000.
Power Input
Connector (See
Table 4 for power
requirements)
E-Bus (Network)
Port Connector
Two-position, locking orange connector used to connect to the E-Bus (network) RapidLink port.
The provided mating plug is a Weidmuller part number 1356060000.
EIA-232 Serial Data DB-9 female connector used to connect to the RapidLink EIA-232 serial data interface port.
Interface Port
The RapidLink EIA-232 interface operates in the DCE mode.
Connector
Modem Interface
Port Connector
RJ-11 connector used to connect the telephone line cable to RapidLink internal 56K bps modem.
Power LED
The Power LED (Green) indicates the presence of input power to the RapidLink Dial-up Network Adapter.
Service LED
The Service LED (Yellow) indicates that the Service Switch is being pressed.
With the Service Switch not pressed, there are three other possibilities:
• LED ON: The RapidLink board Neuron Chip has detected an unrecoverable error and/or has no
application loaded.
• LED BLINKING: The RapidLink Neuron processor is not configured.
• LED OFF: The RapidLink Neuron processor is configured or there is no power.
E-bus Activity LED
The E-Bus Activity LED (Green) indicates LonWorks bus activity.
The two possible states for this LED:
• OFF: No data is being transferred on the LonWorks bus or there is no power to RapidLink.
• BLINKING: LonWorks bus data communication is in progress.
Serial Interface
Activity LED
The EIA-232 Serial Data Port Activity LED (Green) indicates EIA-232 serial data interface port activity.
The two possible states for this LED:
• OFF: No data is being transferred on EIA-232 interface or there is no power to RapidLink.
• BLINKING: EIA-232 serial data interface data communication is in progress.
Modem Interface
Activity LED
The Modem Port Activity LED (Green) indicates activity on the Modem port.
The two possible states for this LED:
• OFF: No data is being transferred on the modem or there is no power to RapidLink.
• BLINKING: Modem data communication is in progress.
MOUNTING
When mounting RapidLink, be sure to provide adequate room
to access and route cables to the device. There should also
be enough room to view LEDs and press the service switch on
the front panel.
Wall Mounting
With Screws (supplied)
Using the supplied screws (1 in. #6 panhead with combination
slot) and, if necessary, wall anchors:
1. Tape template (Fig. 8) to the wall to ensure proper screw spacing.
2. Pre-drill for screws and, if necessary, wall anchors.
3. Remove the template from the wall.
4. Attach the screws to the wall, leaving sufficient space
between screw heads and wall to mount the device.
5. Position the device on the screws and slide it into place.
95-7700–1
4
With Reclosable Fasteners (supplied)
Leaving the fastener pairs mated, proceed as follows:
1. Attach one side of each fastener pair to the bottom of
RapidLink:
a. Remove the paper backing material.
b. Attach the sticky-backed material to the underside
of the device by applying pressure to adhere the
fasteners.
2. Remove the exposed paper backing material.
3. Position the RapidLink on the mounting wall (a smooth,
flat, clean surface).
4. Apply pressure to adhere the fasteners to the wall.
Tabletop Mounting
Using the four polyurethane feet (supplied):
1. Remove the paper backing from the mounting feet.
2. Apply each foot over a screw head (located on the
underside of the device).
Q7770A RAPIDLINK™
CABLING AND CONNECTIONS
Remote Connection
RapidLink has an on-board 56K bps modem that provides for
remote communication to the E-Bus. Fig. 4 shows remote
connection set-up.
1. Plug the DB-9 connector male end into RapidLink.
2. Plug the DB-9 connector female end into the PC serial
interface connector.
PC (DTE)
LonStation configuration for Remote connection:
1. Login to LonStation.
2. Double-click the site icon in the left side tree control.
3. Select site to be connected from left side tree control.
4. Click the tool bar Connect button.
RapidLink (DCE)
DB-9
FEMALE
DB-9
MALE
M22090
Fig. 5. Serial Cable with DB-9 Connectors.
Table 2. PC DB-9 Connector to RapidLink DB-9 Wiring
Terminations. (Use Straight cable.)
LonSpec Configuration for Remote Connection:
1. Open the project and the network.
2. Edit the network to include the phone number to dial.
3. Click File in the pull-down menu.
4. Select the Communication Settings.
5. Choose the port where the modem is connected.
6. Choose the baud rate.
Signal Name
NOTE: Honeywell recommends 38,400 bps.
7. Choose the modem connection type.
RapidLink (DCE)
Connector
DB-9 Female
PC (DTE)
Connector
DB-9 Male
RXD
Pin 3
Pin 2
TXD
Pin 2
Pin 3
Signal Ground
Pin 5
Pin 5
Attaching RapidLink to a 25-pin Serial PC Port
Some PC serial ports have a 25-pin male DB-25 connector.
When connecting to a PC equipped with a DB-25 connector,
use a straight-through cable (not a null-modem cable) with
one end terminating in a DB-9 male connector and the other
end terminating in a DB-25 female connector. See Table 3 for
wiring termination details.
NOTEBOOK PC
MODEM
1.
2.
Plug the DB-9 connector male end into RapidLink.
Plug the DB-25 female end into the PC serial port.
PC (DTE)
TELEPHONE
NETWORK
RapidLink (DCE)
DB-25
FEMALE
DB-9
MALE
M22091
Fig. 6. Serial Cable with one DB-25 (Female) Connector
and one DB-9 Connector (Male).
SERVICE
Table 3. Wiring Terminations for PC DB-25 Connector to
RapidLink DB-9 Connector.
E-BUS PWR RESET
PC (DTE)
Connector DB-25 RapidLink (DCE) DB-9
Signal Name
Male
Connector Female
E-BUS
CABLE
REMOTE SITE
M22086
Fig. 4. RapidLink Remote Connection.
Direct Connection (with 9-pin Serial Cable)
RXD
Pin 3
Pin 2
TXD
Pin 2
Pin 3
Signal Ground Pin 7
Pin 5
Attaching RapidLink to a LonWorks Network
Attaching RapidLink to a 9-pin PC Serial Port
The network connector for the RapidLink is an orange, twoconductor block type. Use the 2-pin connector with screw
terminal terminations that comes with the RapidLink to
connect to the twisted-pair wire for the LonWorks network.
See Fig. 7.
When connecting to a PC equipped with a male DB-9 serial
interface connector, use a standard serial cable (not a nullmodem cable) with one end terminating in a DB-9 male
connector and the other end terminating in a DB-9 female
connector. See Table 2 for connector wiring termination
details.
5
95-7700–1
Q7770A RAPIDLINK™
1. Connect the mini-phono plug of the connector cable to
the LonWorks (E-Bus) interface on either a controller or
a wall module.
2. Connect the cable wire end to the RapidLink E-Bus
mating connector.
3. For E-Bus direct cable wiring:
a. Wire one end of the E-Bus cable to the controller or
wall module.
b. Wire the other end of the E-Bus cable to the mating
E-Bus connector on RapidLink.
Supply power (use a Class 2 power supply only) to the
RapidLink after it is connected to the desired network. Table 4
shows the specification for power input to the RapidLink.
Power can be applied using the supplied screw terminal
mating connector. This allows RapidLink to connect to a
9 to 30 Vac/Vdc power supply.
NOTES:
–
–
When power is first connected, all LEDs flash
briefly and green power indicator LED turns ON.
Once a RapidLink is powered, the service LED
remains off unless the service request switch is
pressed.
Table 4. RapidLink Power Supply Requirements.
Power (Class 2 power
supply only)
NOTEBOOK PC
SERIAL
INTERFACE
CABLE
PC
SERIAL
PORT
Q7770A
RAPIDLINK
E-BUS
CABLE
E-BUS
PORT
M22093
Fig. 7. Connecting the portable operator terminal
to the LonWorks Bus.
95-7700–1
6
Absolute
Minimum Nominal Maximum
Unregulated DC
+9 Vdc
+12 Vdc
+30 Vdc
Unregulated AC
+9 Vac
+12 Vac
+30 Vac
Q7770A RAPIDLINK™
TEMPLATE
DRILL TO ACCEPT 1 IN.
# 6 PAN HEAD COMBINATION
SLOTTED SELF-TAPPING SCREW.
5-1/2
(140)
M22092
Fig. 8. RapidLink Dial-up Network Adapter - wall mounting template.
7
95-7700–1
THIS PAGE INTENTIONALLY LEFT BLANK
95-7700–1
8
Q7770A RAPIDLINK™
APPENDIX A: RAPIDLINK Q7770A1001 REGULATORY INFORMATION
Manufacturer’s Declaration of Conformity
The telephone company may make changes in its facilities,
equipment, or operations, which could affect the operation of
this equipment. If this occurs, the telephone company is
required to provide you with advance notice so you can make
the modifications necessary to maintain uninterrupted service.
FCC Part 15, Class A
Operation is subject to the following conditions:
– This device may not cause harmful electromagnetic
interference.
– This device must accept any interference received
including interference that may cause undesired
operations.
If trouble is experienced with this equipment, check your
connections. There are no user repairs that can be performed
on the device.
Connection to party line service is subject to state tariffs.
Contact the state public utility commission, public service
commission or corporation commission for information.
This equipment complies with Part 15 for Commercial use
only.
UL Listing/CUL Listing
The user is cautioned that any changes or modifications not
expressly approved by the party responsible for compliance
could void the user‘s authority to operate the equipment.
FCC Part 68
This equipment complies with Part 68 of the FCC rules and
the requirements adopted by the ACTA. On the bottom of this
equipment is a label that contains the ACTA product identifier
US: HS9MD00BQ7770A01. If requested, this number must be
provided to the telephone company.
A plug and jack used to connect this equipment to the
premises wiring and telephone network must comply with the
applicable FCC Part 68 rules and requirements adopted by
the ACTA. See installation instructions for details. This
equipment uses the following standard jack types: RJ-11
The REN (Ringer Equivalency Number) is used to determine
the number of devices that may be connected to a telephone
line. In most areas the sum of REN should not exceed five (5).
The REN for this product is 0.
In the unlikely event that this equipment causes harm to the
telephone network, the telephone company can temporarily
disconnect your service. In the event that a disconnection is
deemed necessary, you will be notified of the disconnection
and advised of your right to file a complaint with the FCC.
This equipment is UL Listed and cUL Listed for use with
Honeywell's energy management equipment UL File, E87741.
The UL Control Numbers associated with this File are: 57M1,
58L9, or 680X. The product has been tested to comply with
the requirements of UL 916.
CE Mark Declaration of Conformance
This product bares the CE Marking and is in conformity with
the protection requirements of the following European Council
Directives: 73/23/EEC (the Low Voltage Directive), 89/336/
EEC (the EMC Directive), and 1999/5/EC (the Radio
Equipment and Telecommunications Terminal Equipment
Directive).
Applicable Testing Specifications:
Emissions:
EN55022 Part 15 Class A
EN55022 Part 68.
Immunity:
EN61000-4-5 Level 2
EN61000-4-4 Level 2
EN61000-4.2 Level 3
EN61000-4-6 Level 2
EN61000-4-3
EN61000-4-8
EN61000-4-11
EN55024
9
95-7700–1
95-7700–1
10
11
95-7700–1
Echelon®, LON®, LONWORKS®, Neuron®, and FT 3150® are registered trademarks of Echelon® Corporation.
LONSPEC, and LONSTATION are trademarks of Echelon® Corporation.
Automation and Control Solutions
Honeywell International
Honeywell Europe S.A.
Honeywell International Inc.
1985 Douglas Drive North
Golden Valley, MN 55422
Control Products
Honeywell Building
17 Changi Business Park Central 1
Singapore 486073
3 Avenue du Bourget
1140 Brussels
Belgium
95-7700–1
Honeywell Limited-Honeywell Limitée
35 Dynamic Drive
Scarborough, Ontario
M1V 4Z9
B.B. Rev. 4-04
Printed in U.S.A. on recycled
paper containing at least 10%
post-consumer paper fibers.
Honeywell Latin American
Region
480 Sawgrass Corporate Parkway
Suite 200
Sunrise FL 33325
www.honeywell.com