Models
HB350W 120/277 VAC, 60 Hz
Load @ 120 VAC 0-800 W Ballast/
Tungsten, 1/6 Hp
Load @ 277 VAC 0-1200 W Ballast
HB340W 347/480 VAC, 60 Hz
Load @ 347 VAC 5 A Ballast
Load @ 480 VAC 5 A Ballast
HB330W 208/240 VAC, 60 Hz
Load @ 240 VAC 5 A Ballast
HB300W 24VDC
Use with Wattstopper power pack
Specifications and Features
For use in wet location environments
(indoors and outdoors)
Easy mounting using extender module
mounting accessory
Product Overview
HB3x0W PIR occupancy sensors are
designed for automatic lighting control
in warehouses and other wet location
medium and high bay applications.
The HB3x0W sensors are modular and
consist of two parts, a sensor module
(HB3x0W) and a lens (HBLxW). The
HB3x0W sensor module is a one-
piece self-contained unit with a 1/2”
threaded nipple for attaching to wet
location junction boxes and conduit
hubs, and to the end of a fixture. Three
lens choices are offered, and lenses
are interchangeable. Sensitivity and
time delay adjustments are set using
DIP switches located behind the lens.
Line voltage and low voltage
occupancy sensors
Power consumption for line voltage
models:
HB330W, HB340W: 0.34W
HB350W: 0.36W
Power consumption for low voltage
model:
HB300W: 10mA @ 24VDC
Operating Temperature: -40°F to
158°F (-40°C to 70°C)
Weight: 8 oz (226.8 g)
HB3x0W (sensor module)
Maximum Dew Point: 85°F (29°C)
1/2” Threaded nipple
Five year warranty
SO cable with 18AWG
stranded conductors
DIP switches
PIR
dectector
HBLxW (lens module)
UL and cUL listed
IP65 rated
UL rated raintight (UL244A and
UL508)
Optical
Three interchangeable lenses
(HBL2W, HBL3W, HBL4W)
Lenses sealed and gasketed
Lens choices for mounting
between 8 and 40 feet (lens required
for operation)
Gasket
Threaded
tightening ring
Materials
Polycarbonate, flame retardant
UV resistant
Impact resistant
Recyclable
Meets materials restrictions of RoHS
Factory Defaults
Time Delay:
15 minutes
Sensitivity Mode: Normal
1
WWW.LEGRAND.US/WATTSTOPPER
20
10
WATTSTOPPER®
0
Coverage
30
10
20
20
10
0
10
20
0
10
20
10
20
0
HBL2W side coverage pattern
8
25
Ceiling
0
10 coverage
0
10 pattern
20
20 top
HBL2W
11 7 3 0 3 7 11
25
HBL2W Low Bay Lens
20
0
810
5
25
11 7 3 0 3 7 11
25
0
40 ft
10
10
15
20
20
20
18
15
12
9
6
3
0
3
6
9
12
15
18
20
HBL3W side coverage pattern
20
10
0
10
20
HBL3W top coverage pattern
HBL3W Mid Bay Lens
30
0
27
.83
20
10
R1
12
6
3
0
3
6
20
60 ft
+
12
30
20
27
40
30
20
12
6
0
6
12
20
30
30
HBL4W side coverage pattern
Dimensions
27
20
12
6 3 0 3 6
12
20
30
27
HBL4W top coverage pattern
HBL4W High Bay Lens
2.21”
(56.13mm)
.39”
(9.90mm)
2.21”
(56.13mm)
.39”
(9.90mm)
7.45”
(189.23mm)
4.09”
(103.88mm)
7.45”
(189.23mm)
4.09”
(103.88mm)
3.17”
(80.51mm)
3.17”
(80.51mm)
HB3x0W dimensions (top view)
.66”
.43”
(16.76mm)
(10.92mm)
3.66”
(92.96mm)
HBL2W and HBL3W dimensions
1.61”
(40.89mm)
0.78”
0.45” (19.81mm)
(11.43mm)
1.61”
(40.89mm)
3.66”
.33”
(8.38mm)
.33”
(8.38mm)
HB3x0W sensor module dimensions
WWW.LEGRAND.US/WATTSTOPPER
(92.96mm)
HBL4W dimensions
2
WATTSTOPPER®
Installing and Mounting Instructions
The 1/2" chase nipple facilitates mounting through fixture
knockouts, or attaching to threaded J-boxes or conduit
hubs. An accessory bag with an O-ring and two locknuts is
available to accommodate various mounting needs.
Mount the sensor so that the fixture does not obstruct
the field of view.
"O" Ring
Direct mounting to wet location J-box.
HB3x0W
IP65 Occupancy sensor
with HBLxW lens
Wiring connection
made inside box
Direct mounting to wet location J-box
using conduit hub.
Conduit hub
1/2” O Stamped locknuts
securing nipple
120.90mm
to housing
145.54mm
HBEM3W
Extender
Module
Mounting using an HBEM3W extender
module accessory to attach sensor
to fixture.
HB3x0W
IP65 Occupancy sensor
with HBLxW lens
Wiring Diagrams
120/277VAC Wiring (HB350W)
Important Start-up Information
Neutral
White
Line (Hot)
Load
Black
HB350W
Red
HB350W
Black
Red (Load A)
White
Red with White
Stripes (Load B)
(347 VAC Neutral)
(347 VAC Cap Off)
Phase A
Phase B
HB340W
HB340W
3
WWW.LEGRAND.US/WATTSTOPPER
Load
1. When power is initially applied to the sensor,
the relay will be in a closed position to
enable the lights to turn on immediately.
Consequently, the sensor requires one minute
to warm up before becoming operational. This
warm up period is necessary either upon initial
power up, or upon power up after a temporary
power loss to the circuit.
2. The sensor is shipped with a factory preset
time delay of 15 minutes. Lights will turn off 15
minutes after the last motion is detected.
WATTSTOPPER®
Wiring Diagrams
HB300W Wiring
Power
Pack
Phase A
Phase A Load
Phase B
Phase B Load
Load
Load
White
Black
Red
Red w/white stripes
Black
Red
Black
Hot
Red
Red
White
Blue
Neutral
HB330W
(Common)
(+24VDC)
Black
Red
White
(Control Output)
HB300W
HB330W
Sequence of Operation
The HB3x0W occupancy sensor is designed to mount to a light fixture and control one load in the fixture. The sensor can
be wired to control all ballasts in the fixture, or to control half of the ballasts to provide high/low lighting control. When
motion is detected within the sensor’s coverage area, the relay in the sensor closes, and lighting loads turn on automatically. When motion is no longer detected for the duration of the time delay setting, the relay opens and the lighting
load is turned off. The sensitivity and time delay settings are factory preset at 100% and 15 minutes, respectively, which
are suitable for most high bay applications. However, the values can be easily adjusted for specific applications using
the DIP switches on the unit. Refer to the Installation Instructions for changing factory preset values, and for important
start up instructions.
Ordering Information
Master Pack Details
Inner Pack Details
Catalog #
Master
Pack
Quantity
Height
Weight
(pounds)
Inner
Pack
Quantity
Length
Width
Length
Width
Height
Weight
(pounds)
HB300W
50
18.50
21.50
16.50
25.0
N/A
N/A
N/A
N/A
N/A
HB330W
50
HB340W
50
18.50
21.50
16.50
25.0
N/A
N/A
N/A
N/A
N/A
18.50
21.50
16.50
27.8
N/A
N/A
N/A
N/A
N/A
HB350W
50
18.50
21.50
16.50
25.5
N/A
N/A
N/A
N/A
N/A
HB350W-CC2
50
18.50
21.50
16.50
26.5
N/A
N/A
N/A
N/A
N/A
BZ-50
40
13.58
13.46
9.06
15.0
10
6.30
13.0
3.93
3.55
Catalog #
Case dimensions (inches)
Case dimensions (inches)
Color
Description
Voltage
Load Capacity
HB300W
White
Wet Low Voltage High Bay Sensor (Bulk Packaged)
24 VDC
Refer to Power Pack for Load Capacity
HB330W
White
Wet Line Voltage High Bay Sensor (Bulk Packaged)
208/240 VAC
5 A ballast @ 240 VAC
HB340W
White
Wet Line Voltage High Bay Sensor (Bulk Packaged)
347/480 VAC
5 A ballast @ 347/480 VAC
HB350W
White
Wet Line Voltage High Bay Sensor (Bulk Packaged)
120/277 VAC
0-800 W ballast and tungsten @ 120
VAC or 0-1200 W ballast @ 277 VAC or
1/6 hp motor
HB350W-CC2
White
Wet Line Voltage High Bay Sensor (Bulk Packaged)
120/277 VAC
0-800 W ballast and tungsten @ 120
VAC or 0-1200 W ballast @ 277 VAC or
1/6 hp motor
BZ-50
White
Power Pack
120/230 (1P,
L-N) /277 VAC
Information supplied above is subject to change.
Harmonization code: 8538908080. Country of origin: China.
WWW.LEGRAND.US/WATTSTOPPER
Pub. No. OEM-107 09/2016
4
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertisement