Supervisory Omron OMRONFINS Server

Supervisory Omron OMRONFINS Server
Wonderware Operations Integration – Supervisory
Omron OMRONFINS Server (G-1.2 Series)
Contents
Contents
WONDERWARE OPERATIONS INTEGRATION - SUPERVISORY OMRON
OMRONFINS SERVER (G-1.2 SERIES)............................................................... 3
Legal Information........................................................................................................................................................................... 4
Technical Support.......................................................................................................................................................................... 5
Introduction to the OMRONFINS OI Server................................................................................................................................. 6
Configuring the OMRONFINS OI Server...................................................................................................................................... 7
Direct Serial Communication and Serial Encapsulation........................................................................................................ 7
Configuring a Channel's Communication Settings................................................................................................................ 8
Setting a Device's Station ID.................................................................................................................................................9
OMRONFINS OI Server Reference............................................................................................................................................ 11
Item Reference Syntax........................................................................................................................................................ 11
Address Descriptions............................................................................................................................................................12
Supported Data Types......................................................................................................................................................... 12
Examples of Item References..............................................................................................................................................13
OMRONFINS OI Server Error Codes......................................................................................................................................... 16
Page 2
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server
(G-1.2 Series)
This document describes the technical specifications and configuration options for the Wonderware®
Operations Integration - Supervisory Omron OMRONFINS Server (or OMRONFINS OI Server, for short).
Last revision 2016-06-14
Page 3
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Legal Information
©
2016 Schneider Electric Software, LLC. All Rights Reserved.
No part of this documentation shall be reproduced, stored in a retrieval system, or transmitted by any
means, electronic, mechanical, photocopying, recording, or otherwise, without the prior written permission of
Schneider Electric Software, LLC. No liability is assumed with respect to the use of the information contained
herein.
Although precaution has been taken in the preparation of this documentation, Schneider Electric Software,
LLC assumes no responsibility for errors or omissions. The information in this documentation is subject to
change without notice and does not represent a commitment on the part of Schneider Electric Software, LLC.
The software described in this documentation is furnished under a license agreement. This software may be
used or copied only in accordance with the terms of such license agreement.
ArchestrA, Avantis, DYNSIM, EYESIM, InBatch, InduSoft, IntelaTrac, InTouch, PIPEPHASE, PRO/II,
PROVISION, ROMeo, Schneider Electric, SIM4ME, SimCentral, SimSci, Skelta, SmartGlance, Spiral Software,
VISUAL FLARE, WindowMaker, WindowViewer, and Wonderware are trademarks of Schneider Electric SE, its
subsidiaries, and affiliated companies. An extensive listing of Schneider Electric Software, LLC trademarks
can be found at: http://software.invensys.com/legal/trademarks/. All other brands may be trademarks of
their respective owners.
Schneider Electric Software, LLC
26561 Rancho Parkway South
Lake Forest, CA 92630 U.S.A.
(949) 727-3200
http://software.invensys.com/
For comments or suggestions about the product documentation, send an e-mail message to
ProductDocumentationComments@schneider-electric.com.
Page 4
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Technical Support
Wonderware Technical Support offers a variety of support options to answer any questions on Wonderware
products and their implementation.
Before you contact Technical Support, refer to the relevant section(s) in this documentation for a possible
solution to the problem. If you need to contact technical support for help, have the following information
ready:
•
The type and version of the operating system you are using.
•
Details of how to recreate the problem.
•
The exact wording of the error messages you saw.
•
Any relevant output listing from the Log Viewer or any other diagnostic applications.
•
Details of what you did to try to solve the problem(s) and your results.
•
If known, the Wonderware Technical Support case number assigned to your problem, if this is an ongoing
problem.
Page 5
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Introduction to the OMRONFINS OI Server
These are the technical specifications for Wonderware Operations Integration - Supervisory Omron
OMRONFINS Server.
Requirements
OMRONFINS OI Server requires Wonderware Operations Integration – Core G-1.2 or later.
Supported hardware and software
This OI Server connects to Omron PLCs on a FINS network, which includes the following devices:
•
CS1, CJ1, CJ2, and CP1 series using CS1 mode;
•
CV, CVM1, and CVM1D series using CV mode;
•
Any other device that is FINS compatible.
For Ethernet communication, CS1 PLCs can use either the FINS – UDP (Ethernet) protocol or the RS-232
protocol. (The specific protocol can be selected in the communication settings.) .
For serial communication, CS1 PLCs use a FINS – Hostlink.
To program CS1 PLCs, you need the CX-Programmer programming software. For more information, go to:
http://industrial.omron.eu/en/products/catalogue/automation_systems/software/configuration/cx-one/cxprogrammer.html
Note: Unsolicited messaging is not supported by this OI Server. In other words, this OI Server
cannot receive unsolicited messages that are sent by Omron PLCs.
Conformance
The following hardware and software was used for conformance testing of this OI Server.
Configuration :
Page 6
•
Device: SYSMAC CJ1M (CPU12)
•
Module Port: 10Base-T Ethernet
•
Module IP Address: 10.13.63.89
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Configuring the OMRONFINS OI Server
Each server instance has its own hierarchy of objects, and each object has parameters that you need to
configure in order to establish communication between the OI Server and individual devices on the network.
You can view a OMRONFINS server instance's configuration hierarchy under its Configuration node.
This section only describes how to configure object parameters for a OMRONFINS server instance. For more
general information about adding and configuring objects, see "Configuring Your OI Server" in the Operations
Integration Server Manager Help.
Direct Serial Communication and Serial Encapsulation
This OI Server supports direct serial communication with the target device, as well as serial encapsulation
over a TCP/IP or UDP/IP network link.
Direct serial communication requires that the target device be directly connected to the computer that
is running this OI Server. If you plan to use direct serial communication, you need to know the serial
communication settings (e.g., baud rate, parity, etc.) that have been configured on the device, because you
must configure this OI Server to match those settings.
Serial encapsulation enables serial communication with a target device that is connected to a terminal server
on your TCP/IP or UDP/IP network. The terminal server is like a virtual serial port: it converts TCP or UDP
messages to serial data and then relays them to the connected device. If you plan to use serial encapsulation,
the target device should already be connected to the terminal server, and you need to know the IP address of
the terminal server and the port number assigned to the device.
Serial encapsulation over a TCP/IP or UDP/IP link
All of the serial communication settings are included in the OI Server's channel parameters.
To configure the serial communication settings for a channel:
1. In the Operations Integration Server Manager, navigate to the ChannelSelector object that you want to
configure:
a) Expand the Operations Integration Server Manager, expand the node group, expand Local (or the remote
computer name), and then expand Operations Integration Supervisory Servers.
b) Locate and expand Omron - OMRONFINS, and then expand its Configuration node.
c) Select the ChannelSelector object that you want to configure.
The channel parameters are displayed in the details pane on the right.
2. In the Serial Encapsulation box, select the encapsulation mode:
Option
Description
None
Direct serial communication with the device.
TCP/IP
Serial encapsulation over a TCP/IP Ethernet
connection.
UDP/IP
Serial encapsulation over a UPD/IP Ethernet
connection.
3. If you selected None above, configure the direct serial communication settings:
a) In the COM box, select the COM port to which the target device is connected.
Page 7
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
b) In the Baud Rate, Data Bits, Stop Bits, and Parity boxes, configure the serial communication settings to match
the settings that have already been configured on the target device.
4. If you selected either TCP/IP or UDP/IP above, configure the serial encapsulation settings:
a) In the IP Address box, type the IP address of the terminal server.
b) In the Port Number box, type the port number on the terminal server that has been assigned to the target
device.
c) If you want to make the target device responsible for establishing communication with this OI Server,
select Server Mode.
Note: This option is not available for UDP/IP.
5. Proceed with configuring the rest of the channel parameters, as described in this documentation.
Configuring a Channel's Communication Settings
Configure the communication settings for a selected channel to ensure uninterrupted communication with
the device network.
Connection
The specific transport protocol to be used. Select one of the following options:
Option
Description
UDP
UDP/IP Ethernet network
Serial
Direct serial communication
If you select Serial, you must also configure the serial communication settings above.
Mode
The FINS compatibility mode, which determines the types of Omron devices that the OI Server
can communicate with. Select one of the following options:
Option
Description
CS1
CS1, CJ1, CJ2, CP1 series
CV
CV, CVM1, CVM1D series
Ignore Non Fatal PLC Error
The error mode, determines whether to ignore non-fatal errors on devices. Select one of the
following options:
Option
Description
No
When a non-fatal error happens on a device, the channel shows
status code 64 and all device items are set to BAD quality.
Yes
When a non-fatal error happens on a device, the channel shows
status code 0 (no errors) and sends a warning message to the log. All
the device items stay at GOOD quality.
Advanced
Click this button to open the Advanced Settings dialog box, which provides access to additional
communication settings such as timeouts, retries, and buffer sizes. You might need to change
these settings if the OI Server behaves unexpectedly during run time, but the default settings
should work for most network configurations. For more information about these settings, see
"Advanced Settings" in OI Server Manager Help.
Page 8
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Setting a Device's Station ID
Set the station ID for a selected device so that the OI Server can identify and communicate with it on the
network.
Syntax
For Ethernet communication, the device's station ID must use the following syntax:
[IP address]:[port number]:<subnet>:<node>:[unit ID]:[mode]
For serial communication, the device's station ID must use the following syntax:
<subnet>:<node>:[unit ID]
The following syntax diagram shows all of the possible options:
{ | IP address:port number: } subnet:node { | :unit ID { | : { CS1 | CV } } }
IP address
The IP address of the device on your UDP/IP Ethernet network.
port number
The port number used by the FINS protocol on the device. It is typically 9600, but it can be
changed in the device settings.
subnet
The FINS subnet (0–127) to which the device belongs.
node
The device’s node number (1–128) on the specified FINS subnet.
unit ID
The ID number used for PC interface, as configured in the PLC program.
This parameter is optional; if no value is specified, the default value is 0.
Note: This is not the Unit ID that is configured in the device's hardware settings.
mode
The FINS compatibility mode, which can be one of the following:
Option
Description
CS1
CS1, CJ1, CJ2, CP1 series
CV
CV, CVM1, CVM1D series
When you specify a mode for a single device, it overrides the global Mode setting that you
previously configured in the channel's communication settings.
This parameter is optional; if no value is specified, the global setting is used by default.
Notes
This OI Server does not support simultaneous connections when communicating with devices that use either
the old Ethernet communication modules (e.g., CS1W-ETN01, CS1W-ETN11, CJ1W-ETN11) or the new
Ethernet communication modules that have "ETN11-compatible mode" enabled (e.g., CS1W-ETN21, CJ1WETN21). To work around this limitation, configure each device to use a different port number for the FINS
protocol (e.g., 9600, 9601), and then when you specify the station ID for each device, include the complete IP
address and port number (e.g., 192.168.1.10:9600, 192.168.1.20:9601).
Page 9
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
This OI Server should support simultaneous connections when communicating with devices that use only the
new Ethernet communication modules that are able to send responses to the source, even if the port number
used by the FINS protocol on the source is different from port numbers used by the FINS protocol on the
target devices. However, you must make sure those modules do not have "ETN11-compatible mode" enabled.
Examples
Examples of valid station IDs:
192.168.2.4:9600:1:2:1:C
0:1:0
Page 10
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
OMRONFINS OI Server Reference
Use item references to access data stored in memory registers in connected devices, as well as to access
standard system items in the OI Server itself.
This section only describes the item reference syntax and options for the OMRONFINS server. For more
general information about item references, see "Managing Device Items" and "Item Reference Descriptions" in
the Operations Integration Server Manager Help.
Item Reference Syntax
Item references in this OI Server use the following syntax.
For all multi-byte memory registers, use the following syntax:
<register type><address>@[data type]
<register type><address>[data suffix]
For bit-accessible memory registers — i.e., all types except PVC and PVT — use the following syntax:
<register type><address>:<bit>
<register type><address>.<bit>
For strings, use the following syntax:
<register type><starting address>-<register type><ending address>C
The following syntax diagram shows all of the possible options:
{ { CIO | A | H | W | D | EMarea }address (or starting address){ { @Short | S } | { @BCD | B } | { @Long
| L } | @DWord | { @LBCD | M } | { @Float | F } | { : | . }bit | -{ CIO | A | H | W | D | EMarea }ending
addressC } | { PVC | PVT }address (or starting address){ { @Short | S } | { | @Word | U } | { @BCD | B } |
-{ PVC | PVT }ending addressC } }
register type
The register type or memory area. For extended data memory (EM), the available areas include A
through M.
address
The specific memory address on the device.
data type / data suffix
The formatted data type of the value read from the device memory.
This parameter is optional; if the data type is not specified, the value will be formatted as Word
(i.e., unsigned,16-bit decimal) by default.
bit
The specific bit number in the memory address. Bit 0 is the low bit. Bit 15 is the high bit.
starting address, ending address
The starting and ending addresses of a string. Strings are stored as ASCII data. Each two-byte
register contains two characters, and the string length can be from 1 to 40 registers (i.e., 2 to 80
characters).
Page 11
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Address Descriptions
The address descriptions consist of the register type, its item name and the allowable range of values, the
default data type, allowable suffixes (if any), and allowable access methods.
Register Type
Item Reference
Length
Data Types
Access
0000 to 6143
2 Bytes
Short, BCD
Read/Write
0000 to 6142
4 Bytes
Long, DWord,
LBCD, Float
Read/Write
0000.00 to 6143.15
1 Bit
Boolean
Read/Write
000 to 447
2 Bytes
Short, BCD
Read only
448 to 959
2 Bytes
Short, BCD
Read/Write
000 to 446
4 Bytes
Long, DWord,
LBCD, Float
Read only
448 to 958
4 Bytes
Long, DWord,
LBCD, Float
Read/Write
000.00 to 447.15
1 Bit
Boolean
Read only
448.00 to 959.15
1 Bit
Boolean
Read/Write
000 to 511
2 Bytes
Short, BCD
Read/Write
000 to 510
4 Bytes
Long, DWord,
LBCD, Float
Read/Write
000.00 to 511.15
1 Bit
Boolean
Read/Write
000 to 511
2 Bytes
Short, BCD
Read/Write
000 to 510
4 Bytes
Long, DWord,
LBCD, Float
Read/Write
000.00 to 511.15
1 Bit
Boolean
Read/Write
0000 to 32767
2 Bytes
Short, BCD
Read/Write
0000 to 32766
4 Bytes
Long, DWord,
LBCD, Float
Read/Write
0000.00 to 32767.15
1 Bit
Boolean
Read/Write
A0000 to M32767
2 Bytes
Short, BCD
Read/Write
A0000 to M32766
4 Bytes
Long, DWord,
LBCD, Float
Read/Write
A0000.00 to M32767.15
1 Bit
Boolean
Read/Write
Item Name
Address Range
CIO
CIO
A or AR
Auxiliary Relay
H or HR
Holding Relay
W
Working Relay
D or DM
Data Memory
Expansion Data Memory
EM
Present Value Counter
PVC
0000 to 4095
2 Bytes
Short,
Word, BCD
Read/Write
Present Value Timer
PVT
0000 to 4095
2 Bytes
Short,
Word, BCD
Read/Write
Notes
Supported Data Types
The data type is specified as a suffix in the item syntax. This OI Server supports the following data types.
Page 12
Data Type
Suffix
Description
Range of Values
Boolean
by bit
Single bit.
0 or 1
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Data Type
Suffix
Description
Range of Values
Short
@Short, S
Signed, 16-bit decimal. Bit 0 is the low bit. Bit 14 is the
high bit. Bit 15 is the sign bit.
-32768 to 32767
Word
@Word, U
Unsigned, 16-bit decimal. Bit 0 is the low bit. Bit 15 is
the high bit.
0 to 65535
Long
@Long, L
Signed, 32-bit decimal. Bit 0 is the low bit. Bit 30 is the
high bit. Bit 31 is the sign bit.
-2147483648 to 2147483647
DWord
@DWord
Unsigned, 32-bit decimal. Bit 0 is the low bit. Bit 31 is
the high bit.
0 to 4294967295
Float
@Float, F
32-bit real number.
N/A
BCD
@BCD, B
Two-byte packed BCD. Value range is 0–9999.
Behavior is undefined for values beyond this range.
0 to 9999
LBCD
@LBCD, M
Four-byte packed BCD. Value range is 0–99999999.
Behavior is undefined for values beyond this range.
0 to 99999999
String
C
Null terminated ASCII string.
2 to 80 characters per string
Notes
Examples of Item References
These are examples of valid item references for this OI Server. For more information about the referenced
addresses, see the manufacturer's documentation for your device.
Register Type
Address on the Device
Item Reference
CIO
CIO5000 as Short
CIO5000@Short
CIO5000S
CIO5000 as BCD
CIO5000@BCD
CIO5000B
CIO5000 as Long
CIO5000@Long
CIO5000L
CIO5000 as DWord
CIO5000@DWord
CIO5000 as LBCD
CIO5000@LBCD
CIO5000M
CIO5000 as Float
CIO5000@Float
CIO5000F
Auxiliary Relay
CIO5000 as Bit
CIO5000.00
CIO5000 as String (length of 8 chars)
CIO5000-CIO5003C
A000 as Short
A000@Short
A000S
A000 as BCD
A000@BCD
A000B
A000 as Long
A000@Long
A000L
A000 as DWord
A000@DWord
A000 as LBCD
A000@LBCD
Page 13
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Register Type
Address on the Device
Item Reference
A000M
A000 as Float
A000@Float
A000F
Holding Relay
A000 as Bit
A000.00
A000 as String (length of 8 chars)
A000-A003C
H023 as Short
H23@Short
H23S
H023 as BCD
H23@BCD
H23B
H023 as Long
H23@Long
H23L
H023 as DWord
H23@DWord
H023 as LBCD
H23@LBCD
H23M
H023 as Float
H23@Float
H23F
Working Relay
H023 as Bit
H23.00
H023 as String (length of 8 chars)
H23-H26C
W500 as Short
W500@Short
W500S
W500 as BCD
W500@BCD
W500B
W500 as Long
W500@Long
W500L
W500 as DWord
W500@DWord
W500 as LBCD
W500@LBCD
W500M
W500 as Float
W500@Float
W500F
Data Memory
W500 as Bit
W500.00
W500 as String (length of 8 chars)
W500-W503C
D00102 as Short
D102@Short
D102S
D00102 as BCD
D102@BCD
D102B
D00102 as Long
D102@Long
D102L
Page 14
D00102 as DWord
D102@DWord
D00102 as LBCD
D102@LBCD
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
Register Type
Address on the Device
Item Reference
D102M
D00102 as Float
D102@Float
D102F
Expansion Data Memory
D00102 as Bit
D102.00
D00102 as String (length of 8 chars)
D102-D105C
EMA00200 as Short
EMA00200@Short
EMA00200S
EMA00200 as BCD
EMA00200@BCD
EMA00200B
EMA00200 as Long
EMA00200@Long
EMA00200L
EMA00200 as DWord
EMA00200@DWord
EMA00200 as LBCD
EMA00200@LBCD
EMA00200M
EMA00200 as Float
EMA00200@Float
EMA00200F
Present Value Counter
EMA00200 as Bit
EMA00200.00
EMA00200 as String (length of 8 chars)
EMA00200-EMA00203C
PVC100 as Short
PVC100@Short
PVC100S
PVC100 as Word
PVC100
PVC100@Word
PVC100U
PVC100 as BCD
PVC100@BCD
PVC100B
Present Value Timer
PVC100 as String (length of 8 chars)
PVC100-PVC103C
PVT123 as Short
PVT123@Short
PVT123S
PVT123 as Word
PVT123
PVT123@Word
PVT123U
PVT123 as BCD
PVT123@BCD
PVT123B
PVT123 as String (length of 8 chars)
PVT123-PVT126C
Page 15
Wonderware Operations Integration - Supervisory Omron OMRONFINS Server (G-1.2 Series)
OMRONFINS OI Server Error Codes
The following tables describe the additional error codes that you might receive when poll/poke requests and
operations fail.
Code
Description
Possible Causes
Solution
0
OK
Communication without problems.
Not applicable.
1
Invalid Unit
Unit number in the address field exceeds 31.
Fix the unit number, for serial connection the unit cannot
exceed 31.
2
Fail to allocate memory
The driver could not allocate memory.
•
Check the buffer configuration in the communication
settings and try to reduce the size.
•
Increase the amount of RAM memory available on your
PC or HMI.
3
Invalid Answer
The answer received from the PLC has less
bytes than expected.
This error should never happen unless the OI Server is
connected to an unsupported device.
4
RX Buffer Overflow
The number of bytes sent by the PLC exceeds
the configured buffer size.
Increase the buffer size in the communication settings.
5
Invalid Message Size
The answer sent by the PLC does not have
the expected size.
This error should never happen unless the driver is connected
to an unsupported device.
33281
Invalid Subnet
The subnet configured in the Station field is
invalid.
Check if the subnet configured in the station is correct and that
the subnet is properly configured in the PLC routing table.
-34
Invalid Address
Invalid address specified in Address field
Specify a valid address.
-38
Invalid Station
Invalid station specified in Station field.
Specify a valid station number.
-15
Timeout waiting to start a
message.
•
Disconnected cables.
•
Check the cable wiring.
•
PLC is turned off, or it is in Stop or Error
mode.
•
Check the PLC state. It must be in Run mode.
•
Incorrect station number.
•
Check the station number.
•
Incorrect RTS/CTS control settings.
•
Check the RTS/CTS control settings in thechannel
settings.
•
PLC in Stop or Error mode.
•
Check the cable wiring.
•
Incorrect station number.
•
Check the PLC state. It must be in Run mode.
•
Incorrect parity.
•
Check the station number.
•
Incorrect RTS/CTS control settings.
•
Check the RTS/CTS control settings in thechannel
settings.
-17
Code
0
-15
Page 16
Timeout between rx
char.Invalid Block Size
Description
Possible Causes
Solution
OK
Communicating without error.
None required.
Timeout waiting for message
to start
•
Disconnected cables.
•
Check cable wiring.
•
PLC is turned off, in stop mode, or in
error mode.
•
Check the PLC mode — it must be RUN.
•
Wrong station number.
•
Check the station number.
•
Wrong parity (for serial communication).
•
Increase the timeout in the driver's advanced settings.
•
Wrong RTS/CTS configuration (for serial
communication).
•
Check the RTS/CTS configuration (for serial
communication).