RackLink™ Power Management System

RackLink™ Power Management System
96-01165 / rev 1d / 8-10-12
RackLink™ Power Management System
EXCEPTIONAL SUPPORT & PROTECTION™
RackLink™ series products ensure system reliability and system
uptime, providing intuitive setup and operation, pre-emptive
problem notification and automatic problem resolution.
Features
• Easy set up, with simple plug & play installation
• Monitor and log key environmental variables, including input voltage, load current
and local temperature
RLNK-SW715R
Rackmount Model
Front View
• Tracks and provides instantaneous notification of anomalous voltage, load current
and temperature conditions
• Detailed logging of environmental variables and alerts
• Auto Ping monitors remote IP devices and services and can automatically restart
an unresponsive network device
RLNK-SW715R
Rackmount Model
Rear View
• Proactive & automatic fault resolution
• Local control of individual outlets via manual switches
RLNK-SW215-NS
In-Line Model
• Integrated web server for browser-based access and control of individual outlets
and dry contact outputs
• Open-architecture serial communications protocol provides:
– 100% cloud compliance, without cloud-dependence; and
– Seamless integration into any RS-232 or TCP/IP based architecture
RLNK-MON120-NS
In-Line Model
• Extend control outside the rack to anywhere in the facility through dry contact outputs
by Middle Atlantic Products
Architects’ and Engineers’ Specifications
RackLink™ Series power management products shall be Middle Atlantic Products model #
RLNK-_____(refer to chart). RackLink power products shall be __”H x __”W x __”D
(refer to chart). RackLink shall have a __ amp power capacity (refer to chart). RackLink
shall provide __ surge protection (Basic, 2-Stage with Status Notification, Series refer
to chart). RackLink shall provide __ total outlets, __ of which shall be individually
controllable. RackLink shall provide __ total dry contact outputs, __ of which shall be
individually controllable. RackLink shall provide sequencing (refer to chart for applicable
models). RackLink shall provide auto-shutdown in over or under voltage events with
automatic recovery (refer to chart for applicable models). RackLink shall include a __’
SignalSafe™ power cord (refer to chart). RackLink power products shall monitor and
log -key environmental variables, including input voltage, load current and local
temperature. RackLink shall monitor specific remote IP devices and services and shall
automatically reboot an unresponsive network device. RackLink shall provide
user–defined alert thresholds for input voltage, load current and local temperature
and shall issue e-mail notification on any threshold breach and recovery condition.
RackLink shall automatically power down, or power up equipment as required on
over-temperature condition. RackLink shall allow local export of log files in CSV format,
and shall allow log files to be extracted to 3rd party databases via IP or
RS-232. RackLink shall include an integrated web server for browser-based access
and control. RackLink shall utilize an open-architecture serial communications
protocol that is cloud compliant without being cloud dependant, and provide an API
for seamless integration into any RS-232 or IP based architecture. RackLink shall
allow remote access and control via devices using the iOS and Android™ operating
systems using mobile applications. RackLink shall be fully compliant with any
control system or aggregator. RackLink shall extend control to anywhere in the
facility through dry contacts. RackLink shall be constructed of phosphate pre-treated
steel with a black powdercoat finish. RackLink shall be RoHS EU Directive 2002/95/
EC compliant. RackLink strip shall be GREENGUARD Indoor Air Quality Certified for
Children and Schools. RackLink shall be manufactured by an ISO 9001 registered
company. RackLink shall be warrantied to be free from defects in materials and
workmanship under normal use and conditions for a period of 3 years. Rackmount
power strip shall be ETL Listed to UL standard 60950-1 in US and CSA Listed to
CAN/CSA C22.2 #60950-1 in Canada.
c u s t o m i z a b l e s p e c i f i c at i o n c l i p s ava i l a b l e at m i d d l e at l a n t i c . c o m
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.com
Canada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
96-01165 / rev 1d / 8-10-12/ RackLink™ Power Management System
• All RackLink™ series products are fully compliant with any control system or content
aggregator; drivers available now from select control system partners
RackLink™ Power Management System
Form
Factor
Max
Load
Rated
Load
Surge
Protection
Sequencing
Total
RLNK-MON115-NS
In-Line Module
15A
12A
Basic
No
1
RLNK-MON120-NS
In-Line Module
20A
16A
Basic
No
1
RLNK-SW215-NS
In-Line Module
15A
12A
Basic
No
RLNK-SW220-NS
In-Line Module
20A
16A
Basic
No
RLNK-SW715R
Rackmount
15A
12A
2-Stage
RLNK-SW715R-NS
Rackmount
15A
12A
RLNK-SW620R
Rackmount
20A
RLNK-SW620R-NS
Rackmount
20A
RLNK-SW415R-SP
Half-Rack
RLNK-SW815R-SP
RLNK-SW820R-SP
# of Outlets
Controlled
Controlled Dry
Contacts
Integrated
Web Server
0
0
Yes
0
0
Yes
2
1
1
Yes
2
1
1
Yes
No
7
5
4
Yes
Basic
No
7
5
5
Yes
16A
2-Stage
No
6
4
4
Yes
16A
Basic
No
6
4
5
Yes
15A
12A
Series
Yes
4
4
2
Yes
Rackmount
15A
12A
Series
Yes
8
8
2
Yes
Rackmount
20A
16A
Series
Yes
8
8
2
Yes
Part #
Specification
Connection Type
Line Voltage
AC Power
Event Driven/Responses
(Rackmount Models) 9 ft. SignalSafe™ Cord (15A / 20A)
(In-Line Models) 3 ft. SignalSafe™ IEC (15A / 20A)
Email and/or Control Outlet
AutoPing No
Response/Recovery and/or Dry Contact/Sequence
Nominal: 120VAC
Minimum: 80VAC / Maximum: 140VAC
Maximum Peak Load
15A models: 15 Amps
20A models: 20 Amps
Maximum Cont.Load
15A models: 12 Amps
20A models: 16 Amps
Input Voltage Alert
Low: 105VAC - 110VAC
High: 123VAC - 128VAC
Load Current Alert
Minimum: 0A
Maximum: 15A / 20A (15A models / 20A models)
Temperature Alert
Minimum: 0oF
Maximum: 140oF
Alert Threshold Range
Basic and 2-Stage Surge Specification
Peak Impulse Current
- 30,000 Amps, one time
- 19,500 Amps, two times within 5 minutes
- 7,000 Amps, ten times within 2 minutes
Protection Mode
Line to Neutral only; no ground contamination
Response Time
Less than 1 nanosecond
Surge Energy Dissipation
711 Joules (10 / 100 micro seconds) (2-stage models)
EMI/RF Supression
>20dB Calculated Line to Neutral - 100kHz to 1Mhz - based on nominal impedance
- Maximum peak impulse current pulse as defined
between line and neutral
- Maximum multiple impulse current derated per spec
160 Joules (-NS models)
Over/Under
Temperature
Email and/or Control Outlet
and/or Dry Contact
Over/Under
Input Voltage
Email, and Automatic
Shutdown/Recovery
Over/Under
Load Current
Email
Operating
Temperature Range
32 - 140oF (0-60oC)
Max Thermistor
0-302oF (150oC)
Operating and
Measurement Temp
Humidity Range
0-95% RH,
non-condensing thermistor
Communication
RS-232
TCP/IP
HTTP
(integrated web server)
Rackmount Models:
W 19.25” L 9” H 1.75”
Listed to UL 60950-1 and CSA C22.2 No. 60950-1
Series Protection™ Specification
Voltage Protection Rating
330 V (lowest possible rating)
Clamping Voltage
186 VPEAK (NOMINAL LINE VOLTAGE OF 132 VAC)
UL 1449 Adjunct
Classification Test Results
EMI/RFI Filter, Normal Mode
(50-ohm load)
EMI/RFI Filter, Common Mode
(50-ohm load)
1000 surges, 6000 volts, 3000 amps, B3 pulse.
Measured suppressed voltage: 170 volts, no failures
40 dB @ 100 kHz; 50 dB @ 300 kHz;
50 dB @ 3 MHz; 50 dB @ 30 MHz
18 dB @ 300 kHz; 30 dB @ 1 MHz;
50 dB @ 5 MHz; 50 dB @ 20 MHz
Maximum Applied Surge Voltage
6000 volts*
Maximum Applied Surge Current
Unlimited, due to current limiting*
Maximum Applied Surge Energy
Unlimited, due to current limiting*
Endurance (C62.41-1991
Category B3 pulses)
3 kV>10,000; 6 kV >1000
Dimensions
In-Line Models:
6” x 3” x 2.5” (can be
mounted in any orientation)
Series Protection™ Models:
12 years limited warranty
Warranty
Basic and 2-Stage
Surge Models:
3 years limited warranty
*1.2 x 50 µs pulse, industry standard combination wave surge, as per IEEE C62.41
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.com
Canada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
9.625
[244]
8.88
[225]
Rackmount basic dimensions
17.57 [446]
17.57 [446]
19.00 [483]
8.88
[225]
8.88
[225]
9.625
1.74
[244][44]
(1RACKSPACE)
9.625
9600 BAUD RS232
10/100 FAST ETHERNET
[244]
TEMPERATURE PROBE
ALERT LED
19.00
[483]
SURGE STATUS
INDICATORS
19.00 [483]
BONDING SCREW
SWITCH
GUARD
1.74 [44]
(1RACKSPACE)
DRY CONTACT/SURGE STATUS
9600 BAUD RS232
10/100 FAST ETHERNET
1.74 [44]
(1RACKSPACE)
9600 BAUD RS232
10/100 FAST ETHERNET
TEMPERATURE PROBE
ALERT LED
BONDING SCREW
SWITCH
GUARD
SURGE STATUS INDICATORS
ALERT LED
TEMPERATURE PROBE
BONDING SCREW
SWITCH
GUARD
SURGE STATUS INDICATORS
DRY CONTACT/SURGE STATUS
DRY CONTACT/SURGE STATUS
3.37
[86]
2.93
[75]
IEC INLET
2.91
[74]
MODEL:IEC-C20
In-Line Module basic20A
15Adimensions
MODEL:IEC-C14
3.37
[86]
BONDING
SCREW
3.37
[86]
CABLE RETAINER CLIP
COMPATIBLE WITH
MIDDLE ATLANTIC
IEC INLET
SIGNALSAFE™ CORDS
20A MODEL:IEC-C20
15A MODEL:IEC-C14
IEC INLET
CABLE
RETAINER CLIP
20A MODEL:IEC-C20
COMPATIBLE
WITH
15A MODEL:IEC-C14
BONDING
SCREW
CABLE RETAINER CLIP
COMPATIBLE WITH
MIDDLE ATLANTIC
SIGNALSAFE™ CORDS
BONDING
SCREW
2.93
[75]
2.91
[74]
2.71
[69]
2.91
[74]
6.04
[153]
MIDDLE ATLANTIC
SIGNALSAFE™ CORDS
2.71
[69]
MOUNTING BRACKET
2.93
[75]
DRY CONTACT OUTPUT
MOUNTING BRACKET
TEMP PROBE
ALERT LED
10/100 FAST ETHERNET
DRY CONTACT OUTPUT
6.04
[153]
5.66
[144]
7.42
BRACKET
9600 BAUDMOUNTING
RS-232
[188]
TEMP PROBE
ALERT LED
DRY CONTACT OUTPUT
10/100 FAST ETHERNET
9600 BAUD RS-232
6.04
[153]
OUTLET CONTROL SWITCH
ALERT LEDTHUMB SCREW
MOUNTING
5.66
[144]
RLNK-SW
OUTLET CONTROL SWITCH
MOUNTING THUMB SCREW
OUTLET CONTROL SWITCH
MOUNTING THUMB SCREW
9600 BAUD RS232
TEMP PROBE
10/100 FAST ETHERNET
9600 BAUD RS232
TEMP PROBE
10/100 FAST ETHERNET
RLNK-MON
7.4
[188
9600 BAUD RS-232
2.71
[69]
5.66
[144]
9600 BAUD
RS232
All dimensions in inches unless otherwise
noted
[All dimensions in brackets are in millimeters]
TEMP PROBE
10/100 FAST ETHERNET
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.com
Canada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca
TEMP PROBE
10/100 FAST ETHERNET
7.42
[188]
Half Rack basic dimensions
8.775 [222.9]
SWITCH/CIRCUIT BREAKER
W/ SWITCH GUARD
9.297 [236.1]
LOCAL CONTROL
LOCKOUT INDICATOR
RLNK-SW415R-SP
8.650 [219.7]
DRY CONTACT/SURGE STATUS
9600 BAUD RS-232
LOCAL CONTROL SWITCHES
8.922 [226.6 ]
TEMPERATURE PROBE
10/100 FAST ETHERNET
ALARM INDICATOR
1.735 [44.1]
1.735 [44.1]
10.400 [264.2]
9.728 [247.1]
Rackmount with Series Protection™ basic dimensions
19.00 [483]
LOCAL CONTROL SWITCHES
ALARM INDICATOR
RLNK-SW820R-SP
LOCAL CONTROL
LOCKOUT INDICATOR
SWITCH/CIRCUIT BREAKER
W/ SWITCH GUARD
DRY CONTACT/SURGE STATUS
9600 BAUD RS-232
TEMPERATURE PROBE
10/100 FAST ETHERNET
9.67 [246]
17.25 [438]
All dimensions in inches unless otherwise noted [All dimensions in brackets are in millimeters]
US: New Jersey • California • Illinois • Voice: 973-839-1011 Fax: 973-839-1976 • middleatlantic.com
Canada: Ontario • British Columbia • Voice: 613-836-2501 Fax: 613-836-2690 • middleatlantic.ca