Ruggedized, Fan less, Waterproof Uninterruptible
Smaller Footprint!
Space Saving Design
SX560
SX=Super Extreme Environment
Ruggedized, Fan less,
Waterproof Uninterruptible
Power for Traffic, IT &
Security Applications
Industry proven, on-line protection, 100% of the time,
for reliable and continuous error-free operation,
regardless of utility power quality.
The CLARY SX560 is a 400W/560VA 120VAC power source for electronics
equipment in IT, Traffic, and Security applications. The SX560 delivers
Quick Read Features:
• Space Saving Design: 1U Vertical
constant, conditioned, regenerated AC power which protects equipment
from being disrupted, degraded or damaged due to harmful power events.
CLARY power conditioning completely isolates the cabinet from utility power
enabling error-free operation during surges, sags, spikes, and other power
anomalies. With an optional battery pack, the SX560 system operates as an
Rack Space
• On-Line, Conditioned, Regenerated
Power for Cabinet Equipment
Protection
• USB Connectivity with Monitoring
Center or Other Equipment
On-Line, Double-Conversion UPS that extends the reliability of the cabinet’s
• Power Factor Corrected for
electronics during utility power failures (black-outs). The SX560 is Power
Factor Corrected to reduce utility current draw and wiring requirements.
Reliable & Safe Power
• Operates in Extreme Environments
from -40°C to +74°C (-40°F to
Designed for harsh environments with no forced air cooling. The fully sealed
enclosure will meet IP67 seal, sand, dust and MIL-STD-810A drop, shock &
vibration requirements. The Clary SX560 will operate in temperature
+165°F)
• No forced air, cooled through Chassis.
Dust and sand resistant, waterproof.
extremes from -40 C to 70 C.
1U of Vertical Rack Space, its 9 ½ ” x 12 ½” footprint can fit any cabinet.
The SX560 communicates locally or remotely via serial, USB or an optional
web agent.
SK1-019M02
SK1-019M03
SK7-019M03
COLD START
SEALED SWITCH
ON/OFF
LOAD
SWITCH
RS232-SIGNAL
INTERFACE
USB-TYPE A
SYSTEM ON/OFF
SX560 Specifications
Electrical
Options
Input
Battery Chassis
External Battery Chassis supports
UPS capability. Provides 6 minutes of
back-up time at 100% load. Consult
Factory for other Battery Options and
Extended Run Times.
Rack or W all Mount
Designed to provide 19" Rack
mounting capability.
By-pass Switch
Supports manual and automatic
switching of SX560.
Voltage
120 VAC, (85VAC to 155VAC before
going to battery, when configured with
batteries)
Frequency
40 to 70 Hz
Output
Voltage
120 VAC ±3%
Frequency
50 or 60 Hz ±.25% (Software
Selectable)
Current
4.8A (400W / 570VA)
Crest Factor Ratio
(Non-linear Load
and < 5% THD)
@50% Load Up to 4.8:1
@75% Load Up to 3.2:1
Typical
@100% Load Up to 2.4:1
Total Harmonic
Distortion
(THD) 3.0%
Dynamic Response
±4% for 100% Step Load Change,
0.5 ms Recovery Time
Overload
110% for 10 seconds;
200% for 50 milliseconds
UPS Protection
Input and Output Short Circuit, Input
and Output Overload, Excessive
Battery Discharge
Mechanical
Input
Outputs
Design
Standard Features
Power Factor Corrected Input;
Fully Regenerative; True On-Line
Continuous Power; Low Distortion
Sinewave Output; Designed for Nonlinear Loads; Extended Brownout
Protection
Specifications
Meets FCC Class A, IEEE 587/ANSI
C62.41, IEC 555 @ 120 VAC, IP67 and
NEMA Standards
MTBF
Inverter: > 100,000 hrs
System Calculated from Component
Specifications
Typical Recharge
Time to 85%
Capacity @ 100%
Load
3 to 5 hrs (with extended battery
option)
Controls and Indicators
Anderson SK1-019M03
male connector-sealed
Anderson SK7-019M03
female receptacle-sealed
Overall Dimensions
12 ½" W × 9 1/2" D × 1.7"H
Operating
Temperature
-40˚F to +165˚F (-40˚C to +74˚C)
Humidity
0% to 95% non-condensing
Altitude
Sea Level to 10,000 Feet
Visual Indicators
Battery Status; AC Output; AC Input;
Alarm
Switches
System Power; Cold start; Load
Audible Alarms
Utility Interrupt; Inverter Failure;
Overload; Low Battery; Over
Temperature
Intelligent Computer
Interfaces
DB9-F (RS232 and Signal
Interface pins) and 1 USB
150 East Huntington Drive, Monrovia, CA 91016
The Continuous Power Company™
Tel:800-442-5279 • Fax:626-305-0254 • www.clary.com
Was this manual useful for you? yes no
Thank you for your participation!

* Your assessment is very important for improving the work of artificial intelligence, which forms the content of this project

Download PDF

advertising