zabezpečovací systém
Contents:
1
6.24
6.25
6.26
6.27
6.28
6.29
6.30
6.31
6.32
6.33
6.34
6.35
6.36
6.37
6.38
6.39
6.40
6.41
6.42
6.43
6.44
6.45
6.46
6.47
6.48
Control panel architecture.................................. 3
1.1
2
3
Required system configuration
3
Preparing the control panel for installation ........ 3
Control panel main board................................... 3
3.1
3.2
3.3
3.4
3.5
3.6
3.7
3.8
4
Main board terminal description:
Hard-wired inputs on the main board
Installation of additional hard-wire input modules
Radio module installation
Y,X,V communicator module installation
Control panel memory chip
Wired keypad connection
Control panel resetting
3
4
4
4
4
5
5
5
Control panel power supply ............................... 5
4.1
4.2
4.3
5
Backup battery connection
Power supply connection
Powering-up the control panel for the first time
5
5
5
OASiS wireless devices ..................................... 6
5.1
5.2
5.3
5.4
5.5
6
Enrolling wireless devices to the control panel
Testing enrolled wireless devices
Signal strength measuring
Erasing enrolled devices
Enrolling the control panel to UC and AC modules
6
6
6
6
6
Control panel programming ............................... 6
6.1
6.2
6.3
6.4
6.5
6.6
6.7
6.8
6.9
6.10
6.11
6.12
6.13
6.14
6.15
6.16
6.17
6.18
6.19
6.20
6.21
6.22
6.23
Exit delay time
Entrance delay time
Alarm duration time
PGX and PGY functions
Changing telephone numbers in maintenance mode
Radio interference indication
Radio communications supervision
RESET enabled
Enrollment to a sub control panel for setting control
Master code reset
Enrollment to other devices (UC, AC)
Setting (Arming) without an access code
Triggered-detector indication
Confirmation of intruder alarms
Exit delay beeps
Exit delay beeps while partially setting (arming)
Entrance delay beeps
Setting (arming) confirmed by wired-siren chirp
Sirens always sound during audible alarms
Wireless siren alarm enabled (IW and EW)
Bypass user approval
Final-door detectors
Partial setting (arming) or system splitting
7
7
7
7
7
7
7
7
7
8
8
8
8
8
8
8
8
8
9
9
9
9
9
7
Automatic summer time (daylight saving time)
Pulse reaction of tamper sensors
Operating the PG outputs using ¾ 8 and ¾ 9
Permanent alarm status display for a set system
Tamper alarm if unset
Recording PG output activation to memory
Engineer reset
Social alarm feature
Annual check notification
Only single alarm indication
Setting (arming) by service code
Audible panic alarm
Higher control-panel receiver-sensitivity
Access by code plus card
Audible 24 hour intruder alarm
Service mode only with service and user code
Device reactions and section assignment
Code/card reactions and section assignment
Enrollment by keying in production codes
Automatic setting / unsetting schedule
Changing the service code.
Go to maintenance mode
Setting the internal clock
Editing keypad text
Recommended settings
10
10
10
10
10
10
10
10
10
11
11
11
11
11
11
11
11
12
12
12
13
13
13
13
13
Operating the system....................................... 13
7.1
7.1.1
7.1.2
7.1.3
7.1.4
7.1.5
7.2
7.3
7.4
7.4.1
7.4.2
7.4.3
8
9
10
11
12
13
The system keypad
13
Keypad indicators: ..................................................13
LCD display.............................................................13
Keypad display sleep-mode....................................13
Keys ........................................................................13
Functions beginning with the ¾key........................14
Programming access codes and cards
14
Setting and unsetting (arming/disarming) the system 14
Maintenance Mode
14
Displaying which user/card positions are occupied 14
Bypassing devices ..................................................14
Protecting a car near the system ............................14
Operating/programming the system by PC...... 15
Basic guidance for installers ............................ 15
Trouble-shooting .............................................. 15
Control panel technical specifications.............. 16
Control panel programming sequences........... 17
Programming access codes and cards............ 20
JA-83K control panel installation manual
-2-
MKG51101
This manual is valid for control panel JA-83K The control panel can be configured by a PC running OLink software.
(position 4) must always be connected if the second module is to
operate.
Device installation shall only be undertaken by
qualified technicians holding a training
certificate issued by an authorized distributor.
The manufacturer cannot be held responsible
for any damage or consequences related to the
improper or incorrect installation of this
product
1
Control panel architecture
The JA-83K control panel is a modular unit, with 50 addresses (marked
01 to 50). The heart of the unit is the JA-83K main board with 10 wired inputs.
The following additional modules can be plugged into this board:
x
JA-82R –– a radio module which makes it possible to enrol up to 50
wireless devices of the JA-8x and RC-8x range to the control panel.
x JA-82C –– an extension module which provides 10 additional wired
inputs, thus extending the total capacity to 20 (or 30 as the case may
be) wired inputs. One or two modules can be used.
A communicator can also be used with the control panel:
x JA-8xY –– a GSM communicator which the control panel uses for
transmitting alarm reports to the user and which communicates with the
ARC (alarm receiving centre) via the GSM band. It also enables remote
access via a phone keypad, or system administration via the GSMLink
website (JA-80Y only) or via Olink software running on an internet
enabled computer (JA-82Y only).
x JA-80V –– a LAN (Ethernet) computer network communicator combined
with a phone-line communicator. It allows communication with the ARC
via LAN and transmission of reports via a telephone line. It also
enables system administration via the GSMLink application.
x JA-80X –– a phone-line communicator which is able to communicate
with an ARC and which allows voice-reporting to the user pursuant to
the type of alarm. This module can be used in combination with a JA80Y –– a GSM phone-line backup.
x JA-80Q –– in the case of using a PIR detector with a camera.
The JA-68 outputs module can also be used with the control panel –– e.g.
to provide a link to the transmitter for communication with the surveillance
centre.
x
x
3.
Power input connector –– for connecting the power supply module.
Always unplug the power input and the battery before connecting and
disconnecting the connector.
4.
Connector for the first JA-82C wired input module –– it is designed
for an input module using addresses from L11 to L20.
5.
+ U power output overload indicator for detectors, modules, sirens...
6.
Terminal for connection of detectors, modules and sirens (see 3.1.)
7.
Switch enabling/disabling L1 ... L10 wired input.
8.
E-LINE bus connector for the connection of external devices (keypad,
PC). It is identical to the GND, A, B and +L terminals and it is used with
the connector on the control panel box.
11. I-LINE bus connector for the connection of internal (situated in the box)
devices (communicator, JA-68 module). The bus output cannot be
outside the control panel box.
12. JA-8xY communicator connector or the JA-80Q module when
needed.
13. JA-82R wireless module connector
14. The ““heart beat”” LED (indication of a healthily-running control panel)
15. RESET link –– it is normally open and serves for resetting the system (if
it is short-circuited when the control panel power supply is switched
on). This link can also be used to enter control panel enrollment mode
by briefly shorting the link while the control panel is powered.
1
15
RESET
21 ... 30
2
Required system configuration
The requirements of technical standards (namely of the EN-501-0x
series) should be observed when planning the system structure. The OASiS
control panel complies with safety grade 2. It must have one of the following
configurations as a minimum:
x
Memory chip –– for more information see 3.6
9. and 10. TMP1 and TMP2 Front and rear tamper connector. When it is
not used, couple the pins behind the connector with a shorting link.
When the connector is used, remove the link.
If you add a rear tamper, orientate it correctly according to the front
tamper into the hole in the bottom and push it to the side till the tab clicks.
After that you can mount the spring from the back, connect the cable and
remove the link
The control panel box also houses the power supply and space for a
backup battery (up to 18 Ah). For a view of the control panel case see fig. 17.
1.1
2.
RADIO
3
13
11 ... 20
at least two non-backup-battery sirens (JA-80L or SA-105) + ATS2
class communicator (JA-8xY, JA-80V or JA-80X)
at least one backup-battery siren (JA-80A or OS-360/365/300) + ATS2
class communicator (JA-8xY, JA-80V or JA-80X)
no siren + ATS3 class communicator (JA-8xY or JA-80V)
4
12
ON
OVERLOAD
OFF
Note: the above-recommended configurations are based on the EU
standard EN-50131-1 valid at the time of issuing this manual
2
I-LINE
E-LINE
Preparing the control panel for installation
First, select the correct location of the control panel box. If you are going
to use the radio module, avoid installing the control panel near large metal
objects (they might interfere with radio communication). The same rule
applies to the GSM module (test the strength of the received signal).
5
8
9
10
3.1
Main board terminal description:
+U
backup power supply (10 to 14V), 2A electronic fuse, max.
intermittent load - 2A. If the fuse is blown, the fault is reported
("fault" system event + OVERLOAD indicator flashes on the
main board). If the system is armed, an alarm is triggered.
When the overload current decreases, the power supply is
restored.
GND
common ground connection
01 to 10, COM are hard-wired inputs for the control panel. The reaction to
the triggering of an input is determined by the setting of these
addresses. The natural reaction (a delayed alarm) is set in
the factory and the input is in section C.
EW
external warning output, (max. 0.5A). This output is grounded
during an alarm. The control panel also transmits the external
warning relay signal for wireless sirens.
IW
internal warning output. This output is grounded during an
alarm. A standard siren can be wired between +U and IW
If requested, install a rear tamper sensor and attach a spring to it
(included in the package).
The control panel box can be attached to the wall using screws –– make
marks on the wall using the holes on the box and drill holes for the anchoring
screws. The two top holes are used to hang the box on screws on the wall,
the bottom ones are used to secure it. Route all input cables (power supply,
telephone cable etc.) into the box as well as the battery fixing tape and then
attach the control panel box to the wall.
Control panel main board
Connector for a second JA-82C wired input module –– it is intended
for an input module using addresses from L21 to L30. The first module
JA-83K control panel installation manual
7
11
TMP1
Description: 1. JA-82C connector (addresses 21-30); 2. memory chip; 3. power
supply connector; 4. JA-82C connector (addresses 11-20); 5. +U overload
indicator; 6. terminal; 7. 01-10 input switch; 8. external bus connector; 9,10. front
and rear tamper connector; 11. internal bus connector; 12. JA-8xY connector; 13.
JA-82R connector; 14. the heart beat LED; 15.RESET link
Then make holes for the cables. Lead the power supply cable to the left
side of the power supply (terminal) separately from the other cables.
1.
6
TMP2
fig. 1 Control panel main board
Removal of the control panel board and power supply before adjustment
and installation of the control panel box is recommended. Break out the two
push-out tabs leaving two holes at the bottom of the box (the battery space).
You will use one of these later to pass the power supply cable through. A
battery fixing tape (Velcro fastener tape enclosed in package) can then be
pulled through the holes.
3
14
-3-
MKG51101
GND
A,B
+L
3.2
a pair of programmable outputs. When activated, the outputs
switch to GND, with a maximum load of 0.1A/12V. The
factory-default setting of PGX is the ON/OFF function
(operated by the instruction 81 / 80 or using ON and
#OFF keys). PGY is activated if any part of the system is
armed. The status of PG outputs is also transmitted to AC
and UC wireless output modules by the control panel.
common ground connection
E-LINE digital bus data signals. The bus output can be routed
outside the control panel box.
back-up power supply (10 to 14V) feeding the devices on the
E-LINE bus (e.g. a wired keypad), electronic fuse, max.
intermittent load 200 mA.
ON
OFF
1 2 3 4
1k
1k
1k
1k
fig. 5 Two-loop connection of JS-25 Combo (01 GBS, 02 PIR)
+U
GND
01
02
COM
03
04
PGX, PGY
+U
GND
01
02
COM
03
04
terminals (max. 0.5A). The IW output status is also
transmitted for the wireless IW siren.
The difference between the internal warning (IW) output function and the
external warning (EW) one lies in their behaviour during the entrance delay
period. If any instant reaction detectors are triggered during the entrance
delay period, (e.g. by a child running straight to the living room during
disarming), only an internal warning is triggered. An external warning follows
only if the entrance delay has been exceeded (but no longer than 30
seconds).
ON
OFF
1 2 3 4
Hard-wired inputs on the main board
There are hard-wired input terminals for 01-10 device addresses on the
main board. All hard-wired inputs act identically: double balanced loops which
sense loop stand-by, activation or tampering as follows:
connected to COM via a 1 kȍ resistor (terminating resistor)
connected to COM via a 2k: to 6k: resistor connected to COM via a less than 700 : resistor (shortcircuit) or connected to COM via a more than 6k: resistor
(loop termination)
+U
GND
01
02
COM
03
04
stand-by
activation
tampering
ON
OFF
1 2 3 4
fig. 6 Connection of multiple detectors to the inputs –– schematically
1k
1k
x
x
+U
GND
01
02
COM
03
04
fig. 2 SA-200 magnetic detector connection
ON
x
OFF
1 2 3 4
x
x
x
1k
1k
3.3
Installation
modules
of
additional
hard-wire
input
By adding the JA-82C module it is possible to extend the amount of
inputs to twenty (addresses 01-20). When only one JA-82C module is
installed (extension to twenty inputs) module position 4 must be used see fig. 1.
fig. 3 JS-20 Largo detector connection
+U
GND
01
02
COM
03
04
The used input zone must be terminated by a 1k: resistor in stand-by
state.
When connecting a trigger contact to the zone, always use a parallel
1k: resistor. Thus it is possible to connect up to 5 trigger contacts in
series.
Tamper contacts should be connected in series (without resistors).
They therefore interrupt the whole loop. You can use an unlimited
amount of tamper contacts which can be combined with trigger
contacts (with parallel resistors).
The loop (input) reaction can be set. The NATURAL = delayed loop
reaction is set in the factory.
If you enrol a wireless device to the hard-wired input address, the
corresponding terminal will be disabled (it will not affect the system).
If you do not intend to use the hard-wire input or enrol a wireless
device to its address, switch the corresponding switch to the OFF
position (switch off the input).
When two JA-82C modules are installed, the maximum amount of thirty
hard-wire inputs (addresses 01-30) is reached. All hard-wire inputs behave
identically: they are double balanced inputs which are able to sense stand-by,
activation and tampering and for which examples of connection and
conditions stated in Chapter 3.2 apply in full scope.
ON
OFF
1 2 3 4
When you install the module, relabel the terminal description with a
sticker from the module package pursuant to the current position for which
the module is intended (inputs 11-20 or 21-30). Insert plastic spacing posts
on the openings in the module on the connector side and insert the prepared
module to the selected position in the main board.
1k
3.4
Radio module installation
The JA-82R radio module is installed in position 13 (see fig. 1). The
module antenna is included in the package and it should be inserted in the
groves on the side of the side of the box (see fig. 17). The antenna
connectors are thus connected to the pins on the JA-82R module. The
module installation enables the system to enrol wireless devices.
1k
3.5
fig. 4 One-loop connection of JS-25 Combo
Y,X,V communicator module installation
Screw the selected communicator onto the holder bolted in the bottom
right corner of the control panel box.
JA-83K control panel installation manual
-4-
MKG51101
If you are installing a GSM communicator (Y) and there is a strong GSM
signal in the place of installation, the self-adhesive antenna can be attached
directly to the flat surface of the holder. If there is a weak GSM signal we
recommend using some of the offered rod antennas.
4.1
If you use the combination of a GSM communicator (Y) and a telephone
line communicator (X), install the phone line communicator above the GSM
communicator using the supplied posts.
3.6
Always fix the backup battery in the box
using the supplied (Velcro fastener) tape,
thus avoiding possible injury caused by the
battery falling out of the box.
ATTENTION –– the backup battery is sold
charged, avoid shorting out its terminals!
Control panel memory chip
The control panel memory chip plugs into its own socket. If you take the
memory unit from the control panel and plug it into another control panel main
board of the same type, the control panel settings (enrolled detectors, codes,
set functions, etc.) are transferred.
Note:
x communicator settings are not stored in this memory
x do not plug or unplug the memory when the control panel is
powered
x when you take the memory unit from a damaged control panel, its
contents may be corrupted. It is therefore highly recommended to
back-up the settings in a PC using OLink software
3.7
Backup battery connection
It is possible to use a 12V gel cell backup battery, with a capacity of up to
18Ah in the control panel. The EN 50131-1 standard requires a 12-hour
minimum backup time in case of a power grid failure. For the standby
consumption of all system devices, see fig. 8.
The average backup battery lifetime is up to 5 years after which it must
be replaced. Checking its capacity during regular maintenance is
recommended. The control panel automatically recharges the backup battery
and monitors its condition. When the system runs only on the backup
battery, the battery charge is monitored and a technical alarm is
triggered before its complete depletion. The backup battery is then
disconnected. Once the power supply has been restored, the battery
reconnects and is recharged.
Wired keypad connection
The control panel can be operated and programmed by a JA-81E hardwired keypad. A screened four-cord flat cable connecting the corresponding
terminals should be used for permanent connection between the keypad and
the control panel (see fig. 7.)
Ensure that the battery is correctly connected (Polarity: RED = positive +,
BLACK = negative -).
When connecting a backup battery with screw leads, use two short wires with
a fast-on connector as a size adapter.
The keypad can also be connected to a bus connector on the control
panel box using a flat cable (max 10 metres) with RJ connectors for the
purpose of servicing or system debugging.
device
A
B
C
I-LINE
OASiS
1
4
7
ON
2
5
8
0
ESC
OFF
3
6
9
#
mA
note
JA-83K control panel
30
without a communicator
JA-82R module
20
JA-82C module
15
JA-81E keypad
30
JA-81E RGB keypad
up to 100
JA-80H (N) keypad
60
including WJ-80 interface
JA-80Y communicator
35
JA-80V communicator
30
JA-80X communicator
15
Wireless devices are not powered from the control panel
ABC
A
B
?
fig. 8 power consumption of individual components
4.2
Power supply connection
fig. 7 Wired keypad connection
Only a person with corresponding electrotechnical qualification can connect the power
supply.
The control panel power supply is doubleinsulated (safety class 2) and does not
incorporate a protective grounding wire.
Notes:
x When you use the INP keypad hard-wired input to connect the door
detector, its reaction is always delayed (it triggers an entry delay) and it
is located in section C.
x We recommend having only a single JA-81E hard-wired keypad in the
system.
3.8
Control panel resetting
If you need to set the factory-default settings in the control panel, perform
the following:
A two-cord double-insulated power cable with a minimum cross-sectional
area of 0.75 to 1.5 mm2 should be used to supply power. The power cable
should be connected to an independent circuit breaker (max 10 A), which
should also function as a switch. To disconnect a two-pole power supply a
power supply fuse must also be removed.
1.
Disconnect the back-up battery and the mains (using the terminal
board fuse),
2. Connect the RESET link and leave it connected,
3. Connect the back-up battery and the mains,
4. Wait until the green LED starts flashing and then disconnect the
RESET link.
If you need to reset the control panel with preset parameters according to
EN 50131-3 follow these next steps:
1.
2.
3.
4.
Connect the cable to the power terminals in the control panel. The power
supply is equipped with T 1,6 A / 250 V fuse. Fix the cable firmly using the
cable attaching bracket and two screws included in the package, but first
make sure that the power cords are properly connected in the terminals.
4.3
Disconnect the back-up battery and the mains (using the terminal
board fuse),
Connect the RESET link and leave it connected,
Connect the back-up battery and the mains,
Wait until the green LED starts flashing and key in the sequence
8080 an finally disconnect the RESET link.
Notes:
x After a RESET, all wireless devices are erased from the control panel
and all user codes and access cards are ““forgotten””.
x The Master code changes to 1234, and the service code to 8080.
x If resetting is disabled (see 6.8) it is impossible to reset the control
panel.
4
Control panel power supply
Once the control panel is assembled and all modules are in place, you
can proceed with putting the control panel into operation. We recommend
switching the control panel on without any wired detectors connected, using
only the wired keypad (if it is used in the system) for the first time. Only then
should you continue connecting the detectors –– beware of short circuits.
JA-83K control panel installation manual
Powering-up the control panel for the first time
1. First check all the wiring, and if a GSM communicator is installed, insert its
SIM card (PIN code disabled).
2. Check the backup battery connection
3. Switch the power supply on –– a green LED starts flashing on the control
panel board.
4. If a hard-wired keypad is connected it indicates ““Service”” mode
5. The control panel can also be set up via the supplied interface using OLink
software –– (A virtual keypad can be used in OLink to indicate system
status).
6. If you have neither the wired keypad, nor OLink, enrol a wireless keypad by
the following means:
a) have an opened keypad and its battery ready,
b) check that the green LED in the control panel is flashing,
c) short the RESET link in the control panel for 1 second (enrollment
mode opens),
d) install batteries into the keypad not far from the control panel
e) the keypad emits a beep and enrols to the first free address. After
that it displays ““Enrollment”” and offers another free address for
enrollment
f) Pressing the # key exits enrollment mode and the ““Service”” *)
message appears on the keypad
-5-
MKG51101
g) check whether the keyboard functions in the place where you
intend to install it and then install its plastic rear part.
*) The keypad comes with English texts from production – these can be
changed to other languages – see the manual.
5.3
Note: If the ““Service”” message fails to appear on the connected wired keypad
or if the wireless keypad is not enrolled, the control panel settings are not the
factory-defaults –– perform a reset (see 3.8.)
5
OASiS wireless devices
The control panel had 50 addresses (01 to 50), allowing the enrollment
of up to 50 wireless devices (detectors, keypad, key fobs, sirens etc.). A
device can be assigned to an address either by enrollment or by typing its
serial number while in Service mode (see 6.42).
Enrolling wireless devices to the control panel
1.
The control panel must be in Service mode. If this is not the case,
enter *0 service code (factory default: 8080). The control panel must be
disarmed.
2.
Press the ““1”” key to enter enrollment mode. The first vacant
address is then offered.
3.
You can select the desired address using the 1 and
the address is already occupied, the A indicator is lit),
4.
The device can be enrolled to the selected address by connecting its
battery (power),
5.
Enrollment to the given address is confirmed by the A indicator and
the next vacant address is then offered,
6.
Enrol all devices to the control panel one after another by connecting
batteries to them. Press the # key to exit enrollment mode.
7 keys (If
x
x
x
x
x
5.2
holding two buttons at the same time:
+
or + . This means
that a 4-button key fob can be enrolled to the control panel as two
different pairs of buttons and different features can be assigned to
them – see 6.40,
Only a single device can be enrolled to each address,
When an address is occupied (the A indicator lights), no more new
devices can be enrolled to it,
If a device has already been enrolled to an address, and it is then reenrolled to another address, the device’’s address assignment changes
from the original address to the new one,
If a device cannot be enrolled to the control panel, it does not have a
good connection to the control panel (the device must be at least 2 m
away from the control panel and an antenna must be connected to the
control panel during enrollment),
To re-enroll a device, first disconnect its battery. Then wait about 10
seconds (or, to save time, press and release the tamper switch on the
device), before you switch it on again
A sub-control panel can be enrolled to a master control panel by
keying in the sequence ““299”” on the keypad of the sub control panel
which must be in Service mode,
If you intend to use the final door function, the final door detectors
must be enrolled to addresses from 01 to 05 or from 46 to 50 (see
6.22)
The control panel must have its antenna connected and it must be in
Service mode (If this is not the case, enter *0 service code (factory
default: 8080). The control panel must be disarmed),
2.
Trigger the device to be tested (if it is a detector, close its cover first
and then wait until it is ready for testing),
3.
The keypad (its cover should be flipped open) beeps and displays a
description of the signal received from the device under test
4.
You can test the enrolled devices one after another by activating them
one by one. You can carry the wireless keyboard with you during the
inspection.
Trigger this device. The keypad (its cover should be flipped open)
displays signal quality ranging from 1/4 to 4/4,
4.
Use the 1 and 7 keys to select other enrolled devices and
measure their signal strengths,
5.
Exit signal measuring by pressing the # key
Erasing enrolled devices
1.
The control panel must be in Service mode. If this is not the case,
enter *0 service code (factory default: 8080). The control panel must be
disarmed,
2.
Key in ““1”” to enter enrollment mode and select the desired address
of the device you wish to erase using the keys 1 and 7 ,
3.
Press and hold the ““2”” key until a beep is heard and the A indicator
turns off,
4.
When all the desired devices have been erased press #.
5.5
Enrolling the control panel to UC and AC
modules
If you wish to transmit PGX and PGY programmable output signals to the
UC-82 and AC-82 output modules, you must enroll the control panel to these
modules as follows:
1.
The control panel must be in Service mode. If this is not the case,
enter *0 service code (factory default: 8080). The control panel must be
disarmed,
2.
Enter the control panel enrollment mode on the UC or AC module
(see the manual of the particular module),
3.
Key in 299 on the control panel keypad –– the LEDs on the module will
flash a few times.
Notes:
x we recommend locating the module close to the control panel during
enrollment or carry the wireless keypad close to the module,
x the control panel can be enrolled to the desired number of UC/AC
modules (each PG output can thus have an output at an arbitrary
number of places in the house),
x PG outputs are enrolled to UC and AC module relays individually (PGX
output to the X relay, PGY output to the Y relay). This means that
either one or both modules can be enrolled to the module if requested,
x Only one control panel can be enrolled to a UC or AC receiver (a
control panel repeats its PG signal every 9 minutes).
6
Notes:
x JA-80P and JA-85P motion detectors can be tested max. 15 minutes
after closing their cover. After that the detectors ignore frequent
movements (see the detector manual),
x Devices can also be tested in Service mode –– see 7.4.
JA-83K control panel installation manual
Key in 298, and the lowest enrolled device address is displayed
3.
Notes:
x To erase all wireless devices, press and hold the ““4”” key in enrollment
mode,
x If a wireless keypad is erased by the above mentioned means, it stops
communicating with the control panel and you must re-enrol it again
(see 3.4).
Testing enrolled wireless devices
1.
2.
5.4
Notes:
x Enrolment of a wireless device to an address disables the
corresponding hard-wired input terminal (when the device is
erased, the terminal is enabled again).
x RC-8x type key fobs are enrolled to the control panel by pressing and
x
x
The control panel must have its antenna connected and it must be
in Service mode (If this is not the case, enter *0 service code (factory
default: 8080). The control panel must be disarmed),
Notes:
x The JA-80P and JA-85P motion detectors can be tested max. 15
minutes after closing their cover. After that the detector ignore frequent
movements (see the detector manual),
x Measuring the signals from the JA-80L internal siren can be activated
by pressing its button. The JA-80A outdoor siren and wireless keypad
signal can be measured by triggering the IN input or triggering its cover
tamper switch,
x Each installed device should have the minimum signal strength of 2/4.
If the signal is too weak, the device should be relocated or higher
control panel sensitivity can be selected. (see 6.36) Alternatively, the
control panel can be equipped with an external antenna.
x This measurement shows the strength of the signal received from the
device by the control panel.
x The wireless keypad can be carried during device testing, its tamper
contact can be disabled via the jumper (near the tamper contact –– do
not forget to re-enable the tamper upon finishing the servicing) –– Note:
the keypad usually has a slightly shorter communication range than the
detectors. Therefore, if carried to more-distant detectors the triggering
of the detectors might not be shown.
x The most convenient way of measuring is via a computer using OLink
SW.
Wireless devices can be installed at their intended locations and then
enrolled to the control panel or vice versa. If there are any doubts as to the
suitability of devices for communication, temporarily attach the devices (e.g.
using adhesive tape) in the selected place and test radio communication
before finalizing installation. Follow the manuals of the particular devices
during their installation.
5.1
Signal strength measuring
1.
Control panel programming
The most convenient way to program the system is to use a PC running
OLink software. However, the system can also be programmed by keying in
the below mentioned sequences. The sequence summary table can be found
at the end of this manual.
-6-
MKG51101
x
The control panel must have its antenna connected and it must be in
Service mode (If this is not the case, enter *0 service code (factory
default: 8080). The control panel must be disarmed).
Enter the appropriate programming sequences –– see the following
description (an unfinished sequence can be escaped from by pressing
the # key).
To exit Service Mode press the # key.
x
x
6.1
Notes:
x The PGX and PGY outputs are not only provided as control panel
terminals, but the signals are also wirelessly transmitted for UC and AC
modules.
x The status of PGX and PGY outputs can be displayed by pressing the
““?”” key. The names of the outputs can be edited –– see 6.47.
Example (for unsplit systems): Assigning an ON/OFF function to the PGX
output = sequence 237. Assigning a panic function to the PGY output =
sequence 244.
Exit delay time
An exit delay time occurs while setting (arming) the system. During this
time period delayed or next-delayed detectors can be triggered without an
alarm occurring. To program the delay time, enter:
Factory default setting: PgX= ON/OFF, PgY= anything set
6.5
20x
where x
is a number from 1 to 9 determining the duration in steps
of tens of seconds (1=10 s, 2=20 s,....)
If the control panel is equipped with a JA-8xY, JA-80V or JA-80X
communicator, then this sequence enables the holder of the master code
(system administrator) to program telephone numbers for alarm reporting in
maintenance mode. Programming telephone numbers is the same as in
Service mode (see communicator manual):
If there is a final-door detector in the system then the exit delay is
multiplied by 30 s instead (1=30 s, 2=60 s,...).
Example: To program a 20 seconds exit delay, use the sequence 202 (if
there is a final-door detector, a 60 seconds delay will result).
Factory default setting: x = 3
6.2
Entrance delay time
6.6
21x
is a number from 1 to 9 determining the delay in multiples
of 5 seconds (1=5 s, 2=10 s,....)
If the entrance delay is triggered by a final-door detector, then parameter
x is multiplied by 30 s instead. (1=30 s, 2=60 s,...) –– in this case it means that
the entrance delay would be six times longer than if it had been triggered by
an ordinary detector.
6.7
Alarm duration time
22x
Note: There can be up to 5 different alarms in the system: intruder, tamper,
fire, panic, and technical alarm.
Example: Alarm duration of 5 min. = sequence 225
Factory default setting: 4 minutes
PGX and PGY functions
The functions of PGX and PGY can be programmed by entering
sequences:
x
0
1
2
3
4
5
6
7*
8*
6.8
determines the PG function or the event which triggers a
change of PG state:
Split system
Alarm A = PG on
Alarm B = PG on
Entrance delay A = PG on
Entrance delay B = PG on
A set = PGX on, B set = PGY on
Panic A = PGX on
Panic B = PGY on
Fire = PGX on, dropout = PGY on
disabled
Radio communications supervision
271
indication enabled
270
indication disabled
RESET enabled
281
RESET enabled
280
RESET disabled
Warning: If resetting is disabled and the service code has been forgotten, it
would no longer be possible to enter Service mode. If this happens, send the
control panel back to the manufacturer.
Factory default setting: RESET enabled.
6.9
Enrollment to a sub control panel for setting
control
If the control panel has another OASiS control panel enrolled as a subsystem, then the sub-system reports all alarms, tampering and faults to the
master control panel. The master control panel reacts to particular signals
accordingly, and displays the sub control panel’’s address as the source.
fig. 9 PG outputs settings
* The ON / OFF and 2 second pulse functions can be controlled from
the keypad by keying in * 8, *9 or using the ON and #OFF keys (see 6.26)
or they can be operated by a code or card. These PG output functions can
also be controlled by signals from keyfobs or detectors (see6.40).
JA-83K control panel installation manual
260
If resetting is enabled, it is possible to return the control panel to its
original factory-default settings via the reset link on the main board. (see
section 3.8).
for PGY
Completely (ABC) set = PG on
Anything set = PG on
AB set (not ABC) = PG on
Fire alarm = PG on
Panic = PG on
Any alarm = PG on
(excluding Panic)
AC dropout = PG on
ON/OFF
2 seconds pulse
enabled
Factory default setting: supervision disabled.
for PGX
Unsplit system
261
Notes:
x In the OASiS system, communication is checked every 9 mins.
x In detectors used for car protection, (JA-85P, JA-85B) it is possible to
disable radio communication supervision. It allows car detectors to be
excluded from supervision to avoid alarm triggering when driving the
car away from the system.
x Random dropouts in communication can occur in some installations
near e.g. airports or TV towers. The system is still reliable in such
situations as high-priority transmissions are repeated often. We
recommend disabling communications supervision in cases like this.
x is a number from 0 to 9 determining the alarm duration:
0 = 10 s, 1 = 1 min., 2 = 2 min. up to 8 = 8 min., 9 = 15
min.
24x
Radio interference indication
If enabled, the control panel can routinely check wireless connections to
its devices. If communication with a particular device is lost, the control panel
can communicate a fault indication to the user:
This parameter limits the duration of a triggered alarm. After the alarm
state expires, the control panel will return to its previous state, i.e. as before
the alarm occurred. The alarm state can also be terminated by an authorised
user. To program the alarm duration enter:
where x
programming disabled
Note: In some places the system can be permanently or occasionally
affected by radio interference, e.g. by nearby radar stations, TV transmitters
etc. In most cases the system can tolerate such effects, but with this antijamming function disabled.
Factory default setting: x = 4
23x
250
Factory default setting: disabled.
Example: To program a 20 seconds entrance delay, enter the sequence 214
(if the delay has been activated by a final-door detector, a 120 seconds delay
will result instead).
6.4
programming enabled
The control panel is capable of detecting and indicating radio
communication jamming. If this function is enabled, any radio jamming longer
than 30 s will trigger fault indication and if armed the alarm is triggered.
where x
where
251
Factory default setting: programming disabled.
The entrance delay time is provided to unset (disarm) the system after a
first delayed detector has been triggered. To program this time, enter:
6.3
Changing telephone numbers in maintenance
mode
After sub control panel enrollment to the master control panel, these two
panels are independent concerning setting control. Each panel can be
operated by its own keypads or key fobs. If there is an alarm or fault in the
sub control panel, it is also indicated on the master control panel. In this
configuration it is impossible to control the sub control panel from the master
control panel.
-7-
MKG51101
If it is desired to control a sub control panel from a master control panel
(i.e. setting/unsetting), it is possible to enroll a JA-8x OASiS master control
panel to a sub control panel as a remote control as follows:
1.
First enroll the sub control panel to the desired address in the master
control panel by entering 299 on the sub control panel’’s keypad in
Service Mode –– see 5.1for full details.
2.
Switch the master control panel to Service Mode.
3.
In the sub control panel, enter enrollment mode by keying in ““1”” in
Service Mode and select the desired address.
4.
In the master control panel enter 290. This way the control panel will
enroll to the sub control panel to the desired address as a remote
control.
5.
Switch both control panels to maintenance mode and check that allsection setting of the master control panel also sets the sub control
panel and unsetting the master control panel unsets the sub control
panel too. Expect approximately 2 seconds of delay between control
panels.
x
x
x
x
Notes for operating the sub control panel:
x
x
The sub control panel can still be operated independently via its keyfob
or keypad e.g. it can be set while the master control panel is unset. If
the master control panel changes its status later on, it will then control
the sub control panel to achieve synchronisation.
To disable the master control panel’’s ability to control the sub control
panel, enter the sub control panel’’s enrollment mode, select the
address where the master control panel is enrolled and erase the
master control panel from this address by pressing and holding key 2.
x
x
6.10 Master code reset
If the master code has been forgotten or a card lost, it is possible to use
the following sequence to reset the master code to the factory-default 1234:
x
291
Note: Resetting the master code has no effect on other codes and cards.
Resets are recorded in the control panel memory and sent to the ARC (Alarm
Receiving Centre, previously called a central monitoring station).
x
6.11 Enrollment to other devices (UC, AC)
Note: When the first detector is triggered it begins a process which waits 40
minutes for any possible confirmation of the alarm (unconfirmed alarm status)
during which the system works exactly the same way as if the confirmation
function had not been enabled.
Keying in 299 sends an enrollment signal to enroll the control panel to
UC-82 or AC-82 receiving modules (see 5.5). This sequence can also be
used to enroll a sub control panel to a master control panel (see 6.9).
6.12 Setting (Arming) without an access code
Warning: If intruder alarm confirmation is enabled, it is necessary to install
enough detectors in the building to detect an intruder even if he/she is only
moving in one particular place.
““Hot”” setting keys (short-cut keys for setting) A, B, ABC or entering ““
number”” can be enabled for use without a valid access code or card. If
disabled, then hot key use or entering ““ number”” has to be followed by a
valid access code or card to have any effect:
x
x
Function/sequence
301
300
All-section setting
Setting of A
Setting of AB (or B)
Event memory recall
ABC key
A key
B key
4
Code/card
A key, code/card
B key, code/card
4 code/card
Factory default setting: confirmation disabled
6.15 Exit delay beeps
The exit delay can be indicated by beeps from the keypad and internal
wireless siren. The beeps get faster in the last 5 seconds.
Beeps disabled
341
Beeps enabled
340
Beeps disabled
Factory default setting: Beeps disabled.
Pressing the ? key checks if any detectors are permanently triggered,
e.g. if any doors or windows are open. The following sequence enables the
display of text concerning active detectors.
indication disabled
330
The exit delay caused by partial setting, e.g. using the A or B key, can
also be indicated by keypad beeps and internal-siren beeps. The beeps get
faster in the last 5 seconds. The feature is linked to 331 parameter setting.
6.13 Triggered-detector indication
310
Beeps enabled
6.16 Exit delay beeps while partially setting (arming)
Factory default setting: Setting (arming) without an access code enabled.
indication enabled
331
Factory default setting: Beeps enabled.
fig. 10 setting / arming with or without code
If you remotely operate the system by mobile phone, you can press 1
for the ABC key, 2 for key A, and 3 for key B.
Controlling the PG outputs by keying in 8 or 9 or pressing ON and
#OFF is unaffected by these settings. These keys can however be
disabled by a special sequence (see 6.26).
311
alarm will not be caused but the control panel will record a so-called
unconfirmed alarm.
If any other intruder detector is triggered in a set section within 40
minutes of the above event, an intruder alarm will be triggered. If no
other detector is triggered during this period, the control panel will stop
waiting for confirmation.
The alarm must be confirmed by another detector than the first one,
and if the second one is a motion detector its detection area must not
cover the same area as the first detector to be triggered. This must be
ensured by the proper location of detectors.
An unconfirmed alarm is recorded in control panel memory but can
also be sent to the ARC, or to the user by SMS report.
If the first triggered detector has a delayed reaction, it will start a socalled unconfirmed entrance delay. This delay is indicated the same
way as an ordinary entrance delay, but if no other delayed detector is
triggered during this delay, there will be no alarm if the unconfirmed
entrance delay is exceeded, with another unconfirmed alarm being
recorded in the control panel memory. If there is any other delayed or
next-delayed detector triggered during the entrance delay period, it will
confirm the entrance delay, and if this delay is exceeded (due to no
unsetting being done) it will trigger an intruder alarm at the end of the
delay.
If a delayed detector is triggered within 40 minutes after the triggering
of an unconfirmed alarm or the moment the unconfirmed entrance
delay is exceeded, the confirmed entrance delay starts running and
when it times out (due to no unsetting being done), an intruder alarm is
triggered.
If the unconfirmed entrance delay is confirmed by an instant detector it
will trigger an internal warning (IW) alarm immediately (e.g. an internal
siren) and if the entrance delay times out then an external alarm (EW)
will be triggered.
An unconfirmed alarm can be confirmed by any other intruder detectors
in the system as long as the detectors are assigned to a set (armed)
section.
The confirmation of intruder alarms concerns only detectors with
instant, delayed, or next-delayed reactions. It has no effect on fire,
panic, 24-hour, tamper, or technical alarms. These alarms are triggered
immediately without confirmation.
6.17 Entrance delay beeps
The entrance delay can be indicated by keypad beeps and internal-siren
beeps:
Factory default setting: indication enabled
351
Beeps enabled
350
Beeps disabled
6.14 Confirmation of intruder alarms
Factory default setting: Beeps enabled.
To reduce the risk of false alarms and to comply with British standard BSI
DD243, the control panel allows alarm confirmation logic to be enabled as
follows:
6.18 Setting (arming) confirmed by wired-siren chirp
321
confirmation logic enabled
320
confirmation logic disabled
A hard-wired siren connected to the IW terminal of the control panel can
audibly indicate setting by one beep, unsetting by two beeps and unsetting
after an alarm by three beeps. Four beeps mean an invalid attempt at setting
the system has occurred.
Confirmation logic:
x If the system is set (armed) and any intruder detector gets triggered,
i.e. a detector with an instant, delayed, or next-delayed reaction, an
JA-83K control panel installation manual
-8-
361
Chirps enabled
360
Chirps disabled
MKG51101
Note: In JA-80L wireless sirens, this function can be individually enabled for
each siren. (see the siren manual).
x
Factory default setting: Hard-wired siren chirps disabled
6.19 Sirens always sound during audible alarms
Using this sequence it is possible to disable internal and external sirens
(IW and EW) if any part of the system is unset (partial setting), i.e. when
someone is home.
371
Sirens always sound during audible alarms
370
Sirens only sound during audible alarms when all
sections are set, i.e. no one is at home
Setting (arming) the system with a final-door detector:
x After entering a request to set the system, an exit delay of between 30
to 270 seconds will begin and be indicated.
x If a final-door detector is triggered during the exit delay, the exit delay
will be extended by the time in which the detector is still triggered. So, if
for example, the door is left continuously open, the exit delay will never
end.
x If a final-door detector is de-triggered, the system will wait five more
seconds during which beeping gets faster, and if the door is not
opened again during this short period, the exit delay will terminate and
the system will be set immediately.
x The duration of the exit delay therefore depends on the time the final
door stays open. For instance, in winter if the driveway in front of a
garage needs to be cleared of snow there will be plenty of time to do it,
and in summer when garages can be exited easily and therefore
quickly, the exit delay can be rather shorter. The exit delay only
depends on the length of time the garage door is left open.
x If no final-door detectors are triggered during the exit delay, the system
will provide an exit delay and then set.
x If the final door detector stays continuously triggered, an endless exit
delay will result with the system never being set. This means all
delayed and next-delayed detectors will not be set (armed).
x If there are multiple final-door detectors in the system, the exit delay is
extended if any of them is triggered and ends after all final-door
detectors have been de-triggered.
Factory default setting: Sirens always sound during audible alarms.
6.20 Wireless siren alarm enabled (IW and EW)
This setting is for enabling and disabling wireless sirens in the system:
381
wireless sirens enabled
380
wireless sirens disabled
Note: This setting applies both to internal and external wireless sirens.
Factory default setting: wireless sirens enabled
6.21 Bypass user approval
This setting can change the function of the system when it is set (armed)
and if there is:
x
x
x
x
any detector triggered
any tamper alarm
any trouble in the power source
lost communication with any wireless device (for more than 20
minutes)
x any panic button triggered
If bypass user approval is set (391), then during setting (arming), the
system notes which problems mentioned above are active and displays
informative text on the keypad and only bypasses them if the user approves
the bypassing by keying in a within 6 seconds of being notified.
Unsetting (disarming) the system with a final door detector:
x If a final-door detector gets triggered in a set (armed) system, an
entrance delay will begin with a duration of between 30 and 270
seconds.
x If a normal delayed detector gets triggered while the user enters a
building, the system starts an ordinary entrance delay of between 5
and 45 seconds.
x If a final-door detector is triggered first, a longer entrance delay will
begin. If during this delay an ordinary delayed detector is then
triggered, the remaining entrance delay will then be shortened to the
delay associated with detectors of this kind.
Note: Only use status-reporting detectors such as the JA-81M or JA-82M, or
the hard-wired inputs of wireless keypads, or the hard-wired inputs of a
control panel as final-door detectors. This mode is unsuitable for pulse
detectors such as JA-80P motion detectors, or the hard-wired inputs of JA81E hard-wired keypads which also have a pulse reaction.
The system has a built-in auto-bypass function (setting 390) so that if any
number of detectors are being triggered during setting (arming) then they will
be bypassed and ignored automatically without consulting the user.
391
Approval by pressing the key is requested from the
user
390
Bypassing occurs automatically without user approval
Notes regarding setting the system with (a) triggered detector(s) or
problems as mentioned above:
x Details can be viewed by pressing the ? key (e.g. open doors or
windows).
x If a wireless keyfob is used to set the system and auto-bypass user
approval is enabled, the system will set without bypass approval, i.e.
setting by keyfob does not trigger an approval request.
x The automatic bypass of a detector will end after the detector has been
de-triggered (for example if a door is closed) or the problem
disappears.
x If auto-bypass user approval is enabled and Service mode is being
exited while a detector is being triggered, the installer will be notified
about the bypass. The installer can then approve the bypass by
pressing # twice.
x To comply with the EN-50131-1standard 391 should be set.
Factory default setting: No final-door detectors in the system.
6.23 Partial setting (arming) or system splitting
The control panel can be configured in three ways as follows:
x
x
x
66x
where x
6.22 Final-door detectors
In this mode, up to 5 detectors can be defined as final-door detectors and
assigned to addresses 01 to 05 or 46 to 50 in order to make leaving a
building much easier, especially via a garage:
0 = unsplit system (setting/unsetting as an entire system)
1 = partial setting (for setting sections A, AB, or ABC)
2 = split system (sections A and B can be set/unset
independently by separate users, with section C only being
automatically set when both A and B are manually set)
Notes:
x For an unsplit system, all intruder detectors are set/unset
immediately after the user sets/unsets the system. Assigning wireless
devices, access codes and keyfobs to various sections of the system
has no effect in this mode.
x Partial setting is especially suitable for homes and apartments where
the user wishes to protect different parts of the premises during the
day. Detectors can be assigned to three sections, A, B and C. Using
setting (arming) key A on the system keypad, you can set section A,
e.g. setting the garage area in the afternoon. Using setting key B you
can set sections A and B simultaneously e.g. in the evening before
going to sleep to protect the garage (section A) and the ground floor of
the house (section B). The ABC total-setting button is used when
leaving the home to set all sections, A,B and C. If you then use a valid
access code or card for unsetting (disarming), all sections will be unset.
The assignment of codes or cards to sections has no effect in this
mode. A and B keypad buttons are used for partial setting.
65x
0 = none,
1 = detectors on addresses 01 to 05,
2 = detectors on addresses 46 to 50.
Description of final-door detector mode:
x If a final-door detector is used in the system then the value of x for exit
delay programming is multiplied by 30 s (see 12) thereby extending the
delay, and if an entrance delay is triggered by a final-door detector then
the value of x for the entrance delay is also multiplied by a larger value
of 30 s.
x A final-door detector should be programmed to have a natural reaction,
otherwise it works as it is set (e.g. instant reaction).
x Only door/window detectors, hard-wired control panel inputs or hardwired inputs in the wireless keypad unit to whose alarm input the finalJA-83K control panel installation manual
the entire system sets and unsets together or,
the system partially sets and unsets to protect only certain parts of a
house during the day, while people are still present in the unset parts
or,
the system can be split into two independently set/unset sections for
two separate users and also with a common section if desired.
Program as follows to configure the system as desired:
Factory default setting: Bypassing occurs automatically without user
approval.
where x
door detector is connected should be assigned to the addresses which
you set with this sequence as belonging to final-door detectors.
If a final-door detector is used for a garage door, no instant detectors
should be inside the garage. Next-delay detectors would however be
acceptable.
-9-
MKG51101
x
A keyfob can also be used for partial setting control. Buttons
and
can be programmed to set and unset the entire system, and
x
x
buttons
+
can be programmed for setting (arming) sections A
and AB respectively to partially set the system (this pair of buttons
must be assigned to section A or B if it is to be used for partial setting.
See 6.40 for details on partial setting by keyfob).
Split system mode is especially suitable where two families (A and B)
live in a single house or two companies (A and B) share one building.
The system behaves as two independent systems, one being section A
and the other, section B. There is also a common section C which is
only set if section A and section B are set at the same time and is
commonly used for shared entrances, doors etc. Codes and keyfobs
can be assigned to 3 sections. Codes and keyfobs assigned to section
A allow access to section A only, whereas codes and keyfobs assigned
to section B allow access to section B only. Codes and keyfobs
assigned to section C allow the user to access the whole house, as
they control all sections (similarly to the Master code).
Partial setting only has an effect on intruder detectors, i.e. detectors
with instant, delayed or next-delayed reactions. Detectors with fire,
tamper, panic and 24-hour reactions are always able to trigger their
kind of alarm immediately, whether their section is set (armed) or not.
little of the system is set. This feature can be used to ignore this
requirement if appropriate.
The wireless keypad can continuously display the status if powered by
an external power supply. If powered by internal batteries the keypad
will turn off its display after 20 seconds of not being used (in Service
Mode the display turns off after 15 minutes of no use by the installer).
Factory default setting: only 3 minutes of display time
6.28 Tamper alarm if unset
According to EU legislation an unset (disarmed) system should not
audibly sound a tamper alarm if tampering occurs. If the audible indication of
tamper alarms is required while the system is unset (disarmed) then this can
be enabled by the following sequence:
6841
audible tamper alarm even for an unset system
6840
silent tamper alarm for an unset system
Factory default setting: Unsplit system.
Notes:
x Even if tamper alarms are silent, they are still recorded in the control
panel memory and reported to the end user by SMS, and also to the
ARC if used.
x If the sequence 370 has been programmed, then tamper alarms will be
silent if the system is unset or partially set.
6.24 Automatic summer time (daylight saving time)
Factory default setting: silent tamper alarms for an unset system
If enabled, this feature automatically offsets the system time to that of
summer time, or daylight saving time as it is also known:
6.29 Recording PG output activation to memory
x
6801
automatic summer time enabled
6800
automatic summer time disabled
The activation of PGX and PGY outputs can be recorded in the control
panel’’s memory (for example if the outputs are used for access control). This
can be enabled by the following sequence:
Note: If automatic summer time is enabled, the control panel’’s internal clock
is automatically offset by +1 hour on March 31st at midnight. The offset is then
removed on October 31st at midnight to return to winter time.
react with a tamper alarm to all triggered tamper
sensors
Note: Ignoring permanently triggered tamper sensors is useful for example
when carrying a detached wireless keypad around with you during installation
as this avoids unnecessary tamper indication. If you choose to ignore
permanently triggered tamper sensors, their de-triggering is not reported to
the ARC.
Using this feature the PGX and PGY outputs can be controlled from the
keypad by pressing the 8 and 9 keys (or keys ON and OFF).
6820
control disabled
If this function is enabled the signals from delayed, next delayed and
instant detectors are regularly checked in disarmed mode. If there is no active
signal (no movement inside) for more than 16 hours a panic alarm is
triggered.
social alarm disabled (default)
6900
notification disabled
6901
notification enabled
Notes:
x An annual technical inspection notification is displayed as text on the
keypad display and can also be sent as an SMS to the end user and/or
installer and/or as a report code to an ARC, if used.
x Annual technical inspection notification text disappears on entering
Service Mode.
x When this notification is enabled, exiting Service Mode will cause a
notification to occur in the next year on the first day of the month in
which it was set. (e.g. if you set the annual check notification on the
Notes:
x European legislation requires status displaying to be suppressed within
three minutes of setting (arming) the system, no matter how much or
JA-83K control panel installation manual
6870
This sequence enables the user and installer to be notified of the
necessary time for an annual technical check:
The below sequence enables the permanent display of alarm status on
the keypad unit, even if the system is set.
display time a maximum of 3 minutes if any section is
set (armed)
social alarm enabled
6.32 Annual check notification
6.27 Permanent alarm status display for a set
system
6830
6871
Note: This feature can be used to alert the user that the system is
unintentionally disarmed.
Factory default setting: control enabled
permanent status display enabled
Engineer reset disabled
6.31 Social alarm feature
Notes:
x The PG outputs can only be operated from the keypad if they have
their ON/OFF or pulse functions enabled.
x In addition to controlling the PG outputs using keys ¾8 and ¾9, PG
outputs can also be controlled by access codes, access cards, keyfobs
and detector signals (see 6.40 and 6.41 for details).
x If a PG output should only be operated by a valid access code or card,
then control by ¾8 and ¾9 should be disabled and the codes and
cards should be programmed to control the PG outputs instead (see
6.41).
6831
Engineer reset enabled
6860
Notes:
x To enable the confirmation of intruder alarms (requires two detectors to
be triggered in different zones within a definite period) –– use sequence
321
x Reporting to ARCs must be locked by a digital code.
x The keypad shows the text ““Eng. reset req’’d”” and the system stays
blocked until the ARC code is used via the communicator (see the
communicator manual).
x The feature is supported when a JA-80Y version XA61008 or higher, or
a JA-80V version XA64005 or higher is installed.
6.26 Operating the PG outputs using ¾ 8 and ¾ 9
control enabled
6861
Factory default setting: Engineer reset disabled
Factory default setting: react with a tamper alarm to all triggered tamper
sensors
6821
disabled
This is a special function requested by the DD243:2004 standard. It can
only be used when the alarm system is connected to an alarm-receiving
centre. When a confirmed alarm is activated the control panel is completely
blocked –– it cannot be operated by any user, master or service code until an
engineering reset is performed by an ARC code. This function is required in
some countries only and you can enable it by the following sequence:
This feature allows permanently triggered tamper sensors to be ignored:
6810
6850
6.30 Engineer reset
6.25 Pulse reaction of tamper sensors
ignore permanently triggered tamper sensors, i.e. only
react to an increase in the number of triggered tamper
sensors.
enabled
Factory default setting: recording enabled
Factory default setting: automatic summer time disabled
6811
6851
- 10 -
MKG51101
Notes:
x The system has up to 50 user positions (01 to 50) each capable of
having an access code and an access card assigned to it. If both a
code and a card are assigned to a user then the above sequences
(6950 and 6951) determine whether the user can use a code or a card
or whether he must present both a card and a code to gain control over
the system. If both, a card and a code have to be presented, the order
in which they are done is unimportant.
x If only a card or only a code is assigned to a user, then the above
settings have no effect on users like this.
15th October 2007, the notification is displayed on the 1st October
2008.)
x When this notification is enabled, exiting Service Mode will cause a
notification to occur every twelve months later (the same day and
month).
x If you wish to receive a notification earlier than a year later, change the
internal clock settings to the day and month you prefer before exiting
Service Mode by entering 4hhmmDDMMYY, and then re-adjust the
clock to the correct time in maintenance mode. By tricking the system
this way, you can be notified on the desired date. (see 6.45, entering
and exiting maintenance mode does not change the notification date).
Example: If the date is 10 January 2007 and you wish to receive a
notification 6 months later on 10 July 2007, while still in Service Mode
change the system clock to 10 July 2007, i.e. the day and month of the
desired notification date. Then exit Service Mode and re-adjust the clock to
the correct time in maintenance mode.
Factory default setting: system operated by code or card
6.38 Audible 24 hour intruder alarm
The 24-hour intruder alarm which can be triggered whether the system is
set or not, and can also be silent or audible (IW and EW) according to the
following sequences:
Factory default setting: Annual inspection notification disabled.
6.33 Only single alarm indication
If this function is enabled, then only one intruder alarm may be indicated
at a time. Once an intruder alarm has been triggered and has still not ended,
then no more alarms can be indicated no matter how many more times
triggering occurs. After the alarm has ended, the system is then ready to
indicate the next single intruder alarm.
multiple simultaneous intruder alarms allowed
6911
single intruder alarm allowed only
silent 24-hour intruder alarm
6961
audible 24-hour intruder alarm
Note: If sequence 370 is programmed, the intruder alarm will be silent if any
section in the system is unset.
Factory default setting: audible 24 hour intruder alarm
6.39 Service mode only with service and user code
This is to limit the number of SMS reports sent if hard-wired PIR
detectors capable of being frequently triggered are installed in the system
and the system is not unset (disarmed) properly when someone enters the
building.
6910
6960
To prevent the installer from accessing Service Mode without a user’’s
permission, this feature (if enabled) makes it compulsory for the any user
code (or master code) to be entered directly after entering the service code to
access Service mode. Service Mode can then be entered by keying in Ҙ0
service-code user-code (or master-code).
Note:
x A panic alarm can always be triggered with no limits (except when in
service and maintenance modes),
x Apart from this limitation in the number of simultaneous intruder
alarms, the system also checks to see if any detector is triggering
multiple alarms during the period in which the alarm is set. Any such
undesirable detector is then automatically bypassed every time the
system is set, if it has caused at least four alarms in a row. This
bypass lasts until another event in the system caused either by a
different detector or the user.
6970
Only service code needed.
6971
Service code and user-code (or master-code) needed.
Factory default setting: Only service code needed.
6.40 Device reactions and section assignment
The following sequence programs the characteristics of system devices:
6 1 nn r s
where
nn is the device address from 01 to 50 (01 to 10 …… 30
can either be the hard-wired input terminals in the control
panel or enrolled wireless devices)
r is the reaction index from 0 to 9 –– see fig.
s is the section 1 = A, 2 = B, 3 = C (only has an effect if
partial setting or system splitting is used –– except for PG
output control –– See 6.23)
6.34 Setting (arming) by service code
Normally, it is not allowed to control the system via the service code.
Using this sequence, the installer can be authorized to set and unset the
system by means of a valid service code. This feature should only be enabled
with the explicit approval of the master code holder (system
administrator):
R
6920
disabled
0
6921
enabled
1
Reaction
Disabled
(none)
Natural
Factory default setting: disabled
6.35 Audible panic alarm
If enabled, panic alarms can be indicated by internal and external
warning devices (sirens on IW and EW):
6930
silent panic alarm
6931
audible panic alarm
2
3
4
Panic
Fire
24 hours
5
Next delay
6.36 Higher control-panel receiver-sensitivity
6
Instant
If enabled, this feature can extend the communication range between the
control panel and its wireless devices if there is no radio frequency
interference in the premises.
7
Set
Note: If the sequence 370 is used, panic alarms are silent if any section of
the system is unset.
Factory default setting: silent panic alarm
6940
standard control panel sensitivity
6941
higher control panel sensitivity
Notes
For temporarily disabling codes or devices
including tamper sensors
For detectors = instant, delayed or fire (selectable
in detectors by DIP switch)
For hard-wired inputs of the control panel or
keypad = delayed
Keyfobs
(or ) =set,
(or
) =unset, both
buttons = panic
Code = set/unset (see reaction r=9)
Triggers a panic alarm (audible or silent, see 6.35)
Triggers a fire alarm
Triggers an intruder alarm even if the system is
unset (audible or silent –– see 6.38)
Always provides an exit delay. An entrance delay
is only provided if it is triggered shortly after a
delayed detector.
If activated in a set (armed) section, it triggers an
intruder alarm instantly
Sets its own section of the system
fig. 11 Device reactions
Note: The sensitivity of the control panel receiver should only be increased if
there is no RF interference as the radio range would only be reduced if
interference was present.
Factory default setting: standard control panel sensitivity
6.37 Access by code plus card
This feature increases security against unauthorised setting/unsetting
(arming/disarming):
6950
system access by code or card
6951
system only accessed by code and card if both are
assigned to the same user position
JA-83K control panel installation manual
- 11 -
MKG51101
where
fig. 11 continues
R
Reaction
Notes
8
PG
output control
The value of the s parameter determines which
PG output is controlled: s= 1= PGX, s=2=PGY or
s=3=PGX & PGY. To use this function the PG
output involved has to be programmed to the
ON/OFF or pulse functions.
If the reaction is triggered by:
a code (card) –– the PG output changes its state
(ON,OFF,ON,OFF…………) or a pulsed switching
event is generated after a valid code or card is
used. If a code or card is programmed this way, it
cannot be used for setting (arming) control. One or
more (up to 50) different codes can be
programmed to operate PG outputs, if desired.
a keyfob –– one button in a pair is used to switch a
PG output ON, the second one to switch it off or
each of them generates a pulsed switching event.
If a keyfob is programmed this way, it cannot be
used for setting (arming) control. Each PG output
can have as many associated keyfobs as desired.
a detector –– the PG output copies the status of
the detector or it generates a pulsed switching
event when the detector is triggered. Only one
detector should be programmed to a PG output
ON/OFF reaction and should not be combined with
keyfob or keypad control as the detector repeats
its status every 9 minutes and it would override the
signal from the keypad or keyfob.
Toggles the system status
SET,UNSET,SET,UNSET etc
9
Set/unset
Guidance on assigning codes or cards to sections:
x
x
x
x
x
x
6.42 Enrollment by keying in production codes
3
x
x
x
x
This sequence allows the enrollment of devices by keying in their
production codes:
Assigning keyfobs with natural reactions
to sections
Unsplit
Partial setting
Split system
button
system
set
set A
set A
(or )
2
(or
)
unset
(or
)
set
set A
set B
(or
)
unset
set AB
unset B
(or
)
set
set ABC
set ABC
)
unset
unset ABC
unset ABC
(or
set AB
unset A
6 0 nn xx..x
where:
6.43 Automatic setting / unsetting schedule
This can be used to program an automatic sequence of daily
setting/unsetting events. Up to 10 daily events can be programmed. Events
will occur every day of the week:
6 4 n a hh mm
where:
n is the event number from 0 to 9
a is the type of event from 0 to 6 (see the following table)
hh hours (time of event)
mm minutes (time of event)
Erase the automatic schedule setting by: 64 n 0
a
Guidance on programming reactions:
x
The reaction selected in a detector by its internal DIP switches is only
obeyed by the control panel if the reaction programmed in the
detector’’s address is a natural one (r=1).
x
Keyfobs always enroll a pair of buttons (
+ ) or ( + ). The
natural reaction of such a pair of buttons is shown in the above table. If
any other reaction is selected for a keyfob, this reaction will only apply
+
or
or
0
1
2
3
4
5
6
, or to double buttons
unsplit system
No event
Set all (ABC)
Unset all (ABC) *
Set A**
Set AB**
Unset all (ABC) *
Unset all (ABC) *
split system
No event
Set all (ABC)
Unset all (ABC)
Set A
Set B
Unset A
Unset B
fig. 13 Actions
* the same event in an unsplit system
** only possible if partial setting (arming) is programmed (see 6.23)
Notes:
x The automatic setting/unsetting event schedule can also be
programmed in maintenance mode.
x It is not possible to use the same instant of time for two events. Use
t+1 time for the second event.
+
. The
( ) button has no effect (can still be used for
controlling UC/AC receivers).
Factory default setting: All addresses from 01 to 50 have a natural reaction
(r=1) and are assigned to section C (s=3).
6.41 Code/card reactions and section assignment
The following sequence programs the features of access codes or cards:
Factory default setting: All automatic events switched off.
6 2 nn r s
JA-83K control panel installation manual
nn is the address of the device from 01 to 50
xx...x is the production code of the device (the last eight
digits of the bar code, see the label on the PCB inside the
device)
Notes:
x If the address nn is already occupied, the current device will be erased,
and the new device will then be enrolled instead.
x If a device with production code xx……x has already been enrolled to
another address in the past, and if the device is now enrolled to a new
address, then it will be moved to the new address, releasing the old
address.
x If you enter nn = 01 to 10 (……30), the device will enroll instead of the
corresponding hard-wired input in the control panel (the terminal will be
disabled).
x If eight zeros are entered as a production code, the device already
assigned to the address nn will be erased
fig. 12 Buttons to section
If partial setting is programmed then detectors can be assigned to
sections: A (s=1), B (s=2) a C (s=3). The three possible setting
(arming) options are as follows:
A (using the A key on the keypad, e.g. setting (arming) the garage in
the afternoon),
AB (using the B key on the keypad, e.g. setting (arming) the garage
and the ground floor during the night)
ABC (using the ABC key on the keypad, e.g. to set the entire system
when leaving the house).
In a split system, detectors can be assigned to sections: A (s=1), B
(s=2) a C (s=3). Sections A and B can be set independently and
section C is a common section which only sets when A and B are set.
Partially setting and splitting a system only have an effect on intruder
detectors with instant, delayed or next-delayed reactions. Detectors
with fire, tamper, panic, and 24-hour reactions are continuously ready
to trigger an alarm no matter which section they are assigned to or
whether their section is set or not.
If the selected reaction is PG output control then the s parameter
defines which PG output is controlled: s=1 PGX, s=2 PGY, s=3 PGX
and PGY.
to the first button of the pair, i.e.
If a code/card has a natural reaction, i.e. r=1, then its reaction is set,
unset, set etc. (the same as reaction r=9).
A code/card can also have an alarm reaction designated to it, similar to
detectors.
A code/card set to a Next Delay reaction allows you to set the system
anytime, but unsetting is only possible after an alarm. This feature is
designed for security services staff.
Factory default setting: all codes/cards from 01 to 50 have a natural
reaction (set/unset) and are assigned to section C.
Guidance on assignment to sections:
1
In partial setting (arming) mode assigning codes or cards to sections
has no effect (except for the PG output control reaction). If anything in
the system is set and a card/code is used, the system will then be
unset, and if all sections are unset then the whole system will be set by
a card/code. Partial setting keys A and B on the keypad can be
programmed to be followed by a valid access code if required (see
6.12).
For a split system, a code assigned to section:
A controls section A
B controls section B
C controls section A, B and C.
If the system is not split then the assignment of codes/cards to sections
has no effect, but the s parameter must be entered in the programming
section. Enter s=3 if splitting is not desired.
Guidance on code/card reactions:
fig. 11 Device reactions
s
nn is the user position from 01 to 50
r is the reaction index from 0 to 9 –– see fig.
s is the section 1 = A, 2 = B, 3 = C (only has an effect in a
split system –– except for the PG output control reaction ––
see 6.26).
- 12 -
MKG51101
Factory default setting: in addresses 01 to 50 there is the text “Device”.
Other default text: “Control panel”, “Keypad”, “Communicator”, “Master code”,
users 01 to 50 “Code”,”ARC Code”, “Service code”, “PGX”, “PGY” and
“OASiS JA-80”.
6.44 Changing the service code.
The service code is used to switch into Service mode. To change the
service code, enter:
5 NC NC
where:
6.48 Recommended settings
NC new code (4 digits), the new code has to be entered
twice.
Recommended settings for the following parameters according to
TS 50131-7 and EN 50131-3 are:
Example: The code 1276 can be programmed by entering: 5 1276 1276
Factory default setting: 8080
6.45 Go to maintenance mode
By entering 292 while in Service Mode the system switches to
maintenance mode. In maintenance mode it is possible to program the
devices to be bypassed and to adjust the control panel internal clock (see
7.4).
261
radio interference indication (see 6.6)
271
radio communications supervision (see 6.7)
300
setting (arming) without an access code disabled (see 6.12)
391
auto-bypass user approval (see 6.21)
6841
tamper alarm if unset (see 6.28)
6.46 Setting the internal clock
6830
The control panel has a built in real-time clock which is used to timestamp all recorded events in the control panel memory. Adjust the clock after
installation by entering:
keypad displays status for 3 min. if any button pressed
(see 6.27)
6920
not allowed to control the system via the service code
(see 6.34)
6951
system only accessed by code and card (see 6.37)
6971
service mode only with service and user (master) code
(see 6.39)
4 hh mm DD MM YY
where:
hh is the time in hours (00 to 23)
mm is the time in minutes (00 to 59)
DD is the day (01 to 31)
MM is the month (01 to 12)
YY is the year (00 to 99)
Note: The internal clock can also be adjusted in maintenance mode.
7
Example: On 30 June 2012 at 17:15 enter: 4 17 15 30 06 12
After the control panel is powered up, the clock is set to 00 00 01 01 00.
7.1
6.47 Editing keypad text
7.1.1
The menu can be entered in Service mode by holding the ? key. Then
the internal keypad menu will be displayed. Using the arrows or keys 1
and 7 you can scroll through the menu to Edit text. Press Editing
mode and the name of the device enrolled to address 01 is then
displayed with a flashing cursor on the first text character.
x Key functions:
1 and 7
text scrolling (see table)
3 and 9
character-selection (A,B,C,D.......8,9,0)
4 and 6
cursor control (left/right)
2
delete selected character
8
space
exit editing (& save changes)
List of editable text:
x
01: to 50: Devices
Control panel
Keypad
Communicator
Master code
01: to 50: Code
ARC Code
Service code
PGX and PGY
OASiS JA-80
Keypad indicators:
ABC setting (arming) status of sections –– if all sections are set then all
these indicators (A B & C) are lit.
Flashing
Constantly lit
= alarm, with the simultaneous display of
alarm details on the LCD, e.g.:
Alarm
03: Kitchen
= fault –– details are displayed by pressing
the ““?”” key
Power. Constantly lit = mains and back-up battery ok.
Flashing = power supply problem, control panel powered either
by the mains or by back-up battery only.
description
7.1.2
Names of devices in addresses 01 to 50
Name of control panel (e.g. displayed if its cover is
opened)
Name of hard-wired keypad
Name of the communicator in the control panel
Name of the master code
Names of user codes
Names of ARC code
Name of the service code
Names of programmable outputs
The default text displayed in operating mode if no
other text needs to be displayed. If erased then
nothing will be displayed.
LCD display
The 1st line displays the status: triggered detector, Service mode etc.
In standby mode, it shows the text ““JABLOTRON””. A picture of size 128x48
pixels can be loaded into the keypad . (Olink 1.4 or a higher version is
needed).
The 2nd line displays the name of a device (e.g. 01: Main Door etc.). In
standby mode, it shows the text ““OASiS JA-80”” (editable, see 6.47). The text
can be edited, see 6.47.
Displaying the status of detectors and programmable outputs:
Details on permanently triggered detectors (e.g. open windows) and the
status of the PGX and PGY outputs can be displayed by pressing the ? key.
7.1.3
fig. 14 System texts
Keypad display sleep-mode
In operating mode, the wireless keypad unit displays the system status
for 20 seconds (if battery-powered) after the last interaction with a user, and
then goes into sleep mode. Pressing any key, triggering the keypad input,
pressing or opening the keypad’’s flip cover re-activates the display.
Notes:
x Beetween capital or small letters can switch by key .
x The length of text is limited to the length of the display.
x The text is only stored in the keypad used for editing (different keypads
in the system can show different text if desired).
x Text is stored in the non-volatile memory of keypads, so power
disconnection will not erase any stored text.
x Convenient text editing is possible using a PC running OLink software.
(texts can be edited in the Text synchronization \ Comparison window
(F11))
x Besides device names, keypads also use so-called internal text such
as ““service””, ““maintenance mode”” etc, and this text can also be edited
via OLink software by selecting ““Central”” on the menu and then ““Text
synchronization \ Comparison”” or F11.
x After editing keypad text using OLink software, all keypads (including
wireless ones) must be connected to the digital bus to save the
changes to the keypad units by clicking on the OK button in the
software. (It is recommended to connect JA-81F wireless keypads to
the bus in order to save the text into them as well)
JA-83K control panel installation manual
The system keypad
Indoor keypads model JA-81F (wireless) or JA-81E (wired) can be used
to operate and program the system. Both keypad types provide the same
functionality:
The names of devices and programmable outputs as displayed on the
keypad unit can be edited as follows:
text
Operating the system
The OASiS system can be operated locally using a keypad or a keyfob
and it can also be operated remotely by mobile phone or the Internet (if
equipped with a suitable communicator).
7.1.4
0––9
#
ABC
A
B
?
Keys
digital code entry
function sequences
escape
hot key for setting the entire system (all sections A, B & C)
hot key for setting section A (e.g. afternoon partial setting of
the garage)
in an unsplit system: hot key for setting sections A and B
(e.g. partial night-setting of the garage and the ground floor).
in a split system: hot key for setting section B (C is only set
if both sections A and B are set)
Display of triggered detectors (e.g. open windows), fault
details and PGX / PGY status.
Note: The A and B keys only have a function if partial setting or splitting are
enabled.
- 13 -
MKG51101
7.1.5
7.4
Functions beginning with the ¾key
The following functions are available to the user via the keypad:
1
2
3
4
5
6
7
8
9
0
sets the entire system (the same as key ABC)*
sets section A (the same as key A)*
sets A and B, or just B (the same as key B)*
event memory recall (key 4 scrolls backwards) –– the control
panel records max. 255 of the latest events
new Master Code/Card (5 MC NC NC)
access code/card programming (6 MC nn NC)
for operation while under duress (should be entered before
the access code to secretly signal distress)
PGX control (ON/OFF = 81/80 or enter 8 to trigger if a
pulsed switching reaction is programmed)*
PGY control (ON/OFF = 91/90 or enter 9 to trigger if a
pulsed switching reaction is programmed)*
To enter Service Mode (0 SC –– factory default 8080) or to
enter maintenance mode (0 MC –– factory default 1234)
0 MC
where
x
x
x
x
x
x
x
7.4.1
x
x
x
x
x
x
x
x
x
7.3
Programming access codes and cards
Sequences for programming access codes and cards are described in
the fig. 19. They should only be programmed in the DISARMED state.
The control panel has 1 service, 1 master and 50 user codes.
Only a numerical code can be used as a service code (factory
default 8080) –– see the control panel programming section.
The master code can be a numerical code (factory default 1234) or an
access card. Using this master code/card, other users’’ codes and
cards can be programmed or erased. The master code/card is usually
used by the system administrator.
Each user from 01 to 50 can have a numerical code, or a card, or both
(factory default: all user codes and cards from 01 to 50 are erased).
If a user has both a code and a card, then it is possible to program
whether both a code and card must be presented to the system for
system access, or whether only one of them is required (see 6.37).
The system does not allow the same code or card to be
programmed to multiple positions. (if it is desired to move a
code/card to another position, the card/code has to be erased from its
current position first).
It is possible to display which code/card positions are already occupied
in maintenance mode (see 7.4.1).
The most convenient way to program codes and cards is by using a PC
running OLink software.
The control panel allows a maximum of 10 unsuccessful attempts in a
row to enter a valid code or card. If exceeded, a tamper alarm starts.
1.
The control panel must be in maintenance mode –– if not then enter 0
master code or card (factory default: 1234) while the system is totally
unset.
2.
Press key 5 (the display indicates ““Codes 01: Code””),
3.
Using the arrow keys all user positions (01 to 50) can be scrolled
through, with the A indicator showing whether a code is
programmed or not, and the B indicator showing whether a card is
programmed or not.
4.
To exit this code/card display mode press the # key.
5.
To exit maintenance mode press the # key.
The most convenient way to administer codes is by using a PC running
OLink software (in the Codes window).
7.4.2
1.
2.
3.
4.
5.
6.
7.
Press key ABC, A or B,
Enter a code (or present a card)
If the system is partially set (section A is set), and you wish to extend
the proportion of the system which is set, press the B or ABC key. If
you extend the proportion of the system which is set, then all delayed
or next-delayed detectors in the section(s) going to be set and in the
section currently set, will provide an exit delay which means that if a
user has his system partially set (e.g. night setting) and wishes to exit
the house by walking through the sections that are still set, he will not
need to unset the whole system before leaving the house and setting
the whole system. The route used by the user to leave the house must
be covered by delayed or next-delayed detectors to make this possible
and must be considered at the system design stage.
7.4.3
1.
If the car has a built-in car alarm then an RC-85 transmitter unit can be
connected to the car alarm output and the transmitter unit can be
enrolled to a free address in the OASiS control panel. (See the RC-85
manual) An alarm triggered in the car can be indicated as an OASiS
panic alarm (or a 24-hour reaction can be set), regardless of whether
the system is set or not. Note: if the car alarm confirms setting (arming)
by siren chirps appearing on the alarm output, then these should be
disabled to avoid false alarms.
2.
If the car has no built-in car alarm then JA-85P or JA-85B
detectors can be installed in the car. The car detectors can be
assigned to their own dedicated section in the system, e.g. a split
system where section A could be for the car detectors, and section B
for the house detectors, with no detectors assigned to section C, and
the entry codes/cards assigned to section C to access the whole
system. So when the user enters the house he can set section A to
protect the car, and unset section B to be able to enter the house.
Radio communication supervision should be disabled for the car
detectors to avoid fault notifications when the car is driven away from
the house (see the detector manual).
Enter a valid access code (or present a card).
Setting and unsetting the alarm system is only possible using a JA-81F
or JA-81E indoor keypad or a keyfob.
Entering a valid access code or presenting a valid card to the outdoor
keypad or card reader will always open the electric door lock.
If the system is set, and the door is opened via the outdoor keypad or
reader, an entrance delay will begin. During this delay the system has
to be unset using an indoor keypad unit (or keyfob).
JA-83K control panel installation manual
Protecting a car near the system
The OASiS system can also protect a car (cars) parked in the proximity
of the house.
If the system is equipped with a JA-80H outdoor keypad or a JA-80N
external card reader then the outdoor device could either work the same way
as an indoor keypad unit or it could be programmed only to operate an
electric door lock (known as an outdoor-bypass feature), i.e. an indoor
keypad would then be used to control the alarm system. If the outdoorbypass feature is enabled then:
x
3 to permanently bypass a device (the
indicator will light
continuously)
To cancel the bypassing of a device use the same button as was
originally used for bypassing (2 or 3). Using key 4 will cancel all device
bypasses in the system.
All the desired bypasses can be programmed by repeating step 3 and 4.
Press the # key to exit the bypass menu. Pressing # again exits
maintenance mode.
If a system with bypasses programmed is being set, then bypass text will
be displayed on the keypad unit.
Operating the system from an outdoor keypad:
x
The control panel must be in maintenance mode –– if it is not, then enter
0 master code (factory default: 1234) while the system is totally unset.
Press key 1, to display the control panel’’s bypass menu.
Using the 1 and 7 keys you can scroll through all the devices
able to trigger alarms.
To bypass a device use key:
2 to bypass the device for one setting/unsetting cycle (the
indicator will start flashing)
Setting and unsetting (arming/disarming) the
system
To unset the system from a keypad:
x
Bypassing devices
In maintenance mode it is possible to bypass (disable) individual system
devices (permanently or only for one setting/unsetting cycle):
To set the system from a keypad:
x
Displaying which user/card positions are occupied
To change access codes and cards use sequence 6 MC nn NC (see fig.
19). (the system must be disarmed).
The system can be set and unset from a keypad, a keyfob or remotely by
phone or the Internet or from a PC running OLink software.
x
x
x
Test devices (an alarm cannot be triggered).
Display which code/card positions are currently occupied.
Bypass individual devices (for one setting/unsetting cycle or
indefinitely) - see 7.4.2.
Program the real-time system clock –– see 6.46.
Program the automatic setting/unsetting schedule –– see 6.43.
Program telephone numbers for event reports to the end user (see
6.5).
Exit maintenance mode by pressing the # key.
Which positions in the range 01 to 50 are occupied by codes or cards can
be displayed in maintenance mode as follows:
The system can be controlled by 4-digit codes and by access cards, of
the types PC-01 and PC-02 (EM UNIQUE 125kHz standard).
x
MC = master code (card) –– factory default 1234
In maintenance mode it is possible to:
The functions allow the system to be operated from a mobile phone
keypad (if the control panel is equipped with the relevant communicator).
7.2
Maintenance Mode
Maintenance mode can be entered using a master code or master card
by entering:
- 14 -
MKG51101
8
Operating/programming the system by PC
9
The OASiS system can be operated and programmed locally using a PC
running OLink software. To connect the control panel to the PC use a
JA-80T, JA-82T interface or a JA80-BT wireless Bluetooth interface.
Basic guidance for installers
x
x
OLink software can be used by installers and end users. The software
only allows access to features allowed by the access code (service or user).
If the control panel is equipped with a suitable communicator such as the
JA-80Y (GSM/GPRS) or JA-80V (LAN/telephone line) then the system can
also be accessed from a PC connected to the Internet. For this remote
access it is first necessary to register at www.GSMLink.cz or directly by Olink
v. 2,0 and higher (JA-82Y only).
x
x
x
x
Create an installation plan that sufficiently covers the building to be
protected.
If the customer requests changes to the suggested configuration in
order to reduce the price, especially reducing the number of detectors,
ask for his request to be given to you in writing. (You will avoid future
disputes if the insufficient protection is overcome by intruders.)
Perform the installation in a very professional and conscientious
manner and always tidy up the site afterwards.
It is very important to teach the end user how to use and test the
system and to check his level of understanding.
Get the customer to sign a written statement that the system was
installed according to the customer’’s specifications and that the
customer understands how to operate the system.
Explain the importance of the annual technical inspection of the system
to the customer and offer him this service. For more details see the
relevant EN standards.
For further information see EN 50131-1 and other standards.
10 Trouble-shooting
Problem
The control panel is not in service
mode after being powered up.
It is impossible to enroll a wireless
device to the control panel.
The keypad unit indicates a fault
A motion detector triggers false alarms
for no apparent reason.
The wireless keypad does not indicate
entrance delays by beeping.
Possible causes
Solutions
The control panel does not have factory-default settings.
Reset the control panel.
The device’’s location is unsuitable, the control panel antenna is
disconnected, the device’’s battery was incorrectly installed, the
control panel is not in enrollment mode, the device is too near to
the control panel (it should be at least 2 meters away).
Press the ? key to see the cause.
Animals are moving in the protected area (mice etc), sudden
changes in temperature, significant air movements, movement of
objects having a temperature close to 37°C (e.g. curtains moving
above a radiator)
If the keypad is only battery-powered, then it turns off 20
seconds after the last time a key was pressed. To indicate
entrance delays, first wake it up.
Check and fix the mentioned problems.
React according to the cause displayed.
Change the location of the detector, select a higher
immunity in the detector, use an optional pet lens in
the detector, program alarms confirmed by two
detectors in the control panel.
Install an ordinary magnetic sensor to the entrance
door, wiring it to the keypad input so that opening
the door wakes up the keypad and reports to the
control panel. Alternatively, power the keypad with
an AC adaptor to prevent sleep mode or install an
indoor wireless siren type JA-80L to generate
entrance delay beeps.
fig. 15 Trouble-shooting
JA-83K control panel installation manual
- 15 -
MKG51101
11 Control panel technical specifications
297
External power source 230 V / 50 Hz, max 0.1 A, CLASS PROTECTION II
Power supply
type A (EN 50131-6)
Backup-battery
12 V, 7 to 18 Ah,
typical battery lifetime
approx. 5 years
Maximum recharge time
72 hours
Backup power output (+U terminal)
maximum continuous load 1.1 A
(when an 18 Ah backup battery is used)
Backup power output (+L terminal)
maximum continuous load 0.2 A
power outputs +U +L have electronic fuse
Number of wireless device addresses
50 (requires a JA-82R module)
Number of hard-wired inputs
10 (up to 30 if two JA-82C are plugged in)
double balanced inputs, with triggering and tamper functions
(each wireless detector blocks the hard-wired input to which it is assigned)
External warning output EW*
switching to GND, max. 0.5A
Internal warning output IW*
switching to GND, max. 0.5A
Programmable outputs*
PGX, PGY max. 0.1 A, switching to GND
Event memory
255 latest events, including date and time stamping
Intruder alarm signal or message
after 1 or 2 events (adjustable)
Tamper signal or message
after 1 event
Wrong authorisation code alarm signal or message
after 10 events
Fault signal or message
after 1 event
Security grade
2 according to EN 50131-1, EN 50131-3,
EN 50131-6, EN 50131-5-3
Environmental class
II. indoor-general
(-10 to +40°C) compliant with EN 50131-1
EMC
EN 50130-4, EN 55022
Safety
EN 60950-1
JA-82R radio module
Communications frequency (JA-82R)
868 MHz ISM band
Can be operated according to
ERC REC 7003
Radio emissions
ETSI EN 300220
* these signals are also transmitted wirelessly to wireless sirens and AC
and UC receiver modules.
105
247
25
357
Jablotron Alarms a.s. hereby declares that the JA-83K ““OASiS““
control panel is in compliance with the essential requirements
and other relevant provisions of Directive 204/108/EC,
1999/5/EC 2006/95/EC. The original of the conformity
assessment can be found on the web site www.jablotron.com,
Technical Support section.
270
fig. 16 Control panel box dimensions
Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer or
directly to the manufacturer after use.
RESET
1
11
T1,6A
250V
ON
OFF
2
I-LINE
E-LINE
TMP2
3
4
TMP1
10
9
5
6
7
8
fig. 17 Control panel box layout
Description: 1. switch mode power supply module; 2. power supply terminal; 3. power supply fuse; 4. back-up battery space; 5; band securing the
back-up battery in place; 6. possible hole for cables; 7. external bus connector (OLink; service keyboard); 8. communicator or output module
space; 9. box cover tamper contact; 10. control panel main board (more detail see fig. 1); 11. radio module antenna (if installed)
JA-83K control panel installation manual
- 16 -
MKG51101
12 Control panel programming sequences
Function
Entering enrollment mode
One wireless device (detector, keypad, key
fob, siren or sub control panel) can be enrolled
to each address from 01 to 50.
The system offers vacant addresses one by
one, if all addresses are occupied no devices
can be enrolled.
A device enrolled to address 01 to 30
disables the corresponding hard-wired input
01 to 30.
In addition to enrollment mode, devices can
also be enrolled by keying in their production
codes (see 6.42).
Sequence
Options
Factory
default
Setting to
comply with
EN-50131-1
x devices enroll by connecting
their power (battery) except
keyfobs which enroll by
pressing & holding a pair of
their buttons
x an occupied address is
indicated by the A indicator
being lit
x enrolling a device to a new
address will move it there
Keys:
1 and
1
7 = address
scrolling
holding 2 = erases the
displayed
address
holding 4 = erases all
addresses
#
= exiting
enrollment
mode
nothing
Exit delay time
20x
x = 1 to 9 (x10 s =10 to 90 s)
30s
Entrance delay time
21x
x = 1 to 9 (x 5 s = 5 to 45 s)
20s
Alarm duration time
22x
x = 1 to 8 (min.), 9=15min
x in an unsplit system:
PGX function
0
PGY function
1
23x
24x
2
3
4
5
6
7
8
whole system set (ABC)
= PG on
any system part set = PG
on
AB set (not C) = PG on
Fire alarm = PG on
Panic alarm = PG on
Any alarm = PG on
(excluding Panic)
AC dropout = PG on
PG on/off (by 80 /81 for
PGX and 90/91 for
PGY)
Single 2 s pulse
(keys 8=X, 9=Y)
if a final door detector is used,
then x is multiplied by 30s
instead (i.e. from 30 to 270s)
4 min.
0=10s (for testing)
7
on/off
80/81)
x in a split system
0
1
2
3
4
5
1
any
system
part set
6
7
8
Enablement of telephone number changes
in maintenance mode
25x
251 = YES
250 = NO
NO
Radio interference indication
26x
27x
28x
261 = YES
260 = NO
NO
YES
271 = YES
270 = NO
NO
YES
281 = YES
280 = NO
Radio communication supervision
RESET enabled
Master control panel enrollment to a sub
control panel for setting (arming) control
291
Returns master code to 1234
298
Activates measurement
Enrolling the control panel to UC, AC or a
sub control panel
299
The sequence triggers
enrollment.
Setting (arming) without an access code
30x
301 = YES
300 = NO
YES
31x
311 = YES
310 = NO
YES
Triggered detector indication
by text on the keypad display
see communicator
30 s or longer
YES
The sequence triggers
enrollment.
Measuring signal strength
alarm A = PG on
alarm B = PG on
entrance delay A = = PG on
entrance delay B = PG on
A set = X on, B set = Y on
A panic = X on,
B panic = Y on
Fire = X on,
AC dropout = Y on.
PG on/off (by 80 / 81for
PGX and 90 / 91 for PGY)
Single 2 s pulse
(keys 8=X, 9=Y)
(Un)setting the master
control panel will (un)set the
sub control panel.
The sub control panel must
be in enrollment mode.
290
Master code reset
Notes
It has no effect on other
codes and it is recorded in
the control panel memory
arrow keys scroll
addresses,
# halts measurement.
see 6.9
NO
by keying: A, B, ABC, 1, 2,
3,4
allows the display of open
windows & doors,
to view details press ?
Confirmation of intruder alarms
In this mode, the triggering of an intruder
detector in a set (armed) section will only be
recorded to the memory as an unconfirmed
alarm and if then followed by the activation of
any other intruder detector within 40 minutes,
an alarm will be triggered. If the first triggered
detector has a DEL reaction and it is not
confirmed by any other detector, it will not
trigger an alarm after the entrance delay has
expired.
32x
321 = YES
320 = NO
NO
Exit delay beeps
33x
331 = YES
330 = NO
YES
The last 5 s faster
Exit delay beeps while partially arming
34x
341 = YES
340 = NO
NO
The last 5 s faster
(linked to 33x setting)
An alarm can be confirmed by
any other intruder detector in any
section which is set (armed).
fig. 18 Summary of the programming sequences
JA-83K control panel installation manual
- 17 -
MKG51101
fig. 18 continues
Function
Sequence
Options
Factory
default
Setting to
comply with
EN-50131-1
Notes
Entrance delay beeps
35x
351 = YES
350 = NO
YES
Setting (arming) confirmation by wired-siren
chirp
36x
361 = YES
360 = NO
NO
IW terminal only
Siren always sounds during audible alarms
37x
371 = YES
370 = NO
YES
NO = siren only sounds if the
system is completely set (armed)
Wireless-siren alarms enabled (IW & EW)
38x
381 = YES
380 = NO
YES
NO = siren disabled
Auto-bypass user approval via the key
If a detector is active during setting (arming),
the system will automatically bypass it (them),
immediately (390), or after keying in (391)
39x
390 = NO
NO
Final-door detectors
If this function is used, then Exit & Entrance
delay settings are multiplied by 30s. A triggered
final-door detector extends the exit delay, detriggering of the last final-door detector ends
the exit delay.
65x
Partial setting (arming) or system splitting
66x
Automatic Summer Time
(Daylight Saving Time)
680x
Pulse reaction of tamper sensors
Tamper alarm in response to an increase in the
number of triggered tamper sensors
681x
391 = YES
0
1
2
none
detectors 01 to 05,
detectors 46 to 50
0
1
2
unsplit system
partial setting (A, AB, ABC)
split system A, B &
common section C (set if A
& B are set)
6801 = YES
6800 = NO
6811 ignore permanently
triggered tamper sensors,
i.e. only react to an
increase in the number of
triggered tamper sensors
6810 react with a tamper alarm
to all triggered tamper
sensors
YES
to confirm auto-bypass while
exiting Service mode press #
twice
If multiple F. door detectors are
used, then triggered state=any of
them, non triggered state=all of
them
x=0
0
Changes internal clock + 1h on
Apr.1 & -1h on Nov.1
NO
Suppresses the indication of
permanently triggered tamper
sensors
X=0
Operating the PG outputs using 8 and 9
682x
6821 = YES
6820 = NO
YES
if yes then arrow keys can also
operate PGX
Permanent alarm status display for a set
system
683x
6831 = YES
6830 = NO
NO
suppresses the 3min. display
timeout
Tamper alarm if unset (disarmed)
684x
685x
686x
687x
6841 = YES
6840 = NO
NO
6851 = YES
6850 = NO
YES
6861 = YES
6860 = N0
NO
6871 = YES
6870 = N0
NO
Recording PG output activation to memory
Engineer reset
Social alarm
Annual check requirement display
If enabled then 12 months after exiting Service
Mode an annual technical check request is
displayed on the keypad unit (mobile phone &
ARC notification optional)
690x
6901 = YES
6900 = NO
NO
Only single alarm indication
If enabled then another intruder alarm can not
be triggered during an intruder alarm currently
in progress.
691x
6911 = YES
6910 = NO
NO
Setting (arming) by service code
692x
6921 = YES
6920 = NO
NO
Audible panic alarm
693x
6931 = YES
6930 = NO
NO
Higher control-panel receiver-sensitivity
Extends the communication range if there is no
RF interference
694x
6940 = normal
Access by Code plus Card
If enabled and there is a code and card
assigned to the same user, then both of them
must be presented for setting (arming) control
(in any order).
695x
6951 = Code+Card
Audible 24h intruder alarm
696x
6961 = YES
6960 = NO
YES
Service mode only with
service + user (master) code
697x
6971 = YES
6970 = NO
NO
JA-83K control panel installation manual
YES
Another time period can be
selected by changing the system
date before exiting service mode
YES
6911 = no other alarms are
reported during an intruder alarm
only with the master code
holder’’s approval
normal
6941 = higher
6950 = Code or Card
- 18 -
code or
card
YES
0= silent 24h intruder alarm
YES
MKG51101
fig. 18 continues
Function
Sequence
Device reactions and section assignment
0
x A detector’’s natural reaction can be INS,
DEL or Fire (selectable in the detector)
x The natural reaction of Control panel &
Keypad wired inputs is DEL
(or
1
) = SET
(arm), (or ) = UNSET (disarm) and both
simultaneously = Panic. If a reaction from 2 to
8 is selected (see opposite), only the key
(or
) and double buttons
+
(
+
)
will have it. The ( ) button has no effect
(can still be used for controlling UC/AC
receivers).
x Assignment to sections will only have an
effect on partial arming or if the system is
split (except PG output control)
x For partial arming, a pair of keyfob
buttons assigned to section:
A has the effect:
(or ) = SET A,
B has the effect:
(or
) = SET AB
(or ) = SET A,
C has the effect:
(or
) = SET AB
(or
) = SET ABC,
(or
Factory
default
Setting to
comply with
EN-50131-1
61
nn r s
2
3
4
5
6
7
8
9
disabled (incl. tamper
sensor)
Natural –– this means:
for detectors = selected by
DIP switch in the detector,
for wired inputs = DELay,
for Codes (cards) =
SET/UNSET
Panic
Fire
24 hours
Next DELay
INStant
SET (arm)
PG control (s: 1=PGX,
2=PGY,3=PGX+PGY)
SET/UNSET (toggle)
s = section 1=A, 2=B, 3=C has to be entered even if the
system is not split and setting
(arming)has no meaning.
Notes
When the detector is disabled
(r=0), the tamper sensor is not
triggered,
Natural reaction of control panel
wired inputs (or IN keypad input)
is delayed (DEL)
nn = address 01 to 50
r = reaction:
(detectors, key fobs, control panel and
keypad inputs)
Keyfob natural reactions:
Options
all
Natural
in C
) = UNSET ABC
x In a split system, a keyfob button pair
assigned to section: A=SET/UNSET A, B
=SET/UNSET B, C =SET/UNSET ABC
Code (card) reactions and section
assignment
x A code (card) may have the same kind of
reaction as devices
x Assignment of the code to sections is
useful for split systems only. In a split
system, a code (card) assigned to C will
SET/UNSET all ABC sections.
62
nn r s
60 nn nn = address 01 to 50, xxxxxxxx = last 8 digits of the
xxxxxx production code (below the bar code on the device)
xx
n = action sequence index
Automatic Daily Setting/Unsetting schedule 64 n a
(0 to 9)
hh mm
(arming/disarming)
Enrollment by keying in production codes
a = action:
0 no action
1 SET ABC
2 UNSET ABC
3 SET A
4 SET B (if unsplit then AB)
5 UNSET A
(if unsplit then ABC)
6 UNSET B
(if unsplit then ABC)
hh - hours, mm - minutes
Changing the service code
Go to maintenance mode
Setting the internal clock
Editing keypad text
x Text for device names, code names and PG
output names are stored in each individual
keypad.
JA-83K control panel installation manual
5 NC
NC
292
NC = new code (4 digits)
switches to maintenance mode
4 hh mm DD MM YY
No action
8080
- 19 -
enter NC twice
00:00
1.1.00
x The menu can be entered in Service
mode by holding the ? key. Then the
internal keypad menu will be displayed.
Using the arrows or keys 1 and 7 you can
scroll through the menu to Edit text.
Press Editing mode and the name of
the device enrolled to address 01 is then
displayed with a flashing cursor on the
first text character.
x Key functions:
1 and 7
text scrolling (see table)
3 and 9
character-selection
(A,B,C,D.......8,9,0)
4 and 6
cursor control (left/right)
2
delete selected character
8
space
exit editing (& save changes)
The scheduled actions will
happen every day
Only capital letters can be entered this way. If
there are multiple keypads, each must be edited
individually this way or all of them can be easily
programmed via OLink software
Device
MKG51101
13 Programming access codes and cards
Code name
Amount
Sequence
Service
1
5 NC NC
Master
1
5 MC NC
NC
User
50
6 MC nn
NC
Notes
x Only programmable in Service Mode.
x NC = new code (must be entered twice) –– a card cannot be used.
x Factory-default service code: 8080
x This code can be changed but not erased.
Example: 5 4567 4567
x Only programmable if the system is totally unset (disarmed)
x MC = master code or card (factory default 1234)
x NC = new code or card entry –– a numerical code has to be entered twice, but a card only
presented once
x Either a code or a card can be programmed as a master code (to have both is impossible).
x The Master Code can be changed but not erased.
x The Master Code’’s reaction is set/unset and it is assigned to all sections.
x To reset the Master Code to the factory default 1234, enter 291 in Service Mode (this will only
affect the Master Code).
x To make handing over the system to the end user easier, we recommend programming the
system card (provided with the control panel) to the master code.
Example: 5 1234 and then presenting the card to the keypad’s RFID reader
x Only programmable if the system is totally unset
x MC = Master Code or card.
x nn = user code or card position from 01 to 50.
x NC = new code or card entry.
x Factory default: all user codes and cards are erased.
x Each user position can have both a card and a code programmed to it (by using the sequence
6 MC nn NC twice)
x Each user code can have its own reaction programmed by an installer in Service Mode, and
with a split system, codes can be assigned to different sections.
Example: 6 1234 12 4345 (code 4345 will be programmed to user position 12)
To erase codes/cards enter:
6 MC nn 0000 erases the code and the card in user position nn.
6 MC 00 UC erases the code UC (or card UC) if programmed to any user position.
6 MC 00 0000 erases all user codes and cards in user positions 01 to 50.
fig. 19 Programming access codes and cards (only in the disarmed state)
JA-83K control panel installation manual
- 20 -
MKG51101
Notes:
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising