Touch Advanced Display
PB_TAD_05 2017
TAD
Touch Advanced Display
Product Bulletin
The Touch Advanced Display (TAD) is a comprehensive series
of freely programmable operator interfaces featuring both
IP and MSTP BACnet® communication and colorful, graphic
displays with touch-screen interface.
TAD Displays feature bright TFT widescreen (16:9) displays
of different sizes 4.3”, 7” and 10” with a fully dimmable LED
backlight and resistive touch interface.
The integrated HTML 5.0 web server grants remote access
whenever the units are connected to an accessible IP network.
TAD Series offers an unprecedented price / performance ratio
to meet challenging applications requirements from offices to
control rooms.
They combines state-of-the-art features and top performance
with an outstanding design.
TAD Series is the ideal choice for User Interface applications
enabling an intuitive and easy interaction with the building
automation controls and equipment.
Features
• Standard BACnet Interfaces (IP / MSTP)
The TAD Series fulfill the standard BACnet Operator Display (B-OD) profile enriching its minimum requirements with
Alarms, Time Schedules and Calendars support, enabling users to take full advantage of the features included in the
connected devices.
• Freely Programmable
The Touch-Screen Tailoring Tool (T3) suite allows customizing the TAD user experience tailoring it to the effective User
requirements. Thanks to the extensive library of symbols and widgets, building data and operations are presented in a
consistent way across different applications.
• Web-Browser Widget
Embedded web browser devices are becoming a common demand in the marketplace. TAD features a web-browser
widget that can be included in the User Interface project empowering the end user to connect to simple web pages
and interact with remote systems.
• Embedded Web-Server
The web server capabilities natively included in TAD devices allow users to remotely connect and interact with
the device thought standard internet browsers. The web pages user interface will reflect the same UX of the local
application therefore maintaining a consistent look across different interfaces.
• Simple and Elegant but Robust Design
Its simplicity of design does not preclude the immediate impression of beauty and the IP66 protection rate for the front
of the unit.
PB_TAD_05 2017
General Features
Freely Programmable with T3
Use Cases
Room User Interface
The Touchscreen Tailoring Tool (T3) is the most complete
software platform that currently exists. Such sophistication
is needed to power and simplify the complex connectivity
both on the software and firmware level.
The T3 graphical interface natively supports vectorial SVG
graphic objects, transparency and alpha blending.
It allows easily creating, installing and maintaining
applications in multiple languages to meet global
requirements.
TAD devices can be easily tailored to interact with
terminal unit or room automation controllers through
BACnet protocol. The 4.3” horizontal mounting perfectly fit
this use.
Equipment / Technical Room User Interface
T3 empower programmers with off-line and on-line
simulation. It features a powerful scripting language for
automating HMI applications.
T3 include a rich gallery of objects and symbols respecting
the company UX feeling.
Colorful touch-screen display
TAD series feature different dimensions of bright TFT
widescreen (16:9) display with a fully dimmable LED
backlight. Thanks to a versatile resistive touchscreen
interface, any panel can be operated with a finger, a
fingernail, a stylus or any other object. This widens even
more the applicability a TAD display can fulfill.
Communication Ports
Thanks to their panel mounting options, TAD devices
easily adopt to interface with HVAC/R equipment or
technical rooms mechanical and electrical apparatus.
Building / Floor User Interface
TAD devices offers multiple communication options.
The Ethernet Port supports applications upload /
download, remote internet connection through embedded
web server and BACnet IP communication.
The DB-9 connector, set as RS485 serial port can run
BACnet MS/TP protocol.
A USB port is also available for application download and
trend-logs buffer upload.
BACnet Communication
BACnet communication is available on both IP and MSTP
level of any TAD communication ports.
The TAD series fulfill the standard BACnet Operator
Display (B-OD) profile enriching its minimum requirements
with Alarms, Time Schedules and Calendars support,
allowing users to take full advantage of the features
included in the connected devices.
The use of touch-screen displays to manage entire floors
and even small buildings is getting a common requirement
in technical specifications. TAD panels perfectly fulfill
these needs.
2
PB_TAD_05 2017
Mounting
TAD series are designed for multiple mounting options
including panel front and flush mounting on a wall thanks
to the BOX0x-01 accessories.
The equipment is not intended for continuous exposure
to direct sunlight. It might accelerate the aging process of
the front panel film.
The front IP66 protection rate and simple thus elegant
design allows TAD series display to be installed in
potentially every environment.
The equipment is not intended for installation in contact
with corrosive chemical compounds. Check the resistance
of the front panel film to a specific compound before
installation.
In order to meet the front panel protection classifications,
proper installation procedure must be followed.
Do not use tools of any kind (screwdrivers, etc.) to
operate the touch screen of the panel.
Dimensions (in mm)
Codes
A
B
D
H
L
T
TAD0471
136
96
29
107
147
5
TAD0701
176
136
29
147
187
5
TAD1001
271
186
29
197
282
6
Connectivity
1
Serial port (5v 100mA max.)
2
Ethernet port
3
USB Port (v.2.0, 5V 500mA max.
4
Power Supply (18-32VDC)
3
PB_TAD_05 2017
Wiring
The TAD units are powered through the following shown connector with 18 to 32 VDC supply voltage. Please check the
technical specifications and make sure the power supply has enough power capacity for the operation of the equipment.
The unit must always be grounded to earth. Grounding helps limit the effects of noise due to electro¬magnetic
interference on the control system. Use terminal 3 on the power supply terminal block earth connection.
Serial Port
The TAD serial port is used to communicate with other field devices.
The serial port standard is software programmable and for BACnet MS/TP the RS485 has to be selected. Make sure you
select the appropriate interface in the T3 programming utility.
1
GND
2
3
CHA-
4
CHB-
5
6
+5V
7
CHB+
8
CHA+
9
Note:
To operate RS485, pins 3-4 and 7-8 must be connected externally.
4
PB_TAD_05 2017
Ordering codes
Codes
Description
TAD0471-0
4.3” Touchscreen Advanced Display
TAD0701-0
7.0” Touchscreen Advanced Display
TAD1001-0
10.0” Touchscreen Advanced Display
Accessories (to be ordered separately)
BOX04-01
Wall mount box for TAD04
BOX07-01
Wall mount box for TAD07
BOX10-01
Wall mount box for TAD10
DEMO-STAND07
Counter display structure for TAD07
Programming Tool License (to be ordered separately from SIS Europe)
TTT0103
Touchscreen Tailoring Tool, 1 Key for 3 activations
TTT0110
Touchscreen Tailoring Tool, 1 Key for 10 activations
TTT0130
Touchscreen Tailoring Tool, 1 Key for 30 activations
5
PB_TAD_05 2017
Technical specification
Product codes
TAD0471-0: 4.3” Freely programmable Touchscreen Advanced Display
TAD0701-0: 7.0” Freely programmable Touchscreen Advanced Display
TAD1001-0: 10.0” Freely programmable Touchscreen Advanced Display
Display
TAD0471 4.3” Widescreen TFT 64k Colors, 480 x 272 and LED backlight
TAD0701 7.0” Widescreen TFT 64k Colors, 800 x 480 and LED backlight
TAD1001 10.1” Widescreen TFT 64k Colors, 1024 x 600 and LED backlight
Brightness
200 cd/m2
Touch-screen
Resistive
Supply voltage
18-32VDC
Real-time clock
Yes
Ethernet Port
1 – Port 0 10/100
Serial Port
1 – RS-232 / RS-422 / RS-485 Software Configurable
USB Port
1 – Host v. 2.0, max. 500 mA
Power consumption
TAD0471 250 mA max @ 24 VDC
TAD0701 300 mA max @ 24 VDC
TAD1001 380 mA max @ 24 VDC
Ambient conditions
Operating 0 ÷ 50°C, 5 ÷ 85% RH Noncondensing
Storage -20 ÷ 70°C, 5 ÷ 85% RH Noncondensing
Dimensions (H x W x D)
TAD0471 107 x 147 x 24 mm
TAD0701 147 x 187 x 24 mm
TAD1001 197 x 282 x 25 mm
Weight
TAD0471 0.4 Kg
TAD0701 0.6 Kg
TAD1001 1.0 Kg
Memory
TAD0471 RAM, 256MB Flash, 2GB
TAD0701 RAM, 256MB Flash, 2GB
TAD1001 RAM, 512MB Flash, 4GB
Protection Class
IP66 Front*, IP20 Back
*IP66 rating is achieved strictly respecting the instructions provided.
Compliance
Johnson Controls declares that these products are in compliance with the essential requirements and
other relevant provisions of the EMC Directive and Low Voltage Directive.
Emission EN 61000-6-4, Immunity EN 61000-6-2 for installation in industrial environments
Emission EN 61000-6-3, Immunity EN 61000-6-1 for installation in residential environments
The performance specifications are nominal and conform to acceptable industry standards. For application at conditions beyond these specifications, consult
the local Johnson Controls office. Johnson Controls shall not be liable for damages resulting from misapplication or misuse of its products.
Building Efficiency
Headquarters: Milwaukee, Wisconsin, USA
Branch Officies: Principal Cities World-wide
Metasys® and Johnson Controls® are registered trademarks of Johnson Controls.
All other marks herein are the marks of their respective owners.
© Copyright 2017 Johnson Controls. All rights reserved. Any unauthorized use or copying is strictly prohibited.
www.johnsoncontrols.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising