SCP452, 453 Model 450 Processor

SCP452, 453 Model 450 Processor
Instruction Bulletin
Class 8055 Type SCP452, 453
Model 450 Processor
Bulletin No. 30598-526-01A1
June 1993
Raleigh, NC, U.S.A.
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The application of this product requires expertise in the design
and programming of control systems. Only persons with such
expertise should be allowed to program, install, alter and apply
this product.
Failure to observe this precaution can result in severe personal
injury or death!
CAUTION
EQUIPMENT DAMAGE HAZARD
To avoid improper handling of equipment:
1. Never remove this device while power is ON. Turn power
supply switch to OFF and wait until all indicating lights
are off before removing.
2. Do not subject to static discharge. This module contains
electronic components that are very susceptible to
damage from electrostatic discharge.
Failure to observe this precaution can result in equipment
damage.
PLEASE NOTE
Electrical equipment should be serviced only by qualified electrical maintenance personnel, and this document should
not be viewed as sufficient instruction for those who are not otherwise qualified to operate, service or maintain the
equipment discussed. Although reasonable care has been taken to provide accurate and authoritative information in this
document, no responsibility is assumed by Square D for any consequences arising out of the use of this material.
TRADEMARK NOTICE
SY/MAX, SY/MATE, and SY/NET are registered trademarks of Square D Company.
IO/NET and PASSPORT are trademarks of Square D Company.
IBM is a registered trademark of International Business Machines Corporation.
DEC, DECnet, Q-BUS, ThinWire, ThickWire, UNIBUS, VAX, VMS, VAXBI, and MicroVAX
are registered trademarks of Digital Equipment Corporation.
Motorola is a registered trademark of Motorola Incorporated.
Table of Contents
Section
1
Page
Overview ...............................................................................................................................1-1
1.1
1.2
1.3
1.4
1.5
1.6
1.7
2
Title
Description ......................................................................................................................................1-1
Ethernet Connectivity.......................................................................................................................1-2
SY/MAX Compatibility ......................................................................................................................1-2
Hardware Features...........................................................................................................................1-3
Instruction Set General Information .................................................................................................1-3
Technical Comparison......................................................................................................................1-4
Front Panel Features........................................................................................................................1-5
Specifications .......................................................................................................................2-1
2.1 Model 450 Specifications .................................................................................................................2-1
2.1.1 Electrical Specifications .......................................................................................................2-1
2.1.2 Environmental Specifications ...............................................................................................2-2
2.1.3 Physical Specifications.........................................................................................................2-2
2.1.4 Functional Specifications .....................................................................................................2-3
2.2 New Features ...................................................................................................................................2-5
2.3 Register Usage ................................................................................................................................2-5
2.4 Instruction Set Table.........................................................................................................................2-6
3
Installation ............................................................................................................................3-1
3.1 Operating Chraracteristics ...............................................................................................................3-1
3.1.1 Differences When Used with Certain Modules .....................................................................3-2
3.1.2 Differences in Function.........................................................................................................3-2
3.2 Rack Configuration...........................................................................................................................3-4
3.3 Register Modules .............................................................................................................................3-5
3.4 Installing the Model 450 ...................................................................................................................3-5
3.5 Undervoltage Lockout Circuit Operation and AC Fail Function ........................................................3-7
3.5.1 Troubleshooting Power Problems........................................................................................3-8
3.6 Rack Addressing a Model 450 in the CPU Slot..............................................................................3-10
3.6.1 Initial System Layout .........................................................................................................3-10
3.6.2 Processor Operation .........................................................................................................3-11
3.6.3 Determining Rack Addressing Needs ...............................................................................3-12
3.6.4 Rack Addressing Register Allocation ................................................................................3-13
3.6.5 Rack Addressing Compatibility with Other SY/MAX Processors.......................................3-15
3.7 Rack Addressing Multiple Model 450s in the Same Rack..............................................................3-18
4
Controls and Indicators .......................................................................................................4-1
4.1 Keyswitch Positions..........................................................................................................................4-1
4.2 Indicator LEDs..................................................................................................................................4-2
RUN..................................................................................................................................................4-2
HALT ................................................................................................................................................4-3
MEMORY .........................................................................................................................................4-3
FORCE.............................................................................................................................................4-3
I/O ..................................................................................................................................................4-3
BATTERY LOW ................................................................................................................................4-4
WRITE PROTECT............................................................................................................................4-4
ETHERNET COMM ERROR ...........................................................................................................4-4
Section
5
Title
Page
SY/MAX Communications ...................................................................................................5-1
5.1 General Information .........................................................................................................................5-1
5.2 Connecting Programmers ................................................................................................................5-2
5.3 Connecting Other SY/MAX Devices.................................................................................................5-2
5.3.1 Other Processors................................................................................................................5-4
5.3.2 SY/NET Network Interface ..................................................................................................5-4
5.3.3 Loader/Monitor ....................................................................................................................5-4
5.3.4 Cartridge Tape Loader/Recorder.........................................................................................5-5
5.3.5 Printers................................................................................................................................5-5
5.3.6 D-LOG Data Controller Module...........................................................................................5-5
5.4 Baud Rates ......................................................................................................................................5-5
5.4.1 General Information ............................................................................................................5-5
5.4.2 Altering Baud Rates ............................................................................................................5-6
5.5 Variable Route Statement ................................................................................................................5-7
5.5.1 Description of Operation .....................................................................................................5-7
5.5.2 Implementation....................................................................................................................5-8
5.5.3 Application Considerations..................................................................................................5-8
5.5.4 Example ..............................................................................................................................5-9
5.6 Improving Communications Throughput ........................................................................................5-10
5.6.1 Guidelines .........................................................................................................................5-11
5.6.2 SY/MAX Communications Timeout ...................................................................................5-12
5.7 Technical Data for Communications Ports .....................................................................................5-15
6
Security Features .................................................................................................................6-1
6.1
6.2
6.3
6.4
General Information .........................................................................................................................6-1
Definitions .......................................................................................................................................6-1
Summary of Security Methods.........................................................................................................6-2
Hardware Security Jumper...............................................................................................................6-3
6.4.1 Considerations ......................................................................................................................6-4
6.4.2 Setting the Security Jumper ..................................................................................................6-4
6.5 Selective Port and Route Edit Lockout.............................................................................................6-5
6.6 Keyswitch RUN Position ...................................................................................................................6-5
6.7 Inhibit Rung ......................................................................................................................................6-6
6.7.1 Considerations ......................................................................................................................6-6
6.7.2 Clearing the Inhibit Rung.......................................................................................................6-6
6.8 Safeguard Rung ...............................................................................................................................6-8
6.8.1 Considerations ....................................................................................................................6-10
6.8.2 Timed Interrupt Operation ...................................................................................................6-11
6.9 Password and Restriction Registers ..............................................................................................6-13
6.10 Memory Protect Bit ........................................................................................................................6-14
6.11 Force Inhibit Bit ..............................................................................................................................6-15
6.12 Register Protect Bit ........................................................................................................................6-16
6.13 Fenced Registers Bit......................................................................................................................6-16
7
Floating-Point Math ..............................................................................................................7-1
7.1 Introduction ...................................................................................................................................7-1
7.2 Definition of Terms............................................................................................................................7-1
7.3 Register Usage ................................................................................................................................7-1
7.3.1 Integer Data ..........................................................................................................................7-2
7.3.2 Floating-Point Operations .....................................................................................................7-2
7.4 Addressing Floating-Point Registers ................................................................................................7-2
7.5 Data Transfers (LET) and Comparisons (IF) Using Floating-Point Numbers....................................7-4
7.5.1 Data Transfers (“LET” Instruction).........................................................................................7-4
7.5.2 Comparisons (“IF” Instruction) ..............................................................................................7-5
Section
Title
Page
7.6 Entering Floating-Point Values .........................................................................................................7-5
7.6.1 Entering Floating-Point Numbers Using Data Mode.............................................................7-5
7.6.2 Floating Point Considerations ...............................................................................................7-5
7.7 Displaying Floating-Point Values ......................................................................................................7-6
7.8 Floating-Point Operations within LET and IF Instructions ................................................................7-7
7.8.1 Sequence of Math Operations ..............................................................................................7-8
7.8.2 Math Programming Considerations ......................................................................................7-8
7.9 Floating-Point Operation Using Matrices..........................................................................................7-9
7.10 Combining Floating-Point with Integer Operations.........................................................................7-9
7.10.1 LET Instructions ..................................................................................................................7-9
7.10.2 IF Instructions ....................................................................................................................7-12
7.11 Overflow Errors ............................................................................................................................7-13
7.11.1 Accumulator Operation......................................................................................................7-13
7.11.2 Why Do Overflows Occur? ................................................................................................7-14
7.12 Special Math Functions................................................................................................................7-16
7.12.1 Restrictions .......................................................................................................................7-16
7.12.2 Trigonometric Function Discontinuities ..............................................................................7-17
8
Special Instructions .............................................................................................................8-1
8.1 General Information .........................................................................................................................8-1
8.2 Math and Trigonometric Operations ...............................................................................................8-10
8.2.1 Application Considerations.................................................................................................8-10
8.2.2 Trig and Math Constants ....................................................................................................8-11
8.3 Statistical Operations .....................................................................................................................8-12
8.4 Indirect Register Read Operations.................................................................................................8-13
8.5 Alternate Accumulator Manipulations.............................................................................................8-14
8.6 Bus Write to Microcell ....................................................................................................................8-15
8.6.1 Reading Registers..............................................................................................................8-15
8.6.2 Writing Registers ................................................................................................................8-15
8.7 Miscellaneous Instructions .............................................................................................................8-17
9
PID Operations .....................................................................................................................9-1
9.1
9.2
9.3
9.4
9.5
9.6
9.7
General Information .........................................................................................................................9-1
Register Allocation ...........................................................................................................................9-1
Reverse-Acting Loop........................................................................................................................9-3
Direct-Acting Loop............................................................................................................................9-4
Manual Loop ....................................................................................................................................9-4
Lead/Lag Functions..........................................................................................................................9-5
Application Considerations and Examples.......................................................................................9-7
10 ASCII Communications (Input and Output) .....................................................................10-1
10.1
10.2
10.3
ASCII Input..................................................................................................................................10-1
10.1.1 Description/Initiation .....................................................................................................10-1
10.1.2 Port Configuration .........................................................................................................10-2
10.1.3 Operation ......................................................................................................................10-4
10.1.4 Application Considerations ...........................................................................................10-5
10.1.5 Error Codes ..................................................................................................................10-6
ASCII Output...............................................................................................................................10-7
10.2.1 Standard ASCII Format ................................................................................................10-7
10.2.2 Raw Binary ASCII Format.............................................................................................10-8
10.2.3 Miscellaneous ASCII Formats ......................................................................................10-9
10.2.4 Repeated Character Strings .........................................................................................10-9
10.2.5 XON/XOFF Handshaking .............................................................................................10-9
ASCII - Hexadecimal - Decimal Conversion .............................................................................10-11
Section
Title
Page
11 Sequencer ...........................................................................................................................11-1
11.1 Description and Initiation .............................................................................................................11-1
11.2 Register Block Allocation .............................................................................................................11-2
11.2.1 Configuration Table Registers..........................................................................................11-2
11.2.2 Step Table Registers........................................................................................................11-6
11.3 Application Discussion..................................................................................................................11-7
11.3.1 Required Entries..............................................................................................................11-7
11.3.2 Operating Characteristics ................................................................................................11-8
11.3.3 Typical Operating Modes .................................................................................................11-9
11.4 Application Considerations .........................................................................................................11-16
11.4.1 Error Conditions.............................................................................................................11-16
11.4.2 Operating Mode Register Status Bits ............................................................................11-17
11.5 Examples....................................................................................................................................11-18
12 Battery Backup and Clock/Calendar ................................................................................12-1
12.1 Backup Battery ............................................................................................................................12-1
12.1.1 Description ......................................................................................................................12-1
12.1.2 Low Battery Indication.....................................................................................................12-1
12.1.3 Battery Life Expectancy ..................................................................................................12-1
12.1.4 Replacement Procedure .................................................................................................12-2
12.1.5 Battery Specifications .....................................................................................................12-3
12.2 Real-Time Clock/Calendar...........................................................................................................12-3
12.2.1 Specifications..................................................................................................................12-3
12.2.2 Loading the Time/Date....................................................................................................12-3
12.2.3 Setting the Clock .............................................................................................................12-4
12.2.4 Clock Manipulation..........................................................................................................12-4
13 Processor Control Registers.............................................................................................13-1
13.1 General Information .....................................................................................................................13-1
13.2 Listing of Registers ......................................................................................................................13-3
13.2.1 Group #1: Read/Write Registers .....................................................................................13-3
13.2.2 Group #2: Read-Only Registers....................................................................................13-14
14 Technical Data ....................................................................................................................14-1
14.1 Memory Utilization .......................................................................................................................14-1
14.1.1 Relay Circuits ..................................................................................................................14-1
14.1.2 General Instructions........................................................................................................14-2
14.1.3 IF, LET, and Math Instructions.........................................................................................14-3
14.2 Scanning Techniques...................................................................................................................14-4
14.2.1 General Information ........................................................................................................14-4
14.2.2 Scanning Speed..............................................................................................................14-5
14.2.3 Optimizing Scan Speed ..................................................................................................14-8
14.3 Theory of Operation...................................................................................................................14-11
14.4 Forcing ......................................................................................................................................14-13
14.4.1 Forcing an External Output ...........................................................................................14-14
14.4.2 Forcing an External Input..............................................................................................14-15
14.4.3 Forcing an Internal Relay Equivalent or Data Storage Register ...................................14-16
14.4.4 Application Considerations for Forcing .........................................................................14-16
14.5 Power Up/Down Sequence........................................................................................................14-17
14.5.1 Processor Power-Up Sequence....................................................................................14-17
14.5.2 Processor Scan Start-Up Sequence.............................................................................14-18
14.5.3 Processor Power-Down Sequence ...............................................................................14-19
14.6 Run-Time Operational Checks...................................................................................................14-19
Section
Title
Page
15 Ethernet Communications.................................................................................................15-1
15.1 Introduction ..................................................................................................................................15-1
15.2 Hardware .....................................................................................................................................15-2
15.3 Switch Settings ............................................................................................................................15-4
15.3.1 Least Significant Digit .......................................................................................................15-5
15.3.2 Most Significant Digit ........................................................................................................15-5
15.4 Defining an Ethernet Network with SY/MAX Devices ..................................................................15-7
15.4.1 SY/MAX Drop Numbers....................................................................................................15-7
15.4.2 Routing for Port 3 (Ethernet Port) .....................................................................................15-7
15.5 Registers....................................................................................................................................15-10
15.5.1 Model 450 Register Overview ........................................................................................15-10
15.5.2 Control Processor Registers...........................................................................................15-10
15.5.3 Ethernet NIM Registers ..................................................................................................15-10
15.6 Ethernet Communication Parameters........................................................................................15-12
15.6.1 Setting Ethernet Communication Parameters (7XX0 and 7XX1) ...................................15-13
15.6.2 Evaluating Ethernet Communication Performance (7XX2 - 7XX5).................................15-17
15.6.3 Miscellaneous Considerations (7XX2 - 7XX5)................................................................15-19
15.7 Ethernet Errors and Diagnostics................................................................................................15-20
15.7.1 Ethernet Error Codes......................................................................................................15-21
15.7.2 Ethernet Diagnostic Codes.............................................................................................15-22
15.8 Glossary of Terms......................................................................................................................15-25
APPENDICES
A. Error Codes................................................................................................................... A-1
A.1
A.2
A.3
A.4
A.5
B.
C.
D.
E.
General Information .............................................................................................................. A-1
Peripheral-to-PLC System Interaction Errors........................................................................ A-1
A.2.1 Processor Errors...................................................................................................... A-2
A.2.2 Tape/Disk Errors...................................................................................................... A-2
A.2.3 Transmission Errors................................................................................................. A-2
PLC System Operational Errors.......................................................................................... A-12
A.3.1 General Errors (00001 - 00999)............................................................................. A-14
A.3.2 Processor Communications Port Error (01000 - 09999)........................................ A-15
A.3.3 Register Read After Write Error (10000 - 18192) .................................................. A-16
A.3.4 Slot Error (19000 - 19016) ..................................................................................... A-17
A.3.5 Miscellaneous Errors (29000 - 29999)................................................................... A-17
A.3.6 CPU/LI Errors (30000 - 32700).............................................................................. A-18
Using Error Codes to Isolate PLC System Faults............................................................... A-20
A.4.1 When the Entire PLC System Shuts Down............................................................ A-20
A.4.2 Troubleshooting Checklist ..................................................................................... A-21
Malfunction Examples......................................................................................................... A-23
A.5.1 Sample PLC System Shutdowns........................................................................... A-23
A.5.2 Remote Rack Shutdown ........................................................................................ A-25
A.5.3 Troubleshooting a Remote Rack Shutdown .......................................................... A-26
A.5.4 “PRGMR” or “COMM” Port Errors.......................................................................... A-27
Using LTI/RTI Modules ................................................................................................. B-1
Supplementary Rack Addressing Information .......................................................... C-1
Ethernet Technical Information ................................................................................... D-1
Connecting a VAX Processor to the Model 450 ......................................................... E-1
INDEX ........................................................................................................................................... I-1
Page 1-1
30598-526
1
OVERVIEW
1.1 DESCRIPTION
This instruction bulletin describes the hardware and firmware features and
installation procedures for the SY/MAX Type SCP452 and SCP453 processors.
The SY/MAX Model 450 is a powerful single-slot processor that features a built-in
ThinWire Ethernet communication port. Coupled with SY/MAX support software
running on a host computer, the Model 450 provides a flexible solution for
high-speed information transfer between the manufacturing floor and computer
applications. The Model 450 has a powerful instruction set and can handle more than
4000 I/O in medium to large control applications. The Model 450 may be regarded as
a control processor along with an equivalent “Ethernet Network Interface Module
(NIM)”. See Figure 1-1 to see how registers are divided between the Control
Processor and the Ethernet NIM.
Ethernet NIM
Control Processor
SY/MAX Status/
Control Registers
8192
8001
8000
Not used
Ethernet Network
Parameter Registers
8192
8000
7999
7000
6999
Not used
Not used
4001
4000
Ch 1
4000
Processor
(Image Table)
Registers
2000
Storage
(Mailbox)
Registers
5000
4999
3000
2999
Not used
11
1
NIM Status Registers
1 - 10
Ch 3
Ch 2
Figure 1-1 Model 450 Registers
Chapter 1 - Overview
Page 1-2
30598-526
1.2 ETHERNET CONNECTIVITY
The built-in ThinWire Ethernet port on the Model 450 complies with the IEEE 802.3a
standard and provides high speed (10 Mbit/second) Ethernet connectivity to one or
more host computers and other Model 450 or Model 650 processors. Model 450 and
650 processors are networked using standard ThinWire components and can be
connected to existing Ethernet networks. Model 450 processors can coexist on
Ethernet with other non-SY/MAX devices and protocols such as DECnet and TCP/IP
(Transmission Control Protocol/Internet Protocol). A host computer is not required for
Ethernet communication between Model 450 processors.
Coupling the Model 450 processor with Class 8055 Type SFW390 communication
support software for VAX/VMS provides direct Ethernet connectivity to any DEC
VAX/VMS computer. A combination of up to 100 Model 450 controllers and VAX
host computers running SFW390 Communication Software can exist on one network.
SFW390 is easily linked to host application software using callable subroutines. The
support software provides data register read/write, program upload/ download/verify,
external forcing and a variety of alarm handling functions. Unsolicited messaging
(report by exception) is also supported.
Using SY/MATE Plus programming software with the Model 450 enables both
off-line and on-line program development. All programming, monitoring and disk
functions can be performed via the SY/NET® local area network (LAN). SY/MATE
Plus software also performs these functions with Class 8055 processors over an
Ethernet network.
SY/MATE Plus software supports direct Ethernet network programming for SY/MAX
Model 450 and Model 650 processors. A Class 8010 Type SFI610 communication
interface, mounted in a IBM AT personal computer, provides the network link. The
software offers complete support of all processor programming, configuration,
monitoring and diagnostic functions over a 10BASE2 ThinWire network.
A Model 450 processor uses simple standard SY/MAX read/write instructions to
communicate via the built-in Ethernet port (SY/MAX Channel 3) to other Model 450
or Model 650 processors or host computers. Each Model 450 processor has a
switch-selectable SY/MAX address that is inserted in the address field of the Ethernet
packet. This allows standard SY/MAX routing procedures to be used for Ethernet
network communication.
1.3 SY/MAX COMPATIBILITY
In addition to the high speed Ethernet port, the Model 450 has two RS-422 serial
SY/MAX communication ports (Channels 1 and 2) which permit communication to
other SY/MAX processors via a direct point-to-point connection or over the SY/NET
Local Area Network using a SY/NET Network Interface Module (NIM). The Model
450 can function as a data concentrator to other SY/MAX compatible processors,
collecting data, and sending it via Ethernet to the host computer.
The Model 450 plugs into a register slot of any SY/MAX digital or register rack but
external I/O can only be directly controlled from the CPU slot in the rack. Ladder
programs from other SY/MAX controllers can be ported to the Model 450 requiring
only minor modifications involving addition or modification of SY/MAX read/write
instructions to facilitate Ethernet (Channel 3) communication.
Chapter 1 - Overview
30598-526
Page 1-3
1.4 HARDWARE FEATURES
The Model 450 takes advantage of multiple microprocessors and co-processors
for optimum performance. With a powerful scan processor, the Model 450 offers
scan speed of less than 1 millisecond per K of ladder logic. In addition to the scan
processor, a math co-processor accelerates math operations while a separate
Motorola 68010 processor and an AMD 7992 Ethernet controller provide
efficient Ethernet communications.
The Model 450 is available in a 4K (SCP452) or 8K RAM (SCP453) memory
size. Both versions have an additional 4K of processor image table registers
onboard. Each processor register can be assigned as a data value, 16 digital I/O
points, timer, counter, or other processor functions. In addition to the 4K of
processor registers, another 2000 storage (mailbox) registers are available in the
Ethernet NIM for use as buffer registers for applications requiring a data
concentrator. The storage (mailbox) registers can be accessed without impacting
the Model 450 processor scan time, via port 3.
The Model 450 offers a real-time clock/calendar that may be used for interval
timing of task execution and scanning operations. The clock/calendar and
processor memory are additionally supported by an onboard lithium battery that
allows the clock accuracy and contents of memory to be maintained when power
is removed from the Model 450. The charge levels for the onboard lithium battery
and the batteries in the SY/MAX power supply are monitored, and a front panel
“BATTERY LOW” LED indicates when either or both batteries require
replacement.
To assist in troubleshooting, the Model 450 makes use of diagnostic LEDs. The
LEDs annunciate processor status such as ETHERNET COMMUNICATION
ERROR. In addition to the LEDs, status registers can also be monitored for
troubleshooting purposes.
To maintain system security, the Model 450 has a four-position keyswitch that
allows selection of four operating modes: DISABLE OUTPUTS, HALT, RUN
and RUN/PROGRAM. Multi-level software security features can be used to
prevent data and control program alteration, restrict I/O forcing, prevent viewing
of some or all of the user program, restrict network access of information, and
provide password security.
1.5 INSTRUCTION SET
A versatile and powerful instruction set allows the Model 450 to perform over
100 functions. The instruction set includes full program scan control including
GOTO, subroutine, and timed interrupt capabilities. Also included in the
instruction set is drum sequencer and ASCII input capability. The Model 450 can
process ASCII data as input from devices such as weigh scales and bar code
readers, in addition to supporting SY/MAX ASCII output capabilities for ports 1
and 2.
The Model 450 has more than 60 floating point and special math functions as
well as PID instructions for performing closed loop control. The math processing
power of the Model 450 allows the user to free the host computer from the chore
of handling additional math operations. Refer to the Instruction Set Table in
Chapter 2 for the full list of instructions.
Chapter 1 - Overview
Page 1-4
30598-526
1.6 TECHNICAL COMPARISON
FEATURES
In terms of SY/MAX processor features and functionality, the Model 450 has product
characteristics similar to the Model 400, including the instruction set, method of
program execution, real-time clock/calendar, onboard battery, keyswitch positioning,
and operating modes. The major addition to the Model 450's features and functionality
lies in the capability to communicate over a high-speed Ethernet network. It is also
possible to install multiple Model 450s in one rack assembly, although only the
processor residing in the CPU slot can directly control external I/O.
The Model 450 differs from the Model 400 in several ways, including:
• The Model 450 is approximately 2.5 inches deeper than the Model 400.
• Current requirements are greater than the Model 400: 5.5 A @ 5 volts.
• The Model 450 has a number of Ethernet-related features such as the BNC
connector configuration switches, and Ethernet LED.
• The Model 450 has an additional Ethernet port 3.
Chapter 1 - Overview
30598-526
Page 1-5
1.7 FRONT PANEL FEATURES
LED STATUS INDICATORS
(See also Section 4.2 for more detailed information about LED operation.)
1
2
RUN (GREEN) - When ON steady, the processor is scanning ladder diagram program and
operating on I/O. When FLASHING, the processor is operating on ladder diagram program, but
is not energizing any outputs (Disable Outputs mode).
HALT (RED) - When ON steady, a processor fault has occurred. When FLASHING, the
processor has halted because of some other cause. In both cases, the processor has halted its
execution and is no longer scanning the program. For more information, see Section 4.2.
3
MEMORY (RED) - When ON steady in combination with the HALT LED FLASHING,
indicates that the processor is halted due to a memory error.
4
FORCE (RED) - When ON steady or FLASHING, I/O have been forced to an ON or OFF state,
thereby overriding the ladder diagram program.
5
6
7
8
I/O (RED) - When ON steady in combination with the HALT LED FLASHING, indicates the
processor has halted due to a malfunction in the I/O system. The I/O system is regarded as any
I/O or register module that the processor controls in a rack assembly.
BATTERY LOW (RED) - When ON steady, indicates that the onboard battery is low. When
FLASHING, indicates that the power supply batteries are low. The ON steady condition takes
precedence.
WRITE PROTECT (RED) - When ON steady, indicates that the user memory is protected by
the keyswitch positioned in the RUN mode and/or that the internal write-protect jumper is in the
NO PROGRAM position. When FLASHING, indicates some type of software-generated security
is in effect. The ON steady condition takes precedence.
ETHERNET COMM ERROR (RED) - When ON steady, indicates a fatal Ethernet hardware
error. When flashing, each off-on-off blink of the LED signifies one non-fatal network error. (The
LED flashes for those Ethernet errors that affect this Model 450 only.) Refer to Sections 4.2 and
Chapter 15 for more information.
OTHER PROCESSOR FEATURES
9
BATTERY ACCESS DOOR - Used to gain access to the processor’s on-board backup battery.
See Section 12.1.
10
KEYSWITCH (See Section 4.1)
11
RUN/PROGRAM - In this mode, the processor executes the ladder program and allows changes
to be made to the program while in RUN.
12
RUN - In this mode, the processor executes the ladder program but does not allow changes to be
made to the program while in RUN, or forcing to occur or be changed.
13
HALT - In this mode, the processor does NOT execute the ladder program and all outputs are
turned OFF.
14
DISABLE OUTPUTS - In this mode, the processor executes the ladder program, but outputs are
turned OFF.
15
COMMUNICATION PORTS (See Section 5)
16
RS-422 serial differential ports for connecting programming and peripheral equipment (PRGMR
CHNL 1 on front of unit and COMM CHNL 2 on bottom of unit).
17
ETHERNET port (CHNL 3, bottom rear) for connecting the Model 450 to a high-speed
ThinWire Ethernet network.
Chapter 1 - Overview
Page 1-6
30598-526
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
17
Figure 1-2 Model 450 Front Panel
Chapter 1 - Overview
16
30598-526
2
Page 2-1
SPECIFICATIONS
2.1 MODEL 450 SPECIFICATIONS
2.1.1 Electrical Specifications
Current Draw on SY/MAX Power
Supply
5.5 A ± 10% @ 5VDC ± 5%. The
PS-10, 11, 40, or 41 power supplies
must not be used, due to the current
requirements of the Model 450.
Memory Support Time from
SY/MAX Power Supply Batteries
4 month minimum (battery age less than
two years with only one Model 450 in
the rack). Primary backup power source
for ladder program, storage memory,
and clock/calendar when the Model 450
is in a rack during a power outage.
Battery low voltage status can be
monitored via contact status (bit 17 of
register 8176). Current draw is 80 µA @
4.2 VDC @ 40°C.
Onboard Battery
3.5 to 3.6V AA lithium (Tadiran
TL-5104 or SAFT LS6). Battery low
voltage status can be monitored via contact status (bit 32 of register 8176).
Memory Support Time From
Processor Lithium Battery
For detailed information on the
processor battery, please see Chapter
12.
Undervoltage Lockout Circuit
Halts and resets the Model 450 and
removes it from the SY/MAX bus when
incoming DC supply voltage falls below
4.6 VDC.
Chapter 2 - Specifications
Page 2-2
30598-526
2.1.2 Environmental Specifications
Ambient Temperature
Operational
Storage
32 to 140°F
(0 to 60 °C)
-40 to 176°F
(-40 to 80°C)
Relative Humidity
5-95%, noncondensing
Vibration
Vibrated in three axes from 5 to 14 Hz
at 0.2" (5mm) displacement, and 14 to
200 Hz (two G acceleration maximum)
for 90 minutes per X, Y and Z axis.
Dwell at resonance frequencies for 10
minutes.
Electrical Noise
Passes the following tests for noise:
• NEMA Part ICS 2-230 and IEC 65A
Part 5, Section 2.6.2.4 (Showering
Arc).
• ANSI / IEEE C37.90a, IEEE 472 and
IEC 65A Part 5, Section 2.6.2.5.
(Surge Withstand Capability)
• Chattering Relay (Landis) Test.
• Current Spike (Reversing Motor) test.
• ESD Protection meets IEC 65A Part 5,
Section 2.6.2.2.
2.1.3 Physical Specifications
Dimensions (without key)
(see Figure 2.1)
Width
Height
Depth
Chapter 2 - Specifications
1.5” (3.8 cm)
12.8” (32.5 cm)
9.5” (24.2 cm)
Dimensions (with key)
Key adds an additional .75 inch (1.9 cm)
to the depth when installed.
Weight (approx.)
5.3 pounds (2.4 kg)
30598-526
Page 2-3
Figure 2-1 Model 450 Physical Dimensions
2.1.4 Functional Specifications
Scan Speed
0.8 milliseconds per K Boolean
2.9 milliseconds per K nominal
NOTE: I/O update from the image table for 128 local digital points adds a
minimum of 0.3 milliseconds per scan. Refer to Section 14.2 for a
discussion of execution times.
Logic
Motorola® 68010 processor, Motorola
68881 math coprocessor, and AMD
29116 for ladder processing.
802.3/Ethernet and ThinWire
Specifications
IEEE 802.3 10BASE2 ThinWire
Ethernet
Data Rate
10 Mbits per second
Ethernet Communication
Motorola 68010 and AMD 7992
Ethernet Controller
Nodes per Segment
30
Nodes per Network
100 (using repeaters)
Maximum Segment Length
607 ft. (185 m)
Chapter 2 - Specifications
Page 2-4
30598-526
Maximum End-to-End Network
Length*
3034 ft (925 m or five 185m segments),
using repeaters
Minimum Cable Length between
Nodes
20 in (0.5m)
Maximum Drop Length
Less than 1-1/2 in (4 cm), use direct
connection to “T” connector
Controller
AMD AM7990
Serial Link Interface
AMD AM7992
Coaxial Transceiver Interface
National Semiconductor DP8392
Real-Time Clock/Calendar
Accuracy within one second per day @
77°F (25°C), 16 seconds per day over full
ranges:
Temp.: -32 to 140°F (0-60°C)
Relative Humidity: 5-95%
Memory
4K words (RAM)
8K words (RAM) (see Section 14.1)
SCP452
SCP453
User Memory Utilization
1 word per contact
User Memory Overhead
8 words
Front Panel LEDs
RUN, HALT, MEMORY, FORCE, I/O,
BATTERY LOW, WRITE PROTECT, and
ETHERNET COMM ERROR
External I/O
Over 4,000 digital and over 3,000 analog.
Any mix in groups of 8, 16, 32, or 64
digital points or 4, 8, or 16 analog points
per module is permitted.
Internal Relay Equivalents
16 per unused register (4,000 nominal total)
Processor Registers
Up to 4,000 retentive 16-bit integer
registers or 2,000 retentive 32-bit floating
point registers (in addition to user program
memory)
User-defined Storage (Mailbox)
Registers
2,000 retentive 16-bit integer registers (in
addition to processor registers and user
program memory)
Register Module Compatibility
All SY/MAX modules except Class 8030
Type CRM115 and CRM116 Bus
Expander/Terminator. (See Section 3.1 for
more information.)
*Applies
to 10BASE2 ThinWire Ethernet networks. Longer distances are possible using
repeaters with other media such as 10BASE5 Standard (ThickWire) Ethernet. See
Appendix D.
2.2 NEW FEATURES
Chapter 2 - Specifications
30598-526
Page 2-5
Following are enhancements to the Model 450 that are not offered in the SY/MAX
Models 300, 500, and 700 processors. The Ethernet feature is also not available in the
Model 400.
• Ethernet Communications (Chapter 15).
• Multiple Model 450s in the Same Rack (Section 3.7).
• Real-time Clock/Calendar (Section 12.2).
• Automatic Storage of Error Codes (Control Register 8107, Section 13.2)
• ASCII Input (Section 10.1).
• Drum Sequencer (Chapter 11).
• Onboard Lithium Battery (Section 12.1).
• RUN and RUN/PROGRAM Modes (Keyswitch Positions, Section 4.1).
• Variable ROUTE Rungs (Section 5.5).
• Undervoltage Lockout Circuit (Section 3.5).
2.3 REGISTER USAGE
The Model 450 can rack address up to 4000 user-definable registers, each having a
unique address value of 1 to 4000. These registers are located in an image table in the
Model 450 processor and are used to reflect external I/O and internal relay status, store
data, build shift registers, and accumulate time or count data in timers and counters.
Additional registers are used to indicate overall programmable controller system status
such as errors and keyswitch positions.
Each register is composed of 16 data bits and 16 status bits as illustrated in Figure 2-2.
The data bits are accessible to the user for data storage and may be represented in
binary or word form. The status bits cannot be changed or altered directly by the user,
but can be programmed as contacts or indirect status reads and monitored in the user
memory.
MODEL 450 REGISTER
17 16
32
16 Status Bits
1
16 Data Bits
Figure 2-2 Model 450 Register Structure
Control registers 8001 to 8192 are used to control and monitor the basic operation of
the Model 450. These registers are user-alterable, with the exception of registers 8179
to 8192 which are read-only system status registers, and can only be monitored. See
Section 13 for more information about control registers.
The floating point (FLP) mode combines two contiguous 16-bit data registers to form
one 32-bit floating-point data register. FLP registers allow manipulation of numbers
that contain floating decimal points. Refer to Chapter 7 for an explanation of “Floating
Point Math”.
Chapter 2 - Specifications
Page 2-6
30598-526
Figure 2-3 illustrates the register usage for digital I/O points, analog I/O points, integer
storage registers, and floating-point storage registers. Each digital I/O point occupies
one bit of one register; having 16 digital I/O points requires one complete register.
Each analog I/O point occupies all 16 bits of one register and two complete registers
are needed for each floating-point register.
One Digital I/O Point
16-BIT STORAGE REGISTER
One Integer Data Storage Register
One Analog Integer I/O Point
1/2 of a Floating Point Register
(two 16-bit registers are combined to form one
32-bit register)
Figure 2-3 Register Use
The actual hardware I/O capacity of the Model 450 is over 4,000 digital points and
3,000 analog points.
In addition, the Ethernet NIM has its own unique set of over 3,000 registers. Register
addresses 1 through 10 contain NIM status information, 11 through 2999 are not
accessible, 3000 through 4999 are retentive storage registers. Register addresses 5000
through 6999 are not used, and 7000 through 7999 contain Ethernet network
parameters. Ethernet NIM registers 1-10 and registers 3000-7999 are battery-backed.
See Section 15.4 for additional information.
2.4 INSTRUCTION SET TABLE
Instruction
Description
Remarks
Contacts
Represents ON/OFF status of inputs,
outputs, internal relays, and register bits.
Normally OPEN (NO) or normally
CLOSED (NC).
Input devices can be monitored in
HALT.
Coil
Represents an output connected to the
processor.
Upon a transition to RUN, all coils
are deenergized on the first scan.
During the second scan, all coils
are updated depending on the
solution of the logic in that rung.
Represents control relay functions
Operation is similar to an output,
but output devices are not directly
controlled.
Internal Relays
Chapter 2 - Specifications
Display
R-
30598-526
Instruction
Latch/Unlatch Relays
Display
L
U
Transitional Coil
Master Control Relay
T
MCR
Timer
TMR
Counter
CTR
Drum Sequencer
DRUM
Synchronous Shift
Register
Asynchronous Shift
Register (First In First
Out)
SHFT
FIFO
Data Comparison
IF
[=, ≠, ≥, <]
Page 2-7
Description
Remarks
Duplicates the action of a
mechanically-held latching relay. This is
accomplished through the use of two
internal relay coils with the same
address. Once a latch coil is energized, it
remains ON until the unlatch coil is
energized, even if power is removed.
Latch and unlatch rungs must be
programmed sequentially.
An internal or external coil which is only
energized on a transition of the logic from
OPEN to CLOSED. The output remains
ON for a single processor scan. The logic
must turn the coil OFF and transition to
ON again to re-energize the output coil.
Requires two consecutive I/O
addresses, one to record the
transition and one to remember
the last state. A transitional coil
MUST be assigned an ODD
address number. The processor
uses the next I/O address to
record the last state of this same
coil.
MCR ON allows logic to function. MCR
OFF turns the outputs except latched
coils OFF. MCR controls all succeeding
rungs until a new MCR coil is
programmed or the end of the program is
reached.
Timer register stores a 4-digit decimal
value from 0 to 9999. Selectable time
bases are 0.01 sec., 0.1 sec., and 0.1
min.
Allows for programming ON/OFF
delays and interval timers.
Replaces timing relays and
motor-driven timers.
Counter register stores a four-digit
decimal value from 0 to 9999. UP,
DOWN, and UP/DOWN counters are
standard.
Counters can be cascaded to
obtain a count greater than four
digits.
Simulates the action of a rotary drum
switch.
Manual or automatic time, event,
or a combination of time/event
sequencing.
Used to shift individual bits of a storage
register in either a forward or reverse
direction. 1, 8, or 16-bit channels can be
shifted at a time.
Used in applications that require
the user to keep track of bit
patterns.
Data is loaded into the first zone and
exits out the last zone using IN and OUT
commands, respectively. 8- or 16-bit
channels can be shifted at a time.
Used to record the order of events
as they occur, such as in
conveyor or alarm annunciation.
Compare functions between storage
registers, between an integer and a
constant, or between a floating point
storage register and a constant. When an
IF comparison is true, the IF box acts like
a short circuit.
Up to three comparisons can be
programmed on one line. In
integer mode, numbers from
-32,768 to 32,767 can be
compared. In floating point mode,
a range from -3.4 x 1038 to 3.4 x
1038 and values as small as ± 1.2
x 10-38 are allowed. Math and
SPECIAL functions can be used
in IF statements.
Chapter 2 - Specifications
Page 2-8
30598-526
Instruction
Display
Data Transfer
LET
Transitional LET, IF
TLET
TIF
Indirect Register Read
Transition-sensitive; restricts the
operation of the LET or IF instruction to
one operation for each OPEN to
CLOSED transition of the input condition.
Indirect register read of data field
BCD to Binary
BIN
Chapter 2 - Specifications
Ranges are the same as for Data
Comparison. Math and SPECIAL
functions can be used in LET
statements.
RDDATA
BCD
Advanced Math and
Trig Operations
Transfers data from one storage register
to another or presets a constant into a
storage register. Also performs integer or
floating-point or combined mode math.
Indirect register read of status field
Binary to BCD
Addition
Subtraction
Multiplication
Division
Square Root
Absolute Value
Change Sign
Sine
Cosine
LOG10
LNE
(Y)x
Remarks
RDSTAT
FNDBIT
Standard Math
Operations
(Integer and floating
point math):
Description
LET
IF
+
x
÷
SQRT
ABS
NEGATE
SIN
COS
LOG
LN
Y**X
INVERT
ROUND
XSQRD
HYPOT
HYPXYZ
TANGNT
COSEC
SECANT
COTAN
ARCSIN
ARCCOS
ARCTAN
ARCCSC
ARCSEC
ARCCOT
Locate and clear the first bit (lowest bit
number) set in the indirect register being
read.
Conversion of binary data in a storage
register to its binary coded decimal
(BCD) equivalent within a LET or IF
instruction.
Allows the processor to drive a
BCD-type of LED display.
Conversion of binary coded decimal
(BCD) data in a storage register to its
binary equivalent within a LET or IF
instruction.
Used in applications to convert
the ON/OFF thumbwheel switch
position status to binary form
which the processor can operate
on.
Math operations are performed from left
to right, and are programmed into LET or
IF instructions.
The result of any integer math
operation must not exceed
±32,767, or an overflow condition
will result.
The intermediate result of an
integer computation cannot fall
outside ±2,147,483,647, or an
overflow condition will result.
The result of any floating-point
math operation must not exceed
±3.4 x 1038 or be smaller than
±1.2 x 1038, or an overflow
condition will occur.
The intermediate result of a
floating-point computation cannot
fall outside the range of ±3.4 x
10-4932 to ±1.2 x 10+4932.
Value range for integer math operations:
-32,768 to +32,767
Value range for floating-point math operations:
-3.4 x 1038 to 3.4 x 1038, not smaller than
±1.2 x 10-38.
See Section 7, “Floating-Point Math.”
Divide 1 by the current result (1/x).
Round floating point number to integer.
Square the current result
Calculate 2-dimensional hypotenuse.
Calculate 3-dimensional hypotenuse.
Calculate tangent.
Calculate cosecant.
Calculate secant.
Calculate cotangent.
Calculate arc sine.
Calculate arc cosine.
Calculate arc tangent.
Calculate arc cosecant.
Calculate arc secant.
Calculate arc cotangent.
30598-526
Instruction
Advanced Math and
Trig Operations
(cont’d)
Display
SETDEG
SETRAD
DEGRAD
RADDEG
PI
L2T
L2e
LG2
LN2
EULER
e
1 DEG
1 RAD
e**PI
PI**e
e**e
e**EUL
SQ(e)
SQ(PI)
Statistical Operations
Description
Page 2-9
Remarks
Perform subsequent calculations in
degree mode.
Perform subsequent calculations in
radian mode.
Convert degrees to radians.
Convert radians to degrees.
The following constants are stored to
80-bit precision:
Multiply result by pi (3.14159...).
Multiply result by log base 2 of 10.
Multiply result by log base 2 of natural log e.
Multiply result by log base 10 of 2.
Multiply result by log base e of 2.
Multiply result by EulerÕs Constant.
Multiply result by natural log e.
Multiply result by 1 degree in radians.
Multiply result by 1 radian in degrees.
Multiply result by eπ.
Multiply result by πe.
Multiply result by ee.
Multiply result by eEuler.
Multiply result by square root of e.
Multiply result by square root of pi.
ADDSTA
Store current result in statistical block of
registers consisting of the summation of
previous values, summation of the
squares of previous values, and the
accumulated count of previous values.
VARNCE
Calculate statistical variance on the
accumulated totals in the statistical block.
PID Computations
PIDREV
PIDDIR
PIDMAN
LD/LAG
Calculate reverse-acting PID loop.
Calculate direct-acting PID loop.
Calculate PID loop in manual.
Calculate lead/lag function for PID loop.
Accumulator
Manipulations
Y**ALT
Same as (Y)x except X in this case is
taken from the alternate accumulator
instead of the second argument.
SWAP16
Exchange low and high bytes of the
current intermediate result.
SWAP32
Exchange low and high words of the
current intermediate result.
ACCALT
Exchange current accumulator with the
alternate accumulator.
ADDALT
Add alternate intermediate result from the
alternate accumulator.
SUBALT
Subtract current intermediate result from
the alternate accumulator.
DUPALT
Copy alternate accumulator into current
accumulator.
DUPACC
Copy current accumulator (intermediate
result) into alternate accumulator.
HYPALT
Same as HYPOT except the alternate
accumulator is used instead of the
second argument.
ATNY/X
Similar to ARCTAN except that the
function is performed on the ratio Y/X.
These manipulations maintain an
80-bit precision when performing
calculations that extend beyond a
single rung.
Chapter 2 - Specifications
Page 2-10
30598-526
Instruction
Display
Description
Identify Number Type
NUMTYP
Identifies mathematical classification of
the current intermediate result.
Forcing
CRT INITIATED
Forcing overrides the actual input status
or output as controlled by the ladder
diagram.
Serial Communication
to Other Processors or
Peripherals
TREAD
TWRTE
TALRM
TPRNT
Copy storage register and I/O status
between devices which may be located
up to 10,000 feet apart. All four are
transition-sensitive.
Read
TREAD
Copies storage register data from remote
device to local processor.
Write
TWRTE
Copies storage register data from a local
processor to a remote device.
Alarm
TALRM
Sends a numerical value from a local
processor to a remote device.
Numeric values from -32,768 to
+32,767 can be transferred.
Print
TPRNT
Sends ASCII-coded messages from the
processor to any device that
communicates in ASCII.
Simplified means of producing
alarm messages, production
reports, etc.
ASCII Input
TPRNT
Accommodates a block size of up to 256
characters with block termination based
on either character count or a delimiter
character. Supports various word
structures including parity.
Allows the processor to interface
directly with bar code readers,
weigh scales, and other similar
devices.
^
A logical function used within an IF or
LET command with the following
property: if X and Y are two logic
variables, then the function “X AND Y” is
defined as:
Integer mode only.
(ASCII Input command not
applicable for ETHERNET
(Channel 3) port).
AND
X
0
0
1
1
OR
V
R
0
1
0
1
Requires no additional interface
hardware.
X AND Y
0
0
0
1
A logical function used within an IF or
LET command with the following
property: if P and R are two logic
variables, then the function “P OR R” is
defined as:
P
0
0
1
1
Chapter 2 - Specifications
Y
0
1
0
1
Remarks
P OR R
0
1
1
1
Integer mode only.
30598-526
Instruction
Display
Exclusive OR
(XOR)
Description
Remarks
A logical function used within an IF or
LET command with the following
property: if S and T are two logic
variables, then the function “S XOR T” is
defined as:
Integer mode only.
S
0
0
1
1
T
0
1
0
1
Page 2-11
S XOR T
0
1
1
0
Random Number
Generator
RANDOM
Generates a random integer number.
Results in a positive random
number that ranges from zero to
the value of the argument minus
1.
GOTO
GOTO
Instruction to cause the processor to skip
over a section of the program to another
specified position in the program.
Position is determined by a MARK rung
placed in memory.
Shortens processor scan time
during the immediate jump to a
new rung position in the program.
Can jump forward or backward.
Subroutines
GOSUB
Group of ladder diagram rungs that can
be executed from the user’s ladder
diagram. Only enabled by a GOSUB
instruction programmed in the main
program.
MARK ST.SUB
Denotes the beginning of the subroutine
area.
Applications include variable
sequence machines, recipe
programs, and redundant
processes.
Nesting (subroutines within
subroutines) is allowed up to 8
levels deep.
RTN
The end of a subroutine. Causes the
processor to jump out of the subroutine
and return to the main program.
S8165
A special safeguard rung using register
8165 allowing the following features:
Timed Interrupt,
Communications and
Register Inhibit, Scan
Time Limit
1. Communications Inhibit
Protecting programs.
Used in conjunction with:
8176
2. Program Viewing Inhibit
3. Register Safeguarding
16
4. Timed-Interrupt Scan Control
5. Scan Time Limit
Matrix
M
LET M
IF M
TIF M
A matrix is a group of storage registers
handled as a unit. Formulates
multi-register data transfers and math
functions. Also allows multi-register
compare statements.
Array
A
LET A
IF A
An array is a group of 32-bit floating point
data storage registers operated on as a
unit. Formulates multi-register data
transfers, compares, and math functions.
End of Scan
Communications
Update
S8170
16
Applications include machine
diagnostics and menu selection.
If set to 1, the processor finished
servicing the incoming communications
message before resuming the ladder
scan. See Section 5.6.1.
Chapter 2 - Specifications
Page 2-12
30598-526
Instruction
Immediate I/O Update
Display
S 8176
07
Bus Write to Microcell
Immediate
Communications
Update
SPEC 67
S 8176
Description
Remarks
Setting bit 7 of register 8176 to 1 (with a
ladder rung) causes the processor to
interrupt its memory scan and
immediately update selected external I/O
points. Inputs are written to the image
table and outputs are read from the
image table.
Registers to be updated are
user-defined.
Allows the processor to immediately
update Microcell storage registers via the
backplane.
See Section 8.6.
Processes incoming messages from
communication ports 1, 2, or 3 received
during processor scanning.
11, 12, or 13
Extended EOS Comm
Servicing
S 8170
16
Chapter 2 - Specifications
Allows the processor to utilize more than
5 ms at the end of each ladder scan to
finish processing the entire block of
registers associated with an incoming
COMM message.
Helps preserve data integrity for
multiple register blocks; see
Section 5.6.1.
30598-526
3
Page 3-1
INSTALLATION
This section discusses the following topics related to the Model 450 processor:
• Differences in operating characteristics compared to other SY/MAX devices and
certain functions
• Rack configurations
• Use of register modules
• Installation considerations
• Undervoltage lockout circuit operation
• Rack addressing.
NOTE
If the Model 450 is replacing a SY/MAX Model 300, 500, or 700
processor in an existing system, be sure to read the following
sections to determine if certain processes must be changed
before installing the Model 450 processor.
3.1 OPERATING CHARACTERISTICS OF THE MODEL 450
The Model 450 is compatible with other SY/MAX devices; however, performance
and/or functional characteristics in relationship to the SY/MAX Model 300, 500, and
700 processors may be different. Note that replacing another processor in an existing
system with the Model 450 may require additional changes and the system may not
operate exactly as before. Due to the identical processor architecture and operating
system of the Model 400, aside from the exceptions listed in Section 3.1.2,
“Differences in Function,” the Model 450 operates in a system similarly to a Model
400.
For example, the Model 450's user ladder program is executed based upon the state of
an onboard “image table”. The image table is updated at the end of every scan. This
process is similar to the Model 300 and 400 operation but is different from the method
used by Model 500 and 700 processors. The 500 and 700 use real-time bus updates;
register information being used to execute the ladder program resides in modules
outside of the processor and not in an internal image table.
In some cases, the programmable controller system may respond differently because
of the Model 450's increased processor speed. Also, differences in how the Model 450
implements certain functions, such as forcing, produces results that are not the same as
observed in a Model 500 or 700 system.
Chapter 3 - Installation
Page 3-2
30598-526
3.1.1 Differences When Used with Certain Modules
The following modules produce characteristic differences when used with the Model
450 processor:
Type CRM-115/116 Bus Expander/Terminator Modules
Due to bus timing delays, these modules are NOT compatible with the Model 450. In
most cases, the Type EQ5138-G1/G2 Parallel Digital Driver/Receiver (PDD/PDR)
modules can be substituted. See Appendix C.
Local Interface (LI) and Local IO/NET Interface (LIO) Modules
These modules are compatible with the Model 450, but cannot be used to provide
additional storage registers for the Model 450. The rack addressing that currently
exists for another processor can be used with a Model 450 system. However, any
registers that are assigned to an LI in the CPU rack and that are not assigned to remote
drops will decrease throughput. See Section 3.6.5.
Local Transfer Interface (LTI) Modules
These modules are compatible; however, due to the image table in the Model 450,
certain application considerations must be observed. See Appendix B for operating
considerations when using the Model 450 in a redundant LTI-equipped system.
Parallel Digital Driver/Receiver (PDD/PDR) Modules
These modules (Type EQ5138-G1/G2) are compatible with the Model 450 as long as
certain rack addressing procedures are observed. Refer to the “Rack Addressing
Register Allocation” discussion in Section 3.6.4.
NOTE
If a Model 450 replaces a Model 500 or 700 in an existing system that
contains PDD/PDR modules, rack addressing must be reviewed to
determine if it is suitable or if alterations are required.
3.1.2 Differences in Function
The following functions produce different results when used with the Model 450 than
when used with SY/MAX processors other than the Models 400 and 600.
Results of Forcing I/O
Forcing in the Model 450 is implemented outside of the image table and is actually
performed directly on the external I/O. It is important to note that the forced state may
not be reflected in the image table. For example, the contacts of a forced output reflect
the ladder logic state and not the forced state of the output. Refer to Section 14.4 for
more information.
Timed Interrupt Subroutine
Due to the end-of-scan (EOS) update operation of the image table, a timed interrupt
which executes more than once per ladder scan operates on unchanged external I/O
information. The timed interrupt tolerance must also now allow for the time required to
Chapter 3 - Installation
30598-526
Page 3-3
complete an EOS update since an interrupt cannot be called while external I/O are
being serviced. Refer to Section 6.8.1 for more information.
Matrix IF Instructions
The Model 450 may not scan some conditional elements in a rung that has no effect on
the logical solution of the output. This optimizes scan time and increases processor
scan performance.
For example, if a rung contains a leading contact that is open, other conditional
elements between the contact and the output element have no effect on its logical
solution. If a rung contains a matrix IF instruction preceded by FALSE conditional
logic, the matrix IF instruction is simply skipped over and not scanned. This differs
from the Model 500 and Model 700 where bits 17 and 18 of the status register are reset
when a matrix IF rung is executed FALSE. Thus, bits 17 and 18 in the status register of
the matrix IF box should be ignored when using a Model 450 processor.
Matrix Transitional IF Instruction
As explained previously, the Model 450 does not always scan all conditional elements.
The matrix TIF instruction executes differently than for the Model 500 and 700, and
because of this the matrix TIF instruction must be preceded by a transitional contact.
NOTE
For the Model 450 to behave as described in the programming manual,
the Matrix IF instruction must be preceded by a transitional contact
(that is, a contact energized by a transitional coil).
SCP-344 RAM/UVPROM Processor
The SCP344 requires the programming of two safeguard rungs that reference TLET
S8164 and S8165. If a Model 450 replaces an SCP344, these TLET rungs must either
be removed or replaced with a TLET S8165 safeguard rung with new security features
that are executed in accordance with Section 6.8.
NUMTYP Instruction
If the Model 450 replaces a Model 700 processor, the NUMTYP instruction yields
slightly different results due to the difference in math coprocessors used. Refer to
Section 8.6 for further details.
Asynchronous Shift Register (FIFO)
If the Model 450 replaces a Model 300 processor, the FIFO operation is different in the
handling of the last zone of the stack. In the Model 300, the DATA OUT zone is the
last zone of the stack. In the Model 450 (as in the Model 500 and 700), the
second-to-last zone is the bottom of the stack and the last zone is used as the DATA
OUT zone. Because of this, the Model 450 does not accept a FIFO with a defined stack
of less than 3 registers (ERROR 05 is generated). Refer to the programming
Instruction Bulletin for more information.
Chapter 3 - Installation
Page 3-4
30598-526
Memory Use
If a Model 450 replaces any SY/MAX processor other than Models 400 or 600, more
memory is typically required to store the same program in the Model 450. For
example, each new rung requires an additional 1/3rd of a word, while each new
parallel branch now consumes a complete word. A good rule of thumb when
transferring a program to a Model 450 is to allow 10% more memory than the size of
the original program. See Section 14.1 for more details on memory usage.
Counter Decode Equal to 0
If the Model 450 replaces a Model 300 processor which has a program containing a
counter rung with a decode of 0, the Model 450 will de-energize its associated output
whenever the logic in the CLEAR line is false; under the same conditions, the Model
300 will energize the output. Note that both processors will energize the output when
the decode value equals 0 and the logic in the CLEAR line is true.
Editing in RUN/PROGRAM Mode
If a Model 450 replaces a Model 300, 500, or 700 processor, the scan time may
increase substantially for a single scan when an edit is performed while the processor
is running. The difference in scan speed is a one-time occurrence and slower system
response may be observed than when editing the same program in a Model 300, 500,
or 700 processor. Refer to Section 14.2.2 for additional information when editing in
the RUN/PROGRAM mode.
Multiple Model 450s in the Same Rack
While multiple Model 450s may reside in the same rack, only the processor in Slot 1
can directly control external register modules and I/O. Communication through the
backplane is not supported. Refer to Section 3.7 for information on rack addressing
multiple Model 450s in the same rack.
3.2 RACK CONFIGURATION
Single or multiple Model 450s can be installed in any CPU or register slot of any
SY/MAX register or digital rack assembly. The CPU and register slots are identified in
each rack in Figure 3-1 on page 3-5. The CPU and register slots contain a rear edge
connector that provides the appropriate bus lines, +5VDC, and common for the Model
450 operation. To directly control external I/O and the various I/O modules configured
in any rack, the Model 450 MUST be installed in the CPU slot or Slot 1.
NOTE
If multiple Model 450s are installed in the same rack, only the processor
in Slot 1 can communicate over the backplane with the other modules.
The only way a Model 450 residing in a slot other than Slot 1 can
communicate with other devices is through the Ethernet or serial ports.
Refer to Section 3.7 for information on rack addressing a Model 450 not
installed in the CPU slot (Slot 1).
If the Model 450 is installed in a single rack configuration and only four-function or
eight-function digital I/O are used, rack addressing is not required. The I/O addresses
automatically revert to the default for the local I/O. If the Model 450 is installed in a
Chapter 3 - Installation
Page 3-5
30598-526
multiple rack configuration and register modules (including 16 or 32-function digital
I/O) are used, the corresponding registers and locations must be rack addressed. See
Section 3.6 for more information on rack addressing.
3.3 REGISTER MODULES
Register modules (also referred to as intelligent I/O) usually contain an onboard
microprocessor and can handle more complex input and output data manipulation than
the digital I/O modules. Register modules include analog I/O, BCD multiplexed I/O,
and high-speed counter modules.
The register modules are installed in register slots in the various racks. Depending
upon the type of digital or register rack used, the number of register slots varies from 0
to 15. Figure 3-1 identifies the register slots in each type of digital or register rack.
R4 R3
R
E
G
I
S
T
E
R
R
E
G
I
S
T
E
R
R1 R2
C
P
U
R
E
G
I
S
T
E
R
R2 R1
R
E
G
I
S
T
E
R
C
P
U
R3 R4
R
E
G
I
S
T
E
R
R
E
G
I
S
T
E
R
D
I
G
I
T
A
L
D
I
G
I
T
A
L
R5 R6
R
E
G
I
S
T
E
R
R
E
G
I
S
T
E
R
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
Eight-Function
DIGITAL Rack
(Type HRK150)
R7 R8 R9
R
E
G
I
S
T
E
R
R
E
G
I
S
T
E
R
R
E
G
I
S
T
E
R
R2
R1
R
E
G
I
S
T
E
R
C
P
U
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
D
I
G
I
T
A
L
Eight-Function
DIGITAL Rack
(Types HRK100, HRK200)
REGISTER Rack
(Type RRK)
Figure 3-1 CPU and Register Slot Locations in a Digital or Register Rack Assembly
3.4 INSTALLING THE MODEL 450
To install the Model 450 in a SY/MAX digital or register rack, do the following:
1. Open the battery access door on the front of the Model 450 and observe the battery
contact polarity as shown on the inside of the battery compartment cover. Install
the lithium battery by matching the + and - polarities of the battery and the contacts
in the battery compartment. Close the battery door and tighten the latching screw.
Record the date of the battery installation on the door.
2. If the Model 450 processor is to be installed in a CRK, DRK, or GRK four-function
digital I/O rack, the side plate shipped with the Model 450 must be removed and
replaced with an optional side plate P/N C30609-350-01A (contact a Square D
Chapter 3 - Installation
Page 3-6
30598-526
distributor to obtain this part). The optional plate allows sufficient clearance
between the side plate of the Model 450 and the edge connector in the rack.
3. The Model 450 requires + 5VDC, common, and a proper current rating of 5.5A to
operate. Make sure that the SY/MAX power supply is capable of delivering the
current required by all the devices in the rack and any other racks being driven by
the same supply. The number of Model 450s in the same rack is limited to the
possible current output of the power supply used; a single PS31 or PS61 should not
be used to power more than 3 Model 450s.
NOTE
A PS10, -11,- 40, or -41 power supply does NOT supply enough
current for a Model 450 system. Refer to Instruction Bulletin
#30598-159 or #30598-802 (power supply instruction bulletins) to
calculate the total current requirement for each module and processor
configured in the system and the proper power supply to use.
CAUTION
POTENTIAL EQUIPMENT DAMAGE
Do NOT remove or install a SY/MAX module with power
applied. Turn OFF the power at the power supply and wait
until all LEDs are off before removing the module.
Failure to observe this precaution could result in equipment
damage or personal injury.
WARNING
HAZARDOUS VOLTAGE
Do NOT remove or install a SY/MAX power supply or power
cable to the rack with power applied. Turn OFF the power at
the power supply and remove or unplug the incoming AC
voltage line.
Failure to observe this precaution can result in severe personal
injury or death!
4. Make sure that the rack is mounted in an area where the temperature around the
Model 450 never exceeds 140° F (60°C). Mount the rack so the Model 450 is
installed in a vertical position.
5. Use a Square D Class 8030 Type CC10 power cable to connect the Model 450's rack
to the SY/MAX power supply. Connect the CC10 cable from the power connector
Chapter 3 - Installation
30598-526
Page 3-7
on the rack to the P1 connector on the power supply. If the CC10 cable is not used,
the BATTERY LOW LED on the Model 450 will falsely indicate a low battery.
6. The DlP switches at the rear of the Model 450 have been set at the factory to all 1's,
indicating non-Ethernet mode. The rotary switch factory setting will vary, but its
setting will not affect the drop number, in this mode. See Chapter 15 for information
about Ethernet mode DIP switch settings before installing.
7. To directly control external I/O, the Model 450 MUST be installed in the CPU slot
in the rack assembly. For installation into the CPU or any register slot, apply
steadily increasing pressure to the front of the processor. Press until the Model 450
is firmly seated in the edge connector and is against the stud located above the CPU
slot.
NOTE
The Model 450 can ONLY directly control external I/O if installed in
Slot 1 (the CPU slot) of any digital or register rack. Multiple Model 450
processors can be installed in other register slots; however, external
I/O control is only provided through the CPU slot (1).
8. After the processor is properly seated in Slot R1 or a register slot, close the latching
bar located above the module slots (not applicable for four-function racks).
9. Tighten the captive screw to the bottom of the processor for a solid connection and
ground between the processor and the edge connector in any slot.
10. Install the AC power line to the SY/MAX power supply and turn on the power
switch on the SY/MAX power supply.
11. Multiple Model 450s in the same rack MUST communicate either through Ethernet
or the serial communications ports. Backplane communications for multiple
processors in the same rack IS NOT supported.
12. See Chapter 15 for additional information on Ethernet hardware and installation
considerations.
3.5 UNDERVOLTAGE LOCKOUT CIRCUIT OPERATION AND AC FAIL FUNCTION
The Model 450 is designed with an onboard DC Undervoltage Lockout Circuit (ULC)
that monitors the incoming DC voltage level at the edge connector in either the CPU or
register slots. If the incoming DC voltage falls below 4.6 volts, the processor enters the
HALT state and disconnects from the backplane bus. If a DC undervoltage condition
occurs, the processor is not warned ahead of time to execute an orderly shutdown.
If multiple Model 450s are installed in the same rack, due to circuit tolerance
differences and power distribution characteristics, it is possible that some processors
might continue operating while others have shut down if the DC power is marginal.
When the incoming DC voltage rises above 4.6 volts, the Model 450 executes a
standard power-up initialization sequence, but remains in the HALT mode. To resume
the RUN state, toggle the keyswitch from RUN to HALT, then back to RUN. When the
ULC is triggered, an ERROR 902 (see Appendix A, Table A-3) is posted in register
8175, identifying the failure.
Chapter 3 - Installation
Page 3-8
30598-526
NOTE
When the ULC system is activated, none of the LEDs are illuminated
on the Model 450.
AC FAIL Function
The Model 450 also monitors an incoming DC signal identified as AC FAIL. AC FAIL
is generated from all SY/MAX power supplies and indicates when the incoming line
side voltage to the power supply has been lost or degraded.
The operation of the AC FAIL is different from the ULC because the AC FAIL signal
alerts the processor to execute an orderly shutdown. The ULC is not able to alert the
processor of an impending DC power loss. Abnormal conditions, such as an
overloaded power supply or cable disconnection between the rack and the power
supply, can cause an unexpected interrupt of DC voltage.
As long as the Model 450 is receiving adequate power, at least one of the eight LEDs
on the processor's front panel will be ON. If all of the Model 450 LEDs are OFF (or
flashing erratically), a problem resides in the power source and should be repaired or
replaced. Use the procedures in Section 3.5.1 to determine the various power problems
that may be the cause of a malfunctioning Model 450.
3.5.1 Troubleshooting Power Problems
If the system is powered up and none of the LEDs are illuminated on the Model 450,
use the following procedure to determine the problem:
1. Make sure the SY/MAX power supply is receiving proper incoming AC voltage.
2. Check the in-line AC fuse and replace if blown.
WARNING
HAZARDOUS VOLTAGE
Remove incoming AC power to the power supply before
checking or replacing the AC in-line fuse.
Failure to observe this precaution can result in severe personal
injury or death!
3. Check that the power supply is able to deliver the proper amount of current for the
system configuration. Refer to Instruction Bulletin #30598-156 or #30598-159 for
a listing of current draws for various SY/MAX modules.
NOTE
Each Model 450 requires 5.5 A @ 5VDC to operate.
Chapter 3 - Installation
30598-526
SHIELD
SIGNAL COMMON
SIGNAL COMMON
+5 VDC
5
+5 VDC
4
DATA IN +
3
DATA IN -
2
DATA OUT +
1
DATA OUT -
Page 3-9
9
8
7
6
Figure 3-2 COMM and PRGMR Port Voltage Test Points
If the problem persists:
Check for + 4.75 to + 5.25VDC across pins 5 and 7 of the Model 450's serial port (COMM
or PRGMR port) with a voltmeter. Use Figure 3-2 for pin and signal identification.
• If the voltage across pins 5 and 7 is zero, use the following to determine the problem:
If power is not reaching the rack:
1. Check that the CC10 cable between the power supply and the rack is securely
connected and is making good contact.
2. Visually check that all the pins in the connectors in the power supply, the rack, and
on both ends of the cable are the same height. If one or more are lower, pull the pin
out until it is the same height as the other pins.
3. Check the continuity of the wires in the CC10 cable with a meter. Replace the cable
if an OPEN is detected.
4. Check the voltage at the P1 connector on the SY/MAX power supply. If power is
not present at the P1 connector, replace the power supply.
If DC power is being short-circuited:
1. Turn OFF power to the rack and check that all of the modules are properly seated.
Turn ON power and see if the problem is resolved.
2. If step 1 did not resolve the problem, turn OFF power to the rack, then remove and
reinstall each module one at a time. Turn ON power to the rack after each module
is reinstalled and check for proper operation.
3. If a voltage problem is found in a slot of the rack or the rack has been damaged,
replace the rack.
• If the voltage across pins 5 and 7 is greater than zero but less than 4.6 VDC, the ULC
has properly prevented operation of the Model 450. Use the following procedure to
identify why the low input voltage is being supplied from the power supply.
Chapter 3 - Installation
Page 3-10
30598-526
1. As previously mentioned, the problem could reside in the integrity of the CC10
cable or cable connections. Refer to steps 1 and 2 in the section “If power is not
reaching the rack” on the previous page to check the CC10 cable.
2. Check for excessive current draw from other modules in the rack. Check the current
requirements for each module in the system and the power supply current rating (see
Instruction Bulletin #30598-159). If the power supply is rated under the total system
current requirement, replace the power supply with an appropriately rated power
supply.
3. Once these possibilities have been eliminated, replace the power supply.
If the previous troubleshooting procedures failed to resolve the problem, simplify the
system by turning OFF the power to the rack and removing all of the modules from the
CPU rack except for the Model 450. Turn ON the power to the system and see if the
Model 450 powers up properly.
Power OFF the system, reinstall the next module, and turn power ON checking for
proper operation. Continue with this procedure for the modules that are to be
reinstalled until the problem module or slot is identified. Make sure that the power to
the rack is turned OFF before removing or installing any module. This procedure
offers the best systematic approach for isolating the power or component failure as
quickly as possible.
3.6 RACK ADDRESSING A MODEL 450 IN THE CPU SLOT
A Model 450 Programmable Controller system consists of a Model 450 processor,
digital and/or register racks with SY/MAX power supplies, and various interface and
function modules. A great amount of flexibility exists when configuring and
addressing Model 450 system components. Because of this flexibility, proper rack
addressing is extremely important.
NOTE
The following sections apply ONLY to a Model 450 installed in Slot 1,
the CPU slot. For rack addressing a Model 450 processor that is NOT
installed in Slot 1, no registers are assigned to any slots.
3.6.1 Initial System Layout
Rack addressing is determined by the physical layout of a PLC system and is based on
the following procedure:
1. Determine the physical location of the CPU rack and all other desired digital I/O
and register racks.
Chapter 3 - Installation
30598-526
Page 3-11
NOTE
Remote racks can be located a total cable length of 10,000 feet (3050
meters) away from the CPU rack if LI/RI modules are used. (Refer to
the LI/RI instruction bulletin #30598-247 for more information.)
PDD/PDR modules limit the distance between the racks to 6 feet.
LIO/RIO distance depends on the communication rate. Refer to the
LIO instruction bulletin #30598-782.
2. At each drop location, list the digital I/O requirements (type and quantity) along
with any needed register modules. This determines the total number of modules,
racks and power supplies needed.
3. Based on the total number of I/O modules, determine the number of Local Interface
(LI) modules, Remote Interface (RI) modules, Local IO/NET Interface (LIO)
modules, and Remote IO/NET Interface (RIO) modules needed. See SY/MAX
Local/Remote Interface Modules Instruction Bulletin (#30598-247) and the LIO
instruction bulletin (#30598-782) for further details.
3.6.2 Processor Operation
The Model 450 executes the user's ladder logic program based on an image table. This
image table, which can be visualized as being composed of external I/O and data
storage registers, is updated (inputs are read from, and outputs are written to, the
external world) at the end of every scan. An immediate I/O instruction can be
user-programmed to momentarily interrupt a scan to update a user-defined portion of
the image table (refer to Section 13.2 for information on bit 7 of register 8176).
The Model 450 has 4000 on-board registers; in this respect the Model 450 differs
significantly from the SY/MAX Model 500 or 700. The Model 500 has 460 on-board
registers but is able to address up to 2008; the Model 700, with no on-board registers,
can address up to 8000. These “extra” registers used by Models 500 and 700 do not
actually exist until other register modules such as the Local Interface are installed into
the CPU rack.
The Model 450 is able to address all 4000 of its on-board registers. This means that it
is no longer necessary to add Local Interface modules to obtain extra storage registers,
since these extra registers already exist within the Model 450. Therefore, the only
purpose for adding a Local Interface module to the Model 450's CPU rack is to provide
the serial communication link to any remote I/O.
When a Revision 4.0 (or later) processor is used with the Class 8030 Type CRM250
Local IO/NET Interface Module, up to 4000 registers may be transferred to the Local
Interface for use as external registers. A Revision 4.0 or later processor must be used
with the IO/NET (Passport™ I/O) system.
Local Interface modules can be installed in Slot R2 of the four-function and
eight-function digital racks, and in any slot (except Slot R1) of the HRK-150 and
register racks. Refer to the LIO/RIO instruction bulletins for more information about
using the LIO/RIO modules with specific racks.
Chapter 3 - Installation
Page 3-12
30598-526
NOTE
In the RRK300 rack, slots 17 and 18 cannot be used for a Local
Interface or for a Local lO/NET Interface Module.
Sufficient registers should be assigned to each Local Interface module to account for
all present and anticipated future external I/O, both digital and register, that will exist
on remote drops.
Refer to Section 14.2 for information on what effects rack addressing and register
allocation have on system response, and Instruction Bulletin #30598-247 for more
information on Local and Remote Interface modules. Refer also to the Local IO/NET
Interface Module Instruction Bulletin, #30598-782, for more information about the
LIO/RIO modules.
3.6.3 Determining Rack Addressing Needs
Use the following procedure to determine addressing needs:
1. Create a system layout sketch showing the CPU rack, and all other racks with I/O
wiring. This layout sketch ensures proper assignment of racks to Local Interface
channels. Each Local Interface module has two channels (l and 2); each channel
can address 8 racks (drops). Each Local IO/NET Interface module has one channel
with up to 32 drops physically divided up into 4 channels with 8 logical drops.
Refer to the LIO instruction bulletin (#30598-782) for more information.
2. Rack address the PLC system. Install the Model 450 processor in the R1 CPU slot
in either a digital or register rack. The rack addressing (RK ADDR) mode of the
CRT programmer, or SY/MATE or SY/MATE Plus Programming Software can be
used to allocate registers in the system as discussed below.
3. Install other modules into the register slots of the CPU rack. Addresses for the
modules that are installed in the register slots should be assigned in ascending order.
If the CPU rack is a digital rack, assign the CPU slot sufficient registers to handle
the local digital I/O.
4. Assign sufficient registers to the Local Interface (LI) module to satisfy
requirements for external remote I/O based on the content and quantity of remote
drops.
5. Assign registers to other register modules in the CPU rack such as analog I/O,
BCD multiplexed I/O and high-speed counter modules in accordance with their
Instruction Bulletins.
6. Address remote digital I/O racks and remote register racks within the range of
registers previously assigned to the Local Interface module(s) during the CPU rack
addressing. Local Interface modules communicate with these racks via a Remote
Interface module located in each remote rack.
Only those addresses assigned to the Local Interface slot in the CPU rack can be
utilized by the remote racks. Assign registers to all Channel 1 drops sequentially,
then all Channel 2 drops, followed by Channels 3 and 4 if LIO modules are being
used. There is no need to assign registers to the Local Interface modules to act as
storage registers, since the Model 450 contains all needed storage registers.
Chapter 3 - Installation
30598-526
Page 3-13
a. Addressing the remote digital I/O racks - For all CRK, DRK, GRK, and
HRK racks, Slot 1 is always assigned as many registers as necessary to
handle the local digital I/O. The Remote Interface module is always
inserted into Slot 1 of the remote digital I/O rack. Slot 2 is a register slot
and should be addressed in accordance with the register module residing in
that slot.
b. Addressing the remote register racks - Register rack slots are numbered
from left to right; Slot 1 is the leftmost. The Remote Interface or Remote
IO/NET Interface (RIO) module resides in Slot 1. In the case of the register
racks, the Remote Interface or RIO is not addressed. Register modules are
inserted into the slots to the right of the Remote Interface. The number of
registers assigned to that slot is dependent on the individual register module
requirement.
7. Spare address registers, for future expansion, can be assigned to any unused slot
number for any remote drop. The slot that is assigned with the spare addresses does
not even have to physically exist. For example, addresses can be assigned to Slot 2
(register slot) of a CRK-100 (a rack without a register slot). Any register not
assigned to real world I/O is data-retentive.
NOTE
Any addresses assigned to remote drops utilize serial I/O update
times as shown in the LI/RI or LIO/RIO instruction bulletins. These
update times must be taken into consideration when calculating the
throughput of a system.
8. Data storage registers exist as a continuous “block” of registers. This block begins
with the last address assigned to the CPU rack and ends with register 4000.
NOTE
Unlike the Model 500 and 700 processors, data storage registers do
not have to be assigned to a slot to physically exist. All 4000 registers
exist in the Model 450, and they are ALWAYS available for use—even
if not assigned via rack addressing. For example, if the last register
assigned to a slot in the CPU rack is register 200, then registers 201
to 4000 are available for use as internal I/O or storage registers,
despite the fact they have not been assigned as such.
3.6.4 Rack Addressing Register Allocation
• Default rack addressing (4000 registers in CPU Slot 1) applies when the Model 450
is installed in a digital I/O rack with no companion register modules and no remote
I/O.
• If the Model 450 is installed in a digital I/O rack in a system containing register
modules and/or remote I/O, assign enough registers to Slot 1 for the local digital
I/O.
Chapter 3 - Installation
Page 3-14
30598-526
• If the Model 450 is installed in a register rack, registers do not need to be assigned
to Slot 1.
• Assign only necessary external I/O registers to Local Interface, LIO and other
register modules in the CPU rack; include room for future expansion. There is no
need to assign data storage registers to a Local Interface or LIO module; the Model
450's 4000-register count is fixed and this practice can decrease throughput.
• When assigning registers to a slot containing a Parallel Digital Driver module, some
special application considerations are necessary due to the image table operation of
the Model 450. Observe the following rules:
1. If expansion is to a single remote rack, the Parallel Digital Receiver MUST be
connected to channel 1 of the Parallel Digital Driver. The CPU slot containing
the driver should ONLY be assigned as many registers as required to
accommodate the digital I/O in the remote rack.
2. If expansion is to two remote racks, the rack connected to channel 1 of the
Parallel Digital Driver MUST be an HRK-200 (the second rack can be any
digital rack). The CPU slot containing the driver should be assigned as many
registers as required to accommodate the digital I/O in the two racks. Thus, the
first eight registers assigned will correspond to the I/O in the HRK-200
connected to channel 1, while the balance of the registers (up to a maximum of
16 if both remote racks are HRK-200s) will correspond to the I/O in the second
rack.
NOTE
All registers assigned to the Parallel Digital Driver must have
corresponding EXISTING external I/O. Failure to do this (for example,
an HRK-100 rack connected to a channel receiving more than four
registers) could result in oscillating outputs in the rack.
Refer to Appendix C for additional information.
• When assigning registers to digital I/O in a register module installed in the CPU
rack, assign 1 register to a 16-point module or two registers to a 32-point module;
assign 4 registers to a 64-point module. Register modules should have registers
assigned to the slot that they reside in.
• For remote digital I/O racks, registers for the digital I/O addresses should be
assigned to the slot occupied by the Remote Interface module.
• For remote register I/O racks, do not assign registers to the Remote Interface.
Instead, assign them directly to the slots in which the I/O modules are installed,
including register modules that contain digital I/O.
• To improve throughput when laying out a PLC system, avoid fragmenting registers,
that is, ensure that all 16 bits associated with a register are either all inputs or all
outputs. See Section 14.2.3.
• Any external I/O point can be forced ON or OFF. See Section 14.4.
• Model 450 system availability of 4000 registers is fixed; adding Local Interface,
LIO, or other register modules will not increase the available registers.
• Any of the 4000 on-board registers in the Model 450 that are not assigned to a slot
are available as storage registers.
Chapter 3 - Installation
30598-526
Page 3-15
For more information on rack addressing, refer to Appendix C and the programming
device's Instruction Bulletin.
3.6.5 Rack Addressing Compatibility With Other SY/MAX Processors
The Model 450 can use programming and rack addressing configurations designed for
other SY/MAX processors. An example of how this is accomplished is shown in
Figure 3-3.
CPU Slot 1 & Slot 2
MODEL 500
Registers
1-460
(Internal I/O
and Data
Storage)
Slot 3
REGISTERS
461-972
Registers 461-715
are external I/O,
registers 716-972
are internal I/O
and data storage.
RI
MODULES
LI
MODULE
Registers
461-972
Registers
461-715,
External
I/O
CPU Slot 1
MODEL 450
Slot 3
REGISTERS
461-715
All external I/O
LI/ LIO
MODULE
Registers
461-715
IMAGE TABLE:
Registers 1-460
and 716-972
Internal I/O and
Data Storage*
* Registers 716-4000, although
not assigned, are also available
for internal I/O and data storage.
RI or RIO
MODULES
Registers
461-715,
External
I/O
Figure 3-3 Rack Addressing, Model 450 vs. 500
Referring to Figure 3-3, a common Model 500 configuration is to assign the first 460
registers to Slot 1, and registers 461 through 972 to a Local Interface in Slot 3.
External I/O registers in this configuration begin at register 461 and could extend up to
register 715 (although consuming all 255 external registers, the maximum for a single
Local Interface, would be unusual).
Chapter 3 - Installation
Page 3-16
30598-526
Internal relays and storage registers in this example are located in the first 460
registers, and in registers 716 through 972. Note that for internal relays and data
storage, the Model 500 (or 700) accesses registers that physically reside in the Local
Interface module. The Model 450 uses its own on-board registers for this purpose,
however. The only purpose for the Local Interface (LI) or Local IO/NET Interface
(LIO) when used with a Model 450 is to provide communication between Remote
Interfaces (either RI or RIO) and the CPU rack. Note that an LIO may have all
registers assigned as external, if needed.
Because of the image table, only registers that are exchanged with an RI or RIO need
to be updated by the Model 450 in the LI or LIO. It would be a waste of processing
time and a large amount of unneeded bus activity to shuffle storage registers between
the Model 450's image table and the LI or LIO.
When a PLC system is being newly configured for a Model 450, there is no need to
follow old rack addressing conventions for assigning registers to Local Interface
modules.
System throughput will be adversely affected if extra registers are unnecessarily
assigned to Local Interface to LIO modules located in the CPU rack. For best
throughput, only registers assigned to Remote Interface or Remote IO/NET Interface
modules should be assigned to the Local Interface or Local IO/NET Interface modules.
The sample Model 450 configuration pictured in Figure 3-3 shows 255 registers being
transferred between the processor and the Local Interface or the Local IO/NET
Interface module. The throughput in this example could be improved substantially if
only the registers associated with actual drops are transferred between the Model 450
and Local Interface or Local IO/NET Interface module, as shown in Figure 3-4.
CPU Slot 1
MODEL 450
CPU Slot 3
REGISTERS
461-510
LI/ LIO
MODULE
External I/O
IMAGE TABLE:
Registers 1-460
Internal I/O and
Data Storage*
* Registers 511-4000, although
not assigned, are also available
for internal I/O and data storage.
RI or RIO
MODULES
Registers
461-510,
External
I/O
Figure 3-4 Model 450 Rack Addressed with 50 Remote Registers
If only 50 remote registers need be remotely addressed, the best configuration of the
Model 450 shown in Figure 3-3 that would NOT require the readdressing of registers
in the program, appears as shown in Figure 3-4. This is accomplished by assigning 460
registers to CPU Slot 1, and 50 registers (461-510) to CPU Slot 3. Registers above 510
would not need to be assigned, but would still behave as storage registers.
Chapter 3 - Installation
30598-526
Page 3-17
Refer to Appendix C for additional information on the Local Interface or Local
IO/NET Interface module.
Rack addressing options when using existing programs in the Model 450 are therefore
reduced to two:
1. Preserve the existing rack addressing for ease of transport between different
processors, at a cost of throughput.
OR
2. Modify the existing rack addressing and register allocation to improve system
performance.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
If additional modules exist to the right of the Local Interface (LI) or
Local IO/NET Interface (LIO) module being addressed by the Model
450, the addresses of these modules will change when the number
of registers being assigned to the LI or LIO is changed. The Model
450’s program must be altered to reflect the new addresses.
Failure to observe this precaution can result in equipment damage or
personal injury.
Refer to Appendix C for a detailed discussion of the Model 450's compatibility with
existing processor rack addressing configurations.
The system will operate properly with empty slots in the CPU rack, or the CPU rack
can be altered to “close up” the empty slots. For example, since Slot 2 is left empty
when addressing a Model 500 or 700 system, the LI or LIO module could be placed in
Slot 2. An adjustment could then be made when rack addressing a Model 500-to-450
conversion to move all of the register assignments one slot to the left. This would free
up an additional CPU rack slot, and eliminate the somewhat awkward condition of
having Slot 2 empty.
NOTE
This procedure of moving the LI or LIO to Slot 2 would not require
reallocating these registers—they would maintain their relative
positions. It would, however, require adjustments to rack addressing
and also that all modules in the CPU rack be moved one slot to the left.
Refer to Appendix C for supplementary rack addressing information.
Chapter 3 - Installation
Page 3-18
30598-526
3.7 RACK ADDRESSING MULTIPLE MODEL 450s IN THE SAME RACK
While multiple Model 450s may be installed in a rack for coprocessing applications,
only the processor installed in the CPU slot (Slot 1) can directly control digital and
register modules by way of the backplane. Any coprocessing Model 450s installed
anywhere other than Slot 1 will only draw power from the rack and cannot
communicate via the backplane.
Rack addressing a Model 450 in Slot 1 follows the same rules and procedures
described in Section 3.6, “Rack Addressing a Model 450 in the CPU Slot.” Performing
a rack addressing CLEAR MEMORY or CLEAR PLC procedure on a processor in
Slot 1 will result in the default rack addressing of 4000 registers being assigned to Slot
1. If additional Model 450s are installed in the same rack, and if the Model 450 in Slot
1 has registers assigned to the slots in which they reside, these registers will behave as
though they are assigned to an empty slot (that is, as retentive data storage registers).
Since these additional Model 450s only draw power, they are not active on the bus and
any communication with them must occur either through Ethernet or the two serial
ports.
Any processor not installed in Slot 1 requires NULL rack addressing (that is, no
registers assigned to any slots) to be loaded or else it will not run (ERROR 985).
NULL rack addressing can be created by performing a CLEAR MEMORY or CLEAR
PLC procedure on a Model 450 when it is NOT installed in Slot 1, or by changing the
rack addressing using SY/MATE Plus programming software (see the SY/MATE Plus
instruction bulletin, #30598-322). Following this procedure, no registers will appear
assigned anywhere. The ladder program (with no entry for rack addressing) can then
be loaded into the processor. Once developed, processor memory (NULL rack
addressing and ladder rungs) can be recorded on tape or disk. Though not actually rack
addressed, the first 4000 registers do exist internally.
In summary, multiple Model 450s installed in the same rack obey the following rules:
• If installed in Slot 1, the Model 450 must be loaded with valid rack addressing. Do
not assign registers to any slots in which additional Model 450s reside.
• If installed in other than Slot 1, the Model 450 must be loaded with NULL rack
addressing (with no registers assigned to any slots). NULL rack addressing is
generated by performing a CLEAR MEMORY or CLEAR PLC on the processor
while it is installed in other than Slot 1, or by changing the rack addressing using
the SY/MATE Plus programming software.
This distinction is essentially a safety measure which prevents processors from being
accidentally interchanged; a processor intended for Slot 1 operation will not run unless
it is installed in Slot 1 while a coprocessor (non-Slot 1 processor) does not run unless it
is installed in other than Slot 1.
Chapter 3 - Installation
30598-526
4
Page 4-1
CONTROLS AND INDICATORS
4.1 KEYSWITCH POSITIONS
The key-operated selector switch (Figure 4-1) locks the processor into any one of four
operating modes, each of which is described in this chapter. The key can be removed in
any position.
RUN
PROGRAM
RUN
HALT
DISABLE
OUTPUTS
Figure 4-1 Model 450 Keyswitch
RUN/PROGRAM
In this mode the processor functions the same as in RUN (below), but the program can
be altered by the user via use of the override security position on the programmer.
Forcing can be implemented and altered in this mode.
RUN
In this mode the processor scans and executes the ladder program, and all external
outputs are under control of the ladder program. While in this mode, the processor's
program cannot be altered by any means. Forcing cannot be implemented in this
mode; if already in effect, it cannot be altered.
NOTE
When keyswitching between RUN and RUN/PROGRAM, do so as
quickly as possible. An excessively slow transition may cause the
Model 450 to go into HALT momentarily, then reinitialize before
resuming RUN status.
HALT
In this mode the processor is not scanning the program. All external outputs are turned
off unless other special options are utilized.
DISABLE OUTPUTS
In this mode the processor scans and executes the ladder program, but all external
outputs are kept OFF. Internal outputs and storage registers (counters, timers, etc.)
operate according to the program, as do the LEDs on I/O modules. This mode allows a
Chapter 4 - Controls and Indicators
Page 4-2
30598-526
program to be tested without actually energizing any external devices, thus eliminating
the possibility of machine or process damage should the program be flawed in some
way.
4.2 INDICATOR LEDS
As shown in Figure 4-2, the Model 450 has eight LEDs located on the front panel.
Each LED, except where noted, has three possible states: ON, OFF, or FLASHING.
The following describes the various states of the LED indicators.
RUN
HALT
MEMORY
FORCE
I/O
BATTERY LOW
WRITE
PROTECT
ETHERNET
COMM ERROR
Figure 4-2 Model 450 Indicator Lights
NOTE
If no LEDs illuminate or LED operation is erratic when power is
applied to the Model 450, refer to Section 3.5.
As long as the Model 450 is receiving proper power from the SY/MAX power supply,
at least one LED will be ON or FLASHING. If all LEDs (except RUN) come ON and
stay ON, the Model 450 has failed to initialize properly. Check the processor-to-rack
seating. An “all-ON” condition can also be caused by improper power supplied to the
Model 450.
RUN
ON
The processor is scanning the user program and is operating normally.
This LED will light when the keyswitch is in either the RUN or
RUN/PROGRAM position.
OFF
The RUN LED is off if the processor is halted by the keyswitch being
in the HALT position, or if the processor is instructed to halt via the
programming equipment or user program. This LED will also be OFF
if the processor halts due to any PLC system malfunction.
FLASHING
The RUN LED flashes if the processor is in the DISABLE OUTPUTS
mode due to one of the following conditions:
• Processor keyswitch is in the DISABLE OUTPUTS position.
• Processor has been instructed to run in the DISABLE OUTPUTS
mode by the programming equipment.
• Processor has been instructed to run in the DISABLE OUTPUTS
mode by the user program.
Chapter 4 - Controls and Indicators
30598-526
HALT
ON
Page 4-3
If the HALT LED is ON continuously, the Model 450's
microprocessor is not operating.
Numerous diagnostic checks (power-up, halt-to-run, and run-time)
are performed within the processor to ensure its proper operation. If
an internal malfunction occurs, the processor halts, all external
outputs are turned OFF, and the HALT LED illuminates. Any other
non-internal failure causes the HALT LED to flash.
OFF
The processor is operating in the RUN, RUN/PROGRAM, or
DISABLE OUTPUTS mode (depending on whether the RUN LED is
ON continuously or flashing).
FLASHING
If the HALT LED is flashing, one of the following conditions has
occurred:
• The key selector switch has been placed in the HALT position.
• The user program or programming device has instructed the
processor to halt. In this case, the light will continue to flash until
the HALT bit is cleared.
• A memory or I/O error has occurred in which case either the
MEMORY or I/O light will also be ON.
If needed, the processor can be forced into the HALT mode by the
ladder diagram program or by the correct sequence of keystrokes on a
programming device by setting bits 1 or 3 of control register 8176
within the processor. These bits are called the HALT bit and the
HALT/RUN bit respectively. For detailed information on these bits,
refer to Chapter 13.
MEMORY
FORCE
I/O
ON
The processor has detected an error in the user memory. This
condition can be caused by trying to run the processor with no ladder
program or rack addressing in memory, or if a memory fault is
detected in the ladder program. When the MEMORY LED is ON, the
HALT LED will also be flashing.
OFF
User memory is operational.
FLASHING
Not used.
ON
Indicates that one or more inputs or outputs have been forced to an
ON or OFF state, and that forcing via the COMM port (channel 2) is
disabled (control register 8176 bit 5=1). Forcing overrides the actual
input status or output commands of the ladder program. This forcing
may have been via either the programming equipment or
communication system. See Chapter 5 for information on the
communication ports.
OFF
No I/O is being forced.
FLASHING
Indicates that one or more inputs or outputs have been forced to an oN
or OFF state, and forcing is enabled for the COMM port (control
register 8176, bit 5 = 0).
ON
A malfunction has occurred within the processor's internal I/O
registers, or within the external input/output system. When the I/O
LED is ON, the HALT LED also flashes.
OFF
Internal and external I/O systems are operational.
FLASHING
Not used.
Chapter 4 - Controls and Indicators
Page 4-4
30598-526
BATTERY
LOW
ON
The lithium backup battery inside the Model 450 is low, and needs to
be replaced. See Chapter 12 for battery information.
OFF
Both the onboard lithium battery and the power supply backup
batteries are OK.
FLASHING
The power supply batteries are low, and must be replaced. If both the
lithium battery and the power supply batteries are low, the steady ON
condition prevails.
This condition also occurs if any cable other than a Square D Type
CC10 cable is used to supply the Model 450 with power.
WRITE
PROTECT
ETHERNET
COMM
ERROR
ON
All or part of user memory is protected from alteration. For this LED
to be ON, either the keyswitch is in the RUN position or the
processor's internal write-protect jumper is in the NO PROGRAM
position. See Chapter 6 for information on Memory Security features.
OFF
No security locks are active.
FLASHING
Some type of software security is in effect. See Section 6.
ON
Indicates that the Ethernet NIM communication processor is not
running and cannot be communicated with. All communications
attempted out of Ethernet port 3 will fail (a link error will be returned
in the status register).
When this LED is on, register 8175 will contain error code 929. This
error code refers the user to look at register 8094 for the specific cause
of the failure. The Ethernet error codes stored in register 8094 are
listed in Table 15.10.
OFF
Indicates that the Ethernet NIM is operating properly or is in
non-Ethernet mode.
FLASHING
A flashing LED signifies that non-fatal Ethernet errors are occurring.
These errors (displayed in register 8094) are for informational
purposes, and unless they occur repeatedly, do not require any
remedial action by the user. During this time, the Ethernet NIM
communication processor is still running and can be communicated
with. The non-fatal error codes stored in register 8094 are listed in
Table 15.11.
Chapter 4 - Controls and Indicators
30598-526
5
Page 5-1
SY/MAX COMMUNICATIONS
5.1 GENERAL INFORMATION
This chapter is intended as an overview of communication ports. As shown in
Figure 5-1, the Model 450 has three communications ports (channels):
• PRGMR port (port 1)
• COMM port (port 2
• ETHERNET port (port 3)
Two 9-pin RS422 serial differential ports are for SY/MAX protocol and ASCII
communications. The third, a BNC-type of Ethernet port, connects to a high-speed
Ethernet communications network. This chapter applies primarily to the RS-422 ports;
refer to Chapter 15 for detailed Ethernet information.
PRGMR
CHNL 1
ETHERNET
DROP
#.........
COMM
CHNL 2
Figure 5-1 Model 450 Communications Ports
The PRGMR and COMM ports work identically except that the PRGMR port allows
complete access to the Model 450's systems while the COMM port can be set up to
lock out certain functions. See Sections 6.8 to 6.13 for information on inhibit functions
for all ports.
All three ports support block READ/WRITE commands for a maximum count of 128
registers. All ports also have an automatic timeout feature that monitors
communication integrity when using READ, WRITE, or ALARM statements. Ports 1
and 2 support PRINT statements for both ASCII input and output. However, port 3
supports ASCII output, but not ASCII input. Furthermore, although port 3 supports
ASCII output, currently no devices are available on the Ethernet network to receive
ASCII.
Refer to Chapter 10 for additional ASCII communication information.
Immediate Communications Update is supported for ports 1, 2 and 3. Refer to Chapter
5 for more information on Immediate Communications Update.
Chapter 5 - SY/MAX Communications
Page 5-2
30598-526
The pinout for both RS-422 communications ports is shown in Figure 5-2.
5
+5 VDC
4
DATA IN +
3
DATA IN -
SHIELD
9
SIGNAL COMMON
8
SIGNAL COMMON
7
2
DATA OUT +
+5 VDC
6
1
DATA OUT -
Figure 5-2 PRGMR and COMM Port Pinout
5.2 CONNECTING PROGRAMMERS
Ports 1 and 2 support all SY/MAX programming devices, including the Class 8010
Hand-held Programmer. Since the hand-held programmer obtains its power from the
Model 450, its cable is limited to 6 feet (2 meters) in length. Other SY/MAX
programming devices have their own power supplies, and can be placed up to 10,000
feet (3050 meters) from the Model 450.
Refer to the appropriate programmer Instruction Bulletins for more details on
connecting programmers to the Model 450.
5.3 CONNECTING OTHER SY/MAX DEVICES
Many different peripheral or programming devices can be connected to the
communication ports, greatly expanding the Model 450's capability and range of
applications. Figure 5-3 and Figure 5-4 on the following page give some possibilities
for peripheral connections to communications ports 1 and 2.
Chapter 5 - SY/MAX Communications
30598-526
Network
Interface
Modules
Page 5-3
Other Processors
10,000 ft (3050 m) maximum
CRT Programmer,
Laptop or Personal
Computer with
SY/MATE or
SY/MATE Plus
Programming
Software
10,000 ft (3050 m) maximum
PRGMR
CHNL 1
Hand-Held
Programmer
6 ft (2 m) maximum
Figure 5-3 Possible PRGMR Port (Channel 1) Connections
Printer
Loader/
Monitor
D-LOG
Module
ASCII
Devices
Cartridge Tape
Loader/Recorder
COMM
CHNL 1
Figure 5-4 Possible COMM Port (Channel 2) Connections
Chapter 5 - SY/MAX Communications
Page 5-4
30598-526
Both the PRGMR and COMM ports on the Model 450 support any device that uses the
SY/MAX serial protocol. This includes, but is not limited to, the following devices:
• Other SY/MAX Processors
• SY/NET Network Interface Modules
• Personal Computers running SY/MATE or SY/MATE Plus software packages
• Loader/Monitor
• Cartridge Tape Loader/Recorder
• Printers
• D-LOG Modules
• Microcell Controller
• Speech Modules
Connectable devices are described in this chapter. Since the only difference between
ports 1 and 2 is in security access (Chapter 6), the devices shown in Figures 5.3 and 5.4
can be connected to either communications port 1 or 2. Additional information about
these devices follows. Refer to Chapter 15 for information on connectable Ethernet
devices.
5.3.1 Other Processors
Other SY/MAX processors (Class 8020 Types SCP-1XX, 3XX, 4XX, 5XX, 6XX or
7XX; Class 8055 Types 45X or 650) can be daisy-chained together, allowing them to
share information and to function as an independent distributed control system. See the
specific processor's Instruction Bulletin for more information.
5.3.2 SY/NET Network Interface
The SY/NET Network Interface Module (NIM) is a local area communications
network module capable of interfacing the Model 450 to an entire network of other
programmable controllers, computers, programmers, or other devices. Refer to NIM
Instruction Bulletin #30598-257 for more information.
NOTE
The Model 450 can use variable ROUTE statements for all 3 ports via
Control Registers 8095, 8097 and 8098.
5.3.3 Loader/Monitor
The Loader/Monitor provides a simple and inexpensive method of monitoring l/O
status and register values. It also allows register values to be changed without having to
access the ladder diagram program.
The Loader/Monitor can display alphanumeric messages programmed in Model 450
memory, providing an inexpensive yet powerful method of signaling alarms,
producing reports, and logging data. Refer to the Loader/Monitor Instruction Bulletin
(#30598-163) for more information.
Chapter 5 - SY/MAX Communications
30598-526
Page 5-5
5.3.4 Cartridge Tape Loader/Recorder
By attaching the Cartridge Tape Loader/Recorder to the Model 450, the user's program
can be stored on tape for backup purposes. Then if the user program inside the Model
450 is somehow altered or lost, the taped copy can be downloaded into the Model 450
as a replacement.
5.3.5 Printers
Connecting a printer allows messages generated by the Model 450 to be recorded on
hard copy. A printout ensures a permanent record of any received alarms or data. The
recommended word structure for printers and other ASCII devices is to set the
receiving device for 7-bits with odd parity and two stop bits. Alternate word structures
are available via registers 8099 and 8100 (see Section 13.2).
5.3.6 D-LOG Data Controller Module
The D-LOG gathers data from the Model 450 processor to generate documentation
such as reports, alarm messages, and graphic displays. Refer to the Data Logger
Instruction Bulletin #30598-272 for more specific information about the D-LOG
Module.
5.4 BAUD RATES
5.4.1 General Information
The default communication rate for both the PRGMR and the COMM port is 9600
baud, which is the data rate used when the Model 450 is connected to most peripheral
and programming devices. However, variable baud rates are not supported by Ethernet
port 3, which operates at a fixed rate of 10 megabits/sec.
Several methods are available to change the default baud rate should it be necessary for
a Model 450 port to operate at other than 9600 baud. See Table 5-1 on page 5-6.
NOTE
The baud rate can also be changed by using the DATA ENTER mode of
the SY/MATE Plus Programming Software, or a Hand-held Programmer.
Enter the desired code into Model 450 control register 8169.
Chapter 5 - SY/MAX Communications
Page 5-6
30598-526
Table 5-1: Altering Baud Rates
Operation
Effect on PRGMR Port
Effect on COMM Port
PRINT command specifying
baud rate
Alters baud rate
Alters baud rate
Change the contents of
register 8169 using a LET
command, or while in the
programmer’s DATA ENTER
mode
Alters baud rate
Alters baud rate
CLEAR MEMORY or CLEAR
PLC command
No effect
No effect
Power up
Set to 9600 baud, 8-bit word
with even parity and 1 stop
bit
No effect unless memory is
corrupt. If so, set to 9600
baud.
Corrupt memory; error
message “Clear memory
needed” occurs.
(CLR PLC)
Set to 9600 baud
Set to 9600 baud
5.4.2 Altering Baud Rates
Control register 8169 in the Model 450 contains the bit patterns which determine baud
rate for the communications ports. Bits 1-4 in register 8169 represent the baud rate for
the PRGMR port, while bits 5-8 contain the baud rate for the COMM ports. Bit
patterns are shown in Figure 5-5.
8
7
COMM Port
6
5
4
3
2
1
PRGMR Port
Figure 5-5 Control Register 8169 (Bits 1-8 Shown)
The bit patterns corresponding to the various baud rates for both communication ports
are shown in Table 5-2.
The binary pattern for the PRGMR port is reflected in bits 1 to 4, while the pattern for
the COMM port is in bits 5 to 8.
Chapter 5 - SY/MAX Communications
Page 5-7
30598-526
Table 5-2: Baud Rate vs. Bit Pattern
Baud Rate Code
Baud Rate
Binary
Decimal
0000
0
75
0001
1
110
0010
2
300
0011
3
1200
0100
4
2400
0101
5
4800
0110
6
9600
0111
7
19.2K
Baud rates can also be changed through word attribute registers 8099 and 8100. See
Chapter 10.
5.5 VARIABLE ROUTE STATEMENT
5.5.1 Description of Operation
The Model 450 can use variables to define routing for a communication rung. All three
ports support variable routes for communication rungs. The format of the variable
communication rung is similar to a rung that has a constant route, except that a special
route - 205 - is inserted just after the regular source route identifier in the rung. Three
registers, 8095, 8097 and 8098, are used in conjunction with the variable route.
The generalized rung format for the variable ROUTE statement is shown in Figure 5-6.
TWRTE3
ROUTE
ROUTE
AAA
205
Figure 5-6 Variable ROUTE in a COMMS Rung for Port 3 (Ethernet)
When programming the communication rung that is to have the variable ROUTE, the
first ROUTE in the rung (AAA) should identify the originating device. The second
ROUTE must be programmed with the special number 205. The number 205 causes
the Model 450 to examine either register 8095, (if the Ethernet port is used), 8097 (if
the PRGMR port is used), or 8098 (if the COMM port is used) for ROUTING data.
Registers 8095, 8097 and 8098 act as pointers to a block of from two to eight registers.
The user must load the register number of the first register of this block into either
register 8095, 8097 or 8098; each register in the block must then be preset with the
intended route.
When the Model 450 executes the communication rung and encounters special
ROUTE 205 as the message destination, it will check either register 8095, 8097 or
Chapter 5 - SY/MAX Communications
Page 5-8
30598-526
8098 to find out where the variable ROUTE information is stored. The registers being
pointed to by registers 8095, 8097 and 8098 must contain the intended routes.
The block of registers containing the ROUTE information will vary in length,
depending upon the need for net-to-net routing. Since the length is variable, loading
the value -1 (FFFFH) into a register defines the end of the block. In the majority of
cases (no net-to-net used), the block will consist of only two registers—the first
contains the destination ROUTE itself while the second (containing -1) identifies the
end of the block.
The user must manipulate the contents of the first register in the block to obtain the
variable ROUTE. If net-to-net routing is to be used, the size of the register block
simply expands to accommodate the extra ROUTE information needed. Not until -1 is
encountered in a register will the Model 450 assume that all intended routing
information has been provided.
Thus, since SY/MAX protocol allows for messages to accept net-to-net routing
information that is up to eight levels deep, the maximum block size is seven “route
registers” plus the last (terminator) register that contains -1, up to a maximum total
block size of eight registers. (Note the originating route uses one of the eight levels.)
5.5.2 Implementation
The following steps are required to use the variable ROUTE feature in the Model 450.
1. Program a communication (COMM) rung normally, entering the number 205 as
the destination ROUTE. Note that this also applies to communications that require
multiple routes.
2. Prior to solving the COMM rung TRUE, load the starting register number of a block
of up to eight registers into register 8095 (for the Ethernet port), 8097 (for the
PRGMR port), or 8098 (for the COMM port).
3. Also before solving the rung, preset the “route register” block with the desired
routes. Signify the end of the block by loading -1 (FFFFH) into the register that
immediately follows the register containing the final destination route.
4. Reroute the communication message by changing the routing specified in the
contents of the register block.
5.5.3 Application Considerations
• The maximum count in a Model 450 communication rung is 128 registers.
• The device communicating with the Model 450 may be unable to service the full
128 registers, in which case a transmission error occurs. Following is a list of
register capacities for various SY/MAX devices:
Model 100
Model 300
Model 400
Model 450
Model 500
Model 600
Model 650
Model 700
D-LOG Module
MicroCell Controller
Chapter 5 - SY/MAX Communications
16
16 (15 for Series A)
128
128
128 (Series M and later)
64 (Series L and earlier)
128
128
64
128
128
30598-526
Page 5-9
• The communication statements used with variable ROUTE information are
transition-sensitive.
• The status register monitors rung execution and message completion as in other
COMM statements. In addition, ERROR 03 or 29 indicates an illegal rung
configuration has been generated by the user (illegal route specified, illegal registers
pointed to, etc.).
• The “route register block” should not extend beyond register 4000.
• The address of the status register used in the rung must be less than 4001.
5.5.4 Example
Assume that the contents of registers 61 through 70 will be transferred from a
networked Model 450 at location 101 to registers 91 through 100 in one of two
processors, A and B on the SY/NET network. Processor A is at location 003. Processor
B is on a separate network, at location 102, via a net-to-net link. The net-to-net link is
at location 009.
The configuration of this example is shown in Figure 5-7. Note that Network Interface
Modules (NIMs) are used with each processor.
NOTE
All NIM serial ports in this example must be set to the SY/MAX protocol
operating mode, except for the NET-TO-NET links.
The steps in Section 5.5.2 are used to configure the example shown in Figure 5-7.
0
1
Model 450
0
9
0
3
NIM
(Net-to-Net Link)
NIM
NIM
Processor A
(SY/NET) Network 1
0
9
0
2
NIM
NIM
(Net-to-Net Link)
Processor B
(SY/NET) Network 2
Figure 5-7 Variable ROUTE Example Configuration for Ports 1 and 2
Chapter 5 - SY/MAX Communications
Page 5-10
30598-526
SAMPLE PROCEDURE
1. Program the rung shown in Figure 5-8 in the initiating Model 450.
ROUTE
TWRTE2
101
ROUTE
205
STAT
LOCAL REMOTE COUNT
S60
S61
S91
10
Figure 5-8 Rung for Variable ROUTE Example on Port 2
NOTE
The assigning of register S60 as the status register is arbitrary for this
example. Any unused storage register can be used.
2. The next step is to load the variable ROUTE information into the processor. Do this
by choosing a starting register for the “route register” block; in this example, register
3901 is used. The processor uses register 8098 (COMM port) for storing this variable
ROUTE information; therefore, load 3901 into register 8098. Use the DATA
ENTER mode of a programming device, or a LET rung within the Model 450's
ladder program, to accomplish this.
3. Assuming that it is first necessary to transfer registers 61 through 70 to processor A,
the value 0003 (processor A's location) must be loaded into register 3901. To
terminate the block, load the value -0001 into register 3902 to show the Model 450
the end of the “route register” block. Again, a programming device in the DATA
ENTER mode or a LET rung is used for this.
When enabled by the logic, the communication statement is transmitted out of the
Model 450's channel 2 (COMM) port through the NIM which is set as location 101.
When the logic in this communication rung is enabled, the Model 450 executes the
rung with the following results:
• The ROUTE 205 in the rung causes the Model 450 to interrogate register 8098 for
ROUTE information.
• Register 8098 (holding value 3901) tells the processor to examine register 3901.
• As register 3901 = 3, the value 003 becomes the ROUTE destination.
• The Model 450 next interrogates register 3902. Since 3902 = -1, the Model 450
knows it has all the necessary ROUTE information. The contents of registers 61
through 70 are now sent to processor A's registers 91 through 100.
4. Now assume the register block 61 to 70 is to go to processor B's registers 91 through
100 instead. As transmission to processor B involves a net-to-net link, an additional
ROUTE parameter is needed. Enter the following values into the indicated registers:
Register 3901
0009 (net-to-net link)
Register 3902
0102 (processor B’s location)
Register 3903
-0001 (end ROUTE information)
When the logic in the communication rung is enabled, registers 61 through 70 in the
Model 450 are now routed through location 0009 to processor B at location 102.
5.6 IMPROVING COMMUNICATIONS THROUGHPUT
Because the primary function of a programmable logic controller is the timely
execution of the user program, communication with external devices is subject to
Chapter 5 - SY/MAX Communications
Page 5-11
30598-526
certain rules and limitations. Following is a discussion of some of the potential pitfalls
associated with these rules, as well as some techniques for improving communications
throughput.
Both the sending and receiving of communication characters in READ, WRITE,
ALARM, and PRINT (ASCII input/output) statements can occur at any time while the
processor is scanning. Typically, the impact on scan time for servicing these characters
is slight because of separate microprocessors used for control and communications.
The largest single delay associated with the communication process occurs when a
complete message has been received, and the register data contained in that message
must be incorporated into the processor's image table registers. From 2.5 to 5.0 msec is
allowed for the processor at the end of scan (EOS) to perform this task before scanning
must resume. Note that processors that are in HALT (with HALT LED flashing) can
still respond to incoming messages, but cannot initiate them.
5.6.1 Guidelines
The maximum block size of registers (count) which a user may specify in a message is
128 registers. For communicating a large quantity of registers, throughput is optimized
by transmitting the largest blocks possible; a single transmission with 128 registers is
over 10 times faster than 128 transmissions of 1 register each. The larger the message
block, however, the more time is required at EOS to incorporate this data into the
processor's image table. Because this processing time for 128-register messages can
exceed 5 msec, multiple scans may be required to update all the registers. This presents
a potential application problem if the new data needs to be treated as a contiguous
block for control purposes. A simple example is floating point data, in which an
odd/even pair of registers constitutes one floating point value, and splitting of this
floating point register pair could result in an invalid value used by the PLC.
16
1
Data Field
32
17
Status Field
Bits
Description
1-14
Error Codes (always odd - bit 1 set)
15
Remote device in RUN
16
Successful completion
17
Message sent to buffer
18-21
SY/MAX timer value
22
Input ladder logic solved true
23
SY/MAX timeout occurred
24-32
Register identification code (N/A)
Bits 1-23 are cleared when bit 22 is reset (input logic to Communications rung opens up)
Figure 5-9 Communications Rung (READ, WRITE, PRINT, ALARM)
SY/MAX Status Register
To prevent this potential “splitting” of a message over multiple scans, bit 16 of register
8170 may be set by the user. Setting this bit causes the processor to completely finish
servicing a message at EOS prior to resuming scanning the user program; thus, the 2.5
to 5.0 msec EOS period is extended for as long as necessary, with worst-case extension
Chapter 5 - SY/MAX Communications
Page 5-12
30598-526
being 10 msec total. Therefore, 8170-16 should be set any time multiple registers in a
message must be updated during the same scan (as with floating point data) with the
trade-off being a potential 5 additional msec added on to the present 5 msec EOS time.
In the event a contiguous block of data exceeds 128 registers, application
programming techniques must be used to inhibit control logic operation until all the
new data has been incorporated into registers. In the initiating processor, bit 16 of the
associated communication rung status register is set when an operation is complete;
thus, multiple bit 16's may be monitored to ensure that each associated message has
been completed. Refer to Figure 5.10 for an overview of bit descriptions. However,
when unsolicited WRITE commands are initiated by a remote device, the local device
is not advised when an operation is complete. Therefore, the remote device should use
some of the transmitted registers to advise the local device. One technique is to
increment the first and last register of the contiguous block each time a block of
messages is sent; the local device would then need to be programmed to only act upon
the data when these registers were equal, so as not to be in the middle of an update and
the data can be considered valid.
Another way of improving communications throughput by trading communication
servicing time for scan time is the use of immediate communications update coils in
the user program. Each time an immediate communications update coil (bits 8176-11
through 8176-13 for ports 1 through 3, respectively) is encountered, the processor
checks the indicated port for a received message. If one exists, it will be serviced for
up to 5ms, thus imposing a worst-case scan time impact of 5 msec. For applications in
which it is desirable to trade scan time for improved communications throughput on
port 3, for example, coil 8176-13 could be used as often as desired at multiple program
locations to process existing messages.
5.6.2 SY/MAX Communications Timeout
As discussed in the programming instruction bulletin, bits in the communication status
register (which must be uniquely assigned to the communication statement) can be
used to monitor the communication process. For example, bit 22 is set to 1 when the
input logic to the rung is true. Bit 17 is set to 1 when the message has been loaded into
a communications buffer and is about to be transmitted. Bit 16 is set to 1 when a reply
is received indicating the message transaction is successfully completed. (Bit 1, along
with some combination of bits 2 through 14, is set to indicate an error and to indicate
an unsuccessful message transaction). Finally, bit 15, when set, indicates the remote
device is actively scanning logic or executing a program.
Another feature available to the user is a communications reply timeout flag. This
differs from the Ethernet timeout discussed in Section 15.5.2 in several ways. First, it
can be applied to communications through all 3 ports. More importantly, this timeout
is based on message completion, not just message acknowledgment. For a READ
statement, for example, timing begins when the message is loaded into a
communications buffer (bit 17 set to 1) and ends when the requested data has actually
been received (bit 16 set to 1) or when time has expired or an error reply was received
(bit 1 set to 1). Bit 23 of the communications status register is set any time a complete
message response is not received before a user-specified period after the message has
been initiated. This period is determined by the bit pattern contained in the appropriate
bits of register 8168 at the time the communications rung is first solved true. If the time
period selected in register 8168 is too short, the reply could still arrive after the timeout
(bit 23) is set and the appropriate registers be updated.
Chapter 5 - SY/MAX Communications
30598-526
Page 5-13
Table 5-3: Communication Timeout Ranges for
Register 8168, Bits 1-4, 5-8, and 9-12
BIT PATTERN
(Bits 4-1 for PRGMR; Bits 8-5 for
COMM; Bits 12-9 for Ethernet)
TIME COUNT
(in milliseconds)
0000
0 to 250
0001
250 to 500
0010
500 to 750
0011
750 to 1000
0100
1000 to 1250
0101
1250 to 1500
0110
1500 to 1750
0111
1750 to 2000
1000
0 to 2000
1001
2000 to 4000
1010
4000 to 6000
1011
6000 to 8000
1100
8000 to 10,000
1101
1,000 to 12,000
1110
12,000 to 14,000
1111
14,000 to 16,000
As shown in Table 5-3, two ranges are available: 0 to 2 seconds (with 250 msec
resolution) or 0 to 16 seconds (with 2 sec resolution). Note the time period associated
with a bit pattern is an interval, with the timeout liable to occur anywhere within the
interval. For example, a bit pattern of “0000” can result in a timeout being flagged
anywhere from 0 to 250 milliseconds (maximum) after a message has been sent to the
buffer.
When a message is initiated, the user-specified timeout code for that channel is copied
into bits 18 to 21 of the corresponding communication status register. These bits then
“count down” the time until a reply is received. If a reply is not received (bit 16 or bit 1
set to 1) within the timeout period, bit 23 will be set.
NOTE
Each time the communications rung is solved false, all bits associated
with the communications status register are cleared.
Chapter 5 - SY/MAX Communications
Page 5-14
30598-526
COMM STATUS BIT DEFINITIONS:
Bit 16 only is set: A valid reply has been received; the message was complete before
the timeout elapsed.
Bits 16 and 23 are set: A valid reply was received; however, it was received after the
timeout had elapsed.
Bit 23 only is set: No reply received at all, timeout has elapsed.
Bits 1 and 23 are set: A valid error reply was received either before or after timeout.
Check the data field for the error code.
CONSIDERATIONS FOR USING TIMEOUT
• Bits 1 through 23 in the status register are cleared every time the rung is executed
FALSE (in other words, when the initiating condition in front of the TREAD or
TWRITE statement is open).
• If a message is not acknowledged (no reply), ERROR 13 is posted in the status
register and a processor communications port error is sent to register 8175 and bit
23 is set. For ports 1 and 2, this may occur when cabling to the ports is
disconnected. For port 3, this may occur if the Ethernet NIM portion has shut
down—a fatal Ethernet communications error.
• If an error reply is received, the appropriate error code is posted in the status register
and bit 23 is set, regardless of the actual time elapsed.
• If a valid reply is received after a timeout has occurred and bit 23 is set, bit 16 is set
and bit 23 is latched ON until the communications rung is executed FALSE.
EXAMPLE:
A user wishes to know if a certain ladder-initiated Ethernet message is receiving a
reply within 4 seconds after initiation. The bit pattern 1001 should be loaded into
register 8168 bits 9 through 12 before the communications rung is solved true (for
checking Ethernet port timeout).
If a reply is not received within 4 seconds (4000 milliseconds - the upper timeout
limit), bit 23 of the appropriate status register is set. Keep in mind the bit can be set any
time after 2 seconds has elapsed, as this is the lower timeout limit.
Chapter 5 - SY/MAX Communications
30598-526
Page 5-15
5.7 TECHNICAL DATA FOR COMMUNICATIONS PORTS
Table 5-4: Communications Ports Technical Data
Applicable Port
Technical Characteristic
1
2
Connector Type
D-type, 9-pin female slide lock (RS-422)
ThinWire Ethernet-BNC, with gold-plated conductor
x
x
Communication Method
RS-422 (serial differential)
High speed Ethernet
x
Communication Rates
See Table 5-1 on page 5-6 for baud rate information.
10 megabits/second
x
Maximum Cable Length
10,000 ft (3050 m) at 9600 baud (RS-422)*
Ethernet-maximum:** 607 ft (185 m) per segment, 3034 ft
(925 m or five 185m segments),
with repeaters
3
x
x
x
x
x
x
x
x
Cable Type
Belden #8723 or equivalent (RS-422)
Ethernet-type RG58A/U or RG58C/U 50-ohm coaxial cable
x
Short Circuit Protection
Driver/receiver circuitry
Ethernet
x
Surge Protection
Driver/receiver circuitry
Ethernet
x
x
x
x
No
x
x
Common Mode Voltage Rating
6 volts maximum
x
x
N/A
Auxiliary Power
Powers the hand-held programmer or loader/monitor
x
x
N/A
* Actual cable length for RS-422 communications is subject to installation considerations such as reliable building
ground (signal reference), common mode voltage, signal interference/shielding, etc. If communication
problems are experienced over long cable runs, decreasing the baud rate may result in greater signal integrity.
** Applies to 10BASE2 ThinWire Ethernet networks. Longer distances are possible using repeaters with other media
such as 10BASE5 Standard Ethernet.
Chapter 5 - SY/MAX Communications
30598-526
6
Page 6-1
SECURITY FEATURES
6.1 GENERAL INFORMATION
The Model 450 processor has security features that prevent unauthorized access to user
ladder programs, labels, rack addressing and storage registers. This type of security
protects programming equipment and/or other devices connected directly to the
processor via SY/NET or via Ethernet (Model 450, 650, or a PC with an SFI610).
NOTE
Except where otherwise noted, this section refers to various security
features for all three ports (PRGMR, COMM, and ETHERNET:
Channels 1, 2 and 3, respectively).
Three types of security features are used to protect each of the following:
• Ladder memory
• Data storage registers
• Communications
Section 6.3 contains three tables that summarize all of the available security features in
the Model 450 processor.
6.2 DEFINITIONS
The following terms are used frequently in this chapter.
Editing
The use of external equipment to insert, replace, delete or
clear rungs or rack addressing that exist in the processor
memory.
Register
Storage locations of I/O status, data values, or control
information. Can be either data registers or control
registers.
Non-Priority
Register Read
Access to registers to display or copy (read-only) a value
stored in a Model 450 data register. Non-priority register
reads are normally done through programming equipment
and software packages (for example, SY/MATE Plus
Version 2.0).
Non-Priority
Register Write
To enter or store a new value in a Model 450 data register.
Non-priority reads are normally done through the use of
programming equipment and software packages (for
example, SY/MATE Plus Version 2.0).
Priority Register Read
To read or recall the contents of one or more SY/MAX
registers. Typically this type of communication occurs
between processors (for example, a Model 450 and a Model
650 communicating with each other).
Chapter 6 - Security Features
Page 6-2
30598-526
Priority Register Write To write or store a value into a SY/MAX register. Typically
this type of communication occurs between processors (for
example, a Model 450 and a Model 650 communicating
with each other).
Programming Device
An IBM-compatible computer equipped with SY/MAX
Type SY/MATE Plus Programming Package.
User Memory
The memory in which user-created ladder programs and
rack addressing are stored.
Storage Register
Memory
Memory where data register values are stored in the Model
450, separate from user memory.
6.3 SUMMARY OF SECURITY METHODS
The three tables on this page describe the ladder, register and communication security
features available in the Model 450 processor:
• Table 6-1 covers ladder program security features.
• Table 6-2 covers storage register security features.
• Table 6-3 covers communication security features.
In the following tables, the method of protection is indicated in the left column. What
the method protects is shown in the center column. The right column gives the
subsection of Chapter 6 where that protection feature is described.
Table 6-1: Ladder Program Security Methods
Security Method
Prohibits
See Section
Hardware jumper
Program editing of any kind
6.4
Port/Route edit lockout
Program editing by any port or
route other than the one used by
the initiating equipment
6.5
Keyswitch RUN position
Program editing of any kind,
including forcing
6.6
Inhibit rung
Altering rung within an area defined
by the inhibit rungs
6.7
Safeguard rung
Displaying, by programming
equipment, the ladder areas
defined by the inhibit rungs.
6.8
Password/Restriction register
Editing on a port-by-port basis
6.9
Memory protect bit
Ladder programming or editing*
6.10
* Does not apply to PRGMR port.
Chapter 6 - Security Features
30598-526
Page 6-3
Table 6-2: Register Data Security Methods
Security Method
Prohibits
See Section
Password and restriction registers
8177 and 8178
• External non-programming
devices from alterning registers
on a port-by-port basis
• Programming equipment from
altering register data on a
port-by-port basis
• Forcing of I/O by programming
equipment on a port-by-port basis
6.9
Protect all registers bit
Altering of register data by any
external device*
6.12
Force inhibit bit
Forcing of I/O by programming
equipment*
6.11
Safeguard rung
Programming rungs containing
protected registers
6.8
Fenced registers
Altering of registers that are defined
by user as fenced
6.13
* Does not apply to PRGMR port.
Table 6-3: Communication Security Methods
Security Method
Safeguard rung
Prohibits
See Section
Programming of COMM rungs
(READ, WRITE, PRINT, ALARM)
assigned to user-specified
channels on a port-by-port basis
6.8
6.4 HARDWARE SECURITY JUMPER
Prohibits:
Ladder editing or programming of any kind through any of
the 3 ports (COMM, PRGMR or ETHERNET).
Uses:
Internal jumper, located on a three-pin header. The jumper
is accessed by removing the Model 450's side plate. See
Figure 6-1.
Chapter 6 - Security Features
Page 6-4
30598-526
Top Front of Model 450
U314
U313
Lower PC board
= DISABLED SECURITY
Upper PC board
= ENABLED SECURITY
Figure 6-1 Hardware Security Jumper
The security jumper bridges the center pin of the three-pin header to either the left or
right pin (see Figure 6-1). When the security jumper is in the ENABLED position, all
ladder memory is protected from alteration of any kind. When DISABLED, ladder
memory is accessible to the extent that other security methods allow. The WRITE
PROTECT LED (Section 4.2) illuminates when the jumper is enabled.
6.4.1 Considerations
• The CLEAR PLC command will have no effect when the jumper is enabled.
• An enabled jumper overrides lhe following security features:
1. Inhibit Rung (described in Section 6.7)
2. Memory Protect bit (Section 6.10)
3. Password and Restriction Register features for selective disabling of ports
(Section 6.9)
6.4.2 Setting the Security Jumper
CAUTION
POSSIBLE EQUIPMENT DAMAGE
Remove power from the rack before removing the Model 450 processor.
Failure to observe this precaution can cause equipment damage.
1. Turn off the AC power to the rack where the Model 450 is installed.
CAUTION
STATIC ELECTRICITY
Be sure to use appropriate anti-static devices when handling the board.
Failure to observe this precaution can cause equipment damage.
2. Remove the Model 450 from its rack.
3. Remove the side access plate from the Model 450.
Chapter 6 - Security Features
30598-526
Page 6-5
4. Using a needlenose pliers, place the jumper in the desired position (ENABLED or
DISABLED) as shown in Figure 6-1. Do not leave the jumper off of the header.
It must be in one of the two positions.
5. Replace the side cover on the Model 450, and reinsert it in its rack.
6. Reapply rack power.
6.5 SELECTIVE PORT & ROUTE EDIT LOCKOUT
Prohibits:
Ladder program alteration through any port or by any route
except the port and route used by the initiating
programming device.
Uses:
Control Register 8176, bit 15.
This security feature ensures that only a single programming device on the SY/NET
network has access to the Model 450's memory at any given time. If the SY/NET
network is not in use, the restriction applies channel-by-channel.
To engage the Port/Route Lockout fealure, set bit 15 of Control Register 8176 lo "1"
using the Data Enter mode of the programming device. The Model 450 "remembers"
the port and route that the programming device used to set bit 15. Any attempt to edit
the program through any port or route other than the "remembered" port/route causes
the Model 450 to generate an ERROR 49.
The lockout feature does not prohibit simple interrogation or viewing of the ladder
program, unless other security features that prevent these are active. Register contents
can still be altered (unless other measures are active to prevent this). To release the
lockout, use the programmer that set bit 15 of Register 8176 to "1" (the same
route/port) to reset the bit to "0".
6.5.1 Considerations
• A CLEAR PLC command issued through the PRGMR port of a Model 450 that has
Port/Route Lockout enabled has no effect unless the device sending the CLEAR
PLC is the same device that enabled the lockout.
• Cycling power to the Model 450 will disable the lockout and extinguish the WRITE
PROTECT LED (if no other form of security is active).
• If the lockout is disabled by cycling power, bit 15 of Control Register 8176 may
remain set to 1. This is because the processor retains Control Register contents, but
cannot retain port and route information, when power is removed. Thus, the fact
that bit 15 of 8176 is set to 1 is not a guarantee that the lockout feature is active.
Conversely, if bit 15 is set to 0, the lockout feature may still be active. Only by
setting the bit immediately before editing, and resetting the bit immedialely after
editing can bit indication be considered reliable.
6.6 KEYSWITCH RUN POSITION
Placing the Model 450 keyswitch in the RUN position prohibits any changes from
being made in a ladder program. In addition, the ability to force, or to alter forcing, is
disabled while the keyswitch is in RUN (if changes to a program that is running are to
be made, place the keyswitch in the RUN/PROGRAM position).
Chapter 6 - Security Features
Page 6-6
30598-526
6.7 INHIBIT RUNG
Prohibits:
Altering rungs within protected ladder areas that are
defined by the Inhibit Rungs.
Uses:
Control Register 8176, bit 16
A maximum of two areas of the user ladder program can be protected from being
edited. The two areas that make up a typical ladder program are the Mainline ladder
area and the Subroutine ladder area.
The subroutine area consists of all the subroutines that exist in the user ladder
program. This area starts with the MARK ST SUB rung and proceeds to the last rung
in memory. The mainline ladder area consists of rung number 1 in memory and
proceeds up to, but not including, the MARK START SUB rung.
Protected mainline ladder rungs always start with rung number 1 in the ladder and
consecutively proceed up to the inhibit rung in the mainline area.
The protected subroutine rungs always start with the MARK ST SUB rung and
proceed consecutively to the inhibit rung in that area.
An inhibit rung is inserted into a program by entering a rung containing only a coil (no
conditional logic) addressed Register 8176 bit 16. (See Figure 6-2.)
8176
16
Figure 6-2 Inhibit Rung
6.7.1 Considerations
1. Protection is not enabled until either the processor is power-cycled or the
keyswitch is turned from HALT to RUN.
2. More than one inhibit rung may exist in any given area, but only the earliest (lowest
number) programmed inhibit rung in an area defines the end of a protected ladder.
3. When a CLEAR PLC command is issued to the processor over channel 1, the
protected areas defined by the inhibit rungs will not be cleared. Only the unprotected
areas of the ladder program will be cleared.
6.7.2 Clearing the Inhibit Rung
Clearing the protected and unprotected areas of a ladder program that are protected by
Inhibit Rungs requires that the entire ladder program and all rack addressing be cleared
from the Model 450. This is done by connecting a programmer to the PRGMR
(channel l) port, and then performing the following steps using SY/MATE Plus
Programming Software:
1. Confirm that the security jumper (Section 6.4) is in the DISABLED position.
2. Display the ONLINE/STATUS screen.
3. Press CLEAR MEMORY.
4. Press CLEAR PLC.
Chapter 6 - Security Features
30598-526
Page 6-7
5. Press CONFIRM on the next screen.
6. Access the DATA mode.
7. Store the decimal value -1 in register 8177 (the password register).
8. Repeat steps 2 through 6.
The result of the above CLEAR PLC operation is a completely blank user
memory, meaning that the following is true in the Model 450:
• No ladder program
• Default rack addressing
• Zeroed register values
• No enabled security features.
Figure 6-3 illustrates the operation of the Inhibit rung.
Protected
Mainline
INHIBIT RUNG
8176
16
Unprotected
Mainline
MARK ST. SUB
Protected
Subroutines
INHIBIT RUNG
8176
16
Figure 6-3 Operation of the Inhibit Rung Coil
Chapter 6 - Security Features
Page 6-8
30598-526
6.8 SAFEGUARD RUNG
Prohibits:
1. Displaying, by programming equipment, any rungs
protected by Inhibit Rungs (see Figure 6-3). Two different
groups, each with an Inhibit Rung, can be protected.
Enabled protection applies to both channels.
2. The programming of any COMM rungs (READ, WRITE,
PRINT, ALARM) assigned to user-specified channels on a
channel-by-channel basis.
3. Programming any rungs that contain registers that are
user-defined as protected.
The safeguard rung allows a variety of security protection features to be enabled. To
use the safeguard features the special TLET rung, as described in the following
paragraphs, must be programmed as the first rung in ladder memory. To activate the A,
B1, B2, C1 and C2 parameters in the special TLET rung, an inhibit rung (with coil
addressed as 8176-16) must also be programmed.
The following rung must be rung #1:
—[ TLET S8165 = A; B1; B2; C1; C2; D; E1; E2 ]—
Where:
A is port safeguard code for COMM-rung/view inhibit.
B1 is starting address for Group 1 Safeguarded Registers.
B2 is ending address for Group 1 Safeguarded Registers.
C1 is starting address for Group 2 Safeguarded Registers.
C2 is ending address for Group 2 Safeguarded Registers.
D is the scan time limit in milliseconds.
E1 is tolerance of scan interrupt in 2.5 millisecond counts.
E2 is rate of scan interrupt in 2.5 millisecond counts.
These parameters are explained in detail below.
A
Chapter 6 - Security Features
A number entered here (000 through 007) prevents Channel 1, Channel 2
and/or Channel 3 ports from being assigned to communication rungs (READ,
WRITE, PRINT, ALARM). Table 6-4 shows which number restricts what
ports.
30598-526
Page 6-9
Table 6-4: Port Safeguard Codes
Code
ETHERNET Port
Restricted
COMM Port
Restricted
PRGMR Port
Restricted
X00
NO
NO
NO
X01
NO
NO
YES
X02
NO
YES
NO
X03
NO
YES
YES
X04
YES
NO
NO
X05
YES
NO
YES
X06
YES
YES
NO
X07
YES
YES
YES
When “1” is substituted for “X” as the first digit in the number (that is, 100, 101, etc.
through 107), the ability to view, display, record or print the rungs through all ports is
also prohibited.
EXAMPLE:
To prevent only the PRGMR port (channel 1) from being assigned to communication
rungs AND to inhibit the ability to view, display, record, or print out the program
through any port, enter the number "101" as the port safeguard code.
Safeguarding registers prohibits those registers from being programmed into counters,
timers, or shift registers. Also, safeguarded registers cannot be used to the left of an
equal sign in a LET statement, or have their bits programmed as coils.
Safeguarded registers are also protected from being written to by other SY/MAX
processors unless the other processor's WRITE communication rungs are also
protected from within an Inhibit Rung ladder area.
B1
Starting address for the 1st group of safeguarded registers. The starting
address can be any value from 1 to 4000 or 8001 to 8192.
B2
Ending address for the 1st group of safeguarded registers. This address must
be greater than or equal to B1 and be in the range of 2 to 4000 or 8001 to
8192.
B1, B2, C1, and C2 must be separated by a soft-key-generated semicolon.
C1
Starting address for the 2nd group of safeguarded registers. The starting
address can be any value from 1 to 4000 or 8001 to 8192.
C2
Ending address for the 2nd group of safeguarded registers. This address must
be greater than or equal to C1 and be in the range of 2 to 4000 or 8001 to
8192.
D
Scan time limit in milliseconds. If the Model 450 exceeds the scan time limit,
it will halt with "ERROR 970" in error register 8175. When D is "0", a default
scan time limit of 1 second is assigned.
Chapter 6 - Security Features
Page 6-10
30598-526
6.8.1 Safeguard Rung Considerations
• Zeros should be placed in parameter locations for features that are unused. For
example, if only one group of registers is to be protected, enter "0" for the Cl and C2
parameters.
• If Timed Interrupt tolerance and rate are the only parameters used (no Safeguard
parameters), only values for E1 and E2 need be entered. Because the Safeguard rung
parameters are read from right-to-left, E1 and E2 will be the first parameters
encountered and are interpreted as Timed Interrupt parameters. Omitting values for
other parameters causes them to be ignored.
• Only register 8165 can be assigned as the safeguard TLET rung.
• Only one safeguard TLET rung is allowed in the entire ladder program, and it must
be the first rung in the program.
• Make sure the Model 450 is in HALT before entering the Safeguard rung into the
program. If the Model 450 is in RUN while the rung is entered, the rung will
execute normally and possibly create unwanted values in registers 8165, 8166,
8167, and any others used in the rung.
• Parameters A;B1;B2;C1;C2 of the TLET rung require that an inhibit rung exists in
the ladder program. If no inhibit rung exists, the safeguard parameters
A;B1;B2;C1;C2 are ignored.
• The safeguard TLET rung parameters cannot be altered once the inhibit rung is
programmed and the Model 450 is power-cycled or is keyswitched to RUN. All
ladder program and rack addressing must be deleted before the safeguard rung can
be altered.
• If password register 8177 is included in the block of safeguarded registers, the only
way to override and delete the safeguard rung is to remove the Model 450 from the
rack, and then remove the onboard battery. This allows the memory to completely
discharge.
• To override and delete the safeguard rung, the entire ladder program and all rack
addressing must be cleared from Model 450 memory. This is accomplished by
connecting programming equipment to channel 1 (PRGMR port), and performing
the following steps (steps given are for SY/MATE Plus software):
1. Confirm that the security jumper is in the DISABLED position (Section 6.4).
2. Display the ONLINE/STATUS screen.
3. Press the CLEAR MEMORY soft key.
4. Press the CLEAR PLC soft key, and on the next screen, press CONFIRM.
5. Access the DATA mode.
6. Store the decimal value -1 into register 8177 (the password register).
7. Repeat steps 2 through 6.
The result of the above CLEAR PLC operation is a completely blank user memory,
meaning that the following conditions are true within the Model 450:
• No ladder program
• Default rack addressing
• Zeroed register values
• No enabled security features.
Chapter 6 - Security Features
30598-526
Page 6-11
NOTE
The CLEAR PLC operation clears or resets all processor registers.
However, the Ethernet NIM registers are not cleared. Those registers
not cleared or reset include the ENIM storage (mailbox) registers
(registers 3000-4999) and the Ethernet communication performance
data registers (registers 7000-7999). Two alternatives for clearing or
resetting the ENIM registers exist:
1. Remove the Model 450 from the SY/MAX rack, remove the battery
from the Model 450 and wait for approximately 2 minutes for the
memory to clear. Then replace the battery, place the Model 450 in
the rack and provide power.
2. The second method is to program a series of WRITE rungs into the
PLC to clear the ENIM storage registers (3000-4999). Cycling power
then clears the performance calculations (7XX2-7XX5), but not the
performance parameters (7XX0-7XX1) or the storage registers.
Developing a small utility ladder program to clear the storage
registers and set the default Ethernet parameters may be useful.
This program could then be run anytime a CLEAR PLC is issued to
clear or reset all the desired registers.
6.8.2 Timed Interrupt Operation
The parameters El and E2 in the TLET S8165 rung define the values for timed interrupt
tolerance and timed interrupt rate, respectively.
This method of scan control interrupts the ladder program at specified time intervals to
execute a certain group of rungs (a special subroutine), and then returns to the main
program. This methnd of interrupt is useful for applications where certain inputs of
data must be continuously sampled within a particular repeatable time limit.
Subroutine number 8190 is reserved for the timed interrupt function. 'I'he following
two rungs are used to identify the timed interrupt subroutine:
MARK 8190
RTN 8190
Refer to the "Processor Scan Control" section in the respective programmer manual for
an in-depth discussion of using GOTO, GOSUB, and TIMED INTERRUPT scan
controlling techniques.
The purpose of the timed interrupt is to ensure that, regardless of program length, a
specific block of rungs is executed within a given period of time. Typically this
involves monitoring a select group of inputs while programmed rungs control a select
group of outputs.
Chapter 6 - Security Features
Page 6-12
30598-526
The timed interrupt subroutine should not contain any transition-sensitive rungs, or
any rungs that require multiple program scans to complete their operation. Examples
of these rungs include communication statements (READ, ALARM, WRITE),
transitional coils or TLETs, shift registers, and timers.
While the programmed interrupt rate specifies the rate at which the interrupt is to
occur, it may not always be possible to interrupt the Model 450's scan precisely at that
rate. For example, the processor cannot be interrupted while it is scanning a rung or
during end-of-scan activities such as updating external I/O and servicing
communication ports.
NOTE
RUN mode programming is not allowed when the TIMED INTERRUPT
is enabled; attempts will be rejected with ERROR 79 posted by the
programming software.
For the processor to have sufficient time to call the timed interrupt subroutine, the
programmed tolerance must exceed the external I/O update time plus the
communication port servicing time. The time required to update external I/O is a
function of system layout and rack addressing; refer to Chapter 14 for more
information regarding I/O updating. Servicing the communication ports can require an
additional 5 milliseconds per scan if saturated. These factors can combine to form a
substantial time period during which the Model 450's scan cannot be interrupted.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
A program containing a Timed Interrupt should always be tested first,
under conditions simulating the rack addressing and communication
demands that the system will experience when installed at the actual
job site.
Failure to observe this precaution can cause equipment damage or personal
injury.
In the event that interrupt tolerance errors (ERROR 29102) are encountered, it may be
possible to eliminate these errors by optimizing rack addressing and/or restricting
communication traffic. If errors persist, the programmed tolerance value needs to be
increased.
In the majority of applications that require speed, the inherently fast scan speed of the
Model 450 eliminates the need for the timed interrupt function.
Chapter 6 - Security Features
30598-526
Page 6-13
NOTE
Since the Model 450 updates external I/O at the end of each ladder
scan, any timed interrupt that is executed more than once per scan
must also update the external I/O at the same rate as the timed interrupt
occurs. See the next two paragraphs for more information.
Registers 8105 and 8106, in conjunction with bit 7 of register 8176, can be
programmed to perform an immediate I/O update within the timed interrupt (see
Section 13.2). This selectively updates any registers that require fresh information.
Thus, registers used as inputs within the timed interrupt subroutine should be updated
at the beginning of the subroutine, while output registers within the subroutine should
be updated just before exiting the subroutine.
A scan penalty is paid to accomplish immediate I/O updating, and must be considered
when determining the execution time of the timed interrupt subroutine. (See the
“Execution Times” reference table in Chapter 14.) The time needed for this updating
becomes more and more significant when the ladder portion of the subroutine is short.
To economize these register updates, group together input and output addresses that
are used in the timed interrupt to minimize the scan time impact of performing
immediate I/O updates.
6.9 PASSWORD AND RESTRICTION REGISTERS
The Model 450 processor uses register 8178 for storing an access code and register
8177 for storing a "password" value.
The following restrictions can be imposed on any port by using Password Register
Restriction:
1. Inhibit ladder programming or editing. Restricts the programming or editing of
ladder logic using any programming device. Bit 4, 8 or 12 of register 8178.
2. Prevent programming equipment from forcing I/O registers. Restricts the forcing
of register outputs using programming equipment. Bit 2, 6 or 10 of register 8178.
3. Prevent programming equipment from altering register data. Prevents the use of
programming equipment to write to or change data values that are stored in all
registers. Bit 3, 7, or 11 of register 8178.
4. Prevent any non-programming devices from altering registers. Prevents the use of
processor-to-processor communication (priority communication) to alter data
values stored in all registers. Bit 1, 5 or 9 of register 8178.
The bit pattern in register 8178 (the restriction code register) determines which port
(channel) is protected, and by which restrictions. Table 6-5 shows which bit in register
8178 needs to be turned ON to achieve the desired restriction and port.
Chapter 6 - Security Features
Page 6-14
30598-526
Table 6-5: Restriction Code Bit Table
Register 8178, Bit # ON
Restriction and Port
1
PRGMR port - processor to processor
communications. Restricts writing of data to
Model 450 registers.
2
PRGMR port - forcing of I/O is prevented using
programming equipment.
3
PRGMR port - programming equipment to
processor communications. Restricts writing of
data to Model 450 data registers.
4
PRGMR port - restricts altering the ladder
program in any way.
5
COMM port - same effect as bit 1
6
COMM port - same effect as bit 2
7
COMM port - same effect as bit 3
8
COMM port - same effect as bit 4
9
Ethernet port - same effect as bit 1
10
Ethernet port - same effect as bit 2
11
Ethernet port - same effect as bit 3
12
Ethernet port - same effect as bit 4
To enable the restriction code, a non-zero "password number" must be entered (via the
DATA ENTER mode of a programming device) into register 8177.
Once a password value is entered into register 8177, "-1" is displayed when attempts
are made to monitor this register. This keeps the password confidential. Thus, "-1"
cannot itself be used as a password value.
The restriction code can be altered only by the exact password value entered into
register 8177. When this is done, register 8177 displays "0".
To disable the password/restriction code feature, enter a CLEAR PLC command
through the PRGMR port. This is allowed regardless of the restriction code in effect,
and resets the password register to zero. All rungs not protected by Inhibit Rungs are
also deleted.
6.10 MEMORY PROTECT BIT
Prohibits:
Ladder programming or editing through the COMM or ETHERNET
ports (does not affect the PRGMR port).
Uses:
Control Register 8176, bit 4.
When bit 4 of register 8176 is "ON", all user ladder programs, rack addressing, and
labels are protected from editing. This protection feature affects the COMM and
ETHERNET ports (channels 2 and 3) only. It is ignored by the PRGMR port (channel
1).
To enable the Memory Protect bit, two methods can be used:
Chapter 6 - Security Features
30598-526
Page 6-15
1. Program a rung containing only a coil addressed as bit 4 of register 8176, like this:
8176
04
2. With a programming device in the DATA ENTER mode, enter "1" in bit 4 of
register 8176.
To disable the Memory Protect bit, delete the rung and reset bit 4 to "0".
NOTE
Merely deleting the rung does not turn bit 4 off, and by itself does not
disable Memory Protect.
6.11
FORCE INHIBITBIT
Prohibits:
Forcing of I/O by programming equipment through the COMM or
ETHERNET ports (does not affect the PRGMR port).
Uses:
Control Register 8176, bit 5.
When bit 5 of register 8176 is ON, the forcing of I/O registers (with programming
equipment) through the Model 450’s COMM and ETHERNET ports (channels 2 and
3) is prohibited. This feature is ignored by the PRGMR port (channel 1). See Chapter
14 for more information on forcing.
To enable the Force Inhibit bit, two methods can be used:
1. Program a rung containing only a coil addressed to bit 5 of register 8176, like this:
8176
05
2. With a programming device in the DATA ENTER mode, enter "1" in bit 5 of
register 8176.
To disable the Force Inhibit bit, delete the rung and reset bit 5 to "0".
NOTE
Merely deleting the rung does not turn bit 5 off, and by itself does not
disable Force Inhibit.
Chapter 6 - Security Features
Page 6-16
6.12
30598-526
REGISTER PROTECT BIT
Prohibits:
Altering of register data by any external device through the
COMM or ETHERNET port (does not affect the PRGMR
port).
Uses:
Control Register 8176, bit #6.
When bit 5 of register 8176 is ON, the altering of any Model 450 data registers through
the COMM and ETHERNET ports (channels 2 and 3) is prohibited. This feature is
ignored by the PRGMR port (channel 1).
To enable this feature, two methods can be used:
1. Program a rung containing only a coil addressed to bit 6 of register 8176, like this:
8176
06
2. With a programming device in the DATA ENTER mode, enter "1" in bit 6 of
register 8176.
To disable the Register Protect bit, delete the rung and reset bit 6 to "0".
NOTE
Merely deleting the rung does not turn bit 6 off, and by itself does not
disable Register Protect.
6.13
FENCED REGISTERS BIT
Prohibits:
Altering of any register within a user-defined fenced area
through the COMM or ETHERNET port (it does not affect the
PRGMR port).
Uses:
Control Registers 8173 and 8174.
Registers 8174 and 8173 contain, respectively, the beginning and ending addresses of
an unprotected user-defined block of data registers. All registers outside of the defined
block are protected from alteration by outside devices. The default (power-up) value in
register 8174 is “1”; for 8173 it is “8176”. Therefore, registers 8177 through 8192 are
effectively fenced.
Fenced registers are alterable through the PRGMR port (Channel 1) by other
processors and programmers whose security access level is set to Override.
Chapter 6 - Security Features
30598-526
7
Page 7-1
FLOATING-POINT MATH
7.1 INTRODUCTION
This chapter provides information on the Model 450 floating-point (FP) math
capabilities. Floating-point math allows the Model 450 processors to perform
high-level math operations on data values containing a floating decimal point.
The Model 450's floating-point operation conforms to the ANSI/IEEE Standard 754
pertaining to the 32-bit standard for floating-point math.
7.2 DEFINITION OF TERMS
Compare
(IF lnstruction)
Comparison of a value in one data register to a
constant, to the value of a second register, or to the
result of a math operation.
The result of one math operation in an expression
containing multiple operations.
Math functions + - x ÷
Exceeding the numerical storage range of the data
register.
The final value of any mathematical expression
(result = A + B - C).
Also called a function key (for use on an IBM®
keyboard using SY/MATE Plus Programming
Software).
Storing a constant numerical data value or math result
in a data storage register.
Intermediate Result
Operator
Overflow
Result
Soft Key
Transfer
(LET Instruction)
7.3 REGISTER USAGE
The Model 450 processor uses different methods to handle data stored in integer and
floating-point registers. See Figure 7-1.
16
EVEN or ODD Address
1
INTEGER Storage Register
16
ODD Address
1
16
EVEN Address (ODD Address + 1)
1
FLOATING-POINT Storage Register
Figure 7-1 Floating Point vs. Integer Register
Chapter 7 - Floating-Point Math
Page 7-2
30598-526
7.3.1 Integer Data
The range for an integer data value stored in an integer register (to be used in a math
calculation) is ±32,767. The exceptions to the range limitations are registers used in
timers, counters, and matrix pointers. Registers that store the current time and count
can range from 0 to +9999, while matrix pointers cannot exceed 4000.
7.3.2 Floating-Point Operations
The Model 450 uses two consecutively addressed 16-bit data registers to create a
32-bit floating-point data register, as shown in Figure 7-1.
A floating-point register can contain a number from ±3.4 x 1038 to ±1.2 x 10-38. The
mantissa is limited to seven digits. Values are entered and displayed using scientific
notation. This notation is shown as “E” followed by an integer representing the power
to which 10 is raised and multiplied by the mantissa. For example, “25,000” is
displayed as “2.5 E + 04”. See Section 7.4.
7.4 ADDRESSING FLOATING-POINT REGISTERS
Of the register pair that makes up a floating-point register, only the ODD-numbered
register can be used as the address. If the even address is used, an “Illegal Address”
error results. The Model 450 automatically assigns the even-addressed register that
follows the odd-addressed register. See Section 7.5 for instructions on how to directly
enter floating-point numbers.
When a rung containing a floating-point register is entered into a ladder program, the
letter F (generated by the F REG (Shift-F1) soft key) precedes the odd address value
of that register. See the following example.
EXAMPLE:
Given: A floating-point register pair, F0051/F0052, is used to store the value
0.001234567 (1.234567 x 10-3). The rung used to program this information is shown
in Figure 7-2.
OFFLINE/LADDER/CREATE
LET
F0051 = 1.234567E-03
Figure 7-2 Example 1: Floating Point LET Rung
Procedure: Press the LET (Shift-F6) soft key to produce another menu of soft keys.
This new menu of soft keys describes and defines the various data register types as
shown in the following list:
S REG (F1)
F REG (Shift-F1)
MATRIX (F2)
ARRAY (Shift-F2)
CONST (F3)
FCONST (Shift-F3)
Chapter 7 - Floating-Point Math
Integer Register
Floating-Point Register
Integer Matrix
Floating-Point Matrix
Integer Constant
Floating-Point Constant
30598-526
Page 7-3
Since a floating point register is being used here, press <Shift>-<F1> to use the
F REG soft key, then type 51 to enter the odd register (0051) address. Register F0052
automatically becomes a part of the floating-point register addressed as F0051.
Figure 7-3 shows that register pair 0051 and 0052 will store the value 0.001234567 in
32-bit format.
F0051
F0052
16 Bits
16 Bits
Figure 7-3 Register Structure Example
Once assigned as half of a floating-point register pair, register 0052 cannot be used for
any other purpose in the same ladder program, as the bit pattern is only meaningful as
part of a floating-point pair.
NOTE
Attempting to program an even-numbered floating-point address
results in an error message stating that the address must be odd.
After entering the register address, complete the box by moving the cursor to the right
of the equal sign and pressing the F CONST (<Shift>-<F3>) soft key, followed by the
desired floating-point number.
LADDER PROGRAM REGISTER USAGE
Any of the first 4000 user-addressable registers in the Model 450 can be designated as
floating-point registers. Since each 32-bit floating-point register requires an odd-even
16-bit register pair (32 bits), 2000 floating-point registers can be used.
While it is not necessary to dedicate a block of registers to contain floating-point
values, it is always a good idea to group together registers that serve the same purpose
such as external I/O, internal I/O, integer storage, and floating-point storage.
0001
Designate these
registers as external
I/O points
0256
0257
These can be integer
storage registers
1001
1002
1000
1001
4000
These can be floating
point storage registers
(1500 register pairs)
3999
4000
Figure 7-4 Sample Register Allocation
Chapter 7 - Floating-Point Math
Page 7-4
30598-526
7.5 DATA TRANSFERS (LET) AND COMPARISONS (IF) USING
FLOATING-POINT NUMBERS
Floating-point registers are allowed within two types of ladder program instructions:
• LET instructions
• IF instructions
7.5.1 Data Transfers (“LET” Instruction)
The LET operation copies a value (a constant, data value, or math result) from the right
of the equal sign to the register(s) on the left side of the equal sign. Figure 7-5 shows
the operation of an integer and a floating-point data transfer (LET instruction).
Integer LET:
LET
Register
contents
before rung
is scanned
Register
contents
after rung is
scanned
+ XXXX
+ YYYY
S0011
S0034
+ YYYY
+ YYYY
S0011
S0034
Floating-Point LET:
Register
contents
before rung
is scanned
Register
contents
after rung is
scanned
S0011 = S0034
LET
F0011 = F0035
X.XXX E00
Y.YYY E00
F0011/12
F0035/36
Y.YYY E00
Y.YYY E00
F0011/12
F0035/36
Figure 7-5 Operation of LET Instruction
Chapter 7 - Floating-Point Math
30598-526
Page 7-5
See Section 7.8 for information about math operations allowed within LET and IF
instructions.
7.5.2 Comparison (“IF” Instruction)
The IF instruction compares the contents of an integer or floating-point register on the
left of the COMPARE symbol to a constant or value stored in an integer or register to
the right of the COMPARE symbol.
When comparing two floating-point values for equality, the two values must be exactly
equal before the IF rung executes true.
7.6 ENTERING FLOATING-POINT VALUES
SY/MAX family devices that can enter floating-point data directly into floating-point
registers include:
• Type SPR-300 Deluxe CRT Programmer, Series “i” (Revision 2.6 or later)
• SY/MATE Programming Software
• SY/MATE Plus Programming Software.
In this instruction bulletin, however, SY/MATE Plus Programming Software is used
for programming examples.
7.6.1 Entering Floating-Point Numbers via the Programming
Equipment’s Data Mode
To enter a floating-point value into a register, the keystrokes shown in the following
table are required. Assume that the number 0.001234567 (1.234567 x 10-3) is to be
entered into odd-addressed register 0051.
The [bracket] notation refers to a soft (function) key, while the bold type is a dedicated
keyboard key.
Table 7-1: Steps Required to Enter a Floating-Point Value
Step Number
Keys Used
1
F2 [DATA]
2
51
3
F7 [DISPLY FP]
4
F3 [WRITE DATA]
5
1.234567E-3
6
[ENTER]
Remarks
Accessed from STATUS screen.
Accessed from DATA screen.
Enters the first address of the register pair.
When pressed, the cursor will move down one
line and will show the even-numbered address
(0052) of the selected floating-point register
pair.
Enter the floating-point value.
Loads the number into the register pair.
7.6.2 Floating Point Considerations
• A seven-digit mantissa coupled to a double-digit exponent is the limit of significant
figure accuracy when entering a floating-point number.
• A negative value can be entered by pressing the minus (-) key immediately after
pressing F3 [WRITE DATA].
Chapter 7 - Floating-Point Math
Page 7-6
30598-526
• If a value is not entered in scientific notation, the Model 450 automatically converts
the value to scientific notation when [ENTER] is pressed.
• When entering a value in scientific notation, a negative exponent is specified by
pressing the [-] key after the Shift [E] key.
7.7 DISPLAYING FLOATING-POINT VALUES
When using a programming device, two methods for viewing the data stored in
floating-point registers can be used: from the ONLINE/DATA screen and from the
ONLINE/LADDER screen. Each of these is explained below.
METHOD 1:
From the ONLINE/DATA mode, press NEXT ADDR [F1] to
display registers. (Alternatively, you can type the first register
number and press [F1] to display the following registers.) Next,
press [F7] to see the floating-point values for the registers. Notice
that only the odd-numbered registers have values appearing in them,
because floating point requires a pair of registers (32 bits). (See
Figure 7-6.)
Figure 7-6 Viewing Floating-Point Register F0023 in Data Display Mode SY/MATE Plus Programming Software
Chapter 7 - Floating-Point Math
30598-526
METHOD 2:
Page 7-7
From the ONLINE/LADDER screen, display the rung that is using
the floating-point register by searching for the rung (see Figure 7-7).
Make sure that POLL is ON.
Figure 7-7 Ladder Rung Display Mode - SY/MATE Plus Programming Software
7.8 FLOATING-POINT OPERATIONS WITHIN
LET AND IF INSTRUCTIONS
The Model 450 processor allows the following math functions to be programmed
within “LET” and “IF” instructions:
Table 7-2: Allowable Floating-Point Operations in LET and IF Instructions
Operation
Symbol on Display
Addition
+
Subtraction
-
Multiplication
x
Division
÷
Square Root
SQRT
Sine
SIN
Cosine
COS
Common (Base 10) Logarithm
LOG
Natural (Base e) Logarithm
LN
Absolute Value
ABS
Chapter 7 - Floating-Point Math
Page 7-8
30598-526
Table 7-2: Allowable Floating-Point Operations in LET and IF Instructions
Operation
Symbol on Display
Y to the X Power
Y**X
The functions in Table 7-2 can be performed on any data values; floating point, integer,
or on any constant floating point or integer.
7.8.1 Sequence of Math Operations
Math operations are performed left to right within LET and IF instruction boxes and
may be placed only to the right of the equal (=) sign or compare (<, ≥, etc.) symbol, as
shown in Figure 7-8. Math operations can be placed anywhere within the dotted box.
SIN
LET F0011 =
SQRT
F0021 000 + F0461 004 - 5.675 E00
IN A “LET” BOX
IF F0011 =
F0021 000 + F0461 004 - 5.675 E00
IN AN “IF” BOX
Figure 7-8 Math Operations in LET and IF Boxes
The number of math operations that can be programmed into a “LET” or “IF” rung is
limited by the areas available in one row of the programming device's ladder matrix
display, as shown in Figure 7-9.
1
2
3
4
5
6
7
8
9
10
11
IN A “LET” BOX
(11 “areas” total)
1
2
3
4
5
6
7
8
9
10
IN AN “IF” BOX
(10 “areas” total)
Figure 7-9 Math Operations in LET and IF Boxes
7.8.2 Math Programming Considerations
• The maximum number of areas available in an IF instruction is 10 when contacts
are not programmed in the same rung.
Chapter 7 - Floating-Point Math
30598-526
Page 7-9
• The maximum number of areas available in a LET instruction is 11 when contacts
are not programmed in the same rung.
NOTE
Multiple LET or IF rungs can be used if an instruction requires
too many operations to be contained within one rung.
7.9 FLOATING-POINT OPERATION USING MATRICES
In many floating-point applications, the use of matrices, in addition to single
floating-point registers, will minimize memory requirements.
A floating-point matrix or array is a group of consecutively numbered floating-point
registers. The rules governing the use of matrices are explained in the SY/MATE Plus
Programming Software Instruction Bulletin (#30598-322).
7.10
COMBINING FLOATING POINT WITH INTEGER OPERATIONS
Combining floating-point and integer registers in the same LET or IF instruction is
allowed in the Model 450 processor. The user (programmer) should be very familiar
with programming techniques before attempting this type of programming option.
The following sections provide examples and considerations for combining
floating-point and integer math within the same LET or IF instruction.
7.10.1 LET Instructions
If a single LET instruction contains operations performed on both integer and
floating-point values, the final result is always in the floating-point format. See
Figure 7-10.
The final operation stores the math result in the register specified on the left of the
equal sign. If the math result (floating point or integer) to the right of the equal sign
does not match the register type to the left of the equal sign, the processor converts the
math result to match it. The following paragraphs describe four cases in which this
occurs.
Chapter 7 - Floating-Point Math
Page 7-10
30598-526
LET S0001 = S0002 + F0003 - 4 + S0011 x S0013
STEP 1 Result
(floating point)
STEP 2 Result
(floating point)
STEP 3 Result
(floating point)
STEP 4 Result
(floating point)
Figure 7-10 Operation Sequence in a LET Instruction
Containing Both Integer and Floating-Point Registers
NOTE
Once a floating-point value is encountered, the remaining operations are
automatically converted to floating point by the processor.
Since the processor cannot store a floating-point value in a 16-bit integer register, the
floating-point value is converted to a 16-bit integer value by rounding the decimal
fraction to the nearest whole number. Values less than 0.5 are rounded down; values
greater than 0.5 are rounded up. For a decimal exactly equal to 0.5, the rounded result
is the nearest even integer (for example, 2.5 is rounded down to 2.0; while 3.5 is
rounded up to 4.0).
Chapter 7 - Floating-Point Math
30598-526
Page 7-11
Case 1- Integer Register on the Left, Floating-Point Register on the Right:
LET
Sxxx
=
Fxxx
Convert Fxxx to a 16-bit
integer value, rounding
fraction to the nearest whole
number.
Store this new integer value
in register Sxxx.
The possibility exists in Case 1 for an overflow condition. This is due to the transfer of
a converted floating-point value to an integer register. See Section 7.11, “Overflow
Errors.”
Case 2- Floating-Point Register on the Left, Integer Register on the Right:
LET
Fxxx
=
Syyy
Convert Syyy to a 32-bit
floating-point value with the
fractional portion equal to
.000.
Store this new floating-point
value in register Fxxx.
Case 3- Floating-Point Register on the Left, Floating-Point Register on
the Right:
LET
Fxxx
=
Fyyy
Store Fyyy in register Fxxx.
Case 4- Integer Register on the Left, Integer Register on the Right:
LET
Sxxx
=
Syyy
Store Syyy in register Sxxx.
Chapter 7 - Floating-Point Math
Page 7-12
30598-526
7.10.2 IF Instructions
When an IF instruction performs math operations on both integer and floating-point
values, the final result on the right side of the compare will be a floating-point value.
See Figure 7-11.
IF S0001 ≥ S0002 + F0003 - F0005 - S0007
STEP 1 Result
(floating point)
STEP 4 - Convert
S0001 to a
floating-point
value.
STEP 2 Result
(floating point)
STEP 3 Result
(floating point)
STEP 5 Compare the
floating-point
values.
Figure 7-11 Operation Sequence in an IF Instruction
Containing Both Integer and Floating-Point Registers
If the final result of several operations is a floating-point value for comparison against
an integer value, the integer value is first converted by the Model 450 to an equivalent
floating-point value. The four possible "conversion/comparisons" are as follows:
Case 1- Compare an Integer Value to a Floating-Point Result:
IF
Sxxx
≥
Fyyy
Convert Sxxx to
floating-point format.
Compare
Case 2- Compare a Floating-Point Result to an Integer Value:
IF
Fxxx
≥
Syyy
Compare
Chapter 7 - Floating-Point Math
Convert Syyy to
floating-point format.
30598-526
Page 7-13
Case 3- Compare a Floating-Point Result to a Floating-Point Value:
IF
Fxxx
≥
No conversion needed.
Fyyy
Compare
Case 4- Compare an Integer Value to an Integer Result:
IF
Sxxx
≥
No conversion needed.
Syyy
Compare
7.11 OVERFLOW ERRORS
Overflow errors result from attempts to exceed a storage register's capacity.
7.11.1 Accumulator Operation
When LET instructions (data transfers) or IF instructions (data compares)
containing math operations are scanned, the intermediate and final math results
are temporarily stored in an accumulator. The accumulator contains the current
running total of the math operation and is shown as a shaded rectangle in
Figure 7-12 following.
LET F0001 = F0003 + F0005 + F0007 + F0009
1st Result*
2nd Result*
3rd Result*
2.0
4.0
70
* Given that F0003 = 1.0, F0005 = 1.0, F0007 = 2.0, F0009 = 3.0
Figure 7-12 Accumulator Operation
Chapter 7 - Floating-Point Math
Page 7-14
30598-526
The accumulator can store a much larger value than floating point or integer storage
registers. Numbers in the accumulator can range from ±3.4 x 10-4932 to ±1.2 x 10+4932.
NOTE
The operator has no direct control over the operation or contents of the
accumulator unless one of the "Alternate Accumulator Manipulations"
functions is used. Refer to Section 8. 5 and pages 8-2 and 8-3.
7.11.2 Why Do Overflows Occur?
Overflow errors are generated any time an attempt is made to exceed a storage
register's capacity. Table 7-3 shows register types and allowable storage ranges.
Figure 7-13 on page 7-15 illustrates where overflows can occur.
Table 7-3: Possible Overflow Locations
Register Type
Capacity
Integer
± 32,767*
Integer accumulator
± 2,147,483,647*
Floating point
± 1.2 x 10-38 to
± 3.4 x 1038
Floating-point accumulator
± 1.2 x 10+4932 to
± 3.4 x 10-4932
* Using -32,768 or -2,147,483,648 in a math statement may produce an overflow error.
Although the Model 450’s control processor is designed to prevent the floating-point
math coprocessor generating a result of infinity from a calculation (caught by the
overflow checking), infinity can be introduced into a floating-point register by loading
the values shown in Table 7-4.
Table 7-4: Overflow Indicators
Register
Indication of Exceeding
Positive Overrange Limit
(+3.4 x 1038)
Indication of Exceeding
Negative Overrange Limit
(-3.4 x 1038)
Hexadecimal
Decimal
Hexadecimal
Decimal
F0051
0000
00000
0000
00000
F0052
7F80
32640
FF80
-00128
NOTE
Avoid entering any infinity-producing value into a floating-point register.
Infinity is a mathematically invalid result that defeats the purpose of the
overflow bits, causing these bits to be unreliable. Once present, infinity may
propagate throughout other calculations and produce unwanted results.
Chapter 7 - Floating-Point Math
30598-526
LET*
* For an IF instruction,
an overflow error
causes the rung to
be executed FALSE
and also sets bit 8 of
control register 8176
to 1.
For the LET, an
overflow sets bit 18
of the recipient
status field to 1. The
final result does not
transfer.
Fxxx
=
Fyyy
+
Fzzz
x
Faaa
-
Fbbb
+
Page 7-15
Fccc
Result #1
YES
Accumulator
Overflow?
NO
Result #2
YES
Accumulator
Overflow?
NO
Result #3
YES
Accumulator
Overflow?
NO
Result #4 (FINAL RESULT)
YES
TRANSFER
FINAL
RESULT
Accumulator
Overflow?
NO
RESET OVERFLOW FLAG BIT IF SET
Floating Point or
Integer Overflow?
YES
NO
SET APPROPRIATE FLAG BIT,
AND DO NOT EXECUTE
Figure 7-13 Overflow Error Points
Chapter 7 - Floating-Point Math
Page 7-16
7.12
30598-526
SPECIAL MATH FUNCTIONS
SY/MAX programming tools such as the SY/MATE Plus Programming Software use
the symbols shown in the following table to represent some of the special math
functions.
Table 7-5: Math Functions and Symbols
CRT Symbol
Math Function
SIN
Sine
COS
Cosine
SQRT
Square Root
LOG
Common (base 10) Logarithm
LN
Natural (base e) Logarithm
Y**X
Raise Y to the power of X
ABS
Absolute Value
The special function always operates on the intermediate math result created by any
math expression preceding it (see Figure 7-14).
LET Fxxx = Fyyy* + 2050 + 3000 + 4500
SQRT
3500
6500
Transfer
result
11000
1.048808E02 (Final Result)
*Assume Fyyy = 1.45 E03
Figure 7-14 Special Function Operation
7.12.1 Restrictions
The value that a math function operates on is called the argument. Certain restrictions
apply regarding the sign and magnitude of the argument.
Table 7-6 illustrates the allowable argument conditions for some of the special math
functions.
Chapter 7 - Floating-Point Math
30598-526
Page 7-17
Table 7-6: Allowable Special Function Arguments
ARGUMENT CONDITION
(“Y” indicates argument is allowed. “N” means argument is not
allowed.
Special
Function
Zero
Final
Result
Over
FP
Range
Value
-
Value
+
Intermediate
Result Over
FP Range
Divide
by Zero
SQRT
in LET or IF
Y
N
N
Y
Y
N
SIN/COS
in LET or IF
Y
N
Y
Y
Y
N
LOG/LN
in LET or IF
N
N
Y
Y
Y
N
Y**X (Y)
in LET or IF
Y
N
N
Y
Y
N
Y**X (X)
in LET or IF
Y
N
Y
Y
Y
N
ABS
in LET or IF
Y
N
Y
Y
Y
N
NOTE
Due to the behavior of the math coprocessor, small inaccuracies may
be observed at function range extremes and points of discontinuity.
See Section 7.12.2, “Trigonometric Function Discontinuities”.
7.12.2 Trigonometric Function Discontinuities
The following results may be obtained when nearing points of discontinuity in
calculations:
• The sine of 0, 180 and 360° is 0; the Model 450, however, may yield very small
non-zero results.
• The tangent of 90° is infinity; the Model 450 may report it to be an extremely large
number (3.7El9, typically).
• The tangent of 180° is 0; the Model 450 may show it to be an extremely sma/l
number.
Results similar to the above could occur when using any trigonometric function. If a
problem is anticipated, it should be compensated for in the user program.
Chapter 7 - Floating-Point Math
Page 7-18
30598-526
NOTES
Chapter 7 - Floating-Point Math
30598-526
8
Page 8-1
SPECIAL INSTRUCTIONS
8.1 GENERAL INFORMATION
The Model 450 instruction set has been expanded beyond the use of floating-point
five-function math, sine, cosine, logarithms (base 10 and natural), absolute value, and
exponential math. See Chapter 7 for more information about floating-point math and
using the listed functions.
NOTE
It is strongly recommended that the concepts in Chapter 7 be read and
understood before proceeding with this chapter.
Along with the terminology in Chapter 2, familiarity with the following terms is
necessary to understand the concepts in this chapter.
Floating Point Accumulator
Integer Accumulator
Alternate Accumulator
Intermediate Result (IR)
New Intermediate Result
(NIR)
ARG2
ALT
An 80-bit “scratch-pad” register which contains the
intermediate result of the processor’s floating-point
calculations. It provides precision that would
normally be lost when using a normal 32-bit
floating-point register. (See also Chapter 7 and
Section 8.5.)
A 32-bit register containing the intermediate result of
an integer operation.
A different 80-bit register that can be accessed by the
user to exchange or swap information in the
floating-point accumulator.
The data register immediately to the right of the equal
(=) sign, or the current running total of a computation.
The IR is stored in the accumulator.
The result obtained after applying a SPECIAL
function to the intermediate result.
The notation for the second argument of a
double-argument function.
Notation for the contents of the alternate accumulator.
Programming the special instructions described in this chapter is done by pressing the
SPECIAL soft key, accessible when constructing an IF or LET rung, followed by the
corresponding function number associated with the instruction. The appropriate
function is performed on the intermediate mathematical result that exists just before
encountering the SPECIAL instruction.
NOTE
All mathematical operations are performed from left to right and each
operation is completed before the next operation in the rung is executed.
Certain functions, by definition, require a double argument. Users should program a
semicolon (from the soft key display) after the function number, followed by the
second argument (which may be either a constant or a register value).
Chapter 8 - Special Instructions
Page 8-2
30598-526
Programming any of the single argument functions results in the indicated operation
being performed on the intermediate result. To program, users must begin constructing
a rung using the IF or LET box format. The desired operation can then be applied to
any intermediate result which exists to the right of the equal (=) sign.
To implement the desired function, start from the Offline/Ladder/Create screen
(examples in this chapter show SY/MATE Plus Programming Software screens).
Figure 8-1 shows the Offline/Ladder/Create screen.
Figure 8-1 Offline/Ladder/Create Options
1. Select a LET (Shift-F6) or IF (F6) function. A rung with a LET box appears on the
screen (Figure 8-2).
Figure 8-2 LET Function Box
Chapter 8 - Special Instructions
30598-526
Page 8-3
2. Fill in the register number and move the cursor to the right of the equal sign to fill
in a value.
If you want to have a floating-point register value, select F REG (Shift-F1) before
filling in the register number.
3. From the resulting screen, press the ETC soft key (F8).
Pressing the ETC soft key produces a new display which looks like this:
Figure 8-3 ETC Options
4. From this screen you can insert a SPECIAL instruction by pressing one of the soft
keys, or the F1-SPEC(IAL) soft key. The special instruction name appears in the
upper border of the LET or IF box, and its corresponding instruction number
appears inside the box (Figure 8-4).
To change the SPECIAL instruction, you can either type the instruction number, or
scroll through a list of the instructions by pressing the <Spacebar>. For a list of all
the SPECIAL instructions, see Table 8-1 on page 8-5.
Figure 8-4 SPECIAL Instruction Box
Chapter 8 - Special Instructions
Page 8-4
30598-526
If you are finished constructing the mathematical expression, exit the LET or IF box by
moving the cursor off the box or pressing <Return>. You can also continue building
the expression by following the SPECIAL instruction with either another SPECIAL
instruction or a mathematical operator (+, -, x, ÷). In either case, the SPECIAL
function code number appears in the box to indicate the appropriate SPECIAL
function has been entered in the rung.
Programming a double argument function is similar except that the second argument
needs to be entered before the function is programmed correctly. The second argument
must be provided immediately after the numeric value identifying the SPECIAL
double argument function.
The keystrokes used for the double argument functions are the same as for the single
argument function, but require the following additional keystrokes:
1. Program a LET or IF box with a SPECIAL instruction in it as described on the
previous page.
2. Select a SPECIAL instruction that uses a double argument, for example, DRUM.
Figure 8-5 Programming a SPECIAL Instruction with Two Arguments
3. When you have selected the DRUM instruction, press the <F4> Semicolon (;) soft
key.
4. Type a value: for DRUM, the value would represent the number of steps in the drum
sequence.
PROGRAMMING CONSIDERATIONS
• The first element to the right of the equal (=) sign cannot be a mathematical
operator (+, -, x, or ÷), or a SPECIAL function.
• Entering a numeric value for a SPECIAL function that does not exist generates a
PROCESSOR ERROR 5 when the rung is loaded.
• When programming the SPECIAL functions with two arguments, the EXACT order
of entry is important. The numeric value for the function must be followed
immediately by the semicolon from the soft key display, which in turn must be
followed immediately by the second argument.
Chapter 8 - Special Instructions
30598-526
Page 8-5
Table 8-1 lists all the SPECIAL instructions supported by the Model 450 processor.
Every SPECIAL function rung resembles the example shown in Figure 8-6.
SWAP32
LET
S0010 = S0020
012
Figure 8-6 Sample SPECIAL Function Rung
Both types of the Model 450 can perform all of the listed instructions. The sample
rungs shown in the Example column of Table 8-1 are for illustrative purposes only and
are not intended to produce practical results. Most of the registers shown are integer
type registers. For certain functions (in particular, the trigonometric functions), a
floating-point register would produce more accurate results. Additionally, in most
cases, IF statements could have been used in place of the LET statements.
Table 8-1: SPECIAL Instructions
(Page 1 of 5)
SPECIAL
Function #
Function
0
SIN(X)
1
BIN to BCD
Convert binary
pattern to Binary
Coded Decimal
2
BCD to BIN
Convert BCD value
to binary
3
COS(X)
Calculate cosine of x
4
SQRT
5
LN(X)
6
Action
Example
LET F0011=F0021
SIN
000
LET S0010=S0020
BCD
001
LET S0010=S0020
BIN
002
LET F0011=F0021
COS
003
Calculate square root
of a positive value
LET S0010=S0020
SQRT
004
Calculate natural log
of x
LET F0011=F0021
LN
005
LOG(X)
Calculate common
log of x
LET F0011=F0021
LOG
006
7
|X|
Calculate absolute
value of x
LET S0010=S0020
ABS
007
8
Y**X
Raise Y to the power
of X
Y**X
LET S0010=S0020 008 ; 3
9
Y**ALT
Raise Y to the power
of the value stored in
the alternate
accumulator
10
1/X
Calculate sine of x
Calculate the
reciprocal of x
LET S0010=S0020
Y**ALT
009
LET F0011=F0021
1/X
010
Chapter 8 - Special Instructions
Page 8-6
30598-526
Table 8-1: SPECIAL Instructions
(Page 2 of 5)
SPECIAL
Function #
Action
Example
SWAP 16
High byte and low
byte of Intermediate
Result (IR) are
exchanged
SWAP16
LET S0010=S0020
011
SWAP 32
Most significant word
in the IR becomes
the New Intermediate
Result (NIR)
SWAP32
LET S0010=S0020
012
READ STAT
Indirect register read
of status field (data in
S20 points to
register where status
field is found)
READST
LET S0010=S0020
013
READ DATA
Indirect register read
of data field (data in
S20 points to the
register where data
field is located)
READAT
LET S0010=S0020
014
15
FIND BIT
Indirect register bit
search (find and
reset the lowest bit
set in S20. Store 1 to
16 to identify bit, or
store -32,768 if all
bits are at 0).
FNDBIT
LET S0010=S0020
015
16
NEGATE
Change sign of
current number
NEGATE
LET S0010=S0020
016
17
NUM TYPE
Returns type of
current number
NUMTYP
LET S0010=S0020
017
18
ACC ALT
Exchange current
and alternate
accumulators
ACCALT
LET S0010=S0020
018
19
ADD ALT
Add S20 to alternate
accumulator
ADDALT
LET S0010=S0020
019
20
SUB ALT
Subtract S20 from
alternate
accumulator
SUBALT
LET S0010=S0020
020
21
DUP ALT
Copy alternate
accumulator into
current accumulator
DUPALT
LET S0010=S0020
021
DUP ACC
Copy current
accumulator into
alternate
accumulator
DUPACC
LET S0010=S0020
022
RANDOM
Generates a random
number (from 0 to
value of current
accumulator minus 1)
RANDOM
LET S0010=S0020
023
11
12
13
14
22
23
Chapter 8 - Special Instructions
Function
Page 8-7
30598-526
Table 8-1: SPECIAL Instructions
(Page 3 of 5)
SPECIAL
Function #
Function
Action
24
ROUND
Rounds FP numbers
to integers
ROUND
LET S0010=S0020
024
25
SQUARE
Squares current
result
SQUARE
LET S0010=S0020
025
Example
Calculate
two-dimensional
hypotenuse
26
HYPOT
LET F0021=F0023
IR
2
+ ARG2
HYPOT
026;F007
2
Calculate
two-dimensional
hypotenuse
27
HYPALT
LET F0011=F0021
IR
28
HYP XYZ
2
+ ALT
2
Calculate
three-dimensional
hypotenuse
IR
2
HYPALT
027
2
+ ARG2 + ALT
HYPXYZ
LET F0029=F0031
028; F007
2
29
ADD STAT
Perform statistical
summation
S20=IR=data,
S30=ARG2=pointer
30
VARIANCE
Calculate variance
on statistical
summation
31
TAN (X)
32
COSEC (X)
Calculate 1/sin(x)
33
SECANT (X)
Calculate 1/cos(x)
34
COTAN (X)
Calculate 1/tan(x)
35
ARCSIN (X)
Calculate sin-1(x)
ARCSIN
LET F0011=F0021
035
36
ARCCOS (X)
Calculate cos-1(x)
ARCCOS
LET F0011=F0021
036
37
ARCTAN (X)
Calculate tan-1(x)
ARCTAN
LET F0011=F0021
037
Calculate tangent of
x
ADDST
LET S0010=S0020
029; F007
VARNCE
LET F0011=S0030
030
LET F0011=F0021
TAN
031
LET F0011=F0021
COSEC
032
SECANT
LET F0011=F0021
033
LET F0011=F0021
COTAN
034
Chapter 8 - Special Instructions
Page 8-8
30598-526
Table 8-1: SPECIAL Instructions
(Page 4 of 5)
SPECIAL
Function #
Function
38
ARCTAN (Y/X)
Calculate tan-1(y/x)
39
ARCCSC (X)
Calculate sin-1(1/x)
ARCCSC
LET F0011=F0021
039
40
ARCSEC (X)
Calculate cos-1(1/x)
ARCSEC
LET F0011=F0021
040
41
ARCCOT (X)
Calculate tan-1(1/x)
ARCCOT
LET F0011=F0021
041
42
SET DEGREE
Set degree mode for
trig calculations
SETDEG
LET F0011=F0021
042
43
SET RADIAN
Set radian mode for
trig calculations
SETRAD
LET F0011=F0021
043
44
DEG RAD
Convert degrees to
radians
DEGRAD
LET F0011=F0021
044
45
RAD DEG
Convert radians to
degrees
RADDEG
LET F0011=F0021
045
46
PID REV
Calculate
reverse-acting PID
loop
47
PID DIR
48
PID MAN
49
LEAD/LAG
50
PI
51
Chapter 8 - Special Instructions
Action
Example
LET F0065=F0067
ATNY/X
038 ; 10
LET S0517=51
PIDREV
046
Calculate
direct-acting PID loop
LET S0517=51
PIDDIR
047
Calculate manual
mode for PID loop
LET S0517=51
PIDMAN
048
LET S0056=71
LD/LAG
049
Perform the lead/lag
function on a process
variable
Multiply by pi
(3.1415...)
LET F0011=F0021
PI
050
L2T
Multiply by log base 2
of 10
LET F0011=F0021
L2T
051
52
L2E
Multiply by log base 2
of e
LET F0011=F0021
L2e
052
53
LG2
Multiply by log base
10 of 2
LET F0011=F0021
LG2
053
54
LN2
Multiply by log base e
of 2
LET F0011=F0021
LN2
054
30598-526
Page 8-9
Table 8-1: SPECIAL Instructions
(Page 5 of 5)
SPECIAL
Function #
Function
55
EULER
56
E
57
Action
Example
Multiply by Euler’s
Constant
LET F0011=F0021
EULER
055
Multiply by e (natural
logarithm)
LET F0011=F0021
e
056
1 DEG
Multiply by one
degree (in radians)
LET F0011=F0021
1 DEG
057
58
1 RAD
Multiply by one
radian (in degrees)
LET F0011=F0021
1 RAD
058
59
E**PI
Multiply by e raised
to the power of pi
LET F0011=F0021
e**PI
059
60
PI**E
Multiply by pi raised
to the power of e
LET F0011=F0021
PI**e
060
61
E**E
Multiply by e raised
to the power of e
LET F0011=F0021
e**e
061
62
E**EULER
Multiply by e raised
to the power of
Euler’s Constant
LET F0011=F0021
e**EUL
062
63
SQR(E)
Multiply by the
square root of e
LET F0011=F0021
SQ(e)
063
64
SQR(PI)
Multiply by the
square root of pi
LET F0011=F0021
SQ(pi)
064
65
DRUM
Initiates Drum
Sequencer operation
(the second
argument is the
number of steps in
the sequence). See
Chapter 11.
66
Reserved for
future use
Reserved for future
use
67
Bus Write
to Microcell
Enables backplane
write to Microcell
(the second
argument is the
register count; see
Section 8.6).
DRUM
LET S0021=S0021 065;20
--
LET S0001=S1001
SPEC
067;28
8.2 MATH AND TRIGONOMETRIC OPERATIONS
Chapter 8 - Special Instructions
Page 8-10
30598-526
The operations listed in Table 8-2 are designed to enhance the functions listed in the
programmer Instruction Bulletin. A number of high-precision constants are available
in the Model 450, along with the ability to perform trigonometric operations in either
degree or radian mode.
8.2.1 Application Considerations
The default mode for trigonometric operations is degrees (initially set upon a
HALT-to-RUN transition).
The selected mode remains in effect until either a SPECIAL function 42 or 43 (SET
DEGREE or SET RADIAN, respectively) is encountered, or until a HALT-to-RUN
transition occurs.
Although the CRT is limited to displaying seven figures, the internal accumulator
precision remains at 80 bits and the floating-point register’s precision is 32 bits.
All other rules for IF and LET functions apply.
In Table 8-2 and Table 8-3, the second column shows the SPECIAL function number
used in the LET box to generate that function. It is also the same number that appears
in the “SPEC #” column in Table 8-1 on page 8-5.
Table 8-2: Special Trig/Math Operations
(Page 1 of 2)
Instruction
SPEC #
Description
1/X
10
Takes the reciprocal of the intermediate result
(NIR = 1/IR)
NEGATE
16
Changes the sign of the intermediate result
(NIR = 0-IR)
ROUND
24
Rounds the current intermediate result to the
nearest integer number. The value 0.5 is
converted to the nearest even integer.
SQUARE
25
Squares the intermediate result
HYPOT
26
Calculates the two-dimensional hypotenuse. This
is a double-argument function.
HYPXYZ
28
Calculates the three-dimensional hypotenuse.
This is a double argument function.
SETDEG
42
All subsequent calculations will be performed in
degrees.
SETRAD
43
All subsequent calculations will be performed in
radians.
DEGRAD
44
Converts degrees to radians
RADDEG
45
Converts radians to degrees
TAN
31
Calculates the tangent
COSEC
32
Calculates the cosecant
SECANT
33
Calculates the secant
Chapter 8 - Special Instructions
30598-526
Page 8-11
Table 8-2: Special Trig/Math Operations
(Page 2 of 2)
Instruction
SPEC #
Description
COTAN
34
Calculates the cotangent
ARCSIN
35
Calculates the arc sine
ARCCOS
36
Calculates the arc cosine
ARCTAN
37
Calculates the arc tangent of x
ATNY/X
38
Calculates the arc tangent of y/x
ARCCSC
39
Calculates the arc cosecant
ARCSEC
40
Calculates the arc secant
ARCCOT
41
Calculates the arc cotangent
8.2.2 Trig and Math Constants
Table 8-3 is a list of constants available for use in the Model 450 programming set.
Entering the numeric function results in the intermediate result being multiplied by the
indicated constant, which is stored to 80-bit (18 significant digit) precision.
Table 8-3: Special Constants
Instruction
SPEC #
IR Will Be Multiplied By:
PI
50
Pi to 18 significant digits
L2T
51
Log base 2 of 10
L2e
52
Log base 2 of the value of e
LG2
53
Log base 10 of 2
LN2
54
Log base e of 2
EULER
55
Euler’s Constant
e
56
Natural log e
1DEG
57
One degree, in radians
1RAD
58
One radian, in degrees
e**PI
59
e raised to the power of pi
PI**e
60
Pi raised to the power of e
e**e
61
e raised to the power of e
e**EUL
62
e raised to the power of Euler’s Constant
SQ(e)
63
The square root of e
SQ(PI)
64
The square root of pi
8.3 STATISTICAL OPERATIONS
Chapter 8 - Special Instructions
Page 8-12
30598-526
Note that the new intermediate result in Table 8-4 is denoted as “N”.
Table 8-4: Statistical Functions
Instruction
SPEC #
Statistical Operation
Adds the value preceding the ADDST function to
the statistical block of registers (defined by the
pointer), as follows:
ADDST
29
F1 = SUM(X) =∑X
F3 = SUM(X2) = ∑X2
S5 = N, where N is the number of terms
which have been summed.
To be of practical value, the LET statement that
initiates the ADDST function must be
transition-sensitive. If it is not, the summation
operations will be performed every scan. The
maximum legal value for N is +32,767.
Calculates the variance on the accumulated
statistical block. The number preceding the
VARNCE function in the LET box must point to
the same block of registers used by the ADDST
function.
NIR
N • [ SUM ( x 2 ) ] – [ SUM ( x ) ] 2
= ------------------------------------------------------------------N • (N – 1)
N • Σx 2 – ( Σx ) 2
= --------------------------------------N • (N – 1)
VARNCE
30
Since the standard deviation is, by definition, the
square root of the variance, the standard
deviation can also be obtained by taking the
square root of the result of the VARNCE
operation.
In the same way, the mean can be obtained by
dividing the first floating point register assigned to
the statistical block by the fifth, as in the following:
MEAN
SUM ( x )
F1
= ------------------ = Σx
---- = -----N
N
S5
The number preceding SPECIAL function 29 (ADDST) in the LET box (X) represents
the numeric quantity to be operated on and then stored in the statistical block. The
number can be contained in either an integer or a floating-point register.
The second argument (which follows the semicolon) may be a constant or a variable
and must be an odd integer ranging from 1 to 3995. This integer is used as a pointer to
a user-specified block of 5 registers of accumulated data. Note that the first four
registers are actually a pair of floating-point registers and the fifth is an integer register.
8.4 INDIRECT REGISTER READ OPERATIONS
Chapter 8 - Special Instructions
30598-526
Page 8-13
For the functions listed in Table 8-5, the number preceding the SPECIAL function in
the LET box acts as an indirect pointer to the desired register. The indirect pointer
must be an integer (representing a number or a storage register) ranging from 1 to 4000
or 8097 to 8192.
Table 8-5: Register Read Operations
Instruction
SPEC #
Read Operation
READST
13
Reads the status field of the indicated indirect
register. The status field becomes the new IR
(NIR = status field of the register pointed at by the
IR).
READAT
14
Reads the data field of the indicated indirect
register.The data field becomes the new IR (NIR
= data field of the register pointed at by the IR).
15
Locates and identifies the lowest bit set in the
indirect register data field. The lowest bit position
that is set becomes the new IR, then the bit itself
is reset. If no bits are found to be set, tne NIR
becomes 8000H (-32,768). Thus, the only values
which the NIR can become after execution of
FNDBIT are 1 to 16 (if bit is found), or -32,768 (if
bit is not found). To be of practical value, the LET
statement that initiates the FNDBIT function
should be transition-sensitive. If not, the operation
is performed every scan and the user may not
perceive proper operation.
FNDBIT
Chapter 8 - Special Instructions
Page 8-14
30598-526
8.5 ALTERNATE ACCUMULATOR MANIPULATIONS
The functions listed in Table 8-6 allow access to the two 80-bit floating-point
accumulators in the Model 450. These accumulators maintain a high accuracy which
might otherwise be lost in a standard 32-bit floating point register. See also Section
7.11 and Section 8.1.
Table 8-6: Accumulator Manipulations
Instruction
SPEC #
Read Operation
Y**ALT
9
Similar to the math operation Y*, except that Y is
raised to the power of the alternate accumulator
(NIR=IRALT).
ACCALT
18
Exchanges the intermediate result with the
alternate accumulator (IR becomes ALT and ALT
becomes IR).
ADDALT
19
Adds the intermediate result to the alternate
accumulator. The intermediate result remains the
same.
SUBALT
20
Subtracts the intermediate result from the
alternate accumulator. The intermediate result
remains the same.
DUPALT
21
Duplicates the alternate accumulator. The NIR
assumes the value in the alternate accumulator
(NIR=ALT), and the alternate accumulator
remains unchanged.
DUPACC
22
Duplicates the accumulator (intermediate result).
The intermediate result is copied into the
alternate accumulator (ALT=NIR) and the IR
remains unchanged.
HYPALT
27
Calculates the hypotenuse based on results
stored in the alternate and IR accumulators.
[ NIR = (
ATNY/X
Chapter 8 - Special Instructions
38
IR
2
2
+ ALT ) ]
Calculates the arc tangent for the ratio of the
intermediate result to the second argument
[NIR = ARCTAN (IR/ARG2)]
Page 8-15
30598-526
8.6 BUS WRITE TO MICROCELL
SPECIAL function 67, described in Table 8-7, allows information to be exchanged
with the Microcell by way of the backplane. During data exchange, the image table
operation of the Model 450 processor requires some special considerations not
explicitly stated earlier in this chapter or in Section 11.4 of the Microcell Instruction
Bulletin (#30598-275). The following technique for reading and writing registers
applies to Model 450 processors, Revision 4.00 or later, used with Microcells
which are Revision 4.0 and later. Earlier revision Microcells allow the Model 450
processor to write data over the backplane, but not to read any registers.
Table 8-7: Bus Write to Microcell
Instruction
SPEC #
Bus Write to
Microcell
67
Read Operation
Performs an immediate write of data to the
specified register, with the count value indicated
by the second argument.
8.6.1 Reading Registers
All rack-addressed Microcell registers (maximum of 256) are read by the processor
into its image table as part of normal End-of-Scan updating.
8.6.2 Writing Registers
Any rack-addressed Microcell registers can be written to the processor by utilizing the
following SPECIAL command:
SPEC
LET Saaaa = Sbbbb
67;ccc
Where:
aaaa =
first Microcell destination register
bbbb =
first processor source register
ccc
register count
=
SPECIAL function 67 is similar to an Immediate I/O Update instruction and results in
the contents of the block of processor registers starting at address bbbb to be written to
the block of Microcell registers starting at address aaaa, with the block size
determined by the register count ccc. Note that this is different from a standard LET
statement which only transfers data within the image table registers of the processor.
The following application considerations apply:
• The Microcell must be Rev. 4.0 or greater.
• The format must be exactly as shown in the above example; bit 18 in the status field
of Register aaaa will be set to indicate the instruction has failed to execute due to
improper formatting.
Chapter 8 - Special Instructions
Page 8-16
30598-526
• The Microcell must be located in the same rack as the processor.
• A minimum of 28 registers (maximum of 256) should be rack-addressed to the
Microcell.
• SPECIAL function 67 is intended to be used only for performing direct bus updates
of Microcell registers, and should not be applied to other modules; for other
modules, use the Immediate I/O Update instruction instead.
The following examples illustrate the use of the SPEC 67 function to update registers
in the Microcell. Note any of these registers can be read using standard (for example,
IF) instructions.
Example 1: Updating the FILE COMMAND Registers
Section 11.4 of the Microcell instruction bulletin (#30598-275) shows three examples
for downloading a file, appending an MCM file, and shutting down the MCM by
writing to the first 28 Microcell registers. Each example uses a ladder rung employing
a MATRIX statement to accomplish the register data transfers. Each of these
statements needs to be replaced by the SPECIAL function 67 statement format, with
the “PNTR” value being replaced by the “count” value of the new instruction.
The rung shown in Section 11.4.1, therefore, becomes:
SPEC
LET S0001 = S0031
067 ; 28
Example 2: Reading and Writing the BUS DATA Registers
Assume the first 156 system registers have been rack addressed to the Microcell.
Registers 29-156 are the BUS DATA registers, available for reading and writing
register values. Because these Microcell registers are automatically read into the
processor image table at the end of each scan, they can be monitored with the standard
instruction set.
To write the contents of (for example) registers 1001-1128 into bus data registers
(registers 29-156), use the SPECIAL function 67 instruction as follows:
SPEC
LET S0029 = S1001
067 ; 128
Note that if a regular LET or MATRIX statement was used instead to update registers
29 through 156, only the processor’s internal image table registers would be updated;
these registers would subsequently be overwritten when the corresponding Microcell
registers were automatically read during normal End-of-Scan updating.
Chapter 8 - Special Instructions
30598-526
Page 8-17
8.7 MISCELLANEOUS INSTRUCTIONS
Table 8-8 lists the various miscellaneous instructions available with the Model 450
processor.
Table 8-8: Miscellaneous Instructions
Instruction
RANDOM
SPEC #
23
Action Performed
Generates a random number. The number
preceding the SPECIAL function 23 (RANDOM)
box is used as the argument value for the
generator. The new IR will fall in the range 0 to
(IR-1).
NOTE: An argument value of 0 or 1 will return a
random number value of 0, while an argument
greater than 32,767 or less than 0 produces an
error.
SWAP16
11
Exchanges the high byte (9-16) and low byte (1-8)
of the IR. The IR must be an integer in the range
±32,767.
SWAP32
12
Copies the high word (17-32) of the IR to the low
word (1-16) of the IR. The high word is sign
extended, either all “0”s (if bit 16 is a “0”), or all
“1”s (if bit 16 is a “1”).
17
Identifies the number type of the intermediate
result. The IR becomes a value from 0 to 14,
according to standards applied to the Motorola
68010 microprocessor and 68881 math
coprocessor as shown below:
0
Positive normalized or de-normalized
1
Positive not-a-number
2
Positive infinity
3
Unused
4
Positive zero
5-7 Unused
8
Negative normalized or
de-normalized
9
Negative not-a-number
10 Negative infinity
11 Integer zero
12 Negative zero
13 Negative integer
14 Positive integer
NUMTYP
Chapter 8 - Special Instructions
Page 8-18
30598-526
NOTES
Chapter 8 - Special Instructions
30598-526
9
Page 9-1
PID OPERATIONS
9.1 GENERAL INFORMATION
NOTE
A more complete discussion of the equations and terminologies used
in this chapter can be found in the PID Closed Loop Control Instruction
Bulletin (#30598-301) or the Process Control Module Instruction
Bulletin (#30598-240).
Algorithms are available in the Model 450 processor for solving the following three
types of PID loops:
• Reverse-acting (PIDR)
• Direct-acting (PIDD)
• Manual (PIDM)
The number that precedes the SPECIAL function code number in the LET box (an odd
integer from 1 to 3981) is a pointer to a user-defined block of 18 storage registers.
9.2 REGISTER ALLOCATION
The block of 18 storage registers provides information needed by the Model 450 to
execute the PID algorithms, and must follow the format shown in Table 9-1.
The “L” prefix in Table 9-1 indicates the relative position within the 18-register block.
For example, if registers 51 through 68 are set aside for the PID algorithm registers,
“L1” would refer to register 51, “L5” would refer to register 55, and so on. The
boldface items in Table 9-1 are parameters used in equations.
Table 9-1: PID Register Allocation
(Page 1 of 2)
Register #
Purpose
L1, L2
Integral Summation [SUM(I)]. These two registers must be a floating-point
register.
L3
Value of the process variable used the last time the loop was updated
(PVn-1)
L4
Not used
L5
The output from the loop solution (OUTPUT)
L6
Value of the process variable used during the present loop update (PVn)
L7
The set point (SP)
Chapter 9 - PID Operations
Page 9-2
30598-526
Table 9-1: PID Register Allocation
(Page 2 of 2)
Register #
L8
Purpose
LOOP STATUS
Bit 2
1 if loop is not in manual
0 if loop is in manual
Bit 3
1 if loop is in automatic
0 if loop is not in automatic
Bit 10 1 if loop is direct-acting
0 if loop is reverse-acting
Bit 14 1 if high output limit is exceeded
0 if high output limit is not exceeded
Bit 15 1 if low output limit is exceeded
0 if low output limit is not exceeded
Bit 16 1 if low output limit is illegally set to be higher than the high
limit
L9, L10
Not used
L11
Proportional (gain) constant (Kp). This is a dimensionless number.
L12
Integral (reset) constant (KI) in repeats per minute
L13
Derivative (rate) constant (KD) in seconds
L14
Bias or offset (B) in %
L15
High output limit, in %
L16
Low output limit, in %
L17
Not used
L18
Sample interval (TS in milliseconds)
Programming Considerations
• The tuning parameter values of SP, Kp, KI, KD, and B are entered with
programming equipment or in the user program.
• Registers L5, L6, L7, L14, L15, and L16 are entered to reflect a percent of scale
from 0000 to 9999. The decimal point is implied as XX.XX. For example, an
OUTPUT of 50% is entered as 5000, a PROCESS VARIABLE value of 7475
represents 74.75% of full-scale, etc.
• Registers L11, L12, and L13 are entered in the range of 0 to 32,767 with the
decimal point implied as XXX.XX. For example, a gain of 1.00 is entered as 100, a
reset of 27 repeats per minute is entered as 2700, while a rate of 150 seconds is
entered as 15000.
• Register L18’s (sample interval) implied decimal point is XX.XXX. For example, a
sample interval of 200 milliseconds is entered as 200, while a sample interval of 10
seconds is entered as 10,000.
• The high and low output limits are entered in the same format as the tuning
parameters, as a percent of full-scale.
• The loop algorithm calculates SUM(I) and OUTPUT, and stores PVn-1 for the next
calculation. The user needs to input PVn and transfer the calculated OUTPUT to a
Chapter 9 - PID Operations
30598-526
Page 9-3
real-world analog output register. These manipulations typically occur through
ladder rungs.
• To ensure the integrity of the calculations, the Model 450 performs limit checks on
the variables loaded by the user. Valid ranges are defined as follows:
0 ≥ x ≥ 9999
for OUTPUT, PV, SP, Bias, and High and Low Output Limits
X≥0
for Kp, KI, and KD
X>0
for sample interval Ts
If any of these range limits are not observed, the PID algorithm is not executed and
bit 18 of the destination register (the register to the left of the equal (=) sign in the
PID rung) is set to flag the error. In addition, the processor sets bit 18 of the
out-of-range register to facilitate troubleshooting by identifying the source of the
illegal value.
• All registers in the user-defined PID register block must have addresses in the range
of 1 to 4000.
9.3 REVERSE-ACTING LOOP
The SPECIAL function 46 (PID REV) entry in a LET box calculates a reverse-acting
(PIDR) loop in the following sequence:
1.
K p • K I • T s • ( SP – PV n )
SUM ( I ) = -------------------------------------------------------------------- + SUM ( I )
10
6 • 10
2.
LET L1, L2 = SUM(I)
3.
K p • ( SP – PV n ) K p • K D • ( PV n – 1 – PV n ) B 
OUTPUT =  SUM ( I ) + ------------------------------------------+ ----------------------------------------------------------------- + --------- • 100
10, 000
T S • 1000
100
4. LET PVn-1 = PVn
5. CLEAR bit 10 of register 8 (reverse-acting flag)
6. If low output limit exceeds high output limit, set bit 16 of register 8 to flag this
illegal condition.
7. Check if output exceeds the high output limit. If YES, and KI ≠ 0, a back calculation
is performed on the integral sum.
IF OUTPUT > high output limit:
A. Set bit 14 of register 8.
B. LET L1 = high output limit - OUTPUT + SUM(I)
100
C. LET OUTPUT = high output limit
If OUTPUT < (high output limit + 1) reset bit 14 of register 8 to indicate that
high limit is not exceeded.
8. Check if output is below the low output limit. If YES, and KI ≠ 0, a back calculation
is performed on the integral sum.
Chapter 9 - PID Operations
Page 9-4
30598-526
If OUTPUT < low output limit:
A. Set bit 15 of register 8.
B. LET L1 = low output limit - OUTPUT + SUM(I)
100
C. LET OUTPUT = low output limit
If OUTPUT ≥ low output limit, reset bit 15 of register 8 to indicate that low limit
is not exceeded.
9. The final action in the Reverse-Acting Loop is to store the newly-calculated loop
OUTPUT value in L5 and in the SPECIAL 46 (PIDR) LET box register which is
just to the left of the equal (=) sign.
9.4 DIRECT-ACTING LOOP
The SPECIAL 47 (PIDD) LET box calculates a direct-acting (PIDD) loop. The
algorithm is identical to the one used for the reverse-acting loop, except that the sign
for the mathematical differences between SP and PV terms is reversed.
The change in sign results in changes to the first, third, and fifth steps of the sequence
in Section 9.3. All other steps are the same as shown in Section 9.3.
As with the PIDR, the newly-calculated loop OUTPUT value is stored both in register
L5 and in the register to the left of the equal (=) sign in the SPECIAL 47 (PIDD) LET
box.
1.
K p • K I • T s • ( PV n – SP )
SUM ( I ) = -------------------------------------------------------------------- + SUM ( I )
10
6 • 10
2. Same as PIDR
3.
K p • ( PV n – SP ) K p • K D • ( PV n – PV n – 1 ) B 
OUTPUT =  SUM ( I ) + ------------------------------------------- + ----------------------------------------------------------------- + --------- • 100
10, 000
T S • 1000
100
4. Same as PIDR
5. Set bit 10 of register 8 (direct-acting flag)
6. Same as PIDR
7. Same as PIDR
8. Same as PIDR
9. Same as PIDR
10. Same as PIDR
11. Same as PIDR
9.5 MANUAL LOOP
The SPECIAL 48 (PIDM) instruction in a LET box causes the PID loop to be
manually (PIDM) controlled. The number preceding 48 in the LET box must point to
the same block of 18 registers as did the PIDR or PIDD loop algorithm.
The PIDM loop is executed as follows to facilitate a bumpless transfer to AUTO:
Chapter 9 - PID Operations
30598-526
Page 9-5
1. LET SP = PVn (sets the setpoint equal to the process variable)
2. LET B = OUTPUT (sets bias equal to the loop output)
3. LET SUM(I) = 0 (zeroes out the integral summation)
4. LET PVn-1 = PVn
5. The final action in the Manual-Acting Loop is to transfer the OUTPUT value in L5
to the SPECIAL (PIDM) instruction 48 LET box register which is just to the left of
the equal (=) sign.
NOTE
When adjusting the OUTPUT while under manual control, the user must
make the adjustments to the L5 output register in the 18-register block and
not directly to the register assigned to the external output. See Example 1 in
Section 9.7.
9.6 LEAD/LAG FUNCTIONS
Note that this function is also described in detail in the SY/MAX Class 8040 Type
PCM110 Process Control Module Instruction Bulletin (#30598-240). You may want to
refer to that manual for additional information.
The SPECIAL instruction 49 (LED/LAG) in a LET box performs a LEAD/LAG
calculation on the process variable (PV). The number preceding 49 in the LET box is
used as a pointer to a user-defined block of 7 registers. This number must be an integer
from 1 to 4993.
In the following table, a “Z” prefix is used to denote the 7 storage registers that are
used in the LEAD/LAG calculations. Characters in boldface represent variables used
in the equations that follow.
The LEAD/LAG algorithm calculates Qn based on user-entered values for Ts, Td, and
Ti. Since these values are stored in integer registers, they contain an implied decimal
point that must be entered in the following format:
For Td and Ti
For Ts
XXX.XX
XX.XXX
Table 9-2: LEAD/LAG Register Allocation
Register Number
Function
Z1
The resulting calculation for this lead/lag update (Qn)
Z2
The process variable used in this update (PVn)
Z3
The sample interval in milliseconds (Ts)
Z4
The lead time constant in hundredths of a second (Td)
Z5
The lag time constant in hundredths of a second (Ti)
Z6
The resulting calculation from the previous update (Qn-1)
Z7
The process variable from the previous update (PVn-1)
Chapter 9 - PID Operations
Page 9-6
30598-526
Other Considerations
• The process variable (PV) must be loaded into register Z2.
• The calculated value of Qn must be transferred into the PIDD or PIDR loop register
L6 (the process variable register).
• The LEAD/LAG algorithm retains Qn-1 and PVn-1 for the next calculation.
• To ensure the integrity of the calculations, the processor performs limit checks on
the variables loaded by the user. Valid ranges are defined as follows:
0 ≤ X ≤ 9999
for PV
X≥0
for Td and Ti
X>0
for sample interval Ts
If any of these range limits are not observed, theLEAD/LAG algorithm is not executed
and bit 18 of the destination register (the register to the left of the equal (=) sign in the
LEAD/LAG rung) is set to flag the error. In addition, the processor sets bit 18 of the
out-of-range register to facilitate troubleshooting by identifying the source of the
illegal value.
See Example 2 in Section 9.7 for typical ladder rungs required.
The SPECIAL instruction 49 in a LET box causes the following steps to occur:
1.
Qn
Ti Qn – 1
PV n
T d PV n – 1
Ts
Td
--------- • -------------- +  ------------ + --------- • ----------- –  --------- • ------------------
100 100
1000 100
100
100
100
= ------------------------------------------------------------------------------------------------------------------------------------------ • 100
Ts
Ti
------------ + --------1000 100
2. LET PVn-1 = PVn (prepare for next calculation)
3. LET Qn-1 = Qn (prepare for next calculation)
Chapter 9 - PID Operations
30598-526
Page 9-7
NOTE
Since the LEAD/LAG algorithm performs a calculation, it is governed by the same
rules as any calculation. If the result of the calculation cannot be represented as
a 16-bit integer (-32767 to 32767), then numerical overflow errors (refer to
Section 7.11, “Overflow Errors”) will occur. When this happens, the LEAD/LAG
calculation is not executed.
Overflow may occur the very first time the LEAD/LAG function is calculated
whenever the lag constant (Z5) is set to ‘0000’. As a strictly lead calculation, the
algorithm simplifies as follows:
10 • T d
Q n = PV n + ------------------ • ( PV n – PV n – 1 )
Ts
From this relationship it can be shown that if (Td/Ts) is greater than or equal to 1,
then for PVn - PVn -1 values greater than 2978 (approximately 29.78 percent of
scale) numerical overflow will occur. The first time the calculation is performed,
PVn -1 is equal to ‘0000’. It is also possible for signals with a low signal-to-noise
ratio for overflow to occur periodically during normal ladder scanning.
The LEAD/LAG algorithm in lead only mode is a differentiator. A differentiator is
designed to amplify signal, with noise included. The overflow condition can be
detected and appropriate application action can be taken. Assume the following
LEAD/LAG rung:
LED/LAG
LET
S0500 = 0201
0049
If overflow occurs in this ladder rung, overflow bit 0500-18 will become energized,
and the LEAD/LAG algorithm will not execute. This overflow bit can be used by an
application rung to compensate for the overflow condition.
0500
LET
S0207 = S202
-18
9.7 APPLICATION CONSIDERATIONS AND EXAMPLES
While the loop algorithms in this section are the same as shown in Instruction
Bulletins #30598-301 and #30598-240, certain differences exist in the way the
processor executes and implements the results. For example, although the loop update
time is user-specified, the processor scan time and I/O update time must be fast enough
to accommodate the loop time.
The concept of throughput must be understood, and the SPECIAL instruction set for
the processor (see Chapter 8 of this instruction bulletin) must be read and understood
as well. A working knowledge of PID operation and a good grasp of the terminology
contained in Instruction Bulletins #30598-301 and #30598-240 is recommended
before proceeding with this chapter.
The instruction bulletin, SY/MAX Class 8010 PID Closed Loop Control Using the
SY/MAX Model 300 Programmable Controller, describes the use of a PID control
program that can be loaded into a Model 300 or 500 processor via cartridge tape. The
discussions of the PID control equation in Chapters 2 and 3 of that bulletin should be
Chapter 9 - PID Operations
Page 9-8
30598-526
compared to the algorithms for PIDD and PIDR in this instruction bulletin; they are
identical except for data on sample interval.
Note also the similarities between the register usage table in Section 3.2 of instruction
bulletin #30598-301 and the usage in the Model 450. Loop number, alarm status, and
alarm acknowledge registers are not used in the Model 450, but the loop status does
use several bits. The PVn-1, integral sum Most Significant Digit and integral sum Least
Significant Digit registers also differ from instruction bulletin #30598-301.
Instruction Bulletin #30598-240, SY/MAX Class 8040 Type PCM110 Process Control
Module, describes the PID algorithm available in the firmware of the PCM. The PID
control equation in Figure 8.2 of that instruction bulletin should be compared to the
PIDD and PIDR algorithms in this processor bulletin. Note that the PID algorithm A in
the PCM bulletin is the same one used for the Model 450.
The register usage table in the PCM bulletin should be compared to the usage of the
Model 450. Register differences exist because the PCM, being a dedicated closed-loop
controller, has many features not found in the Model 450. References to alarm status,
remote setpoint, deadband, etc., as well as listings beyond loop register 15, do not
apply to the algorithm used by the Model 450 (although applying a LEAD/LAG
function to the process variable does exist in the form of a SPECIAL instruction 49
LET box). The following examples show how some of these special functions are
utilized.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
The following examples are intended for use only as guidelines
when implementing the algorithms. It is the user’s responsibility
to understand these examples before incorporating these or any
other rungs into a working program.
Failure to observe this precaution can cause equipment damage or
personal injury.
Example 1: Reverse-Acting Single PID Loop (PIDR Loop)
Givens:
• The setpoint (SP) and tuning (Kp, KI, KD, and B) parameters are already set.
• The process variable input is in register 513.
• The process variable output is in register 517.
• The 18-register PID definition register block consists of registers 51-68.
• Reverse-acting PID control will be applied based on a 200-ms loop update time.
• The loop calculations must be performed at 200-millisecond intervals. For this
example, the necessary repeatability will be achieved with a timed interrupt
subroutine. Note the use of timed interrupt precludes RUN-mode programming. If
RUN-mode programming must be perserved, some other technique (such as using
register 8166 to regulate repeatability) must be used to ensure execution based on
the 200-millisecond sample interval time.
• If the loop is not in AUTO, loop control will default to MANUAL.
Chapter 9 - PID Operations
30598-526
Page 9-9
Rungs Needed:
1. TIMED INTERRUPT RUNG - The following rung must be the very first rung in
the program if a timed interrupt subroutine is used. It allows the main program to
call the subroutine containing the PID algorithm at specified intervals. In this
example, the subroutine is called every 200 milliseconds with a tolerance of 15
milliseconds (see Chapter 6). Note that use of the timed interrupt subroutines does
not allow for RUN-mode programming.
TLET
S8165 = 6;80
2. SAMPLE INTERVAL RUNG - The following rung establishes the sample interval
in milliseconds in register 68 (L18). The interval in this example is 200
milliseconds; this value must agree with the value in rung 1, and represents the
frequency with which the routine must be executed.
LET
S68 = 200
3. HIGH OUTPUT LIMIT RUNG - The following rung programs the high output limit
into register 65 (L15). In this example, the maximum high limit of 9999 is
programmed.
LET
S65 = 9999
4. LOW OUTPUT LIMIT RUNG - The following rung programs the low output limit
into register 66 (L16). In this example, the minimum low limit of 0000 is
programmed.
LET
S66 = 0000
The mainline user program exists here, between Rung
4 above and Rung A below.
A. SUBROUTINE AREA RUNG - The following rung appears only once in any
program, and serves to mark the memory area which holds all subroutines.
MARK ST.SUB
B. START SUBROUTINE RUNG - The following rung marks the point at which
the timed interrupt subroutine begins.
LET
S68 = 200
Chapter 9 - PID Operations
Page 9-10
30598-526
C. COPY PV RUNG - The following rung copies the process variable from the
external input register (513 in this example) into the loop process variable
register (56 in this example, defined as L6 in the register block).
LET
S56 = S513
D. EXECUTE PIDM CALCULATION RUNG - The following rung begins PIDM
calculations if bit 2 in register 58 has been reset; if bit 2 = 0, then loop is in
MANUAL. Register 51 is the pointer that both points to the register block 51-68
and also defines register 51 as L1, 52 as L2, and so on. Register 517 is this
example’s external output register, where the calculated output is placed.
58
PIDM
LET
S517 = 51
48
02
E. EXECUTE PIDR CALCULATION RUNG - The following rung begins PIDR
calculations if bits 2 and 3 in register 58 have been set. These two bits
correspond to the “mode status” bits previously described. Bit 2 set to “1”
indicates the loop is NOT in manual, while bit 3 set to “1” indicates the loop is
in the AUTO mode. Again, register 51 is the pointer that both points to the
register block 51-68 and also defines register 51 as L1, 52 as L2, and so on.
Register 517 is this example’s external output register where the calculated
output is placed. To change this loop to a PIDD (direct) loop, you need only
change SPECIAL instruction 46 to 47 in the following rung:
58
58
PIDD
LET
03
S517 = 51
46
02
F. RETURN FROM SUBROUTINE RUNG - The following rung identifies the
end of the timed interrupt subroutine.
RTN 8190
Programming Considerations for Example 1
• The execution time of the timed interrupt subroutine should be kept as short as
possible. The rungs that establish the loop initialization constants (for sample
interval, high output limit and low output limit—rungs 2, 3 and 4 in Example 1) are
programmed in the mainline area of the ladder program.
• Rung C in the subroutine (which transfers the process variable into register L6) is
executed immediately before the PID rungs (D and E) so that the most recent input
update is used in the PID computations.
• Bit 2 of register 58 controls whether the loop is under manual or automatic control.
In Example 1, the loop can be disabled (no PID computations performed) if bit 2 of
register 58 is equal to 1 (loop not in MANUAL) and bit 3 of register 58 is equal to 0
(loop not in AUTOMATIC).
• Rungs D and E can be programmed in any order.
• The OUTPUT for rungs D and E also exists in register 55 (L5). Programming the
Chapter 9 - PID Operations
30598-526
Page 9-11
external output register 517 avoids programming the additional rung: LET S517 =
S55.
• If the loop is executed in MANUAL (bit 2 of register 58 = 0), the output must be
adjusted in register 55, not in register 517. For example, to set the output to 50% of
full-scale range, the value 5000 is entered into register 55. When the processor
executes rung D, the contents of register 55 are transferred into register 517. If 5000
had been entered in register 517, it would have been overwritten by the current
contents of S55 in the transfer operation.
• The worst-case execution time for the block of rungs within the timed interrupt
subroutine is approximately 1 millisecond.
• There is no absolute limit to the number of PID loops that the processor can
execute. Practical limitations for a given system are a function of the number of
available registers, system throughput, and the user’s ability to manage multiple
loops. Additional PID loops can be executed by either adding the necessary blocks
of rungs into the MARK ST. SUB area or by multiplexing the loop algorithm by
changing the pointer from a constant to a variable and the output register from a
single address to a matrix. The first method is simple; the second requires
experience in advanced programming.
• System throughput decreases for every PID loop added to the program. The
interrupt rate must be infrequent enough to allow the processor to scan the
remainder of the program in a reasonable amount of time for the application.
• If the PID algorithm fails to execute as expected, check to see if bit 18 of register
517 is set to indicate an out-of-range condition. If set, monitor the other registers in
the block to determine which register is out of range, as indicated by bit 18 of the
offending register.
• If the execution time of the timed interrupt subroutine exceeds the interrupt rate,
ERROR 29100 is generated and the processor halts.
• If the interrupt tolerance is too restrictive, ERROR 29102 is generated and the
processor halts.
Example 2: LEAD/LAG Function Used with Example 1 Program
NOTE
The Process Control Module Instruction Bulletin (#30598-240)
contains additional information on the LEAD/LAG function.
Assume the same conditions exist as in Example 1 except that the LEAD/LAG
function is to be applied. Additional given conditions for the LEAD/LAG portion of
the program are therefore required.
Givens:
• The process variable exists in register 513.
• Registers 71-77 (Z1-Z7) make up the block that defines the LEAD/LAG function.
• The sample interval Ts is preset in register 73 (Z3).
Chapter 9 - PID Operations
Page 9-12
30598-526
NOTE
The user must enter the LEAD/LAG time constants (TD and TI) in
registers 74 (Z4) and 75 (Z5) respectively.
The following rungs must appear in the timed interrupt subroutine and replace Rung C
as shown in Example 1.
LET
S73 = 200
This rung presets the sample interval (in
milliseconds) into register 73 (Z3). This number
must correspond to the timed interrupt interval
specified in rung 1 and also match the interval
specified for the PIDR or PIDD algorithm.
LET
S72 = S513
This rung loads the process variable into register
72 (Z2) for use in the LEAD/LAG calculation.
LED/LAG
LET
Chapter 9 - PID Operations
S56 = 71
49
This rung performs the LEAD/LAG function on
the process variable currently loaded in register
72 (Z2). The number 71 is the pointer that points
at registers 71-77. The calculated Qn is placed in
register 56 for use in the upcoming PIDM or
PIDR calculations.
30598-526
10
10.1
Page 10-1
ASCII COMMUNICATIONS (Input and Output)
ASCII INPUT
NOTE
Since ASCII input may not be assigned to the Ethernet port
(Channel 3), this section applies only to ports 1 and 2 (PRGMR and
COMM ports).
The Model 450 uses an enhanced PRINT rung format to allow inputting of
ASCII-coded data. Termination of the ASCII input string can be done either by
character count, character delimiter, or both.
10.1.1 Description/Initiation
The ASCII input programming format is similar to that of ASCII output. A special
register address (S8006) is inserted as the first register in the PRINT statement and is
used to identify the mode. Subsequent entries in the PRINT statement further define
the function. The ASCII input rung must be programmed with all entries as shown in
Figure 10-1.
BAUD
TPRINTY
X
STAT
REG
REG
REG
SAAAA S8006 SBBBB SCCCC
ALPHA
DD
Figure 10-1 ASCII Input Rung
Each rung parameter in Figure 10-1 is explained as follows:
LOGIC
Y
X
SAAAA
S8006
Upon becoming TRUE, the port specified by Y is enabled to
accept ASCII input characters. When FALSE, the port
ignores the ASCII input and reverts to SY/MAX protocol
communication, unless a complete ASCII input string was
not received when previously TRUE. See Section 10.1.3.
Y is the CHANNEL that receives the input, being either 1
(PRGMR port) or 2 (COMM port). The serial word structure
for channel 1 is defined in register 8099. The structure for
channel 2 is in register 8100. See Figure 3.
X is the BAUD RATE for the selected channel (Y). See
Figure 5 for available baud rates.
SAAAA is the STATUS REGISTER assigned to this
communication rung. DO NOT use this user-specified
register for any other purpose in the program. Error codes
that may appear in the status register are listed in Section
10.1.5.
S8006 is not actually a register, but is the COMMAND that
defines the box as an ASCII input box.
Chapter 10 - ASCII Communications
Page 10-2
30598-526
SBBBB
SCCCC
DD
SBBBB identifies the STARTING REGISTER for storing
the data block. The block can hold no more than 256 ASCII
characters. If more than 256 characters are input, an error is
sent to the status register and ERROR 19 is posted. This
register is the start address, not a pointer to a start address.
Each register in the block will contain a single character
(stored in the least significant byte).
SCCCC identifies the register whose contents specify the
number or characters to be input. When this number of
ASCII characters has been received, the ASCII input string is
terminated and bit 16 of the associated status register is set
ON.
DD is the contents of the ALPHA box that identifies the
ASCII character specified by the user as the block terminator
(delimiter). The desired terminator character should be
loaded, followed by a space (space bar) character to shift the
character into position. When this character has been
received, the ASCII input string is terminated and bit 16 of
the associated status register is set ON.
CAUTION
POSSIBLE DATA LOSS
At the end of every block of received data, the Model 450
appends a null (00) character to mark the end of the block. Due
to this feature, the user MUST reserve one additional register
beyond the maximum character count for the block size. If
insufficient registers are reserved, incoming data may
overwrite register data that is used for other purposes in the
program.
Failure to observe this precaution can cause equipment damage or
personal injury.
NOTES
• If no characters are entered for DD in the ALPHA box, the default
block terminator is a space (20H).
• Setting the contents of SCCCC to zero defaults to the maximum
input block size of 256 characters.
• If both SCCCC and DD are specified, the ASCII input block will
stop upon reaching the first condition to be satisfied.
10.1.2 Port Configuration
Both the PRGMR and COMM ports of the Model 450 are configured as RS-422 ports.
The pinout for these ports is shown in Figure 10-2.
Chapter 10 - ASCII Communications
Page 10-3
30598-526
5
SHIELD
+ 5VDC
9
SIGNAL COMMON
SIGNAL COMMON
4
8
DATA IN +
3
DATA IN -
7
DATA OUT +
2
6
+ 5VDC
DATA OUT -
1
Figure 10-2 PRGMR and COMM Port Pinout
NOTE
RTS and CTS hardware handshaking signals are not supported.
Pins 5, 6, 7 and 8 are used for +5VDC and signal commons.
When configuring each of the PRGMR and COMM ports for ASCII input, registers
8099 (for PRGMR) and 8100 (for COMM) are used. Figure 10-3 illustrates what each
of the bits in these two registers is used for and how to configure the port for the
desired word structure.
15 CNTL-C
Flag
(See Sect.
10.1.4)
1 = Received
0 = Not Rec’d
16 Clear Queued
Buffers
(See Section 10.1.4)
1 = Active
0 = Inactive
16
13 Activate Periodic
DLE/ENQ Stream
(ASCII Output)
1 = Active
0 = Suppressed
(See Section 13.2)
14 Reset Bit 8 for 8-bit
word length
(ASCII Output)
1 = Reset
0 = Unaltered
(See Section 10.2.1)
14
15
13
12
11
REGISTER 8099 PRGMR Port
REGISTER 8100 COMM Port
10
9
8
6
7
5
4
1 = Enabled
0 = Disabled
(See Section 10.2.5)
9 and 10 Stop Bits
10
9
# of Stop Bits
0
0
1
1
** Invalid
ASCII and SY/MAX protocol
word length
7 and 8 Parity Bits
1 =Yes
0 = No
2
1-4Baud Rate
(See Table 10-2)
11 XON/XOFF Select:
(ASCII Output)
12 Store Null
Characters
3
5 and 6 Word Length Bits
8
7
Parity Type
6
5
0
0
Even
0
0
8
0
1
Odd
0
1
7*
1
0
None
1
0
6**
1
1
None
1
1
None
*
Length in Bits
Invalid SY/MAX protocol word length
Figure 10-3 PRGMR and COMM Port Configuration Registers
Chapter 10 - ASCII Communications
Page 10-4
30598-526
10.1.3 Operation
When the logic preceding the ASCII input box transitions from FALSE to TRUE, the
specified port is enabled to receive ASCII, queueing up an input buffer. Once enabled,
the port remains enabled to accept an ASCII input string even if the logic preceding the
ASCII input box becomes FALSE.
Incoming characters are then stored in a communications port buffer until a complete
ASCII string has been received. As soon as the final character is received, the port
buffer ignores future ASCII characters. These characters are lost unless another port
buffer has been queued to accept them. A total of 11 buffers exists for both ports. Of
these, up to 9 can be allocated by the processor to a single port. This makes it possible
to anticipate multiple ASCII input strings by enabling multiple ASCII input rungs, or
even by repeatedly transitioning the logic of a single rung, since a new buffer is
allocated (queued) upon every transition.
The port buffer is then read by the processor during its end-of-scan communications
port servicing and the ASCII characters are moved into the registers specified in the
ASCII input rung.
Bits in the status register reflect the above situations; bit 22 is set to “1” when the input
logic is TRUE, bit 17 is set when a port buffer is enabled for input, and bit 16 is set
when a complete ASCII input string has been received and processed by the CPU.
Table 10-1 shows which status bits are set based on the ASCII input rung’s current
logical state and whether a port buffer is queued for ASCII input from a previous
FALSE-to-TRUE logic transition.
Buffers become “linked” with the ASCII input rungs in the order in which they are
executed TRUE, unless all 9 buffers have been allocated. In this case, even though
status register bit 22 is set, bit 17 is not. This indicates that all buffers are queued. A
buffer is not freed up until a complete ASCII string has been received and the buffer
has been read by the Model 450 during its end-of-scan activities.
Table 10-1: Bit Status vs. Logic and Buffer States
Buffer
Queued
Port ASCII
Input Status
FALSE
No
TRUE
Logic
Resulting Bit Status
Bit 16
Bit 17
Bit 22
Input Disabled
0
0
0
Yes
Input Enabled
0
1
1
TRUE
No
Input Complete
1
1
1
FALSE
Yes
Input Enabled
0
0*
0
TRUE
No
(all previously
allocated)
Input Enabled
X
(don’t care)
0
1
* When logic is FALSE, the status bits are cleared but the buffer remains in queue.
Chapter 10 - ASCII Communications
Page 10-5
30598-526
NOTE
If all 9 buffers are simultaneously used for ASCII input while priority
SY/MAX communications (READ, WRITE, ALARM) are transmitting
out the other port, port 2 (COMM) must be used for ASCII input; port 1
(PRGMR) is used for SY/MAX communications.
Table 10-2: Baud Rate and Bit Pattern
Baud Rate Code
Baud Rate
Binary Bits 4321
Decimal
0000
0
50
0001
1
110
0010
2
300
0011
3
1200
0100
4
2400
0101
5
4800
0110
6
9600
0111
7
19.2K
10.1.4 Application Considerations
• ASCII storage registers contain the binary code for the ASCII character, not the
character itself. For example, the ASCII character “0” is represented as “48”
(decimal), where an ASCII “A” is represented as “65” (decimal).
• One ASCII character is stored per register (in the least significant byte).
• ASCII input information does not appear in the storage registers until a complete
block, defined by the block size or the terminator, has been received.
• Null (00) characters may either be disregarded or stored as valid characters. See bit
12 in Figure 10-3 on page 10-3.
• If null characters are disregarded, the end of the input register block is defined either
by the block terminator or by the first register to contain a null character.
• The following description applies to bits 15 and 16 of port attribute registers 8099
and 8100.
Bit 16 - When set, aborts any pending ASCII input instructions and clears any port
buffers queued for an ASCII input string. This is a means of error recovery when
characters in an ASCII input string are lost or garbled. Setting bit 16 to “1” through
a coil in the ladder program gives the user a means of purging the input buffers in
preparation for a new ASCII string.
Chapter 10 - ASCII Communications
Page 10-6
30598-526
NOTE
In order to work properly, bit 16 MUST be set via a coil in the ladder
program and NOT by any other means, such as a LET or via DATA
ENTER, COMMs, etc.
Bit 15 - acts as a flag that recognizes an ASCII input BREAK command. Upon
receiving a CTRL-C (03H), bit 15 latches ON. For example, when programmed as a
contact to control bit 16, a CTRL-C character issued from the ASCII output device
purges any queued ASCII input buffers.
• Both bits 15 and 16 of the port attribute register are reset to “0” upon power-up.
• Upon a power cycle, port 1 (PRGMR) resets to 9600 baud, 8-bit word, even parity,
with one stop bit in order to be compatible with the SY/MAX protocol. Port 2
(COMM) retains any changes made to its attributes.
• DEL/CLR ALL does not cause port attributes to reset to the default values unless
prompted by a “CLR MEMORY NEEDED”.
• Because valid ASCII characters are defined as seven bits long, the Model 450 (when
configured to receive an eight-bit ASCII word) masks off the state of bit 8 in the
incoming character.
• Halting the Model 450 or setting bit 16 of register 8099 or 8100 to “1”, while
awaiting an ASCII input string, clears any queued port buffers, halts the ASCII
input instruction, and generates ERROR 17 in the status register.
• The ASCII input function only operates properly when the device that is outputting
the ASCII characters is directly connected to a Model 650 port. ASCII sent over the
network is not accepted by the ASCII input function.
• When a port is queued for ASCII input while FORCING is active, the “ASCII port”
is assumed to be dedicated to the ASCII input function. If the cable is removed from
the other communication port, no DLE/ENQ characters are transmitted out the
ASCII port to inquire if a programming device is present.
• If a port's word structure is altered, it remains altered even after the port reverts to
SY/MAX protocol. SY/MAX protocol requires an 8-bit word with even parity, and
one stop bit, to operate correctly.
• The ASCII input data block (of up to 256 characters) must be stored in register
addresses 4000 or less.
• The status register used in the ASCII input rung MUST have a register address of
4000 or less.
10.1.5 Error Codes
The error codes shown in Table 10-3 apply to the ASCII input operation and may
appear in the status register of the ASCII input rung (“SAAAA”, in Figure 10-1 on
page 10-1).
Chapter 10 - ASCII Communications
30598-526
Page 10-7
Table 10-3: ASCII Input Error Codes
Error Number
10.2
Description
11
Receiver overflow. The Model 450 is unable to handle incoming
characters fast enough, due to the servicing of other interrupts.
13
Parity error
15
Framing error. Typically due to baud rate or word structure
problems.
17
Input was terminated before a complete ASCII string was
received. Results from either the CPU going to HALT or bit 16 of
register 8099 or 8100 being set. If bit 16 is set, buffers queued for
ASCII input are cleared.
19
Buffer overflow. The 256-character buffer was filled before the
terminating character was received.
ASCII OUTPUT
The capability for outputting ASCII characters via PRINT statements exists for both
the PRGMR and COMM ports on the Model 450 (Ports 1 and 2, respectively). Refer to
the appropriate programmer instruction bulletin (#30598-167, 30598-174 or
30598-717) for general information on programming PRINT rungs.
NOTE
Since ASCII output can be assigned only to ports 1 and 2 (PRGMR
and COMM ports), the baud rate and ASCII output considerations do
not affect port 3 (ETHERNET).
10.2.1 Standard ASCII Format
The standard ASCII characters are output as RS-422 signals (see Figure 10-2 on page
10-3 for port pinout) defaulting to 8-bit words with even parity and 1 stop bit,
transmitted at 9600 baud.
If the receiving device does not automatically mask off bit 8 (typically indicated when
half the characters are received correctly, the other half garbled), set bit 14 of register
8100 for port 2 (register 8099 for port 1) to 1 to cause the processor to perform the
mask. Another alternative to match output default settings is to set up the receiving
device for a 7-bit word with odd parity and 2 stop bits. Other settings may be
accommodated by adjusting registers 8099 or 8100; refer to Figure 10-3 on page 10-3.
Standard PRINT statements allow outputting fixed ASCII characters (represented by
ALPHA entries in the PRINT rung) and register contents (represented by REG entries
in the PRINT rung). This allows an English-language message to be augmented with
variable register data. Each REG entry will result in 6 ASCII characters being
transmitted, representing up to 5 decimal places plus sign (if negative) or space (if
Chapter 10 - ASCII Communications
Page 10-8
30598-526
positive). Leading zeros will automatically be transmitted as spaces. Each standard
ASCII PRINT statement automatically appends a <CR> and <LF> to the ASCII string,
unless suppressed with a semicolon (;) in the last ALPHA position.
10.2.2 Raw Binary ASCII Format
While the standard ASCII format will handle the majority of ASCII output
applications, some of the special control codes (ESC, DLE, for example) cannot be
accommodated by the ALPHA entries. Any 7-bit ASCII code (0 through 127) can be
output using the Raw Binary ASCII format.
To invoke the Raw Binary format, use the same PRINT statement as for the standard
format, with two exceptions:
• REG S8004 must be the first element following STAT in the horizontal PRINT box
(see Figure 10-4).
• All subsequent elements of the box should be REG, not ALPHA.
To output the ASCII codes, store the desired 8-bit patterns in the registers specified by
the REG elements. The data in each register will be treated as a pair of 8-bit characters
(low-byte bits 1-8, high byte bits 9-16) with each byte ranging from 0 through 127.
The high-byte character is transmitted first, followed by the low-byte character. If the
register consists of a single byte (0-127), then that byte, representing a single ASCII
character, is transmitted.
EXAMPLE:
This example demonstrates the use of register 8004 in a PRINT rung to set the
Model 450's “raw binary” output format.
10
TPRINT2
BAUD
STAT
REG
REG
REG
00300
S0025
S8004
S0501
S0502
-08
Figure 10-4 Raw Binary Example
To output a carriage return (CR), a line feed (LF), and the number “1”, three bytes are
required. This requires assigning two registers--the first register contains the <CR> in
the high byte and the <LF> in the low byte. The second register's low byte contains the
number “1”. Registers 501 and 502 are used in this example to contain the ASCII
codes which can be found in Table 10-4 on page 10-11.
A suggestion on how to store these values is to multiply the desired high byte of
register 501 (the <CR> is ASCII 13) by 256, then add the low byte (the <LF>, ASCII
10) to the product. This yields 3338, which is stored in register 501. This leaves the
single byte (the number “1”); store its ASCII value (49) directly in the low byte of
register 502.
When the contact 10-08 is closed in the sample rung, a <CR> followed by a <LF>
followed by the number “1” will be sent out of port 2 at 300 baud.
Chapter 10 - ASCII Communications
30598-526
Page 10-9
APPLICATION CONSIDERATIONS
• Default format is standard ASCII for each new PRINT rung.
• Multiple formats may be used in the same rung by entering a REG value of S8001
(for standard ASCII) or S8004 (for Raw Binary ASCII).
• Raw binary format character entries should be REG elements, not ALPHA.
• The processor automatically appends a <CR> and <LF> at the end of any standard
ASCII PRINT statement unless suppressed by a semicolon; no characters are
appended to a Raw Binary ASCII PRINT statement.
• Data is transmitted as a 7-bit ASCII word with odd parity and 2 stop bits, except for
Raw Binary format, which is an 8-bit data word with even parity and 1 stop bit.
• Baud rates up to 19.2K are allowed, and BAUD RATE should be specified in each
PRINT rung.
• Each PRINT rung must have a unique status register.
• If a PRINT rung is programmed to transmit no data, a single NULL (00 hex) will be
transmitted.
10.2.3 Miscellaneous ASCII Formats
Up to this point, the REG elements in a PRINT box could be output as a standard
decimal value (5 digits plus sign in the standard ASCII format) or as an ASCII
character representation (in the “raw binary” ASCII format). It is also possible to print
out the register contents in two other formats: a 16-digit binary representation of the
register bit pattern (all characters either “0” or “1”) or a 4-digit hexadecimal
representation (characters 0 through F).
To invoke the 16-digit binary representation, have REG S8002 be the first element
following STAT in the horizontal PRINT box; for the 4-digit hexadecimal
representation, use REG S8003 as the first element. All subsequent REG elements of
the PRINT box will be output in the respective format.
NOTE
To cause a PRINT box format to revert to the standard ASCII default
of 5 digits plus sign, replace S8002 or S8003 with S8001.
10.2.4 Repeated Character Strings
For applications which require outputting the same character numerous times, another
special format is available. By having REG S8005 as the first element following STAT
in the horizontal PRINT box, subsequent REG elements will be interpreted so that the
low byte represents the ASCII character (0-127) and the high byte the number of times
this character is to be repeated (up to a maximum of 192). If the high byte = 0 or is
greater than 192, no data is sent.
10.2.5 XON/XOFF Handshaking
For all PRINT formats, the Model 450 can be enabled to support XON/XOFF software
handshaking while outputting ASCII. Setting bit 11 of register 8099 (PRGMR port) or
8100 (COMM port) to 1 allows a receiving device (a printer, for example) attached to
Chapter 10 - ASCII Communications
Page 10-10
30598-526
the respective port to instruct the Model 450 to stop sending ASCII. The device does
this by sending a “DC3” (13H or CTRL-S) to the Model 450. When the receiving
device is again ready to accept ASCII, it sends a “DC1” (11H or CTRL-Q) to the
Model 450.
NOTE
When XON/XOFF is active while SY/MAX communications (READ,
WRITE, ALARM) are being transmitted out the other port, port 2
(COMM) must be used for the ASCII function; port 1 (PRGMR) or
port 3 (Ethernet) must therefore be used for the SY/MAX protocol
device.
Chapter 10 - ASCII Communications
Page 10-11
30598-526
10.3
ASCII - HEX - DECIMAL CONVERSION
Table 10-4 shows ASCII characters and their hexadecimal and decimal equivalents.
Table 10-4: ASCII-Hex-Decimal Conversion Table
ASCII
Character
NUL
VALUE
Decimal (Hex)
00
(0000H)
ASCII
Character
Space
VALUE
Decimal (Hex)
32
(0020H)
ASCII
Character
@
VALUE
Decimal (Hex)
64
(0040H)
ASCII
Character
‘
VALUE
Decimal (Hex)
96
(0060H)
SOH
01
(0001H)
!
33
(0021H)
A
65
(0041H)
a
97
(0061H)
STX
02
(0002H)
“
34
(0022H)
B
66
(0042H)
b
98
(0062H)
(0063H)
ETX
03
(0003H)
#
35
(0023H)
C
67
(0043H)
c
99
EOT
04
(0004H)
$
36
(0024H)
D
68
(0044H)
d
100 (0064H)
ENQ
05
(0005H)
%
37
(0025H)
E
69
(0045H)
e
101 (0065H)
ACK
06
(0006H)
&
38
(0026H)
F
70
(0046H)
f
102 (0066H)
BEL
07
(0007H)
‘
39
(0027H)
G
71
(0047H)
g
103 (0067H)
BS
08
(0008H)
(
40
(0028H)
H
72
(0048H)
h
104 (0068H)
HT
09
(0009H)
)
41
(0029H)
I
73
(0049H)
i
105 (0069H)
LF
10
(000AH)
*
42
(002AH)
J
74
(004AH)
j
106 (006AH)
VT
11
(000BH)
+
43
(002BH)
K
75
(004BH)
k
107 (006BH)
FF
12
(000CH)
,
44
(002CH)
L
76
(004CH)
l
108 (006CH)
CR
13
(000DH)
-
45
(002DH)
M
77
(004DH)
m
109 (006DH)
SO
14
(000EH)
.
46
(002EH)
N
78
(004EH)
n
110 (006EH)
SI
15
(000FH)
/
47
(002FH)
O
79
(004FH)
o
111 (006FH)
DLE
16
(0010H)
0
48
(0030H)
P
80
(0050H)
p
112 (0070H)
DC1
17
(0011H)
1
49
(0031H)
Q
81
(0051H)
q
113 (0071H)
DC2
18
(0012H)
2
50
(0032H)
R
82
(0052H)
r
114 (0072H)
DC3
19
(0013H)
3
51
(0033H)
S
83
(0053H)
s
115 (0073H)
DC4
20
(0014H)
4
52
(0034H)
T
84
(0054H)
t
116 (0074H)
NAK
21
(0015H)
5
53
(0035H)
U
85
(0055H)
u
117 (0075H)
SYN
22
(0016H)
6
54
(0036H)
V
86
(0056H)
v
118 (0076H)
ETB
23
(0017H)
7
55
(0037H)
W
87
(0057H)
w
119 (0077H)
CAN
24
(0018H)
8
56
(0038H)
X
88
(0058H)
x
120 (0078H)
EM
25
(0019H)
9
57
(0039H)
Y
89
(0059H)
y
121 (0079H)
SUB
26
(001AH)
:
58
(003AH)
Z
90
(005AH)
z
122 (007AH)
ESC
27
(001BH)
;
59
(003BH)
[
91
(005BH)
{
123 (007BH)
FS
28
(001CH)
<
60
(003CH)
\
92
(005CH)
|
124 (007CH)
GS
29
(001DH)
=
61
(003DH)
]
93
(005DH)
}
125 (007DH)
RS
30
(001EH)
>
62
(003EH)
^
94
(005EH)
-
126 (007EH)
US
31
(001FH)
?
63
(003FH)
_
95
(005FH)
DEL
127 (007FH)
Chapter 10 - ASCII Communications
Page 10-12
30598-526
NOTES
Chapter 10 - ASCII Communications
30598-526
11
11.1
Page 11-1
SEQUENCER
DESCRIPTION AND INITIATION
The Model 450 processor is equipped with a Sequencer function that allows output of
information based on time driven and/or input- driven conditions.
Operational Attributes
• Up to 255 steps can be defined in a sequence.
• Up to 64 outputs can be controlled.
• Stepping can be performed forward, reverse, or non-sequentially.
• Automatic or manual operation is allowed.
• An automatic step advance can be based on time, events (up to 16 inputs), or both.
• Time accumulated during a step can be held (paused).
• Output state change can be inhibited despite step completion.
• Individual step times can be programmed with a resolution of 0.1 second.
• A sequence can be repeated, or halted after a single pass.
• As many Sequencers can be programmed as allowed by register availability.
The Sequencer is initiated through the SPECIAL function 65 (DRUM) command. This
command points to a block of registers which contain the operating parameters of the
Sequencer.
The minimum rungs needed to program one Sequencer are shown in Figure 11-1.
LOGIC
Sequencer RESET/ENABLE Bit
(D2-01)
DRUM
LET
SZZZZ = XXXX
065; YYY
Figure 11-1 Sequencer Initiation Rungs
Chapter 11 - Sequencer
Page 11-2
30598-526
The rung variables in Figure 11-1 are:
LOGIC
Logic in the first rung allows the Sequencer to be
reset, or enabled to operate.
A dummy output register. The data in this register will
always be the current step number. The recommended
programming parameter is: ZZZZ = XXXX.
A value that points to the definition register block.
This value must be a constant and range from 1 to
3985. Subtract 6 more for each additional step, for
example, the next step would be 3985 - 6 = 3979.
SPECIAL instruction 65. Specifies the Sequencer
function.
The number of steps in the Sequencer. Must be a
constant from 1 to 255.
SZZZZ
XXXX
DRUM 065
YYY
NOTE
Placing logic in front of the LET box could result in the Sequencer’s not
being executed.
11.2 REGISTER BLOCK ALLOCATION
The overall length of each Sequencer register block is variable and changes depending
on the number of steps programmed into the Sequencer.
The first 10 registers in the block are always the configuration table registers and serve
to define conditions for all steps. Each step also requires 6 registers to define itself.
Figure 11-2 illustrates how the Sequencer registers are allocated. Since each step used
within the Sequencer requires 6 registers, the total number of registers required per
Sequencer is calculated as follows:
[6 x (number of steps) + 10]
See Section 11.2.1 for information on the configuration table registers; see Section
11.2.2 for the step table registers.
NOTE
The “D” prefix is intended to convey the idea that the register numbers
in Figure 11-2 represent relative positions, not fixed register numbers.
11.2.1 Configuration Table Registers
The first 10 registers in each Sequencer register block are the configuration table
registers. Their function, which affects all steps in the Sequencer, is described in Table
11-1 on page 11-4.
Chapter 11 - Sequencer
30598-526
D1
Current Step
D2
Operating Mode
D3
Current Step Running Time
D4
Pointer to Input Register
D5
Pointer to 1st Output Register
D6
Output Width Definition
D7
1st Non-Sequential Step Register
D8
2nd Non-Sequential Step Register
D9
Step During Previous Scan
D10
Spare
D11
Step #1 Time Condition Advance
D12
Step #1 Input Condition Advance
D13
Step #1 Output States (1st Register)
D14
Step #1 Output States (2nd Register)
D15
Step #1 Output States (3rd Register)
D16
Step #1 Output States (4th Register)
D17
Step #2 Time Condition Advance
D18
Step #2 Input Condition Advance
Page 11-3
Configuration
Table
Registers (see
Table 11-1 on
page 11-4)
Step #1
Table
Registers (see
Table 11-3 on
page 11-6)
Step #2
Table
Registers (see
Table 11-3)
(In this case, registers 17 through 22 will perform the
same functions as registers 11 through 16 except that
conditions for Step #2 are defined.)
Figure 11-2 Register Allocation
Chapter 11 - Sequencer
Page 11-4
30598-526
Table 11-1: Configuration Table Registers
Chapter 11 - Sequencer
Register No.
Purpose
D1
Current step number. Indicates which step is presently
executing. If changed by the user, the sequencer will
immediately go to the indicated step.
D2
Operating mode register. This register defines the
sequencer’s operating conditions. See Table 11-2 for a
definition of each bit in this register; see Sections 11.4.1
and 11.4.2 for descriptions of the status bits.
D3
Amount of time that the current step has been
executing. When this register is greater than or equal to
the “step time” condition advance (D11, D17, etc.), a
step advance based on time is enabled.
D4
Pointer to the input register. Bits in the register being
pointed to will be compared with the “step input”
condition advance (D12, D18, etc.). When the pattern of
specified “1”s is matched, a step advance based on
input conditions is enabled. If contents are zero,
sequencer operates strictly on time condition advance.
D5
Pointer to the first output register. The contents of
this register point to (define) the first register address of
the output field.
D6
Bit width of output data. Valid range is from 1 to 64.
This register defines how many bits (beginning with the
output register defined by register D5) make up the
output field. A value greater than 16 will begin with the
low-order bits of the next consecutive register; for
example, if register 21 is pointed to as the first output
register, and output width = 18, sequencer outputs will
be written to register 21 and the first 2 (least significant)
bits of register 22. Bits 3-16 of register 22, along with
registers 23 and 24, are unaffected.
D7
Non-sequential step register. Setting bit 8 of the
operating mode register D2 causes the sequencer to
jump to the step loaded by the user in this register. Note
that this jump occurs when conditions for advancing out
of the current step are satisfied.
D8
Same as D7 except that D8 works in conjunction with
bit 9 of the operating mode register D2. Registers D7
and D8 function identically; two registers are provided
for flexibility and ease of use, specifically to avoid
software timing problems or race conditions.
D9
Used by the Model 450 to keep track of the step
executed during the previous scan. If this register is
not equal to the current step register (D1), the
sequencer immediately goes to the new step pointed at
by D1.
D10
Spare (not presently used)
30598-526
Page 11-5
Table 11-2: Operating Mode Register (D2) Bit Definition
Register No.
Purpose
1
Reset/Enable Sequencer (1 = Enable; 0 = Reset).
When initially enabled, sequencer begins with Step #1.
Outputs pointed to by registers D5 and D6 will assume
the state dictated by Step Register D13 (and D14-D16 if
D6 ≥ 17).
2
Sequence Step Direction (1 = reverse; 0 = forward)
3
Run/Pause Select (1 = pause; 0 = run). When this bit =
0, elapsed time for a step is allowed to accumulate.
When bit = 1, time will not accumulate.
4
Automatic Step Advance Inhibit (1 = hold data; 0 =
advance step). When bit = 0, outputs assume the next
state when conditions for an automatic step advance
have been satisfied. When bit = 1, outputs retain their
previous state whether or not the automatic step
advance conditions have been satisfied.
5
Auto/Manual Select (1 = manual operation; 0 =
automatic operation). When in Auto mode, sequencer is
controlled by time/input advance information. When in
Manual mode, sequencer advance is controlled by bit 7.
6
Single Pass/Repeat Select (0 = single pass; 1 = auto
recycle). When bit = 0, sequencer will execute the
sequence one time. At the conclusion of the sequence
(the last step), all outputs will reset and the “current
step” register D1 will indicate “0”. When bit = 1,
sequencer will proceed to step #1 after meeting all
required conditions for advancing beyond the last step.
7
Manual advance (1 = advance, 0 = maintain). If bit 5 =
1, toggling this bit from 0 to 1 will advance the
sequencer.
8
Sequential/non-sequential (1 = next step not
sequential; 0 = next step sequential). When set to 1, the
next step advance will be to the step indicated in D7.
9
Same as bit 8, except that the next step is indicated in
register D8.
10
Time and/or input condition advance (1=OR;
0=AND). When 0, step advance is enabled when input
condition is satisfied only after the time advance
condition has been met. When this bit = 1, the step
advance is enabled when either the time or input
condition has been satisfied.
11-16
Spares (not presently used)
17*
Sequence completed.
18*
Error bit. See Section 11.4.1.
19*
Manual advance history.
20*
Time advance enabled.
21*
Input advance enabled.
22*
Reset/Enable history.
23*
Step advance just occurred.
* Read-Only Status Bit; see Sections 11.4.1 and 11.4.2.
Chapter 11 - Sequencer
Page 11-6
30598-526
11.2.2 Step Table Registers
The step table registers apply only to a particular step in a sequence. The fixed size for
each step table register block is 6 (see Figure 11-2 on page 11-3).
Since the step registers begin immediately after the configuration registers, the first
block of step registers occupies the 11th through the 16th register in the Sequencer’s
overall block of registers. Additional step table register blocks occupy the 17th through
the 22nd, the 23rd through the 28th, and so on, as needed.
Table 11-3 shows the purpose of each of the six step table registers. Each block of step
table registers contains the same parameters (that is, register 11 defines the same
parameter for the first step register block as does register 17 for the second step register
block). Similarly, register 12 is the same as register 18, register 13, matches register
19, and so on.
Table 11-3: Step Table Registers
Register No.
Purpose
D11/D17/...
Time Condition Advance Register. Contains the
user-specified step time of this step (entered in 0.1
second increments). When this time is less than or
equal to the Current Step Running Time Register D3, a
step advance based on time is enabled. If this
register=0, then the step is strictly input-driven.
D12/D18/...
Input Condition Advance Register. Indicates bits that
need to be set before a step advance based on an input
condition is enabled. If this register = 0, then step
advance is based solely on time. If a step advance is
contingent on both time and inputs, normal sequencer
operation is such that a comparison for inputs will not be
made until after the time condition has been satisfied
(modifiable by bit 10, register D2).
D13/D19/...
Defines the output states of the first output register
for each respective step. These bits are written to the
“pointed at” register from the first output register for the
step currently being executed.
NOTE: Either register D11/17/... or D12/18/... must
contain non-zero numbers before this register is
relevant. If both of the conditional advance registers = 0,
the step is advanced through.
Chapter 11 - Sequencer
D14/D20/...
Same as register D13/D19/... except that these are the
output states for the second register (bits 17 to 32). This
register is only relevant if output width (D6) ≥ 17.
D15/D21/...
Same as register D13/D19/... except that these are the
output states for the third register (bits 33 to 48). This
register is only relevant if output width (D6) ≥ 33.
D16/D22/...
Same as register D13/D19/... except that these are the
output states for the fourth register (bits 49 to 64). This
register is only relevant if output width (D6) ≥ 49.
30598-526
11.3
Page 11-7
APPLICATION DISCUSSION
The Sequencer provides flexibility for tailoring Sequencer operation to specific needs.
This translates into developing a basic sequential algorithm which can then be
modified to perform either semi- or non-sequentially. Up to this point the functions of
the registers and control bits have been mechanically presented. The purpose of this
section is to discuss, from an application standpoint, how to put all of these bits and
registers to work in practical situations.
11.3.1 Required Entries
Regardless of how the Sequencer will be used, the following are required actions:
1. The two rungs shown in Figure 11-3 must be entered. Since the LET rung must be
executed every scan (even when the Sequencer is reset), there must not be any logic
in front of the LET rung itself.
LOGIC
Sequencer RESET/ENABLE Bit
(D2-01)
DRUM
LET
SZZZZ = XXXX
065; YYY
Figure 11-3 Minimum Sequencer Initiation Rungs
2. When programming the LET rung, the user-defined block of registers that regulates
the Sequencer must be entered correctly. Whatever register is specified to the left of
the equal (=) sign contains the current step number. It is suggested that ZZZZ be
equal to XXXX so that the Sequencer can be located in the program by searching for
the first register in the block.
3. The rung containing the RESET/ENABLE bit should precede the LET rung. Other
rungs can then be used to preset register values or control bits.
4. The following registers are part of the basic Sequencer set-up procedure and must
be included in the Sequencer program:
• Register D2, Bits 2 through 10. Note the default here is all “0”s, meaning
forward step/single-pass automatic operation.
• Register D4. Points to the register that is used to determine input conditions for
advance. If sequence advance is based solely on time, register D4 should equal
“0”.
• Register D5. Points to the first output register written to by the step output states.
• Register D6. Identifies the total number of output bits occupying contiguous
registers beginning with the register pointed at by register D5.
• Registers D11 (1st step), D17 (2nd step), D24 (3rd step), etc. For each step,
specifies the binary pattern of “1”s that, when matched by the binary pattern in
the input register pointed at by D4, enables a step advanced based on inputs. If
the step advance is based solely on time, the specified binary pattern in these
registers should be all “0”s.
Chapter 11 - Sequencer
Page 11-8
30598-526
• Registers 13 through 16 (1st step), 19 through 22 (2nd step), 25 through 28
(3rd step), etc. Output bit patterns that are user-created for each step, in
accordance with the output field indicated by register D6.
11.3.2 Operating Characteristics
The Sequencer executes during each scan of the ladder program to assure program
control of the outputs based on user-defined states. The Sequencer operates as follows:
1. When the Sequencer is RESET (bit 1 of the Operating Mode register = 0), all
outputs in the program that are specified by registers D5 and D6 in the Sequencer
are turned OFF. Current Step register (D1) is reset to zero. Current Step Running
Time register D3 is also reset to zero.
2. When the Sequencer is ENABLED (bit 1 of Operating Mode register = 1), the
specified output states of step 1 (defined by registers D13 through D16) are
transferred to the outputs defined by both the pointer register D5 and output width
register D6. The Current Step Running Time register begins to accumulate time.
3. Step conditions for the next advance contained in registers D11 and D12 are
compared with the real-time states of the Current Step Running Time register D3
and with the bit pattern of the input register being pointed at by register D4. Bit 10
of the Operating Mode register is checked to determine if either or both conditions
must be met before a step advance. The Current Step Running Time register
accumulates time as long as bit 3 of the operating mode register is not set to “1”.
4. During every scan, in conjunction with the above comparisons, the Sequencer
checks the status of bit 5 in the Operating Mode register D1. This is a check for
AUTO or MANUAL operation. If MANUAL is set, the time and input advance
parameters become meaningless since step advance is based solely on bit 7 being
toggled from “0” to “1”.
5. Whether in AUTO or MANUAL, the Sequencer now knows what criteria to monitor
when determining a step advance.
6. If the Sequencer is in AUTO and the appropriate criteria for a step advance are
satisfied, bit 4 of register D2 is checked to see if advance is inhibited.
7. If bit 4 = 0 (advance not inhibited), bits 8 and 9 of register D2 are checked to see if
the advance is non-sequential.
8. If the advance is sequential, bit 2 of register D2 is checked to determine if the
advance is forward (incrementing) or reverse (decrementing).
9. The Sequencer checks to see if it has just completed a pass through the final step. If
it has, then bit 6 of register D2 is also checked.
10. Finally, if a step change is warranted, the output states for the appropriate step are
written to the outputs being pointed at. The entire process then restarts.
The values of these Sequencer control registers and bits can be changed by the user at
any time.
Chapter 11 - Sequencer
30598-526
Page 11-9
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
Altering control register bits with a programming device may affect
actual equipment under control of the programmable control system.
Make sure that all effects of altering control bits are understood prior
to their alteration.
Failure to observe this precaution can result in equipment damage or
personal injury.
11.3.3 Typical Operating Modes
This section presents insights into setting up the Sequencer for execution of some
typical configurations. The focus here is on manipulating bits within the Operating
Mode Register (Register D2, described in Table 11-2 on page 11-5).
As discussed in Section 11.3.1, registers 4, 5 and 6 of the Configuration Table indicate
the Input Pointer, Output Pointer, and Output Width. These three registers, along with
all the Step Table registers for Time Advance, Input Advance, and output states of each
step, provide the necessary information for Sequencer operation. Normally, these
registers, once set, remain set in that pattern. To guarantee the set pattern, however, it is
advised to program additional LET rungs while configuring the Sequencer.
Although only two rungs are mandatory for Sequencer initiation (Figure 11-3 on page
11-7), it is a good idea to use as many additional LET rungs in the program as
practical. Using “LET presets” to set Sequencer values eliminates the chance of the
values being lost, since the values are preserved in the ladder program.
A good practice is to locate the LET presets in the beginning of the program in
conjunction with a GOTO that bypasses these statements after the Sequencer is
initialized. This bypassing procedure eliminates the time penalty that redundant and
unnecessary scanning of the LET rungs incurs.
Of course, the Operating Mode register bits can also be programmed into the ladder
program. However, rungs containing these bits must be executed every scan. To ensure
proper set-up, the Operating Mode register rungs should be located between the two
mandatory rungs as shown in Figure 11-4.
The Sequencer is now assumed to be properly set up. Some common Sequencer
operating modes are explained in the following section and include TIME, EVENT,
TIME/EVENT COMBINATION, and MANUAL sequencing.
Sequencer RESET/ENABLE Bit (D2-01)
LOGIC
Place Operating Mode Register rungs in this area
DRUM
LET
SZZZZ = XXXX
065; YYY
Figure 11-4 Operating Mode Rungs
Chapter 11 - Sequencer
Page 11-10
30598-526
Time Sequencing Only
The following parameters apply for a time-advanced Sequencer:
• Operation is automatic; bit 5 of register D2 = “0”.
• Since no Input Advance condition is used, set register D4 (and D12/D18/...,
depending on the number of steps) to “0”.
• Enter the Time Advance condition into register D11 (and D17/D23/..., depending on
the number of steps). The time is entered in tenth of a second (0.1 second)
increments.
• Maximum time value for a single step is 32,767 (3,276 seconds, or 54 minutes and
36 seconds).
Operation: When bit 1 of register D2 is set to “1”, the output pattern associated with
Sequencer step #1 (registers D13 through D16) is written into the output register(s)
being pointed at by registers D5 and D6 (STEP #1 ACTIVE).
When the time specified by register D11 has accumulated in register D3, the output
pattern associated with Sequencer step #2 (registers Dl9 through D22) is written into
the output registers being pointed at by registers D5 and D6 (STEP #2 ACTIVE).
Register D3 resets and begins timing again. When the time specified by register D17
has accumulated in D3, the advance to step #3 occurs (STEP #3 ACTIVE).
This process continues as long as bit 1 of register D2 is set to “1” and bit 5 of register
D2 (Auto/Manual Select) is set to “0”. When the last step in the Sequencer has been
executed, bit 6 of register D2 (Repeat/Single Pass Select) is checked to determine
whether the Sequencer should “wrap around” to its step #1 or halt. If the Sequencer
halts (bit 6 = “0”), all outputs are turned OFF.
Possible Modifications: While the Time-Advanced Sequencer is running, the
following modifications can be made:
Instead of incrementing forward, the Sequencer can be set to operate in reverse (set bit
2 of D2 to “1”).
Upon step completion, non-sequential operation can be obtained (Bits 8 and 9 in
register D2: bit 8 set to “1” executes the next step according to register D7, while bit 9
set to “1” non sequentially executes the next step in accordance to the contents in
register D8). Instantaneous non-sequential operation can also be obtained by altering
register D1.
The Current Step Running Time can be held (inhibited from timing) by setting bit 3 of
register D2 to “1”.
If the same output pattern must be maintained for more than the maximum time value
(3,276 seconds), simply repeat the output pattern in multiple steps with appropriate
Time Advance conditions.
A step advance inhibit is enabled by setting bit 4 of register D2 to “1”. This inhibits an
advance even if the time requirement for the advance has elapsed.
Chapter 11 - Sequencer
30598-526
Page 11-11
INPUT SEQUENCING ONLY
The following parameters apply to an input-advanced Sequencer:
• Operation is automatic; bit 5 of register D2 = “0”.
• Load register D4 with the address of the input register being pointed at. This is used
for comparison to determine advance conditions.
NOTE
Register D4 is simply a pointer and is not the register that is actually
compared.
• All Time Condition advance registers (D11, D17, and so on, depending on the
number of steps being used) should be set to “0”.
• Input Condition advance registers (D12, D18, and so on, depending on the number
of steps) should be preset with the bit pattern which, when compared to the register
pointed at by D4, allows a step advance.
NOTE
The bit pattern of “1”s and “0”s does not have to match exactly; it is only
the “1”s in the Input Condition Advance register which have to be
matched by the corresponding bits in the pointed-to register. The “0”s
are not matched. This means that if an advance is dependent upon one
or more bits being “0”, these bits need to be inverted before being
compared.
Example: If the necessary condition for advancing to the next step is having bits 2 and
3 ON, then these two bits should be the only bits set in the Input Condition advance
register. As soon as bits 2 and 3 are ON in the pointed-to register, a step advance is
enabled regardless of how many other bits are ON in the register being pointed at.
Operation: When bit 1 of register D2 is set to “1”, the output pattern associated with
Sequencer step #1 (registers D13 through D16) is written into the output register(s)
pointed at by registers D5 and D6 (STEP #l ACTIVE).
When the bit pattern of “1”s specified in register D12 is matched by the pattern in the
input register being pointed at by D4, the following occurs: The output pattern
associated with Sequencer step #2 (registers Dl9 through D22) is written into the
output register(s) being pointed at by D5 and D6 (STEP #2 ACTIVE).
Comparison for the third step advance is made with register D18. This process
continues for as long as bit 1 of register D2 is set to “1” and bit 5 of register D2
(Auto/Manual Select) is set to “0”.
After the last Sequencer step is executed, bit 6 of register D2 (Repeat/Single-pass
Select) is checked to determine whether the Sequencer should “wrap around” to step #l
or halt. If the Sequencer halts (bit 6 = “0”), all outputs are turned OFF.
Chapter 11 - Sequencer
Page 11-12
30598-526
Possible Modifications: While the Input Advanced Sequencer is running, the same
modifications apply as for the Time Advanced Sequencer (Forward/Reverse stepping,
non-sequential stepping, etc.). One exception is the current step running time
parameter, which is not applicable in a Sequencer based solely on input conditions.
COMBINATION TIME AND EVENT/INPUT SEQUENCING
The following parameters apply to a Sequencer whose advances are based on both
time and inputs:
• Operation is automatic; bit 5 of register D2 = “0”.
• Register D4 should point to the register address whose bit pattern is used to compare
for a step advance.
NOTE
Register D4 is simply a pointer and is not the register that is actually
compared.
• The Time Condition advance registers (D11, D17, etc., depending on the number of
steps) should be loaded with times in tenth of a second (0.1 second) increments.
NOTE
If a given step advance is to be based solely on input, “0” should be
entered into the Time Condition register for that step.
• The Input Condition advance registers (D12, D18, etc., depending on the number of
steps) should be loaded with the bit patterns which, when compared to the register
pointed at by D4, allow a step advance. As explained on page 11, it is only the “1”s
in the Input-Condition advance register that are compared.
NOTE
If a given step advance is to be based solely on input, “0” should be
entered into the Input Condition register for that step.
• If both time and event sequencing are specified in a step, an advance is not enabled
until the input condition has been m.et after the time condition is satisfied (unless
bit 10 of register D2 = “1”). This occurs even if the input condition has previously
been met. If bit 10 of register D2 = “1”, then a step advance is enabled upon either
condition being satisfied.
Operation: When bit 1 of register D2 is set to “1”, the output pattern associated with
Sequencer step #1 (registers D13 through D16) is written into the output registers
being pointed at by registers D5 and D6 (STEP #1 ACTIVE).
When register D3 is greater than or equal to D11 (that is, the time condition is
satisfied), the pattern of “1”s specified by register D12 is compared to the input register
pointed at by register D4. When all the “1”s in D12 are matched by the register pointed
Chapter 11 - Sequencer
30598-526
Page 11-13
at by D4, the output pattern associated with Sequencer step #2 (registers D19 through
D22) is written into the output register(s) being pointed at by D5 and D6 (STEP #2
ACTIVE).
Register D3 resets and begins timing again. Comparison for the third step advance is
made using registers D17 (for time) and D18 (for input). This process continues as
long as bit 1 of register D2 is set to “1” and bit 5 of register D2 (Auto/Manual Select)
is reset to “0”.
After the last Sequencer step is executed, bit 6 of register D2 (Repeat/Single-Pass
Select) is checked to determine whether the Sequencer should “wrap around” to step #l
or halt. If the Sequencer halts (bit 6 = “0”), all outputs are turned OFF.
Possible Modifications: While the combination Time and Input Advanced Sequencer
is running, the same modifications apply as for the Time Advanced Sequencer
(Forward/Reverse stepping, non-sequential stepping, etc.). One exception is the
current step running time parameter, which is not used if a particular Sequencer step is
based solely on input conditions.
A manual Sequencer does not rely on time and/or input conditions to advance. Instead,
advance is determined solely by the state of bit 7 in register D2, which is toggled
manually.
NOTE
If an input condition exists for advance, it is ignored. If a time condition
exists, register D3 does not accumulate time. If desired, the input and/or
time conditions for advance can be loaded in anticipation of automatic
operation, because all input and time conditions are simply ignored in
the manual Sequencer.
The following parameters apply to a manual Sequencer:
• Operation is manual; bit 5 of register D2 is set to “1”.
• The Sequencer is advanced by toggling bit 7 of register D2 from “0” to “1”.
Operation: When bit 1 of register D2 is set to “1”, the output pattern associated with
Sequencer step #1 (registers D13 through D16) is written into the output registers
being pointed at by D5 and D6 (STEP #l ACTIVE).
If bit 5 of register D2 is set to “1”, the next step advance occurs when bit 7 of register
D2 is toggled from “0” to “1”. At this time the output pattern associated with
Sequencer step #2 (registers D19 through D22) is written to the output register(s)
pointed at by D5 and D6.
NOTE
To prepare for another step advance, bit 7 of register D2 must be reset
to “0” before being toggled back to “1”.
Chapter 11 - Sequencer
Page 11-14
30598-526
Sequencer behavior can be set to automatic at any time by resetting bit 5 of register D2
to “0”. After the last Sequencer step is executed, bit 6 of register D2
(Repeat/Single-Pass Select) is checked to determine whether the Sequencer should
“wrap around” to step #l or halt. If the Sequencer halts (bit 6 = “0”), all outputs are
turned OFF.
Possible Modifications: While the manual Sequencer is running, the same
modifications apply as for the automatic advance Sequencer (Forward/Reverse
stepping, non-sequential stepping, etc.). Bit 4 of register D2 only applies to the AUTO
mode operation and cannot be used to inhibit a MANUAL step advance.
NON-SEQUENTIAL STEPPING
Regardless of whether the Sequencer is operating in the manual or automatic mode, it
is possible to alter the default incremental-forward stepping mode in the following
ways:
1. Reverse advance (decrement step).
2. Non-sequential advance (that is, jump to a step not immediately preceding or
following the current step).
3. Immediate and unconditional non-sequential advance to another step, even though
the advance conditions for the present step are not satisfied.
4. Inhibit a step advance while in the AUTO mode, causing the current step to be
maintained despite any satisfied conditions for automatic advance that are present.
The non-default advance conditions are as follows:
Reverse (Decremental) Stepping. Set bit 2 of register D2 to “1”, causing the
Sequencer to step backward (reverse mode). Decrementing from Sequencer step #l
causes the Sequencer to go to step O (all outputs OFF) unless bit 6 of register D2 is set
(REPEAT mode), in which case the Sequencer goes to the last step.
NOTE
Bit 2 of register D2 has a lower priority than bits 4 (Step Inhibit), 8 or 9
(Non-Sequential Step) or setting Register D1 to the desired step.
If the reverse mode is selected before Sequencer enabling, the Sequencer—upon
initialization—jumps to the last step.
Non-Sequential Advance. Set bit 8 of register D2 to “1”, and load register D7 (first
non-sequential step register) with the number of the next desired step, or set bit 9 of
register D2 to “1” and load register D8 with the number of the next desired step.
Bit 8/Register D7 and Bit 9/Register D8 function identically; two pairs are provided
for user convenience.
NOTE
If both register pairs are enabled simultaneously, Bit 8/Register D7
takes precedence.
Chapter 11 - Sequencer
30598-526
Page 11-15
When either of these bit/register pairs is activated, the Sequencer goes to the step
specified in either register D7 or D8 when the next step advance occurs. The number
entered in these registers must be a valid step number (zero is NOT a valid step
number); otherwise no advance takes place. Outputs remain as defined for the current
step and bit 18 of register D2 is set to “1” to indicate an error.
If a non-sequential advance is specified prior to Sequencer enabling, the Sequencer
advances—upon initialization—to the specified non-sequential step.
Immediate And Unconditional Non-Sequential Advance. Loading a step number into
register D1 (Current Step Number) causes the Sequencer to jump unconditionally to
that step upon the next program scan. The Sequencer detects this by storing the step
executed during the previous scan in register D9.
At the beginning of each new scan, D9 is compared with D1. If they differ, the
Sequencer immediately jumps to the new step specified in D1. Normal Sequencer
operation resumes from that point—register D3 resets and begins timing, and the Input
Condition advance register for the new step is used for comparison.
NOTE
The new step that is jumped to must be valid for the Sequencer range
defined. If the step is invalid, no step change occurs; outputs remain as
defined for the previous step and bit 18 of register D2 is set to “1” to
indicate the error.
If an immediate and unconditional non-sequential advance is specified prior to
Sequencer enabling, the Sequencer—upon initialization—advances to the first step for
one scan before jumping to the selected step. Similarly, if a step advance is enabled
while an immediate and unconditional non-sequential advance is specified, the
advance goes active for one scan before reverting to the specified step.
Inhibit a Step Advance (AUTO mode only). Set bit 4 of register D2 to “1”. This
prevents the Sequencer from advancing beyond the current step, even if conditions for
advance are satisfied when in the Automatic mode.
The Automatic Step Advance Inhibit applies regardless of whether the step change is
to be forward or reverse.
As soon as bit 4 of register D2 is reset to “0”, output control reverts to control of the
automatic advance condition. For example, if the only condition for advance is inputs
(which happen to be satisfied), the step advance occurs the instant that bit 4 is reset to
“0”.
If a step advance is inhibited before Sequencer enabling, the Sequencer—upon
initialization—advances to the first step. The next step advance is inhibited, provided
the inhibit remains selected and the Sequencer is in Automatic mode.
Bit 4 only applies to automatic mode operation (bit 5 of register D2 = “0”) and does
not inhibit a manual or Immediate and Unconditional Non-Sequential Step Advance.
Chapter 11 - Sequencer
Page 11-16
30598-526
11.4 APPLICATION CONSIDERATIONS
This section presents a collection of miscellaneous considerations for Sequencer
operation.
11.4.1 Error Conditions
Bit 18 of the Operating Mode register (register D2) is used to flag invalid Sequencer
operating conditions. When an invalid operation is detected by the Sequencer, bit 18 is
set to “1”.
If the error is generated while the Sequencer is running, the condition of the previous
step is retained. If the error exists prior to Sequencer enabling, no step execution
occurs until the error is corrected.
The most common reasons for bit 18 to be set are listed below:
1. An undefined (non-existent) step has been specified in registers D1, D7 or D8.
NOTE
Neither D7 nor D8 are checked until either bit 8 or bit 9 of the Operating
Mode register = “1”.
2. The number of steps specified exceeds 255 (the Sequencer does not commence
operation at all until this error is corrected).
3. An invalid Register Block starting address has been given in the Sequencer's
configuration rung (Figure 11-1 on page 11-1).
4. An invalid Output Width Definition has been entered into register D6 (width must
be in the range 1 to 64).
5. Register D4 = “0”, but a Step Input Advance condition register (D12, D18, etc.)
exists and is not equal to “0”.
When any of these error conditions appear, the Sequencer is reporting that it has been
asked to perform an illegal operation.
When defining a register block for the Sequencer to use, make sure that sufficient
registers exist between the start of the block and the last available register in the Model
450 (register 4000 is the last). Otherwise, the Sequencer flags an invalid operating
condition and sets bit 18 of the register indicated to the left of the equal (“=”) sign.
To guarantee sufficient registers, apply the following equation (from Section 11.2):
Total Registers per Sequencer = [6x (# of steps) + 10]
Subtract the total registers per Sequencer from 4000 to obtain the highest address that
the Sequencer can be started at.
Example: A 50-step Sequencer is to be programmed into the Model 450. From the
equation above, the registers required for this Sequencer are:
[6X(50) + 10] =310
The highest address at which this Sequencer can be located is therefore:
4000-310 = Register 3690
Chapter 11 - Sequencer
30598-526
Page 11-17
The Sequencer's register block must begin at an address no higher than 3690.
NOTE
Do not use registers allocated for a Sequencer for any other purpose.
11.4.2 Operating Mode Register Status Bits
Bits 17 through 23 of the Operating Mode register (D2) are read-only bits that are used
to monitor the status of the Sequencer. The addresses of these bits can be programmed
as contacts in the Model 450's user memory to provide detailed information on
Sequencer operation. All of these status bits are reset to “0” when the Sequencer is
reset (when bit 1 of register D2 is set to “0”). Each of the status bits is described below:
Bit 17 - Sequence Complete. When set, indicates that the Sequencer has just
completed the final step. If bit 6 of register D2 = “0” (Single-Pass Sequence selected),
bit 17 remains set at “1” until the Sequencer is reinitialized by toggling bit 1 of register
D2 from “0” to “1”. If bit 6 of register D2 = “1” (Repeat Sequence selected), bit 17 is
set at “1” for only a single Model 450 scan as the Sequencer “wraps around” from the
final step to the first step.
Bit 18 - Error Bit. This bit is described in Section 11.4.1.
Bit 19 - Manual Advance History. When set to “1”, a manual advance has occurred.
This bit is used to ensure that the manual advance bit (bit 7 of register D2) is
transition-sensitive.
Bit 20 - Time Advance Enabled. When set to “1”, the time advance condition for the
current step has been satisfied.
Bit 21- Input Advance Enabled. When set to “1”, the input advance condition for the
current step has been satisfied.
Bit 22 - Reset/Enable History. When set to “1”, the Sequencer has been enabled. This
bit is used to ensure that the reset/enable bit (bit 1 of register D2) is
transition-sensitive.
Bit 23 - Step Advance Flag. When set to “1”, a step advance has just occurred.
Typically this bit is set for a single scan.
OTHER CONSIDERATIONS
Although all possible operating configurations cannot be examined, the following
items should be considered when programming the Sequencer:
• Output Status. Output states associated with a given step are written only if a step
change occurs; they are not refreshed each time the Sequencer is scanned. If the
CPU is halted or power is removed when the Sequencer is in the middle of
executing a step, the output states are not updated when programming execution
resumes until a step change actually occurs. When the CPU resumes operation
from a halt condition or power cycle, the external output registers are automatically
reset. Sequencer output states that are directly written to external outputs remain
OFF until the currently executing step has finished and a step advance has occurred.
Chapter 11 - Sequencer
Page 11-18
30598-526
If the user wishes to preserve the Sequencer output conditions for a given state
following a processor halt or power cycle, specify an internal storage register(s)
in D5 and D6 and perform a data transfer from the storage register to the external
output register.
• External Outputs. Due to Image Table updating, output states that are associated
with a given step are not written to external outputs until the end of the Model 450's
ladder scan. The only exception to this is if the Immediate I/O Update function (bit
7 of 8176) is used.
• Rung Programming. It is recommended that any rungs used to modify the
Sequencer's operation be programmed before the Sequencer initiation rung.
• Subroutines. Since Sequencers are designed to be executed during each ladder
scan, they should NOT be used in subroutines or in any part of a ladder diagram that
could be skipped. Also, no logic should be placed in front of the SPECIAL function
65 rung, to ensure the instruction is always executed.
• MCR. When preceded by a disabled MCR, the sequencer operation state is frozen:
If reset, the Sequencer remains reset, while if in the middle of the step, the output of
that step is maintained.
• Address Range. All registers in the user-defined sequencer register block must have
addresses in the range of 1 to 4000.
11.5
EXAMPLES
This section provides a simulated Sequencer to help clarify the Sequencer's set-up and
operating procedures.
SAMPLE SET-UP:
Assume the following Sequencer conditions for the example:
Number of Steps
Registers Required
Beginning Register Address
Ending Register Address
Output Register Address
Output Width
Input Register Address
20
130 = [(16X20) + 10]
0751
0880
0004
12 bits,
(register #4,
bits 1 through 12
0001 (any or all of the 16 bits
can be used to establish advance
conditions).
Upon Sequencer initialization (step #t), assume that bits 2, 3 and 4 of the output
register (#4) are to be set to “1”. The initiation rungs needed are shown in Figure 11-5.
Chapter 11 - Sequencer
Page 11-19
30598-526
0752
LOGIC
01
DRUM
LET
S0751 = 00751
065; 20
Figure 11-5 Example 1: Initiation Rungs
In the first rung shown in Figure 11-5, 0752-01 is the RESET/ENABLE bit for the
Sequencer. In the second rung, 0751 is the address that identifies the start of the
register block. DRUM and 65 identify the special instruction as a Sequencer, while 20
is the number of steps in the Sequencer.
Following the guidelines in Section 11.3.1, the following registers have to be set up for
the first step (step #l) in Example 1:
0752 (D2)
0754 (D4)
0755 (D5)
0756 (D6)
0761 (D11)
0762 (D12)
0763 (D13)
0764 through 0766
(D14 through
D16)
Operating Mode (assume for now the default
operation).
Pointer to Input Register 0001. Preset to 1.
Pointer to Output Register 0004. Preset to 4.
Output Width Definition. Preset to 12.
Time Condition Advance. Assume that bits 2 through
4 of register 0004 must be ON for 60 seconds to
satisfy the time advance requirement. Preset to 600
(60 ÷ 0.1 second increments).
Input Condition Advance. Assume a step advance is
enabled when bits 1, 3 and 4 of register 0001 are set to
“1”. Preset to 13 (decimal value. For corresponding
binary pattern, see Figure 11-7 on page 11-20).
Step #1 Output States bits 1 through 16. Since bits 2, 3
and 4 of register 0004 are set to “1”, preset to 14
(decimal value). For the corresponding binary pattern,
see Figure 11-6 on page 11-20.
Step #1 Output States bits 17 through 64. Since the
Sequencer's output width is less than 17, these
registers are not applicable.
The remaining 19 steps in the Sequencer must be set up separately and are not shown
here.
SAMPLE OPERATION
Before bit 1 of register 0752 (D2) is energized, registers 0751 and 0753 equals zero
and bits 1 through 12 of register 0004 are reset to “0” every time the initiation rungs
(Figure 11-5) are scanned by the Model 450.
When bit 1 of register 0752 is set to “1”, the following occurs:
1. The Sequencer sets register 0751 to “1”.
Chapter 11 - Sequencer
Page 11-20
30598-526
2. Output information in registers 0763 through 0766 is transferred to the output
registers specified by 0755 (D5) and 0756 (D6). Since D5 = 4 and D6 = 12, bits 1
through 12 of register 0763 are transferred to bits 1 through 12 of register 0004.
Since register 0763 = 14, bits 2 through 4 of this register are set to “1” while bit 1
and bits 5 through 12 are set to “0” as shown in Figure 11-6:
1
16
0004
x
x
x
x
0
0
0
0
0
0
0
0
1
1
1
0
0763
1
16
x = “Don’t Care”; not transferred
Figure 11-6 Transfer of 12-Bit Output Width
3. If the output width in this example were specified as 52 instead of 12 (register 0756
= 52), additional output registers would be used. As shown in Figure 11-7, all 16 bits
of registers 0763, 0764 and 0765, along with bits 1 through 4 of register 0766 are
written to registers 0004, 0005, 0006 and the first four bits of 0007. If the bit patterns
of Figure 11-7 are involved in a transfer, it is necessary to preset register 0764 with
the decimal value -24,562 (A00EH), register 0765 with decimal 16,391 (4007H),
and register 0766 with decimal 15 (000FH). These settings allow the multi-register
transfer to take place.
1
16
1
16
0005
0004
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
0
0
1
0
0
0
0
0
0
0
0
0
1
1
1
0
0764
0763
Bits 5-16 are not part of the
sequencer.
1
16
0006
1
16
1
16
1
16
0007
0
1
0
0
0
0
0
0
0
0
0
0
0
1
1
1
0765
16
1
x
x
x
x
x
x
x
x
x
x
x
1
1
1
1
1
16
x = “Don’t Care”; not transferred
Figure 11-7 Transfer of 52-Bit Output Width
Chapter 11 - Sequencer
x
0766
Page 11-21
30598-526
4. Bit 23 of register 0752 is set to “1” for one scan.
5. Register 0753 (D3) begins to time (to be compared with register 0761) to determine
Time Advance enable.
6. The bit pattern of register 0001 (the Input Register pointed at by register 0754) is
compared to register 0762 to see if the condition for Input Advance is satisfied. The
Input Advance does not enable a step advance until the time condition (register 0753
= register 0761) has been satisfied.
7. Step advance to step #1 is now complete. Assuming no Operating Mode register bits
are set, the next step advance occurs when bits 1, 3 and 4 (specified in register 0762)
of register 0001 (pointed at by register 0754) are set to “1” as shown in Figure 11-8
following.
1
16
x
x
x
x
x
0
0
0
0
0
x
x
x
x
x
x
x
0
0
0
0
0
0
x
0001
0
1
1
0
1
0762
1
16
x = “Don’t Care”; not compared
Figure 11-8 Input Advance Condition Satisfied
Before this comparison occurs, the time condition for advance (60 seconds) must be
satisfied.
NOTE
If it is desired to have the step advance in this example based solely on
time, presetting register 0762 to zero allows the advance to occur after
60 seconds. If a strictly input-based advance is desired, presetting
register 0761 to zero allows an advance as soon as bits 1, 3 and 4 of
register 0001 are set to “1”.
Following is a list of options that are not necessary for basic Sequencer operation. The
description of Sequencer operation continues (at step #7) after the options.
OPTIONS:
Now that the Sequencer is enabled, a variety of operating modes can be selected by
altering the bits in the Operating Mode register (register 0752). Some possibilities are
listed below:
Reverse Sequencing - Set bit 2 of register 0752 to “1”, and the Sequencer runs in
reverse. If the Sequencer is currently at step #1, enabling bit 2 advances the Sequencer
to step #20 (the last step) instead of to step #2.
Prevent Time Accumulation - Set bit 3 of register 0752 to “1” and no time
accumulates in the Current Step Running Time register (0753).
Chapter 11 - Sequencer
Page 11-22
30598-526
Inhibit A Step Advance - Set bit 4 of register 0752 to “l” and the Sequencer does not
advance from the current step, even if time (register 753 = 600) and/or input (bits 1, 3
and 4 of register 0001 = “1”) conditions are satisfied. Also, output register 0004 does
not change.
Manual Operation - Set bit 5 of register 0752 to “1” and the Sequencer ignores both
time and input advance conditions. Toggle bit 7 of register 0752 to manually step the
Sequencer.
Non-Sequential Stepping - Bits 8 and 9 of register 0752 are used to make the
Sequencer jump to a step that is not in numerical order (for example, jump from step #l
to step #4, ignoring #2 and #3). Register 0757 or 0758 needs to be loaded with a valid
step number (1 to 20); otherwise the current step is maintained. If bit 8 or 9 of 0752 is
set, and advance conditions are satisfied, the Sequencer jumps to the step specified in
register 0757 (if bit 8 is set) or register 0758 (if bit 9 is set).
NOTE
If an immediate jump to a non-sequential step is desired, load the valid
step number (1-20) into register 0751. Step advance occurs even if time
and/or input conditions are not satisfied.
Time or Input Condition Advance - Set bit 10 of register 0752 to “1” and a step
advance is enabled as soon as either register 0753 = 600 (60 seconds) or bits 1, 3 and 4
of register 0001 are set to “1”.
8. Sequencer step #2 - Assume the initial conditions of this example are unchanged
and that no Operating Mode register bits are set to “1”. Fix the output bit pattern for
step #2 so that bits 1, 4 and 5 of register 0004 are set to “1” (all other bits “0”). This
is accomplished by setting register 0769 to 25 (0019H). Figures 11-9 and 11-10 are
the requirements and results of Sequencer step #2.
1
16
x
x
x
x
x
0
0
0
0
0
x
x
x
x
x
x
x
1
1
x
1
0
0
0
0
0
0
1
1
0
1
0001
0
0762
1
16
x = “Don’t Care”; not compared
Figure 11-9 Step #2 Advance
When register 0001 matches register 0762 (as shown in Figure 11-10), and register
0753 ≥ register 0761 (step #1 has been running for at least 60 seconds), the following
occurs:
Chapter 11 - Sequencer
Page 11-23
30598-526
1
16
x
x
x
x
x
0
0
0
0
0
x
x
x
x
x
x
x
0
0
0
0
0
0
x
0001
0
1
1
0
1
0762
1
16
x = “Don’t Care”; not compared
Figure 11-10 Step #2 Result
For manual operation (bit 5 of register 0752 = “1”), register 0004's pattern would
change from the pattern in register 0763 to the pattern of 0769 when bit 7 of 0752 is
toggled from “0” to “1”.
This procedure is followed for each step as long as the Sequencer is enabled. If the
Sequencer is disabled by resetting bit 1 of register 0752, the outputs are turned OFF
and the current step register (0751) is reset to 0. Upon reaching the last step (step 20),
bit 6 of register 0752 is monitored. If bit 6 is set, the next step advance is to step 1 and
the Sequencer operation continues. If bit 6 is reset, the next step advance concludes the
sequencing operation and all outputs are turned OFF.
Chapter 11 - Sequencer
Page 11-24
30598-526
NOTES
Chapter 11 - Sequencer
30598-526
12
Page 12-1
BATTERY BACKUP AND CLOCK/CALENDAR
12.1 BACKUP BATTERY
12.1.1 Description
The Model 450 uses two methods to supply backup power to the onboard volatile
RAM and real-time clock/calendar circuitry in the event that line power to the power
supply is interrupted:
1. Batteries located in the SY/MAX power supply (PS-21, 31, for example) are the
primary source of backup power for the Model 450 RAM and real-time
clock/calendar in the event that +5VDC from the power supply is lost. Refer to
Instruction Bulletin #30598-156, #30598-159 or #30598-802 for information on
the power supply batteries.
2. The Model 450's onboard lithium battery supplies power to the RAM and real-time
clock/calendar if the voltage from the batteries in the power supply is not sufficient
to retain valid data in the RAM. The battery also maintains the RAM contents and
clock/calendar accuracy if the processor is removed from the rack or shipped to use
in another location. All 8192 Control Processor registers are battery-backed.
Ethernet NIM registers 1 to 10, 3000 through 3999, and 7000 through 7999 are
battery-backed.
12.1.2 Low Battery Indication
The condition of either the SY/MAX power supply batteries or the Model 450's
onboard lithium battery is indicated with the BATTERY LOW LED on the front panel
of the processor (see Chapter 4 for additional information about this LED). Low
battery condition may also be monitored as the status of a contact (bit 17 of register
8176 for the power supply batteries, bit 32 of register 8176 for the on-board lithium
battery). See Chapter 13 for information on register 8176.
NOTE
If the onboard battery is not installed, the BATTERY LOW indicator will
signal a low internal battery condition.
12.1.3 Battery Life Expectancy
The life expectancy of the onboard lithium battery is dependent on the time that the
battery must supply current to the Model 450, and on the physical age of the battery.
Figure 12-1 gives a rough estimate of how long the Model 450's RAM is supported
when a battery ranging from new to five years old is installed in a Model 450. The
BATTERY AGE assumes the battery has been installed in the Model 450 but not
supplying current, and that the Model 450 has been at its maximum operating
temperature of 60°C. The RAM DATA RETENTION TIME is based on a Model 450
at 40°C, since the processor is not at operating temperature while on lithium battery
backup.
Chapter 12 - Battery Backup and Clock/Calendar
Page 12-2
30598-526
30
25
20
15
RAM
DATA RETENTION
TIME (MONTHS)
Model 450 RAM
supported at 40°C
10
5
12
36
24
48
60
LITHIUM BATTERY AGE (MONTHS)
Battery Installed in Model 450 Operating at 60°C
No Current Being Drawn from Battery
Figure 12-1 Backup Lithium Battery Life
12.1.4 Replacement Procedure
The internal lithium battery is replaced by unscrewing the small access cover on the
front panel of the Model 450. The battery can be changed while the Model 450 is
operating. If the processor is installed in a rack which is supplying either regular or
battery power, there is an unlimited time in which to replace the battery.
NOTE
For maximum onboard battery life, the Model 450 should remain in the
rack, connected to the power supply, as much as possible. In this way, the
power supply batteries—not the internal battery—are supplying any
needed backup power.
Chapter 12 - Battery Backup and Clock/Calendar
Page 12-3
30598-526
12.1.5 Battery Specifications
Square D Part Number
Manufacturer
Mfg. Type Number
Mfg. Catalog Number
Rated Voltage
Capacity (200 µA @ 3V)
29904-08961
Tadiran Electronic Industries Inc.
TL-5104
15-51-04-210-000
Lithium AA, 3.5 to 3.6 V
1.9 Amp Hours
(Typical cells stored at 25°C for one year)
(Alternate manufacturer source is SAFT, battery type LS6, catalog number 500200)
12.2 REAL-TIME CLOCK/CALENDAR
The Model 450 is equipped with a battery-backed real-time clock/calendar. The
clock/calendar keeps track of seconds, minutes, hours, day of the week, day of the
month, month, and year and clock compensates for leap years.
Values for the real-time clock/calendar reside in registers 8109 through 8115. These
registers are updated in the Model 450 image table each hour by the regulation
circuitry within the real-time clock. In between the hourly updates, the clock is
updated second-by-second by the software oscillator in the Model 450.
Note that if memory is lost because of no battery backup, the clock must be manually
reset.
12.2.1 Specifications
Format
24-hour (“military”) time. If 12-hour (AM/PM) mode
is desired, the user program must perform the
conversion.
Accuracy
Less than one second per day @ 25 °C, 16 seconds per
day over the 32 to 140 °F (0 to 60 °C) range
Set Method
Write to registers using one of the following methods:
• Model 450 user program
• Programming equipment
• Other processors
• D-LOG Module
12.2.2 Loading the Time/Date
Model 450 registers 8108 through 8115 are assigned to the clock/calendar. Table 12-1
shows the function of each of these registers:
Table 12-1: Clock/Calendar Registers
Register
Function
Decimal Range
8108
Set clock
(see Section 12.2.4)
-1,0, or +1
8109
Seconds
0-59
8110
Minutes
0-59
8111
Hours
0-23
8112
Day of week
1-7
(1 = Sunday)
8113
Day of month
1-31
8114
Month
1-12
8115
Year
1980 - 2079
Chapter 12 - Battery Backup and Clock/Calendar
Page 12-4
30598-526
Set the current time of day in the clock using the following procedure:
1. Using a programming software package such as SY/MATE Plus Software, load
“-1” into register 8108. This interrupts the updating of the image table clock
registers; it does not affect the real-time clock itself.
2. Access each of the registers shown in Table 12-1 by starting with register 8109.
Register 8108 is only used to transfer data to the clock.
3. While in ONLINE DATA mode, load each of the registers 8109-8115 with the
appropriate value. These are control registers; it is necessary to enter the value in
WRITE DATA mode, and then move the cursor off the register field to load the
value.
EXAMPLE:
To set the current time as 3:10 PM on Friday, February 26th, 1993, the following
values would be entered into registers 8109-8115:
8109...........................00 (seconds)
8110...........................10 (minutes)
8111...........................15 (hours)
8112...........................6 (day of week)
8113...........................26 (day of month)
8114...........................2 (month)
8115...........................1993 (year)
12.2.3 Setting the Clock
After the loading procedure in Section 12.2.2 has been completed, the values in the
image table must be transferred to the clock. This is accomplished by loading the
decimal value 0 (zero) into register 8108. The instant that this value is loaded into
register 8108, the clock resumes keeping time using the loaded values.
TO UPDATE AND RESTART THE CLOCK:
8108...........................0
12.2.4 Clock Manipulation
NORMAL OPERATION (Register 8108 set to 0)
When manipulating the clock, it is important to realize that the clock circuitry itself is
running regardless of whether the Model 450 is rack-powered or not.
During “normal” clock operation, the user-accessed image table registers are updated
directly from the clock once each hour. During each hour, the Model 450's oscillator
regulates the updating of the image table each second. The specified drift of the
software oscillator while the Model 450 is powered up is ± 1.8 seconds per hour. This
drift is eliminated each time the real-time clock performs its hourly updates on the
image table registers.
SET CLOCK OPERATION (Register 8108 set to -1)
To set the clock either in ONLINE/DATA mode or by an instruction in the user
program, it is first necessary to set register 8108 to “-1”. This prevents the image table
from being updated by either the real-time clock or by the Model 450's software
oscillator.
Chapter 12 - Battery Backup and Clock/Calendar
30598-526
Page 12-5
NOTE
The clock itself continues to run internally when register 8108 is set to “-1”.
After the desired values have been loaded into registers 8109-8115 (see Section
12.2.2), reset register 8108 to “0” (see Section 12.2.3). This action transfers the values
in 8109-8115 to the real-time clock itself and normal operation resumes (that is, the
image table registers are updated each second by the software oscillator and each hour
by the real-time clock).
NOTE
If out-of-range values are entered into any register, the values are rejected
and an ERROR 42 is displayed on the programmer.
STOPWATCH OPERATION (Register 8108 set to +1)
A special operational mode is enabled when register 8108 is set to “+1”. In this
“stopwatch” mode, the hourly updates of the image table by the real-time clock are
inhibited, but the second-by-second updates by the software oscillator continue. When
register 8108 is reset to “0”, normal clock operation resumes and the image table
registers are updated with the most current hourly time in the real-time clock.
This stopwatch mode can be very useful for timing discrete events. Since the software
oscillator continues to run, time can be accumulated without being overwritten by an
update from the real-time clock. At the conclusion of the timed event, resetting register
8108 to “0” resumes normal operation and registers 8109 to 8115 are updated
automatically by the real-time clock. There is no need to reset the time of day since
this is retained in the real-time clock during the event's timing.
The three modes of operation are summarized below in Table 12-2.
Table 12-2: Clock Operation Modes
Register 8108
Set to:
Clock Mode
External Clock Registers Being
Updated by:
Software
Real-Time Clock
-1
Set Clock
NO
NO
0
Normal
YES
YES
+1
Stopwatch
YES
NO
In summary, when register 8108 is set to “-1” external clock registers are not updated
by either the real-time clock or the software oscillator. This allows a user to preset the
clock registers for the instant when register 8108 is user-reset to “0”. The preset values
are simultaneously transferred to the real-time clock at this point. If register 8108 is set
to “+ 1", the clock registers operate in the “stopwatch” mode.
Chapter 12 - Battery Backup and Clock/Calendar
Page 12-6
30598-526
NOTES
Chapter 12 - Battery Backup and Clock/Calendar
30598-526
13
Page 13-1
PROCESSOR CONTROL REGISTERS
13.1 GENERAL INFORMATION
NOTE
See Section 15.5.3 for an overview of Ethernet NIM (Control) Registers.
The Model 450 Control Processor uses a total of 4192 register addresses. These
processor registers are separated into the groups illustrated in Figure 1-1.
Control registers are reserved for Model 450 control functions. Register addresses
8093-8192 are reserved for these control functions within the control processor.
A register consists of 32 bits. Bits 1 through 16 are referred to as the data field, while
bits 17 through 32 are referred to as the status field. The status field is unalterable, but
may contain useful information about how the register is being used. The structure of a
data register is shown in Figure 13-1.
The control register addresses can be divided into two groups as follows:
Group #1 consists of addresses 8093-8178. Both the data field and status field of
group #I can be examined by the user; however, only the data field can be altered.
Group #2 consists of registers 8179-8192. This group is used by the processor for
certain “bookkeeping” functions. Only the data field is accessible to the user and it can
only be examined, not altered.
Table 13-1 provides a list of processor control registers organized by their functions.
Chapter 13 - Processor Control Registers
Page 13-2
30598-526
Table 13-1: Processor Control Registers by Function
ASCII Data Registers
Command identifier for ASCII input
Command identifiers for ASCII output format
Group #1 Control Register Function
(Read/Write Registers)
Application security
Baud rate
Clock
Register Number
8006
8001-8005
Register Number
8177-8178
8169
8108-8115
Communications monitor timeout
8168
Division remainder
8171
End of Scan communication extension
8170
Error code storage register
8175
Error register stack pointer
8107
Ethernet
8093-8094
Fenced registers
8173-8174
Immediate I/O update
8105-8106
Indirect ROUTE
LI/LIO configuration and status
8095, 8097-8098
8119-8163
Primary processor control register
8176
Safeguard rung
8165
Scan time control
Scan time value
Serial comm. port configuration
Tick register
Group #2 Control Register Function
(Read Only Registers)
Error registers
Memory
8166-8167
8172
8099-8100
8164
Register Number
8183-84
8180-8182, 8187, 8189-8192
Primary processor status
8186
Processor type and revision level
8188
Users can examine control registers and their individual bits by viewing them on a
programmer or by using them as contacts within the ladder program.
Chapter 13 - Processor Control Registers
Page 13-3
30598-526
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
Altering control register bits with a programming device may affect
actual equipment under control of the programmable control system.
Make sure that all effects of altering control bits are understood prior
to their alteration.
Failure to observe this precaution can result in equipment damage or
personal injury.
If control register bits are to be altered, the DATA mode of a programmer can be used
or the bit can be programmed in the ladder as a coil.
13.2
LISTING OF REGISTERS
8001-8005: Command identifiers (not actual storage registers) which identify the
ASCII output format.
These registers are used as commands to set the format of the Model 450's output data
when the Model 450 is executing a PRINT statement and are not intended as usable
storage registers for other purposes. Available formats include:
•
ASCII in decimal, hexadecimal, or binary
• “Raw binary” data
• Repeated character strings
Refer to the programming device's instruction bulletin for programming information
and Section 10.2 for application information.
8006:
Acts as the command identifier (not an actual storage register) for
the ASCII input format. See Chapter 10.
8007-8092:
Not available.
13.2.1 GROUP #1: Read/Write Registers
8093:
The 16-bit data field stores the SY/MAX drop number on Ethernet indicated
by the rotary and DIP switches. Refer to Section 15.5.3 for Ethernet NIM
Register 3 (similar to register 8093). The 16-bit Status field stores the version
for the Ethernet communications software. Status field information is stored
in a Binary Coded Decimal (BCD) format. The first two BCD digits (most
significant byte) show the major software revision, followed by an implied
decimal point. The last two BCD digits (least significant byte) indicate the
minor revision of the software. For example:
17
32
0
0
0
0
0
0
0
1
0
Major Rev.
1
0
0
1
0
0
0
0
0
0
2
Minor Rev.
Figure 13-1 Register 8093 Status Field
Chapter 13 - Processor Control Registers
Page 13-4
30598-526
Register 8093's status field indicates a major software revision of 1 and a
minor revision of 20. This is read as revision 1.20 of the Ethernet
communications software.
8094:
Ethernet Port Comms Error. In those cases where register 8175 contains
error code 929, register 8175 points to register 8094. Register 8094
contains additional information about the nature of the ETHERNET
Port Comms error (see Section 15.7).
8095:
Acts as a pointer for the indirect ROUTE LIST using the ETHERNET
(Channel 3) port. See Section 5.5.
8096:
Not used.
8097:
Acts as a pointer for the indirect ROUTE LIST using the PRGMR
(channel 1) port. See Section 5.5.
8098:
Same function as 8097, except controls COMM (Channel 2) port.
8099:
PRGMR port (channel 1) attributes. Refer to the following tables
and Chapter 10 for bit explanations of this register.
Table 13-2: Register 8099, Bits 1-4 (Baud Rate)
Bit Pattern
Baud Rate
0000
50
0001
110
0010
300
0011
1200
0100
2400
0101
4800
0110
9600
0111
19200
Table 13-3: Register 8099, Bits 5-6 (Word Size)
Chapter 13 - Processor Control Registers
Bit Pattern
Word Size
00
8 bit
01
7 bit
10
6 bit
11
5 bit
30598-526
Page 13-5
Table 13-4: Register 8099, Bits 7-8 (Parity)
Bit Pattern
Parity
00
Even
01
Odd
10
No parity
11
No parity
Table 13-5: Register 8099, Bits 9-10 (Stop Bits)
Bit Pattern
Stop Bits
00
1
01
1.5
10
2
11
2
Table 13-6: Register 8099, Bit 11(ASCII Output Control Function Bit)
(see Section 10.2.5)
Bit Pattern
Function
0
XON/XOFF Disabled
1
XON/XOFF Enabled
Table 13-7: Register 8099, Bit 12 (ASCII Input Null (00) Characters)
Bit Pattern
Function
0
Null ignored
1
Null stored
Table 13-8: Register 8099, Bit 13 (Transmit Periodic DLE/ENQ
Stream—SY/MAX Protocol-Handshaking Characters)
Bit Pattern
Function
0
Suppressed
1
Active
Chapter 13 - Processor Control Registers
Page 13-6
30598-526
Table 13-9: Register 8099, Bit 14 (Mask 8th Bit of ASCII Output
Word: Reset Model 450’s 8th ASCII Output Bit to 0)
Bit Pattern
Function
0
No mask
1
Mask 8th bit
Table 13-10: Register 8099, Bit 15 (CTRL-C Flag)
Bit Pattern
Function
0
Not received
1
Received
Table 13-11: Register 8099, Bit 16 (Clear Queued ASCII Input
Buffers)
Bit Pattern
Function
0
Inactive
1
Active
8100:
COMM (channel 2) attributes—same bit patterns as 8099.
8101 to 8104:
Not used.
8105:
Pointer to the first register for Immediate I/O Update instruction. See
bit 7 of register 8176 later in this section.
8106:
Register block size for the Immediate I/O Update instruction. See bit
7 of register 8176 later in this section.
8107:
Pointer to the Error Register Stack (16 register block). Can be set by
entering a register number point to the beginning of a block of 16
registers that preserve error codes appearing in register 8175.
Reserve this 16-register block—which can be assigned to any
register between 1 and 3985—exclusively for use as the Error
Register block.
In normal operation, error codes appearing in register 8175 are
zeroed when the fault is cleared. Register 8107 provides a valuable
troubleshooting aid by allowing the user to create a history of error
codes.
As each new error is received, it is inserted into the first register
position in the 16-register stack. Errors already in the stack are
pushed down one position. When the stack is full, the oldest error is
pushed out of the stack and is lost.
For example, if a particular error code occurs more than once
consecutively (that is, if ERROR 20001 enters the stack four
Chapter 13 - Processor Control Registers
30598-526
Page 13-7
consecutive times), it only appears once in the stack. Thus, multiple
failures may only produce one error code in the stack if the failures
are all caused by the same error code condition.
8108:
Clock - Command Register (1 = Set; 0 = Run).
8109:
Clock - seconds (0-59).
8110:
Clock - minutes (0-59).
8111:
Clock - hours (0-23).
8112:
Clock - day of week (1-7; 1 = Sunday).
8113:
Clock - day of month (1-31).
8114:
Clock - month (1-12).
8115:
Clock - year (1980-2079).
8116-8118:
Not used.
8119:
Last register defined for channel 2 of the 15th LI module (or
Channel 4 of the 7th LIO module; see the LIO instruction bulletin
#30598-782).
8120-8163:
For use in communicating with Local Interface modules. Each
2-channel LI module utilizes up to 3 processor control registers for
monitoring I/O and system control communications. Registers
8161-8163 of this group are reserved for the first LI module as
follows:
(8161)
Control Register for channel 2 of the first Local Interface module,
used to monitor and control the conditions of the remote racks that
contain the register modules and I/O connected to channel 2 of this
local interface. The bit pattern of 8161 is as follows:
Bits 1-8: The HALT/RUN bit can be set to force the corresponding
drop to shut down.
Bit 9: The FREEZE/RESET bit allows the user to choose if the
channel should freeze (remain in last previous state) or reset (turn
OFF) when a communication error exists. 1=FREEZE, 0=RESET.
Bit 10: XMIT FAULT TOLERANCE bit. When set to “1”, allows up
to 10 attempts to re-establish communication prior to generating an
error. When this bit is reset to “0”, only three attempts are allowed.
Bit 13: The FAILURE OVERRIDE bit allows the system to
continue operation should communication to the remote I/O racks
fail. 1 = Failure Override Mode; 0 = Normal Operation.
Bit 15: AUTO RESTART bit. When set, automatically attempts to
reestablish communication should an I/O fault occur on the channel.
1 = Auto Restart ON; 0 = Auto Restart OFF. Must be set in
conjunction with bit 13 to be practical.
The remainder of the bits in register 8161's data field are unused.
(8162)
Channel 1 of the first Local Interface module. (This register
performs the same function as register 8161, except that it monitors
and controls Channel 1.)
(8163)
Error code control register for the first local interface. Refer to
Appendix A for the error code table.
8164:
A 2.5 ms “tick” register. Increments every 2.5 milliseconds
Chapter 13 - Processor Control Registers
Page 13-8
30598-526
regardless of the RUN/HALT status of the Model 450. All 32 bits of
the register are used to keep track of accrued time. Maximum
accrued time is 4 months. This register is reset upon its “rollover” or
power up and can be preset by a programmer or from the ladder
program. Whenever the data field of register 8164 is reset to zero,
the status field also reverts to zero.
If the contents of register 8164 are used in an IF or LET rung,
register 8164 should be “ORed” with zero before performing the
data compare (IF) or transfer (LET). This effectively masks off the
16 bits of the status field, and prevents an overflow condition from
occurring if any of these bits are nonzero.
EXAMPLE: LET S3995=S8164 executes as expected until register
8164 exceeds +32,767, at which time the contents of register 3995
stops changing. Bit 18 (overflow) of register 3995 is set to indicate
the overflow condition. If register 3995 should remain
“free-running,” use the following rung:
LET S3995 = S8164 v 00000
After reaching +32,767, the contents of register 3995 changes to
-32,768 then decrements back to zero.
8165:
Used to establish safeguard rung parameters (see Section 6.8). Also
contains the number of “ticks” remaining before the next timed
interrupt is due to be called.
8166:
Programmable minimum scan-time register. A positive number
entered into this register establishes the minimum CPU ladder
program scan time, to a resolution of 2.5 milliseconds. The Model
450 executes the user program followed by a series of “idle”
instructions until the minimum scan time has elapsed. The desired
scan time can be entered in 2.5 ms increments that are rounded up.
For example, entering a minimum scan time of 98, 99 or 100 ms
results in a ladder program scan time of not less than 100 ms and not
more than 102.5 ms. Any scan time entered is subject to being
increased by the I/O update time, plus the 5 ms port servicing delay.
8167:
This register contains the programmable scan limit when the special
safeguard rung (TLET S8165) is not used. When the scan time in
milliseconds exceeds the contents of this register, the processor halts
and generates ERROR 970. Maximum allowable scan time is 32.765
seconds. If this register contains zero, the scan time is limited to 1
second. If this register contains a value larger than 1 second (1000),
it automatically is reset to zero (that is, 1 second) upon power up.
Accuracy is within 2.5 milliseconds, rounded up.
8168:
Communications monitor timeout. This register defines the time
allocated for receiving a reply to a READ, WRITE, or ALARM rung
before declaring a message timeout and setting bit 23 of the
communication status register. Bits 1-4 are used with the PRGMR
(Channel l) port, bits 5-8 with the COMM (Channel 2) port, and bits
9-12 with the ETHERNET (Channel 3) port.
The following table identifies the time interval range for bits in the
8168 register and is valid for all ports:
Chapter 13 - Processor Control Registers
30598-526
Page 13-9
Table 13-12: Register 8168, Bits 1-4, 5-8, and 9-12
Bit Pattern
(Bits 1-4 for PRGMR,
Bits 5-8 for COMM,
Bits 9-12 for ETHERNET)
8169:
Time Count in Milliseconds
0000
0 to 250
0001
250 to 500
0010
500 to 750
0011
750 to 1000
0100
1000 to 1250
0101
1250 to 1500
0110
1500 to 1750
0111
1750 to 2000
1000
0 to 2000
1001
2000 to 4000
1010
4000 to 6000
1011
6000 to 8000
1100
8000 to 10,000
1101
10,000 to 12,000
1110
12,000 to 14,000
1111
14,000 to 16,000
This register assigns the baud rate for the Model 450's two
communication ports. The first half of this register's data field is divided
into two groups of 4 bits each. Each group of bits contains the baud rate
for an individual port (channel).
The following table lists the channel-to-bit association for the PRGMR
(Channel 1) port and the COMM (Channel 2) port.
Table 13-13: Register 8169, Bits 1-4 and 5-8
Bit Pattern
(Bits 1-4 for PRGMR,
Bits 5-8 for COMM)
8170:
Baud Rate
0000
50
0001
110
0010
300
0011
1200
0100
2400
0101
4800
0110
9600 (default)
0111
19200
Only bit 16 of register 8170 is used; it activates the communication
completion feature of the Model 450. Bit 16 of this register is also called
the task swap enable/disable bit. If the bit is set to 1 by the user,
Chapter 13 - Processor Control Registers
Page 13-10
30598-526
End-of-scan communication servicing could be extended an additional 5
milliseconds to allow for complete message servicing. (See Sections
5.6.1 and 14.2.2.)
8171:
Contains the remainder of the most recent integer division performed.
Remainder's sign (+) agrees with the numerator.
8172:
Processor scan time in milliseconds. Scan time is the length of time
required for the Model 450 to make one pass through user memory and
includes end-of-scan I/O update and communication port servicing
times.
8173:
Fenced registers ending address (as entered by user). The ending point
of the block of registers accessible via the COMM port (Channel 2).
8174:
Fenced registers beginning address (as entered by the user). The
beginning point of the block of registers accessible via the COMM port.
See Section 6.13 for more information on the use of fencing.
8175:
Error code storage. Refer to Appendix A for descriptions of these codes.
This register contains the last ERROR NUMBER which occurred. If
there is more than one error, the most serious or highest priority error
code is stored. The contents of register 8175 are cleared after a
HALT-to-RUN keyswitch toggle, provided the cause of the error was
eliminated. An exception to this are errors in serial communication,
which clear as soon as a successful communication message has been
exchanged through the indicated port. Errors occurring in register 8175
can be preserved in an “error register stack” using register 8107.
8176:
Primary Processor Control Register. Table 13-14 explains each bit in
this register, showing soft key equivalents for SY/MATE Plus Software
from the ONLINE/STATUS/PLC OPER screen.
The individual bits of register 8176 are used for system monitoring and
control. Because it is possible to alter the state of the data field bits, the
user has the capability to change specified processor conditions. These
bits can be altered by a CRT programmer, SFW Software's DATA
ENTER mode, SY/MATE Plus Software’s ONLINE/ DATA mode or by
a ladder rung in memory. Bits 17-32 are read-only. Bits 1 through 16 are
alterable. Exceptions to this involve the use of certain memory write
protection modes. See Chapter 6, “Security Features.”
Table 13-14: Register 8176, Bits 1-32
Bit
Chapter 13 - Processor Control Registers
Purpose
(SY/MATE Plus Soft Key)
1
Processor HALT (F1)
2
Processor Disable Outputs (F2)
3
Processor HALT/RUN (F3)
4
Memory Protection (F4)
5
Force Inhibit (F5)
6
Register Protection (F6)
7
Immediate I/O Update
8
IF Rung Overflow Flag
9
Control Register Data Corruption Flag
10
MATRIX or ARRAY Overflow Flag
11
Immediate Communications Update, Ch 1
30598-526
Page 13-11
Table 13-14: Register 8176, Bits 1-32
Purpose
(SY/MATE Plus Soft Key)
Bit
12
Immediate Communications Update, Ch 2
13
Immediate Communications Update, Ch 3
14
Not used
15
Port and Route Edit Lockout Control
16
Inhibit Coil Address
17
Low Internal or Power Supply Battery
18
OPEN Contact Address
19
SHORT Contact Address
20
Not used
21
First Dummy Scan
22
Second Dummy Scan
23
Normal Program Scan
24-31
32
Not used
Internal Battery Low
REGISTER 8176 READ/WRITE BITS
The following bits can be altered by the user. Note that Bits 1-6 can be
altered from the ONLINE/STATUS/PLC OPER screen in SY/MATE
Plus Programming Software; soft keys are indicated in Table 13-13.
Bit 1: When this bit is set ON, it prevents the Model 450 from scanning
the ladder program. The processor can be placed in the HALT mode by
either putting the processor keyswitch in the HALT position or by
programming and energizing coil 8176-1 in the ladder diagram
program. Toggling the keyswitch into and out of HALT or setting and
resetting 8176-3 resets this bit to OFF.
Bit 2: When this bit is set ON, the processor operates in the DISABLE
OUTPUTS mode. The processor can be placed in the DISABLE
OUTPUTS mode either by putting the keyswitch in the DISABLE
OUTPUTS position, or by programming and energizing coil 8176-2 in
the ladder diagram program.
Bit 3: This bit operates as a remote HALT/RUN switch (1 = Processor
Halt; 0 = Processor Run). The HALT condition overrides the RUN
condition. Putting the keyswitch in HALT or setting bit 3 to “1” halts the
processor. To put the processor in RUN, however, the keyswitch must be
in RUN or RUN/PROGRAM and bit 3 must be “0”.
NOTE
Performing a CLR PLC operation does NOT reset bit 3; once set, it must be
individually reset by the user.
Bit 4: Setting this bit to “1” protects user memory from being altered via
the COMM port (Channel 2) and ETHERNET Port (Channel 3). For
further details refer to Section 6.10. 1 = Memory Protected; 0 = Memory
Accessible.
Chapter 13 - Processor Control Registers
Page 13-12
30598-526
Bit 5: Setting this bit to “1” inhibits the forcing of any I/O via the
COMM port and ETHERNET port (Channel 3). 1 = Force Inhibit;
0=Forcing Allowed. I/O can still be forced using programming
equipment through the PRGMR port (Channel 1). (See Section 6.11.)
Bit 6: In addition to the fencing capabilities of the Model 450, setting
this bit protects any registers from being altered via the COMM port and
ETHERNET port (Channel 3). Registers can still be forced or altered
through the PRGMR port using programming equipment. 1 = Register
Protect; 0=Register Accessible. (See Section 6.12.)
Bit 7: Activates the Immediate I/O Update feature of the Model 450.
When the Model 450 encounters a rung containing an energized bit
8176-7, it momentarily stops scanning the ladder program and updates
the external I/O that are defined by registers 8105 and 8106 (inputs are
written to the image table; outputs are read from the image table). Upon
completion of I/O updating, normal scanning resumes. If either 8105 or
8106 is set to “0”, only the local digital I/O are updated (this default
does not apply to local register modules).
Bit 8: The Model 450 is capable of complex COMPARE functions (for
example, IF S50 = S60 x S70...). If the integer or floating point math
operation within a COMPARE statement results in a value beyond the
processor's capability, bit 8 is set to “1”. This bit is reset to “0” at the
beginning of each new scan.
NOTE
If register 8106 (the register block size for the Immediate I/O Update
instruction) causes the range of the Immediate I/O Update to exceed the
last register in the processor (4000), no immediate I/O update will occur.
Bit 9: This bit is set if the Model 450 detects a control register checksum
error upon power-up. ERROR 900 or 901 appears in register 8175
unless overwritten by a higher-priority error. Also indicates that all
control registers have been set to their default values and that all data
storage registers have been reset to “0”. Typically this bit is set if battery
backup has failed for any length of time. Bit 9 is reset by a CLEAR PLC
or DATA ENTER operation.
Bit 10: This bit is set to “1” if an overflow occurs during a MATRIX or
ARRAY operation and is reset at the beginning of a new MATRIX or
ARRAY rung.
Bit 11: When this bit is set to “1”, the Model 450 interrupts the normal
ladder scan and performs up to 5 milliseconds of servicing on any
pending communication in the buffer for the PRGMR (Channel 1) port.
Normal ladder scan continues upon completion of the communication
servicing.
Bit 12: Performs the same function as bit 11, except for the COMM
(Channel 2) port.
Bit 13: Performs the same function as bit 11, except for the ETHERNET
(Channel 3) port.
Bit 14: Not used.
Bit 15: Setting this bit to “1” prevents program editing through either
Chapter 13 - Processor Control Registers
30598-526
Page 13-13
port and any route by any device other than the device which set the bit
to “1”. (See Section 6.5.)
Bit 16: This “inhibit rung” can be placed within the main ladder
program to prevent altering and/or viewing of certain rungs. (See
Section 6.7.)
REGISTER 8176 READ-ONLY BITS
The following bits cannot be altered by the user in any way, however,
these can be examined as contacts in the program:
Bit 17: This bit is set to “1” when either the Model 450's internal lithium
battery or the power supply batteries are low. This bit can be used in
conjunction with bit 32 of this register which signifies that only the
internal lithium battery is low. See Section 12.1.2 for more information
about low battery indication.
Bit 18: “OPEN”. This bit is always de-energized, and is used to signify
an OPEN in the ladder program.
Bit 19: “SHORT”. This bit is always de-energized. A normally-closed
contact in the ladder program uses this bit to signify a SHORT.
Bit 20: Reserved for processor internal use.
Bit 21: Set to “1” during the first power-up dummy scan.
Bit 22: Set to “1” during the processor's second power-up dummy scan.
Bit 23: This bit is set to “1” whenever the Model 450 is scanning the
ladder program after executing the first two dummy scans.
Bits 24 to 31: Reserved.
Bit 32: Set to “1” when the voltage of the Model 450's internal lithium
battery falls below the point needed to maintain memory in RAM. This
bit can be used in conjunction with bit 17 to provide a better idea of
which battery is defective or missing. See Section 13.1.2 for more
information about low battery indication.
8177:
Password register. Contains a value that determines if register 8178
controls editing, forcing, and register write restrictions. If a zero is in
register 8177, then any value in register 8178 is ignored. When reading
register 8177, if a zero is stored then a zero is displayed. If any other
value than zero is stored in register 8177, then “-1” is displayed to keep
the password a secret. See Section 6.9 for information.
8178:
Restriction register. Each of the first 12 bits in this register determines
which security feature is enabled for the PRGMR, COMM, and the
ETHERNET port. See Table 13-15 to determine which security is in
effect when the indicated bits are set to “1”.
Chapter 13 - Processor Control Registers
Page 13-14
30598-526
Table 13-15: Register 8178, Bits 1-12
Bit
Security Measure in Effect When Bit is Set to “1”
1
Restricts priority writing t registers through the PRGMR port
2
Restricts the forcing of registers through the PRGMR port
3
Restricts non-priority writing to registers through the PRGMR port
4
Restricts program editing through the PRGMR port
5
Restricts priority writing to registers through the COMM port
6
Restricts the forcing of registers through the COMM port
7
Restricts non-priority writing to registers through the COMM port
8
Restricts program editing through the COMM port
9
Restricts priority writing to registers through the ETHERNET port
10
Restricts the forcing of registers through the ETHERNET port
11
Restricts non-priority writing to registers through the ETHERNET port
12
Restricts program editing through the ETHERNET port
NOTE
The CLEAR PLC operation is always allowed through the PRGMR port.
13.2.2 GROUP #2: Read-Only Registers
8179:
8180:
8181:
8182:
8183:
8184:
8185:
8186:
Not used.
Percentage of memory used on high-speed scanning processor (compiled
user memory).
Indicates the total amount of ladder program memory (MSW) in bytes
available to the user. This figure reflects intermediate memory.
Indicates the amount of ladder memory (LSW) in bytes that is available for
use. This figure reflects intermediate memory.
Stores information on some types of errors. See Appendix A.
Same as 8183. See Appendix A.
Indicates the number of rack addressing rungs that are programmed into the
Model 450.
Primary Processor Status Register. The individual bits of this register are
used for indicating certain processor conditions. These bits can be examined,
but cannot be altered in any way. See Table 13-16 for an explanation of each
of the bits in register 8186.
Table 13-16: Register 8186, Bits 1-16
Bit
Model 450 Status When Bit is Set to “1”
1
Halted
2
Outputs disabled
Chapter 13 - Processor Control Registers
Page 13-15
30598-526
Table 13-16: Register 8186, Bits 1-16
Bit
Model 450 Status When Bit is Set to “1”
3
Running
4
MEMORY LED is ON
5
FORCE LED is ON
6
I/O LED is ON
7
Key is in HALT position
8
Key is in DISABLE OUTPUTS position
9
Key is in RUN position (if bits 7, 8, and 9 are “0”, then key is in
RUN/PROGRAM position)
10
WRITE PROTECT LED is ON or FLASHING (hardware or software
security is enabled)
11
BATTERY LOW LED is ON or FLASHING
12-16
Not used
8187:
Indicates the number of ladder rungs that are programmed in user
memory.
8188:
The three most significant digits of the 16-bit data field of this
register identify the type of Model 450. The least significant digit
identifies the major revision level. (that is, for the 4K version,
revision 4.XX, the digits are 4524; for the 8K version, revision
4.XX, the digits are 4534). The 16-bit Status field stores both the
major and minor revisions for the Control Processor software. The
data for this field is stored in a Binary Coded Decimal (BCD)
format. The first two BCD digits (most significant byte) show the
major software revision, followed by an implied decimal point. The
last two BCD digits (least significant byte) indicate the minor
revision of the software. For example:
0
0
0
0
0
0
0
4
0
Major Rev.
1
0
0
1
0
0
0
0
0
0
2
Minor Rev.
Figure 13-2 Register 8188 Status Field
Register 8188’s status field indicates a major software revision of 1
and a minor revision of 20. This is read as revision 4.20 of the
control processor software.
8189:
Memory word information. Bits 1 through 8 indicate total
intermediate memory available in bytes (MSW: Most Significant
Word). Bits 9 through 16 indicate the number of bytes that make up
a user word.
Chapter 13 - Processor Control Registers
Page 13-16
30598-526
8190:
Total intermediate memory available in bytes (LSW: Least
Significant Word).
8191:
Intermediate memory used in bytes (MSW).
8192:
Intermediate memory used in bytes (LSW).
Chapter 13 - Processor Control Registers
30598-526
14
Page 14-1
TECHNICAL DATA
This chapter provides supplementary technical details on memory use, scan speed, and
general processor operation.
14.1 MEMORY UTILIZATION
The Model 450 contains two copies of the user memory: an intermediate code memory
and a compiled code memory. Intermediate code is the “universal language” that all
SY/MAX programmers and processors “speak”, while compiled code allows for fast
program execution.
Since these two memories reside in separate locations, each has its own allocated
space. Either memory can be the limiting factor for the user program size, depending
on which instructions are used. The programming device's status screen displays the
amount of intermediate memory used, as well as the amount of available memory.
The amount of compiled memory used is monitored in register 8180 as a percentage of
the total available memory. As the user program is developed, available memory in the
compiled area decreases, indicated by register 8180.
As shown in Table 14-1 and Table 14-2 on the next two pages, compiled memory use
is generally greater than intermediate memory used for a given instruction. Thus
compiled memory space will usually be consumed faster than the intermediate
memory space. As the size of the program increases, both registers 8180 and the
“MEMORY USED” display on the status screen of the programming device need to be
monitored to determine the remaining memory space.
The following sections explain memory use for relay circuits, general instructions, and
IF/LET/MATH instructions.
14.1.1 Relay Circuits
In general, the amount of memory required for relay circuits is determined by counting
the number of contacts, parallel branches, and coils in each rung. A contact or coil
(including its address number), requires 1 word of intermediate memory (the coil
requires 3 words of compiled memory). Spaces do not require any words of memory.
The sample rung in Figure 14-1 requires 11 words of intermediate memory and 13
words of compiled memory (*), as illustrated by the numbers associated with each
contact and output:
1
2
3
4
11
(11-13)*
5
8
9
6
10
7
PARALLEL BRANCHES (4)
Figure 14-1 Rung Using 11 Words of Intermediate Memory
and 13 Words of Compiled Memory
Chapter 14 - Technical Data
Page 14-2
30598-526
Each rung of intermediate memory also requires an additional 1/3rd of a word. This
1/3rd word cannot be represented by the “Memory Used” display on the programmer.
For example, if a contact and a coil are added to user memory, the programmer may
indicate that 3 words of intermediate memory were consumed. The third word here is
the fractional (1/3rd) word rounded up to a whole word.
14.1.2 General Instructions
Table 14-1 shows memory use for most Model 450 instructions. See Section 14.1.3 for
special considerations on the IF, LET, and math functions. INT refers to intermediate
memory, while COMP refers to compiled memory. Each instruction will consume the
indicated number of words from the respective memories.
Table 14-1: Memory Use (General Instructions)
Words of
Memory Used
INT
Words of
Memory Used
COMP
Contact
1
1
Parallel Branch
1
1
Coil
1
3
Coil, Latch/Unlatch
1
2
Coil, Transitional
1
5
Master Control Relay
1
3
Timer
6
7
Counter
6
8
Shift / FIFO Register (Sync./ asynch, respectively)
6
5
MARK/GOTO/MARK ST. SUB
4
1
GOSUB
4
3
RETURN/RTN
3
1
Register READ/WRITE
61
4
ALARM Message
5*
4
Print ASCII
22
33
Immediate I/O or Communications Update
1
1
Instruction
GENERAL RUNGS
SUBROUTINES
PRIORITY COMMUNICATIONS
1
2
3
Chapter 14 - Technical Data
Add one word per route.
Add one word per register or one word for each two characters.
Add one word if more than three registers or ALPHA boxes, two words if more than six registers or
ALPHA boxes.
30598-526
Page 14-3
14.1.3 IF, LET, and Math Instructions
In an IF or LET instruction, the amount of memory required is a function of the type(s)
of operation being performed. In addition to intermediate memory (INT) used, Table
14-2 also shows entries for compiled memory (COMP A and COMP B). From Table
14-2, any IF or LET statement (including matrix) requires a fixed quantity of words for
the basic instruction, plus one or more additional words for each addition, subtraction,
AND, OR, or EXCLUSIVE OR performed in the horizontal box.
Table 14-2: Memory Used (IF, LET, and Math Instructions)
Words of
Memory
Used
INT
Words of
Memory
Used
COMP A
Words of
Memory
Used
COMP B
LET (data transfer)
3
5
21
LET (matrix data transfer)
5
5
4*
IF (compare)
3
5
3*
IF (matrix compare)
5
5
4**
AND/OR/XOR
1
2
1
Binary-to-BCD (BCD), BCD-to-Binary (BIN)
1
-
1
Addition/Subtraction
1
2
1
Multiplication/Division/Square Root
1
-
1
12
1
Instruction
LET, IF, AND,OR
INTEGER MATH
FLOATING POINT MATH
Addition/Subtraction/Multiplication/Division/Square
Root/Sine/Cosine/Base 10 and Base E Logarithms/
Y**X
1
2
If the first number in a LET or IF box is a floating-point constant, then one extra word of memory is used.
If any number in a LET or IF box is a floating-point constant, then two words of memory are required.
In Table 14-2, the COMP A column should be used when an IF or LET box contains
only integer values and performs ONLY the following operations: compare (=, ≠, <,
≥), addition, subtraction, logical AND, OR, or EXCLUSIVE OR.
The following sample rung illustrates this memory use:
0003
LET S0101 = S0201 - 00010
01
Chapter 14 - Technical Data
Page 14-4
30598-526
This rung requires a total of five words of intermediate memory: one word for the
contact, three words for the basic LET itself, and one word for the subtraction
operation, as well as eight words of compiled memory (one for the contact, five for the
basic LET, and two for the subtraction). If the above rung was changed to a MATRIX
LET, the intermediate memory consumed would increase to seven words, while the
compiled memory would remain at eight.
Use the COMP B column in Table 14-2 whenever a floating-point operation is used
within an IF or LET box or if the box includes any operation other than compare,
addition, subtraction, AND, OR, or EXCLUSIVE OR. If an IF or LET box meets this
condition, word usage for the entire box should be calculated using the COMP B
column. The following sample rung illustrates this procedure.
0003
LET S0101 = S0201 - 00010 x S0005
01
Since this LET box now contains multiplication, the rung requires a total of six
intermediate memory words: (three for the basic LET, one for the contact, one each for
the subtraction and multiplication operations, and five words of compiled memory
(one for the contact, two for the basic LET, and one each for the subtraction and
multiplication)).
14.2 SCANNING TECHNIQUES
14.2.1 General Information
The Model 450 contains a high-speed scan processor, math coprocessor, and control
processor. The scan processor executes certain types of tasks in parallel and executes
the ladder program faster than the control processor for better throughput. The Model
450 control program execution time is based primarily on three factors:
1. Scan time of the user ladder program itself.
2. External I/O Update time (including forcing, if active).
3. Servicing of external communications.
The Model 450 makes use of an image table memory to hold the state of the first 4000
registers to make logical program decisions. The contents of the image table are
exchanged with the external I/O. The present I/O state is transferred to the image table
at the end of every scan.
The time necessary to perform this external I/O update is a function of the number of
I/O registers assigned to other modules in the system and how many of these registers
are fragmented (containing both input and output data in the same register).
Servicing of external communications is normally limited to 5 msec per scan unless
the user sets bit 8170-16 or requests an immediate communications update; refer to
Section 14.2.2.
Chapter 14 - Technical Data
30598-526
Page 14-5
14.2.2 Scanning Speed
In addition to the time needed to execute the ladder program, the scan time of the
Model 450 is composed of the time needed to update the external I/O plus the time to
service the communication ports. In general, the following equation can be used to
estimate scan speed:
ST = [K x (LUP)] + [0.04 x (ER)] + [0.45 x (FER)] + COM
Where:
ST
K
LUP
ER
FER
COM
is the SCAN TIME in milliseconds
is the LADDER SCAN SPEED per K of user program (estimated from
execution times in Table 14-3 on the next page).
is the LENGTH of USER PROGRAM in thousands of words
(K words).
is the number of EXTERNAL REGISTERS.
is the number of FRAGMENTED EXTERNAL REGISTERS, and
is the time required to service the three communications ports.
Table 14-3 on page 14-6 provides a list of typical operations and an approximation of
associated execution times. For operations not listed, execution times are difficult to
estimate because of the complexity of certain operations. Table 14-3 on page 14-6
provides relative comparison times, indicating which functions are more
processor-intensive.
The user is advised that scan times may not be consistent, depending on rung true/false
conditions and the amount of communications traffic from Table 14-3 on page 14-6;
numerous instructions are listed which are not executed when their input logic is false.
For example, executing a repeat MATRIX LET of 100 registers will increase scan time
by almost 10 msec when true. The PID instruction is also shown to be scan-intensive.
Scan time is also clearly affected by non-sequential program control instructions such
as GOTO, GOSUB, and TIMED INTERRUPT. For scan-critical applications, users
should be aware of the scan impact of worst-case logical execution paths. Register
8166 (minimum scan time register) can be used to “smooth out” widely varying scan
times.
Refer to Section 14.2.3 for information on optimizing scan speed.
NOTES
• It is possible to get a processor HALT condition if the scan time value
becomes more than the maximum scan time.
• When editing while the processor is in RUN/PROGRAM, the program
scan time may increase significantly as discussed below.
When performing an edit while the processor is executing the user program, the
normal processor scan time may be momentarily increased. The increased scan time is
a one-time occurrence and is caused by the processor loading the new rung(s) into the
location in memory where the program resides.
Depending upon the program complexity, the type of edit performed, and the memory
location where the edit takes place, the scan time may increase several hundred
milliseconds. The longer and more complex the program (for example, multiple
MARK rungs, GOTO, and GOSUB commands) and the earlier in memory that the edit
takes place, the greater the scan-time increase.
Chapter 14 - Technical Data
Page 14-6
30598-526
For any given program, the worst-case scan time can be measured by monitoring
register 8172 (scan-time register) while performing an insert of rung 1. If an excessive
increase in scan time cannot be tolerated while scanning the user program, edits can be
prevented by leaving the keyswitch in RUN. Alternately, register 8167 (programmable
scan limit) may be preset to halt program execution based on a user-specified
maximum scan time limit.
A processor which is called upon to service its communications ports (such as when a
programmer is connected) will also experience a worst-case scan time extension up to
5 msec at End of Scan (EOS). Note this is 5 msec total for all 3 ports. An Immediate
Comms Update instruction also exists (bit 11, 12, or 13 of register 8176) which allows
the user to interrupt scanning to service the communication ports more frequently,
allowing better Comms throughput at the expense of longer overall scan time.
In addition, a special control bit (8170-16) may be set by the user to cause the
processor to completely finish servicing an entire message block at the end of scan.
This ensures a given message block will have all registers incorporated into the image
table at the end of the same scan. The potential scan time impact is to add on up to an
extra 5 msec (10 msec total) at EOS. Refer to Sections 5.6.1 and 13.2 for more about
Register 8170-16.
Table 14-3: Execution Times for Typical Operations
(Page 1 of 2)
Instruction to be Executed
Execution Time in Microseconds
(except where noted)
All Model 450s
Contact1
0.8
Coil (including MCR and latch/unlatch)
1.4
Transitional coil
1.4
Timer
(Disabled/Enabled)
14.4/18.2
Counter
(Disabled/Enabled)
20.5/23.0
IF1
(Integer/Floating Point)
12.0/122
LET1
(Integer/Floating Point)
10.0/128
Matrix LET1
(Integer)
Chapter 14 - Technical Data
97 per register
Math
(Integer/Floating Point)
Addition
Subtraction
Multiplication
Division
5.3/46.0
5.3/46.0
122/46.4
122/46.4
Logical AND, OR, XOR
3.7
30598-526
Page 14-7
Table 14-3: Execution Times for Typical Operations
(Page 2 of 2)
Instruction to be Executed
Execution Time in Microseconds
(except where noted)
All Model 450s
Shift
96 + 2 per register
FIFO
102 + 2 per register
PID1 (Rev. or Dir.)
740 (typical)
PID1
116 (typical)
(Manual)
Immediate I/O Update2
140 + 40 per register
T WRITE, T READ, T ALARM
133
T PRINT
183 (typical)
SIN/COS/TAN
239
LN/LOG
154
Y**X
352
Add Stat
335
Variance
273
MARK ST SUB
0
MARK
0.5
GOTO1
1.4
GOSUB1
72.0
(with RTN)
External I/O Update Time2
MIX #13
0.8 milliseconds per K of ladder
MIX #24
3.2 milliseconds per K of ladder
#35
2.7 milliseconds per K of ladder
MIX
1
2
3
4
5
320 per 8 local unfragmented registers
per scan
If rung is TRUE up to that point; if FALSE, the instruction is not executed and time is
reduced. See Section 14.2.3, “Rung Execution Algorithm Guidelines.”
123 microseconds per register for Class 8030 Type RIM121 analog input, 75
microseconds per register for Class 8030 Type ROM121 analog output.
Mix #1 is composed of all Boolean rungs.
Mix #2 is 50% Boolean, 34% IF and LET rungs, 8% counters, and 8% timers.
Mix #3 is 80 Boolean, 5% timers, 5% counters, and 10% addition/subtraction.
CONSIDERATIONS FOR “TIME MIXES” #1-#3
• On an average, only 66% of any rung must be executed.
• Boolean assumes an average of two contacts for each coil.
• External I/O Update or communication processing time is not included in any of the
mix execution times.
Chapter 14 - Technical Data
Page 14-8
30598-526
14.2.3 OPTIMIZING SCAN SPEED
In some ways, optimizing the scan speed of a Model 450 processor is no different than
the procedure used for any computing device. For example, the Model 450 program is
compiled from intermediate code into a 64-bit word compiled format that allows rapid
execution by the scanning processor.
While this intermediate to 64-bit compiled code conversion operation is transparent to
the user, the Model 450's instruction set contains scan control instructions like GOTO
and GOSUB that allow skipping over sections of a program that do not require
scanning at a particular time. This “skipping over” process saves scan time and
improves performance (throughput). This simple technique should not be overlooked
when dealing with programs containing sections that do not require constant scanning.
When laying out and programming any system, applying knowledge of how that
system behaves to the system's configuration can optimize its performance.
The next few pages discuss some simple guidelines (most of which have been
previously mentioned in this manual) for economizing scan time.
RACK ADDRESSING GUIDELINES
Minimizing external I/O update time using good rack addressing techniques is
demonstrated by the example in Section 3.6.5. When rack addressing a system
containing Local Interface (LI) Modules, scan speed is optimized by assigning only
those registers necessary for remote I/O operation to an LI. Assigning registers
unnecessarily to an individual LI results in needless end-of-scan register transfers
between the Model 450 and the LI's data storage registers.
The equation in Section 14.2.2 shows that updating an unfragmented register on the
bus requires 40 microseconds. If the conditions of the example in Section 3.6.5 are
used, the unnecessary assignment of all 512 LI module registers decreases throughput:
Update Time for 512 Registers = 512 x 0.04 ms = 20.5 ms per scan, and
the Update Time for 50 Registers = 50 x 0.04 ms = 2.0 ms per scan.
SUMMARY: In the scan time calculations, 18.5 milliseconds is needlessly added to
the scan time for unnecessary updating over the bus. Thus, assign only needed registers
for external I/O to the LI or LIO modules.
When assigning registers to other register modules in the CPU rack, ONLY assign as
many registers as needed by the module. For example, assign only one register to a
16-point digital I/O module, or four registers to a four-channel analog module.
Assigning registers needlessly to the module results in a longer scan time.
EXTERNAL I/O REGISTER GUIDELINES
The equation in Section 14.2.2 demonstrates that the time required to update a register
increases tenfold when the register is fragmented instead of unfragmented. A
fragmented register refers to an external I/O register containing both input and output
points. Thus, when using four-point and eight-point digital I/O modules, lay out the
programmable control system so that all points of a particular external I/O register are
assigned as either inputs or outputs.
Chapter 14 - Technical Data
30598-526
Page 14-9
For example, if a Model 450 is being used in an HRK-type rack (eight-function rack),
both modules associated with an external I/O register should be either inputs or
outputs. This principle applies to remote I/O registers as well.
NOTE
Fragmenting registers forces the processor to make decisions that
consume valuable processing time. These time-consuming decisions can
be eliminated if external I/O registers are made up strictly of inputs or
outputs.
RUNG EXECUTION ALGORITHM GUIDELINES
The Model 450 executes ladder rungs in such a way that elements of conditional logic
may actually be skipped over if the logical outcome of the rung is no longer in doubt.
This applies to logically TRUE as well as logically FALSE rungs.
A good example of this is shown in the following:
IF M0501 =...
The matrix IF instruction shown above only executes if the leading contact is
CLOSED. If OPEN, the matrix IF is skipped over (no pointer information is updated)
and the coil is turned OFF. If the leading contact is CLOSED, the matrix IF is scanned
to determine the state of the coil. If the order of the conditional elements was inverted
(that is, the matrix IF came before the contact), although logically equivalent, the
execution time could increase dramatically for the FALSE condition since in this
configuration the matrix IF would always be executed.
If proven FALSE, the contact is skipped over; the savings in scan time, however,
would be negligible compared to the savings if the matrix IF were not scanned at all.
A similar principle applies to saving processor time for the TRUE condition shown
below:
IF M0501 =...
If the contact shown above is closed, the coil is ON regardless of the condition of the
matrix IF instruction. In this case, the matrix IF does not need to be executed and some
scan time could be saved in the process.
Chapter 14 - Technical Data
Page 14-10
30598-526
However, if the matrix IF and the contact were interchanged, the matrix IF always
executes first. This may have an adverse effect on the rung's execution time.
Another simple rung execution technique can be applied to LET statements. Since the
LET only executes if the rung is TRUE, any initialization constants scanned more than
once will needlessly consume processing time and should be avoided in the user
program.
SUMMARY: When placing a premium on optimizing scan time, examine rungs for
logical equivalence to see if interchanging conditional elements will reduce the
execution time.
SCANNING PROCESSOR VERSUS CONTROL PROCESSOR GUIDELINES
Any functions that cannot be handled by the scanning processor must be “handed off”
to the control processor. Since the control processor is also tasked with handling other
system interrupts, longer scan times can result.
Such multitasking operation makes it very difficult to quantify precise execution times
for these instructions as it cannot be predicted in advance how many other demands
(such as communications handling) are being made on the control processor at the
time of the “hand-off”.
As shown in Table 14-3 on page 14-6, execution times can vary widely. This variation
occurs because some of the instructions are executed by the scan processor while
others must be handled by the control processor. For example, integer addition and
subtraction are handled by the scan processor, while integer multiplication division
and all floating-point operations are handled by the math coprocessor.
Since integer multiplication and division and floating-point math operations are
handled by the math coprocessor, the control processor must act as an intermediary
between the scanning processor and the math coprocessor. While this is occurring, the
scanning processor remains idle until the result is computed. This makes for an
efficient use of processing power.
Keep the following points in mind when comparing the operation of the scanning
processor with the control processor:
• Although GOSUB and RTN instructions have to be executed by the control
processor, their careful use can result in a great savings in throughput.
• Shift register and FIFO operations are executed by the control processor; their
execution times are affected by the number of registers involved.
• Matrix operations must be performed by the control processor and can significantly
influence scan time depending on their size and pointer configuration. Each matrix
operation requires approximately 97 microseconds to calculate a new element.
- When using matrix LET statements, use “level” or “incremental” LETs over
“repeat” LETs wherever possible. This distributes the increased processing time
over many scans.
- For matrix IFs, use “level” instead of “repeat” whenever possible. If “repeat”
must be used, follow the principles given in the previous Rung Execution
Algorithm Guidelines section to save scan time.
Chapter 14 - Technical Data
30598-526
14.3
Page 14-11
THEORY OF OPERATION
The Model 450 consists of several major subsystems, all under the control of a central
processing unit (refer to Figure 14-2 while reading this section).
Floating-Point
Math Coprocessor
(Motorola 68881)
Intermediate
User
Memory
Real-Time Clock
Serial
Communication
Interface
Compiled
User
Memory
CONTROL
PROCESSOR
(Motorola 68010)
Scan
Processor
(AMD 29116)
Ethernet
Interface*
Keyswitch and
Status LEDs
Slot #1
Detect
SY/MAX
Bus
Interface
Image
Memory
3-State
Control
* See Figure 14-3 for a block diagram of
Ethernet components.
SY/MAX BUS
Figure 14-2 Block Diagram of Model 450 Operation
The control processor is a Motorola Type 68010 and is responsible for performing
and/or coordinating all functions of the Model 450, including interrupts and error
conditions from the serial communications interface, SY/MAX bus, scan processor,
and math coprocessor.
Scanning in the Model 450 processors is performed by an Advanced Micro Devices
(AMD) Type 29116 processor utilizing a 64-bit compiled word.
Floating-point operations are performed by a Motorola Type 68881 math coprocessor.
The system clock runs at 8 MHz.
Each subsystem within the Model 450 is briefly explained in the following paragraphs.
Control Processor: This device either performs or coordinates all of the processor's
functions, including communication via the two serial RS-422 ports. The control
processor also compiles the ladder program in the Compiled User Memory, controls
interrupts and error conditions, and handles SY/MAX bus duties.
Math Coprocessor: The coprocessor allows the Model 450 processor to perform
floating-point math operations.
Chapter 14 - Technical Data
Page 14-12
30598-526
Scan Processor: Performs computation of the Model 450's output states based on the
current condition of inputs and registers.The computations and sequence in which they
are performed are determined by the Compiled User Memory. The I/O states and
register values are obtained from the Image Table Memory.
Image Table Memory: The Image Table Memory consists of battery-backed RAM
that provides 16-bit data and status fields for user registers 1 through 4000 and control
registers 8093 through 8192. Parity protection is provided for this memory. This
memory contains both the internal and external I/O and registers.
Between scans, the control processor outputs the current values in this memory to the
appropriate external devices. The control processor also updates the Image Table
Memory according to the external I/O registers to prepare for the next scan.
User Memory: Partitioned into two distinct portions for maximum efficiency in
scanning and program manipulation:
1. Intermediate Code User Memory: This battery-backed memory occupies 4K or 8K
words of the control processor's operating (scratch) memory.
The Intermediate User Memory is only accessible by the control processor. It serves
as the source for the compile operations which generate the instructions for the
Compiled User Memory.
2. Compiled Code User Memory: Consists of battery-backed CMOS static RAM that
provides 32K of 64-bit word user program storage. Each word is composed of the
scan processor instructions and control codes. This memory serves as the executive
memory for the scan processor and can be randomly accessed by the control
processor for program loading and editing purposes.
Serial Communication Interface: Controls the two RS-422 ports on the front of the
Model 450 (PRGMR Channel 1 and COMM/Channel 2). More information on these
ports is found in Chapter 5.
SY/MAX Bus Interface: Allows the Model 450 to control a SY/MAX digital or
register rack as a bus master.
Ethernet Interface: Controls the ETHERNET port (Channel 3). The Ethernet
Interface converts data from the Ethernet packet into SY/MAX format so it can be
processed by the control processor. See Figure 14-3.
Real-Time Clock/Calendar: Provides the Model 450 with time-of-day and date
information. This information can be used throughout the entire programmable
controller system. For more information on the clock see Section 12.2.
Chapter 14 - Technical Data
30598-526
Page 14-13
ThinWire Ethernet
Scan
Processor
Ethernet
Transceiver
Processor
Registers
Ethernet
Controller
Address
Switches
Communication
Processor
Control
Processor
Dual-Port
Registers
Bus
Interface
All LEDs
Ethernet NIM
Storage Registers
Figure 14-3 Block Diagram of Model 450 Ethernet Interface
14.4 FORCING
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Since forcing overrides the actual logic of the control program, ONLY
QUALIFIED PROGRAMMERS who understand the contents of this
section should use the forcing capability.
Failure to observe this precaution can result in equipment damage, severe
personal injury, or death!
Forcing allows an external input or output to be turned ON or OFF via the programmer
keyboard and overrides the ladder logic state of the external field device. Forcing is
permitted from all ports.
In the Model 450, forcing is implemented just before updating the external I/O at the
end of scan. The forced state of an output WILL NOT be reflected in the image table,
meaning that the user program logic executes and is based on the actual image table
logic state and not on the forced state. This operation differs in comparison to other
SY/MAX processors.
The forced state of an input is written to the image table. Since forcing is only
implemented in the external I/O at the end of scan, forcing an internal relay or data
Chapter 14 - Technical Data
Page 14-14
30598-526
storage register does not alter the actual logic state in the user ladder program. The
programmer indicates the bits of an internal relay or data register to be forced even
though they are not actively changed. This operation differs from other SY/MAX
processors and is discussed further in the following paragraphs.
Since forcing is implemented on external I/O and not in the image table, the following
rules govern what is observed and how the programmable controller system behaves.
14.4.1 Forcing an External Output
A forced external output causes the associated external field device to assume the
forced state. The programming device reflects this when displaying a forced rung by
changing the graphics highlighting (reverse video; line thickness) on the forced
element. If relay contacts with the output address are used in the program, they will
assume the logic state of the output as executed in the image table. Since the relay
contacts and coil displayed on the programmer reflect the forced state and not the
image table logic state, this may conflict with the way the logic is actually being
executed.
EXAMPLE:
Consider the rungs shown in Figure 14-4. Contact 13-02 is an external input, while
coils 14-16, 13-11, and 13-12 are external outputs. The following conditions apply to
the rungs:
I 13
O 14
02
16
I 14
O 13
16
11
I 14
O 13
16
12
Figure 14-4 Forcing Example
CONDITION:
RESULT:
COMMENTS:
Chapter 14 - Technical Data
Output 14-16 is forced ON, while input 13-02 is
OPEN.
The external device wired to output 14-16 is
energized, and the graphics highlighting changes that
is used for coil and relay contacts with address 14-16.
The programming device displays the output contacts
and coil forced ON to reflect the forced state. For
detailed information about how the SY/MATE Plus
Programming Software represents forced states,
please refer to that instruction bulletin (#30598-322).
Even though the N.O. relay contact 14-16 is forced
“ON”, output 13-11 is OFF while output 13-12 is ON.
This occurs because coil 14-16 and its associated
relay contacts are actually OFF in the image table
(because contact 13-02 is OPEN).
30598-526
Page 14-15
If contact 13-02 is CLOSED instead of OPEN, the image table logic coincidentally
agrees with the forced state; output 13-11 is ON while output 13-12 is OFF.
If it is desired to have the contacts of coil 14-16 follow the logic state of the coil, the
proper technique is to force external input 13-02 as discussed in the next section.
14.4.2 Forcing an External Input
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
Forcing an unlatch coil ON actually latches the coil. Beware of
inadvertently causing equipment to operate or to shut down.
Failure to observe this precaution can result in equipment damage, severe
personal injury, or death!
A forced external input overrides the actual condition of the input field device and
causes the associated bit address in the Model 450's image table to assume the forced
state. The programming device indicates the forced state. As long as the forced
external input bit is not altered in the ladder program (which can only happen if the
input bit was incorrectly programmed as a coil), this forced bit state is used when the
ladder program is executed.
EXAMPLE:
Assume the same rungs are used in this example as in the previous “EXTERNAL
OUTPUT” example.
CONDITION:
Input 13-02 is forced ON, external field input is OFF.
RESULT:
As long as the state of bit 13-02 is not altered in the
user ladder program, the forced state is preserved in
the image table no matter what the state of the
external field device's input is. This means that output
14-16 is actually turned ON in the image table along
with the external device connected to output 14-16.
The relay contacts of coil 14-16 properly reflect the
state of the coil. Output 13-11 is ON, while output
13-12 is OFF.
Chapter 14 - Technical Data
Page 14-16
30598-526
14.4.3 Forcing an Internal Relay Equivalent or Data Storage Register
As noted before, forcing is a condition that applies only to external I/O.
NOTE
Attempting to FORCE an internal relay equivalent or a bit in a data storage
register has NO EFFECT on its state in the image table when used to
execute the ladder program. This is true even though the programming
device displays the FORCED state.
Since there is no external I/O associated with a forced internal relay equivalent or
storage register bit, the Model 450 has no way of implementing thc forced state. The
programming device, however, shows the bit as forced; this may conflict with the way
the rung is actually being executed.
This situation is somewhat analogous to the behavior of contacts that use the same
address as a forced coil. The contacts indicate a forced state, but in actuality assume
the logic state of the output as executed in the image table. In the case of an internal
relay there is no external output associated with the address. The Model 450 has
nothing to force externally, and the internal relay contacts continue to follow the logic
of the coil as instructed by the user program.
To summarize, perform forcing ONLY on external inputs and outputs. Forcing an
internal relay equivalent or bit in a data storage register has no effect on the register
and can produce information that is subject to misinterpretation on the programming
device screen.
14.4.4 Application Considerations for Forcing
Any external I/O register is forcible. This includes local digital I/O in a register rack
and digital I/O controlled via the Parallel Digital Driver/Receiver (PDD/PDR)
modules.
• Registers above 4000 are not forcible.
• Bits in a maximum of 256 registers can be forced simultaneously.
• Forcing can always be cleared by cycling power.
• Forcing can be inhibited or if already in effect, prevented from being altered by
placing the keyswitch in the RUN (as opposed to RUN/PROGRAM) position. See
the note following these application considerations.
• When the TIMED INTERRUPT subroutine is programmed and the Model 450 is in
the RUN/PROGRAM mode, forced I/O can be released by the CLEAR ALL
FORCE command (in SY/MATE Plus Software, soft key F6 in the
ONLINE/LADDER/FORCE screen).
• Software security can be invoked to restrict forcing on a port basis; see Sections 6.9
and 6.11.
• Each forced register adds approximately 100 microseconds to the I/O update time at
the end of the processor's scan, regardless of the number of bits forced in the
register. Thus, forcing one bit in a register causes the same time penalty as forcing
all 16 bits in that register.
Chapter 14 - Technical Data
30598-526
Page 14-17
NOTE
3 Special Cases of Forcing
Case 1: If a FORCE command is issued through port 3 only, and both ports
1 and 2 are disconnected or powered down, forcing is not
released.
Case2: If a FORCE command is issued through port 1 or port 2 and both
ports 1 and 2 are disconnected or powered down, forcing is
released.
Case 3: If a FORCE command is issued through port 1 or port 2 and port
3 and both ports 1 and 2 are disconnected or powered down,
forcing is released.
14.5
POWER UP/DOWN SEQUENCE
14.5.1 Processor Power-Up Sequence
Upon application of power to the Model 450, the following start-up sequence occurs:
1. External outputs are turned OFF.
2. A self-test sequence is performed to determine proper operation. If any part of the
self-test sequence fails, the Model 450 will not go into RUN.
The following components are checked when the self-tests are run:
• The executive PROM (checksummed and validated)
• User memory
• Intermediate user memory
• Internal RAM
• Compiled user memory
• Image memory
• Scan processor operation
• Control processor operation
• Watchdog timer
• Math coprocessor
3. Memory corruption test takes place. If an error is found, the MEMORY LED is
turned ON and the Model 450 does not execute the existing programmed memory.
4. A minimum 1-second delay is generated to allow I/O data to stabilize. The delay
may be longer depending on the register cards installed in the processor system and
the quantity of memory in the processor.
5. The I/O forcing memory is reset inside thc Model 450, thereby releasing all forced
I/O.
6. Input status is updated in the image table memory.
Chapter 14 - Technical Data
Page 14-18
30598-526
NOTE
The total time required for all power-up sequence activities is about 12
seconds. During this time, the processor does not respond to any
communication activity, and any attached programming device appears to
be inactive (in reality, the programming device is being asked to “wait” by
the processor).
7. If the processor keyswitch is in the RUN, RUN/PROGRAM, or DISABLE
OUTPUTS position, the sequence continues with the “Processor Scan Start-up
Sequence” described in the following section.
14.5.2 Processor Scan Start-Up Sequence
Upon changing the processor keyswitch from any position to the DISABLE
OUTPUTS, RUN, or RUN/PROGRAM position, the following sequence occurs:
1. A self-test is run which checks that:
• A valid user program is loaded
• All user-programmed MARKs and related GOTO and GOSUB rungs are
properly programmed
• All programmed I/O devices are checked.
2. Two dummy scans are conducted:
• Dummy Scan #1 simulates the presence of an MCR in the OFF state and executes
the scan so that DISABLE OUTPUTS is ON. Subroutines are scanned first, then
the regular ladder program is scanned. This scan has the effect of turning OFF all
coils, except for those programmed as internal latches. Outputs in the image table
are not transferred to the I/O devices during this scan. The timed interrupt is not
executed. During this scan, bit 21 of register 8176 is set to “1”.
• Dummy Scan #2 removes the simulated MCR, but keeps DISABLE OUTPUTS
set ON. The ladder is scanned normally. During this scan, timed interrupts are
not executed. At the end of this scan the image table is transferred to the external
I/O and programmable interrupt scheduling begins. During this scan, bit 22 of
register 8176 is set to “1”.
3. Normal ladder program scanning begins. Bit 23 of register 8176 is set to “1”.
NOTE
The total time for keyswitched start-up activities is about 5 seconds. During
this time the Model 450 does not respond to any communication activity.
An attached programming device appears to be inactive (although in reality
it is simply being asked to “wait” by the Model 450). If the programmable
control system includes a serial interface module (LI, LTI, LAI or LIO),
start-up time may be up to 15 seconds if the serial interface is showing an
error condition.
Chapter 14 - Technical Data
30598-526
Page 14-19
14.5.3 Processor Power-down Sequence
When the Model 450 processor enters a halted state or if power is removed from the
system, the Model 450 performs an orderly shutdown procedure that resets all external
outputs to their OFF state and halts the memory scan. If Local Interface (LI) or LIO
modules are used in the system, outputs can be specified to FREEZE instead of turning
OFF. For further information on using the FREEZE bit, please refer to the Local
Interface Module Instruction Bulletin (#30598-247), or to the Local IO/NET Interface
Module Instruction Bulletin (#30598-782).
The programmable controller system power supply continues operating, with no
interruptions in the operation, through any power loss or “brown-out” condition of
approximately 16 milliseconds or less. After this period of time, the processor shuts
down and restarts when proper power is restored.
In addition to all external outputs being reset to OFF in the modules, the registers that
are rack addressed to the output modules are also reset to 0 in the processor image
table. This occurs not only during the CPU power-down sequence, but also during
RUN-to-HALT transitions.
14.6
RUN-TIME OPERATIONAL CHECKS
The Model 450 performs a number of internal diagnostic checks. Among these are:
1. A continuous check is made to ensure that the internal clock driving the processor
logic is fully operational (hardware watchdog time-out).
2. Hardware circuitry halts the processor in the event the microprocessor fails to report
every 2.5 milliseconds (software watchdog time-out).
3. Each word of user ladder and register memory incorporates a parity bit. The
processor checks each examined word as it is executed for proper parity. If an error
is detected, the processor halts operation and turns external outputs off. (In this case,
the HALT LED flashes and the MEMORY LED is illuminated.)
4. The control processor gives the scan processor a rung to execute at the end of each
scan (a “fault rung”). If the rung is executed incorrectly, all outputs are turned OFF
and an error is generated.
Chapter 14 - Technical Data
Page 14-20
30598-526
NOTES
Chapter 14 - Technical Data
30598-526
15
Page 15-1
ETHERNET COMMUNICATIONS
15.1 INTRODUCTION
Ethernet is a data communications network used to allow computers and electronic
devices to talk to each other. This is accomplished with a coaxial cable and the
appropriate Ethernet software on each device connected to the cable (and hence the
network).
Ethernet is a non-deterministic network, which means that it cannot be determined
when a particular device will have an opportunity to 'talk' on the network to another
device. Ethernet operates on a first-come, first-serve basis. Other devices must wait
until the first device is done communicating, and then attempt to be the first one to talk
again. (This method is known as CSMA/CD or Carrier Sense, Multiple Access/
Collision Detect. CSMA/CD is a data communications networking standard classified
in the IEEE 802.3 standard.)
Since Ethernet is non-deterministic, there must be some method of waiting and
attempting to access the network if it is currently serving some other device. Thus the
concept of time-outs and retries is utilized to provide for multiple attempts to 'talk' on
Ethernet. The SY/MAX Model 450 provides a way for Programmable Controllers to
'talk' on Ethernet by using standard ladder programming communication rungs
(READ, WRITE and ALARM) for communication port 3. See Section 5.6 for detailed
information on SY/MAX communications.
This section is intended as a more detailed analysis of the inherently non-deterministic
nature of Ethernet communications. The SY/MAX Model 450 is designed to get up
and running with minimal configuration. Upon setting up the Model 450 for the first
time, a user simply needs to select a unique SY/MAX drop number for Ethernet and
follow standard network connection and start-up practices. Communications on
Ethernet is then as simple as programming a communications rung into a ladder
program in the Programmable Controller. Default values are set up for the Ethernet
parameters, but can be altered by a user to help optimize Ethernet communications.
Section 15.6 explains how to set these parameters and interpret performance data to
further fine-tune the Ethernet network.
The topics discussed here may be different for communications on ports 1 and 2 of the
Model 450. Consult the appropriate SY/NET instruction bulletin for information
pertaining to SY/NET and/or point-to-point SY/MAX communications.
The SY/MAX Model 450 processor has the ability to directly connect to a ThinWire
Ethernet Local Area Network (LAN) and communicate with up to 29 other SY/MAX
Ethernet compatible devices, with unique drop numbers. Through the use of Ethernet
repeaters, this number can be expanded to up to 99 other devices, for a total of 100
SY/MAX devices.
The connection is accomplished with standard ThinWire cables, terminators and
connectors. A unique SY/MAX address (drop #) on Ethernet is assigned to each Model
450 using a small rotary switch and DIP switches located at the rear of its cabinet.
Chapter 15 - Ethernet Communications
Page 15-2
30598-526
15.2 HARDWARE
All processors sharing the same Ethernet segment must be located within 607 feet (185
meters) of each other, as illustrated in Figure 15-1, unless repeaters are used.
Model 450
Model 650
Model 450
Model 650
Drop #0
Drop #1
Drop #2
Drop #N
(max. 30)
Other
non-SY/MAX
devices
ThinWire
and BNC
Drop
length=zero
Terminator
(50 ohms)
Type CCK613
Minimum Cable Length
Between Units 20 inches (1/2 m)
Maximum Overall
Cable Length for
ThinWire = 607 feet
(185 meters)
on
Ethernet
Terminator
(50 ohms)
Type CCK613
Tee Connector
Type CCK612
Figure 15-1 Possible Ethernet Configuration
The following hardware is required to connect each Model 450 processor in any size
Ethernet configuration (also refer to Table 15-1):
• Cable - Standard RG58 A/U or RG58 C/U coaxial cable, 0.2" diameter, 50-ohm,
single shield. Belden® Type 8219, 8259, or equivalent.
• Tee Connector - Square D Class 8030 Type CCK-612. One of these is required for
each 450 on the network. BNC Tee connector with jack-plug-jack (FMF)
arrangement.
• Terminator (50 ohm) - Square D Class 8030 Type CCK-613 (contains 2). Two
terminators are required, one for each end of the network.
• Pre-assembled Cable - Square D Class 8030 Type CC-601, 20 inches long (1/2
meter). This is the only preassembled cable available from Square D.
• Cable Ends - Square D Class 8030 Type CCK-611 contains two male crimp-style
BNC plugs. Cable and crimp tool (AMP CERTI-CRIMP Hand Tool P/N 220187-1)
must be purchased separately.
Chapter 15 - Ethernet Communications
30598-526
Page 15-3
Table 15-1: Ethernet Hardware
Item
Description
Cable
RG58 A/U or RG58 C/U single shielded, 50-ohm cable
with BNC plug connectors (Belden 8219, 8259, or
equivalent)
Tee Connector
Class 8030 Type CCK612 (AMP P/N 221543-2)
Terminators (2)
Class 8030 Type CCK613 (50-ohm, 1 watt BNC
terminators - AMP P/N 221629-4, contains 2)
Cable End Connector
Class 8030 Type CCK611 contains two male crimp-style
BNC plug connectors (AMP P/N 227079-5)
Pre-assembled Cable
1/2 meter length, Class 8030 Type CC601. Other cable
lengths must be assembled by the user.
NOTES
•
The 20-inch (1/2 meter) cable is the mandatory minimum cable
length between processors. Each Ethernet ThinWire segment may
not exceed 607 ft. (185m); the total end-to-end length of the link (with
repeaters) may not exceed 3,034 feet (925 meters). See Appendix D
for information on cabling other than Thinwire.
• It is extremely important that cable connections within the Ethernet be
solidly made. Cold solder joints, poor connections, and other
assembly flaws can cause intermittent communications problems. For
highest reliability, all connectors should have gold-plated conductors.
Also, avoid crushing the cable or placing sharp bends in it.
INSTALLATION CONSIDERATIONS
• For proper operation, the LAN to which the Model 450 is connected must conform
to all IEEE 802.3 specifications.
• Model 450s can be installed in any register slot in any SY/MAX rack. While
multiple Model 450s may be installed in the same rack, only the processor in slot 1
can directly control I/O.
• Each Model 450 draws 5.5 A. While a single rack can hold multiple Model 450s,
the power supply must be properly sized to handle the large load imposed by
multiple processors. Loading restrictions preclude powering more than 3 Model
450s from the same power supply.
• For future expansion, empty tee or barrel connectors can be inserted at minimum
intervals of 1/2 meter in a cable.
• The tee connector must be directly attached to the BNC connector on the Model
450, that is, no “dropline” length is allowed between the tee connector and the
processor.
• When adding processors to a functioning Ethernet, the cable connection should be
made while the new member is powered down. In this way, network members can
be added or removed from the Ethernet without powering down the link or
interrupting network operation.
Chapter 15 - Ethernet Communications
Page 15-4
30598-526
• Ensure the rubber insulating “boots” provided with the cable ends and terminators
are installed. These are to prevent the link from being unintentionally grounded by
accidentally coming into contact with the rack chassis or other means of current
conduction.
• The Ethernet circuitry and cable is isolated from processor digital circuitry
(300VDC, transformer-coupled). While bonding the cable conductors, tee
connectors, or terminators to chassis/earth ground is not required for proper
operation of the link, local electrical code requirements must be observed when
laying out the installation. At no time, however, should the link be grounded in
more than one location.
• To ensure reliable communications, it is recommended that all connectors have
gold-plated conductors.
• The Ethernet cable should not be included in the same tray or conduit with power
wiring, and should be routed so as to avoid passing in close proximity to electrically
noisy devices such as power transformers, arc welders, or contactors.
• See Appendix D for additional Ethernet information.
15.3 SWITCH SETTINGS
Figure 15-2 shows the location of the rotary and DIP switch banks on the processor.
The Model 450 has a 16-position rotary switch and a 4-DIP switch bank for
configuring the Ethernet. Accessible from the rear of the processor, both switches are
used to encode a unique drop number from 0 to 99. Switch functions are described in
the following sections.
Rotary Switch
4-DIP Switch Bank
4
3
2
1
Bottom Rear View
of Model 450
Figure 15-2 Rotary and DIP Switch Locations
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
Ensure that each device attached to Ethernet is assigned a unique
drop number, or the network will not operate properly.
Failure to observe this precaution can cause equipment damage or
personal injury.
Chapter 15 - Ethernet Communications
30598-526
Page 15-5
15.3.1 Least Significant Digit
The decimal rotary switch (see Figure 15-2) establishes the least significant digit
(LSD) of the SY/MAX drop number on Ethernet. Each rotary switch setting (0 to 9)
corresponds to a unique SY/MAX drop number on Ethernet ranging from 0 to 9. Other
switch settings are invalid. See Table 15-2 for switch settings.
Table 15-2: Least Significant Digit Switch Settings (Rotary Switch)
Switch Setting
LSD
0
0
1
1
2
2
3
3
4
4
5
5
6
6
7
7
8
8
9
9
NOTE
Use care when adjusting the rotary switch, as the separation between
positions is very small. The data field of register 8093 reports the
selected rotary switch position (in addition to the DIP switch settings).
If the contents of register 8093 do not reflect the apparent switch
position, rotate the switch several full turns to “wipe” the contacts.
15.3.2 Most Significant Digit
Immediately below the rotary switch is a DIP switch bank containing four switches.
The four switches encode the high or most significant digit (MSD) digit of the drop
number. The 4-bit binary code must be between 0 and 9 for network operation; other
settings are invalid. Refer to Figure 15-3 and Table 15-3 for MSD switch settings.
Chapter 15 - Ethernet Communications
Page 15-6
30598-526
4
4
3
2
1
3
Left = Open = Off
2
1
Bottom Rear View
of Model 450
Right = Closed = On
= Switch toggled to this position
Figure 15-3 DIP Switch Settings
Table 15-3: Most Significant Digit Switch Setting (4-DIP Switch)
1
2
3
4
MSD
Open
Open
Open
Open
0
Open
Open
Open
Closed
1
Open
Open
Closed
Open
2
Open
Open
Closed
Closed
3
Open
Closed
Open
Open
4
Open
Closed
Open
Closed
5
Open
Closed
Closed
Open
6
Open
Closed
Closed
Closed
7
Closed
Open
Open
Open
8
Closed
Open
Open
Closed
9
Closed
Closed
Closed
Closed
Disabled
Note that switch settings other than those in Table 15-3 are invalid.
After the drop number is set on the rotary and DlP switches, record the number on the
front panel label for visual SY/MAX drop number on Ethernet identification, as shown
in Figure 15-4.
Chapter 15 - Ethernet Communications
30598-526
Page 15-7
PRGMR
CHNL 1
ETHERNET
DROP..........
COMM
CHNL 2
Write in SY/MAX
Drop No. on
Ethernet
here
Figure 15-4 ETHERNET Port Identification Label
NOTE
The DIP switches have been set at the factory to all “1”s, indicating
non-Ethernet mode. The rotary switch factory setting will vary, but its
setting will not affect the drop number in this mode. See Section 15.7 for
additional error message information.
15.4
DEFINING AN ETHERNET NETWORK WITH SY/MAX DEVICES
15.4.1 SY/MAX Drop Numbers
Each SY/MAX device on Ethernet must contain a valid drop number, in order to
communicate with other SY/MAX devices on Ethernet. The rotary switch and 4 dip
switches select the SY/MAX drop number for each device on Ethernet. SY/MAX
devices must be numbered 0-99. See Section 15.3 for a complete explanation of valid
and invalid switch settings.
NOTE
All SY/MAX drop numbers on Ethernet must be unique.
15.4.2 Routing for Port 3 (ETHERNET Port)
To communicate with other SY/MAX devices on the network, the drop number of the
originating (source) device and the drop number of the destination (target) device must
be known. In some situations, additional drop numbers must also be known. See
Appendix E for additional Ethernet routing information.
Chapter 15 - Ethernet Communications
Page 15-8
30598-526
How to Use Routing
This section consists of three sample access routes from the Control Processor and
Ethernet NIM portions of a Model 450. See Figure 15-5 for a map of the access routes.
You should also be familiar with the variable route statements discussed in Chapter 5.
Routing information is programmed into the Communication rung (READ, WRITE or
ALARM) of the device initiating communications.
Ethernet NIM
Control Processor
SY/MAX Status/
Control Registers
8192
8001
8000
Not used
Ethernet Network
Parameter Registers
8192
8000
7999
7000
6999
Not used
Not used
4001
4000
Ch 1
4000
Processor
(Image Table)
Registers
2000
Storage
(Mailbox)
Registers
5000
4999
3000
2999
Not used
11
1
NIM Status Registers
Ch 3
Ch 2
Figure 15-5 Model 450 Registers
Chapter 15 - Ethernet Communications
1 - 10
Page 15-9
30598-526
• Example 1—Control Processor to Control Processor
Figure 15-6 shows drop #36 reading control processor (image table) register 1001 of
drop #84 into its own control processor register 2001.
ROUTE
TREAD3
036
ROUTE
STAT
084
S2000
LOCAL
REMOTE
COUNT
S2001
S1001
001
Figure 15-6 Rung for Reading One Image Table Register into Another
on Ethernet Port 3
• Example 2—Control Processor to Another Processor's ENIM
Figure 15-7 shows drop #36 reading drop #84's Ethernet NIM storage (mailbox)
register 3001 into drop #36's control processor (image table) register 2101.
ROUTE
TREAD3
036
ROUTE
200
ROUTE
STAT
LOCAL
REMOTE
COUNT
084
S2000
S2101
S3001
001
Figure 15-7 Rung for Reading a Mailbox Register into an Image Table
Register on Ethernet Port 3
• Example 3—Control Processor to Its Own ENIM
Figure 15-8 writes drop #36's control processor (image table) registers 2001 to 2128
into its own Ethernet NIM storage (mailbox) registers 3001 to 3128.
TWRTE3
ROUTE
ROUTE
ROUTE
STAT
LOCAL
REMOTE
COUNT
036
200
036
S4000
S2001
S3001
128
Figure 15-8 Rung for Writing an Image Table Register into Its Own
Mailbox Register
NOTE
Routes 202, 203, and 233-254 apply only to ports 1 and 2, not to
Ethernet Port 3. Further information can be found in the instruction
bulletin for the Multi-Media Network Interface Module (#30598-365), or
for other Network Interface Modules.
When your Model 450 is received from the factory, the switch settings will be
configured for non-Ethernet mode. This mode allows a user to power up the Model 450
and use it as a Programmable Controller control processor, but will not allow Ethernet
communications. Non-Ethernet mode is indicated by all four DIP switches set down
(all “1”s), regardless of the rotary switch position. Any switch settings other than valid
Chapter 15 - Ethernet Communications
Page 15-10
30598-526
drop numbers (0-99) or non-Ethernet mode will result in an Error 918, Illegal Drop
Number.
NOTE
If the processor is being used to communicate on Ethernet through Port
3 and on SY/NET through connection to a NIM on Ports 1 or 2, the
processor may represent a different SY/MAX device drop number on
each network. The Ethernet drop number is determined by the switch
settings on the processor while the SY/NET drop number is determined
by the switch settings on the NIM. It may therefore be convenient to
coordinate the two networks when possible to use the same drop
number for both Ethernet and SY/NET networks.
15.5 REGISTERS
This section lists the Model 450 registers related to Ethernet. See Figure 15-5 on page
15-8 for a spatial representation of the Control Processor, Ethernet NIM and Channels
1, 2 and 3 in the context of the Model 450.
15.5.1 Model 450 Register Overview
Table 15-4 and Table 15-5 outline the function of all Model 450 Control Processor and
Ethernet NIM registers. Specific information about Control Processor registers can be
found in Chapter 13.
Table 15-4: Model 450 Control Processor Register Use
Register
Range
1-4000
Control Processor Function
Type
(R/W=Read/Write;
R=Read only)
Processor registers
R/W
8001-8178
Model 450 control registers (see Chapter 13)
R/W
8179-8192
Model 450 control registers (see Chapter 13)
R
15.5.2 Control Processor Registers
The Control Processor portion of the Model 450 consists of two parts. Registers
1-4000 are standard SY/MAX read/write registers, and registers 8001-8192 are
SY/MAX control registers with several registers added for Ethernet considerations.
See Chapter 13 for specific control register information.
15.5.3 Ethernet NIM Registers
The Ethernet NIM (ENIM) portion of the Model 450 contains another 8192 registers.
See Section 15.4.2 for examples of how to access the ENIM registers.
Chapter 15 - Ethernet Communications
30598-526
Page 15-11
Registers 1-10 are “read-only” ENIM status registers:
• Register 1 - has the device type (for example, Model 450) stored in its data field.
• Register 2 - has the Ethernet NIM processor revision number within it. This register
contains the ENIM processor revision number in decimal. For example, a Revision
3.30 ENIM processor will have 0330D in this field.
• Register 3 - contains the SY/MAX drop number on Ethernet, indicated by the DIP
and rotary switches.
• Registers 4-10 - (currently not used) have zeros in them and are read only.
Registers 11-2999 are not accessible. Reading or writing to these registers will result
in a communications status register Error 03, Illegal Address.
Registers 3000-4999 are user-defined standard read/write SY/MAX storage registers.
Registers 5000-6999 are not accessible. Reading or writing to these registers will
yield a communications status register Error 03, Illegal Address.
Registers 7000-7999 are user-selectable read/write registers for storing Ethernet
performance parameters and data. Following are the Ethernet network parameters that
can be accessed from read/write registers 7000-7999 (note that XX is the address or
drop number of the receiving SY/MAX device on Ethernet):
• 7XX0 - Timeout time = the amount of time, in 10 msec increments, that each
SY/MAX device will wait before assuming that no ACK has been received.
• 7XX1- Total number of retries = number of communication retries (in addition to
the original communications attempt) attempted with each SY/MAX device before
declaring an error.
• 7XX2 - Average time to complete a SY/MAX transaction on Ethernet with each
indicated drop number.
• 7XX3 - Total number of retries for each 1024 attempted transactions (milliretries).
This number divided by 1024 yields the average number of retries per SY/MAX
transaction attempted.
• 7XX4 - Maximum time to complete a transaction (maximum time it takes to send a
COMMAND or REPLY and receive an ACK).
• 7XX5 - Maximum number of retries to complete a transaction.
• 7XX6 - 7XX9 - Reserved for future use.
Registers 8000-8192 are not accessible. Reading or writing to these registers will
yield a communications status register Error 03, Illegal Address.
Chapter 15 - Ethernet Communications
Page 15-12
30598-526
NOTE
The CLEAR PLC operation clears or resets all processor registers.
However, the Ethernet NIM registers are not cleared. Those registers
not cleared or reset include the ENIM storage (mailbox) registers
(registers 3000-4999) and the Ethernet communication performance
data registers (registers 7000-7999). Two alternatives for clearing or
resetting the ENIM registers exist:
1. Remove the Model 450 from the SY/MAX rack, remove the battery
from the Model 450 and wait approximately 2 minutes for the
memory to clear. Then replace the battery, place the Model 450 in
the rack and provide power.
2. Another method is to program a series of WRITE rungs into the
Programmable Controller to clear the ENIM storage registers
(3000-4999). Cycling power then clears the performance
calculations (7XX0-7XX5), but not the performance parameters
(7XX0-7XX1) or the storage registers. Developing a small utility
ladder program to clear the storage registers and set the default
Ethernet parameters may be useful. This program could then be run
anytime a CLEAR PLC is issued to clear or reset all the desired
registers.
See Section 6.8 for more information on CLEAR PLC.
Table 15-5: Ethernet NIM Register Use
Register
Range
1-10
11-2999
Ethernet NIM Function
NIM status registers
Type
(R/W=Read/Write;
R=Read only)
R
Reserved for future use
N/A
3000-4999
NIM storage registers
R/W
5000-6999
Reserved for future use
N/A
7000-7999
Contains Ethernet network parameters
R/W
8000-8192
Reserved for future use
N/A
15.6 ETHERNET COMMUNICATION PARAMETERS
REMINDER
Be sure that all SY/MAX devices on Ethernet have a unique SY/MAX
address ranging from 0 to 99.
In the ENIM of the Model 450 Programmable Controller, 1000 registers have been set
aside to store Ethernet communication parameters for communicating with up to 99
Chapter 15 - Ethernet Communications
30598-526
Page 15-13
other SY/MAX devices (100 total SY/MAX devices) on Ethernet. The distinction
“SY/MAX” devices is made because other non-SY/MAX devices may be on Ethernet,
but have their own unique Ethernet address and will not affect SY/MAX or be affected
by non-SY/MAX products on the network. Thus, the total number of devices on
Ethernet is only limited by Ethernet physical and electrical limitations, while the total
SY/MAX limit is 100 devices, providing other requirements are met also.
The 1000 ENIM parameter registers are numbered 7000-7999 and are Read/Write
registers. They are organized in groups of 10 registers for each of the 100 SY/MAX
drops on Ethernet, although only 6 of these 10 registers (7XX0-7XX5) are currently
being used, with the 4 remaining registers (7XX6-7XX9) reserved for future product
enhancements to the Model 450. Avoid using these 4 reserved registers for storage, so
as to maintain compatibility with future releases of this product. This helps preserve
ladder program and operational upward compatibility.
The registers are organized by the SY/MAX Ethernet drop number. For SY/MAX
address 00 (drop 00), the registers start at 7000 and end at 7009. For SY/MAX address
01 (drop 01), the registers start at 7010 and end at 7019 (and so on up to 7999). In this
way, the 1000 registers divided by 10 registers per drop number make up 100 drops
(the maximum number of devices of any combination of Model 450's, VAX computers
and other SY/MAX devices). The middle two numbers of the register indicate which
drop that register is associated with. For example, register 7010 is associated with
SY/MAX drop 01. The shorthand notation for this encoding method is 7XX0, where
XX indicates the SY/MAX drop number.
15.6.1 Setting Ethernet Communication Parameters (7XX0 and 7XX1)
Since the Ethernet Local Area Network (LAN) is a non-deterministic network, there
are no guarantees as to when or if you can begin communication on the LAN. The first
two registers for each drop, 7XX0 and 7XX1, allow the user/programmer to establish
the length of the Ethernet timeout and the number of retries, respectively, when the
Programmable Controller is communicating (for example, through a READ or WRITE
rung for port 3) with a device on Ethernet with SY/MAX drop number XX (see Table
15-6 on page 15-14).
The timeout register, 7XX0, indicates how many 10 msec units to wait before it is
assumed that no ACK has been received from a remote device and attempt another
retry. The total number of retries (in addition to the original communication attempt) is
indicated in the retry register, 7XX1. Upon power-up of the Model 450, the 7XX0
registers default to a value of 100. This means that one hundred 10 msec units
(equivalent to 1 second) is the time the Ethernet processor in the Model 450 will wait
before attempting to re-transmit the COMMAND. Register 7XX1 defaults to 2 retries,
before posting an Error 17, indicating a remote device is inactive. A valid ACK and
retry can still occur, however, despite thc fact that an error message has been posted.
Chapter 15 - Ethernet Communications
Page 15-14
30598-526
Table 15-6: Timeout Time and Retries
XX = Ethernet
(SY/MAX) Drop No.
or Address
Register
Address
Range
Parameter
Units
Default
Max.
Min.
7XX0
Timeout
Time
10 ms
100
65536
1
7XX1
No. of
Retries
1 retry
2
255
0
7XX0 (Timeout Time)
The amount of time, in 10 msec units, that each
SY/MAX device waits before assuming a message
was lost (no acknowledgment returned on Ethernet).
The default is 100 units or 1 second.
Number of timeout units multiplied by 10 msec = Total Time
For example, 100 timeout units multiplied by 10 msec
= l sec. Timeout time can be set for a maximum of
65535 units x 10 msec or approximately 11 minutes.
The minimum is 1 unit or 10 msec. If the timeout is
set to 0, it defaults to 1. The timeout time for that
address or drop number being communicated to is set
up in the initiating device's 7XX0 register (not the
receiver's 7XX0 register).
16
1
7XX0 - Full 16 bits used as unsigned integer
Timeout - 65535 is the maximum value (full 16 bits
used) a user can place in this register. This is treated
as an unsigned integer. Any attempts to use a negative
number (signed integer) will result in the
corresponding unsigned integer being used. If a zero
(0) is placed in this register, the system will use a
count of 1 for actual communications. The zero (0)
will still remain in the register and will appear in any
attempt to read this register, but the value of 1 will
actually be used for communications. Thus, with the
above exceptions, there is no explicit range checking
on the data put in by the user.
7XX1 (Number of Retries)
Chapter 15 - Ethernet Communications
The number of attempts by a processor to
communicate with other SY/MAX devices before
indicating an error. Retries keep occurring until a
positive Acknowledgment is returned over Ethernet.
The number of retries defaults to 2, has a maximum of
255 and a minimum of 0. The number of retries for
the address or drop number being communicated to is
set up in the initiating device's 7XX1 register.
Page 15-15
30598-526
16
1
X X X X X X X X
X = “don’t care” bits
7XX1 - Lower 8 bits used as unsigned integer
255 retries is the maximum value (lower 8 bits of
register used only) used by the Programmable
Controller for Ethernet communications. Anything
greater than 255 put in the register will result in the
high byte of 7XX1 being truncated and the lower byte
used for actual communications, although the full
16-bit value will remain in the register. Similarly, if a
negative number is used, the number of retries
corresponding to the lowest byte (high byte truncated)
will result. A value of zero (0) can be legitimately
used, resulting in no retries (only the original
communication attempted). However, this is usually
not a practical parameter, since the Ethernet network
may be busy. Thus, there is no explicit range checking
on the data put in by the user.
Timeout and Retry Example
Both the 7XX0 and the 7XX1 registers for SY/MAX drop #22 can be changed by
using the following rungs in a ladder program:
NOTE
Bit 8176-22 can be used to set up new Ethernet parameters prior to
program execution. This is made possible by using the second dummy
scan of the control processor to set up the parameters. Adding the ladder
rung shown in Figure 15-9 allows you to set up the parameters before
program execution. This particular example sets up time-outs and retries
in drop #36. See Chapter 13 for more information about Register 8176
(Primary Control Processor).
Chapter 15 - Ethernet Communications
Page 15-16
30598-526
8176
LET S3000 = 00055; 00005
22
Ladder Rung to Establish ENIM Preset Value
8176
TWRTE3
ROUTE
ROUTE
ROUTE
022
200
022
STAT
S0100
LOCAL
REMOTE
COUNT
S3000
S7360
002
22
Ladder Rung to Transfer ENIM Preset Values to ENIM Register
TWRTE3
ROUTE
ROUTE
STAT
LOCAL
REMOTE
COUNT
022
036
S0200
S3000
S3200
128
Figure 15-9 User-Modified Timeout and Retry Example Rungs
In this example, rungs from a Model 450 with a SY/MAX drop number of 22 on
Ethernet will set up Ethernet parameters for communication with SY/MAX drop 36 on
Ethernet. The first rung presets register S3000 = 55 (representing a timeout of 550
msec) and S3001 = 5 (for 5 retries). The second rung then writes from drop 22 to its
own ENIM parameter registers 7360 and 7361. This sets up the Ethernet
communication parameters for communicating with SY/MAX drop 36. Finally, at
some later point in the program, the last rung shown writes from drop 22, registers
3000 through 3127, to drop 36, registers 3200 through 3327, using the Ethernet
communication parameters established in registers 7360 (550 msec time-outs) and
7361 (5 retries).
Figure 15-10 on page 15-17 represents 3 SY/MAX drops with 1000 read/write
registers each (7000-7999) available for network parameters.
For instance, at the top center of Figure 15-10, the timeout time was left at the default
of 100 (register 7220) for communications between drop #36 to drop #22. And the
number of retries (2) is also left at the default set in register 7221. So the timeout time
is 100 units (also the default) or 100 x 10 ms or 1 second. Register 7221 also specifies
that the message will be transmitted once and then retried twice, if necessary, until it is
acknowledged by drop # 22.
Registers 7230 to 7239 are available for when drop #36 communicates with drop #23,
registers 7240 to 7249 are available for when drop #36 communicates with drop #24,
and so on.
The box on the bottom left of Figure 15-10 represents drop #22's Ethernet network
parameters. The timeout time of 55 is set in register 7360 for when drop #22
communicates with drop #36. The number of retries is set in register 7361 for drop #22
to retry another 5 times, if necessary, until it receives an acknowledgment. The
remaining parameters in registers 7362 through 7369 contain transmission
performance data. So all drops may have their 1000 registers (10 per drop) set up for
each of the 100 drops. However, if values are not placed in the registers, they will
default to the values shown in Table 15-6 on page 15-14.
Chapter 15 - Ethernet Communications
30598-526
7220
7221
7222
7223
7224
7225
7226 to
7230
7231
.
.
.
7236 to
7XX0 to
7840
7841
.
.
.
7846 to
7850
7851
7852 to
Ethernet
parameters set
up for when
drop #36
communicates
with drop #22
Timeout = 100 (for drop #22)
Retries = 2
Avg. Timeout
Avg. Retries
Max. Timeout
Max. Retries
7229 Reserved for future use
Timeout = 132 (for drop #23)
Retries = 26
Page 15-17
Ethernet
parameters set
up for when
drop #36
communicates
with drop #84
7239 Reserved for future use
7XX9 Parameters for drops not shown
Timeout = 50
Retries = 17
7849 Reserved for future use
Timeout = 187
Retries = 77
7999 Etc.
#36
Ethernet
parameters
set up for
when drop #84
communicates
with drop #22
Model 450
drop #36
Model 450
drop #84
Model 450
drop #22
7360
Timeout = 55 (for drop #36)
7361
Retries = 5
7362
Avg. Timeout
7363
Avg. Retries
7364
Max. Timeout
7365
Max. Retries
7366 to 7369 Reserved for future use
7XX0 to 7XX9 Parameters for drops not shown
7840
Timeout = 13 (for drop #84)
7841
Retries = 149
7842 to 7999 Etc.
#22
Ethernet
parameters
set up for
when drop #22
communicates
with drop #36
7220
Timeout = 243 (for drop #22)
7221
Retries = 56
7222
Avg. Timeout
7223
Avg. Retries
7224
Max. Timeout
7225
Max. Retries
7226 to 7229 Reserved for future use
7XX0 to 7XX9 Parameters for drops not shown
7360
Timeout = 655 (for drop #36)
7361
Retries = 254
7362 to 7999 Etc.
#84
Figure 15-10 Examples of Ethernet Parameters Set Up on Registers 7XX0-7XX9
15.6.2 Evaluating Ethernet Communication Performance (7XX2-7XX5)
NOTE
Writing zeros to 7XX2-7XX3 does not have the effect of zeroing out
calculations performed previously. However, writing zeros to 7XX4 and
7XX5 does zero out previously performed calculations.
Registers 7XX2-7XX5 represent performance information for communicating with
various SY/MAX devices on Ethernet. They provide a means of monitoring Ethernet
communications and changing parameters in 7XX0 and 7XX1 based on these
performance values. These registers are read/write registers, but are intended to be
examined only, as data is calculated and updated by the Programmable Controller
Chapter 15 - Ethernet Communications
Page 15-18
30598-526
periodically and placed in these registers. Writing to these registers may only have a
temporary effect, as new data is calculated dynamically and replaces previous data in
these registers. These registers are only updated when communications (COMMANDs
and REPLYs) are active with drop XX. The specific times at which they are updated
are explained in the following paragraphs.
As mentioned earlier, Registers 7XX2-7XX5 are ordinarily computed by the Ethernet
NIM. Table 15-7 summarizes 7XX2-7XX5's communications performance
parameters.
Table 15-7: Ethernet Communication Performance Parameters
(7XX2-7XX5)
Register
Address Range
Parameter
Units
7XX2
Avg. time to complete a transaction
10 msec
7XX3
Avg. number of retries for each attempted
transaction
Retries per 1024
attempted
7XX4
Maximum time to complete a transaction
10 msec
7XX5
Maximum number of retries for each attempted
transaction
Retries per
transaction
7XX2 - Avg. time to complete a SY/MAX transaction on Ethernet
This is the average time it takes to send a SY/MAX
COMMAND or REPLY to drop XX and receive an
ACK. All transmissions (the original plus the retries)
are included in this calculation. Like 7XX0 and
7XX4, this is expressed in 10-msec units.
7XX3 - Total no. of retries for each 1024 attempted transactions (milli-retries)
This number divided by 1024 yields the average
number of retries per SY/MAX transaction attempted.
This was done to preserve the accuracy of the average
in an integer format.
7XX4 - Maximum time to complete a transaction
This is the maximum time it takes to send a
COMMAND or REPLY and receive an ACK.
Assuming 7XX0 has not been decreased, the value of
7XX4 will be equal or less than the value of 7XX0.
The value of 7XX4 can be cleared to generate a new
maximum time.
7XX5 - Maximum number of retries for each attempted transaction
This is the maximum number of retries that occurred
during a SY/MAX COMMAND or REPLY
transaction. Assuming that the value of 7XX1 was not
decreased, the value of 7XX5 would be equal to or
less than 7XX1. Like 7XX4, the value of 7XX5 can
be cleared to generate a new maximum.
Chapter 15 - Ethernet Communications
30598-526
Page 15-19
The example shown in Figure 15-9 on page 15-16 (User-Modified Timeout and Retry
Example Rungs) illustrates the process needed to set Ethernet communication
parameters (7XX0 and 7XX1). This is a result of ladder programming packages
having no access directly to monitor and edit data in the ENIM registers, and thereby
having to do so through ladder programming. It may be helpful, if the required
registers are not needed for other purposes, to map the active ENIM parameter
registers into registers 3000-3999 of the processor registers. In reference to the
example configuration in Figure 15-11, the following rungs in drop 36 could be used to
map performance data for drops 22 and 84 into the processor image table registers.
8164
ROUTE
TREAD3
036
ROUTE
200
ROUTE
036
STAT
LOCAL
S 2000
S3222
STAT
LOCAL
REMOTE
S7222
COUNT
00 4
10
ROUTE
8164
TREAD3
036
ROUTE
200
ROUTE
036
S 2001
S3842
REMOTE
S7842
COUNT
004
10
Figure 15-11 Sample Ethernet Communication Performance Rungs
In this example 8164-10 is used to trigger the read rungs. Register 8164 is the
Programmable Controller timer register and bit 10 is set approximately once every 2
seconds. Thus the performance data for drops #22 and #84 is updated about once every
2 seconds. Other methods could be used to trigger when the update actually takes
place.
Now since the data is updated in the processor registers, it can be viewed via a ladder
programming device on a data screen. It should be noted that to change the parameters
(7XX0 or 7XX1), the appropriate WRITE rungs still need to be added to the ladder
program, as the ENIM registers cannot be changed with a ladder programming device.
(For additional information on using SY/MATE Plus Programming Software to change
the ENIM registers, please refer to instruction bulletin #30598-322.)
The previous two examples allow the user to set the communication parameters for
drops 22 (7220 and 7221) and 84 (7840 and 7841) and then examine the performance
(7222-7225 and 7842-7845) and make adjustments accordingly. For example, if the
performance data (averages and maximums) are near the maximum value set by the
user (as indicated in 7220-7221 and 7840-7841), perhaps the timeout should be
extended and/or the replies increased.
15.6.3 Miscellaneous Considerations (7XX2-7XX5)
Upon power up, registers are set to zero (0) and updated under the following
circumstances. The retry variables (7XX3 and 7XX5) are updated when:
• An ACK is received in response to a command that is sent out
• The maximum number of retries is met (timed out)
Chapter 15 - Ethernet Communications
Page 15-20
30598-526
The time variables (7XX2 and 7XX4) are updated when:
• An ACK is received
• A NAK is received
• A timeout occurs
• A transmission error is received.
All the above registers are cleared when the Ethernet communication port fails or the
Programmable Controller is powered up.
If registers 7XX0 and/or 7XX1 were changed prior to any communications with drop
XX or if the default values were used for communications, then 7XX3 and 7XX5
should always be less than the value specified in 7XX1. It is possible, however, that if
7XX1 was subsequently changed to a lower value after communications had been
activated, that the previous running average (7XX3) and peak retries (7XX5) could be
higher than the newly updated maximum user specified in 7XX1 (which is now set
lower than before). Keep in mind that 7XX3 is in milli-retries, that is, the number of
retries for 1024 attempted transactions. Writing zero (0) to these registers for a specific
drop after communication has already been active will NOT clear these calculations in
7XX2 and 7XX3. Thus, care must be exercised when interpreting these values if
time-outs (7XX0) or retries (7XX1) have been changed after communication has been
active for drop XX.
If ENIM registers 7XX0 and 7XX1 are changed while comms rungs are still waiting
for ACKs to outstanding COMMANDS, the new values entered will be used in
determining timeouts and retries. For example, assume initially 7XX0 is set to 200 (2
seconds) and 7XX1 is set to 10 retries, and 5 READ/WRITE rungs are solved true and
sent to the communication buffers. If 7XX0 and 7XX1 are changed back to 100 and 2
respectively (the default values), the new values (1 second and 2 retries) will govern
communications with drop XX.
Reserved Registers (Registers 7XX6-7XX9)
Registers 7XX6-7XX9 are reserved for future use. These registers should not be used
for storage purposes, so that upward compatibility with future SY/MAX devices is
ensured.
15.7 ETHERNET ERRORS AND DIAGNOSTICS
This section describes errors related to Ethernet only. For other Model 450 operational
errors, see Appendix A.
Any errors and/or diagnostic conditions which are related to Ethernet communications
are posted in processor control register 8094. Ethernet Errors also post a value of 929
in processor control registers 8175 to indicate that an Ethernet error has occurred and
directs the user to examine register 8094 for more specific information. Ethernet
Diagnostic codes are posted to register 8094 under various conditions, but do NOT
post an error indicator in 8175 and usually do not require any action by the user to fix
them. (Refer to Section 15.7.2 for more information.) They are primarily intended for
informational purposes. Each group of codes has various effects on processor
execution, Ethernet communications, and LED activity. Refer to Table 15-8 for various
Ethernet LED and processor states grouped by error code.
Chapter 15 - Ethernet Communications
Page 15-21
30598-526
Table 15-8: Register 8094 Ethernet Error Codes by LED and Processor
Error Codes
Ethernet LED
Port 3 Activity
Ladder Scan
<900
Flashing
Continuous
Continuous
900-919
Solid
Halt
Continuous
≥920
Solid
Halt
Halt
Processor LED states are described in Section 4.2. Depending on the nature of the
Ethernet Comm Error, the status of the processor and/or the network is indicated.
15.7.1 Ethernet Error Codes
Register 8175 represents the starting point for all SY/MAX error code investigations,
including Ethernet errors. In those cases where register 8175 contains error code 929,
register 8094 will contain additional information about the nature of the Ethernet
failure. Table 15-9 lists Ethernet-related errors which may be found in register 8175.
Table 15-9: SY/MAX - Ethernet Errors in Register 8175
Error Code
Description
929
Ethernet communication error; refer to register S8094
979
Processor installed in slot 1 with rack addressing missing
985
Processor is not installed in slot 1 though rack addressing is present
Handshake failure between control processor and communication
processor
30600
Error 985 or 979 typically occurs when using multiple Model 450s in the same rack.
Model 450 register 8094 is used to store communication error codes related to error
929. Table 15-10 shows error codes that may appear in register 8094, along with a
brief description of each.
Table 15-10: Ethernet Errors in Register 8094
Error Code
Description
916
Ethernet connector problem
917
Duplicate drop number*
918
Illegal drop number*
919
General hardware failure
920
Local RAM READ-after-WRITE test failure
921
Local RAM destructive READ-after-WRITE test failure
Chapter 15 - Ethernet Communications
Page 15-22
30598-526
Table 15-10: Ethernet Errors in Register 8094
Error Code
Description
922
Shared RAM READ-after-WRITE test failure
923
Shared RAM destructive READ-after-WRITE test failure
924
Link controller initialization test failure
927
Link controller run-time failure
30500
Bus signal error due to time-out
30600
Handshake failure between control processor and communication
processor
30800
Software diagnostic error
30900
Parity error
31100
Ethernet NIM PROM Checksum error
32700
Main processor failure
*Check
DIP and/or rotary switch settings and examine register 8093.
15.7.2 Ethernet Diagnostic Codes
There are several conditions which may occur on Ethernet which post diagnostic codes
in the processor control register 8094 (see Table 15-11). Unlike the error codes in
Section 15.7.1, there is no corresponding error code posted in register 8175 to indicate
a diagnostic code in register 8094. The Ethernet network LED flashes when a
diagnostic error code is occurring. These codes remain in register 8094 until another
diagnostic condition occurs and that code replaces the previous one. These codes result
from transient errors and, unless they occur frequently, do not require any action by the
user. Both the processor and Ethernet communications continue as usual.
These codes may prove useful in determining network problems if any of these codes
occur repeatedly or often. The following diagnostic codes refer to errors detected by
the Local Area Network Controller for Ethernet (LANCE) chip used in the Model 450.
Additional troubleshooting help can be found in Appendix A, “Error Codes.” If any of
these error codes occurs repeatedly, an Ethernet 802.3 protocol analyzer should be
used to troubleshoot and determine which devices on Ethernet may be sending or
receiving improper Ethernet packets.
Chapter 15 - Ethernet Communications
30598-526
Page 15-23
Table 15-11: Ethernet Diagnostic Codes in Register 8094
Diagnostic
Code
Description
Solution
800
Unable to connect to Ethernet.
This error occurs when the
processor is set to a valid
Ethernet SY/MAX drop number,
but is unable to initially connect
to the network. Probably due to
an improper connection or
termination of the network
cable. This is similar to error
916, the difference being that
error 916 occurs after Ethernet
communications have already
been active, whereas diagnostic
800 occurs after power-up but
before any communications are
initiated.
Connect and/or check cable and
cable terminations.
801
LANCE - Collision. No heartbeat
collision after packet sent by this
device.
No user action required.
Possible faulty device.
802
LANCE - Missed packet. This
error indicates that an Ethernet
packet intended for a device
was missed by that device due
to all buffers currently being
used.
Transmitting device will
probably retransmit packet.
Analyze traffic patterns on
network.
803
LANCE - Improper frame size.
This error indicates that the
incoming packet contains a
non-integer multiple of 8 bits
and there was an incorrect
CRC.
Ethernet packet is discarded.
Analyze Ethernet packets.
804
LANCE - Buffer Overflow
condition. This error indicates
that the LACNE has overflowed
internal LANCE buffers to
service incoming messages.
No user action required.
Ethernet packet is discarded.
Jabber-related error.
805
LANCE - Incorrect CRC
detected. This error indicates
the Cyclic Redundancy Check
(CRC) code in the Ethernet
packet does not match the CRC
calculated for the data
contained in the packet.
No user action required.
Ethernet packet is discarded.
Error is due to noise, faulty or
improper cable connection or
incorrect packet transmission or
reception.
806
LANCE - Doesn’t own any more
buffers. This error indicates that
the LANCE cannot store any
more of the packet because
there are no available buffers.
No user action required.
Ethernet packet is discarded.
Jabber-related error.
Chapter 15 - Ethernet Communications
Page 15-24
30598-526
Table 15-11: Ethernet Diagnostic Codes in Register 8094
Diagnostic
Code
Description
Solution
807
LANCE - End of Ethernet packet
not detected. An Ethernet
packet larger than the maximum
allowed was received. This type
of packet is called a jabber.
Check cable and terminations
on the network. Ethernet packet
is discarded.
808
LANCE - Late collision on
Ethernet. A collision has
occurred on Ethernet after the
time allowed for a “normal”
collision. This does not cause
the LANCE to retry any
messages.
Check cable and terminations
on the network. Ensure that
distance specifications have not
been violated.
809
LANCE - Loss of carrier
detected. The LANCE cannot
detect the Ethernet carrier on
the network.
Check cable and terminations
on the network.
810
LANCE - Maximum number of
collisions occurred. Sixteen
collisions have occurred on the
network during attempts to
transmit a message. This may
cause a RETRY of the
message.
Check cable and terminations
on the network. Analyze traffic
volume on the network.
811
Unable to communicate on
Ethernet. This error occurs
when a processor connected to
the network and having a valid
Ethernet SY/MAX drop number
is no longer able to
communicate on the network.
Probable cause is a loose or
disconnected tee connector at
the processor. In pre-Revision
1.21 processors, this condition
was indicated by error code 916
and required that the error
condition be removed and
power be cycled to the
processor in order to resume
Ethernet communications.
Connect and/or check Ethernet
tee connectors, cable and cable
terminations. Reconnecting the
tee connector should allow
resumption of Ethernet
communications without the
need to cycle power to the
processor.
TROUBLESHOOTING NOTES
•
Packet errors can be analyzed with a LAN 802.3 protocol analyzer.
• Cable, connector, and terminator errors can be analyzed by
physical inspection and with a device with Time Domain
Reflectometer (TDR) capabilities.
• Noisy networks can be analyzed with oscilloscopes or spectrum
analyzers.
Chapter 15 - Ethernet Communications
30598-526
Page 15-25
15.8 GLOSSARY OF TERMS
The following terms are commonly used throughout this manual and the SFW390
(#30598-737) Instruction Bulletin. They apply primarily to the Model 450 and
SFW390's version of Ethernet:
ACK
A response from an external device to the sender of a
data message. An ACK indicates that one or more
messages were received and accepted by the
destination.
Alarm Queues
Areas of memory supported by the SFW390 software
and designed to hold three different classifications of
alarms: Faults, Alerts and Warnings. Faults are
classified as the most severe and Warnings are
classified as the least severe.
Application
A specific process or task, such as tracking and
comparing production per machining device, to which
a computer solution can be applied.
Asynchronous
A mode of processing in which a user task can
continue to execute after a read or write without
having to wait for the request to be fulfilled. (See
synchronous.) This would allow multiple reads and/or
writes to be outstanding at the same time, for
example. Register reads and writes using SFW390 or
Model 450s can be either synchronous or
asynchronous.
Bridge
Similar to a repeater in its ability to connect segments
of a network. It also has the capability to screen
information being transferred between segments of a
network.
CSMA/CD
Carrier Sense Multiple Access with Collision
Detection. This is a method for controlling access by
devices all sharing a single transmission medium.
Other methods include token passing and token ring.
Ethernet (Equivalent NIM)
The hardware and firmware internal to the Model 450
programmable controller that serves as an embedded
Network Interface Module and functions to:
• Send/Receive Ethernet packets to/from VAX
computers and other Model 450 programmable
controllers
• Store/Retrieve SY/MAX data to/from the
Ethernet (Equivalent) NIM registers
• Send/Receive SY/MAX packets to/from the
Model 450 programmable controller. There is
also an equivalent NIM component of the
SFW390 software that functions in the same
manner as the Model 450's equivalent NIM. The
equivalent NIM portion of the SFW390 is often
referred to in the SFW390 manual as the
SFW390 Ethernet Configuration Registers.
Figure E-2 in Appendix E illustrates the location
of the equivalent NIM in both the programmable
controller and SFW390.
Chapter 15 - Ethernet Communications
Page 15-26
30598-526
Ethernet
A specification for local communication networks that
employs coaxial cable as a passive communications
medium to interconnect different kinds of computers,
information processing products, and office
equipment at a local site.
External Device
Refers to a Model 450 programmable controller, or
another computer running SFW390 software (or
equivalent) connected to the host computer via the
Ethernet network.
Gateway
In LANs, a computer system and its associated
software that permit 2 networks using different
protocols to communicate with each other. A gateway
translates all protocol levels from physical layer up
through applications layer, and can thus be used to
interconnect networks that differ in every detail.
Global Alarm Queues
System-wide alarm queues, accessible from any
application program. SFW390 supports global alarm
queues which are specified in the configuration file.
Any external device or internal process can write to a
global queue and any application program can view,
clear or acknowledge entries from them.
Global Mailbox Registers
System-wide registers, accessible from any
application program. Global mailbox parameters are
specified in the configuration file. Any external device
or application program can read or write the global
mailbox registers.
Host Computer
A computer attached to a network that provides such
services as computation, database access, or special
processes or programming languages. The VAX
computer running with a VMS operating system is the
host computer when using SFW390.
IEEE 802.3
IEEE 802.3 is a specification for a communications
standard written by the Institute of Electrical and
Electronic Engineers based on the Ethernet
specification. Sometimes referred to as ThickWire
Ethernet (10BASE5).
IEEE 802.3a
This is a sub-specification of 802.3, which is based on
the ThinWire Ethernet specification (10BASE2).
LAN - Local Area Network
A cabling system, usually installed at the periphery of
a building, which uses a proprietary protocol and
enables a single vendor's equipment to transmit or
receive data.
Local Alarm Queues
Alarm queues belonging to and managed by an
individual application program. The SFW390
supports both local mailboxes and local alarm queues.
Any external device or internal process can write to a
task's local queue but only the owner task can view,
clear or acknowledge entries from them.
Local Mailbox Registers
Mailbox registers belonging to and managed by an
individual application program.
Chapter 15 - Ethernet Communications
30598-526
Page 15-27
Mailbox Registers
Areas of memory used to emulate a set of SY/MAX
general purpose registers. Also called a “register file”.
Each application program may have a set of local
mailbox registers. In addition, there may be a set of
global mailbox registers. The principal purpose of
these mailbox registers is to allow application
programs to receive unsolicited messages.
NAK
A response from an external device to the sender of a
data message. A NAK may cause several messages to
be retransmitted.
Network
A group of computing devices (computers,
programmable controllers, and so forth) that are
connected to each other by communication lines to
share information and resources.
Node
An end point of any branch of a network, or a junction
common to two or more branches of a network.
Protocol
A set of mutually agreed-upon rules for exchanging
information between computers and computer-based
equipment.
Reference
A calling convention in which a variable's address is
passed to the function, that is, by reference.
Repeater
A device used to extend transmission ranges/distances
by restoring signals to their original size or shape.
Reply Timeout
When a reply to a command originated by a user
process is not received within the reply timeout
period, the function generating the command will set
the status variable appropriately and (for synchronous
operation) return an error in the function return.
Response Timeout
When a response (an ACK or NAK) from a
destination device is not received within the timeout
period, the message will be retried. This timeout
applies to a response (for example, ACK or NAK)
from a transport protocol entity on an external device,
and should not be confused with a reply timeout.
The response timeout period is user-adjustable. Refer
to Section 15.6.2 for more information.
Retry
After a NAK or a response timeout a message will be
retransmitted. The number of retries that will be
attempted for a message is user-adjustable.
Segment
A continuous length of cable used to connect devices.
ThinWire Ethernet defines a segment as being RG-58
cable and extending no more than 185m.
Synchronous
A mode of processing in which a user task issues a
read or write request and then waits until that request
is fulfilled before continuing to execute. (See
asynchronous.) All register reads and writes using
SFW390 can be either synchronous or asynchronous.
Terminator
A special connector used on both ends of an Ethernet
segment. This connector provides the 50-ohm (or
Chapter 15 - Ethernet Communications
Page 15-28
30598-526
other value) termination resistance needed for the
cable.
ThickWire (10BASE5)
Standard Ethernet baseband coaxial cable that serves
as the backbone transmission medium for the Local
Area Network. Primarily used for facility-wide
installations.
ThinWire (10BASE2)
A wiring scheme which uses a type of (thin) coaxial
cable for use in Ethernet. Primarily used in office
environments. A DEC® trademark used to describe its
IEEE 802.3 compliant Ethernet products used for
local distribution of data communications.
Chapter 15 - Ethernet Communications
30598-526
APPENDIX A
Page A-1
ERROR CODES
A.1 GENERAL INFORMATION
Errors detected by the processor and error codes displayed on the monitor provide the
operator with information useful in isolating problems.
Some errors are indicated as self-explanatory messages on the screen. Other error
indications involve error code numbers. Since the messages are self-explanatory, this
appendix concerns only the numbered error codes. These error code numbers can be
broken into two general categories and are indicated in different locations on the
monitor screen.
In the first category are the peripheral-to-PLC system interaction errors in which
three classifications of error codes exist: processor, transmission, and tape. These
errors are indicated in a window on the screen or in some special cases, in the status
register of a communications rung.
In the second category are the PLC-system operational errors which are errors
detected within the processor or any one of the modules contained in a programmable
controller system. These errors are indicated in the monitor's ONLINE/STATUS mode
display next to the label Error Number. The number displayed is also the number
contained in the error code control register 8175 or possibly in a Local Interface
Module error code control register (when using remote I/O).
Normally when correct programmable controller system operation is restored, the
error code is cleared. The Model 450 contains a valuable troubleshooting feature
that allows users to store up to 16 of the most recent error codes in a user-defined
register block, or “error register stack.” This feature must be enabled by entering
a beginning storage register number in register 8107. The order of occurrence of
errors can be determined by analyzing this register stack pointed to by register 8107.
See Section 13.2, “Control Registers,” for more information about register 8107.
A.2 PERIPHERAL-TO-PLC SYSTEM INTERACTION ERRORS
Peripheral-to-PLC system interaction errors are assocated with attempts to perform
illegal operations with the processor, or they may indicate that the communication
hardware is not functioning properly. This category of error is only generated when
the keyboard is used for commanding processor operations or when the processor is
attempting communication with other responding devices.
The three classifications of peripheral-to-PLC system interaction error codes are:
• Processor
• Transmission
• Tape
When an error occurs while a programmer, SY/MATE, or SY/MATE Plus
Programming Software is being used with the processor, one of the three types of
messages (processor, transmission, or tape) will be shown on the display along with
a number. The errors are listed and described in Table A-1. If a peripheral-to-PLC
system interaction error occurs while the processor is executing a communication
rung, a processor error is generated. The error code number also appears in the status
register of the communication rung which failed to execute properly.
Appendix A - Error Codes
Page A-2
30598-526
A.2.1 Processor Errors
Processor errors indicate that the operation attempted was not successfully completed.
The error code numbers range from 01 through 153. To resolve the error situation,
follow these steps:
1. Find and read the error code description in Table A-1.
2. Press the DELETE key (press the ESCAPE key with SY/MATE Plus) to clear the
error indication if the error was displayed on a monitor.
3. Follow the instructions in the "Recovery Procedure" column in Table A-1.
Error codes indicated by an asterisk (*) in the table may also be displayed in the status
register of a communications rung. Errors preceded by an "at" sign (@) may
sometimes be confused with transmission errors but can be differentiated by noting
that the words "Transmission Error" precede the error number in the case of a
transmission error.
A.2.2 Tape/Disk Errors
Tape or disk errors are generated when tape or disk operations are performed. When
the processor is operating with a Loader/Recorder or a MicroCell® Controller through
the use of communications rungs, the status register of that rung can be checked for the
presence of an error condition. Tape/disk errors are indicated with a bullet (•) in
Table A-1.
A.2.3 Transmission Errors
Communications errors due to hardware problems are displayed on the screen by the
message "Transmission Error" followed by a number.
The error code numbers that appear most frequently are numbers 1, 72, and 74. When
one of these errors occurs, follow these steps:
1. Check all cable connections and baud rates (register 8169).
2. Press the <ESC> key to clear the error indication.
3. When all connections are secure, retry the operation.
If the error persists, halting and cycling power to the processor causes the PRGMR
port to revert to default baud and word structure and may allow successful
communication with the programmer or workstation.
Appendix A - Error Codes
30598-526
Page A-3
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 1 of 10)
Error Code No.
@01*
@
•
*
Error Description (Possible Causes)
Recovery Procedure
Illegal protocol opcode; the SY/MAX device does
not recognize the instruction.
Reenter the desired operation.
02
Illegal intermediate code format.
Reenter the desired operation.
03
An illegal address has been attempted. SY/MAX
device does not contain the requested register(s).
1. For processors, use programming equipment to
check rack addressing and determine what
registers are present.
2. For D-LOG modules, check program for DIM
(DIMension) statement to allocate the S and F
arrays.
3. Change communications to access an existing
register.
04
Illegal rack addressing has been attempted.
Attempt was made to incorrectly edit rack
addressing.
1. Error may have been data-entry related; follow
rack addressing rules.
2. Check that hardware configuration is suitable for
the intended rack-addressing.
05*
1. An instruction has been attempted which is not
supported in this type processor. (Example:
square root calculation attempted in Model 300
processor.)
2. Incorrect mode set for NIM port connected to a
processor (receiving device). Mode set for
8881 mode or peripheral mode.
3. In a Net-to-Net link, the two NIMs have different
address settings (on thumbwheels), or link is
between '0' port on one and '1' port on the other.
1a. Check processor instruction set.
1b. Stop trying function in a processor with
reduced capability.
1c. Substitute a more capable processor, such as
Model 400 for Model 300.
2. Check NIM (Network Interface Module) mode
switch setting on side of module.
3. Check NIM (Network Interface Module) network
device number on front of module.
06
Item being searched for cannot be found.
Examine ladder diagram program. Use XREF
mode as alternate to SEARCH.
07*
An attempt has been made to alter data in a
protected register.
Check control register 8176 or 8178. Have an
authorized person unprotect the protected register.
08
An attempt has been made to alter protected
memory.
Check control register 8176 or 8178. Have an
authorized person unprotect the protected register.
09*
An attempt has been made to alter data in a READ
ONLY register or a register containing external
inputs.
Check rack addressing. Error 09 is seen frequently
when using Series G Model 300 Processor, LI and
intelligent I/O modules in CPU rack. This system
has special rack addressing requirements.
10
An attempt has been made to exceed memory
limitations.
Check CRT's CPU status screen for processor
memory size and words of memory used using
CRT programmer.
1. Examine program for wasteful use of memory.
2. Reduce non-essential data, like labels and rung
comments.
3. Substitute a SY/MAX device with more memory.
11*
Communications error. Receiving SY/MAX device
went into an oveflow condition.
Reenter the desired operation.
Errors preceded with the “at” sign (@) may at times be confused with transmission errors; note that the words “Transmission Error”
precede the error number if the error is a transmission error.
= Tape/disk error
May also be displayed in the status register of a communications rung
Appendix A - Error Codes
Page A-4
30598-526
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 2 of 10)
Error Code No.
@
•
*
Error Description (Possible Causes)
Recovery Procedure
12
Illegal CPU rack addressing. Attempted rack
addressing is incompatible with processor
hardware.
1. Refer to rack addressing section in programming
instruction bulletin.
2. Determine register capability of processor.
3. The Model 500 and 700 processors require
register assignments in the CPU rack to be
divisible by 4.
4. Substitute alternate processor.
13*
Communications error (link error). Message was
sent by processor; no response received. May be
caused by:
• Broken cable between the processor (initiating
device) and NIM.
• Local cable doesn't have CTS and RTS
jumpered at the NIM end of cable (CTS is low).
• Mismatched baud rates between processor
(initiating device) and NIM port.
• All network modules must be set for the same
network size, 30 drops or 100 drops, controlled
by DIPswitches and by software on SY/LINK
interface.
• Network interface module is powered down.
• Bad processor driver/receiver chips in port.
• Bad NIM driver/receiver chips in port.
1.Check cable connections between devices.
2. Check baud rates for compatibility between
communicating devices.
3. Check integrity of communication ports.
4. Check dipswitch settings on NIMs.
5. Check that NIMs have power applied to them.
6. Replace NIM and/or processor.
14
The operation that has been attempted is not
allowed in RUN.
1. Determine impact of halting SY/MAX device.
2. Halt SY/MAX device.
3. Perform operation in HALT mode.
15*
Communications overflow. The processor cannot
manage all communication mesages in the
allotted time.
1. Check the baud rate for compatibility between
communicating devices.
2. Reduce message activity reaching the
processor.
3. Schedule messages outgoing from processor to
slower rate. Do this using bit 16 of mesage #N in
order to trigger message #N+1.
4. Consolidate registers within processors so data
can be communicated in blocks.
5. Reenter the desired operation.
16
The register count in a communication rung is too
large for the processor.
The Model 300 register count maximum is 16.
The Model 400 register count is 128.
The Model 450 register count is 128.
The Model 500 pre-Series M register count is 64.
The Model 500 Series M and later is 128.
The Model 600 register count is 128.
The Model 650 register count is 128.
The Model 700 maximum register count is 64.
The PCM-110 Process Control Module register
count is 64.
Reduce the length of the message to proper
number of registers and perform multiple
communications.
Errors preceded with the “at” sign (@) may at times be confused with transmission errors; note that the words “Transmission Error” precede
the error number if the error is a transmission error.
= Tape/disk error
May also be displayed in the status register of a communications rung
Appendix A - Error Codes
30598-526
Page A-5
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 3 of 10)
Error Code No.
Error Description (Possible Causes)
Recovery Procedure
17*
Unable to establish communications to remote
SY/MAX device. This error is generated by a NIM
module or a SY/LINK interface.
Possible causes include:
• The second (or later) route address doesn't
exist in the network.
• Cable between remote NIM and receiving
device is broken or disconnected.
• Cable at remote NIM port doesn't have RTS
and CTS jumpered (CTS is low).
• Network (blue) cable shorted or open; Tee
connector or cable connector shorted or open;
Missing cable terminator(s); incorrect cable;
Cable length too long; Drop line(s) too long.
• Incorrect network baud rate set at local NIM
and/or remote NIM.
• Remote device powered down.
• Baud rates of remote NIM port and receiving
device port mismatched.
• Broken cable in Net-to-Net link.
• Mismatched baud rates in Net-to-Net link.
• Net-to-Net link cable doesn't have RTS and
CTS jumpered (CTS is low).
• Bad driver/receiver in receiving device.
• Bad driver/receiver in remote NIM.
1. Check cable connections at local and at remote
devices. Make sure cables are making good
contact.
2. Check BAUD rates for compatibility between
devices.
3. Check Network baud rate settings on side of
Network Interface Module.
4. Check that routing is correct and to valid device.
If using SY/LINK interface, use route xx,1xx to
use RS-422 port direct to a SY/MAX device.
5. Verify that remote device is present and powered
by performing communication with programming
equipment.
6. Confirm that port on remote SY/MAX device is
operable by performing communication with
programming equipment. If port is failed, move
cable to another SY/MAX device port. If all ports
are failed, repair or substitute SY/MAX device.
7. Check that the program in the remote SY/MAX
device is not changing the baud rate of the
communications ports.
8. Use substitute cable(s) to isolate failed cable or
connector on cable.
18
The rung number used is not allowed.
Reenter proper rung number.
19*
An illegal READ parameter has been assigned.
Check communication statement.
20
Channel number in a communication rung is too
large for the processor, or no channel number has
been specified. Valid channel numbers are 1 to 4.
1. Only the Model 700 allows channel number 4.
The Models 450 and 650 allow 1, 2, and 3.
Reduce channel number to 1 or 2 to work in a
Model 300, 400, 500 or 600 processor.
2. If installing a Model 700 program in another
processor, check for additional
communica?tions rungs using illegal channel
numbers.
21*
Cannot change a forced bit or write to an external
output while the bus master (processor or RI) is
in HALT.
1. Stop attempting to change the forced bit or stop
writing to external output of halted processor.
2. Determine reason bit is forced or reason
processor is halted. It may be critical.
22
The forcing function has been deliberately
inhibited from the processor COMM port.
Check Control Register 8176 or 8178.
23*
An attempt has been made to alter data in a
fenced register. A range of SY/MAX processor
registers hasbeen deliberately fenced.
1. Choose another register to alter.
2. Check Control Register 8173 and 8174.
3. Determine reason registers are fenced. It may
be critical.
4. Have an authorized person un-fence the
registers if possible. This requires the use of
programming equipment.
24
An attempt has been made to force a non-forcible
register.
If it is required to alter data in the non-forcible
register, modify via program control or DATA
ENTER mode.
@
•
*
Errors preceded with the “at” sign (@) may at times be confused with transmission errors; note that the words “Transmission Error” precede
the error number if the error is a transmission error.
= Tape/disk error
May also be displayed in the status register of a communications rung
Appendix A - Error Codes
Page A-6
30598-526
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 4 of 10)
Error Code No.
CPU error.
Check CPU control register 8175.
26
Rack addressing and user memory overlap.
Reduce rack addressing or program size and/or
reload program from tape/disk.
27*
Memory Error
A CLEAR PLC operation is required. If condition
persists, replace processor.
28
An illegal baud rate was selected. The SY/MAX
device cannot communicate at the selected baud
rate.
1. Check Control Register S8169.
2. Choose an alternate, usually lower, baud rate.
3. Change external device to the new baud rate.
29*
An attempt has been made to send a message
with an illegal route. Selected route is
incompatible with hardware configuration.
Possible causes:
• Route does not match network setting of NIM or
SY/LINK; check NIM module settings vs.
communications programming.
• Too many or too few route values in the
comunications rung; edit rung with
programming equipment.
• The use of route "201" as initial route can
alleviate this problem for portable hardware
applications; edit communication rungs with
programming equipment. Note: "201" can only
be used in first route position.
• One of the NIM ports in the route address has
been incorrectly set to Net-to-Net mode.
• In a Net-to-Net link, one of the NIM ports has
been incorrectly set to SY/MAX mode.
Check route information in communications rung.
Check NIM (Network Interface Module) network
device number on front of module.
Check NIM (Network Interface Module) network
switch setting mode on side of module.
30
An attempt has been made to alter protected
memory after the protect inhibit coil was entered in
memory.
Processor security has been invoked by the user to
prevent this operation. Check ladder program, and
choose another location to write to.
31* •
End of file encountered before the operation could
be completed.
Attempt operation again. Try to determine if the
problem is the tape or drive unit.
Editing operation is not allowed in protected
memory.
Processor security has been invoked by the user to
prevent this operation.
File data error detected; the block of data involved
in the READ or WRITE operation was faulty.
Attempt operation again. Try to determine if the
problem is the tape or drive unit.
34
For UVPROM processors only. The UVPROM is
not programmed or is not present. Read after
Write error, parity error, or security jumper was
removed and no UVPROM inhibit coil was
programmed into memory.
1. Check that UVPROM is present.
2. Verify that PROM inhibit coil was programmed
into memory.
35*•
The tape cartridge is not seated properly or is
missing, the RECORD tab on the cartridge has
been set to the WRITE INHIBIT position, or the
disk is write protected.
1. Examine tape cartridge and reseat.
2. Run directory to confirm that no valuable files
are on media.
3. Remove write protection and proceed.
33* •
•
*
Recovery Procedure
25*
32
@
Error Description (Possible Causes)
Errors preceded with the “at” sign (@) may at times be confused with transmission errors; note that the words “Transmission Error” precede
the error number if the error is a transmission error.
= Tape/disk error
May also be displayed in the status register of a communications rung
Appendix A - Error Codes
30598-526
Page A-7
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 5 of 10)
Error Code No.
@
•
*
Error Description (Possible Causes)
Recovery Procedure
36
Replace rung operations are not allowed on this
rung.
Use insert and delete operations only.
37* •
An attempt to skip or read a file was made when
already past the last file on the tape/disk.
Repack and rewind tape and try operation.
38
Program view inhibit in effect. Certain rungs have
been deliberately view inhibited.
Processor security has been invoked by the user to
prevent this operation.
39*
Alarm already set.
The D-LOG module already has received an alarm.
Modify D-LOG BASIC program to process alarms
more quickly.
40
Hardware memory security in effect. Memory
security jumper has been installed.
1. Remove power to processor.
2. Remove processor from rack, and remove
jumper.
3. Replace processor in rack, reapply power and
reprogram.
41*
An illegal register write.
The D-LOG module does not accept a register
WRITE into certain registers. Check registers in
D-LOG; change to a lower register, usually below
4000.
42
Illegal file number.
Refer to MicroCell Instruction Bulletin 30598-275.
43*
An illegal operation has been attempted.
D-LOG module is keyswitch protected.
44
File not found.
Refer to MicroCell Instruction Bulletin 30598-275.
45*
Operation not allowed. D-LOG tape operation in
progress. D-LOG cannot process certain
commands when in tape mode.
Retry after D-LOG tape operation is complete.
46
Protected file.
Refer to MicroCell Instruction Bulletin 30598-275.
47*
Operation is not allowed due to keyswitch position.
Adjust keyswitch position.
48
Programming MCR in subroutine area is not
allowed.
Illegal operation. Edit program to remove MCR;
rework control algorithm.
49
Register, channel or I/O is safeguarded. A
RAM/PROM processor has had registers
deliberately safeguarded.
The edit must be done by changing the safeguard
TLET rung located in the PROM portion of memory.
Check rung number 1 (TLET 8165).
50
Rack addressing is not alterable when forcing is
active. SY/MAX processors inhibit this possibility.
Illegal operation. Remove forcing before
performing rack address operation.
51*
A module is not seated properly, missing, no rack
address was assigned to the module, or the
address exceeds the capability of the processor.
1. Reseat suspect module(s).
2. Verify that all modules are present and
accounted for.
3. Confirm that rack addressing is correct.
4. Check processor address capability.
52
Illegal file type.
Refer to MicroCell Instruction Bulletin 30598-275.
Errors preceded with the “at” sign (@) may at times be confused with transmission errors; note that the words “Transmission Error” precede
the error number if the error is a transmission error.
= Tape/disk error
May also be displayed in the status register of a communications rung
Appendix A - Error Codes
Page A-8
30598-526
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 6 of 10)
Error Code No.
53*•
@
•
*
Error Description (Possible Causes)
Recovery Procedure
Illegal media format. Erase track/Clear memory
required.
Try erasing tape.
54
Illegal MARK number.
Use an unused or legal MARK number, that is, a
number below 8190.
55•
File operation aborted.
Retry.
56
Unused as a processor error.
Refer to MicroCell Instruction Bulletin 30598-275.
57
COMMS Queue Buffer Forced Emptied.
Refer to MicroCell Instruction Bulletin 30598-275.
58
Unused as a processor error.
Refer to MicroCell Instruction Bulletin 30598-275.
59
Battery Low
Refer to MicroCell Instruction Bulletin 30598-275.
60
Illegal MARK number for GOTO or GOSUB.
GOTO and GOSUB with number above 8190 not
allowed. Edit rungs to correct error.
61
MARK ST. SUB cannot be inserted - append only.
Load MARK Start Sub only at end of user memory.
62
RTN (return) rungs not allowed in ladder area.
Confine use of RETURN to subroutine area.
63
MARK number previously used.
Each MARK instruction must have a unique number
assigned. Edit rungs to correct error.
64
Operation not allowed while processor in RUN.
Cannot delete a RTN (Return) if any GOSUB
contains the same MARK number.
Illegal operation. Perform operation in HALT mode.
65
Operation not allowed. Cannot delete MARK Start
Subroutine unless all subroutines are deleted.
Illegal operation. Delete all subroutines prior to
deleting MARK ST. SUB (Start Subroutine).
66
Cannot delete MARK having RTN (return).
Delete RTN (Return) first.
67
RTN (Return) must have an associated MARK.
Add MARK or delete RTN (Return).
68
Only one RTN (Return) per MARK number is
allowed.
Illegal operation. Check program; the MARK
already has an associated RTN (Return).
69
Operation not allowed while processor is in RUN.
GOSUB cannot invoke a subroutine having no
RTN (Return).
Program Return statement or remove GOSUB.
70
Operation not allowed while processor is in RUN.
GOTO to MARK with RTN (Return).
RTN (Return) should only be used to conclude a
subroutine not a GOTO statement.
71
Operation not allowed while processor is in RUN.
Cannot delete MARK until all GOSUBs or GOTOs
with the same MARK are deleted.
Edit ladder to remove appropriate GOSUBs and
GOTOs and then delete the associated MARK.
72*
Operation not allowed while processor is in RUN.
Unused MARK number.
The MARK must be programmed before the GOTO
or GOSUB is programmed.
73
Unused as a processor error.
Errors preceded with the “at” sign (@) may at times be confused with transmission errors; note that the words “Transmission Error”
precede the error number if the error is a transmission error.
= Tape/disk error
May also be displayed in the status register of a communications rung
Appendix A - Error Codes
30598-526
Page A-9
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 7 of 10)
Error Code No.
Error Description (Possible Causes)
74*
Unused as a processor error. (Transmission error
74 is generated by the CRT.)
Possible reasons for transmission error 74 may be:
75
Unused as a processor error
76
Unused as a processor error
77
Unused as a processor error
78
Unused as a processor error
79
Operation is not allowed when the processor is in
RUN with programmable timed interrupt enabled.
Not allowed to program or edit ladder or clear all
forced I/O when processor is in RUN. Perform
operation in HALT mode.
80
Operation cannot be initiated due to insufficient
data. Too few parameters are indicated after a
command word.
Refer to MicroCell Instruction Bulletin 30598-275.
81
The command is not recognized. Examine for
validity.
Refer to MicroCell Instruction Bulletin 30598-275.
82
Illegal parameter. Re-check command syntax for
valid numeric values, register addresses, register
values, route values and filespec.
Refer to MicroCell Instruction Bulletin 30598-275.
83
Illegal source parameter. Out of range or not a
numeric value.
Refer to MicroCell Instruction Bulletin 30598-275.
84
Illegal destination parameter. Out of range or not
a numeric value.
Refer to MicroCell Instruction Bulletin 30598-275.
85
Invalid filespec. Inproper use of BUS port in
command device, ID doesn't match device in fdp,
or channel number above 5.
Refer to MicroCell Instruction Bulletin 30598-275.
86
Invalid input channel. Improper use of BUS port in
command device, ID doesn't match device in fdp,
or channel numbe above 5.
Refer to MicroCell Instruction Bulletin 30598-275.
87
Invalid output channel. Improper use of BUS port
in command device, ID doesn't match device in
fdp, or channel numbe above 5.
Refer to MicroCell Instruction Bulletin 30598-275.
88
Device not available. Bubble 'dead' (no 12VDC,
etc.)
Refer to MicroCell Instruction Bulletin 30598-275.
89
A serial link cannot be established. No
acknowledgement received.
Refer to MicroCell Instruction Bulletin 30598-275.
90
Hardware read fault. Checksum mismatch.
Refer to MicroCell Instruction Bulletin 30598-275.
91
Hardware write fault.
Refer to MicroCell Instruction Bulletin 30598-275.
@
•
*
Recovery Procedure
Check cable connections between devices.
Check baud rates for compatibility between
devices.
Check integrity of communication ports.
Check that NIM has power applied to it.
Replace NIM and/or processor.
Errors preceded with the “at” sign (@) may at times be confused with transmission errors; note that the words “Transmission Error” precede
the error number if the error is a transmission error.
= Tape/disk error
May also be displayed in the status register of a communications rung
Appendix A - Error Codes
Page A-10
30598-526
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 8 of 10)
Error Code No.
Error Description (Possible Causes)
92
An attempt to read data failed. Software
checksums mismatch outside of bubble RAM disk.
Refer to MicroCell Instruction Bulletin 30598-275.
93
An attempt to write data failed.
Refer to MicroCell Instruction Bulletin 30598-275.
94
An attempt to read from the directory has failed.
Refer to MicroCell Instruction Bulletin 30598-275.
95
An attempt to write to the directory has failed.
Refer to MicroCell Instruction Bulletin 30598-275.
96
Space reserved for directory data is full.
Refer to MicroCell Instruction Bulletin 30598-275.
97
Device space is full. Bubble or RAM full.
Refer to MicroCell Instruction Bulletin 30598-275.
98
The indicated file is not found in MCM memory.
Refer to MicroCell Instruction Bulletin 30598-275.
99
The file has been restricted and may not be
accessed. Attribute is limiting access.
Refer to MicroCell Instruction Bulletin 30598-275.
100
File already exists.
Refer to MicroCell Instruction Bulletin 30598-275.
101
The indicated file is already opened.
Refer to MicroCell Instruction Bulletin 30598-275.
102
An error exists in the format of the file. Format
doesn't match file type.
Refer to MicroCell Instruction Bulletin 30598-275.
103
The wrong type of file was indicated.
Refer to MicroCell Instruction Bulletin 30598-275.
104
Open attempt to open file.
Refer to MicroCell Instruction Bulletin 30598-275.
105
An external I/O attempted to unopen a file.
Refer to MicroCell Instruction Bulletin 30598-275.
106
An attempt was made to write to a read-only file.
Refer to MicroCell Instruction Bulletin 30598-275.
107
Record out of range. Offset is outside of program
size.
Refer to MicroCell Instruction Bulletin 30598-275.
108
Too many files are open. The attempt to open
another file exceeds MCM limitations.
Refer to MicroCell Instruction Bulletin 30598-275.
109
Operation aborted by user.
Refer to MicroCell Instruction Bulletin 30598-275.
110
A source filespec is required before the intended
operation will intitiate.
Refer to MicroCell Instruction Bulletin 30598-275.
111
A destination filespec is required before the
intended operation will initiate.
Refer to MicroCell Instruction Bulletin 30598-275.
112
The maximum number of files has been opened.
Subsequent attempts to open files without first
closing a selected or open file will not be allowed.
Refer to MicroCell Instruction Bulletin 30598-275.
113
The indicated source device and file type are not
in agreement. Recheck the fdp specification.
Refer to MicroCell Instruction Bulletin 30598-275.
114
The indicated destination device and filetype are
not in agreement. Recheck the fdp specification.
Refer to MicroCell Instruction Bulletin 30598-275.
115
Device timeout. Received acknowledgement, but
no reply.
Refer to MicroCell Instruction Bulletin 30598-275.
116
An attempt has been made to access a protected
system file.
Refer to MicroCell Instruction Bulletin 30598-275.
117
Illegal filetype. Filetype number out of range.
Refer to MicroCell Instruction Bulletin 30598-275.
Appendix A - Error Codes
Recovery Procedure
30598-526
Page A-11
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 9 of 10)
Error Code No.
Error Description (Possible Causes)
Recovery Procedure
118
Device number out of range.
Refer to MicroCell Instruction Bulletin 30598-275.
119
A filetype (f)dp must be indicated in the command
syntax.
Refer to MicroCell Instruction Bulletin 30598-275.
120
A device f(d)p must be indicated in the command
syntax.
Refer to MicroCell Instruction Bulletin 30598-275.
121
A port number fd(p) must be specified in the
command syntax.
Refer to MicroCell Instruction Bulletin 30598-275.
122
The communication routing must be defined in the
filespec syntax.
Refer to MicroCell Instruction Bulletin 30598-275.
123
The selected group of data must be defined with a
filename.
Refer to MicroCell Instruction Bulletin 30598-275.
124
The offset defining the starting point for data
retrieval within the file is not valid. Check value
and format for out of range, non-data.
Refer to MicroCell Instruction Bulletin 30598-275.
125
The count specified is invalid. Check if needed,
out of range, non-data.
Refer to MicroCell Instruction Bulletin 30598-275.
126
The device indicated in the source and destination
filespec cannot be identical.
Refer to MicroCell Instruction Bulletin 30598-275.
127
A duplicate label already exists.
Refer to MicroCell Instruction Bulletin 30598-275.
128
File mismatch. Compare command.
Refer to MicroCell Instruction Bulletin 30598-275.
129
The register address attempted is not valid.
Address above 8192 or below 0.
Refer to MicroCell Instruction Bulletin 30598-275.
130
The filename indicated is invalid.
Refer to MicroCell Instruction Bulletin 30598-275.
131
Write data error.
Refer to MicroCell Instruction Bulletin 30598-275.
132
Unused
Refer to MicroCell Instruction Bulletin 30598-275.
133
Insufficient data for write.
Refer to MicroCell Instruction Bulletin 30598-275.
134
Unused
Refer to MicroCell Instruction Bulletin 30598-275.
135
Invalid read parameter.
Refer to MicroCell Instruction Bulletin 30598-275.
136
A communication parity error exists.
Refer to MicroCell Instruction Bulletin 30598-275.
137
Busy data transfer, or weld in progress.
Refer to MicroCell Instruction Bulletin 30598-275.
138
Communication overrun error.
Refer to MicroCell Instruction Bulletin 30598-275.
139
Communication framing error.
Refer to MicroCell Instruction Bulletin 30598-275.
140
Dropped unexpected reply message. Reply
message received after device timeout (error 115),
or no command expecting a reply.
Refer to MicroCell Instruction Bulletin 30598-275.
141
Job space full. Maximum of eight jobs.
Refer to MicroCell Instruction Bulletin 30598-275.
142
Unused
Refer to MicroCell Instruction Bulletin 30598-275.
143
Unused
Refer to MicroCell Instruction Bulletin 30598-275.
Appendix A - Error Codes
Page A-12
30598-526
Table A-1: Peripheral-to-PLC System Interaction Errors
(Page 10 of 10)
Error Code No.
Error Description (Possible Causes)
Recovery Procedure
144
Unused
Refer to MicroCell Instruction Bulletin 30598-275.
145
Write sequence not initiated.
Refer to MicroCell Instruction Bulletin 30598-275.
146
Unused
147
Memory full.
148
Unused
149
No data found.
Refer to MicroCell Instruction Bulletin 30598-275.
150
An attempt to stop attached Batch Job.
Refer to MicroCell Instruction Bulletin 30598-275.
151
Illegal communication to COMM Port.
Refer to Transfer Network Interface Module
Instruction Bulletin #30598-150.
152
Unused
153
Error noted during a transfer.
Refer to MicroCell Instruction Bulletin 30598-275.
Refer to Transfer Network Interface Module
Instruction Bulletin #30598-150.
A.3 PLC SYSTEM OPERATIONAL ERRORS
PLC system operational errors occur somewhere in the overall PLC system and consist
of a five-digit decimal value. These error codes (ERROR NUMBERS) are the
contents of the Control Register 8175 data field (bits 1-16). Seven possible
classifications of operational error codes exist (see Table A-2). Section A.3.1 through
Section A.3.6 describe each type of error.
When an error condition occurs, the appropriate error code is loaded into Control
Register 8175 only if the register contains zero or if it currently contains an error code
of lower priority (a smaller number). The previous error code is then lost (in a Model
300) or moved to Register 8183 (in a Model 500 or 700), or possibly moved to a stack
of 16 registers designated by Register 8107 in a Model 400, 450, 600 and 650
processors.
Appendix A - Error Codes
30598-526
Page A-13
Table A-2: PLC System Operational Errors
Error Number
Type of Error
00001 - 00999
General Error
01000 - 09999
Processor Communications Port Error
10000 - 18192
Read After Write Error
19000 - 19016
Slot Error
20000 - 28192
Slot Register Error
29000 - 29999
Miscellaneous Error
30000 - 32700
CPU/LI Error
The same operational errors are used by the Local/Remote Interface and by the
Transfer Interface System to indicate errors in devices under their control. In this case,
control register 8175, which is the Error Number in the monitor ONLINE/STATUS
mode display, indicates the starting register address of the Local Interface or Local
Transfer Interface which has the problem. Once located, inspection of the error code
control register associated with the Local Interface or Local Transfer Interface
(example: S8163) will reveal which of the remote devices contains the error.
Appendix A - Error Codes
Page A-14
30598-526
A.3.1 General Errors (00001 - 00999)
The error code for general errors consists of the last three digits in the five-digit error
number in the status display. See Table A-3 for a description of the general error codes.
Format of General Error Code
0 0 E EE
Error Code
(See Table A-3)
NOTE
91X or 929 error codes indicate an Ethernet problem; see Section 15.7
for more information.
Table A-3: General Errors (00001 - 00999)
Error Code
(EEE)
Description
900
Control registers are corrupted.*
901
Data registers are corrupted.*
902
Undervoltage Lockout is engaged (see Section 3.5).
960
HALT or HALT/RUN bit is set.
962
Tolerance is equal to or greater than the rate.
963
Timed interrupt timebase is less than 3.
964
GOTO and GOSUB are assigned the same MARK.**
965
Illegal internal error code.
966
User subroutine stack error.**
967
A MARK rung with the same number is required.**
968
GOTO to MARK doesn’t require a RTN rung.**
969
A subroutine MARK is lacking a RTN (Return).
970
Scan time of processor is greater than 1 second, or scan limit in register
8167 has been exceeded.***
971
Long scan due to LTI start-up transfer (check register 8184 for elapsed
time in milliseconds).
979
Rack addressing is missing.
980
Keyswitch is in RUN, but no program is in memory.
983
Safeguarding rung is illegally programmed or missing.
984
An undefined register is programmed in user memory.***
985
The processor is not installed in slot 1 although rack addressing is
present.
*
Toggling the keyswitch allows the CPU to go into RUN. Control registers are normalized
and data registers are cleared.
**
S8184 will contain the MARK number.
***S8184
Appendix A - Error Codes
will contain the rung number being executed when the error occurred.
30598-526
Page A-15
A.3.2 Processor Communications Port Error (01000 - 09999)
A communications port error occurs whenever the processor does not receive a valid
reply to a message it sends out of one of its serial ports. The error is cleared if a
subsequent transmission does receive a valid reply.
To clear a communications port error, toggle the processor keyswitch from HALT to
RUN, or clear register 8175. Be sure to check remote device and cable connections.
The third and fourth digits in the five-digit error number identify what type of
communications error occurred, while the second digit in the error number is the port
in which the error occurred.
See Table A-4 for a description of the communications port error codes.
Format of Communications Port Error Code
0 P E E0
Error Code
(See Table A-4)
Port Number
Indicates which processor port is experiencing
the error (1 = Ch 1; 2 = Ch 2)
Table A-4: Communications Errors (01000 - 09999)
Error Code
(EE)
Description
11
Communicatios overflow
12
Buffer overflow
13
Illegal data
14
Wrong reply (odd/even)
15
Checksum error
16
Framing error
17
Parity error
18
Unable to communicate through indicated port
19
Retry timeout
Appendix A - Error Codes
Page A-16
30598-526
A.3.3 Register Read After Write Error (10000 - 18192)
A read after write error indicates a particular bit in a register has not maintained the
condition written to it by the processor. The error code consists of the last four digits of
the five-digit error number, and will point out which register encountered the problem.
Format of Read After Write Error Code
1 E E EE
Error Code
Points to the register that encountered
the problem
By displaying the status field (bits 17-32) of the control register containing the read
after write error code, the bit or bits causing the malfunction will be indicated by a “1”.
Since each register contains both a status field and a data field, control register 8184 is
used to indicate which set of bits contains the problem.
- - - - E
Bits in Control Register 8184
0 = Data Field
1 = Status Field
If the faulty register is used to control outputs, and Control Register 8184 indicates the
bad bits are contained in the data field, the most likely cause for the problem is an
output module.
Figure A-1 can help isolate the output module having a read-after-write problem. The
status field of register 8175 is divided either four ways (for four-function output
modules), or two ways (for eight-function modules):
32
29 28
4-Function
Module #4
25 24
21 20
4-Function
Module #2
4-Function
Module #3
17
4-Function
Module #1
or
32
25
8-Function
Module #2
24
17
8-Function
Module #1
Figure A-1 Status Field (Bits 17-32) of Register 8175
If any of the bits in the status field of register 8175 are set to “1”, that bit was read
incorrectly. If, however, all bits in the register are at “0”, then a parity error was
detected. At least one bit should normally be “1”.
Appendix A - Error Codes
30598-526
Page A-17
A.3.4 Slot Error (19000 - 19016)
In the event of a slot error, the error code consists of the last two digits in the five-digit
error number, and points out the slot number experiencing the error.
Format of Slot Error Code
1 9 0 EE
Error Code
Points to the slot number that experienced the
problem
A.3.5 Miscellaneous Errors (29000 - 29999)
In miscellaneous errors, the error code consists of the last three digits of the five-digit
error number. See Table A-5 for a description of the miscellaneous error codes.
Format of Miscellaneous Error Code
2 9 E EE
Error Code
(See Table A-5)
Table A-5: Miscellaneous Errors 29000 - 29999)
(Page 1 of 2)
Error Code
(EEE)
Description
000
Subroutine nesting error.*
100
The time to process the timed interrupt subroutine has exceeded the time
base.*
101
Timed interrupt routine is missing.
102
The time required to solve a rung has exceeded the tolerance set within a
timed interrupt.*
103
Attempted to set up timed interrupt while interrupt is already running.
104
Attempted to return from a timed interrupt that wasn’t running.
300
Mixed Primary/Back-up LTIs in CPU rack.**
301
LTI timeout on EOS transfer.***
302
LTI timeout on start-up transfer.***
500
Register assignment conflict: number of assigned Local Interface
registers must be at least 8 for one defined channel and 12 for two
defined channels.
501
Insufficient number of local interface control registers.
510
RTI wired improperly: Ports A & B are mixed.
511
LTIs in CPU racks A and B have equal states of operation and no primary
determination can be made in HALT.
512
Backup transfer system cannot be in RUN when primary transfer system
is in DISABLE OUTPUTS.
Appendix A - Error Codes
Page A-18
30598-526
Table A-5: Miscellaneous Errors 29000 - 29999)
(Page 2 of 2)
Error Code
(EEE)
Description
513
Rack addressing between LTIs in racks A & B is not the same.
514
Backup cannot be run with test bit set when primary goes to HALT.
Backup must also go to HALT.
515
Backup cannot become primary until synchronization has occurred and
primary goes to HALT.
516
Backup unable to become primary because a remote bus error exists.
This error is also produced by the primary to allow transfer to backup
when primary is keyswitched to HALT.
517
Backup has lost synchronization and does not have RTC Failure Override
bit set.
518
Two primary processors were found in RUN; this processor was halted
with a bus error.
*
Control register 8184 contains the rung number where the error occurred. If 8184 is
zero, check the rack addressing.
**
The data field of Control Register 8184 contains the bit table of primary or backup
status (bit set means primary), while the status field of control register 8175 identifies
the slots that contain LTIs (bit set means LTI is present).
***
The data field of Control Register 8184 identifies the first register assigned to the LTI
that caused the error. The status field of 8175 contains the elapsed time (in milliseconds)
that the scan was held.
A.3.6 CPU/LI Errors (30000 - 32700)
If there is a problem with the processor (CPU), Local Interface Module (LI), or Local
IO/NET Interface Module (LIO), one of the error codes shown in Table A-6 may
appear. The five-digit error code provides the error type number (TT), the channel
number (C), and drop number (D).
Format of CPU/LI Error Code
3 T T CD
Drop Number
Drop “0” indicates that the error is a CPU
or LI/LIO error. Drop numbers greater than
zero indicate a Remote Interface (RI/RIO)
error.
Channel Number
Channel “0” indicates that the error is a
CPU or LI/LIO error.
Channel numbers greater than zero
indicate a Remote Interface (RI/RIO)
error.
Error Type Number
(See Table A-6)
Appendix A - Error Codes
30598-526
Page A-19
Table A-6: CPU/LI Errors (30000 - 32700)
Error Type
(TT)
Description
00
Status register - READ/WRITE parity error.
01
Image RAM - READ/WRITE parity error.
02
Internal register data error.
03
Illegal PROM format.
04
Illegal opcode encountered while processor was in RUN mode.
05
Bus signal error (interrupt detected on bus).
06
Software watchdog error.
07
Not used.
08
Software diagnostic error.
09
User memory - READ/WRITE parity error.
10
Illegal data in user memory.
11
PROM memory is corrupted.
12
Illegal addressing map code.
13
Transmission error exceeded tolerance.
14
Loss of transmission.
15
Number of external I/O registers assigned exceeds the module’s capacity.
16
Too many registers are assigned to the drop.
17
More than 8 drops per channel are assigned.
18
Number of channels addressed exceeds module capacity, or channel 2 of
LTI system is not rack-addressed.
19
Addressing map checksum error.
20
Bus error - watchdog timeout.
21
CPU diagnostic error.
22
Parity circuit is non-functional.
23
Clear line error.
24
Executive scratch RAM error.
25
Watchdog tolerance error.
26
Hardware diagnostic error.
27
Module is inactive.
Appendix A - Error Codes
Page A-20
30598-526
A.4 USING ERROR CODES TO ISOLATE PLC SYSTEM FAULTS
When a PLC system malfunctions after it has been operating correctly, one of three
situations can arise:
1. The entire PLC system shuts down and the processor halts.
2. One or more drops may shut down and the processor remains in run.
3. A runtime communications port error is detected.
Once the malfunction is identified as existing in one of these three categories, the PLC
System Operational Error Codes can be used to isolate the fault.
Recognition of the first category is obvious; however, the second category can exist
only when the PLC system includes remote I/O and the Failure Override bit (bit 13) is
set in the Local Interface Module, Local IO/NET Interface Module, or Local Transfer
Interface Module. (For more information on the Local Interface Module (LI), please
refer to Instruction Bulletin #30598-175; for more information about the Local
IO/NET Interface Module (LIO), please refer to Instruction Bulletin #30598-782.)
The third category of malfunction deals with communications to external devices and
requires that control register 8175 be monitored by the program for errors in the range
01000 to 09999. These types of errors are generated by the processor itself and not by
an external device.
Each of the three malfunction situations is described in the following sections.
A.4.1 When the Entire PLC System Shuts Down
When the processor halts, control register 8175 should be the first point of
interrogation. Register 8175 stores the last error code that occurred; if more than one
error occurred, the most serious or highest-priority error code is stored in that register.
(See Chapter 13 for additional information about control registers.) The error code in
Register 8175 will be within the error number ranges shown in the first column of
Table A-7. The table also provides references to sections and tables in this instruction
bulletin that describe the error type.
Table A-7: PLC System Operational Errors
Appendix A - Error Codes
Refer to
Section
Refer to
Table
General Error
Section A.3.1
on page A-14
Table A- 3 on
page A-14
10000 - 18192
Read After Write Error
Section A.3.2
on page A-15
19000 - 19016
Slot Error
Section A.3.3
on page A-16
20000 - 28192
Slot Register Error
Section A.3.4
on page A-17
29000 - 29999
Miscellaneous Error
Section A.3.5
on page A-17
Table A- 5 on
page A-17
30000 - 32700
CPU/LI/LIO Error
Section A.3.6
on page A-18
Table A- 6 on
page A-19
Error Number
Type of Error
00001 - 00999
30598-526
Page A-21
If a slot register error (code 20000-28192) is indicated, one of two courses of action
can be taken, depending on the specific register number shown in the last four digits of
the error code.
1
If the indicated register is the first one assigned to a register module,
interrogating the status field of that register will indicate the error. Refer to the
appropriate register module instruction bulletin for more specific information.
2
If the indicated register is the first one assigned to a Local Interface Module
(LI) or to a Local IO/NET Interface Module (LIO), used with remote I/O,
further interrogation of the LI or LIO error code register is required. Refer to
Appendix D of the LI/RI instruction bulletin (#30598-247) to determine the
address of the LI error code registers. Refer to the LIO instruction bulletin
(#30598-782) for information about the LIO error code registers. If only a single
LI or LIO exists in the system, register 8163 is the error code register.
When the LI or LIO error code register is interrogated, the error code number will
be in the following ranges:
10000 - 18192
20000 - 28192
30000 - 32728
Read After Write Error
Slot Register Error
Processor/LI (or LIO) Error
In the case of a read after write error (code numbers 10000 - 18192), the affected
bit or bits are indicated in the status field of the LI or LIO error code register.
A.4.2 Troubleshooting Checklist
The following checklist provides a procedure to follow when examining a PLC system
if it shuts down completely.
Step 1
Interrogate
contents of
Register 8175
IF 30000-32700
Go to Section A.2.1,
“Processor Errors”
IF 29000-29999
Go to Section A.3.5,
“Miscellaneous Errors”
IF 20000-28192
Go on to Step 2
IF 10000-18192
Read status field of S8175 for bits and
refer to Section A.3.3.
IF 0001-9999
Go to Section A.3.1, “General Errors”;
interrogate control register S8184
when indicated.
Appendix A - Error Codes
Page A-22
30598-526
Step 2
Determine the
slot to which the
register is
assigned using
the error code
(register number)
indicated by the
last four digits of
the error number.
Step 3
Interrogate the LI
or LIO error code
register.
IF the indicated
register is
assigned to a
register module
Examine the status field of the register
number indicated by the error code.
Refer to the appropriate register
module instruction bulletin for the
meaning of the error number.
IF the indicated
register is assigned
to an LI or LIO
module
Interrogate the LI or LIO error code and
go on to Step 3.
IF the LI or LIO
error code is
30000-32728
Go to Section A.2.1, “Processor
Errors,” and follow the instructions
given for the error code.
IF the LI or LIO
error code is
20000-28192
Referring to the register number shown
by the error code (last 4 digits),
determine the slot to which the register
is assigned. The register module in that
slot is the module that generated the
error.
Examine the status field of that register.
Refer to the appropriate register
module instruction bulletin for the
meaning of the error number.
IF the LI or LIO
error code is
10000-18192
Step 4
Make sure that
the LI or LIO
Module is seated
securely.
Appendix A - Error Codes
Examine the status field of the LI or LIO
error code register for an indication of
the affected bits. Refer to Section A.3.3.
30598-526
Page A-23
A.5 MALFUNCTION EXAMPLES
Shown in Figure A-2 is a sample PLC system experiencing one of four different
malfunctions. Each area of malfunction is indicated by a circled number. The steps
needed to isolate each type of problem, based on the checklist in Section A.4.2, are
explained.
The problem areas are:
1. The processor itself
2. The Local Register Module
3. The Remote Register Module
4. The Remote I/O Module
5. The interconnecting cables.
A.5.1 Sample PLC System Shutdowns
The following “shutdown” examples are not intended to show all possible PLC system
malfunctions; they illustrate only some of the more typical problems encountered with
PLC systems.
Refer to Figure A-2 and to Section A.4.2 when reviewing the following examples.
4-POINT DIGITAL I/O MODULES
1
M450
2
LI
3
4
101
117
9
1
REG
REG
REG
RI
5
1
1
RI
2
3
25
41
REG
REG
4
5
42
1
2
100
116
CPU RACK
3
132
24
8
40
DROP 1
5
56
DROP 2
NOTE: Arbitrary register assignments have been
added to this diagram to aid in the following
explanations.
Figure A-2 Sample PLC System
Appendix A - Error Codes
Page A-24
30598-526
1
MALFUNCTION IN THE PROCESSOR
A malfunction in the processor itself would cause the system to shut down. The PLC
system troubleshooting checklist in Section A.4.2 should be used when working with
this example.
Result of Step 1: Since the malfunction occurred in the processor itself,
interrogating control register 8175 will result in an error code number that will help
further identify the processor fault. A typical error code in this instance would range
from 30000 to 32700.
2
MALFUNCTION IN A LOCAL REGISTER MODULE (LOCATED IN CPU
RACK)
A major malfunction in a register module located in the CPU rack would cause the
system to shut down, regardless of whether any Failure Override bits are set. The PLC
system troubleshooting checklist in Section A.4.2 should therefore be used.
Result of Step 1: Interrogating control register 8175 would result in an error code
number 20101.
Result of Step 2: The error code indicates the register module existing in slot #3 of
the CPU rack has malfunctioned, since it is the module containing register 101 as the
first register address. By looking at the status field of register 101 and then referring to
the appropriate register module instruction bulletin, the specific error can be
determined.
3
MALFUNCTION IN A REMOTE REGISTER MODULE
A malfunction in a register module located in a remote rack would cause the system to
shut down if the Failure Override bit in the LI/LIO module is not set. If this is the case,
the troubleshooting steps shown in Figure A-3 on page A-26 should be used.
Result of Step 1: Interrogating control register 8175 would result in an error code
number 20001.
Result of Step 2: The register number indicated in the error code is 001, which is the
first register in the LI/LIO. Interrogating the LI/LIO error code register (in this case
8163), will provide additional information as to which module in the remote I/O
system caused the shutdown.
Result of Step 3: Interrogating the LI/LIO error code register would result in an
error code number 20041. Since the register module in drop 2, slot 3 contains register
41, that module is responsible for the system shutdown. By looking at the status field
of register 41 and then referring to the appropriate register module instruction bulletin,
the specific error can be determined.
4
MALFUNCTION IN A REMOTE DIGITAL I/O MODULE
A malfunction in a digital output module located in a remote rack will cause the
system to shut down if the Failure Override bit in the LI/LIO module is not set. If this
is the case, the troubleshooting steps shown in Figure A-3 on page A-26 should be
used.
Result of Step 1: Interrogating control register 8175 would result in an error code
number 20001.
Appendix A - Error Codes
30598-526
Page A-25
Result of Step 2: The register number indicated in the error code is 001, which is the
first register in the LI/LIO. Interrogating the LI/LIO error code register (in this case
8163), will provide additional information as to which module in the remote I/O
system caused the shutdown.
Result of Step 3: Interrogating the LI/LIO error code register would result in an
error code number 10001. Looking at the status field of register 8163 will provide the
bit mask that indicates which output module associated with register 001 caused the
failure.
5
COMMUNICATION ERROR BETWEEN LI AND RI MODULES, OR
BETWEEN LIO/RIO/DRIO MODULES
A communication error that occurs between local and remote interface modules
(LI/LIO or RI/RIO/DRIO) will cause the system to shut down if the Failure Override
bit in the LI/LIO module is not set. If this is the case, the troubleshooting steps shown
in Figure A-3 on page A-26 should be used.
Result of Step 1: Interrogating control register 8175 would result in an error code
number 20001.
Result of Step 2: The register number indicated in the error code is 001, which is the
first register in the LI/LIO. Interrogating the LI/LIO error code register (in this case
8163), will provide additional information as to which module in the remote I/O
system caused the shutdown.
Result of Step 3: Interrogating the LI/LIO error code register would result in an
error code number 31412. By referring to Section A.3.1, you would see that a
transmission error has occurred on channel 1, drop 2. Transmission errors result from
many causes, including defective cables, electrical noise, LI/LIO or RI/RIO
communication chip malfunction, inadequate power, or improperly set DIP switches.
Further investigation is required to pinpoint the problem.
Setting the Failure Override bit for the respective channel experiencing the failure (bit
8162-13 for this example), allows the processor to ignore the error and remain in RUN,
although information associated with the failed drop is no longer valid. Similarly,
setting the Auto Restart bit for the channel (bit 8162-15) causes the LI/LIO module to
keep attempting to reestablish communication. Thus, in the event the transmission
error was caused by a transient condition, the failed drop experiences only a
momentary disruption.
A.5.2 Remote Rack Shutdown
When a remote rack halts without causing the rest of the system to halt (Failure
Override bit set for that channel), the error code register of the LI or LIO module
controlling that drop will contain the error number of the fault. When the LI error code
register is interrogated, the number will be in the the following ranges:
10000 - 18192
20000 - 28192
30000 - 32700
Read After Write Error
Slot Register Error
Processor/LI (or LIO) Error
In the case of a read after write error (code numbers 10000 - 18192), the affected
bit or bits are indicated in the status field of the LI or LIO error code register.
Appendix A - Error Codes
30598-526
Page A-26
A.5.3 Troubleshooting a Remote Rack Shutdown
The LI or LIO error code register is the key to determining the cause of a remote rack
shutdown.
Interrogate
contents of
appropriate LI
or LIO error
code register
IF 30000-32728
Go to Section A.2.1,
“Processor Errors”
IF 20000-28192
Using the register number from the
error code (last four digits), determine
the slot to which the register is
assigned. The register module in that
slot generated the error. Examine the
status field of that register, then refer to
the appropriate register module
instruction bulletin for the meaning of
the error number.
IF 10000-18192
Examine the status field of the LI/LIO
error code register for an indication of
the affected bits. Refer to Section 3.3,
“Register Read After Write Error
(10000 - 18192)”.
Figure A-3 Troubleshooting Steps for a Remote Rack Shutdown
Using malfunctions #3 and #4 in Figure A-2 on page A-23 as examples, and following
the procedures in the troubleshooting diagram, go through the following steps to
isolate each type of problem.
The two main problem areas are 1) the remote register module and 2) the remote I/O
module.
1
MALFUNCTION IN A REGISTER MODULE LOCATED IN A REMOTE
RACK
A malfunction in a register module located in a remote rack will cause only that rack
(drop) to shut down, assuming the Failure Override bit in the LI/LIO module is set. If
this is the case, use the procedures shown in Figure A-3.
Following are the results of applying these procedures:
Result: Interrogating the LI/LIO error code register (8163 in this case) would result in
an error code 20041. Since the register module in drop 2, slot 3 contains register 41,
that module is responsible for the system shutdown. Examine the status field of
register 41 and refer to the appropriate register module instruction bulletin to
determine the specific error.
Appendix A - Error Codes
30598-526
2
Page A-27
MALFUNCTION IN A DIGITAL I/O MODULE LOCATED IN A REMOTE
RACK
A malfunction in a digital output module located in a remote rack will cause only that
rack (drop) to shut down, assuming the Failure Override bit in the LI/LIO module is
set. If this is the case, use the procedures shown in Figure A-3.
Result: Interrogating the LI/LIO error code register (8163 in this case) would result
in an error code number 10001. Looking at the status field of register 8163 will provide
the bit mask that indicates which output module associated with register 001 caused
the failure.
A.5.4 “PRGMR” or “COMM” Port Errors
These kinds of errors are different from the processor errors associated with
communications listed earlier in this Appendix in that processor communication port
errors are detected by the processor rather than by the external communicating device.
The only processor error that has any relationship to processor communication port
errors (01000-09999) is processor error code 13. When error 13 is indicated in a status
register of a communications rung, interrogation of control register 8175 results in the
display of one of the processor communication port errors (01000-09999).
Communications port errors can also be detected when an external device is asking for
information from the processor.
Appendix A - Error Codes
Page A-28
30598-526
NOTES
Appendix A - Error Codes
30598-526
Page B-1
APPENDIX B
USING THE PROCESSOR WITH THE LOCAL/REMOTE
TRANSFER INTERFACE MODULES
The purpose of this appendix is to point out some of the operating characteristics to be
expected when using the Local/Remote Transfer Interface (LTI/RTI) modules (Class
8030 Type CRM230/232 modules) with the Model 450 processor.
NOTE
Be sure that you are familiar with the material contained in the LTI/RTI
instruction bulletin (#30598-251) when using this appendix.
Because the LTI/RTI Instruction Bulletin (#30598-251) is geared to the Model 500 and
700 processors and was written before the Model 450's creation, some of the
information contained in that bulletin does not apply to Model 450 operation.
CAUTION
UNINTENTIONAL EQUIPMENT OPERATION
Certain application considerations must be observed when
using the Model 450 in systems with Transfer Interfaces. This is
particularly true in systems originally designed for Model 500 or
Model 700 processors. Do not use the Model 450 with LTI/RTI
systems until you are familiar with the material in this Appendix.
Failure to observe this precaution can cause equipment damage or
personal injury.
B.1 GENERAL INFORMATION
As described in the Local/Remote Transfer Interface System Instruction Bulletin
(30598-251), system redundancy is actually accomplished via the LTI modules, not the
processor. Through the LTI-to-LTI high-speed Register Transfer Channel (RTC) link
and the respective LTI-to-RTI I/O channel links, the primary and backup LTI modules
exchange the information necessary to maintain the backup in a state of readiness to
seize control of the system's I/O in the event of a failure in the primary rack.
Because the register data actually resides in the image table of the Model 450, it must
be passed from the primary Model 450 CPU to the primary LTIs, then to the backup
LTIs, and finally to the backup Model 450 CPU. The quantity of registers to update is a
function of rack addressing and the type of transfer (start-up or end-of-scan) that is
occurring.
Appendix B - Using the Processor with LTI/RTI Modules
Page B-2
30598-526
B.2 RACK ADDRESSING
Because the Model 450 occupies a single slot, the first LTI module can be installed in
slot 2 of the CPU rack. When rack addressing the system, assign only as many
registers to the LTI slot as is required by the user program. Because registers assigned
to the LTI(s) are exchanged during a start-up transfer, any registers that are
unnecessarily assigned will extend the start-up transfer time. Thus, when laying out the
system, use storage registers with low-numbered addresses.
Start-up transfer time can be further reduced by setting the Start-up Transfer Register
equal to the number of registers that are assigned to the LTI slot (the Start-up Transfer
Register is the first of four registers assigned to LTI channel 2, drop 1). As explained in
Section B.3 following and in Section 5.4.2 of the LTI/RTI bulletin, this practice
minimizes the number of registers that the primary LTI writes to the backup LTI.
In a multiple LTI system, group the data storage registers in the last (rightmost) LTI, as
shown in Section 5.3.6 of the LTI/RTI bulletin. As previously mentioned, assign only
as many registers to the LTI slot as is required by the user program. Also, the Start-up
Transfer Register for each LTI should be set equal to the last (highest) register assigned
to the LTI slot.
B.3 STARTUP TRANSFER DELAY
Use the following equation to estimate total start-up transfer delay time:
DELAY (msec) = (0.03 x RA) + (0.26 x ERT) +(0.17 x IRT)
Where:
RA is the total number of registers rack addressed to the LTI
ERT is the number of external I/O registers in the LTI being transferred
IRT is the number of internal storage registers in the LTI being transferred.
Assume, from the example of the LTI/RTI Instruction Bulletin Section 5.4.2, that
1,000 registers are to be transferred from the primary to the backup (as specified by
setting S73 = 1,000). In accordance with Section B.2 and the above equation, if 1,000
registers are rack addressed to the LTI, total start-up transfer delay is:
(0.03 x 1000) + (0.26 x 76) + (0.17 x 924) = 207 milliseconds
If the start-up transfer was not preset to limit (to 1000) the number of registers
transferred and the maximum number of registers were rack addressed to the LTI
(4096), the start-up delay would be much longer. The start-up delay now becomes:
(0.03 x 4096) 1 (0.26 x 76) ~ (0.17 x 4,020) = 826 milliseconds
In a multiple LTI system, start-up transfer delay time will be longer than indicated by
the above equation. In many cases, the delay time will exceed one second, and will be
based on system configuration factors such as the number of LTIs present and the
register distribution between them. When this occurs, error 971 will appear in register
8175 and the actual elapsed time in milliseconds will be posted in register 8184. It may
be possible to decrease this time by following the recommendations of the LTI/RTI
Instruction Bulletin, Section B.2, especially rack addressing to the LTIs only the
quantity of registers utilized in the user program.
Appendix B - Using the Processor with LTI/RTI Modules
30598-526
Page B-3
NOTE
The processor's scan time limit (default is 1 second) is not active
during a start-up transfer. If the scan limit is exceeded, Error 971 is
posted in the backup processor as a flag to note the long transfer
time, and is not indicative of a system error or improper operation.
B.4 END-OF-SCAN (EOS) TRANSFER
At the end of each ladder scan, 32 registers can be transferred from the primary LTI to
the backup LTI via the Register Transfer Channel (RTC). Transferring these registers is
intended to maintain synchronization of critical internal registers that might otherwise
differ. This difference may be due to communication with external devices, timer drift,
etc.
NOTES
• Unlike the SY/MAX Models 500 or 700, the position of the Model 450's
32-register EOS transfer block is FIXED. It must occupy relative
registers 260-291 assigned to an LTI. Thus, any program written for the
Model 500 or 700 that uses the EOS Transfer feature must be
configured for this restriction.
• Enabling the EOS Transfer feature adds approximately 6 milliseconds
to the processor scan time.
• An easy way to determine the starting address for the EOS transfer
block is to add 259 to the first register assigned to the LTI slot
(provided, of course, that at least 291 registers are assigned to the
LTI).
To set up the EOS transfer, preset the contents of the EOS Transfer Register to the
address of the 260th register assigned to the LTI (the EOS Transfer Register is the
second of four registers assigned to LTI channel 2 drop 1). To execute the transfer, set
the EOS Transfer Register bit (bit 16 of the backup LTI's RTC Control Register). This
causes the values of the 32 registers (registers 260 through 291) to be transferred at the
end of every scan.
Refer to the multiple LTI example in Section 5.3.6 of the LTI/RTI bulletin. Because the
first two LTIs do not have at least 291 registers assigned to them, no EOS transfer is
possible. The rightmost LTI, however, could transfer registers 396-427 (relative
registers 260-291). To activate the transfer, preset the EOS Transfer Register (S202)
equal to 396, and set the EOS Transfer Register bit to “1” (bit 16 of register 8155).
If more than 32 registers need to be transferred, use a matrix instruction within the
application program to transfer different 32-register blocks into the EOS Transfer block
(registers 396-427 in the above example). Refer to Section B.8 for an application
example.
Appendix B - Using the Processor with LTI/RTI Modules
Page B-4
30598-526
B.5 I/O UPDATE
As described in Section 14.2 of this bulletin, the Model 450 performs an I/O update of
modules in the CPU rack at the end of every scan. For an LTI, the first 291 registers (if
this many are assigned) MUST be transferred between the image table of the Model
450 and the LTI(s). This transfer, along with some “overhead” due to LTI-to-processor
handshaking, results in an I/O update time of about 15 milliseconds per LTI. This 15
milliseconds must be added to the scan speed equation of Section 14.2.2 of this
bulletin.
NOTES
• The “ER” (unfragmented register) and “FER” (fragmented register)
terms in the scan speed equation apply to non-LTI modules in the
CPU rack, and will therefore be zero or so close to zero that they
can typically be disregarded.
• In a multiple LTI system, the I/O updates are additive. If fewer
than 291 registers are assigned to a given LTI, the I/O update time
for that LTI is proportionally less than 15 milliseconds.
The I/O update time of 15 milliseconds per LTI assumes that the assigned registers are
unfragmented; LTI update times will increase by 0.45 milliseconds for every
fragmented register (a register containing both input and output points).
B.6 FORCING
WARNING
UNINTENTIONAL EQUIPMENT OPERATION
The forced state of I/O does not transfer when system control is
switched from Primary to Backup. During a transfer, be aware of
any changes in system behavior that may occur due to active
forcing; ensure that I/O is correctly forced.
Failure to observe this precaution can cause equipment damage,
severe personal injury, or death!
Forcing is implemented differently in the Model 450 than in Model 500 or 700
processors. As described in Section 14.4 of this manual, forcing in a Model 450 is a
condition that should be applied to external I/O only. Forcing bits of an internal storage
register causes a programming device to display the forced state, while the image table
in the Model 460 actually processes the information based on the logic state.
Appendix B - Using the Processor with LTI/RTI Modules
30598-526
Page B-5
NOTE
If a bit of an internal storage register is forced in a primary, a
Start-up Transfer will cause the same bit in the backup to reflect
the forced state. This is a “one-shot” transfer that may cause
unintended results, especially if the bit(s) are within a data
storage register not controlled by the user ladder program. Avoid
this situation by following Section 14.4's recommendations to
perform forcing ONLY ON EXTERNAL INPUTS AND OUTPUTS.
B.7 PRIMARY AND BACKUP READ/WRITE BIT EXCHANGE
Section 5.4.5 of the LTI/RTI bulletin describes a method for exchanging the status of
eight user-selectable bits residing in the fourth register that is assigned to the Remote
Transfer Channel (Channel 2, Drop 1). The Model 450 processor does not support this
bit-exchanging capability.
B.8 EOS TRANSFER EXAMPLE
This example describes how to implement an end of scan (EOS) register block transfer
between the primary and backup LTIs when the block to be transferred is outside the
fixed register location. Because the block of 32 registers associated with this EOS in a
Model 400, 450, 600, or 650 is fixed as relative registers 260 through 291, additional
registers outside this range must be multiplexed through them to the backup processor.
Following is an example of how to accomplish this multiplexing operation using
GOTO/MARK loops with INCREMENTAL LET MATRIX ladder rungs.
The ladder rungs are divided into two groups:
• The primary group of rungs controls the uploading of the fixed block of transfer
registers into the primary LTI from other locations in the primary processor.
• The secondary or backup group of rungs downloads the register data transferred
through the fixed block area to their correct locations in the backup processor.
Because either processor can become primary or backup at any time, it is necessary to
have both sets of ladder rungs resident in each processor. To determine which set of
rungs is operated on in each processor, the primary/backup status bit 8161-20 from the
LTI's Remote Transfer Channel (RTC) Status register is used in conjunction with a
GOTO branch to allow the correct rungs to be scanned depending on that processor's
current primary or backup status.
Rack addressing for this example assumes that at least 1000 registers are assigned to
the LTI slot, that registers 5 through 8 are assigned as the RTC registers (LTI Channel
2, Drop 1), and has registers S260 through S291 acting as the fixed 32 register transfer
block or window between the primary and backup LTIs.
To manage the multiplexing operation, a pointer value indicating the location where the
transfer block was uploaded from the primary processor must be sent to the backup
processor so the registers can be downloaded to the correct location. The first register
(S260) of the fixed transfer block of 32 is reserved for this duty. The remaining 31
registers of the fixed transfer block contain the actual multiplexed register data to be
transferred.
Appendix B - Using the Processor with LTI/RTI Modules
Page B-6
30598-526
The following RTC and Control registers are important to LTI operations:
Register
Description
S5
Start-up Transfer Register - determines the number
of registers transferred from the primary processor to
the backup processor at start-up. A default value of
zero causes all 4096 registers of the LTI to be
transferred.
S6
End-of-Scan Transfer Register - determines the
starting register location of the block of 32 registers to
be transferred from the primary to backup processors.
In the Model 400, 450, 600 and 650 processors, the
relative starting location of this block of 32
end-of-scan transfer registers is fixed and is defined
as the 260th register assigned to the LTI; the user
must preset this information as part of the ladder
program.
S7
Processor Scan Synchronization Register determines the allowed variation between scan times
of the primary and backup processors. Set to zero for
default value of 100 msec.
S8
Primary/Backup Read/Write Bit Exchange - not
supported by the Model 400, 450, 600, or 650
processors. Should be set to zero.
S8176
Processor Control Register - Bit 23 (Normal
Program Scan) allows the ladder rung in which it is
used to establish preset conditions before a processor
commences normal ladder scanning.
S8161
Remote Transfer Channel (RTC) Status Register Bit 20 of this status register determines whether the
LTI being used is either the primary (bit 20 is ON or
set to 1) or backup (bit 20 is OFF or set to 0).
Bit 16 - EOS Transfer - When set to ON (1) in a
backup LTI that is scanning ladder, the backup LTI
requests an end-of-scan transfer of the fixed 32
register transfer block from the primary.
The following internal processor registers were chosen as temporary storage locations
for the multiplexing of data registers through the fixed 32-register block between the
primary and backup processors. These registers should be chosen from an unused
internal register area not involved in the end-of-scan block transfer or other storage
purposes. The registers shown below were arbitrarily chosen for this example only.
Register
Description
S260
First register of the fixed transfer register block. Used
as the pointer to identify the starting address of the
block currently being multiplexed.
S292
Starting location of a block of data registers to be
transferred from the primary processor to the backup
processor at end-of-scan.
This starting location can be calculated by subtracting
one (1) from the starting register address of the block
Appendix B - Using the Processor with LTI/RTI Modules
30598-526
Page B-7
of internal data registers to be transferred at
end-of-scan. This starting location will be passed to
the backup processor through the first relative fixed
register (S260) of the transfer window.
This register is later used as a pointer in one of the
multiplexing matrices to keep track of the starting
location for the next block of registers to be
transferred through the fixed register window
(S260-S291).
S293
This register is used as a pointer in one of the
multiplexing matrices to keep track of the next
register to be loaded or unloaded. This register should
be initialized to zero and cleared after each 32 register
end-of-scan transfer is complete.
The status bit 17 of the above matrix pointer registers is used in the example as a
contact to exit the GOTO/MARK loops since it will come ON (1) whenever the
incremental matrix PNTR register value equals its SIZE.
S294
This intermediate register is used in the matrix
routines to pass the register data between the fixed
transfer block register and the processor’s storage
location.
The following example can be broken up into three groups of rungs, each regulating an
aspect of the End-of-Scan (EOS) register transfer.
The first group, rungs 1 through 3, will set up or initialize the RTC registers, EOS
Transfer Bit and the first data register's starting location of the block of registers to be
transferred.
The second group, rungs 4 through 11, are the rungs required by the backup processor
to download or distribute the data registers passed to it through the fixed transfer
register block by the primary processor.
These first two groups of rungs should always be placed ahead of the processor's
operational ladder program to allow early initialization of the transfer process and the
downloading of current data from the primary processor.
The last of the three groups of rungs in this example, rungs 12 through 20, are used by
the primary processor to upload the block of data registers for transfer to the backup
processor through the fixed transfer block. This last group of rungs should always be
placed at the end of thc mainline ladder program, before the MARK START
SUBROUTINE rung. This will allow the primary processor to upload current data
register values to the backup processor.
Following is an example of the ladder rungs used to perform this EOS register block
transfer. The word “block” must be emphasized here since this routine will only
operate on one continuous unbroken sequence or block of internal processor data
registers. Note that these registers must be rack addressed to the LTI slot in order to be
exchanged. In this example, data registers 601 through 1000 will be transferred from
the primary to the backup Model 450 processor.
This 500-register transfer will require 17 processor ladder scans to complete, as only
31 registers can be transferred per each EOS interval. Because either processor in a
Appendix B - Using the Processor with LTI/RTI Modules
Page B-8
30598-526
transfer system can be primary or backup, all twenty of the following rungs used in
this multiplexing example should be included in both the primary and backup
processor ladder programs. This will allow the status of either processor to change at
any time and still maintain the EOS register transfer multiplexing process. Each ladder
rung of this routine is preceded by a brief description of its purpose.
SETUP AND INITIALIZATION RUNGS (1 through 3)
RUNG 0001
This set-up rung presets the RTC registers assigned to LTI channel 2, drop 1. The
second argument's (S6) value of “260” matches the relative starting register address of
the fixed register block window used for EOS transfers. Note that S5 should normally
be set equal to the largest register address assigned to the LTI slot; this example uses
the default value of 0.
8176
LET
S0005 = 0; 0260; 0; 0
23
RUNG 0002
This rung loads register S292 with the starting location (501 - 1 = 500) of the first
register of the block of 500 to be transferred by the primary processor after system
start-up.
8176
LET
S0292 = 500
23
RUNG 0003
This rung sets the EOS Transfer Bit in the backup LTI only.
8176
8161
20
16
BACK-UP (REGISTER DOWNLOAD) RUNGS (4 through 11)
RUNG 0004
Branch around rungs 5 through 10 if this is the primary processor.
8161
GOTO 0001
20
Appendix B - Using the Processor with LTI/RTI Modules
30598-526
Page B-9
RUNG 0005
Initializes subsequent matrix rung's pointer (PNTR) register to 0.
LET
S0293 = 0000
RUNG 0006
Load data register S292 with the starting location where the following block of 31
registers transferred to the backup processor are to be located.
LET
S0292 = S0260
RUNG 0007
The start of the backup processor’s download loop.
MARK
0002
RUNG 0008
Incremental LET matrix rung that uploads each of the 31 fixed transfer block registers
into register S294. PNTR register S293 increments for each pass through the loop
(note—pointers used in “incremental matrix” statements pre-increment before
execution of the rung). The size of this matrix rung is always 31 since the first register
(S260) transfers the starting location of the block of 31 registers that follow to the
backup processor.
SIZE
LET
PNTR
S00294 = M0260 0031 + S0293
Appendix B - Using the Processor with LTI/RTI Modules
Page B-10
30598-526
RUNG 0009
Incremental LET matrix rung that downloads each of the 31 registers transferred at the
EOS to the correct location in the backup processor. The starting location for this
storage operation was passed to pointer register S292 through transfer block register
S260 in rung 6. The size of this matrix should always be equal to the last address of the
total block of data registers to be transferred to the backup processor (in this case,
register 1000).
SIZE
LET
PNTR
M0001 = S0294 1000 + S0292
RUNG 0010
Continue to loop until all 31 registers transferred at EOS to the backup processor have
been downloaded to the correct locations before proceeding to the mainline ladder
program.
0293
GOTO 0002
17
RUNG 0011
Last rung of the backup group, branched to from rung 4 if processor is primary.
MARK
0001
This area (following the last rung of the backup group) should contain the
processor’s mainline ladder program. The following primary group of rungs
should be placed at the end of the mainline ladder program but before any
MARK START SUBROUTINE rung.
Appendix B - Using the Processor with LTI/RTI Modules
30598-526
Page B-11
PRIMARY (REGISTER UPLOAD) RUNGS (12 through 20)
RUNG 0012
Branch around rungs 13 through 19 if this is the backup processor.
8161
GOTO 0003
20
RUNG 0013
Initializes subsequent matrix rung's pointer (PNTR) register to zero.
LET
S0293 = 0000
RUNG 0014
Load the first register (S260) of the fixed register transfer block with the starting
location of the following block of 31 registers to be uploaded to the backup processor.
LET
S0260 = S0292
RUNG 0015
The start of the primary processor’s upload loop.
MARK
0004
RUNG 0016
Incremental LET matrix rung that preloads each of the 31 registers to be transferred at
the EOS from the locations in the primary processor. The starting block location for
this routine was loaded into pointer register S292 by either rung 2 or 19. The size of
this matrix should always be equal to the last address of the total block of data registers
to be transferred to the backup processor (in this case, register 1000).
SIZE
LET
PNTR
S0294 = M0001 1000 + S0292
Appendix B - Using the Processor with LTI/RTI Modules
Page B-12
30598-526
RUNG 0017
Incremental LET matrix rung that preloads each of the 31 registers to be transferred at
the EOS from the locations in the primary processor. The starting block location for
this routine was loaded into pointer register S292 by either rung 2 or 19. The size of
this matrix should always be equal to the last address of the total block of data registers
to be transferred to the backup processor (in this case, register 1000).
SIZE
LET
PNTR
M0261 = S0294 0031 + S0293
RUNG 0018
Branch to rung 15 and continue to loop until all 31 registers to be transferred to the
backup processor at EOS have been loaded into the fixed register transfer block.
0293
GOTO 0004
17
RUNG 0019
The pointer register S292 was incremented until equal to the last address (1000) of the
register block transferred, and activated contact S292-17 to restart the process again.
This rung then reloads pointer register S292 with the original starting location (501 - 1
= 500) of the entire register block.
0292
LET S0292 = 500
17
RUNG 0020
Last rung of the primary group, branched to from rung 12 if processor is backup.
MARK
0003
This example illustrates the ladder rungs required for multiplexing more than 32
registers (in this case, registers 501 through 1000) through the LTI’s EOS transfer
block. The End-of-Scan transfer ladder rung routine shown in this example can be
modified to fit any desired size register block to be transferred by changing the values
of the starting location and last register address of the block in rungs 2, 9, 16, and 19.
Further modification of this routine will be required if relative fixed register block
transfer window addresses other than S260-291 are used by the LTIs, as could happen
in a multiple-LTI system.
Appendix B - Using the Processor with LTI/RTI Modules
30598-526
Page C-1
APPENDIX C
SUPPLEMENTARY RACK ADDRESSING INFORMATION
This appendix provides additional information on register allocation and updating, and
supports Sections 3.1, 3.6, 3.7 and 14.2.
References to Local Interface (LI) also generally refer to the Local IO/NET Interface
(LIO) Module, except for specific references to scan time. Be sure to refer to the LIO
instruction bulletin (#30598-782) for detailed information about the LIO.
C.1 MODEL 450 SYSTEM REGISTER UPDATING
The Model 450 contains 4000 on-board registers; this is the maximum number it is
capable of addressing. Adding a Local Interface (LI) module will not increase the
addressing capability beyond this number. Thus, the Model 450 already has all of the
data storage registers it can handle. By the same token, any registers that have to be
updated in other modules will add to the scan time.
Simply stated, the more registers the Model 450 needs to read and write on the bus, the
longer the scan time will be, as indicated in the scan speed equation in Section 14.2.2.
To some extent, the Model 450 makes “decisions” to optimize throughput. For
example, the Model 450 will interrogate register modules in the CPU rack which have
had registers assigned to them to determine the module type. If the module is not a
Local Interface, the Model 450 determines whether it is an input or output device and
then simply reads or writes the assigned number of registers at the end of each scan. If
the module interrogated is a Local Interface, some additional decision making will
occur, as discussed in the following sections.
If no module is present, the assigned registers revert to the image table of the Model
450 and behave like regular storage registers.
C.2 RACK ADDRESSING A NEW SYSTEM
For a listing of ground rules to follow when rack addressing, refer to Section 3.6 for
discussions on determining rack addressing needs and rack addressing register
allocation.
C.2.1 General Rules
The Model 450 initially defaults to 4000 registers assigned to CPU slot #l; this applies
to installations in which the Model 450 is installed in a digital I/O rack with no other
register modules and no remote I/O.
Registers may or may not require assignment to CPU slot #1, depending on whether
the processor is installed in a digital or register rack.
Appendix C - Supplementary Rack Addressing Information
Page C-2
30598-526
When assigning registers, start with the CPU rack: If installed in a digital I/O rack, slot
#l needs to have sufficient registers assigned to handle the local digital I/O. If installed
in a register rack, it is not necessary to assign registers to slot #1. Each slot in the CPU
rack should have as many registers assigned to it as required to satisfy external I/O
needs. Once registers have been allocated in thc CPU rack, whatever registers remain
unassigned (up to 4000) are available for data storage.
There is no need to assign registers in multiples of four. Also, it is now possible to
force the 16-point and 32-point digital I/O when used in the CPU rack. If a slot
contains a Local Interface or LIO, assign only enough registers to service external I/O;
any data storage registers assigned to a Local Interface or LIO will adversely affect
throughput. It is a good idea, however, to anticipate any future expansion.
Avoid “fragmenting” registers when setting up a PLC system (see Chapter 14). A
fragmented register is one that contains both inputs and outputs, as could occur in
systems that use 4-point and 8-point digital I/O. For example, if bits 1 through 8 of
register 1 are inputs, and bits 9 through 16 are outputs, then register 1 is fragmented. If,
however, all bits of register 1 are inputs or outputs, then no fragmentation exists.
Fragmenting registers increases scan time. From the scan time equation in Section
14.2.2:
ST = [K x (LUP)] + [0.04 x (ER)] + [0.45 x (FER)] + COM
Where:
ST
K
LUP
ER
FER
COM
is the SCAN TIME in milliseconds.
is the LADDER SCAN SPEED per K of user program.
is the LENGTH OF USER PROGRAM in K words.
is the number of EXTERNAL REGISTERS.
is the number of FRAGMENTED EXTERNAL REGISTERS.
is the time required to service the communication ports, 5 msec
maximum.
Note how scan time is extended an additional 450 microseconds for each fragmented
register.
As with the Model 300 (which also uses an image table), the Model 450 uses bit 7 of
primary control register 8176 to activate an immediate I/O update. Unlike the Model
300, the registers to be updated are now variable and can be user-specified. Refer to the
description of bit 7 of register 8176, and control registers 8105 and 8106, in Section
13.2 of this manual.
MODEL 450 IN A DIGITAL RACK
If the Model 450 is used in a digital I/O rack which contains one or more register
modules (as could occur with the HRK-150 rack), assign enough registers for all local
digital I/O to the CPU slot (slot #1). Next, assign registers in ascending order to slot 2
(and to slots #3 and #4 if the rack used is an HRK-150).
MODEL 450 IN A REGISTER RACK
If the Model 450 is used in a register rack, registers do not need to be assigned to the
Model 450 itself (CPU slot 1); assign registers in ascending order beginning with slot
#2.
Appendix C - Supplementary Rack Addressing Information
30598-526
Page C-3
NOTE
For systems using a PDD/PDR combination, see Section C.2.3; for Local
Transfer Interface considerations, see Appendix B.
C.2.2 Local Interface (LI) Updating
If the Model 450 detects that registers are assigned to a Local Interface module in a
CPU rack slot, more decision-making occurs to optimize throughput.
When a Local Interface is detected, the Model 450 next checks to see if any remote
drops are assigned. If not, no registers will be transferred from the image table of the
Model 450 to the LI. In essence, the Model 450 makes a decision to not “waste” any
processing time writing storage registers to an LI, as storage registers already exist in
the Model 450 itself.
As soon as one or more remote drops are assigned, however, the Model 450 must
update the LI or LIO registers that are used on the remote drops. These LI/LIO
registers are now assigned to external I/O instead of simply data storage. Since an LI
cannot exchange more than 255 registers assigned to remote drops, the Model 450, in
an attempt to optimize throughput, never transfers more than 255 registers to an LI,
even if the user has assigned the additional registers to the LI slot. This could occur if
an existing rack addressing configuration is being used. This relates to a previously
described principle for optimizing throughput: only assign those registers to an LI or
LIO necessary to service external I/O.
Note that an LIO will exchange all registers assigned to it with the Model 450 since all
registers in an LIO can be external I/O.
EXAMPLE: If an LI has 4 drops assigned, with 8 registers per drop, a total of 32
registers are required for external I/O. Use the scan time equation on the previous page
to estimate the scan speed impact. Assuming no fragmented registers, if 32 registers
are assigned to the LI, scan time is increased by 0.04 milliseconds x 32 = 1.3
milliseconds. If the LIO had 512 registers assigned to it, the scan time is increased by
0.04 milliseconds x 512 = 20.4 milliseconds.
If, however, the LI had 512 registers assigned to it, the scan time increases by 0.04
milliseconds x 255 = 10.2 milliseconds for the same user configuration. Thus, rack
addressing can have a substantial impact on system scan time.
CRM-210/211/214
There is no reason to use a CRM-211 Local Interface Module in place of a CRM-210
in a Model 450 system, since the extra data storage registers are not used by the Model
450. Also, the CRM-214 (LAI) register allocation and updating methods are identical
to Local Interface register updating.
C.2.3 PDD/PDR Updating
The Parallel Digital Driver/Receiver modules (Class 8030 Type EQ5138-G1 and -G2)
were originally designed to allow real-time digital I/O bus updates with the Model 500
and Model 700, which don't have the Model 450's on-board image table. As the Model
450 does use an image table, oscillating output behavior may be observed when the
Model 450 is used with the PDD/PDR. This behavior is due to register wraparound.
Appendix C - Supplementary Rack Addressing Information
Page C-4
30598-526
Wraparound is discussed in the PDD/PDR Instruction Bulletin under “Application
Considerations with the Model 300". It is a phenomenon in which registers that are
assigned to the PDD, but do not correspond to physically existing external l/O, cause
digital bus update problems. Wraparound occurs because the registers that do not
correspond to physically existing external I/O interfere with the registers that do.
Wraparound can be avoided by properly addressing the PDD/PDR.
For COMPLETE information on proper rack addressing, see Section 3.6.4 for a
discussion on “Rack Addressing Register Allocation”.
In brief, the guidelines for proper PDD/PDR rack addressing are:
1. If a single remote rack is used, it must be connected to channel 1 of the PDD.
When rack addressing, only assign as many registers to the PDD as required by the
external I/O of the rack (consistent with one of the previously established “general
rules”). For example, if the remote rack is a CRK-300, DRK-300, or HRK-100,
assign 4 registers to the PDD; if the remote rack is an HRK-200, assign 8 registers
to the PDD.
2. If two remote racks are used, the rack connected to channel 1 of the PDD must be
an HRK-200. When rack addressing, only assign as many registers to the PDD as
required by the external I/O. In this way, the first 8 registers are automatically
allocated to the HRK-200 attached to channel 1, while the remaining registers
beginning with register 9 (up to 16 if the second rack is also an HRK-200) will be
allocated to the second rack.
NOTE
If the second rack is a CRK-300, DRK-300, or HRK-100, assign ONLY a
total of 12 registers to the PDD.
Another thing to note is that the original design intent of the PDD/PDR was to allow
for real-time bus updates which, by definition, no longer occur due to the Model 450's
image table operation and end-of-scan updating.
Finally, one advantage of using the Model 450 is that I/O points accessed via a
PDD/PDR are now forcible.
C.3 COMPATIBILITY WITH EXISTING SY/MAX PROCESSOR RACK ADDRESSING
CONFIGURATIONS
Existing rack addressing configurations for Model 300, 500, and 700 systems can
normally be used with a Model 450, although system characteristics may change due
to the faster ladder program scan speed and image table updating technique employed
by the Model 450.
From the discussion thus far, it should be apparent that existing rack addressing
configurations may not represent an optimum register allocation, at least in terms of
throughput. An exception to compatibility is the CRM-115/116 Bus
Expander/Terminator module set, although this exception can usually be
accommodated by replacing them with either PDD/PDR or LI modules. See also
Section 3.6.5 for other potential exceptions.
Appendix C - Supplementary Rack Addressing Information
30598-526
Page C-5
Example #1: A Model 300 in a digital I/O rack (shown in Figure C-1).
R2
R1
Model 300
Ribbon cable to
second rack if
R2 contains a
CRM-115
Digital I/O
CRK, DRK, GRK, or HRK (except HRK-150) Rack
Figure C-1 Processor Location in CRK, DRK, GRK, HRK Racks
Slot 1 in Figure C-1 would typically be assigned 1, 2, 4, 8, 96, 108, or 112 registers;
any registers remaining (up to 112) are assigned to slot 2. If slot 2 of the CPU rack
contains a module other than a CRM-115, the existing rack addressing can be used. As
always, registers up to 4000 can be used for data storage.
MODEL 300 WITH A CRM-115 IN THE CPU RACK
If slot 2 in Figure C-1 contains a CRM-115, slot 1 has been assigned 112 registers,
except for those rare systems which use a register module in slot R2 of the second
rack.
If slot 2 of the second rack is unused, the best solution is to replace the CRM-115/116
with the PDD/PDR (Class 8030 Type EQ5138-G1 and G2). Although the rack
addressing will have to be altered so that registers 1 to 4 are assigned to CPU slot 1,
and registers 5 to 8 are assigned to CPU slot 2, no registers need be re-addressed in the
ladder program. Registers 9 to 4000 are available as storage registers.
If slot 2 of the second rack contains a register module, the PDD/PDR is no longer an
option and an LI/RI must be used. In the event that slot 2 of the second rack contains a
register module other than an LI, rack addressing will have to be adjusted to
accommodate the change (the Remote Interface gets coded as drop 1, with digital I/O
registers assigned to slot 1 of drop 1 while the registers for slot 2 are assigned to slot 2
of drop 1). As before, no registers need be re-addressed in the ladder program and the
balance of the registers (out to 4000) are available as storage registers.
If slot 2 of the second rack contains an LI, the LI should be moved to the CPU rack to
replace the CRM-115, and a Remote Interface should replace the CRM-116. Rack
addressing will have to be adjusted to accommodate the change, and the existing drops
will have to be re-coded. The new Remote Interface will become drop 1, and the other
drops will have to increment by 1. The good news is that, once again, no registers will
need to be re-addressed in the ladder program, as the drop re-coding will preserve their
relative position.
Appendix C - Supplementary Rack Addressing Information
Page C-6
30598-526
Example #2: Model 300 in an HRK-150 rack (Figure C-2).
R4
R3
R2
Model 300, 400, 450, 600, or 650
R1
Digital I/O
HRK-150 Rack
Figure C-2 Processor Location in HRK-150 Rack
By virtue of the digital I/O, slot 1 will typically be assigned 4 registers. Modules in
slots 2, 3, and 4 will have registers assigned in accordance with their requirements.
Existing rack addressing can be used.
Example #3: Models 300, 400, 450, 600, 650, 500, or 700 in an RRK-type rack
(Figure C-3).
R1
R2
R3
R4
R5
R6
R7
R8
...
R8
...
Type RRK-XXX Rack with Model 300, 400, 450, 600, or 650 Installed
R1
R2
R3
R4
R5
R6
R7
Type RRK-XXX Rack with Model 500 (Double-Width) or 700 (Dual-Module) Installed
Figure C-3 Processor Location in RRK Racks
Appendix C - Supplementary Rack Addressing Information
30598-526
Page C-7
The Model 500 would normally have registers assigned to slot l; whether registers are
assigned to slot 1 or not, existing rack addressing configurations will not present a
problem for the Model 450, which could be used to replace any of the existing
processors.
Replacing a Model 300 is the “cleanest” replacement, since like the Model 450 it is a
single-width module. When replacing a Model 500 or 700, the question arises how to
treat the newly-empty slot 2. The answer is it can either be left empty, or the rest of the
modules can be moved one slot to the left, with a corresponding adjustment of rack
addressing. This can be accomplished without changing register assignments in the
ladder program, as the relative positions of the registers are preserved.
Appendix C - Supplementary Rack Addressing Information
30598-526
Page D-1
APPENDIX D
ETHERNET TECHNICAL INFORMATION
D.1 OVERVIEW
The unique feature of the Model 450 processor is its ability to directly connect to an
IEEE 802.3a/ThinWire Ethernet Local Area Network (LAN) and communicate with
other SY/MAX devices. Because the Model 450 communicates on Ethernet, a
communications standard used by many vendors, it is important to understand its
operating characteristics and how they affect the operation of SY/MAX devices. This
Appendix is not intended as a comprehensive explanation of the theory and operation
of Ethernet, but rather as a review of the terminology and overall concepts as they
relate to the Model 450 processor.
D.2 SPECIFICATIONS
The following 802.3a specifications in Table D-1 apply to the LAN on which the
Model 450 resides. The specifications for 802.3 are also included as reference for
applications in which a repeater is used to connect ThinWire to ThickWire.
Table D-1: 802.3a Compared to 802.3 Specifications
802.3a
802.3
Data Rate
10Mbps
10Mbps
Signalling
Baseband
Baseband
Maximum Segment Length
185 m
500 m
Maximum Drop Cable Length
0m
50 m
Maximum Cable Segments
5
5
Maximum Repeaters
4
4
Maximum Total Distance
Maximum total distance is
determined by IEEE 802.3
configuration rules.
Maximum Nodes per Segment
30
100
Minimum Segment Length
0.5 m
2.5 m
IEEE 802.3 NETWORK CONFIGURATION RULES
NOTE
To ensure reliable data communication and safety practices, be sure to
comply with the IEEE/ANSI Std. 802.3-1985 (ISO/DIS8802/2) and
IEEE/ANSI Std. 802.2a-1988 standards documents, or an equivalent
reference, when laying out Ethernet networks.
Appendix D - Ethernet Technical Information
Page D-2
30598-526
Aside from the previous specifications, IEEE defines rules that must be adhered to
when laying out a system. These rules deal mainly with the number of segments, the
cable for these segments, and the number of repeaters to tie these segments together.
These rules must be followed to ensure proper Model 450 communications.
Repeaters
The Model 450 communicates through IEEE 802.3-compliant repeaters as long as the
IEEE rules on the number of repeaters, cable type, and maximum segments are met.
Bridges
The Model 450 also communicates through IEEE 802.3-compliant bridges. It will not
communicate through protocol-dependent devices such as translator bridges or
Gateways.
Cabling
The Model 450 has hardware on-board that allows it to directly connect to ThinWire
Ethernet (RG-58) cabling. The use of other cable such as ThickWire and fiber optics
are only supported through the use of repeaters and bridges.
D.3 DESCRIPTION
Physical Layout
An IEEE 802.3a/ThinWire Ethernet LAN consists of up to 30 devices with unique
addresses connected by up to 185 meters of RG-58 cable. Each device is connected to
the cable by a BNC tee-connector and the cable is terminated at each end with a
50-ohm terminator (see Figure D-1). Tee-connectors must be at least 1/2 meter apart.
Devices can be added and removed from the network without disruption of the
network.
4
5
0
4
5
0
RG-58 Cable - 185 m max.
30 Devices max.
BNC Tee-Type
Connectors
50-Ohm
Terminator
Figure D-1 Base Configuration for 802.3a ThinWire
Appendix D - Ethernet Technical Information
50-Ohm
Terminator
30598-526
Page D-3
To expand a network, repeaters are added to extend beyond the 185-meter segment
limit. The 802.3a specifications call for no more than 5 segments, assuming the
appropriate cable types are used (see Figure D-2).
4
5
0
4
5
0
4
5
0
R
RG-58 Cable - 185 m max.
30 Devices max.
802.3a
ThinWire
Repeater
BNC Tee-Type
Connectors
50-Ohm
Terminator
50-Ohm
Terminator
Figure D-2 Base Configuration with Repeater
To further expand, repeaters that allow for ThinWire to ThickWire and/or fiber optics
Ethernet are added to a network to allow for communications between other than
ThinWire devices. Using ThickWire, the network can extend 500 m per segment and
up to 100 devices (see Figure D-3). Refer to IEEE 802.3 standards for additional
multimedia Ethernet connection information.
4
5
0
4
5
0
DEC
VAX/VMS
Computer
R
Transceiver
802.3a
Media
Converting
Repeater
50-Ohm
Terminator
RG-58 Cable - 185 m max.
30 Devices max.
ThickWire
or Fiber
Optic
Cable
Terminator
for
ThickWire,
fiber optics,
etc.
Figure D-3 Base Configuration with Repeater to ThickWire Ethernet
Appendix D - Ethernet Technical Information
Page D-4
30598-526
Access Method
Access to an Ethernet LAN is accomplished using a CSMA/CD (Carrier Sense
Multiple Access with Collision Detection) protocol. A device on a CSMA/CD network
gains access by first checking to see if any other device is currently communicating on
the network. If the network is busy, the node waits until the network is available. If the
network is available, the device begins to send its message to another device or group
of devices. Upon completion, the network is again freed for another device to send a
message. If two devices begin to send a message at the same time, a collision occurs.
In that case, both devices back off for a random period of time before trying to re-send.
What this means to a Model 450 on an Ethernet network is that other devices and the
amount of network traffic can have a significant effect on the time taken to access the
network and communicate.
Other Non-SY/MAX Device Issues
Ethernet specifications define the physical and data layers for devices to communicate.
That is, it provides a means by which devices can share a common signalling medium
and pass messages. Messages can only be “understood,” however, between devices
having the same higher-level protocols.
The Model 450 contains hardware and software allowing it to pass information to
other devices on a ThinWire Ethernet network. But since the upper-level protocol of
the Model 450 is SY/MAX protocol, only those devices on the network that have the
ability to interpret this SY/MAX language (currently Model 450s, Model 650s, and
VAX/VMS-based computers running Square D Class 8055 Type SFW390) are able to
understand the information being transferred.
Example
Assume that a ThinWire Ethernet LAN has the following devices:
5
Model 450 processors
1
DEC VAX computer running SFW390
1
DEC VAX computer without SFW390
2
IBM personal computers with Ethernet interface cards installed.
The Model 450 can theoretically send message to any device on the network. The DEC
VAX with SFW390 and the other Model 450s receive and understand these messages.
Even though other DEC VAX and IBM computers receive the messages and are able to
tell from what node numbers they were sent, the messages are not understood and are
discarded.
The reverse is also true. Non-SY/MAX devices can send messages to a Model 450, but
because the Square D devices understand a different protocol, the messages are not
understood and are discarded.
D.4 THROUGHPUT
The throughput of a communication system is composed of 3 basic elements.
1. The sending device’s time to prepare a message and process it up to the point of its
being sent out onto the network.
Appendix D - Ethernet Technical Information
30598-526
Page D-5
2. The network transfer time—the time to gain access to the network, send the message
at one end, and receive it at the other end.
3. The receiving device’s time to process the information and move it into the user
memory.
In this case, the sending and receiving device can be either a Model 450 or a VAX
computer running Class 8055 Type SFW390 software. With the Model 450, it is
possible to determine (using processor scan times) the number of registers transferred,
the number of other communication packets being sent, the worst-case time to prepare
a message to be sent, or the time for a message to be processed after receipt.
In the case of network transfer time, 802.3a/Ethernet, like all CSMA/CD networks, is a
non-deterministic means of communication. That is, the time required for a node to
gain access to the network is directly dependent on the number of nodes on the
network, the average length of messages being sent, and so on. Because of this, the
worst-case time for a node to gain access to the network and send a message cannot be
determined.
Because it is impossible to offer an equation to determine worst-case time for a Model
450 to gain control of a network, care should be taken when designing a system in
which time-critical or real-time control information must be transferred in a specified
time period.
Appendix D - Ethernet Technical Information
Page D-6
30598-526
NOTES
Appendix D - Ethernet Technical Information
30598-526
Page E-1
APPENDIX E
CONNECTING THE VAX PROCESSOR TO THE
SY/MAX MODEL 450 PROGRAMMABLE CONTROLLER
E.1 HARDWARE AND SOFTWARE REQUIREMENTS
The SFW390 software allows SY/MAX Models 450 and 650 programmable
controllers and VAX computers to effectively communicate over an Ethernet
Communications Network. The SFW390 software requires that the host computer is
equipped with appropriate Ethernet controller hardware and driver software.
E.1.1 Hardware
The SFW390 software is designed to work with any of the Digital Equipment
Corporation (DEC) Ethernet controller hardware available for VAX computers.
Following is a list of Ethernet controllers available for VAX computers, current as of
the date of this publication. Part numbers and installation hardware are available
through DEC.
Controller
Bus Architecture
DELUA
DEUNA
UNIBUS
UNIBUS
DELQA
DESQA
DEQNA
Q-BUS
Q-BUS
Q-BUS
DEBNI
DEBNA
DESVA
VAXBI
VAXBI
MVAX2000 (ThinWire)
Other Ethernet hardware, such as cabling, transceivers, repeaters, tee-connectors, and
terminators are also required to set up an Ethernet network. These are available from
DEC and other sources.
The same cabling, tee-connectors, and terminators used with a SY/MAX Model 400 or
600 programmable controller are also used to connect a Model 450 programmable
controller to the ThinWire Ethernet network. Specific information about the required
cabling can be found in Chapter 15 and in Appendix D of this instruction bulletin.
E.1.2 Software
The host computer must have appropriate Ethernet driver software. The Ethernet driver
software is supplied as an integral component of the VMS operating system by DEC.
No special installation requirements for the Ethernet driver software currently exist.
SFW390 does not require that users have a DECnet license.
E.2 CONNECTION DIAGRAM
Figure E-1 on page E-2 shows a sample network of 5 SY/MAX devices: three VAX
computers (SY/MAX drops 3, 5, and 6) and two Model 450 programmable controllers
(SY/MAX drops 10 and 15). The SFW390 software uses the Ethernet driver to
communicate with programmable controllers and other VAX computers.
Appendix E - Connecting a VAX Processor to the Model 450
Page E-2
30598-526
As shown in Figure E-1, any other non-SY/MAX devices, like terminal servers and
other computers, can share the Ethernet without interference. Ethernet network
segments connected by a repeater are treated as a single Ethernet network for the
purposes of communication between VAX computers and Model 450 programmable
controllers.
VAX
VAX
Applications
Terminal
Server
LAT
DEC
Net
Applications
SFW
390
LAT
Ethernet driver
Drop 5
DEC
Net
SFW
390
Ethernet driver
ThickWire Ethernet
Drop 6
VAX
Applications
Repeater
LAT
DEC
Net
SFW
390
Ethernet driver
ThinWire Ethernet
Drop 7
Drop 15
Drop 10
Model 650
Model 450
PLC
1
3
Equiv.
NIM
PLC
1
3
Equiv.
NIM
2
2
Figure E-1 ThinWire Ethernet Network Connected to a ThickWire
Ethernet Network via a Repeater
E.3 NETWORK CONFIGURATION INFORMATION
The type SFW390 software supports communication between a VAX computer and up
to 99 other devices, consisting of Model 450 Programmable Controllers and host
computers running SFW390 (or equivalent) software, for a total of 100 devices.
Devices such as terminal servers and other host computers not running SFW390
software (or equivalent) do not count towards the 100-device total. They can, however,
coexist on the same Ethernet network.
Model 450 programmable controllers are connected together by means of a ThinWire
(Type 10BASE2) Ethernet network. Host computers having a ThinWire (10BASE2)
Ethernet interface can attach directly to this network. Host computers having a
standard (10BASE5) Ethernet interface may connect to Model 450 programmable
controllers through the using of an appropriate repeater (see Figure E-1).
Appendix E - Connecting a VAX Processor to the Model 450
30598-526
Page E-3
The IEEE/ANSI Std. 802.3-1985 (ISO/DIS 8802/2) and IEEE/ANSI Std. 802.3a-1988
specify a maximum of 100 stations per 10BASE5 coax segment and a maximum of 30
stations per 10BASE2 coax segment. Through the use of repeaters, it is possible to
have a large number of stations on an Ethernet network. Minimum cable length
between two stations on a 10BASE2 coax segment is 2 feet (approximately 0.5 meter).
The maximum distance between any two stations on a 10BASE2 coax segment is
limited to 607 feet (approximately 185 meters), in accordance with the above
specifications.
NOTE
To ensure reliable data communication and safety practices, be sure to
comply with the IEEE/ANSI Std. 802.3-1985 (ISO/DIS8802/2) and
IEEE/ANSI Std. 802.2a-1988 standards documents, or an equivalent
reference, when laying out Ethernet networks.
E.4 ROUTING INFORMATION
Standard SY/MAX routing is used with the SFW390 software and the Model 450.
Routing is the data instruction that controls how messages are communicated from one
device to another. A route actually consists of a route block structure, but is identified
by a user as a series of numbers separated by commas. The series of commas which
comprise a route include the numbers identifying the sender of a data message (this
can be a specific task running in a VAX computer, or it can be a specific Model 450
programmable controller) and the numeric identifier of the intended destination
location (this can be a specific task in a VAX computer, a certain Model 450
programmable controller on the SY/NET network, a global queue, mailbox register, or
Ethernet configuration register).
Route values of (000-199) are the general route values used to direct a communication
to specific devices on the network. Above this range, however, are three special route
values that may also be used; route 200, route 201, and route 204. Route 200 directs
the communication to the equivalent NIM within the VAX computer or the
programmable controller. Route 201 indicates a “whoever-I-am” source route and
route 204 indicates a “don’t care” route and is typically ignored as if it were not there.
These special routes are explained in greater detail in Section E.4.3, “Special Routing
Considerations,” and in Section 15.4.2.
E.4.1 VAX-Initiated Messaging
Depending upon your operation, the routing from source device to destination device
is done differently. Table E-1 on page E-5 describes the methods used to route
communications for each of three categories of VAX computer-initiated message
transmissions. These categories include local register Read and Write operations,
Reads and Writes to global mailboxes or global alarm queues, and Reads and Writes to
Ethernet configuration registers. Notes referenced in each of the tables can be found in
Section E.4.3. In addition, Figure E-2 on page E-4 can be used as a reference for the
examples provided with each explanation. In Figure E-2, the enlargement representing
the VAX at Drop 6 illustrates the internal architecture of the tasks, mailboxes, and
alarm queues.
Appendix E - Connecting a VAX Processor to the Model 450
Page E-4
30598-526
TASK
User
Application
Program
Local
Mailbox
Regs.
Local
Alarm
Queue
User
Appl.
User
Appl.
User
Appl.
Virtual
NIM
Virtual
NIM
Virtual
NIM
13
5
VAX
Application
Terminal
Server
LAT
DEC
Net
99
TASK
6
Virtual
NIM
Global
Resource
Manager
Equiv.
NIM
SFW
390
System
Task
106
Global
Mailbox
Regs.
Regs.
Ethernet driver
Drop 6
Drop 5
ThickWire Ethernet
VAX
Application
Repeater
LAT
DEC
Net
SFW
390
Ethernet driver
ThinWire Ethernet
Drop 3
Drop 15
Drop 10
Port 3
Port 3
PLC
PGR
COM
1
2
Regs.
Equiv.
NIM
PLC
PGR
COM
Model 450
1
2
Regs.
Equiv.
NIM
Model 650
Figure E-2 Possible Ethernet Network Configuration with Model 450/650
Programmable Controllers and VAX Computers Running SFW390
(including illustrations of VAX architecture)
Appendix E - Connecting a VAX Processor to the Model 450
Global
Alarm
Queue
30598-526
Page E-5
Table E-1: Methods Used to Route VAX-Initiated Communications
(Page 1 of 2)
First Route #
Second Route #
Third Route #
Fourth Route #
None
None
When performing local register Read and Write operations:
1. From a VAX computer to the same
VAX computer
Source task
number
Destination task
number
5,
99
Examples:
Task 5 on VAX 6 reads registers from
Task 99 on VAX 6
Task 1 on VAX 3 reads from its own
local mailbox registers
2. From a VAX computer to a second
VAX computer
See item #5 in
Section E.4.3
Source task
number
Source VAX
number
Destination VAX
number
Destination task
number
1,
3,
6,
13
Source task
number
Source VAX
number
Destination PLC
None
5,
6,
15
Example:
Task 1 on VAX 3 reads registers from
Task 13 on VAX 6
3. From a VAX computer to a
programmable controller (PLC)
Example:
Task 5 on VAX 6 writes to
programmable controller registers in
Model 650 #15
When performing Read and Write operations with global mailboxes and alarm queues:
1. From a VAX computer to the same
VAX computer
Source task
number
Source VAX
number
Source VAX
number plus 100
(see item #1 in
Section E.4.3)
None
201,
(see item 4 in
section E.4.3)
3,
106
Source task
number
Source VAX
number
Destination VAX
number plus 100
(see item #1 in
Section E.4.3)
4,
3,
106
Source task
number
Source VAX
number
200
(see item #2 in
Section E.4.3)
Destination PLC
4,
5,
200,
15
Example:
An unspecified task on VAX 3 reads
from its own global mailbox registers
2. From a VAX computer
to a second VAX
computer
None
Example:
Task 4 on VAX 3 writes an alarm to a
global alarm queue on VAX 6
3. From a VAX computer
to a programmable controller
(PLC)
Example:
Task 4 on VAX 5 writes to Equivalent
NIM mailbox registers of Model 650
#15
Appendix E - Connecting a VAX Processor to the Model 450
Page E-6
30598-526
Table E-1: Methods Used to Route VAX-Initiated Communications
(Page 2 of 2)
First Route #
Second Route #
Third Route #
Fourth Route #
None
When performing Reads or Writes to Ethernet configuration registers:
1. From a VAX computer to the same
VAX computer
Source task
number
200
(see item #3 in
Section E.4.3)
VAX number
1,
200,
3
Source task
number
Source VAX
number
200
(see item #2 in
Section E.4.3)
Destination VAX
number
1,
3,
200,
5
Source task
number
Source VAX
number
200
Destination PLC
12,
5,
200,
10
Example:
Task 1 on VAX 3 reads from its own
Ethernet configuration registers
2. From a VAX computer
to a second VAX
computer
Example:
Task 1 on VAX 3 writes to the Ethernet
configuration registers of VAX 5
3. From a VAX computer
to a programmable controller
(PLC)
Example:
Task 12 on VAX 5 reads from the
Ethernet configuration registers of
Model 450 #10
E.4.2 Model 450 or Model 650 PLC-Initiated Messaging
Depending upon your operation, the routing from source device to destination device
is done differently. Table E-2 describes the methods used to route communications for
each of three categories of PLC-initiated message transmissions. These categories
include local register Read and Write operations, Reads and Writes to global
mailboxes or global alarm queues, and Reads and Writes to Ethernet configuration
registers. Notes referenced in each of the tables can be found in Section E.4.3. In
addition, Figure E-2 on page E-4 can be used as a reference for the examples provided
with each explanation. In Figure E-2, the enlargement representing the VAX at Drop 6
illustrates the internal architecture of the tasks, mailboxes, and alarm queues.
Table E-2: Methods Used to Route PLC-Initiated Communications
(Page 1 of 2)
First Route #
Second Route #
Third Route #
Fourth Route #
None
When performing local register Read and Write operations:
1. From a Model 650 to a VAX
computer
Source PLC
Destination VAX
number
Destination task
number
15,
5
7
Example:
Model 650 #15 reads mailbox registers
from task 7
Appendix E - Connecting a VAX Processor to the Model 450
30598-526
Page E-7
Table E-2: Methods Used to Route PLC-Initiated Communications
(Page 2 of 2)
2. From one Model 650 PLC to
another
First Route #
Second Route #
Third Route #
Fourth Route #
Source PLC
Destination PLC
None
None
15,
10
Example:
Model 650 #15 writes to registers in
PLC #10
When performing Read and Write operations with global mailboxes and alarm queues:
1. From a Model 450 PLC to a VAX
computer
Source PLC
Destination VAX
number plus 100
(see item #1 in
Section E.4.3)
None
None
10,
105
Source PLC
200
Destination PLC
None
15,
200,
10
Example:
Model 450 #10 writes an alarm to a
global alarm queue on VAX 5
2. From a Model 650 PLC to a Model
450 PLC
Example:
Model 650 #15 writes to Equivalent
NIM mailbox registers in PLC #10
When performing Reads or Writes to Ethernet configuration registers:
1. From a Model 650 PLC to a VAX
computer
Source PLC
200
(see item #2 in
Section E.4.3)
Destination VAX
number
15,
200,
6
Source PLC
200
(see item #2 in
Section E.4.3)
Destination PLC
200,
15
None
Example:
Model 650 #15 reads Ethernet
configuration registers from VAX 6
2. From one Model 650 PLC to
another
None
Example:
An unspecified PLC reads Ethernet
configuration registers from the
Equivalent NIM of Model 650 #15
201,
(see item #2 in
Section E.4.3)
Appendix E - Connecting a VAX Processor to the Model 450
Page E-8
30598-526
E.4.3 Special Routing Considerations
1. When the destination of a route instruction is a VAX computer’s global queue or
mailbox, the destination drop number is 100 plus the VAX computer’s drop
number. For example, the global alarm queue in VAX 6 would be specified as 106,
and if task 10 on VAX 3 writes to the global alarm queue in VAX 6, the entire route
would be 10, 3, 106.
2. Route 200 is a special route whose function indicates that registers in the Equivalent
NIM of a PLC, or the Ethernet configuration registers in the VAX are to be read in
the form of register data. For example, when reading from the Ethernet
configuration registers in VAX 6, the destination route instruction would be ..., 200,
6. When reading from the Equivalent NIM in PLC 10, the destination route
instruction would be ..., 200, 10.
3. When a task within a VAX reads from the Ethernet configuration registers within
that same VAX, the route consists of the source task number, followed by the
number 200, followed by the VAX number. For example, when task 4 on VAX 5
reads from the Ethernet configuration registers within VAX 5, the route is 4, 200, 5.
4. The route instruction 201 can be used in the source route when the initiating task
chooses to communicate over the network without specifying its own route address.
For example, if an unspecified task on VAX 3 reads from PLC #15, the route is 201,
3,15.
The special 201 route, which can only be used in the first routing instruction (with
one exception) can replace either a task number (VAX-initiated message) or a
programmable controller number (PLC-initiated message). The 201 route can
appear in the last routing instruction only when the destination drop is the same as
the source drop (for example, 201, 200, 201 from a PLC will read its Equivalent
NIM registers).
Route 201 is sometimes referred to as the “whoever I am” route.
5. When a task reads its own local mailbox, it reads an empty route, which is signified
by 255 in the first route number.
Appendix E - Connecting a VAX Processor to the Model 450
Printed in U.S.A. 0693 DLC