Emotron Fieldbus HMS Gateway Anybus

Emotron Fieldbus HMS Gateway Anybus
Emotron Fieldbus
HMS Gateway Anybus Communicator
Quick Start Guide
English
Quick start to HMS Gateway Anybus Communicator
This document provides a short example on how to
configure the Anybus Communicator Gateway from HMS
with Emotron MSF 2.0 and Emotron VFX/FDU 2.0.
NOTE: All support/questions regarding configuration/
installation of the gateway are handled by HMS
Industrial Networks, http://www.hms.se/
Questions regarding the Softstarter or Variable Speed Drive,
VSD, are handled by CG Drives & Automation.
The following examples show how to configure the
telegrams on the sub network side where the gateway works
as a modbus-rtu master.
Examples of configuration files for the HMS gateway are
found under FDU/VFX and MSF at:
http://www.emotron.com/services-support/file-archive.
The files can be downloaded and reconfigured to your
specific application/needs.
General configuration Gateway
NOTE: Please refer to the Anybus Communicator manual
on www.hms.se for detailed information.
The following text describes step by step how to configure
the gateway and sub network.
NOTE: Preconfigured examples both for MSF 2.0 and
VSD 2.0 may be downloaded from www.emotron.com
under File archive.
1. Start ABC Config Tool program.
2. Choose Blank Configuration and press OK.
NOTE: The wizard does not allow byte swapping,
therefore the manual configuration mode is
recommended.
Hint! Keep the following manuals nearby before continuing:
For VSD:
•
Emotron VFX/FDU 2.0 Instruction manual
•
Emotron I/O board 2.0 Option (describes process data
mapping)
•
Emotron Isolated RS232/485 2.0 Option (describes
modbus rtu protocol)
For Softstarters:
•
Emotron MSF 2.0 Instruction manual
•
Emotron MSF 2.0 Fieldbus Option (describes process
data mapping)
•
Emotron MSF 2.0 Serial Communication Option
(describes modbus protocol)
In the following examples the modbus registers for the 4
bytes process data (described in each corresponding fieldbus
manual) are mapped to the double port memory of the
gateway. This enables access (read/write) of selected modbus
registers from the fieldbus side.
CG Drives & Automation 01-5971-01r0
Fig. 1
1
3. Click on Fieldbus to the left and choose Fieldbus type to
the right.
Fig. 2
4. Click on Sub-Network to the left
5. Make appropriate settings for baudrate, data bits (8),
parity (none), physical interface and stop bits (2) matching the settings in MSF/FDU/VFX.
Fig. 3
2
CG Drives & Automation 01-5971-01r0
6. Expand Sub-Network structure (with +) to the left and
add the number of slave nodes you want on the sub network. Click on the Sub-Network and select “Add node”
to add a new node. You may rename the name of the
“New Node” to something more appropriate, e.g. like
“Inverter2”.
7. For each node you add you must select a unique address,
matching the address setting in the product (MSF, FDU
or VFX). To do this, click on the Node name and select
Slave address to the right.
Fig. 4
8. Right click on the node name again and select “Add
transactions”.
9. Continue to chapter Setup sub network for your specific
product.
CG Drives & Automation 01-5971-01r0
3
Setup sub network for MSF 2.0
First setup the MSF menus:
For detailed menu information, please check manuals listed
above.
Setup the following menus:
[200] Selection of control sources – set to 3 = Serial
communication control
[270] Serial comm unit address
[271] Serial comm baudrate
[272] Serial comm parity – set to 0 = No parity
[273] Serial comm contact broken
NOTE: The exact same address, baudrate etc. should be
configured for the gateway.
We will now continue our configuration of the gateway to
setup a modbus rtu message that will read and write modbus
registers containing the 4 byte fieldbus process data.
Fig. 5
Under “transactions” you can now fill in the following data
(right click on the Query or Response field and add Byte
constant/Word constant or Data according to the table
below).
4
CG Drives & Automation 01-5971-01r0
Query msg MSF
Table 1
Field name Query
Set to
Right click on query and add as…
Slave Address
Same as in MSF
Byte constant
Function
Set to 0x41 for MSF
(Emotron specific function code for process Byte constant
data registers only)
Read Starting Address (Hi,Lo)
0x26F1
Word constant
Quantity to Read (Hi,Lo)
0x0003
Word constant
Write Starting Address (Hi,Lo)
0x26F1
Word constant
Quantity to Write (Hi,Lo)
0x0003
Word constant
Write byte count
0x06
Byte constant
Data 1
Data length 0x0002
Data location 0x0400
(This status reg must be read but is not
mapped to process data area)
Byte swap: Don’t care
Data
Data 2
Data length 0x0002
Data location 0x0202 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Data 3
Data length 0x0002
Data location 0x0200 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Checksum
Use default values
Checksum
Response msg MSF
Table 2
Field name Response
Set to
Right click on response and add as…
Slave Address
Same as in MSF
Function
Set to 0x41 for MSF
(Emotron specific function code for process Byte constant
data registers only)
Byte Count
0x06
Byte constant
Data 1
Data length 0x0002
Data location 0x0400
(This status reg must be read but is not
mapped to process data area)
Byte swap: Don’t care
Data
Read Register Value 1
Data length 0x0002
Data location 0x0002 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Read Register Value 2
Data length 0x0002
Data location 0x0000 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Checksum
Use default values
Checksum
CG Drives & Automation 01-5971-01r0
Byte constant
5
Setup sub network for FDU/VFX
2.0
First setup the VSD menus:
For detailed menu information, please check manuals listed
above.
Setup the following menus:
[214] Reference control
[215] Run/Stp control
[216] Reset control
[261] Com type – Set to RS232/485
[2621] Baud rate
[2622] Address
NOTE: The exact same address, baud rate etc. should be
configured for the gateway.
We will now continue our configuration of the gateway to
setup a modbus rtu message that will read and write modbus
registers containing the 4 byte field bus process data.
Fig. 6
Under “transactions” you can now fill in the following data
(right click on Query or Response field and add Byte
constant/Word constant or Data according to table below).
6
CG Drives & Automation 01-5971-01r0
Query msg Inverter
Table 3
Field name Query
Set to
Right click on query and add as…
Slave Address
Same as in Inverter
Byte constant
Function
Set to 0x17 Read/Write Multiple registers
Byte constant
Read Starting Address (Hi,Lo)
0x26F2
Word constant
Quantity to Read (Hi,Lo)
0x0002
Word constant
Write Starting Address (Hi,Lo)
0x26F2
Word constant
Quantity to Write (Hi,Lo)
0x0002
Word constant
Write byte count
0x04
Byte constant
Data 1
Data length 0x0002
Data location 0x0202 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Data 2
Data length 0x0002
Data location 0x0200 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Checksum
Use default values
Checksum
Response msg Inverter
Table 4
Field name Response
Set to
Right click on response and add as…
Slave Address
Same as in Inverter
Byte constant
Function
Set to 0x17 Read/Write Multiple registers
Byte constant
Byte Count
0x04
Byte constant
Read Register Value 1
Data length 0x0002
Data location 0x0002 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Read Register Value 2
Data length 0x0002
Data location 0x0000 (optional)
Byte swap: Swap 2 bytes (optional)
Data
Checksum
Use default values
Checksum
CG Drives & Automation 01-5971-01r0
7
General hints
Speeding up the sub network
The speed on the sub network depends on several issues:
•
Baud rate
•
Telegram length/amount of data
•
Number of slave nodes on the RS485 sub network
(sharing bandwidth to master)
•
Update time (i.e. minimum time between two
transactions)
In general it is preferred to achieve a fast response. Try to
keep the time between two transactions of a kind as short as
possible. This can be altered by marking the Query to the
left and altering the Update time (10 ms) value to the right,
see Fig. 7.
Fig. 7
Data location & byte swapping
PLC’s of different brands may use different data formats
(little endian or big endian). Depending on this you may
have to perform byte swapping, either in the PLC or in the
Gateway.
NOTE: The Data length value must be set to 0x0002
before you can alter the Byte swap setting.
You may also swap registers (words) if necessary by altering
the Data location in the DP memory.
Example for Profibus:
The Anybus communicator gateway (Profibus DP) has been
configured for a VSD FDU/VFX 2.0 exactly as in the
example above. This means that the process data mapping
will be exactly the same with the gateway as for the Fieldbus
I/O board 2.0 option (standard Profibus option).
8
CG Drives & Automation 01-5971-01r0
Fig. 8
Using a profibus DP Master simulator with 4 bytes of
process data in/out.
The first output data
Byte 1: is set to 0x03=Run and Run to the right
Byte 2: Drive mode = speed, and parameter set A
Byte 3 and 4: Reference Signal.
According to Fig. 8, the first output data:
Byte 1: is set to 0x03=Run and Run to the right
Byte 2: is set to 0x00 which corresponds to Drive
mode=speed, and parameter set A
Byte 3 and 4: Reference Signal.
Input data:
Byte 1: is 0x8B=1000 1011b=Running, run right, Relay 1
on , Run Ctrl=run/stp by com.
Byte 2: is 0x00=Drive mode speed, no warning/error status.
Byte 3: AnOut1 value
Byte 4: AnOut2 value.
Input data
Byte 1: is 0x8B = 1000 1011b = Running, run left, Relay1
on, Run Ctrl=1=run/stp by com.
Byte 2: is 0x00 = Drive mode speed, no warning/error
status.
Byte 3: AnOut1 value
Byte 4: AnOut2 value.
Network comparison chart
The example above is a configuration for a Profibus
network. Profibus uses the Big endian format, which means
that the most significant byte (MSB) comes first (on the
lowest memory address).
If you use another network which uses the little endian
format, you may change the byte swapping in the example
above, either in the gateway or in your PLC.
Table 5
Example data format network comparison list
Network
Data format
Profibus
MSB first
Ethernet/IP
LSB first
CC-Link
LSB first
DeviceNet
LSB first
CANopen
LSB first
Modbus RTU
LSB first
Modbus/TCP
LSB first
The mapping is 1:1 compared to the Fieldbus I/O board 2.0
Option manual, i.e. same byte order.
In the same manner the MSF example above will give a 1:1
mapping according to the process data in the Emotron MSF
2.0 Fieldbus Option manual.
CG Drives & Automation 01-5971-01r0
9
Mörsaregatan 12
Box 222 25
SE-250 24 Helsingborg
Sweden
T +46 42 16 99 00
F +46 42 16 99 49
www.emotron.com / www.cgglobal.com
CG Drives & Automation, 01-5971-01r0 2012-04-02
CG Drives & Automation Sweden AB