Krack CS/CD/CP Series CS/CD/CP Air Cooled Condensing Unit Operating and Installation Manual
Below you will find brief information for Air Cooled Condensing Unit CS/CD/CP Series CS/CD/CP. The CS/CD/CP series air-cooled condensing units are designed for use in commercial refrigeration applications. The units are available in a variety of sizes with different compressor types. The units are designed for ease of installation and maintenance.
advertisement
Assistant Bot
Need help? Our chatbot has already read the manual and is ready to assist you. Feel free to ask any questions about the device, but providing details will make the conversation more productive.
▼
Scroll to page 2
of
16
CS*/CD*/CP* Series Air Cooled Condensing Units Operating an d Installation Manual CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) TABLE OF CONTENTS I. Receipt of Equipment………………………………2 II. Piping………………..…………………………….4 III. System Evacuation….…………………………….5 IV. Electrical………………..………………………...5 V. Charging the System..……………………………..5 VI. Operation Checkout………………….…………...6 VII. Features and Controls……….……………….…..6 VIII. Normal Maintenance……………………………8 TABLES: Table 1A&B: Recommended Line Sizes…….………..9, 10 Table 2A,B&C: Condensing Unit Refrigerant Charge..11, 12, 13 Table 3A&B: Low Pressure Control Settings…………14 CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 1 Commercial Large Condensing Unit Model Key CP I - 0700 H 2 Condensing Unit Family CS - Single Compressor CP - Parallel Compressors CD - Dual Compressors Compressor Manufacturer C - Carlyle Semi-Hermetic D - Copeland Discus I - Ingersoll Rand Semi-Hermetic V - Copeland Screw Total HP 0100 = 10 HP w/std condenser 0101 = 10 HP w/oversized condenser 0700 = (2) 35 HP w/std condenser 0701 = (2) 35 HP w/oversized condenser M Voltage K - 208/230/3/60 M - 460/3/60 P - 575/3/60 U - 380/3/50 Refrigerant 2 (V) - R22 4 (S)- R404A 7 (P) - R507 Temperature H - High M - Medium L - Low I. RECEIPT OF EQUIPMENT A) DAMAGE CHECK All equipment should be carefully checked for damage as soon as it is received. If any damage is evident, a notation must be made on the delivery receipt before it is signed and claim should then be filed against the freight carrier. B) CHECK VOLTAGE Carefully check nameplate voltage and current characteristics to be sure unit is compatible with power supply. C) HANCDING Never hoist the unit from any point excepting the base lifting holes provided for this purpose. Lift with spreader and hooks as shown in Figure 1. When moving unit by forklift, lift from compressor end ONLY. Do not lift from condenser end. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 2 Figure 1. D) LEVELING AND BOLT DOWN PROCEDURE A solid level foundation should be provided for the unit large enough to accommodate the full length of the base rails. If the mounting location is not sturdy and perfectly level, place shims under low points before tightening down with hold-down bolts. Improper bolting-down procedure can seriously warp the framework, particularly with the large condenser fan units (3 fans or more). E) UNIT LOCATION Large air-cooled condensing units dissipate a tremendous amount of heat and require large volumes of air. Short-circuiting of the condenser air, or restricting the free entry of air into the coil will result in reduced capacity and highpower consumption. Take care to reduce such negative operation effects by providing for unrestricted free airflow into and from the unit. At most, the unit should not be positioned so as to have no more than one of its sides positioned close to a vertical building side or wall. At that point, this should be a minimum of 3’ unit-to-wall free air clearance distance. F) LOSS OF GAS HOLDING CHARGE Each Condensing unit is evacuated to remove moisture, leak tested, and then shipped with a gas holding charge. Absence of this charge may indicate a leak has developed in transit. The system should not be charged with refrigerant until it is verified that there is no leak or the source of the leak is located. G) CHECK COMPRESSOR The compressor is bolted to the base of the condensing unit using solid mounting techniques. Check the compressor mounting bolts. Tighten these bolts as much as possible to prevent excess vibration. Check electrical junction connections of the compressor; tighten only those that may have come loose during transit. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 3 II. PIPING 1) REFRIGERATION PIPING Use ACR grade copper tubing, or conform otherwise to local and national codes. Piping methods must meet these codes and result in acceptable piping practice. A) SUCTION LINE Design and sizing of the suction line is critical to maintain: 1) Proper refrigerant velocity 2) Practical pressure drop (usually equivalent to 2 F maximum) 3) For proper oil return, all horizontal lines should be sloped downwards toward compressor at 1 inch per 10 feet. Suction line risers must be trapped at the bottom of the rise and at every 20-foot increment for proper oil return. The proper balance is to design suction lines for approximately 1,200 ft. per min. velocity in risers and approximately 600 ft per min. velocity in horizontal lines. “P” traps should be installed at the bottom of all risers in suction lines for proper oil return. Table 1 lists common suction line sizing that can be used with-but not instead of -ASHRAEguidelines. Suction lines should not be exposed to heat unless insulated. Insulation also prevents sweating and subsequent damage to goods. B) LIQUID LINE Avoid excessive liquid line pressure drop by using Table 1 and ASHRAE guidelines to size the liquid line. Install a liquid line solenoid valve at the evaporator. On parallel compressor systems, if one compressor cycles off due to part load conditions, suction lines must be sized to allow for oil return under reduced load conditions. 2) LINE FABRICATION & SOLDERING Copper pipe should be cut with a wheel type cutter and not with a hacksaw. Using a hacksaw produces copper filings that can cause problems if it gets into the system. Also, if the pipes to be used are not capped and perfectly clean, they should be cleaned with a clean lint free rag before fabrication into the system. Soft solders should be avoided wherever possible, as in most cases they require the use of a flux. Most of the low temperature solder flux consists of heavy wax type materials which if allowed to enter the system cause excessive service problems in the form of wax at expansion valves which looks like moisture but cannot be removed by the average dryer core. Where silver brazing must be used between copper and brass or copper and steel joints, care should be taken to avoid excessive use of flux lest it be introduced into the system to create problems at a later date. EasyFlo or silver solders that contain sufficient silver content to still retain joint strength and yet require minimum use of flux are recommended here. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 4 For copper-to-copper joints phos-copper solders with 4 to 15% silver content are recommended. No flux is required, and the resultant joints are of maximum strength without brittleness. Nitrogen should be used to exclude the oxygen within the pipes during soldering in order to prevent the creation of large quantities of copper oxide. Copper oxide is a good abrasive and if it gets into the compressor it can cause excessive wear and/or shorting out of electric motor windings. 3) LEAK TESTING When all refrigeration connections have been completed, the entire system must be tested for leaks. With all valves in the system open, pressurize the system to no more than 175 PSIG with refrigerant and dry nitrogen. The use of an electronic type leak detector is highly recommended. III. SYSTEM EVACUATION CAUTION: DO NOT use the compressor as a vacuum pump. DO NOT start the compressor while it is in vacuum. A two-stage vacuum pump is recommended if moisture is to be removed by evacuation. A singlestage pump will not remove moisture. An electronic vacuum gauge calibrated in microns is recommended for recording vacuum. Connect the vacuum meter to some point on the system, such as the purge connection on the condenser, so the actual vacuum is read rather than the vacuum at the vacuum pump. The pump should be connected to both the low and high pressure sides with copper tube or high vacuum hoses (1/2 inch I.D. minimum) A vacuum of 500 microns and below is recommended to effectively remove moisture from the system. Close the valve at the pump and watch the gauge. If the system contains moisture or a leak is present the vacuum gauge will show a rise in pressure. When there is no visible rise in system pressure for 12 hours after the vacuum valve is shut off, evacuation is complete. IV. ELECTRICAL The power supply voltage, phase and frequency must match what is shown in the condensing unit data plate. All wiring must be carefully checked against the condensing unit wiring diagram. V. CHARGING THE SYSTEM Weigh the refrigerant cylinder before charging the system so an accurate record can be made of the amount of refrigerant put in the system. Connect the suction service gauge to the compressor suction service valve and the discharge service gauge to the receiver outlet port. The third hose from the charging manifold should be connected to the refrigerant cylinder. CAUTION: NEVER charge liquid refrigerant through the suction side of the system. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 5 When initially charging a system that is in a vacuum, liquid refrigerant can be directly added into the receiver until the system pressure equalizes with pressure in the refrigerant cylinder. Start the system and finish charging until the sight glass is clear. Outdoor condensing units are furnished with a condenser flooding type of head pressure control valve for cold weather operation. This valve should be set at 180 psig for better performance for this unit. The correct refrigerant charge must be added at start up. Table 2 indicates the refrigerant charge at different ambient temperature. Determine the ambient temperature at the time of charging the system and locate this temperature at the top of table 2. Next locate the condensing unit model number and the refrigerant type on the left side of the table. Read from left to right until you reach the column for the days ambient temperature. Record the condensing unit charge at this set of conditions. Next locate the column for the winter design temperature and record the condensing unit charge. The difference between these two values is the additional refrigerant that must be added to the system for proper winter operation. VI. OPERATION CHECKOUT 1) Check electrical connections, fan blade set screws and refrigerant connections. Be sure they are tight. 2) Check the low pressure control setting. See Table 3 for proper setting. 3) With the system operating, check the supply voltage. It must be within +/- 10% of the voltage marked on the unit nameplate. 4) Check the room thermostat setting. Be sure it functions properly. 5) Check the compressor amp draw. It must not exceed the value on the unit data plate. 6) After the room temperature is reached, the expansion valve superheat must be checked. Too low suction superheat may cause liquid to return to the compressor. Too high suction superheat may cause excessive discharge temperatures. For maximum system capacity the minimum superheat must be 20 F and the maximum superheat must be 30 F to 40 F at the compressor for medium and low temperature, respectively. 7) After several hours of operation, check the compressor oil level. The oil level should be 1/2 the way up on the glass with the compressor off. Care must be taken to be sure the proper lubricant is used. 8) On freezer system after the coil is frosted, manually advance the defrost timer to initiate a defrost. Observe the defrost cycle to see if all controls are functioning properly and that the coil is clear of all frost before the system returns to refrigeration. Reset the defrost timer to the correct time of day. 9) After the room has reached temperature and the liquid line solenoid has closed, check the compressor to be sure it has pumped down and shut off. If the compressor continues to run, check the low pressure control setting as outlined in step #2. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 6 VII. FEATURES AND CONTROLS 1) REFRIGERANT OIL The oil level should be 1/2 the way up on the glass in the compressor with the compressor off. Oil level should be checked frequently during startup and during the first 48 hours of operating time. Since no dependable rule of thumb can be used, the only safe method is to carefully check the oil level and add as little oil as needed. If oil is required to be added, an oil pump is recommended to pump the oil directly into the compressor against suction pressure. Refrigerant oil should be purchased in sealed containers and should not be left open to atmosphere. Exposure to air and moisture for extended periods will result in contamination of the oil and cause harmful reactions in the compressor. Do not transfer oil from one container to another. 2) HIGH AND LOW PRESSURE CONTROLS CS/CD/CP’s are furnished with individual manual reset high-pressure and low-pressure controls. These are safety controls for the system. (See Table 3). 3) OIL FAILURE SWITCH Each compressor on the Model CS/CP/CD unit has its own electronic oil pressure control. Should oil pump differential pressure, measured between the pump inlet and outlet, fall below 9 psig for a period of two minutes, the control will open and stop the compressor. A trip of the oil pressure safety control is a warning that the compressor has been running without proper lubrication. Repeated trips of the control are a clear indication that something in the system requires immediate attention and corrective action. If system is plagued with oil failure safety switch tripouts, it is almost always traceable to one of the following sources. a) b) c) d) e) f) g) h) i) j) Shortage of oil in the compressor Oil trapping in the system Liquid slug back to the compressor for some reason. Compressor short cycling Refrigerant in the oil on startup Malfunctioning oil pump Clogged on the oil suction screen Excessively low suction pressure Possibly a defective control, but not probable Low refrigerant charge in low ambient conditions 4) CRANKCASE HEATERS Crankcase heaters are provided to reduce the possibility of refrigerant condensing in the crankcase oil. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 7 NOTE: The use of a crankcase heater installed on the compressor does not always assure that liquid refrigerant will not condense in the oil under severe weather conditions. If the compressor is subjected to extremely low temperatures and the evaporator is in a relatively warm location, the temperature at the compressor may still drop below evaporator temperature in which case liquid refrigerant will condense in the oil. 5) ELECTRICAL POWER Control voltage is 230/60/1 as standard. All condensing units are factory tested for operation before leaving the plant and direction of rotation of all condenser fans are checked to see that they are the same. However, on installation, phase reversals may cause the fans to run backward. It’s obvious that this can only be corrected in the field. On start-up, be sure to check that fan rotation is according to arrow decal on or near the fan blade. Airflow is up (vertical). Reversing of any two wires of the power supply to the condenser fan contactor will change the direction of the fan rotation. 6) CONDENSER FAN CYCLING Pressure switches are included to cycle all but the first condenser fan(s) in response to head pressure. See Table 4 for suggested pressure settings used on all multiple condenser fan systems. 7) LOW AMBIENT FLOODING CONTROLS ARE STANDARD Condenser Liquid Flooding utilizes a field-adjustable (100 to 225 psig) condensate holdback valve. Head pressure control valve for this unit should be set at 180 psig. 8) PUMPDOWN & RESET SWITCH With toggle switch down in the reset and pumpdown position, the control circuit is reset and the liquid line solenoid valve is de-energized. This allows the compressor to pumpdown on the low-pressure control. With the toggle switch up in the run position, the liquid solenoid valve is energized and allows the system to cycle on the room thermostat. VIII. NORMAL MAINTENANCE 1) Check compressor oil sight glass for proper level and check visible piping for oil spots, which may indicate a refrigerant leak. 2) Check liquid refrigerant sight glass for proper charge. If refrigerant must be added, use charging procedure outline in section V. 3) Check inlet airside of condenser; surface should be free of foreign matter. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 8 TABLE 1A RECOMMENDED LINE SIZES FOR R-22 SUCTION LINE SIZE SUCTION TEMPERATURE SYSTEM CAPACITY BTU/H +20° F Equivalent Suction Line Length 25' 50' 75' 100' -20° F Liquid Line Equivalent Suction Line Receiver to Expansion Valve Length 25' 50' 75' 100' 25' 50' 75' 100' R-22 36,000 7/8 1 1/8 1 1/8 1 3/8 1 1/8 1 3/8 1 3/8 1 3/8 3/8 1/2 1/2 1/2 42,000 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 3/8 1/2 1/2 1/2 48,000 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1/2 1/2 1/2 1/2 54,000 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1/2 1/2 1/2 1/2 60,000 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1/2 1/2 1/2 1/2 66,000 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1/2 1/2 5/8 5/8 72,000 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 1/2 1/2 5/8 5/8 78,000 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 1/2 1/2 5/8 5/8 84,000 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 2 1/8 2 1/8 1/2 5/8 5/8 5/8 90,000 1 1/8 1 3/8 1 3/8 1 5/8 1 3/8 1 5/8 2 1/8 2 1/8 1/2 5/8 5/8 5/8 120,000 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 5/8 5/8 5/8 7/8 150,000 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 5/8 7/8 7/8 7/8 180,000 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 5/8 7/8 7/8 7/8 210,000 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 5/8 7/8 7/8 7/8 240,000 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 5/8 7/8 7/8 7/8 300,000 2 1/8 2 1/8 2 1/8 2 5/8 2 1/8 2 5/8 3 1/8 3 1/8 7/8 7/8 1 1/8 1 1/8 360,000 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 3 1/8 3 1/8 7/8 7/8 1 1/8 1 1/8 480,000 2 1/8 2 5/8 2 5/8 2 5/8 7/8 1 1/8 1 1/8 1 1/8 600,000 2 1/8 2 5/8 3 1/8 3 1/8 7/8 1 1/8 1 1/8 1 3/8 720,000 2 5/8 3 1/8 3 1/8 3 1/8 7/8 1 1/8 1 1/8 1 3/8 840,000 2 5/8 3 1/8 3 1/8 3 5/8 1 1/8 1 1/8 1 3/8 1 3/8 960,000 2 5/8 3 1/8 3 1/8 3 5/8 1 1/8 1 3/8 1 3/8 1 3/8 Line sizes, which are shaded, indicate the maximum suction line size that may be used for a riser. In no case should the riser exceed the horizontal line size. Properly placed suction traps must be used to insure proper oil return. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 9 TABLE 1B RECOMMENDED LINE SIZES FOR R-404A and R-507 SUCTION LINE SIZE SYSTEM CAPACITY BTU/H SUCTION TEMPERATURE +20° F Equivalent Suction Line Length 25' 50' 75' 100' -20° F Liquid Line Equivalent Suction Line Receiver to Expansion Valve Length 25' 50' 75' 100' 25' 50' 75' 100' R-404A and R-507 36,000 42,000 48,000 54,000 60,000 66,000 72,000 78,000 84,000 90,000 120,000 150,000 180,000 210,000 240,000 300,000 360,000 480,000 600,000 7/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 1 1/8 1 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 3 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 3 1/8 3 1/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 1/8 2 5/8 1 1/8 1 3/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 1 3/8 1 3/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 1 3/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 1 5/8 2 1/8 2 1/8 2 1/8 2 5/8 2 5/8 2 5/8 2 5/8 3 1/8 1/2 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1/2 1/2 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1/2 1/2 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8 1 1/8 1 3/8 1 3/8 1/2 1/2 5/8 5/8 5/8 5/8 5/8 5/8 5/8 7/8 7/8 7/8 7/8 7/8 1 1/8 1 1/8 1 3/8 1 3/8 1 5/8 Line sizes, which are shaded, indicate the maximum suction line size that may be used for a riser. In no case should the riser exceed the horizontal line size. Properly placed suction traps must be used to insure proper oil return. CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 10 TABLE 2A CS* CONDENSING UNIT REFRIGERANT CHARGE - POUNDS CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* CS* Model 0100 0150 0200 0250 0300 0350 0400 0500 0600 0101 0151 0201 0251 0301 0351 0401 0501 0601 0220 0270 0300 0151 0221 0271 0301 0150 0200 0250 0300 0350 0400 0151 0201 0251 0301 0351 0401 0220 0270 0300 0221 0271 0301 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 L2 L2 L2 L2 L2 L2 L2 M4 M4 M4 M4 M4 M4 M4 M4 M4 M4 M4 M4 L4 L4 L4 L4 L4 L4 Refrigerant R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A Above 70 F 29.1 31.6 31.6 42.4 53.2 55.7 72.5 80.6 97.1 31.6 42.4 42.4 42.3 55.7 80.4 91.2 112.9 137.0 31.6 36.9 36.9 36.9 36.9 36.8 50.2 27.9 27.9 37.4 46.9 42.2 70.8 37.4 37.4 49.0 63.9 71.0 95.1 29.3 39.5 44.8 39.5 39.4 52.2 50 F 39.8 37.3 37.3 50.7 64.2 58.6 76.0 97.0 101.8 42.4 58.4 58.4 48.0 63.9 91.5 132.9 129.4 158.4 47.5 60.3 60.3 60.3 60.3 53.8 75.6 33.4 33.4 45.4 57.4 45.0 75.7 52.1 52.1 57.1 72.9 100.2 134.1 37.9 52.1 61.2 58.9 53.1 72.4 30 F 43.6 44.8 44.8 61.9 79.0 71.9 89.6 119.3 120.0 48.3 67.1 67.1 60.6 82.7 116.6 155.9 166.9 208.2 51.8 66.6 66.6 66.6 66.6 62.1 87.9 40.2 40.2 55.6 70.9 53.3 91.9 60.2 60.2 74.1 90.2 116.3 155.6 43.3 60.2 71.8 64.8 60.9 83.9 10 F 45.9 49.0 49.0 68.2 87.4 84.0 101.9 131.8 136.4 51.6 72.1 72.1 67.1 92.4 129.7 168.7 186.4 234.0 54.1 70.0 70.0 70.0 70.0 54.9 77.0 44.2 44.2 61.5 78.7 60.9 106.8 64.9 64.9 83.2 99.6 125.7 168.1 46.6 64.9 77.9 68.3 54.9 74.7 0F 46.8 50.6 50.6 70.5 90.4 88.5 106.6 136.4 142.6 53.0 74.1 74.1 69.5 95.9 134.5 173.8 193.5 243.3 55.2 71.5 71.5 71.5 71.5 68.4 97.3 45.7 45.7 63.6 81.6 63.8 112.5 66.8 66.8 86.5 103.1 129.4 173.1 47.9 66.8 80.4 69.8 67.1 93.0 Below -20 F 48.4 53.1 53.1 74.2 95.3 95.4 113.7 143.7 152.2 55.5 77.8 77.8 73.4 101.7 142.2 183.5 205.0 258.4 57.1 74.1 74.1 74.1 74.1 71.4 101.6 48.1 48.1 67.1 86.1 68.2 121.0 70.3 70.3 91.8 108.7 136.4 182.4 50.3 70.3 84.9 72.4 70.0 97.1 * - Ingersoll Rand or Discus Compressors CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 11 TABLE 2B CD* CONDENSING UNIT REFRIGERANT CHARGE – POUNDS Model* CD* 0100 CD* 0150 CD* 0160 CD* 0180 CD* 0200 CD* 0240 CD* 0300 CD* 0400 CD* 0500 CD* 0600 CD* 0700 CD* 0800 CD* 1000 CD* 1200 CD* 0101 CD* 0151 CD* 0161 CD* 0181 CD* 0201 CD* 0241 CD* 0301 CD* 0401 CD* 0501 CD* 0601 CD* 0701 CD* 0801 CD* 1001 CD* 1201 CD* 0440 CD* 0540 CD* 0600 CD* 0441 CD* 0541 CD* 0601 CD* 0400 CD* 0500 CD* 0600 CD* 0700 CD* 0800 CD* 0401 CD* 0501 CD* 0601 CD* 0701 CD* 0801 CD* 0440 CD* 0540 CD* 0600 CD* 0441 CD* 0541 CD* 0601 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 L2 L2 L2 L2 L2 L2 M4 M4 M4 M4 M4 M4 M4 M4 M4 M4 L4 L4 L4 L4 L4 L4 Refrigerant R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A Above 70 F 14.7 17.4 17.3 17.3 29.0 31.6 32.9 32.9 42.3 53.2 55.7 80.4 80.3 104.8 17.4 17.3 20.0 31.6 32.9 32.9 42.3 42.4 42.3 55.7 80.4 90.8 117.9 136.6 23.9 27.8 36.9 27.8 33.2 44.7 29.0 37.3 46.9 42.2 70.8 37.4 49.0 63.9 70.7 94.7 30.5 39.4 39.5 39.5 44.8 52.2 50 F 18.5 24.5 20.2 20.2 33.4 37.3 34.5 34.5 44.4 64.2 58.6 84.5 83.9 108.7 26.0 22.7 27.9 42.4 37.1 37.1 48.0 58.4 48.0 63.9 91.5 95.9 122.3 141.6 36.5 44.5 60.3 44.5 63.8 69.9 30.9 39.8 57.4 45.0 75.7 52.1 51.7 72.9 75.8 101.5 33.3 42.9 52.1 58.9 70.2 72.4 30 F 19.8 27.0 24.0 24.0 39.1 44.8 41.2 41.2 53.4 79.0 71.9 102.3 89.7 110.6 28.0 25.7 32.3 48.3 46.6 46.6 60.6 67.1 60.6 82.7 116.6 126.1 147.4 157.9 42.7 52.6 66.6 52.6 71.9 82.1 37.1 48.0 70.9 53.3 91.9 60.2 74.1 90.2 96.5 129.2 41.9 54.4 60.2 64.8 78.0 83.9 10 F 20.7 28.5 26.1 26.1 42.4 49.0 47.3 47.3 61.5 87.4 84.0 118.5 109.1 130.4 29.3 27.4 34.7 51.6 51.6 51.6 67.1 72.1 67.1 92.4 129.7 145.9 176.9 198.1 37.2 45.3 70.0 45.3 76.1 71.1 42.7 55.5 78.7 60.9 106.8 64.9 83.2 99.6 110.4 147.7 46.5 60.5 64.9 68.3 82.4 74.7 0F 21.0 29.0 26.9 26.9 43.6 50.6 49.6 49.6 64.6 90.4 88.5 124.6 117.5 144.0 29.8 28.1 35.7 53.0 53.4 53.4 69.5 74.1 69.5 95.9 134.5 152.3 1067.7 209.5 47.3 58.7 71.5 58.7 78.0 91.3 44.9 58.4 81.6 63.8 112.5 66.8 86.5 103.1 115.0 153.9 48.2 62.8 66.8 69.8 84.3 93.0 Below -20 F 21.6 30.0 28.2 28.2 45.6 53.1 53.2 53.2 69.2 95.3 95.4 133.8 126.4 155.1 30.7 29.4 37.5 55.5 56.3 56.3 73.4 77.8 73.4 101.7 142.2 164.1 203.1 231.5 49.4 61.5 74.1 61.5 81.2 95.5 48.1 62.7 86.1 68.2 121.0 70.3 91.8 108.7 123.4 165.0 51.0 66.4 70.3 72.4 87.6 97.1 All units have two refrigerant circuits. Refrigerant charge shown is per circuit. * - Ingersoll Rand or Discus Compressors CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 12 TABLE 2C CP* CONDENSING UNIT REFRIGERANT CHARGE - POUNDS CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* CP* Model 0500 0600 0700 0800 1000 1200 0501 0601 0701 0801 1001 1201 0440 0540 0600 0441 0541 0601 0500 0600 0700 0800 0501 0601 0701 0801 0440 0540 0600 0441 0541 0601 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 H2 L2 L2 L2 L2 L2 L2 M4 M4 M4 M4 M4 M4 M4 M4 L4 L4 L4 L4 L4 L4 Refrigerant R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-22 R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A R-404A Above 70 F 50 F 80.4 84.5 107.9 129.9 112.9 118.8 160.7 168.9 160.5 167.8 144.1 149.5 80.4 91.5 112.9 129.4 137.0 158.4 181.5 191.9 170.3 176.7 199.4 206.8 44.7 69.9 52.6 85.9 58.3 104.5 52.6 85.9 63.4 124.5 73.9 123.6 70.8 75.7 95.1 116.1 85.7 91.4 141.6 151.4 99.4 115.7 106.7 123.4 141.4 149.2 159.6 171.6 52.2 57.1 75.0 81.9 75.2 100.2 75.2 113.7 100.7 152.1 105.7 146.3 30 F 102.3 159.7 145.4 204.6 179.5 152.1 116.6 166.9 208.2 252.3 225.6 237.9 82.1 102.1 116.8 102.1 140.6 147.9 91.9 143.2 108.0 183.9 149.6 157.6 193.0 226.1 74.1 104.6 116.3 125.6 167.9 169.3 10 F 118.5 176.3 169.5 236.9 218.3 190.6 129.7 186.4 234.0 291.7 283.6 317.1 71.1 87.3 123.3 87.3 149.1 125.6 106.8 158.8 123.2 213.6 167.8 175.9 220.8 262.5 83.2 116.9 125.7 132.4 177.0 150.9 0F 124.6 182.4 178.6 249.1 235.0 217.3 134.5 193.5 243.3 304.7 2064.8 339.3 91.3 114.2 126.2 114.2 152.8 165.9 112.5 164.6 129.1 225.0 174.5 182.7 230.1 274.6 86.5 121.4 129.4 135.4 181.0 187.5 Below -20 F 133.8 192.2 192.4 267.7 252.8 238.3 142.2 205.0 258.4 328.2 334.3 382.1 95.5 119.7 131.2 119.7 159.1 174.1 121.0 173.7 137.9 242.1 185.2 193.5 246.8 296.3 91.8 128.6 136.4 140.5 187.9 195.8 * - Ingersoll Rand or Discus Compressors CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 13 TABLE 3A LOW PRESSURE CONTROL SETTINGS Minimum + Temperature 50 F 40 F 30 F 20 F 10 F 0F -10 F -20 F Max Cut In 70 Psig 55 Psig 40 Psig 30 Psig 20 Psig 15 Psig 10 Psig 8 Psig R-22 Cut Out 30 Psig 25 Psig 20 Psig 10 Psig 5 Psig 0 Psig 0 Psig 0 Psig R-404A Max Cut In Cut Out 85 Psig 40 Psig 70 Psig 35 Psig 50 Psig 30 Psig 40 Psig 20 Psig 30 Psig 10 Psig 25 Psig 5 Psig 15 Psig 0 Psig 10 Psig 0 Psig + Temperature is the minimum ambient temperature at the condensing unit or the box design temperature, whichever is lower. Example #1: 30 F minimum ambient, -20 F freezer. Use -20 F value from Table. Example #2: -10 F minimum ambient, +35 F cooler. Use -10 F value from Table. TABLE 3B HIGH PRESSURE CONTROL SETTINGS R-22 R-404A/R-507 400 Psig 400 Psig CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 14 CS/CD/CP AIR COOLED CONDENSING UNITS (P/N E207120C R2) 15
advertisement
Key Features
- Air-cooled condensing units
- Available in a variety of sizes
- Different compressor types
- Ease of installation and maintenance
- Designed for commercial refrigeration applications
Frequently Answers and Questions
How do I check the compressor oil level on my Krack CS/CD/CP air-cooled condensing unit?
The oil level should be 1/2 the way up on the glass in the compressor with the compressor off. Oil level should be checked frequently during startup and during the first 48 hours of operating time.
What is the correct refrigerant charge for my Krack CS/CD/CP air-cooled condensing unit?
The correct refrigerant charge is listed in Table 2 of the manual. The charge will vary depending on the ambient temperature and the size of the unit.
How do I adjust the low pressure control on my Krack CS/CD/CP air-cooled condensing unit?
The low pressure control setting is listed in Table 3 of the manual. The setting will vary depending on the minimum ambient temperature or the box design temperature, whichever is lower.