Untitled
1
UL Product Range
SIGNALING
ULCF3000 & ULCF3000RM Control Panels
Overview
Features
The Cooper ULCF3000 is a high specification
analogue, wall or rack mounted, UL Listed fire
system available in various loop configurations. It
combines sophisticated functionality with simple
operation and aesthetically pleasing design.
• Touchscreen Display
• 2 or 4 Class A Style 7 SLC loops
• Event History Buffer (9,999 events) with Date/Time
stamp
• 4 Notification appliance circuits (NAC's) outputs.
• Dedicated alarm, trouble, AC trouble relays
• Short circuit isolators incorporated into each loop
• Up to 200 addresses per loop
• Fully monitored network cable up to 126 panels
• Optional integral printer
• Alarm Verification
• PAS (Positive Alarm Sequence)
• Pre-Signal per Point (NFPA 70, 72 compliant)
• Remote Alarm Silence, Reset, Disablement and
Drill via addressable modules
The control panel has the ability to support complex
cause and effect programming and a wide range of
user controllable functions make the system ideal for
a diverse range of projects from industrial
applications through to large multi site commercial
developments.
The ULCF3000 uses soft addressing to minimise
installation time and remove the potential for error
associated with manual addressing.
Each of the system components have been
specifically designed to operate as part of a
ULCF3000 UL Listed system providing assurance
that the panel, the detectors, the interfaces and the
ancillaries are all fully compatible with each other and
that the full range of system functionality is supported
by each device.
4AC5
FIRE ALARM
EQUIPMENT
Benefits
• Supports a comprehensive range of soft
addressing modules and devices for greater
flexibility in design
• Menu driven graphical user interface for ease of
operation
• Reduced commissioning time through soft
addressing and auto learn functions
• Programming and trouble shooting time minimised
by using a range of features such as auto config,
walk test, system details, analogue values, etc
2
Technical Specification
Code
ULCF3000 and ULCF3000RM
Discription
UL Analgue Contorl Panel
Standards
UL864 9 eddition
Primary Operating Supply
120/240 V, 60 Hz, 2.0 A Supervised
Dimensions
D2
W
th
Secondary Operating Supply
battery Voltage
24 V dc
battery Charge Current
1.0 A (max)
Battery Derating Factor
0.1
battery Capacity Supervised
12 Ah (max)
H
Notification Appliance Circuits
D1
Class B, Style Y, Sounder Group 1 sounder 1, Sounder Group 1 sounder 2,
Sounder Group 2 sounder 1, Sounder Group 2 sounder 2
Output Voltage
24 V dc
Output Current
0.75 (max)
Line Impedance
50 ohms
H (mm)
395
W (mm)
332
D (mm)
115
When the product is powered by 240 V ac, the
maximum current of 3.0 A is shared between
these circuits.
When the product is powered by 120 V ac, the
Dimensions
Dimensions
maximum current of 2.25 A is shared between
these circuits.
D2
D2
Supervised, Power limited, Regulated
W
W
Notification Appliance Circuits
Class B, Style Y, SYNC MODULE. NAC1, NAC2
Output Voltage
24 V dc
Output Current
0.5 Amp (max)
Line Impedance
50 ohms (max)
H
H
The maximum current of 0.5 Amp is shared
between these circuits.
Supervised, Power limited, Regulated
Alarm, Trouble Contacts. Relay Expansion
Unity Power Factor
30 V dc
D1
D1
For connection to power limited sources only
Aux Relay (AC Trouble) Contacts
Unity Power Factor
30 V dc, 1 Amp
H (mm)
W (mm)
D (mm)
H (mm)
W (mm)
D (mm)
For connection to power limited sources only
Signaling Line Circuit Style [7] Class [A] – (Addressable Loop)
Rated Voltage
24 V dc
Maximum Current
500 mA
Line Impedance
50 Ω (max)
Supervised, Power limited
Network SLC
Voltage
5 V dc
Current
100 mA (max)
Line Impedance
50Ω (max)
Power Limited
Limited to same-enclosure Installations
Compatibility
Suitable for use with
Cooper UL fire systems
Product Codes
Code
ULCF30002G
ULCF30004G
ULCF30002GP
ULCF30004GP
ULCF30002GNC
ULCF30004GNC
ULCF30002GPNC
ULCF30004GPNC
ULCF30002GRM
ULCF30004GRM
ULCF30002GPRM
ULCF30004GPRM
ULCF30002GNCRM
ULCF30004GNCRM
ULCF30002GPNCRM
ULCF30004GPNCRM
ULR3000L2
ULR3000L4
ULR3000L2NC
ULR3000L4NC
Description
2 Loop Panel
4 Loop Panel
2 Loop Panel c/w Integral Printer
4 Loop Panel c/w Integral Printer
2 Loop Panel c/w Network Card
4 Loop Panel c/w Network Card
2 Loop Panel c/w Integral Printer, Network Card
4 Loop Panel c/w Integral Printer, Network Card
2 Loop Panel Red Metal Box
4 Loop Panel Red Metal Box
2 Loop Panel c/w Integral Printer Red Metal Box
4 Loop Panel c/w Integral Printer Red Metal Box
2 Loop Panel c/w Network Card Red Metal Box
4 Loop Panel c/w Network Card Red Metal Box
2 Loop Panel c/w Integral Printer, Network Card Red Metal Box
4 Loop Panel c/w Integral Printer, Network Card Red Metal Box
Rack mounted 2 Loop Panel
Rack Mounted 4 Loop Panel
Rack Mounted 2 Loop Panel c/w Network Card
Rack Mounted 4 Loop Panel c/w Network Card
ULCF3000 & ULCF3000RM Control Panels
3
UL Product Range
SIGNALING
ULCF3000PR Passive Repeater Panel
2 x 49 backlit LCD display and 6 supervisory LED’s
4AC5
FIRE ALARM
EQUIPMENT
Overview
Features
The ULCF3000PR passive repeater panel, is a cost
effective system which can be programmed via its
informative display to be either fully passive
(display only) or semi passive (restricted system
control).
• Fully passive
• Up to 200 Repeaters can be
connected to the loop
• Surface or semi-recessed
mounting
• 2 x 40 backlit LCD display and
6 supervisory LED’s
• Compact size
When loop connected the repeater panel will display
the system information text of the connected control
panel and will provide a fire indication, with panel
number, of any connected network control panel that
has fire activation.
The ULCF3000PR repeater panel does not require
system programming, with the exception of local text
information.
In addition to this repeater panels main menu driven
2 x 40 backlit LCD display, which provides system
status information, it also has 6 supervisory LED’s
(Power On, Alarm, Trouble, Supervisory, Test In
Progress, and Scroll).
Benefits
• Menu driven easy to operate
• Simple connection to panel
SLC circuit reduces wiring
and time
• Distance run up to 2kms from
main panel without additional
cable and equipment, saving
cost
Simple user interface
4
Technical Specification
Code
ULCF3000PR
Description
Repeater Panel, Passive
Standards
UL864 9th edition
Standard Connections
System Indicators
LED’s
Power on, Alarm, Trouble, Test, Supervisory,
Scroll LED’s
Mains Input, Supervised
Voltage
120 V ac to 240 V ac, 60 Hz
Current
35 mA
SLC Field Wiring
Current
0.354 mA
Wiring Gauge
12 (max) AWG
Wiring Class
Class A Style 7
Ground Fault
0.1 Ohm
Supervisory, Power Limited
Yes
Line Impedance
50 Ω (max)
Batteries
Batteries
1x12 V dc, 3.2 Ah, 0.1 derating
Battery Charge Current
0.4 Amp
Standby Period
24 hours + 30min alarm
Download Comms
RS232 port
Environmental
Operating Temperature
0°C to 49°C
Humidity (Non Condensing)
0 to 93 %RH
Physical
Dimensions (H x W x D)
270mm x 332mm x 90mm
Weight
3.6kg (with batteries)
Ingress Protection
IP30
Construction
PC/ABS, UL94 5VA rating
Colour
Light Grey or Graphite
Cable Entry
12 x 20mm knockouts top of backbox
Compatibility
Suitable for use with
Cooper UL fire systems
Dimensions
D1
W
H
1
2
3
4
5
D2
H (mm)
395
W (mm)
332
D (mm)
115
Product Codes
Code
ULCF3000PR
Description
Repeater Panel, Passive
ULCF3000RP - Repeater Panel, Passive
5
UL Product Range
SIGNALING
ULCTPR3000 Network Repeater Panel, Touch Screen
Overview
Features
The ULCTPR3000 repeater panel provides
sophisticated ‘touch screen’ functionality yet
achieves a simple end-user interface operation
within a compact panel design.
• Plug and play. All information is downloaded
through the network
• Touch-screen display
• Integrated network capability allows networking
with the latest Cooper range of analogue fire
alarm control panels
• Multi language capability
• PSU approved to EN54 pt4 and UL864 9th Edition
• Up to 126 repeaters can be connected to the
network
• Programmable as an active or passive repeater
• Dual redundant network card to enhance system
integrity
The CTPR3000 is designed to work with all UL Listed
Cooper analogue fire alarm control panels as a
network repeater. The Cooper ‘touch-screen’
repeater panel is easy to install and commission. All
text is transmitted via the network and is
automatically updated.
4AC5
FIRE ALARM
EQUIPMENT
Benefits
• Plug and play requires no programming
• Easy to operate touch screen display
• System integrity, fire alarm system continues to
operate even if there is a short circuit or open joint
on cable
• Easy to change the language to suit the operator
6
Technical Specification
Code
ULCTPR3000
Description
Repeater Panel, Touch Screen
Standards
UL864 9th edition, NFPA 70-72
Mounting the Backbox
270.00
141.80
System Indicators
LED’s
128.20
Power on, Alarm, General Trouble, General
Supervisory, Power Trouble, System Trouble,
Test, NAC Trouble.
120 V ac to 240 V ac, 60 Hz
Current
100 mA
Network SLC
5 V dv, 11 mA (max)
Line impedance
50 Ohm (max)
345.00
Voltage
229.80
Mains Input, Supervised, Power Limited
Batteries
Batteries
2x12 V dc, 7 Ah, 0.1 derating
Battery Charge Current
1.0 Amp
Standby Period
24 hours + 30min. alarm
Programable Relay
Programable Relay (Fire)
30 V, 1 Amp, Resistive
Download Comms
Download Comms
RS232 port
Environmental
Operating Temperature
0°C to 49°C
Humidity (Non Condensing)
0 to 93 %RH
50.00
Physical
Dimensions (H x W x D)
395mm x 332mm x 115mm
Weight
9kg (with batteries)
Ingress Protection
IP40
Construction
PC/ABS, UL94 5VA rating
Colour
Graphite
Display
Touch Screen
Cable Entry
11 x 20mm knockouts top of backbox
325.00
4kg (without batteries)
Compatibility
Suitable for use with
Cooper UL analogue addressable fire systems
Dimensions
D
H
W
H (mm)
395
W (mm)
332
D (mm)
115
Product Codes
Code
ULCTPR3000RP
Description
Repeater Panel, Touch Screen
ULCTPR3000 Repeater Panel, Touch Screen
7