Factory Gateway - Pro

Factory Gateway - Pro
Pro-face Network Protocol Converter
Factory Gateway (FGW)
RS-232/RS-422 Serial to Ethernet HMI Network Protocol Converter
FGW-SE41-24V
The Factory Gateway operates as a protocol converter enabling direct communications between host
controllers or retrofitting legacy RS-232 or RS-422 serial devices into today’s Ethernet networks.
Peer-to-Peer information exchange in a bidirectional format is supported between host PLC controllers
using the Factory Gateway. The unit can also be configured to interface temperature, PID, and level controls to
an Ethernet based communications network connected to Windows-based SCADA software.
The Factory Gateway is configured using Pro-face’s very popular GP-PRO 03 HMI Development software
package. A wide variety of serial and Ethernet protocols are available to interface to most industrial-based
equipment. Combined with GP Pro Server for Windows allows seamless information exchange and data
collection between factory floor I/O and controller devices to the control room.
FEATURES
• Serial to Ethernet Network Converter
• Peer-to-Peer Communications
• Ideal for Factory Retrofits
• RS-232/422 Com Port Configurable
• Stores HMI Application Image in
Unit for Remote Monitoring
• 10-BaseT Ethernet
• UL, cUL Certified
• DC Powered
• DIN Rail Mounted
INFORMATION & COMMUNICATION
Data
Collection
Remote
Monitoring
Data
Sharing
RetroFitting
⇔
Peer-to-Peer
Data Aquisition Applications
Remote Monitoring by PC
and by Internet
Protocol Conversion
Data Collection
Data Monitoring
Protocol Conversion
Collect production
data and replay the
data for system
analysis.
Simple and quick remote
monitoring using graphic
data stored in Factory
Gateway units.
Data Sharing
Transfer collected
For daily reports
production data to
common PC
applications via ADO,
DDE, DLL, OPC, or
SQL interfaces.
For historical data
Multi-point Remote
Monitoring via a
Web Server
Build a monitoring
system using the
Internet or an intranet.
Page 1
Link PLCs of same or different
manufacturers without special
programming.
Factory Retro-Fits
Monitor and use production
data collected from
factoryfloor
controllers.
FACTORY GATEWAY SPECIFICATIONS
FUNCTIONAL SPECIFICATIONS
Models
Serial (COM 1) Interface
Interfaces
Tool Connector
Ethernet Interface
FGW-SE41-24V
Asynchronous Transmission Method: RS-232C / RS-422, Data Transmission Speed: 2400bps to 187.5kbps,
Data Length: 7 or 8 bits, Parity Stop Bit: 1 or 2 bits, Parity: None, Odd or Even
Asynchronous TTL level nonprocedural command interface
IEEE802.3 (10Base-T)
GENERAL SPECIFICATIONS
DC 24V (DC 19.2V to DC 28.8V)
AC 500V, 20mA for up to 1 minute (between charging and FG terminals)
10W or less
0°C to 55°C
-20°C to 60°C
10%RH to 90%RH (non-condensing, wet bulb temperature: 39°C or less)
IEC61131-2(JIS B 3501)Compliant
When vibration is NOT continuous:10Hz to 57Hz 0.075mm, 57Hz to 150Hz 9.8m/s2
When vibration is continuous:10Hz to 57Hz 0.035mm, 57Hz to 150Hz 4.9m/s2; X, Y, Z directions for 10 times (80min.)
IEC61131-2 (JIS B 3501) Compliant; 147m/s2, X, Y, Z directions for 3 times
Immunity: 6kV (IEC 61000-4-2 Level 3)
DIN rail mount
EN55011 class A, EN61000-6-2, UL508, CAN/CSA-C22.2 No.1010
W37[1.46] x H131[5.16] x D105[4.13] mm[in.] (excluding projections)
0.6kg [1.3lb.] or less (main unit only)
Environmental
Electrical Input Voltage
Voltage Endurance
Power Consumption
Ambient Operating Temp.
Storage Temperature
Storage Humidity
Vibration Resistance
Shock Resistance
Electrostatic Discharge
Installation
Structural
Agency Certifications
External Dimensions
Weight
Examples of functions made possible by combining Factory Gateway with optional software.
EXTERNAL DIMENSIONS
MANUFACTURING DEVICES / PLCs
Unit: mm [in.]
PLCs:
Fanuc
FATEK
Fuji
GE Fanuc Automation
Hitachi
Izumi/Idec
Keyence
Koyo/PLC Direct
Matsushita Electric
Matsushita
Electric Works/NAIS
Mitsubishi
Modicon
Omron
ORIM VEXTA
Rockwell (Allen-Bradley)
Sharp
Shinko
Siemens (SIMATIC)
Toshiba
Toshiba Machine
Toyota
Yaskawa
Yokogawa
Invertors:
Servos:
Matsushita Electric
Temperature
Controllers:
Fuji
Toho
OMRON
RKC
Shinko Technos
Yamatake
Yokogawa M&C
Fuji
Mitsubishi
ORDERING INFORMATION
ORDER NUMBER
DESCRIPTION
FGW-SE41-24V
Ethernet w/ RS-232/RS-422 Serial Port, 4MB mem, 24VDC, UL/cUL, CE
OPTIONAL ACCESSORIES
GPW-CB02
GPW-CB03
RS-232 HMI Programming Cable: Connects HMI to PC Port 9 pin D-Sub
HMI Programming Cable: Connect HMI to PC USB port
Xycom Automation, Inc.
a Pro-face America Company
734-429-4971
Fax: 734-429-1010
http://www.xycom.com
Customer Support Hotline:
734-944-0482
© 2005 Xycom Automation, Inc. Is a wholly owned subsidiary of Pro-face America, Inc. Specifications may change without notice.
Xycom Automation is a trademark of Xycom Automation. Other brand or product names are the property of their respective owners.
Page 2
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement