Snap Track Mount Single Resolver Decoder

Snap Track Mount Single Resolver Decoder
Snap Track Mount
Single Resolver Decoder
Model DM2-STRAK-xxxx
and DS2-STRAK-xxxx
Autotech’s Single Resolver Decoder Model DM2-STRAKxxxx is a snap track mounted single resolver decoder especially designed for OEMs. The unit can be ordered with PNP
sourcing, NPN sinking (high or low true logic), or with TTL
type of outputs. It operates from 11–28 VDC input power. The
decoder provides complimentary quadrature phase outputs.
·
Decoder for single resolver
·
Short circuit proof resolver interface
·
Broken resolver cable indication
·
PNP sourcing, NPN sinking (high or low true logic) or
TTL outputs
·
Short circuit protected outputs and output shorted indicator (only with P & N type of outputs)
The unit has built-in diagnostics for broken resolver cable and
for shorted outputs (P and N outputs only). Two LED indicators provide positive indication of a properly working unit.
The resolver interface is short circuit proof.
Specifications
Input power: 11–28 VDC, 6 W
Operating temperature: –10 to +130 °F
Position transducer: Autotech’s RL100 single resolver,
such as; RL100, RL101, RL50, RL501, E1R, E7R, E8R, or
E9R series.
Maximum cable length between resolver and DM2:
2500 feet
Output format: Factory scale quadrature
Output type:
P: PNP sourcing
Logic True: Transistor ON, 1.7 V drop @100 mA
Logic False: Transistor OFF, 0.2 mA leakage
@ 50 VDC
N: NPN sinking (LOW TRUE LOGIC)
Logic True: Transistor ON, 1.1 V drop @100 mA
Logic False: Collector open, 0.1 mA leakage@ 50 VDC
C: NPN sink transistor (HIGH TRUE LOGIC)
Logic True: Collector open, 0.1 mA leakage @ 50 VDC
Logic False: 1.1 V drop @ 100 MA
MAN-DM2-001 Rev 01 11/02/99
T: TTL output, 5 V logic with multiplexin g
Logic True: 3.00 mA max, 2 V min
Logic False: 24.0 mA max, 0.8 Vmax
Output data update:
Transparent:
Output data is continuously updated.
Slave Systems:
Slave units must be used in conjunction with an Autotech
Master Unit. They cannot be used as stand-alone units.
Up to seven slaves may be added to one master unit. The
slave shares the position transducer with the master.
Autotech Instruction Manual
1
Installation and Wiring
Wiring Diagram
Output Configurations and Load Wiring
Broken Resolver Cable
Output Fault
N Type of Output
Common
NC
Cust VS+ (For Outputs)
NC
NC
Z
NC
Z
NC
B
NC
B
NC
A
NC
A
NC
PLS
Output
NC
TB1
NC
NC
NC
NC
P Type of Output
NC
NC
NC
NC
Common
TB2
11-28 VDC
Input
TB3
DIP Switch Settings
1
2
PLS
Output
Function
Not Used
3
4
Function
Not Used
T Type of Output
Sw
#
On/ Function
Off
5
Not Used
6
Always Off
PLS
Output
S1
S2
S3
S4
NC
NC
NC
NC
R1
R2
NOTE: Slave units share the position
transducer with the master.
TB4
2
Autotech Instruction Manual
MAN-DM2-001 Rev 01 11/02/99
Terminal Block on a
Single-Turn Resolver
Wiring Table for Single-turn Resolver
SAC-RL100-xxx
CBL-10T22-xxxx
Wire color
Function
Resolver
Terminal
MS Connector
Pin #
Black/Green
Green
Rotor R1
Rotor R2
R1 (RL)
R2 (RH)
F
E
Black/Yellow
Yellow
Stator S1
Stator S3
S1
S3
D
C
Black/Blue
Blue
Stator S2
Stator S4
S2
S4
B
A
Shield
Case Ground
GND
G
(Green Screw)
MS Connector on a
Single-Turn Resolver
Notes:
1. Black/Green indicates a black wire with green stripes.
2. MS connector: MS3112E-12-10P; Mating connector: MS3116F-12-10S
(Autotech part # ECM-10REC-ITT).
3. MS connector is not available with E8R series.
Grounding and Shielding
1. Resolver wiring must be done using twisted pairs in cable
with an overall foil shield. The twisted pairs must be wired
as per wiring instructions. See the How to Order section
for suitable cable offered by Autotech.
2. It is recommended that the shielded resolver cable be
routed in its own conduit or cable tray.
3. All shielded resolver cable must be kept at a minimum distance of 2 inches from all high voltage or inductive wiring.
4. All shielded resolver cable must be kept at a minimum distance of 12 inches from all motor wiring controlled by AC
or DC drives.
6. The shield drain wires may be terminated in one of two
ways:
a) Connect to chassis ground at each end and not connected to signal reference at any point in the system.
b) Connect to signal reference at the decoder only. The
shield drain should remain unconnected at the resolver
end and the shield should not touch earth ground at any
point in its run.
NOTE: Resolvers with MS connectors have shield drain
wire pre-terminated for method a).
Method a) is recommended for all Autotech products.
In certain circumstances, in unusual EMI conditions,
method b) may be necessary after consulting factory.
5. All ground planes (chassis grounds) in the total system
must be held to the same RF potential, by good metallic
connections to building frames, conduit or wiring trays.
MAN-DM2-001 Rev 01 11/02/99
Autotech Instruction Manual
3
How to Order
1. Decoder
D M 2 - STRAK - xxxx x
1
2
Single resolver decoder, snap track mounted
3
1: where M is for Master, substitute an S for a Slave unit
2: where xxxx is for pulses per turn (up to 1024) (Consult factory for any other scaling)
3: where X is:
P: PNP sourcing outputs
N: NPN sinking outputs, low true logic
C: NPN sinking outputs, high true logic
T: TTL outputs, 5 V logic with multiplexing
2. Resolver
Autotech single turn resolver, such as; RL100, RL101, RL50, RL501, E1R, E7R, E8R, or E9R series. See Autotech Catalog for ordering.
SAC-RL100-010 Brushless resolver, single-turn, NEMA 13, 5/8" shaft dia, with wiring terminal block.
SAC-RL100-M11 Above resolver with MS connector
3. Cables
CBL-10T22-x xxx 22AWG, 10 conductor (5 twisted pairs), overall foils shielded cable, for wiring resolver and/or outputs.
Length in feet
Standards lengths are 010, 020, 050 feet and increments of 50 ft. (Ex. 100, 150, 200, etc.)
Connector
C: Without connector
M: With 10 pin MS connector (for use with SAC-RL100-M11)
4
Autotech Instruction Manual
MAN-DM2-001 Rev 01 11/02/99
WARRANTY
Autotech Controls warrant their products to be free from defects in materials or workmanship for a period of one year from the date of shipment, provided the products
have been installed and used under proper conditions. The defective products must be returned to the factory freight prepaid and must be accompanied by a Return
Material Authorization (RMA) number. The Company's liability under this limited warranty shall extend only to the repair or replacement of a defective product, at The
Company's option. The Company disclaims all liability for any affirmation, promise or representation with respect to the products.
The customer agrees to hold Autotech Controls harmless from, defend, and indemnify Autotech Controls against damages, claims, and expenses arising out of subsequent sales of Autotech Controls' products or products containing components manufactured by Autotech Controls and based upon personal injuries, deaths,
property damage, lost profits, and other matters which Buyer, its employees, or subcontractors are or may be to any extent liable, including without limitation penalties imposed by the Consumer Product Safety Act (P.L. 92-573) and liability imposed upon any person pursuant to the Magnuson-Moss Warranty Act (p.l. 93-637),
as now in effect or as amended hereafter.
No warranties expressed or implied are created with respect to The Company's products except those expressly contained herein. The customer acknowledges the
disclaimers and limitations contained and relies on no other warranties or affirmations.
CAUTION
Autotech Controls' products are carefully engineered and rigorously tested to provide many years of reliable operation. However any solid-state device may fail or malfunction sometime.The user must ensure that his system design
has built-in redundancies if Autotech Controls' product is being used in applications where a failure or malfunction of
the unit may directly threaten life or cause human injury. The system should be so designed that a single failure or
malfunction does not create an unsafe condition. Regularly scheduled inspections, at least once a week, should be
made to verify that the redundant circuits are fully functional. All faults should be immediately corrected by repair or
replacement of the faulty unit. In addition, the user may have to comply with OSHA, ANSI, state or local standards of
safety. The user of Autotech Controls' products assumes all risks of such use and indemnifies Autotech Controls
against any damages.
The information in this installation manual has been carefully checked and is believed to be accurate; however, no responsibility is assumed for inaccuracies. Autotech Controls
reserves the right to make changes without further notice to
any products herein to improve reliability, function or design. Autotech Controls does not assume any liability arising out of application or use of any product described herein.
MAN-DM2-001 Rev 01 11/02/99
Autotech Controls does not recommend the use of its products in applications wherein a failure or malfunction of the
unit may directly threaten life or cause human injury. The
user of Autotech Controls' products assumes all risks of such
use and indemnifies Autotech Controls against all damages.
© Copyright 1993–2003 by Autotech Controls, Limited
Partnership. All rights reserved.
Autotech Instruction Manual
5