NTCL01 Termination Unit (Introduction)

NTCL01 Termination Unit (Introduction)
SECTION 1 - INTRODUCTION
INTRODUCTION
The Communication Termination Unit (NTCL01) provides a termination point for a Network Interface Slave Module (INNIS01)
or a Loop Interface Module (INLIM03). The TCL gives the option
of using twinaxial or coaxial cable to connect the NIS to the
INFI-NET communication network or the LIM to Plant Loop.
Jumper settings on the TCL select the type communication
cable. Figure 1-1 shows an example of the NTCL01 within a
PCU on the INFI-NET communication network.
INTENDED USER
Technicians should read the manual before installing and
operating the TCL. Do not put the TCL into operation until you
read and understand this instruction.
OIS
INFI-NET
10 MBAUD
PROCESS
CONTROL UNIT
PCU
NTCL01
INNIS01 INNPM01
CONTROLWAY (1 MBAUD)
MFP
MFP
MFP
UP TO 32
MODULES
MFP
MFP
T00760A
Figure 1-1. The NTCL01 within a PCU on INFI-NET
I-E96-422A
INTRODUCTION
1-1
INTRODUCTION
®
HARDWARE DESCRIPTION
The TCL attaches to a Field Termination Panel (NFTP01), inside
the INFI 90® cabinet, with two mounting screws and one
ground screw. It is a printed circuit board that consists of:
•
•
•
•
•
Terminal strips
BNC connectors
Electronic components
Jumpers
Fuse
FEATURES
The NTCL01 provides connectors for both twinaxial cable and
coaxial cable. Jumpers on the circuit board set the impedance
to match the communication cable. The +24 VDC supplied to
the board is fused, protecting the electronic circuitry on board.
INSTRUCTION CONTENT
This manual has five sections and two appendices.
Introduction
Installation
Maintenance
Repair/Replacement
Procedures
Provides an overview of the TCL.
Explains physical installation, wiring and cable requirements,
jumper settings, etc.
Contains a maintenance schedule.
Explains how to replace the fuse or the module.
Support Services
Explains training, documentation and how to order parts from
Bailey Controls.
Appendices
Briefly discuss the modules that can use the TCL and provide a
cross-reference of dipswitch and jumper settings for those
modules.
HOW TO USE THIS MANUAL
Read this manual before installing the TCL. Do the installation
steps in order. Do not operate the TCL until you complete all
the steps in this section. Refer to the appendices for specific
module and cable questions.
® Registered trademark of Elsag Bailey Process Automation.
HARDWARE DESCRIPTION
1-2
I-E96-422A
INTRODUCTION
GLOSSARY OF TERMS AND ABBREVIATIONS
Term
Definition
FTP
Field Termination Panel. A panel inside the INFI 90 cabinet on which to mount termination units.
TU
Termination Unit. Provides input/output connection between plant equipment and the
INFI 90/Network 90 process modules.
Coaxial cable
A special type of communications cable that can transmit data at high speed.
Twinaxial cable
A cable composed of two insulated conductors that are twisted together and attached
or bound with a common covering.
NOMENCLATURE
Hardware
Nomenclature
Network Interface Slave Module
Loop Interface Module
INNIS01
INLIM03
Cables
Twinaxial Communication Cable
(PVC, lugs at both ends)
(non-PVC, lugs at both ends)
NKPL01
NKPL02
TCL to INFI-NET Adapter Cable
NKTL01-3
Coaxial Communication Cable
(PVC, BNC connectors)
(non-PVC, BNC connectors)
NKCL01
NKCL02
TCL to TCL Cable
NKTT01
TCL to LIM Cable
(PVC)
(non-PVC)
NKLS03
NKLS13
TCL to NIS Cable
(PVC)
(non-PVC)
NKLS01
NKLS11
Field Termination Panel
NFTP01
REFERENCE DOCUMENTS
Document No.
I-E96-422A
Document
I-E96-601
INFI-NET Communications Modules
I-E96-605
Bus Interface Module/Loop Interface Module
GLOSSARY OF TERMS AND ABBREVIATIONS
1-3
INTRODUCTION
®
SPECIFICATIONS
Power Requirements
Voltage
24 VDC
Current
19.7 mA maximum
15.8 mA typical
Mounting
Screw mounts to the field termination panel.
Cooling Requirements
No cooling necessary when used in Bailey cabinets and operated within
stated environmental limits.
Operating Temperature
0o to 70oC (32o to 158oF).
Relative Humidity
5% to 90% (± 5%) up to 55oC (131oF) noncondensing.
5% to 40% (± 5%) up to 70oC (158oF) noncondensing.
Air Quality
Bailey equipment should be operated and stored in a noncorrosive environment.
Certification
CSA certified as process control equipment for use in an ordinary (nonhazardous) location.
Specifications are subject to change without notice.
SPECIFICATIONS
1-4