FMC monitoring and control units

FMC monitoring and control units
Issued: 1/09
Supersedes:
FMC
Monitoring and Control Units
Product Description
The FMC hardware series are especially designed for
waste and clean water systems, both in construction
and functionality. The RTUs1 are developed to meet
the demands of powerful flexible monitoring and
control units and are prepared to work with various
types of communication e.g. SCADA system, radio,
cellular systems, dedicated and dialled-up telephone
lines.
The FMC series complies with the required
electromagnetic emission and immunity standards.
The front panel is user-friendly with self-instructive
symbols. The RTUs are easy to install and
commission.
Approved standards
EMC emission standard EMC immunity standard LVD CSA EN 61000-6-4
EN 61000-6-2
EN 60947-1
C22.2 No. 14-95
Environment
Operational temperature Storage temperature Humidity (non-condensing) -20 - +50°C
-10 - +65°C
90 % RH
Cabinet
Size (l x w x h) 320x145x261mm
Weight, total 2.5 kg
Mounting Wall
Cable entries 7 holes
Enclosure IP65
Material
Enclosure Encloure, Lid Polystyrene
Polycarbonate
Size (l x w x h) 296x271x62 mm
Weight, total 2 kg
Mounting Wall
Connectors 1 DB 37
Wire terminals 68, screw locked
Cable
Front panel to I/O unit Double shielded 37 pole
Length 2,0 m
Minimum bend radius 50 mm
Data processing power
Processor Elan SC400 (486)
Executed word length, protected mode 32 bits
Clock frequency 66 MHz
Primary memory 8 Mbytes, D-RAM
Secondary memory 4 Mbytes, flash drive
Battery backup NiMH 3.6 V
Watchdog Yes
Expandable system
Frontal mounting
Front panel; front side Front panel; backside I/O unit I/O unit
IP 65
IP 20
IP 20
Frontal unit
Size (l x w x h) 325x216x52 mm
Weight, total 2 kg
Mounting Rectangular Hole
Surface seal EPDM rubber
Connectors 3 DB 9, 1 DB 37
The possible number of inputs and outputs for
FMC 150-600 can be expanded to 600 when
external RIO modules are connected. The FMC unit
communicates with the RIO modules on a SIOX
field bus and an optional SIOX driver is mounted in
the FMC to run the SIOX bus.
Issued: 1/09
FMC
Monitoring and Control Units
Communication
The FMC series is equipped with serial
communication ports for local PC connection
and modems. In addition, the FMC unit has an
optional PC card modem for communication
with e.g. SCADA system.
Accessories
Standard software
Level sensor
Modem
Power supply
Over voltage protection
SIOX driver
RIO modules
Supersedes:
Issued: 1/09
Supersedes:
FMC
Monitoring and Control Units
• = included
Technical data
Digital inputs
FMC
150
FMC
200
FMC
400
FMC
500
16
16
16
16
16
8
8
8
8
8
4
4
4
4
•
FMC
100
FMC
600
All inputs are individually opto-isolated
Locic 0:
-3 - +5V
locic: 1
1:1-30 V, 6-30 mA
Digital outputs
All outpots are individually isolated
Relay outputs:
6
Type:
Normally open, unprotected
Max load:
2 A 250V AC/DC
Solid state outputs:
Type:
2
Normally open, unprotected
Output:
100 mA, 250V AC/DC
Leakage current max:
0,01mA
Analogue inputs
All inputs are individually opto-isolated
Resolution:
12bits
Signal range:
4-20 mA
Internal dynamic resistanc, full scale:
50 Ohm
inaccuracy, full scale, typ.:
0.1%
Voltage drop
8V
Communication
Modem Connection:
PCMCIA slot
•
•
•
•
•
RS232
3
3
3
3
3
3
•
•
•
•
600
600
600
600
600
•
•
•
•
•
•
5
5
5
5
5
5
16
16
16
16
7
13
13
16
Communication port:
Bus communication:
Optional SIOX Driver
Max number of I/O:
User interface
Display:
LCD 2x16 character, LED backlight
Push buttons:
Alarm indications:
LEDs
16
Pump well indications:
LEDs
RTU status indications:
LEDs
5
5
5
5
5
5
24 V DC -15% - + 20%
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
Power supply
Supply voltage:
Current consumption (no load:):
1A
Fuse:
2A
Digitals inputs, max load:
Analogue inputs, max load:
0,5 A
24 V, 80 mA
Description of functions
Interface
COM1
RS232
COM2
RS232
COM3
COM4
RS232
Dialled-up connection GSM modem
X
X
Dialled-up connection external modem
X
X
Radio communication, polled system
X
X
Dedicated line modem
X
X
Dedicated line 232/RS485 converter
X
X
X
PCMCIA modem.
Service
X
132,5
+ + + + +
37 39 41 43 45 47 49 51
- - - - 38 40 42 44 46 48 50 52
ANALOGUE INPUTS
4-20mA
Voltage drop = 8V
53 54
55 56
57 58
59 60
61 62
DIGITAL OUTPUTS
Relay outputs
2A 250V AC/DC
63 64
65 66
67 68
100mA 250V AC/DC
Semiconductor outputs
Connection drawing
10
+ + + + + + + + + + + + + + + + + +
1 3 5 7 9 11 13 15 17 19 21 23 25 27 29 31 33 35
- - - - - - - - - - - - - - - - - 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 32 34 36
DIGITAL INPUTS
Logical 1 = 11 - 30V, 6 - 30mA
Logical 0 = -3 to +5V
Issued: 1/09
Supersedes:
FMC
Monitoring and Control Units
296
276
296
295
325
150,5
150,5
281
296
324,5