WebMeter Internal Web Server Feature

WebMeter Internal Web Server Feature
70072-0116-10
12/2007
TECHNICAL NOTE
WebMeter® Internal Web Server Feature
Several Ethernet‐equipped PowerLogic® ION® meters offer WebMeter capability, allowing you to view meter data and perform basic meter configuration using a web browser. The meter can be connected to your corporate Ethernet network, like any other network device, and you can access it with Internet Explorer. NOTE
Your meter must have its web server enabled for users to view meter data or configure meter settings.
See “Enabling/Disabling Meter Web Server Functionality” on page 9 for more information.
In This Document
Viewing WebMeter Data on the Internet . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Viewing Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Setting the default home page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Creating Custom Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Custom Web Page Setup . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Creating Custom Web Pages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Configuring Your Meter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Using the Setup Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Using the Network Setup Page . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
Setup Errors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Enabling/Disabling Meter Web Browser Configuration . . . . . . . . . . . . . . . . 8
Enabling/Disabling Meter Web Server Functionality . . . . . . . . . . . . . . . . . . . 9
PowerLogic, ION, ION Enterprise,
MeterM@il, WebMeter and
Modbus are either trademarks or
registered trademarks of
Schneider Electric.
Electrical equipment should be
installed, operated, serviced, and
maintained only by qualified
personnel. No responsibility is
assumed by Schneider Electric for
any consequences arising out of
the use of this material.
© 2007 Schneider Electric.
All rights reserved.
www.powerlogic.com
Using WebMeter in a Modbus Network . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Hardware . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Framework . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Additional Information
Your meter’s technical documentation
ION Reference
Viewing WebMeter Data on the Internet
WebMeter Internal Web Server Feature
Viewing WebMeter Data on the Internet
With the WebMeter feature, you can view various power measurements over the web, in both HTML and XML formats. There are two types of web pages you can use to view meter data: default and custom. The default pages display pre‐determined sets of values while custom pages can be created to display any values you require. The default web pages vary slightly from meter to meter. However, typical pages and their displayed values include:
Operation: real‐time voltages, currents, power (kW, kVAR, kVA), power factor and frequency
Consumption: accumulated energy and peak demand
Power Quality: voltage and current harmonics and voltage disturbances
Trending & Forecasting: graphical view of trends and forecasts for selected parameters.
Although you cannot create more default pages, you can make minor alterations to the existing ones.
Viewing Web Pages
See “Setting the default home page” on page 4 for instructions on how to change the default home page. NOTE
Some meters use frames to organize their web pages. If your meter uses frames, only the IP Address
appears in the Address field of the browser, regardless of which page you are currently viewing. To find
the full name of a web page in this case, right-click on the main area of the page and select Properties.
Look at the Address (URL) field to find the name of the web page (with the .html extension), for example,
WebPage.html.
Viewing default web pages
1.
Start your web browser.
2.
Enter the meter’s IP address into the browser’s address field. The default meter home page appears (this varies depending on the meter).
NOTE
Depending on your meter and its security settings, you may be prompted to enter a user name and the
meter password. Type them and click OK.
3.
To view data on other web pages, click the links at the side or top of the page.
To view only one particular page, enter the address of the page and use the .html extension. For example:
http://10.1.50.42/webpage1.html.
Page 2
© 2007 Schneider Electric. All rights reserved.
WebMeter Internal Web Server Feature
Viewing Web Pages
See “Configuring Your Meter” on page 6 for information on the Setup and Network Setup pages.
Viewing Trending & Forecasting pages
NOTE
To view trending and forecasting pages, your meter must have this feature and you need to install the
ActiveX control on your computer. To install the ActiveX control, navigate to /.../ION Setup/ProEssentials
Graph Install.exe. Double-click on the file and follow the instructions in the installation wizard. If you do
not have ION Setup on your workstation, you can download the file from the Support area of the
PowerLogic website.
1.
Start your web browser. 2.
Enter the meter’s IP address into the browser’s Address field. The default meter home page appears (this varies depending on the meter).
3.
Click the Trending & Forecasting link.
4.
Select the quantity and the interval you want to view on the graph. Refer to your meter’s User Guide for more information on the web pages associated with the trending and forecasting feature.
Viewing custom web pages
1.
Start your web browser.
2.
Enter the meter’s IP address into the browser’s Address field. The default meter home page appears (this varies depending on the meter). 3.
To view a custom page in HTML, click the links at the side or top of the page. To view only one particular page, enter the address of the page and use the .html extension. For example:
http://10.1.50.42/webpage1.html
4.
To view a custom page in XML, enter the address of the page with the .xml extension. For example:
http://10.1.50.42/webpage1.xml
5.
To view the meter’s catalog XML web page, enter the following address:
http://<enter meter IP address here>/catalog.xml
See “Creating Custom Web Pages” on page 4 for information on creating custom web pages.
© 2007 Schneider Electric. All rights reserved.
Page 3
Creating Custom Web Pages
WebMeter Internal Web Server Feature
Setting the default home page
Use ION software to set which web page is the default home page when you connect to the meter.
NOTE
Some meters use frames to organize their web pages. If your meter uses frames, only the IP Address
appears in the Address field of the browser, regardless of which page you are currently viewing. To find
the full name of a web page in this case, right-click on the page and select Properties. Look at the Address
(URL) field to find the name of the web page (with the .html extension), for example, WepPage.html. Enter
the full name, with the .html extension, in the Default Web Page register.
Using ION Setup
1.
Open ION Setup and connect to your meter in Advanced Mode. 2.
Navigate to the Comm Module folder and double‐click on the Ethernet module in the right‐hand pane.
3.
Select the Setup Registers tab, select the Default Web Page register and click Edit.
4.
Type the name of the new default home page (including the .html extension) and click OK.
5.
Click Send to save your changes to the meter.
Using ION Enterprise
1.
Connect to your meter in Designer and open the Communications Setup folder.
2.
Right‐click in the center of the Ethernet module. The ION Module Setup screen appears. 3.
Double‐click the Default Web Page setup register and enter the name of the new default home page (including the .html extension).
4.
Select Send & Save to save your changes to the meter.
Creating Custom Web Pages
The Web Page module is used to create custom pages with parameters that you specify. These pages can be created as either HTML or XML. The XML pages display only XML code in the browser unless they are linked to an XSLT stylesheet.
Custom Web Page Setup
The Web Page module has the following setup registers: Page Title: The title (and link text) for the customized web page.
Page Location: The location (or address) of the web page. XSLT Stylesheet1: The URL where the XSLT stylesheet is located (optional).
Page 4
© 2007 Schneider Electric. All rights reserved.
WebMeter Internal Web Server Feature
Creating Custom Web Pages
Gatewayed Device Namespace1: The namespace attribute in the Device element of XML messages generated by the module. Gatewayed Device Name1: The name attribute in the Device element of XML messages generated by the module. HTML Refresh Rate: How often (in seconds) the web page is updated or refreshed when viewed in a browser.
HTTP Expires: The length of time after which the web page expires, in seconds.
1
These registers only apply to XML web pages Refer to the ION Reference for more information on using the Web Page module. Creating Custom Web Pages
Use ION software to create custom web pages.
Using ION Setup to create custom web pages
1.
Open ION Setup and connect to your meter in Advanced Mode. 2.
Navigate to the Web Page Module folder.
3.
Select Insert > Module and double‐click on the Web Page module that appears in the right‐hand pane to configure.
4.
Select a source and click Edit to link the module to the parameters you want to view via the web page.
5.
On the Setup Registers tab, select a register and click Edit to configure the module. See “Custom Web Page Setup” on page 4 for a list of setup registers and their functions.
6.
Click Send to save your changes to the meter.
Using ION Enterprise to create custom web pages
© 2007 Schneider Electric. All rights reserved.
1.
Open the meter in Designer.
2.
Drag a Web Page module from the Toolbox.
Page 5
Configuring Your Meter
WebMeter Internal Web Server Feature
3.
Right‐click the module to enter setup. See “Custom Web Page Setup” on page 4 for a list of setup registers and their functions,
To change the module Label (name) from its default setting, check “Use Custom Label” and enter the new name.
To change a Register Label (name) from its default setting, double‐click on the register, check “Use Custom Label” and enter the new name.
To change a Register Value from its default setting, double‐click on the register, then enter the new value. 4.
Link the source inputs of the Web Page module to the outputs of other modules that you want to view via the web page. You can have up to 50 sources per Web Page module.
5.
Click Send & Save to save your changes to the meter.
Configuring Your Meter
Use the Setup and Network Setup pages to configure your meter via a web browser.
If security is enabled, you must enter a user name and the meter password when you change a parameter. Security is enabled by default. Contact your ION software administrator for a user name and the meter password.
NOTE
If you try to configure a meter when meter configuration via a web browser is disabled, an error message
displays. To enable meter configuration via a web browser, see “Enabling/Disabling Meter Web Browser
Configuration” on page 8.
Since every meter family has different default web pages, the following instructions may not be exactly the same as for your meter.
Page 6
© 2007 Schneider Electric. All rights reserved.
WebMeter Internal Web Server Feature
Using the Setup Page
Using the Setup Page
Use the setup page to change various power measurement parameters and nameplate information for your meter.
Configuring your meter with the Setup page
1.
Start your web browser.
2.
Enter the meter’s IP address into the browser’s Address field. The default meter home page appears.
NOTE
If Advanced Security is enabled on your meter, you must enter a user name and password before the
meter home page appears. To configure your meter with a web browser, your user name and password
must have “Full Meter Config Access” on the meter.
3.
Click the Setup link to access the Setup page (or pages).
4.
Change the parameters you want to modify. Once you are satisfied with your changes, proceed to step 5.
Undo Changes
To undo your changes, revert to the previous settings by clicking another link on the page and then returning to the Setup page. Using your browser’s Back button does not undo changes.
5.
Click Save. Depending on your meter and its security settings, you may need to enter a user name and the meter password. If requested, enter them and click OK.
The Setup Confirmation screen appears. This screen shows all the parameters, including your changes.
Using the Network Setup Page
The Network Setup page is available on selected meters. Use the Network Setup page to configure your meter’s network settings.
CAUTION
Some changes made to your network settings can result in loss of communication with your meter. Be
sure to note existing settings before changing them, in case you need to re-establish communications.
Configuring your meter with the Network Setup page
© 2007 Schneider Electric. All rights reserved.
1.
Start your web browser.
2.
Enter the meter’s IP address into the browser Address field. The default meter home page appears.
3.
Click on the Network Setup link to access the Network Setup page.
4.
Change the parameters you want to modify. Once you are satisfied with your changes, proceed to step 5. Page 7
Setup Errors
WebMeter Internal Web Server Feature
Undo Changes
To undo your changes, revert to the previous settings by clicking another link on the page and then returning to the Network Setup page. Using your browser’s Back button does not undo changes.
5.
Click Save. Depending on your meter and its security settings, you may need to enter a user name and the meter password. If requested, enter them and click OK.
The Network Setup Confirmation screen appears. This screen shows all the parameters, including your changes.
NOTE
When changing settings on the Network Setup page, there can be a small communication delay with your
meter. Wait a few seconds before you attempt to navigate to other pages or make other configuration
changes. The length of delay depends on your network configuration and conditions.
Setup Errors
If an error occurs when you attempt to save the new settings to the Setup or Network Setup page, an error message displays. The error message and a brief description of the error display on the confirmation page. Any parameters which are not successfully set are highlighted in red and remain unchanged on the meter.
If you still want to change the parameter values, determine the cause of each error (e.g. incorrect parameter value). Then, using your browserʹs Back button, return to the Setup or Network Setup page and attempt the changes again.
For more information regarding error messages, contact Technical Support.
Enabling/Disabling Meter Web Browser Configuration
Enable and disable web browser configuration of the meter using ION software or the meter’s front panel.
Using the front panel
Refer to your meter’s User Guide for information on how to enable/disable web browser configuration of the meter using the front panel. Using ION Setup
Page 8
1.
Open ION Setup and connect to your meter in Advanced Mode. 2.
Navigate to the Comm Module folder and double‐click on the Ethernet module in the right‐hand pane.
3.
Select the Setup Registers tab. Select the Webserver Config Access register and click Edit.
4.
Select Enabled or Disabled and click OK.
5.
Click Send to save your changes to the meter.
© 2007 Schneider Electric. All rights reserved.
WebMeter Internal Web Server Feature
Enabling/Disabling Meter Web Server Functionality
Using ION Enterprise
1.
Open the meter in Designer and open the Communications Setup folder.
2.
Right‐click in the center of the Ethernet module. The ION Module Setup screen appears. 3.
Double‐click the Webserver Config Access setup register and change the value to “Enabled” or “Disabled”.
4.
Click Send & Save to save your changes to the meter.
Enabling/Disabling Meter Web Server Functionality
Enable and disable the web server functionality of the meter using ION software or the meter’s front panel.
Using the front panel
Refer to your meter’s User Guide for information on how to enable/disable web server functionality of the meter using the front panel.
Using ION Setup
1.
Open ION Setup and connect to your meter in Advanced Mode. 2.
Navigate to the Comm Module folder and double‐click on the Ethernet module in the right‐hand pane.
3.
Select the Setup Registers tab, select the Enable Webserver register and click Edit.
4.
Select Yes or No and click OK.
5.
Click Send to save your changes to the meter.
Using ION Enterprise
© 2007 Schneider Electric. All rights reserved.
1.
Open the meter in Designer and open the Communications Setup folder.
2.
Right‐click in the center of the Ethernet module. The ION Module Setup screen appears. 3.
Double‐click the Enable Webserver setup register and change the value to “Yes” or “No”.
4.
Click Send & Save to save your changes to the meter.
Page 9
Using WebMeter in a Modbus Network
WebMeter Internal Web Server Feature
Using WebMeter in a Modbus Network
Below is a typical application of the WebMeter feature in a Modbus Network.
Modbus Master Device
IP Address: 192.168.1.5
Ethernet
RS-485
(Modbus network)
Modbus Slave Device
Unit ID: 113
Location: Office
HTML web page
Factory Module
Office
Label
Value 1
Label
Value 2
Label
Value 3
Device Namespace = Miami.CompanyX
Device Name - MainMeter
Web Page Module
Value 1
Modbus Import
Module
Value 2
Value 3
Slave Addr = 113
http://192.168.1.5/Office.html
Source 1
Source 2
Source 3
XML web page
Gatewayed Device Namespace = Default
Gatewayed Device Name = Office
Page Location = Office
<Device label=”Office”
xlink:type=”locator”
xlink:href=”http://
192.168.1.5/Office.xml”
device Type:”7350”...>
<Data updateTime = “07/
26/02 8:31:36 AM”>
<D ...value=”Value 1”/>
<D ...value=”Value 2”/>
<D ...value=”Value 3”/>
</Data>
</Device>
http://192.168.1.5/Office.xml
Hardware
In this example, the ION7550 meter is WebMeter enabled, and is acting as Modbus master to the ION7300 meter (acting as Modbus slave). The IP Address of the
ION7550 meter is 192.168.1.5 and it is also connected to the workstation PC via the Ethernet.
The ION7300 meter’s Unit ID is 113 and its location is Office. It is serially connected to the ION7550 meter using RS‐485 cable.
Framework
The framework for the ION7550 meter shows how the different modules are configured to produce a custom web page for the ION7300 meter.
Page 10
© 2007 Schneider Electric. All rights reserved.
WebMeter Internal Web Server Feature
Using WebMeter in a Modbus Network
Factory Module
The Factory module has been configured so that the setup register Device Namespace value is “Miami.CompanyX” and the setup register Device Name value is “MainMeter”.
Modbus Import Module
Three values (Value 1, 2 and 3) are imported from the ION7300 meter via the Modbus Import module. These values are then linked to the Web Page module for display on the web page. The Slave Addr setup register’s value is “113” which corresponds to the Unit ID of the Slave meter.
Web Page Module
The Web Page module has Values 1, 2 and 3 for its sources. Setup register Gatewayed Device Namespace has a default value which means the register inherits the value from the Factory module’s Device Namespace setup register. In this example, the value is “Miami.CompanyX”. Setup register Gatewayed Device Name value is “Office”. This value is important if more than one gatewayed device is sending XML data to the Web Page module. Otherwise, it can be left as default in which case the register inherits the value from the Factory module’s Device Name setup register. In this example, the value would be “MainMeter”.
The value of the Page Location setup register is “Office”. Since the ION7550 meter’s IP Address is 192.168.1.5, the web page for the ION7300 meter is found at: http://192.168.1.5/Office.html (or .xml).
© 2007 Schneider Electric. All rights reserved.
Page 11