SYSC MLX - Acuity Brands

SYSC MLX - Acuity Brands
Catalog Number
Notes
Type
Lighting Control System
FEATURES
Network System Controller
The Synergy MLX system controller adds programming, automation and
networking capabilities to a Synergy system. Capabilities include individual
circuit switching control of lighting functions for a wide variety of applications.
System outputs respond to time-of-day schedules via the internal time
clock. Additionally, inputs can be accepted from external devices such as
simple switches, photocells, occupancy sensors, digital remotes and other
control systems to directly control lighting or override scheduled events. Over
4,000,000 Synergy MLX controllers may be interconnected to provide access
to more than 500,000,000 control outputs from a single switch or schedule.
®
• Supports all Synergy power modules
• Seven-day scheduling with astronomic clock
• Holiday schedule dates
• Load prioritization setup
• Exclusive Script Logic Application Language
• Programmable switches with interpanel linking
• Support for SEQUEL® dimming control stations
• Support for Synergy® digital remote stations
• Timed switch overrides
• Analog source monitoring with multiple set points
• Integral keypad with backlit display
• All programming stored in non-volatile industrial flash memory card
• Automatic system event logging
• Integral lamp burn hours and start counters
•BACnetTM compliant network
• Integral RS232 ports
• Optional PC software
• Modem option (only one per Synergy system required) allows for remote
dial up programming and troubleshooting.
• Optional support for Legacy MiniPac, Sequel, and MaxStar dimmer
cabinets.
• English, Spanish or French operation
• UL and C-UL listed; CEC certified
Warranty
Three-year limited warranty. Complete warranty terms located at:
www.acuitybrands.com/CustomerResources/Terms_and_conditions.aspx
Note: Actual performance may differ as a result of end-user environment
and application.
Specifications subject to change without notice.
SYSC MLX
BACnetTM is an exclusive
trademark of ASHRAE.
Synergy Controller Features
MLS Controller
MLX Controller
48
96 Total w/Secondary Cabinet
48
96 Total w/Secondary Cabinet
40
96 Total w/Secondary Cabinet
40
96 Total w/Secondary Cabinet
Dimmer Capacity
30
60 Total w/Secondary Cabinet
30
60 Total w/Secondary Cabinet
DALI Capacity
(loops)
18
36 Total w/Secondary Cabinet
18
36 Total w/Secondary Cabinet
DMX512 Input
DMX Channel-to-Output Configured
via controller software
System Functions
Relay Capacity (No
Breakers)
Relay Capacity
(With Breakers)
Scheduling
100 schedules/unlimited events
100 schedules/unlimited events
Analog Input
YES
YES
PC Support
YES
YES
Script Logic
YES
YES
Logging
YES
YES
Priority Logic
YES
YES
Network
YES
YES
BACnet®
NO
YES
RS232
YES
YES
YES, optional
Modem
YES, optional
Sequel Stations
YES
YES
Legacy Dimmers
YES, optional
YES, optional
Digital Remotes
YES
YES
ORDERING INFORMATION
Example: SYSC MLX
Choose the boldface catalog nomenclature that best suits your needs and write it on the
appropriate line. Order accessories as separate catalog number.
SYSC
MLX
Series
Controller type
Options
MLX Network system
controller with
programmer
MODEM Modem for remote dial-up access
DMX Dimming interface, required for connection to DMX 512 control signal
LEGACY Allows control of one complete network
(255 dimmers) of Legacy MiniPac,
Sequel, and MaxStar dimmer cabinets.
Replaces master controller on existing
Legacy system.
Controls
©1998-2016 Acuity Brands Lighting, Inc., Rev. 05/12/16
SYSC network requires:
• Ethernet networks - CAT5 cable
• Twisted pair ARCnet network:
Synergy SYA CABLES2 (plenum rated)
OR
Belden 3105A (non plenum rated)
Accessories
Order as a separate item.
SYA SKIT Permits two SYE enclosures to operate with a single MLX controller
SYSW CONFIG WindowsTM configuration software and cable
SYA CABLES2 Synergy plenum rated RS485
network cable (Specify length:
250', 500' or 1000')
SYSC-MLX
SYSC MLX Network System Controller
SPECIFICATIONS
MECHANICAL
• Chassis: plug-in assembly with locking screws, field-installable in SYE
enclosure.
ENVIRONMENTAL
• Operation and storage temperature: 32-104°F (0-40°C).
• Humidity: 10-90% non-condensing.
ELECTRICAL
• Power input: 24VDC maximum, supplied by enclosure power supply.
• Data port: front-mounted DB9 RS232 serial communications connector
accessible without removal of cover.
• Internal RS232 Port for connection to A/V systems.
• Internal RS485 Port for connection to SEQUEL control stations Synergy®
digital remote stations, and other network devices.
• Internal RS485 ARCNETTM (ANSI 878.1) Port for connection to other Synergy
controllers and BACnetTM systems.
• Internal Ethernet Port for connection to other Synergy® controllers and /or
BACnetTM systems.
• Internal MSTP Port for connection to other Synergy® controllers and or
BACnetTM systems. Disables use of digital control stations.
FUNCTIONAL
• Program entry: numeric keypad (0-9, back and enter), “soft” function keys,
navigation key cluster (up, down, + and -) for menu navigation and logical entry
selections.
• LCD display: four-line, 80-character with back light.
• LED indicators: network status, local status and DMX true indication.
• Outputs: 128 maximum per controller in typical configurations; map inputs and
schedules to any combination of connected relays, dimmers or controllable
circuit breakers.
• Groups: map output relays and dimmers into logical groups (zones) for association to inputs and schedules.
• Switch inputs: 128 maximum per controller, soft-linked through the program to
control any combination of outputs; one minute to 100 hour time-out function
per switch.
• Analog input: maximum of 48, each capable of multiple set-point operation or
tracking operation.
• Priority on switch: switch input set to priority on cannot be overridden off by
any other source until the priority on condition is removed.
• Priority off switch: switch input set to priority off cannot be overridden on by
any other source until the priority off condition is removed.
DIMENSIONS
All dimensions are inches (millimeters).
Controller weight = 5.5 lbs. (2.6 kg)
6
(152)
10.25
(260)
5.5
(140)
FUNCTIONAL
Soft Function
Keys
DB9 Serial Port
Four-line, 80 Character LCD
Display with Backlight
System Status
LED Indicators
Navigation Keys
• Four levels of priority provide for layering of manual and automatic
functions, supports all 16 BACnetTM priority levels via network commands.
• Schedules: Maximum of 100 independent schedules of time events, number
of events per schedule limited only by system resources. Schedules may be
assigned to days of the week, days of the year, or recurring holiday dates
through 12/31/2200.
• Warn off: automatic flash of lights at scheduled off to warn occupants of
impending off; user selectable from one to 99 minutes.
• Logging: automatic logging of system events including on events, off events,
relay run time, relay starts, alarms, power up, power down, override on and
override off; 10,000 event maximum storage with automatic overwrite of oldest
data, view log data on LCD display or printout.
• DMX Control: control connected loads with DMX control signal using optional
DMX input card. May be configured via hardware settings or through controller software to provide prioritized and conditional control of loads along with
other input devices and schedules.
• Legacy Dimmer Control: control up to 255 legacy MiniPac, Sequel, and MaxStar dimmers with optional LEGACY card. Synergy controller replaces function
of master controller in existing systems. Legacy dimmers may be controlled by
any input or schedule in the Synergy system.
• PC software: program the controller, download data, upload data and
monitor status using optional Windows 95/98TM, NT, 2000 or XP software via
front-mounted DB-9 RS232 port, network connection or optional modem connection.
• Sixty digital stations maximum per MLX controllers.
• Room Assignment: digital station control of up to a 4x8 room matrix that may
be dynamically joined and separated to accommodate partitioned spaces.
Join/separate action for each set of rooms may be triggered by switch input,
digital station, time schedule, or partition sensor.
NETWORK
• Protocol: BACnetTM, (ANSI / ASHRAE 135-1995) used for network communications.
• Hardware: RS485 ARCNETTM (ANSI 878.1) token passing, 156 Kbps transmission speed. Approved cables include Synergy SYA CABLES2 (plenum-rated)
or Belden 3105A (non plenum rated).
Synergy Lighting Controls
SYSC-MLX
©1998-2016 Acuity Brands Lighting, Inc., Rev. 05/12/16
1335 Industrial Blvd, Conyers, GA 30012
Phone: 800-533-2719
www.synergylightingcontrols.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising