HID EDGE EVO EH400-K/ESH400-K Networked Controller Installation Guide
EDGE EVO EH400-K/ESH400-K is a next generation access control hardware solution, a true IP solution that offers fully distributed intelligence and decision making right to the door, leveraging the IT infrastructure to the maximum extent possible. EDGE EVO reduces installation costs by not requiring a separate local power supply in many circumstances. The Standard Networked Controller is a fully integrated single-door controller offering discrete I/O and Wiegand/Clock-and-Data interfaces to readers.
Advertisement
Advertisement
INSTALLATION GUIDE
EDGE EVO®
Standard Networked Controller
EH400-K/ESH400-K
82000-921 D.2
EDGE EVO is the next evolution in access control hardware solutions. A true IP solution that meets the demands of open architecture, IP-centric environments, EDGE EVO provides fully distributed intelligence and decision making right to the door, leveraging the IT infrastructure to the maximum extent possible. Leveraging Power-over-Ethernet (PoE),
EDGE EVO reduces door installation costs by not requiring a separate local power supply under many circumstances.
The Standard Networked Controller is a fully integrated single-door controller offering discrete I/O and Wiegand/
Clock-and-Data interfaces to readers. Additionally, connect native Hi-O™ devices (readers, locks, pushbuttons) and
EDGE EVO Hi-O Modules to the Hi-O bus, providing secure communication around the door. Hi-O involves devices with built-in intelligence and a CANbus that links all the devices together. Password protect or encrypt Hi-O CANbus data traffic. Each Hi-O device (such as the push plate, electric strike, card reader and door operator) is connected to the
CANbus by a single, four-wire cable. Two wires supply power and the other two are used for data communication.
Specifications
CONDITIONS VOLTAGE DC CURRENT POWER
OPERATING
TEMPERATURE
CABLE LENGTH
REGULATORY
REF NUMBER
DC Input (NSC)
DC Input (MAX)
Supervised inputs
(AC, Batt, REX, Door Mon) (MAX)
Data 1/CLK , Data 0 / Data (MAX)
GRN LED, RED LED, Beep, Hold (MAX)
External Tamper (MAX)
CAN DC
PWR Output
(MAX)
AUX 12/24 VDC Input
PoE Input
+12 VDC
+24 VDC
0.18 Amp 2.16 W
0.14 Amp 3.36 W
PoE (+48 VDC NOM) 0.085 Amp 4.08 W
+12 VDC
+24 VDC
PoE (+48 VDC NOM) 0.30 Amp 14.40 W
0-+5VDC Reference
0.005 Amp
(sink)
N/A
0.025 W
N/A
+5VDC (NOM)
0.005 Amp
(sink)
0.025 W
0.02 Amp 0.100 W
+10.8 to +24 VDC 1 .2 Amp* 28.80 W
+ 24 VDC (NOM) 0.4 Amp* 9.60 W
0.32 Amp* 3.92 W
32° - 122°F
(0° - 50° C)
Hi-O CANbus
Total Length:
100 ft (30 m)
22 AWG
0.65 mm
0.33 mm
2
30 ft (10 m)
22 AWG
0.65 mm
0.33 mm
2
AUX 12 VDC
Reader DC
PWR Output
(MAX)
AUX 24 VDC
PoE Input
AUX 12 VDC
Input
+9.8 to +12.25 VDC 0.60 Amp* 7.35 W
0.58 Amp* 7.11 W
8.40 W
RJ-45
328 ft (100 m)
Category 5 K
KE400CX
1
X
2
N
Strike***/
AUX Relays
NC or NO
DC Output
(MAX)
AUX 24 VDC
Input
PoE Input
AUX/PoE
Input
Unregulated
(Wet) Jumpers
+10 to +12 VDC
+23 to +24 VDC
Regulated (Wet)
Jumpers - 12 VDC +10 to +12 VDC
Unregulated
(Wet) Jumpers
+16.5 to +24 VDC
Regulated (Wet)
Jumpers - 12 VDC +10 to +12 VDC
Jumpers Set to
Dry
+12 to +24 VDC
External
0.70 Amp* 16.80 W
8.40 W
0.36 Amp* 8.64 W
0.58 Amp* 6.96 W
2 .00 Amp ** 48.00 W
Legend
AUX = Auxillary input or output
CAN = CANbus
NSC = Normal Standby Condition
PoE = Power over Ethernet
NC = Normally Closed
NO = Normally Open
* Combined output ratings not to exceed V*I = W:
• 1.2 Amp (+ 24 VDC Aux Input, 28.8 W)
• 1.2 Amp (+ 12 VDC Aux Input, 12.96 W)
** Each relay
*** Shared between each relay
Regulatory Reference
Number Deciphering
X
1
X
2
= K for Black
G for Gray
= N for non-Solo
S for Solo
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
Installation
1
Power Analysis
Before starting installation, determine which components will be used in the system and analyze the power requirements to avoid over-loading the EDGE EVO Hi-O Networked Controller & Reader
(EH400-K).
The following steps illustrate sizing power requirements for the system.
Step 1
Identify System Components
Identify the components that will be used in the system. A typical installation may include the following components:
• Door Position Switch – Detects when the door is open or closed.
• Magnetic Lock – Holds the door locked.
• Request to Exit (REX) Switch – Unlocks the door when exiting the secured area.
• EDGE EVO Hi-O Standard Networked Controller (EH400-K) – Provides access control and manages all peripherals around the door.
• iCLASS® Wiegand Reader – Provides entry into the secured area.
Step 2
Create System Layout
Using the components identified in Step 1 Identify System Components create the system layout.
In this example, the EH400-K is connected to the remote server through an Ethernet connection and manages door peripherals over the Hi-O bus. Controlling downstream door peripherals, the EH400-K is a fully integrated single-door controller offering discrete I/O and Wiegand/Clock-and-Data interfaces to external readers. The EH400-K receives inputs from the Door Position Switch and REX Switch to drive the Magnetic Lock output.
Unprotected
Area cted
Protected Area Remote Area
Ethernet Data
Ethernet Switch
Wiegand Reader
Door Position
Switch
EH400-K
Physical Access
Control Server
(real-time functions not required )
REX Switch
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 2
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
Step 3
Analyze Power Requirements
A - Door Peripheral Operational Currents
For the door peripherals identified in Step 1 Identify System Components, consult the vendor
data sheets to determine the operational current draw. Typical operational current draw is provided below.
Note: See individual peripheral data sheets for actual operational current draw.
Device
Door Position Switch
(For example, Securitron MSS)
Mag Lock
(For example, Securitron M32)
REX Switch
(For example, Securitron EEB) iCLASS Wiegand Reader
Conditions
V in
= 12VDC
V in
= 24VDC
V in
= 12VDC
V in
= 24VDC
V in
= 12VDC
V in
= 24VDC
V in
= 12VDC
Typical Operational Current
15mA
15mA
300mA
150mA
28mA
38mA
150mA
B - Match I/O Requirements to the Hi-O Interface Device
For the door peripherals identified in Step 1 Identify System Components, the system requires
direct connection to I/O interface and Wiegand/Clock-and-Data ports of the EH400-K. A separate Hi-O Interface Device is not required.
C - Compute and Compare Overall Current Draw
Calculate the total current draw for all door peripherals, all Hi-O interface devices, and all Hi-O enabled readers with the following equation, adding terms as required.
I total
= I dps
+ I mag
+ I rex
+ … + I
EDM-M
For this example, the total current draw equals the following:
I total
@ +12VDC = 15mA + 300mA + 28mA + 150mA* = 493mA
I total
@ +24VDC = 15mA + 150mA + 38mA + 150mA* = 353mA
Compare the required current draw (I total
) to the output current capacity of the EH400-K to
select the EH400-K power scheme. See Specifications. The CAN DC PWR Output represents
the entire power output capacity of the EH400-K.
Device Port
Standard Networked Controller
(EH400-K)
CAN DC PWR Output (MAX)
Conditions
AUX +12/24 VDC Input
PoE Input
V out
+10.8 to +24VDC
+24VDC (NOM)
I out
1.2 Amp
0.4 Amp
In this example, the EH400-K provides sufficient power when operated with a PoE injector or
+12/24VDC auxiliary power supplies.
Directly connect the door peripherals identified in Step 1 Identify System Components to the
EH400-K I/O ports per the Specifications for the selected input power scheme.
Ensure all door peripherals connected to the Strike/AUX relays or the Reader DC PWR
Output, or both, do not exceed 1.2 Amps (AUX Input) or 0.4 Amps (PoE Input) combined.
Alternatively, the door peripherals may be connected to the Strike/AUX relays configured for
Dry contact up to 2 Amps per relay.
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 3
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
Step 4
Select Power Scheme
Select the appropriate power scheme to meet overall current draw. Using the analysis from the previous sections equates to the following two power scheme options.
Power Scheme 1
Standard Networked Controller power is derived from PoE. Insert a UL294 Listed PoE Injector in the Ethernet line to power the Standard Networked Controller.
Unprotected
Area cted
Protected Area Remote Area
Ethernet Data
UL 294 PoE
Injector
Ethernet Switch
Door Position
Switch
EH400-K
Physical Access
Control Server
(real-time functions not required )
REX Switch
Power Scheme 2
Standard Networked Controller power derived from an external +12VDC or +24VDC power supply. Standard Networked Controller is connected directly to the Ethernet switch without a
PoE Injector.
Protected Area Remote Area
+ 12 / 24VDC
Power Supply
Ethernet Data
Ethernet Switch
Door Position
Switch
EH400-K
Physical Access
Control Server
(real-time functions not required )
REX Switch
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 4
An ASSA ABLOY Group brand
INSTALLATION GUIDE
2
Mounting
EDGE EVO
82000-921 D.2
Junction box not included.
3
Wiring
ATTENTION
Observe precautions for handling
ELECTROSTATIC SENSITIVE DEVICES
GRP SEL
Restore Network
Defaults Jumper
Hi-O Group Select Jumper
( )
NC
COM
NO
Relay Jumpers
NC
COM
NO
P9 P5 P8 P6 P4 P7
AUX
GND
AUX
+DC
Link LED
CAP
Activity LED
CAN_L
CAN_H
GND
CAN V+
*
Reader Tamper -
Reader Tamper +
Hold
Beep
RED LED
GRN LED
*
Data1 / CLK
Data0 / Data
GND
RDR PWR
Hi-O Group Select Jumper
( )
Optional
Supervised Inputs
1-6K
1-6K
1-6K
N/O
N/C
*
AC FAIL
INPUT SENSE
BATT FAIL
INPUT SENSE
REX
-
+
-
+
Ethernet / PoE
Auto-Detected
1-6K
N/O
-
+
Door Mon
Note: Connect the Door Monitor to avoid a Force Door Alarm.
* = Internal Optical Tamper Disable
Legend
CAN_H = Hi-O CANbus High
CAN_L = Hi-O CANbus Low
GND = Ground
CAN V+ = Hi-O CANbus Positive
Supply
CAUTION: Some magnetic locks exhibit both high inrush current when activated and a high instantaneous break voltage when de-energized due to magnetic field collapse. It is recommended you use of a snubber circuit across the controlling relay terminals to protect the controlling relay contacts. Go to
www.hidglobal.com
> Support and search for "Edge Solution 891" to access How do I
wire a High In-Rush Current locking device to VertX/EDGE EVO. Not evaluated by UL.
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 5
An ASSA ABLOY Group brand
INSTALLATION GUIDE
4
Install to Backplate
EDGE EVO
82000-921 D.2
Contact EDGE EVO with the information provided in the next section.
5
Contact
Contact EDGE EVO through one of the following methods:
Direct Connect
If connecting EDGE EVO to a network using static IP addressing or if the Discovery GUI is not installed on the PC, use this method.
Note: The computer must be running Windows 2000 or XP and be configured for DHCP.
1.
Disconnect the computer from the network and directly connect EDGE EVO to the computer with an Ethernet cable.
2. Select Start > Run and enter ipconfig /renew.
3. Open a web browser and enter 169.254.242.121 into the Address field
.
Discovery GUI (for DHCP Networks)
With a DHCP network, use the HID Discovery GUI on the PC to locate and connect the Controller.
Note: The Controller must be connected to the network before power is applied for DHCP to function.
Java is required for the Discovery GUI.
1.
With the PC connected to the same network as the Controller, double-click hid-discovery.exe.
Note: If the HID Discovery Application is not on the PC, download the application from www.hidglobal.com/drivers . Search for “Discovery” and the DISCOVERY GUI download window will appear.
2. Select the device from the list and click the Launch Browser button.
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 6
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
6
Configure
The web browser will prompt for login information.
Note: To correct errors in the controller Network Configuration or if the admin password is not
available, see Appendix B: Troubleshooting.
1.
From the
Login
screen enter
admin
, leaving the
Password
field empty.
2. Follow the instructions on the web browser screen to configure EDGE EVO.
Note: On subsequent sessions, the password may be changed by the user. The password must be between 6 to 10 characters long and can include all printable ASCII characters from 32 to 126
(decimal). Reference: http://www.asciitable.com.
For EDGE EVO Solo, see the EDGE EVO Solo User Guide, 83000-902, rev B.x.
7
Power & Testing
Test the system once per year using the web Graphical User Interface to ensure all wiring and configuration is correct.
For additional installation information, such as Passive Infrared Device (PIR) and other active REX devices, as well as connecting fire relays, see http://www.hidglobal.com
> Support and search for
"EDGE EVO."
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 7
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
Appendix A
Hi-O Interface Modules
Hi-O interface modules are used to interface the EDGE EVO Networked Controller. Hi-O interface modules connect the native Hi-O bus with additional components around and behind doors and other access points.
For Hi-O interface module wiring, see their respective Installation Guides: go to www.hidglobal.com
> Support > Document Library and search the document type
Installation Guide.
EDM-M
EIM-M
EWM-M
EDWM-M
ELM
EVM
Model Description
EDGE EVO Door Module
EDGE EVO Input Module
EDGE EVO Reader Module
EDGE EVO Door & Reader Module
EDGE EVO Lock Module
EDGE EVO Voltage Module
82342
82340
82360
82363AM
82301
82365
Part Number
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 8
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
Appendix B
Troubleshooting
See Section 3: Wiring to clarify the procedures in this appendix.
B.1
Network Defaults Jumper Procedures
Use the applicable Network Defaults Jumper procedure to correct potential errors in an EDGE EVO and
EDGE EVO Solo controller Network Configuration or if the admin password is not available.
EDGE EVO (EH400-K)
This Network Defaults Jumper procedure requires physical access to the EDGE EVO controller. Physical access provides the necessity to place a jumper over the debug port prior to the controller rebooting.
The controller reconfigures the network settings to the factory defaults when the jumper is on the debug port during a reboot. From this point, configuration (or re-configuration) proceeds normally.
A jumper is supplied with the EDGE EVO for the Hi-O termination; borrow this jumper to perform this process. Replace the jumper to the Hi-O termination after restoring network defaults.
1.
Remove the back plate on the EDGE EVO.
2. Loosen the Mylar cover.
Note: For the jumper location, see the diagram in Section 3: Wiring.
3. Reboot the controller and place the supplied jumper over pins 3 and 5 of the Debug port after the beep. The Debug port is an eight pin header, located above and to the right of the Ethernet connector, underneath the Mylar.
Note: The network reset opportunity occurs for 30 seconds, while rebooting the controller. On an
EDGE EVO, a second beep occurs to signal the end of the 30 second period.
4. After 30 seconds, the beeper stays on constantly to indicate success. When an error occurs, you receive a single beep.
5. Remove the jumper; return it to the Hi-O termination header and cycle power. The controller resets in approximately 60-seconds. Once the reset is complete, you hear the single beep. After the 30-second window, you hear the second beep. The controller is fully functional during this time.
CAUTION: During the controller rebooting process, all network configuration information is overwritten and returned to the original defaults.
6. Configure the controller for your installation parameters.
7. Reinstall the back plate of the EDGE EVO.
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 9
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
EDGE EVO Solo (ESH400-K)
This procedure will reset the password for the admin user, the admin user can reset the user password if installer lock is enabled. This process requires:
• 5-10 minutes to complete.
• Contacting HID Global technical support by e-mail or phone with the unit's MAC Address to obtain the new generated password that is required in the following procedure.
• Physical access to the EDGE EVO Solo device.
• A pair of needle-nose pliers to work with a small jumper.
Note: This procedure works for all released versions of EDGE EVO Solo but must be followed very carefully for the process to work.
1.
Remove the jumper from the HiO Termination pins. This is located to left of the HiO four-pin connector. This jumper will be used through the remainder of the procedure.
2. Power Cycle the EDGE EVO Solo unit.
3. Between 10 and 25 seconds after power is applied, place a jumper over pins 3 and 5 of the Debug
Port (eight pin header located above and to the right of the Ethernet connector, underneath the
Mylar - see graphic below). If no jumper is applied during this period the unit will continue to operate as normal and no reset will occur.
Note: If the jumper is applied before power is applied to the unit, no reset procedure is completed, and the unit will fail to boot correctly.
4. Provided the jumper is correctly fitted within the specified time, the unit will beep with 2 short beeps, then a pause. This beep/pause cycle will continue indefinitely until the jumper is removed.
5. Remove the jumper. The beeps will cease.
6. Wait a minimum of 1 second then reapply the jumper. The jumper must be reapplied within 15 seconds of removing it. If the jumper is not reapplied within this time, the device will emit 10 short beeps and the unit will automatically reboot. In this case the password will not have been reset.
7. The unit will beep with 2 short beeps, then a pause. This beep/pause cycle will repeat indefinitely until the jumper is removed.
8. Remove the jumper to complete the process.
9. The beeps will cease. The admin password is now reset to the value provided by HID Global
Technical Support. The unit will beep quickly 10 times and then automatically reboot.
The password reset process is now complete.
10. Reinstall the jumper borrowed from the HiO Termination pins. This is located to left of the HiO four-pin connector.
11. Connect to the unit via the JumpStart application, configured IP Address, or Alias IP Address.
12. The web browser will prompt for a username and password.
13. Login with username: admin and the password will be the 8-digit alphanumeric value you obtained from HID Global Technical Support.
14. It is recommend you immediately go and modify the password(s) using the Password option within the Preferences link.
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 10
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
B.2
Internal Optical Tamper
To disable the internal optical tamper sensors:
• Right side of PCB (reader interface board): attach a jumper wire from P2 pin 10 to P2 pin 5.
• Left side PCB (door interface board): attach a jumper wire from P3 pin 1 to P3 pin 2.
CAUTION: The EH400-K ships from HID Global with these jumpers pre-installed on the connectors.
Removing these jumpers causes false tampers to trigger.
Note: If desiring an external tamper, wire an unsupervised Normally Closed contact, replacing one of the pre-installed jumpers.
B.3
Relay Jumpers
AUX Wet
CAN V+
AUX Wet
+12VDC
3 1 3 1 3
AUX Dry
1
P9
3
DS Wet
CAN V+
1 3
DS Wet
+12VDC
1 3
DS Dry
1
P6
P5 P4
P8 P7
JUMPER =
B.4
Tamper (Reader Interface Board)
The Reader Tamper + and - are implemented allowing a connection for an open collector external tamper from a reader, such as iCLASS.
Note: Connect P2, Pin 2 (GND) from the Reader Interface Board to the same ground as the reader power if the reader is not powered by the unit's 12 VDC output port.
B.5
Door Interface Board Groups 1 and 2
Following are the inputs for Group 1 and Group 2 configurations.
Input
AC -
AC +
BATT -
BATT +
REX -
REX +
Door Mon -
Door Mon +
Group 1
Port
P3
P3
P3
P3
P3
P3
P3
P3
Pin
Pin3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9
Pin 10
Input 4 -
Input
Input 4 +
Input 3 -
Input 3 +
Input 2 -
Input 2 +
Input 1 -
Input 1 +
Group 2
Port
P3
P3
P3
P3
P3
P3
P3
P3
Pin
Pin3
Pin 4
Pin 5
Pin 6
Pin 7
Pin 8
Pin 9
Pin 10
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 11
An ASSA ABLOY Group brand
INSTALLATION GUIDE
EDGE EVO
82000-921 D.2
Regulatory
UL
Connect only to a Listed Access Control / Burglary power-limited power supply, or Listed Access Control / Burglary PoE (Power-over-Ethernet) adapter.
All National and local Electrical codes apply. Install in accordance with NFPA70 (NEC), Local Codes, and authorities having jurisdiction. Host-based security, Ethernet / Host
Communication, has not been evaluated by UL. Ethernet port has been evaluated for supplemental use only.
Indoor use only.
The EDGE EVO family has been evaluated for standalone Access Control.
Mount onto UL Listed Single-Gang electrical box.
Hi-O Networked Controller and EDGE EVO Modules are UL Listed for installation within the protected area.
All panic and alarm hardware and equipment shall be UL Listed.
All cabling and wire shall be UL Listed or Recognized and suitable for the application.
All splices and connections shall be mechanically secure and bonded electrically.
EDGE EVO was evaluated for use with all Listed HID Global Wiegand models: iCLASS, Indala Prox, HID Prox, bioCLASS, SmartID, SmartTRANS, and Mag Stripe series (with and without keypad), up to 128-bit formats. EDGE EVO was evaluated for use with all HID Global Hi-O iCLASS readers.
Hi-O Networked Controller is UL Listed for installation in the unprotected area, as well as within the protected area.
CAUTION: Any changes or modifications to this devise not explicitly approved by the manufacturer could void your authority to operate this equipment.
FCC
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Canada Radio Certification
This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.
Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes:
(1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
CE MARKING
HID Global hereby declares that these proximity readers are in compliance with the essential requirements and other relevant provisions of Directive 1999/5/EC.
Por el presente, HID Global declara que estos lectores de proximidad cumplen con los requisitos esenciales y otras disposiciones relevantes de la Directiva 1999/5/EC.
HID Global déclare par la présente que ces lecteurs à proximité sont conformes aux exigences essentielles et aux autres stipulations pertinentes de la Directive
1999/5/CE.
A HID Global, por meio deste, declara que estes leitores de proximidade estão em conformidade com as exigências essenciais e outras condições da diretiva 1999/5/EC.
HID Global bestätigt hiermit, dass die Leser die wesentlichen Anforderungen und anderen relevanten Bestimmungen der Richtlinie 1999/5/EG erfüllen.
HID Global dichiara che i lettori di prossimità sono conformi ai requisiti essenziali e ad altre misure rilevanti come previsto dalla Direttiva europea 1999/5/EC.
Download copies of the R&TTE Declaration of Conformity (DoC) at http://www.hidglobal.com/certifications .
JAPAN MIC
この装置は認証済みです。
TAIWAN NCC
經型式認證合格之低功率射頻電機,非經許可,公司、商號或使用者均不得擅自變更頻率、加大功率或變更原設計之特性及功能。低功率射頻電機之使用不
得影響飛航安全及干擾合法通信;經發現有干擾現象時,應立即停用,並改善至無干擾時方得繼續使用。前項合法通信,指依電信法規定作業之無線電通信。
低功率射頻電機須忍受合法通信或工業、科學及醫療用電波輻射性電機設備之干擾。
According to «Administrative Regulations on Low Power Radio Waves Radiated Devices» without permission granted by the NCC, any company, enterprise, or user is not allowed to change frequency, enhance transmitting power or alter original characteristic as well as performance to an approved low power radio-frequency devices. The low power radio-frequency devices shall not influence aircraft security and interfere legal communications; If found, the user shall cease operating immediately until no interference is achieved. The said legal communications means radio communications is operated in compliance with the Telecommunications Act.
The low power radio-frequency devices must be susceptible with the interference from legal communications or ISM radio wave radiated devices.
This product includes software developed by the OpenSSL Project for use in the OpenSSL Toolkit ( http://www.openssl.org
).
HID Global
Americas & Corporate
611 Center Ridge Drive
Austin, TX 78753
USA
Support: 866-607-7339
Fax: 949-732-2120
Asia Pacific
19/F 625 King's Road
North Point, Island East
Hong Kong
Support: 852-3160-9833
Fax: 852-3160-4809
For additional offices around the world, see www.hidglobal.com corporate offices.
HID Global Customer Support: support.hidglobal.com
Patent Pending
Check reader label for current regulatory approvals.
Europe, Middle East & Africa
Haverhill Business Park Phoenix Road
Haverhill, Suffolk CB9 7AE
England
Support: 44 (0) 1440 711 822
Fax: 44 (0) 1440 714 840
This Installation Guide is for informational purposes only. HID makes no warranties, expressed or implied, in this summary. Company, product names and data used in sample output are fictitious. Specifications are subject to change without notice.
© 2014 - 2016 HID Global Corporation/ASSA ABLOY AB. All rights reserved. HID, the HID logo, iCLASS, EDGE EVO, and Hi-O are trademarks or registered trademarks of HID
Global in the U.S. and/or other countries. All other trademarks, service marks, and product or service names are trademarks or registered trademarks of their respective owners.
hidglobal.com
Page 12
An ASSA ABLOY Group brand
Download
Advertisement
Key features
Fully integrated single-door controller
Discrete I/O and Wiegand/Clock-and-Data interfaces
Hi-O bus
Power-over-Ethernet (PoE)
Built-in intelligence
Password protect or encrypt Hi-O CANbus data traffic
Reduces installation costs
Leveraging the IT infrastructure to the maximum extent possible
Frequently asked questions
The Network Defaults Jumper is used to correct potential errors in an EDGE EVO and EDGE EVO Solo controller Network Configuration or if the admin password is not available.
To disable the internal optical tamper sensors on the right side PCB (reader interface board), attach a jumper wire from P2 pin 10 to P2 pin 5. To disable the internal optical tamper sensors on the left side PCB (door interface board), attach a jumper wire from P3 pin 1 to P3 pin 2.
You can directly connect the EDGE EVO to the computer with an Ethernet cable. Select Start > Run and enter ipconfig /renew. Then open a web browser and enter 169.254.242.121 into the Address field.