Elevation Window Actuator System

Elevation Window Actuator System
Elevation Window
Actuator System
Wiring Guide
1
What Type of System?
Keypad
Wall Switch or Smart
Home
• You cannot use a Keypad and Wall Switch on the same system
• Connecting to a ‘Smart Home’ is the same as using a Wall Switch, except, replace the open and
close buttons with Relays which get triggered by the Smart Home system
2
Network Cable
•
•
•
•
•
•
•
Network Cable is not provided
It must be a twisted pair cable
Shielded cable is recommended to help reduce noise
Cat 5 or Cat 6 is a readily available cable which is acceptable
There must be a terminating resistor at each end of the network
Resistors come with the Keypad and Network Adaptor
Maximum cable length = 300m
3
Basic Keypad System
• Every device on the system must be connected
to the network cable between the two resistors.
• Devices can be connected to the network cable
in any order .
4
Basic Wall Switch System
• Every device on the system must be connected
to the network cable between the two resistors.
• Devices can be connected to the network cable
in any order .
5
Keypad Connection
• The Keypad comes with a 1m Cable, cut and strip the
end to expose the coloured wires as shown.
• Keep the Ferrite Ring end to attach to the Keypad.
• Note: The data/communication terminals use 5 volts
and will be damaged if connected to the power supply.
6
Wall Switch or Smart Home
Connection
• Smart home system needs two relay outputs
(open and close).
• The relay must be triggered for a 2 second pulse
to ensure all windows open or close.
• Note: The data/communication terminals use 5
volts and will be damaged if connected to the
power supply.
7
Single Actuator Connection
• Note: The data/communication terminals use 5
volts and will be damaged if connected to the
power supply.
8
Synchronised Actuator Connection
• The slave Actuator receives communication
through the synchronisation cable and does
not connect to the network cable.
• Note: The data/communication terminals use
5 volts and will be damaged if connected to
the power supply.
9
Rain Sensor Connection
• The Network Adaptor must not be installed outside
where it can get wet.
• The Rain Sensor is designed to be mounted outside
where rain will fall on the green/gold surface.
• Note: The data/communication terminals use 5
volts and will be damaged if connected to the
power supply.
10
Keypad System Cable Lengths
• There must be 1m of cable from the last device at
each end of the Network to the terminating resistors.
11
Wall Switch System Cable Lengths
• There must be 1m of cable from the last device at
each end of the Network to the terminating resistors.
12
Keypad System Limits
Keypads
1
1
1
1
1
2
2
2
2
2
Rain Sensors
0
1
2
3
4
0
1
2
3
4
Windows
30
29
28
27
26
30
29
28
27
26
• Keypads must not exceed two per network
• Rain Sensors must not exceed 4 per network
• Windows + Rain Sensors must not exceed 30
13
Wall Switch System Limits
Switches
1
1
1
1
2
2
2
3
3
4
Rain Sensors
0
1
2
3
0
1
2
0
1
0
Windows
29
28
27
26
28
27
26
27
26
26
• Switches + Rain Sensors must not exceed 4
• Switches + Rain Sensors + Windows must not exceed 30
14
Elevation System Single Power
Supply
• It is possible to use one large power supply to power multiple devices.
15
Keypad System Power
Requirements
• Synchronised Actuators both need 750mA
16
Wall Switch System Power
Requirements
• Synchronised Actuators both need 750mA
• A Network Adaptor connected to a Rain Sensor draws
more current than a Network Adaptor connected to a
Wall Switch or Smart Home.
• A Network adaptor connected to a Smart Home
(relays) will also draw 100mA.
17
Elevation System Single Power
Supply
• Power supply must always be 24V DC.
• Power supply must have a current
rating high enough for all devices it is
powering.
• Electrician must ensure voltage drop
does not exceed 1V (must have 23V
minimum at all devices).
Device
Max Current Draw
Quantity
Total
(max current x Quantity)
Actuator
750mA
28
21000
Keypad
100mA
2
200
Rain Sensor
350mA
2
700
Total
21900mA = 21.9Amps
18